Residential ventilation concepts based on the idea of displacement airflow distribution

Size: px
Start display at page:

Download "Residential ventilation concepts based on the idea of displacement airflow distribution"

Transcription

1 A strategy for reducing energy demand Student: Aris Gkitzias (I.D: ) Mentors: Dr. Regina Bokel, Ir. John van der Vliet MSc graduation project Department of Building Technology, faculty of architecture

2 CONTENTS A. INTRODUCTION RESEARCH QUESTION B. BASIC THEORY C. THERMAL STRATIFICATION SIMULATION MODELS + DEVELOPMENT AND VALIDATION OF THE PROPOSED MODEL D. CASE STUDIES + DESCRIPTION THE VENTILATION SYSTEMS THAT ARE TESTED E. BASIC SIMULATION PARAMETERS OF THE SYSTEMS F. SIMULATION RESULTS G. COCLUSIONS Residential ventilation practices: a) Decentralized inlets - intelligent demand control b) Balanced ventilation - HRU (BVS-HR) 01/50

3 A. introduction PROBLEM STATEMENT: Building Practice Minimize Heat losses by making the buildings a) more air tight b) more insulated How do we approach residential ventilation in such a context of energy reduction? 02/50

4 A. introduction PROBLEM STATEMENT: Building Practice Minimize Heat losses by making the buildings a) more air tight b) more insulated Residential ventilation practices: a) Decentralized inlets - intelligent demand control b) Balanced ventilation - HRU (BVS-HR) 03/50

5 A. introduction PROBLEM STATEMENT: Building Practice Minimize Heat losses by making the buildings a) more air tight b) more insulated Residential ventilation practices: a) Decentralized inlets - intelligent demand control b) Balanced ventilation - HRU (BVS-HR) 04/50 MV

6 A. introduction Problem statement: Building Practice Minimize Heat losses by making the buils a) more air tight b) more insulated Residential ventilation practices: RESEARCH FIELD : Airflow distribution Mixed air distribution Partially mixed air distribution Displacement air distribution a) Decentralized inlets - intelligent demand control b) Balanced ventilation - HRU (BVS-HR) MV DV 05/50

7 A. introduction temperature and contaminant stratification supply Displacement temperature air range distribution 16 C C) discharge velocities, 0.20 to 0.35m/s a stratified ventilation system with higher supply temperatures for cooling than mixing system, providing better indoor quality RESEARCH QUESTION: if under the climatic conditions of the Netherlands, it is more energy efficient than a traditional mixing system, providing better thermal comfort during summer if it creates better indoor air quality in dwellings? if it is possible to integrate displacement ventilation in residential buildings without a lot of design limitations? 06/50

8 A. introduction Methodology Step 01 Step 02 Step 03 Step 04 Research question: energy consumption comparison IAQ comparison key design limitation for the dwellings General literature research for the understanding of the physics and the requirements of DV Review existing simulation methods Analyze papers that comply with the conditions that we have in a dwelling Develop and validate the model Derive in some conclusions and estimations about what happens in dwellings Simulation in specific study cases Use the IAQ conclusions in the design airflow requirements in the study case in practice through the case study Output: The development of the simulation model A critical comparison in terms of energy consumption and IAQ between MV and DV 07/50

9 B. basic theory AIRFLOW DISTRIBUTION METHODS - uniform temperature and contaminant concentration - supply temperature range 3 C - 32 C - discharge velocities >3 m/s - temperature and contaminant stratification - supply temperature range 16 C C) - discharge velocities, 0.20 to 0.35m/s a stratified ventilation system with higher supply temperatures for cooling than mixing system, providing better indoor quality Normally used as a flexible in the design system both for cooling and heating in different type of buildings Mixed air distribution Displacement air distribution MV DV 08/50

10 AIRFLOW DISTRIBUTION METHODS - uniform temperature and contaminant concentration - supply temperature range 3 C - 32 C - discharge velocities >3 m/s B. basic theory - temperature and contaminant stratification - supply temperature range 16 C C) - discharge velocities, 0.20 to 0.35m/s a stratified ventilation system with higher supply temperatures for cooling than mixing system, providing better indoor quality Normally used as a flexible in the design system both for cooling and heating in different type of buildings Mixed air distribution Displacement air distribution 09/50

11 B. basic theory IAQ - Ventilation effectiveness e e=1,2 17% cut of the design airflow, Qv Mixed air distribution Ventilation effectiveness In front of standing person In front of seated person DV Ventilation effectiveness for DV MV 1,2-1,6 0,88-0,96 1,3-1,9 0,90-0,97 ASHRAE standard 62.1 (2007) 1,2 NEN-EN 15242(2007) 1,0 2,0 Displacement air distribution ε CO2 concentration 10/50 Mean age of air

12 C. simulation models METHODS OF SIMULATING THE THERMAL STRATIFICATION IN DV J. Lau & Q. Chen model developed by Carrilho da Graca a 3-node simplified energy conservation nodal - plume theory and the research that P.F. Linden has done on displacement ventilation E. L. Olsen & Q. Chen Semi-empirical models embedded in Energy Plus T f estimated from the model developed by (Mundt, 1990) implemented in the building thermal analysis software tool EnergyPlus T f estimated from a model developed by (Chen, et al., 1999) ASHRAE Research Project - RP-949 : 11/50

13 C. simulation models PROPOSED 3-AIRNODE MODEL IN TRNSYS-TRNFLOW Link the height of the 2 nd airnode with the Stratification height in order to simulate the main temperature and contaminant layers that are created in a room with displacement airflow distribution Airflow coupling between the three airnodes uses the mass flow in order to have: Q in =Q coupling-1 = Q coupling-2 =Q out Internal gains distribute all the internal gains between proportionally 2 nd and 3 rd airnode, except of the gains from the lights that are assigned only in the 3 rd airnode 12/50

14 VALIDATION OF THE THERMAL STRATIFICATION IN THE PROPOSED MODEL C. simulation models case 01 experiment in chamber case 02 - experiment in chamber case 03 CFD simulation case 04 - experiment in chamber Test conditions Bjorn/Nielsen- Case 01 Chen/Yuan-Case 02 Huang/Chen- Case 03 Lee-Chen -Case 04 T s C ,3 19 T surounding C 20-22? 0-10? T window C ?? A window m 2-4,32 2x 2,6 7,2 A floor m , ,16 Room height (H) m 4,7 2,4 2,5 2,43 Q v m 3 /h ,7 22,5 293,4 ACH h -1 0,7 4 0,36 6 Q people + equip W 2x75 (2x75) x75 (2x75) +200 Q light W ,4 Rc walls (K m2)/w 3 4 3,8 5,45 Rc roof (K m2)/w ,45 U- value window (W/ (K m2) - 1,4 1,27 1,3 g-value window - 0,58 0,59 0,298 13/50

