1 Chapter 14 Special Requirements For Health Care Facilities 14.1 GENERAL This Chapter applies to special fixtures and systems that occur in health care facilities and to the special plumbing requirements in such facilities. Ordinary plumbing in such facilities shall comply with the other applicable Chapters of this Code WATER SERVICE Where required by the Authority Having Jurisdiction, hospitals and similar health care facilities shall have dual water service lines to maintain a water supply in the event of a water main failure. Where possible, the service pipelines shall be connected to different water mains so that a single water main break can be isolated and repaired without shutting off all water service to the facility MEDICAL GAS AND VACUUM PIPING SYSTEMS General The installation of medical gas and vacuum piping systems shall be in accordance with the requirements of either NFPA 99 - Standard for Health Care Facilities or NFPA 99C - Gas and Vacuum Systems Professional Qualifications of Installers, Inspectors and Verifiers Installers (including brazers), inspectors, and verifiers of medical gas and vacuum systems shall meet the requirements of ANSI/ASSE Series Professional Qualification Standard for Medical Gas Systems Installers, Inspectors, and Verifiers, or the equivalent PROTRUSIONS FROM WALLS Drinking fountains, control valves, medical gas station outlets, vacuum inlet stations, risers, cleanout covers, and other devices shall be fully-recessed in corridors and other areas where patients may be transported on a gurney, hospital bed, or wheelchair. Protective guards shall be provided where necessary MENTAL PATIENT ROOMS Piping and drain traps in mental patient rooms shall be concealed. Fixtures and fittings shall be vandal-proof PROHIBITED LOCATIONS FOR ICE STORAGE Ice makers or ice storage chests shall not be located in a Soiled Utility Room or similar areas where subject to possible contamination National Standard Plumbing Code 181
2 14.7 CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION a. Backflow prevention shall be in accordance with Section b. Vacuum breakers for bedpan washers shall be not less than 5 feet above the floor CLINICAL SINKS AND BEDPAN WASHERS General a. Clinical sinks and bedpan washers, and flushing-rim service sinks shall be installed in the same manner as water closets. Where such fixtures have a vent connection on the inlet side of their trap, a local vent shall be provided in accordance with Section b. Clinical sinks shall not be used as a substitute for non-flushing service sinks, nor shall a non-flushing service sink be utilized to clean bedpans. c. Vacuum breakers for bedpan washers shall be installed in accordance with Section 14.7.b LOCAL VENTS AND STACKS FOR CLINICAL SINKS OR BEDPAN WASHERS General Where clinical sinks or bedpan washers have provisions for a local vent, a local vent shall be extended to the outdoors above the roof. Local vents shall terminate in accordance with Section Local vents from clinical sinks or bedpan washers shall not be connected to vapor vents for sterilizers or to any drainage system vent Material Local vent piping shall be of a material acceptable for sanitary vents in accordance with Section Required Size and Arrangement A local vent serving a single clinical sink or bedpan washer shall be not less than 2" pipe size. Where such fixtures are installed back-to-back or are located above each other on more than one floor, a local vent stack may be provided to serve multiple fixtures. A 2" local vent stack may serve up to three fixtures. A 3" local vent stack may serve up to six fixtures. A 4" local vent stack may serve up to twelve fixtures. In multiple installations, the connections to the local vent stack shall be made using sanitary tee or tee-wye fittings oriented for upward flow from the branch. A branch connection to a local vent stack shall extend not more than 5 feet horizontally and shall be sloped not less than 1/4 inch per foot back towards the fixture served Provisions for Drainage Provisions shall be made for the drainage of vapor condensation within local vent piping. A local vent serving a single fixture may drain back to the fixture served. The base of a local vent stack serving one or more fixtures shall be directly connected to a trapped and vented waste branch of the sanitary drainage system. The trap and waste branch shall be the same size as the local vent stack. The trap seal depth shall be not less than 3 inches. The vent for the waste branch shall be 1-1/4" minimum size, but not less than one-half the size of the waste branch Trap Priming The waste trap required under Section shall be primed by at least one clinical sink or bedpan washer on each floor served by the local vent stack. A priming line not less than 1/4" OD size shall be extended from National Standard Plumbing Code
