General information on refrigerant controllers

Size: px
Start display at page:

Download "General information on refrigerant controllers"

Transcription

1 General information on refrigerant controllers Condensing pressure controller The condensing or condenser pressure controller is a back pressure controller and its task is to maintain the condensing pressure of a refrigeration system at a specific minimum level. If when using two-way controllers there is the risk that the pressure in the receiver falls too low, a bypass line with a receiver pressure controller (differential pressure valve) must be included. When using a condensing pressure controller it should be ensured that the receiver volume and the refrigerant charge are assessed correctly. It regulates depending on the pressure at the inlet side. The condensing pressure regulator is installed at the outlet of the condenser. The selection is made on the basis of the manufacturers' performance data. Evaporating pressure regulators The evaporating or suction pressure regulator has the task of maintaining the evaporating pressure above a set value independent of cooling load fluctuations or capacity changes. It regulates depending on the pressure at the inlet side. The evaporating pressure controller is installed in the suction line after the evaporator. The selection is made on the basis of the manufacturers' performance data. Start controller The start controller has the task of protecting the compressor against overload due to excessively high suction pressure during start-up. (e.g. after defrosting the refrigeration system, long standstill periods) It regulates depending on the pressure at the outlet side. The start controller is installed in the suction line before the compressor. The selection is made on the basis of the manufacturers' performance data. Capacity controller The capacity or hot gas bypass controller has the task of adapting the compressor capacity to the evaporator capacity for fluctuating system capacities. It regulates depending on the compressor suction pressure by bypassing hot gas from the discharge side to the suction side. The capacity controller is either installed between discharge side and suction side or between discharge line and evaporator of a refrigeration system. When installing it between discharge side and suction side, it is necessary to install a reinjection valve for desuperheating the suction vapour. The selection is made on the basis of the manufacturers' performance data. Application and installation: There are two typical applications. Hot gas bypass into the evaporator inlet (100% capacity regulation possible) Fig.1 Hot gas bypass into the suction line (max. 40% capacity regulation) Fig.2 Temperature controller The temperature controller has the task of keeping the set media temperature constant by controlling the refrigerant mass flow at the evaporator outlet. It regulates depending on the sensor temperature. The temperature controller is installed in the suction line after the evaporator. The selection is made on the basis of the manufacturers' performance data. Edition 2014 Components Catalogue Page 4/87

2 Refrigerant Controllers Hot Gas Bypass Controller Series ACP Characteristics ALCO Direct acting hot gas bypass controllers Compact valve with angle solder connection Internal pressure equalisation Adjustment range: 1,0-6,0 bar abs Max. operating pressure: 31 bar Long service life due to high-quality materials and special manufacturing processes EDP-No. Connections ODF Nominal bypass capacity Q N [kw] Inlet Outlet R 134a R 407C R404A R507 ACP /4" 3 0,21 0,41 0,30 0,30 ACP /4" 3 0,50 0,89 0,68 0,68 ACP ,18 2,12 1,59 1,59 The nominal capacities are based on an evaporating temperature (saturated vapour) of +4 C and a condensing temperature (saturated liquid) of +38 C, as well as a liquid subcooling of 1K at the valve inlet. For other operating conditions see factors on page 4/89. Refrigerant Controller Hot Gas Bypass Controller Series CPHE Characteristics ALCO Direct acting hot gas bypass controllers Exchangeable valve inserts Valve bases with angle solder flange Valve bonnets with external pressure equalisation Adjustment range: -0,4-5,0 bar Max. operating pressure: 35 bar Long service life due to high-quality materials and special manufacturing processes Outstanding partial load behaviour due to double seat design of the valve inserts Special pipe connections and flanges available on request. Product name Nominal bypass capacity Q N [kw] Valve insert Standard flange Valve bonnet R134a R407C R404A R507 EDP-No. EDP-No. EDP-No. CPHE - 1 3,5 5,8 4,5 4,5 CPHE - 2 6,4 10,4 8,1 8,1 CPHE ,0 20,0 15,0 15,0 X B5B X B8B X B5B C MM Internal soldering 12 x A 576 MM Internal soldering 16 x Internal soldering 22 x CPHE - 3,5 13,0 22,0 17,0 17,0 X 9117-B7B X CPHE ,0 27,0 21,0 21,0 CPHE ,0 34,0 26,0 26,0 X 9117-B9B X 9166-B10B Internal soldering 22 x CPHE ,0 58,0 45,0 45,0 X 9144-B13B Internal soldering 22 x The nominal capacities are based on an evaporating temperature (saturated vapour) of +4 C and a condensing temperature (saturated liquid) of +38 C, as well as a liquid subcooling of 1 K at the valve inlet. For other operating conditions see factors on page 4/89. Dimensions Product name A [mm] CPHE CPHE CPHE CPHE-3,5 210 CPHE CPHE CPHE Page 4/88 Components Catalogue Edition 2014

3 Refrigerant Controller Hot Gas Bypass Controller Series ACP and CPHE Correction table for series ACP and CPHE ALCO For different evaporating temperatures the refrigerating capacity to be reduced, referred to as bypass capacity Q Byp, must be multiplied by the correction factor K Byp. The result is the nominal bypass capacity Q N, for which the controller must be selected. Q Byp x K Byp = Q N Refrigerant R134a R407C R404A R507 Condensing temperature [ C] Correction factor K Byp Evaporating temperature [ C] ,78 0,77 0,78 0, ,99 0,94 0,93 0, ,35 1,21 1,15 1, ,83 0,82 0,83 0, ,99 0,95 0,95 0, ,26 1,17 1,13 1, ,86 0,85 0,87 0,91 0,97 1, ,99 0,95 0,94 0,96 1,00 1, ,26 1,13 1,09 1,08 1,10 1, ,86 0,85 0,87 0,91 0,97 1, ,99 0,95 0,94 0,96 1,00 1, ,26 1,13 1,09 1,08 1,10 1,14 Edition 2014 Components Catalogue Page 4/89

4 Evaporating pressure controllers PRE Evaporating pressure controllers of the PRE series prevent the evaporating pressure from falling below a preset value. The most important application is the operation of multiple evaporators with different evaporating temperatures on a common suction line. Characteristics ALCO Compact housing for easy installation also under limited space conditions Schrader valve as standard equipment for easy adjustment Direct acting controller Balanced port design for precise control characteristics also under unfavourable conditions (pressure fluctuations) Adjustment range: 0,5-6,9 bar Factory setting: 2 bar Max. operating pressure: 25 bar Pressure change per rotation: PRE-11: 0,6 bar PRE-21: 0,4 bar Weight: PRE-11 0,6 kg PRE-21 1,3 kg Nominal capacity 1) Pipe connection Orig. Nr. EDP-No. [kw] Flare Solder Solder R 134a R404A R507 R 407C [UNF] [in] [mm] PRE-11A ,0 4,5 4,5 4, PRE-11B ,0 4,5 4,5 4, PRE-21C ,4 11,1 11,1 11,1 28 PRE-21D ,4 11,1 11,1 11,1 1 1 The nominal capacities are based on an evaporating temperature (saturated vapour) of +4 C and a condensing temperature (saturated liquid) of +38 C, as well as a liquid subcooling of 1K at the valve inlet. Correction table for series PRE ALCO Valve selection for operating conditions deviating from +38 C / +4 C and 1 K subcooling at the valve inlet. Q n x Q 0 = K t Q n = Nominal capacity of the valve Q 0 = Required refrigerating capacity PRE-*** Refrigerant R134a R407C R404A R507 Condensing temperature [ C] Correction factor K Byp Evaporating temperature [ C] ,04 1,51 2, ,92 1,34 1, ,83 1,20 1, ,76 1,10 1, ,02 1,42 2, ,94 1,31 1, ,84 1,17 1, ,77 1,06 1, ,35 1,91 2,77 4,18 6, ,05 1,46 2,07 3,05 4, ,88 1,22 1,71 2,48 3, ,77 1,06 1,48 2,12 3, ,35 1,91 2,77 4,18 6, ,05 1,46 2,07 3,05 4, ,88 1,22 1,71 2,48 3, ,77 1,06 1,48 2,12 3,13 Page 4/90 Components Catalogue Edition 2014

5 Start controller PRC Start controllers of the PRC series have the task of protecting the compressor motor against overload in systems in which high suction pressures can occur. High suction pressures can occur during start-up of a refrigeration system, under high cooling loads as well as after defros- Characteristics ALCO Compact housing for easy installation also under limited space conditions Schrader valve as standard equipment for easy adjustment Direct acting controller Balanced port design for precise control characteristics also under unfavourable conditions (pressure fluctuations) Adjustment range: 0,5-6,9 bar Factory setting: 2 bar Max. operating pressure: 25 bar Pressure change per rotation: PRC-11: 0,6 bar PRC-21: 0,4 bar Weight: PRC-11 0,6 kg PRC-21 1,3 kg Nominal capacity 1) Pipe connection Orig. Nr. EDP-No. [kw] Flare Solder Solder R 134a R404A R507 R 407C [UNF] [in] [mm] PRC-11A ,0 4,5 4,5 4, PRC-11B ,0 4,5 4,5 4, PRC-21C ,4 11,1 11,1 11,1 28 PRC-21D ,4 11,1 11,1 11,1 1 1 PRC-21E ,4 11,1 11,1 11, The nominal capacities are based on an evaporating temperature (saturated vapour) of +4 C and a condensing temperature (saturated liquid) of +38 C, as well as a liquid subcooling of 1K at the valve inlet. Performance tables for series PRC ALCO Valve selection for operating conditions deviating from +38 C / +4 C and 1 K subcooling at the valve inlet. (Capacities are based on a pressure drop of 0,07 bar) PRC-11* PRC-21* Refrigerant R134a R407C R404A R507 Refrigerant R134a R407C R404A R507 Evaporating temperature [ C] Capacity [kw] Valve setting [ C] ,1 3,9 5,3 1 2,4 4,7 7 3,3-6 3,1 4,8-1 2,9-27 1,6 2,9 3,7 3,9-20 1,9 3,5 4,5-14 2,2 4,5-10 3,1-27 1,6 2,9 3,7 3,9-20 1,9 3,5 4,5-14 2,2 4,5-10 3,1 Evaporating temperature [ C] Capacity [kw] Valve setting [ C] ,2 10,3 12,9 1 6,1 12, ,9 13,9-1 9,2-27 4,8 8,2 8,2 8,2-20 5,7 9,8 9,8-14 6,8 11,6-10 8,1-27 4,8 8,2 8,2 8,2-20 5,7 9,8 9,8-14 6,8 11,6-10 8,1 Edition 2014 Components Catalogue Page 4/91