15 C. simulation models VALIDATION OF THE THERMAL STRATIFICATION IN THE PROPOSED MODEL case 01 experiment in chamber case 02 - experiment in chamber case 03 CFD simulation case 04 - experiment in chamber Comparison between the TRNSYS-TRNFlow simulation and the empirical models 14/50

16 C. simulation models VALIDATION OF THE THERMAL STRATIFICATION IN THE PROPOSED MODEL case 01 experiment in chamber case 02 - experiment in chamber case 03 CFD simulation case 04 - experiment in chamber Two different methods of vertical airflow coupling. 15/50 For the selection of the final simulation model the main target was to use a model that will not underestimate the calculation of the heating demand for DV.

17 DWELLING TYPES Case study TYPE - 02 D. case studies Typical floor plan of a gallery housing complex Section and configuration of a central exhaust design of a gallery housing complex Floor plan 16/50

18 DWELLING TYPES Case study TYPE - 01 Case study TYPE - 02 D. case studies Floor plan Wall and window properties tot. thickness [mm] u-value [W/m 2 K] g- value External walls 290 0,33 - Internal walls 100 2,50 - Roof 460 0,20 - Floor 200 3,63 - Window (TYPE-01) ,83 0,75 Window (TYPE-02) ,27 0,6 Floor plan 17/50

19 VENTILATION CONCEPTS - ALL SYSTEMS D. case studies DV MV MENNS Integration of the ductwork design and the ventilation components in dwelling TYPE-02 18/50

20 VENTILATION CONCEPTS - ALL SYSTEMS D. case studies The ductwork exhaust design is similar in all the systems 19/50 DV mechanical balanced ventilation with heat recovery and displacement air flow distribution MV mechanical balanced ventilation with the same heat recovery unit like in DV, but with a mixing air flow distribution MENNS Decentralized self-regulating inlets which are controlled by a central unit This central unit adjusts the speed of the exhaust fan and subsequently the amount of air passing through the inlets.

21 VENTILATION CONCEPTS - DISPLACEMENT VENTILATION D. case studies Design limitations The estimation of the adjacent zone in order to avoid draught and thermal discomfort The avoidance of shortcut phenomena The integration of the relatively big diffusers and the vertical ducts 20/50

22 VENTILATION CONCEPTS - DISPLACEMENT VENTILATION Design limitations D. case studies The integration of the relatively big diffusers and the vertical ducts Airflow grilles above the door to ensure the escape on the warm and contaminated air 21/50 Exhaust from the wet rooms Enough distance of the diffusers from the radiators to shortcut phenomena

23 VENTILATION CONCEPTS - DISPLACEMENT VENTILATION Design limitations D. case studies The integration of the relatively big diffusers and the vertical ducts Airflow grilles above the door to ensure the escape on the warm and contaminated air 22/50 Exhaust from the wet rooms Enough distance of the diffusers from the radiators to shortcut phenomena

24 VENTILATION CONCEPTS - DISPLACEMENT VENTILATION Design limitations Airflow grilles above the door to ensure the escape on the warm and contaminated air The integration of the relatively big diffusers and the vertical ducts D. case studies Exhaust from the wet rooms 23/50 Enough distance of the diffusers from the radiators to shortcut phenomena

25 AIRFLOW LINK NETWORK IN TRNSYS E. simulation parameters Similar structure for both study cases TYPE-01 & 02 Thermal and External airnodes MV DV DV Q in Supply air flow [m 3 /h] Q c Coupling airflow between airnodes of the same zone [m 3 /h] Q e Exhaust air flow [m 3 /h] Q o Airflow through large openings, gaps above or below the doors [m 3 /h] Q infilt Infiltration airflow [m 3 /h] 24/50

26 DUCTWORK DESIGN IN TRNFLOW E. simulation parameters Similar structure for both study cases TYPE-01 & 02 MV 25/50

27 DUCTWORK DESIGN IN TRNFLOW E. simulation parameters Similar structure for both study cases TYPE-01 & 02 DV 26/50

28 pressure loss [Pa] recovery efficiency [%] pressure loss [Pa] Residential ventilation concepts based on the idea of displacement airflow distribution DUCTWORK DESIGN IN TRNFLOW E. simulation parameters fan curve CFM14 (mode-1) CFMe (mode-4) K2E 190(c) K2E 190(a) airflow [m3/h] CFM14-T (mode-1) CFMe (mode-7) K2E 190(d) Fan curve & HRU Heat exchanger pressure losses & efficiency RVU-S3-225 RVU-S3-280 RVU-S3-325 RS160 (300) RS160 (400) RS160 (500) 27/50

29 MODELING OF HRU & HEATING COIL IN TRNSYS SIMULATION STUDIO E. simulation parameters Heat Recovery : (DV & MV) efficiency 85% Heating coil: DV : outlet set point temperature coil is 15 o C MV: outlet set point temperature coil is 8 o C MENSS: outlet set point temperature coil is 8 o C HRU Bypass: (DV & MV ) during winter the exhaust temperature from the unit (auxiliary node: AN_S09_HR1) should not be below 0 C High cut-out temperature exhaust from house (AN_S09_HR1) 24 C 28/50

30 DEMAND CONTROL SCENARIA WINTER - Demand controlled E. simulation parameters MV DV Demand control Max fan speed 100% Demand control based on the occupancy schedule Bedroom 01 Bedroom 02 Living room Kitchen Bathroom People People People People People 00:00-07: :00-08: :00-12:00 12:00-13: :00-17: :00-18: :00-23: :00-24: Max supply [m 3 /h] Max Exhaust [m 3 /h] Living Room 135 Kitchen 150 Bedroom Bedroom Bathroom 50 WC 25 Total /50

31 DEMAND CONTROL SCENARIA WINTER - Demand controlled E. simulation parameters MENNS MV MV DV Demand control Max fan speed 100% Demand control based on the occupancy schedule Bedroom 01 Bedroom 02 Living room Kitchen Bathroom People People People People People 00:00-07: :00-08: :00-12:00 12:00-13: :00-17: :00-18: :00-23: :00-24: Max supply [m 3 /h] Max Exhaust [m 3 /h] Living Room 135 Kitchen 150 Bedroom Bedroom Bathroom 50 WC 25 Total /50

