Akva Vita TDP-F District heating flat station for direct heating and domestic hot water systems

Size: px
Start display at page:

Download "Akva Vita TDP-F District heating flat station for direct heating and domestic hot water systems"

Transcription

1 Akva Vita TDP-F District heating flat station for direct heating and domestic hot water systems Akva Vita TDP-F Table of contents Akva Vita TDP-F...1 Table of contents...1 Safety notes...2 Delivery...2 Transport and storage...2 Mounting...3 Pipes connections...4 Electrical connection...4 Filling, start-up...4 Control...5 Maintenance...7 Troubleshooting DHW...8 Troubleshooting HE...9 DH-SMT/PL VI.KR.Z1.02 Danfoss 09/2006 1

2 Safety notes Following instructions refer to the standard design of the Akva Vita TDP-F flat station. Special versions of flat stations are available on request. To avoid injury of persons and damages to the device, it is absolutely necessary to carefully read and observe these instructions. Necessary assembly, start-up and maintenance work must only be performed by qualified and authorized personnel. Please comply with the instructions of the system manufacturer or system operator. Unused connections and shut-off valves must be sealed with a plug. The plugs can be removed by an authorized service technician only. Warning of high pressure and temperature The maximum temperature of the flow medium in a flat station is 90 C. The maximum operating pressure of the flat station is 10 bar. Be aware of the installation s permissible system pressure and temperature. The risk of persons being injured and equipment damaged increases considerably if the recommended permissible operating parameters are exceeded. We recommend installation of safety valve, however, always in accordance with local regulations. Warning of hot surface The flat station has got hot surfaces, which can cause skin burns. Please be extremely cautious in close proximity to the flat station. Warning of transport damage Before installation of flat station, please make sure that the flat station has not been damaged during transport. Noise level 55 db Corrosion protection All pipes and components are made of stainless steel and brass. The maximum chloride compounds of the flow medium should not exceed 300 mg/l. The risk of equipment corrosion increases considerably if the recommended permissible chloride compounds are exceeded. Delivery The Akva Vita TDP-F flat station is delivered without cover as a standard. Optional flat station equipment: - thermostatic by-pass, - connection pipe for circulation, - circulation pump, - safety valve / non-return valve, - return temperature limiter, - DHW flow limiter - ball valves w. and w/o pocket for pressure/ thermometer gauge 3/4 ext. thread - ball valves w and w/o pocket for pressure/ thermometer gauge 3/4 int. thread - thermometer Ø35 - zone valve with actuator - connection rail with 7 connections 3/4 (int. thread), insulated or non-insulated, - room thermostat with day and /or week program, - heat meter (DH supply), - cold water meter - white-lacquered steel sheet cover Standard delivery: The flat station is prepared for by-pass or DHW circulation control. Equipment for by-pass or DHW circulation control is optional equipment and must be ordered separately. In case of DHW circulation control remember to mount circulation pump and non-return valve (this is not part of the delivery and must be fitted remotely on site). Transport and storage If the flat station is stored before installation in a warehouse or any other room, make sure that the place is dry and heated. During transport of the flat station to an installation place it is recommended to lift it with special straps attached to the bottom (by flat station support construction). 2 VI.KR.Z1.02 Danfoss 09/2006 DH-SMT/PL

3 Mounting The flat station must be installed and connected by authorized service personnel. Installation must be in compliance with the local standards and regulations. Allow for adequate space around the flat station for mounting and maintenance purposes. Prior to the Akva Vita TDP-F installation all flat station pipes and connections should be cleaned and rinsed. Due to vibrations during transport all connections must be checked and tightened before the flat station is installed. The picture shows Akva Vita TDP-F flat station with by-pass control. Switching to DHW circulation control is possible from a constructional point of view, requiring only an additional connection pipe incl. fittings. Control change from by-pass to circulation - Loosen nut (1) on the T-piece on the top part of the plate heat exchanger, remove blind plate and mount connection pipe for circulation (optional feature). - Remove conical screw (2) (4 mm) on the T-piece above the PM controller. - Loosen and move capillary tube with union nut from pos 3. to pos Screw the conical screw from pos 2 (4 mm) on to the muff at pos Connect circulation installation system with connection pipe for circulation. - Remember pump assembly and non-return valve mounting in the circulation installation system. (not part of the delivery) The pump must pump water in direction towards the flat station. Heat meter assembly, fitting piece The flat station is equipped with a fitting piece for insertion of heat meter. Assembly of heat meter - Loosen nuts from fitting piece, remove fitting piece and replace with heat meter. - Mount the heat meter according to the medium flow direction. After mounting of heat meter remember to check all threaded connections. DCW meter The flat station is equipped with a fitting piece for insertion of DCW meter. Assembly of DCW meter Please refer to above assembly instructions for heat meter Zone valve with actuator The flat station is equipped with a fitting piece for insertion of zone valve with actuator. Assembly of zone valve with actuator Please refer to above assembly instructions for heat meter. Return temperature limiter The flat station is equipped with a fitting piece for insertion of return temperature limiter. Assembly of return temperature limiter Please refer to above assembly instructions for heat meter. DH-SMT/PL VI.KR.Z1.02 Danfoss 09/2006 3

