TECHNICAL DOCUMENTATION DTR AIR WATER HEATERS IN STEEL CASING S SERIES

Size: px
Start display at page:

Download "TECHNICAL DOCUMENTATION DTR AIR WATER HEATERS IN STEEL CASING S SERIES"

Transcription

1 TECHNICAL DOCUMENTATION DTR AIR WATER HEATERS IN STEEL CASING S SERIES

2 ENG Technical documentation Table of contents. INTRODUCTION. PRECAUTIONS. TRANSPORT.3 PACKAGE CONTENT.4 USE AND PRINCIPLE OF OPERATION. DEVICE CONSTRUCTION, DIMENSIONS, TECHNICAL DATA. CONSTRUCTION. DIMENSIONS.3 TECHNICAL DATA 3. ASSEMBLY 4. INSTALLATION INSTRUCTIONS. PRECAUTIONS & WARNINGS 6. CONTROLS 7. CONNECTION SCHEMES 8. TERMS OF WARRANTY 8. WARRANTY CARD 8. WARRANTY FORM 8.3 SERVICE FORM Axial blowing fan: protective grd made of steel wire galvanizes, metal blades. The moto has gor the safety degree IP 4. Rate current,4-,8a. -phase, 3-stage device. Depending on the model we offer fans with a diameter 3-4mm in S3S series. Rotating mounting bracket: Holders are additional elements to assemble the device. The are solid and durable, it is possible to assemble the device on the wall or ceiling. It is also possible to regulate the angle of slope in three (3) versions. Fixed holders: made of steel, element for mounting the device on the wall or ceiling. Solid and durable construction, possible to assemble device in parallel on the angle 6 and 4.. DIMENSIONS. INTRODUCTION Thank you very much for purchasing Reventon Group device. We would like to congratulate you on excellent choice.. PRECAUTIONS The buyer and the user of the device should read carefully the following instructions and proceed to the content recommendations. Proceeding due to S -3S the following instruction guarantees the correct usage and safety. In case of any doubts please contact the producer. The producer reserves the rights to make changes to the technical documentation without previous notice. The producer is not responsible for the damages which occur due to improper installation, not keeping the device in repair or using the device out of line. The installation should be carried out by the professional installers, who possess the qualifications to install these types of devices. The installers are responsible for making the installation as instructed in the technical data. Regulations and safety rules must be followed. During the installation, use, service and periodical inspections all regulations and safety rules must be followed. In case of unserviceable please.3 TECHNICAL DATA plug out the device and contact with the authorized person or the producer.. TRANSPORT During the acceptance of goods, it is needed to check the device to exclude any damages. During the transport, it is needed to use the proper equipment, it is necessary to carry the device by two people. In case of any damages please fill in the damage report in presence of the supplier. - Air water heater - Operation and maintenance manual and warranty card Nominal heating capacity water 9/7 C and inlet air temperature C kw Heating power range kw Maximum airow Horizontal range Number of rows in heater.4 USE AND PRINCIPLE OF OPERATION Devices Reventon Group S-3S series are used to heat spaces such as: production halls, warehouses, commercial room, service spaces, garages, workshops, greenhouses, tents, shops, malls, shopping malls and churches. Air water heaters must be connected to central heating system. Application of modern technologies in Reventon Group devices guarantees high effectiveness and comfort of the consumption. Original colors of the devices match to every interior. The device is made very precisely and will work smoothly for many years. Unit of measure TECHNICAL DATA.3 PACKAGE CONTENT S -3S m³/h 3 bieg bieg bieg m number S-3S S3-3S S4-3S 6,7 9,4, 9, ,,3,9 Air temperature rise. * C 6,7 7, 48,7 9,6 C MPa 3 bieg bieg bieg A Power supply voltage V~Hz * The product has got the two years of warranty. Motor speed Rev. /min 3 bieg bieg bieg. DEVICE CONSTRUCTION, DIMENSIONS, TECHNICAL DATA Motor power W 3 bieg bieg bieg Motor IP Ferrules diameter Weight Noise,6,6,6,6,4,3,,8,3,,8,3,,84,6,4 3/ 3/ 3/ 3/ /4 3/4 3/4 3/ kg db 3 bieg bieg bieg * Temperature rise according to parameters: water 9/7 C and inlet air temperature C. Air stators: are made of gavanized steel, powder painted in RAL 748. It is possible to adjust manually the air stators to achieve the needed direction of the airflow. Waga Heating coil: Heating coil- made of aluminim and copper. The maximum temperature of the heating factor is C; maximum pressure,6 MPa; headers diameres 3/4". Depending on the model we offer, or 3-row heating coils. S-3S dm³ Rated current Casing: made of galvanized steel casing, powder painted in RAL 9 color. S4-3S Capacity of water Maximum temperature of heating agent Maximum operating pressure. CONSTRUCTION - Casing - Air stators - Heating coil - Axial blowing fan - Rotating mounting bracket S3-3S

3 S-3S S-3S S-3S 9/7 8/6 7/ -, - 9,4 6,7 4,,7-9,6-6,9 4,3, ,4 7, 4,4,9 9,44 7,9,3, 9,6 3,,7,63,,4, ,8 9,8 6,7 33,4 4 9, 6,8 9, 36,,98,8,74,6,,86,74,63,,4 the heat exchanger [kpa] S-3S S-3S S-3S /3 9/7 8/ ,4 7,3 4, ,44 38,8 34 9,4 4,9,7 34, 9,8,3,9 6,8 9,9 6,8 3,6 3,3 36,8,,3,,9,74 8,7,6 7, 34, 4,8,,7,,9,,9 7 -,3 4,, 7,8 4,,,4,3, S-3S S-3S S3-3S 7/ /3 9/ ,,6, 6,9,8,4 7,8 8,7 4,7 68,9 6,3, 44,3 36,8 6, 9,7 6,4 3,8 -,4,3,4 4,7 39,8 44,3 48,7,9,3,,9,74,6,93,74,,38, 3,4,66,9,9, S3-3S S3-3S S3-3S 8/6 7/ / , ,4 3, 4 4,8 37,9 3, 3,3 33,3 37,8 4, 46,3, 6,8 3,3 39, 43,4,7,33,98,64,3,36,66, , - 38,9 3, 3,6 6,3 9,3,8,9 9,3,,69,3,,7, S4-3S S4-3S S4-3S 9/7 8/6 7/ - 78,6 6 3, ,7 3,9 3,3 9 9,3 37,,6 S4-3S /3,3 43, 6, ,7 69,9 6, 4, 33,8 6,,7 4,7 34,,8 48,3 6,7 3,3 37,7 4,9,8, 7 3,3 37,,84 3,7,64,4,8,48,67,6,87,49, ,4 3,,8 7,6 9,,4 6,3, 6,4,88,3,,76,4 9 3

