1 Air cooled multifunction chillers 21,8 222 kw COOLING 25,2 236 kw HEATING technicalcatalogue T_MLTPF_0413_GB

2 INDEX GENERAL CHARACTERISTICS... 3 SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3 WORKING LIMITS... 4 WORKING LOGIC... 6 WORKING DIAGRAMS... 7 MAIN COMPONENTS... 9 OPTIONAL ACCESSORIES TECHNICAL DATA ACOUSTIC DATA ELECTRIC DATA MP.COM: MICROPROCESSOR CONTROL SYSTEM IDEA : DYNAMIC CONTROL SYSTEM OF DEFROSTING CYCLES OPTIONAL ACCESSORIES PUMPING GROUP OPTIONAL ACCESSORIES - WATER TANKS OPTIONAL ACCESSORIES SILENCING PLENUM ON CONDENSER AIR DISCHARGE OPTIONAL ACCESSORIES KIT FOR OUTDOOR INSTALLATION UNIT DRAWINGS RC GROUP S.p.A. T_MLTPF_0413_GB R410A

3 GENERAL CHARACTERISTICS Packaged multifunction liquid chillers, for independent or simultaneous production of chilled water for cooling and hot water for heating (4 pipes plant), throughout the year. The machines are designed for indoor installation and ducting for air suction and discharge. For outdoor installation the use of the dedicated optional kit is mandatory. The machine must be installed under a cover or anyway protected against atmospherics agent. Framework with sections of thick steel for high resistance to the greatest stress during handling and transport. Machines supply fully assembled with refrigerant charge and control systems. The installation requires electrical and hydraulic connections only allowing high costs and time reduction. Final assembly on all machines before shipment including running test, reading and monitoring of operating parameters, alarms simulation and visual check. Design, assembly and test as per the Company Quality Assurance program in full compliance with ISO RC Group has been the first Italian company in its segment to get the ISO 9001 in October 13 th, 1991 with certificate nr The machines are in full compliance with European Directive 2006/42CE, 2006/95CE, 2004/108CE, 97/23CE and subsequent amendments. SERIES IDENTIFICATION MULTIPLO PF Multifunction liquid chiller for four pipes plant with single condensing coil in vertical position, scroll compressors, plug fans and welded plate heat exchangers. Horizontal air suction and vertical discharge. R410A refrigerant charge. S version: single refrigerant circuit Cooling capacity 21,8 222,0 kw Heating capacity 25,2 236,0 kw MODEL IDENTIFICATION MULTIPLO PF 55 P 2 S C 2 55 Cooling capacity (kw) P Compressor type P Scroll fully-hermetic R410A 2 Compressors number S C Refrigerant circuit S Single refrigerant circuit Cabinet 2 Cabinet size RC GROUP S.p.A. T_MLTPF_0413_GB R410A 3

4 Chilled outlet water temperature WORKING LIMITS COOLING chilled water production Working limits diagram for chilled water production according to the ambient temperature and chilled water outlet temperature. WORKING LIMITS IN COOLING MODE ( C) B A 5 0 Use glycol solution Use glycol solution and BRINE kit ( C) Ambient temperature WARNING When machine works with partial load on the same circuit, these limits can be furtherly increased. OPERATING ENVELOPE A Machine operating envelope whose cooling capacity is calculable with the electronic selection program RC WORLD. OPERATING ENVELOPE B Machine operating envelope where you need to contact RC Group sales department to calculate the cooling capacity. The values are indicative. The working temperatures are influenced by a series of variables as: Working conditions Thermal load Active capacity steps Cleanness status of the finned pack heat exchanger Set of the microprocessor control 4 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

5 Hot outlet water temperature HEATING Hot water production for heating Working limits diagram for hot water production for heating according to the ambient temperature and hot water outlet temperature. WORKING LIMIT IN HEATING MODE ( C) A B ( C) Ambient temperature OPERATING ENVELOPE A Machine operating envelope whose thermal capacity is calculable with the electronic selection program RC WORLD. OPERATING ENVELOPE B Machine operating envelope where you need to contact RC Group sales department to calculate the thermal capacity. The values are indicative. The working temperatures are influenced by a series of variables as: Working conditions Thermal load Active capacity steps Cleanness status of the condensing coils Set of the microprocessor control ANTIFREEZE MIXTURES Antifreeze mixtures has to be used when the machine working conditions foresees the chilled outlet liquid temperature as shown in the table: PROPYLENE GLYCOL Chilled outlet liquid temperature from the machine Percentage in weight of the mixture ETHYLENE GLYCOL Chilled outlet liquid temperature from the machine Percentage in weight of the mixture C % C % WARNING The values are referred to machine working temperature and not to freezing temperature of the used liquid. The use of antifreeze mixtures causes a reduction of the machine performance, Please refer to the RC WORLD electronic catalogue to obtain the effective performance. RC GROUP S.p.A. T_MLTPF_0413_GB R410A 5

