INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

Size: px
Start display at page:

Download "INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM"

Transcription

1 INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM Mingjie Zheng Research Laboratory, SANKO AIR CONDITIONING CO., LTD. Nagoya, , JAPAN ABSTRACT In large enclosures such as gymnasiums, it is difficult to control the air temperature and create a comfortable climate for people with respect to the heating condition. There are two main reasons that the air temperature in an occupied area is not increased efficiently in large enclosures. 1) Hot supplied air goes up and stays in the upper area due to buoyancy and it takes long time to reach the lower occupied area. 2) The heat capacity of the building structure affects the air temperature and cold air stays in the lower area. In this paper, the results of measurements regarding the pick-up time and the thermal environment of the residential region in a large gymnasium with under-floor air return system were considered. Furthermore, the effects of simultaneous use of the panel heater and the air supply method on the pick-up characteristic in heating condition and the energy consumption of the HVAC system to be investigated is discussed by coupled analysis of AHU outlet air temperature control simulation and CFD including the building structure. KEYWORDS Large Gymnasium, Characteristics in Heating Condition, PI control, CFD INTRODUCTION It is inefficient heating method in large space such as gymnasium when the location of air outlet or inlet is not appropriate even if the capacity of heat source and air conditioner is adequate. For instance, when the warmed air is supplied along the upper wall, the pick-up time in heating condition will become longer since the warm air stays in the upper area of the room and do not come down to the residential region 1) (Figure 1). In this paper, the measurement results regarding the pick-up time in heating condition and the thermal environment of residential region in a large gymnasium with the under-floor air return system were considered as a solution for this problem (Figure 2). The air supply method of HVAC system in the building to be investigated is designed to be alternative between the under-floor air supply method (Figure 2) and the under-floor air return method (Figure 3). The panel heater is also equipped in the seating area on the second floor. As a consequence, the pick-up time in heating condition of the HVAC system to be investigated is affected by the air supply method and whether or not the panel heater is simultaneously used in addition to the initial room temperature, the initial of structures under the floor and the thermal storage property of floor. Therefore, in this study, the effects of the simultaneous use of panel heater and the air supply method is investigated on the pick-up characteristics in heating condition and on the energy consumption of the HVAC system by the coupled analysis of supply air temperature control simulation and CFD including the building structures. Corresponding Author: Tel: , Fax: address: zheng@sanko-air.co.jp

2 Outlets Outlets Inlets Stay of warm air Spaces under Floor Spaces under Floor Exhaust Openin g Stay of cool air Inlets 2F Seats for audiences Outlets Machine Room 2F seats for audiences Machine Room Return air Return air duct Supply air Supply air duct Figure1. Problem of Air Condition in Heating Condition of Large Enclosure Figure2. Outline of Under-Floor Air Return System Figure3. Outline of Under-Floor Air Supply System MEASUREMENT OUTLINE The building to be investigated is Jukai Dome built on June 05 in. The overviews of the building and the HVAC system are presented in Table 1 and 2, respectively. The items, places and devices of measurement are presented in Table 3, and the shape of the building and the measurement points are shown in Figure 4. The set values associated with the control system at the time of measurement are presented in Table 4. Three cases, of which the presence or absence of simultaneous use of panel heater is combined with two types of air supply method, were established in the measurement. However, valid measurement results were obtained only from the cases with simultaneous use of panel heater due to various reasons. Therefore, there was no other way but to examine the effects of the simultaneous use of panel heater and the air supply method on the pick-up time in heating condition by performing coupled analysis of supply air temperature control simulation and CFD including the building structures. Table1 Outline of Building Location Odate City, Akita Prefecture usage Dome Total floor area 8,367m 2 Height 19.1m Main structure RC wooden(parts) S Seats 1,600 Table2 Outline of HVAC System Air(Water) supply [m 3 /h] Outdoor air volume [m 3 /h] Heating ability [kw] Setting position [m] Supply along wall 1FL ,000 42, Supply from floor surface Arena floor surface Panel heater FL+0.3 Table3 Measurement items, places and devices Measurement items Measurement places(refer figure 3) Measurement devices Temperature and humidity in arena A B E 2*3 Wireless small-sized residential region audience seats C D 2*2 thermometer and hygrometer Floor surface D E 1*2 ceiling A B 1*2 Small-sized thermometer Surface temperature Concrete surface of Measurement pointb E 1*2 Small-sized thermometer South wall surface 1 Small-sized thermometer Under floor temperature and humidity Under floor 3 Wireless small-sized thermometer and hygrometer Temperature near ceiling Near point A B 1*2 Central monitor Outlet and inlet temperature Outlet, inlet 4*2 Wireless small-sized thermometer and hygrometer AHU supply and return air temperature Outlet and inlet of AHU 4*2 Central monitor Supply and return water temperature Outlet and inlet of heat source 1*2 Central monitor Outdoor air temperature and humidity Out space of dome 1 Central monitor