4 3. ASSEMBLY - Before plugging the electric supply check the leak tightness. Air water heaters Reventon Group S-3S series can be assembled on the wall or ceiling via rotating mounting brackets. The drawings below show the ways of assembly. In the bigger accommodation, it is recommended to assemble more than one device. Follow the parameters which are provided on the drawings. - The device does not consist of the anti-frost protection. The temperature in the room should not go below C. In such case please empty the device out of water. - It is recommended to check the electric installation before the first start. - It is recommended to use the external current deferential protection. - After the turn off, the elements of device may be warm. - After operating time of the device, please utilize it concerning the local norms and regulations. It is recommended to clean the device periodically: źheating coil blow through by compressed air, źfan casing and blades clean form the dirt. - If the device is not used for a longer time disconnect the voltage supply. - The device is transported with the closed air stators. It is essential to open them in 3 % before first start. Not keeping to the following recommendation may cause the damages of the fan. Reventon Group devices can be assembled on the wall or ceiling via rotating mounting bracket. It is possible to assemble the device in parallel on the angle 6. Please follow the parameters as shown below. - Opening the air stators must be made by two hands in parallel. Not keeping to the following recommendation may cause the damages of the air stators. REGULACJA STOPNIA NACHYLENIA PRZY UŻYCIU UCHWYTÓW MONTAŻOWYCH 4. INSTALLATION INSTRUCTIONS The installation should be made by the qualified staff, who possess the needed rights to install electrical devices, as instructed in the following documentation. The duct size for air water heaters Reventon Group S-3S series should be chosen by the designer. While plugging the device to the water installation do remember to hold its stub pipes by pipes spanner, not keeping to the recommendation may cause the damages of the heating coil.. PRECAUTIONS & WARNINGS All works concerning electrical installation should be made by the qualified staff, who possess the qualifications due to the domestic and local norms. These recommendations include service and disassembly as well. Not following to the recommendations may cause electrocution, device damages or its incorrect work. Outlet - Before service or exchange of the device it is obligatory to cut off the current supply. - Do not cover the inlet and outlet of the device. - Do not use the device in room with high moisture or close to the water basin. - Do not install, service the device with wet hands or barefoot. - Do not use the device in room with flammable fumes, gas and high concentration of dust. - The device should be kept out of reach of children and animals. - During the assembly use the filter on the hydraulic supply. - The device should be secured against pressure increase in the water installation. Inlet

5 Fan speed controller HC A 6. CONTROLS designed to change the single-phase fan's speed voltage controlled in industrial supply and heating systems To make easier the usage of the Reventon Group devices we also offer the additional controls: Power supply voltage: 3V /6Hz Allowable current output: A Maximum ambient temperature 4 C Maximum temperature controller 7 C, limited motor protection. Dimensions: 4 mm x 9 mm x mm Weight: 8, kg Degree of protection: IP 4 3-stage speed controllers with thermostat Controller is used to regulate devices equipped with 3-stage fans. It has 3-stage speed control and thermostat built in. In addition, the unit controls the operation of the actuators installed on the control valve. Works in both heating and cooling modes. Voltage: 3V /6Hz Rated current: 3A Temperature range: C~3 C operating modes: continuous and thermostatic Control accuracy: < C Working environment parameters: C Dimensions: x8x4 mm Weight:,kg Degree of casing's protection: IP3 Fan speed controller HC 4A designed to change the single-phase fan's speed voltage controlled in industrial supply and heating systems Power supply voltage: 3V /6Hz Allowable current output: 4 A Maximum ambient temperature 4 C Maximum temperature controller 7 C, limited motor protection. Dimensions: 4mm x 9 mm x mm Weight:,kg Degree of protection: IP 4 Fan speed controller HC,A designed to change the single-phase fan's speed voltage controlled in industrial supply and heating systems Power supply voltage: 3V /6Hz Allowable current output:, A Dimensions: 6mm x 76mm x 6mm Degree of protection: IP 4 Two-way valve with actuator ¾ Power: 3V /6 Hz Total current: <,A Input: <, (3,3VA) Auxiliary microswitch: A Maximum operating temperature: 6ºC Degree of protection: IP4 Closing time: -6 min Adjustment stroke: 3,6 mm Fan speed controller HC 3A designed to change the single-phase fan's speed voltage controlled in industrial supply and heating systems Module relay RM-6A Relay module RM-6A opens and closes the circuit to affect the work Power supply voltage: 3V /6Hz Allowable current output: 3 A Dimensions: 6mm x 76mm x 6mm Obudowa w stopniu ochrony : IP 4 of other devices. It can be used to connect a receiver with higher power than the relay in the controller allows. Maximum rated current is 6A. Power supply: 3 V AC Maximum rated current: 6 A Input: NO/COM Input SL Connection of a regulator with the voltage relay 3 V Output signal: relay NO/COM/NC Dimension: 47 x 47 x mm Fan speed controller HC A designed to change the single-phase fan's speed voltage controlled in industrial supply and heating systems Power supply voltage: 3V /6Hz Allowable current output: A Maximum ambient temperature 4 C Maximum temperature controller 7 C, limited motor protection. Dimensions: mm x 7 mm x mm Weight: 3,8 kg Degree of protection: IP 4 Programmable room thermostat HC Number of temperature levels: Hysteresis:, /ºC Power: baterie AA Switching: 3 VAC/Hz (3) A Operating temperature range: -4ºC Temperature control range: -3ºC Accuracy of temperature:,ºc Number of programs: 9 Fan speed controller HC 7A designed to change the single-phase fan's speed voltage controlled in industrial supply and heating systems Manual thermostat HC Power supply voltage: 3V /6Hz Allowable current output: 7 A Maximum ambient temperature 4 C Maximum temperature controller 7 C, limited motor protection. Dimensions: 4 mm x 9 mm x mm Weight: 6,4 kg Degree of protection: IP 4 Operating temperature: -4ºC Temperature control range: -3ºC Accuracy of temperature: ºC Number of programs: Rated current: 3A COOPERATION WITH EQUIPMENT HC A HC 7 A HC A HC 4 A RM-6A FSHC-67 FS7HC-68 FSHC-69 FS4HC-6 RM6A Model HC3S HC, A Code RTHC3S-779 FSHC- REVENTON S-3S 7 7 REVENTON S-3S REVENTON S3-3S REVENTON S4-3S 3 HC 3 A FS3HX-

