SPLIT SYSTEM AIR CONDITIONER

Size: px
Start display at page:

Download "SPLIT SYSTEM AIR CONDITIONER"

Transcription

1 TECHNICAL DATA & SERVICE MANUAL Indoor Unit MCA201R MCA271R MCA351R Outdoor Unit GR201R GR271R GR351R SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT OUTDOOR UNIT /2002

2 Important! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices given in this manual. This symbol refers to a hazard or WARNING unsafe practice which can result in severe personal injury or death. This symbol refers to a hazard or CAUTION unsafe practice which can result in personal injury or product or property damage. If Necessary, Get Help These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions. In Case of Improper Installation The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. Special Precautions WARNING When Wiring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM. Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. When Transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. When Installing In a Ceiling or Wall Make sure the ceiling/wall is strong enough to hold the units weight. It may be necessary to construct a strong wood or metal frame to provide added support. In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors. In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration. In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle. In a Snowy Area (for Heat Pump-type Systems) Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents. When Connecting Refrigerant Tubing Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leakfree connection. Check carefully for leaks before starting the test run. When Servicing Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. Others CAUTION Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas. i ii

3 Table of Contents Page 1 OPERATING RANGE 1 2 SPECIFICATIONS Unit Specification Indoor Unit Outdoor Unit Other Component Specifications 5 3 DIMENSIONAL DATA Indoor Unit Outdoor Unit 7 4 REFRIGERANT FLOW DIAGRAM 8 5 PERFORMANCE DATA P Air Throw Distance Chart Cooling Capacity Heating Capacity 13 6 ELECTRICAL DATA Electrical Characteristic Electric Wiring Diagrams 15 7 FUNCTION Cool Mode Operation Heat Mode Operation Auto Cool/Heat mode operation Dry Mode Operation Protection Operation in Cool and Dry Operation Mode Protection Operation in Heat Mode) Cool Draft Prevention (Heating Others Features 26 8 TROUBLESHOOTING Check before and after troubleshooting Check Power Supply Wiring Check Indoor Unit Wiring Check Power Supply Check Lead wires and Connector in Indoor and Outdoor Units Air Conditioner Does not work Some Parts of Air Conditioner does not operate Air Conditioner operates, but abnormalities are observed If a Sensor is defective 35 9 CHECKING ELECTRICAL COMPONENTS Measure of insulation Resistance Check Continuity for Electrical Parts Checking Motor Capacitor 37 iii

4 1.OPERATING RANGE Cooling Heating Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 32 C D.B. / 23 C W.B. 43 C D.B. Minimum 19 C D.B. / 14 C W.B. 19 C D.B. Maximum 27 C D.B. 24 C D.B. / 18 C W.B. Minimum 16 C D.B. -5 C D.B. / -6 C W.B. DB-Dry Bulb WB-Wet Bulb 1

5 2.SPECIFICATIONS 2-1 Unit Specification Model Unit Voltage Rating Indoor Unit MCA201R MCA271R MCA351R Outdoor Unit GR201R GR271R GR351R 230 V 50 Hz Performance Capacity Cooling / Heating W BTU/h Air Circulation Hi-Me-Low m 3 /hr Moisture Removal Liters/h Electrical Rating Running Amperes A Power Input W Power Factor % C.O.P W/W Compressor locked rotor amperes A Features Controls / Temperature Control Microprocessor / I.C. thermostat Control Units Wireless remote control unit Timer 24 hr ON o OFF Fan Speed Indoor/Outdoor 3-Auto / 1 Air Flow Direction (indoor) Horizontal Manual Vertical Auto Air Filter Washable, Anti-Mold Compressor Rotary ( Hermetic ) Refrigerant/Amount charged at shipment g R R R Refrigerant Control Capillary Operation Sound Indoor: hi / Me / Lo db-a Outdoor: Cool/Heat db-a Refrigerant Tubing Connections Flare Max Allowable tubing length at shipment mt 7.5 Refrigerant tube Narrow tube mm (in) 6.35 (1/4 ) diameter Wide tube mm (in) 9.52 (3/8 ) 9.52 (3/8 ) 12.7 (1/2 ) Max allowable tubing Lenght mt Refrigerant g/m Dimensional & Weight Indoor Unit Outdoor Unit Height mm Unit dimensions Width mm Depth mm Height mm Package dimensions Width mm Depth mm Weight Net Kg Shipping Kg Shipping volume m DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Cooling : Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 24 C W.B. Heating : Indoor air temperature 20 C D.B. Outoor air temperature 7 C D.B. / 6 C W.B. 2

6 2-2 Indoor Unit Model Unit MCA201R MCA271R MCA351R Controller PCB Part No Controls Control circuit fuse WSA-LTR Microprocessor 250 V 3.15 A Remote Control Unit Fan & Fan Motor Type Cross-Flow Q.ty.Dia. and length mm 1- θ 95 / 617 Fan motor model.q.ty KFV4Q-11HP-S No of poles rpm (230V,hi) Nominal output W 10 BRN-WHT VLT-WHT Coil Resistance (Ambient Temp.) VLT-ORG 63.4 YEL-ORG YEL-PNK Safety device Type Internal Fuse Operating temp. Open C 145 +/-5 Close C - Run capacitor µf Vac Flap Motor Type Stepping Motor Model MP24GAI Rating 12 VDC Coil resistance (Ambient temp 25 C) ohm 380 Heat Exch.Coil Coil Aluminium plate fin/ Copper tube Rows 2 Fin pitch mm 1.6 Face area m DATA SUBJECT TO CHANGE WITHOUT NOTICE 3

7 2-3 Outdoor Unit Model Unit GR201R GR271R GR351R Compressor Type Rotary (Hermetic) Compressor model mm RH130VHAT RH154VHAT RH189VHAF Nominal output Compressor oil Diamond MS 56.Amount cc Coil resistance (Ambient temp 25 C)+/- 7% cr Ω cs Ω Safety device Type Overload relay Operating temp Open C 150 +/ / /-5 Close C 90 +/ / /-10 Operating amp(ambient temp 25 C) - Run capacitor µf VAC Grank case heater Fan & Fan Motor Type Propeller Q.ty.Dia. and length mm θ 370 Fan motor model.q.ty K35610-M No of poles rpm (230V,hi) Nominal output W 22 Ω BRN-WTH 374 +/- 7% Coil Resistance (Ambient Temp.20 C) Ω PNK-BRN 484 +/-7% - Safety device Type Internal protector Operating temp. Open C Close C Auto Run capacitor µf 1.5 Vac 400 Heat Exch.Coil Coil Aluminium Plate fin / Copper tube Rows 1 Fin pitch mm Face area m External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE 4

8 2-4 Other Component Specifications Indoor unit Transformer (TR) TPN Primary 230V 50HZ Rating Secondary 12 V 300mA Capacity Coil resistance Ω (at 21 C) Primary 495 Secondary 2.86 Thermal cut-off temp. 125 C Thermistor (Coil sensor) NTC - TERMISTOR Resistance KΩ 10 at 25 C Thermistor (Room sensor) Resistance KΩ Outdoor Unit 4-Way Valve (Solenoid coil) CHV01A(coil) CHV-0101 (valve) Coil rating 230V-50HZ Coil resistance KΩ /- 7% Thermostat ( Defrost thermo ) NTC - TERMISTOR Operating Temp C 2 / 15 +/-2 ON Resistance KΩ 10 at 25 C 5