3 Table4 Control set value in measurement Warming up time(no outdoor air) 30 minutes Return air set temperature 15 Panel heater operating time 60 minutes Proportional band(p) 3 Outlet set temperature of boiler 75 Integral time(ti) 7 s Control time step 30 s Integral sample period(dt) s WS-2 FL+1,0 FL+0 FL+1,0 FL+0 FL+1,0 FL+1,0 FL+1,0 FL+0 FL+0 FL+0 (a) Cross-sectional view [mm] SA-3 F-1 C SA-1 A E B D F-2 SA-2 WS-2 SA-4 (b) Floor plan [mm] surface temperature air temperature surface temperature Supply air temperature Inlet air temperature Air temperature measurement position Figure4. Building shape and measurement points (A - E) MEASUREMENT RESULTS AND DISCUSSION PICK-UP CHARACTERISTIC IN HEATING CONDITION OF UNDER-FLOOR AIR RETURN SYSTEM The measurement results of the temperature in residential region and the under-floor return air under simultaneous use of panel heater and under-floor air return are shown in Figure 5, and the timely change of air temperature at each measurement point is presented in Figure 6. The pick-up time in heating condition in arena

4 and the seating area was 70 and 60 minutes, respectively. Since the heat is absorbed by the building structures under the floor, the air temperature around the inlet under the floor was lower than that around the floor opening except for the value measured at when the HVAC system started to operate. Hence, the air temperature around the inlet under the floor was lower than that of residential region. temperature [ ] audience seat arena return air set temperature :30 11:30 :30 13:30 temperature[ ] :30 11:30 :30 13:30 inlet return air Figure5. Temperature in residential region Figure6. Under-floor air temperature valve open rate[%] suitable open rate request open rate 0 :00 :30 11:00 11:30 Figure7. AHU valve opening rate(2/) DISCUSSION REGARDING THE SUPPLY AIR TEMPERATURE CONTROL METHOD The AHU supply air temperature is controlled by the return air temperature. However, the return air temperature and the inlet air temperature (similar to the temperature in the residential region of arena) are different as shown above. For instance, as seen in Figure 5, the air temperature measured at 1.1m above the arena floor was higher than the set value of 15 at. This happened because the outlet air temperature was over controlled since the return air temperature was below 15 even though the inlet air temperature around the floor opening was higher than 15. Therefore, it seems that the control temperature (= the return air temperature) or the set value of room air temperature should be set slightly lower if the temperature of structure under floor is lower than the inlet air temperature when heating. COUPLED ANALYSIS OF SUPPLY AIR TEMPERATURE CONTROL SIMULATION AND CFD In order to investigate the effect of simultaneous use of panel heater and the air supply method on pick-up characteristics in heating condition, the coupled analysis was performed for the outlet air temperature control simulation and unsteady state CFD including the building structure. Table5 Calculation condition of building skin, floor and under floor concrete Outer wall Inner wall ceiling window floor slub Surface heat transfer coefficient [W/(m 2 K)] Outer surface temperature [ ] Initial temperature [ ] ANALYSIS METHOD The space to be investigated and the locations for the air outlets are symmetric between East and West sides of the building. Hence, only the West side of the space to be investigated was considered for CFD analysis. It is necessary to replicate the temperature change of return air and outlet air precisely in order to perform the analysis including the HVAC operating state which changes with time. The return air temperature depends on the indoor vertical temperature distribution, the heat transfer characteristic of the surface and the heat capacity of the building structure. Therefore, the material and the construction of each building structure are included in CFD model in order to replicate the heat capacity of structure. The heat transfer coefficient, the surface temperature and the initial temperature, which are all required for calculation, are shown in Table 5. In order to replicate the supply air temperature, it is necessary to model AHU hot water valve opening rate appropriately. In general, the amount of heat exchange of AHU is the exponential function of the hot water flow

5 rate, and it is considered that the amount of heat exchange of AHU is proportional to the valve opening rate since the actual valve has equal percentage characteristic. The temperature difference between the outlet and inlet of the hot water coil is a linear function of the hot water valve opening since the HVAC system is a CAV system. Then, the demand opening rate of AHU hot water valve is obtained by the following formula using the return air temperature calculated with CFD, the set value of room temperature, and the control parameter of hot water valve opening rate as shown in Table Demand Opening Rate = e + e dt (1) p Ti 0 Where, e is the difference between return air temperature and set temperature. However, immediately after the operation start of HVAC system, even if the AHU hot water valve opening rate is demanded to be 0%, the temperature difference between the outlet air and return air could not become the maximum right away since the outlet air temperature is affected by the heat capacity of AHU, operation time of the hot water valve and the heat loss from the supply air duct. In order to calculate the outlet air temperature correctly, the data such as the temperature around the air supply duct are required; however, it is very difficult to obtain these data. Therefore, in this study, suitable valve opening rate is calculated from the following formula, assuming that the maximum temperature difference between the measured outlet air temperature and the return air temperature is equivalent to the temperature difference observed with the maximum AHU hot water valve opening rate (=88%), and it is set to be the hot water valve opening rate for the time period from the HVAC system start until 90 minutes later. suitable open zone rate = MAX outlet air temperature AHU inlet temperature ( AHU outlet air temperature AHU inlet air temperature) Where, the value 88 is the maximum demand valve opening rate calculated by the formula (1) using the return air temperature difference between the measurement data obtained on February and the set value. The demand opening rate and the suitable opening rate of AHU hot water valve calculated by the measurement data taken on February are shown in Figure 7. This shows that the suitable opening rate is becoming larger gradually, unlike the demand opening rate, during the period from the HVAC system start until approximately 90 minutes later due to the reasons associated with the heat capacity of the AHU and duct as well as operation time of the hot water valve, etc. Therefore, in the following simulation, the suitable opening rate which had been calculated by the measurement taken on February is set as the AHU hot water valve opening rate when the demand opening rate is larger than the suitable opening rate during the period from the HVAC system start until 90 minutes later. In addition, the AHU hot water valve opening rate is estimated by the following equation assuming that the heat loss from the air supply duct is approximately 5%. AHU hot water valve opening rate = Demand opening rate 0.95 (3) Based on all above, the AHU hot water valve opening rate can be estimated for all the periods. Then, the outlet air temperature is calculated assuming the inlet/outlet temperature difference of hot water coil to be proportional to the valve opening rate. The calculation method for outlet air temperature hourly in each case is described as the following. step 1. The suitable opening rate of hot water valve is calculated from the temperature difference between outlet air and return air measured hourly on February. step 2. The return air temperature is obtained by performing CFD for 5 minutes with the initial value of the outlet air temperature as the measurement taken on February. step 3. The AHU hot water valve opening rate at the time step now is determined by comparing the calculated return air temperature to the suitable opening rate obtained in the step 1. Then, the outlet air temperature of the next time step is calculated using the following formula. air 88 (2)

