External insulated volume. control damper
|
|
- Rachel Madlyn Dean
- 5 years ago
- Views:
Transcription
1 EPP Air Handling Unit with swept internal air flow paths Steel powder coated frame Acoustic Air treatment zone External insulated volume control damper 24V Actuators to dampers Internal louvre grille supplied as a standard in white. Other colours available upon request Linear grille for recirculation and natural ventilation air paths Recirculation and natural ventilation air volume control damper Halifax House, Cressex Business Park High Wycombe Buckinghamshire HP12 3SE T: +44 (0) F: +44 (0) E: info@monodraught.com W:
2 Hybrid Thermal Mixing (HTM) system - Façade Plus series (F+) Façade Plus series (F+) The Hybrid Thermal Mixing (HTM) system from Monodraught is designed to provide natural ventilation, hybrid ventilation incorporating mixed tempered air for winter periods with the ability to provide secure night time cooling and boosted levels of ventilation during summer. The system is designed to work in conjunction with natural ventilation provided by manual or automatic windows and can be used in single sided or cross flow ventilation strategies. The units can be mounted horizontally above windows or mounted vertically to the sides of rooms and can also be ducted to provide ventilation to deep plan rooms. The system comprises of an intelligent and fully automatic control system coupled with a low energy ventilation system which switches between operational modes dependant on season, external/internal temperature conditions and indoor air quality (IAQ). Designed to meet Priority School Building Programme requirements, the Monodraught HTM F+ series uses exceptionally low specific fan powers and features an intelligent control system which is supplied as standard with full data logging facility, temperature control and CO 2 control. With the optional BACnet module, each unit has the ability to output key performance data to a central BMS to show compliance within PSBP guidelines. TECHNICAL DETAILS Material: EPP (Expanded Polypropylene) 100% recyclable. ABS, aluminium and rubber sealed volume control dampers. Composite high density glass wool cladding. Performance: Daytime hybrid ventilation rate of approximately 200 l/s (SFP 0.15). Night time hybrid ventilation rate of approximately 300 l/s (SFP 0.30). U-value through external air shut off damper = 1.2 Wm²K. Air tightness = 2 Options: BACnet BMS interconnection module. Alternative grille colours available on request. System Requirements: Connection to clean outside air source (inlet positioned away from sources of pollution). 240V 3A fused switched spur mounted within 1m of unit. 2 F +
3 Dimensions: 1000 mm deep x 500 mm high, width varies with model. System Width Natural Ventilation Effective Free Area Weight of System Typical Louvre Size required (50%) 1000 mm 0.36 m 2 32 kg 1300 mm x 500 mm 1500 mm 0.5 m 2 40 kg 1800 mm x 500 mm Façade Plus series (F+) SPECIFICATION Hybrid thermal mixing ventilation system to suit a façade application. Each system is supplied complete with a fully automatic control system managing a low energy fan, insulated external volume control damper with rubber sealed low leakage aerofoil blades and re-circulation volume control damper. System constructed from EPP airflow paths and composite panels providing high levels of acoustic operation and composite panels to meet BB93 requirements. Systems are available in two widths of 1000 mm or 1500 mm wide with an overall height 500 mm and a depth of 1000 mm. Installed using drop rod (provided by others) or Gripple supports with white panel finish or boxing in by others following installation. White louvred supply grille and white linear recirculation grille are provided as standard. Fully automatic intelligent control system with traffic light indicator for manual window operation, temperature and carbon dioxide sensing and user overrides. Seasonal time and date clock built in with full data logging functionality. Optional BACnet module is available to allow BMS data interconnection. An external weather louvre (provided by others) is required for connection to HTM F+. Louvre panel to be supplied fitted with bird guard mesh and a spigot/ transition. HTM F+ system to be capable of providing an assisted ventilation rate of 200 l/s and night time purge mode of 300 l/s to provide secure night time cooling. Each system to provide a natural ventilation air path to assist natural ventilation through openable windows and reduce fan operation. CONTROLS AND USER INTERFACE Wall mounted user controls with: Room Temperature and CO 2 sensor. On/Off control. High, Medium(auto) and Low fan speed settings. LED wall panel to indicate when to open windows. 3 F +