6 Condensing Pressure Controllers KVR Characteristics DANFOSS The controller KVR is used to maintain a constant and sufficiently high condensing pressure in the air-conditioning units and refrigeration systems with air-cooled condensers. It regulates as a function of the input pressure. Vibration damping ensures long service life and precise control. Schrader valve for manometer connection Can be used as a relief valve between the high and low pressure sides Hermetically brazed housing For R 22, R 134a, R 404A, R 12, R 502 and other fluorinated refrigerants Control range: 5 to 17,5 bar Max. temperature: 105 C (130 C with Schrader valve removed) Min. temperature: -40 C Perm. operating pressure: 28 bar Orig. No. EDP-No. Nominal liquid capacity 1 ) (evaporator capacity) [kw] Nominal hot gas capacity 1 ) (evaporator capacity) [kw] Pipe connection R 134a R 404A R 507 R 407C R 134a R 404A R 507 R 407C Flare 2 ) Solder KVR L /4"UNF 034L mm KVR L ,3 36,6 36,6 54,4 11,6 12,0 12,0 14,3 7 UNF 034L mm KVR L mm KVR L mm 93,7 93,7 139,3 34,9 34,9 37,3 KVR L mm 1) Specified at t 0 = -10 C, condensing temperature t k = +30 C and a pressure drop across the valve of Δp = 0,2 bar for the liquid capacity and 0,4 bar for the hot gas capacity, offset = 3 bar 2) KVR is supplied without flare union nuts. Separate union nuts can be supplied. The chosen connection sizes must not be too small, since flow velocities over 40 m/s in the nozzles of the controller can cause flow noises. KVR 12 KVR 15 KVR 22 KVR 28 KVR 35 KVR 12 KVR 15 KVR 22 KVR 28 KVR 35 KVR 12 KVR 15 KVR 22 KVR 28 KVR 35 Condensing temperature t K [ C] Offset 3 bar Offset 3 bar Pressure drop Δp [bar] Pressure drop Δp [bar] 0,1 0,2 0,4 0,8 1,6 0,1 0,2 0,4 0,8 1,6 R 134a R 134a Liquid capacity Q 0 [kw] (Evaporator capacity) R 134a Hot gas capacity Q 0 [kw] (Evaporator capacity) ,7 57,5 81,4 115,0 163,0 5,4 7,6 10,7 14,7 19, ,1 52,5 74,2 105,0 149,0 5,6 7,9 11,1 15,4 20, ,4 47,3 66,9 94,7 134,0 5,8 8,2 11,6 16,1 21, ,7 42,0 59,4 84,1 119,0 6,0 8,5 11,9 16,6 22, ,9 36,6 51,8 73,3 104,0 6,1 8,6 12,1 16,9 23, ,0 147,0 208,0 295,0 418,0 14,4 20,2 28,2 38,8 51, ,9 134,0 190,0 269,0 361,0 15,0 21,0 29,5 40,8 55, ,5 121,0 171,0 242,0 343,0 15,5 21,8 30,6 42,5 57, ,0 108,0 152,0 215,0 305,0 15,9 22,4 31,5 43,9 60, ,3 93,7 133,0 188,0 266,0 16,1 22,7 32,0 44,7 61,7 R404A/R507 R404A/R507 Liquid capacity Q 0 [kw] (Evaporator capacity) R404A/R507 Hot gas capacity Q 0 [kw] (Evaporator capacity) ,9 46,4 65,6 92,9 131,3 5,8 8,1 11,3 15,8 21, ,4 41,6 58,8 83,2 117,6 6,1 8,4 11,8 16,5 22, ,9 36,6 51,8 73,3 103,7 6,1 8,5 12,0 16,8 23, ,4 31,6 44,7 63,3 89,7 6,1 8,6 12,1 16,9 23, ,8 26,6 37,6 53,2 75,4 6,1 8,6 12,1 16,9 23, ,0 118,7 168,0 238,3 337,1 15,8 22,2 31,1 43,2 58, ,2 106,1 150,2 213,2 301,4 16,7 23,5 33,1 46,1 63, ,3 93,7 132,3 188,0 265,7 17,6 24,8 34,9 48,7 67, ,2 81,0 114,5 161,7 228,9 18,3 25,9 36,4 51,0 70, ,1 68,0 96,2 136,5 193,2 18,9 26,6 37,5 52,6 73,2 R407C R407C Liquid capacity Q 0 [kw] (Evaporator capacity) R407C Hot gas capacity Q 0 [kw] (Evaporator capacity) ,9 65,0 91,9 130,0 184,1 6,5 9,1 12,7 17,6 24, ,3 59,8 84,7 119,8 169,6 6,8 9,6 13,5 18,8 25, ,4 54,4 77,0 109,0 154,3 7,1 10,2 14,3 19,9 27, ,9 49,4 69,8 98,8 139,8 7,5 10,7 14,9 21,0 29, ,0 43,9 62,0 87,9 124,4 7,8 11,1 15,6 22,0 30, ,6 166,3 235,2 332,9 471,1 17,1 24,0 33,6 46,7 63, ,2 153,1 216,6 306,5 433,8 18,0 25,4 35,7 49,8 68, ,5 139,3 197,1 278,9 394,7 19,0 26,8 37,7 52,6 72, ,3 126,2 178,7 252,7 357,7 19,9 28,2 39,7 55,6 77, ,4 112,3 158,8 224,8 318,2 20,8 29,3 41,3 57,9 80,5 Correction factors for the evaporating temperature: System capacity x Correction factor = Table capacity t 0 [ C] ±0 +10 R 134a 0,88 0,92 0,96 1,00 1,04 1,08 R 404A 0,85 0,9 0,95 1,00 1,05 1,09 R407C 0,89 0,89 0,96 1,00 1,03 1,07 R 507 0,84 0,84 0,95 1,00 1,05 1,10 Page 4/92 Components Catalogue Edition 2014

7 Receiver Pressure Controllers NRD Characteristics DANFOSS Receiver pressure controller for maintaining a sufficiently high receiver pressure for air-cooled refrigeration sytems (summer-winter operation) and heat recovery systems. NRD is a factory-set differential pressure controller which opens when the pressure drop across the valve is 1,4 bar and is fully opened at a pressure drop of 3,0 bar. Pipe connection Orig. No. EDP-No. kv-value 1) Solder Solder [in] [mm] NRD 12S ,86 12 NRD 12S ,86 1 /2" 1) kv-value is the flow rate in m3/h at a pressure drop across the valve of 1 bar, ρ = 1000 kg/m 3. Receiver Pressure Controllers KVD Characteristics DANFOSS The KVD is a modulating pressure controller. It opens when the pressure in the receiver falls and directs gas via a bypass in order to maintain the (adjustable) pressure in the receiver set at the controller. KVD and KVR constitute a control system for maintaining a constant and equal condensing and receiver pressure in systems with heat recovery as well as in air-conditioning units and refrigeration systems with air-cooled condensers. Modulating pressure controller Schrader valve for manometer connection Hermetically brazed housing For R 22, R 134a, R 407C R 404A, R 507 and other fluorinated refrigerants Control range: 3 to 20 bar Media temperature: -45 to 100 C Perm. operating pressure 28 bar Pipe connection Orig. No. EDP-No. kv-value 1) Flare Solder Solder [UNF] [in] [mm] KVD L ,75 3 /4" KVD L ,75 12 KVD L ,75 1 /2" KVD L ,75 7 KVD L , ) kv-value is the flow rate in m3/h at a pressure drop across the valve of 1 bar, ρ = 1000 kg/m 3. The chosen nominal connection diameter must not be too small since flow velocities over 40 m/s in the controller nozzle can cause flow noises. Edition 2014 Components Catalogue Page 4/93

8 Evaporating pressure controller KVP Characteristics DANFOSS The KVP is installed in the suction line after the evaporator. It is used for: 1. The maintenance of a constant evaporating pressure and consequently a constant surface temperature on the evaporator. The regulation is modulating. By throttling in the suction line, the amount of refrigerant is matched to the evaporator load. 2. Protection against too low evaporating pressure (e.g. to protect against freezing in a water cooler). The controller closes when the pressure in the evaporator falls below the set value. 3. Differentiation of the evaporating pressure of a refrigeration system with one compressor and multiple evaporators with different evaporating temperatures. Precise, adjustable pressure regulation Wide capacity and operating ranges Vibration damping Compact angle construction for easy installation in any position Hermetically brazed housing Available in many sizes in flare and ODF solder design For R 22, R 134a, R 404A, R 12, R 502 and other fluorinated refrigerants Control range: ±0 to +5,5 bar Max. temperature: 100 C Perm. operating pressure 18 bar Nominal capacity 1) Pipe connection Orig. No. EDP-No. [kw] Flare Solder Solder R 134a R404A R507 R 407C [UNF] [in] [mm] 034L /4" KVP L L /2" 2,8 3,6 3,6 3,7 034L KVP L KVP L L KVP L ,1 7,7 7,7 7,9 1 1 KVP L ) The nominal capacity is the capacity of the controller at evaporating temperature t 0 = -10 C, condensing temperature tk=+25 C, pressure loss in the controller Δp=0,2 bar, offset=0,6 bar. 2) KVR is supplied without flare union nuts. Separate union nuts can be supplied. The chosen connection size must not be too small, since gas velocities over 40 m/s in the nozzles of the controller can cause flow noises. Controller capacity Q 0 [kw] at offset = 0,6 bar KVP 12 KVP 15 KVP 22 KVP 28 KVP 35 Pressure drop in the controller Δp [bar] Offset 0,6 bar Evaporating temperature t 0 [ C] ±0 5 R 134a 0,1 1,8 2,1 2,3 2,6 2,9 3,2 3,6 3,9 0,2 2,5 2,8 3,2 3,6 4,0 4,5 5,0 5,5 0,3 2,9 3,4 3,8 4,3 4,9 5,4 6,0 6,6 0,4 3,2 3,7 4,3 4,9 5,5 6,1 6,8 7,6 0,5 3,4 4,0 4,6 5,3 6,0 6,8 7,5 8,3 0,6 3,5 4,2 4,9 5,7 6,4 7,3 8,1 9,0 0,1 3,9 4,5 5,0 5,6 6,2 6,9 7,6 8,4 0,2 5,3 6,1 6,9 7,8 8,7 9,6 10,6 11,7 0,3 6,3 7,2 8,2 9,3 10,4 11,6 12,9 14,2 0,4 6,9 8,0 9,2 10,5 11,8 13,2 14,6 16,2 0,5 7,3 8,6 10,0 11,4 12,9 14,5 16,1 17,9 0,6 7,5 9,0 10,5 12,1 13,8 15,6 17,4 19,3 The values specified in the performance table are based on the evaporator capacity at a liquid temperature t V =+25 C at the inlet of the thermostatic expansion valve, a pressure drop Δp in the controller as well as a controller offset s=0,6 bar. Dry saturated vapour at the inlet of the controller is preconditioned. When dimensioning, the evaporator capacity must be multiplied by a correction factor depending on the liquid temperature t V at the inlet of the thermostatic expansion valve and the permissible offset of the controller. The corrected capacity is then looked up in the performance table. Page 4/94 Components Catalogue Edition 2014

