THERMOSYS 4.3. Getting Started Guide

Size: px
Start display at page:

Download "THERMOSYS 4.3. Getting Started Guide"

Transcription

1 THERMOSYS 4.3 Getting Started Guide February 2016

2 Table of Contents 1 Installation and File Organization THERMOSYS by Example THERMOSYS Component Descriptions Compressor Condenser Thermostatic Expansion Valve Evaporator Box Model Simulink Blocks: On-Off Controller and Simulation Settings Additional THERMOSYS Models Not Applied in this Example Running Simulations Future Updates and Advanced Use

3 Overview: THERMOSYS is a toolbox designed for the Simulink environment within MATLAB that models and simulates vapor compression systems. Component models including a compressor, evaporator, condenser, multipurpose tank, valves, and more allow the simulation of these systems. Coupled with the power of the existing Simulink library, control schemes can be applied in order to aid the design and effective control of thermal systems. NOTE: This Getting Started Guide is for versions of MATLAB prior to 2012b. A second guide for Matlab 2012b and newer will be issued soon with updated screenshots for the new User Interface. 1 Installation and File Organization THERMOSYS includes separate instructions for installation and licensing which should be followed before using the program. Before each use of THERMOSYS, ensure that the entire install folder and its subfolders are part of the MATLAB path. The Simulink Library Browser will display the THERMOSYS toolbox if this is done properly. The toolbox should display a Components and a Fluid Properties icon. The Components section is where the user can drag blocks into Simulink models. With this in mind, we can close Simulink and take a moment to browse through the THERMOSYS install directory. Within the install folder, several other subfolders and files are available and discussed below: Component S-Functions This contains the code that each Simulink block calls. These are compiled code and are unavailable for viewing or editing. Fluid Tables This directory contains fluid property tables for the different refrigerants and gases used within THERMOSYS. THERMOSYS includes properties for Air, Ammonia, CO 2, Glycol(75%)/Water(25%), R21, R134a, R245fa, R404a, R407c, R410a, R507a, and Water. In a pending update, software will be provided that allows for the generation of these tables for additional refrigerants using the NIST software REFPROP. Heat Transfer Coefficients This contains heat transfer coefficients necessary for the models. These are compiled code and are unavailable for viewing or editing. HelpFiles This contains the various help files about the various components which will be accessible in the MATLAB Simulink help browser. Icons This directory contains the images used in each of the THERMOSYS blocks. It is not recommended that these be altered. Licensing This directory contains initialization and validation files for the THERMOSYS licensure system. The thermosys.license.dat file you will receive after sending in your license request should be placed in this folder. Sample Systems This directory contains sample refrigeration systems. These are useful for reference and show many different block connections. They also demonstrate how other Simulink blocks can be used to implement control on the systems. 3

4 Single Component Models This directory contains simple examples with individual components for a basic understanding of their inputs and outputs. Support Functions Some of these functions are called within the various component models, while others are user-oriented utilities. Within this folder, Fluid Table Generation has compiled code which generates fluid property tables from REFPROP. However, the MATLAB interface provided with the purchase of REFPROP is only compatible with MATLAB versions prior to For this reason, a separate package for fluid property tables is in development that is compatible with current versions. With the current release, these functions are not packaged for standalone use, and are only called by the THERMOSYS blocks when needed. slblocks.m This file automatically adds the THERMOSYS toolbox to the Simulink Library Browser. It must be part of the MATLAB path before opening Simulink, but no other user interactions are needed. thermosys.mdl This file contains the actual THERMOSYS blocks. Within this file, the masks (which contain the user interface and default parameters) can be viewed and edited. Editing the block masks is not recommended. The user may simulate their own system by dragging and dropping blocks from this file or the Library Browser into a new Simulink model, as shown in Section 2 of this guide. 2 THERMOSYS by Example The following is a demonstration example using Sample System #3 to get users started with THERMOSYS. Open Sample_3_TXV_Box_On_Off_Cycling.mdl in the Sample Systems. This can be accomplished by either double clicking the file within your file browser (which should then open MATLAB and the sample), or by opening the file within MATLAB or Simulink. Sample 3 is used for this demonstration as it includes a wide variety of components along with a usercreated control system (using non-thermosys Simulink blocks). These include a refrigeration loop consisting of a compressor, condenser, expansion valve, and evaporator. This loop (in conjunction with a simple On-Off controller) regulates the temperature within a Box Model (essentially a room affected by its environment). This example, as provided, regulates the temperature of the box to a value between 19 and 20 degrees C. With the sample open, run the model by clicking the play button shown at the left below in Figure 1. One can then double-click the eyeglasses-shaped icon within the model as indicated in the right of the figure below to open a scope view of the box temperature changing in time. Figure 1. Running and Viewing Sample 3. 4

5 After running the simulation for a few seconds, it is advised to click the Autoscale button within the scope view or to select Autoscale from the right-click drop-down menu. NOTE: repeatedly autoscaling the embedded scopes in the examples can crash the simulation. This is not the case for the discrete scope blocks like. If the simulation crashes when autoscaling the scope accept the error message and restart the simulation. When run successfully, the scope should display a drop in temperature to 19 degrees, and at this point the refrigeration system shuts down, allowing the environment to heat the box. With more simulation time, the refrigeration system enables again when the temperature has risen to 20 degrees. A sample of system pressures and box temperature output with the TXV cycling on and off is shown below in Figure 2. Figure 2. Sample 3 Successful Code Output (3000 sec.). 2.1 THERMOSYS Component Descriptions All components applied in Sample 3, their connections, and their initial conditions are now described in detail. Special considerations for the components will also be mentioned. Following the THERMOSYS components used in Sample 3, the remaining Simulink components will be overviewed in the Section 2.3. In this example, all inputs and outputs to most blocks are linked to Simulink standard goto and from tags for neatness. Figure 3 shows the full simulation model. 5