32 DEMAND CONTROL SCENARIA WINTER - Demand controlled E. simulation parameters MENNS MV MV DV DV-17%cut Demand control based on the occupancy schedule Bedroom 01 Bedroom 02 Living room Kitchen Bathroom People People People People People 00:00-07: :00-08: :00-12:00 12:00-13: :00-17: :00-18: :00-23: :00-24: Max supply [m 3 /h] Max Exhaust [m 3 /h] Living Room 135 Kitchen 150 Bedroom Bedroom Bathroom 50 WC 25 Total /50

33 ENERGY CONSUMPTION-SIMULATION SCENARIO B WINTER - Demand controlled E. simulation parameters MENNS MV DV DV-17%cut Max fan x1 speed 100% Demand con. Max fan x2 speed 100% Demand con. Max fan x2 speed 100% Demand con. Max fan x2 speed 83% Demand con. SUMMER- Hybrid ventilation Max fan x1 speed 100% constant Max fan x2 speed 100% constant Max fan x2 speed 100% constant Max fan x2 speed 100% constant 33/50

34 ENERGY CONSUMPTION-SIMULATION SCENARIO A WINTER SUMMER Full Fan Speed E. simulation parameters MENNS MV DV DV-17%cut Max fan x1 speed 100% constant Max fan x2 speed 100% constant Max fan x2 speed 100% constant Max fan x2 speed 100% constant 34/50

35 WHOLE YEAR PRIMERY ENERGY CONSUMPTION F. results primary energy sens. heating [MJ] heat. coil [MJ] MENSS_ TYPE-01_ Max. exhaust fan speed all year MV_ TYPE-01_ Max. fan speed all year DV_TYPE- 01_ Max. fan speed all year DV_TYPE- 01_ Max. fan speed all year -17% cut in ACH fans [MJ] Total [MJ] The BVS-HR systems are more energy efficient than MENNS under all cases. Under the same ACH DV is not significantly more energy efficient. primary energy sens. heating [MJ] heat. coil [MJ] MENSS_ TYPE-01_ demand controlled MV_ TYPE-01_ demand controlled - hybrid DV_TYPE- 01_ demand controlled - hybrid DV_TYPE- 01_ demand controlled -17% cut in ACH fans [MJ] Total [MJ] /50

36 WHOLE YEAR PRIMERY ENERGY CONSUMPTION F. results primary energy sens. heating [MJ] heat. coil [MJ] MENSS_ TYPE-01_ Max. exhaust fan speed all year MV_ TYPE-01_ Max. fan speed all year DV_TYPE- 01_ Max. fan speed all year DV_TYPE- 01_ Max. fan speed all year -17% cut in ACH fans [MJ] Total [MJ] The BVS-HR systems are more energy efficient than MENNS under all cases. Under the same ACH DV is not significantly more energy efficient. primary energy sens. heating [MJ] heat. coil [MJ] MENSS_ TYPE-01_ demand controlled MV_ TYPE-01_ demand controlled - hybrid DV_TYPE- 01_ demand controlled - hybrid DV_TYPE- 01_ demand controlled -17% cut in ACH fans [MJ] Total [MJ] /50

37 WHOLE YEAR PRIMERY ENERGY CONSUMPTION F. results MENSS_TY DV DV_TYPE- TYPE-02_ MV_ MV_ DV_TYPE- 02_ 02_ fan primary exhaust Max. TYPE-02_ 02_ 02_ fan speed Max. fan energy fan exhaust speed fan Max. speed fan speed Max. fan 100% speed - all fan 100% speed all 100% speed all all 100% speed all all 17% year cut -17% yea all year year year year year cut all year in ACH sens. heating sens heating [MJ] heat. [MJ] coil heat [MJ] coil [MJ] fans [MJ] fans [MJ] Total [MJ] Total [MJ] The BVS-HR systems are more energy efficient than MENNS under all cases. Under the same ACH DV is not significantly more energy efficient. primary energy sens. heating [MJ] heat. coil [MJ] MENSS_TY PE-02_ demand controlled MV_ TYPE-02_ demand controlled - hybrid DV_TYPE- 02_ demand controlled - hybrid DV_TYPE- 02_ demand controlled -17% cut in ACH fans [MJ] Total [MJ] /50

38 Pressure Drop [Pa] Residential ventilation concepts based on the idea of displacement airflow distribution PRIMERY ENERGY CONSUMPTION -fans The influence of the ducts in the pressure drop is insignificant compared to the filter and the HRU. The fan energy consumption in TYPE-01 is higher for DV (under same airflow) due to the small length of the ducts, thus the extra vertical dusts of DV affect the total pressure drop more than the low drop diffusers. F. results Pressure drop_dv [Pa] Type :centifugal fan K2E 190(d) Press. drop_dv (Gallery Apart.)_sup. stream [Pa] Press. drop_mv (Gallery Apart.)_sup. stream [Pa] primary energy MENSS_ TYPE-01_ Max. exhaust fan speed all year MV_ TYPE-01_ Max. fan speed all year DV_TYPE- 01_ Max. fan speed all year DV_TYPE- 01_ Max. fan speed all year -17% cut in ACH fans [MJ] /50

39 Pressure Drop [Pa] Residential ventilation concepts based on the idea of displacement airflow distribution PRIMERY ENERGY CONSUMPTION -fans The influence of the ducts in the pressure drop is insignificant compared to the filter and the HRU. The fan energy consumption in TYPE-02 is lower for DV (under same airflow) due to the bigger length of the ducts, thus low drop diffusers affect positively the total pressure drop more than the extra vertical dusts of DV F. results Pressure drop_dv [Pa] Type :centifugal fan K2E 190(d) Press. drop_dv (Gallery Apart.)_sup. stream [Pa] Press. drop_mv (Gallery Apart.)_sup. stream [Pa] primary energy MENSS_TY PE-02_ Max. exhaust fan speed all year MV_ TYPE-02_ Max. fan speed all year DV_TYPE- 02_ Max. fan speed all year DV_TYPE- 02_ Max. fan speed all year -17% cut in ACH fans [MJ] /50