9 Controller capacity Q 0 [kw] at offset = 0,6 bar DANFOSS KVP 12 KVP 15 KVP 22 KVP 28 KVP 35 KVP 12 KVP 15 KVP 22 KVP 28 KVP 35 KVP 12 KVP 15 KVP 22 KVP 28 KVP 35 Pressure drop in the controller Δp [bar] Evaporating Pressure Controllers KVP Offset 0,6 bar Evaporating temperature t 0 [ C] ±0 5 R 404A 0,1 1,4 1,6 1,8 2,1 2,3 2,6 2,8 3,2 0,2 1,9 2,2 2,5 2,8 3,2 3,6 4,0 4,4 0,3 2,2 2,5 3,0 3,5 3,9 4,4 4,8 5,4 0,4 2,4 2,9 3,3 3,9 4,3 4,9 5,5 6,2 0,5 2,5 3,1 3,6 4,2 4,8 5,5 6,1 6,8 0,6 2,6 3,2 3,9 4,4 5,1 5,8 6,5 7,4 0,1 2,9 3,4 3,9 4,4 5,0 5,5 6,0 6,8 0,2 4,0 4,7 5,4 6,2 6,8 7,7 8,4 9,6 0,3 4,7 5,5 6,4 7,3 8,2 9,2 10,3 11,6 0,4 5,1 6,1 7,2 8,2 9,3 10,5 11,7 13,2 0,5 5,5 6,6 7,7 9,0 10,2 11,4 12,9 15,4 0,6 5,7 6,9 8,2 9,6 10,9 12,4 13,8 15,7 R 507 0,1 1,4 1,6 1,8 2,1 2,3 2,6 2,8 3,2 0,2 1,9 2,2 2,5 2,8 3,2 3,6 4,0 4,4 0,3 2,2 2,5 3,0 3,5 3,9 4,4 4,8 5,4 0,4 2,4 2,9 3,3 3,9 4,3 4,9 5,5 6,2 0,5 2,5 3,1 3,6 4,2 4,8 5,5 6,1 6,8 0,6 2,6 3,2 3,9 4,4 5,1 5,8 6,5 7,4 0,1 2,9 3,4 3,9 4,4 5,0 5,5 6,0 6,8 0,2 4,0 4,7 5,4 6,2 6,8 7,7 8,4 9,6 0,3 4,7 5,5 6,4 7,3 8,2 9,2 10,3 11,6 0,4 5,1 6,1 7,2 8,2 9,3 10,5 11,7 13,2 0,5 5,5 6,6 7,7 9,0 10,2 11,4 12,9 15,4 0,6 5,7 6,9 8,2 9,6 10,9 12,4 13,8 15,7 R 407C 0,1 1,6 1,8 2,0 2,3 2,7 3,0 3,3 3,6 0,2 2,2 2,5 2,8 3,2 3,7 4,1 4,6 5,1 0,3 2,6 3,0 3,4 3,9 4,4 4,9 5,5 6,2 0,4 2,8 3,3 3,8 4,4 5,1 5,7 6,3 7,1 0,5 2,9 3,6 4,2 4,8 5,5 6,2 7,0 7,9 0,6 3,1 3,7 4,5 5,1 5,9 6,7 7,5 8,4 0,1 3,4 3,9 4,5 5,0 5,7 6,3 7,1 7,9 0,2 4,6 5,4 6,1 6,9 7,9 8,8 9,8 10,9 0,3 5,4 6,4 7,3 8,4 9,5 10,7 11,8 13,3 0,4 6,0 7,0 8,2 9,4 10,8 12,1 13,5 15,2 0,5 6,4 7,6 8,9 10,3 11,8 13,3 14,9 16,8 0,6 6,5 7,9 9,4 11,0 12,7 14,3 16,1 18,1 The values specified in the performance table are based on the evaporator capacity at a liquid temperature t v = +25 C at the inlet of the thermostatic expansion valve, a pressure drop Δp in the controller as well as a controller offset s=0,6 bar. Dry saturated vapour at the inlet of the controller is preconditioned. When dimensioning, the evaporator capacity must be multiplied by a correction factor depending on the liquid temperature t v at the inlet of the thermostatic expansion valve and the permissible offset of the controller. The corrected capacity is then looked up in the performance table. Correction factors for the liquid temperature t V t V [ C] R 134a 0,92 0,96 1,0 1,05 1,10 1,16 R 404A/R 507 0,89 0,94 1,0 1,07 1,16 1,26 R 407 C 0,91 0,95 1,0 1,05 1,11 1,18 Correction factors for offset Offset [bar] 0,2 0,4 0,6 0,8 1,0 1,2 1,4 KVP 12 KVP 15 2,5 1,4 1,0 0,77 0,67 0,59 KVP 22 KVP28 KVP35 1,4 1,0 0,77 0,67 0,59 0,53 Edition 2014 Components Catalogue Page 4/95

10 Start Controllers KVL Characteristics DANFOSS Kvl start controllers are installed in the suction line before the compressor. The KVL protects the compressor motor against overload during start-up after long standstill periods or after the defrosting period (high pressure in the evaporator). Precise, adjustable pressure regulation Large capacity and operating ranges Vibration damping Compact angle construction for easy installation in any position Hermetically brazed housing Control range: 0,2 bis 6,0 bar Max. Medium temperature 150 C Perm. operating pressure: 18 bar Nominal capacity [kw] 1 ) Pipe connection Orig. No. EDP-No. Flare R 134a R 404A R 507 R 407C 2 ) Solder Solder [UNF] [in] [mm] 034L /4" KVL L ,3 6,3 6,3 6, L /2" 034L KVL L ,3 6,3 6,3 6, KVL L L KVL L ,2 15,9 15,9 16,4 1 1 KVL L ) The nominal capacity is the capacity of the controller at evaporating temperature t 0 = -10 C, condensing temperature t K =+25 C, Pressure drop in the controller Δp=0,2 bar. 2) KVR is supplied without flare union nuts. Separate union nuts can be supplied. The chosen connection size must not be too small, since gas velocities over 40 m/s in the nozzles of the controller can cause flow noises. Page 4/96 Components Catalogue Edition 2014

11 Start Controllers KVL Capacity R 134 a DANFOSS Pressure Max suction Maximum controller capacity Q 0 [kw] drop in the pressure at suction gas temperature t controller S at the outlet of the controller [ C] p Δp [bar] S [bar] ± ,8 1,2 2 2,9 3,3 3,1 2,2 0,3 0,1 3 2,9 3,3 3,7 4,1 4,1 2,4 4 2,9 3,3 3,7 4,1 4,6 5,1 4,4 0,7 5 2,9 3,3 3,7 4,1 4,6 5,1 5,6 5,6 1,8 6 2,9 3,3 3,7 4,2 4,6 5,1 5,6 6,2 6,7 KVL 12 KVL 15 KVL 22 KVL 28 KVL 35 0,2 0,3 0,1 0,2 0,3 1 2,6 1,6 2 4,2 4,7 4,4 3,1 0,4 3 4,2 4,7 5,3 5,9 5,8 3,4 4 4,2 4,7 5,3 5,9 6,5 7,2 5, ,2 4,7 5,3 5,9 6,5 7,2 7,9 8 2,6 6 4,2 4,7 5,3 5,9 6,5 7,2 7,9 9,5 8,7 1 3, ,2 5,8 5,5 3,8 0,5 3 5,2 5,8 6,5 7,2 7,1 4,2 4 5,2 5,8 6,5 7,2 8,0 8,9 7,3 1,1 5 5,2 5,8 6,5 7,2 8,0 8,9 9,8 9,8 3,2 6 5,8 6,5 7,2 8,0 8,9 9,8 10,7 10,7 11,7 1 4,0 2,5 2 7,3 7,8 6,9 4,8 0,6 3 7,3 8,2 9,3 10,3 9,1 5,2 4 7,3 8,2 9,3 10,3 11,5 12,7 9,2 1,4 5 7,3 8,2 9,3 10,3 11,5 12, ,6 3,9 6 7,3 8,2 9,3 10,3 11,5 10,7 14,0 15,4 15,3 1 5,6 3,5 2 10,5 11,1 9,8 6,7 0,9 3 10,5 11,8 13,2 14,7 12,9 7,2 4 10,5 11,8 13,2 14,7 16,3 18,1 13, ,5 11,8 13,2 14,7 16,3 18,1 19,9 17,8 5,6 6 10,5 11,8 13,2 14,7 16,3 18,1 19,9 21,9 15,3 1 6,9 4,3 2 12,9 13,7 12,1 8,2 1,1 3 12,9 14,5 16,2 18,1 15, ,9 14,5 16,2 18,1 20,1 22,2 5 12,9 14,5 16,2 18,1 20,1 22,2 24,5 21,9 6,8 6 12,9 14,5 16,2 18,1 20,1 22,2 24,5 26,9 26,6 The values specified in the performance tables are based on the evaporator capacity at a liquid temperature t V =25 C at the inlet of the thermostatic expansion valve. Correction factors When dimensioning, the evaporator capacity must be multiplied by a correction factor depending on the liquid temperature t v at the inlet of the thermostatic expansion valve. The corrected capacity is then looked up in the performance table. t V [ C] R 134a 0,88 0,92 0,96 1,00 1,05 1,10 1,16 1,23 1,31 System capacity x Correction factor = Table value Edition 2014 Components Catalogue Page 4/97

12 Start Controllers KVL Capacity R 404A / R 507 DANFOSS Pressure Max suction Maximum controller capacity Q 0 [kw] drop in the pressure at suction gas temperature t controller S at the outlet of the controller [ C] p Δp [bar] S [bar] ± ,9 2 2,5 2,4 1,7 0,3 0,1 3 2,5 2,9 3,2 3,2 1,9 4 2,5 2,9 3,2 3,6 4,0 3,4 0,5 5 2,5 2,9 3,2 3,6 4,0 4,5 4,5 1,5 6 2,5 2,9 3,2 3,6 4,0 4,5 4,9 5,5 2,1 KVL 12 KVL 15 KVL 22 KVL 28 KVL 35 0,2 0,3 0,1 0,2 0,3 1 1,3 2 3,6 3,4 2,5 0,4 3 3,6 4,0 4,6 4,5 2,7 4 3,6 4,0 4,6 5,1 5,7 4,8 0,8 5 3,6 4,0 4,6 5,1 5,7 6,3 6,4 2,2 6 3,6 4,0 4,6 5,1 5,7 6,3 7,0 7,8 2,9 1 1,6 2 4,4 4,2 3,0 0,4 3 4,4 5,0 5,6 5,6 3,3 4 4,4 5,0 5,6 6,3 7,0 5,9 1,0 5 4,4 5,0 5,6 6,3 7,0 7,8 7,8 2,6 6 4,4 5,0 5,6 6,3 7,0 7,8 8,6 9,6 3,5 1 2,0 2 5,9 5,4 3,7 0,5 3 6,2 7,1 8,0 7,2 4,2 4 6,2 7,1 8,0 9,1 10,0 7,4 1,2 5 6,2 7,1 8,0 9,1 10,0 11,2 10,1 3,3 6 6,2 7,1 8,0 9,1 10,0 11,2 12,4 12,4 4,4 1 2,7 2 8,4 7,6 5,4 0,9 3 8,9 10,1 11,4 10,3 5,9 4 8,9 10,1 11,4 12,9 14,3 10,6 1,7 5 8,9 10,1 11,4 12,9 14,3 15,9 14,4 4,6 6 8,9 10,1 11,4 12,9 14,3 15,9 17,5 17,6 6,3 1 3,1 2 10,4 9,3 6,5 1,1 3 10,9 12,5 14,0 12,5 7,2 4 10,9 12,5 14,0 15,8 17,6 13,0 2,1 5 10,9 12,5 14,0 15,8 17,6 19,6 17,7 5,6 6 10,9 12,5 14,0 15,8 17,6 19,6 21,6 21,7 7,7 The values specified in the performance tables are based on the evaporator capacity at a liquid temperature t V = 25 C at the inlet of the thermostatic expansion valve. Correction factors When dimensioning, the evaporator capacity must be multiplied by a correction factor depending on the liquid temperature t v at the inlet of the thermostatic expansion valve. The corrected capacity is then looked up in the performance table. t V [ C] R 404A/R 507 0,84 0,89 0,94 1,00 1,07 1,16 1,26 1,40 1,57 System capacity x Correction factor = Table value Page 4/98 Components Catalogue Edition 2014