6 outlet air + MAX( outlet temperature = AHU inlet air air temperature AHU inlet temperature air temperature ) valve opening rate (4) step 4. Using the calculated return air temperature as an input to CFD, the step 2 is repeatedly performed until the calculation time is over. 3-dimensions computational fluid analysis program based on the standard k-ε model, with which the result is obtained with relatively rough divisions 2), is used for the unsteady state CFD analysis. The SIMPLE method, which is less strict with calculation time interval ( t) and less diverge in calculation 3), is used as the finite difference scheme of time. However, it has been indicated that the number of repeated calculation become unstable and the accuracy of the solution is lost when t is too large with the SIMPLE method though it gives a fairly stable result even if the value of t has been set somewhat large 4). Therefore, the value of t was set as large as possible as a precondition that the stability and accuracy of the solution are to be secured. In terms of the primary analysis condition associated with convergence of unsteady state CFD analysis, the following conditions were set; Mesh Number = 79(x) 56(y) 5(z) (irregular interval), the convergence constant of simultaneous linear equations is to be 0.01, and the convergence judgment condition of pressure modification is to be 1.0E-4. REPERTABILITY OF SIMULATIONS The timely change of the measurement and the calculated value of air temperature at 1.1m above the arena floor, the AHU return air temperature, the surface temperature under the floor and the ceiling temperature on February is shown in Figure Although the calculated value of the temperature at each measurement point did not replicate the measured value perfectly, the change tendency over time of them is almost the same one. Therefore, by using the prepared model, it is possible to consider the effect of each factor on pick-up time in the heating condition. DISCUSSION BY SIMULATION In order to investigate the effects of simultaneous use of the panel heater and the air supply method on the pick-up characteristic in heating condition, coupled analysis of AHU outlet air temperature control simulation and unsteady state CFD including the building structure was performed with the calculation conditions shown in Table 6. The comparisons in changes over time among three cases of the air temperature at 1.1 m above the arena floor, the AHU return air temperature, the surface temperature under the floor, and the ceiling temperature are described in Figures -15. The pick-up time in heating condition and the calculated sum of HVAC energy consumption are shown in Table 7 for each case. Table 6 Calculation of each CASE CASE Panel yes no yes heater HVAC Under-floor Under-floor Under-floor system return air return air supply air Table 7 Calculation of each CASE CASE Measurement Pick-up time in heating condition [min] Energy consumption of HVAC system [kw h] THE EFFECT OF SIMULTANEOUS USE OF PANEL HEATER As shown in Figure, even though the air temperature at 1.1m above the arena floor is lower when only HVAC system (Case-2) is used compared to when the panel heater (Case-1) is simultaneously used in the first 50 minutes period after the start of HVAC system, the difference between the two cases becomes small afterward. This happens since the outlet air temperature is low in the first 50 minutes period after the start of HVAC system and therefore the heating effect of the panel heater becomes obvious while it diminishes as the outlet air