4 Pipes connections Internal installation and district heating* pipes connections must be made by means of threaded or welded connections. Connections: 1 District heating (DH) supply 2 District heating (DH) return 3 Domestic cold water (DCW) inlet 4 Domestic cold water (DCW) outlet 5 Domestic hot water (DHW) 6 Heating (HE) supply 7 Heating (HE) return 8 Circulation - optional Connection sizes: DH + DCW + DHW: HE + optional circ.: G ¾ (int. thread) G ¾ (int. thread) Dimensions (mm): Without cover: H 640 x W 565 x D 110 (incl. ball valves) H 520 x W 565 x D 110 (excl. ball valves) With cover: H 740 x W 600 x D 150 * District heating (DH) - In the following DH is specified as the heat source for the substations. However, also other heat sources such as an oil or gas boiler or solar heating etc. could be used as the primary supply for the fitted substations, enabling the Danfoss Redan substations to be used in numerous schemes with different energy sources, depending on the local operating conditions. In order to simplify we have decided to use DH as designation for the primary supply. Electrical connection The flat station needs no electrical installation to the main supply or earth grounding. Filling, start-up Prior to the Akva Vita TDP-F installation all its pipes and connections should be cleaned and rinsed. Before starting-up, check if: - pipes are connected according to the circuit diagram, - release valves are shut-off, - threaded connections are tightened. The heat exchanger must be filled with water so that the pressure slowly reaches the working pressure. After that the shut-off valves should be opened and the operation of the heat exchanger must be observed (e.g. temperatures, pressure, thermal expansion, leakages). If the heat exchanger operates operates unproblematically, it can be taken into continuous use. All Danfoss heat exchangers and flat stations have been pressure tested prior to delivery. 4 VI.KR.Z1.02 Danfoss 09/2006 DH-SMT/PL

5 Control 1. Differential pressure controller The differential pressure controller reduces the fluctuating pressure in the district heating network to a small and invariable operating pressure in the flat station. The required room temperature is controlled on your radiator thermostats (fixed setting throughout the year). It is recommended that all radiators are opened a little in each room. The flat station can be equipped with dp controller type TD200 or AVPL, depending on customer demand. TD200 The differential pressure controller is preset from factory and should not be adjusted afterwards. AVPL The AVPL must be mounted in the return. The dp controller can be set at any differential pressure between 5 kpa and 25 kpa (0,05 bar and 0,25 bar). The dp controller is preset on 10 kpa (0,1 bar) and can be adjusted afterwards. 2. HE temperature control The HE temperature in the house is controlled by radiator thermostats. As an option the Akva Vita TDP-F flat station can be equipped with an electronic programmable room thermostat and a zone valve with actuator. In this case temperature is controlled by the room thermostat and radiator thermostats. Please note that the room thermostat keeps the temperature in the whole apartment according to setting room parameters. Consult additional maintenance instructions for room thermostat for further information. It is recommended to avoid fully opened thermostats on some radiators and fully shut-off thermostats on others. Higher temperature at the top and lower temperature at the bottom part of radiators means that the system operation is correct. To keep correct temperature and friendly microclimate for human beings in the apartment, it is recommended to ensure regular airing in rooms. 3. Limiting flow controller (return flow) Optional substation equipment, which is mounted on district heating company request. Limiting flow controller should be set to the required maximum return temperature, in compliance with the local demands. Approximate thermostat scale setting: I = 10 C 1 = 20 C 2 = 30 C 3 = 40 C 4 = 45 C I = 50 C (max. temp.) To ensure sufficient cooling and proper operation the HE return temperature (thermometer indication on secondary return) must be lower than the temperature set on the flow controller. DH-SMT/PL VI.KR.Z1.02 Danfoss 09/2006 5

6 4. DHW temperature control The DHW temperature is controlled by a proportional valve the PM controller. The DHW temperature control is realized by turning the lever towards the red (hot) or blue (cold) mark. The temperature should be set to C at normal use (7-8 l/min). The temperature should never exceed 55 C to avoid lime scale precipitation in the heat exchanger. If it is not possible to set the temperature according to the above recommendations, it is recommended to change the standard controller setting. PM controller The PM controller can operate in three basic settings: - High - Standard default - Low Approximate setting of PM controller is dependent on district heating supply temperature and p: Supply temperature: Disposable differential pressure p (bar): > C low low standard C low standard standard C low high high Setting changes: - dismount lever by using the attached Allen wrench, - remove plastic cap, - mount lever again and turn it: - 1 rotation clockwise high, - 1 rotation counter clockwise low, - mount cap and lever again. 6 VI.KR.Z1.02 Danfoss 09/2006 DH-SMT/PL

7 Thermostatic by-pass (optional) As an option the flat station can be equipped with a by-pass thermostat, Danfoss FJVR, which ensures that hot water is available immediately when tapping starts. It is recommended to set the thermostat in pos. 3. If the water temperature rises too slowly it can be necessary to set the thermostat at higher value, however, not higher than in position 4. DHW circulation (optional) As an option the flat station can be equipped with connection pipe for circulation with adjustable setting of DHW circulation. If the Akva Vita TDP-F flat station is connected to the circulation system in the building, the thermostat will control the circulation water temperature. This ensures that hot water is available at the tap point without any waiting time and water waste. It is recommended to set the thermostat in pos. 2-2,5. If the circulation pump is switched off, the thermostat should be closed. In case the Akva Vita TDP-F flat station has been delivered with by-pass control and this must be changed to DHW circulation, this can be done by performing control change from by-pass to circulation, as described on page 3. Approximate thermostat scale setting: I = 10 C 1 = 20 C 2 = 30 C 3 = 40 C 4 = 45 C I = 50 C (max. temp.) 5. Filters Filters should frequently be cleaned from sediments by authorized personnel, according to producer s instructions and depending on the flat station s operating conditions. Maintenance It is necessary to check and maintain the flat station on a regular basis in order to keep it in good operating condition. The frequency of the maintenance and service inspections should be according to system manufacturer specifications and local legislation. However, maintenance inspections should take place at least twice each year (before and after the heating season). In addition to the check of the flat station as to its functionality, it is also recommended to check if the following system parameters are compliant with the requirements of the system manufacturer and local regulations: - no leakages, - correct temperatures in the distribution network, - stable district heating supply and return temperatures, - correct cooling of the district heating supply, - DHW temperature (requested temperature should be in accordance with the local regulations), - pressure drops in filtering and water conditioning plants (filters, sludgers etc.), - pressure drops in the heat exchanger (primary and secondary side of heat exchanger). The flat station operator should consider the above parameters and prepare written maintenance reports. Service inspections by authorized personnel are usually more precise (complex) than user maintenance inspections and the intervals between them are longer. DH-SMT/PL VI.KR.Z1.02 Danfoss 09/2006 7