6 Figure 3. Full Simulation Loop for Sample 3 (block displays in Text mode) Compressor Figure 4. Compressor Block. The Compressor Block shown in Figure 4 has four inputs and two outputs. The [rpm] from tag feeds into the compressor s input. The evaporator exit pressure [Pe_out] is fed into the compressor s input pressure ( ) and the desired compressor output pressure [Pc_out] is assigned to the compressor block s output pressure input ( ). Finally 6

7 the compressor s input enthalpy ( ) is set to the evaporator s exit enthalpy [He_ro]. On the output side, the compressor block produces the mass flow rate ( which this example assigns into the [m_comp] tag. Aside from the block connections, there are additional parameters that must be set by double clicking the block. The Compressor Parameters tab contains the input for the internal compressor volume and outlet enthalpy time constant, which are constant during the simulation, and the compressor map file name CompProp. The Refrigerant Properties tab has an input for the refrigerant data filename (ex. R134a ); additional fluid files can be generated and must be placed in the Thermosys/Fluid Tables folder, and the selected refrigerant should be consistently selected across all blocks connected to each flow loop (note: in Thermosys 4.3, the selected fluid name of each block is displayed at the top of the block). Inlet and outlet pressures and temperatures are specified as initial conditions and should correspond with the surrounding components. The Initial Conditions tab allows setting initial inlet and outlet pressures and temperatures, as well as initial mass flow and compressor speed. The temperature and pressure for these locations are related and should be consistent. For example, if a saturated vapor exits the compressor, temperature and pressure are direct functions of one another. Compliance with the refrigerants properties will help ensure a stable system. Mass flow and compressor speed define their respective initial conditions and are straightforward. The Display tab allows the user to choose between Symbol and Text display modes Condenser Figure 5. Condenser Block. The Condenser Block shown in Figure 5 takes in an air flow (with temperature) as well as a refrigerant input mass flow rate, output mass flow rate, and refrigerant input enthalpy, and it returns the refrigerant output pressure, enthalpy and temperature along with some additional diagnostics. This totals five inputs and seven outputs. As with the compressor, most of the inputs and outputs are either pulled from from tags, or pushed into goto tags, to keep the inter-block connections clean. The incoming air mass flow rate ( ) is assigned from the [mc_air_in] tag. The input air temperature ( ) pulls from the [Tc_air_in] tag. The refrigerant mass flow from the compressor [m_comp] is supplied to the refrigerant mass flow 7

8 input ( ), and the desired condenser output mass flow rate (determined by the TXV valve) [m_valve] is passed into the appropriate condenser block input (.. The enthalpy of the refrigerant (coming from the compressor) [Hk_ro] is fed into the appropriate input ( ). The important outputs for the condenser are refrigerant output pressure ( )) which feeds into the [Pc_out] tag (and therefore into the TXV valve), and refrigerant output enthalpy ( ) which goes into the [Hc_ro] tag (and from there the TXV valve).). In addition to these two outputs, another five are provided, but for this example, they are not used to feed into any other blocks, and are simply attached to scopes so their values can be observed. These additional five outputs are: the refrigerant output temperature, the air output temperature, the wall temperature during the 3 operating phases (Superheated, Two-phase, Sub-cooled), the lengths for each phase zone, and the current mass in the condenser. When double clicking the block, its parameters are shown. The Condenser Block has six tabs with inputs to be set by the user: Condenser Exchange Geometry, Wall Properties, Parameter Adjustment Factors, Refrigerant Properties, Air Properties and Display. The user should refer to the THERMOSYS help files for further information Thermostatic Expansion Valve Figure 6. Thermal Expansion Valve Block (TXV). The Thermostatic Expansion Valve (TXV) Block shown in Figure 6 is a metering device, placed between the condenser and evaporator, which has some means of control based on the evaporator exit conditions. This block takes in the desired input and output pressure and input fluid enthalpy, and returns the corresponding mass flow rate and exit fluid enthalpy, as well as some valve parameters. As in this example, the pressure exit on each side of the valve is determined by other components, so [Pc_out] and [Pe_out] are inputs feeding in from the 8

9 compressor and the evaporator into the corresponding block inputs and, respectively. Note that [Pe_out] is used twice as an input. The second instance corresponds to the label P eqlzr in the library blocks, and in this case is set to match the downstream pressure of the evaporator [Pe_out]. This allows simulation of an internally equalized TXV. Attach a different pressure source to the P eqlzr to simulate an externally equalized TXV. The valve has a switch for enabling and disabling, which is supplied a constant value of 1 (indicating enable) in this Sample. When the switch has input equal to 0, the valve is closed, mass flow rate will report zero. Outputs for the valve are mass flow through the valve ( which is tied to the [m_valve] tag, and output enthalpy sample. which is not used by any other blocks in this Double clicking on the TVX block brings up its parameters which are organized on five tabs: Valve, Cv Data, Bulb, Display, and Refrigerant Properties, which all contain inputs to be set up by the user. More information on how to set up these tabs is available in the THERMOSYS help files Evaporator Figure 7. Evaporator Block. Much like the condenser, the evaporator takes in an air mass flow rate and temperature, as well as a refrigerant input and output mass flow rate and enthalpy, and returns the corresponding output refrigerant pressure, temperature and enthalpy, as well as the output air temperature. It further returns some additional evaporator diagnostics and values. In this example, the evaporator air input mass flow rate ( ) takes in the [me_air_in] tag, and the air temperature (coming from the [Te_air_in]) is fed into the evaporator air 9

