30RYH "B" Ductable Heat Pumps with Integrated Hydronic Module AQUASNAP

Size: px
Start display at page:

Download "30RYH "B" Ductable Heat Pumps with Integrated Hydronic Module AQUASNAP"

Transcription

1 30RYH "B" Ductable Heat Pumps with Integrated Hydronic Module Nominal cooling capacity 7-76 kw Nominal heating capacity 8-78 kw 50 Hz AQUASNAP Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. For the operation of the control please refer to the Pro-Dialog Control manual for the 30RA/RH - 30RY/RYH "B" series Installation, operation and maintenance instructions

2 CONTENTS - INTRODUCTION Installation safety considerations Equipment and components under pressure Maintenance safety considerations Repair safety considerations PRELIMINARY CHECKS Check equipment received Moving and siting the unit DIMENSIONS/CLEARANCES PHYSICAL DATA ELECTRICAL DATA APPLICATION DATA Unit operating range Heat exchanger water flow rates Minimum water flow rate Maximum evaporator water flow rate Water loop volume RYH unit operating range at full and part load in cooling mode RYH unit operating range at full and part load in heating mode Pressure drop in the plate heat exchangers ELECTRICAL CONNECTION Power supply Voltage phase imbalance (%) RECOMMENDED WIRE SECTIONS Field control wiring WATER CONNECTIONS Operating precautions and recommendations Hydronic connections Frost protection Installation of the accessory condensate recovery pan NOMINAL SYSTEM WATER FLOW CONTROL Water flow control procedure Pump curve and water flow control as a function of the system pressure drops Pump pressure/flow rate curves Available static system pressure Duct connection START-UP Preliminary checks Actual start-up Operation of two units in master/slave mode Supplementary electric resistance heaters...25 The drawings in this document are for illustrative purposes only and is not part of any offer for sale or contract. 2

3 CONTENTS (continued) 2 - MAINTENANCE General maintenance of the refrigerant circuit Refrigerant charge volume Verification of the charge Apparent and actual subcooling Refrigerant guidelines Recharging liquid refrigerant Undercharge Characteristics of R407C Electrical maintenance Condenser coil AQUASNAP MAINTENANCE PROGRAM Maintenance schedule Description of the maintenance operations START-UP CHECKLIST FOR 30RYH HEAT PUMPS

4 - INTRODUCTION Prior to the initial start-up of the 30RYH units, the people involved in the on-site installation, start-up, operation, and maintenance of this unit should be thoroughly familiar with these instructions and the specific project data for the installation site. The 30RYH liquid chillers are designed to provide a very high level of safety during installation, start-up, operation and maintenance. They will provide safe and reliable service when operated within their application range. This manual provides the necessary information to familiarize yourself with the control system before performing start-up procedures. The procedures in this manual are arranged in the sequence required for machine installation, start-up, operation and maintenance. Be sure you understand and follow the procedures and safety precautions contained in the instructions supplied with the machine, as well as those listed in this guide. Earthquake resistance has not been verified for standard units.. - Installation safety considerations This machine must be installed in a location that is not accessible to the public and protected against access by non-authorised people. After the unit has been received, when it is ready to be installed or reinstalled, and before it is started up, it must be inspected for damage. Check that the refrigerant circuit(s) is (are) intact. Ensure especially that no components or pipes have shifted (e.g. following a shock). If in doubt, carry out a leak tightness check and verify with the manufacturer that the circuit integrity has not been impaired. If damage is detected upon receipt, immediately file a claim with the shipping company. Do not remove the skid or the packaging until the unit is in its final position. These units can be moved with a fork lift truck, as long as the forks are positioned in the right place and direction on the unit. The units can also be lifted with slings, using only the designated lifting points marked at the four corners at the unit base. These units are not designed to be lifted from above. Use slings with the correct capacity, and always follow the lifting instructions on the certified drawings supplied with the unit. Safety is only guaranteed, if these instructions are carefully followed. If this is not the case, there is a risk of material deterioration and injuries to personnel. Never cover any safety devices. This applies to the globe valve in the water circuit and the globe valve(s) in the refrigerant circuit(s). In certain cases the globe stops are installed on ball valves. These valves are factory-supplied lead-sealed in the open position. This system permits isolating and removing the globe stop for checking and replacing. The globe stops are designed and installed to ensure protection against fire risk. Removing the globe stops is only permitted if the fire risk is fully controlled and the responsibility of the user. All factory-installed globe valves are lead-sealed to prevent any calibration change. If the globe valves are installed on a reversing valve (change-over), this is equipped with a globe valve on each of the two outlets. Only one of the two glove valves is in operation, the other one is isolated. Never leave the reversing valve in the intermediate position, i.e. with both ways open (locate the control element in the stop position). If a globe stop is removed for checking or replacement please ensure that there is always an active globe stop on each of the reversing valves installed in the unit. Provide a drain in the discharge circuit, close to each valve, to avoid an accumulation of condensate or rain water. The safety valves must be connected to discharge pipes. These pipes must be installed in a way that ensures that people and property are not exposed to refrigerant leaks. These fluids may be diffused in the air, but far away from any building air intake, or they must be discharged in a quantity that is appropriate for a suitably absorbing environment. Periodic check of the globe valves: See paragraph Maintenance safety considerations. Accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation or explosions. Inhalation of high concentrations of vapour is harmful and may cause heart irregularities, unconsciousness, or death. Vapour is heavier than air and reduces the amount of oxygen available for breathing. These products cause eye and skin irritation. Decomposition products are hazardous..2 - Equipment and components under pressure These products incorporate equipment or components under pressure, manufactured by Carrier or other manufacturers. We recommend that you consult your appropriate national trade association or the owner of the equipment or components under pressure (declaration, re-qualification, retesting, etc.). The characteristics of this equipment/these components are given on the nameplate or in the required documentation, supplied with the products. Do not introduce high static and dynamic pressure compared with the existing operating pressures - either service or test pressures in the refrigerant circuit or in the heat transfer circuit, especially: - limiting the elevation of the condensers or evaporators - taking the circulating pumps into consideration. Ensure that the valve(s) (if used in the refrigerant circuit) are correctly installed, before operating the unit (the valves are not systematically installed on the units, but may be required by certain national safety codes, depending on the destination country). 4

5 .3 - Maintenance safety considerations Engineers working on the electric or refrigeration components must be authorized and fully qualified to do so (electricians trained and qualified in accordance with IEC Classification BA4). All refrigerant circuit repairs must be carried out by a trained person, fully qualified to work on these units. He must have been trained and be familiar with the equipment and the installation, and he must wear the necessary protective items (gloves, glasses, protective clothes, safety shoes). Soldering and welding: Component, piping and connection soldering and welding operations must be carried out using the correct procedures and by qualified operators. Pressurised containers must not be subjected to shocks, nor to large temperature variations during maintenance and repair operations. Never work on a unit that is still energized. Never work on any of the electrical components, until the general power supply to the unit has been cut using the disconnect switch in the control box. If any maintenance operations are carried out on the unit, lock the power supply circuit in the open position ahead of the machine. If the work is interrupted, always ensure that all circuits are still deenergized before resuming the work. ATTENTION: Even if the unit has been switched off, the power circuit remains energized, unless the unit or circuit disconnect switch is open. Refer to the wiring diagram for further details. Attach appropriate safety labels. Operating checks: During the life-time of the system, inspection and tests must be carried out in accordance with national regulations. The information on operating inspections given in annex C of standard EN378-2 can be used if no similar criteria exist in the national regulations. Safety device checks (annex C6 EN378-2): The safety devices must be checked on site once a year for safety devices (high-pressure switches), and every five years for external overpressure devices (safety globe valves). Contact Carrier Service for a detailed explanation of the high-pressure switch test method. If the machine operates in a corrosive environment, inspect the protection devices more frequently. Regularly carry out leak tests and immediately repair any leaks..4 - Repair safety considerations All installation parts must be maintained by the personnel in charge, in order to avoid material deterioration and injuries to people. Faults and leaks must be repaired immediately. The authorized technician must have the responsibility to repair the fault immediately. Each time repairs have been carried out to the unit, the operation of the safety devices must be re-checked. If a leak occurs or if the refrigerant becomes polluted (e.g. by a short circuit in a motor) remove the complete charge using a recovery unit and store the refrigerant in mobile containers (careful in case the refrigerant decomposes due to high temperature increases, as the decomposition products are dangerous). If a leak occurs, evacuate all refrigerant, repair the leak detected and recharge the circuit with the total R407C charge, as indicated on the unit name plate. Only charge liquid refrigerant R407C at the liquid line. Ensure that you are using the correct refrigerant type before recharging the unit. Charging any refrigerant other than the original charge type (R407C) will impair machine operation and can even lead to a destruction of the compressors. The compressors operating with this refrigerant type are charged with a synthetic polyolester oil. These units have a hermetic refrigerant circuit and the original charge need not be topped up. Do not use oxygen to purge lines or to pressurize a machine for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances. Never exceed the specified maximum operating pressures. Verify the allowable maximum high- and low-side test pressures by checking the instructions in this manual and the pressures given on the unit name plate. Do not use air for leak testing. Use only refrigerant or dry nitrogen. Do not unweld or flamecut the refrigerant lines or any refrigerant circuit component until all refrigerant (liquid and vapour) has been removed from chiller. Traces of vapour should be displaced with dry air nitrogen. Refrigerant in contact with an open flame produces toxic gases. The necessary protection equipment must be available, and appropriate fire extinguishers for the system and the refrigerant type used must be within easy reach. Do not siphon refrigerant. Avoid spilling liquid refrigerant on skin or splashing it into the eyes. Use safety goggles. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, immediately and abundantly flush the eyes with water and consult a doctor. Never apply an open flame or live steam to a refrigerant container. Dangerous overpressure can result. If it is necessary to heat refrigerant, use only warm water. 5

