Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

Size: px
Start display at page:

Download "Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier"

Transcription

1 Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier Rohit R. Parab Mechanical Engineering Department Vishwakarma Institute of Technology, Pune, India Laxmikant D. Mangate Mechanical Engineering Department Vishwakarma Institute of Technology, Pune, India ABSTRACT A Heat Pipe is a simple device which is used to transfer heat from one location to another, using evaporation condensation cycle. It combines the principles of both thermal conductivity and phase transition to efficiently manage the transfer of heat between two interfaces. Heat pipe are used in number of applications ranging from electronics equipment cooling to HVAC. In current project performance characteristics of heat pipe as dehumidifier are experimentally investigated. A heat pipe dehumidifier is designed and tested at various inlet conditions of temperature and relative humidity. The energy-saving ratio with the heat pipe dehumidifier ranges from 6.4 % to 14.4 % according to the performance testing. Also effect of change in ADP (Apparatus Dew point ) also studied.the dehumidification capacity and the cooling coil power increases, but the energy saving ratio is reduced with the increase of air relative humidity, dry bulb temperature and air quantity. Keywords Heat Pipe, AHU, Dehumidifier, Energy consumption NOMENCLATURE Cp Specific heat h Enthalpy h fg Latent heat of vaporization Q Heat transfer rate Q L Latent heat Q S Sensible heat m a mass of air R Gas constant ρ Density K Thermal conductivity AHU air handling unit(s) ASHRAE American society of heating, refrigerating and air conditioning engineers SHR Sensible heat ratio V Velocity P Pressure CFM cubic feet per minute DBT Dry-bulb temperature WBT Wet-bulb temperature ADP Apparatus dew point RH Relative humidity h Coefficient of Convection Re Reynolds Number Pr Prandtl Number. INTRODUCTION One of the key global challenges which we are facing today is depletion of natural resources. Scarcity of these resources has led to increase in cost energy in exponential manner. Thus expected surge in prices is much more compared to other commodities. In addition, in order to curb carbon dioxide emissions certain protocols climate change convention Kyoto protocol have been imposed on all nations. As manufacturing industries worldwide have been focusing on reduction in costs, reduction 26 Rohit R. Parab, Laxmikant D. Mangate

2 in energy costs is one of key strategy for manufacturing organizations Humidity control is essential for material processing, space conditioning of habitable buildings, and industrial air-conditioning consumes significant quantities of electrical energy. Two methods for reducing humidity are either to increase size of air conditioners to over cool the air and remove moisture and then again heat the air before circulating it,.another method is using desiccant system to capture moisture in one area and release it in another by applying heat. Both these method consume considerable amount of energy thus increasing energy bills. Heat pipe eliminates the need for reheat or desiccant systems and increases the dehumidifying capacity of an air conditioner by as much as 70%. The technology uses about 40% less energy than electric reheat systems and approximately 25% less energy than other types of reheat methods. Reducing humidity is vital from health conditions perspective.it helps in prevention of growth of mold, mildew, fungus, and dust mites all common allergy agents. Heat pipe as dehumidifier can help cure sick building problems with conditioned fresh air and, as a result, can improve employee productivity M/s Flash Electronics (India) Pvt. Ltd. is one of the established unit in Indian market and a trusted supplier to major Indian two and three wheeler manufacturers. Annual energy cost of the M/s Flash Electronics (India) Pvt. Ltd., is to the tune of Rs Lacs. With spiraling energy costs, FEIPL is keen to trim down energy consumption and cost. The present assignment is for checking levels of energy efficiency at the FEIPL plant 1. The energy audit was conducted which aimed at recording and quantification of the energy consumption at this unit. Subsequently, it also tries to explore the possibilities of conserving energy through better production practices and employment of latest technologies. As FEIPL is into manufacturing of Electrical and Electronic component for automobile sectors,maintaining temperature and humidity is crucial.as per guidelines temperature to be maintained is C and Humidity to be maintained in % RH.same temperature is required in Office area from human comfort perspective.for maintaining the same AHU (Air handling unit) provided to Electronics and Sensor department Table 1 :Increase In Electrical load year over year Machine Load Utility Load Plant load Before After Data shows that there is nearly 16.6 % increase in machine load whereas whopping 108% increase in Utility load.utility load which was 28 % of plant before has increased significantly to 41 % of plant load PERFORMANCE STUDY OF AHU The AC plant has 2 nos. (2 x 20 HP) AHU s for supplying air to the aforementioned areas (electronic section, reception and ignition coil section etc). Table below gives the rated and actual measured air flow rates and power consumption for the blowers. Table 2 :Performance Study of AHU (Shop floor) No. Particulars Value 1 Supply air velocity m/sec Supply air DBT, C 19 3 Supply Air WBT, C 16 4 Supply air Enthalpy, kj/kg Return air temp, DBT, C Return air velocity, m/sec Return air WBT, C Return air Enthalpy, kj/kg RH % at served area AHU 1, blower -1, kw AHU 1, blower -2, kw Rohit R. Parab, Laxmikant D. Mangate