13 Start Controllers KVL Capacity R 407C DANFOSS Pressure Max suction Maximum controller capacity Q 0 [kw] drop in the pressure at suction gas temperature t controller S at the outlet of the controller [ C] p Δp [bar] S [bar] ± ,6 1,0 2 2,5 2,8 2,7 1,9 0,2 0,1 3 2,5 2,8 3,2 3,6 3,6 2,0 4 2,5 2,8 3,2 3,6 4,1 4,6 3,6 0,1 5 2,5 2,8 3,2 3,6 4,1 4,6 5,1 4,9 1,0 6 2,5 2,8 3,2 3,6 4,1 4,6 5,1 5,6 6,0 1,3 KVL 12 KVL 15 KVL 22 KVL 28 KVL 35 0,2 0,3 0,1 0,2 0,3 1 2,2 1,5 2 3,5 4,0 3,8 2,7 0,2 3 3,5 4,0 4,6 5,3 5,0 2,9 4 3,5 4,0 4,6 5,3 5,9 6,5 5,1 0,1 5 3,5 4,0 4,6 5,3 5,9 6,5 7,3 6,9 6 3,5 4,0 4,6 5,3 5,9 6,5 7,3 8,0 8,4 1,8 1 2,7 1,7 2 4,4 5,0 4,7 3,3 0,3 3 4,4 5,0 5,7 6,4 6,2 3,5 4 4,4 5,0 5,7 6,4 7,2 8,1 6,2 0,2 5 4,4 5,0 5,7 6,4 7,2 8,1 8,9 8,5 1,6 6 4,4 5,0 5,7 6,4 7,2 8,1 8,9 9,9 10,3 2,2 1 3,4 2,2 2 6,2 6,8 6,1 4,1 0,4 3 6,2 7,1 8,1 9,2 8,0 4,3 4 6,2 7,1 8,1 9,2 10,3 11,3 7,9 0,2 5 6,2 7,1 8,1 9,2 10,3 11,6 12,8 10,9 2,1 6 6,2 7,1 8,1 9,2 10,3 11,6 12,8 14,2 13,3 2,7 1 4,9 3,1 2 8,9 9,6 8,5 5,8 0,2 3 8,9 10,1 11,5 13,1 11,3 6,1 4 8,9 10,1 11,5 13,1 14,6 16,1 11,2 0,3 5 8,9 10,1 11,5 13,1 14,6 16,4 18,2 15,4 3,0 6 8,9 10,1 11,5 13,1 14,6 16,4 18,2 20,1 18,8 3,9 1 5,9 3,8 2 10,9 11,9 10,5 7,1 0,5 3 10,9 12,6 14,2 16,0 13,9 7,5 4 10,9 12,6 14,2 16,0 17,9 19,8 13,7 0,3 5 10,9 12,6 14,2 16,0 17,9 20,1 22,4 18,8 3,6 6 10,9 12,6 14,2 16,0 17,9 20,1 22,4 24,7 23,1 4,8 The values specified in the performance tables are based on the evaporator capacity at a liquid temperature t V = 25 C at the inlet of the thermostatic expansion valve. Correction factors When dimensioning, the evaporator capacity must be multiplied by a correction factor depending on the liquid temperature t v at the inlet of the thermostatic expansion valve. The corrected capacity is then looked up in the performance table. t V [ C] R 407C 0,88 0,91 0,95 1,00 1,05 1,11 1,18 1,26 1,35 System capacity x Correction factor = Table value Edition 2014 Components Catalogue Page 4/99

14 Capacity Controllers KVC Characteristics DANFOSS The KVC is a Placed in a bypass between high and low pressure sides of the refrigeration system, KVC imposes a lower limit on the suction pressure of the compressor by letting hot gas overflow from the high pressure side to the low pressure side. Exact, adjustable pressure regulation Wide capacity and operating ranges Vibration damping Compact angle construction for easy installation Hermetically brazed design For R 22, R 134a, R 404A, R 12, R 502 and other fluorinated refrigerants Control range: 0.2 to 6,0 bar Max. Medium temperature 150 C Perm. operating pressure: 28 bar Pipe connection Nominal capacity [kw] Orig. No. EDP-No. 1 ) Flare 2 ) Solder Solder R 134a R 404A R 507 R 407C [UNF] [in] [mm] 034L /4" KVC L ,8 6,9 6,9 8, L /2" 034L KVC 15 9,4 13,6 13,6 16,4 034L KVC L ,0 17,4 17,4 21, ) The nominal capacity is the capacity of the controller at evaporating temperature t 0 = -10 C, condensing temperature t K =+25 C, Offset=0,7 bar 2 ) KVR is supplied without flare union nuts. Separate union nuts can be supplied. The chosen connection size must not be too small, since gas velocities over 40 m/s in the nozzles of the controller can cause flow noises. If the discharge line temperature, according to the compressor specifications, is too high, it is recommended to install an injection valve into a bypass between the liquid line and the suction line of the compressor. Spare capacity R 134a DANFOSS Offset Q 1 ) [kw] at suction gas temperature t S after the pressure reduction [ C] Δp [bar] ,10 1,4 1,4 1,5 1,7 1,7 0,15 2,1 2,3 2,4 2,5 2,6 0,20 2,9 3,0 3,1 3,2 3,4 KVC 12 0,30 3,7 3,9 4,1 4,3 4,5 0,50 4,2 4,3 4,5 4,8 4,9 0,70 4,4 4,5 4,8 5,0 5,2 1,00 4,8 5,0 5,2 5,5 5,8 1,20 5,1 5,4 5,6 5,8 6,1 0,10 2,1 2,3 2,4 2,5 2,6 0,15 2,9 3,0 3,1 3,2 3,4 0,20 3,7 3,9 4,1 4,3 4,5 KVC 15 0,30 5,1 5,4 5,6 5,8 6,1 0,50 7,4 7,7 8,0 8,4 8,7 0,70 8,7 9,1 9,4 9,9 10,2 1,00 9,9 10,2 10,7 11,3 11,7 1,20 10,6 11,1 11,6 12,2 12,6 0,10 2,3 2,4 2,5 2,6 2,8 0,15 3,2 3,3 3,5 3,6 3,7 0,20 4,3 4,4 4,6 4,9 5,1 KVC 22 0,30 5,2 5,5 5,7 6,0 6,3 0,50 8,9 9,3 9,7 10,1 10,5 0,70 11,0 11,6 12,0 12,6 13,1 1,00 13,7 14,3 14,9 15,6 16,3 1,20 15,0 15,7 16,3 17,2 17,8 1) The nominal capacities are based on a liquid temperature t V = 25 C at the inlet of the evaporator Correction factors When dimensioning, the bypass capacity must be multiplied by a correction factor depending on the liquid temperature t K. The corrected capacity is then found in the performance table. t V [ C] R 134 a 0,90 0,93 0,96 1,00 1,05 1,10 1,13 1,18 1,24 Page 4/100 Components Catalogue Edition 2014

15 Spare capacity R 404A/R 507 DANFOSS KVC 12 KVC 15 KVC 22 Spare capacity R 407 C DANFOSS Capacity Controllers KVC Offset Q 1 ) [kw] at suction gas temperature t S after the pressure reduction [ C] Δp [bar] ,10 1,9 2,0 2,1 2,2 2,3 2,4 0,15 3,0 3,1 3,3 3,4 3,5 3,6 0,20 3,9 4,1 4,2 4,5 4,7 4,7 0,30 5,1 5,4 5,6 5,8 6,0 6,1 0,50 5,7 6,0 6,4 6,6 6,8 7,0 0,70 6,0 6,4 6,6 6,9 7,2 7,3 1,00 6,6 6,9 7,2 7,5 7,8 8,0 1,20 7,0 7,4 7,7 8,0 8,4 8,5 0,10 3,0 3,1 3,3 3,4 3,5 3,6 0,15 3,9 4,1 4,2 4,5 4,7 4,7 0,20 5,1 5,4 5,6 5,8 6,0 6,1 0,30 7,0 7,4 7,7 8,0 8,4 8,5 0,50 10,1 10,6 11,1 11,6 12,0 12,3 0,70 11,8 12,5 13,0 13,6 14,1 14,4 1,00 13,5 14,2 14,8 15,5 16,1 16,4 1,20 14,5 15,3 16,0 16,6 17,3 17,7 0,10 3,2 3,3 3,5 3,6 3,7 3,8 0,15 4,3 4,6 4,8 5,0 5,2 5,3 0,20 5,8 6,1 6,4 6,7 7,0 7,1 0,30 8,2 8,6 8,9 9,3 9,8 9,9 0,50 12,1 12,8 13,4 13,9 14,4 14,7 0,70 15,2 16,0 16,6 17,4 18,1 18,4 1,00 18,8 19,8 20,7 21,5 22,4 22,8 1,20 20,5 21,6 22,6 23,5 24,5 25,0 Offset Q 1 ) [kw] at suction gas temperature t S after the pressure reduction [ C] Δp [bar] R 407C 0,10 2,4 2,6 2,7 2,8 2,9 3,0 0,15 3,7 3,9 4,0 4,2 4,3 4,6 0,20 4,8 5,0 5,2 5,4 5,6 5,8 KVC 12 0,30 6,3 6,5 6,9 7,0 7,2 7,6 0,50 7,0 7,3 7,7 7,9 8,1 8,6 0,70 7,4 7,7 8,1 8,4 8,7 9,0 1,00 8,1 8,5 8,8 9,1 9,4 9,8 1,20 8,7 9,1 9,5 9,8 10,1 10,6 0,10 3,7 3,9 4,0 4,2 4,3 4,6 0,15 4,8 5,0 5,2 5,4 5,6 5,8 0,20 6,3 6,5 6,9 7,0 7,2 7,6 KVC 15 0,30 8,7 9,1 9,5 9,8 10,1 10,6 0,50 12,4 12,9 13,5 14,0 14,4 15,0 0,70 14,5 15,2 15,9 16,4 16,9 17,7 1,00 16,5 17,3 18,2 18,7 319,2 20,2 1,20 17,8 18,6 19,5 20,1 20,8 21,7 0,10 3,9 4,1 4,3 4,4 4,6 4,8 0,15 5,4 5,6 5,9 6,1 6,2 6,5 0,20 7,2 7,5 8,0 8,1 8,3 8,8 KVC 22 0,30 8,9 9,2 9,7 10,0 10,3 10,8 0,50 14,9 15,5 16,4 16,8 17,3 18,1 0,70 18,7 19,4 20,4 21,0 21,6 22,7 1,00 22,7 24,0 25,2 26,0 26,8 27,9 1,20 25,2 26,3 27,7 28,5 29,3 30,7 1) The nominal capacities are based on a liquid temperature t V = 25 C at the inlet of the evaporator Correction factors When dimensioning, the bypass capacity must be multiplied by a correction factor depending on the liquid temperature t K. The corrected capacity is then found in the performance table. t V [ C] R 404A/R 507 0,84 0,89 0,94 1,00 1,07 1,16 1,26 1,40 1,57 R 407C 0,88 0,91 0,95 1,00 1,05 1,11 1,11 1,26 1,35 Edition 2014 Components Catalogue Page 4/101