7 temperature rises afterward. Therefore, the pick-up time in heating condition in Case-2 is longer only by minutes than that in Case-1. Also, it is considered as an error of CFD that the calculated value of pick-up time in heating condition in Case-1 is minutes longer than the measured value. THE EFFECT OF AIR SUPPLY METHOD In case of the under-floor air supply system (Case-3), the temperature in the arena residential region is lower than that in Case-1 in the first 45 minutes period after the start of HVAC system. This happens because the temperature of the air outlet from the floor opening is lowered due to the heat absorption by the building structure under the floor. After 45 minutes from the start of HVAC system, since the AHU outlet air temperature rapidly increased due to the integral action of PI controller, the pick-up time in heating condition of Case-3 is shortened by minutes than that of the under-floor air return system (Case-1) to 50 minutes. In addition, according to Figure 13, the floor surface temperature in Case-3 is higher than that in other cases. This indicates that, in case of under-floor air supply system, outstanding floor heating effects are obtained from the under-floor return air. However, the ceiling temperature in Case-3 is lower than those in other cases. This indicates that the indoor vertical air temperature difference of under-floor air supply system is less than that of under-floor air return system. According to Table 7, the sum of the HVAC energy consumption during the calculation period (1.5h) in Case-3 is 155.4[kW h], lower than that in Case-1 by 33.1[kW h]. Namely, the sum of the HVAC energy consumption during the calculation period when the under-floor space is used as air supply route is less by 17% than that when the under-floor space is used as air return route. CONCLUSIONS In this study, the pick-up characteristic in heating condition of a large-scale gymnasium with under-floor air supply/return system is considered by measurement and simulation, and the following findings were obtained. 1. It is considered that the control temperature (= return air temperature) or the set room air temperature should be slightly lowered when the temperature of under-floor structure is lower than the inlet air temperature in heating condition. 2. Compared to the case with the heating system only, the pick-up time in heating condition is shortened approximately by minutes in case of simultaneous use of panel heater. 3. Compared to the under-floor air return system, floor heating effect could be obtained in the under-floor air supply system. Hence, the pick-up time in heating condition is shortened approximately by minutes, and the HVAC energy consumption is reduced by 17.5% approximately too. ACKNOWLEDGMENT I wish to express my most sincere thanks to the members concerned in Odate City, the Urban Regeneration Mechanism and the Odate City JYUKAI park gymnasium for their cooperation to measurement. REFERENCES 1. Nobuyuki Kobayashi et al. (03) Study on Heating System of Gymnasiums, SHASE Transactions, No.89 (Japanese) 2. Shinnsuke Katou ( ) Application to indoor atmosphere of CFD (1~7), SHASE, volume (Japanese) 3. Kouji Sakai and Osamu Ishihara (02) A Measurement of Thermal Performance of Floor Inlet Air-Conditioning System Applied for Gymnasium, AIJ Summaries of Technical Papers of Annual Meeting (Japanese) 4. Koji Sakai and Masaki Manage (03) CFD Simulation of Gymnasium Adopted Floor Outlet Air Conditioning System (Part.1) A Study on Numerical Analysis of Time Dependence Room Air Flow, SHASE Technical Papers of Annual Meeting (Japanese)

8 5. Mingjie Zheng et al (04) Indoor Climate of a Large Enclosure with Under Floor Return System in Heating Condition, SHASE Technical Papers of Annual Meeting (Japanese) 6. Mingjie Zheng (07) Indoor Climate of a Large Enclosure with Under Floor Supply/Return System in Heating Condition, AIJ Tokai Chapter Architectural Research Meeting (Japanese) FL+1.1m temperature [ ] measurement calculation return air temperature [ ] measurement calculation 9: 9: :00 9: 9: :00 Figure 8. Air temperature(fl+1.1m, B) Figure 9. Return air temperature floor surface temperature [ ] 9: measurement calculation 9: :00 ceiling surface temperature [ ] measurement calculation 9: 9: :00 Figure. Floor surface temperature(b) Figure 11. Ceiling temperature(b) CASE-1 CASE-2 CASE-3 CASE-1 CASE-2 CASE-3 FL+1.1m temperature [ ] 9: 9: :00 9: 9: :00 return air temperature [ ] Figure. Air temperature(fl+1.1m, B) Figure 13. Return air temperature floor surface temperature [ ] CASE-1 CASE-2 CASE-3 9: 9: :00 ceiling surface temperature [ ] CASE-1 CASE-2 CASE-3 9: 9: :00 Figure. Floor surface temperature(b) Figure 15. Ceiling temperature(b)

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon

More information

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Y. Momoi 1, K. Sagara 1, T. Yamanaka 1 and H. Kotani 1 1 Osaka University, Graduate School of Eng., Dept.

More information

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect A Numerical Investigation on the Effect of Operation Control of a Multi-Split Air-Conditioning System on Indoor Thermal Environment H. Matsunaga 1,*, S. Iizuka 1, M. Okumiya 1, G. Yoon 2, and H. Niwa 3

More information

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Comparison of Thermal Comfort by Radiant Heating and Convective Heating Journal of Engineering, Project, and Production Management 2015, 5(1), 26-35 Comparison of Thermal Comfort by Radiant Heating and Convective Heating Shigeru Imai 1 and Shoichi Kojima 2 1 MSc Student, Department

More information

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Liu Jing 1, Yoshihiro Aizawa 2, Hiroshi Yoshino 3 1 School of Municipal

More information

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research

More information

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen Numerical Simulation of Ventilation Efficiency in Commercial Kitchen Yasushi Kondo 1, Shin-ichi Akabayashi 2, Osamu Nagase 3 and Akihiko Matsuda 4 1 Dept of Architecture, Musashi Institute of Technology,

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0141 ISBN: 978-83-7947-232-1 Prediction of exhaust gas stagnation in common corridor of apartments with gas water heater Takuro Nakamura

More information

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings - 1 - Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings Mamoru Hamada, Living Environment Systems Laboratory, Mitsubishi Electric Co., Kamakura, Kanagawa, Japan Naomichi

More information

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose

More information

AMOUNT OF MOISTURE PRODUCED INSIDE BATHROOM AND APPURTENANT CHANGING ROOM

AMOUNT OF MOISTURE PRODUCED INSIDE BATHROOM AND APPURTENANT CHANGING ROOM AMOUNT OF MOISTURE PRODUCED INSIDE BATHROOM AND APPURTENANT CHANGING ROOM K. Yokoo 1, S. Tanabe 1, Y. Aizawa 2, K. Inagaki 2, D. Kawamata 2, H. Amai 1, K. Watanabe 1, and T. Nishimasu 1 1 Waseda University,