9 3.DIMENSIONAL DATA 3-1 Indoor Unit 6

10 3-2 Outdoor Unit 7

11 4.REFRIGERANT FLOW DIAGRAM 8

12 5.PERFORMANCE 5-1 Air Throw Distance Chart COOLING Room ir temp : 27 C Fan Speed : High Axis Air Velocity (m/s) Vertical distance (m) Horizontal distance (m) Axis air velocity Flap angle 0 30 HEATING Room ir temp : 20 C Fan Speed : High Axis Air Velocity (m/s) Vertical distance (m) Horizontal distance (m) Axis air velocity Flap angle

13 COOLING Room ir temp : 27 C Fan Speed : High Axis Air Velocity (m/s) Vertical distance (m) Horizontal distance (m) Axis air velocity Flap angle 0 30 HEATING Room ir temp : 20 C Fan Speed : High Axis Air Velocity (m/s) Vertical distance (m) Horizontal distance (m) Axis air velocity Flap angle

14 5-2 Cooling Capacity Indoor Unit Otdoor Unit MCA271R GR271R 230 V Single Phase 50 HZ RATING CAPACITY 2.45kW AIR FLOW RATE 420m³/h EVAPORATOR CONDENSER ENT.TEMP. C OUTDOOR AMBIENT TEMP. C W.B. D.B TC 2,32 2,25 2,15 2,01 1,86 CM 0,70 0,75 0,80 0,88 0,96 21 SHC 1,59 1,56 1,51 1,44 1,37 23 SHC 1,80 1,77 1,72 1,65 1, SHC 2,01 1,97 1,92 1,85 1,78 27 SHC 2,22 2,18 2,13 2,01 1,86 29 SHC 2,32 2,25 2,15 2,01 1,86 31 SHC 2,32 2,25 2,15 2,01 1,86 TC 2,51 2,42 2,30 2,16 1,99 CM 0,72 0,77 0,82 0,91 0,98 21 SHC 1,39 1,35 1,30 1,24 1,16 23 SHC 1,60 1,56 1,50 1,44 1, SHC 1,81 1,76 1,71 1,65 1,57 27 SHC 2,02 1,97 1,91 1,85 1,77 29 SHC 2,24 2,17 2,12 2,06 1,98 31 SHC 2,44 2,38 2,30 2,16 1,99 TC 2,66 2,57 #2,45 2,30 2,12 CM 0,75 0,79 0,85 0,93 1,01 21 SHC 1,17 1,13 1,08 1,01 0,94 23 SHC 1,37 1,34 1,28 1,22 1, SHC 1,57 1,54 1,49 1,43 1,35 27 SHC 1,77 1,75 1,69 1,63 1,56 29 SHC 1,97 1,95 1,90 1,84 1,76 31 SHC 2,18 2,16 2,10 2,04 1,97 TC 2,82 2,73 2,60 2,44 2,25 CM 0,77 0,81 0,88 0,96 1,04 23 SHC 1,15 1,11 1,06 1,00 0, SHC 1,35 1,32 1,27 1,20 1,13 27 SHC 1,55 1,52 1,47 1,41 1,33 29 SHC 1,75 1,73 1,68 1,61 1,54 31 SHC 1,96 1,93 1,88 1,82 1,75 TC 3,01 2,89 2,73 2,55 2,38 CM 0,78 0,83 0,90 0,98 1, SHC 1,13 1,08 1,02 0,96 0,89 27 SHC 1,32 1,28 1,23 1,16 1,10 29 SHC 1,52 1,49 1,43 1,37 1,30 31 SHC 1,74 1,70 1,64 1,57 1,51 TC : Total Cooling Capacity KW SHC : Sensible Heat Capacity KW CM : Compressor Input KW Rating Condition (#Mark) are Outdoor Ambient Temperature Indoor Unit Entering Air Temp C D.B. 27 C D.B / 19 C W.B.

15 Indoor Unit Otdoor Unit MCA351R GR351R 230 V Single Phase 50 HZ RATING CAPACITY 3.15 kw AIR FLOW RATE 450 m³/h EVAPORATOR CONDENSER ENT.TEMP. C OUTDOOR AMBIENT TEMP. C W.B. D.B TC 2,99 2,90 2,76 2,59 2,39 CM 0,95 1,01 1,09 1,19 1,30 21 SHC 2,05 2,01 1,94 1,86 1,76 23 SHC 2,32 2,27 2,21 2,12 2, SHC 2,59 2,53 2,47 2,38 2,29 27 SHC 2,86 2,80 2,73 2,59 2,39 29 SHC 2,99 2,90 2,76 2,59 2,39 31 SHC 2,99 2,90 2,76 2,59 2,39 TC 3,23 3,11 2,96 2,78 2,56 CM 0,97 1,04 1,11 1,23 1,33 21 SHC 1,79 1,74 1,67 1,59 1,49 23 SHC 2,06 2,00 1,93 1,85 1, SHC 2,33 2,27 2,20 2,12 2,01 27 SHC 2,60 2,53 2,46 2,38 2,28 29 SHC 2,88 2,79 2,73 2,64 2,54 31 SHC 3,14 3,05 2,96 2,78 2,56 TC 3,42 3,31 #3,15 2,96 2,73 CM 1,02 1,07 1,15 1,26 1,37 21 SHC 1,50 1,45 1,38 1,30 1,21 23 SHC 1,76 1,72 1,65 1,57 1, SHC 2,02 1,98 1,91 1,84 1,73 27 SHC 2,28 2,25 2,18 2,10 2,00 29 SHC 2,53 2,51 2,44 2,36 2,26 31 SHC 2,80 2,77 2,70 2,62 2,53 TC 3,63 3,51 3,34 3,14 2,89 CM 1,04 1,10 1,19 1,30 1,41 23 SHC 1,48 1,43 1,36 1,28 1, SHC 1,73 1,69 1,63 1,55 1,45 27 SHC 2,00 1,96 1,89 1,81 1,71 29 SHC 2,25 2,22 2,16 2,07 1,98 31 SHC 2,52 2,49 2,42 2,34 2,25 TC 3,88 3,71 3,51 3,28 3,05 CM 1,06 1,13 1,21 1,33 1, SHC 1,45 1,39 1,31 1,23 1,15 27 SHC 1,70 1,65 1,58 1,49 1,41 29 SHC 1,96 1,92 1,84 1,76 1,68 31 SHC 2,24 2,18 2,10 2,02 1,94 TC : Total Cooling Capacity KW SHC : Sensible Heat Capacity KW CM : Compressor Input KW Rating Condition (#Mark) are Outdoor Ambient Temperature Indoor Unit Entering Air Temp 35 C D.B. 27 C D.B / 19 C W.B. 12

16 5-3 Heating Capacity Heating capacity ratio (%) Point of Rating Condition Outdoor temperature ( C D.B.) NOTE 1) Point of Rating condition Black dot in the chart indicate the following rating condition. Indoor: 20 C D.B. Outdoor: 7 C D.B. / 6 C W.B. 2) Above characteristics indicate instantaneous operation, which does no take into account defrost operation. 3) Fan speed: High 4) Because this air conditioner heats a room by drawing in the heat of the outside air (heat pump system),the heating efficiency will fall when the outdoor temperature is very low. If sufficient heat cannot be obtained with this air conditioner, user another heating appliance in conjunction with it. 13