6 During refrigerant removal and storage operations follow applicable regulations. These regulations, permitting conditioning and recovery of halogenated hydrocarbons under optimum quality conditions for the products and optimum safety conditions for people, property and the environment are described in standard NFE Any refrigerant transfer and recovery operations must be carried out using a transfer unit. A 3/8 SAE connector on the manual liquid line valve is supplied with all units for connection to the transfer station. The units must never be modified to add refrigerant and oil charging, removal and purging devices. All these devices are provided with the units. Please refer to the certified dimensional drawings for the units. Do not drain water circuits containing industrial brines, without informing the technical service department at the installation site or a competent body first. Close the entering and leaving water shutoff valves and purge the unit hydronic circuit, before working on the components installed on the circuit (screen filter, pump, water flow switch, etc.). Periodically inspect all valves, fittings and pipes of the refrigerant and hydronic circuits to ensure that they do not show any corrosion or any signs of leaks. Do not re-use disposable (non-returnable) cylinders or attempt to refill them. It is dangerous and illegal. When cylinders are empty, evacuate the remaining gas pressure, and move the cylinders to a place designated for their recovery. Do no incinerate. Do not attempt to remove refrigerant circuit components or fittings, while the machine is under pressure or while it is running. Be sure pressure is at 0 kpa before removing components or opening a circuit. Any manipulation (opening or closing) of a shut-off valve must be carried out by a qualified and authorised engineer. These procedures must be carried out with the unit shut-down. NOTE: The unit must never be left shut down with the liquid line valve closed, as liquid refrigerant can be trapped between this valve and the expansion device. (This valve is situated on the liquid line before the filter drier box.) Do not attempt to repair or recondition any safety devices when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. If necessary, replace the device. Do not install safety valves in series or backwards. CAUTION Do not step on refrigerant lines. The lines can break under the weight and release refrigerant, causing personal injury. No part of the unit must use feet, racks or supports during operation. Periodically monitor and repair or if necessary replace any component or piping that shows signs of damage. Do not climb on a machine. Use a platform, or staging to work at higher levels. Use mechanical lifting equipment (crane, hoist, etc.) to lift or move heavy components such as compressors or plate heat exchangers. For lighter components, use lifting equipment when there is a risk of slipping or losing your balance. Use only original replacement parts for any repair or component replacement. Consult the list of replacement parts that corresponds to the specification of the original equipment. 6

7 2 - PRELIMINARY CHECKS 2. - Check equipment received Inspect the unit for damage or missing parts. If damage is detected, or if shipment is incomplete, immediately file a claim with the shipping company. Confirm that the unit received is the one ordered. Compare the name plate data with the order. The unit name plate must include the following information: - Version number - Model number - CE marking - Serial number - Year of manufacture and test date - Refrigerant used and refrigerant class - Refrigerant charge per circuit - Containment fluid to be used - PS: Min./max. allowable pressure (high and low pressure side) - TS: Min./max. allowable temperature (high and low pressure side) - Globe valve cut-out pressure - Pressure switch cut-out pressure - Unit leak test pressure - Voltage, frequency, number of phases - Maximum current drawn - Maximum power input - Unit net weight High pressure Low pressure Min. Max. Min. Max. PS (bar) TS ( C) Pressure switch cut-out pressure (bar) 29 - Valve cut-out pressure (bar) Test pressure, unit leak test (bar) 5 Confirm that all accessories ordered for on-site installation have been delivered, and are complete and undamaged. The unit must be checked periodically during its whole operating life to ensure that no shocks (handling accessories, tools etc.) have damaged it. If necessary, the damaged parts must be repaired or replaced. See also chapter Maintenance Moving and siting the unit Moving See chapter "Installation safety considerations" Siting the unit Always refer to the chapter "Dimensions and clearances" to confirm that there is adequate space for all connections and service operations. For the centre of gravity coordinates, the position of the unit mounting holes, and the weight distribution points, refer to the certified dimensional drawing supplied with the unit. CAUTION: Only use slings at the designated lifting points which are marked on the unit. Before siting the unit check that: the permitted loading at the site is adequate or that appropriate strengthening measures have been taken; the surface is horizontal, flat and intact; a channel is provided all the way around the unit to collect the condensate water. In heat pump mode it may be necessary to remove up to 5 litres of water per hour. if the unit is not equipped with the accessory condensate recovery pan, reference is made to the installation conditions in chapter 0.4; there is adequate space above the unit for air flow; there are adequate support points and that they are in the right places; the location is not subject to flooding; units with the outdoor installation option should not be installed where there is a risk of snow build-up. In areas that are subject to long periods of sub-zero temperatures raise the unit to a higher level. Baffles may be necessary to deflect strong winds and to prevent snow from blowing directly into the unit. They must not restrict air flow into the unit. CAUTION: Before lifting the unit, check that all casing panels are securely fixed in place. Lift and set down the unit with great care. Tilting and jarring can damage the unit and impair unit operation. The 30RYH units can be hoisted with rigging. Coils should always be protected against crushing while a unit is being moved. Use struts or spreader bars to spread the slings above the unit. Do not tilt a unit more than 5. WARNING: Never push or lever on any of the enclosure panels of the unit. Only the base of the unit frame is designed to withstand such stresses. 7

8 Checks before system start-up Before the start-up of the refrigeration system, the complete installation, including the refrigeration system must be verified against the installation drawings, dimensional drawings, system piping and instrumentation diagrams and the wiring diagrams. During the installation test national regulations must be followed. If no national regulation exists, paragraph 9-5 of standard EN can be used as a guide. External visual installation checks: Compare the complete installation with the refrigeration system and power circuit diagrams. Check that all components comply with the design specifications. Check that all safety documents and equipments that are required by current European standards are present. Verify that all safety and environmental protection devices and arrangements are in place and comply with the current European standard. Verify that all document for pressure containers, certificates, name plates, files, instruction manuals that are required documents required by the current European standards are present. Verify the free passage of access and safety routes. Check that ventilation in the plant room is adequate. Check that refrigerant detectors are present. Verify the instructions and directives to prevent the deliberate removal of refrigerant gases that are harmful to the environment. Verify the installation of connections. Verify the supports and fixing elements (materials, routing and connection). Verify the quality of welds and other joints. Check the protection against mechanical damage. Check the protection against heat. Check the protection of moving parts. Verify the accessibility for maintenance or repair and to check the piping. Verify the status of the valves. Verify the quality of the thermal insulation and of the vapour barriers. 8

9 3 - DIMENSIONS/CLEARANCES 30RYH RYH Legend: All dimensions are given in mm Power supply 820 Water inlet Water outlet 000 Required clearances for air flow NOTE: Air entering connection Air leaving connection Power cable entry A B C Non-certified drawings. Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an installation. For the location of fixing points, weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings. Install a condensate collection channel around the unit, or install the accessory condensate recovery pan. The unit must be installed level in both axes (less than 2 mm tolerance per metre). 9