6 7. CONNECTION SCHEMES LEGEND:. Power. Main switch, overcurrent circuit breaker * 3. Air water heater Reventon S series 4. 3-stage speed controllers with thermostat A-work in continuous mode B-operation in thermostatic mode. Two-way valve with actuator HC ¾ " 6. Fan speed controller HC 7. Manual thermostat HC 8. Digital programmable thermostat HC 9. Relay module RM-6A * main switch and safety fuses are not included in the set

7

8

9

10 8. TERMS OF WARRANTY I.Reventon Group Sp. z o.o. [Ltd.] 3B Montazowa Street, 43-3 Bielsko-Biała, Poland, is the producer of the Reventon Group brand. The warranty concerns the following devices and it is valid for (two) years: - air water heater Reventon S-3S - air water heater Reventon S-3S - air water heater Reventon S3-3S - air water heater Reventon S3-3S 7kW 3V 9kW 3V kw 3V 9kW 3V II. Warranty is valid in the European Union. III.The terms of warranty are valid from purchasing the device (the date issuing a document confirming the purchase of the device) but not further than 3 (thirty) months from leaving the producer s warehouse. IV.The defects revealed during the warranty period will be removed free of charge in 4 working days. The service will be done by the installation company due to the terms included in warranty card. The elements will be supplied by the Reventon Group Sp. z o.o. during the warranty period. V.Warranty does not cover the parts of the device subject to normal maintenance and the cases as below: a) Mechanical defects, damages from the impact of the improper transportation or damages through improper storage. b) Defects through: - improper usage and service; - using the device in the improper conditions (too high humidity, too high or too low temperature, impact of the surrounding, sun etc.); -modified equipment that has been modified or repaired without written agreement of the producer; - connecting additional equipment, which is not recommended by the producer or inconsistent with the technical documentation; - improper power supply. c) Elements which wear and tear such as discolor or using. VI.All changes in record in the warranty terms or any constructive modifications, independent service outside the Reventon Group Sp. z o.o. service or use, uncaring, makes the warranty not valid. VII.To obtain the service it is needed to send to the producer warranty card with the signature, document confirming the purchase, (copy of the invoice) and correctly filled the warranty form. VIII. Not following to any of warranty regulations makes the warranty not valid. IX.All correspondence, returns, complains should be send to the following address: Reventon Group Sp. z o.o. 3B Montazowa Street, 43-3 Bielsko-Biała, Poland or serwis@reventongroup.eu The producer reserves the rights to make changes to the technical documentation without previous notice.

11 Warranty card : : : : : Reventon Group [Ltd.] 3B Montazowa Street, 43-3 Bielsko-Biała, Poland

12 Reventon Group Sp. z o.o., ul.montażowa 3B, 43-3 Bielsko-Biała, Polska,

TECHNICAL DOCUMENTATION DTR AIR WATER HEATERS IN STEEL CASING S SERIES

TECHNICAL DOCUMENTATION DTR AIR WATER HEATERS IN STEEL CASING S SERIES TECHNICAL DOCUMENTATION DTR AIR WATER HEATERS IN STEEL CASING S SERIES ENG Technical documentation Table of contents 1. INTRODUCTION 1.1 PRECAUTIONS 1.2 TRANSPORT 1.3 PACKAGE CONTENT 1.4 USE AND PRINCIPLE

More information

Technical documentation DTR AIR WATER HEATERS IN EPP CASING HC-3S SERIES

Technical documentation DTR AIR WATER HEATERS IN EPP CASING HC-3S SERIES Technical documentation DTR AIR WATER HEATERS IN EPP CASING HC-S SERIES PL TECHNICAL DOCUMENTATION Table of contents Heating coil: made of aluminum and copper. The temperature of the heating factor is

More information

Technical documentation DTR

Technical documentation DTR Technical documentation DTR ENG TECHNICAL DOCUMENTATION Table of contents. INTRODUCTION. PRECAUTIONS. TRANSPORT. PACKAGE CONTENT. USE AND PRINCIPLE OF OPERATION. DEVICE CONSTRUCTION, DIMENSIONS, TECHNICAL

More information

Technical documentation

Technical documentation Technical documentation AIR WATER HEATERS IN STEEL CASING S SERIES MODELS: REVENTON GROUP S1-3S REVENTON GROUP S2-3S REVENTON GROUP S3-3S REVENTON GROUP S4-3S ENG TECHNICAL DOCUMENTATION Table of contents

More information

Technical documentation: S1 S2 S3 S4

Technical documentation: S1 S2 S3 S4 Technical documentation: S1 S2 S3 S4 1 Table of contents: 2 1. Introduction 3 1.1 Precautions 3 1.2 Transport 3 1.3 Package content 4 1.4 Use and principle of operation 4 2. Schematic diagram 4 2.1 Construction

More information

Technical documentation DTR. Farmer HCF in EPP casing

Technical documentation DTR. Farmer HCF in EPP casing Technical documentation DTR Farmer HCF in EPP casing ENG TECHNICAL DOCUMENTATION Table of contents. INTRODUCTION. PRECAUTIONS. TRANSPORT. PACKAGE CONTENT.4 USE AND PRINCIPLE OF OPERATION. DEVICE CONSTRUCTION,

More information

Technical documentaton DTR. Farmer

Technical documentaton DTR. Farmer Technical documentaton DTR Farmer ENG TECHNICAL DOCUMENTATON Table of contents. INTRODUCTION. PRECAUTIONS. TRANSPORT. PACKAGE CONTENT. USE AND PRINCIPLE OF OPERATION. DEVICE CONSTRUCTION, DIMENSIONS, TECHNICAL