17 6.ELECTRICAL DATA 6-1 Electrical Characteristics COOLING MCA R Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 230 V 50 Hz Rating Conditions Running Amps. A Power Input KW Full Load Conditions Running Amps A Power Input KW Rating Condition : Indoor air Temperature 27 C D.B. / 19 C W.B. Outdoor Air Temperature 35 C D.B. Full Load condition : Indoor Air Temperature 32 C D.B. / 23 C W.B. Outdoor Air Temperature 4. C D.B. HEATING MCA R Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 230 V 50 Hz Rating Conditions Running Amps. A Power Input KW Full Load Conditions Running Amps A Power Input KW Rating Condition : Indoor air Temperature 20 C D.B Outdoor Air Temperature 7 C D.B./ 6 C W.B. Full Load condition : Indoor Air Temperature 27 C D.B. Outdoor Air Temperature 24. C D.B. / 18 C W.B. 14

18 6-2 Electric Wiring Diagrams WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts Legend CM Compressor Motor C1,C2,C3 Capacitor FLP Louvers Motor FMO Outdoor Fan Motor FMI Indoor Fan Motor REC ASSY Remote Control PCB1 Indoor PC board TH1,TH2 Thermistor TP1,TP2 Terminal Plate 15

19 7-1 Cool Mode Operation (RT - SPT) [ o c] over 3 min over 5 min COMP ON OFF OFAN ON OFF H over 30 sec IFAN M L RV ON OFF In Cool Mode, the operation of the Compressor (COMP), Outdoor Fan (OFAN) and Indoor Fan (IFAN) are determined by the difference between the Room Temperature (RT) and the Set Point Temperature (SPT) as in the graph above. Notes: 1. In this graph, the IFAN is operating in the Auto Fan Speed setting. If the user has selected the low, medium or high fan speed, the IFAN will run constantly at that speed only. 2. In addition to the value of (RT-SPT), the operations of the relays are also controlled by protection delays. For example, (a) the minimum On/Off time of the COMP is 5 min and 3 min respectively, and (b) the IFAN can change speed only after it has operated at the same speed for 30 sec. 16

20 7-2 Heat Mode Operation (RT - SPT) [ o c] COMP ON OFF H 30 sec IFAN M L OFF RV ON OFF Note 1 Note 2 The Heat Mode operation is similar to the Cool Mode operation. The COMP, OFAN and IFAN are mainly controlled by the value of (RT SPT). In the graph above, the IFAN is operating in Auto Fan speed mode. Therefore, the IFAN speed changes automatically according to the (RT - SPT). Note 1: The 30s IFAN operation is for purging the heat from the in-coil after COMP has stopped. Note 2: The IFAN will not be turned on until the in-coil temperature is high enough (as shown in the graph below) to prevent the unit from supplying cool air. IFAN Speed Any Low Stop ICT = Any = Low = In-coil Temperature Hi, Med or Low fan speed which is selected by the user. In Auto Fan Speed Mode, the fan speed is selected by the unit automatically instead. The indoor fan is forced to operate at low speed ICT [ o c] 17

21 7-3 Auto (Cool/Heat) Mode Operation (RT - SPT) [ o c] COMP & OFAN ON OFF ON RV OFF Auto Heat Mode Auto Cool Mode Auto Heat Mode In Auto Mode, the unit switches between the Auto Cooling Mode and Auto Heating Mode automatically to maintain the room temperature (RT) at the set point temperature (SPT). 18

22 7-4 Dry Mode Operation (RT - SPT) [ o c] Time [min] -2 DRY DRY-ON DRY-OFF IFAN COMP & OFAN LOW OFF ON OFF 5 minutes COMP ON time Max 15 minutes 3.5 min Max 15 minutes 6 min (Note 1) (Note 2) In Dry Mode, the unit operates in a mild cool mode to lower the humidity of the room. In order to maintain a high efficiency in the drying operation without over lowering the room temperature excessively, the Dry Mode is different from the Cool Mode in two ways. 1. The IFAN is forced to operate at low speed only. And, the IFAN is turned off with the COMP. 2. The unit operates in either the Dry-on state or the Dry-off state. If RT = SPT, the unit will operate in Dry-off state. The COMP is forced to operate for 6 min after it has stopped working for 15 min. If RT > SPT, the unit will operate in Dry-on state. The COMP is forced off for 3.5 min after it has been working for 15 min. Note 1: COMP is forced off in Dry-on state. Note 2: COMP is forced to operate in Dry-off state. 7-5 Fan Mode Operation In Fan Mode, the indoor fan is turned on to improve the air circulation in the room. COMP and OFAN remain OFF all the time. Note: If the user has selected the Auto Fan Speed setting, the IFAN speed would be selected by the unit automatically according to the difference between RT and SPT, as in Cool Mode. 19

23 7-6 Protection Operations in Cool and Dry Modes 1. Indoor Coil Defrost Protection The in-coil defrost protection can prevent the ice formation at the in-coil when the ambient temperature is low. ICT [ o c] t1 t2 t3 OFAN ON OFF COMP ON OFF IFAN ON OFF t1 = 5 min minimum for each COMP starting t2 = OFAN cycling (alternate between ON and OFF every 30 sec) for 20 min maximum t3 = COMP and OFAN stop for 10 min minimum 20 17

24 2. Outdoor Coil High Pressure Protection The out-coil high pressure protection prevent the build up of high pressure at the out-coil during cooling operation. OCT [ o c] COMP ANY OFF COMP is forced OFF OFAN ANY ON OFAN follow operation of COMP OFAN is forced ON (Note 1) IFAN ANY L IFAN is forced LOW OPER LED ON BLINK Note 1: In some applications, the outdoor fan and the compressor are controlled together by the COMP relay output from the controller. In this case, it will take more time for the out-coil to cool down during the high pressure protection, because the outdoor fan will be turned off with the compressor instead of working as in the graph above. 21

25 7-7 Protection Operations in Heat Mode Outdoor Coil Deice Protection The deice process is controlled by an Ice Detection Algorithm (IDA). The IDA is an unique control algorithm incorporated to maintain optimal utilization of the heat pump capacity, especially in below-zero outdoor temperature condition. The out-coil deicing will be activated not only by static temperature detection as normally done, but also while ice forming is detected on the out-coil. COMP to ON DI = 40 (or 10) DT = 5 1 Activate DDt setting Routine Start counting TLD DTF = 0 No OCT < DOC? No TLD > DI & OCT < DST (during last 3 minutes) Yes DDT and DTF information from Deicing Dynamic Threshold setting routine DTF=1 & OCT < DDT No (during last 3 minutes) & ICT < 40 deg Yes Yes Deicer activation (see Notes) Deicer activation (see Notes) LDT > DT + TimeD No LDT < DT-TimeD or LDT < DTmin No Yes Yes DI = TLD - DIT DI = TLD + DIT DI = TLD No DI < DImin Yes DI = DImin No DI > DImax Yes DI = DImax DT = LDT 1 22

26 1st COMP start, OR deice complete Yes No Reset TLD cnt to 0 DTF = 0 IFAN/OFAN speed change Yes No Reset SCT cnt to 0 DTF = 0 TLD > TST AND SCT > SCD Yes No DDT = OCT - TempD DTF = 1 DDT and DTF information to main algorithm Explanation: The Ice Forming Detection will be done by two algorithms 1. In Dynamic Temp Detection, the ice formation will be detected by (i) Compare the OCT with a Deicing Dynamic Temperature Threshold, and (ii) Detect the drop in ICT which accompany the ice formation. 2. The Static Temp Detection will be done by comparing the OCT with a Deicing Static Temperature Threshold. The Deicing Data Record is used to determine the time delay between two deicing cycles. In general, the time delay will be increased if the last deicing cycle can be completed quickly. 23

