H29A Series Compressor Applications. Application Bulletin 139

Size: px
Start display at page:

Download "H29A Series Compressor Applications. Application Bulletin 139"

Transcription

1 H29A Series Compressor Applications Application Bulletin 139

2 Application Bulletin Subject: H29A Series Compressor Applications Number: 139 Release EN: J28319 Date: 4/26/02 Revision EN: Z27301 Date: 10/2/15 This Application Bulletin is for air-to-air air conditioning and heat pump applications only. For other applications or deviations from this Bulletin, please call Bristol s Applications Engineering Department at (276) The Bristol H29A compressors are among the most advanced reciprocating compressors in the industry today. Mechanical design and gas management make the H29A compressors very efficient and quiet. The following guidelines were developed for the H29A compressors through actual system testing as well as laboratory testing. 1.0 Crankcase Heat A crankcase heater is not required on systems when the total system charge is below the compressor charge limitation. Total charge includes the allowance for the tube size and length plus the tolerance of the charging equipment. Immersion type 30 and 40 watt PTCR crankcase heaters are available. To increase the longevity of the compressor bearings a crankcase heater is recommended to prevent liquid refrigerant from migrating into the compressor. Liquid refrigerant can dilute the oil causing excessive bearing wear. Refer to Application Bulletin 135, Crankcase Heaters. Compressors 50,000 BTU and higher should use 40-watt crankcase heaters. 2.0 Accumulators Heat pump systems require an accumulator and all other systems should be tested to see if accumulators will be required to limit liquid refrigerant returning to the compressor (for suggested testing, see Application Bulletin 101, section 4 on Suction Line Accumulators). Systems with a total charge below the compressor charge limitation normally will not require an accumulator. A double-sided see-through sight glass installed in the suction line of the compressor during all tests will assist the system designer in making this decision. Large volumes of liquid refrigerant repeatedly flooding back to the compressor during the off-cycle, defrost cycle or excessive floodback during steady operation can dilute the oil to the point that the bearings are inadequately lubricated, causing excessive bearing wear. 3.0 Motor Protection Inherent internal line break motor protection is provided. 4.0 Starting Characteristics The H29A single-phase compressor employs the highest efficiency motor available today. Because of this ultimate efficiency, the compressor will always need some method of start assist. A PTCR start assist device may be used on systems where the pressure equalizes in the off-cycle. If non-bleed expansion valves are used or other reasons exist that will not allow pressure equalization prior to compressor start-up, then a Page 2

3 start capacitor and potential relay are required. The PTCR device is not required when a start capacitor and relay are used. High torque start components are available for the H29A models. To determine the components needed for each application, start tests must be run at worst case conditions (lowest voltage, highest ambient and highest pressure differential) the unit is designed to operate. PTCR s and start components for each model are listed in Table Excessive Continuous Liquid Floodback Tests The following tests are for all systems including those designed with an accumulator. These tests are used to determine if the system needs design changes. Bristol testing has indicated that adding an accumulator as the only solution to excessive flooding, in most cases, is inadequate. Two excessive liquid floodback tests are required on heat pumps. One for the heating mode and one for cooling. Air conditioners will require the cooling test. The test set up is the same for heat pumps and air conditioners. Before starting the test, thermocouples should be attached to the suction and discharge tubes approximately 10 to 12 inches from the compressor. A thermocouple should also be attached to the sump of the compressor (as close to bottom center as possible, all TCs must be insulated). The system charge for this test should be 20% greater than design specifications using a 25 foot line set. The 20% overcharge simulates commonly found overcharge in the field. The evaporator should be elevated 5 feet above the condensing unit. Should you have any questions, please call Bristol s Applications Engineering Department. 5.1 Heating Mode Excessive Continuous Liquid Floodback Test The defrost control must be disconnected to prevent unit from defrosting. Outdoor ambient must be 17 F DB, 15 F WB and indoor ambient 70 F DB, 60 F WB maximum. Outdoor unit fan motor must be disconnected. Run unit until pressures and temperatures are stabilized. See examples and Discharge superheat should not be less than 50 F. Examples: For R22 at 168 psig discharge, the saturated condensing temperature is 90 F Example No. 1: Assume actual discharge temperature of 140 F Discharge superheat = 140 F- 90 F = 50 F Therefore no system design change is required Example No. 2: Assume actual discharge temperature of 130 F Discharge superheat = 130 F - 90 F = 40 F Therefore system design change is required Note: Discharge superheat may run as low as 10 F (5.6 K) during start-up operation, as long as the temperature increases steadily and exceeds the minimum value before the compressor cycles off. The sump over saturated suction temperature should also be above the minimum value before cycling off. Extended operation is normally required to heat up the oil sump adequately, especially with low discharge superheat. If temperature is less than 50 F, system design must be changed. Page 3