8 Troubleshooting DHW Problem Possible cause Solution In general: Does the PM controller work incorrectly? In general: Are the operating conditions satisfactory? PM controller leaking; Water leaking from Allen screws at the central part of PM controller. DHW tap load too low DHW tap load too low; Tap temperature too low; Tap temperature fluctuates; DH return water temperature too high while on standby; The plate heat exchanger is cold DH return water temperature too high while on standby; The plate heat exchanger is hot Primary return temperature too high during hot water tapping. Connecting pieces of the PM controller do not fit the flat station If the quantity of tapping water is normal (temperature unimportant) it indicates that the PM controller works correctly. The flat station requires a DH supply temperature of minimum 60 C and a differential pressure during operation according to the information stated in the product sheet for Akva Vita TDP-F. One of the two O-rings is defective (does not influence the PM operation). If a non-return valve is installed in the DCW inlet (e.g. in the house service connection or in DCW meter) a safety valve should be mounted between the non-return valve and the heat exchanger. The diaphragm of the PM controller is defective. PM controller wrongly adjusted, Strainer in DH supply clogged, Defective non-return valve in thermostatic battery (DHW tap temperature lower than DHW from flat station), Defective non-return valve in hotwater circulation (circulation return pipe is getting cold during tapping of hot water), Lime scale precipitation in the plate heat exchanger for DHW (primary Δt too low during DHW tapping), Dirt in PM controller, DCW flow too high (big nominal diameter of pipe, high DCW pressure), in total max litres per minute. The by-pass thermostat is defective or wrongly adjusted. Dirt (sand, iron splinters or similar) in PM controller. Controller does not close. Noise from flow can often be heard. Lime scale precipitation in the plate heat exchanger for DHW In particular when replacing PM controller in old flat station Locate defect in another part of the installation (see below) Contact district heating supplier. Replace PM controller (use new sealing). Replace diaphragm or PM controller. Setting, see Regulation chapter. Clean strainer. Clean or replace non-return valve. Clean or replace non-return valve. Replace the plate heat exchanger. Cleaning, see PM controller instruction. DCW reduction. Replace or adjust by-pass thermostat correctly Move handle several times between red and blue markings; at the same time do several hotwater tappings. Clean PM controller. Replace plate heat exchanger Loosen Allen screws; turn half of the PM controller VI.KR.Z1.02 Danfoss 09/2006 DH-SMT/PL

9 Troubleshooting HE If operating disturbances occur, the following basic features should be checked before carrying out actual troubleshooting: - the substation is connected to electricity (applies only to substations with room thermostat), - the strainer on the district heating supply pipe is clean, - the supply temperature of the district heating is at the normal level (summer, at least 60 C - winter, at least 70 C), - the differential pressure is higher than or equal to the normal (local) differential pressure in the district heating network if in doubt, ask the district heating plant, - there is pressure on the system. Problem Possible cause Solution Strainer clogged on DH or HE side (radiator circuit). Clean gate/strainer. No heat Uneven heat distribution Supply temperature too low Poor cooling Filter in the district heating meter clogged. Defective or wrongly adjusted differential pressure controller. Defective room thermostat/actuator - or possibly dirt in the zone valve housing. Air pockets in the system. Air pockets in the system. Strainer clogged. Too small heating surface/too small radiators in relation to the total heating requirement of the building. Poor utilization of existing heating surface. The system is single-pipe. Clean the filter (after consulting the district heating plant). Check the operation of the differential pressure controller clean the valve seat if required. Check the operation of the room thermostat/actuator - clean the zone valve seat if required. Air the installation thoroughly. Air the installation thoroughly Clean gate/strainer. Increase total heating surface. Make sure the heat is distributed evenly across the full heating surface. It is recommended to avoid fully opened thermostats on some radiators and fully shut-off thermostats on others. Higher temperature at the top and lower temperature at the bottom part of radiators means that the system operation is correct. It is extremely important to keep the flow temperature to the radiators as low as ever possible, while maintaining a reasonable level of comfort. DH-SMT/PL VI.KR.Z1.02 Danfoss 09/2006 9

10 Danfoss Redan A/S Sindalsvej DK-8240 Risskov, Denmark Phone: Fax: VI.KR.Z1.02 Danfoss 09/2006 DH-SMT/PL

Akva Vita TDP District heating flat station for direct heating and domestic hot water systems

Akva Vita TDP District heating flat station for direct heating and domestic hot water systems Akva Vita TDP District heating flat station for direct heating and domestic hot water systems Akva Vita TDP Table of contents Akva Vita TDP... 1 Table of contents... 1 Safety notes... 2 Delivery... 2 Transport

More information

Akva Lux TDP-F District heating flat station for direct heating and domestic hot water systems

Akva Lux TDP-F District heating flat station for direct heating and domestic hot water systems Akva Lux TDP-F District heating flat station for direct heating and domestic hot water systems Akva Lux TDP-F Table of contents Akva Lux TDP-F... 1 Table of contents... 1 Safety notes... 2 Delivery...

More information

Akva Vita Instantaneous water heater

Akva Vita Instantaneous water heater Akva Vita Instantaneous water heater Akva Vita Table of Contents Akva Vita... 1 Table of Contents... 1 Safety notes... 2 Delivery... 2 Transport and storage... 2 Mounting... 3 Pipes connections... 4 Electrical

More information

Akva Lux VX District heating substation for indirect heating and domestic hot water systems

Akva Lux VX District heating substation for indirect heating and domestic hot water systems Akva Lux VX District heating substation for indirect heating and domestic hot water systems Akva Lux VX Table of Contents Akva Lux VX... 1 Table of Contents... 1 Safety notes... 2 Delivery... 2 Transport

More information

HW 22 District heating substation for indirect heating and domestic hot water systems

HW 22 District heating substation for indirect heating and domestic hot water systems HW 22 District heating substation for indirect heating and domestic hot water systems HW 22 Table of contents HW 22... 1 Table of contents... 1 Safety notes... 2 Delivery... 2 Transport and storage...