10 4 - PHYSICAL DATA 30RYH Nominal cooling capacity* kw Nominal heating capacity** kw Operating weight kg with hydronic module, single pump with hydronic module, dual pump without hydronic module Refrigerant charge R-407C kg Compressors Hermetic scroll compressors, 48.3 r/s Quantity No. of capacity steps Minimum capacity % Control type PRO-DIALOG Plus Air heat exchanger Grooved copper tubes, aluminium fins Fan Axial with available pressure Quantity Available static pressure Pa Total air flow (high speed) l/s Speed (high/low speed) r/s 24/2 24/2 24/2 24/2 24/2 24/2 24/2 24/2 24/2 Water heat exchanger Direct-expansion welded plate heat exchanger Water volume l Max. water-side operating pressure kpa Option without hydronic module Unit with hydronic module Hydronic module Pump (centrifugal) Single multicell pump, 48.3 r/s Single composite monocell pump, 48.3 r/s Quantity Expansion tank volume l Expansion tank pressure*** kpa Water connections Threaded male gas connections Victaulic (with and without hydronic module) (sleeves for welding or screw connections supplied) Diameter in -/4 -/4 -/4 -/ Outside tube diameter in -/4 -/4 -/4 -/ mm * Nominal conditions: water heat exchanger entering/leaving temperature 2 C/7 C, outdoor air temperature 35 C. ** Nominal conditions: air heat exchanger entering/leaving temperature 40 C/45 C, outdoor air dry bulb temperature 7 C. *** When delivered, the pre-inflation of the tank keeps the plated membrane in the upper part of the tank. To permit changing the water volume, change the inflation pressure to a pressure that is close to the static head of the system (see below), fill the system with water (purging the air) to a pressure value that is 0 to 20 kpa higher than the pressure in the tank. Static head, m/pressure, bar/pressure, kpa 5-0,5-50 / / 5 -,5-50 / / 25-2, ELECTRICAL DATA 30RYH (without hydronic module) Power circuit Nominal power supply V-ph-Hz Voltage range V Control circuit supply The control circuit is supplied via the unit-mounted transformer Maximum unit power input* kw Nominal unit current draw** A Maximum unit current draw at 360 V*** A Maximum unit current draw at 400 V**** A Maximum start-up current Standard unit A With electronic starter option A Short-circuit stability and protection See table on the next page * Power input of the compressor(s) + fan at maximum unit operating conditions: entering/leaving water temperature = 5 C/0 C, maximum condensing temperature of 67.8 C and 400 V nominal voltage (values given on the unit name plate). ** Nominal unit current draw at the following conditions: evaporator entering/leaving water temperature 2 C/7 C, outdoor air temperature 35 C. The current values are given at 400 V nominal voltage *** Maximum unit operating current at maximum unit power input and 360 V nominal voltage. **** Maximum unit operating current at maximum unit power input and 400 V nominal voltage (values given on the unit name plate). Maximum instantaneous starting current at 400 V nominal voltage and with compressor in across-the-line-start (maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor). Maximum instantaneous starting current at 400 V nominal voltage and with compressor with electronic starter (maximum operating current of the smallest compressor(s) + fan current + reduced start-up current of the largest compressor). Hydronic module Single pump Shaft power kw Power input* kw Maximum current draw at 400 V** A Dual pump Shaft power kw Power input* kw Maximum current draw at 400 V** A Note: The water pump power input values are given for guidance only. * To obtain the maximum power input for a unit with hydronic module add the maximum unit power input from the top table to the pump power input (*) from the table above. ** To obtain the maximum unit operating current draw for a unit with hydronic module add the maximum unit current draw from the top table to the pump current draw from the table above. 0

11 Compressor usage and electrical data COMPRESSOR 30RYH Reference code I Nom I Max LRA* Circuit DQ 2 CA 00EE A A A DQ 2 CA 002EE A A A2 A DQ 2 CA 025EE A A DQ 2 CA 03EE A A A2 A+A2 DQ 2 CA 036EE A A A+A2 Legend: I Nom Nominal current draw at Eurovent conditions (see definition of conditions under nominal unit current draw), A I Max Maximum operating current at 360 V, A LRA Locked rotor current, A * With option 25 (electronic starter) the LRA value is reduced by 40%; the maximum start-up time per compresor is <0.8 seconds. Short-circuit stability and protection 30RYH Short-term short-circuit stability (s) With fuse Other fuses Other protection type Without fuse rms value/peak rms value rms value I 2 t (A 2 s)/peak limit ka* ka ** ka*** ka**** /7.5 40A gl:00 50A gl: /9 63A gl:00 80A gl: /7.5 80A gl:50 00A gl: /2 25A gl:25 60A gl:6 * This value corresponds to the switch/disconnect capacity, to the power distribution bus bar system capacity (if used) and to the protection circuit capacity in the standard unit. ** If the available short-circuit current is higher, the unit can be protected by the fuse shown for the specific level. The fuses (not supplied for Carrier units) are as recommended, to be installed upstream of the unit. A fused disconnect switch, equipped with fuses, can be installed in place of the standard unit switch. This should be done on site; please contact the local service department or a qualified electrician. Alternatively please order the special version from the factory by contacting your local Carrier dealer. List of recommended components with Siemens reference details: 30RYH Fused disconnect Contact protection Control handle NH Fuses New protection level with fused diconnect switch, rms value, ka** A: 3KL72-3AA00 3KX7-32-AA00 Use from disconnect switch 40 A 00gL: 3NA3 87 (3 off) A: 3KL74-3AA00 3KX7-32-AA00 of the standard unit 80 A 00gL: 3NA3 824 (3 off) 00 *** Shows the new protection values with higher-capacity fuses than those specified in the previous column. If such fuses are part of the electrical installation upstream of the unit, this is sufficient as anti-short circuit protection to the specified level, without additional protection. **** If a protection device, other than the recommended fuses above, is used for the installation to ensure that no additional protection is required, the protection device must have the specified thermal limit (I 2 t) and limit effect characteristics for the short-circuit current. If the protection device does not have the specified characteristics, one of the specified protection fuses from the previous columns must be installed. Electrical data notes for 30RYH units: 30RYH units have a single power connection point. The control box includes the following standard features: - Starter and motor protection devices for each compressor, fan, optional pump - Control devices Field connections: All connections to the system and the electrical installations must be in full accordance with all applicable codes. The Carrier 30RYH units are designed and built to ensure conformance with local codes. The recommendations of European standard EN (machine safety - electrical machine components - part : general regulations - corresponds to IEC ) are specifically taken into account when designing the electrical equipment. IMPORTANT: Generally the recommendations of IEC are accepted as compliance with the requirements of the installation directives. Conformance with EN is the best means of ensuring compliance with the Machines Directive.5.. Annex B of EN describes the electrical characteristics used for the operation of the machines.. The operating environment for the 30RYH units is specified below: a. 30RYH Indoor installation Environment* - Environment as classified in IEC : - ambient temperature range: +5 C to +40 C, class AA4 - humidity range (non-condensing)*: 50% relative humidity at 40 C 90% relative humidity at 20 C - altitude: 2000 m - indoor installation* - presence of water, class AD2* (possibility of water droplets) - presence of hard solids, class AE2* (no significant dust present) - presence of corrosive and polluting substances, class AF (negligible) - vibration and shock, class AG2, AH2 Competence of personnel, class BA4* (trained personnel - IEC 60364) b. 30RYH outdoor installation Environment** - Environment as classified in EN 6072 (corresponds to IEC 6072): - outdoor installation** - ambient temperature range: -0 C to +46 C, class 4K3** - altitude: 2000 m - presence of hard solids: class 4S2** (no significant dust present) - presence of corrosive and polluting substances, class 4C2 (negligible) - vibration and shock, class 4M2 Competence of personnel, class BA4** (trained personnel - IEC 60364) 2. Power supply frequency variation: ± 2 Hz. 3. The neutral (N) conductor must not be connected directly to the unit (if necessary use a transformer). 4. Overcurrent protection of the power supply conductors is not provided with the unit. 5. The factory-installed disconnect switch(es)/circuit breaker(s) is (are) of a type suitable for power interruption in accordance with EN The units are designed for connection to TN networks (IEC 60364). For IT networks the earth connection must not be at the network earth. Provide a local earth, consult competent local organisations to complete the electrical installation. NOTE: If particular aspects of an actual installation do not conform to the conditions described above, or if there are other conditions which should be considered, always contact your local Carrier representative. * The protection level required to conform to this class is IP2B (according to reference document IEC 60529). All 30RYH units are protected to IP23C and fulfil this protection condition. ** The required protection level for this class is IP43BW (according to reference document IEC 60529). All 30RYH units are protected to IP45CW and fulfil this protection condition.