4 5.1.2 Sump temperature should be 30 F warmer than the saturated temperature equivalent of the suction pressure. Example: For R22 at 15 psig suction, the saturated evaporator temperature is -12 F Example No. 1: Assume actual sump temperature of 28 F D temperature = 28 F - (-12 F) = 40 F Therefore no system design change is required Example No. 2: Assume actual sump temperature of 15 F D temperature = 15 F - (-12 F) = 27 F Therefore system design change is required If temperature is less than 30 F, system design must be changed. 5.2 Cooling Mode Excessive Continuous Liquid Floodback Test Operate the system for 1 hour; outdoor unit must be in 95 F DB, 75 F WB ambient and indoor unit at 67 F DB, 57 F WB with evaporator air flow reduced 50% to simulate dirty air filter Discharge superheat should not be less than 50 F. Example: For R22 at 260 psig discharge, the saturated condensing temperature is 120 F Example No. 1: Assume actual discharge temperature of 170 F Discharge superheat = 170 F- 120 F = 50 F Therefore no system design change is required Example No. 2: Assume actual discharge temperature of 150 F Discharge superheat = 150 F F = 30 F Therefore system design change is required If temperature is less than 50 F, system design must be changed Sump temperature should be 50 F warmer than the saturated temperature equivalent of the suction pressure. Example: For R22 at 68 psig suction, the saturated evaporator temperature is 40 F Example No. 1: Assume actual sump temperature of 70 F D temperature = 70 F - 40 F = 30 F Therefore no system design change is required Example No. 2: Assume actual sump temperature of 65 F D temperature = 65 F - 40 F = 25 F Therefore system design change is required If temperature is less than 30 F, system design must be changed. Page 4

5 6.0 Excessive Liquid Floodback Cycling Test This test is run to determine how much liquid actually gets into the compressor during system on/off cycles. To complete this test a sample compressor must be obtained with a sight tube to measure liquid level in the compressor or set the compressor on calibrated scales to measure pounds and ounces. Evaporator should be elevated 5 feet higher than the condensing unit. System charge for this test should be 20% greater than design specifications using a 25 foot line set. Operate the system in the cooling mode for 1 hour before testing at each of the ambient temperatures indicated in Table 1. Shut outdoor unit off (compressor and fan). Keep evaporator blower running. System on/off time and number of cycles is different for each of the 3 tests shown in Table 1. Observe and record the amount of liquid refrigerant (height or weight) at the start of each on cycle. If the compressor slugs or makes a metallic sound on start up, system design change is required. Test No. 1 No. 2 No. 3 Indoor Ambient ( F) Outdoor Ambient ( F) System On-time (Minutes) System Off-time (Minutes) Number of On/Off Table 1 Page 5

6 60 Hertz H29A Electrical Components Model Run Cap µfd/ volts Required Standard PTCR Start Cap High Torque GE Relay 3ARR3*XX* H29A353CBC 40/ C /330 3ARR22*3S* H29A383CBC 45/ C /330 3ARR22*3S* H29A423CBC 45/ C /330 3ARR22*3P* H29A443CBC 45/ C /330 3ARR22*3P* H29A473CBC 55/ C /330 3ARR22*3N* H29A503CBC 55/ C /330 3ARR22*3N* H29A543CBC 60/ C /330 3ARR22*3N* H29A583CBC 60/ C /330 3ARR22*24R* H29A623CBC 60/ C /330 3ARR22*24R* White- Rodgers 128**6-**X*X* 4*S* 4*S* 4*P* 4*P* 4*N* 4*N* 4*N* 5*R* 5*R* Table 2 Source for the PTCR 305 Series: Ceramite Corporation th Avenue Grafton, WI Phone: (414) Fax: (414) Source for the GE Relays: General Electric Appliance Control Division West Wall Street Morrison, IL Phone: (815) Source for the White-Rodgers Relays: White-Rodgers Division Emerson Electric Company 9797 Reavis Road St. Louis, MO Phone: (314) Indicates style of mounting bracket and other options Page 6

7 7.0 Recommended PTCR Usage PTCR recommended by Bristol Compressors are in two classifications: standard starter and optional starter. a. Standard starters* can be used where the PTCR ambient does not exceed 115 F and/or the voltage does not drop below 197 volts (Table 3). b. Optional starter** should be used where the PTCR ambient exceeds 115 F and/or the voltage is or can be below 197 volts (Table 3). c. Cool down time between starts should be five minutes on each starter. Bristol H29A Model Number Table 3 Standard Starter* Cera-Mite P/N +Suffix indicates style of mounting and other options (see Appendices 1, 2 and 3) Optional Starter** Cera-Mite P/N H29A353CBC 305C C19+/305C9/305C11 H29A383CBC 305C C19+/305C9/305C11 H29A423CBC 305C C9+/305C11 H29A443CBC 305C C9+/305C11 H29A473CBC 305C C9+/305C11 H29A503CBC 305C C9+/305C11 H29A543CBC 305C9+ *** H29A583CBC 305C C9+/305C11 H29A623CBC 305C C9+/305C11 *** Where no optional starter is available, a system time delay greater than five minutes can be evaluated before reverting to a start capacitor and relay (see electrical data sheet). Source for the PTCR 305 Series: Ceramite Corporation th Avenue P. O. Box 166 Grafton, WI Phone: (414) Fax: (414) Page 7