3 the discharge or fixture-side of the vacuum breaker protecting the fixture water supply to the local vent stack. A trap having not less than a 3-inch water seal shall be provided in the priming line. The line shall prime the trap at the base of the local vent stack each time that a fixture is flushed STERILIZERS General The requirements of this Section apply to sterilizers and bedpan steamers. Such equipment shall be installed in accordance with this Code and the manufacturer s instructions Indirect Waste Connections All waste drainage from sterilizers and bedpan steamers shall be indirectly connected to the sanitary drainage system through an air gap, in accordance with Chapter 9. Indirect waste pipes shall be not less than the size of the drain connection on the fixture. Separate waste pipes shall be provided for each fixture, except that up to three sterilizers may have a common indirect waste pipe if its developed length does not exceed 8 feet. The size of such common indirect waste pipes shall be not less than the aggregate cross-sectional area of the individual sterilizer drain connections. Except for bedpan steamers, indirect waste pipes shall not require traps Floor Drains a. A trapped and vented floor drain, not less than 3" pipe size, shall be provided in each recess room or space where recessed or concealed portions of sterilizers are located. The floor drain shall drain the entire floor area and shall receive the indirect waste from at least one sterilizer. Where an air gap fitting is provided, the waste pipe from the fitting may connect to the body of the floor drain above its trap seal. b. Where required by the sterilizer manufacturer, a floor drain shall be located directly beneath the sterilizer within the area of its base Cooling Required Waste drainage from condensers or steam traps shall be cooled below 140 F before being discharged indirectly to the sanitary drainage system Traps Required for Bedpan Steamers A trap having a minimum seal of 3 inches shall be provided in the indirect waste pipe for a bedpan steamer, located between the fixture and the air gap at the indirect waste receptor VAPOR VENTS AND STACKS FOR STERILIZERS General Where sterilizers have provisions for a vapor vent and such a vent is required by their manufacturer, a vapor vent shall be extended to the outdoors above the roof. Sterilizer vapor vents shall terminate in accordance with Section 12.4 and shall not be connected to local vents for clinical sinks or bedpan washers or to any drainage system vent Material Sterilizer vapor vent piping shall be of a material acceptable for sanitary vents in accordance with Section National Standard Plumbing Code 183
4 Required Size and Arrangement a. Sterilizer vapor vents and stacks for individual sterilizers shall be not less than the size of the sterilizer vent connection, except that stacks shall be not less than 1-1/2" pipe size. Where vapor vent stacks serve more than one sterilizer, the cross-sectional area of the stack shall be not less than the aggregate cross-sectional areas of the vapor vents for all of the sterilizers served. b. In single and multiple installations, the connections to the vapor vent stack shall be made using sanitary tee or tee-wye fittings oriented for upward flow from the branch. A branch connection to a sterilizer vapor vent stack shall extend not more than 5 feet horizontally and shall be sloped not less than 1/4 inch per foot away from the sterilizer and toward the vent stack Provisions for Drainage Provisions shall be made for the drainage of vapor condensation within sterilizer vapor vent piping. The base of stacks shall drain indirectly through an air gap to a trapped and vented waste receptor connected to the sanitary drainage system DRAINAGE FROM CENTRAL VACUUM SYSTEMS General Provisions for drainage from medical, surgical, dental, and similar central vacuum systems shall be as required by either NFPA 99 - Health Care Facilities or NFPA 99C - Gas and Vacuum Systems. In addition, drainage from dental and other vacuum systems that collect fluid waste centrally shall comply with Sections through Positive Pressure Drainage from Air/Waste Separators in Dental Vacuum Systems a. The waste outlet from an air/waste separator on the discharge side of a vacuum pump or blower shall be direct-connected to the sanitary drainage system through a deep-seal trap that is conventionally vented within the plumbing system. The trap vent shall extend vertically to not less than 6 inches above the top of the separator before making any horizontal turns. The vacuum exhaust air flow from the separator shall be separately vented to outodoors as required under NFPA 99 and NFPA 99C. b. The trap and drain branch size shall be at least two pipe sizes larger than the waste pipe from the separator, but not less than 1-1/2" pipe size. The vent shall be the full size of the trap and drain. The trap seal shall be at least two times the exhaust backpressure in the separator, but not less than 4 inches deep Gravity Drainage from Waste Holding Tanks in Dental Vacuum Systems a. The drainage from waste holding tanks shall extend from the vacuum check valve on the waste outlet of the tank and be direct-connected to the sanitary drainage system through a deep-seal trap that is conventionally vented within the plumbing system. In addition, a vent shall be installed between the vacuum check valve and the drain trap, on the inlet side of the trap, to seal the check valve when the holding tank is operating under vacuum and collecting waste. This vent shall be connected to the plumbing system vents. Both vents shall extend vertically to not less than 6 inches above the top of the holding tank before making any horizontal turns. b. The trap and drain size shall be at least two pipe sizes larger than the waste outlet and vacuum check valve, but not less than 2" pipe size. The trap shall be not less than 4 inches deep. The vent for the vacuum check valve shall be not less than the size of the check valve. The trap vent shall be not less than one-half the size of the trap and drain branch National Standard Plumbing Code