40 PRIMERY ENERGY CONSUMPTION -sensible heating F. results Small benefit (under same airflow) mainly due to higher recovered temperature from HRU. Without HRU the heating demand would be higher. significant benefit only under 17% cut of the design airflow (due to higher ventilation efficiency). sens. heating [MJ] Jan.- Feb. MV_TYPE- 1_ max fan speed _no HRU DV_TYPE- 1_max fan speed _no HRU MV_TYPE- 1_ max fan speed _ HRU DV_TYPE- 1_ max fan speed _ HRU 6496, , , ,94 primary energy sens. heating [MJ] 40/50 MENSS_ TYPE-01_ Max. exhaust fan speed all year MV_ TYPE-01_ Max. fan speed all year DV_TYPE- 01_ Max. fan speed all year DV_TYPE- 01_ Max. fan speed all year -17% cut in ACH

41 DV - MV TYPE-01 (THERMAL STRATIFICATION AND HIGHER SUPPLY TEMPERATURE FROM HRU) F. results primary energy MV_ TYPE 01 _ fan speed 100% all year DV_ TYPE 01 _ fan speed 100% all year DV_ TYPE 01 _ fan speed 100% -17% cut all year 41/50 sens. heating [MJ]

42 THERMAL COMFORT DURING SUMMER Use of operative temperatures DV is widely used as a passive cooling strategy, it is reasonable that lower temperatures are rendered in the occupied zone with DV.. F. results 43/50

43 THERMAL COMFORT DURING SUMMER Use of operative temperatures DV is widely used as a passive cooling strategy, it is reasonable that lower temperatures are rendered in the occupied zone with DV.. F. results 44/50 Use of a correction factor.

44 THERMAL COMFORT DURING SUMMER F. results Hours above 25,5 C (percentage of the total occupation time) 29.34% 20.42% 22.65% 16.48% 2.85% 2.75% 6.36% 10.83% 9.21% L - 1,2 ACH K - 1 ACH B - 1 ACH L - 1,2 ACH K - 1 ACH B - 1 ACH L - 1,45 ACH K - 1,45 ACH B - 1,4 ACH HRU bypass at 24 o C Max fan x2 speed 100% constant DV MV 45/50 DV - fan K2E 190(d) Q v (tot)= 225 m 3 /h (HRU bypass 24 o C) MV- fan K2E190(d) Q v (tot)= 225 m 3 /h (HRU bypass 24 o C) MV- fan K3G190 Q v (tot)= 275 m 3 /h (HRU bypass 24 o C) Simulation time frame 1 st June 31 st August % h>25,5 o C % h>26,5 o C Living Room ACH=1,2 2,85% 0,00% Kitchen ACH=1 2,75% 0,00% Bedroom -01 ACH=1 6,36% 0,00% Living Room ACH=1,2 20,42% 2,09% Kitchen ACH=1 22,65% 0,66% Bedroom -01 ACH=1 29,34% 5,03% Living Room ACH=1,45 10,83% 0,47% Kitchen ACH=1,45 9,21% 0,00% Bedroom -01 ACH=1,4 16,48% 2,42%

45 THERMAL COMFORT DURING SUMMER F. results Hours above 25,5 C (percentage of the total occupation time) 12.20% 0.85% 0.76% 3.51% 5.98% 5.65% 0.00% 0.00% 0.00% HRU bypass all the summer time L - 1,2 ACH K - 1 ACH B - 1 ACH L - 1,2 ACH K - 1 ACH B - 1 ACH L - 2 ACH K - 2 ACH B - 1,8 ACH DV MENSS 46/50 DV - fan K2E 190(d) Q v (tot)= 225 m 3 /h (no HRU) MV - fan K2E190(d)(natural ventilation) MV Q v (tot)= 225 m 3 /h (no HRU) (natural ventilation) MV Qv= 366 m 3 /h (no HRU) Simulation time frame 1 st June 31 st August % h>25,5 o C % h>26,5 o C Living Room ACH=1,2 2,85% 0,00% Kitchen ACH=1 2,75% 0,00% Bedroom -01 ACH=1 6,36% 0,00% Living Room ACH=1,2 20,42% 2,09% Kitchen ACH=1 22,65% 0,66% Bedroom -01 ACH=1 29,34% 5,03% Living Room ACH=2 10,83% 0,47% Kitchen ACH=2 9,21% 0,00% Bedroom -01 ACH=1,8 16,48% 2,42%

46 G. conclusion Energy benefit of DV compared to traditional Mixing systems DV is not clearly more energy efficient in terms of the total energy consumption under the same airflow compared to MV % 15.95% There is real energy benefit when DV works with 17% cut of the design airflow energy due to higher ventilation efficiency. In case 17% cut of the design airflow the better IAQ quality of DV is minimized -6.59% -4.09% Max. fan speed all year demand controlled- hybrid Max. fan speed all year -17% cut in ACH demand controlled -17% cut in ACH 23.28% 18,36% 4.35% 2.18% Max. fan speed all year demand controlled- hybrid Max. fan speed all year -17% cut in ACH demand controlled -17% cut in ACH 47/50

47 G. conclusion Energy benefit of DV compared to traditional Mixing systems DV is not clearly more energy efficient in terms of the total energy consumption under the same airflow compared to MV. Hours above 25,5 C (percentage of the total occupation time) 20.42% 22.65% 29.34% There is real energy benefit when DV works with 17% cut of the design airflow energy due to higher ventilation efficiency. 2.85% 2.75% 6.36% In case 17% cut of the design airflow the better IAQ quality of DV is minimized Thermal comfort during summer L - 1,2 ACH K - 1 ACH B - 1 ACH L - 1,2 ACH K - 1 ACH B - 1 ACH Hours above 25,5 C (percentage of the total occupation time) DV renders lowers temperature during the summer time compare to MV. However, MENSS with higher airflow supply is the same efficient as DV and requires also less energy as the supply fan do not have to work. 5.98% 5.65% 3.51% 0.85% 0.76% L - 1,2 ACH K - 1 ACH B - 1 ACH L - 2 ACH K - 2 ACH B - 1,8 ACH 12.20% 48/50

48 G. conclusion Indoor Air Quality DV systems have higher ventilation efficiency (1,2) - ASHRAE standard 62.1 (2007) The undisputable acceptance that DV under all boundary conditions has higher ventilation efficiency is quite risky. Limitations 24.66% 15.95% Restrictions maybe make the design of displacement ventilation less flexible However, they do not consist significant constraining factors, especially for new dwellings -6.59% -4.09% Max. fan speed all year demand controlled- hybrid Max. fan speed all year -17% cut in ACH demand controlled -17% cut in ACH Recommendations Since the energy benefit of DV is mainly a consequence of the higher ventilation efficiency. More research with thermal measurements and CFD simulation is required to verify the huger ventilation efficiency in dwellings % 18,36% CFD and measurements are required for the further calibration of the propose model in TRNSYS-TRNFlow. 4.35% 2.18% Max. fan speed all year demand controlled- hybrid Max. fan speed all year -17% cut in ACH demand controlled -17% cut in ACH 49/50