6 STORING TEMPERATURE If the machine is not installed on receipt and is stored for a long time, store it in a protected place, at temperatures ranging between -30 C and 50 C in absence of superficial condensation and direct sun light. WORKING LOGIC Multifunction liquid chiller with independent or simultaneous production of chilled and hot water for 4 pipes plants. WORKING LOGIC According to the request, the unit can produce chilled water and hot water for heating, as indicated in the below scheme, that summarizes the various working conditions. The unit cooling and heating functions are enabled by selectors placed on the electric board. The pumps indicated in the scheme are optional accessories and they are factory installed inside the chiller. The pumps are active only when the relative working mode is enabled. 4 PIPES PLANT Cooling selector Heating selector ON REMOTE OFF ON REMOTE OFF MULTIPLO PF can produce chilled water or hot water with variable loads up to 50% of the nominal. Unit equipped with two compressors can partialize their operation so as to obtain different working conditions as per following table: Component On Component Off Cool % UNITS EQUIPPED WITH 2 COMPRESSORS Heat % Compressor 1 Compressor 2 Cool % UNIT EQUIPPED WITH 1 COMPRESSOR Heat % Compressor Defrosting Defrosting Defrosting 6 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

7 WORKING DIAGRAMS CHILLED WATER PRODUCTION BT VR VIC VE2 VS VR C COM COM VE3 RL FG IL VE1 EV HOT WATER PRODUCTION FOR HEATING BT VR VIC VE2 VS VR C COM COM VE3 RL FG IL VE1 EV COM VIC BT Compressor Cycle inversion valve Gas/air heat exchanger CO EV VE VR Condenser Evaporator Expansion valve Check valve VS RL FG IL Solenoid Valve Liquid receiver Gas filter Liquid indicator RC GROUP S.p.A. T_MLTPF_0413_GB R410A 7

8 CHILLED WATER + HOT WATER PRODUCTION FOR HEATING BT VR VIC VE2 VS VR C COM COM VE3 RL FG IL VE1 EV DEFROSTING BT VR VIC VE2 VS VR C COM COM VE3 RL FG IL VE1 EV COM VIC BT Compressor Cycle inversion valve Gas/air heat exchanger CO EV VE VR Condenser Evaporator Expansion valve Check valve VS RL FG IL Solenoid Valve Liquid receiver Gas filter Liquid indicator 8 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

9 MAIN COMPONENTS FRAMEWORK Base, self supporting frame and panelling in steel plate with protective surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with epoxy powders. Colour: RAL 9002 COMPRESSORS Orbiting spiral (SCROLL) hermetic compressors with spiral profile optimized for R410A refrigerant. ON / OFF capacity control (0 / 100% each compressor). 2-pole 3-phase electric motor with direct on line starting. Phase sequence electronic relay. Crankcase heater. Electric motor thermal protection via internal winding temperature sensors. Terminal box with IP54 enclosure class. Rubber supports. PLANT SIDE HEAT EXCHANGER Copper brazed plate type with cover plates, plates and connections in AISI 316 stainless steel: Anticondensate insulation made of polyurethane. Temperature sensors on water inlet and outlet. Differential water pressure switch for water flow control. Antifreeze heater. AIR/GAS HEAT EXCHANGER Heat exchanger coil with internally corrugated copper tubes and high efficiency aluminium fins, specifically developed to provide high heat transfer and lower pressure drops. The combination of two factors, special tubes and fins, allow to optimally combine the following aspects: - Maximum capacity relative to the size of the exchanger. - Minimum charge of refrigerant. - Reduction of the air flow required for the heat exchange. Particular circulation on refrigerant side, in order to optimize performance in heat pump mode. Ambient temperature sensor Frame in galvanized steel. FANS SECTION Centrifugal fans with backward curved blades, single suction and without scroll housings (Plug-fans). Brushless type synchronous EC motor with integrated electronic commutated system and continuous variation of the rotation speed. The motor rotation control is obtained with the EC system (Electronic Commutation) that manage the motor according to the 0 10V proportional signal coming from the microprocessor control. Maintenance-free bearings IP54 enclosure class. REFRIGERANT CIRCUIT Components for the single refrigerant circuit: Reversing valve for refrigeration cycle inversion. Electronic expansion valves: o For P1 units: o - One electronic expansion valve. For P2 units: - One valve on plant side heat exchanger. - One valve on source side heat exchanger (finned coil). The valve allows high performance and system efficiency thanks to a timely and accurate response to changes in temperature and pressure. The electronic expansion valve exclude the installation of the electromagnetic valve on liquid line. Thermostatic expansion valve for defrosting check on air/gas heat exchanger. Sight glass. Liquid receiver with service valve and safety valve. Filter dryer on liquid line. Solenoid valves on liquid lines. Service valves on liquid line and gas discharge. Safety valve on low pressure side. RC GROUP S.p.A. T_MLTPF_0413_GB R410A 9