4 Façade Plus series (F+) TYPICAL INSTALLATION/OPERATION DETAIL Cross Flow: Openable windows Summer Day Summer Night Winter Day Monodraught HTM F+ system mounted at the rear of a room to assist with cross flow ventilation using openable windows on the facade. System automatically provides secure night time cooling through natural ventilation opening or fan assisted if required. Winter ventilation automatically modulates dampers to mix re-circulated air with external air to ensure optimum ventilation temperatures. Single Sided Flow: Openable windows Summer Day Summer Night Winter Day Monodraught HTM F+ system mounted on the façade (can be ducted to provide ventilation to the rear of deep plan rooms) to assist with single sided ventilation using openable windows. System automatically provides secure night time cooling through natural ventilation opening or fan assisted if required. Winter ventilation automatically modulates dampers to mix re-circulated air with external air to ensure optimum ventilation temperatures. Single Sided Flow: Classroom 1 Classroom 2 Full height glazing & openable windows Plan View - Summer Day Section - Summer Night Section - Winter Day Monodraught HTM F+ units can be mounted vertically on the façade and can be ducted to provide ventilation to the rear of deep plan rooms to assist with single sided ventilation from manually openable windows. The duct can be a builders work plenum and is shown here with three linear grilles. This installation method allows full height glazing to be used at the elevation to maximise daylight levels within the room. 4 F +
5 WIRING DETAILS Standard Connections Optional Connections Façade Plus series (F+) OPTIONS Widths 1000 mm, or 1500 mm (10 or 15). Horizontal or Vertical Mounting (H or V). White panel finish for exposed installation or Silver panel finish for boxing in by others (W or S). Order code example HTM F+ (15, H, W). Controls interconnection options include: Master / slave mode to synchronise multiple units in a single zone. Inhibit input to enable / disable HTM F+ series system from BMS or Fire Alarm circuit. TYPICAL SPECIFICATION...No. Monodraught Hybrid Thermal Mixing ventilation systems to suit a façade application (HTM F+ code). Overall dimensions are 1000 mm/1500 mm wide x 1000 mm deep x 500 mm high. Each system is supplied complete with a low energy fan to provide 200 l/s (SFP 0.15) for mixed ventilation air, with the capability for night time purge mode of 300 l/s (SFP 0.30) to provide secure night time cooling, an insulated external volume control damper with rubber sealed low leakage aerofoil blades and a re circulation volume control damper. The system comes complete with a fully automatic intelligent control system including a wall mounted controller with integral temperature & carbon dioxide sensor, user overrides, and a traffic light indicator to advise room occupants regarding window operation. A built in seasonal time and date clock with full data logging functionality is also included. 5 F +
6 Façade Plus series (F+) The system is constructed from EPP airflow paths with composite cladding, providing high levels of acoustic attenuation and is supplied with Gripple fixings for installation. The HTM is suitable for boxing in following installation. Please note, the external weather louvre and transition to HTM are to be supplied, by others. Monodraught are able to provide a separate quotation for these items if required. CONTROL STRATEGY The HTM F+ incorporates a fully automatic control system based on a seasonal control strategy. The seasonal strategy is determined by time and date but is weather compensated to pick up unseasonal conditions. The system looks to provide natural ventilation as the default method of ventilation indicating when manual windows should be utilised to maximise IAQ and maintain comfort levels. The control system incorporates a number of temperature sensors integral to the unit to monitor external temperature, mixed air temperature and supply air temperature. In addition, a wall mounted controller fitted with an internal temperature, CO 2 sensor and user override and a manual window traffic light indicator are included as standard. Data is stored per minute on an integral data card for data analysis and compliance requirements as required. During daytime periods in the Spring, Summer and Autumn seasons, if the internal room temperature exceeds 26 C or the CO 2 level goes above 1500 ppm, the system will provide a boosted level of ventilation until which time optimum conditions are met. If the external temperature is below 15 C the system will operate under a hybrid ventilation strategy as per winter mode. During Summer periods between midnight and 7 am and the internal temperature is above 18 C, the system will provide night time cooling providing a peak ventilation rate of 300 l/s until such time that the internal temperature goes below 18 C. During Winter periods the system will operate under a hybrid ventilation strategy utilising the fan to mix and re-circulate warm room air to minimise cold draughts. All settings are customisable during commissioning phase. WINTER TIME THERMAL MIXING Depending on the external air temperature, the system will introduce ventilation air mixed with recirculated room air with the ratio of mixed to fresh air to minimise cold draughts and maintain IAQ / comfort conditions. Generally the system will try to supply a mixed air temperature above 15 C. Thermal Mixing Conditions: Internal room temperature = 23 C Ventilation rate set at 200 l/s External Temperature range varies Mixing of recirculation and external air supplies vary to maintain minimum supply air temperature of 15 C. System automatically modulates over 100% and these mixing levels are for representation only. 6 F +