3 Sr.No Table 3: Performance Study of AHU (Office ) Particulars value Supply air DBT C 17.1 Supply air WBT C 16.1 Supply air Enthalpy KJ/Kg Return Air temp DBT C 22.2 Return air Velocity m/s 4 Return air WBT C 18.9 Return air enthalpy KJ/Kg RH at served area % 74 Density of supply air kg/m mass flow of air (kg/hr) As it can be seen from data is that air is overcooled in AHU and then humidification process followed due to which is increase in Electric energy consumption and electric energy cost EXPERIMENTAL SETUP AND MEASUREMENTPROCEDURE The test section consists of two air ducts of 0.15 X 0.15 m 2 section areas connected together by heat pipe heat exchanger. Heat pipes were installed by drilling holes in the duct A refrigeration machine consisting of; Blower, cooling coil along with the measuring instruments were used to supply the return cold air to the condenser Side of the heat pipe. A blower of variable speed installed before the cooling coil. The refrigeration unit was charged with chilled water and the evaporator was made from cooling coil, installed in the duct of 0.15 X 0.15 m 2 inside dimensions. The return cold and fresh warm air ducts were insulated with glass wool of 25 mm thickness to minimize the heat transfer to surrounding The air temperature and relative humidity at inlet and outlet of the two ducts were measured with Hygrometer steady state conditions were ensured before taking measurements during experiment. The refrigeration unit was operated and after enough time, the temperatures and humidity of fresh and return air before and after heat pipe heat exchanger were recorded, when they reached steady state i.e. nearly constant. The ratio between return cold and fresh air mass flow rates was obtained. The recorded data of the air were represented on the psychometric chart. Fig. 1: Experimental set up to measure heat pipe performance The air parameter range provided by the test system is: Room temperature -18~35, Relative humidity 50%~85%, Air quantity 25 CFM The heat pipe dehumidifier is tested at different dry bulb temperature and different wet bulb temperature (relative humidity). The working conditions and the results about the parameters, such as, dehumidification capacity, cooling coil power, heat pipe saving and energy saving ratio are listed in table The air parameters captured in the dehumidifier at different points. Point 1 is the state of high temperature wet air, point 2 is low temperature wet air after pre-cooling in evaporation side of heat pipe, point 3 is low temperature dry air after passing through cooling coil to low temperature and dehumidification, point 4 is dry air after passing through heat pipe condensation side to increase temperature Wet air and reheat low temperature dry air, 1-2 and 3-4 show the processes and the energy saving ratio. Point 5 is point after low temperature and dehumidification in the similar power condition of cooling coil with heat pipe, it can be indicated that point 4 has a higher air temperature and a lower relative humidity than point Rohit R. Parab, Laxmikant D. Mangate

4 RESULTS Graph was plotted for cooling coil power required with and without heat pipe and energy saving shown on the graphs the temperature of experimental cooling coil can also be varied by varying temperature Of water circulated through it.this temperature difference obtained by adding ice at inlet water and recording The temperature.for varying inlet temperature and humidity humidifier was used Readings were taken at various inlet DBT i.e at 25,26,27,28,29,30 degcelsius and graphs were plotted,results indicated that there is almost linear variation observed in the outlet temperature w.r.t. changing cooling coil temp Fig. 2: Variation of cooling coil power with and without heat pipe with respect to Variation in inlet DBT and RH 1. The cooling coil power reduced greatly with the using of heat pipe. 2. Heat pipe heat exchanger tested for various inlet and outlet temperature conditions and 3. results show that there is significant drop in energy consumption Energy saving ratio observed during experiments from 8.4% to 14.4 %.Thushas substantial potential of saving electrical energy consumption required for cooling coil Graph was plotted for Specific humidity at inlet and outlet conditions.specific humidity indicates mass of water vapor present in air w.r.t. dry air.difference in specific humidity would indicate that there is substantial amount of moisture removed from the process Fig. 3:Variation of Humidity ratio with and without heat pipe with respect to Variation in inlet DBT and RH Fig. 4:Effect of changing cooling coil ADP CONCLUSIONS The test indicates that: 1) Heat pipe has a good operating effect, the air temperature has a great change after passing through heat pipe, the energy saving effect is marked. The cooling coil power with using heat pipe has been greatly reduced, the energy saving ratio of heat pipe is range from 6.4 to 14.4 % 2) Air relative humidity is linearly proportional to the dehumidification capacity and increase cooling coil power but the energy saving ratio of heat pipe is reduced. 3) Under constant relative humidity, dehumidification capacity and cooling coil power decrease along with the decrease of dry bulb temperature, but the energy saving ratio of heat pipe dehumidifier increase. 4) Under condition of the same dry and wet bulb temperature, dehumidification capacity and cooling coil power reduce along with the reduction in airflow quantity but the energy saving ratio increases. 29 Rohit R. Parab, Laxmikant D. Mangate