More information

Technical documentaton DTR. Farmer

Technical documentaton DTR. Farmer Technical documentaton DTR Farmer ENG TECHNICAL DOCUMENTATON Table of contents. INTRODUCTION. PRECAUTIONS. TRANSPORT. PACKAGE CONTENT. USE AND PRINCIPLE OF OPERATION. DEVICE CONSTRUCTION, DIMENSIONS, TECHNICAL

More information

Technical documentation WATER HEATED AIR CURTAIN MODELS: REVENTON GROUP AERIS 100WN-1P REVENTON GROUP AERIS 150WN-1P REVENTON GROUP AERIS 200WN-1P

Technical documentation WATER HEATED AIR CURTAIN MODELS: REVENTON GROUP AERIS 100WN-1P REVENTON GROUP AERIS 150WN-1P REVENTON GROUP AERIS 200WN-1P Technical documentation WATER HEATED AIR CURTAIN MODELS: REVENTON GROUP AERIS 100WN-1P REVENTON GROUP AERIS 150WN-1P REVENTON GROUP AERIS 200WN-1P ENG TECHNICAL DOCUMENTATION Table of contents 1. INTRODUCTION

More information

PRICE LIST VALID FROM 1st October 2017

PRICE LIST VALID FROM 1st October 2017 PRICE LIST VALID FROM 1st October 2017 Product AIR WATER HEATERS MADE IN EPP CASING, HC SERIES 230V Air water heater HC20-3S 22kW WHHC20-3S-17 229 028601330 Air water heater HC30-3S 26kW WHHC30-3S-1760

More information

Reventon Group [Ltd.] 3B Montażowa Street, Bielsko-Biała, Poland VAT ID tel.

Reventon Group [Ltd.] 3B Montażowa Street, Bielsko-Biała, Poland VAT ID tel. CATALOG 17 Reventon Group [Ltd.] B Montażowa Street, - Bielsko-Biała, Poland VAT ID 97-67--6 export@reventongroup.eu www.reventongroup.eu tel. + 7 tel. + 77 TABLE OF CONTENTS ABOUT US AIR WATER HEATERS

More information

HEATING AND COOLING DEVICE AGC

HEATING AND COOLING DEVICE AGC GDYNIA HEATING AND COOLING DEVICE - AGC 2013 1/8 HEATING AND COOLING DEVICE AGC SERVICE phone.: (+48 58) 783 99 50/51 Fax: (+48 58) 783 98 88 mobile: (+48) 510 098 081 E-mail: serwis@klimor.pl GDYNIA,

More information

INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS

INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS TSEK VENCO Havalandırma ve Makina San.ve Tic. A.Ş. 2004. Cad. No:5 45400 OSB Turgutlu MANISA / TURKİYE Tel: +90 (236) 332

More information

HyBo - Hydraulic Interface Unit AMBIENT HEATING AND DOMESTIC HOT WATER PRODUCTION FOR CENTRAL HEATING SYSTEM UNIT CODE EHIU1

HyBo - Hydraulic Interface Unit AMBIENT HEATING AND DOMESTIC HOT WATER PRODUCTION FOR CENTRAL HEATING SYSTEM UNIT CODE EHIU1 HyBo - Hydraulic Interface Unit AMBIENT HEATING AND DOMESTIC HOT WATER PRODUCTION FOR CENTRAL HEATING SYSTEM UNIT CODE EHIU1 INSTALLATION, COMMISSIONING AND OPERATING INSTRUCTIONS Contents Unit as delivered

More information

TECHNICAL MANUAL YEFB HIGH PRESSURE DUCTED UNIT

TECHNICAL MANUAL YEFB HIGH PRESSURE DUCTED UNIT 1. GENERAL INFORMATION 1.1 Applications page 2 1.2 Operation» 2 1.3 Performances» 2 1.4 Product range» 2 1.5 Selection software» 2 2. DIMENSIONS AND WEIGHTS» 3 3. COMPONENTS 3.1 Structure» 4 3.2 Coils»

More information

ErP OPERATIONS MANUAL FOR AIR HEATER PROTON ECO. PROTON ECO Three-speed AC-motor

ErP OPERATIONS MANUAL FOR AIR HEATER PROTON ECO. PROTON ECO Three-speed AC-motor 05010416 OPERATIOS MAUAL FOR AIR HEATER PROTO ECO ErP 2015 PROTO ECO Three-speed Safety precautions Construction and dimensions Technical parameters Installation E RU www.protongroup.org COTETS Operations

More information

Weekly thermostat for boilers Galan - regulator for management of heating elements and circuit SolarSentinel-DBTW Users guide.

Weekly thermostat for boilers Galan - regulator for management of heating elements and circuit SolarSentinel-DBTW Users guide. Weekly thermostat for boilers Galan - regulator for management of heating elements and circuit SolarSentinel-DBTW Users guide. SHORT DESCRIPTION: 1. Device is applicable to: - Burners; - Electric boiler;

More information

1.1 VTS: number 1 in the world pillars of success

1.1 VTS: number 1 in the world pillars of success Heating Unit 01 VTS GROUP 1.1 VTS: number 1 in the world 1.2 3 pillars of success 02 2.1 water hearers Modernity Innovativeness Energy efficiency 2.2 Assembly 2.3 VR-D destratifier 2.4 Automation 03 TECHNICAL

More information

Operating manual. Pellet boiler. Orlan Pellet ISO 9001

Operating manual. Pellet boiler. Orlan Pellet ISO 9001 Operating manual Pellet boiler Orlan Pellet ISO 9001 Contens 1. Boiler s use...................................................................... 3 2. Boiler s way of working...........................................................

More information

Installation & Operating Manual ZM kW Universal Oil Heater. ZMH Ltd t/a Z M Heaters T (0)

Installation & Operating Manual ZM kW Universal Oil Heater. ZMH Ltd t/a Z M Heaters  T (0) Installation & Operating Manual ZM-130 16 32kW Universal Oil Heater OVERVIEW Dfdfdfdsfd Dfdfffdfdf Dfdfdf 4 1. Overheat thermostat 2. Combustion chamber lid 3. Oil feed line 4. Activation thermostat 5.

