1 GB Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport 3. Storage 4. Installation 4.1 Prior to attachment 4.2 Attachment 4.3 Mounting brackets 4.4 Duct connection 4.5 Electric connection 5. Start of operation 5.1 Prior to start of operation 5.2 Motors with Y/Δ starting 5.3 Starting procedure 6. Maintenance 6.1 Protection prior to inspection and maintenance 6.2 Fan casing 6.3 Impeller 6.4 Motor 6.5 Dismounting of motor 6.6 Mounting of motor 6.7 Blade pitch adjustment 6.8 Fault localization 7. Test of operability and operating condition 7.1 Periodic inspection 8. Sound 9. Attestation of conformity 1. Application are sturdy axial flow fans designed for both the daily ventilation requirements under normal conditions and smoke/heat exhaustion in the event of a fire in all kinds of commercial and industrial buildings. are tested and approved to meet the requirements of fans for smoke exhaustion class F300 (300 C for 60 minutes) and F400 (400 C for 120 minutes) according to standard: EN Handling 2.1 Marking The ACN smoke exhaust fan is provided with a standard nameplate with Novenco's name and address. It also mentions type/size e. g. ACN 1000/380, number of blades, year of production, weight, serial number/order number (production number). Furthermore, it mentions maximum temperature and working period in minutes and if the fan is supplied with approval number, class/category are also mentioned as well as test standard applied (EN ). Fan pressure, air quantity, output and maximum speed per minute. The fan is also provided with a motor nameplate with relevant motor data including insulation class of the motor. 160, 230, 280, 330 and Type ACN-smoke Fan size 2.2 Weight The total weights shown in table 1 apply to axial flow fan type ACN-smoke. The total weight is determined on the basis of type/size of fan and maximum motor size employed and is in terms of kg. 2.3 Transport When transporting the fans take care that no water (e. g. rainwater) gets into the motor or other sensitive components. are delivered on pallets or bearers to allow fork-lift transport. The forks of the fork-lift truck must lift underneath the frame. Set down the fan as slowly as possible and on a soft foundation. Vibrations, shocks, and fall may result in imbalance and deformation and may damage the motor bearings. Motor size Motor type Motor Weight (kg) Table 1. Example of total weights (Fan incl. motor, LOHER 4-pole) [kg] MU

2 3. Storage can stand outdoor storage for 1 month provided the packing is intact. Fans with no packing must be stored in a sheltered place. If the fans are stored indoors under wellventilated conditions with no risk of condensation the storage period may be extended to 6 months. The storage place must not be exposed to vibrations likely to damage the motor bearings. If the storage period exceeds 3 months, it is recommended to turn the impeller regularly by hand. 4. Installation Figure 1. Mounting foot for type ACN 4.1 Prior to attachment Prior to attachment make sure that the impeller rotates freely in the fan casing, wherever possible with equal distance between blade tip and fan casing throughout the circumference. 4.2 Attachment Fans must always be installed so that the rotating parts cannot be touched. The fan must be provided with a wire guard on the inlet and outlet sides. If ducts are connected, they should be provided with wire guards on the inlet side. The fan is provided with an arrow-plate denoting the direction of air flow through the fan casing. See during installation that the fan is oriented so as to provide the desired direction of air flow in the system. The best way of installing the fan is using mounting feet (available as optional extras), but it may also be suspended in the fan casing flanges or in special carriers. The carriers must not hamper the free inlet and outlet of air. When the fan has been finally secured make sure that the impeller rotates freely in the casing. If the motor is provided with drain holes for condensed water the fan must be oriented so that the holes turn downwards (lowest point). Generally, it is of the utmost importance for the performance and sound level of an axial flow fan that the air flow is unimpeded and free from eddies. Figure 2. ACN with mounting foot and antivibration mountings 4.3 Mounting feet Mounting feet for type ACN-smoke consist of two mounting plates (see fig. 1item 01). Mount two stiffeners (item 02) between these by means of joining elements (item 03). Stiffeners are only available from fan size 630 mm inclusive. To prevent vibrations spreading from the fan to the surroundings, anti-vibration mountings may be inserted between fan and support and flexible connections fitted in the ducts before and after the fan (available as optional extras). Secure anti-vibration mountings (fig. 2 item 06) in the mounting feet by means of bolts (item 05). Mount base plates (item 07) for attachment in the foundation/floor at the bottom of the rubber element. The natural frequency of the support must differ at least 20% from the fan speed. The anti-vibration mountings serve to ensure that the natural frequency of the system does not exceed 10 Hz and that the damping is at least 80% at 1500 r.p.m. 2