5 ACKNOWLEDGMENTS The authors are grateful to Vishwakarma Institute of Technology, Pune, India for providing space for experimentation. The authorsalso want to thank Mr.AjyakumarAmbike,LaxmanPawashe,AtulTotade,SunilShirgave for their immense support for the Project REFERENCES [1] Parkcheol-woo et.al. Energy consumption reduction technology in manufacturing-a selective review of Policies, Standards, andresearch, InternationalJournal of precision engineering and manufacturing Vol.10, no.5, (2009) [2] Wan J.W et.al, The effect of heat pipe air handling coil on energy consumption in central air conditioning system,journal of Energy and building (2007) [3] MostafaA.Abd El-baky,MousaM.Mohamed, Heat pipe heat exchanger for heat recovery in air conditioning Journal of Applied Thermal Engineering 27 (2007) [4]AliakbarAkbarzadeh Application of heat pipe heat exchanger to humidity control in Air-conditioning systems Applied Thermal Engineering Vol. 17, No. 6,(1997) , [5] Senthilkumar, R., et.al., Thermal Analysis of Heat Pipe Using Self Reweting Fluids, Journal of Thermal Science,, Vol. 15, No. 3, (2011 ) [6] Senthilkumar, R., et.al, Thermal analysis of heat pipe sing Taguchi Method International Journal of Engineering Science and Technology Vol. 2,No.4, (2010), [7] Xiaobao Zhao et.al. Performance test and Energy saving analysis of heat pipe dehumidifier Journal HVAC Technologies for Energy Efficiency Vol.4 (2006) 4-5 [8] Nemec Peter et.al., Thermal Performance Measurement of Heat pipe Global Journal of Technology and Optimization Vol.2 (2011) [9] Sivaraman B. and Krishna.N Experimental analysis of heat pipe solar collector with different L/di ratio of Heat pipe,journal of scientific and Industrial research Vol.64, (2005), [10] DharP.L.,SinghS.K, Studies on solid desiccant based hybrid air-conditioning systems, Applied Thermal Engineering Vol.21 (2001) [11] Dr.Niu.L.J., Technology options for humidity control for hotels in Southeastern China Climate Journal of HKIE Transactions, Vol 8. No2, (2001) 20-24, [12] AhmadzadehtalatapehM,Yau Y.H, The application of heat pipe heat exchangers to improve the air quality and reduce the energy consumption of the air conditioning system in a hospitalward A full year model simulation, Journal of Energy and Building Vo.43 (2011), [13] Heat Pipes Theory, Design, Applications by David Reay and Peter Kew [14] Refrigeration and Air conditioning by R.K Rajput [15] Refrigeration and Air conditioning by P.L.Anantnarayan 30 Rohit R. Parab, Laxmikant D. Mangate

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

Modified Air Cooler with Split Cooling Unit

Modified Air Cooler with Split Cooling Unit Modified Air Cooler with Split Cooling Unit Nishant Dhanore 1, Krishna Shrivastava 2 1 SSBT s College of Engineering and Technology, Jalgaon (M.S.), India 2 Associate Professor, Mech. Engg. Dept. SSBT

More information

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY MASS & E ERGY BALA CES I PSYCHROMETRIC PROCESSES EXPERIME T 3 1. OBJECTIVE The object of this experiment is to observe four basic psychrometric processes

More information

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED International Journal of Mechanical Engineering and Technology (IJMET) Volume 7, Issue 3, May June 2016, pp.329 341, Article ID: IJMET_07_03_030 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=7&itype=3

More information

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance #1 Jaydev S. Bade, #2 Dr. Nitin U. Korde 1 Department of Mechanical Engineering, Savitribai Phule