More information

Fan Coil Unit 1. BOSCH Climate Fan Coil Unit

Fan Coil Unit 1. BOSCH Climate Fan Coil Unit Fan Coil Unit 1 BOSCH Climate 000 Fan Coil Unit 2 Fan Coil Unit Introduction to Bosch Thermotechnology Bosch Thermotechnik GmbH is a leading supplier of resourceefficient heating products and hot water

More information

TermEfekt USER S MANUAL AIR HEATER. Model PGA 14

TermEfekt USER S MANUAL AIR HEATER. Model PGA 14 Przedsiębiorstwo Produkcyjno-Wdrożeniowe ARAJ sp. z o.o. 55-080 Kąty Wrocławskie, ul. Mireckiego 30 POLAND USER S MANUAL AIR HEATER TermEfekt Model PGA 14 Kąty Wrocławskie, 2004 Product identification

More information

VMA-VMB NOVA AIR HEATERS. NoVa air heaters

VMA-VMB NOVA AIR HEATERS. NoVa air heaters VMA-VMB NOVA AIR HEATERS NoVa air heaters PRODUCT FACTS PRODUCT The Novenco NoVa air heaters are water-based units with hot-water heating coils and axial flow fans fitted in cabinets. VMA for 10-20 C cooling

More information

No. 1 in Europe New on offer air curtain GUARD

No. 1 in Europe New on offer air curtain GUARD No. 1 in Europe New on offer air curtain H E A T E R S A I R C U R T A I N S No. 1 in Europe SONNIGER IS AN EUROPEAN PRODUCER OF MODERN, ECOLOGICAL/ECO-FRIENDLY AND OPTIMALLY SELECTED UNITS FOR INDUSTRIAL

More information

Roof top SPACE RPC 450Z R407C M011

Roof top SPACE RPC 450Z R407C M011 Roof top SPACE RPC 450Z R407C M011 Page : 1 / 5 Independant roof mounted unit, cooling only, ready to be installed, designed for air conditioning of large volumes for industrial or commercial use. As per

More information

ErP OPERATIONS MANUAL FOR AIR HEATER PROTON AST. PROTON AST Air Heater with the anemostat

ErP OPERATIONS MANUAL FOR AIR HEATER PROTON AST. PROTON AST Air Heater with the anemostat 05010416 OPERATIOS MAUAL FOR AIR HEATER PROTO AST ErP 2015 PROTO AST Air Heater with the anemostat Safety precautions Construction and dimensions Technical parameters Installation E RU www.protongroup.org

More information

INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS

INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS TSEK VENCO Havalandırma ve Makina San.ve Tic. A.Ş. 2004. Cad. No:5 45400 OSB Turgutlu MANISA / TURKİYE Tel: +90 (236) 332

More information

ErP OPERATIONS MANUAL FOR AIR HEATER PROTON EL. PROTON EL Electric heating.

ErP OPERATIONS MANUAL FOR AIR HEATER PROTON EL. PROTON EL Electric heating. OPERATIONS MANUAL FOR AIR HEATER PROTON EL ErP 2015 05010416 05022916 PROTON EL Electric heating Safety precautions Construction and dimensions Technical parameters Installation EN RU www.protongroup.org

More information

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories > HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION Available range Unit type IP Reversible heat pump (reversible on the refrigerant side) ECO-FRIENDLY REFRIGERANT GAS Versions (heat recovery) VB Base

More information

How to install and use your storage heater

How to install and use your storage heater How to install and use your storage heater Storage Heaters NST.M and NST.A This manual Introduction First of all, we would like to thank you for having bought an EV product; one that we hope will give

More information

ErP OPERATIONS MANUAL FOR AIR HEATER PROTON JET. PROTON JET Air Heater with with AirJet nozzle.

ErP OPERATIONS MANUAL FOR AIR HEATER PROTON JET. PROTON JET Air Heater with with AirJet nozzle. OPERATIOS MAUAL FOR AIR HEATER PROTO JET ErP 2015 05010516 PROTO JET Air Heater with with AirJet nozzle Safety precautions Construction and dimensions Technical parameters Installation E RU www.protongroup.org

More information

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ SERIES: EWCBZ - Heat pump MODELS: 70, 80, 00, 0, 60, 00, 40, 00, 50 COOLING CAPACITIES from 5,9 kw to 78,5

More information

Fan Heaters Type TXI, WBK, WBG, Delta & VLE

Fan Heaters Type TXI, WBK, WBG, Delta & VLE Fan Heaters Type TXI, WBK, WBG, Delta & VLE Sinus Jevi has an extensive program of high quality fan heaters for every application. From cost effective model TXI to high power stationary model VLE, all

More information

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4 Installation Operation Maintenance Ductable water unit FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

USERS MANUAL FOR GAS BOILERS

USERS MANUAL FOR GAS BOILERS USERS MANUAL FOR GAS BOILERS PLEASE READ THE MANUAL CAREFULLY: IT CONTAINS IMPORTANT INFORMATION REGARDING SAFETY, INSTALLATION, USE AND MAINTENANCE OF THE APPLIANCE MODELS: NOVADENS 24 NOVADENS 24C NOVADENS

More information

CNBOP-PIB Standard Fire Protection

CNBOP-PIB Standard Fire Protection Centrum Naukowo Badawcze Ochrony Przeciwpożarowej im. Józefa Tuliszkowskiego Państwowy Instytut Badawczy CNBOP-PIB-BA-01E:2014 Revision 1, February 2014 CNBOP-PIB Standard Fire Protection Laboratory Tests

More information

CAW Ceiling-mounted fan heaters for hot water

CAW Ceiling-mounted fan heaters for hot water Ceiling-mounted fan heaters for hot Ceiling-mounted fan heaters for hot Ceiling-mounted fan heaters for hot ceiling-mounted fans are used for heating entrances, warehouses, industrial premises, workshops,

More information

WHE 2.24 / WHE 2.24 FF

WHE 2.24 / WHE 2.24 FF EN Wall-hung gas boilers WHE 2.24 WHE 2.24 FF User Guide 300011777-001-C . Contents 1 Introduction.............................................................................3 1.1 Symbols used...........................................................................................3