3 4.4 Duct connection In order to achieve the capacities stated on the performance curves the fans must be provided with ducts as shown in fig. 3 and fig. 4. The duct or inlet cone on the fan inlet side must be designed to ensure smooth and undisturbed flow of the air; ACN-smoke fans are prepared for circular duct connection on both inlet and outlet sides. Flanges supplied as standard for type ACN comply with EUROVENT 1/2. Systems with higher vibration level or more exacting performance requirements must be provided with expansion joints between fan and duct, and ducts must not be supported by the fan. It is important to allow for free areas to facilitate mounting and dismounting as well as ordinary maintenance. Figure 3. Installation in duct system Figure 4. Inlet cone for connection to duct 4.5 Electric connection Connection to the mains is made according to current legislation and by authorized personnel. Connection to the mains is effected direct in the motor terminal box or in the terminal box mounted on the outside of the fan casing (see fig. 6). Connection is made according to connection diagram on the inside of the terminal box cover. Having wired the motor terminal box, check that the direction of rotation of the impeller complies with the arrow-plate fitted on the outside of the fan. 5. Start of operation 5.1 Prior to start of operation Approval (prior to start of operation). After installation of the axial flow fans their correct installation, operation and interaction must be established through an approval test. The person responsible for the operation of the system must take the initiative for this test. The approval test must be confirmed by the person responsible for the operation of the system and the documentation must be kept and produced whenever asked for. Prior to start of operation check that the fan and duct connections are clean and free from tools and foreign substances. Also check that the electric connections meet the prescribed requirements, that any wire guard fitted on the fan inlet or outlet side is correctly mounted and that the direction of rotation of the fan complies with the arrow-plate (check by short-time operation). 5.2 Motors with Y/Δ starting The relay must be set to the calculated time. 5.3 Starting procedure Start the fan Check that no abnormal noises occur. See that the vibration level is normal. The vibration level at the fan operating speed must not exceed 7 mm/s rms, measured radially at 2 points, 90º offset and at the free shaft end of the motor. Otherwise, the fan must be balanced. Operation at a higher vibration level exceeding 11 mm/ s rms* is not allowed in case of fixed fan position. Operation at a higher vibration level exceeding 18 mm/s rms* is not allowed in case of position on feet or anti-vibration mountings. After 30 minutes of operation check that the fan operates normally. * ISO 2954, Requirements for instruments for measuring vibration severity. 6. Maintenance 6.1 Protection prior to inspection and maintenance When the fan is out of operation for reasons of inspection or repair/maintenance, the electric system must be switched off and protected so that the fan is not cut in unintentionally. 6.2 Fan casing The fan casing requires no maintenance other than ordinary cleaning. If the fan casing is painted, the painted surface should be checked regularly and repaired where necessary. 3

4 6.3 Impeller From the factory the impeller is supplied with the blades adjusted to the pitch corresponding to the desired operating point (pressure and air flow) at the fan speed in question. To ensure vibration free operation the impeller has been carefully balanced in this position. Vibrations occurring during operation will normally be due to accumulations of dust or dirt on the hub and blades, and will disappear after cleaning. Should this not be the case, expert assistance should be called in immediately, as continued vibrations will shorten the life of the motor bearings. 6.4 Motor The motor normally only requires maintenance of the bearings as indicated in the maintenance instructions for electric motors. 6.5 Dismounting of motor for types ACN-smoke (see fig. 5) Prior to commencing the work, switch off the current and disconnect the motor cable. Next, dismount any ducts on the fan inlet and outlet sides. Remove the impeller centre screw (see item 01), centre disc (see item 02) and hub cover (see item 03). Dismount the impeller by means of a puller fastened in the 2 threaded holes of the hub boss/threaded holes for puller (see item 05). Detach the motor by loosening the screws in the motor shell (see item 06). Now the motor (see item 11) and motor flange (see item 10) can be removed. In dismounting and disassembling the fan be careful not to expose the individual parts to shocks etc. likely to damage the motor bearings or other fan components. 6.6 Mounting of motor for types ACN-smoke (see fig. 5) After servicing remount the motor, take care that the motor flange (item 10) is correctly located and that the motor shaft is concentrically placed in the fan casing before tightening the bolts (item 06). Mount the impeller (item 04) on the motor shaft by means of a tool fastened in the threaded hole of the motor shaft. Fix the impeller hub to rest against the motor shaft collar. Check that the blade clearance of the impeller is the same throughout the circumference of the casing. If that is not the case, adjust the motor location in the suspension arrangement. Now mount centre screw (item 01), centre disc (item 02), and hub cover (item 03). Replace lock washers/lock nuts during fan assembly. Finally connect motor cable (item 13) in terminal box (item 12) and ducts, if any. To start the fan follow the procedure described in section 5. Start of operation. 6.7 Blade pitch adjustment The blade pitch has been adjusted in the factory with a special tool (mounting fixture) to deliver the performance required by the customer/order on delivery. If the fan performance is required to be changed it is possible to change the blade pitch. It requires knowledge of the motor load and the max. permissible blade pitch on the graph as related to the motor rating (in case of blade pitch increase). Contact Novenco before any such adjustment of the blade pitch. Novenco can supply special tools for blade pitch adjustment and instructions for impeller balancing. The brochure Blade Angle Tool is available on request. Figure 5. Dismounting/mounting of axial flow fan 4