More information

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Available online at   Energy Procedia 6 (2011) MEDGREEN 2011-LB Available online at www.sciencedirect.com Energy Procedia 6 (2011) 759 768 MEDGREEN 2011-LB Comparison of two methods of improving dehumidification in air conditioning systems: hybrid system (refrigeration

More information

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area MMS DEZFOULI, SOHIF MAT, K.SOPIAN Solar Energy Research Institute (SERI, Universiti

More information

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure. 1 PSYCHROMETICS Psychrometry is the study of the characteristics of moist air. We will see soon that evaporation of moisture from the skin can have a significant impact on thermal comfort. The rate of

More information

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY Xiaoyun Xie, Yidan Tang, Xiaoqin Yi, Shuanqiang Liu,Yi Jiang Department of Building Science and Technology,

More information

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches? SIDDHARTH INSTITUTE OF ENGINEERING & TECHNOLOGY :: PUTTUR (AUTONOMOUS) (Approved by AICTE, New Delhi & Affiliated to JNTUA, Anantapuramu) (Accredited by NBA & Accredited by NAAC with A Grade) (An ISO 9001:2008

More information

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE Journal of Sustainability Science and Management Volume 9 Number 1, June 2014: 150-155 ISSN: 1823-8556 Penerbit UMT PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE ARFIDIAN

More information

Optimisation of cooling coil performance during operation stage for improved humidity control

Optimisation of cooling coil performance during operation stage for improved humidity control Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 741 Optimisation of cooling coil performance during operation stage for improved humidity control S.C. Sekhar * and L.T. Tan National

More information

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK St.MARTIN S ENGINEERING COLLEGE Dhulapally, Secunderabad-500 014 Subject: REFRIGERATION AND AIR CONDITIONING Class : ECE III 1 Define Unit of refrigeration. 2 Define C.O.P. QUESTION BANK 3 What is the

More information

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER International Journal of Scientific & Engineering Research, Volume 5, Issue 10, October-2014 676 Performance Evaluation of Alternative Evaporative Cooling Media Rajesh Maurya*, Dr. Nitin Shrivastava, Vipin

More information

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University Scientific Principals and Analytical Model Charcoal Cooler Lisa Crofoot MECH 425, Queens University 1.0 Scientific Principles Evaporative cooling is based on the principle that water requires heat energy

More information

Recent Advances in Energy, Environment and Economic Development

Recent Advances in Energy, Environment and Economic Development Experimental Investigation of Solar Hybrid Desiccant Cooling System in Hot and Humid Weather of Malaysia MM SALEHI DEZFOULI, Z HASHIM, MH RUSLAN, B BAKHTYAR, K SOPIAN, A ZAHARIM, S MAT, A RACHMAN, Solar

More information

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER Gourav Roy; Taliv Hussain; Rahul Wandra Department of Mechanical Engineering, Lovely Professional

More information

Theoretical Performance Analysis Of Direct Evaporative Cooler In Hot And Dry Climates

Theoretical Performance Analysis Of Direct Evaporative Cooler In Hot And Dry Climates INTERNATIONAL JOURNAL OF SCIENTIFIC & TECHNOLOGY RESEARCH VOLUME 3, ISSUE 4, APRIL 214 ISSN 2277-8616 Theoretical Performance Analysis Of Direct Evaporative Cooler In Hot And Dry Climates Ibrahim U. Haruna,

More information

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,

More information

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road 517583 AUTONOMOUS QUESTION BANK (DESCRIPTIVE) Subject with Code : Refrigeration and Air Conditioning (16ME8806) Course & Branch:

More information

EXPERIMENTAL STUDY OF AIR FLOW RATE EFFECTS ON HUMIDIFICATION PARAMETERS WITH PREHEATING AND DEHUMIDIFICATION PROCESS CHANGING

EXPERIMENTAL STUDY OF AIR FLOW RATE EFFECTS ON HUMIDIFICATION PARAMETERS WITH PREHEATING AND DEHUMIDIFICATION PROCESS CHANGING EXPERIMENTAL STUDY OF AIR FLOW RATE EFFECTS ON HUMIDIFICATION PARAMETERS WITH PREHEATING AND DEHUMIDIFICATION PROCESS CHANGING Ayad T. Mustafa College of Engineering, Nahrain University, Jadiriya, Baghdad,

More information

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler International Journal of Thermal Technologies E-ISSN 2277 4114 2015 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Effect of Operating Parameters on the

More information

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator 18 R. Saidur et al./journal of Energy & Environment, Vol. 6, May 2007 Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator R. Saidur, M. A. Sattar, M.