More information

Electronically controlled instantaneous water heater. MCX: 27300, and models. Installation instructions

Electronically controlled instantaneous water heater. MCX: 27300, and models. Installation instructions Electronically controlled instantaneous water heater MCX: 27300, 27400 and 27600 models Installation instructions These appliances deliver water not exceeding 50 ºC in accordance with AS3498. 1. Overview

More information

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS CROWN Boiler Co Santa-Fe Series Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS These instructions must be affixed on or adjacent to the air handler Models: SAC049A20 SAC059A25

More information

INSTALLATION OPERATION & MAINTENANCE INSTRUCTION

INSTALLATION OPERATION & MAINTENANCE INSTRUCTION INSTALLATION OPERATION & MAINTENANCE INSTRUCTION TSEK HEAT RECOVERY UNITS MODELS CONTENTS Page 1. INTRODUCTION 2 2. HEAT RECOVERY UNITS and MODELS 2 3. TECHNICAL SPECIFICATIONS for HEAT RECOVERY UNITS

More information

Technical Guide. Installation, Operation and Care. EP E series 7 step electric boilers 26 and 42 kw

Technical Guide. Installation, Operation and Care. EP E series 7 step electric boilers 26 and 42 kw Technical Guide Installation, Operation and Care EP E series 7 step electric boilers 26 and 42 kw Arkelstorpsvägen 88, 291 94 KRISTIANSTAD Tel +46 44-22 63 20, Telefax +46 44-22 63 58 e-mail: info@varmebaronen.se

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS RH-24-HAC-P-1L-C-SDE*F Horizontal Single Stage R410a Model Size 24 Reversing (Heating AND Cooling) 208/230-1-60VAC Liquid to Air Geothermal Heat Pumps Maritime Geothermal Ltd.

More information

technical data Fan coil unit FWB small duct unit

technical data Fan coil unit FWB small duct unit technical data Fan coil unit FWB small duct unit TABLE OF CONTENTS FWB 1. Nomenclature ---------------------------------------------------------------------- 2 2. Features -----------------------------------------------------------------------------

More information

TTK 75 ECO OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75ECO-TC-002-EN

TTK 75 ECO OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75ECO-TC-002-EN TTK 75 ECO EN OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75ECO-TC-002-EN Table of contents Notes regarding the operating manual... 01 Information about the device... 02 Safety... 04 Transport...05 Start-up...05

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS RH-12-HAC-P-1L-C-SDE*F Horizontal Single Stage R410a Model Size 12 Reversing (Heating AND Cooling) 208/230-1-60VAC Liquid to Air Geothermal Heat Pumps Maritime Geothermal Ltd.

More information

Roof top SPACE RPC 315Z R407C MA00

Roof top SPACE RPC 315Z R407C MA00 Client : TIHE SERV Contact : Romeo Staicu Your reference : Your contact : Phone : E-mail : Page : 1 / 6 Roof top SPACE RPC 315Z R407C MA00 Independant roof mounted unit, cooling only, ready to be installed,

More information

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL Heating, Air Conditioning, Ventilation Отопление-Кондиционеры-Вентиляция MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL 1. Usage MTM 8-30 universal oil heater is designed for heating commercial rooms

More information

Air-Water heat pump Small GT

Air-Water heat pump Small GT Catalogue No.... KJ... Production date... Installation and operation manual Air-Water heat pump Small GT The heat pump generates DHW at a maximum temperature of 50 C Distributor: ver. 21/04/2015 Please

More information

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1 UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS GPE 802 Kc + CF + GP + MV + P1 130 Above picture is only indicative and is not binding. AIR R-410A

More information

HIGH TEMPERATURE AIR SOURCE HEAT PUMP WATER HEATER

HIGH TEMPERATURE AIR SOURCE HEAT PUMP WATER HEATER HIGH TEMPERATURE AIR SOURCE HEAT PUMP WATER HEATER BIGGER-H SERIES JIAXING MES NEW ENERGY TECHNOLOGY CO.,LTD. High quality- We believe that quality is the best business plan R&D team- Professional R&D

More information

Air curtain.

Air curtain. Air curtain www.wingbyvts.com 01 VTS GROUP 1.1 VTS: Manufacturer No. 1 in the world 1.2 3 constituents of success 02 2.1 air curtains 2.2 Silence and power 2.3 Design and performance 2.4 Quality and design

More information

Comfort Air Curtains with in-built dynamic advertising

Comfort Air Curtains with in-built dynamic advertising Comfort Air Curtains with in-built dynamic advertising www.stavoklima.eu Li-DR Air Curtains Li-DR Contents Contents: page Introduction... 2 Air Curtains Li with in-built dynamic advertising (DR)... 3 Description

More information

Duct Heaters volts/1 phase volts/3 phase volts/3 phases volts/3 phases. Flange Type Duct Heater.

Duct Heaters volts/1 phase volts/3 phase volts/3 phases volts/3 phases. Flange Type Duct Heater. Duct Heaters Synheat duct heaters come in various sizes and dimensions to fit any compartment. There are three types of duct heaters available: open coil, tubular element or finned tubular heating elements

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products, Inc. 700 Thimble Shoals Blvd, Suite 109 Newport News, VA. 23606-2575 Tel: (757) 873 6800 Fax: (757) 873 3632

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

Gas heaters and convectors ROBUR

Gas heaters and convectors ROBUR Gas heaters and convectors ROBUR Table of Contents Robur M general characteristic...3 Robur M dimensions...3 Robur M construction...4 Robur M technical data...5 Robur M installation...6 Robur M accessories...7

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING USER S MANUAL VCU/ Series CENTRIFUGAL FAN IN SCROLL CASING 2 CONTENTS Introduction Use Delivery set Designation key Technical data Safety requirements Design and operating logic Mounting and set-up Connection

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side s Frost detector for use on the air side QAF64.2-J QAF64.6-J With active capillary tube sensing element for acquiring the lowest temperature within a range of 0 15 C With startup function Operating voltage

More information

AQUATHERM LTD INSTALLATION AND OPERATION OF ELECTRIC BOILERS

AQUATHERM LTD INSTALLATION AND OPERATION OF ELECTRIC BOILERS AQUATHERM LTD INSTALLATION AND OPERATION OF ELECTRIC BOILERS MRE-М; MХE-М; MХE-ММ Bulgaria Sofia 1504 32 Danail Nikolaev Blvd. http://aquatherm-bg.net aquatherm@windowslive.com Tel/fax: +359 29 434 434