More information

Study on Drying Shrinkage Strain and Moisture Transfer in Concrete with Finish Coating Materials

Study on Drying Shrinkage Strain and Moisture Transfer in Concrete with Finish Coating Materials Study on Drying Shrinkage Strain and Moisture Transfer in Concrete with Finish Coating Materials Takuya Hasegawa 1,* and Osamu Senbu 1 1 Hokkaido University, Japan * Kita 13, ishi 8, Kita-ku, Sapporo 060-8628,

More information

Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li

Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li Aalborg Universitet Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li Published in: Clima 2010 : 10th Rehva World Congress Publication date:

More information

Residential Building Walls and Environment in Amman, Jordan

Residential Building Walls and Environment in Amman, Jordan Int. J. of Thermal & Environmental Engineering Volume 3, No. 2 (211) 1-7 Residential Building Walls and Environment in Amman, Jordan S. J. Sulaiman*, N. Beithou Department of Mechanical Engineering, Applied

More information

STUDY ON THE EFFECTIVENESS OF AIR-CONDITIONING AND VENTILATION SYSTEMS BY CFD ANALYSIS IN HOUSES

STUDY ON THE EFFECTIVENESS OF AIR-CONDITIONING AND VENTILATION SYSTEMS BY CFD ANALYSIS IN HOUSES STUDY ON THE EFFECTIVENESS OF AIR-CONDITIONING AND VENTILATION SYSTEMS BY CFD ANALYSIS IN HOUSES Hiroko Kaji 1, Shin-ichi Akabayashi 1, and Jun Sakaguchi 2 1 Division of Science and Technology, Graduate

More information

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen * Journal of Environmental Protection, 2013, 4, 638-646 http://dx.doi.org/10.4236/jep.2013.46073 Published Online June 2013 (http://www.scirp.org/journal/jep) The Research of Performance Comparison of Displacement

More information

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM Yoshihiro Aizawa 1, Shin-ichi Tanabe 2, Kanako Yokoo 2, Kentaro Watanabe 3, and Hideki Amai 4 1 Tokyo Gas Co. Ltd., Tokyo, Japan 2 Waseda

More information

Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement

Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement Daisuke Ogura 1, Masahide Inuzuka 2, Shuichi Hokoi 1, Takeshi Ishizaki 2, Hiroyuki Kitahara

More information

Development of Induction Heating Device for Corner of Bloom in Continuous Casting machine

Development of Induction Heating Device for Corner of Bloom in Continuous Casting machine Technical Report Development of Induction Heating Device for Corner of Bloom in Continuous Casting machine Yasuaki MIURA Plant & Machinery Division Steel Plant Engineering Department Ⅱ Continuous Caster

More information

Estimation of Spray Lubrication and Die Temperature for Die Wear Life Prediction in Hot Forging

Estimation of Spray Lubrication and Die Temperature for Die Wear Life Prediction in Hot Forging 0 Research Report Estimation of Spray Lubrication and Die Temperature for Die Wear Life Prediction in Hot Forging Masatoshi Sawamura, Yasuhiro Yogo, Sayuri Kondo, Toshiaki Tanaka, Koukichi Nakanishi, Toshiyuki

More information

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model Yoshiyuki Shimoda, Osaka University Takuro Fujii, Osaka University Takao Morikawa, Osaka University Minoru

More information

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Effects of Latent/Sensible Heat Separation -Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Shotaro Sakai 1,*, Takashi Akimoto 1, Yumiko Miyasaka 2 1 Shibaura

More information

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air Anna Pacak 1,*, Andrzej Jedlikowski 1, Demis Pandelidis 1, and Sergey Anisimov 1 1 Wrocław University of

More information

HEAT EXCHANGER FORMULAS & EXAMPLE

HEAT EXCHANGER FORMULAS & EXAMPLE Formulas for Heat Exchanger System using a Modulating Control Valve Definition of Terms and Units: E = Mean Heat Transfer Rate or Heat Load (Btu/hr) E D = Design Heat Load (Btu/hr) U = Overall Heat Transfer

More information

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING Vladimír Zmrhal 1, Jan Hensen 2 and František Drkal 1 1

More information

APPLICATION OF HEAT PUMP SYSTEM FOR ECO-FRIENDLY VEHICLES

APPLICATION OF HEAT PUMP SYSTEM FOR ECO-FRIENDLY VEHICLES Numbers of Abstract/Session (given by NOC) - 1 - APPLICATION OF HEAT PUMP SYSTEM FOR ECO-FRIENDLY VEHICLES Toshihisa Kondo, Acting Manager, Future Systems Designing Group, Automotive Thermal Systems Department,

More information

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN -9 The 5 World Sustainable Building Conference, Tokyo, 7-9 September 5 (SB5Tokyo) ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN Kahori GENJO Dr.Eng. Shin-ichi MATSUMOTO Dr.Eng

More information

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

ZONE MODEL VERIFICATION BY ELECTRIC HEATER , Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting

More information

Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump

Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump Koji Fujita, Graduate Student, Graduate School of Science and Technology, Kobe University; 039d892n@stu.kobe-u.ac.jp Atsushi