12 6 - APPLICATION DATA 6. - Unit operating range Water heat exchanger (evaporator) Minimum C Maximum C Water entering temprature (at start-up) 7.8 * 35 Water leaving temprature (in operation) 5 ** 0 Water entering temprature (at shut down) - 60 Air heat exchanger (condenser) Entering air temprature -0*** 46*** Heating mode Water heat exchanger (condenser) Minimum C Maximum C Water entering temp. (at start-up) 0 50 Water leaving temp. (in operation) Water entering temp. (at shut-down) 3 60 Air heat exchanger (evaporator) Entering air temp. -0*** 40*** Do not exceed the maximum operating temperature. * For a system requiring operation below 7,8 C, contact Carrier SA. ** For a system requiring operation below 5 C, anti-freeze must be added to the unit. *** Maximum outside temperature: For transport and storage of the 30RYH units the minimum and maximum allowable temperatures are 20 C and +60 C. It is recommended that these temperatures are used for transport by container Heat exchanger water flow rates 30RYH Evaporator water flow Min. flow rate Max. flow rate* Max. flow rate** Single pump Dual pump l/s l/s l/s l/s * Maximum flow rate at an available pressure of 50 kpa (unit with hydronic module). ** Maximum flow rate at a pressure drop of 00 kpa in the plate heat exchanger (unit without hydronic module) Minimum water flow rate If the installation flow rate is below the minimum flow rate, recirculation of the evaporator water flow may take place, leading to the risk of excessive fouling Maximum evaporator water flow rate This is limited by the permitted evaporator pressure drop. Also, a minimum evaporator T of 2.8 K must be guaranteed, which corresponds to a water flow rate of 0.9 l/s per kw Water loop volume Minimum water loop volume The minimum water loop volume, in litres, is given by the following formula: Volume = CAP (kw) x N* = litres, where CAP is the nominal cooling capacity at nominal operating conditions. Application N* Air conditioning 30RYH RYH Industrial process cooling 30RYH (See note) NOTE: For industrial process cooling applications, where high stability of the water temperature levels must be achieved, the values above must be increased. This volume is required to obtain temperature stability and precision. To achieve this volume, it may be necessary to add a storage tank to the circuit. This tank should be equipped with baffles to allow mixing of the fluid (water or brine). Please refer to the examples below. Bad Bad Good Good Maximum water loop volume Units with hydronic module incorporate an expansion tank that limits the water loop volume. The table below gives the maximum loop volume for pure water or ethylene glycol with various concentrations. 30RYH RYH (in litres) (in litres) Pure water Ethylene glycol 0% Ethylene glycol 20% Ethylene glycol 35% EG: Ethylene glycol 2

13 6.6-30RYH unit operating range at full and part load in cooling mode C Pressure drop in the plate heat exchangers Entering air temperature Pressure drop, kpa Water flow rate, l/s C Evaporator water leaving temperature Notes Evaporator DT = 5 K 2 The evaporator and the hydronic circuit pump are frost protected down to -20 C. Operating range with required anti-freeze solution and special Pro-Dialog control configuration Legend 30RYH RYH RYH RYH RYH RYH RYH RYH RYH RYH unit operating range at full and part load in heating mode C Entering air temperature C Evaporator leaving water temperature 3

14 7 - ELECTRICAL CONNECTION 30RYH Control box X A A PE S L L2 L3 Y RYH Control box X B B PE S L L2 L3 Y Legend Main disconnect switch PE Earth connection S Power supply cable section (see table "Recommended wire sections"). For copper cables use electrolytic copper (AMP type) cable stiffeners with 6 mm terminal for sizes 07 to RYH X (mm) Y (mm) NOTES: The 30RYH units have only one power connection point located at the main disconnect switch. Before connecting electric power cables, it is imperative to check the correct order of the 3 phases (L - L2 - L3). Non-certified drawings. Refer to the certified drawings supplied with the unit or available on request. 4

15 7. - Power supply The power supply must conform to the specification on the chiller name plate. The supply voltage must be within the range specified in the electrical data table. For connections refer to the wiring diagrams. WARNING: Operation of the chiller with an improper supply voltage or excessive phase imbalance constitutes abuse which will invalidate the Carrier warranty. If the phase imbalance exceeds 2% for voltage, or 0% for current, contact your local electricity supply source at once and ensure that the chiller is not switched on until corrective measures have been taken Voltage phase imbalance (%) 00 x max. deviation from average voltage Average voltage Example: On a 400 V - 3 ph - 50 Hz supply, the individual phase voltages were measured to be: AB = 406 V ; BC = 399 ; AC = 394 V Average voltage = ( )/3 = 99/3 = say 400 V Calculate the maximum deviation from the 400 V average: (AB) = = 6 (BC) = = (CA) = = RECOMMENDED WIRE SECTIONS Wire sizing is the responsibility of the installer, and depends on the characteristics and regulations applicable to each installation site. The following is only to be used as a guideline, and does not make Carrier in any way liable. After wire sizing has been completed, using the certified dimensional drawing, the installer must ensure easy connection and define any modifications necessary on site. The connections provided as standard for the field-supplied power entry cables to the general disconnect/ isolator switch are designed for the number and type of wires, listed in the table below. The calculations are based on the maximum machine current (see electrical data tables) and the standard installation practises, in accordance with IEC 60364, table 52C. - For 30RYH units, installed outside, the following standard installation practises have been maintained: No.7: suspended aerial lines, and No. 6: buried conduit with a derating coefficient of 20. The calculation is based on PVC or XLPE insulated cables with copper core. A maximum ambient temperature of 46 C has been taken into consideration. The given wire length limits the voltage drop to < 5% (length L in metres - see table below). IMPORTANT: Before connection of the main power cables (L - L2 - L3) on the terminal block, it is imperative to check the correct order of the 3 phases before proceeding to the connection on the main disconnect/isolator switch Field control wiring Motor The maximum deviation from the average is 6 V. The greatest percentage deviation is:00 x 6/400 =.5 % This is less than the permissible 2% and is therefore acceptable. For the field control wiring of the following elements please refer to the 30RA/RH - RY/RYH B series Pro-Dialog Plus Control manual, and the certified wiring diagram supplied with the unit: - Unit start/stop - Heating/cooling selection - Set-point selection - Customer interlock - (example: auxiliary contact of the chilled water pump contactor) - General alarm reporting, circuit A and circuit B Units S Min. (mm 2 ) Cable type L (m) S Max. (mm 2 ) Cable type L (m) by phase by phase 30RYH 07 x 6 XLPE Cu 90 x 6 PVC Cu RYH 02 x 6 XLPE Cu 90 x 6 PVC Cu RYH 026 x 6 XLPE Cu 90 x 6 PVC Cu RYH 033 x 6 XLPE Cu 90 x 6 PVC Cu RYH 040 x 6 XLPE Cu 90 x 6 PVC Cu RYH 050 x 6 XLPE Cu 80 x 25 PVC Cu RYH 060 x 0 XLPE Cu 0 x 25 PVC Cu RYH 070 x 0 XLPE Cu 00 x 35 PVC Cu 30 30RYH 080 x 6 XLPE Cu 25 x 50 PVC Cu 350 S Power supply cable section (see the diagram in chapter: "Electrical connection") 5