7 Thermal Mixing Conditions Internal Room Temperature 23 o C Ventilation Rate 200 l/s External Temperature range varies Mixing of recirculation and external air supplies vary to maintain minimum supply air temperature of 15 o C. System automatically modulates over 100% and these mixing levels are for representation only Resulting mixed air temperature passed into room (temperature reading 1 m from edge of diffuser) Min supply temperature Façade Plus series (F+) 0 Text 15 Mixing Rate 2:5-60 l/s Fresh air 140 l/s Recirculated air Mixing Rate 1:2-70 l/s Fresh air 130 l/s Recirculated air Mixing Rate 2:3-80 l/s Fresh air 120 l/s Recirculated air Mixing Rate 3:4-85 l/s Fresh air 115 l/s Recirculated air Mixing Rate 4:5-90 l/s Fresh air 110 l/s Recirculated air Mixing Rate 1:1-100 l/s Fresh air 110 l/s Recirculated air 19.1 Mixing Rate 3:2-120 l/s Fresh air 80 l/s Recirculated air 18.3 Mixing Rate 2:1-130 l/s Fresh air 67 l/s Recirculated air 17.7 Mixing Rate 3:1-150 l/s Fresh air 50 l/s Recirculated air TESTING During December 2013 an HTM F+ system was installed within a climatic test chamber and a special heat sensitive membrane was fitted running through the centre of the system. An insulated chamber fitted below the HTM F+ system was heated to 23 C to represent an internal room condition. Thermal imaging video cameras were used to record the temperature profile of the mixing of air in real time. The thermal imaging cameras were set to record three zones with averaged temperature readings within each zone :- external air temperature, internal room air temperature and mixed supply air temperature. The system was then set to provide 200 l/s of mixed ventilation air to represent maximum daytime ventilation rates. Zone 1 is recording the external air temperature with an average temperature within the measured zone of 11.7 C Zone 2 is recording an internal room temperature with an average temperature within the measured zone of 22.7 C Zone 3 is recording the mixed air supply temperature with an average temperature within the measured zone of 16.4 C 7 F +
8 DELIVERING SUSTAINABLE SOLUTIONS
Hybrid Thermal Mixing Ventilation Systems
Established in 1974 Hessle High School- Courtesy of DLA Architects Hybrid Thermal Mixing Ventilation Systems High-performance, low carbon ventilation Table of Contents Introduction to Monodraught... 3
More informationTypical Operating & Maintenance Manual for SOLA-BOOST X-Air Project Name
Typical Operating & Maintenance Manual for SOLA-BOOST X-Air Project Name Enclosed in this package is the following information: Company details Maintenance Programme Equipment schedule Manufacturers product
More informationHYBRID PLUS2 AIRCOOL VENTILATORS
NEW PRODUCT CI/SfB (57.7) Xy Uniclass Ss_65_40_33_56 February 2018 HYBRID PLUS2 AIRCOOL VENTILATORS................................ ........................................................ HYBRID PLUS2
More informationHYBRID PLUS2 AIRCOOL VENTILATORS
NEW PRODUCT CI/SfB (57.7) Xy Uniclass Ss_65_40_33_56 February 2018 HYBRID PLUS2 AIRCOOL VENTILATORS................................ ........................................................ HYBRID PLUS2
More informationEco Active H E A T R E C O V E R Y S Y S T E M S H Y B R I D U N I T. W: T:
Eco Active H Y B R I D U N I T W: www.gdl.co.uk T: 01457 861538 Eco Active Hybrid Unit The Eco Active Hybrid unit is designed to provide ventilation in both summer and winter seasons. Ventilation is achieved
More informationEco Active H E A T R E C O V E R Y S Y S T E M S. Heat Recovery Penthouse Turret. W: T:
Eco Active Heat Recovery Penthouse Turret W: www.gdl.co.uk T: 01457 861538 Heat Recovery Penthouse Turret The HRPT provides ventilation into spaces all year round. The unit provides 100% fresh air whilst
More informationX-Stream Air Natural Ventilation kits are predominantly designed for self-installation. Suitable for ventilating existing and new build applications.
X- StreamSystems X-Stream Air Natural Ventilation kits are predominantly designed for self-installation. Suitable for ventilating existing and new build applications. Contact us on: 01384 455811 Visit
More informationACTIVE VENTILATION SYSTEMS
...................................... CI/SfB (57) Uniclass L75 June 2013 Contents Passivent Active Ventilation 3 The need for ventilation 4 What is Active Ventilation? 5 Active Transfer - Atrium System
More informationINTELLIGENT VENTILATION CONTROLS NATURAL AND HYBRID PLUS SYSTEMS
CI/SfB (57) Uniclass Ss_75_70_52_94 July 2017 INTELLIGENT VENTILATION CONTROLS NATURAL AND HYBRID PLUS SYSTEMS................................ 2...................................................................