10 temperature slot ( ). As the evaporator is placed between the TXV valve and the compressor, its input refrigerant mass flow ( ) comes from the [m_valve] tag, which takes it values from the TXV block, and the desired output mass flow rate ( ) takes its value from the compressor mass flow rate [m_comp]. Finally, the refrigerant s input enthalpy ( ) takes its value in this example from the refrigerant coming out of the condenser, [Hc_ro]. The output refrigerant pressure ( ) is fed into the [Pe_out] tag for use in the TXV and Compressor, as is the output refrigerant enthalpy ( ) to the [He_ro] tag, also needed for the Compressor s input side. The refrigerant output temperature is moved into the [Te_ref_out] tag for use with the TXV, while the air temperature is moved into the [Te_air_out] tag for use as a Box Model Block input. The refrigerant s effective cooling power ( ) is passed into the [Capacity] flag for use with the box model. The remaining the parameters are not needed for this example, and are attached to the scope for observation. For a full description of these as well as the Evaporator mask parameters inputs, see the THERMOSYS help files Box Model Figure 8. Box Model Block. The Box Model block is used for simulating a refrigerated trailer or similar enclosure exposed to outside elements with the effect of altering the interior environment. The inputs are: Q ref. [W] which is fed from [Capacity] from the Evaporator V dot [m 3 /hr] which is determined from [me_air_in] and [Te_air_out] from the Evaporator T amb. [C] which is assumed to be the same as the Condenser air input [Tc_air_in] 10

11 Various input conditions [Wind], [Solar], [Door], and [Product] defined as Box Model Inputs (see Figure 9 below) Outputs include the resultant internal air temperature (which is subsequently pushed to the [Te_air_in] flag, and used as input air for the evaporator), the internal and external Wall temperatures, the product temperature, and a load vector containing various heat loads in Watts. The Box Model parameters are organized on five tabs: Box listing box dimensions, UA value, and initial temperatures Product listing product dimensions and thermal characteristics Door listing door dimensions, and protection rating Solar listing emissivity of the box and the solar view factor Display which allows the user to select between the Text and Symbol display modes Figure 9. Box Model Inputs. 2.2 Simulink Blocks: On-Off Controller and Simulation Settings 11

12 Figure 10. Simulink Blocks. This example uses Simulink blocks to define constant environmental inputs for the Box Model. In addition, a simple controller is made in which the air temperature leaving the box is compared to a set point. If the temperature reaches the set point, an off signal is sent and the compressor is spun down (rpm = 0). In addition, the air cooling for the evaporator and condenser is disabled. When the temperature reaches an upper bound these are re-enabled. More complicated controls can be implemented (for instance, see Sample 1: TXV PI Control for an example of a proportional-integral controller), and parameters held constant in this example could be allowed to vary, such as RPM. PID controls are also possible, varying parameters such as compressor rpm or external air temperature. This illustrates the power of THERMOSYS within Simulink : any control scheme imaginable can be applied to these thermodynamic systems. 2.3 Additional THERMOSYS Models Not Applied in this Example Electronic Expansion Valves (EEV): These have very similar inputs/outputs/parameters to the TXV. There are both map and poly versions. The former has its parameters empirically mapped, while the latter is instead fitted with a polynomial. The Electric Expansion Valve - Poly is included in Sample 4. Multipurpose Tank Block: This block can be used to model a variety of refrigerant tanks applied in a system design, for example a receiver placed between the evaporator and compressor, or at the exit of the condenser to avoid undesirable fluid phases in the compressor and expansion valves respectively. 12

13 Hydraulic Resistance Block: This calculates a mass flow rate from a pressure difference in a tube and returns the new enthalpy. There are three versions of this corresponding to three different models: (1) The Static Valve model which requires only specification of a flow coefficient and a max flow; (2) the Full model which accounts for the pipe dimensions and uses an adaptive iterative model dependent on the flow being vapor to vapor, two-phase to two-phase, or two-phase to vapor transition; and (3) the Swamee- Jain model (non-iterative). Plate Heat Exchanger Blocks: Two fluid models for plate heat exchangers for both condenser and evaporator roles have been added to THERMOSYS. These operate on similar principles to the finned tube heat exchanger blocks. The details are described further in the help files. 3 Running Simulations Once a model has been built, linked, and has all its initial conditions defined, it is ready to be simulated. In the example, press Ctrl + e to enter the configuration parameters, or choose Configuration Parameters from the Simulation drop down menu. Start and stop times are editable problem variables within this window. It is strongly recommended to begin any new THERMOSYS models by using the parameters defined here and in the other Samples as they are relatively stable for similar configurations. If stability or accuracy is problematic, adjusting step sizes and error tolerances are options, but will increase computation time. See Figure 11 for the recommended settings. Figure 11. Configuration Parameters. 13

14 Results can be stored with Simulink scope blocks and exported at will, or passed back into MATLAB, using standard Simulink blocks. Users can create their own blocks to streamline this process in the event large amounts of data collection are necessary. 4 Future Updates and Advanced Use As mentioned above, while several fluid property tables are currently included in THERMOSYS 4.3, a software package for creating fluid property tables is in development. The default maps for the compressor and TXV performance are calibrated to specific hardware. The help files contain instructions on how to create user-defined maps for valves and compressors. Additionally, if THERMOSYS 4.3 is used with Matlab 8 (R2012b) or newer, the fluid tables will automatically populate a drop-down list, instead of the user needing to type in filenames. 14

AIR CONDITIONER PERFORMANCE RATING

AIR CONDITIONER PERFORMANCE RATING HPRATE V5.1 AIR CONDITIONER PERFORMANCE RATING by G.L. Morrison MechLab The University of New South Wales.EDU.AU September 2012 Version 5.1 HPRATE 5 Air Conditioner Performance Rating 1 HPRATE AIR CONDITIONER

More information

Simscape Refrigerant Loop Product

Simscape Refrigerant Loop Product Aims The product is an easy to use simscape simulator with simple GUI or HMI allowing to define: - the different configurations of the physical system - the different operating modes: start, stop, load

More information

Ion Gateway Cellular Gateway and Wireless Sensors

Ion Gateway Cellular Gateway and Wireless Sensors Page 1 of 9 Account & Network Setup If this is your first time using the Ion Gateway online system site you will need to create a new account. If you have already created an account you can skip to the

