HEATEC TEC-NOTE. Operation and maintenance Heatec thermal fl uid heaters industrial series IMPOPRTANT NOTICE! CONTENTS. Publication No.

Size: px
Start display at page:

Download "HEATEC TEC-NOTE. Operation and maintenance Heatec thermal fl uid heaters industrial series IMPOPRTANT NOTICE! CONTENTS. Publication No."

Transcription

1 HEATEC TEC-NOTE Operation and maintenance Heatec thermal fl uid heaters industrial series CONTENTS Important Notice...1 Intended users...2 Scope...2 Prior to initial startup...2 Preliminary tasks...2 Purging water from the system...2 Checking limit circuit devices...2 Routine operation...3 Starting and shutting down the heater...3 Cleaning strainers...3 Lubrication...3 Maintenance schedule...4 troubleshooting basics...10 Shock hazards...10 Low media level switch Circulating pump motor auxiliary contacts Low gas pressure switch High gas pressure switch...12 High media temperature controller...12 temperature limits of exhaust gases Combustion air motor auxiliary contacts Low combustion air pressure switch Fuel oil pump auxiliary contacts Low fuel oil pressure switch Pilot gas regulator Figure 2. Heatec vertical helical coil heater. the burner is on its bottom and is up-fi red. Publication No IMPOPRTANT NOTICE! We strongly recommend that you arrange for an experienced fi eld technician from our service department to commission your heater. He will also instruct your operators in the safe operation of your heater. Figure 1. two Heatec horizontal helical coil heaters. One has an output of 60 million Btu/hour. the other has an output of 0.7 million Btu/hour. Figure 3. Heatec 3-pass vertical heater. Its burner is on its top and is down-fi red.

2 Intended users Information in this document is intended for use by plant personnel responsible for operation and maintenance of your new Heatec heater. Scope This Tec-Note outlines the tasks that must be performed for initial startup (commissioning) of your Heatec helical coil heater. It also covers routine operation, maintenance and troubleshooting. It applies to Heatec industrial series of heaters that heat thermal fluid. We make these heaters in various configurations and sizes according to customer specifications and preferences. (See Figures 1, 2, and 3.) Consequently, most have significant differences in components, differences in piping systems and differences in their use. Because of these differences, some information in this document omits details on how to perform the tasks. Moreover, the figures shown are for a typical heater and may differ significantly from your particular unit. But despite differences, information herein gives a preview of what commissioning entails and serves as a guide for the tasks covered. Our field technician will thoroughly cover the details of your particular heater when he commissions it. Interchangeable terms The terms media, thermal fluid and hot oil are used interchangeably. All three refer to the same thing. Prior to initial startup Please read the safety information shown in Heatec Tec-Note It is the first Tec-Note in this manual. The following tasks should be done prior to initial startup and prior to arrival of the person who will commission your heater: The incoming gas supply line pressure should match the pressure shown on the P&ID drawing furnished with the heater. The heater should be properly installed, piped, and wired. The control panel should be checked for proper supply voltage and for proper control voltage. The equipment that is to be heated by thermal fluid should be fully piped and leak-tested. The thermal fluid circuit should be filled with thermal fluid. Thermal fluid strainers should be cleaned after the system is filled. Preliminary tasks: When a Heatec technician commissions your heater, he will perform the following tasks before initial startup of your heater: 1. Make sure the valves for differential pressure switch(es) are open. 2. Make sure that sight gauge valves are open. 3. Turn on all breakers inside the control panel. 4. Lockout electrical power at the control panel and check thermal fluid pumps for proper alignment and free rotation of their shafts. 5. Restore power to the control panel and purge air from thermal fluid pumps. 6. Check all devices in the 3-P limit circuit. 7. Set up the temperature controllers on the control panel with their appropriate settings. Initial settings for purging water from the system are as follows: Set point of modulating controller is 230 degrees F. Set point of high media temperature controller is 280 degrees F. Purging water from the system The Heatec technician will purge water from your thermal fluid system as part of the commissioning operation. This task requires firing the burner and heating the thermal fluid. Note: The burner on your heater must be tuned after the heater is installed at your facility for local altitude conditions. The Heatec technician that commissions your heater will do that. If you do not plan to have a Heatec technician to commission your heater, you should have a qualified burner technician to perform the initial startup of the burner and tune it for the local altitude conditions. Purging the system can take from two hours to two days or longer, depending on the amount of thermal fluid in the system and the amount of water in the thermal fluid. Purging water from the thermal fluid system involves venting the expansion tank to atmosphere and boiling out the water entrained in the thermal fluid. This is done using the modulation controller to gradually raise the temperature of the thermal fluid from 230 degrees F to about 20 degrees above operating setpoint (PV) in increments of 10 degrees. The high media temperature controller must also be reset about 50 degrees higher than the modulation controller each time the modulation controller is reset. Before purging, valves must be set to circulate the thermal fluid through the expansion tank as it circulates through the system. After purging, the temperature controllers and valves must be reset for normal operation. Page 2 Publication No

3 Routine operation After your heater has been commissioned, your operators can take over its routine operation, maintenance and troubleshooting. Instructions for those tasks are included in the remainder of this document. Starting and shutting down the heater (Fig. 9) 1. To start the heater, turn on the thermal fluid pump and the burner. 2. To shut down the heater, turn off the burner and the thermal fluid pump. Cleaning strainers (F, Fig. 7) 1. Shutdown the heater. 2. Allow the heater and its thermal fluid to cool down.!warning Wear appropriate protective gloves and clothing suitable for handling liquids with temperatures of 350 degrees F or more. Contact with hot thermal fluid can cause severe burns. Handle it with extreme care to avoid contact or spills. 3. Set all valves to mode for Clean Strainer (Fig. 4). 4. Place a bucket or other container (with a capacity of at least 5 gallons) under each strainer drain. 5. Open drain valves to drain thermal fluid from the strainers. Do not re-use this fluid. Dispose of it according to applicable codes. 6. Unbolt the square flange from the bottom of the strainer. Remove the flange, allowing the strainer basket to slide out. 7. Clean the strainer basket. 8. Re-install the strainer basket. 9. Close drain valves. 10. Set valves to mode for RUN as indicated in Figure 4. Lubrication All Heatec heaters have components that require periodic lubrication. Figure 5 lists the components and the recommended lubricants. Maintenance schedule The next page of this document provides a list of items that should be checked periodically to ensure safe, troublefree operation of your Heatec heater. Figure 4. Valve settings for operating modes. Valves in heater thermal fluid piping Operating mode Purge Block Valve A, Fig. 7 Inlet Valves E, Fig. 7 Purge Valve B, Fig. 7 Expansion Valve D, Fig. 7 Discharge Valves K, Fig. 7 Run Open Open Closed Open Open Purge Closed Open Open Open Open Clean Strainer Open Closed Closed Open Closed Figure 5. Lubrication requirements. See Fig. 7 Name Lubricant Frequency (all valves) Valves with grease fittings High temp lithium grease monthly H Thermal fluid pumps High temp lithium grease 2800 hrs operation I Thermal fluid pump motors High temp lithium grease 3 months (NOT SHOWN) Modulating actuator linkage joints General purpose oil monthly Page 3 Publication No