More information

WL Instantaneous water heater

WL Instantaneous water heater WL Instantaneous water heater WL Table of contents WL...1 Table of contents...1 Safety notes...2 Delivery...2 Transport and storage...2 Mounting...3 Pipes connections...3 Electrical connection...3 Filling,

More information

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................

More information

Operating Guide. Termix Solar A+/B+ 1.0 Table of Contents. 1.0 Table of Contents

Operating Guide. Termix Solar A+/B+ 1.0 Table of Contents. 1.0 Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................

More information

MAKING MODERN LIVING POSSIBLE. Akva Lux II TDP-F. Instructions for installation and use. Danfoss District Energy

MAKING MODERN LIVING POSSIBLE. Akva Lux II TDP-F. Instructions for installation and use. Danfoss District Energy MAKING MODERN LIVING POSSIBLE Instructions for installation and use Danfoss District Energy substations Type 004U8264 Type 0048089 Cover for wall-mounting Type 0048044 Cover for recess mounting 1.0 Contents

More information

Installation Guide. Termix Distribution unit. 1.0 Table of Contents. 1.0 Table of Contents

Installation Guide. Termix Distribution unit. 1.0 Table of Contents. 1.0 Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................

More information

Instructions for installation and use Akva Lux II VX substations 1. Contents

Instructions for installation and use Akva Lux II VX substations 1. Contents Akva Lux II VX thermostatic control Akva Lux II VX thermostatic control, and optional junction box + zone valve Akva Lux II VX (ECL 110) Akva Lux II VX HWP (ECL210) Akva Lux II VX H2WP (ECL 210) 1. Contents

More information

Reno Exchange of gas boilers.

Reno Exchange of gas boilers. District heating substation for exhange of Gas Boilers Akva Lux II TDP Reno District district heating substation for heating and domestic hot water. Reno Exchange of gas boilers. www.danfoss.com 1.0 Content

More information

Domestic hot water (DHW) The substation can be supplied with connection pipes for DHW cylinder on the supply or return line.

Domestic hot water (DHW) The substation can be supplied with connection pipes for DHW cylinder on the supply or return line. MAKING MODERN LIVING POSSIBLE VX Solo II Substation for single-family, semi-detached and terraced houses as well as flats District heating substation for indirect heating. With connection pipes for W cylinder.

More information

60 C water temperature ensures thermal disinfection during hot water production

60 C water temperature ensures thermal disinfection during hot water production Product Catalog - Product Sheets Work smarter and get the complete overview of Danfoss Systems & Water Heaters for domestic hot water and district heating applications 60 C water temperature ensures thermal

More information

Instructions. VX Solo II. 1.0 Table of contents

Instructions. VX Solo II. 1.0 Table of contents 1.0 Table of contents 1.0 Table of contents...1 2.0 Safety notes...2 3.0 Storage and Handling...2 4.0 Disposal...2 5.0 Diagram - Examples...3 5.1 H (ECL 110) - With one heating circuit...3 5.2 H2 (ECL

More information

MAKING MODERN LIVING POSSIBLE. Akva Vita II TD & S Akva Lux II / Akva Les II TD & S. Instructions for installation and use. Danfoss District Energy

MAKING MODERN LIVING POSSIBLE. Akva Vita II TD & S Akva Lux II / Akva Les II TD & S. Instructions for installation and use. Danfoss District Energy MAKING MODERN LIVING POSSIBLE Akva Vita II TD & S Akva Lux II / Akva Les II TD & S Instructions for installation and use Danfoss District Energy Akva Vita II TD Akva Lux II TD Akva Les II TD Akva Vita

More information

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT Technical Data SD 4511A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE T14 & T14D TEMPERATURE PILOT PRINTED IN U.S.A. SD 4511A/9811 5 13 /16 D 4 7 /8 1 13 /16 T14 PILOT

More information

30% Safe. Take lead on your project with an efficient system concept. Technical handbook Danfoss EvoFlat systems from A-Z. evoflat.danfoss.

30% Safe. Take lead on your project with an efficient system concept. Technical handbook Danfoss EvoFlat systems from A-Z. evoflat.danfoss. MAKING MODERN LIVING POSSIBLE Technical handbook Danfoss EvoFlat systems from A-Z Take lead on your project with an efficient system concept Safe and comfortable EvoFlat systems provide heating and domestic

More information

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16)

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16) Data sheet Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16) Description XB06 IHPT The XB is a brazed plate heat exchanger designed for use with district heating systems

More information

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16)

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16) Data sheet Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16) Description XB06 IHPT The XB is a brazed plate heat exchanger designed for use with district heating systems

More information

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16)

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16) Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16) Description XB06 The XB is a brazed plate heat exchanger designed for use with district heating systems (i.e. air conditioning,

More information

Empty unit Cover Water Total weight 15 kg 8 kg 10 kg 33 kg

Empty unit Cover Water Total weight 15 kg 8 kg 10 kg 33 kg DE LUXE Substation Introduction The HERZ DE LUXE Substation is a firmly mounted unit for providing hot water. In contrast to a hot water boiler which heats and then stores the water before it is being

More information

Wall-mounted substation PKL-113

Wall-mounted substation PKL-113 Wall-mounted substation PKL-113 You have chosen a high-quality product to your home. We hope you will be as pleased with the substation as those customers we have served for over 30 years! Application

More information

Automatic balancing valves ASV-PV (new generation) DN 32-50

Automatic balancing valves ASV-PV (new generation) DN 32-50 Automatic balancing valves ASV-PV (new generation) DN 32-50 ASV-PV DN 32-50 Description ASV whiteboard animation SMT/SI ASV valves are automatic balancing valves. Together with Danfoss presetting radiator

More information

a Danfoss Platform for Flensburg Secondary Network

a Danfoss Platform for Flensburg Secondary Network DSP MINI a Danfoss Platform for Flensburg Secondary Network General description and application The DSP MINI is designed for use in district heating networks, suitable for heating and for providing DHW

More information

ELECTRIC BOILERS FOR CENTRAL HEATING

ELECTRIC BOILERS FOR CENTRAL HEATING ELECTRIC BOILERS FOR CENTRAL HEATING TermoMax INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS FOR INSTALLATION We reserve the right of alternations WE ARE NOT LIABLE FOR DAMAGES RESULTING FROM NON- OBSERVING

More information

INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE

INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE SPECIFICATIONS... 1 OVERVIEW... 2 PRECAUTIONS... 2 MOUNTING LOCATION... 2 CONNECTION TO BOILER PRIMARY PIPING:... 3 ELECTRICAL CONNECTION... 4 FLUSHING THE

More information

541D19 SERIES. Technical Manual. A Division of Aquion Partners L.P.