5 Protection from Sewage Backup in Dental Vacuum Systems A floor drain or other trapped and vented receptor shall be provided near the connection of the drain from a dental vacuum air/waste separator or waste holding tank to the sanitary drainage system that will overflow in the event of a backup in the sanitary drainage system and prevent the backup from reaching the level of the trap for the air /waste separator or the drain check valve for the waste holding tank. The trap of the floor drain or receptor shall be primed if it does not receive an indirect waste discharge ASPIRATORS Provisions for aspirators or other water-supplied suction devices shall be installed only with the specific approval of the Authority Having Jurisdiction. Where aspirators are used for removing body fluids, they shall include a collection bottle or similar fluid trap. Aspirators shall indirectly discharge to the sanitary drainage system through an air gap, in accordance with Chapter 9. The potable water supply to an aspirator shall be protected by a vacuum breaker or equivalent, in accordance with Sections 14.7 and National Standard Plumbing Code 185
Special Requirements For Health Care Facilities
Chapter 14 Special Requirements For Health Care Facilities 14.1 GENERAL This Chapter applies to special fixtures and systems that occur in health care facilities and to the special plumbing requirements
More informationRead Only Document Not For Distribution
Chapter 9 Indirect Waste Piping and Special Wastes 9.1 INDIRECT WASTES 9.1.1 General Drains from fixtures, fixture compartments, equipment, appliances, appurtenances, and other devices requiring protection
More informationAPPENDIX L ALTERNATE PLUMBING SYSTEMS
ALTERNATE PLUMBING SYSTEMS L 1.0 General. L 1.1 Applicability. The intent of this appendix is to provide clarification of procedures for the design and approval of engineered plumbing systems, alternate
More informationINSPECTION OF COMMERCIAL KITCHEN PLUMBING
INSPECTION OF COMMERCIAL KITCHEN PLUMBING 801.1 SCOPE Food-handling establishments 2 - by John Williams, Jr. Plumbing Control Supervisor Onondaga County Water Environment Protection Commercial Kitchens
More information2016 Plumbing Supplemental Plan Review List
Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Plumbing Supplemental Plan Review List POTABLE WATER SYSTEM P1. Specify which fixtures are for private use and which are for
More informationRead Only Document Not For Distribution
Chapter 5 Traps, Cleanouts and Backwater Valves 5.1 SEPARATE TRAPS FOR EACH FIXTURE a. Plumbing fixtures shall be separately trapped by a water seal trap placed as close as possible to the fixture outlet.
More informationSCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING
SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm
More information2015 UPC Chapter 8 Indirect Wastes RV
PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.
More informationSanitary Drainage Systems
11.1 MATERIALS See Section 3.1. Sanitary Drainage Systems 11.2 BUILDING SEWERS AND BUILDING DRAINS 11.2.1 Sewer or Drain in Filled Ground Chapter 11 Building sewers or building drains that are installed
More informationICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.
ICP Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A 1 inch diameter faucet, where the inside edge of the spout opening is 2.5 inches away
More informationCONTINUING EDUCATION UPC Definitions Code Course. 4 hours Course # ID09143 (CODE) PO Box Spokane, WA
AMERICAN PLUMBING INSTITUTE 2015 33 CONTINUING EDUCATION PO Box 31131 Spokane, WA 99223-3018 www.apiceu.com 2009 UPC Definitions Code Course 4 hours Course # ID09143 (CODE) DISCLAIMER NOTE: This course
More informationDefinitions UPC Code - Chapter 2 Definitions A-I
2015 UPC Code - Chapter 2 Definitions A-I Definitions 201.1 Applicability. For the purpose of this code, the following terms have the meanings indicated in this chapter. 202.0 Definition of Terms. 202.1
More information2015 UPC CODE - CHAPTER 8 INDIRECT WASTES
801.0 General. 2015 UPC CODE - CHAPTER 8 INDIRECT WASTES 801.1 Applicability. This chapter shall govern the materials, design, and installation of indirect waste piping, receptors, and connections; and
More informationc. Direct or indirect?
~ \ 1.) GENERAL a. Definitions: Chapter B Code References (1) Air-break Comm 81.01 (5) (2) Air-gap, drain system Comm 81.01 (6) (3) Flood level rim Comm 81.01(102) (4) sink Comm 81.01(105) (5) Indirect
More informationDEFINITIONS CHAPTER 2
CHAPTER 2 DEFINITIONS SECTION 201 GENERAL 201.1 Scope. Unless otherwise expressly stated, the following words and terms shall, for the purposes of this code, have the meanings shown in this chapter. 201.2
More informationDEFINITIONS CHAPTER 2
CHAPTER 2 DEFINITIONS SECTION PC 201 GENERAL 201.1 Scope. Unless otherwise expressly stated, the following words and terms shall, for the purposes of this code, have the meanings shown in this chapter.