4 MAINTENANCE SCHEDULE Heatec heaters should be checked periodically according to the requirements below. Failure to properly maintain your heater could result in a fire or explosion. REQUIREMENT WEEKLY MONTHLY QUARTERLY YEARLY Check for proper level of thermal fluid. Sight gauge on expansion tank should show at least 3 inches. Clean ultraviolet flame detector lens. Check intake area of blower to make sure it is not blocked by foreign material and is free from buildup of dirt. Check flame to ensure burner shows no symptoms of being in need of tuning. During normal operation check all pressure gauges and thermometers on heater for normal values. Check all operating and limit controls and settings to make sure they are set properly and are working properly. Check strainers to ensure they are not dirty. Check heater and piping to ensure there are no leaks of thermal fluid. Check heater to ensure there is no structural damage to heater shell, end plates, etc. or signs of over heating. Check pilot assembly to make sure spark gap is 1/8 to 3/16 inch. Check burner control linkage to make sure it is not binding or loose. Have exhaust stack gases analyzed and have burner tuned by a specialist Have thermal fluid analyzed to ensure it is not degraded. Lubricate heater components, including linkage, valves, motors, pumps. (Lubricate monthly or as recommended by the manufacturer.) Check fuel gas strainer (Y, Fig. 8) to ensure it is not dirty. Page 4 Publication No

5 A B C D E F Q P O N M L K J A. B. C. D. E. F. G. H. I. I Level gauge Expansion tank Vent/fill connection Nitrogen connection Purge line Expansion line Pump skid (see Figure 7) Differential pressure switch Combustion air filter/silencer H J. K. L. M. N. O. P. Q. G Combustion air blower Fuel train (see Figure 8) Burner Economizer thermal fluid outlet Economizer Economizer thermal fluid inlet Exhaust stack Screen and rain cap Figure 6. Typical industrial heater. Page 5 Publication No

6 A B L K J E D C F G I H A. Purge block valve B. Purge valve C. Thermal fluid return inlet D. Expansion valve E. Inlet valves F. Strainers with drains G. Inlet pressure/vacuum gauges H. Thermal fluid pumps I. Pump motors J. Discharge pressure gauges K. Discharge valves L. Check valves NOTE This pump skid is shown with two sets of pumps and associated components. One serves as a primary while the other serves as a backup or alternate. Both are not normally operated simultaneously. The control panel has separate controls for each pump. The controls and wiring diagrams are labeled to distinguish the two pumps from each other. The pumps should be labeled to match the controls when the heater is installed. Figure 7. Pump skid with two pumps. Page 6 Publication No

7 A B C D E F G H I J K L TO BURNER Z Y W V U T S R Q P O N M A. Pilot manual block valve B. Pilot gas regulator C. Pilot pressure gauge and isolation valve D. Pressure test connection P1 E. Secondary pilot shutdown valve F. Pilot vent valve G. Pressure test connection P2 H. Pilot primary shutdown valve I. Pressure test connection P3 J. Primary manual block valve K. Ratio regulator L. Limiting orfice M. Pressure test connection M4 N. Pressure gauge O. High gas pressure switch P. Primary shutdown valve Q. Normally open vent valve R. Pressure test connection M2 S. Secondary shutdown valve T. Pressure test connection M1 U. Low gas pressure switch V. Main pressure gauge and isolation valve W. Relief valve (when required). Main Gas (trim) regulator Y. Y-strainer Z. Secondary manual block valve Figure 8. Fuel train. Page 7 Publication No

8 BURNER DISPLAY MODULATING CONTROLLER A BLV512 B NET BACK MODE RESET MDFY C OFF N HIGH MEDIA TEMPERATURE CONTROLLER HIGH STACK TEMPERATURE CONTROLLER D RESET OPEN M E OFF ON L POWER ON BURNER F K HEATER ALARM PUMP P1A RUNNING G P1A OFF P1B J ALARM SILENCE PUMP SELECTOR H HOLD NORMAL LOW FIRE HOLD PUMP P1B RUNNING I EMERGENCY-STOP EMERGENCY-STOP A. Burner management control B. Burner modulating controller C. Power disconnect switch D. High stack temperature controller E. Burner switch F. Pump P1A running indicator light G. Pump selector switch H. Pump P1B running indicator light I. Emergency stop switch J. Low fi re hold switch K. Alarm silence switch L. Heater alarm silence indicator light M. Power indicator light N. High media temperature controller NOTE: Separate controls are provided for the two heater pumps. The controls and wiring diagrams are labeled to distinguish the two pumps from each other. However, their designations may vary from one heater to another. In any case, the pumps should be always be labeled to match the controls when the heater is installed. Figure 9. Operating controls. Page 8 Publication No

9 L A K B C D E F J G I H A. Breaker auxiliary contacts for fuel oil pump motor B. Breaker auxiliary contacts for combustion air blower motor C. Breaker disconnect for combustion air blower motor D. Breaker disconnect for fuel oil pump motor E. Contactor for combustion air blower motor F. Auxiliary contacts for combustion air blower motor G. H. I. J. Auxiliary contacts for fuel oil pump motor Contactor for fuel oil pump motor Contactor for media circulating pump motor Auxiliary contacts for media circulating pump motor K. Breaker disconnect for media circulating pump motor L. Breaker auxiliary contacts for media circulating pump motor Figure 10. Components of motor controllers inside the control panel. Page 9