49 THANK YOU! ARIS GKITZIAS 50/50

Displacement Ventilation

Displacement Ventilation Displacement Ventilation Displacement Ventilation Displacement Ventilation vs. Dilution Ventilation Characteristics Design Considerations Layout and Selection Product Overview Casino Case Study Dilution

More information

Yan Xue 1 and Qingyan Chen 2,1* Abstract

Yan Xue 1 and Qingyan Chen 2,1* Abstract 1 2 3 4 5 6 7 8 9 1 11 12 13 14 15 16 17 18 19 2 21 22 23 24 25 26 27 28 29 3 31 32 33 34 35 36 37 38 Xue, Y. and Chen, Q. 214. Influence of floor plenum on energy performance of buildings with UFAD systems,

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen * Journal of Environmental Protection, 2013, 4, 638-646 http://dx.doi.org/10.4236/jep.2013.46073 Published Online June 2013 (http://www.scirp.org/journal/jep) The Research of Performance Comparison of Displacement

More information

Typologies of Hybrid Ventilation in Schools

Typologies of Hybrid Ventilation in Schools Typologies of Hybrid Ventilation in Schools Peter van den Engel Delft Technological University, the Netherlands Corresponding email: p.vd.engel@deerns.nl SUMMARY This article is the result of a study on

More information

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING Rebeca Barbosa 1, Martin Barták 1, Jan L. M. Hensen 1, 2, Marcel G. L. C. Loomans 2 1 Czech Technical

More information

Underfloor Air Distribution:

Underfloor Air Distribution: Underfloor Air Distribution: An underfloor air distribution system utilizes a plenum space between the structural slab and the underside of a raised floor to distribute the conditioned air to the room.

More information

Space Air Diffusion II

Space Air Diffusion II MEBS6008 Environmental Services II http://me.hku.hk/bse/mebs6008/ Space Air Diffusion II Ir. Dr. Sam C. M. Hui Visiting Assistant Professor Department of Mechanical Engineering The University of Hong Kong

More information

Residential Heat Recovery Ventilation. REHVA European Guidebook No 25

Residential Heat Recovery Ventilation. REHVA European Guidebook No 25 Residential Heat Recovery Ventilation REHVA European Guidebook No 25 REHVA European Guidebook No 25 2 Limited to mechanical supply and exhaust ventilation Targeted to engineers, HVAC consultants and contractors

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0188 ISBN: 978-83-7947-232-1 Dispersion of pollutants released at floor level under three types of heating systems: A CFD study. Laura

More information

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems CBE Timothy Moore CENTER FOR THE BUILT ENVIRONMENT SimBuild

More information

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and Displacement Ventilation Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and DV Systems, Objectives: Understand Differences between: Well Mixed, Partially Stratified and Fully

More information

Villa Bagatelle Technical Report

Villa Bagatelle Technical Report Downloaded from orbit.dtu.dk on: Dec 27, 2018 Villa Bagatelle Technical Report Cox, Rimante Andrasiunaite Publication date: 2015 Document Version Publisher's PDF, also known as Version of record Link back

More information

Comfort and health-indoor air quality

Comfort and health-indoor air quality Comfort and health-indoor air quality 1 The human body has a complicated regulating system to maintain the human body temperature constant most of the time, which is 98.6 F (36.9 C) regardless of the environmental

More information

Figure 1: Low energy dwellings testsite

Figure 1: Low energy dwellings testsite Seventh International IBPSA Conference Rio de Janeiro, Brazil August 13-15, 2001 SIMULATION OF DEMAND CONTROLLED VENTILATION IN A LOW-ENERGY HOUSE Netherlands Energy Research Foundation J.C. Römer P.O.

More information

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2 Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2 john.woollett@swegon.se, jonas.akesson@swegon.se SUMMARY The main focus of the paper will be on active beam technology regarding

More information

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon

More information

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 TESTING AND VALIDATION OF SIMULATION TOOLS OF HVAC MECHANICAL EQUIPMENT INCLUDING THEIR CONTROL STRATEGIES. PART II: VALIDATION

More information

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

International Forum on Energy, Environment Science and Materials (IFEESM 2015) The Comparison and Analysis of Humidity Environment between Floor and Ceiling Radiant Cooling Systems that Combined with Displacement Ventilation Kai SUN 1 a *, Chuan-hui ZHOU 1 1 College of Urban Construction,

More information

Simplified Space-Heating Distribution using Radiators in Super-Insulated Apartment Buildings

Simplified Space-Heating Distribution using Radiators in Super-Insulated Apartment Buildings Simplified Space-Heating Distribution using Radiators in Super-Insulated Apartment Buildings L. Georges*, K. Wen*,c, M.J. Alonso b, M. Berge*, J. Thomsen b and R. Wang c *Energy and Process Engineering

More information

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING Vladimír Zmrhal 1, Jan Hensen 2 and František Drkal 1 1

More information

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed

More information

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Liu Jing 1, Yoshihiro Aizawa 2, Hiroshi Yoshino 3 1 School of Municipal

More information

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,

More information

Ventilation Strategies for Healthy IEQ and Energy Efficiency

Ventilation Strategies for Healthy IEQ and Energy Efficiency Ventilation Strategies for Healthy IEQ and Energy Efficiency Lars Ekberg Energy Management AB A Chalmers Industriteknik Company The purpose of ventilation + - Pollution Climate Heat Pollution 2 Examples

More information

New Convection Correlations for Cooled Ceiling Panels in Room with Mixed and Stratified Airflow

New Convection Correlations for Cooled Ceiling Panels in Room with Mixed and Stratified Airflow 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in HVAC&R Research, Vol. 12, No. 2, April 2006. For personal use only. Additional distribution

More information

ω = (1) Kirby S. Chapman Ph.D.