5 Novenco A/S Industrivej 22 Tel. (+45) DK-4700 Naestved Fax (+45) Denmark External terminal box Electric cable/ Flexible metallic conduit 9. Attestation of conformity EU Attestation of Conformity The Machinery Directive 2006/42/EC, part 2, A Metal cable gland (relief) Nut Novenco A/S Industrivej 22 DK-4700 Naestved Hereby declares that axial flow fans type ACN-smoke have been manufactured in conformity with the Council's directives 2006/42/EC regarding mutual approximation of the machinery laws (the Machinery Directive) of the member states. Figure 6. Electric connection through fan casing to external terminal box 6.8 Fault localization These are likely causes of breakdowns/ failures: Deficiency in performance: Blocked air supply to the fan inlet side: Damper closed Duct choked Supply fan, if any, stopped Motor defective Motor disconnected Wrong direction of rotation of impeller Noise/vibrations: Bearings in electric motor defective Impeller out of balance Impeller worn/damaged Bolts/components loose Impeller blades have different pitch angles Fan operates in the stalling area. May result in breakdown. Repair failures, see Deficiency in performance. to a time switch or carbon monoxide alarm. 7.1 Periodic inspection Novax smoke exhaust fans must always be kept in operational and perfect condition by the user. The fans should be inspected twice a year to ensure a satisfactory function and long life. The inspection must include: Measuring of power consumption Measuring of vibrations on fan casing Check of torque for fixing bolts and correction of it, if necessary. Visual inspection of impeller, fan casing, and connection to the electricity supply Cleaning: inside with pressure air outside with water It is recommended to enter all values and observations in a log. Applied standards: EN ISO : Safety of machinery part 1 EN ISO : Safety of machinery part 2 EN ISO 13857: Safety of machinery - Safety distances EN : Smoke and heat control systems - Part 3, class 1 EN : Safety of machinery - Electrical equipment of machines Part 1: General Requirements It is a condition that Novenco's instructions for installation have been followed. Naestved, Steen Hansen R&D Manager Novenco A/S 7. Test of operability and operating condition ACN-smoke approved for smoke control must be tested four times a year as to operability and operating condition. If smoke exhaust fans type ACN-smoke are used for standard ventilation as well, a test every six months is sufficient if the regular starts of the fans ensure at least one start a day - as a result of connection 8. Sound The sound generation of the fans depends on installation and operating conditions, which means that no general data of the sound generation can be given. Reference is made to our catalogues or computer programs for calculation of the specific sound generation. 5

ACN SMOKE INSTALLATION AND MAINTENANCE

ACN SMOKE INSTALLATION AND MAINTENANCE NovAx ACN SMOKE INSTALLATION AND MAINTENANCE 918149-0 English 918149-0 GB Installation and maintenance NovAx smoke exhaust fan type ACN smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport

More information

AZN ATEX INSTALLATION AND MAINTENANCE

AZN ATEX INSTALLATION AND MAINTENANCE ZerAx AZN ATEX INSTALLATION AND MAINTENANCE 924714-0 English 924714-0 GB ZerAx axial flow fans type AZN ATEX Installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Temperature

More information

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 916503-0 GB Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 1. Main components 2. Application 3. Handling 3.1 Marking 3.2 Weight 3.3 Transport 4. Storage 1. Main components: Types ARC,

More information

English CNA-CNB. Centrifugal fans Installation and maintenance

English CNA-CNB. Centrifugal fans Installation and maintenance 916505-0 English CNA-CNB Centrifugal fans Installation and maintenance 916505-0 GB Centrifugal fans types CNA, CNB, CNA-M and CNB-M installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2

More information

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE 2 GLEC-6 - Installation and maintenance CONTENTS 1 Important information... 3 2 Safety notes... 3 3 Technical description...4 4 Transport... 6 5

More information

Installation and maintenance instructions for cabin units type vertical IDAC (V50)

Installation and maintenance instructions for cabin units type vertical IDAC (V50) GB Installation and maintenance instructions for cabin units type vertical IDAC (V50). Application. Bundled parts. Handling. Marking. Weight. Transport. Storage 5. Installation 5. Mounting 5. Water trap

More information

EC Box Fan www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions CONTENTS Paragraphs Safety 1 Handling/Storage 2 Installation (Mechanical) 3 Fig. 1: Fig. 2: Tilt Mechanism

More information

GLEB Kitchen exhaust fan

GLEB Kitchen exhaust fan GLEB Kitchen exhaust fan Installation and Maintenance??.1.2013 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

SMHA Hatch High temperature fan HT-fan Installation and Maintenance

SMHA Hatch High temperature fan HT-fan Installation and Maintenance High temperature fan HT-fan Installation and Maintenance 22.8.2012 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance TOP ECOSMART TWINFANS (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use Installation and Maintenance The EMC Directive 2014/30/EU The Low Voltage directive 2014/35/EU INDOOR USE ONLY Introduction

More information

Novenco jet fans. AUO / ARO / AUT / ART / CGF January 2010

Novenco jet fans. AUO / ARO / AUT / ART / CGF January 2010 Novenco jet fans AUO / ARO / AUT / ART / CGF January 2010 Product facts Product Novenco jet fans are produced in unidirectional (AU_ and CGF) and reversible (AR_) versions. AUT/ART circular Basic jet fans

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

IEC- Direct-driven radial fans with IEC-Standardmotor

IEC- Direct-driven radial fans with IEC-Standardmotor EHND / ERND / ERNE / Contents. / Page 1. / Safety... 2 2. / Description... 4 3. / Condition of use... 4 4., / Storage, Transport... 5 5. / installation... 6 6. / operation... 8 7. / maintenance... 9 8.