10 Troubleshooting basics Although troubleshooting is something you normally do only after your heater has a problem, it is useful to gain knowledge of how things work beforehand. We recommend that you get familiar with the information in this document without waiting for a problem to develop. Most of the devices covered in this document are incorporated in the heater s 3 P interlock circuit. Each of these devices is intended to detect a specific abnormal operating condition. If any of these devices encounters the abnormal condition for which it is intended, it will shut down the burner and activate the heater s warning system. On some heaters the warning system uses a red light on top of the panel. It flashes when an abnormal condition triggers a shutdown. Other heaters use an audible alarm. The heater may also be wired into a remote control system that indicates an abnormal shutdown. You must find and fix the problem before you can restart the heater. If a shutdown happens you will see a LOCKOUT message on the burner display (Fig. 9). The first line of the message indicates the operating condition when the lockout happened. The second line indicates what abnormal condition triggered the lockout. The lockout message may identify one of the limit devices in the 3 P interlock circuit as the cause of the shutdown. A clogged strainer is often the source of one or more abnormal conditions that will open an interlock device in the 3 P circuit. It can cause high media temperature. It can cause high stack temperature. And it can cause inadequate pressure differential across the coil. Improper settings of a differential pressure switch is also a common cause of 3 P interlock shutdowns. Lockout messages on the burner display may indicate that a shutdown was caused by abnormal conditions not related to the 3 P circuit. A message that says M-8 LIMIT OPEN is usually caused by a problem with the burner modulation motor. A message that says LOCKOUT STANDBY FALSE FLAME usually indicates a faulty flame scanner (when there is really not a flame in the burner). A message that says LOCKOUT PTFI FLAME FAIL is usually caused by a problem with the flame scanner, or with fuel, or with ignition. A message that says LOCKOUT AUTO FLAME FAIL is usually caused by a problem with fuel or combustion air. There is also the possibility that an interlock device itself has malfunctioned and has caused a shutdown. Or there may be yet another cause. In reality, troubleshooting is a process of elimination that starts with the lockout message. For example, assume the burner shuts down and the display says LOCKOUT LO MEDIA LEVEL. Obviously, the first thing to do is to check the level of thermal fluid in the expansion tank. If it is actually too low, fixing the problem may be as simple as adding thermal fluid to the system and making sure there is no leak in the piping system. If it is not too low, the next thing to check is the media level switch located in the expansion tank. If the switch is okay the problem is almost certainly to be a faulty wiring connection or relay. The information in this document should enable you to determine whether various interlock circuit devices are working properly. Shock hazards Troubleshooting instructions in this document are intended for use by plant personnel who understand electrical shock hazards and how to avoid them. Such persons should also know about the usual burn hazards present when working with thermal fluids heated to temperatures in excess of 300 degrees F. Some procedures require making electrical tests and settings inside the heater electrical control panel while it is open and electrical power is turned on. This should be done only by persons authorized by their employer to work inside panels while significant electrical hazards are present. Employers and/or owners should have prescribed safety procedures for such work. Page 10 Publication No

11 Low media level switch This switch (Fig. 11) shuts down the burner if the level of media in the expansion tank gets too low for safe operation. The switch is wired into the 3 P interlock circuit. escape. There is no opening between the float housing and the switch housing. (The float mechanism has a magnet that activates the switch inside the switch housing.) You can open or replace the switch housing without draining the expansion tank. However, you must drain the tank before removing the float housing. If the first check determines that the switch is working when closed, proceed with the second check to ensure that opening its contacts will shut down the burner. Remove the switch cover. Use the flat side of a screwdriver to depress the trip mechanism so as to open the switch contacts (Fig. 12). Figure 11. Low media level switch. Before checking the switch for proper operation, confirm that the expansion tank (B, Fig. 6) contains an adequate level of thermal fluid media. Do this by viewing the level gauge (A, Fig. 6). to make sure the level of the fluid is above the spot where the switch is installed in the tank. Also verify that the float inside the tank is properly oriented by checking the bushing at the back of switch on the outside of the tank. One of the six flat sides of the hex on the bushing should be stamped with the letter T. This flat side of the bushing should be on top and should appear to be level. There are two checks that you should make to determine if the switch circuit is working properly. The first check determines if the switch contacts are actually closed as they should be when there is an adequate level of media in the expansion tank. The second check makes sure that opening the switch contacts will actually shutdown the burner as it should. To do the first check, open the control panel (Fig. 9) and turn on power to the panel while it is open. Locate the two terminals where the level switch wires are connected. Check for 120 VAC between each terminal and neutral. If the voltage is present at both terminals, the switch is closed and is working properly. If voltage is present on one of the terminals, but not the other, the switch circuit is open and there is a problem with the switch circuit. Remove the screw-on cover plate from the back of the switch and see if there is a loose wire or an obvious problem with the micro-switch or the linkage that activates the switch. Otherwise, replace the entire switch, including the float portion. Note: The switch has two parts: a switch housing and a float housing. The float housing protrudes inside the tank and seals the opening so that thermal fluid cannot Figure 12. Opening the contacts of a low media level switch. Opening the switch should cause the following reactions, which indicate that the switch is operating properly: 1. Circulating pump should shut off. 2. The burner should shut down. 3. The message on the bottom line of the Fireye display module should read LOCKOUT LOW MEDIA LEVEL. Circulating pump motor auxiliary contacts This is a module with contacts (J, Fig. 10) that prevent operation of the burner unless the contactor for the media circulating pump motor is actuated (closed). The contacts are wired into the 3 P interlock circuit. The module has a plunger that opens and closes the contacts by engagement with the contactor. If the contactor opens, its plunger will open the contacts and shut off the burner. Check the auxiliary contacts as follows: With the burner operating, trip the breaker disconnect for the media circulating pump motor (K, Fig. 10). Page 11

12 This should cause the auxiliary contacts to open. The following reactions should occur, indicating that the contacts are operating properly: 2. The message on the bottom line of the Fireye display module should read CIRC PUMP AU CT. Reset circulating pump circuit breaker. Low gas pressure switch This switch (U, Fig. 8) shuts down the burner if the gas pressure goes lower than the setpoint on the switch. The switch is wired into the 3 P interlock circuit. Check the switch as follows: Shut off the primary manual block valve (J, Fig. 8) and set BURNER switch (E, Fig. 9) to ON. Remove the plug from pressure test connection M1 (T, Fig. 8) below the pressure switch. Open its valve allowing gas to escape. The following reactions should occur, indicating that the switch is operating properly: The display on the Fireye burner management control (A, Fig. 9) should read LOCKOUT 3 P INTLK OPEN. Reinstall plug in the connection. Slowly re-open the primary manual block valve (J, Fig. 8). The low gas pressure switch (U, Fig. 8) should automatically reset. Reset the Fireye control (A, Fig. 9). High gas pressure switch This switch (O, Fig. 8) shuts down the burner if the gas pressure increases higher than the setpoint on the switch. The switch is wired into the 3 P interlock circuit. Check the switch as follows: With the burner operating, remove the cover from the switch. Be careful not to touch the live terminals. Adjust the switch to a lower setting that causes the switch to open. The following reactions should occur, indicating that the pressure switch is operating properly: The burner should shut down. The display on the Fireye burner management control (A, Fig. 9) should read LOCKOUT 3 P INTLK OPEN. Re-adjust the high pressure switch to its previous position. The switch should automatically reset. Reinstall its cover. High media temperature controller This controller (N, Fig. 9) shuts down the burner if the media temperature exceeds its setpoint. The temperature controller is manually preset to a set point (SP) that has been established by the customer for the individual heater. It can be changed in the field by an operator. The controller monitors the temperature signal from a thermocouple mounted in the outlet of the helical coil. Check the controller as follows: With the burner operating, note the PV (process variable) temperature shown on the high media temperature controller (N, Fig. 9). Change the SP (setpoint) to a value lower than the temperature noted. The following reactions should occur, indicating that the controller is operating properly: 2. The message on the display on the Fireye burner management control (A, Fig. 9) should read LOCKOUT HI MEDIA TEMP. Be sure to reset the controller to its previous setpoint and push SET/ENT button. Depress and hold the reset button on the controller for 3 seconds. Temperature limits of exhaust gases Each heater has a system to shut down the burner if the heater exhaust gas exceeds preset limits. Two different systems are used. One system employs a thermocouple and a temperature controller (D, Fig. 9) which can be adjusted in the field. The other system uses a temperature switch (Fig. 13) instead of a thermocouple and controller. The operating temperature of the switch should not be adjusted in the field. The temperature controller (D, Fig. 9) is manually preset to a set point (SP) that has been established by the customer for the individual heater. It can be changed in the field by an operator. The controller monitors the temperature signal from the thermocouple, which is mounted in the exhaust stack. If the temperature of the exhaust gas exceeds the set point, the controller will open the interlock circuit and shutdown the burner. The controller and thermocouple can be checked for proper operation as described below. With the burner operating, note the PV (process variable) temperature shown on the high stack temperature controller (D, Fig. 9). Change the SP (setpoint) to a value lower than the temperature noted and push the SET/ENT button. Page 12