ω = (1) Kirby S. Chapman Ph.D. White Paper: Relative Humidity Impacts of the AirFloor System in the Built Environment Kirby S. Chapman Ph.D. kirby.chapman@scavengetech.com Introduction Relative humidity is specified as one of the seven

More information

Jim Aswegan Chief Engineer

Jim Aswegan Chief Engineer Displacement Ventilation Jim Aswegan Chief Engineer Displacement Ventilation Systems Comfort & Contaminate Control DV Concepts & System Benefits Outlet Types and Air Patterns Example l Space Layouts Displacement

More information

Optimisation of cooling coil performance during operation stage for improved humidity control

Optimisation of cooling coil performance during operation stage for improved humidity control Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 741 Optimisation of cooling coil performance during operation stage for improved humidity control S.C. Sekhar * and L.T. Tan National

More information

AERECO DEMAND CONTROLLED VENTILATION COMBINING INDOOR AIR QUALITY AND ENERGY SAVINGS

AERECO DEMAND CONTROLLED VENTILATION COMBINING INDOOR AIR QUALITY AND ENERGY SAVINGS AERECO DEMAND CONTROLLED VENTILATION COMBINING INDOOR AIR QUALITY AND ENERGY SAVINGS INNOVATION THAT EXCELS IN AIR QUALITY AND ENERGY SAVINGS Aereco demand controlled ventilation Combining indoor air quality

More information

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001 This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.

More information

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room Yanli Ren 1 ; Deying Li 2 ; Yufeng Zhang 1 1 School of Environment Science and Engineering, Tianjin University, Tianjin 300072,

More information

HRU ECO 3 RF APPENDIX Q ELIGIBLE NEW

HRU ECO 3 RF APPENDIX Q ELIGIBLE NEW NEW HRU ECO 3 RF ULTRA HIGH EFFICIENCY (95%) WHOLE HOUSE HEAT RECOVERY VENTILATION SYSTEM (MVHR) COMPLYING WITH SYSTEM 4 OF ADF2006 VENTILATION AIR CONDITIONING AIR CLEANING HEATING APPENDIX Q ELIGIBLE

More information

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation Downloaded from orbit.dtu.dk on: Mar 02, 2018 Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation Wu, Xiaozhou; Fang, Lei; Olesen, Bjarne

More information

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me!

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me! 97.501B Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-24800 Monitored In-Situ Performance of Residential Air-Co onditioning Systems Sponsored By: Arizona Public Service Company

More information

design brief This design brief provides an introduction into the design and application of DV. It addresses the following issues:

design brief This design brief provides an introduction into the design and application of DV. It addresses the following issues: energydesignresources design brief DISPLACEMENT VENTILATION Summary Displacement ventilation (DV) is an alternate air distribution method for commercial and industrial spaces. 1 Used since the late 1970s

More information

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia To cite this article: N A Malek

More information

ROOM AIR STRATIFICATION IN COMBINED CHILLED CEILING AND DISPLACEMENT VENTILATION SYSTEMS

ROOM AIR STRATIFICATION IN COMBINED CHILLED CEILING AND DISPLACEMENT VENTILATION SYSTEMS ROOM AIR STRATIFICATION IN COMBINED CHILLED CEILING AND DISPLACEMENT VENTILATION SYSTEMS Stefano Schiavon, Ph.D., P.E. Center for the Built Environment, University of California at Berkeley, Member ASHRAE

More information

Don t Turn Active Beams Into Expensive Diffusers

Don t Turn Active Beams Into Expensive Diffusers This article was published in ASHRAE Journal, April 2012. Copyright 2012 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be

More information

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa Aalborg Universitet The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa Published in: COLD CLIMATE HVAC 2009 Publication date: 2009

More information

COMPARISON OF THE USE TRICKLE VENTILATORS IN EUROPEAN RESIDENTIAL VENTILATION STANDARDS

COMPARISON OF THE USE TRICKLE VENTILATORS IN EUROPEAN RESIDENTIAL VENTILATION STANDARDS COMPARISON OF THE USE TRICKLE VENTILATORS IN EUROPEAN RESIDENTIAL VENTILATION STANDARDS Jelle Laverge 1, Arnold Janssens 1 1 Faculty of Engineering and Architecture, Ghent University, Gent, Belgium. Abstract

More information

Computerized Simulation of Automotive Air-Conditioning System: A Parametric Study

Computerized Simulation of Automotive Air-Conditioning System: A Parametric Study www.ijcsi.org 787 Computerized Simulation of Automotive Air-Conditioning System: A Parametric Study Haslinda Mohamed Kamar 1, Nazri Kamsah 2 and Mohd Yusoff Senawi 3 1 Department of Thermo-Fluid, Universiti

More information

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY Proceedings of BS5: 4th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 5. AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN

More information

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.

More information

Mechanical Ventilation with Heat Recovery: Designing and implementing a robust and effective ventilation system

Mechanical Ventilation with Heat Recovery: Designing and implementing a robust and effective ventilation system Viewpoint August 2012 Mechanical Ventilation with Heat Recovery: Designing and implementing a robust and effective ventilation system Dr Sarah Price and Helen Brown Summary Mechanical Ventilation and Heat

More information

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM , Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,

More information

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA CITY OF DANA POINT COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 33282 Golden Lantern, Suite 209 Dana Point, CA 92629 949 248 3594 www.danapoint.org INDOOR AIR QUALITY B011 AIR 2013 CALIFORNIA CODES CODE

More information

MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS

MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS Clayton Miller 1,* and Chandra Sekhar 1 1 National University of Singapore, Singapore * Corresponding email: miller.clayton@nus.edu.sg

More information

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY Xiaoyun Xie, Yidan Tang, Xiaoqin Yi, Shuanqiang Liu,Yi Jiang Department of Building Science and Technology,

More information

Dwelling Ventilation Strategies, Including ASHRAE 62.2 ASHRAE Ventilation for Acceptable Indoor Air Quality

Dwelling Ventilation Strategies, Including ASHRAE 62.2 ASHRAE Ventilation for Acceptable Indoor Air Quality Dwelling Ventilation Strategies, Including ASHRAE 62.2 National Weatherization Conference 2005 ASHRAE 62.1 2001 Ventilation for Acceptable Indoor Air Quality Rick Karg 2005 R.J. Karg Associates rjkarg@karg.com

More information

WORKSHOP VENTILATION- PSYCHROMETRICS-AHU

WORKSHOP VENTILATION- PSYCHROMETRICS-AHU Alkis Triantafyllopoulos Mechanical Engineer Member TEE, MASHRAE a.trianta@gmail.com WORKSHOP VENTILATION- PSYCHROMETRICS-AHU Based on ASHRAE 62 Purpose Set minimum Outdoor Air ventilation Rates Air Quality

More information

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING DA Hindoliya and SC Mullick * Centre for Energy Studies, Indian

More information

Benefits Offered by Passive Dehumidification Wheel Speed Control

Benefits Offered by Passive Dehumidification Wheel Speed Control Benefits Offered by Passive Dehumidification Wheel Speed Control White paper By John Fischer Benefits Offered by Passive Dehumidification Wheel Speed Control The most significant advantage of the Pinnacle