More informationSummary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016
Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Ohio Administrative Code Rule Number OPC Section IPC origin Reason for proposed 4101:3-2-01 Alternate on-site 2015 Added definition
More informationPLUMBING REQUIREMENTS
PLUMBING REQUIREMENTS This handout is a compilation of the standard requirements based on the State Plumbing Code and City Ordinance for projects of this type. This information sheet does not contain all
More informationCRAFTSMAN EXAMINATION, JUNE 2007 PLUMBING ANSWER SCHEDULE
No. 9195 CRAFTSMAN EXAMINATION, JUNE 2007 PLUMBING ANSWER SCHEDULE Plumbers, Gasfitters and Drainlayers Board, 2007. All rights reserved. No part of this publication may be reproduced by any means without
More informationBACKFLOW PREVENTION GUIDE FOR COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL DEVELOPMENTS
AG AVB PVB DCVA PA 1 Abattoir (slaughter house) 2 Air compressor oil cooler 3 Agricultural chemicals (sprayers 4 Animal watering 5 Apartment building (within the scope of Part 3 of the Ontario Building
More informationPlumbing. Definitions. Background Factors. Air Chambers. Air Gap (Drainage System) Air Gap (Water Distribution System) Air Lock.
Plumbing Plumbing may be defined as practice, materials, and fixtures used in the installation, maintenance, and alteration of all piping, fixtures, appliances, and appurtenances in connection with sanitary
More informationDEFINITIONS CHAPTER 2
CHAPTER 2 DEFINITIONS SECTION 201 GENERAL 201.1 Scope. Unless otherwise expressly stated, the following words and terms shall, for the purposes of this code, have the meanings shown in this chapter. 201.2
More informationMATERIALS Traps TRAPS. No. IPC IRC Description
MATERIALS Traps TRAPS MAX " MAX 0" No. IPC IRC Description 00. P0.6 00. P0.6 00. P0. 00. () P0.6 Exc. Vertical distance from fixture to the trap weir can not exceed ". Horizontal distance from the fixture
More informationTABLE OF CONTENTS. CHAPTER 2 DEFINITIONS General Applicability Definition of Terms General...
TABLE OF CONTENTS CHAPTER 1 ADMINISTRATION..............1 101.0 General.......................1 101.1 Title..........................1 101.2 Scope........................1 101.3 Purpose......................1
More informationSTACKS AND STACK VENTS
CHAPTER 9 VENTS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of vent systems. 901.2 Trap seal protection. The plumbing
More informationTABLE OF CONTENTS Limitations of Authority...6 Table Plumbing Permit Fees...7
TABLE OF CONTENTS CHAPTER 1 ADMINISTRATION.............1 101.0 General.......................1 101.1 Title..........................1 101.2 Scope........................1 101.3 Purpose......................1
More informationPLUMBING INSTALLATIONS
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT PLUMBING INSTALLATIONS A homeowner guide to plumbing requirements for single-family dwellings November 2017 contents Permit Requirements... 3 Inspection Requirements...
More informationRead Only Copy Not For Distribution. Chapter 10. Water Supply and Distribution 10.1 QUALITY OF WATER SUPPLY 10.2 RESERVED 10.
Water Supply and Distribution 10.1 QUALITY OF WATER SUPPLY a. Only potable water shall be supplied to plumbing fixtures used for drinking, bathing, culinary use or the processing of food, medical or pharmaceutical
More informationMethods of Venting Plumbing Fixtures and Traps in the 2018 IPC
People Helping People Build a Safer World Methods of Venting Plumbing Fixtures and Traps in the 2018 IPC Installation, Flexibility and Opportunity for Savings Lee Clifton, Senior Director of PMG Resources,
More informationCHAPTER 9 VENTS SECTION
CHAPTER 9 VENTS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of vent systems. 901.2 Trap seal protection. The plumbing
More informationPRE-INSTALLATION GUIDE
Dry Vacuum System Part Numbers V3, V5, V7, 2V3, 2V3CT, 2V5, 2V5CT, 2V7, 3V5 and 4V5 PRE-INSTALLATION GUIDE All pumps comply with NFPA 99C level 3 requirements. All installations must conform to local codes.
More informationDESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES
2.05 PLUMBING GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.05 It is expected that the plumbing design professional will conform to accepted good engineering design practices.
More informationTABLE OF CONTENTS. CHAPTER 2 DEFINITIONS General Applicability Definition of Terms General...