541D19 SERIES. Technical Manual. A Division of Aquion Partners L.P. 541D19 SERIES Technical Manual A Division of Aquion Partners L.P. Table of Contents Introduction... Page 1 Technical Specifications... Page 2 Flow Diagrams... Page 3 Injector & Flow Control Selection Injector...

More information

T. +44 (0) E.

T. +44 (0) E. Twin Plate Heat interface unit for indirect heating and instantaneous domestic hot water with electronic thermostatic control. Designed for wall-mounting. Application The is the complete solution for hot

More information

heat interface units A BOILER WITHOUT A FLAME

heat interface units A BOILER WITHOUT A FLAME A BOILER WITHOUT A FLAME heat interface units Communal Heat Networks A central boiler house will generate heat which is distributed through a network of pipe to each home or apartment in the building.

More information

ModuSat TP. Energy. Heat Interface Units

ModuSat TP. Energy. Heat Interface Units Energy Twin Plate Heat interface unit for indirect heating and instantaneous domestic hot water with electronic thermostatic control. Designed for wall-mounting. Application The is the complete solution

More information

Temperature controller for steam (PN 25) AVT / VGS - external thread

Temperature controller for steam (PN 25) AVT / VGS - external thread Data sheet Temperature controller for steam (PN 25) AVT / VGS - external thread Description The controller has a control valve VGS, thermostatic actuator and handle for temperature setting. Thermostatic

More information

Installation Guide DSA 1 MINI. Contents

Installation Guide DSA 1 MINI. Contents Installation Guide DSA 1 MINI Contents 1.0 Table of contents...1 2.0 Safety note...2 3.0 Storage and Handling...5 4.0 Disposal...5 5.0 Diagrams...6 6.0 Mounting...7 7.0 Installation and Start-up...8 7.1

More information

ECL Comfort 110, application 116

ECL Comfort 110, application 116 Operating Guide ECL Comfort 110, application 116 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

Temperature controller AVT with safety temperature monitor STM / VGS for steam (PN 25)

Temperature controller AVT with safety temperature monitor STM / VGS for steam (PN 25) Data sheet Temperature controller AVT with safety temperature monitor STM / VGS for steam (PN 25) Description STW871 The controllers are: - Type-tested acc. to EN 14597 and protect against exceeding temperatures:

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

Partner Valve/High Quality Ball Valve LENO MSV-S

Partner Valve/High Quality Ball Valve LENO MSV-S Partner Valve/High Quality Ball Valve LENO MSV-S Description LENO MSV-S is a partner valve for all manual balancing valves in the LENO family. LENO MSV- S can also be applied as a high quality ball valve.

More information

Herz York Direct Heat Interface Unit

Herz York Direct Heat Interface Unit www.herzvalves.com Herz York Direct Heat Interface Unit The Modern Solution for Apartment Heating and Domestic Hot Water Services General Description The Herz York Direct HIU is suitable for all community

More information

ModuSat TP. Energy. Heat Interface Units

ModuSat TP. Energy. Heat Interface Units Energy Twin Plate Heat interface unit for indirect heating and instantaneous domestic hot water with electronic thermostatic control. Designed for wall-mounting. Application The is the complete solution

More information

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602* User's Guide VI.7C.E6.02 2005.09 C37 *VI7CE602* *087R8070* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8070* *VI7CE602* Mixing controller with ON / OFF controlled

More information

AVTI Multifunctional self - acting controller

AVTI Multifunctional self - acting controller AVTI Multifunctional self - acting controller Description / Application AVTI is a self - acting combined controller developed for controlling small heat units with a room heating system and a hot service

More information

Contact person RISE Date Reference Page Björn Folkeson P03675B 1 (11) Energy and circular economy

Contact person RISE Date Reference Page Björn Folkeson P03675B 1 (11) Energy and circular economy Contact person RISE Björn Folkeson 2017-08-15 7P03675B 1 (11) Energy and circular economy +46 10 516 54 46 bjorn.folkeson@ri.se Gemina Termix A/S Navervej 15-17 DK-7451 SUNDS Danmark Testing of a HIU according

More information

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502* User's Guide VI.7C.C5.02 2005.09 C66 *vi7cc502* *087R8069* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8069* *vi7cc502* Mixing controller with PI controlled

More information

30% Take lead on your project with an efficient system concept. lower energy.