More information

No. 1 in Europe New on offer air curtain GUARD

No. 1 in Europe New on offer air curtain GUARD No. 1 in Europe New on offer air curtain H E A T E R S A I R C U R T A I N S No. 1 in Europe SONNIGER IS AN EUROPEAN PRODUCER OF MODERN, ECOLOGICAL/ECO-FRIENDLY AND OPTIMALLY SELECTED UNITS FOR INDUSTRIAL

More information

INSTALLATION AND MAINTENANCE MANUAL. Alcor FA

INSTALLATION AND MAINTENANCE MANUAL. Alcor FA INSTALLATION AND MAINTENANCE MANUAL IST 03 F 048-01 Alcor FA Aluminium electric radiators with heat transfer fluid EN Dear customer, Thank you for choosing our product. Read this manual carefully before

More information

TSL hand dryer. installation + maintenance

TSL hand dryer. installation + maintenance TSL-3002 hand dryer installation + maintenance contents 3 Safety and Warnings 4 Box Contents 5 Technical Data 6 Before You Install 7 How to Install 10 Commissioning 12 Operation 12 Maintenance 13 Recommended

More information

TopVent Design Handbook

TopVent Design Handbook TopVent Design Handbook Recirculation Units and Supply Air Units for Heating and Cooling High Spaces TopVent Content TopVent DHV Recirculation unit for heating high spaces TopVent NHV Recirculation unit

More information

Bi2 4tubes * SLR 4T Fan coil radiator for heating and cooling at the same time. FEATURES. Cools, Dehumidifies, Heats and Filters

Bi2 4tubes * SLR 4T Fan coil radiator for heating and cooling at the same time. FEATURES. Cools, Dehumidifies, Heats and Filters Bi2 4tubes * SLR 4T Fan coil radiator for heating and cooling at the same time. FEATURES Cools, Dehumidifies, Heats and Filters Simultaneous Cooling + Heating Double HE Coil AC Motor Version with heating

More information

Electronically controlled instantaneous water heater. CEX 9-U: C models. Installation instructions

Electronically controlled instantaneous water heater. CEX 9-U: C models. Installation instructions Electronically controlled instantaneous water heater CEX 9-U: 27910-50 C models Installation instructions For 50 ºC models, the appliance delivers water not exceeding 50 ºC in accordance with AS3498. 1.

More information

Drying Ovens Models F3 - F6 - F9

Drying Ovens Models F3 - F6 - F9 Instruction and Maintenance Manual Drying Ovens Models F3 - F6 - F9 SUMMARY 1. GENERAL INFORMATION.....3 2. SPECIFICATIONS...4 2.1. General Specifications...4 2.2. Oven general description...4 2.3. Thermal

More information

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

LINEAR HEAT DETECTION CABLE DURÁN-SAFE LINEAR HEAT DETECTION CABLE DURÁN-SAFE Installation & User Manual 2017 DURAN ELECTRONICA S.L. - All rights reserved www.duranelectronica.com TABLE OF CONTENTS pages 1. INTRODUCTION...5 2. FUNCTIONING...5

More information

39HX. High-efficiency dual-flow air handling unit PRODUCT SELECTION DATA. Plug & play unit (built-in control) Class A+ across entire range

39HX. High-efficiency dual-flow air handling unit PRODUCT SELECTION DATA. Plug & play unit (built-in control) Class A+ across entire range PRODUCT SELECTION DATA Plug & play unit (built-in control) Class A+ across entire range Classic/Vertical/ceiling-mounted dualflow units High-efficiency heat recovery unit High performance plug fan High-efficiency

More information

The guarantee on this appliance is valid for 12 months from the first day of installation.

The guarantee on this appliance is valid for 12 months from the first day of installation. Users Manual Dear Customer, Thank you for choosing an ARISTON boiler. We guarantee that your boiler is a reliable and technically sound product. This Users Manual provides detailed instructions and recommendations

More information

SG-WS type EXCHANGERS FOR TAP WATER HEATING ELECTRIC STORAGE TAP WATER HEATERS GUARANTEE CERTIFICATE. volume: 80, 100, 120, 140, 200, 300 and 380 dm 3

SG-WS type EXCHANGERS FOR TAP WATER HEATING ELECTRIC STORAGE TAP WATER HEATERS GUARANTEE CERTIFICATE. volume: 80, 100, 120, 140, 200, 300 and 380 dm 3 GUARANTEE CERTIFICATE Date of assembly Stamp and signature of the fitter GUARANTEE VOUCHER 1 GUARANTEE VOUCHER 2 GUARANTEE VOUCHER 3 GUARANTEE VOUCHER 4 GUARANTEE VOUCHER 5 Cat. no. Factory no. Date of

More information

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB T_SMT_0609_GB 4,9 49,5 kw Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans INDEX SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3 CE CONFORMITY... 3 WORKING

More information

HOT TAP WATER EXCHANGER with solar pump-group ENSOL IT INSTALLATION AND OPERATION MANUAL WARRANTY CARD

HOT TAP WATER EXCHANGER with solar pump-group ENSOL IT INSTALLATION AND OPERATION MANUAL WARRANTY CARD HOT TAP WATER EXCHANGER with solar pump-group ENSOL IT 200 300 500 INSTALLATION AND OPERATION MANUAL WARRANTY CARD Contents: 1. Structure and Intended Use... 3 2. Safety devices and conditions for safe

More information

80HMA. Comfort Module Range for Monobloc Heat Pumps. Nominal heating capacity 4-20 kw Nominal cooling capacity 4-20 kw. Features

80HMA. Comfort Module Range for Monobloc Heat Pumps. Nominal heating capacity 4-20 kw Nominal cooling capacity 4-20 kw. Features Comfort Module Range for Monobloc Heat Pumps Quality Management Systems Comfort module with two-zone kit Single-zone comfort module 8HMA Nominal heating capacity 4- kw Nominal cooling capacity 4- kw The

More information

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION ECO-FRIENDLY REFRIGERANT GAS INSTALLATION AND OPERATION MANUAL Dear Customer, Thank you for having purchased a FERROLI product. It is the result of many years