27 7-7-2Indoor Coil High Pressure Protection in Heat Mode The in-coil high pressure protection prevent the build up of high pressure at the in-coil during heating operation. ICT [ o c] 64 A B COMP ANY OFF COMP is forced OFF OFAN ANY OFF Note: The operation temperatures shown as A and B in the chart differ by models. MCA201R MCA271R MCA351R A B

28 7-8 Cold Draft Prevention (Heating) This function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat exchange coil have sufficiently warmed up. When 10 minutes has elapsed, the fan speed is automatically switched to set speed regardless of indoor heat exchange coil temperature. Indoor heat exchange coil temp. ( C) Max.10 minutes Tc Indoor Fan OFF Set Speed NOTE The operation temperature shown as Tc in the chart differ by models. MCA201R MCA271R MCA351R Tc

29 7-9-1 Sleep Function Room temperature is automatically controlled to compensate for body temperature variations while sleeping. This mode of operation is designed for maximal comfort in both COOL and HEAT modes. RT 7-12 Hours Sleep operation Unit is turned to SB after Sleep SPT+3 SPT+2 Cool, Dry modes SPT+1 SPT SPT-1 SPT-2 SPT-3 Heat mode Start Sleep Time [Hr] Daily Timer Function Unit can be programmed to be ON and OFF automatically at preset time everyday, by using a remote controller. The resolutions of the ON/OFF timers are 10 min IFEEL Function This feature is provided if the unit is used together with a remote controller with the I-FEEL function. When this function is selected, the remote controller sends the room temperature measured by its build-in thermistor to the air con for more accurate temperature control Louver Control The airflow louver can be driven by either a 12V DC stepping motor or an AC motor. The louver can be set to operate at auto swing mode or fix position mode. Three additional features are provided if the louver is controlled by a DC stepping motor.? Different swing positions (range) for Heat Mode and Cool Mode operation? Last louver position in fix position mode is stored in the EEPROM, and is restored when the unit is turned on.? The louver is closed automatically when the unit is switched to standby mode. 26

30 7-9-5 Manual Unit Control and LED indicators The push button switch and the LED indicators on the display panel let the user to control the unit operation without a remote controller. Their operations are provided below. LED indicators: STAND BY INDICATOR OPERATION INDICATOR TIMER INDICATOR 1. Lights up when the Air Conditioner is connected to power and ready to receive the R/C commands 2. Blinks continuously in case of any thermistor failure. 1. Lights up in operation mode (Note: OFF in standby mode). 2. Blinks for 0.5 sec., to announce that a R/C infrared signal has been received and stored. 3. Blinks continuously during? OCT High Pressure Protection Mode? Deicing in Heating Mode 1. Lights up during Timer and Sleep operation. 2. Active On/Off timer setting will become invalid after a power failure. When this happens, the unit is forced to restart in STBY mode, and the Timer Indicator is blinked continuously until (i) the unit is switched to OPER Mode again, or (ii) any message from the R/C is received. Push Button switches: MODE BUTTON (Cool, Heat, SB) Use to cycle the operation mode of the A/C unit among COOL, HEAT and SB modes, without using the R/C. Every time this switch is pressed, the next operation mode is selected, in the order : SB => Cool Mode => Heat Mode => SB => Recovery from Power Failure Last unit settings (SPT, operation mode, louver settings, etc) are saved in the EEPROM in the unit. In case of power failure, these settings are restored automatically. 27

31 8.TROUBLESHOOTING 8-1 Check before and after troubleshooting WARNING Hazardous voltage can cause ELECTRICAL SCHOCK or DEATH. Disconnect power or turn off circuit breaker before you start checking or servicing. 8-2 Check power supply wiring Check that power supply wires are connected to terminals L and N on the terminal plate in the indoor unit. 8-3 Check indoor unit wiring Check that inter-unit wiring is correctly connected to the outdoor unit from the indoor unit 8-4 Check power supply Check that voltage is in specified range (+/- 10% of the rating) Check that power is being supplied. 8-5 Check lead wires and connectors in indoor and outdoor units Check that coating of lead wires is not damaged Check that lead wires and connectors are firmly connected Check that wiring is correct. 28

32 8-6 Air Conditioner does not operate Circuit breaker trips (or fuse blows). A. when the circuit breaker is set to ON, it is tripped soon.(resetting is not possible) There is possibility of ground fault Check insulation resistance If resistance value is 2MΩor less, insulation is defective ( NO ) WARNING 1 Remove inter-unit wires from terminal platea in outdoor unit Mesaure insulation resistance of outdoor unit. NO Insulation of outdoor unit is defective Measure insulation resiatance of electical parts in outdoor unit. 2 Remove inter-unit wires from terminal plate un outdoor unit. Then, pull the power plug out of the wall outlet. Measure insulation resistance of indoor unit NO Insulation of indoor unit is detective. Measure insulation resiatance of electical parts in indoor unit. 29

33 B. Circuit breaker trips in several minutes after turning the air conditioner on. There is a possibility of short circuit Check capacity of circuit breaker. Capacity of circuit breaker is suitable. Measure resistance of outdoor fan motor winding NO Replace with suitable one (lager capacity) In case of Heating operation: Measure resistance of 4-way valve s winding Measure resisatnce of compressormotor winding Neither indoor nor outdoor unit runs A. Power is not supplied Check power supply. Power is being supplied to the indoor unit B. Check Push bottom selector in the indoor unit. Circuit breaker i tripped Power failure Reset breaker Wait for recovery or contact power company Push the button switch under the indoor unit pannel. The indoor unit and outdoor unit doesn t runs Indoor PCB Ass y is defective C. Check remote control unit Try to run with another remote control unit. OK First remote control unit is detective. Check for residue buildup on transmitter of remote control unit Clean transmitter.. Check for residue buildup on remote control receiver on front of indoor unit. 30 Clean Receiver.

34 D. Check fuse on the indoor PCB Ass y Check fuse on indoor PCB Ass y for continuity OK Measure resistance of indoor and outdoor fan motor winding OK Check operation lamp to see if light is ON Measure resistance of compressor motor winding Light is OFF OK Measure resistance of primari and secondary winding of transformer Measure coil resistance of power relay in outdoor unit. Indoor PCB Ass y is detective. Replace the fuse E. Check TIMER on the remote control unit Timer i turned On.Check to see YES if is displayed on remote control Cancel the timer mode push the buttom CLEAR Only outdoor unit does not run A Check setting temperature COOL HEAT Is room temperature too low? Is room temperature too high? NO Try to lower setting temperature by temperature setting button Outdoor unit still does not run NO Try to raise setting temperature by temperature setting button Outdoor unit still does not run Try to use another remote control unit Try to use another remote control unit OK OK Remote control unit is defective Remote control unit is defective 31

35 B Check PCB Ass y in either indoor or outdoor unit Indoor PCB Ass y is defective Only indoor unit does not run Indoor PCB Ass y is defective 8-7 Some part of air conditioner does not operate Only indoor fan does not run Check fan rotation Turn fan gently once or twice by hand Fan cannot be turned Check fan casing foreign matter on inside Fan motor burnout or foreign matter in bearings Remove foreign matter or repair Repair or replace Measure resistance of indoor fan motor winding OK Check fan motor capacitor Only flap motor does not run Measure resistance of flap motor winding 32