30% Take lead on your project with an efficient system concept. lower energy. Technical handbook Danfoss EvoFlat systems from A-Z Take lead on your project with an efficient system concept 30% lower energy consumption by individual metering in each apartment www.evoflat.danfoss.com

More information

HX-30/40 and HX-30/40 S Glass and Dishwashers

HX-30/40 and HX-30/40 S Glass and Dishwashers HX-30/40 and HX-30/40 S Glass and Dishwashers INSTALLATION OPERATION VERSION 18/01/00 2 Installation and Operation Instructions for Model HX-30/40 and HX-30/40 S (with built-in softener) Content Page 1

More information

CALEFFI. SATK wall-mounted heat interface unit Fitted for connection to DHW storage. SATK40 series 01216/14 GB

CALEFFI. SATK wall-mounted heat interface unit Fitted for connection to DHW storage. SATK40 series 01216/14 GB 4 RESET ON DHW CH FAULT SATK wall-mounted heat interface unit Fitted for connection to DHW storage SATK4 series ACCREDITED CALEFFI 6/4 GB ISO 9 FM 64 ISO 9 No. The latest generation of heat interface units

More information

HERZ Differential Pressure Control Valve 4002

HERZ Differential Pressure Control Valve 4002 HERZ Differential Pressure Control Valve 4002 Data sheet 4002, Issue 0118 Dimensions in mm B1 B2 1 4002 41 1 4002 61 1 4002 71 1 4002 42 1 4002 62 1 4002 72 1 4002 43 1 4002 63 1 4002 73 1 4002 44 1 4002

More information

Installation and Commissioning Instructions FMU3 Floor Mixing Unit with Grundfos UPM3 Pump

Installation and Commissioning Instructions FMU3 Floor Mixing Unit with Grundfos UPM3 Pump Installation and Commissioning Instructions FMU3 Floor Mixing Unit with Grundfos UPM3 Pump Reduced Installation time Precision regulation Minimal tooling required 100% tested prior to packaging High quality

More information

SEALED THERMAL STORE

SEALED THERMAL STORE ISSUE 3 0717 INSTALLATION AND USER GUIDE ENERGYMANAGER SEALED THERMAL STORE ADVANCE APPLIANCES LTD PLEASE RETAIN AND ENSURE SERVICE RECORDS ARE KEPT UP TO DATE. SCHEMATIC DIAGRAM OF ENERYMANAGER THERMAL

More information

CONNECTION OPTIONS FOR MANIFOLDS & CONTROL UNITS

CONNECTION OPTIONS FOR MANIFOLDS & CONTROL UNITS CONNECTION OPTIONS FOR MANIFOLDS & CONTROL UNITS INSTALLATION INSTRUCTIONS FOR CONTROL BOXES Pay attention to the total pressure loss when connecting UV4- to the control boxes for heating areas > 16 m²!

More information

s y ens Av Avensys FIN EST RUS SLO RUS UAE

s y ens Av Avensys FIN EST RUS SLO RUS UAE 34 224 34 225 Avensys Avensys GB D...1...5 I...5 N...9 GR...13 TR...17 BG...21 RO...25 GB...2 NL...6 FIN...10 CZ...14 SK...18 EST...22 RUS CN...26 F...3 S...7 PL...11 H...15 SLO...19 LV...23 RUS...27 E...4

More information

Intatherm Safe Touch Basin Tap IT1008CP

Intatherm Safe Touch Basin Tap IT1008CP Intatherm Safe Touch Basin Tap IT1008CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept any responsibility

More information

Thermostatic mixing valve VADO-PRO-100P

Thermostatic mixing valve VADO-PRO-100P Thermostatic mixing valve VADO-PRO-100P IMPORTANT Installer: This Manual is the property of the customer and must be retained with the product for maintenance and operational purposes INTRODUCTION Thermostatic

More information

SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production

SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production SATK0 - SATK0 series ACCREDITED ISO 900 FM 009/ GB replaces dp 009/ GB Function The latest generation of Heat Interface

More information

Avensys Avensys FIN EST SLO RUS UAE

Avensys Avensys FIN EST SLO RUS UAE 34 037 Avensys Avensys GB D...1...5 I...5 N...9 GR...13 TR...17 BG...21 RO...25 GB...2 NL...6 FIN...10 CZ...14 SK...18 EST...22 CN...26 F...3 S...7 PL...11 H...15 SLO...19 LV...23 RUS...27 E...4 DK...8

More information

Hot Chocolate Dispenser

Hot Chocolate Dispenser Hot Chocolate Dispenser Instruction manual Model: CN219-A AU Telephone Helpline: 1300225960 Safety Tips Position on a flat, stable surface. A service agent/qualified technician should carry out installation

More information

INSTALLTION FOR THERMOSTATIC VALVES

INSTALLTION FOR THERMOSTATIC VALVES SS-TH1000 ½ THERMOSTATIC VALVE SS-TH3000 ¾ THERMOSTATIC VALVE SS-TH2000 ½ THERMOSTATIC VALVE WITH BUILT IN VOLUME CONTROL SS-TH4000 ¾ THERMOSTATIC VALVE WITH BUILT IN VOLUME CONTROL Features: Ability to

More information

LYRA 1000 VVS Installation and Operation Manual LYRA 1000 VVS THERMAL STORE LYRA 1000 VVS

LYRA 1000 VVS Installation and Operation Manual LYRA 1000 VVS THERMAL STORE LYRA 1000 VVS www.regulus.eu LYRA 1000 VVS Installation and Operation Manual LYRA 1000 VVS THERMAL STORE EN LYRA 1000 VVS CONTENTS 1 Description... 3 1.1 Models... 3 1.2 Tank protection... 3 1.3 Thermal insulation...

More information

Operating Guide. ECL Comfort 210 / 296 / 310, application A247 / A Table of Contents

Operating Guide. ECL Comfort 210 / 296 / 310, application A247 / A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 6 2.1 Before you start.....................................................

More information

Installation S

Installation S Installation S59-2025 Thermostatic Mixing Valve (TMV25) with Optional Cabinet S59-2025RE (with Recess-Mounted Enamel Cabinet) S59-2025RS (with Recess-Mounted Stainless Steel Cabinet) S59-2025SE (with Surface-Mounted

More information

1 valve needed instead of 3 for pressure, flow and zone control of water-based heating systems.