More information

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Numerical Simulation of a New Cooling System for Commercial Aircrafts Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Numerical Simulation of a New Cooling System for Commercial Aircrafts Karin

More information

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014 Solar Charge controller with Ethernet Release : 19 June 2014 Hardware Version : Version 1 Firmware version 1 PC Application Software : Version 1.0.0.0 Hardware Description : The Solar Smart regulator was

More information

Installing ProSeries 2005

Installing ProSeries 2005 Installing ProSeries 2005 The following instructions will walk you through Installing and Launching ProSeries 2005. Before you begin your installation, it is very important to make note of the following

More information

LineGuard 2300 Program User Manual (FloBoss 107)

LineGuard 2300 Program User Manual (FloBoss 107) Form A6251 Part Number D301346X012 November 2012 LineGuard 2300 Program User Manual (FloBoss 107) Remote Automation Solutions Revision Tracking Sheet November 2012 This manual may be revised periodically

More information

Milestone XProtect Alarm Matrix Integration 1.0

Milestone XProtect Alarm Matrix Integration 1.0 Milestone XProtect Alarm Matrix Integration 1.0 Milestone XProtect Alarm Matrix Integration 1.0 Target Audience This document is aimed at system users and provides descriptions on how to install, configure

More information

Monitoring Operator Guide. Access Control Manager Software Version

Monitoring Operator Guide. Access Control Manager Software Version Monitoring Operator Guide Access Control Manager Software Version 5.10.10 2018, Avigilon Corporation. All rights reserved. AVIGILON, the AVIGILON logo, ACCESS CONTROL MANAGER, ACM, ACM VERIFY AND TRUSTED

More information

SPLIT SYSTEMS SELECTION & OPTIMIZATION GUIDE

SPLIT SYSTEMS SELECTION & OPTIMIZATION GUIDE SPLIT SYSTEMS SELECTION & OPTIMIZATION GUIDE www.addison-hvac.com Creating a New Project 1. Open the ACE Interface within the web browser. ACE performs best using the Google Chrome browser. Do not use

More information

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS V. La Rocca 1, A. Messineo 2, D. Panno 1 1 Department of Energy, University of Palermo 2 Engineering Faculty, Kore

More information

Installing ProSeries 2004

Installing ProSeries 2004 Installing ProSeries 2004 The following instructions will walk you through Installing and Launching ProSeries 2004. Before you begin your installation, it is very important to make note of the following

More information

Tutorial: How to Download and Install Lumberyard v or greater

Tutorial: How to Download and Install Lumberyard v or greater Tutorial: How to Download and Install Lumberyard v1.9.0.0 or greater This tutorial walks you through the steps in downloading and installing the Lumberyard engine onto your computer, we will also cover

More information

Jurnal UMP Social Sciences and Technology Management Vol. 3, Issue. 3,2015

Jurnal UMP Social Sciences and Technology Management Vol. 3, Issue. 3,2015 The Design of a Heat Exchanger Shell - Tube as Evaporator an Absorption Chiller Cycle to Reduce the Temperature of the Air Entering Diesel Engine Heavy Loads 75% And 50% of the Engine Part Seyyede Sepideh

More information

Bosch TCU Integration Module Administrator's Guide

Bosch TCU Integration Module Administrator's Guide Bosch TCU Integration Module 1.0 - Administrator's Guide 10 Dec 2008 Rev 1.2 Table of Contents 1 Overview... 3 1.1 Compatibility...3 1.2 References...3 2 Installation... 4 3 Configuration... 5 3.1 System

More information

Avigilon System Integration Guide. for the Avigilon Control Center and Access Control Manager

Avigilon System Integration Guide. for the Avigilon Control Center and Access Control Manager Avigilon System Integration Guide for the Avigilon Control Center and Access Control Manager 2014-2016, Avigilon Corporation. All rights reserved. AVIGILON, the AVIGILON logo, AVIGILON CONTROL CENTER,

More information

TIL Suite simulates Thermal Systems. Software containing models for thermophysical properties, thermal components and systems

TIL Suite simulates Thermal Systems. Software containing models for thermophysical properties, thermal components and systems TIL Suite simulates Thermal Systems Software containing models for thermophysical properties, thermal components and systems TIL Model library for thermal components & systems Continually developed and

More information

Procidia iware AlarmWorX32. AlarmWorX32 Viewer January 2010

Procidia iware AlarmWorX32. AlarmWorX32 Viewer January 2010 Procidia iware AlarmWorX32 AlarmWorX32 Viewer Siemens Protection AG 2008. notice All / Copyright rights reserved. notice Introduction / Contents Procidia iware is an operator interface software designed

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A Installation & Service Manual S E C T I O N 26 Enviroguard III ENVIROGUARD III is a patented refrigerant control system that utilizes floating head technology (Nature s Cooling). The amount of liquid refrigerant

More information

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Marco Alexandre Onofre Dias This paper presents a model that was implemented

More information

Niagara4 Technical Certification Program Student Guide DAY 1 DAY 2

Niagara4 Technical Certification Program Student Guide DAY 1 DAY 2 Niagara4 Technical Certification Program Student Guide DAY 1 Welcome Course Introduction Platforms & Stations Niagara4 Fundamentals Simple Logic: Hot Water Pump Control (Thermostatic) Simple Logic: Hot

More information

Alarm Coordination Connected Components Building Block. Quick Start

Alarm Coordination Connected Components Building Block. Quick Start Alarm Coordination Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.