36 8-7-3 Only outdoor fan does not run Check fan rotation Turn fan gently once or twice by hand Fan cannot be turned Check fan casing foreign matter on inside Fan motor burnout or foreign matter in bearings Remove foreign matter or repair Repair or replace Measure resistance of outdoor fan motor winding OK Check fan motor capacitor 8-7-4Only compressor does not run Check compressor motor capacitor (C1) Overload Klixon is working YES Measure resistance of compressor motor winding Temperature of compressor is abnormally high. YES Refigerant gas shortage YES Recover refrigerant NO NO Measure power supplì voltage. The voltage is too low Rotor may be locked up Evacuate the air conditioner Measure winding resistance of power relay YES Replacement compressor Charge refrigerant. 33

37 8-8 Air conditioner operates, but abnormalities are observed Operation does not switch from HEAT to COOL (or COOL to HEAT). Remote control unit may be detective. Reciver in lamp Ass y may be detective. Measure resistance of 4-way valve s winding COOL HEAT Check voltage between terminals No.1 and N, must be 230 VAC No voltage appears OK Check wiring connection Indoor PCB Ass y is defective HEAT COOL Check voltege between terminals No. 1 and N, must be 0 Volt 34

38 8-9 If a sensor is defective ICT (indoor coil sensor) OCT(outdoor coil sensor) RAT (room ambient temperatur) are defetive. Stand by lamp on front side of indoor unit is flashing on and off. (*) YES Thermistor ICT and OCT and RAT are defective YES Repalce thermistor. NOTE Allarm signal (*) Stan by lampoon the front side of the indoor unit will flash on and off when the thermistor is defective. At the same time the outdoor unit will stop. Indoor operate only for ventilation. Temparature sensor Lead wires 35

39 9.CHECKING ELECTRICAL COMPONENTS 9-1 Measurement of Insulatipon Resisatnce The insulation is good condition if the resistance exceeds 2MΩ 9-1-1Power Supply Wires Clamp the grounding terminal of the power plug with a lead clip of the insulation resistance tester and measure the resistance by placing a probe on either of the two power terminals.(fig 1) Then, also measure resistance between the grounding and other power terminals (Fig 1) NOTE The shape of the power plug may differ from that of the air conditioner which you are servicing Indoor Unit Clamp an aluminium plate fin or copper with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw where power supply lines are connected on the terminal plate.(fig 2) Outdoor Unit Fig. 2 Clamp an aluminium plate fin or copper with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw on the terminal plate.(fig 2). Note that ground line terminal should be skipped 9-2 Measurement of Insulation resistance for electrical Parts Disconnect the lead wires of the desired electric part from terminal plate, capacitor, etc. Similarly disconnect the connector. Then measure the insulation resistance. (Fig 3 and 4) Fig. 3 NOTE Refer to Electric Wiring Diagram If the probe cannot enter the poles because the hole is too narrow the use a probe with a thinner pin Fig. 4 36

40 9-2-1 Measurement continuity of the Fuse The fuse is situated on Indoor PCB Ass y (Fig 5) Disconnect the fuse from PCB Ass y. Then check if there is continuity on the fuse(fig 6) Measure the Capacity of the Run Capacitor Disconnect the lead wires of the desired electric part from terminal plate. Similarly disconnect the connector. Then measure the capacity. (Fig 7) Fig. 7 Fig. 5 Fig. 6 37

41 R.D. 28 Reyrieux BP Trévoux CEDEX France Tél Fax R.C.S. Bourg-en-Bresse B

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: MCAF72R5TA- MCAF92R5TA- MCAF122R5TA-

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: MCAF72R5TA- MCAF92R5TA- MCAF122R5TA- TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: MCAF72R5TA- MCAF92R5TA- MCAF122R5TA- SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MCAF72R5TA- 387104015 MCAF92R5TA- 387104016 MCAF122R5TA- 387104017

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: GRF188R5TAA GRF228R5TAA GRF228R7TAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. GRF188R5TAA 38.7107.083 GRF228R5TAA 38.7107.084 GRF228R7TAA 38.7107.085

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF94R5 CAF124R5 SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. CAF94R5 387106979 CAF124R5 387106980 0.8180.361.0 07/2005 IMPORTANT! Please read before

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT:. TRIAL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. 38.7107.102. 0.8180.611.02 09/2012 IMPORTANT! Please read before installation This air conditioning

More information

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA 0.8180.472.0 07/2005 Page 1. SPECIFICATIONS 3 1-1 Unit Specifications 3 1-2 Major Component Specifications 4 2. DIMENSIONAL DATA 6 2-1 Unit Dimensions 6 3. ELECTRICAL

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: AE726SCL AE752SCL AE71SCL3 AE735SCL AE752SCL3 AE100SCL3 AE764SCL3 AE125SCL3 SPLIT SYSTEM AIR CONDITIONER Model No. AE726SCL AE735SCL AE752SCL AE752SCL3 AE764SCL3

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: ASR609CL ASR612CL ASR609CL ASR612CL

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: ASR609CL ASR612CL ASR609CL ASR612CL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: ASR609CL ASR612CL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. ASR609CL 387006970 ASR612CL 387006971 0.8180.250.0 05/2002 IMPORTANT! Please read

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF97R5IAA CAF98MR5IAA CAF127R5IAA CAF128MR5IAA CAF187R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. CAF97R5IAA CAF127R5IAA CAF187R5IAA CAF98MR5IAA CAF128MR5IAA

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL KS1872 + C1872 + CL1872 KS2472 + C2472 + CL2472 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KS1872 KS2472 Product

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AE22AH 387031006 AE28AH 387031007 AE38AH 387031008

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CLM97 CLM7 CLM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No.

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL HEAT PUMP MODELS INDOOR UNIT: MPAF188R5TAA MPAF228R5TAA COOLING MODELS MPAF188C5TAA MPAF228C5TAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MPAF188R5TAA 38.7104.033

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL AW22AL AW28AL AW38AL

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL AW22AL AW28AL AW38AL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW22AL 387030005 AW28AL 387030006 AW38AL 387030007 AW42AL 387030094 0.8180.467.0

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA

More information

SPLIT SYSTEM AIR CONDITIONER

SPLIT SYSTEM AIR CONDITIONER TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: MRAF99R5IAA MRAF129R5IAA MPAF99R5IAA MPAF129R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MRAF99R5IAA 38.7104.065 MRAF129R5IAA 38.7104.062 MPAF99R5IAA

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: DUAL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. 38.7107.098 38.7107.103 38.7107.106 0.8180.597.03 09/2012 IMPORTANT! Please read before installation

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513 TECHNICAL & SERVICE MANUAL SA 123A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-123A 1 851 006 95 Australia SA 123A REFERENCE NO. SM700513 IMPORTANT! Please Read Before

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A TECHNICAL & SERVICE MANUAL SA 183A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. SA-183A 1 851 006 96 Destination Australia SA 183A REFERENCE NO. SM700514 IMPORTANT! Please Read Before

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338 TECHNICAL & SERVICE MANUAL SA 128S5 FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-128S5-A 1 851 004 09 General (50Hz) & Europe SA 128S5 REFERENCE NO. SM700338 IMPORTANT!