More information

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant Proceedings of the World Congress on Momentum, Heat and Mass Transfer (MHMT 16) Prague, Czech Republic April 4 5, 216 Paper No. ENFHT 111 DOI: 1.11159/enfht16.111 Experimental Investigation of a Multi

More information

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System Feasibility of a Liquid Desiccant Application in an Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, S.K.Han 1, S.Y. Cho 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang

More information

EXPERIMENTAL INVESTIGATION OF HYBRID NANOFLUID ON THERMOSYPHON TYPE WICKLESS HEAT PIPE HEAT EXCHANGER THERMAL PERFORMANCE

EXPERIMENTAL INVESTIGATION OF HYBRID NANOFLUID ON THERMOSYPHON TYPE WICKLESS HEAT PIPE HEAT EXCHANGER THERMAL PERFORMANCE EXPERIMENTAL INVESTIGATION OF HYBRID NANOFLUID ON THERMOSYPHON TYPE WICKLESS HEAT PIPE HEAT EXCHANGER THERMAL PERFORMANCE Mr. Jaydev S. Bade 1, Dr. Nitin U. Korde 2 1 Student, Mechanical Engineering Department,

More information

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island Session: HVAC 101 HVAC 101 Steve Sain Sain Engineering Associates, Inc. August 9, 2016 Rhode Island Convention Center Providence, Rhode Island Why? 2 Acknowledgements 3 Disclaimer I m gonna shoot down

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering) Set No. 1 IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec - 2014 REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering) Time: 3 hours Max. Marks: 75 Answer any FIVE Questions All Questions

More information

Comfort and health-indoor air quality

Comfort and health-indoor air quality Comfort and health-indoor air quality 1 The human body has a complicated regulating system to maintain the human body temperature constant most of the time, which is 98.6 F (36.9 C) regardless of the environmental

More information

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011 Performance evaluation of two stage indirect/direct evaporative cooler with alternative shapes and cooling media in direct stage Kulkarni.R.K 1, Rajput S.P.S 2 1 SVPM College of Engineering, Malegaon(bk),

More information

AR/IA/UP 241 Lecture 5: Psychrometrics

AR/IA/UP 241 Lecture 5: Psychrometrics Faculty of Architecture and Planning Thammasat University AR/IA/UP 241 Lecture 5: Psychrometrics Author: Asst. Prof. Chalermwat Tantasavasdi 1. Definition of Psychrometric Chart The word psychrometry is

More information

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1998 Effects of Frost Formation on the External Heat Transfer Coefficient of

More information

Performance Optimization of the Evaporative Condenser Design

Performance Optimization of the Evaporative Condenser Design Performance Optimization of the Evaporative Condenser Design Mit. C. Patel P.G.Student, Mech. Engg.Dept. Institute of Technology, Nirma University, Ahmadabad, Prof. B. A. Shah Mechanical Engineering Department

More information

INSTITUTE OF AERONAUTICAL ENGINEERING

INSTITUTE OF AERONAUTICAL ENGINEERING 1 P a g e INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad -00 043 MECHANICAL ENGINEERING QUESTION BANK Name : REFRIGERATION AND AIR CONDITIONING Code : A60334 Class : III B. Tech

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) 4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao

More information

International Journal of Advanced Engineering Research and Science (IJAERS) Vol-3, Issue-2, Feb- 2016] ISSN:

International Journal of Advanced Engineering Research and Science (IJAERS) Vol-3, Issue-2, Feb- 2016] ISSN: Fabrication of Direct Evaporative Cooler and its Performance Analysis for Different Materials In Hot and Dry Climates Utkarsh Tripathi 1, Dr. R.M.Sarviya 2, Veeresh Fuskele 3 1Department of Mechanical

More information

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM 551B 581B DuraPac Plus Series Sizes 036-150 3to12 1 / 2 Tons Cancels: New PAD 551B.36.2 10/1/04 CONTENTS Page INTRODUCTION.................................