1 valve needed instead of 3 for pressure, flow and zone control of water-based heating systems. AB-PM Consistent hydronic control Continuous energy savings AB-PM automatic balancing valve for a reliable and energy-saving heating system. 1 valve needed instead of 3 for pressure, flow and zone control

More information

AQUABLEND 1500 SOLAR THERMOSTATIC MIXING VALVE

AQUABLEND 1500 SOLAR THERMOSTATIC MIXING VALVE AQUABLEND 1500 SOLAR THERMOSTATIC MIXING VALVE Installation, Operating & Maintenance Instructions ATM715 I00005_Jun 16 NOTE: THIS DOCUMENT IS TO BE LEFT ONSITE WITH FACILITY MANAGER AFTER INSTALLATION

More information

Design & Product Guide. Danfoss FlatStations.

Design & Product Guide. Danfoss FlatStations. Design & Product Guide Danfoss FlatStations www.sav-systems.com Rev: 8.0 07/2016 About SAV Systems SAV has been operating in the UK since 1988. SAV Systems is a leading provider of innovative building

More information

Sanitary Water Tank INSTALLATION & SVC MANUAL

Sanitary Water Tank INSTALLATION & SVC MANUAL http://biz.lgservice.com Sanitary Water Tank INSTALLATION & SVC MANUAL MODEL : PHS Series CAUTION Before Servicing the unit, read the safety precautions in this manual. Only for authorized service personnel.

More information

WH-TD20B3E5 WH-TD30B3E5

WH-TD20B3E5 WH-TD30B3E5 Order No: PHAAM1004143C2 WH-TD20B3E5 WH-TD30B3E5 WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public. It does not contain

More information

ECL Comfort 110, application 130

ECL Comfort 110, application 130 Operating Guide ECL Comfort 110, application 130 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

TECHNICAL PROPERTIES OF THE APPLIANCE

TECHNICAL PROPERTIES OF THE APPLIANCE TGR 30-120 SM EN Dear buyer, thank you for purchasing our product. Prior to the installation and first use of the electric water heater, please read these instructions carefully. THIS APPLIANCE IS NOT

More information

Increase the attractiveness of your multi-family building

Increase the attractiveness of your multi-family building Modern heating technology for housing associations Increase the attractiveness of your multi-family building Energy-efficient and reliable heating solutions. Up to 23% energy savings thanks to intelligent

More information

Weather compensated flow temperature control of heating and boiler systems

Weather compensated flow temperature control of heating and boiler systems Instructions ECL Comfort 110 Application 130 Weather compensated flow temperature control of heating and boiler systems User guide, Installation & Maintenance DH-SMT/DK VI.KT.G3.02 Danfoss 06/2008 How

More information

1year. The natural connection between energy savings and a balanced two-pipe system.

1year. The natural connection between energy savings and a balanced two-pipe system. The natural connection between energy savings and a balanced two-pipe system Our Renovation + Solution is your automatic technology for perfect Hydronic Balancing of communal installations. 1year payback

More information

General System Layout Sketch

General System Layout Sketch General System Layout Sketch EZ-37 Solar Panels PV panel Glycol Fill Valve Expansion Tank ` 1 Introduction This document describes how to install a Heliatos GH type solar water heating system. These systems

More information

VXi. Indirect, fully insulated district heating subtations Akva Lux II VXi, VXi Solo. Fully insulated for very low heat losses.

VXi. Indirect, fully insulated district heating subtations Akva Lux II VXi, VXi Solo. Fully insulated for very low heat losses. Indirect, fully insulated district heating subtations Akva Lux II VXi, VXi Solo Indirect district heating substation for heating and domestic hot water. VXi Fully insulated for very low heat losses. www.danfoss.com

More information

WATER FILTRATION SYSTEM (USF3) OWNER S MANUAL

WATER FILTRATION SYSTEM (USF3) OWNER S MANUAL WATER FILTRATION SYSTEM (USF3) OWNER S MANUAL 1 INTRODUCTION Congratulations on choosing Permatech to improve the quality of your water. You will immediately begin to notice the numerous benefits of having

More information

product overview ProControl

product overview ProControl product overview ProControl 2016 product overview ProControl 2016 4 The company AFRISO Sp. z o.o. was founded in 1997. Since that time we keep doing our best to increase AFRISO brand awareness among Installers.

More information

MINIATURE THERMOSTATIC VALVE

MINIATURE THERMOSTATIC VALVE SS-TH500-1/2 Features: Ability to pre-select water temperature thus conserving water Compensates for water pressure fluctuations preventing scalding Safety button at 100 F prevents accidental scalding

More information

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE 780EN www.caleffi.com Recess Mounted Heat Interface Unit - SATK series SATK0-60 series INSTRUCTIS FOR INSTALLATI, COMMISSIING AND MAINTENANCE Function The SATK series HIU allows independent control of

More information

Avensys Avensys FIN EST SLO RUS UAE

Avensys Avensys FIN EST SLO RUS UAE 34 039 Avensys Avensys GB D...1...5 I...5 N...9 GR...13 TR...17 BG...21 RO...25 GB...2 NL...6 FIN...10 CZ...14 SK...18 EST...22 CN...26 F...3 S...7 PL...11 H...15 SLO...19 LV...23 RUS...27 E...4 DK...8

More information

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102*

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102* User's Guide VI.KM.E1.02 2005.09 C62 *VIKME102* *087R8091* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8091* *VIKME102* Double mixing controller C62 VI.KM.E1.02

More information

VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 500 l capacity

VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 500 l capacity VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 0 l capacity Datasheet Part no. and prices: see pricelist VITOCELL 300-V Type EVA and EVI Vertical DHW cylinder made from stainless steel 5/2012 Product

More information

Mercury Mixing Kit (Code: ME1053)

Mercury Mixing Kit (Code: ME1053) Mercury Mixing Kit (Code: ME1053) The installation and commissioning of the UFH mixing kit system must be exclusively performed by qualified personnel in accordance with the national guidelines and/or

More information

INSTALLATION MANUAL. Domestic hot water tank with option kit for air to water heat pump system EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 EKUHWB

INSTALLATION MANUAL. Domestic hot water tank with option kit for air to water heat pump system EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 EKUHWB INSTALLATION MANUAL Domestic hot water tank with option kit for air to EKHWSU50BV EKHWSU00BV EKHWSU00BV EKUHWB EKUHWWB EKHWSU50BV EKHWSU00BV EKHWSU00BV EKUHWB EKUHWWB CONTENTS Page INTRODUCTION Introduction...