More information

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air Anna Pacak 1,*, Andrzej Jedlikowski 1, Demis Pandelidis 1, and Sergey Anisimov 1 1 Wrocław University of

More information

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS Staņislavs GENDELIS, Andris JAKOVIČS Laboratory for mathematical modelling of environmental

More information

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger Toke Rammer Nielsen, Associate Professor, Department of Civil Engineering, Technical University of Denmark; trn@byg.dtu.dk

More information

Temperature Distribution of Rotary Heat Recovery Units

Temperature Distribution of Rotary Heat Recovery Units Temperature Distribution of Rotary Heat Recovery Units Bjørn R. Sørensen, dr.ing. Narvik University College, P.O.Box 385, N-8505 Narvik, Norway Corresponding email: brs@hin.no SUMMARY This paper deals

More information

DESCRIPTION OF TECHNOLOGY

DESCRIPTION OF TECHNOLOGY March 2009 Underfloor Air Distribution INTRODUCTION Copyright 2009 Glumac. All rights reserved. While this Green Paper discusses primarily the use of raised access floors for air distribution, HVAC integration

More information

Joseph Lstiburek, Ph.D., P.Eng, ASHRAE Fellow. Building Science. Adventures In Building Science. presented by

Joseph Lstiburek, Ph.D., P.Eng, ASHRAE Fellow. Building Science. Adventures In Building Science. presented by Joseph Lstiburek, Ph.D., P.Eng, ASHRAE Fellow Building Science Adventures In Building Science presented by www.buildingscience.com Build Tight - Ventilate Right 2 Build Tight - Ventilate Right How Tight?

More information

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS Risto Kosonen, Panu Mustakallio Arsen Melikov 2, Marcin Duszyk 2 Oy Halton Group Ltd., Helsinki, Finland. 2 International

More information

Displacement Ventilation in Classrooms

Displacement Ventilation in Classrooms TWO DIFFUSERS, THE WHITE COLUMNS ON EACH SIDE OF THE WHITEBOARD, PROVIDE COOL SUPPLY AIR TO THE DEMONSTRATION DV CLASSROOM. THE DV CLASSROOM DEMONSTRATION FEATURED A CUSTOMIZED ROOFTOP HVAC UNIT. Displacement

More information

PERFORMANCES OF DAHT CONNECTED TO BUILDING AIRTIGHTNESS AND INDOOR HYGRO- THERMAL CLIMATE

PERFORMANCES OF DAHT CONNECTED TO BUILDING AIRTIGHTNESS AND INDOOR HYGRO- THERMAL CLIMATE PERFORMANCES OF DAHT CONNECTED TO BUILDING AIRTIGHTNESS AND INDOOR HYGRO- THERMAL CLIMATE Masy Gabrielle 1, Lebrun Jean 2, Gendebien Samuel 3, Nicolas Hansen 1, Marc Lengele 4, and Luc Prieels 5 1 CECOTEPE

More information

Center for the Built Environment October 2013

Center for the Built Environment October 2013 Thermal Comfort in the Context of Radiant Systems Center for the Built Environment University of California Berkeley Center for the Built Environment October 2013 Overview of talk A brief summary of research

More information

BEST PRACTICE RECOMMENDATIONS

BEST PRACTICE RECOMMENDATIONS Second and Delaware, Kansas City, MO BEST PRACTICE RECOMMENDATIONS PHIUS 1 OUTLINE VENTILATION & COMPONENT REQUIREMENTS UNDER PHIUS+ COMPARISON TO OTHER VENTILATION STANDARDS: ASHRAE 62.2 2016 ERV/HRV

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Heat Transfer Basics Human Body Heat Exchange Radiant Cooling Basics Radiant Cooling Suitability? Radiant

More information

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Comparison of Thermal Comfort by Radiant Heating and Convective Heating Journal of Engineering, Project, and Production Management 2015, 5(1), 26-35 Comparison of Thermal Comfort by Radiant Heating and Convective Heating Shigeru Imai 1 and Shoichi Kojima 2 1 MSc Student, Department

More information

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Evaluation and Design Optimization of Refrigerated Display

More information

Thermal Comfort with Convective and Radiant Cooling Systems

Thermal Comfort with Convective and Radiant Cooling Systems Proceedings of 9 th Windsor Conference: Making Comfort Relevant Cumberland Lodge, Windsor, UK, 7-10 April 2016. Network for Comfort and Energy Use in Buildings, http://nceub.org.uk Thermal Comfort with

More information

Effects of Kitchen Ventilation on Residential Dwellings

Effects of Kitchen Ventilation on Residential Dwellings Effects of Kitchen Ventilation on Residential Dwellings Anthony C. Jellen Engineering i Projects Incorporated 1 Personal Background U.S.N. (1994 2000) BS B.S. in Civil Engineering (2005) PHRC employee

More information

DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION

DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION 2 AERECO DX system DX SYSTEM A COMPLETELY NEW HEAT RECOVERY VENTILATION RANGE With the experience of a very innovative room-by-room demand

More information

HRU ECO 3 RF APPENDIX Q ELIGIBLE NEW

HRU ECO 3 RF APPENDIX Q ELIGIBLE NEW NEW HRU ECO 3 RF ULTRA HIGH EFFICIENCY (95%) WHOLE HOUSE HEAT RECOVERY VENTILATION SYSTEM (MVHR) COMPLYING WITH SYSTEM 4 OF ADF2006 VENTILATION AIR CONDITIONING AIR CLEANING HEATING APPENDIX Q ELIGIBLE

More information

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER 2000 Elsevier Science Ltd. All rights reserved. Air Distribution in Rooms, (ROOMVENT 2000) Editor: H.B. Awbi 731 IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

More information

Eco Active H E A T R E C O V E R Y S Y S T E M S. Heat Recovery Penthouse Turret. W: T:

Eco Active H E A T R E C O V E R Y S Y S T E M S. Heat Recovery Penthouse Turret. W:   T: Eco Active Heat Recovery Penthouse Turret W: www.gdl.co.uk T: 01457 861538 Heat Recovery Penthouse Turret The HRPT provides ventilation into spaces all year round. The unit provides 100% fresh air whilst

More information

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect A Numerical Investigation on the Effect of Operation Control of a Multi-Split Air-Conditioning System on Indoor Thermal Environment H. Matsunaga 1,*, S. Iizuka 1, M. Okumiya 1, G. Yoon 2, and H. Niwa 3

More information

Mechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation

Mechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation Mechanical Technical Report 1 Standard 62.1 Ventilation Compliance Evaluation Lutheran Theological Seminary at Philadelphia The New Learning Center Prepared For: William P. Bahnfleth, Ph.D., P.E. Department

More information

Passivhaus. sally godber MEng CEng MIMechE WARM: Low Energy Building Practice. The first 3 in the UK.