More information

IP TRONIK. Project Scope: Simulation of car refrigerant circuit with the software GT SUITE and its comparison with real test bench measurements

IP TRONIK. Project Scope: Simulation of car refrigerant circuit with the software GT SUITE and its comparison with real test bench measurements IP TRONIK EICHSTÄTT GMBH Project Scope: Simulation of car refrigerant circuit with the software GT SUITE and its comparison with real test bench measurements Christian Schwegler 17. October 2016 Table

More information

CALIBRATABLE 7-FUNCTION THERMO- HYGROMETER USER S MANUAL

CALIBRATABLE 7-FUNCTION THERMO- HYGROMETER USER S MANUAL CALIBRATABLE 7-FUNCTION THERMO- HYGROMETER USER S MANUAL EP8710 Please read this manual carefully and thoroughly before using this product. TABLE OF CONTENTS Introduction.................... 2 4 Key Features.......................

More information

Simplex Panel Interface Guide

Simplex Panel Interface Guide Simplex Panel Interface Guide February 2016 SATEON Software Integrations Simplex Panel Interface Guide Issue 1.0, released February 2016 Disclaimer Copyright 2016, Grosvenor Technology. All rights reserved.

More information

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2 Modern Applied Science; Vol. 9, No. 13; 2015 ISSN 1913-1844 E-ISSN 1913-1852 Published by Canadian Center of Science and Education The Design of a Shell-Tube Heat Exchanger as Evaporator an Absorption

More information

Technical Information

Technical Information Date of last update: 02-08 Ref: Application Engineering Europe COPELAND SCROLL COMPRESSORS USING VAPOUR INJECTION FOR REFRIGERATION CONTENTS 1 Introduction...1 2 Principle of Operation...1 3 Capacity Effect...2

More information

DeltaV Operate. DeltaV Operate. Introduction. DeltaV Product Data Sheet. Robust and secure plant operations

DeltaV Operate. DeltaV Operate. Introduction. DeltaV Product Data Sheet. Robust and secure plant operations February 2016 Page 1 DeltaV Operate You can easily manage your process with. Robust and secure plant operations Powerful operator interface, optionally up to four monitors Constant visibility and access

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

BRS Mechanically-Agitated BioReactor MA 100. Quick Reference Guide Ver2.0

BRS Mechanically-Agitated BioReactor MA 100. Quick Reference Guide Ver2.0 BRS Mechanically-Agitated BioReactor MA 100 Quick Reference Guide Ver2.0 Manufacturer: BioReactor Sciences 1150 Home Place Drive Lawrenceville, GA 30043 USA Phone: 404.307.7100 Email: info@bioreactorsciences.com

More information

Milestone SMI Intrepid II Perimeter Module 1.1 User s Manual

Milestone SMI Intrepid II Perimeter Module 1.1 User s Manual Milestone SMI Intrepid II Perimeter Module 1.1 User s Manual Target Audience for this Document This document is aimed at system users and provides descriptions on how to install and maintain the Milestone

More information

HERCULES 6 GRAPHICS SYSTEM

HERCULES 6 GRAPHICS SYSTEM HERCULES 6 GRAPHICS SYSTEM USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web: www.protec.co.uk

More information

Alarm System Example

Alarm System Example Alarm System Example ASD:Suite Copyright 2013 Verum Software Technologies B.V. ASD is licensed under EU Patent 1749264, Hong Kong Patent HK1104100 and US Patent 8370798 All rights are reserved. No part

More information

1.1. SCOPE OF THE WORK:

1.1. SCOPE OF THE WORK: Chapter 1: Introduction 1 1. INTRODUCTION 1.1. SCOPE OF THE WORK: Multi-stage refrigeration systems are an area of growing industrial importance in large plants. These systems are known to be large power

More information

How to Configure the Alarm Action Outgoing Cell Call MultiLogger Application Note #14

How to Configure the Alarm Action Outgoing Cell Call MultiLogger Application Note #14 5 Gould Road, PO Box 2155 New London, NH 03257 Voice: (603) 526-9088 info@canarysystems.com www.canarysystems.com Overview How to Configure the Alarm Action Outgoing Cell Call MultiLogger Application Note

More information

Mechanical Heat Pump R515

Mechanical Heat Pump R515 P.A.Hilton Ltd Mechanical Heat Pump R515 Above: R515 shown fitted with standard wattmeter Stabilises in minutes allowing many tests to be conducted in a typical laboratory period. Allows a complete refrigerant

More information

i-vu CCN 4.0 Owner s Guide

i-vu CCN 4.0 Owner s Guide i-vu CCN 4.0 Owner s Guide CARRIER CORPORAION 2007 A member of the United echnologies Corporation family. Stock symbol UX. 11-808-377-01 07/07 able of Contents ACCESSING YOUR SYSEM... 3 YOUR SYSEM DEAILS...

More information

ENSC 388: Engineering Thermodynamics and Heat Transfer

ENSC 388: Engineering Thermodynamics and Heat Transfer ENSC 388: Engineering Thermodynamics and Heat Transfer Experiment 3: Free and Forced Convection Objective Determination of heat transfer coefficient for free and forced convection for different geometries.

More information

Technical Bulletin (TB-0037)

Technical Bulletin (TB-0037) Technical Bulletin (TB-0037) BITZER Software Guide Version 4, January 2015 DEFINITION OF TERMS Terms Found in the BITZER Software Condenser Capacity: The power needed to reject heat from the refrigerant

More information

SR SERIES WATER SOURCE HEAT PUMP SYSTEM SELECTION AND OPTIMIZATION GUIDE

SR SERIES WATER SOURCE HEAT PUMP SYSTEM SELECTION AND OPTIMIZATION GUIDE SR SERIES WATER SOURCE HEAT PUMP SYSTEM SELECTION AND OPTIMIZATION GUIDE Fresh Access Pro http://freshaccesspro.com/erep/ This guide is intended for use by qualified professionals to assist in properly

More information

Alarms Updated 03/26/2018

Alarms Updated 03/26/2018 Updated 03/26/2018 Table of Contents Alarms Alarms in OneView...1 Types of Alarms...1 Setting up Alarms...2 Alarm Configuration...4 Customize Alarm Parameters...5 List of Configured Alarms...7 Acknowledging

More information

Technical Information

Technical Information Date of last update: May-12 Ref: : Application Engineering Europe ENHANCED VAPOUR INJECTION (EVI) FOR ZH*KVE SCROLL COMPRESSORS 1 Introduction... 2 2 Principle of operation... 2 3 Capacity effect... 3

More information

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University Scientific Principals and Analytical Model Charcoal Cooler Lisa Crofoot MECH 425, Queens University 1.0 Scientific Principles Evaporative cooling is based on the principle that water requires heat energy

More information

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger "COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger" 1 Prof.Gaffar G.Momin, 2 Sagar B. Tupe, 2 Swapnil A. Parate 2 Omkar G. Yewale 2 Aakash P.