TABLE OF CONTENTS CHAPTER 1 ADMINISTRATION................1 101.0 Title, Scope, and General...........1 101.1 Title............................1 101.2 Purpose.........................1 101.3 Plans Required...................1
More information1 Exam Prep Plumber s Handbook Tabs and Highlights
1 Exam Prep Plumber s Handbook Tabs and Highlights These 1 Exam Prep Tabs are based on the Plumber s Handbook Revised 2006. Each Tabs sheet has five rows of tabs. Start with the first tab at the first
More informationIPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.
IPC Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A vent stack handling 25 dfu s with a developed length of 35 feet shall be inches minimum
More informationPRE-INSTALLATION GUIDE
DENTAL VACUUM SYSTEMS PRE-INSTALLATION GUIDE for MODELS VS20 & VS40 Check VacStar Model Being Installed: VS20 VS40 Model VS20 Model VS40 Doctor: Address: Phone#: Dealer: Dealer Address: PRODUCT SPECIFICATIONS
More informationAPPENDIX J ILLUSTRATIONS
The following figures have been included in the 1994 edition of the Standard Plumbing Code to aid in interpreting this code. The figures are not to be construed as superseding the written text, but merely
More informationThe following test is Continuing Education for: Master Plumbers, Journeyman Plumbers, UDC Plumbing Inspectors, and Commercial Plumbing Inspectors.
The following test is Continuing Education for: Master Plumbers, Journeyman Plumbers, UDC Plumbing Inspectors, and Commercial Plumbing Inspectors. You can complete the test by printing a hard copy, or
More informationCHAPTER 31. VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R
CHAPTER 31 VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R This page left intentionally blank. 426R 2003 INTERNATIONAL RESIDENTIAL CODE For SI: PIPE SIZE (inches) TABLE P3107.3 COMMON VENT SIZES
More informationPLUMBING FIXTURES Reserved
CHAPTER 27 PLUMBING FIXTURES Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 395R This page left intentionally blank. 396R 2003 INTERNATIONAL RESIDENTIAL CODE SECTION P2708 SHOWERS P2708.1 General. Shower
More informationPipe Sizing Table. Hydraulic Load Served (fixture units)
MODULE 1 INTRODUCTION Notes: A Pipe Type Horizontal branch Pipe Sizing Table Hydraulic Load Served (fixture units) Size (in.) Code Reference 2 + 1.5 = 3.5 2 7.4.9.1.(1) B Soil stack 13.5 + 13.5 = 27 3
More informationMechanical Inspection Plumbing
0811 Fixtures Sinks, drinking fountains, water closets, showers, etc. Classroom Sinks. Classroom sinks (19) are enameled cast iron self rimming side ledge with gooseneck faucet trim with index handles,
More information2006 INTERNATIONAL PLUMBING CODES HANDBOOK
2006 INTERNATIONAL PLUMBING CODES HANDBOOK 2006 INTERNATIONAL PLUMBING CODES HANDBOOK R. Dodge Woodson McGraw-Hill New York Chicago San Francisco Lisbon London Madrid Mexico City Milan New Delhi San Juan
More informationCHAPTER 10 TRAPS AND INTERCEPTORS
CHAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved
More informationMatrix of changes for the National Standard Plumbing Code July 2013
Matrix of changes for the National Standard Plumbing Code July 2013 Item # Section Number Person Submitting Change Committee Action 10-77 10.20.8 and Table 3.1.3 XI Certification 10-82 12.16 Size and Lengths
More informationSystem Name. Customer Awareness- Cross Connections and Backflow Prevention
System Name Customer wareness- Cross Connections and ackflow Prevention In our industrial world, many things present a potential source of pollution to our drinking water. Pesticides and herbicides that
More informationDenotes a new question! Denotes a revised/revisited question. September 2009 General:
General: 1) (Q) What does a contractor/permit holder have to supply for an inspection? (A) Section 107.2 of the NC Administrative Code states that it is the duty of the permit holder to provide access
More information1 Exam Prep Plumbing State Contractors Practice Exam 2
1 Exam Prep Plumbing State Contractors Practice Exam 2 1 According to Chapter 64E-6, when sizing a grease interceptor used in a restaurant, the correct formula is. A. (S) x (EW 12) x (LF) B. (S) x (GS)
More informationPENNSYLVANIA. Downloaded
Housekeeping/Laundry/Maintenance 205.26. Laundry. PENNSYLVANIA Downloaded 01.15.11 (a) A laundry room shall be provided in a facility where commercial laundry service is not used for the washing of soiled
More informationPLUMBING FIXTURES CHAPTER 27
CHAPTER 27 PLUMBING FIXTURES SECTION P2701 FIXTURES, FAUCETS AND FIXTURE FITTINGS P2701.1 Quality of fixtures. Plumbing fixtures, faucets and fixture fittings shall be constructed of approved materials,
More informationCHAPTER 10 TRAPS AND INTERCEPTORS TABLE 10-1 HORIZONTAL LENGTHS OF TRAP ARMS (EXCEPT FOR WATER CLOSETS AND SIMILAR FIXTURES) 1, 2
CHAPTER 10 TRAPS AND INTERCEPTORS < 1001.0 Traps Required. Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.1, shall be separately trapped by an approved type
More informationLand Use and Environmental Service Agency (Code Enforcement) Plumbing 2010
General: 1) (Q) Who enforces the cutting and notching requirements found in the plumbing code? (A) The plumbing inspector would question the contractor initially. A building inspector would either take
More informationIs Sewer Gas Giving Your Customers the Wrong Impression?