More information

Novenco Air Handling Units

Novenco Air Handling Units Novenco Air Handling Units Climaster ZCF Guide 919432-0 GB Important This document is provided As is and is subject to change without notice. Novenco reserves this right due to continuous product development.

More information

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use TOP INDOOR USE ONLY Introduction Units are rectangular in section and have circular/rectangular rigid spigots at each end. Four matching mounting feet are supplied with the unit. Full size access panels

More information

STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE

STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE ISO 9001 : 2000 STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE CUSTOMER : 1 CONTENTS 1 SAFETY... 5 1.1 General... 6 1.2 Description of symbols and pictograms... 6

More information

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING USER S MANUAL VCU/ Series CENTRIFUGAL FAN IN SCROLL CASING 2 CONTENTS Introduction Use Delivery set Designation key Technical data Safety requirements Design and operating logic Mounting and set-up Connection

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RFEC/U/2017-1 (EN) (valid since 18.08.2017) ROOF FANS RF/EC...-... / RFV/EC...-... Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the

More information

AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance

AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance 1.0 INTRODUCTION AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance The Nuaire Short Cased Axial Fan range is produced in a range of sizes from 250mm to 1600mm diameter. Cases are manufactured

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RF/U/2017 (ENGLISH) (valid since 13.10.2017) ROOF FANS RF / RFV Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the right to modify this

More information

AXPR Wall Mounted Axial Panel Fans

AXPR Wall Mounted Axial Panel Fans Bulletin 78-January-03-06 AXPR Wall Mounted Axial Panel Fans INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance instructions for the AXPR

More information

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original)

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original) Montageanleitung (Original) (Translation of the original) DE MA_ 1.0 06/2014 Taperlock Clamping-bush system _0 _1 Fixed hub Inlet nozzle with IMV 1. Revision index Revision Date MA_ 1.0 06/2014 2. Safety

More information

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL CONTENT 3 Introduction 3 General 3 Safety rules 3 Storage and transportation rules 3 Manufacturer s warranty 4 Fan design 4 Delivery set 5 Technical data

More information

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL CENTRIFUGAL FAN IN SCROLL CASING Helix S-Vent EN OPERATION MANUAL Helix / S-Vent www.blaubergventilatoren.de CONTENTS CONTENTS 3 Introduction 3 Use 3 Delivery set 4 Technical data 10 Safety requirements

More information

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPORATION P.O. BOX 2300 JACKSONVILLE, FLORIDA 32203 PHONE (904) 389-3646 FAX (904) 387-3449 E-MAIL - fans@coolair.com MNEFDD54 & MNBCDD54 GALVANIZED

More information

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEB KITCHEN exhaust FAN >> Installation and Maintenance Kitchen Exhaust Fan GLEB Installation and Maintenance Important Information, Safety notes, Technical Description

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble,

More information

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug

More information

Installation/Instruction Manual

Installation/Instruction Manual 1510876HC8902 Pressurized ventilators (for device cooling) Model Blade diameter (cm) Indoor or outdoor EF-20UYS-UL EF-25UAS-UL EF-30UBS-UL 20 25 30 Indoor Installation/Instruction Manual For customers

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL

INSTALLATION, OPERATION & MAINTENANCE MANUAL CENTRAL FANS COLASIT LTD Unit 12A, Palmers Road, East Moons Moat, Redditch. Worcs. B98 0RF Tel: 01527-517200 Fax: 01527-517195 Edition 04_13 INSTALLATION, OPERATION & MAINTENANCE MANUAL CIV Fan Range Valid

More information

AXIS-QA G TUBO-M/MZ AXIAL FANS. Axis / Tubo OPERATION MANUAL

AXIS-QA G TUBO-M/MZ AXIAL FANS. Axis / Tubo OPERATION MANUAL TUBO-M/MZ AXIS-QA AXIS-Q TUBO-F AXIS-QR AXIS-F AXIS-QRA AXIS-QA G AXIAL FANS EN OPERATION MANUAL www.blaubergventilatoren.de CONTENT 3 Introduction 3 General 3 Safety rules 3 Transport and storage requirements

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

Marley Ultra Quiet Fan

Marley Ultra Quiet Fan USER MANUAL Marley Ultra Quiet Fan DESIGNED FOR INDUCED-DRAFT COOLING TOWER APPLICATIONS M2012-1165 ISSUED 8/2012 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. safety and

More information

Owners Manual. SM-HP A SM-HP8-10 Meter. Manual D

Owners Manual. SM-HP A SM-HP8-10 Meter. Manual D DuraCore TM Fan Owners Manual SM-HP8-64-360A SM-HP8-10 Meter Manual 9-1473D 1 4 5 7 8 9 6 MONEL HARDWARE 7 8 9 STAINLESS HARDWARE 00 FAN BLADE FAN HUB 3 Fan Components Marley Order No. Trial Pitch Angle