8 8.0 PTCR Start Assist Device The PTCR, or start thermistor, can be used on Bristol s H25A/H26A/H27A Inertia compressor. This bulletin is issued to inform users about how the PTCR operates and also to provide some guides for system design and troubleshooting. 8.1 How the PTCR Operates: Figure 1 Figure 2 These devices are intended to provide additional starting torque for permanent split capacitor type motor compressors by increasing the current in the auxiliary winding during starting. The devices are to be connected across the run capacitor (in series with the auxiliary or start winding, see Figure 1). When the devices are near room temperature, the resistance is low. Upon energization, the PTCR material rapidly (approximately in 1/2 second) heats up and the resistance increases to a value that permits only milliamperes of current to flow (see Figure 2). Essentially, the devices are selflimiting in current. Note that any wires in the control box should not touch the case of the PTCR since the PTCR case temperature may reach 200 F (93.3 C). Also, wiring used when connecting to the terminals of the PTCR should be rated 105 C. 8.2 PTCR Troubleshooting Step 1: Certain problems may lead to start failure in new, properly wired units. They include: a. Voltage measured at the compressor terminals during start-up is too low. b. Compressor discharge and suction pressures are not equalized. c. Improper thermostat location: If the indoor thermostat is incorrectly located, it may short cycle, meaning the thermostat may open and close the compressor contactor within a period of a few minutes. The unit should be off for approximately five minutes for the PTCR to cool sufficiently. d. Opening and closing the disconnect while servicing the unit: During installation and service, there are many reasons why a service technician may wish to restart a unit shortly after it was shut off. Again, units equipped with a PTCR must remain off for approximately five minutes. Page 8

9 8.2.2 Step 2: e. Control box temperature: Very high air temperatures (on a black roof for instance) and intense sunlight can increase the temperature of the control box and everything in it. These hotter temperatures may extend the time required for the PTCR to cool. If the compressor should short cycle before the PTCR is able to cool enough to start the compressor, the compressor may hum but not rotate (lock rotor). Eventually the compressor or system overload may open. If abnormal conditions occur that prevent the PTCR device from assisting the compressor in starting, the optional starter listed in Table 3 should be used in place of the standard starter. Measure the resistance: Remove the PTCR from the unit. Wait at least ten minutes for the PTCR to cool before measuring the resistance. Leave the jumper wire in place on 305C9 and 305C11 as shown in Appendix 1. The resistance of a cold PTCR measured with an ohmmeter should be as follows: 305C9 PTCR: Between 10 and 20 ohms 305C11 PTCR: Between 15 and 25 ohms 305C19 PTCR: Between 20 and 40 ohms 305C20 PTCR: Between 25 and 40 ohms Page 9

10 Appendix 1 Page 10

11 Appendix 2 Page 11

12 Appendix 3 Page 12

13 Release EN Number J28319 Release Date 4/26/02 Revisions L /31/03 X /29/14 Page 13

A Series Inertia Compressor Applications. Application Bulletin 115

A Series Inertia Compressor Applications. Application Bulletin 115 A Series Inertia Compressor Applications Application Bulletin 115 Application Bulletin Subject: A Series Inertia Compressor Applications Number: 115 Release EN: 006X04 Date: 1/6/92 Revision EN: Z27301

More information

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models)

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models) 4-1280 Application Engineering Bulletin AE-1280R4 Revised April, 1995 APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models) Introduction The Compliant Scroll Compressor has been

More information

AIR TO AIR HEAT PUMP SYSTEM DESIGN

AIR TO AIR HEAT PUMP SYSTEM DESIGN 17-1243 Application Engineering Bulletin AE-1243-R5 Revised March 1, 1983 AIR TO AIR HEAT PUMP SYSTEM DESIGN In a world growing increasingly short of natural energy sources, the pressure for more efficient

More information

LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS

LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS 22-1182 Application Engineering Bulletin AE-1182-R24 Revised April 1, 1993 LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS One of the major causes of compressor failure is damage

More information

AE October 1965 Reformatted October Hot Gas Bypass Control Systems

AE October 1965 Reformatted October Hot Gas Bypass Control Systems Hot Gas Bypass Control Systems AE21-1160 AE21-1160 October 1965 Reformatted October 2010 On many refrigeration and air conditioning systems, the refrigeration load will vary over a wide range. This may

More information

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

POLICY BULLETIN Tecumseh Compressor Company Compressor Group PAGE: 1 of 4 A rotary compressor is a precision piece of equipment, designed and manufactured to very close tolerances. For superior performance and long term reliability the following parameters must