More information

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY L Fang 1,2,, G Zhang 1,2 and PO Fanger 1,2 1 International Centre for Indoor Environment and Energy,

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Shoeb Inamdar 1, H. S. Farkade 2 P.G. Student, Department of Mechanical Engineering, Govt. College of Engg. Amravati. Maharashtra,

More information

Design and Development of Combined Direct and Indirect Evaporative Cooling System

Design and Development of Combined Direct and Indirect Evaporative Cooling System ISSN 2395-1621 Design and Development of Combined Direct and Indirect Evaporative Cooling System #1 Pallavi B. Bedre, #2 H.U.Tiwari 1 pallavi.bedre@gmail.com 2 sharvay12 @rediffmail.com #12 Pimpri-Chinchwad

More information

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION ENERGY EFFICIENT DEHUMIDIFICATION PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM Provides a very high degree of latent cooling using only a minimal amount of conventional cooling input Substantial energy

More information

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential

More information

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to

More information

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM - 1 - EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM Shun YOSHIOKA, Hyunyoung KIM, Kazushige KASAI, Daikin Industries,

More information

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump To cite this article: Yefeng Liu et al 2018 IOP

More information

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in

More information

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL International Journal of Technical Innovation in Modern Engineering & Science (IJTIMES) Impact Factor: 3.45 (SJIF-2015), e-issn: 2455-2585 Volume 3, Issue 10, October-2017 PERFORMANCE ANALYSIS OF VAPOUR

More information

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling Dr. Akash Langde 1, Zeeshan Jamal 2, Shahrukh Jamal 3, Mohammad Shumoil Ansari 4 1Professor, Department of Mechanical Engineering,

More information

THE COOLING CAPACITY AND PRESSURE DROP IN A HYBRID CLOSED CIRCUIT COOLING TOWER

THE COOLING CAPACITY AND PRESSURE DROP IN A HYBRID CLOSED CIRCUIT COOLING TOWER Proceedings of the International Conference on Mechanical Engineering 25 (ICME25) 28-3 December 25, Dhaka, Bangladesh ICME5- HE COOLING CAPACIY AND PRESSURE DROP IN A HYBRID CLOSED CIRCUI COOLING OWER

More information

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning HVAC 101 The Basics of Heating, Ventilation and Air Conditioning HVAC Heating, Ventilation and Air Conditioning Provides comfort for people Allows humans to exist under adverse conditions. Comfort Comfort

More information

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System International Conference on Civil, Transportation and Environment (ICCTE 201) Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System Pengjie Fan1, a, Caihua Liang1,

More information

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant M. Honma, T. Tamura, Y. Yakumaru and F. Nishiwaki Matsushita Electric Industrial Co., Ltd. Living Environment

More information

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters #1 Harshad D Kopurwar, #2 Pravin T Nitnaware, #3 Tapobrata Dey 1 harshvardhan1590@gmail.com #1 Mechanical

More information

ENSC 388: Engineering Thermodynamics and Heat Transfer

ENSC 388: Engineering Thermodynamics and Heat Transfer ENSC 388: Engineering Thermodynamics and Heat Transfer Experiment 3: Free and Forced Convection Objective Determination of heat transfer coefficient for free and forced convection for different geometries.

More information

A/C Cooling Load calculation and measurement

A/C Cooling Load calculation and measurement Testo Inc. 40 White Lake Rd. Sparta NJ 07871 (800) 227-0729 A/C Cooling Load calculation and measurement When we talk about sizing an air conditioning appliance (tons of cooling, BTU/h or KW), we are specifying

More information

Two Stage Indirect/Direct Evaporative Cooling

Two Stage Indirect/Direct Evaporative Cooling Two Stage Indirect/Direct Evaporative Cooling Abstract The performance of two-stage indirect/direct evaporative cooling system is experimentally investigated. For this purpose, a two-stage evaporative

More information

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer GRD Journals- Global Research and Development Journal for Engineering Volume 2 Issue 6 May 2017 ISSN: 2455-5703 Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer Gokul G Nair Dr. Jeoju

More information

The Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc.

The Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc. The Basics - B Practical Psychrometrics Jerry Cohen President Jacco & Assoc. Who is Jacco Established 1968 Hudson, Ohio Columbus, Ohio Toledo, Ohio Focused on the Engineered Environment Systems Knowledgeable

More information

II. OBJECTIVE OF RESEARCH

II. OBJECTIVE OF RESEARCH Enhancement of Coefficient of Performance of Vapor Compression Refrigeration System Using Diffuser at let of Condenser Mr. Nurul Seraj 1, Dr. S. C. Roy 2 1 Student, 2 Head of Department, Department of

More information

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1

More information

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12 EXPERIMENTAL ANALYSIS OF THE EFFECT OF FIN GEOMETRY ON HEAT TRANSFER RATE THROUGH THE REFRIGERATOR CONDENSER ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

More information

Dynamic performance of a novel dew point air conditioning for the UK buildings

Dynamic performance of a novel dew point air conditioning for the UK buildings *Corresponding author: xudongzhao@nottingham. ac.uk Dynamic performance of a novel dew point air conditioning for the UK buildings... Xudong Zhao *, Zhiyin Duan, Changhong Zhan and Saffa B. Riffat School