More information

ECOSMART TWINFANS. (EST-X/R/B) 1 phase, Direct Drive, Run & Standby For External, Roof Mounted and Internal use Installation and Maintenance

ECOSMART TWINFANS. (EST-X/R/B) 1 phase, Direct Drive, Run & Standby For External, Roof Mounted and Internal use Installation and Maintenance EST-X Figure 1. EST-X unit. Removable top panel D Control module located internally External Commissioning box Table 1. EST-X Dimensions (mm) Weight Code A B C D dia. (kg) EST1-X 705 505 355 125 22 EST2-X

More information

ultra quiet fan USER MANUAL INSTALLATION OPERATION MAINTENANCE

ultra quiet fan USER MANUAL INSTALLATION OPERATION MAINTENANCE USER MANUAL ultra quiet fan INSTALLATION OPERATION MAINTENANCE Z0414808 rev A ISSUED 02/2014 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. safety and handling Safety Warning

More information

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance.

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance. ESX-X Figure 1. ESX-X units. Removable top panel A D Control module located internally External Commissioning box Table 1. ESX-X Dimensions (mm) Spigot Weight Code A B C D dia (kg) ESX1-X 705 505 355 125

More information

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP)

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) Our Expertise, Your Air-Moving Solution ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) PART# 0601710001_rev_A INSTALLATION, OPERATION & MAINTENANCE MANUAL Please read and save these instructions for future reference.

More information

EYS SEPARATOR EYS 01 G. USER MANUAL for EYS SCREW-PRESS SEPARATOR MODEL EYS 01 G. User Manual for EYS 01G Screw-Press Separator

EYS SEPARATOR EYS 01 G. USER MANUAL for EYS SCREW-PRESS SEPARATOR MODEL EYS 01 G. User Manual for EYS 01G Screw-Press Separator USER MANUAL for EYS SCREW-PRESS SEPARATOR MODEL EYS 01 G User Manual for EYS 01G Screw-Press Separator Table of Contents Page 1. Introduction 2 2. General Safety Instructions 3 3. Installation 5 4. Start-up

More information

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D CENTRIFLOW 3D Plug fan GMEC >> Installation and Maintenance air comfort CentriFlow 3D 2 Plug Fan CentriFlow 3D GMEC Installation and Maintenance Important Information, Safety notes, Technical Description

More information

TUNNEL FANS STANDARD AND HOT SMOKE

TUNNEL FANS STANDARD AND HOT SMOKE TUNNEL FANS STANDARD AND HOT SMOKE NovAx tunnel fans PRODUCT FACTS Product Novenco tunnel fans are produced with either round or rectangular outer dimensions. Both types are made in unidirectional (AUC

More information

PROCEDURE FOR INSTALLATION, MAINTENANCE AND OPERATION OF NYBORG AXIAL FANS, DIRECT DRIVEN.

PROCEDURE FOR INSTALLATION, MAINTENANCE AND OPERATION OF NYBORG AXIAL FANS, DIRECT DRIVEN. Document NYP1505C Approved by NN Issued 11.05.11 Issued by OMK Revision (no and date) PROCEDURE FOR INSTALLATION, MAINTENANCE AND OPERATION OF NYBORG AXIAL FANS, DIRECT DRIVEN. Limitation: This manual

More information

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL INLINE CENTRIFUGAL FAN OPERATION MANUAL www.blaubergventilatoren.de CONTENT 3 Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 4 Fan design 4 Delivery

More information

INLET DAMPER WALL FAN UNIT

INLET DAMPER WALL FAN UNIT FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPORATION P.O. BOX 2300 JACKSONVILLE, FLORIDA 32203 PHONE (904) 389-3646 FAX (904) 387-3449 E-MAIL - agfans@coolair.com INLET DAMPER WALL FAN UNIT

More information

PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS

PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS AIR COMFORT AIR TREATMENT 9933 GB 2016.05.25 PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN» INSTALLATION AND MAINTENANCE INSTRUCTIONS contents Page Installation options...... 2 Checks to be

More information

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS Contents Page User instructions 3-5 General 3 Fan installation 3-4 Maintenance 3 Electrical installation 5 Troubleshooting 5 Technical description 6-8 General

More information

for Ultima-Tig and for Ultima-Tig-Cut

for Ultima-Tig and for Ultima-Tig-Cut User manual for Ultima-Tig and for Ultima-Tig-Cut Inelco Grinders A/S, Industrivej 3, DK-9690 Fjerritslev, Denmark 1/7 EU statement of compliance Manufacturer: INELCO GRINDERS A/S Industrivej 3 9690 Fjerritslev

More information

KQ Series. Multistage Booster Pump System. Installation Manual. ISO 9001 Certified KQ200/400 KQ800

KQ Series. Multistage Booster Pump System. Installation Manual. ISO 9001 Certified KQ200/400 KQ800 KQ Series Multistage Booster Pump System Installation Manual KQ200/400 KQ800 ISO 9001 Certified Description The KQ series booster pump is an all-in-one compact and reliable automatic multistage centrifugal

More information

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN EQLK, DIRECT-DRIVEN INSTALLATION AND MAINTENANCE INSTRUCTIONS Contents Page Installation options...... 2 Checks to be made prior to commissioning...2 Electrical connections.....2 Measures before starting.....