More information

AE R17 November 2016

AE R17 November 2016 AE4-1344 R17 November 2016 Application Guidelines for Copeland RFT, RRT, RST Compressors For Refrigerants R-134A, R-450A,R-513A, R-290, R-404A, R-448A, R-449A and R-507 Section TABLE OF CONTENTS Page Safety

More information

Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors

Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors AE4-1296 R3 March 2013 Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Instructions... 2 Safety Icon Explanation... 2

More information

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration Calhoon MEBA Engineering School Study Guide for Proficiency Testing Refrigeration 1. To prevent an injury when working with refrigerants, what safety precautions are necessary? 2. When halogens are in

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-193 REV. 3 Supersedes Form No. A22-193 Rev. 2 Commercial High-Efficiency Condensing Units 15 & 20 TON MODEL [52.8 & 70.3 kw] 10 & 12.5 TON MODEL [35.2 & 44.0 kw] 10 THROUGH 20 NOMINAL TON

More information

Application Engineering

Application Engineering Application Engineering Application Guidelines For ZR90K3 to ZR19M3 and ZR250KC to ZR300KC Copeland Scroll Compressors AE-1316 R1 August 2009 Introduction This bulletin describes the operating characteristics,

More information

Heat Pump Defrost Board Replacement Kit

Heat Pump Defrost Board Replacement Kit Bard Manufacturing Company, Inc. Bryan, Ohio 43506 8620-223 Heat Pump Defrost Board Replacement Kit KIT FEATURES This kit is made up of the current defrost control board 8201-129 and a new defrost sensor.

More information

SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS

SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS PREFACE This service manual is primarily intended for the use of qualified individuals specially trained and experienced in the service of this type of equipment

More information

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM EFFICIENT UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase REFRIGERATION CIRCUIT S 2- stage scroll compressors

More information

ThermoSaver TM Hot Gas Defrost System

ThermoSaver TM Hot Gas Defrost System PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin K40-THERM-PDI-15 Part # 1069130 PRODUCT SUPPORT web: k-rp.com/ts email: mdcu-lgcu@k-rp.com

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 2-Stage R-410A Split System These units have been designed and tested for capacity & efficiency in accordance with A.H.R.I. Standards.

More information

WCH5**4. Product Specifications

WCH5**4. Product Specifications HEAT PUMP HIGH EFFICIENCY 15 SEER 1-1/2 THRU 5 TONS SPLIT SYSTEM ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 208 / 230 Volt, 1- phase, 60 Hz This product has been designed and manufactured to meet ENERGY

More information

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz ENVIRONMENTALLY SOUND REFRIGERANT N4H4 Performance Series Product Specifications 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION

More information

R4H4. Product Specifications

R4H4. Product Specifications R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY BALANCED REFRIGERANT 1-1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Scroll compressors on

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

Product Data PH13(N,P)R FEATURES AND BENEFITS. SPLIT SYSTEM HEAT PUMP For Use With R Refrigerant 1---1/2 TO 5 TONS ( )

Product Data PH13(N,P)R FEATURES AND BENEFITS. SPLIT SYSTEM HEAT PUMP For Use With R Refrigerant 1---1/2 TO 5 TONS ( ) (N,P)R SPLIT SYSTEM HEAT PUMP For Use With R --- 22 Refrigerant 1---1/2 TO 5 TONS (018 --- 060) Product Data *Units factory---shipped with no refrigerant. Dry nitrogen charge only. FEATURES AND BENEFITS

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET General Piping Recommendations and Refrigerant Line Length for Split-System Air Conditioners and Heat Pumps GENERAL GUIDELINES This Split-System (Air Conditioning Condensing/Heat

More information

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation INTRODUCTION In recent years air conditioning industry technology has advanced rapidly. An important byproduct of this growth has been development of the heat pump. Altogether too much mystery has surrounded

More information

SERVICE MANUAL Residential Small Package Products Air Conditioners and Heat Pumps Using R 410A Refrigerant

SERVICE MANUAL Residential Small Package Products Air Conditioners and Heat Pumps Using R 410A Refrigerant Residential s Air Conditioners and Heat Pumps Using R 410A Refrigerant TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 INTRODUCTION... 2 INSTALLATION GUIDELINE... 2 ACCESSORY DESCRIPTIONS... 2 LOW AMBIENT

More information

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO.

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO. wiring diagrams AIR-COOLED CONDENSING UNIT 566D Sizes 120-240 Cancels: New WD 566D.120.1 11/15/96 UNITS PRODUCED AFTER JANUARY, 1996 INDEX UNIT 566D 120-240 ELECTRICAL CHARACTERISTICS (V-Ph-Hz) SCHEMATIC

More information

Warm Case Troubleshooting Guide 9/18/2014

Warm Case Troubleshooting Guide 9/18/2014 Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last

More information

R4H4. Product Specifications

R4H4. Product Specifications ENVIRONMENTALLY SOUND REFRIGERANT R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION

More information

AE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A

AE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A AE4-1392 July 2014 Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A Section TABLE OF CONTENTS Page Safety Safety Instructions...2 Safety Icon Explanation...2 Instructions

More information

AE R21 September 2017

AE R21 September 2017 September 2017 Application Guidelines for Copeland AF, AR & AS Refrigeration Hermetic Compressors For Refrigerants R-22, R-134A, R-404A, R-507, R-290, R-450A, R-513A, R-448A, R-449A TABLE OF CONTENTS Revision

More information

TEMPERATURE & PRESSURE CONTROLS

TEMPERATURE & PRESSURE CONTROLS TEMPERATURE & PRESSURE CONTROLS RANCO LUBE OIL PROTECTION CONTROLS These lube oil protection controls guard pressure-lubricated refrigeration compressors against major damage due to loss of oil pressure.