More informationINTELLIGENT VENTILATION CONTROLS: NATURAL AND HYBRID SYSTEMS
...................................... CI/SfB (57) Uniclass L751 September 2012................. FURTHER.............. INFORMATION........... INTELLIGENT VENTILATION CONTROLS: NATURAL AND HYBRID SYSTEMS
More informationNATURAL VENTILATION CONTROL SYSTEMS
...... CI/SfB (57.9) Uniclass L755 September 2005 NATURAL VENTILATION CONTROL SYSTEMS... . 2 ...... Passivent ventilation control systems have been have been specially developed to meet the requirements
More informationThe new Xcell EC High Efficiency Range Fresh air pure and simple
The new Xcell EC High Efficiency Range Fresh air pure and simple The new Xpelair saving energy, saving money 2 www.xpelair.co.uk Introducing the NEW Xpelair Xcell EC High Efficiency range. The Xcell EC
More informationSUNWARM AIR SOLAR PRE-HEAT VENTILATION SYSTEM
SOLAR PRE-HEAT VENTILATION SYSTEM SUNWARM USES SOLAR ENERGY TO REDUCE THE HEATING DEMAND OF THE HOME AS WELL AS PROVIDING A COMPLETE VENTILATION SOLUTION. 76 BENEFITS Sunwarm Air provides both a ventilation
More informationRegulations covering Heating and Ventilation equipment in Schools
Contents Regulations, Heat / Ventilation in Schools 1-2 Controlling Fresh Air 3-4 Natural Ventilation 5 Mechanical Cooling 6 Acoustic Performance 7 Performance Data 8 Energy Consumption 8 Dimensions 9-11
More informationSwegon CASA W130. Ventilation unit with counter-flow plate heat exchanger HOME VENTILATION
Swegon CASA W130 Ventilation unit with counter-flow plate heat exchanger Ventilation unit for residential houses under 250 m². The unit has counter-flow plate heat exchanger. Suitable also for renovation
More informationCZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES
High efficiency air to water heat pumps with E.V.I. compressors infolinia: +48 691 262 691-15 C +63 C +43 C E.V.I. HP The series of high efficiency heat pumps has been specifically designed for use with
More informationPRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h
PRODUCT DATA COMFORT 40 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 40 m /h COMFORT 40 Product description The Comfort 40 is an energy-efficient ventilation
More informationeco PREMIUM ENERGY RECOVERY UNIT» Technical instruction
Air Comfort Air Treatment Energy Recovery eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction eco PREMIUM - Technical Instruction REDA 2 Contents Description Applications... 3 Quality & environment...
More informationCZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES
High efficiency air to water heat pumps with E.V.I. compressors -15 C +63 C E.V.I. The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems or
More informationLZT High efficiency air to water heat pumps with E.V.I. compressors
High efficiency air to water heat pumps with E.V.I. compressors -20 C +43 C +65 C E.V.I. C.O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating
More informationTOSHIBA AIR CONDITIONING
Digital Inverter Standard Specification R32 Introduction The following specification describes the Toshiba Digital Inverter Heat Pump air conditioning system(s) to be installed at the below site: (ADD
More informationDescription of the functions, IQlogic
, IQlogic General Control...168 Status...168 IQnavigator hand-held terminal and image management...169 Dashboard...169 Main setup...170 Air flow Regulation mode...171 Boost...171 Unit...171 Air adjustment...171
More informationPRODUCT DATA COMBI 300 POLAR BY NILAN. Ventilation with passive & active heat recovery. Active heat recovery. Passive heat recovery.
PRODUCT DATA COMBI 300 POLAR BY NILAN Ventilation with passive & active heat recovery Domestic Passive heat recovery Active heat recovery Ventilation < 350 m 3 /h Comfort heating Comfort cooling COMBI
More informationFUNCTION MANUAL, INSTALLATION GOLD RX/PX/CX/SD Generation F. Applicable to Program Version 1.27 and newer versions
FUNCTION MANUAL, INSTALLATION GOLD RX/PX/CX/SD Generation F Applicable to Program Version 1.27 and newer versions Content 1. Image Management...3 2. Main Setup...4 3. Filter Calibration...4 4. Functions...5
More informationLZA High efficiency air to water heat pumps with HP compressor
High efficiency air to water heat pumps with HP compressor -10 C +43 C +60 C HP C.O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems
More informationSwegon CASA R120. Ventilation unit with rotary heat exchanger HOME VENTILATION
Swegon CASA R120 Ventilation unit with rotary heat exchanger Ventilation unit for residential houses, multi-storey buidings and holiday cottages under 230 m 2. The unit is equipped with rotary heat exchanger.