More information

JM Aerofoil Fans Bulletin JMA60-05

JM Aerofoil Fans Bulletin JMA60-05 www.howden.com JM Aerofoil Fans Bulletin JMA60-05 Introduction The high performance JM Aerofoil Fan Benefits of the JM Aerofoil Fan include compactness, low cost, high efficiency and rugged design. Availability

More information

Operating Instruction Centrifugal fans without scroll (Translation of the Original) BA-RLE-AC /2014 RLE RLA

Operating Instruction Centrifugal fans without scroll (Translation of the Original) BA-RLE-AC /2014 RLE RLA Operating Instruction Centrifugal fans without scroll (Translation of the Original) EN RLE RLA Content 1. Important information 2. Safety notes 3.Technical description 4. Transport 5. Mounting / Installation

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) 52" Belt Drive, Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before

More information

USER S MANUAL. VKP Series INLINE FAN

USER S MANUAL. VKP Series INLINE FAN USER S MANUAL Series INLINE FAN 2 CONTENTS Safety requirements 3 Introduction 5 Use 5 Delivery set 5 Designation key 5 Technical data 5 Design and operating logic 8 Mounting and set-up 8 Connection to

More information

Marley X7 Fan USER MANUAL DESIGNED FOR INDUCED-DRAFT COOLING TOWER APPLICATIONS

Marley X7 Fan USER MANUAL DESIGNED FOR INDUCED-DRAFT COOLING TOWER APPLICATIONS USER MANUAL Marley X7 Fan DESIGNED FOR INDUCED-DRAFT COOLING TOWER APPLICATIONS M2010-1234A ISSUED 3/2012 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. Fan Components 1

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL SWP (Models SWP08 through SWP20) OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES Bucket Fan 420 Bucket Fan 1055 Bucket Fan 1460 420 1055 1460 2 Bucket Fan CONTENT INTRODUCTION 3 USE 3 WHAT S INCLUDED IN THE BOX 3 DESIGNATION

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V.

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. Irene 52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz TABLE OF CONTENTS Tools and Materials Required... 1 Package Contents... 1 Safety Rules... 2 Mounting Options... 3 Hanging

More information

Industrivej 3-9 DK 9460 Brovst KEF-MOTOR A/S. Fax Instruction Manual PSD 200 Industrial Grinders

Industrivej 3-9 DK 9460 Brovst KEF-MOTOR A/S. Fax Instruction Manual PSD 200 Industrial Grinders KEF-MOTOR A/S Industrivej 3-9 DK 9460 Brovst Tlf. +45 9823 6088 Fax. +45 9823 6144 1. Instruction Manual PSD 200 Industrial Grinders EU declaration of conformity KEF-MOTOR A/S Industrivej 3-9 DK-9460 Brovst

More information

OPERATING MANUAL NanoFlow

OPERATING MANUAL NanoFlow OPERATING MANUAL NanoFlow 101-160601800 Operating Manual 2017-02-10 EN From Serial No. 9328.1416 Fremco A/S Ellehammervej 14 9900 Frederikshavn Denmark Tel. +45 72 30 12 13 ORIGINAL Table of Contents Technical

More information

CENTAFLEX Series A Assembly and operating instructions CF-AR M EN Rev. 2

CENTAFLEX Series A Assembly and operating instructions CF-AR M EN Rev. 2 Contents 1 General remarks... 5 2 Safety... 6 2.1 Safety remarks... 6 2.1.1 Signal words... 6 2.1.2 Pictograms... 7 2.2 Qualification of deployed personnel... 7 2.3 Intended application... 7 2.4 Application

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance DUCTABLE WATER UNIT FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4 Installation Operation Maintenance Ductable water unit FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

Supply air unit VEKA Installation & Maintenance

Supply air unit VEKA Installation & Maintenance November 2008 Safety instructions Operating the air treatment unit and accessory components WARNING Before the air treatment unit is taken into service, any free connections must be provided with protective

More information

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz Please do not use any electric or battery powered tools in the assembly and installation of this or any Matthews Fan Company

More information

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer)

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) Galvanized Panel Fan IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble, install, operate

More information

Handling or using the product improperly and in disregard of the instructions with this mark might result in serious bodily injury or death.

Handling or using the product improperly and in disregard of the instructions with this mark might result in serious bodily injury or death. Please Read: Safety Precautions DC AC In order to ensure that this product is used safely, be sure that you read and understand the following precautions fully and use the product only as directed. Be

More information

Original instructions. Operation Manual & Cautions

Original instructions. Operation Manual & Cautions Original instructions Operation Manual & Cautions Thank you for purchasing the Mistresa from Showa Denki. This manual explains the specifications for the [Mistresa units from CRN Series]. Please read the

More information

1 - Donkin Fans. Majax-2 Aerofoil Axial Flow Fans

1 - Donkin Fans. Majax-2 Aerofoil Axial Flow Fans 1 - mj,, Donkin Fans Majax-2 Aerofoil Axial Flow Fans - IW '~AJAX-2 GENERAL SPF ~IFICATION Majax-2 axial flow fans are manufactured in diameters ranging from 315mm to 2000mm (available in 2250mm on request),