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-194 REV. 2 Supersedes Form No. A22-194 Rev. 1 Commercial High-Efficiency Condensing Units RAWL High Efficiency 6.5 & 7.5 TON MODEL [22.86 & 26.38 kw] TABLE OF CONTENTS Model Number Designation...2

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 13 SEER R-410A High Efficiency Split System These units have been designed and tested for capacity & efficiency in accordance with

More information

AE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors

AE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors October 2017 1.5 to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury

More information

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation Form 30-217 / January 2007 Heat Reclaim Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation While the vapor-compression cycle has

More information

ThermoSaver TM Hot Gas Defrost System

ThermoSaver TM Hot Gas Defrost System PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin B40-THERM-PDI-14 1069132 ThermoSaver TM Hot Gas Defrost System For use on select

More information

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N PROAIR Air Conditioner CR29 Model INSTRUCTION MANUAL Rev. I P/N 89104461 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

PACKAGE AIR CONDITIONER

PACKAGE AIR CONDITIONER PACKAGE AIR CONDITIONER FORM NO. ATZ-206 TZAA- HIGH EFFICIENCY SERIES NOMINAL SIZE 10 TON [35.2 kw] 10 TON MODEL [35.2 kw] This product is shipped with a nitrogen holding charge that must be vented prior

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING UNIT OBJECTIVES After studying this unit, the reader should be able to Select the correct instruments for checking an air conditioning unit

More information

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the operation of reverse-cycle refrigeration (heat pumps) Explain

More information

Unit Dimension. Unit Nomenclature DEHUMIDIFIER NOMENCLATURE UNIT VOLTAGE: 2: 240/1/60 5: /3/60 9: 480/3/60 8: 600/3/60

Unit Dimension. Unit Nomenclature DEHUMIDIFIER NOMENCLATURE UNIT VOLTAGE: 2: 240/1/60 5: /3/60 9: 480/3/60 8: 600/3/60 Unit Dimension Unit Nomenclature DEHUMIDIFIER NOMENCLATURE R K D A - 0050 - C Z - M 4-8 UNIT VOLTAGE: 2: 240/1/60 5: 208-240/3/60 9: 480/3/60 8: 600/3/60 REFRIGEREANT R-404a MEDIUM TEMPERATURE SCROLL COMPRESSOR

More information

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support Contact information Instructors: Don Reynolds 616-560-9903 Doug McGee 517-294-3932 Factory Tech Support 888-593-9988 Product Improvements for 2017 Todays Objectives Job Site Information Sheets Low Ambient

More information

September 2016 AE Application Guidelines for Copeland CS**KIE Compressors in Ice Machines AE4-1421

September 2016 AE Application Guidelines for Copeland CS**KIE Compressors in Ice Machines AE4-1421 AE4-1421 September 2016 Application Guidelines for Copeland CS**KIE Compressors in Ice Machines TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions... 2 Safety Icon Explanation... 2

More information

Refrigerant Transfer and Compressor Damage

Refrigerant Transfer and Compressor Damage Refrigerant Transfer and Compressor Damage While a piston or scroll compressor refrigeration system with a low-side oil sump is shut down, all is not at rest in the refrigerant circuit. Cutaway views of

More information

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s) Electrical Problems Fuse(s) blow or circuit breaker trips Does the unit use circuit breakers or fuses? Fuse(s) Circuit breakers Are the fuses dual element time delay? Is the circuit breaker HACR rated?

More information

Application Engineering

Application Engineering APPLICATION GUIDELINES FOR ZB*KC/ZB*KCE COPELAND SCROLL REFRIGERATION COMPRESSORS 7 TO 15 HP AE4-1318 R1 June 2008 Introduction The Copeland Scroll ZB*KC/ZB*KCE refrigeration compressor product offering

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure

More information

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons) ENGINEERING DATA HEAT PUMP OUTDOOR UNITS HP40 50HZ Capacity 6.2 to 16.3 (21 200 to 55 500 Btuh) Heating Capacity 6.4 to 16.1 (21 800 to 55 500 Btuh) Bulletin No. 490088 October 2004 Supersedes August 1999

More information

208/230/1/60 5/8 5/8 5/8 5/8 5/8 20 CLIMATUFF /230/1/

208/230/1/60 5/8 5/8 5/8 5/8 5/8 20 CLIMATUFF /230/1/ Service Facts Split System Heat Pump 4TWB4024E1000A IMPORTANT This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this unit.