More informationiq Star LYRA II chilled beam cassette
iq Star LYRA II chilled beam cassette Key features Ventilation Heating and cooling Compact chilled beam Adjustable induction Flow Pattern Control Integrated control In option: Demand Controlled Ventilation,
More informationPREEVA air handling unit
APPICATINS Heating, ventilation, cooling, heat recovery >> FACTRIES >> commercial premises >> WAREHUSES >> HAS >> SPRTS & EISURE >> PACES F WRSHIP >> RESTAURANTS PREEVA air handling unit www.reznor.eu
More informationThe Sentinel Kinetic Horizontal Range
Lo-Carbon Sentinel Kinetic Horizontal Features & Benefits Manufactured in the UK Building Regulations DF compliant Recognised in SP PCDB Energy Savings Trust best practice compliant Up to 81% heat recovery
More informationHomepage > Products > Decentralised ventilation systems > Vertical units > Type FSL-V-ZAB/SEK FSL-V-ZAB/SEK
Homepage > Products > Decentralised ventilation systems > Vertical units > Type FSL-V-ZAB/SEK FSL-V-ZAB/SEK SUPPLY AND EXTRACT AIR UNIT WITH HEAT EXCHANGER AND HEAT RECOVERY, SECONDARY AIR OPTION, FOR
More informationHalton Rex for Vario R6O - Variable air volume chilled beam
Halton Rex for Vario R6O - Variable air volume chilled beam Halton Rex for Vario chilled beam is: Combined cooling, heating, and supply air unit for flush installation within a suspended ceiling Well suited
More informationCeiling diffusers. Type DLQL
X X testregistrierung Type Horizontal one-way air discharge Horizontal two-way air discharge Horizontal four-way air discharge Horizontal duct connection For horizontal one-way to four-way air discharge,
More informationPRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h
PRODUCT DATA COMFORT 5000 BY NILAN Ventilation & passive heat recovery Commercial Passive heat recovery Ventilation < 5300 m 3 /h COMFORT 5000 The Comfort 5000 is a ventilation unit suitable for central
More informationAir Handling Units. direct drive - belt drive - custom built
for fresher air Air Handling Units direct drive - belt drive - custom built Vectaire Ltd is a member of: ; Fan Manufacturers Association; Smoke Control Association; Residential Ventilation Association;
More informationNatural Ventilation Controller with 24vDC drive NVC-1204
Natural Ventilation Controller with 24vDC drive NVC-1204 BACnet Enabled C-036 08/11 FEATURES > 24V DC supply > Native BACnet communications > Master/Slave grouping (shared information) > 3 x 0-10V outputs
More informationBACKGROUND VENTILATION SOLUTIONS FOR DOMESTIC BUILDINGS
...................................... CI/SfB (57) Uniclass L753 July 2015 BACKGROUND VENTILATION SOLUTIONS FOR DOMESTIC BUILDINGS................................................................... ...................................................................................
More informationZehnder Comfosystems. ComfoAir 180 Datasheet
Zehnder Comfosystems Heating Cooling Fresh Air Clean Air ComfoAir 180 Datasheet Zehnder Comfosystems ComfoAir 180 Physical specifications The Zehnder ComfoAir 180 heat recovery ventilation system is an
More informationCI/SfB (57) Uniclass Pr_30_59_96 December 2017 TRICKLE VENTILATORS...
CI/SfB (57) Uniclass Pr_30_59_96 December 2017 TRICKLE VENTILATORS... ................................................ TRICKLE VENTILATORS..................................................................
More informationHalton Vario Design Guide
Halton Vario Design Guide Enabling Wellbeing Table of contents 1. Halton Vario - ventilation and air conditioning system overview 3 1.1 Room level, Zonal level and central level 4 1.2 Flexible design and
More informationSmall Room Heat Recovery Ventilation
Small Room Heat Recovery Ventilation Ideal for smaller spaces that would benefit from heat recovery, such as staff rooms or offices Version 3.1 2 Breathing Buildings Small Room Heat Recovery 3 Small Room
More informationSIMPLICITY OR FULL MODULARITY?
D E S I G N I N G I N N O V A T I V E S O L U T I O N S AIR CONDITIONING & HEATING SOLUTIONS SIMPLICITY OR FULL MODULARITY? IDROFAN, BECAUSE YOU SHOULD NOT HAVE TO CHOOSE. Hydronic ducted fan coils Cooling
More informationNatural Ventilation Controller with 24vDC drive NVC-1204
Natural Ventilation Controller with 24vDC drive NVC-1204 BACnet Enabled C-038 08/16 FEATURES SPECIFICATION > 24V DC supply > Native BACnet communications > Master/Slave grouping (shared information) >
More informationSentinel Demand Energy Recovery Ventilation
Welcome to the world of Sentinel Demand Energy Recovery Ventilation Sentinel Totus 2 Demand Energy Recovery Ventilation (D-ERV) is a new heat recovery demand ventilation system designed to meet modern
More informationCHILLED BEAM CASSETTE IQ STAR LYRA
CHILLED BEAM CASSETTE IQ STAR LYRA TECHNICAL CATALOGUE 2 IQ Star LYRA Chilled beam cassette - Technical catalogue IQ STAR LYRA CHILLED BEAM CASSETTE The LYRA chilled beam cassette is a compact chilled
More informationPRODUCT DATA COMFORT 600 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 800 m 3 /h
PRODUCT DATA COMFORT 00 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 800 m /h COMFORT 00 Product description The Comfort 00 is an energy-efficient ventilation
More informationSpecification Data. General:
Specification Data General: Zone Units (ACU s) will be draw through vertical type having double skin construction. All Zone Units will have all necessary components such as control valves and motors to
More informationFans Air Handling Units Air Distribution Products Fire Safety Air Conditioning Air Curtains and Heating Products Tunnel Fans. Geniox.