More information

13-1. Temperature Regulator

13-1. Temperature Regulator -1 Step 0 Type/Structure/Features Please refer to this for type, structure and features of. Step 1 Selection Please look at the ID chart to choose the right products depending on the intended uses. Details

More information

ir-range 8G /03.15 Changes reserved.

ir-range 8G /03.15 Changes reserved. U s e r m a n u a l ic-range is-range ir-range 8G.52.80.00/03.15 Changes reserved. Contents 1. Introduction...3 2. Safety...5 3. Boiler description...6 4. Display and functions...7 4.1 DHW and Heating

More information

Radiator Trap Radiator Valve

Radiator Trap Radiator Valve Radiator Trap Radiator Valve -1 Step 0 Type/Structure/Features Please refer to this for structure and features of Radiator Trap, Radiator Valve, and Cold & Hot Water Valve. Oventrop GmbH & Co. KG For products

More information

F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual

F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual 008094 All fire extinguishers should be installed, inspected and maintained in accordance with

More information

Roth fixed-value control set with high-efficiency pump

Roth fixed-value control set with high-efficiency pump Energy Systems Roth fixed-value control set with high-efficiency pump Assembly Instructions Living full of energy Contents General information Intended use 3 Benefits 3 Layout/Components 3 Installation/Electrical

More information

Installation Instructions

Installation Instructions IMPORTANT Installation and final temperature adjustment are the responsibility of the installer. Installation Instructions Thermostatic Mixing Valve for Sinks/Faucets Inlet Outlet Model Connection Connection

More information

EcoAdvance Dual Plate

EcoAdvance Dual Plate EcoAdvance Dual Plate Heat Interface Unit Art.nr. 52057 - Rev. A - 26-04-2016 Changes and misprints reserved Installation & user manual Store this manual at your unit Explanation symbols and abbreviations

More information

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW)

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW) Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW) The contents of this publication are based on the latest information available and the materials that are used at the time of printing.

More information

Installation S

Installation S Installation S59-3080 Thermostatic High-Low Mixing Valve (HL80) with Optional Cabinet S59-3080RE (with Recess-Mounted Enamel Cabinet) S59-3080RS (with Recess-Mounted Stainless Steel Cabinet) S59-3080SE

More information

Installation S

Installation S Installation S59-3045 Thermostatic High-Low Mixing Valve (HL45) with Optional Cabinet S59-3045 (Valve Only) S59-3045RE (with Recess-Mounted Enamel Cabinet) S59-3045RS (with Recess-Mounted Stainless Steel

More information

ThermoClean Domestic water heating system with legionella growth prevention through thermal disinfection

ThermoClean Domestic water heating system with legionella growth prevention through thermal disinfection ThermoClean Domestic water heating system with legionella growth prevention through thermal disinfection Description/Application The ThermoClean system is compact and effective solution for legionella-free

More information

SHOWER SOFTENER-CEASA 1

SHOWER SOFTENER-CEASA 1 SHOWER SOFTENER-CEASA 1 Application: The product is mainly used for shower water softening, but can also be used for floor heating, beauty salons, hairdressing salons, washing machines etc. The softener

More information

Minimalist Bottom Outlet Thermostatic Bar Shower. Telephone Product Specification

Minimalist Bottom Outlet Thermostatic Bar Shower. Telephone Product Specification Product Specification ~ Minimum Working Pressure 0.5 bar ~ Maximum Working Pressure 4.0 bar ~ Cold Water Supply Temp 4-20 c ~ Hot Water Supply Temp 55-85 c ~ Fixing Centres 150mm +/- 20mm ~ Outlet size

More information

Installation and operation manual for mixing modules FH-MJB and FH-MJC

Installation and operation manual for mixing modules FH-MJB and FH-MJC 40 30 20 50 60 Installation and operation manual for mixing modules FH-MJB and FH-MJC Application The FH-MJB and FH-MJC mixing shunts are designed to supply floor heating areas up to approx. 40 m 2 (from

More information

HERZ Regulating valve 4002

HERZ Regulating valve 4002 HERZ Regulating valve 4002 Data sheet 4002, Issue 0214 Dimensions in mm B1 B2 1 4002 41 1 4002 61 1 4002 42 1 4002 62 1 4002 43 1 4002 63 1 4002 44 1 4002 64 1 4002 45 1 4002 65 1 4002 46 1 4002 66 DN

More information

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION SOLARCYL IM/SC INSTALLATION MANUAL This manual gives detailed advice for installation and should be read carefully prior to fitting any unvented

More information

5231 Series. Low Lead High Flow Thermostatic Mixing Valves. Installation, commissioning and service instructions ASSE 1017 NA10341

5231 Series.   Low Lead High Flow Thermostatic Mixing Valves. Installation, commissioning and service instructions ASSE 1017 NA10341 NA31 www.caleffi.com Low Lead High Flow Thermostatic Mixing Valves Copyright 1 Caleffi Installation, commissioning and service instructions Function 531 Series ASSE 17 model 531 series high flow thermostatic

More information

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2 Cleaning unit for coolant :_decftez`_>r_fr] Book No.: 1271526-02 V2 Alfa Laval Separation AB Separator Manuals, dept. SKEL S-147 80 Tumba, Sweden Telephone: +46 8 53 06 50 00 Telefax: +46 8 53 03 10 40

More information

OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE

OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE FOAM FIRE EXTINGUISHERS MODEL 254-6 LITER AFFF FOAM WITH SPRAY NOZZLE Model 250 2 ½ GAL.LON AFFF FOAM WITH ASPIRATED NOZZLE MODEL 252 2 ½ GAL.LON FFFP (ALCOHOL RESISTANT) FOAM WITH ASPIRATED NOZZLE OWNER'S

More information