Passivhaus. sally godber MEng CEng MIMechE WARM: Low Energy Building Practice. The first 3 in the UK. Passivhaus The first 3 in the UK sally godber MEng CEng MIMechE www.peterwarm.co.uk Intro to me/warm Mechanical Engineer Background in building services Set up WARM Jan 2009 Involved in 5 Passivhaus schools

More information

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency Haiye Lou TurboMoni Applied Dynamics Lab Abstract It is often happened, when a project

More information

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps AM-4249223-1 - Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps Christian K. Bach, Graduate Student, Eckhard A. Groll, Reilly Professor, James

More information

Slimline 150 & 300 Exceptionally low energy consumption. High Efficiency, Low Profile Heat Recovery Range

Slimline 150 & 300 Exceptionally low energy consumption. High Efficiency, Low Profile Heat Recovery Range & 300 Exceptionally low energy consumption High Efficiency, Low Profile Heat Recovery Range & 300 High Efficiency, Low Profile Heat Recovery Range High-efficiency, low profile MVHR units to deliver exceptionally

More information

Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2

Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2 A CFD Analysis of Smoke Movement in Steel Industry Sheds Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2 Mechanical Dept. Dr.Babasaheb Ambedkar College of Engineering and Research,

More information

Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement

Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement Daisuke Ogura 1, Masahide Inuzuka 2, Shuichi Hokoi 1, Takeshi Ishizaki 2, Hiroyuki Kitahara

More information

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance Jong Min Choi, W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building

More information

The Corbioli House is a single-family house situated

The Corbioli House is a single-family house situated All-in-one high-performing system for ZEB houses Maria Ferrara Grant researcher TEBE Research Group Energy Department Politecnico di Torino at Turin, Italy maria.ferrara@polito.it Frederic Kuznik Full

More information

ENERGY EFFICIENCY BRIEF REPORT

ENERGY EFFICIENCY BRIEF REPORT ENERGY EFFICIENCY BRIEF REPORT 1 Odooproject s energy efficient building design was mainly formed by the tight interaction of students from the Faculty of Architecture and the Faculty of Mechanical Engineering

More information

EEN-E Measurement and Control of Energy Systems DRYING OF BIOMASS IN A FIXED BED DRYER LABORATORY EXERCISE INSTRUCTIONS

EEN-E Measurement and Control of Energy Systems DRYING OF BIOMASS IN A FIXED BED DRYER LABORATORY EXERCISE INSTRUCTIONS EEN-E1040 - Measurement and Control of Energy Systems DRYING OF BIOMASS IN A FIXED BED DRYER LABORATORY EXERCISE INSTRUCTIONS Aalto University Laboratory of Energy Efficiency and Systems 2016 Table of

More information

LEED for Homes Points

LEED for Homes Points LEED for Homes Points This document is a guideline of the maximum potential points American ALDES ventilation products can contribute to obtaining certification under the US Green Building Council s (USGBC)

More information

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN , Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen

More information

Clearing the Air: Ventilation. RESNET Building Performance Conference San Diego, CA February 17 th, 2015

Clearing the Air: Ventilation. RESNET Building Performance Conference San Diego, CA February 17 th, 2015 Clearing the Air: Ventilation RESNET Building Performance Conference San Diego, CA February 17 th, 2015 Agenda Value of mechanical ventilation and indoor air quality. Three major components: Local mechanical

More information

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System Feasibility of a Liquid Desiccant Application in an Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, S.K.Han 1, S.Y. Cho 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang

More information

Heat pump and energy recovery systems

Heat pump and energy recovery systems SBS5311 HVACR II http://ibse.hk/sbs5311/ Heat pump and energy recovery systems Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Oct 2017 Contents Basic concepts Air-to-air

More information

European Parliament and of the Council with regard to energy labelling of residential ventilation units. (Text with EEA relevance) (2016/C 416/06)

European Parliament and of the Council with regard to energy labelling of residential ventilation units. (Text with EEA relevance) (2016/C 416/06) C 416/16 EN Official Journal of the European Union 11.11.2016 Commission communication in the framework of the implementation of Commission Regulation (EU) No 1253/2014 implementing Directive 2009/125/EC

More information

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure. 1 PSYCHROMETICS Psychrometry is the study of the characteristics of moist air. We will see soon that evaporation of moisture from the skin can have a significant impact on thermal comfort. The rate of

More information

SUNWARM AIR SOLAR PRE-HEAT VENTILATION SYSTEM

SUNWARM AIR SOLAR PRE-HEAT VENTILATION SYSTEM SOLAR PRE-HEAT VENTILATION SYSTEM SUNWARM USES SOLAR ENERGY TO REDUCE THE HEATING DEMAND OF THE HOME AS WELL AS PROVIDING A COMPLETE VENTILATION SOLUTION. 76 BENEFITS Sunwarm Air provides both a ventilation

More information

Heat Recovery Units. Heat Recovery 1

Heat Recovery Units. Heat Recovery 1 Heat Recovery Units Heat Recovery 1 Heat Recovery Unit Why? A heat recovery unit (HRU) can help make mechanical ventilation more cost effective by reclaiming energy from exhaust airflows. HRUs use air-to-air

More information

indirect evaporative cooling: interaction between thermal performance and room moisture balance

indirect evaporative cooling: interaction between thermal performance and room moisture balance indirect evaporative cooling: interaction between thermal performance and room moisture balance M. Steeman 1, A. Janssens 1, M. De Paepe 2 1 Department of Architecture and Urban Planning, Ghent University,

More information

The Experimental Validation of Numerical Modeling of the Air Distribution in the Indoor Ice Rink Arena

The Experimental Validation of Numerical Modeling of the Air Distribution in the Indoor Ice Rink Arena Proceedings of the World Congress on Mechanical, Chemical, and Material Engineering (MCM 2015) Barcelona, Spain July 20-21, 2015 Paper No. 276 The Experimental Validation of Numerical Modeling of the Air

More information

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.

More information

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 SAE Alternate Refrigerant Cooperative Research Program Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 To: Alternate Refrigerant Task Force Members From: Ward Atkinson

More information