More information

ND4000 Manual Marine Hydraulics

ND4000 Manual Marine Hydraulics ND4000 Manual Marine Hydraulics Version 1.0 May 2012 Page 1 Contents Line Counter Components... 3 Proximity Sensors... 3 Connecting the Proximity Sensors to the SSCD... 3 Fuse... 3 USB... 4 Computer Display...

More information

Electronic Pellet Burner Controller NPBC-V3-1

Electronic Pellet Burner Controller NPBC-V3-1 Electronic Pellet Burner Controller NPBC-V3- SOFTWARE VERSION 3.2/3. page of 3 CHANGES IN THE TECHNICAL AND USER GUIDE OR IN THE SOFTWARE VERSION Technical and User Guide's version Changes Page 2.8. The

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER Poster P.4.2 - - ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER Jan Sedlar, University Centre for Energy Efficient Buildings and Faculty of Mechanical Engineering, Czech Technical University in Prague, Czech

More information

1 Air Handling Units In ICE

1 Air Handling Units In ICE 1 Air Handling Units In ICE From version 3.0, there is a library of common air handling units (AHU) in the distribution. A simulated building can have several AHUs. The following limitations apply: - every

More information

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR SAFETY MANUAL SIL 2 Certified Model FP-700 Combustible Hydrocarbon Gas Sensor Version 2.0 1 SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR This manual addresses the specific requirements and recommendations

More information

Installer Manual KNX Touchscreen Thermostat

Installer Manual KNX Touchscreen Thermostat Installer Manual 02952 KNX Touchscreen Thermostat Index GENERAL FEATURES AND FUNCTIONALITY from page 5 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 7 COMMUNICATION OBJECTS GENERAL FEATURES AND FUNCTIONALITY

More information

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 111 CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 7.1 INTRODUCTION Energy is the primary component to run any system in the world. According to

More information

(Refer Slide Time: 00:00:40 min)

(Refer Slide Time: 00:00:40 min) Refrigeration and Air Conditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 10 Vapour Compression Refrigeration Systems (Refer Slide

More information

Oil Stabilization Optimization

Oil Stabilization Optimization Oil Stabilization Optimization 1 Workshop A poor-boy stabilization scheme is used to separate an oil and gas mixture into a stabilized oil and a saleable gas. A simple three-stage separation with heating

More information

Carwin COMPRESSOR SELECTION PROGRAM

Carwin COMPRESSOR SELECTION PROGRAM Carwin COMPRESSOR SELECTION PROGRAM IMPORTANT! READ CAREFULLY BEFORE USING By using this disk covering a software program entitled CARLYLE SELECTION PROGRAM WINDOWS (Software), you indicate your acceptance

More information

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs User Manual Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs Models 89800-03 and 89800-04 THE STANDARD IN PRECISION MEASUREMENT Table of Contents

More information

Operations Manual TS400. Test Station for G450/G460 Gas Detector

Operations Manual TS400. Test Station for G450/G460 Gas Detector TS400 Test Station for G450/G460 Gas Detector Operations Manual 1194 Oak Valley Dr, Ste 20, Ann Arbor MI 48108 USA (800) 959-0329 (734) 769-0573 www.goodforgas.com GfG Products for Increased Safety Congratulations

More information

SBS5311 HVACR II Experiment 2: Analysis of the Combined Rankine and Vapour Compression Cycle

SBS5311 HVACR II   Experiment 2: Analysis of the Combined Rankine and Vapour Compression Cycle Introduction SBS5311 HVACR II http://ibse.hk/sbs5311/ Experiment 2: Analysis of the Combined Rankine and Vapour Compression Cycle The Rankine cycle is an idealized thermodynamic cycle of a heat engine

More information

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO User s Manual Copyright 2017 SELCO SELCO Betonvej 11 - DK-4000 Roskilde Denmark Phone: 45 7026 1122 - Fax: 45 7026 2522 e-mail: selco@selco.com www.selco.com Table of contents 1 INTRODUCTION...4 2 SOFTWARE

More information

GEM-C Wireless User & Installation Manual. Revision October Apollo Solar Electric Limited. Documentation

GEM-C Wireless User & Installation Manual. Revision October Apollo Solar Electric Limited. Documentation Documentation GEM-C Wireless User & Installation Manual Revision October 2014 Apollo Solar Electric Limited Contents GEM-C Wireless User Manual 3 Important Safety Information 3 Introduction 4 The GEM-C

More information

Added password for IP setup page : Password must be in IP format!

Added password for IP setup page : Password must be in IP format! NETWORK POWER MONITOR Release : 21 August 2014 Hardware Version : Version 7 Firmware version 1.00 PC Application Software : Version (latest)...2 Added password for IP setup page : Password must be in IP

More information

CODAC Core System 5.4 CS-Studio Release Notes

CODAC Core System 5.4 CS-Studio Release Notes IDM UID UBEVKZ VERSION CREATED ON / VERSION / STATUS 01 Feb 2017 / 1.0 / Approved EXTERNAL REFERENCE / VERSION User Manual CODAC Core System 5.4 CS-Studio Release Notes In CODAC Core System 5.4, CS-Studio

More information

Electronic Pellet Burner Controller NPBC-V3M

Electronic Pellet Burner Controller NPBC-V3M Electronic Pellet Burner Controller NPBC-V3M SOFTWARE VERSION 3.3a/3.2 page of 27 CHANGES IN THE USER MANUAL OR IN THE CONTROLLER'S SOFTWARE Version of the user manual Changes Page 2.2. The software version

More information

Simple Compression Refrigeration Circuit Unit TSCR

Simple Compression Refrigeration Circuit Unit TSCR Engineering and Technical Teaching Equipment Simple Compression Refrigeration Circuit Unit TSCR PROCESS DIAGRAM AND UNIT ELEMENTS ALLOCATION ISO 9001: Quality Management (for Design, Manufacturing, Commercialization

More information

Virtual Household Refrigerators at Steady-State and Transient Conditions. Numerical Model and Experimental Validation.