Fans Air Handling Units Air Distribution Products Fire Safety Air Conditioning Air Curtains and Heating Products Tunnel Fans Geniox Quick guide Copyright: Systemair A/S, 1. edition 2017. We accept no liability
More informationCI/SfB X. EnviroPak Series GAS FIRED HEATING, VENTILATION AND COOLING UNITS
CI/SfB 56.83 X EnviroPak Series GAS FIRED HEATING, VENTIATIN AND CING UNITS EnviroPak Series GAS FIRED HEATING, VENTIATIN AND CING UNITS Introduction The Reznor EnviroPak is a new generation of gas fired
More informationDemand-controlled Ventilation Leading edge products for demand-controlled ventilation
Overview Demand-controlled Ventilation Leading edge products for demand-controlled ventilation Demand-controlled ventilation offers great comfort and low operating costs When the room is in use, ventilation
More informationWZT High Efficiency Air to Water Split System Heat Pumps With E.V.I. Compressors
High Efficiency ir to Water Split System Heat Pumps With E.V.I. ompressors -20 +43 +65 HP E.V.I..O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor
More informationVentilation in balance
Ventilation in balance control and operation Airlinq IF 2013 The Airlinq AM L control panel has won two design awards at if 2013 for its innovative design one award for if product design and if communication
More informationLZT LZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSION ACCESSORIES
High efficiency air to water heat pumps with E.V.I. compressors -15 +63 E.V.I..O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems
More informationNatural Ventilation. e-stack A-Series Ventilation System for Buildings with Atria. Installation and Maintenance. Palletised
Natural Ventilation e-stack A-Series Ventilation System for Buildings with Atria Installation and Maintenance The EMC Directive 004/108/EC The Low Voltage directive 006/95/EC Important Notes to Designers
More informationUnits for suspended ceilings
X X testregistrierung Units for suspended ceilings Type, hinged induced air grille, water connections Active chilled beam with two-way air discharge and horizontal heat exchanger, suitable for grid ceilings
More informationHRV Enthalpy. Catalogue
HRV Enthalpy Catalogue BM896 Iss 02 - Enthalpy MVHR Contents HRV1.35 Q Plus - Enthalpy...3 HRV2 Q Plus - Enthalpy...5 HRV3 Q Plus - Enthalpy...7 HRV10.25 Q Plus - Enthalpy...9 Heat Water vapour Gases and
More informationLZT High efficiency air to water heat pumps with E.V.I. compressors
High efficiency air to water heat pumps with E.V.I. compressors -20 +43 +65 E.V.I..O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems
More informationCaice Attenuator Selector - Specifier Edition
Fan Coil Unit Acoustic Performance Guarantee Modular Product Selection Low Noise Levels Efficiency Energy Saving Prestige Attenuation Controls Package Plenum Heating Cooling Fan Coil Unit Acoustic Performance
More informationCI/SfB X. DF / IDF Series GAS FIRED COMBINED HEATING AND VENTILATION
CI/SfB 56.83 X DF / IDF Series GAS FIRED COMBINED HEATING AND VENTILATION DF / IDF Series GAS FIRED COMBINED HEATING AND VENTILATION Introduction Nordair Niche is one of the UK's leading specialists in
More informationCeiling swirl diffusers
X X testregistrierung Ceiling swirl diffusers Type Plenum box with damper blade and square diffuser face Horizontal swirling air discharge For comfort zones, with fixed air control blades Circular and
More informationBENSON AMBIRAD. ... EnviroAir Gas Fired Heating, Ventilation & Cooling Units ... HEATI NG AND VENTILATION S OLUTIONS
BENSN... EnviroAir Gas Fired Heating, Ventilation & Cooling Units... AMBIRAD HEATI NG AND VENTILATIN S LUTINS EnviroAir... Gas Fired Heating, Ventilation & Cooling Units... The Benson EnviroAir is a new
More informationCeiling swirl diffusers
X X testregistrierung Ceiling swirl diffusers Type Plenum box with damper blade (optional) Horizontal swirling air discharge With very low sound power level for comfort zones, with fixed air control blades
More informationPRODUCT DATA COMFORT 1200 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 1400 m 3 /h
PRODUCT DATA COMFORT 00 BY NILAN Ventilation & passive heat recovery Commercial Passive heat recovery Ventilation < 00 m /h COMFORT 00 The Comfort 00 is a ventilation unit suitable for central ventilation
More informationAir Handling Units. direct drive - belt drive - custom built
for fresher air Air Handling Units direct drive - belt drive - custom built Vectaire Ltd is a member of: ; Fan Manufacturers Association; Smoke Control Association; Residential Ventilation Association;
More informationIndirect Evaporative Air Conditioning
Indirect Evaporative Air Conditioning World leading climate control solutions Seeley International is Australia s largest air conditioning manufacturer and a global leader in developing ingenious, energy-efficient
More informationLSK LSK. Air to water chillers and heat pumps VERSIONS ACCESSORIES
Air to water chillers and heat pumps The water chillers range have been designed for small and medium residential and commercial applications. The water chillers are suitable for water outlet temperatures
More informationiq Star LYRA II chilled beam cassette
Key features The LYRA II cassette is an active chilled beam for ventilation, cooling and heating. This diffusion system offers high flexibility thanks to the combination of Flow Pattern Control, Coanda