13 The following reactions should occur, indicating that the controller is operating properly: 2. The message on on the display on the Fireye burner management control (A, Fig. 9) should read LOCKOUT HI STACK TEMP. Be sure to reset the controller to its previous setpoint and push SET/ENT button. Depress and hold the reset button on the controller for 3 seconds. Temperature switches are preset by the manufacturer to open at a specified temperature. We usually order them set for 1,000 degrees F. Although they can be ordered for other temperatures, they should not be changed in the field. The switch is wired into the 3 P interlock circuit. If the temperature of the exhaust gas exceeds the preset temperature, the switch will open the interlock circuit and shutdown the burner. The switch can be checked for proper operation as described below. With the burner operating, remove cover from the high flue gas temperature switch. Use the flat side of a screwdriver to depress the tiny button on the switch to open its contacts (Fig. 13). Be careful not to touch live terminals on the switch. The following reactions should occur, indicating that the switch is operating properly: 2. The message on on the display on the Fireye burner management control (A, Fig. 9) should read LOCKOUT HI STACK TEMP. Reset the switch, using the insulated handle of a screwdriver to press the reset button on the switch. This avoids the possibility of electrical shock from the exposed terminals next to the reset button. Combustion air motor auxiliary contacts This is a module with contacts that prevent operation of the burner unless the contactor for the combustion air motor is actuated (closed). The contacts are wired into the 3 P interlock circuit. The module has a plunger that opens and closes the contacts by engagement with the contactor. If the contactor opens, its plunger will open the contacts and shut off the burner. Check the auxiliary contacts as follows: With the burner operating, trip the breaker disconnect for the combustion air blower motor (C, Fig. 10). This should cause its auxiliary contacts (F Fig. 10) to open. The following reactions should occur, indicating that the contacts are operating properly: 2. The display on the Fireye burner management control (A, Fig. 9) should read LOCKOUT AIR AU CT. Reset the breaker disconnect for the combustion air blower motor. RESET BUTTON Figure 13. Checking high flue gas stack temperature switch. Page 13

14 Low combustion air pressure switch This switch (Fig. 14) shuts down the burner if combustion air is too low for safe operation. The switch is wired into the 3 P interlock circuit. Figure 14. Low combustion air switch. Check the switch as follows: With the burner off, unlatch the auxiliary contacts module and physically remove it from the burner circuit breaker with wires attached. Pull out the blue plunger on the module (Fig. 15) and hold it out so as to close its contacts. Fuel oil pump auxiliary contacts This is a module with contacts that prevent operation of the burner unless the contactor for the fuel oil pump motor is actuated (closed). The contacts are wired into the 3 P interlock circuit. The module has a plunger that opens and closes the contacts by engagement with the contactor. If the contactor opens, its plunger will open the contacts and shut off the burner. Check the auxiliary contacts as follows: With the burner operating, trip the breaker disconnect for the fuel oil pump motor. This should cause the auxiliary contacts to open. The following reactions should occur, indicating that the contacts are operating properly: 2. The display on the Fireye burner management control (A, Fig. 9) should read FUEL PUMP AU CT. Reset fuel pump circuit breaker. Low fuel oil pressure switch This switch (Fig. 16) shuts down the burner if fuel oil pressure is too low. The switch is wired into the 3 P interlock circuit. switch Figure 15. Pulling out plunger on an auxiliary contacts module. Restart the burner. Trip the burner circuit breaker. The following reactions should occur, indicating that the pressure switch is operating properly: 2. The display on the Fireye burner management control (A, Fig. 9) should read LOCKOUT LO AIR PRES. Re-insert the auxiliary contacts module into the breaker disconnect. Figure 16. Low fuel oil pressure switch. Check the switch as follows: With the burner off, unlatch the auxiliary contacts module and physically remove it from the fuel pump circuit breaker with wires attached. Pull out the blue plunger on the module (Fig. 15) and hold it out so as to close its contacts. Page 14

15 Restart the burner. Trip the fuel pump circuit breaker. The following reactions should occur, indicating that the pressure switch is operating properly: 2. The display on the Fireye burner management control (A, Fig. 9) should read LOCKOUT LO FUEL PRES. Pilot gas regulator This regulator (B, Fig. 8) controls pressure of the pilot gas. Its switch is not wired into the 3 P interlock circuit. Check the regulator as follows: 1. Make sure that pressure in gas supply line is according to that specified in the applicable P&ID drawing. To check the pressure, connect a pressure gauge in place of the plug in the bottom of the Y-strainer (Y, Fig. 8). 2. Connect a manometer to pressure test connection (I, Fig. 8). 3. Start the burner. When Fireye flame monitor indicates PTFI, check to see that the pressure on the manometer is 6 to 8 inches WC. If not, remove cap from pilot gas regulator and adjust the regulator to attain this presure. NOTE: Some burners require pilot pressures other than 6 to 8 inches. Be sure to check the burner manufacturer s specifications for the pilot pressure required for the burner on your heater. Heatec, Inc Wilson Road Chattanooga, Tennessee (423) (800) Fax (423) Heatec, Inc. Page 15

HEATEC TEC-NOTE. TROUBLESHOOTING Heatec thermal fluid heaters. Scope CONTENTS. Variations. Publication SAFETY

HEATEC TEC-NOTE. TROUBLESHOOTING Heatec thermal fluid heaters. Scope CONTENTS. Variations. Publication SAFETY HEATEC TEC-NOTE TROUBLESHOOTING Heatec thermal fluid heaters CONTENTS Safety...1 Scope...1 Variations...1 Intended users...2 Troubleshooting basics...2 Low media level switch...6 Circulating pump motor