More information

Heat transfer and heating rate of food stuffs in commercial shop ovens

Heat transfer and heating rate of food stuffs in commercial shop ovens Sādhanā Vol. 32, Part 5, October 2007, pp. 535 544. Printed in India Heat transfer and heating rate of food stuffs in commercial shop ovens P NAVANEETHAKRISHNAN,PSSSRINIVASAN and S DHANDAPANI Department

More information

1.1. SCOPE OF THE WORK:

1.1. SCOPE OF THE WORK: Chapter 1: Introduction 1 1. INTRODUCTION 1.1. SCOPE OF THE WORK: Multi-stage refrigeration systems are an area of growing industrial importance in large plants. These systems are known to be large power

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 217 Europe July 2-5, 217, Lublin, Poland Paper ID 95 ISBN: 978-83-7947-232-1 Verification of gymnasium designed by high thermal insulation considering elderly people in disaster Koki

More information

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1 Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9

More information

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING Rebeca Barbosa 1, Martin Barták 1, Jan L. M. Hensen 1, 2, Marcel G. L. C. Loomans 2 1 Czech Technical

More information

TESTS OF ADSIL COATING

TESTS OF ADSIL COATING TESTS OF ADSIL COATING Test B - Long Term Test FSEC-CR-1259-01 July 11, 2001 Prepared for: Bob Suggs Florida Power & Light Company 9250 W. Flagler Street Miami, Florida 33174 Principal Investigator Dr.

More information

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? Corresponding author: Jasmin Geppert University of Bonn Household and Appliance Technology Section Nussallee 5 D-53115 Bonn E-Mail: haushaltstechnik@uni-bonn.de

More information

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space Available online at www.sciencedirect.com Procedia Engineering 31 (2012) 734 738 International Conference on Advances in Computational Modeling and Simulation A Numerical study of the Fire-extinguishing

More information

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos Evaluation of A Plate Desiccant Outdoor Air-conditioning System Utilizing Cogenerated Hot Water Using A Numerical Model T. Baba 1, B. Park 1 1, *1, and T. Nagai 1 Department of Architecture, Tokyo University

More information

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Mingsheng Liu, Ph.D., P.E. Energy Systems Laboratory Texas A&M University College Station, Texas

More information

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs Abstract Fan and coil evaporators as used in the industrial refrigeration industry can be certified for performance per ANSI/AHRI Standard 420-2008, Performance Rating of Forced-Circulation Free-Delivery

More information

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Evaluation and Design Optimization of Refrigerated Display

More information

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline ME 414/514 HVAC Systems Overview Equipment Outline 2-1 The Complete System 2-2 The Air-Conditioning and Distribution System 2-3 Mechanical Equipment Air-handling Equipment Heating Equipment Boilers Furnaces

More information

Multiphase-Simulation of Membrane Humidifiers for PEM Fuel Cells

Multiphase-Simulation of Membrane Humidifiers for PEM Fuel Cells Multiphase-Simulation of Membrane Humidifiers for PEM Fuel Cells STAR Global Conference Sebastian Bilz, Vladimir Buday, Carolus Gruenig, Thomas von Unwerth Vienna, March 17-19, 2014 1 CFD Simulation of

More information

ASHRAE JOURNAL ON REHEAT

ASHRAE JOURNAL ON REHEAT Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide

More information

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,

More information

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE Satoru Ito 1, Keisuke Tsukada 1, Nobuyoshi Tsuzuki 2, Takao Ishizuka 3 and Hiroshige Kikura 3 1 Department of nuclear Engineering, Graduate

More information

COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION

COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION Kuklane, Kalev Published in: [Host publication title missing] Published: 2014-01-01 Link to publication Citation for published

More information

PERFORMANCE ANALYSIS OF GROUND SOURCE HEAT PUMPS FOR DOMESTIC HOT WATER SUPPLY IN THE LOW ENERGY HOUSE AND ITS APPLICATION

PERFORMANCE ANALYSIS OF GROUND SOURCE HEAT PUMPS FOR DOMESTIC HOT WATER SUPPLY IN THE LOW ENERGY HOUSE AND ITS APPLICATION - 1 - PERFORMANCE ANALYSIS OF GROUND SOURCE HEA PUMPS FOR DOMESIC HO WAER SUPPLY IN HE LOW ENERGY HOUSE AND IS APPLICAION akao Katsura, Fujiwara Environmental Science Institute Ltd, Sapporo, Japan Katsunori

More information

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling The cooling capacity of the Thermo Active Building System combined with acoustic ceiling Peter Weitzmann, Technical consultant, BuildDesk A/S; peter.weitzmann@builddesk.dk Emanuele Pittarello, MSc, International

More information

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.