16 Capacity Controllers CPCE and LG Characteristics DANFOSS CPCE is used as a capacity controller for adapting the compressor capacity to the actual evaporator load. The CPCE is installed in a bypass between the low and high pressure sides of refrigeration systems. It is specially designed for hot gas induction between the evaporator and the thermostatic expansion valve. Injection should be done by an LG liquid gas mixer. Excellent control accuracy. Direct connection to the suction line regulates hot gas induction independent of the pressure drop in the evaporator. The LG ensures homogeneous mixing of liquid and gaseous refrigerants in the evaporator. Suitable for use with R 22, R 134a, R 404A, R507, R407C and other fluorinated refrigerants. The addition of hot gas into the evaporator ensures better oil transport to the compressor. Protection against low evaporating temperatures, i.e. prevents icing of the evaporator. LG by itself can be used for adding hot gas when hot gas defrosting. Control range: 0 to 6 bar Maximum medium temperature: 140 C Perm. operating pressure: 21,5 bar Maximum test pressure: 28 bar Capacity Controllers Pipe connection Nominal capacity Orig. No EDP-No. 1) [kw] Flare Solder Solder R 134a R 404A R 507 R 407C [UNF] [in] [mm] 034N /4" CPCE 12 7,9 16,4 16,4 19,0 034N /2" 12 CPCE N ,6 24,2 24,2 27, CPCE N ,2 32,0 32,0 37, ) The nominal capacity is the controller capacity at a suction gas temperature of t S =-10 C and a condensing temperature of t k =+25 C. Subcooling temperature Δt S =4 K. Liquid gas mixer Pipe connection [mm] Orig. No. EDP-No. Expansion valve Hot gas Liquid distributor Solder ODM Solder ODF Solder ODF [in] [mm] [in] [mm] [in] [mm] LG G /2" LG G /2" LG G LG G Dimensioning The following specifications should be available for the selection of a CPCE capacity controller: Refrigerant Min. suction gas temperature t S Compressor capacity P V at min. suction gas temperature Min. evaporator capacity Q 0 Condensing temperature t k The controller capacity can then be calculated as the compressor capacity minus the evaporator capacity at minimum suction gas temperature and condensing temperature. The LG liquid gas mixer is dimensioned according to the connection nozzles. Capacity The capacities resulted by reducing the suction pressure / the suction gas temperature by Δt S = 4K. The specified suction gas temperatures are minimum values, i.e. values after the reduction. The specified capacities are composed of the hot gas capacity of the CPCE controller as well as the additional capacity of the thermostatic expansion valve in order to keep the superheat constant across the evaporator. Correction factors Suction gas temperature t S after the reduction [ C] Refrigerant suction gas temperature Δt S [K] R 134a 0,1 0,5 0,9 1,0 1,0 1,0 1,0 R 404A, R 507 0,3 0,9 1,0 1,0 1,0 1,0 1,0 ±0 R 134a 0,1 0,3 0,7 1,0 1,0 1,0 1,0 R 404A, R 507 0,2 0,9 1,0 1,0 1,0 1,0 1,0-10 R 134a 0,1 0,3 0,6 1,0 1,0 1,4 1,4 R 404A, R 507 0,1 0,5 1,0 1,0 1,0 1,0 1,0-20 R 134a 0,1 0,3 0,6 1,0 1,5 2,2 2,4 R 404A, R 507 0,1 0,3 0,7 1,0 1,0 1,0 1,0-30 R 134a 0,1 0,3 0,6 1,0 1,5 2,2 2,9 R 404A, R 507 0,1 0,3 0,6 1,0 1,3 1,4 1,4-40 R 404A, R 507 0,1 0,3 0,6 1,0 1,5 2,0 2,2 The correction table is used when the suction gas temperature change differs from 4 K. The table values are then multiplied by the found correction factor. Page 4/102 Components Catalogue Edition 2014

17 Capacity R 134a DANFOSS CPCE 12 CPCE 15 CPCE 22 Capacity R 404A/R 507 DANFOSS CPCE 12 CPCE 15 CPCE 22 CPCE 12 CPCE 15 CPCE 22 Capacity Controllers CPCE and LG Suction gas temperature t S after the pressure/temperature Controller capacity Q [kw] at condensing temperature t K [ C] reduction [ C] ,3 10,4 14,4 18,0 22,6 ±0 7,8 11,3 14,4 18,1 22,6-10 5,8 7,9 10,8 14,4 18,1-20 3,4 4,6 6,1 8,3 10,6-30 2,0 2,8 3,7 4,9 6, ,3 15,2 21,1 26,5 33,2 ±0 11,4 16,6 21,2 26,6 33,2-10 8,3 11,6 15,7 21,1 26,6-20 4,8 6,6 8,8 11,9 15,2-30 2,6 3,5 4,9 6,4 8, ,1 20,4 28,0 35,2 43,9 ±0 15,1 22,8 28,1 35,2 43, ,9 15,2 20,9 27,7 35,2-20 6,4 8,8 11,8 15,7 20,3-30 3,7 5,0 6,8 8,9 11,3-40 Suction gas temperature t S after the pressure/temperature Controller capacity Q [kw] at condensing temperature t K [ C] reduction [ C] ,5 15,5 20,6 25,7 31,1 ±0 12,2 16,4 20,6 25, ,9 16,4 20,7 25, ,1 16,4 20, ,3 13,8 17,9-40 5,5 7,5 9, ,0 22,8 30,3 37,8 46,9 ±0 18,0 24,2 30,3 37, ,1 24,2 30,4 37, ,1 24,3 30, ,0 20,3 26,5-40 8,0 10,6 13, ,6 30,2 40,1 49,9 62,3 ±0 23,8 32,0 40,1 49, ,3 32,0 40,1 50, ,3 23,1 40, ,9 26,7 34, ,6 14,2 18 Leistung R 407 C DANFOSS Suction gas temperature t S after the pressure/temperature Controller capacity Q [kw] at condensing temperature t K [ C] reduction [ C] ,7 18,3 23,5 28,2 33,4 ±0 14,4 19,0 23,2 27, ,1 19,0 23,3 27, ,1 18,8 23,1 27,4-30 8,7 11,7 15,0 18,0-40 4,6 5,9 7, ,1 26,9 34,6 41,4 49,0 ±0 21,1 27,9 34,2 41, ,2 27,9 34,2 40, ,1 27,6 33,9 40, ,5 17,0 21,6 26,3-40 6,3 8,1 10, ,7 35,5 45,8 54,9 64,9 ±0 28,0 37,0 45,4 54, ,4 37,1 45,4 53, ,3 36,6 44,8 53, ,8 22,6 28,7 34,8-40 8,6 11,1 14,3 Edition 2014 Components Catalogue Page 4/103

18 Venturi - Distributors Application Subdividing the evaporator into several parallel sections of equal pipe length and equal heat transfer capacity offers advantages where, due to the required surface, very long evaporator pipes would be a result. The advantage: When connecting large pipe lengths of the same diameter in series, the transfer capacity does not increase to the same extent as the surface according to the pipe length. The extended flow path with simultaneous increased refrigerant throughput results in a strong increase of the pressure drop. This results in an increased gas volume which leads to a reduction of the refrigerant amount drawn in by the compressor - thus also to a reduction of refrigerating capacity. Evaporators are therefore subdivided into several parallel sections with a relatively short pipe length. The individual sections are fed by a liquid distributor which has the task of distributing the refrigerant-vapour mixture coming from the throttling device equally to the individual sections. Since liquid distributors are not controllers, but rather only additional devices, they are not able to adjust the refrigerant supply according to the different demands of the individual sections. equal pipe lengths equal flow resistance equal transfer capacity and the distributor pipes to the individual coils have equal lengths and diameters. Installation The liquid distributor should be installed in vertical position. The distributor pipes must be of equal length. The liquid distributor can be mounted directly on the expansion valve. If a pipe bend between expansion valve and liquid distributor cannot be avoided, then a straight piece of pipe should be installed between the pipe bend and the liquid distributor, whose length is at least 7 times the pipe diameter. Nominal capacity Q N per distributor pipe kw Evaporating Capacity in kw for 1 m distributor pipe with Δp = 1 bar temperature Outer diameter of the distributor pipes Ø 6 mm t 0 C R 134a R 407C R 404A / R ,30 5,30 3,30 ± 0 2,30 3,70 2, ,60 2,60 1, ,10 1,80 1, ,79 1,30 0, ,55 0,88 0, ,41 0,65 0, ,27 0,43 0,27 The specified values are based on a liquid temperature t u = 35 C and a pipe length of 1 m. The pressure drop (across distributor and distributor pipes) at nominal capacity is approx. 1 bar. Example Given: Evaporator capacity Q 0 = 30 kw Refrigerant R407C Evaporating temp. t 0 = -10 C Injection n = 10-fold Distributor pipe length I = 0,8 m correction Korrekturfaktor factor K I Diagram: Pipe length correction factor K I ,3 0,4 0,5 0,6 0,7 0,8 0,9 1,5 2,0 1,0 Distributor Verteilerrohrlänge pipe length I (m) From the pipe length-correction factor diagram the factor K I =1,12 is obtained for the distributor pipe length 0,8 m. Using the equation Q RI = Q 0 n. K I 30 the length-compensated distributor capacity is determined: Q RI= = 2,67 kw 10. 1,12 Selection EDP-No. Designation Venturi distributor 12/6/2 (VK 0) Venturi distributor 12/6/3 (VK 0) Venturi distributor 12/6/4 (VK I) Venturi distributor 12/6/5 (VK I) Venturi distributor 16/6/4 (VK II) Venturi distributor 16/6/5 (VK II) Venturi distributor 16/6/6 (VK II) Venturi distributor 16/6/7 (VK II) Venturi distributor 16/6/8 (VK II) Venturi distributor 16/6/9 (VK III) Venturi distributor 16/6/10 (VK III) Venturi distributor 16/6/11 (VK III) Venturi distributor 16/6/12 (VK III) Page 4/108 Components Catalogue Edition 2014