16 9 - WATER CONNECTIONS For size and position of the unit water inlet and outlet connections refer to the certified dimensional drawings supplied with the unit. The water pipes must not transmit any radial or axial force to the heat exchangers nor any vibration. The water supply must be analysed and appropriate filtering, treatment, control devices, shutoff and bleed valves and circuits built in, to prevent corrosion (example: damage to the protection of the tube surface if the fluid is polluted), fouling and deterioration of the pump fittings. Before any start-up verify that the heat exchange fluid is compatible with the materials and the water circuit coating. In case additives or other fluids than those recommended by Carrier s.a are used, ensure that the fluids are not considered as a gas, and that they belong to class 2, as defined in directive 97/23/EC. Carrier s.a. recommendations on heat exchange fluids:. No NH 4+ ammonium ions in the water, they are very detrimental for copper. This is one of the most important factors for the operating life of copper piping. A content of several tenths of mg/l will badly corrode the copper over time. 2. Cl - Chloride ions are detrimental for copper with a risk of perforations by corrosion by puncture. If possible keep below 0 mg/l. 3. SO 4 2- sulphate ions can cause perforating corrosion, if their content is above 30 mg/l. 4. No fluoride ions (<0. mg/l). 5. No Fe 2+ and Fe 3+ ions with non negligible levels of dissolved oxygen must be present. Dissolved iron < 5 mg/ l with dissolved oxygen < 5 mg/l. 6. Dissolved silicon: silicon is an acid element of water and can also lead to corrosion risks. Content < mg/l. 7. Water hardness: TH >2.8 K. Values between 0 and 25 can be recommended. This will facilitate scale deposit that can limit corrosion of copper. TH values that are too high can cause piping blockage over time. A total alkalimetric titre (TAC) below 00 is desirable. 8. Dissolved oxygen: Any sudden change in water oxygenation conditions must be avoided. It is as detrimental to deoxygenate the water by mixing it with inert gas as it is to over-oxygenate it by mixing it with pure oxygen. The disturbance of the oxygenation conditions encourages destabilisation of copper hydroxides and enlargement of particles. 9. Specific resistance electric conductivity: the higher the specific resistance, the slower the corrosion tendency. Values above 3000 Ohm/cm are desirable. A neutral environment favours maximum specific resistance values. For electric conductivity values in the order of S/cm can be recommended. 0. ph: Ideal case ph neutral at C (7 < ph < 8). ATTENTION: Charging, adding or draining fluid from the water circuit must be done by qualified personnel, using air vents and materials suitable for the products. The water circuit charging devices are field-supplied. Charging and removing heat exchange fluids should be done with devices that must be included on the water circuit by the installer. Never use the unit heat exchangers to add heat exchange fluid Operating precautions and recommendations The water circuit should be designed to have the least number of elbows and horizontal pipe runs at different levels. Below the main points to be checked for the connection: Comply with the water inlet and outlet connections shown on the unit. Install manual or automatic air purge valves at all high points in the circuit. Use an expansion device to maintain pressure in the system and install a safety valve as well as an expansion tank. Units with a hydronic module include the safety valve and the expansion tank. Install thermometers in both the entering and leaving water connections. Install drain connections at all low points to allow the whole circuit to be drained. Install stop valves, close to the entering and leaving water connections. Use flexible connections to reduce the transmission of vibrations. Insulate all pipework, after testing for leaks, both to reduce thermal leaks and to prevent condensation. If the external unit water pipes are in an area, where the ambient temperature is likely to fall below 0 C, insulate the piping and add an electric heater. The internal unit piping is protected down to -20 C. NOTE: For units not equipped with a hydronic module a screen filter must be installed as close to the heat exchanger as possible, in a position that is easily accessible for removal and cleaning. Units with hydronic module are equipped with this type of filter. The mesh size of the filter must be.2 mm. The plate heat exchanger can foul up quickly at the initial unit start-up, as it complements the filter function, and the unit operation will be impaired (reduced water flow rate due to increased pressure drop). Before the system start-up verify that the water circuits are connected to the appropriate heat exchangers (e.g. no reversal between evaporator and condenser). Do not introduce any significant static or dynamic pressure into the heat exchange circuit (with regard to the design operating pressures). The products that may be added for thermal insulation of the containers during the water piping connection procedure must be chemically neutral in relation to the materials and coatings to which they are applied. This is also the case for the products originally supplied by Carrier s.a. 6

17 9.2 - Hydronic connections The diagram on the next page shows a typical hydronic installation. When charging the water circuit use air vents to evacuate any residual air pockets Frost protection The plate heat exchangers, the piping and the hydronic module pump can be damaged by frost, despite the built-in anti-freeze protection of these units. The frost protection of plate heat exchanger and all hydronic module components is guaranteed down to -20 C (sizes only) by automatically energized heaters and pump cycling. Never switch off the evaporator and hydronic circuit heaters or the pump, otherwise frost protection cannot be guaranteed. - To prevent corrosion by differential aeration, the complete drained heat transfer circuit must be charged with nitrogen for a period of one month. If the heat transfer fluid does not comply with the Carrier S.A. regulations, the nitrogen charge must be added immediately Installation of the accessory condensate recovery pan Ref. No.: 30RY EE -- 30RYH RY EE -- 30RYH In heat pump mode it may be necessary to remove up to 5 litres of water per hour. Carrier can supply an accessory condensate recovery pan to be positioned under the unit. This pan is connected to the condensate recovery systems via a threaded " diameter gas pipe. For this reason the main unit disconnect switch (QS0) as well as the auxiliary protection switch (QF0) for the heaters must always be left closed (for location of QS and QF 0 see wiring diagram). To ensure frost protection down to -20 C, water circulation in the water circuit must be maintained by periodically switching on the pump. If a shut-off valve is installed, a bypass must be included as shown below. Winter position F A O F B Legend A Unit B Water network C Closed O Open IMPORTANT: Depending on the atmospheric conditions in your area you must do the following when switching the unit off in winter: - Add ethylene glycol with an adequate concentration to protect the installation up to a temperature of 0 K below the lowest temperature likely to occur at the installation site. - If the unit is not used for an extended period, it is recommended to drain it, and as a safety precaution introduce ethylene glycol in the heat exchanger, using the water entering purge valve connection. At the start of the next season, refill the unit with water and add an inhibitor. - For the installation of auxiliary equipment, the installer must comply with basic regulations, especially for minimum and maximum flow rates, which must be between the values listed in the operating limit table (application data). Legend Condensate recovery pan 2 Connection 2 7

30HZ/HZV Water-Cooled/Condenserless Liquid Chillers. Nominal cooling capacity 30HZ: kw Nominal cooling capacity 30HZV: kw

30HZ/HZV Water-Cooled/Condenserless Liquid Chillers. Nominal cooling capacity 30HZ: kw Nominal cooling capacity 30HZV: kw 0HZ/HZV 04-280 Water-Cooled/Condenserless Liquid Chillers Nominal cooling capacity 0HZ: 14-78 kw Nominal cooling capacity 0HZV: 126-75 kw 50 Hz Installation, operation and maintenance instructions CONTENTS

More information

30RQ Reversible Air-to-Water Heat Pumps with Integrated Hydronic Module

30RQ Reversible Air-to-Water Heat Pumps with Integrated Hydronic Module 30RQ 262-522 Reversible Air-to-Water Heat Pumps with Integrated Hydronic Module Nominal cooling capacity 240-465 kw Nominal heating capacity 270-560 kw 50 Hz Carrier is participating in the Eurovent Certification

More information

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity kw. 50 Hz. Installation, operation and maintenance instructions

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity kw. 50 Hz. Installation, operation and maintenance instructions 30RB 262-802 Air-Cooled Liquid Chillers Nominal cooling capacity 260-760 kw 50 Hz Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified

More information

30XW - 30XWH Water-Cooled Liquid Chillers

30XW - 30XWH Water-Cooled Liquid Chillers 30XW - 30XWH Water-Cooled Liquid Chillers Nominal cooling capacity: 275-1765 kw Nominal heating capacity: 320-1875 kw 50 Hz Installation, operation and maintenance instructions Contents 1 - INTRODUCTION...4

More information

30RW/RWA. Water-Cooled/Condenserless Liquid Chillers with Integrated Hydronic Modules PRO-DIALOG INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

30RW/RWA. Water-Cooled/Condenserless Liquid Chillers with Integrated Hydronic Modules PRO-DIALOG INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS PRO-DIALOG INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Water-Cooled/Condenserless Liquid Chillers with Integrated Hydronic Modules 30RW/RWA Nominal cooling capacity 110-310 kw / 50 Hz Original

More information

30XAS Air-Cooled Liquid Chillers

30XAS Air-Cooled Liquid Chillers 30XAS Air-Cooled Liquid Chillers Nominal cooling capacity: 235-484 kw 50 Hz PRO-DIALOG + Installation, operation and maintenance instructions Contents 1 - INTRODUCTION...4 1.1 - Installation safety considerations...4

More information

30GX HXC Screw Compressor Water-Cooled Liquid Chillers and Air-Cooled Liquid Chillers

30GX HXC Screw Compressor Water-Cooled Liquid Chillers and Air-Cooled Liquid Chillers 30GX 082-358 30HXC 080-375 Screw Compressor Water-Cooled Liquid Chillers and Air-Cooled Liquid Chillers Nominal cooling capacity 30HXC: 290-1286 kw Nominal cooling capacity 30GX: 282-1203 kw 50 Hz GLOBAL

More information

61AF. High-temperature heat pumps. Nominal heating capacity kw. 50 Hz. Installation, operation and maintenance instructions

61AF. High-temperature heat pumps. Nominal heating capacity kw. 50 Hz. Installation, operation and maintenance instructions 6AF High-temperature heat pumps Nominal heating capacity -05 kw 50 Hz Installation, operation and maintenance instructions Contents - INTRODUCTION...4. - Check equipment received... 4. - Installation safety