More information

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom Improvement of Temperatures Stratification caused by Air-conditioner by means of Ceiling Fan in Classroom Natsuka Wakamatsu 1, Yoshihisa Momoi 1, Toshio Yamanaka 1, Kazunobu Sagara 1, Hisashi Kotani 1

More information

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System Feasibility of a Liquid Desiccant Application in an Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, S.K.Han 1, S.Y. Cho 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang

More information

ECL Comfort 110, application 116

ECL Comfort 110, application 116 Operating Guide ECL Comfort 110, application 116 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

A study of Transient Performance of A Cascade Heat Pump System

A study of Transient Performance of A Cascade Heat Pump System Available online at www.sciencedirect.com ScienceDirect Energy Procedia 79 (2015 ) 131 136 2015 International Conference on Alternative Energy in Developing Countries and Emerging Economies A study of

More information

Simulation of Full-scale Smoke Control in Atrium

Simulation of Full-scale Smoke Control in Atrium Available online at www.sciencedirect.com Procedia Engineering 11 (2011) 608 613 The 5 th Conference on Performance-based Fire and Fire Protection Engineering Simulation of Full-scale Smoke Control in

More information

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

International Forum on Energy, Environment Science and Materials (IFEESM 2015) The Comparison and Analysis of Humidity Environment between Floor and Ceiling Radiant Cooling Systems that Combined with Displacement Ventilation Kai SUN 1 a *, Chuan-hui ZHOU 1 1 College of Urban Construction,

More information

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia To cite this article: N A Malek

More information

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED - 133 - STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED Y. Mikame 1,2, N. Kawabata 1, M. Seike 1, M. Hasegawa 1 1 Kanazawa University, Japan 2 Metropolitan Expressway Company

More information

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER 2000 Elsevier Science Ltd. All rights reserved. Air Distribution in Rooms, (ROOMVENT 2000) Editor: H.B. Awbi 731 IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 504/220-7475 A CRITIQUE OF HUGHES ASSOCIATES, INC. PAPER TITLED: Analysis of the Performance of Ganged

More information

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology IJIRST International Journal for Innovative Research in Science & Technology Volume 1 Issue 11 April 2015 ISSN (online): 2349-6010 CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

More information

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump Available online at www.sciencedirect.com Procedia Engineering 8 (2011) 165 170 2 nd International Science, Social-Science, Engineering and Energy Conference 2010: Engineering Science and Management Hot

More information

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016 Downloaded from vbn.aau.dk on: marts 27, 2019 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger Toke Rammer Nielsen, Associate Professor, Department of Civil Engineering, Technical University of Denmark; trn@byg.dtu.dk

More information

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length HEIMO WALTER Institute for Thermodynamics and Energy Conversion Vienna University

More information

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 TESTING AND VALIDATION OF SIMULATION TOOLS OF HVAC MECHANICAL EQUIPMENT INCLUDING THEIR CONTROL STRATEGIES. PART II: VALIDATION

More information

Computer Modelling and Simulation of a Smart Water Heater

Computer Modelling and Simulation of a Smart Water Heater Computer Modelling and Simulation of a Smart Water Heater Maria Kathleen Ellul University of Malta ellul_maria@yahoo.com Adrian Muscat University of Malta adrian.muscat@um.edu.mt Abstract A computational

More information

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room Yanli Ren 1 ; Deying Li 2 ; Yufeng Zhang 1 1 School of Environment Science and Engineering, Tianjin University, Tianjin 300072,

More information

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU Energy and Buildings 39 (2007) 702 708 www.elsevier.com/locate/enbuild Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU Ming-Tsun Ke a, *, Kuo-Liang

More information

K.F. Fong *, C.K. Lee, T.T. Chow

K.F. Fong *, C.K. Lee, T.T. Chow Investigation on radiative load ratio of chilled beams on performances of solar hybrid adsorption refrigeration system for radiant cooling in subtropical city K.F. Fong *, C.K. Lee, T.T. Chow Building

More information

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Performance of an Improved Household Refrigerator/Freezer

Performance of an Improved Household Refrigerator/Freezer Performance of an Improved Household Refrigerator/Freezer D. O. Ariyo Department of Mechanical Engineering, School of Engineering, Federal Polytechnic, Offa, Nigeria Y. L. Shuaib-Babata Department of Mechanical

More information

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY Xiaoyun Xie, Yidan Tang, Xiaoqin Yi, Shuanqiang Liu,Yi Jiang Department of Building Science and Technology,

More information

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning ISBN 978-93-84468-94-1 International Conference on Education, Business and Management (ICEBM-2017) Bali (Indonesia) Jan. 8-9, 2017 An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

Recent Advances in Energy, Environment and Economic Development

Recent Advances in Energy, Environment and Economic Development Experimental Investigation of Solar Hybrid Desiccant Cooling System in Hot and Humid Weather of Malaysia MM SALEHI DEZFOULI, Z HASHIM, MH RUSLAN, B BAKHTYAR, K SOPIAN, A ZAHARIM, S MAT, A RACHMAN, Solar

More information

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand Mohammed Mutafi 1, Mohammad Nasif 1*, William Pao 1 and

More information

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger "COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger" 1 Prof.Gaffar G.Momin, 2 Sagar B. Tupe, 2 Swapnil A. Parate 2 Omkar G. Yewale 2 Aakash P.