More informationCI/SfB (57.7) 2nd edition
CI/SfB (57.7) 2nd edition Sentinel Totus D-ERV Range Following on from the highly successful award winning Sentinel demand ventilation system, Vent-Axia has taken the next step by incorporating the Sentinel
More informationBXC AIR EXHAUST GRILLE FOR MECHANICAL VENTILATION WITH AUTOMATIC AIRFLOW CONTROL
BXC AIR EXHAUST GRILLE FOR MECHANICAL VENTILATION WITH AUTOMATIC AIRFLOW CONTROL 2 AERECO Air exhaust grille for mechanical ventilation with automatic airflow control AERECO Air exhaust grille for mechanical
More informationCI/SfB (57.7) 1st Edition. Vent-Axia Sentinel Kinetic Horizontal Range. Vent-Axia MVHR Units
CI/SfB (57.7) 1st Edition Vent-Axia MVHR Units Vent-Axia Sentinel Kinetic Horizontal Range Lo-Carbon Sentinel Kinetic Horizontal MVHR Units Features & Benefits Manufactured in the UK Building Regulations
More informationSentinel Kinetic MVHR RANGE
V:\Technical\ARTWORK\Fitting & Wiring\Word Files COMPLETE\442073 W.doc Sentinel Kinetic MVHR RANGE User Instructions Stock Ref. N 438342 Kinetic V 438222 Kinetic B Right 438222L Kinetic B Left 443319 Kinetic
More informationType TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES
Homepage > Products > Air Diffusers > Ceiling diffusers > Ceiling swirl diffusers > Type TDF-SilentAIR Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES
More informationSwegon CASA R85. Ventilation unit with rotary heat exchanger HOME VENTILATION
Swegon CASA R85 Ventilation unit with rotary heat exchanger Ventilation unit for residential houses, multi-storey buidings and holiday cottages under 170 m 2. The unit is equipped with rotary heat exchanger.
More informationInstallation and Maintenance
1.0 INTRODUCTION MRXBOXAB-ECO-LP1SW (Standard Unit) MRXBOXAB-ECO-LP1-OHSW (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery for Ceiling Void Mounting Installation and Maintenance The
More informationDERV / ERV DEHUMIDIFICATION & ENERGY RECOVERY V E N T I L A T O R U N I T S I N N O V AT I O N W I T H S T Y L E
DERV / ERV DEHUMIDIFICATION & ENERGY RECOVERY V E N T I L A T O R U N I T S I N N O V AT I O N W I T H S T Y L E INTRODUCTION DERV/ERV Introduction Dehumidification & Energy Recovery Ventilator DERV units
More informationPARAGON. Compact comfort module. Key figures
Compact comfort module www.eurovent-certification.com www.certiflash.com Comfort module is the name of a new family of compact comfort modules especially designed for use in hotels and hospitals. provides
More informationDemandAire. amaximize Energy Efficiency aincreased Kitchen Comfort acustomizable Systems. Demand Control Kitchen Ventilation System
Demand Control Kitchen Ventilation System Standard 0. Compliant 08 Listed amaximize Energy Efficiency aincreased Kitchen Comfort acustomizable Systems www.streivor.com Standard and Code Requirements for
More informationAir Handling Units. Geniox. Quick guide
Air Handling Units Geniox Quick guide Copyright: Systemair A/S, 2. edition 2018. We accept no liability for printing errors or alterations of products. The dimensions and data used in this leaflet are
More informationAERECO DEMAND CONTROLLED VENTILATION COMBINING INDOOR AIR QUALITY AND ENERGY SAVINGS
AERECO DEMAND CONTROLLED VENTILATION COMBINING INDOOR AIR QUALITY AND ENERGY SAVINGS INNOVATION THAT EXCELS IN AIR QUALITY AND ENERGY SAVINGS Aereco demand controlled ventilation Combining indoor air quality
More informationDemand Controlled Ventilation - With the windows shut! AHUs. For consistently good indoor air quality DATA LO GG ER. Scan to visit website
Demand Controlled Ventilation - With the windows shut! BMS DATA LO GG ER For consistently good indoor air quality AHUs Scan to visit website Rev: 3.0-09/2016 BMS DATA LO GG ER AHUs Welcome to AirMaster
More informationPREEVA EC Gas Fired Heating, Ventilation & Cooling Units
... PREEVA EC Gas Fired Heating, Ventilation & Cooling Units... ErP 2018 ErP Lot 21 Seasonal Efficiency and Nx compliant ErP 2018 ErP Lot 21 Seasonal Efficiency and Nx compliant PREEVA EC... Gas Fired
More informationHomepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD. Type ADD
Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD Type ADD FOR THE CREATIVE DESIGN OF CEILINGS IN COMFORT ZONES, WITH FIXED AIR CONTROL BLADES
More informationSystem architecture. Air treatment Index
System architecture Air treatment Index 88 Index Chilled-water air treatment units Type Range Cooling capacity, kw Heating capacity, kw Air flow, l/s Chilled-water terminal units Cassette Cabinet Concealed
More informationSPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw
SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:
More informationCeiling air diffuser INDULTHERM INDULTHERM-e
Technical Information Ceiling air diffuser INDULTHERM INDULTHERM-e Effective cooling and heating with a diffuser Thermomechanical or electrical switching Draught-free air distribution for cooling down
More informationSAVE VTC 700. Heat Recovery Ventilation Unit
Heat Recovery Ventilation Unit 207581-EN_GB 23-08-2011V.A001 Contents 1 Warnings... 1 2 Introduction... 2 3 Interface description... 3 3.1 Control panel... 3 3.2 Display symbols... 4 4 Menu settings...