More information

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 Ameya P. Shrivastava 1, Choudhari Chandrakishor S. 2 1,2 Mechanical Department, AISSMS College of Engineering, Pune 411001, (India) ABSTRACT HCFC

More information

A review on Efficient Technique of Air-Conditioning Rajesh Kumar, Pravesh Mishra, Ram Raja

A review on Efficient Technique of Air-Conditioning Rajesh Kumar, Pravesh Mishra, Ram Raja A review on Efficient Technique of Air-Conditioning Rajesh Kumar, Pravesh Mishra, Ram Raja Abstract This is a review paper of Suryavanshi at al. Two stages evaporative cooling (TSEC) is an alternative

More information

Investigation of an evaporative air cooler using solar energy under Algerian climate

Investigation of an evaporative air cooler using solar energy under Algerian climate Available online at www.sciencedirect.com Energy Procedia 6 (2011) 573 582 MEDGREEN2011-LB Investigation of an evaporative air cooler using solar energy under Algerian climate S. Elmetenani a,*, M.L. Yousfi

More information

Review of Thermosyphon heat exchanger charged with hybrid nanofluid for waste heat recovery applications

Review of Thermosyphon heat exchanger charged with hybrid nanofluid for waste heat recovery applications Review of Thermosyphon heat exchanger charged with hybrid nanofluid for waste heat recovery applications 1 Jaydev S. Bade, 2 Nitin Korde, 3 Anurag Hatwar 1 ME Heat Power GHRCOEM, Ahmednagar 2 Department

More information

STUDY OF PERFORMANCE AND POSSIBLE CONFIGURATION OF HYBRID AIR CONDITIONING SYSTEM WITH AND WITHOUT COMBINED PELTIER MODULE AND EARTH HEAT EXCHANGER.

STUDY OF PERFORMANCE AND POSSIBLE CONFIGURATION OF HYBRID AIR CONDITIONING SYSTEM WITH AND WITHOUT COMBINED PELTIER MODULE AND EARTH HEAT EXCHANGER. STUDY OF PERFORMANCE AND POSSIBLE CONFIGURATION OF HYBRID AIR CONDITIONING SYSTEM WITH AND WITHOUT COMBINED PELTIER MODULE AND EARTH HEAT EXCHANGER. 1 Avinash B. Lohar, 2 Nitin V. Sali 1 M.E. Student,

More information

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China Humidity Control Systems for Civil Buildings in Hot Summer and Cold Winter Zone in China Xiaoping Yu Doctoral Candidate Chongqing University of Science & Technology Chongqing, China, 400042 xiaoyup@163.com

More information

2. CURRICULUM. Sl. No.

2. CURRICULUM. Sl. No. . CURRICULUM Sl. No. Code Title No. of Lecture Hours 1 RAC 001 Fundamentals of Refrigeration and Air 60 conditioning RAC 00 Psychrometry, Heat load Estimation for 70 Air conditioning and Refrigeration

More information

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA Ninth International IBPSA Conference Montréal, Canada August 15-18, 25 SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS Chaoqin Zhai 1, Xiaohong

More information

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES THERMAL SCIENCE, Year 2011, Vol. 15, No. 2, pp. 467-475 467 EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES by Krishnasamy SENTHILKUMAR a* and Pss

More information

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification Charles J. Cromer, PhD, P.E.; Florida Solar Energy Center, 1679 Clearlake Road, Cocoa, FL, 321-638-14,

More information

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled

More information

Feasibility Analysis of Regeneration of Silica Gel Used in Dehumidification Process of Air Conditioning by the Condenser Waste Heat of Air Conditioner

Feasibility Analysis of Regeneration of Silica Gel Used in Dehumidification Process of Air Conditioning by the Condenser Waste Heat of Air Conditioner Feasibility Analysis of Regeneration of Silica Gel Used in Dehumidification Process of Air Conditioning by the Condenser Waste Heat of Air Conditioner Priyanka Nath, Jitul Baruah Guest Lecturer, Department

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile Available online at www.pelagiaresearchlibrary.com Advances in Applied Science Research, 2013, 4(5):232-237 ISSN: 0976-8610 CODEN (USA): AASRFC Performance analysis of ejector refrigeration system with

More information

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance

More information

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection. Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using

More information

SPLIT-SYSTEM RESIDENTIAL HEAT PUMP WITH SEPARATE DEHUMIDIFICATION OPERATING MODE

SPLIT-SYSTEM RESIDENTIAL HEAT PUMP WITH SEPARATE DEHUMIDIFICATION OPERATING MODE SPLIT-SYSTEM RESIDENTIAL HEAT PUMP WITH SEPARATE DEHUMIDIFICATION OPERATING MODE Oved W. Hanson, Senior Principal Engineer, Applied Research Department, Lennox Industries Inc., Carrollton, Texas, USA Robert

More information

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)

More information

Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device

Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device J R Mehta 1, A A Sujela 2 1 Department of Mechanical Engineering, Faculty of Technology and Engineering,The Maharaja

More information

Experimental Investigations of Heat Pump for Domestic and Light Commercial Market.