Is Sewer Gas Giving Your Customers the Wrong Impression? Prepared by Dialectic INTRODUCTION We ve all been there. You walk into a public restroom and you immediately wonder if one of the toilets is overflowing.
More informationDrain and Vent Systems 6 CE Hours
Drain and Vent Systems 6 CE Hours Wisconsin Contractors Institute N27 W23953 Paul Road, Suite 203 Pewaukee, WI 53072 www.wicontractorsinstitute.com 262-409-4282 What is the purpose of this course? The
More informationFood Service Plan Review Information
Food Service Plan Review Information New or remodeled food preparation facilities, and those changing ownership, must undergo a plan review process prior to a health permit being issued. The purpose of
More informationPRE-INSTALLATION GUIDE
Dry Vacuum System Part Numbers V15, 2V15, 3V15 and 4V15 PRE-INSTALLATION GUIDE All pumps comply with NFPA 99C level 3 reuirements. All installations must conform to local codes. System being installed:
More informationMINIMUM CONSTRUCTION STANDARDS AND SPECIFICATIONS CHECKLIST
Rev: 10/23/08 MINIMUM CONSTRUCTION STANDARDS AND SPECIFICATIONS CHECKLIST The following standards apply to constructing, renovating or converting buildings to use for preparing, processing, storing or
More informationNew Food Service Plan Review Checklist
New Food Service Plan Review Checklist The following items should be completed before you return your application. Read Starting a Food Service Brochure to help you in the process. Confirm whether property
More informationDansereau Dental. P r e - C o n s t r u c t i o n G u i d e
P r e - C o n s t r u c t i o n G u i d e 2 0 1 4 A m e r i c a s D e n t a l E q u i p m e n t C o m p a n y Dansereau Dental (800) 423-5657 / WWW.DHPDENTAL.COM M a n u fa c t u r e d i n U S A f o r
More informationProVent Systems Plumbing Fundamentals. Educational Literature. Comparison of ProVent Design Rules and The International Plumbing Code
ProVent Systems Plumbing Fundamentals Educational Literature Comparison of ProVent Design Rules and The International Plumbing Code Guide to Contents Topics and Descriptions Page Interior views of the
More informationLOCAL AMENDMENTS TO THE UNIFORM PLUMBING CODE 2006 EDITION
CHAPTER 23.25 LOCAL AMENDMENTS TO THE UNIFORM PLUMBING CODE 2006 EDITION Sections 23.25.100 Local amendments to the Uniform Plumbing Code, 2006 Edition2 23.25.102-103 Delete... 2 23.25. 204.0 "B" definitions...
More informationCHAPTER VI BUILDING PLUMBING
CHAPTER VI BUILDING PLUMBING 6.1. INTRODUCTION The chapter covers questions related to water demand, distribution and drainage. The basic principles for planning and installing common plumbing systems
More informationNORTH CAROLINA. Downloaded (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided:
Housekeeping/Laundry/Maintenance NORTH CAROLINA Downloaded 01.15.11 (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided: (3) a soiled utility room with counter,
More informationCONNECTICUT. Downloaded
Housekeeping/Laundry/Maintenance J. Laundry. CONNECTICUT Downloaded 01.15.11 (1) This service, if provided, shall be used exclusively for laundry and shall be remote from resident and food service areas,
More informationplumbing for greywater
plumbing for greywater october 2015 christina bertea ~union trained journeywoman plumber (1978) ~plumbing contractor (1996) ~greywater action singingwater@jps.net plumbing for greywater basic parts of
More informationThe following test is Continuing Education for: Master Plumbers, Journeyman Plumbers, UDC Plumbing Inspectors, and Commercial Plumbing Inspectors.