More information

TECHNICAL DATA & SERVICE MANUAL MULTI-SPLIT SYSTEM AIR CONDITIONER

TECHNICAL DATA & SERVICE MANUAL MULTI-SPLIT SYSTEM AIR CONDITIONER TECHNICAL DATA & SERVICE MANUAL Outdoor Unit GR54M2C Indoor Unit MCA27MC (X2) MULTI-SPLIT SYSTEM AIR CONDITIONER Indoor Unit Outdoor Unit MCA27MC GR54M2C 0.8180.195.0 04/2001 IMPORTANT! Please Read Before

More information

TECHNICAL & SERVICE MANUAL SAP K181A + SAP C181A

TECHNICAL & SERVICE MANUAL SAP K181A + SAP C181A TECHNICAL & SERVICE MANUAL SAP K181A SAP K241A + SAP C181A + SAP C241A FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K181A S 1 852 068 06 SAP K241A

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 93AH FILE NO. SA 93AH REFERENCE NO. SM700510

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 93AH FILE NO. SA 93AH REFERENCE NO. SM700510 TECHNICAL & SERVICE MANUAL SA 93AH FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-93AH 1 851 006 97 Australia SA 93AH REFERENCE NO. SM700510 IMPORTANT! Please Read Before

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K303A + SAP C303A FILE NO. REFERENCE NO. SM Destination: Australia

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K303A + SAP C303A FILE NO. REFERENCE NO. SM Destination: Australia AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP K303A + SAP C303A FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K303A A 1 852 098 83 Outdoor Model No.

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K301AH + SAP C301AH FILE NO. SAP K301AH SAP C301AH REFERENCE NO.

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K301AH + SAP C301AH FILE NO. SAP K301AH SAP C301AH REFERENCE NO. TECHNICAL & SERVICE MANUAL SAP K301AH + SAP C301AH FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K301AH S 1 852 071 34 Outdoor Model No. Product Code

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL AWR222CLE - AER222SC AWR222CLE - AER222SC3 SPLIT SYSTEM AIR CONDITIONER 0.8180.076.0 03/00 Important! Please Read Before Starting This air conditioning system meets strict safety

More information

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA ARGO 245C / 3SC Cooling only model ARGO 235H / 3HP Heat pump model 0.8180.405.2 09/2006 Table of contents Page A SPECIFICATIONS 1) Unit specifications 3

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL XH7R / CH7R, C7R XH7R / CH7R, C7R XH7R / CH7R, C7R TH7R / CH7R, C7R TH7R / CH7R, C7R TH7R / CH7R, C7R THH7R / CH7R THH7R / CH7R FILE NO. KH7R / CH7R, C7R KH07R / CH07R,

More information

SPLIT SYSTEM AIR CONDITIONER

SPLIT SYSTEM AIR CONDITIONER TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: MPAFIA0R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MPAFIA0R5IAA 38.7104.074 0.8180.590.01 10/2012 IMPORTANT! Please read before installation

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL XHS1271 & PNR-XS1872 + CH1271 XHS1872 & PNR-XS1872 + CH1872 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) XHS1271

More information

MULTI-SPLIT SYSTEM AIR CONDITIONER

MULTI-SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP KM97AHA ( 2) + SAP CM1827AHA FILE NO. Destination: Australia MULTI-SPLIT SYSTEM AIR CDITIER Indoor Model No Product Code No. Outdoor Model No. Product Code No. SAP KM97AHA

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL MCAF94R5IAA + GRF97R5I MCAF124R5IAA + GRF127R5I FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. MCAF94R5IAA

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL XS171 & PNRXS187 + C171 XS171 & PNRXS187 + CL171 XS187 & PNRXS187 + CH187 XS187 & PNRXS187 + CL187 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL KS0971 + C0971 + CL0971 KS1271 + C1271 + CL1271 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KS0971 KS1271 Product

More information

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA ARGO 245SCH2O( I ) Cooling only model ARGO 235HPH2O( I ) Heat pump model 0.8180.519.1 11 / 2007 Table of contents Page A SPECIFICATIONS 1) Unit specifications

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 19,100 BTU/h,200 BTU/h 30,600 BTU/h Outdoor Model No. CU-3KE19NBU CU-4KE24NBU

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL REVE DCI HPL/SCL 0.8180.615.01 06/2012 Pagina 1 Table of contents Page A SPECIFICATIONS 1) Unit specifications 3 2) Major Component specifications 4 B OPERATING RANGE 6

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL KHS308 + CH308 KHS368 + CH368 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KHS308 KHS368 Product Code No. 85 354 8 85 354 9 Outdoor

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KE30NKU + CU-KE30NKU CS-KE36NKU + CU-KE36NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KE30NKU CS-KE36NKU Product Code No. 1 852 360 88

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL TECHNICAL & SERVICE MANUAL INDOOR UNIT: MCAF94MR5IAA MCAF124MR5IAA MCAF184MR5IAA MCAF244MR5IAA NOV.2003 Destination: General area (50Hz) Europe (50Hz) Australia (50Hz) General area (60Hz) DC INVERTER MULTI-SYSTEM

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS - Wall-mount indoor unit - OPERATING LIMITS Cooling Maximum conditions Heating Maximum conditions Outdoor temperature : 122 F (50 C) D.B. Outdoor temperature : 75 F (24 C) D.B.

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : KMS0772 FILE NO. KMS0972 KMS1272 KMS1872 KMS2472 Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL MCAF88R5I + GRF86R5I MCAF48R5I + GRF46R5I FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. MCAF88R5I MCAF88R5IAA

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KS30NKU + CU-KS30NKUA CS-KS36NKU + CU-KS36NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KS30NKU CS-KS36NKU Product Code No. 852 360 86

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL XHS7 & PNRXS87 + CH7 XHS87 & PNRXS87 + CH87 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) XHS7 (PNRXS87) XHS87 (PNRXS87)

More information

Part 3 Troubleshooting

Part 3 Troubleshooting Part Troubleshooting What is in this part? This part contains the following chapters: Chapter See page Troubleshooting 2 Error Codes: Hydro-box 7 Error Codes: Outdoor Units Error Codes: System Malfunctions

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE9NB4U & CZ-18BT1U CS-MKE12NB4U & CZ-18BT1U CS-KE18NB4UW & CZ-18BT1U DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 9,000BTU / h 11,900BTU / h 17,500BTU

More information

Room Air Conditioner CONTENTS CS-E9BKP CU-E9BKP5 CS-E12BKP CU-E12BKP5. Order No: MAC C2

Room Air Conditioner CONTENTS CS-E9BKP CU-E9BKP5 CS-E12BKP CU-E12BKP5. Order No: MAC C2 Order No: MAC008C Room Air Conditioner CS-E9BKP CU-E9BKP5 CS-EBKP CU-EBKP5 CONTENTS Page Page Features Functions Product Specifications 6 Dimensions 0 5 Refrigeration Cycle Diagram 6 Block Diagram 7 Wiring

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU / h 11,900BTU / h 17,500BTU / h 24,200BTU / h

DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU / h 11,900BTU / h 17,500BTU / h 24,200BTU / h AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKS7NKU CS-MKS9NKU CS-MKS12NKU CS-MKS18NKU CS-MKS24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : MCAF78MR5I MCAF98MR5I MCAF128MR5I MCAF188R5I MCAF248R5I FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity

More information

TEST RUN SERVICE MANUAL

TEST RUN SERVICE MANUAL TEST RUN SERVICE MANUAL Model No. Outdoor Unit ME Class Model Name HP U-MEE 0HP U-0MEE HP U-MEE HP U-MEE HP U-MEE HP U-MEE 0HP U-0MEE U-MEEE U-0MEEE U-MEEE U-MEEE U-MEEE U-MEEE U-0MEEE Indoor Unit Class