More information

Axial flow fan AXICO ANTI-STALL

Axial flow fan AXICO ANTI-STALL Product data sheet: AXICO ANTI-STALL Axial flow fan AXICO ANTI-STALL Model FPAC and FPMC axial flow fans with controllable pitch blades. Air flow range: 3-110 m³/s (10.000 400.000 m³/h). Pressure rise:

More information

Long Case Axial Fan. Installation and Wiring Instructions V/1/50Hz & V/3/50Hz

Long Case Axial Fan. Installation and Wiring Instructions V/1/50Hz & V/3/50Hz Long Case Axial Fan Installation and Wiring Instructions 220-240V/1/50Hz & 380-415V/3/50Hz RAD INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLAS SAV THS INSTRUCTIONS Installation and Wiring Instructions

More information

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH THE ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH THE ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS eturboprop High Pressure Axial Fans Installation and Wiring Instructions Stock Ref. 45012 50012 56012 63012 45032 50032 56032 63032 PLAS RAD ISTRUCTIOS I COJUCTIO WITH TH ILLUSTRATIOS. PLAS SAV THS ISTRUCTIOS

More information

Installation and Wiring Instructions

Installation and Wiring Instructions Powerline (TDF) Installation and Wiring Instructions TDF32014 TDF38014 TDF42014 TDF48014 TDF38034 TDF42034 TDF48034 TDF52034 TDF52036 TDF60034 TDF60036 PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE STARTING

More information

SOUND-INSULATED FAN. Iso-B OPERATION MANUAL

SOUND-INSULATED FAN. Iso-B OPERATION MANUAL SOUND-INSULATED FAN Iso-B EN OPERATION MANUAL Iso-B www.blaubergventilatoren.de CONTENTS Safety requirements... 3 Introduction... 5 Purpose... 5 Delivery set... 5 Technical data... 6 Design and operating

More information

Electric Blower Motor Operating Instructions and Warnings

Electric Blower Motor Operating Instructions and Warnings ZF-9503-4E Electric Blower Motor Operating Instructions and Warnings Centrifugal Motor Direct-coupling Blower Thank you for purchasing Showa Denki s blower. These Operating Instructions and Warnings provide

More information

Design and manufacture of agitators since INSTALLATION MANUAL Start-up and maintenance. Top-entry agitators

Design and manufacture of agitators since INSTALLATION MANUAL Start-up and maintenance. Top-entry agitators Design and manufacture of agitators since 94 Top-entry agitators CONTENTS Page - Introduction - Precautions prior to start-up 4 - Safety recommendations 6.. Protection against the risk of explosion 6..

More information

Centrifugal Fan Turbofan Type KT/KP

Centrifugal Fan Turbofan Type KT/KP Instruction Manual TF-113-01 Centrifugal Fan Turbofan Type KT/KP Do not carry out operation, inspection or maintenance of the fan until you read this manual and understand the content. Keep this manual

More information

TTV 4500 / TTV 4500 HP / TTV 7000

TTV 4500 / TTV 4500 HP / TTV 7000 TTV 4500 / TTV 4500 HP / TTV 7000 EN OPERATING MANUAL AXIAL FAN TRT-BA-TTV4500-4500HP-7000-TC-003-EN Table of contents The current version of the operating manual can be found at: Notes regarding the operating

More information

NHS VERTICAL AGITATOR

NHS VERTICAL AGITATOR INSTALLATION, SERVICE AND MAINTENANCE INSTRUCTIONS NHS VERTICAL AGITATOR INOXPA, S.A. c/telers, 54 Aptdo. 174 E-17820 Banyoles Girona (Spain) Tel. : (34) 972-57 52 00 Fax. : (34) 972-57 55 02 Email: inoxpa@inoxpa.com

More information

p Permanent magnet water cooled motors Additional manual

p Permanent magnet water cooled motors Additional manual p Permanent magnet water cooled motors Additional manual Safety Instructions 1 General General safety regulations, safety precautions and specific agreements made for each work site shown in this document

More information

IPVB EC inline power venter

IPVB EC inline power venter Installation and operation manual IPVB 300-500 EC inline power venter READ AND SAVE THESE INSTRUCTIONS! Product information Chapters 1 + 2 Mechanical installation Chapter 3 Electrical installation Chapter

More information

AXIAL FAN User s manual. Quiet-dMEV 100 DC.

AXIAL FAN User s manual. Quiet-dMEV 100 DC. AXIAL FAN User s manual Quiet-dMEV 100 DC www.ventilation-system.com CONTENTS Delivery set... 6 Brief description... 6 Operating guidelines... 6 Designation key... 7 Installation and set-up... 7 Fan options...