19 Condensing Pressure Control Valve ORI, ORD, OROA These products are distributed primarily in Switzerland Characteristics SPORLAN Condensing pressure control valves were developed in order to ensure smooth operation of refrigeration systems with air-cooled condensers in the winter. If the condenser is designed properly, then there are no problems operating the system at high outside temperatures in the summer. If the system needs to be operated at cold outside temperatures, however, some problems exist if no corresponding control system is in place. For very low condensing pressures, the differential pressure at the expansion valves can become too little in winter. The result is a mass flow which is too low in relation to the compressor capacity because the evaporators are not sufficiently charged and the system oscillates to the off position via the low pressure switch. In order to solve these problems, the flow of refrigerant condensate to the receiver is reduced by means of a condensing pressure control valve. In this way, liquid refrigerant is accumulated in the condenser and therefore the effective heat transfer surface for condensation is reduced. This creates an increase in pressure on the discharge side. By transferring hot gas into the receiver (in many cases via a hot gas differential pressure valve) the pressure in the liquid line is then increased. Thus there is enough differential pressure for correct operation of the expansion valves again. For various reasons, in Germany, Sporlan condensing pressure controllers of the model series ORI(T) are preferred to the other Sporlan models OROA-5 and LAC. Technical data and dimensions Standard factory settings EDP-No. Pipe connection Dimensions Solder ODF A B C D E F G I Inlet 1 Inlet ➁ Outlet [barg] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [in] [in] [in] ORI /225-H 8,3 on request ORI /225-H ORD , ORD , OROA-5 12, ,5 on request on request Dimension drawing and type code Edition 2014 Components Catalogue Page 4/109

20 Condensing Pressure Control Valve These products are distributed primarily in Switzerland Performance data Qo [kw] for winter operation Performance data Qo [kw] for summer operation Minimum Pressure Valve type Pressure Valve type Setpoint ambient tem- drop drop Refrigeranperature valve OROA-5 ORD-4 setting Refrigerant across the across the valve OROA-5 ORI-6 ORI-10 [barg] [ C] [bar] [bar] R 407C 12,4 R 134a 6,9 R 410A 20,3 R 404A R , , , , , , , , , , , , , ,70 0,70 0,70 1, , , , , , , , , , , , , R 407C 0, , , , R 134a 0, , , R 410A 0,21 0,28 0, R 404A 0, , , , R 507 0, , , Valve capacities are based on: evaporating temperature -20 C, condensing temperature 43 C, subcooling 6 K. Valve capacities are based on: evaporating temperature -20 C, condensing temperature 35 C, subcooling 6 K. Page 4/110 Components Catalogue Edition 2014

21 Evaporating Pressure Controllers ORIT These products are distributed primarily in Switzerland Characteristics SPORLAN Evaporating pressure controllers regulate constant pressure at the valve inlet. This is why their type designation is the same as those of condensing pressure control valves (ORI Open on Rise of Inlet Pressure). Only the lower range for the setpoint value makes it clear that an ORI valve is a condensing pressure control valve. If the load at the evaporator increases, then the valve opens. Applications * The valve prevents the evaporating pressure from falling below the setpoint value, e.g. in order to avoid ice formation at the evaporator or to limit dehumidification. * Maintaining a higher evaporating temperature e.g. in refrigerated appliances for fruits, cheese or vegetables. * Evaporating temperature limitation in water cooling units. ORI(T) valve types are available with 2 different valve seat sizes. The direct-acting evaporating pressure control valve requires the evaporating pressure to rise above the setpoint value in order to achieve the desired valve capacity. The nominal capacities are based on a pressure rise of 0,55 bar at the setting range 0/3,45 barg and a pressure rise of 0,83 bar at the setting range 2,07/6,90 barg. The control valves should be selected for the maximum desired pressure rise using the correction factors below. Selection: Oper. Nominal capacity Q 1 Pressure range N ) Pipe connection pressure EDP-No. [kw] Flare Solder [Psig] [bar] [bar] R 134a R404A R507 R 407C [SAE] [ODF] /2" /2" 0/50 0-3, ORIT-6 20, ,30 3,89 3,89 4, /2" /2" 30/100 2,0-6, /50 0-3, ORIT-10 13, ,39 9,59 9,59 12, /100 2,0-6, ) The nominal capacity is based on: evaporating temperature +5 C; Δp bar Edition 2014 Components Catalogue Page 4/111

Capacity regulators, type CPCE and LG REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Capacity regulators, type CPCE and LG REFRIGERATION AND AIR CONDITIONING. Technical leaflet Capacity regulators, type CPCE and LG REFRIGERATION AND AIR CONDITIONING Technical leaflet Introduction CPCE capacity regulators adapt compressor capacity to actual evaporator load. They are designed for

More information

Hot gas bypass regulator, type CPCE Liquid gas mixer, type LG (accessory)

Hot gas bypass regulator, type CPCE Liquid gas mixer, type LG (accessory) Data sheet Hot gas bypass regulator, type CPCE Liquid gas mixer, type LG (accessory) CPCE hot gas bypass regulator adapt compressor capacity to actual evaporator load. They are designed for installation

More information

Refrigeration and Air Conditioning Controls. Applications. PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING

Refrigeration and Air Conditioning Controls. Applications. PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING Refrigeration and Air Conditioning Controls Applications PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING Introduction Danfoss PM regulators have been on the market

More information

Check valve Types NRV and NRVH

Check valve Types NRV and NRVH Check valve s NRV and NRVH NRV and NRVH can be used in liquid. suction and hot gas lines in refrigeration and air conditioning plant with HCFC. HFC and HC flammable refrigerants. The valves ensure the

More information

FSW SECTION. Product guide. Expansion Valves, Solenoid Valves Water Valves & Oil Pressure Switches F SECTION. 71

FSW SECTION. Product guide. Expansion Valves, Solenoid Valves Water Valves & Oil Pressure Switches F SECTION.   71 FSW Product guide F SECTION Expansion Valves, Solenoid Valves Water Valves & Oil Pressure Switches For more information visit www.fsw.uk.com 71 Danfoss Expansion Valves T* Range - Order valve and orifice

More information

MAKING MODERN LIVING POSSIBLE. Thermostatic expansion valves, type TR 6 REFRIGERATION & AIR CONDITIONING DIVISION.

MAKING MODERN LIVING POSSIBLE. Thermostatic expansion valves, type TR 6 REFRIGERATION & AIR CONDITIONING DIVISION. MAKING MODERN LIVING POSSIBLE Thermostatic expansion valves, type REFRIGERATION & AIR CONDITIONING DIVISION Technical leaflet Technical leaflet Thermostatic expansion valves, type Contents Page Introduction........................................................................................3

More information

Liquid Distributor Type RD

Liquid Distributor Type RD MAKING MODERN LIVING POSSIBLE Data sheet Liquid Distributor Type RD The RD refrigerant distributors distribute liquid refrigerants from the thermostatic expansion valve to individual sections of the evaporator.

More information

RD refrigerant distributors, for thermostatic expansion valves REFRIGERATION AND AIR CONDITIONING. Technical leaflet

RD refrigerant distributors, for thermostatic expansion valves REFRIGERATION AND AIR CONDITIONING. Technical leaflet RD refrigerant distributors, for thermostatic expansion valves REFRIGERATION AND AIR CONDITIONING Technical leaflet Introduction RD refrigerant distributors distribute liquid refrigerants from the thermostatic

More information

Tube-in-tube heat exchanger Type HE

Tube-in-tube heat exchanger Type HE Data sheet Tube-in-tube heat exchanger Type HE Tube-in-tube heat exchanger type HE is used primarily for heat transfer between the liquid and suction lines of the refrigeration plant. The purpose is to

More information

Thermostatic Expansion Valves Type TR 6

Thermostatic Expansion Valves Type TR 6 MAKING MODERN LIVING POSSIBLE Data sheet Thermostatic Expansion Valves Introduction The series is a hermetic tight design, designed and developed with features especially for use in applications such as:

More information

Tube-in-tube heat exchanger Type HE

Tube-in-tube heat exchanger Type HE MAKING MODERN LIVING POSSIBLE Data sheet Tube-in-tube heat exchanger Type HE Tube-in-tube heat exchanger type HE is used primarily for heat transfer between the liquid and suction lines of the refrigeration

More information

Refrigerant valves. Valves for precise control and optimum energy efficiency in refrigeration systems. Answers for infrastructure.

Refrigerant valves. Valves for precise control and optimum energy efficiency in refrigeration systems. Answers for infrastructure. Refrigerant valves Valves for precise control and optimum energy efficiency in refrigeration systems Answers for infrastructure. MVL661.. MVS661..N and matching ASR valve insert The new generation MVL661..

More information

Zero ODP and negligible GWP when using hydrocarbons. Zero. portfolio for hydrocarbons.

Zero ODP and negligible GWP when using hydrocarbons. Zero. portfolio for hydrocarbons. Danfoss components for hydrocarbon refrigeration Leapfrog Extensive to a portfolio long-term and solution expertise with for safe Danfoss and optimised wide product use of hydrocarbons portfolio for hydrocarbons

More information

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job. June 01 / BULLETIN - 3-Way Valves The right solenoid valve for any job. Page 2 / Bulletin - Advantages Sporlan 3-Way Valves 3-Way Pilot eliminates costly high- to low-side leaks. "B" reduces total installed

More information

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE REFRIGERATION AND AIR CONDITIONING. Technical leaflet Capacity regulator (hot gas bypass), type TUH/TCHE/ REFRIGERATION AND AIR CONDITIONING Technical leaflet Contents Page Introduction........................................................................................3

More information

Bulletin , March Electric Hot Gas Bypass Valves

Bulletin , March Electric Hot Gas Bypass Valves Bulletin 100-60, March 2018 Electric Hot Gas Bypass Valves PAGE 2 / Bulletin 100-60 10 FEATURES AND BENEFITS SDR-4 Direct temperature control Tight shutoff when closed Can be interfaced with direct digital

More information

Product Catalog VALVES

Product Catalog VALVES SUIKA CLIMATE Product Catalog VALVES CONTACT WEB Info@suikaclimate.com ADDRESS Fremont, CA, 94555 TELEPHONE +1 (800) 625 0589 +1 (510) 859 8003 Suika Climate Toeflex ABOUT US Suika Climate (US), Toeflex

More information

Thermostatic Expansion Valves

Thermostatic Expansion Valves Thermostatic Expansion Valves Alco TI Series with Interchangeable Orifice Assembly TI Series Valves with interchangeable orifi ces provide the capability of changing capacity with only the change of an

More information

Thermostatic Expansion valves, type TUA/TUAE REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Thermostatic Expansion valves, type TUA/TUAE REFRIGERATION AND AIR CONDITIONING. Technical leaflet Thermostatic Expansion valves, type A/AE REFRIGERATION AND AIR CONDITIONING Technical leaflet Thermostatic expansion valves, type A/AE Contents Page Introduction... Features... Standard range... Technical

More information

PULSE WIDTH MODULATING VALVES

PULSE WIDTH MODULATING VALVES PULSE WIDTH MODULATING VALVES PARKER PULSE WIDTH MODULATING VALVES MODEL HP P4144 MODELS CS & DS P4145 Features Long life (100 million cycles). Suitable for all common refrigerants except ammonia. Maximum

More information

THERMAL SOLUTIONS COAXIAL HEAT EXCHANGERS WKE, WKC

THERMAL SOLUTIONS COAXIAL HEAT EXCHANGERS WKE, WKC THERMAL SOLUTIONS COAXIAL HEAT EXCHANGERS WKE, WKC COAXIAL HEAT EXCHANGERS WKE, WKC APPLICATIONS Wieland coaxial heat exchangers are used as evaporators (WKE) or as condensers (WKC). They consist of one