More information

INVERTER SPLIT SYSTEM AIR CONDITIONER

INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV91EH + SAP-CRV91EH FILE NO. INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. Outdoor Model No. Product Code No. Destination SAP-KRV91EH 1 852 065

More information

SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS

SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS SPECIFICATION... 1 FUNCTIONS... 5 SERVICE FUNCTION EXPLANATION... 7 OPERATION DETAILS... 8 TROUBLESHOOTING GUIDE... 13 PERFORMANCE

More information

CN Fixed RPM Series REFRIGERANT HEATPUMP R410A

CN Fixed RPM Series REFRIGERANT HEATPUMP R410A CN Fixed RPM Series REFRIGERANT R410A HEATPUMP REV: 01 Oct 2008 LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a Revision# in the footer of each effected page

More information

AUTO COOL DRY FAN SPEED AIR SWING OFF ON TIMER TIMER OFF/ON FAN SPEED MODE TEMP AIR SWING TIMER ON SET OFF CANCEL AC RC SET CHECK CLOCK RESET

AUTO COOL DRY FAN SPEED AIR SWING OFF ON TIMER TIMER OFF/ON FAN SPEED MODE TEMP AIR SWING TIMER ON SET OFF CANCEL AC RC SET CHECK CLOCK RESET AUTO COOL DRY MODE TIMER ON OFF TIMER OFF/ON TEMP ON TIMER FAN SPEED AIR SWING SET 1 2 3 FAN SPEED AIR SWING OFF CANCEL AC RC SET CHECK CLOCK RESET Order No: PAPAMY1611008CE Indoor Unit CS-MPS9SKH CS-MPS12SKH

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE FILE. SVM-04004-3 SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-13UKHP-E3 / RAS-13UAH-E3 RAS-10UKHP-E3 / RAS-10UAH-E3 RAS-07UKHP-E3 / RAS-07UAH-E3 RAS-13UKP-E3 / RAS-13UA-E3 RAS-10UKP-E3 / RAS-10UA-E3

More information

Wall Mounted Split Systems

Wall Mounted Split Systems MWM - 2005 Wall Mounted Split Systems Models: MWM 007F/FR MWM 010F/FR MWM 015F/FR MWM 020F/FR MWM 025F/FR MWM 030F/FR Contents Features... 1 Nomenclature... 2 Specifications... 3 Performance Table... 11

More information

V ~, 50Hz 1Ph. High Wall Split Systems Heat Pump 9K - 12K - 18K - 24K - 28K. Auto. Auto Fan Speed. Auto. Smart LCD Wireless Control.

V ~, 50Hz 1Ph. High Wall Split Systems Heat Pump 9K - 12K - 18K - 24K - 28K. Auto. Auto Fan Speed. Auto. Smart LCD Wireless Control. HFC4 1 0 A 0-40V ~, 0Hz 1Ph High Wall Split Systems Heat Pump 9K - 1K - 18K - 4K - 8K R-410A Compressor Super Quiet AMS Anti-dust Filters Auto Fan Speed Timer Functions Defrost Protection Smart LCD Wireless

More information

Service Manual. Room Air Conditioner Split Wall-Mounted Type. Applies to: HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1

Service Manual. Room Air Conditioner Split Wall-Mounted Type. Applies to: HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1 Service Manual Room Air Conditioner Split Wall-Mounted Type Applies to: HSG-09CRN1 HSG-12CRN1 HSG-18CRN1 HSG-24CRN1 HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1 NOTE: Please read this first before servicing

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Solenoid Valve Kit For 3WAY VRF System CZ-PXXXHR3 () IMPORTANT! Please Read Before Starting This solenoid Valve kit must be installed by the sales dealer or installer. This information

More information

Service Manual. Compact Series REFRIGERANT R407C R22 COOLING ONLY HEAT PUMP. Indoor Units Outdoor Units IOD 7 CON 7 IOD 9 CON 9 IOD 12 CON 12

Service Manual. Compact Series REFRIGERANT R407C R22 COOLING ONLY HEAT PUMP. Indoor Units Outdoor Units IOD 7 CON 7 IOD 9 CON 9 IOD 12 CON 12 Service Manual Compact Series Indoor Units Outdoor Units IOD 7 CON 7 IOD 9 CON 9 IOD 12 CON 12 REFRIGERANT R407C R22 COOLING ONLY HEAT PUMP SEPTEMBER - 2005 LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES

More information

Service Manual & Installation Manual

Service Manual & Installation Manual GE Consumer & Industrial Appliances Service Manual & Installation Manual Split System Air Conditioner Model numbers: GE AIR F24 GE AIR F34 GE AIR F41 1 2 3 Introduction and Features Model Remarks GE AIR

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH530 Models MU-GE50VB- E1 - E1 Indoor unit service manual MS/MSH-GE VB Series (OBH529) CONTENTS 1. TECHNICAL CHANGES 2 2. PART

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE OUTDOOR AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE DR_AS037EF_01 2016.12.05 Notices: Product

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE -(1) SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-24UKHP-E3 / RAS-24UAH-E3 RAS-18UKHP-E3 / RAS-18UAH-E3 RAS-24UKP-E3 / RAS-24UA-E3 RAS-18UKP-E3 / RAS-18UA-E3 RAS-24UKP-AR3 / RAS-24UA-AR3 RAS-18UKP-AR3

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL For Extra Cold Climate Area INDOOR ASU18RLF ASU24RLF OUTDOOR AOU18RLXFWH AOU24RLXFWH DR_AS014EF_04 2017.03.10 Notices: Product specifications

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA OUTDOOR AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA DR_AS049EF_02 2017.10.11 Notices: Product

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless Split System Sizes 09 to 36 Installation Instructions NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS

More information

High Wall Split Systems Cool Only 9K - 12K - 18K - 24K. Auto. Auto. Fan Speed. Smart LCD Wireless Control. Auto Mode.

High Wall Split Systems Cool Only 9K - 12K - 18K - 24K. Auto. Auto. Fan Speed. Smart LCD Wireless Control. Auto Mode. HFC4 1 0 A 0-40V ~, 0Hz 1Ph High Wall Split Systems Cool Only 9K - 1K - 18K - 4K R-410A IAQ $ Auto Auto Fan Speed Timer s Easy Flexible Installation Smart LCD Wireless Control Auto Mode Auto Restart Easy

More information

XLF Series REFRIGERANT R410A HEAT PUMP COOLING ONLY SM XLF 1-A.1 GB

XLF Series REFRIGERANT R410A HEAT PUMP COOLING ONLY SM XLF 1-A.1 GB XLF Series Indoor Units XLF 9 XLF 12 Outdoor Units ONG3-9 ONG3-12 REFRIGERANT R410A HEAT PUMP COOLING ONLY AUGUST 2008 LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated

More information

YC ON-OFF SERIES. Service Manual

YC ON-OFF SERIES. Service Manual YC ON-OFF SERIES Service Manual CONTENTS 1. Precaution... 3 1.1 Safety Precaution... 3 1.2 Warning... 3 2. Model Lists... 6 3. Dimension... 7 3.1 Indoor Unit... 7 3.2 Outdoor Unit... 11 4. Refrigerant