More information

568X, 587X, 588X Series

568X, 587X, 588X Series Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16

S SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16 Webster Pumps "S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16 PLEASE READ THE FOLLOWING INFORMATION PRIOR TO INSTALLING AND USING Webster PUMPS or HAYWARD VALVES,

More information

Eliza 56 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz

Eliza 56 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz Eliza 56 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz Please do not use any electric or battery powered tools in the assembly and installation of this or any Matthews Fan Company

More information

SAM TURBO INDUSTRY LIMITED

SAM TURBO INDUSTRY LIMITED INSTRUCTIONS ON INSTALLATION, OPERATION AND MAINTENANACE FOR SAM TURBO PUMP TYPE MD SAM TURBO INDUSTRY LIMITED NEELAMBUR, COIMBATORE-641 014. INDIA PH: 0422-3058899(50 LINES), FAX: 3058000, E-MAIL: mktg@sampumps.com,

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS CEILING FAN INSTALLATION AND OPERATION INSTRUCTION FAN RATING AC 120V. 60Hz UL LISTED MODEL: AC-552OD WEIGHT OF FAN: 6.82 KGS 1. TOOLS AND MATERIALS REQUIRED Philips screw

More information

MEV-DC. Continuous Mechanical Extract Ventilation Units Installation and Maintenance. Figure 3. Fixing screw hole.

MEV-DC. Continuous Mechanical Extract Ventilation Units Installation and Maintenance. Figure 3. Fixing screw hole. MEV-DC Continuous Mechanical Extract Ventilation s Installation and Maintenance The EMC Directive 2014/30/EU The ow Voltage directive 2014/35/EU 1.0 Introduction uaire's MEV-DC units are designed to provide

More information

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions. Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

SEMAK VITABLEND STICK BLENDER MODELS VB250, VB360, VB410 & VB510

SEMAK VITABLEND STICK BLENDER MODELS VB250, VB360, VB410 & VB510 SEMAK VITABLEND STICK BLENDER MODELS VB250, VB360, VB410 & VB510 OPERATION AND WARRANTY BOOKLET VB250 VB360 VB410 VB510 SEMAK AUSTRALIA: FACTORY 18, 87-91 HALLAM SOUTH ROAD, HALLAM VIC 3803 PH 03 9796

More information

USER S MANUAL. Centrifugal inline fan. VKMz 100 Q VKMz 100 VKMz 125 Q VKMz 125. VKMz 250 Q VKMz 250 VKMz 315 Q VKMz 315

USER S MANUAL. Centrifugal inline fan. VKMz 100 Q VKMz 100 VKMz 125 Q VKMz 125. VKMz 250 Q VKMz 250 VKMz 315 Q VKMz 315 USER S MANUAL VKMz 100 Q VKMz 100 VKMz 125 Q VKMz 125 VKMz 150 VKMz 160 VKMz 200 Q VKMz 200 VKMz 250 Q VKMz 250 VKMz 315 Q VKMz 315 Centrifugal inline fan VKMz CONTENTS Contents... 2 Safety requirements...

More information

ISCG90SS _03 ISCG90SS

ISCG90SS _03 ISCG90SS ISCG90SS 60900355_03 ISCG90SS GB IE [01] x 1 [02] x 1 [03] x 1 [04] x 8 [05] x 1 [06] x 4 [07] x 1 [08] x 1 [09] x 1 [10] x 4 [11] x 4 [12] x 1 [13] x 4 (6x70mm) [14] x 8 (6.3x17x2mm) 1 : 1 [15] x 4 (3.9x18mm)

More information

XB-EFA-8L-BK & XB-EFA-8R-BK

XB-EFA-8L-BK & XB-EFA-8R-BK Supply & Extract Ventilation Unit with Heat Recovery The EMC Directive 2014/30/EU The Low Voltage Directive 2014/35/EU The information contained in this document provides details of installation, operation

More information

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) www.blowtech.in we make air move Blowtech Air Devices Pvt. Ltd. was founded in 1988 and quickly established

More information

VUT 350 H VUT 500 H VUT 530 H VUT 600 H VUT 1000 H VUT 2000 H HEAT RECOVERY AIR HANDLING UNIT

VUT 350 H VUT 500 H VUT 530 H VUT 600 H VUT 1000 H VUT 2000 H HEAT RECOVERY AIR HANDLING UNIT РУКОВОДСТВО USER S MANUAL ПОльзователя VUT 350 H VUT 500 H VUT 530 H VUT 600 H VUT 1000 H VUT 2000 H HEAT RECOVERY AIR HANDLING UNIT 2 CONTENTS Safety requirements 3 Introduction 5 Use 5 Delivery set 5

More information

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2 Cleaning unit for coolant :_decftez`_>r_fr] Book No.: 1271526-02 V2 Alfa Laval Separation AB Separator Manuals, dept. SKEL S-147 80 Tumba, Sweden Telephone: +46 8 53 06 50 00 Telefax: +46 8 53 03 10 40

More information

Enviro KES INSTALLATON MANUAL

Enviro KES INSTALLATON MANUAL Enviro KES INSTALLATON MANUAL Spring Air Systems Inc., Oakville, Ontario Phone (905) 338-2999, Fax (905) 338-0179, info@springairsystems.com www.springairsystems.com KES Installation Manual. This publication

More information

60, 52" or 42" CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz

60, 52 or 42 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz Super Janet 60, 52" or 42" CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz FOR DAMP LOCATION Please do not use any electric or battery powered tools in the assembly and installation

More information