More information

CHECK VALVES INSTALLATION

CHECK VALVES INSTALLATION CHECK VALVES 35 CHECK VALVES APPLICATIONS The check valves illustrated herein are designed for use with refrigerant fluids CFC, HCFC and HFC. Castel check valves can be used on any section of a refrigerating

More information

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES November 2006 / BULLETIN -60 ELECTRIC DISCHARGE BYPASS VALVES PAGE 2 / Bulletin -60 10 FEATURES AND BENEFITS Direct temperature control Tight shutoff when closed Can be interfaced with direct digital controls

More information

Head Pressure Control Valves

Head Pressure Control Valves Head ontrol s High and Low mbient Stability The design of air conditioning systems utilizing air cooled condensing units involves two main problems that must be solved if the system is to operate reliably

More information

Technical Information

Technical Information Date of last update: 02-08 Ref: Application Engineering Europe COPELAND SCROLL COMPRESSORS USING VAPOUR INJECTION FOR REFRIGERATION CONTENTS 1 Introduction...1 2 Principle of Operation...1 3 Capacity Effect...2

More information

HANDBOOK REGULATOR VALVES. Ed REGULATOR VALVES RP-ED 01/ ENG 1

HANDBOOK REGULATOR VALVES. Ed REGULATOR VALVES RP-ED 01/ ENG 1 HANDBOOK Ed. 2017 RP-ED 01/2017 - ENG 1 DIRECTIVE 2014/68/EU ISSUED OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL OF 15 MAY 2014 ON PRESSURE EQUIPMENT Directive 2014/68/EU (PED Recast) applies to the design,

More information

Thermostatic expansion valves for ammonia Type TEA

Thermostatic expansion valves for ammonia Type TEA Data sheet Thermostatic expansion valves for ammonia Type TEA Thermostatic expansion valves regulate the injection of refrigerant liquid into evaporators. Injection is controlled by the refrigerant superheat.

More information

Suction Accumulators. Introduction. Suction Accumulators

Suction Accumulators. Introduction. Suction Accumulators Introduction The purpose of the Suction Accumulator is to provide temporary storage for any liquid refrigerant and oil that is returning to the compressor from the evaporator. The accumulator s internal

More information

OIL SEPARATORS APPLICATIONS

OIL SEPARATORS APPLICATIONS OIL SEPARATORS APPLICATIONS The oil separators, shown in this chapter, are classified Pressure vessels in the sense of the Pressure Equipment Directive 97/23/EC, Article 1, Section 2.1.1 and are subject

More information

Flexible. Upgrade and service with ease Extend lifetime with modular design. Thermostatic expansion valves Type TE5-55

Flexible. Upgrade and service with ease Extend lifetime with modular design.   Thermostatic expansion valves Type TE5-55 MAKING MODERN LIVING POSSIBLE Upgrade and service with ease Extend lifetime with modular design Thermostatic expansion valves Type TE5-55 Flexible Upgrade with backward compatible valve technology. Mix

More information

ThermoSaver TM Hot Gas Defrost System

ThermoSaver TM Hot Gas Defrost System PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin K40-THERM-PDI-15 Part # 1069130 PRODUCT SUPPORT web: k-rp.com/ts email: mdcu-lgcu@k-rp.com

More information

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ SERIES: EWCBZ - Heat pump MODELS: 70, 80, 00, 0, 60, 00, 40, 00, 50 COOLING CAPACITIES from 5,9 kw to 78,5

More information

LINE COMPONENTS VALVES

LINE COMPONENTS VALVES VALVES DANFOSS THERMOSTATIC EXPANSION VALVES - T2 T2 thermostatic expansion valves regulate the injection of refrigerant liquid into evaporators. The refrigerant superheat determines the amount. Large

More information

Technical description. Atec.

Technical description. Atec. www.thermia.com Thermia Värmepumpar is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions.

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

Danfoss Scroll for Refrigeration MLM / MLZ

Danfoss Scroll for Refrigeration MLM / MLZ s Danfoss Scroll for Refrigeration MLM / MLZ 50-60 Hz - R404A - R507 - R134a - R22 - R407A - R407F http://danfoss.us.com/ Contents Features... 6 Scroll compression principle... 7 The scroll compression

More information

500 EX Fusion Compressor Series

500 EX Fusion Compressor Series 500 EX Fusion Compressor Series R404A M/T R404A L/T Capacity RANGE 13.8kW - 20.4kW 7.7kW -11.2kW Copeland Fusion Semi-Hermetic Horizontal Scroll Compressors For Medium and Low Temperature Applications

More information

A Treatise on Liquid Subcooling

A Treatise on Liquid Subcooling A Treatise on Liquid Subcooling While the subject of this article is Liquid Refrigerant Subcooling, its affect on the operation of the thermostatic expansion valve (TEV), and ultimately on system performance

More information

General Characteristics SM185S3QC. Dimensions. Terminal box. Electrical Characteristics. Recommended Installation torques

General Characteristics SM185S3QC. Dimensions. Terminal box. Electrical Characteristics. Recommended Installation torques Datasheet, technical data Performer scroll compressor, SM185-3 General Characteristics Model number (on compressor nameplate) Code number for Singlepack* Code number for Industrial pack** Drawing number

More information

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration 11.1 Introduction Preservation of foods is a vital processing step in food processing. There are

More information

y Small dimensions. Easy to install in refrigerated counters or cold rooms

y Small dimensions. Easy to install in refrigerated counters or cold rooms MAKING MODERN LIVING POSSIBLE Data sheet Thermostat Type KP The KP Thermostats are temperaturecontrolled electrical switches. All KP Thermostats have a single pole double throw (SPDT) changeover switch.

More information

EC3-X33 Stand-alone Superheat Controller

EC3-X33 Stand-alone Superheat Controller is a stand-alone universal superheat controller for air conditioning, refrigeration and industrial applications such as chillers, industrial process cooling, rooftops, heat pumps, package unit, close control,

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

280 SERIES STEAM CONVERTING VALVE SIZING AND SELECTION. 1. Introduction Design Properties Sizing and Selection Criteria...

280 SERIES STEAM CONVERTING VALVE SIZING AND SELECTION. 1. Introduction Design Properties Sizing and Selection Criteria... Contents 1. Introduction... 2 2. 280 Design Properties... 3 3. 280 Sizing and Selection Criteria... 4 3.1 Definitions... 4 3.2 Operating Conditions... 4 3.3 Valve/Pipe Dimensioning... 5 3.4 Valve Design...

More information

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

SOLENOID VALVES FOR REFRIGERATING SYSTEMS SOLENOID VALVES FOR REFRIGERATING SYSTEMS APPLICATIONS The solenoid valves, shown in this chapter, are classified Pressure accessories in the sense of the Pressure Equipment Directive 97/23/EC, Article

More information

Revolutionary ETS Colibri valves Engineered to give you maximum flexibility and dependability

Revolutionary ETS Colibri valves Engineered to give you maximum flexibility and dependability Revolutionary ETS Colibri valves Engineered to give you maximum flexibility and dependability ETS Colibri brings to the market one of a kind, uniquely designed electric expansion valve. Innovative Design

More information

KCS-Line Air Cooled Condensers

KCS-Line Air Cooled Condensers PRODUCT DATA & INSTALLATION Bulletin K50-KCS-PDI-5 Part # 1085695 PRODUCT SUPPORT web: k-rp.com/kcs email: acc-fc@k-rp.com call: 1-844-893-3222 x526 scan: KCS-Line Air Cooled Condensers R407A R407C R448A

More information

Easy. Products and technologies for all your application needs, today and tomorrow. Quick Select Guide 2017

Easy. Products and technologies for all your application needs, today and tomorrow. Quick Select Guide 2017 Quick Select Guide 2017 Products and technologies for all your application needs, today and tomorrow REFRIGERATION & AIR CONDITIONING COMPONENTS Easy Find the right products fast with our Quick Select

More information

Sporlan Valve Division Parker Hannifan/CIC Group

Sporlan Valve Division Parker Hannifan/CIC Group www.parker.com/cic Sporlan Valve Division Parker Hannifan/CIC Group Matt McGrath, SW Regional Sales Manager Bob Dolan, Sales Engineer - Atlanta www.parker.com/cic Why Discuss TEVs Today? Expansion Valves

More information

ThermoSaver TM Hot Gas Defrost System

ThermoSaver TM Hot Gas Defrost System PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin B40-THERM-PDI-14 1069132 ThermoSaver TM Hot Gas Defrost System For use on select

More information

SEMI-HERMETIC SCREW COMPRESSORS

SEMI-HERMETIC SCREW COMPRESSORS SEMI-HERMETIC SCREW COMPRESSORS 50 Hz // SP-00-5 EN HS.53 // HS.64 // HS.74 // HS.5 // HS.95 WITH IQ MODULE BIGGER MODELS BITZER Innovation Targets Semi-hermetic screw compressors Products for refrigerants

More information

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA242H WA36H NOTE: Electrical data presented in this manualsupersedes any other data for the above listed models. Bard Manufacturing

More information

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10 Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW Compressors Scroll Serie: Series: Emissione: Issue: SCAEY Catalogo: Leaflet: Sostituisce: Supersedes: DE 88 04/11 12/10 Index

More information

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES SECTION 23 23 00 REFRIGERANT PIPING AND SPECIALITIES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Refrigerant piping. 2. Unions, flanges, and couplings. 3. Pipe hangers and supports. 4. Refrigerant

More information

Operating instructions for semi-hermetic motorcompressors

Operating instructions for semi-hermetic motorcompressors Operating instructions Page 1 Operating instructions Type: HG 4/310-8/4 S HG 4/385-8/4 S HG 4/465-8/4 S HG 4/555-8/4 Page 2 Page 3 Contents Page 1. Safety instructions...4 2. Main and functional parts...4

More information

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax: TECHNICAL MANUAL CX(E) SPLIT SYSTEMS CONTENTS INDEX PART NUMBERS, OPTIONS, UNIT COMBINATIONS, DIMENSIONS & WEIGHTS 3 PERFORMANCE DATA & AIR FLOW 4 SOUND POWER AND SOUND PRESSURE LEVELS 5 ELECTRICAL DATA

More information

T2 thermostatic expansion valves regulate the injection of refrigerant liquid into evaporators. The refrigerant superheat determines the amount.

T2 thermostatic expansion valves regulate the injection of refrigerant liquid into evaporators. The refrigerant superheat determines the amount. DANFOSS THERMOSTATIC EXPANSION - T2 T2 thermostatic expansion valves regulate the injection of refrigerant liquid into evaporators. The refrigerant superheat determines the amount. FEATURES Large temperature

More information

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison Emerging Technologies: VFDs for Condensers Douglas T. Reindl Director, IRC University of Wisconsin-Madison University of Wisconsin-Madison 1 We ve looked at VFDs on Evaporators and compressors, what is

More information

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou Condensers ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM A. Hadawey, Y. T. Ge, S. A. Tassou 4 7 8 5 3 2 6 1 Produced by: The Centre for Energy and Built Environment

More information

Compressed air preparation Compressed air storage Moisture management. Catalog #1

Compressed air preparation Compressed air storage Moisture management. Catalog #1 Compressed air preparation Compressed air storage Moisture management Catalog #1 This Catalogue is valid from May 2015. All previous catalogues lose their validity with the publication of the new catalogue.