More information

AE R8 March 2015

AE R8 March 2015 March 2015 Copeland Discus Compressors with Demand Cooling System TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to Risk

More information

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL BY DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL In the September/October 2005 issue of HPAC Magazine, the case was made for reducing head pressure to increase compressor efficiency, thereby lowering its

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 10 SEER Standard Efficiency Split System These units have been designed and tested for capacity and efficiency in accordance with

More information

INSTRUCTIONS! DO NOT DISCARD!

INSTRUCTIONS! DO NOT DISCARD! INSTRUCTIONS! DO NOT DISCARD! CAUTION! Do NOT install where injury might occur due to Moving parts, Sharp corners, Hot surfaces or electrical components d N0417 Page 1 of 10 INSTALLATION INSTRUCTIONS CAUTION

More information

N4H4. Product Specifications

N4H4. Product Specifications 14 SEER HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase, 208/230 Volt 3- phase, 460 Volt 3- phase; 60 Hz REFRIGERATION CIRCUIT S Scroll compressors

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation

More information

AFI2538AE* AFI 2538AE*0, MFI2568AE* MFI2568AE*0 CAUTION

AFI2538AE* AFI 2538AE*0, MFI2568AE* MFI2568AE*0 CAUTION Bottom Mount Refrigerator Technical Information AFI2538AE* AFI 2538AE*0, MFI2568AE* MFI2568AE*0! CAUTION Due to a possibility of personal injury or property damage, always contact an authorized technician

More information

Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors

Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors August 2017 Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Safety... 2 Safety Instructions... 2 Safety Icon Explanation... 2 Instructions

More information

APPLICATION GUIDELINE & SERVICE MANUAL R 410A & R 22 Split System AC & HP

APPLICATION GUIDELINE & SERVICE MANUAL R 410A & R 22 Split System AC & HP APPLICATION GUIDELINE & SERVICE MANUAL R 410A & R 22 Split System AC & HP TABLE OF CONTENTS PAGE PAGE UNIT IDENTIFICATION... 2 REFRIGERATION SYSTEM REPAIR... 24 26 SAFETY CONSIDERATIONS... 4 INTRODUCTION...

More information

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION CONDITIONERS DRY CHARGE UNITS PRODUCT SPECIFICATIONS Bulletin No. 20636 May 204 Supersedes March 202.5 to 5 Tons MODEL NUMBER IDENTIFICATION L C S 3 DC - 036-230 - 2 Lennox Minor Revision Number Air Conditioner

More information

SPLIT-SYSTEM HEAT PUMP UNIT. Model PH12 SS-PH12-11 FEATURES

SPLIT-SYSTEM HEAT PUMP UNIT. Model PH12 SS-PH12-11 FEATURES AVAILABLE Nominal sizes are available from 018 SIZES: through 060 to meet the needs of residential and light commercial applications. EFFICIENCY: CERTIFICATION: ELECTRICAL RANGE: FAN MOTOR: CABINET: UNIT

More information

Operation and Maintenance Manual

Operation and Maintenance Manual Warranty Information Ritchie Engineering guarantees YELLOW JACKET products to be free of defective material and workmanship which could affect the life of the product when used for the purpose for which

More information

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual RecoverX Oil-Filled Hermetic Refrigerant Recovery System Operation and Maintenance Manual Table of Contents Page General Safety Instructions 2-3 System Overview 3 Operating Guide 4 Restart Procedure 4

More information

AIR COOLED PACKAGED CHILLER

AIR COOLED PACKAGED CHILLER AIR COOLED PACKAGED CHILLER UNIC sal is equipped to produce a wide range of COOLER Air conditioning and Refrigeration units, conforming to the international standards and works continually to improve its

More information

Data Aire, Inc. reserves the right to make design changes for the purpose of product improvement or to withdraw any design without notice.

Data Aire, Inc. reserves the right to make design changes for the purpose of product improvement or to withdraw any design without notice. Data Aire, Inc. reserves the right to make design changes for the purpose of product improvement or to withdraw any design without notice. Table of Contents 1.0 Introduction 1.1 Inspection...4 1.2 Description...4

More information

Due to a possibility of personal injury or property damage, always contact an authorized technician for service or repair of this refrigerator.