More information

38RA Air-Cooled Condensing Units AQUASNAP. For the operation of the control please refer to the Pro-Dialog Control manual for the 38RA series

38RA Air-Cooled Condensing Units AQUASNAP. For the operation of the control please refer to the Pro-Dialog Control manual for the 38RA series 38RA 040-60 Air-Cooled Condensing Units Nominal cooling capacity 40-5 kw 50 Hz AQUASNAP For the operation of the control please refer to the Pro-Dialog Control manual for the 38RA series Installation,

More information

30RB B 30RB Air-Cooled Liquid Chillers. Nominal cooling capacity kw. 50 Hz

30RB B 30RB Air-Cooled Liquid Chillers. Nominal cooling capacity kw. 50 Hz 30RB 162-262 B 30RB 302-802 Air-Cooled Liquid Chillers Nominal cooling capacity 163-760 kw 50 Hz Unit with low-noise option shown Installation, operation and maintenance instructions Contents 1 - INTRODUCTION...4

More information

38RA Air-Cooled Condensing Units. For the operation of the control please refer to the Pro-Dialog Control manual for the 38RA series

38RA Air-Cooled Condensing Units. For the operation of the control please refer to the Pro-Dialog Control manual for the 38RA series 38RA 040-60 Air-Cooled Condensing Units Nominal cooling capacity 40-5 kw 50 Hz For the operation of the control please refer to the Pro-Dialog Control manual for the 38RA series Installation, operation

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

61AF-A. High-temperature heat pumps PRO-DIALOG INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS. Nominal heating capacity kw 50 Hz

61AF-A. High-temperature heat pumps PRO-DIALOG INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS. Nominal heating capacity kw 50 Hz PRO-DIALOG INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS High-temperature heat pumps 6AF-A Nominal heating capacity -0 kw 50 Hz Original document CONTENTS - INTRODUCTION...5. - Check equipment received...5.

More information

30HXC Screw Compressor Water-Cooled Liquid Chillers INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

30HXC Screw Compressor Water-Cooled Liquid Chillers INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Screw Compressor Water-Cooled Liquid Chillers 30HXC 080-375 Nominal cooling capacity 30HXC: 286-1300 kw 50 Hz / 60Hz Original instructions CONTENTS

More information

30RH B Nominal cooling capacity kw Nominal heating capacity kw

30RH B Nominal cooling capacity kw Nominal heating capacity kw Air-to-Water Heat Pumps with Integrated Hydronic Module AQUASNAP Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products.

More information

30XB - 30XBP. Air-Cooled Screw Chillers INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS. Nominal cooling capacity: kw - 50Hz

30XB - 30XBP. Air-Cooled Screw Chillers INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS. Nominal cooling capacity: kw - 50Hz INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Unit with options 5 & 23A Air-Cooled Screw Chillers 30XB - 30XBP Nominal cooling capacity: 270-688 kw - 50Hz Original document CONTENTS - INTRODUCTION...4.

More information

38RBS Air-Cooled Condensing Units

38RBS Air-Cooled Condensing Units 38RBS 039-60 Air-Cooled Condensing Units Nominal cooling capacity 40-60 kw 50 Hz For the operation of the control please refer to the Pro-Dialog+ Control manual for the 38RBS 039-60 series Installation,

More information

30HXC - 50 HZ. Water-Cooled Screw Compressor Liquid Chillers. Nominal cooling capacity kw

30HXC - 50 HZ. Water-Cooled Screw Compressor Liquid Chillers. Nominal cooling capacity kw Water-Cooled Screw Compressor Liquid Chillers Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. 0HC - 50 HZ Nominal

More information

AQUACIAT CALÉO. High-temperature heat pumps

AQUACIAT CALÉO. High-temperature heat pumps 10198 08-2017 AQUACIAT CALÉO High-temperature heat pumps Instruction manual Contents 1 - INTRODUCTION...4 1.1 - Check equipment received... 4 1.2 - Installation safety considerations... 4 1.3 - Equipment

More information

30GK. Air-Cooled Liquid Chillers. Nominal cooling capacity kw

30GK. Air-Cooled Liquid Chillers. Nominal cooling capacity kw Air-Cooled Liquid Chillers Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. 30GK Nominal cooling capacity 238-725

More information

50AZ/UZ Packaged Rooftop Cooling Only Units and Heat Pumps

50AZ/UZ Packaged Rooftop Cooling Only Units and Heat Pumps 50AZ/UZ Packaged Rooftop Cooling Only Units and Heat Pumps Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. Installation,

More information

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation.

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation. Air-Cooled Liquid Chillers with Integrated Hydronic Module Model shown is with Euro Pack option Nominal cooling capacity 260-760 kw The new generation of Aquasnap Puron liquid chillers features the latest

More information

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw AIR-COOLED LIQUID CHILLER REVERSIBLE AIR-TO-WATER HEAT PUMP PRO-DIALOG PLUS 30RB/RQ 039S-60S Refrigerant HFC-40A Nominal cooling capacity 40-58 kw Nominal heating capacity 4-59 kw The new generation of

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

30GX - 50 Hz. Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER. Nominal cooling capacity kw

30GX - 50 Hz. Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER. Nominal cooling capacity kw Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER 30G - 50 Hz Nominal cooling capacity 384-03 kw The 30G units are air-cooled chillers, designed from the ground up to meet the needs of today and

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

Unit with optional hydronic module 61WG/30WG. Nominal cooling capacity kw Nominal heating capacity kw

Unit with optional hydronic module 61WG/30WG. Nominal cooling capacity kw Nominal heating capacity kw Water-Sourced Liquid Chillers/Heat Pumps with or without Integrated Hydronic Module www.eurovent-certification.com www.certiflash.com Unit with optional hydronic module Standard unit 6WG/30WG Nominal cooling

More information

INSTALLATION, OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S

INSTALLATION, OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Unit with low-noise option Air-Cooled Liquid Chillers 30RBM 60-520 30RBP 60-520 Nominal cooling capacity 64-528 kw 50 Hz Original instructions CONTENTS

More information

61AF High-Temperature Monobloc Air-to-Water Heat Pumps with Integrated Hydronic Module. Nominal heating capacity kw.

61AF High-Temperature Monobloc Air-to-Water Heat Pumps with Integrated Hydronic Module. Nominal heating capacity kw. High-Temperature Monobloc Air-to-Water Heat Pumps with Integrated Hydronic Module www.eurovent-certification.com www.certiflash.com Heating system control (accessory) 6AF 0-05 Nominal heating capacity

More information

30GX 50 Hz. Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER. Nominal cooling capacity kw

30GX 50 Hz. Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER. Nominal cooling capacity kw Air-Cooled Screw Compressor Liquid Chillers GLOAL CHILLER Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. 30G 50

More information

AQUASNAP JUNIOR 30RHV

AQUASNAP JUNIOR 30RHV High-Efficiency Air-To-Water Heat Pumps Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. AQUASNAP JUNIOR 3RHV 6-11

More information

30GSA Series. Installation, Start Up and Service Instructions. Air-Cooled Scroll Chiller. Nominal : Tons

30GSA Series. Installation, Start Up and Service Instructions. Air-Cooled Scroll Chiller. Nominal : Tons 30GSA Series Nominal : 18-48 Tons Air-Cooled Scroll Chiller Installation, Start Up and Service Instructions 1 INTRODUCTION Prior to the initial start-up of the units, the people involved should be thoroughly

More information

30RB /30RQ

30RB /30RQ Air-Cooled Liquid Chillers Reversible Air-to-Water Heat Pumps PRO-DIALOG + 30RB /30RQ Nominal cooling capacity 30RB: 40-160 kw Nominal cooling capacity 30RQ: 40-150 kw Nominal heating capacity 30RQ: 40-160

More information

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation.