More information

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING M. POIRIER, D. GIGUÈRE, Z. AIDOUN, M. OUZZANE Natural Resources Canada, CANMET Energy Technology Centre-Varennes 1615, Lionel

More information

HEAT REMOVAL TESTS FOR THE HIGH PERFORMANCE VAULT STORAGE SYSTEM OF SPENT NUCLEAR FUEL

HEAT REMOVAL TESTS FOR THE HIGH PERFORMANCE VAULT STORAGE SYSTEM OF SPENT NUCLEAR FUEL HEAT REMOVAL TESTS FOR THE HIGH PERFORMANCE VAULT STORAGE SYSTEM OF SPENT NUCLEAR FUEL M. Oda*, M. Shimizu*, N. Kumagai*, H. Kanai**, M. Tanabe** *Nuclear Fuel Cycle Group, Power & Industrial Systems R&D

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

Compression of Fins pipe and simple Heat pipe Using CFD

Compression of Fins pipe and simple Heat pipe Using CFD Compression of Fins pipe and simple Heat pipe Using CFD 1. Prof.Bhoodev Mudgal 2. Prof. Gaurav Bhadoriya (e-mail-devmudgal.mudgal@gmail.com) ABSTRACT The aim of this paper is to identify the advantages

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) 4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao

More information

Weather compensated flow temperature control of heating and boiler systems

Weather compensated flow temperature control of heating and boiler systems Instructions ECL Comfort 110 Application 130 Weather compensated flow temperature control of heating and boiler systems User guide, Installation & Maintenance DH-SMT/DK VI.KT.G3.02 Danfoss 06/2008 How

More information

HYBRID GAS HEAT PUMP WATER HEATER WITH THERMAL EFFICIENCY 120% 23rd World Gas Conference, Amsterdam Main Author. Atsuya Tajima Japan

HYBRID GAS HEAT PUMP WATER HEATER WITH THERMAL EFFICIENCY 120% 23rd World Gas Conference, Amsterdam Main Author. Atsuya Tajima Japan 23rd World Gas Conference, Amsterdam 2006 Verwijderd: DRD HYBRID GAS HEAT PUMP WATER HEATER WITH THERMAL EFFICIENCY 120% Main Author Atsuya Tajima Japan ABSTRACT In Japan, electric heat pump water heaters

More information

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Conceptual Design of a Better Heat Pump Compressor for Northern Climates Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1976 Conceptual Design of a Better Heat Pump Compressor for Northern Climates D. Squarer

More information

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Effect of the Use Pattern on Performance of Heat Pump Water Heater Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Effect of the Use Pattern on Performance of Heat Pump Water Heater

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection. Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using

More information

STUDY ON A FLOOR SUPPLY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED PCM

STUDY ON A FLOOR SUPPLY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED PCM STUDY ON A FLOOR SULY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED CM S. Takeda, K. Nagano, K. Nakayama, K. Shimakura Hokkaido University Sapporo, 060-8628 Japan Tel: +81-11-706-7597

More information

Challenges and Methods of Estimating a Conceptual HVAC Design

Challenges and Methods of Estimating a Conceptual HVAC Design Challenges and Methods of Estimating a Conceptual HVAC Design ABSTRACT In any conceptual HVAC design, estimators are faced with the challenge of trying to capture all of the pieces that complete a system.

More information

Prediction of Soil Infiltration Rate Based on Sand Content of Soil

Prediction of Soil Infiltration Rate Based on Sand Content of Soil Agricultural Engineering Research Journal 3 (): 0-4, 013 ISSN 18-3906 IDOSI Publications, 013 DOI: 10.589/idosi.aerj.013.3..1109 Prediction of Soil Infiltration Rate Based on Sand Content of Soil 1 1 Majid

More information

ISSN: [Agcaoili S. O., 7(3): March, 2018] Impact Factor: 5.164

ISSN: [Agcaoili S. O., 7(3): March, 2018] Impact Factor: 5.164 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY EVALUATION OF A HOME-MADE SOLAR BOX HEATER FOR DOMESTIC HEATING Shirly O. Agcaoili 1/ 1/ Researcher and Faculty Member of the

More information

ASHRAE Standard 62 Ventilation Report Technical Assignment #1. Calvert Memorial Hospital Prince Frederick, MD

ASHRAE Standard 62 Ventilation Report Technical Assignment #1. Calvert Memorial Hospital Prince Frederick, MD ASHRAE Standard 62 Ventilation Report Technical Assignment #1 Prepared By: Holly Mawritz October 6, 2004 Table Of Contents: Executive Summary 2 Assumptions 3 Procedure 4 Sample Calculations 5 System and

More information

EXPERIMENTAL AND THEORTICAL STUDY OF THE THERMAL PERFORMANCE OF HEAT PIPE HEAT EXCHANGER

EXPERIMENTAL AND THEORTICAL STUDY OF THE THERMAL PERFORMANCE OF HEAT PIPE HEAT EXCHANGER International Journal of Mechanical Engineering and Technology (IJMET) Volume 7, Issue 3, May June 2016, pp.102 111, Article ID: IJMET_07_03_009 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=7&itype=3

More information

DESIGN WITH HEAT LOAD SIMULATION OF COMBINED PASSIVE-ACTIVE SYSTEMS

DESIGN WITH HEAT LOAD SIMULATION OF COMBINED PASSIVE-ACTIVE SYSTEMS Ninth International IBPSA Conference Montréal, Canada August 18, DESIGN WIH HEA LOAD SIMULAION OF COMBINED PASSIVEACIVE SYSEMS Mitsuhiro Udagawa 1, Hyunwoo Roh 2 Department of Architecture, Kogakuin University,

More information

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink 1 Asoka R.G, 2 Aishwarya N, 3 Rajasekar S and 4 Meyyappan N 1234 Department of Chemical Engineering Sri Venkateswara College of Engineering,

More information