Due to a possibility of personal injury or property damage, always contact an authorized technician for service or repair of this refrigerator. Bottom Mount Technical Information Due to a possibility of personal injury or property damage, always contact an authorized technician for service or repair of this refrigerator.! CAUTIN All safety information

More information

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N SPECTRACOOL Air Conditioner N21 Model INSTRUCTION MANUAL Rev. G P/N 89115088 TABLE OF CONTENTS WARRANTY AND RETURN POLICY...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

Glass Door Merchandiser. Model RM-49

Glass Door Merchandiser. Model RM-49 Glass Door Merchandiser Model Number: Issued: 02-22-2017 Revised: 02-22-2017 2 TABLE OF CONTENTS UNIT FEATURES 4 Page CROSS SECTION VIEWS 5 EXPLODED VIEW 6, 7 REFRIGERATION SYSTEM 8, 9 CONDENSING UNIT

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant

More information

AE R9. AE R9 May Application Guidelines For K4 Refrigeration Copeland Scroll Compressors Horsepower

AE R9. AE R9 May Application Guidelines For K4 Refrigeration Copeland Scroll Compressors Horsepower AE4-1302 R9 May 2014 Application Guidelines For K4 Refrigeration Copeland Scroll Compressors 7.5-15 Horsepower TABLE OF CONTENTS Section Page Section Page Safety Instructions... 2 Safety Icon Explanation...

More information

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh AIR CONDITIONERS 13ACXN PRODUCT SPECIFICATIONS

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh AIR CONDITIONERS 13ACXN PRODUCT SPECIFICATIONS PRODUCT SPECIFICATIONS AIR CONDITIONERS 13ACXN MERIT Series R-410A Bulletin No. 210831 January 2018 Supersedes Bulletin No. 210739 SEER up to 15.50 1.5 to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh

More information

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11 SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual No.: 2100-479 Supersedes: NEW File: Volume

More information

Refrigeration / Air Conditioning Systems Circuit Drawings. Student Resource Package No: NR 24

Refrigeration / Air Conditioning Systems Circuit Drawings. Student Resource Package No: NR 24 Refrigeration / Air Conditioning Systems Circuit Drawings Nominal Student Hours: Student Resource Package No: NR 24 24 Hours. Delivery: Recognition of Prior Learning: Package Purpose: Suggested Resources:

More information

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N PROAIR Air Conditioner CR43 Model INSTRUCTION MANUAL Rev. H P/N 10-1008-130 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

Scroll Compressors for Heat Pump Applications ZH12K4E to ZH11M4E, ZH06KVE to ZH48KVE

Scroll Compressors for Heat Pump Applications ZH12K4E to ZH11M4E, ZH06KVE to ZH48KVE Scroll Compressors for Heat Pump Applications ZH12K4E to ZH11M4E, ZH06KVE to ZH48KVE About this guideline... 1 1 Safety instructions... 1 1.1 Icon explanation... 1 1.2 Safety statements... 1 1.3 General

More information

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N T-SERIES Air Conditioner T43 Model INSTRUCTION MANUAL Rev. I P/N 10-1008-145 TABLE OF CONTENTS Warranty and Return Policy...2 IMPORTANT NOTICE...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING

More information

JBL2088HES JBL2088HES0, JBR2088HES JBR2088HES0, JFC2089HEP JFC2089HEP0, JFC2089HES JFC2089HES0, JFC2089HPF JFC2089HPF0, JFC2089HPY JFC2089HPY0

JBL2088HES JBL2088HES0, JBR2088HES JBR2088HES0, JFC2089HEP JFC2089HEP0, JFC2089HES JFC2089HES0, JFC2089HPF JFC2089HPF0, JFC2089HPY JFC2089HPY0 Bottom Mount Refrigerator Technical Information JBL2088HES JBL2088HES0, JBR2088HES JBR2088HES0, JFC2089HEP JFC2089HEP0, JFC2089HES JFC2089HES0, JFC2089HPF JFC2089HPF0, JFC2089HPY JFC2089HPY0 Due to a possibility

More information

Otherwise, you can continue reading the file on the following pages.

Otherwise, you can continue reading the file on the following pages. If you d like to be able to print this file out to study off-line or use on the job, a printable version is available for an administrative fee of $3.97 USD. To download the unlocked file, click here.

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N T-SERIES Air Conditioner T29 Model INSTRUCTION MANUAL Rev. I P/N 89104464 TABLE OF CONTENTS Warranty and Return Policy...2 IMPORTANT NOTICE...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE

More information

HVAC/R Refrigerant Cycle Basics

HVAC/R Refrigerant Cycle Basics HVAC/R Refrigerant Cycle Basics This is a basic overview of the refrigeration circuit and how it works. It isn t a COMPLETE description by any means, but it is designed to assist a new technician or HVAC/R

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS INSTALLATION AND OPERATING INSTRUCTIONS HIGH-EFFICIENCY CONDENSING UNITS RAWD- 6 1 2 & 7 1 2 TON RAWE - 6 1 2 & 7 1 2 TON! RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!! WARNING

More information

Glass Door Merchandiser. Model RM-45-SD

Glass Door Merchandiser. Model RM-45-SD Glass Door Merchandiser Model Number: Issued: 02-22-2017 Revised: 02-22-2017 2 TABLE OF CONTENTS UNIT FEATURES 4 Page CROSS SECTION VIEWS 5 EXPLODED VIEW 6, 7 REFRIGERATION SYSTEM 8, 9 CONDENSING UNIT