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : MPAF90MRI MPAF0MRI MPAF80RI MPAF0RI DC INVERTER MULTISYSTEM AIR CONDITIONER Capacity Indoor Model No..6 kw.0 kw. kw 7.0 kw MPAF90MRI MPAF0MRI MPAF80RI MPAF0RI Wall

More information

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. Please void OBH733 REVISED EDITION-A. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH733 REVISED EDITION-B Models MUZ-GL09NA

More information

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 Indoor unit service manual MSZ-DM VA Series (OBH750) CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES

More information

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF AOU 9RLFW AOURLFW R40A CONTENTS. DESCRIPTION OF EACH CONTROL OPERATION. COOLING

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG18KLCA ASYG24KLCA OUTDOOR AOYG18KLTA AOYG24KLTA DR_AS069EF_01 2018.03.16 Notices: Product specifications and design are subject to

More information

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467. SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-HC35VA- E2 and MUZ-HC35VAB- E2 have been added. Please void OBH467 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH467 REVISED EDITION-B

More information

Service Manual. LEX Series REFRIGERANT R410A COOLING ONLY HEAT PUMP. Indoor Units Outdoor Units LEX 7 ONG 7 LEX 9 ONG 9 LEX 12 ONG 12 LEX 14 ONG 14

Service Manual. LEX Series REFRIGERANT R410A COOLING ONLY HEAT PUMP. Indoor Units Outdoor Units LEX 7 ONG 7 LEX 9 ONG 9 LEX 12 ONG 12 LEX 14 ONG 14 Service Manual LEX Series Indoor Units Outdoor Units LEX 7 ONG 7 LEX 9 ONG 9 LEX 12 ONG 12 LEX 14 ONG 14 REFRIGERANT R410A COOLING ONLY HEAT PUMP JANUARY - 2006 LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE

More information

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH502 Wireless type Models MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA Indoor unit service manual MSZ-D NA Series (OBH501) MSY-D

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G09LTCB AS G12LTCB AS G14LTCB OUTDOOR AO G09LTCN AO G12LTCN AO G14LTCN 1. INDOOR UNIT : AS G09LTCB AS G12LTCB AS G14LTCB DTR_AS057E_01

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 58 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING... 4 DIMENSIONS... 5 CLEARANCES...

More information

TAC-09CS/K TAC-12CS/K TAC-18CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-12CHS/K TAC-18CHS/K TAC-24CHS/K

TAC-09CS/K TAC-12CS/K TAC-18CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-12CHS/K TAC-18CHS/K TAC-24CHS/K TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE040427 Models TAC-07CS/K TAC-09CS/K TAC-2CS/K TAC-8CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-2CHS/K TAC-8CHS/K TAC-24CHS/K CONTENTS. IMPORTANT

More information

Concealed Ducted Split Series R-407C MBH

Concealed Ducted Split Series R-407C MBH Concealed Ducted Split Series R-407C 4-60 MBH Ducted Split with Hermetic Compressor Tropical 50 Hz For more technical information please visit Table of Contents INTRODUCTION NOMENCLATURE UNIT RATING SUMMARY

More information

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE FILE. SVM-05009-2 SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-24UKHP-E4 / RAS-24UAH-E4 RAS-18UKHP-E4 / RAS-18UAH-E4 RAS-24UKP-E4 / RAS-24UA-E4 RAS-18UKP-E4 / RAS-18UA-E4 RAS-24UKP-AR4 / RAS-24UA-AR4

More information

TECHNICAL & SERVICE MANUAL WIRED REMOTE CONTROLLER STK-RCS-7TWSUA FILE NO. Product Code No Model No. STK-RCS-7TWSUA

TECHNICAL & SERVICE MANUAL WIRED REMOTE CONTROLLER STK-RCS-7TWSUA FILE NO. Product Code No Model No. STK-RCS-7TWSUA TECHNICAL & SERVICE MANUAL STK-RCS-7TWSUA FILE NO. Destination: North America WIRED REMOTE CONTROLLER Model No. STK-RCS-7TWSUA Product Code No. 1 852 353 85 REFERENCE NO. SM700799 Important! Please Read

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A09LEC AS A12LEC OUTDOOR AO R09LECN AO R12LECN 1.INDOOR UNIT : AS A09LEC AS A12LEC DTR_AS047E_01 2010.10.05 1. INDOOR UNIT CONTENTS

More information

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A Revision E: Capacity corrections have been corrected [7-1. 2), 3)]. OBH502 REVISED EDITION-D is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH502 REVISED EDITION-E Models MUZ-D30NA / - 1 / -

More information

Ductless Split Air Conditioner

Ductless Split Air Conditioner Ductless Split Air Conditioner Service Manual Indoor HSU09VHG(DB)-W HSUVHG(DB)-W HSU8VHH(DB)-W HSUVHG(DB)-W Outdoor HSU09VHG(DB)-G HSUVHG(DB)-G HSU8VHH(DB)-G HSUVHG(DB)-G Design may vary by model number.

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH Revision D: Capacity corrections have been corrected [7-1. 2), 3)]. OBH684 REVISED EDITION-C is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH684 REVISED EDITION-D Models MUZ-FH06NA MUZ-FH09NA

More information

Hi - Wall Split Systems 12K - 18K - 24K

Hi - Wall Split Systems 12K - 18K - 24K R22 220-240V ~ 50Hz 1Ph Hi - Wall Split Systems 12K - 18K - 24K Technology Tropical Compressor Super Quiet Auto Auto Fan Speed Auto Restart Function Self diagnostic function Active Carbon Electrostatic

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LMCA AS G09LMCA AS G12LMCA AS G14LMCA OUTDOOR AO G07LMCA AO G09LMCA AO G12LMCA AO G14LMCA 1. INDOOR UNIT : AS G07LMCA AS G09LMCA

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AO* R09LECN AO* R12LECN

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AO* R09LECN AO* R12LECN SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS* A09LEC AS* A12LEC AO* R09LECN AO* R12LECN R410A CONTENTS 1. DESCRIPTION OF EACH CONTROL

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

Room Air Conditioner Service and Parts Manual

Room Air Conditioner Service and Parts Manual Cool Dry Temp Mode Room Air Conditioner Service and Parts Manual F Fan Speed hr Timer 0n 0ff Money Saver Fan Only Auto Swing Power CP06 CP08 93011401_01 CONTENTS 1. PREFACE 1.1 SAFETY PRECAUTIONS...2 1.2

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 12 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS... 5 CLEARANCES... 5

More information

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC Revision A: MUZ-HM09/12NA- U8, MUZ-HM09/12NA2- U8, MUZ-HM15/18NA- U1, MUZ-HM15/18NA2- U1 and MUZ-HM24NA2- U1 have been added. Please void OBH747. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A.

More information

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS OWNER S MANUAL High-Wall Fan Coil Unit Page GENERAL 2,3 OPERATING MODES 2 REMOTE CONTROL 2 OPERATION 3-9 REMOTE CONTROL OPERATION 3 INDOOR UNIT DISPLAY 5 EMERGENCY OPERATION 5 PRESSING THE ON/OFF BUTTON

More information

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type)

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) TECHNICAL MANUAL & PARTS LIST DRAFT INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) SRK20ZD-S - 1 - INDOOR UNIT Model SRK20ZD-S OUTDOOR UNIT Model SRC20ZD-S REMOTE

More information

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table)

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table) 1 2 Warning: - Do not place your hand or any other objects into the air outlet and fan. It could damage the heat pump and cause injuries; - In case of any abnormality with the heat pump, cut off the power

More information