More informationSEQUENCE OF OPERATIONS
SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,
More informationAdvanced Air. Hard Wired Damper Control Panels. Systems 10, 11, & 12. Hard-Wired Systems. Bespoke Systems Available. Value Engineered Solutions
ISSUE A, MAY 2008 Hard Wired Damper Control Panels Systems 10, 11, & 12 Hard-Wired Systems Bespoke Systems Available Value Engineered Solutions Overview The Hard-Wired Control Panels On a number of projects
More informationAir handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses
REC Temovex 4S-EC-RS Experts on indoor climate in low-energy houses RT 4S-EC-RS REC Temovex 4S-EC-RS ECO2 control system for low-energy and passive houses Comprises: - Air flow boost for warm and cold
More informationIndirect Evaporative Air Conditioning
Indirect Evaporative Air Conditioning World leading climate control solutions Seeley International is Australia s largest air conditioning manufacturer and a global leader in developing ingenious, energy-efficient
More informationDo More With Less
1300 306 125 www.livezi.com.au Do More With Less Livezi have been the leaders in residential multizone full temperature systems since the mid nineteen nineties. Our 2012 product line-up represents the
More informationInstallation and Maintenance
1.0 INTRODUCTION MRXBOXAB-ECO-LP1 (Standard Unit) MRXBOXAB-ECO-LP1-OH (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery for Ceiling Void Mounting Installation and Maintenance The LP1
More informationIntroducing the RetroVent
Fans For Life Introducing the RetroVent Features Benefits Made in the UK Flying the flag for UK manufacturing, lower carbon footprints and total control over quality Tubular heat recovery cell Designed
More informationPremium Efficiency Heat Recovery Unit. D-AHU Modular L. Air Handling Units
Premium Efficiency Heat Recovery Unit D-AHU Modular L Air Handling Units About Daikin Our promise is to ensure that customers can depend on Daikin for the ultimate in comfort, so that they are free to
More informationUnits for suspended cei lings
. X X testregistrierung Units for suspended cei lings Type, hinged induced air grille, water connections Chilled Beams No. 09.2.432 Eurovent certification HYGIENISCH GETESTET V DI 6022 Tested to VDI 6022
More informationType PWX HORIZONTAL CHASSIS TYPE WATERSIDE FANCOILS FOR CONCEALED OR EXPOSED INSTALLATIONS
Homepage > Products > Fancoil units > Type PWX Type PWX HORIZONTAL CHASSIS TYPE WATERSIDE FANCOILS FOR CONCEALED OR EXPOSED INSTALLATIONS Nominal sizes 60, 90, 120, 150, 180 and 205 Volume flow rate range
More informationCI/SfB (57.5) November 2008
CI/SfB (57.5) climate systems November 2008 High-comfort, low-energy ventilation An energy efficient, fresh, clean and healthy climate - all year round Ubbink Heat Recovery Ventilation (HRV) systems provide
More informationFire and Smoke Control Systems
Control Systems Electrical Mechanical Standard Panel Modular design for control and monitoring Premier Panel Customised design for control and monitoring Fully Addressable Fully programmable data wired
More informationMetropolitan high output natural and powered trench heaters
Metropolitan high output natural and powered trench heaters High output trench heaters Typically used in large glazed areas to reduce glazing losses, these units are the perfect way to enhance comfort.
More informationAssigning profiles to a Breathing Buildings NVHR Unit (NVHR900 & NVHR1100)
Assigning profiles to a Breathing Buildings NVHR Unit (NVHR900 & NVHR1100) This document provides a comprehensive step-by-step guide to assigning operating profiles for an NVHR unit to an existing IES
More informationPRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h
PRODUCT DATA COMFORT 450 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 450 m 3 /h COMFORT 450 Product description The Comfort 450 is an energy-efficient ventilation
More information