More information

CONDOR-H (horizontal) / CONDOR-V (vertical)

CONDOR-H (horizontal) / CONDOR-V (vertical) Refrigeration & limate omponents Solutions 3.1 TY-EN 3.1- / -18 ONDOR-H (horizontal) / ONDOR-V (vertical) n Applications ensure cooling, condensation and storage of refrigerant in refrigerating and air

More information

Danfoss scroll compressors SH- In parallel installation

Danfoss scroll compressors SH- In parallel installation MAKING MODERN LIVING POSSIBLE Application guidelines Danfoss scroll compressors SH- In parallel installation 50 Hz - 60 Hz - R410A www.danfoss.com CONTENTS General overview...4 Benefits... 4 Scope...

More information

Danfoss scroll compressors SH - In parallel installation

Danfoss scroll compressors SH - In parallel installation Application guidelines Danfoss scroll compressors SH - In parallel installation 50 Hz - 60 Hz - R410A http://cc.danfoss.com Contents General overview... 5 Benefits... 5 Scope... 5 Design challenge...

More information

EC3-X33 Stand-alone Superheat Controller Technical Data

EC3-X33 Stand-alone Superheat Controller Technical Data Technical Data EC3-X33 is a stand-alone universal superheat controller for air conditioning, refrigeration and industrial applications such as chillers, industrial process cooling, rooftops, heat pumps,

More information

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation INTRODUCTION In recent years air conditioning industry technology has advanced rapidly. An important byproduct of this growth has been development of the heat pump. Altogether too much mystery has surrounded

More information

Accumulators - Suction Line

Accumulators - Suction Line ACCUMULATORS Accumulators - Suction Line kw Cap at Evap. Temp. -6 C Size Connection R22 R404A / R507C F0804 1/2" ODS Vertical 4.6 4.8 F0805 5/8" ODS Vertical 6.9 7.2 F0806 3/4" ODS Vertical 9.2 9.6 F0807

More information

Compendium DES July 2016, CARN

Compendium DES July 2016, CARN Compendium DES July 2016, CARN 1 Contents Contents... 2 1. Energy balance... 4 Using Energy Balance for analyzing energy systems... 4 Energy Balance definition... 4 Steady state, steady flow... 4 Methodology...

More information

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N E S A RE F R E IG RA N T G TECHNICAL MANUAL -FRIEND Y CONDENSING UNITS FOR OUTDOOR INSTALLATION O L CMA C 2 The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual,

More information

RSES Technical Institute Training Manual 2 72 hours, 72 NATE CEHs, 7.2 CEUs

RSES Technical Institute Training Manual 2 72 hours, 72 NATE CEHs, 7.2 CEUs Lesson 1 - Trade Tools Explain the importance of using proper tools and test instruments. List the various types of wrenches and describe their use. Describe the proper procedures for bending, flaring,

More information

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System

More information

KTL Two-Way Low Profile Evaporators

KTL Two-Way Low Profile Evaporators PRODUCT DATA & INSTALLATION Bulletin K30--PDI-16 Part # 87830 PRODUCT SUPPORT web: k-rp.com/ktl email: evaps@k-rp.com call: 1-844-893-3222 x520 scan: Two-Way Low Profile Evaporators High, Medium and Low

More information

Parilla Thermal Storage Project Case Study. May Page 1 of 11

Parilla Thermal Storage Project Case Study. May Page 1 of 11 Parilla Thermal Storage Project Case Study May 2014 Page 1 of 11 BACKGROUND Parilla Premium Potatoes is a large refrigerated storage facility (Figure 1) located in South Australia; the facility consists

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A900-22007), 120/208/240/1/60, R404A, LT/MT APPS Introduction The superheat controller is designed

More information

Performance Requirements for Air-Cooled Condenser

Performance Requirements for Air-Cooled Condenser #120 ACRD Requirements for Selecting 3 rd Party Remote Air-Cooled Condenser and Flooded Receiver Abstract The InRow RD (ACRD600, ACRD601, ACRD602, ACRD600P, ACRD601P, ACRD602P) is an air-cooled DX air

More information

Temperature controller for steam (PN 25) AVT / VGS - external thread

Temperature controller for steam (PN 25) AVT / VGS - external thread Data sheet Temperature controller for steam (PN 25) AVT / VGS - external thread Description The controller has a control valve VGS, thermostatic actuator and handle for temperature setting. Thermostatic

More information

Semi-hermetic GEA Bock Compressors. Single-stage and Two-stage Reciprocating Compressors HG (HA) engineering for a better world

Semi-hermetic GEA Bock Compressors. Single-stage and Two-stage Reciprocating Compressors HG (HA) engineering for a better world Semi-hermetic GEA Bock Compressors Single-stage and Two-stage Reciprocating Compressors HG (HA) engineering for a better world GEA Refrigeration Technologies In touch with our customers GEA Refrigeration

More information

Filter Driers with Replaceable Core

Filter Driers with Replaceable Core STANDARD Filter Driers with Replaceable Core The filter driers with replaceable core (HTG series) are used in liquid line and suction line of refrigerating, freezing and air conditioning system. The filter

More information

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad- 500 043 B.Tech (III II SEM) MECHANICAL ENGINEERING REFRIGERATION AND AIR CONDITIONING Prepared by, Dr. CH V K N S N Moorthy, Professor

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information

Air Cooled Scroll Chiller / Heat Pump

Air Cooled Scroll Chiller / Heat Pump Air Cooled Scroll Chiller / Heat Pump SRA 145 Nominal Capacity 67.5 to 1080 kw Refrigerant: R407C and R134a Contents Features 1 MV7 Control 3 Physical Data R407c 5 Physical Data R134a 6 Unit Performance

More information

Process glycol chillers

Process glycol chillers Process glycol chillers The most advanced solutions in refrigeration technology. According to normative EN378 y F-Gas Compact chillers for outdoor installation Natural refrigerant Integrated hydraulic

More information

Technical Information

Technical Information Date of last update: May-12 Ref: : Application Engineering Europe ENHANCED VAPOUR INJECTION (EVI) FOR ZH*KVE SCROLL COMPRESSORS 1 Introduction... 2 2 Principle of operation... 2 3 Capacity effect... 3

More information

MAKING MODERN LIVING POSSIBLE. Check valve for EVRA, EVRAT and PM valves in liquid lines type NRVS. Technical brochure

MAKING MODERN LIVING POSSIBLE. Check valve for EVRA, EVRAT and PM valves in liquid lines type NRVS. Technical brochure MAKING MODERN LIVING POSSIBLE Check valve for EVRA, EVRAT and PM valves in liquid lines type NRVS Technical brochure Introduction NRVS NRVS mounted on PM and EVRA valve Check valve type NRVS has no damping

More information

Warm Case Troubleshooting Guide 9/18/2014

Warm Case Troubleshooting Guide 9/18/2014 Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last

More information

CDS 80. Continuous ventilation without dehumidification can be selected on the CDS 80 control panel.

CDS 80. Continuous ventilation without dehumidification can be selected on the CDS 80 control panel. DEHUMIDIFICATION 9 CDS 80 FUNCTION The CDS 80 works in accordance with the condensation principle. A fan draws the humid air into the dehumidifier and through an evaporator coil. When passing through the

More information

TURBOIL (welded) / TURBOIL-F (flanged)

TURBOIL (welded) / TURBOIL-F (flanged) Refrigeration & limate omponents Solutions 41.1 TY-EN 41.1-6 / 02-2018 TURBOI (welded) / TURBOI-F (flanged) n Applications Separation and recovery of the oil carried by the refrigerant in vapour phase

More information

Air-Cooled Condensing Units with Compact Screw Compressors

Air-Cooled Condensing Units with Compact Screw Compressors LK-SCUTB March 2015 Air-Cooled Condensing Units with Compact Screw s Technical Bulletin Models SSV DSV Table of Contents Nomenclature Chart... 2 Introduction... 3 Bitzer TM s... 4 Magnum TM Microprocessor...

More information

Maneurop reciprocating compressors NTZ

Maneurop reciprocating compressors NTZ Maneurop reciprocating compressors NTZ R404A - R507-60 Hz http://danfoss.us.com/ Content Maneurop reciprocating compressors...5 Features...5 Specifications...6 Technical specifications and nominal ratings...6

More information

Temperature controller AVT with safety temperature monitor STM / VGS for steam (PN 25)

Temperature controller AVT with safety temperature monitor STM / VGS for steam (PN 25) Data sheet Temperature controller AVT with safety temperature monitor STM / VGS for steam (PN 25) Description STW871 The controllers are: - Type-tested acc. to EN 14597 and protect against exceeding temperatures:

More information

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration.

More information

Danfoss scroll for refrigeration LLZ013 to low temperature

Danfoss scroll for refrigeration LLZ013 to low temperature MAKING MODERN LIVING POSSIBLE Application guidelines Danfoss scroll for refrigeration LLZ013 to 033 - low temperature 50-60 Hz - R404A - R507 http://cc.danfoss.com Contents Features...4 Scroll compression

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

Performance of an Improved Household Refrigerator/Freezer

Performance of an Improved Household Refrigerator/Freezer Performance of an Improved Household Refrigerator/Freezer D. O. Ariyo Department of Mechanical Engineering, School of Engineering, Federal Polytechnic, Offa, Nigeria Y. L. Shuaib-Babata Department of Mechanical

More information

MAKING MODERN LIVING POSSIBLE. MLZ / MLM Refrigeration scroll compressors Hz - R404A - R507 - R134a - R22. Selection & application guidelines

MAKING MODERN LIVING POSSIBLE. MLZ / MLM Refrigeration scroll compressors Hz - R404A - R507 - R134a - R22. Selection & application guidelines MAKING MODERN LIVING POSSIBLE MLZ / MLM Refrigeration scroll compressors 50-60 Hz - R404A - R507 - R134a - R22 Selection & application guidelines Contents Features... 4 Scroll compression principle...

More information

13-1. Temperature Regulator

13-1. Temperature Regulator -1 Step 0 Type/Structure/Features Please refer to this for type, structure and features of. Step 1 Selection Please look at the ID chart to choose the right products depending on the intended uses. Details

More information

Energy Use in Refrigeration Systems

Energy Use in Refrigeration Systems 2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is

More information

Operating instructions Open two-stage compressor FZ 16

Operating instructions Open two-stage compressor FZ 16 Page 1 Operating instructions Type: FZ 16 / 2051- R 22 FZX 16 / 2051- R 404 A FZX 16 / 2051- R 410 A Page 2 Contents Page 1. Safety instructions...3 2....3 3. Brief description...3 4. Main and function

More information

REFRIGERATION PRODUCTS

REFRIGERATION PRODUCTS SE REFRIGERATION PRODUCTS Smart Electric products offer reliable and longer lasting solutions for refrigeration. We know how important it is to keep systems clean and running at its full efficiency for

More information

HVAC Service Technicians Training Center

HVAC Service Technicians Training Center HVAC Service Technicians Training Center 48-03 32 nd Place, Long Island City, NY 11101 Tel: (718) 472-0404 (718) 472-0414 Fax: (718) 433-0676 Introduction to the Refrigeration Cycle: Part 1 (AC/R-1) This

More information