The following test is Continuing Education for: Master Plumbers, Journeyman Plumbers, UDC Plumbing Inspectors, and Commercial Plumbing Inspectors. You can complete the test by printing a hard copy, or
More informationPRE-INSTALLATION GUIDE
DENTAL VACUUM SYSTEMS PRE-INSTALLATION GUIDE for MODELS VS50, VS50H, VS80 & VS80H Model VS50 Model VS50H Model VS80 Model VS80H This VacStar Model is being installed: (AS CHECKED) VS50 VS80 VS50H VS80H
More informationChapter 4: Fixtures, Faucets & Fittings:
Table of Contents Chapter 1 Administration 0 Chapter 2 Definitions 0 Chapter 3 General Regulations 0 Chapter 4 Fixtures, Fau & Fit. 12 Chapter 5 Water Heaters 14 Chapter 6 Water Supply & Dist. 10 Chapter
More informationA GUIDE TO PASSING THE PLUMBING EXAM
A GUIDE TO PASSING THE PLUMBING EXAM BASED ON THE INTERNATIONAL PLUMBING AND FUEL GAS CODES WRITTEN BY JOHN WHITE REVISED 2014 2007-2014 This manual is the sole property of Energy Marketing Services. No
More informationFrequently Asked Questions
Frequently Asked Questions 1. What is back-siphonage? Back-siphonage is the reversal of normal flow in a system caused by a negative pressure (vacuum or partial vacuum) in the supply piping. 2. What factors
More informationGIANT. Little. Guidelines for Sizing. Pump Company. Sewage Pumps & Systems. Sewage Pumps & Systems
Sewage Pumps & Systems GIANT Little Pump Company Guidelines for Sizing Sewage Pumps & Systems These guidelines cover the steps that need to be taken to accurately select the correct sewage pump and applicable
More informationCHAPTER 5 Water, Plumbing, and Waste
CHAPTER 5 Water, Plumbing, and Waste Parts 5-1 Water 5-2 Plumbing System 5-3 Mobile Water Tank 5-4 Sewage, Other Liquid Waste, and Rainwater 5-5 Refuse, Recyclables, and Returnables 5-1 Water 5-101 Source
More informationFIXTURES, FAUCETS AND FIXTURE FITTINGS
CHAPTER 4 FIXTURES, FAUCETS AND FIXTURE FITTINGS SECTION 401 GENERAL 401.1 Scope. This chapter shall govern the materials, design and installation of plumbing fixtures, faucets and fixture fittings in
More informationCHAPTER 10 TRAPS AND INTERCEPTORS The vent pipe opening from a soil or waste No more than one (1) approved slip joint
CHAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved
More informationBuilding Utilities 1 Plumbing and Sanitary Systems
Building Utilities 1 Plumbing and Sanitary Systems Taken from UST Architecture exams by Arch. Rafael Alli Recommended review material for UST Preboard Exam Prepared by: arkireviewph.multiply.com Types
More informationCHAPTER 9 VENTS. run undiminished in size and as directly as possible from the building drain through to the open air above the roof.
CHAPTER 9 VENTS SECTION 90 GENERAL run undiminished in size and as directly as possible from the building drain through to the open air above the roof. 90. Scope. The provisions of this chapter shall govern
More informationWastewater. Guidelines for Sizing mscdirect.com. Call MSC today to learn about the latest LittleGiant products.
Wastewater Guidelines for Sizing Features These guidelines cover the steps which need to be taken to accurately select the correct sewage pump and applicable systems to use in sewage ejectors. Work through
More informationTable B.1 Guide to degree of hazard - Point of use cross-connections (See Clauses and B.2.)
HAZARD TYPE LIST Canadian Standards Association Selection and installation of backflow preventers Table B.1 Guide to degree of hazard - Point of use cross-connections (See Clauses 5.4.1 and B.2.) Agricultural
More informationCHAPTER 2 DEFINITIONS. Back-Siphonage The flowing back of used, Backwater Valve A device installed in a drainage. bathtub.
CHAPTER 2 DEFINITIONS 201.0 General. For the purpose of this code, the following terms have the meanings indicated in this chapter. No attempt is made to define ordinary words which are used in accordance
More informationIntroduction to Supermarket Vacuum Condensate Drainage Systems by AcornVac, Inc.