Experimental Investigations of Heat Pump for Domestic and Light Commercial Market. Experimental Investigations of Heat Pump for Domestic and Light Commercial Market. Mr. Mohite Sachin Kumar Sr. Lecturer, Mechanical Department,A.G. Patil Polytechnic Institute, Vijapur Road, Solapur (Maharashtra),

More information

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms Min Suk Jo, Jang Hoon Shin, Won Jun Kim and Jae Weon Jeong * Department of Architectural

More information

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes ME 410 - Mechanical Engineering Systems Laboratory Experiment 3 - Mass and Energy Balances in Psychrometric Processes Assist.Prof.Dr. Özgür BAYER, A-123 AIR-CONDITIONING (A/C) Goal: Control temperature

More information

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Mingsheng Liu, Ph.D., P.E. Energy Systems Laboratory Texas A&M University College Station, Texas

More information

Numerical Simulation of Window Air Conditioner

Numerical Simulation of Window Air Conditioner Numerical Simulation of Window Air Conditioner Mathewlal T 1, Kalpesh Patil 2, Gauri Thorat 3, Anisha Ankush 4, Ambarish Pote 5, Kartik Doshi 6 ( 1 Associate ProfessorMechanical Engineering Department,

More information

Practical Fundamentals of Heating, Ventilation and Air Conditioning (HVAC) for Engineers and Technicians

Practical Fundamentals of Heating, Ventilation and Air Conditioning (HVAC) for Engineers and Technicians Presents Practical Fundamentals of Heating, Ventilation and Air Conditioning (HVAC) for Engineers and Technicians Revision 11.2 Website: www.idc-online.com E-mail: idc@idc-online.com IDC Technologies Pty

More information

Heat pump and energy recovery systems

Heat pump and energy recovery systems SBS5311 HVACR II http://ibse.hk/sbs5311/ Heat pump and energy recovery systems Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Oct 2017 Contents Basic concepts Air-to-air

More information

Performance investigation of Air-conditioning system using ejector as expansion device

Performance investigation of Air-conditioning system using ejector as expansion device International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Performance

More information

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

S.A. Klein and G.F. Nellis Cambridge University Press, 2011 12.A-1 A mixture of helium and water vapor is flowing through a pipe at T= 90 C and P = 150 kpa. The mole fraction of helium is y He = 0.80. a.) What is the relative humidity of the mixture? b.) What is

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical

More information

Review on Waste Heat Recovery Techniques in Air Conditioning Application

Review on Waste Heat Recovery Techniques in Air Conditioning Application International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Review Article Review

More information

How to ensure Thermal Comfort in buildings with CFD

How to ensure Thermal Comfort in buildings with CFD How to ensure Thermal Comfort in buildings with CFD Using CFD Simulations to analyze and improve HVAC Systems Simulation in your browser How to Ensure Thermal Comfort in Buildings with CFD How to use CFD

More information

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Temperature. In the HVAC area, we talk about two kinds of temperatures. HEATING and COOLING HEATING and COOLING PSYCHROMETRIC CHART Temperature In the HVAC area, we talk about two kinds of temperatures. One is called dry bulb (DB) temperature, a fancy name for the reading

More information

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1 HEFAT27 5 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp PERFORMANCE ANALYSIS OF AIR-COOLED CONDENSER USING MICRO-FIN TUBES P.A.Patil

More information

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants CHENNUCHETTY CHINNARAJ * Associate Professor in Mechanical Engineering, Government College of

More information

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos Evaluation of A Plate Desiccant Outdoor Air-conditioning System Utilizing Cogenerated Hot Water Using A Numerical Model T. Baba 1, B. Park 1 1, *1, and T. Nagai 1 Department of Architecture, Tokyo University

More information

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32 Paper O.1.2.4-1 - Full and Partial Load Performances of RAC and CAC Heat Pump using R-32 Sungjin In, Graduate student, Sungkyunkwan University, Suwon, Gyunggi-do, 440-746, Korea Keumnam Cho, Professor,

More information

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET

More information