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation. Air-Cooled Liquid Chillers with Integrated Hydronic Module www.eurovent-certification.com www.certiflash.com Model shown is with low-noise option 30RB 162-802 Nominal cooling capacity 162-774 The Aquasnap

More information

30RB /30RQ

30RB /30RQ Air-Cooled Liquid Chillers Reversible Air-to-Water Heat Pumps www.eurovent-certification.com www.certiflash.com 30RB /30RQ Nominal cooling capacity 30RB: 39-157 Nominal cooling capacity 30RQ: 38-149 Nominal

More information

AR Ductable Air-Cooled Liquid Chillers Ductable Reversible Air-to-Water Heat Pumps

AR Ductable Air-Cooled Liquid Chillers Ductable Reversible Air-to-Water Heat Pumps Ductable Air-Cooled Liquid Chillers Ductable Reversible Air-to-Water Heat Pumps AR05 039-60 Normal cooling capacity AR05: 40-50 kw Nominal heating capacity AR05: 40-60 kw The new generation of liquid chillers/air-to-water

More information

Technical Service Manual

Technical Service Manual Technical Service Manual Water-cooled Screw Chiller Model: Commercial Air Conditioner Division Midea Group Address: Midea Headquarters Building, 6 Midea Avenue, Beijiao, Shunde, Foshan, Midea CAC After-service

More information

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation Air-Cooled Liquid Chillers www.eurovent-certification.com www.certiflash.com Quality Management Systems 0RB 008-05 Nominal cooling capacity 8- The new generation of Aquasnap liquid chillers was designed

More information

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient PRODUCT SELECTION DATA Easy and fast installation Compact, reliable and efficient Class A variable speed circulator available Air-Cooled Liquid Chillers 0RB 008-015 CARRIER participates in the ECP programme

More information

30RB/RQ 039S-160S. Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: kw Nominal heating capacity: kw

30RB/RQ 039S-160S. Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: kw Nominal heating capacity: kw Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: 40-158 kw Nominal heating capacity: 41-159 kw Carrier China Carrier Corporation is a subsidiary of the United Technologies

More information

30HXC Nominal cooling capacity kw

30HXC Nominal cooling capacity kw WTER-COOLED SCREW COMPRESSOR LIQUID CHILLERS 0HXC Nominal cooling capacity 286-102 kw The 0HXC units are water-cooled chillers, designed from the ground up to meet the needs of today and tomorrow: - Non-ozone

More information

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module PRODUCT SELECTION DATA. Compact design

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module PRODUCT SELECTION DATA. Compact design PRODUCT SELECTION DATA Compact design Alluminium micro-channel heat exchanger technology Fully equipped hydronic module Partial heat reclaim Total heat reclaim Direct expansion free-cooling Air-Cooled

More information

30XA Air-Cooled Liquid Chillers. Nominal cooling capacity kw

30XA Air-Cooled Liquid Chillers. Nominal cooling capacity kw Air-Cooled Liquid Chillers 30XA 252-1702 Nominal cooling capacity 270-1700 kw The Aquaforce liquid chillers are the premium solution for industrial and commercial applications where installers, consultants

More information

AQUASNAP 30RA / 30RH

AQUASNAP 30RA / 30RH LLOYD'S REGISTER QUALITY ASSURANCE AQUASNAP 30RA / 30RH I S O 9 00 1 PRO-DIALOG control INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Air-cooled liquid chillers and reversible air-to-water heat

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

50VZ/PZ 38VZ/PZ+40PZ. Vertical Air-Cooled Split-System Cooling Units and Heat Pumps. Installation, operation and maintenance instructions

50VZ/PZ 38VZ/PZ+40PZ. Vertical Air-Cooled Split-System Cooling Units and Heat Pumps. Installation, operation and maintenance instructions 50VZ/PZ 38VZ/PZ+40PZ Vertical Air-Cooled Split-System Cooling Units and Heat Pumps Installation, operation and maintenance instructions 1 CONTENTS START-UP CHECKLIST... 3 PHYSICAL DATA... 4 ELECTRICAL

More information

AQUASNAP AIR CONDITIONING MADE SIMPLE 30RA/30RH AQUASNAP LIQUID CHILLERS HEAT PUMPS

AQUASNAP AIR CONDITIONING MADE SIMPLE 30RA/30RH AQUASNAP LIQUID CHILLERS HEAT PUMPS AQUASNAP TM AQUASNAP LIQUID CHILLERS HEAT PUMPS 30RA/30RH AIR CONDITIONING MADE SIMPLE BOLT DOWN, PLUG IN... READY THE IDEAL ALL-IN-ONE SOLUTION With the Aquasnap everything is included to reduce the complexity

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

30RBY/RQY Ductable Air-Cooled Liquid Chillers/ Ductable Air-to-Water Heat Pumps PRO-DIALOG +

30RBY/RQY Ductable Air-Cooled Liquid Chillers/ Ductable Air-to-Water Heat Pumps PRO-DIALOG + Ductable Air-Cooled Liquid Chillers/ Ductable Air-to-Water Heat Pumps PRO-DIALOG + Quality Management Systems 30RBY/RQY 017-033 Nominal cooling capacity 15-33 kw Nominal heating capacity 17-31 kw The new

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

38RBS Air-Cooled Condensing Units. Nominal cooling capacity: kw. Features. Easy and fast installation

38RBS Air-Cooled Condensing Units. Nominal cooling capacity: kw. Features. Easy and fast installation Air-Cooled Condensing Units 8RBS 09-60 Nominal cooling capacity: 40-60 The new generation of condensing units was designed for commercial (air conditioning of offices, hotels etc.). The units integrate

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models:

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models: INSTALLATION, OPERATION AND MAINTENANCE MANUAL BHW MEDIUM STATIC PRESSURE DUCTABLE TYPE Models: 174 205 358 410 515 720 724 Cooling capacities from 3,1 to 25 KW Heating capacities from 4,5 to 55,5 KW Thank

More information

Installation Instructions

Installation Instructions 30GTN015-035 Reciprocating Liquid Chillers with ComfortLink Controls 50/60 Hz Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION.................................1-11

More information

38RBS Air-Cooled Condensing Units. product selection data. commercial and industrial applications. compact design.

38RBS Air-Cooled Condensing Units. product selection data. commercial and industrial applications. compact design. product selection data commercial and industrial applications compact design Quiet operation Air-Cooled Condensing Units CARRIER participates in the ECP programme for LCP/HP Check ongoing validity of certificate

More information

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw TECHNICAL INSTRUCTIONS CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw CHG 1 CHG 1 8. kw. kw.7 kw 1. kw April 7 19 - GB - 2 MARKING This product marked conforms to the essential

More information

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers Self-adjusting electronic control Cooling capacity: 35 to 700 kw 410A Cooling Operation DYNACIAT - DYNACIAT POWER

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

Scroll Water Cooled Chiller

Scroll Water Cooled Chiller Scroll Water Cooled Chiller SRW145 Nominal Cooling Capacity 77 to 1232 kw Refrigerant: R407C and R134a Contents Features 1 MV7 Control 3 Physical Data 5 Unit Performance 8 Chiller Selection 9 Physical

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

AHU INSTALLATION & OPERATION MANUAL

AHU INSTALLATION & OPERATION MANUAL AHU INSTALLATION & OPERATION MANUAL VERSION 2 AIR HANDLING UNIT MODELS: AHU 500, AHU 900, AHU 1200, AHU 1700, AHU 2000, AHU 2500, AHU3500, AHU 4500, AHU 5000, AHU 6000, AHU 7000, AHU 8000, AHU 10000, AHU

More information

Midea R134a 50Hz l Flooded type water cooled screw chiller (PCB Control)

Midea R134a 50Hz l Flooded type water cooled screw chiller (PCB Control) DM15-01.01.18en Midea R134a 50Hz l Flooded type water cooled screw chiller (PCB Control) Applicable Model: MWSC340A-FB3 MWSC440A-FB3 MWSC540A-FB3 MWSC690A-FB3 MWSC805A-FB3 MWSC890A-FB3 MWSC1080A-FB3 MWSC1200A-FB3

More information

30RB A /30RQ

30RB A /30RQ Air-Cooled Liquid Chillers Reversible Air-to-Water Heat Pumps www.eurovent-certification.com www.certiflash.com 30RB A /30RQ Nominal cooling capacity 30RB: 40-156 Nominal cooling capacity 30RQ: 38-149

More information

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT Concepcion Carrier Air conditioning Company Philippines INSTALLATION, START-UP AND SERVICE INSTRUCTIONS 38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT CONTENTS Safety Considerations 1 Complete

More information

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY Easy and fast installation Hydronic module available Compact, reliable and efficient Nominal cooling capacity : 8-40 kw Nominal heating capacity : 17-40 kw 50 410A Cooling or heating USE The air-to-water

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS Concepcion Carrier Air conditioning Company Philippines INSTALLATION MANUAL, START-UP & SERVICE INSTRUCTIONS 38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS CONTENTS: Physical Data and Dimensions........