More information

NIBE SPLIT ACVM 270 Air/water heat pump

NIBE SPLIT ACVM 270 Air/water heat pump NIBE SPLIT ACVM 270 Air/water heat pump NIBE SPLIT ACVM 270 system with complete indoor module NIBE SPLIT ACVM 270 is a complete modern heat pump system that offers effective technical energy saving and

More information

Drying Ovens for Fluxes Models F100 F200 - F400

Drying Ovens for Fluxes Models F100 F200 - F400 Instruction and Maintenance Manual Drying Ovens for Fluxes Models F100 F200 - F400 SUMMARY 1. GENERAL INFORMATION....2 2. SPECIFICATIONS.....3 2.1. General Specifications...3 2.2. Oven general description...3

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

TERM-E ELECTRIC HEATING AND VENTILATION UNITS

TERM-E ELECTRIC HEATING AND VENTILATION UNITS ELECTRIC HEATING AND VENTILATION UNITS INTENDED USE The heating units with axial fans, metal casing and electric heaters are designed to heat rooms such as: industrial halls, workshops, warehouses, commercial

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

FLAME AMPLIFIER MODULE 3001

FLAME AMPLIFIER MODULE 3001 SYSTEM 3000 / 4000 FLAME AMPLIFIER MODULE 3001 TECHNICAL DESCRIPTION EDITION TB_3001_EN_REV03 BFI Automation Mindermann GmbH, Eggerscheidter Str. 57, D-40883 Ratingen Phone +49 (0) 2102 96 82 0, Fax +49

More information

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort Application guide FLATAIR - FLCK/FLHK Providing indoor climate comfort MSL60E-0701 12-2006 Congratulations you have made a wise choice and we feel sure that it will meet your expectation INDEX CONTENTS

More information

Utopian Split A/C. Thank you for purchasing this quality Split A/C system!

Utopian Split A/C. Thank you for purchasing this quality Split A/C system! Utopian Split A/C Thank you for purchasing this quality Split A/C system! Please read through this manual completely, and keep it in case you need to reference the information in the future. Any operation

More information

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:

More information

РУКОВОДСТВО USER ПО MANUAL ЭКСПЛУАТАЦИИ CENTRIFUGAL INLINE FANS VKM / VKMZ / VC SERIES

РУКОВОДСТВО USER ПО MANUAL ЭКСПЛУАТАЦИИ CENTRIFUGAL INLINE FANS VKM / VKMZ / VC SERIES РУКОВОДСТВО USER ПО MANUAL ЭКСПЛУАТАЦИИ CENTRIFUGAL INLINE FANS / Z / VC SERIES 2 / z / VC CONTENT Use Delivery set Structural designation key Main technical data Safety requirements Fan design Connection

More information

Guide Specifications PART 1 GENERAL 1.01 SUMMARY

Guide Specifications PART 1 GENERAL 1.01 SUMMARY Guide Specifications PART 1 GENERAL 1.01 SUMMARY A The environmental control system shall be designed specifically for precision temperature control applications. It will automatically monitor and control

More information

BSK-RPR Fire Damper. Additional operating instructions according to

BSK-RPR Fire Damper. Additional operating instructions according to Additional operating instructions according to BSK-RPR Fire Damper Contents GENERAL CONDITIONS... 1 DESCRIPTION... 3... 4 EC Certificate of Conformity 0761 CPD 0245 Declaration of Performance 09-22-DoP-BSK-RPR-2013-07-01

More information

FagronLab NP-1 UV. Negative pressure workbench. User Manual

FagronLab NP-1 UV. Negative pressure workbench. User Manual Negative pressure workbench User Manual Table of contents 1. Introduction... 3 2. Service... 3 3. Warranty... 3 4. Application range... 4 5. Main technical parameters... 4 6. Performance index... 5 Vibration

More information

DUCTIMAX 2-8 kw. Medium available static pressure ducted hydronic units. Duct unit DUCTIMAX

DUCTIMAX 2-8 kw. Medium available static pressure ducted hydronic units. Duct unit DUCTIMAX Duct unit DUCTIMAX Medium available static pressure ducted hydronic units DUCTIMAX - 8 kw NEW PRODUCT JUNE 05 Performance and compactness in recessed ceiling installations ERGO Supervision Plus -pipe system

More information

Product is subject to and complies with Regulation (UE) N.327/2011. cert. n Fan Coil Unit Cassette SkyStar Jumbo ECM. technical catalogue

Product is subject to and complies with Regulation (UE) N.327/2011. cert. n Fan Coil Unit Cassette SkyStar Jumbo ECM. technical catalogue cert. n. 0545 Product is subject to and complies with Regulation (UE) N.327/2011 Fan Coil Unit Cassette SkyStar Jumbo ECM technical catalogue SkyStar Jumbo ECM Table of contents SkyStar Jumbo ECM TABLE

More information

JH Series Installation

JH Series Installation JH Series Installation Space Heating / Fresh Air Make-Up From the Manufacturers of Hi-Velocity Systems TM Includes: JH-15 JH-30 Module-JH-Series-Installation-Manual-010118 Installation JH fan coils by

More information

Fan heater SWT Ceiling mounted fan heater with water heat

Fan heater SWT Ceiling mounted fan heater with water heat Fan heater heat 3 models Fan heater Ceiling mounted fan heater with water heat Application The fan heater is used for heating entrances, stores, industrial premises, workshops, sports halls, garages and

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL INSTALLATION, OPERATION AND MAINTENANCE MANUAL Air Curtains: RECESSED WINDBOX (M, ECM, G, ECG), RECESSED COMPACT (M, ECM, G, ECG), RECESSED DAM (M, ECM, G, ECG) Please, read these instructions carefully

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01 b cool manufacturers of air-conditioning equipment ltd BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION Ver. 1.01 Ver. 3.02 01_18 BCool# 1 brt c/h r407c / r410a

More information

New Industrial Dual Flow Unit Coolers

New Industrial Dual Flow Unit Coolers New Industrial Dual Flow Unit Coolers One single smart platform offering a wide range of solutions 01 Applications Thanks to a considerable air flow and an optimal air distribution, the new Dual Flow Units

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information