More information

HEATEC TEC-NOTE STARTUP HC AND HCS SERIES HELICAL COIL HEATERS

HEATEC TEC-NOTE STARTUP HC AND HCS SERIES HELICAL COIL HEATERS RESET MDFY Part No. 5014130 Part No. 5014131 HEATEC TEC-NOTE STARTUP Revised 7-12-12 HC AND HCS SERIES HELICAL COIL HEATERS SAFETY Before starting your heater please read the safety information shown in

More information

BURNER MANAGEMENT CONTROLS

BURNER MANAGEMENT CONTROLS HEATEC TEC-NOTE SCOPE This document applies to burner management controls used on Heatec Firestorm water heaters (Fig. 1). It only covers controls of Firestorm heaters in current production. Some earlier

More information

HHW-80 ECOHEAT Operation, Service & Parts Manual

HHW-80 ECOHEAT Operation, Service & Parts Manual HHW-80 ECOHEAT Operation, Service & Parts Manual CEI Enterprises An Astec Company Albuquerque, New Mexico, U.S.A. ii C18-054, CEI HHW-80 ECOHEAT C18-054, CEI HHW-80 ECOHEAT WARNING! IMPROPER INSTALLATION,

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners 1 1. General Installation Information (to be completed by technician) Date installed: Location (city & state): Cleaner s name: National Board number (boiler): Installed by (company): Installed by (technician):

More information

HEATEC TEC-NOTE Publication No

HEATEC TEC-NOTE Publication No EC TEC-NOTE Setting differential pressure switches on Heatec thermal fluid heaters industrial series WHAT THIS DOCUMENT COVERS This document covers setting DP (differential pressure) switches used on Heatec

More information

New Power Vented Rheem FVIR Tanks

New Power Vented Rheem FVIR Tanks Technical Bulletin B06-08 Sept 26/ 2006 New Power Vented Rheem FVIR Tanks In the coming weeks new power vented FVIR tanks will be arriving in the field from our tank manufactures. We are supplying some

More information

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler ClearFire Model CFH Horizontal Steam Boiler Startup Guide 750-293 www.cleaverbrooks.com Improper installation, adjustment, service, or maintenance can cause equipment damage, personal injury, or death.

More information

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not

More information

Each burner shall be equipped with a Micro-Processor Based Burner Management Flame Safeguard and Parallel Positioning Control System.

Each burner shall be equipped with a Micro-Processor Based Burner Management Flame Safeguard and Parallel Positioning Control System. Product Guide Specification Nexus Integrated Burner Control System 1. General 1.1 Overview Each burner shall be equipped with a Micro-Processor Based Burner Management Flame Safeguard and Parallel Positioning

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS GENERAL INDEECO Industrial Control Panels are designed to provide years of trouble free operation if properly

More information

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit Packaged Gas/Electric Units Owner s Guide to Operating and Maintaining Your Gas/Electric Unit ELECTRICAL SHOCK HAZARD. FIRE OR EXPLOSION HAZARD Disconnect power at fuse box or service panel before performing

More information

OPERATING AND MAINTENANCE MANUAL

OPERATING AND MAINTENANCE MANUAL OPERATING AND MAINTENANCE MANUAL NVPOM-0104 TABLE OF CONTENTS Section Page 1 SPECIFICATIONS...1 1.1 Nova Plus Specifications...1-1 1.2 Warranty...1-2 2 GENERAL BURNER DESCRIPTION...2 2.1 Burner...2-1 2.2

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

WD7664 / WD7663 Maxon Burner Ellis Whisper Dryer Installation & Start UP

WD7664 / WD7663 Maxon Burner Ellis Whisper Dryer Installation & Start UP WD7664 / WD7663 Maxon Burner Ellis Whisper Dryer Installation & Start UP Receiving Do a quick visual inspection on the truck for any major damage prior to signing the paperwork. Damage should be noted

More information

User s Information Manual

User s Information Manual 48AJ,AK,AW,AY020-060 Single-Package Rooftop Gas Heating Units with COMFORTLINK Controls and Scroll Compressors User s Information Manual NOTE TO INSTALLER This manual should be left with the equipment

More information

User s Information Manual

User s Information Manual 62DA,DB,DC,DD07-38 Vertical or Horizontal Dedicated 100% Outdoor Air Unit with Optional Gas Heat User s Information Manual NOTE TO INSTALLER This manual should be left with the equipment owner. : If the

More information

Columbia Boiler Company

Columbia Boiler Company EMG Series Boilers Available in Natural Gas & Propane Rev 12012 Columbia Boiler Company PO Box 1070 Pottstown, PA 19464 Tel (610) 473-8457 Fax (610) 367-6800 Website www.columbiaboiler.com Email cbcsales@ptd.net

More information

User s Information Manual

User s Information Manual 48N2,N3,N4,N5,N6,N7,N8,N9 75-150 Ton Gas Heating/Electric Cooling Units with ComfortLink Controls User s Information Manual NOTE TO INSTALLER: This manual should be left with the equipment owner. : If

More information

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw SEMI-INSTANTANEOUS ENERGY: STEAM TO WATER U-TUBE SINGLE-WALL & DOUBLE-WALL HEAT EXCHANGERS FLOOR DRAIN Typical Construction Figure 34-1 FLOOR DRAIN 1. U-tube

More information

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!! Sample Written Program For Your Company For BOILER SAFETY Provided By: P.O. Box 2136 Slidell, LA 70458 Phone: 985-781-1444 Fax: 985-781-1446 Email: info@se-safety.com Purpose Boiler Safety Program The

More information

WD7664 / WD7663 Maxon Burner. Ellis Whisper Dryer Installation & Start UP

WD7664 / WD7663 Maxon Burner. Ellis Whisper Dryer Installation & Start UP Title WD7664 / WD7663 Maxon Burner Ellis Whisper Dryer Procedure No. Installation & Start UP Procedure Author Chris Giordano Effective 1/23/17 Revision A Submitted By Chris Giordano Supersedes Date Revision

More information

CEI Jacketed Firebox Heater Operation, Service & Parts Manual

CEI Jacketed Firebox Heater Operation, Service & Parts Manual CEI Jacketed Firebox Heater Operation, Service & Parts Manual Heater models 1200 ~ 6300 CEI Enterprises Albuquerque, New Mexico, U.S.A. ii Jacketed Firebox Heaters Contents Section 1: Introduction... 1

More information

USER'S MANUAL PGE Single Package Rooftop

USER'S MANUAL PGE Single Package Rooftop USER'S MANUAL PGE Single Package Rooftop Gas Heating/Electric Cooling Units Sizes 036-150 3 to 12-1/2 Tons NOTE TO INSTALLER: This manual should be left with the equipment owner. WARNING: If the information

More information

DIRECTIVE NO: D-B

DIRECTIVE NO: D-B DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting

More information

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed

More information

GAS RACK OVENS WITH ELECTRONIC OVEN CONTROL

GAS RACK OVENS WITH ELECTRONIC OVEN CONTROL GAS RACK OVENS WITH ELECTRONIC OVEN CONTROL MODELS DRO2G DRO2GH GAS GAS 701 S. RIDGE AVENUE TROY, OHIO 45374-0001 937-332-3000 www.hobartcorp.com FORM 19202 Rev. D (Dec. 2003) IMPORTANT FOR YOUR SAFETY

More information

KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters. Table of Contents FOR YOUR SAFETY.

KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters. Table of Contents FOR YOUR SAFETY. KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters Table of Contents FOR YOUR SAFETY Page # Topic If you smell gas: 1 Description of Operation 1 Receiving the

More information

Packaged Gas/Electric

Packaged Gas/Electric Packaged Gas/Electric Units Owner's Guide to Operating and Maintaining Your Gas/Electric Unit ELECTRICAL SHOCK HAZARD. FIRE OR EXPLOSION HAZARD Failure to follow this warning can result in Disconnect power

More information

5.0 ALARMS & TROUBLESHOOTING

5.0 ALARMS & TROUBLESHOOTING 5.0 ALARMS & TROUBLESHOOTING 5.1 - INTRODUCTION: Included in this section is a general guide for determining the possible causes of a failure and possible solutions. This guide is not intended to be all-inclusive.

More information

This document was created with FrameMaker 4.0.4

This document was created with FrameMaker 4.0.4 This document was created with FrameMaker.0. WELCOME TO TODAY S GENERATION OF COMFORT Congratulations! Your new, higher efficiency gas furnace is a sound investment which will reward you and your family

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS.......................... 2 INTERMITTENT IGNITION DEVICE...........

More information

IFT-RC150 IntelliFire Touch Remote Control Installation Instructions

IFT-RC150 IntelliFire Touch Remote Control Installation Instructions IFT-RC150 IntelliFire Touch Remote Control Installation Instructions Leave this manual with party responsible for use and operation. 1. Introduction The IFT-RC150 is a wall mounted device that is designed

More information

USERS INFORMATION MANUAL FOR GAS FIRED BOILERS

USERS INFORMATION MANUAL FOR GAS FIRED BOILERS USERS INFORMATION MANUAL FOR GAS FIRED BOILERS CATALOG NO.: 2000.52G Effective: 06-01-00 Replaces: 07-01-94 WARNING: If the information in this manual is not followed exactly, a fire or explosion may result

More information

LGB Gas fired boiler

LGB Gas fired boiler LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms

More information

Low pressure boiler* inspection and maintenance

Low pressure boiler* inspection and maintenance 2-12.001 May 2011 Low pressure boiler* inspection and maintenance Introduction Even as our society evolves into a more technologically advanced, economically driven environment, many businesses and their

More information

Dexter Commercial Vended Stack Washer Dryer. Dryer Troubleshooting, Fault Codes, And Schematics. Starting serial number (12/13)

Dexter Commercial Vended Stack Washer Dryer. Dryer Troubleshooting, Fault Codes, And Schematics. Starting serial number (12/13) Dexter Commercial Vended Stack Washer Dryer Dryer Troubleshooting, Fault Codes, And Schematics Starting serial number 481983 8533-070-001 (12/13) Dryer Trouble Shooting Electronic Control Diagnostic Lights

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL 2005 Lennox Industries Inc. Dallas, Texas, USA USER S INFORMATION MANUAL 13GCSX SERIES UNITS GAS PACKAGED UNITS (2 5 TONS) Armstrong # 38152A068 505,058M 05/09 Supersedes 08/05 Table of Contents Litho

More information

BERMAD Fire Protection

BERMAD Fire Protection Model: 400E-3M Bermad Electro-Pneumatically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING See unit nameplate for manufacturer and address. 507350-03 3/2016 Supersedes 9/2015 KG 024, 030, 036, 048, 060, 072, 074, 090 (2, 2-1/2, 3, 4, 5, 6 and 7-1/2 Tons) KG 092, 102, 120, 150 (7-1/2, 8 1/2,

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY...................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS.......................... 2 INTERMITTENT IGNITION DEVICE..........

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

SECTION WATER-TUBE BOILERS

SECTION WATER-TUBE BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections

More information

MULTIPLEX SELF RECUPERATIVE gas burner

MULTIPLEX SELF RECUPERATIVE gas burner Installation - Maintenance MULTIPLEX SELF RECUPERATIVE gas burner SERIES MPSR The Nu-way Multiplex Recuperative System offers the alternative of a self-recuperative burner or a separate recuperator and

More information

AFUE 95% Heating Input 50,000 to 200,000 Btuh

AFUE 95% Heating Input 50,000 to 200,000 Btuh PRODUCT SPECIFICATIONS WATER HEATERS / BOILERS GWM-IE Gas-Fired, Modulating, Condensing, Wall Hung Hot Water Boiler Bulletin No. 210650 March 2018 Supersedes December 2015 AFUE 95% Heating Input 50,000

More information

95M-200. Gas-Fired Direct Vent Modulating Hot Water Boiler. Control Manual And Troubleshooting Guide. P/N , Rev.

95M-200. Gas-Fired Direct Vent Modulating Hot Water Boiler. Control Manual And Troubleshooting Guide. P/N , Rev. 95M-200 Gas-Fired Direct Vent Modulating Hot Water Boiler Control Manual And Troubleshooting Guide P/N 24000604, Rev. C [04/09] WARNING! Revise boiler control parameters only if you fully understand the

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW/HORIZONTAL & DOWNFLOW TWO STAGE INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this manual is not

More information

southbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS:

southbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS: INSTALLATION AND OPERATION MANUAL GAS BOILERS MODELS: CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) southbend A MIDDLEBY COMPANY 1100 Old Honeycutt Road Fuquay-Varina, NC 27526 (919) 552-9161

More information

Natural Gas & Propane Burners

Natural Gas & Propane Burners Natural Gas & Propane Burners WARNING! IF YOUR PARTS WASHER USES A GAS BURNER: If you do not follow installation and operating instructions exactly, a fire or explosion may result, causing loss of life,

More information

Diocese of Cleveland Facilities Services Corporation

Diocese of Cleveland Facilities Services Corporation Diocese of Cleveland Facilities Services Corporation BOILER MAINTENANCE and SERVICING SEASONAL MAINTENANCE - to be performed by trained boiler technician or boiler contractor only: 1. Disassemble the low

More information

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. To obtain maintenance and repair standards for boiler burners (Section 15555A) and boiler tubes (Section 15555B), contact the DPS Project

More information

Installation Instructions

Installation Instructions Model 500-SP OVENPAK Burners Page 2300-S-1 Installation Instructions General Instructions Important: Do not discard packing material until all loose items are accounted for. To prevent damage in transit,