More information

Installation Instructions

Installation Instructions . AquaSnap 30MPA,MPW015-071 Liquid Chillers with Scroll Compressors and ComfortLink Controls 50/60 Hz Installation Instructions CONTENTS Page GENERAL........................................ 1 SAFETY CONSIDERATIONS.....................1,2

More information

38XTZ ABZ 007, 008, 016, 020 and ALZ 011 and 014. Split system air-cooled air conditioners. Models 38XTZ 016 to 024 MASTER LINK I

38XTZ ABZ 007, 008, 016, 020 and ALZ 011 and 014. Split system air-cooled air conditioners. Models 38XTZ 016 to 024 MASTER LINK I 38XTZ 007-024 40ABZ 007, 008, 016, 020 and 024 40ALZ 011 and 014 Split system -cooled conditioners MASTER LINK I Models 38XTZ 016 to 024 40ABZ/ALZ Carier is participating in the Eurovent Certification

More information

Screw Water Cooled Chiller SCW210

Screw Water Cooled Chiller SCW210 Screw Water Cooled Chiller SCW210 Nominal Cooling Capacity 185.1 to1480.8 kw Refrigerant: R407C and R134a Contents Features 1 MV7 Control 3 Physical Data 5 Unit Performance 8 Chiller Selection 9 Physical

More information

Installation Instructions

Installation Instructions AQUAFORCE 30XW150-400 Water-Cooled Liquid Chillers Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INTRODUCTION.................................1,2 System Design...................................

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TSA Series 6 to 20 Ton AIR CONDITIONERS 6 20 TONS 506147 01 06/11 Supersedes 3/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act

More information

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION ECO-FRIENDLY REFRIGERANT GAS INSTALLATION AND OPERATION MANUAL Dear Customer, Thank you for having purchased a FERROLI product. It is the result of many years

More information

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE TEcHnIcal InsTRucTIons PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE PHRIE 095 PHRIE 1 PHIE 095 PHIE 1 PHRIE 155 PHRIE 157 PHRIE 175 PHRIE 177 PHRIE 195 PHRIE 197 PHRIE 7 PHRIE

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

General safety precautions English

General safety precautions English English A min (m 2 ) 550 530 540 510 520 490 500 470 480 450 460 430 440 410 420 390 400 370 380 350 360 330 340 310 320 290 300 270 280 250 260 230 240 210 220 190 200 170 180 150 160 130 140 110 120

More information

General safety precautions English

General safety precautions English English A min (m 2 ) 550 530 540 510 520 490 500 470 480 450 460 430 440 410 420 390 400 370 380 350 360 330 340 310 320 290 300 270 280 250 260 230 240 210 220 190 200 170 180 150 160 130 140 110 120

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

40 RM/RMS Packaged Air-Handling Units

40 RM/RMS Packaged Air-Handling Units ConcepcionCarrier Air conditioning Company Philippines 40 RM/RMS 008034 Packaged AirHandling Units INSTALLATION MANUAL, STARTUP & SERVICE INSTRUCTIONS Contents Page Page Safety Considerations 1 40RM Physical

More information

Operating Instruction Centrifugal fans without scroll (Translation of the Original) BA-RLE-AC /2014 RLE RLA

Operating Instruction Centrifugal fans without scroll (Translation of the Original) BA-RLE-AC /2014 RLE RLA Operating Instruction Centrifugal fans without scroll (Translation of the Original) EN RLE RLA Content 1. Important information 2. Safety notes 3.Technical description 4. Transport 5. Mounting / Installation

More information

MODELS B1PA024, 030 AND 036

MODELS B1PA024, 030 AND 036 STELLAR 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.26-N1Y (892) 511.26-N1Y (893) MODELS B1PA024, 030 AND 036 035-11622 GENERAL YORK Model B1PA units are factory assembled heat

More information

30RB /30RQ

30RB /30RQ AIR-OOLE LIQUI HILLER REVERSIBLE AIR-TO-WATER HEAT PUMP PRO-IALOG PLUS * Unit with low noise option 30RB9-80/30RQ0-46 Refrigerant HF-40A Nominal cooling capacity 93-78 kw Nominal heating capacity 7-0 kw

More information

R100 Oil-Less Refrigerant Recovery Unit

R100 Oil-Less Refrigerant Recovery Unit R100 Oil-Less Refrigerant Recovery Unit Operation Manual 1 INTRODUCTION Welcome to simple, efficient refrigerant recovery with your new YELLOW JACKET Refrigerant Recovery Unit, R100. This unit combines

More information

30XAS Air-Cooled Liquid Chillers PRO-DIALOG + Nominal cooling capacity kw. Features and advantages. Very economical operation

30XAS Air-Cooled Liquid Chillers PRO-DIALOG + Nominal cooling capacity kw. Features and advantages. Very economical operation Air-Cooled Liquid Chillers PRO-DIALOG + 30XAS 242-482 Nominal cooling capacity 235-484 kw The 30XAS Aquaforce liquid chillers are the premium solution for industrial and commercial applications where installers,

More information

61WG/30WG/30WGA. Water-Cooled and Condenserless Liquid Chillers Water-Sourced Heat Pumps. product selection data. 30WG optimized for cooling

61WG/30WG/30WGA. Water-Cooled and Condenserless Liquid Chillers Water-Sourced Heat Pumps. product selection data. 30WG optimized for cooling product selection data 30WG optimized for cooling 6WG optimized for heating Compact design Plug and play approach High efficiency Water-Cooled and Condenserless Liquid Chillers Water-Sourced Heat Pumps

More information

Installation Instructions

Installation Instructions PREFERREDT SERIES AIR CONDITIONER WITH PURONR REFRIGERANT 1-1/2 TO 5 NOMINAL TONS Installation Instructions Fig. 1 --- 538A NOTE: Read the entire instruction manual before starting the installation. TABLE

More information

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons 0TJ06-03S Side Discharge Single-Package Rooftop Units 0/ Hz to 30 Nominal Tons Product Data The 0TJ-S series is a special side discharge version packaged unit with capacities of -30 Tons. This unit can

More information

Vertical Concealed Fan Coil. FCVC Series MANUAL INSTALLATION, OPERATION, & MAINTENANCE

Vertical Concealed Fan Coil. FCVC Series MANUAL INSTALLATION, OPERATION, & MAINTENANCE MANUAL INSTALLATION, OPERATION, & MAINTENANCE Vertical Concealed Fan Coil FCVC Series v100 Issue Date: 12/21/15 2015 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Safety

More information

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC! COIL Manufacturing Inc. When you want Quality, specify COLMAC! Installation, Operation, and Maintenance ENG00018621 Rev A Air Cooled Fluid Coolers Contents 1. SAFETY INSTRUCTIONS... 1 2. MODEL NOMECLATURE...

More information

CH250 AND CH251 CHILLERS

CH250 AND CH251 CHILLERS CH250 AND CH251 CHILLERS Operator s & Installation Manual Release Date: April 19, 2004 Publication Number: 620914801 Revision Date: May 15, 2015 Revision: G Visit the Cornelius web site at www.cornelius.com

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Indoor liquid chiller with integrated hydraulic module Water-cooled: CGWN 205-206 - 207-208 - 209-210 - 211-212 -213-214 - 215 Condenserless: CCUN 205-206 - 207-208 -

More information

CHILLER. Operator s & Installation Manual

CHILLER. Operator s & Installation Manual CHILLER MODELS: CH1001-A Operator s & Installation Manual Release Date: August 9, 2002 Publication Number: 620914301 Revision Date: May 6, 2010 Revision: E Visit the IMI Cornelius web site at www.cornelius.com

More information

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit Packaged Gas/Electric Units Owner s Guide to Operating and Maintaining Your Gas/Electric Unit ELECTRICAL SHOCK HAZARD. FIRE OR EXPLOSION HAZARD Disconnect power at fuse box or service panel before performing

More information

ACTIVA SERIES ROOF TOP Air Conditioners 017/040

ACTIVA SERIES ROOF TOP Air Conditioners 017/040 ACTIVA SERIES ROOF TOP Air Conditioners 017/040 Installation manual Ref.: N-40388_EN 0112 Index Index 1 Installation manual...1 1.1 Safety instructions...2 1.2 Icons used in this document...2 1.3 Instructions

More information

Compact and silent Scroll compressors All-season operation

Compact and silent Scroll compressors All-season operation Compact and silent Scroll compressors All-season operation Cooling capacity: 40 to 161 kw 410a Cooling only Use The new generation of CONDENCIAT condensation units is the solution for all split-system

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:

More information

High temperature air-to-water heat pumps

High temperature air-to-water heat pumps Designed to replace conventional boilers and produce domestic hot water 4 High temperature hot water (+65 C) 4 Winter operation (-20 C) 4 High energy efficiency (CP) 4 Compact and quiet 4 Scroll compressors

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information