Virtual Household Refrigerators at Steady-State and Transient Conditions. Numerical Model and Experimental Validation. Virtual Household Refrigerators at Steady-State and Transient Conditions. Numerical Model and Experimental Validation. Nicolás ABLANQUE, Carles OLIET, Joaquim RIGOLA, Carlos-David PEREZ-SEGARRA Universitat

More information

Bristol s Six Principles for Good Solar Hydronic Design SLASH-D: Software for Solar Heating Design

Bristol s Six Principles for Good Solar Hydronic Design SLASH-D: Software for Solar Heating Design This is the unedited version of the article that appeared in Plumbing Engineer and Plumbing and Hydronics Contractor in May 2013. It is the 59 th article by Bristol Stickney, Chief Technical Officer of

More information

Ambient Temperature/ Relative Humidity & Dew Point Temperature Sensors to USB Output. Model LFS108B

Ambient Temperature/ Relative Humidity & Dew Point Temperature Sensors to USB Output. Model LFS108B Ambient Temperature/ Relative Humidity & Dew Point Temperature Sensors to USB Output Model LFS108B Copyright 2018 - LLC. All rights reserved. Table of Contents Quick Start... 3 1- Introduction... 4 2-

More information

EnergyGauge USA Release Notes

EnergyGauge USA Release Notes EnergyGauge USA 5.0.02 Release Notes The latest release of EnergyGauge USA, Version 5.0.02, provides new features and bug fixes. This version includes new features for HERS raters. Key features added since

More information

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +

More information

Millennium Xtra. Millennium ATMA setup and configuration guide. May Millennium Group, Inc.

Millennium Xtra. Millennium ATMA setup and configuration guide. May Millennium Group, Inc. Millennium Xtra Millennium ATMA setup and configuration guide May 16 2017 Millennium Group, Inc. 16 Tech Circle Natick, MA 01760 P: 508-655-1340 F: 508-651-2902 Millennium ATMA setup and configuration

More information

PowerRouter application guideline

PowerRouter application guideline PowerRouter application guideline Software installation tool - version 3.4 Before operating the PowerRouter, you may initialize the PowerRouter by using the PowerRouter software installation tool. The

More information

Milestone XProtect Alarm Matrix Integration 1.0

Milestone XProtect Alarm Matrix Integration 1.0 Milestone XProtect Alarm Matrix Integration 1.0 Milestone XProtect Alarm Matrix Integration 1.0 Target Audience This document is aimed at system users and provides descriptions on how to install, configure

More information

Configuration and Operation Manual for the Unipos

Configuration and Operation Manual for the Unipos AxxonSoft Configuration and Operation Manual for the Unipos Integration Module Version 1.1 Moscow 2010 Contents CONTENTS... 2 1 LIST OF TERMS... 4 2 INTRODUCTION... 6 2.1 Document purpose... 6 2.2 Purpose

More information

CLIMA I Thermostat ZENNIO

CLIMA I Thermostat ZENNIO ZENNIO CLIMA CLIMA I Thermostat ZENNIO Edition 2 INTRODUCTION INDEX 1. INTRODUCTION... 3 2. DEVICES WITH THERMOSTAT... 5 3. THERMOSTAT CONFIGURATION... 7 3.1. TYPE OF CONTROL... 7 3.1.1. 2 POINTS WITH

More information

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this lecture are to: 1. Importance of complete vapour compression refrigeration

More information

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING Tempered Water Logic Control OPERATION l TROUBLE SHOOTING English For MPE Multiple Chiller Units Control Panel TEMPERED WATER SYSTEMS L-2199 Rev. 20080223 Revision: L-2199 20101104 *** IMPORTANT NOTICE

More information

HPE Knowledge Article

HPE Knowledge Article HPE Knowledge Article HPE Intelligent Management Software - How to Switch On/Off the Sound Alarms Article Number mmr_sf-en_us000005241 Environment HPE Intelligent Management Center Issue Enable Sound Alarms

More information

Chapter 11. Refrigeration Cycles. Study Guide in PowerPoint

Chapter 11. Refrigeration Cycles. Study Guide in PowerPoint Chapter 11 Refrigeration Cycles Study Guide in PowerPoint to accompany Thermodynamics: An Engineering Approach, 7th edition by Yunus A. Çengel and Michael A. Boles The vapor compression refrigeration cycle

More information

OPERATION MANUAL. Packaged air-cooled water chillers and packaged reversible air to water heatpumps EWAQ009ACV3 EWAQ010ACV3 EWAQ011ACV3

OPERATION MANUAL. Packaged air-cooled water chillers and packaged reversible air to water heatpumps EWAQ009ACV3 EWAQ010ACV3 EWAQ011ACV3 OPERATION MANUAL Packaged air-cooled water chillers and packaged reversible air to EWAQ009ACV3 EWAQ010ACV3 EWAQ011ACV3 EWYQ009ACV3 EWYQ010ACV3 EWYQ011ACV3 EWAQ009ACW1 EWAQ011ACW1 EWAQ013ACW1 EWYQ009ACW1