What is Vacuum Drainage? Vacuum Condensate Drainage Systems are simply a viable alternative to underground piping that uses the combined energies of vacuum pressure and gravity for the collection and disposal
More informationCHAPTER 2 DEFINITIONS
CHAPTER 2 DEFINITIONS 201 GENERAL 201.1 Scope For the purpose of this code, certain abbreviations, terms, phrases, words and their derivatives shall be construed as set forth in this chapter or the chapter
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 22 40 00 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Faucets for lavatories, bathtubs, bathtub/showers, showers and sinks. 2. Flushometers. 3. Toilet
More information2009 IPC ,IMC Q &A ANDIFGC
2009 IPC,IMC ANDIFGC Q &A TABLE OF CONTENTS PREFACE.... ix ABOUT THE INTERNATIONAL CODE COUNCIL...x IPC CHAPTER 1 SCOPE AND ADMINISTRATION...1 Section 101 General... 1 Section 102 Applicability... 1 Section
More informationMASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following sanitary drainage piping specialties:
SECTION 221319 - SANITARY WASTE PIPING SPECIALTIES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following sanitary drainage piping specialties: 1. Backwater valves. 2. Cleanouts. 3. Floor
More informationPLUMBING DESIGN GUIDELINES SECTION DESIGN GUIDELINES DUVAL COUNTY PUBLIC SCHOOLS
The Design Guidelines, which follow, are intended to supplement the Educational Specifications and State Requirements for Educational Facilities (SREF). Note: All fittings shall be installed by no less
More informationFOOD ESTABLISHMENT CONSTRUCTION GUIDE Revised December 19, 2011 Reviewed January 10, 2014
FOOD ESTABLISHMENT CONSTRUCTION GUIDE Revised December 19, 2011 Reviewed January 10, 2014 This construction guide is to be used in conjunction with the Oklahoma Food Service Establishment Regulations (OAC
More informationSECTION MORTUARY EQUIPMENT
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 00 MORTUARY EQUIPMENT SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section that are
More informationCHaPTeR 10. TRaPS and INTeRCePTORS. Table 10-1 Horizontal lengths of Trap arms (except for water closets and similar fixtures)*
CHaPTeR 10 TRaPS and INTeRCePTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved
More informationEffingham County Health Department "Where Prevention Begins" 901 West Virginia Phone (217) Effingham, Illinois Fax (217)
Effingham County Health Department "Where Prevention Begins" 901 West Virginia Phone (217) 342-9237 Effingham, Illinois 62401 Fax (217) 342-9324 Opening a Food Establishment in Effingham County Guidelines
More informationCHAPTER 10 TRAPS AND INTERCEPTORS
CAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved
More informationSTUDENT NOTES Plan, size and layout sanitary pipe work and fixtures
4. SANITARY PLUMBING FULLY VENTED SYSTEM On completion of this module, the student should be able to: Design, install and develop bills of quantities for a fully vented modified system for commercial and
More informationA. This Section includes the following emergency plumbing fixtures:
Page 224500-1 SECTION 224500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationLevel I Chapter 1 Worksheet
Chapter 1 Worksheet 1. For applicability requirements of the Plumbing Code, refer to: a. Building Code b. Administration and Enforcement Code c. Plumbing Code d. Residential Code 2. The provisions of the
More informationPLAN REVIEW SUBMITTAL GUIDE
PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide
More information2018 International Fire Code. Add new text as follows:
CCC-F-1-18 IFC: 311.2.2, 403.11.1.2, 1010.3.2; IBC: 424.3, 428.3.9, 506.2.2.1, 506.2.4.1, 1705.12.6, 2603.3, 3104.5.3, 2606.7.4; IRC: R101.2, R302.2.2, R313, R313.1, R313.1.1, R313.2, R313.2.1, R325.3,
More informationDESIGN STANDARDS SECTION PLUMBING FIXTURES AND EQUIPMENT. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.
PART 1 - GENERAL 1.1 Toilet rooms and utility rooms to have floor drains at lowest point. 1.2 Utilize Exposed Flushometers. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.
More informationPro Vent TM. Provent Systems Inc Capital Circle Lawrenceville Georgia
Pro Vent TM Guide to Design and Usage Provent Single System Handling Installation Corrosion Ease Simplicity Resistance IPMO Copyright (c) 2014, Pro Vent Systems Inc., plus *2016 Revisions ll Rights Reserved
More informationInstall Configurations
Table of Contents EQUIPMENT SPECS: 1 WATER SUPPLY CONFIGURATIONS 2 OPTION 1 (OPTIMIZED): BRING WATER TO MACHINES 2 OPTION 2 (ENHANCED): INSTALLING A DEDICATED WATER SOURCE 3 OPTION 3 (ENHANCED CONT.):
More informationIPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.
IPC Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. The minimum air gap for a fixture with an effective open of 1/2", located away from a
More informationStructural Guidelines. Food Service Establishments. Retail Food Stores
Structural Guidelines for Food Service Establishments and Retail Food Stores Jefferson County Department of Health Food & Lodging Protection Division 1 Before construction or remodeling of a food service
More information