More information

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND Aqua Balance AquaBalance TM CONTROL MODULE QUICK START GUIDE 10 1 Domestic Hot Water temperature setpoint decreasing button 2 Domestic Hot Water temperature setpoint increasing button 3 Central Heating

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL HOT WATER HEATING BOILERS DOMESTIC WATER HEATERS 150,000-300,000 Btu/hr MODELS EB-EWU-02 IMPORTANT INSTALLER - AFFIX INSTALLATION MANUAL ADJACENT TO THE BOILER CONSUMER - RETAIN

More information

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Capacities W E A R E F R I E N D L Y T O T H E E A R T H Gas Fired DOUBLE-EFFECT Chiller-Heater Absorption Principle Yazaki MG-Series

More information

Fig. 1 - Unit PGD4, PGS4, WPG4

Fig. 1 - Unit PGD4, PGS4, WPG4 OWNER S MANUAL 14 SEER Single -Package Air Conditioner and Gas Furnace System with R -410A Refrigerant Single Phase 2 to 5 Nominal Tons Three Phase 3 to 5 Nominal Tons PGD4andPGS4SeriesE,WPG4SeriesB Fig.

More information

User's Infomation Manual

User's Infomation Manual User's Infomation Manual 574A GAS HEATING/ELECTRIC COOLING Cancels: OM01-69 OM10-28 02-07 NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Note to Installer:

More information

100T399-SOLA SUPPLEMENT TO INSTALLATION & OPERATION MANUAL INCLUDED WITH WATER HEATER (SERIAL NUMBERS BEGINNING LK AND LATER)

100T399-SOLA SUPPLEMENT TO INSTALLATION & OPERATION MANUAL INCLUDED WITH WATER HEATER (SERIAL NUMBERS BEGINNING LK AND LATER) 100T399-SOLA SUPPLEMENT TO INSTALLATION & OPERATION MANUAL INCLUDED WITH WATER HEATER (SERIAL NUMBERS BEGINNING LK AND LATER) WARNING If the information in these instructions is not followed exactly, a

More information

TO DO IF YOU SMELL GAS

TO DO IF YOU SMELL GAS User's Information Document 1125B User's Information Manual for Endurance EBP Series Modulating Combination Boiler (natural or propane gas) EDP Series Modulating Hydronic Boiler (natural or propane gas)

More information

O PE R AT I ON HO851G REVOLVING TRAY OVEN. MODEL HO851G GAS ML Pan ML Pan ML Pan ML Pan

O PE R AT I ON HO851G REVOLVING TRAY OVEN. MODEL HO851G GAS ML Pan ML Pan ML Pan ML Pan O PE R AT I ON HO851G REVOLVING TRAY OVEN MODEL HO851G GAS ML-132160 24 Pan ML-132161 18 Pan ML-132258 36 Pan ML-132259 30 Pan 701 S. RIDGE AVENUE TROY, OHIO 45374-0001 937-332-3000 www.hobartcorp.com

More information

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS MVB, TYPE WH - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 3500.952C Effective: 06-25-15 Replaces: 12-22-09 DIVISION 23 34 36.29 COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

More information

Niles Steel Tank Hot Water Generator Installation and Operation Manual

Niles Steel Tank Hot Water Generator Installation and Operation Manual Niles Steel Tank Hot Water Generator Installation and Operation Manual Contents: Contents 1 Hazard definitions 1 1. General Information.... 2 Availability... 3 Optional Control Packages... 5 2. Installation....

More information

Emerson Blue Easy Set 1H/1C

Emerson Blue Easy Set 1H/1C Emerson Blue Easy Set 1H/1C Model: 1F86EZ-0251 Non-Programmable Thermostat with 3 Temperature Pre-Sets Home, Sleep and Away Installation Instructions and User Guide Message to Homeowner Congratulations

More information

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING See unit nameplate for manufacturer and address. 507258-04 7/2018 Supersedes 10/2017 ZG 036, 048, 060, 072, 074 (3, 4, 5 and 6 Tons) ZG 092, 102, 120, 150 (7-1/2, 8-1/2, 10 and 12 Tons) ROOFTOP UNITS ZG

More information

ED510 DISPLAY MODULE. FOR USE WITH FIREYE FLAME-MONITOR AND MicroM BURNER MANAGEMENT CONTROLS DESCRIPTION INSTALLATION APPROVED

ED510 DISPLAY MODULE. FOR USE WITH FIREYE FLAME-MONITOR AND MicroM BURNER MANAGEMENT CONTROLS DESCRIPTION INSTALLATION APPROVED ED-5101 APRIL 3, 2013 ED510 DISPLAY MODULE FOR USE WITH FIREYE FLAME-MONITOR AND MicroM BURNER MANAGEMENT CONTROLS APPROVED DESCRIPTION The ED510 Display Module is designed to operate with the FLAME-MONITOR

More information

Gas Fired Humidifier. SKG Series Combustion Field Adjustment Instructions. SKG Combustion Field Adjustment Instructions

Gas Fired Humidifier. SKG Series Combustion Field Adjustment Instructions. SKG Combustion Field Adjustment Instructions Fired Humidifier SKG Series SKG - 180301 Standard Combustion Adjustment SKG Fired Humidifier All installation work must be carried out by suitably qualified personnel and must conform to local codes and

More information

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System. The Fireye EP260, EP270 (early spark termination), or EP265 (pilot stabilization) programmer modules are used with the FLAME-MONITOR Burner Management Control System (P/N E110). Several operational characteristics

More information

V-VTP Maintenance Manual

V-VTP Maintenance Manual V-VTP Maintenance Manual PO Box 501 Denver, NC 28037 ph: 704-483-9316 / fx: 704-483-4538 sales@leonardautomatics.com - http://leonardautomatics.com Maintenance Guide Proper maintenance of the tunnel finisher

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 1005A-2005A SUGGESTED SPECIFICATIONS Catalog No.: 6000.63B Effective: 3-01-15 Replaces: 9-01-09 WATER-TUBE POOL HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes condensing,

More information

READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING 2005 Lennox Industries Inc. Dallas, Texas, USA 505,058M (38152A068) 08/05 Supersedes 06/05 13GCSX Series Units Improper installation, adjustment, alteration, service or maintenance can cause property damage,

More information

KGA092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

KGA092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING See unit nameplate for manufacturer and address. 506380 01 11/2009 KGA024, 030, 036, 048, 060, 072 (2, 2 1/2, 3, 4, 5, and 6 Tons) KGA092, 102, 120, 150 (7 1/2, 8-1/2, 10, and 12 Tons) KGA180, 210, 240,

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 504A-2004A SUGGESTED SPECIFICATIONS Catalog No.: 2000.933C Effective: 06-25-15 Replaces: 12-21-09 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C)