More information

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION INSTRUCTIONS...4

More information

HP13 WARNING WARNING. Service Literature HP13 SERIES UNITS

HP13 WARNING WARNING. Service Literature HP13 SERIES UNITS Service Literature Corp. 0610 L1 Revised 07 2006 HP13 SERIES UNITS HP13 The HP13 is a high efficiency residential split system heat pump unit, which features a scroll compressor. HP13 units are available

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 1F82-51 Programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

R100 Oil-Less Refrigerant Recovery Unit

R100 Oil-Less Refrigerant Recovery Unit R100 Oil-Less Refrigerant Recovery Unit Operation Manual 1 INTRODUCTION Welcome to simple, efficient refrigerant recovery with your new YELLOW JACKET Refrigerant Recovery Unit, R100. This unit combines

More information

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL 500644 FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES A047-001 FIGURE 1: Demand Defrost Control Module ANTI-SHORT CYCLE DELAY

More information

7 to 15 Ton ZR*KC and ZP*KC Copeland Scroll Compressors

7 to 15 Ton ZR*KC and ZP*KC Copeland Scroll Compressors 7 to 15 Ton ZR*KC and ZP*KC Copeland Scroll Compressors AE4-1303 R15 AE4-1303 R15 June 2016 TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2 Instructions

More information

A 14 SEER Heat Pump with R---410A Refrigerant Series

A 14 SEER Heat Pump with R---410A Refrigerant Series MODEL NUMBER NOMENCLATURE PH14 N B 018 00G B A 14 SEER Heat Pump with R---410A Refrigerant Series Electrical Supply N=208/230---1 P=208/230---3 E=460/3 B R---410A Nominal Capacity 018 1 1/2Tons 024 2Tons

More information

CAUTION. All safety information must be followed as provided in Service Manual RS ! WARNING

CAUTION. All safety information must be followed as provided in Service Manual RS ! WARNING Amana Technical Information³Refrigerator P1303511W Due to a possibility of personal injury or property damage, always contact an authorized technician for servicing or repair of this refrigerator. Refer

More information

4A6H5049E1000B 208/230/1/ /8 7/8 7/8 7/8 DURATION 208/230/1/ /230/1/ SPINE FIN 13 LBS., 10 OZ. YES

4A6H5049E1000B 208/230/1/ /8 7/8 7/8 7/8 DURATION 208/230/1/ /230/1/ SPINE FIN 13 LBS., 10 OZ. YES Service Facts Split System Heat Pump 4A6H5049E1000B IMPORTANT This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this unit.

More information

Compressor Capacity Control: A New Direction

Compressor Capacity Control: A New Direction Purdue University Purdue e-pubs nternational Compressor Engineering Conference School of Mechanical Engineering 1998 Compressor Capacity Control: A New Direction J. Loprete Bristol Compressors B. Johnson

More information

Model No. GB-PAC-08E4. 8,000 BTU Portable Air Conditioner Operating Instructions

Model No. GB-PAC-08E4. 8,000 BTU Portable Air Conditioner Operating Instructions Model No. GB-PAC-08E4 8,000 BTU Portable Air Conditioner Operating Instructions Thank you for choosing a Soleus Air Powered by Gree Portable Air Conditioner. This owner s manual will provide you with valuable

More information

REFRIGERANT RECOVERY Log Book

REFRIGERANT RECOVERY Log Book REFRIGERANT RECOVERY Log Book R E F R I G E R A N T L O G 1) Policy 2) Troubleshooting 3) Condensers Replaced 4) Compressors Replaced 5) Appliance Disposal 6) Accidental Venting 7) R22 NEW 8) R22 Recover

More information

NM952 SERVICE PARTS TABLE OF CONTENTS. Cabinet Air Cooled Refrigeration Water Cooled Refrigeration Water System Gearmotor...

NM952 SERVICE PARTS TABLE OF CONTENTS. Cabinet Air Cooled Refrigeration Water Cooled Refrigeration Water System Gearmotor... This parts list contains the service parts and wiring diagrams for this model. Check the model number in question to be sure that it is applicable to this parts list. NM9 SERVICE PARTS TABLE OF CONTENTS

More information

Contour TM Screw Compressors

Contour TM Screw Compressors Contour TM Screw Compressors Semi-Hermetic Compact Operating Instruction SCH1 High Temp Compressors Form No. 99-77 1. Introduction This series of semi-hermetic compact screw compressors is designed for

More information

XC16. ELITE SERIES R 410A Two Stage Compressor SilentComfort Technology A I R C O N D I T I O N E R S

XC16. ELITE SERIES R 410A Two Stage Compressor SilentComfort Technology A I R C O N D I T I O N E R S A I R C O N D I T I O N E R S XC16 ELITE SERIES R 410A Two Stage Compressor SilentComfort Technology E N G I N E E R I N G D A T A Bulletin No. 210465 May 2006 SEER up to 16.50 2 to 5 Tons Cooling Capacity

More information