More information

CompleteView Alarm Client User Manual. CompleteView Version 4.6.1

CompleteView Alarm Client User Manual. CompleteView Version 4.6.1 CompleteView Alarm Client User Manual CompleteView Version 4.6.1 Table of Contents Introduction... 1 Overview...2 System Requirements...2 Configuration... 3 Starting the Alarm Client...3 Menus...3 File

More information

Technical Information

Technical Information Date of last update: May-15 Ref: C7.19.2/0813-0515/E Application Engineering Europe ZF* REFRIGERATION COPELAND SCROLL COMPRESSORS USING R407A, R407F, R448A OR R449A IN LOW TEMPERATURE APPLICATIONS ZF*

More information

INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold

INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold LOW VAC INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold REF HIGH SPECIAL FEATURES Low battery indicator Displays 63 refrigerants Displays corresponding saturation, dew or bubble point temperature

More information

SIMATIC IPC DiagBase SIMATIC. Industrial PC SIMATIC IPC DiagBase. Introduction. DIAG software components. Quick-Start Guide

SIMATIC IPC DiagBase SIMATIC. Industrial PC SIMATIC IPC DiagBase. Introduction. DIAG software components. Quick-Start Guide Introduction 1 DIAG software components 2 SIMATIC Industrial PC Operating Manual Quick-Start Guide 3 Hardware and software requirements 4 Installing and removing the software 5 Description of the Management

More information

VIDEO CONTROLS LIMITED

VIDEO CONTROLS LIMITED VIDEO CONTROLS LIMITED MAXCOM PRO SERIES TELEMETRY CONTROL SYSTEMS Operation Guide for use with MaxCom 3V, MaxCom 3VE, MaxCom 4V and MaxCom4VE Document Code number - CI431V2 Table of Contents Safety Instructions

More information

Moxa Proactive Monitoring User s Manual

Moxa Proactive Monitoring User s Manual User s Manual Edition 2, May 2016 www.moxa.com/product 2016 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used only

More information

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology IJIRST International Journal for Innovative Research in Science & Technology Volume 1 Issue 11 April 2015 ISSN (online): 2349-6010 CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

More information

CALIBRATABLE 3-FUNCTION THERMO- HYGROMETER USER S MANUAL

CALIBRATABLE 3-FUNCTION THERMO- HYGROMETER USER S MANUAL CALIBRATABLE 3-FUNCTION THERMO- HYGROMETER USER S MANUAL EP8703 Please read this manual carefully and thoroughly before using this product. TABLE OF CONTENTS Introduction................. 2 3 Key Features....................

More information

Substation Monitoring System

Substation Monitoring System Substation Monitoring System SF6 Gas Density Monitoring System Description Introduction As a result of recent European legislation on the control of greenhouse gasses, utilities and manufacturers alike

More information

Avigilon Control Center 5 System Integration Guide

Avigilon Control Center 5 System Integration Guide Avigilon Control Center 5 System Integration Guide for Paxton Net2 Access Control Systems 2014 Avigilon Corporation. All rights reserved. Unless expressly granted in writing, no license is granted with

More information

Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler

Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler Author: Volodymyr Voloshchuk Vl.volodya@gmail.com Introduction In

More information

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 SAE Alternate Refrigerant Cooperative Research Program Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 To: Alternate Refrigerant Task Force Members From: Ward Atkinson

More information

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink 1 Asoka R.G, 2 Aishwarya N, 3 Rajasekar S and 4 Meyyappan N 1234 Department of Chemical Engineering Sri Venkateswara College of Engineering,

More information

EkoAir Heat exchanger selection manual.

EkoAir Heat exchanger selection manual. EkoAir Heat exchanger selection manual. Table of content Calculation types.... 3 Calculation procedure, calculation example for fluid / fluid.... 4 Printouts.... 6 Calculation of evaporator.... 7 Calculation

More information

Avigilon System Integration Guide. for the Avigilon Control Center and Access Control Manager

Avigilon System Integration Guide. for the Avigilon Control Center and Access Control Manager Avigilon System Integration Guide for the Avigilon Control Center and Access Control Manager 2014-2017, Avigilon Corporation. All rights reserved. AVIGILON, the AVIGILON logo, ACC, AVIGILON CONTROL CENTER,

More information

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

1 DOCUMENT REVISION CONTROL ELEMENTS... 9 CONTENTS Contents 1 DOCUMENT REVISION... 8 2 SOFTWARE VERSION... 8 3 BASIC DESCRIPTION... 8 4 CONTROL ELEMENTS... 9 4.1 BASIC DISPLAYS...10 4.2 CONTROL KEYS...11 4.2.1 Rotary button (Press / Turn)...11

More information

Transient Groundwater Analysis with Slope Stability

Transient Groundwater Analysis with Slope Stability Transient Groundwater Analysis with Slope Stability 19-1 Transient Groundwater Analysis with Slope Stability This tutorial describes how to use Slide to calculate factors of safety for a dam subjected

More information

presentations the week of the final exams. Anyone who misses the appointment will receive a grade of zero.

presentations the week of the final exams. Anyone who misses the appointment will receive a grade of zero. CS 116 Section 4 PROJECT Spring 2016 Grade: Up to 12 points. Rules: To be worked on individually. Must be presented to the instructor in person in order to be graded. Similar projects will both receive

More information

Monitoring Software for NPBC-V3M-1 User Manual

Monitoring Software for NPBC-V3M-1 User Manual Monitoring Software for NPBC-V3M-1 User Manual User Manual ver 1.5 page 1 of 14 Contents: 1. Introduction... 3 2. Requirements... 3 3. Installing the software... 4 4. Connecting the devices... 4 5. Updating

More information

Smoke Layer Height and Heat Flow through a Door

Smoke Layer Height and Heat Flow through a Door Smoke Layer Height and Heat Flow through a Door 2018 Smoke Layer Height and Heat Flow through a Door In this tutorial you will simulate a growing fire in the corner of a 5m x 5m room. The room has a 1m

More information