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C) Models 51, 51-S and 53 Boiler Water Feeders Models 51-2, 51-S-2 and 53-2 Feeder Cut-Off Combinations McDonnell & Miller Installation & Maintenance Instructions MM-315(C) OPERATION Maximum Water Supply

More information

V SERIES HDR GAS RANGES

V SERIES HDR GAS RANGES SERVICE MANUAL ONE POWERFUL PACKAGE V SERIES HDR GAS RANGES TOPS Open Top Hot Top Griddle Top Work Surface BASES Standard Oven Convection Oven Cabinet Base - NOTICE - This manual is prepared for use by

More information

Energy-Efficient, Environmentally-Friendly Heating Solutions. Baxi Luna HT Residential Troubleshooting Guide

Energy-Efficient, Environmentally-Friendly Heating Solutions. Baxi Luna HT Residential Troubleshooting Guide Energy-Efficient, Environmentally-Friendly Heating Solutions Baxi Luna HT Residential Troubleshooting Guide WARNING! THIS DOCUMENT IS INTENDED ONLY AS AN EDUCATIONAL TOOL THIS TROUBLESHOOTING GUIDE, AND

More information

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD Corona Corporation This instruction manual contains important information for safe use of this device. Keep this instruction manual

More information

Model No: Little Devil II (inc ss)

Model No: Little Devil II (inc ss) GAS HEATER Model No: Little Devil II (inc ss) PART NO: 6926020, 6926025 (SS) OPERATION & MAINTENANCE INSTRUCTIONS LS1213 INTRODUCTION Thank you for purchasing this CLARKE Gas Heater. Before attempting

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 2505-4005 SUGGESTED SPECIFICATIONS Catalog No.: 6000.70 Effective: 09-15-16 Replaces: NEW WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes condensing, gas-fired

More information

Control Panel For Water Wash Hoods AM2

Control Panel For Water Wash Hoods AM2 Control Panel For Water Wash Hoods AM2 For further information Call: (919) 554-1025 Or Fax: (919)554-1525 Aqua-Matic 117 Franklin Park Ave. Youngsville, NC 27506 TABLE OF CONTENTS AQUA-MATIC LIMITED WARRANTY

More information

Owner s Information Manual

Owner s Information Manual 48ES---A and 48VL---A Comfort and Performance 13 and 14 SEER Single Packaged Air Conditioner and Gas Furnace System With Puron (R---410A) Refrigerant Single and Three Phase 2---5 Nominal Tons (Sizes 24---60)

More information

INSTALLATION INSTRUCTIONS # BURNER ASSEMBLY REPLACEMENT

INSTALLATION INSTRUCTIONS # BURNER ASSEMBLY REPLACEMENT INSTALLATION INSTRUCTIONS # 00-858726 BURNER ASSEMBLY REPLACEMENT C24GA BURNER ASSEMBLY REPLACEMENT Verify steamer has a K3 relay (1, Fig. 1) installed. If K3 relay is not in steamer, one must be installed

More information

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV ClearFire Economizer Model ECF Integral or External Addendum to manuals 750-295 CFH and 750-269 CFV CB-8466 08/2011 1-GENERAL The Model ECF economizer is a stainless steel coil tube arrangement using

More information

Eclipse Self-Check UV Scanner

Eclipse Self-Check UV Scanner 856 Instruction Manual 10/18/2010 Eclipse Self-Check UV Model 5602-91 Version 1 Introduction The self-check UV is used for continuous gas or oil flames. A mechanical shutter in the scanner closes briefly

More information

INSTALLATION & MAINTENANCE MANUAL GAS FIRED DOOR HEATER Series 79, DH22 AND DH24

INSTALLATION & MAINTENANCE MANUAL GAS FIRED DOOR HEATER Series 79, DH22 AND DH24 INSTALLATION & MAINTENANCE MANUAL GAS FIRED DOOR HEATER Series 79, DH22 AND DH24 DM018 REV 4/23/18 Order # Model # Mounting Position Wiring Dia. Symbol MFR S NAME PART NO. PUBLICATION NO. DESCRIPTION HARTZELL

More information

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION R SERIES 35-703 120 VAC Microprocessor-Based Intermittent Pilot Ignition Control F-35-703 July 2016 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

SERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS

SERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS SERIES 35-63J INSTALLATION INSTRUCTIONS FOR REPLACING JOHNSON CONTROLS G77X AND OTHER MODELS WITH FENWAL SERIES 35-63J IP IGNITION CONTROL APPLICATIONS The Fenwal 35-63J series Intermittent Pilot Ignition

More information

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 0804 L2 Revised 05 05 2008 G71MPP G71MPP SERIES UNITS G71MPP series units are high efficiency multi position (upflow, downflow, horizontal right and left) gas furnaces equipped

More information

CSD-1 COMMERCIAL BOILER CONTROLS

CSD-1 COMMERCIAL BOILER CONTROLS SUPPLEMENTAL INSTALLATION AND OPERATING INSTRUCTIONS CSD- COMMERCIAL BOILER CONTROLS P/N 400043, Rev. A [/03] CSD- COMMERCIAL BOILER CONTROLS! WARNING Fire, explosion, asphyxiation and electrical shock

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification LMV52 Control Product Description February 3, 2017 The LMV52 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft burners.

More information

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance Model: 400E-5M Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset Installation Operation Maintenance Application Engineering Bermad 1. Safety First BERMAD believes

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC2 THRU NVC6 ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx WITH CONTROLINKS CONTROLS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas

More information

NOZZLE MIX COMBINATION BURNER NMC200 SERIES

NOZZLE MIX COMBINATION BURNER NMC200 SERIES NOZZLE MIX COMBINATION BURNER NMC200 SERIES INSTRUCTIONS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its

More information

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS XPAK FT TYPE H - MODELS 088AR-398A SUGGESTED SPECIFICATIONS Catalog No.: 2100.91 Effective: 05/01/15 Replaces: new DIVISION 23 52 33.13 WALL-HUNG STAINLESS STEEL HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 2-Stage R-410A Split System These units have been designed and tested for capacity & efficiency in accordance with A.H.R.I. Standards.

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2004-28 TSG-SOLO-9/04 Table of Contents INTRODUCTION Page 1 SERVICING TIPS AND INSTRUCTIONS Page 3 CONTROL MODULE DISPLAY -

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

IMPORTANT SAFETY INFORMATION! WARNING ALWAYS keep electric cords, home furnishings, drapes, clothing, papers, or other combustibles at least 3 feet (0

IMPORTANT SAFETY INFORMATION! WARNING ALWAYS keep electric cords, home furnishings, drapes, clothing, papers, or other combustibles at least 3 feet (0 Electric Fireplace Factory Model: EF-30D CONSUMER SAFETY INFORMATION Read this manual before installing and operating this appliance Failure to follow these instructions may result in electric shock, fire

More information