10 Safety valve on high pressure side. Pressure transducers with indication, control and protection functions, on low and high refrigerant pressure. High pressure safety switch with manual reset. Oil drainage and oil recovery systems. Check valves. IDEA defrosting system. RC Group patented defrosting system based on a dynamic reading of the evaporating parameters. Through sensors the microprocessor realize the real ice presence on the gas/air heat exchanger and activates the defrosting cycle only when necessary, with consequent energy saving. Refrigerant circuit with copper tubing with anticondensate insulation of the suction line. Plastic capillary hoses for pressure sensors connection. R410A refrigerant charge. ELECTRICAL PANEL In accordance with EN norms, suitable for outdoor installation, IP54 enclosure class, complete with: Main switch with door lock safety. Magnetothermic switch or fuses for each compressor. Magnetothermic switches for fans or water pumps (if scheduled). Contactors for each load. Transformer for auxiliary circuit and microprocessor supply. Panel with machine controls. Power supply: 400/3/50. CONTROL SYSTEM MP.COM microprocessor system with graphic display for control and monitor of operating and alarms status. The system includes: - Voltage free contact for remote general alarm. - Main components hour-meter. - Clock card for alarms date and time displaying and storing. - Non-volatile Flash memory for data storage. - Menu with protection password. - LAN connection. HYDRAULIC CONNECTIONS OF HEAT EXCHANGERS The heat exchangers threaded hydraulic connections are available up to a diameter of 2" included, and correspond to ISO 228/1 G M. The pipes threaded hydraulic connections are available up to a diameter of 2" included, and correspond to ISO 7/1 R. The hydraulic connections with flange (FL) are supplied as standard with counter flange. The hydraulic connections with grooved end are supplied as standard with flexible joint and adapter pipe. 10 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

11 OPTIONAL ACCESSORIES The descriptions of these additional components can be found in Chapter OPTIONAL ACCESSORIES. Pumping group with 1 pump for chilled water. The pumping group includes the chilled water safety flow switch. Pumping group with 2 pumps for chilled water. The pumping group includes the chilled water safety flow switch. Pumping group with 1 pump for hot water. The pumping group includes the hot water safety flow switch. Pumping group with 2 pumps for hot water. The pumping group includes the hot water safety flow switch. Chilled water storage tank. Hot water tanks. Silencing plenum on condenser air discharge. Kit for outdoor installation. OTHER OPTIONAL ACCESSORIES BRINE kit for chilled water production up to 12 C. WARNING With BRINE Kit it is mandatory to use antifreeze mixture. Refer to the paragraph ANTIFREEZE SOLUTION. The use of antifreeze mixtures causes a reduction of the machine performance, Please refer to the RC WORLD electronic catalogue to obtain the effective performance. Condensing coil protection net. Air/gas heat exchanger in Cu/Al coated execution. Air/gas heat excanger in special execution (please contact the RC GROUP Commercial Dept.). Spring antivibrating supports - not installed. Rubber supports - not installed. Heating system for electrical panel (suggested for operating condition of the machines with negative ambient temperature). Expansion valve energy reserve module to allow the closure of the valve in the event of lack of power supply. Water flow switch. Power factor capacitor for motor compressor - cos 0,9. MP.COM microprocessor control accessories: - Remote terminal. - Serial port RCcom, MBUS/JBUS. - Serial port LON. - Serial port BACnet for Ethernet SNMP TCP/IP. - Serial port BACnet for MS/TP. - Serial port for GSM model. - Data logger for the memorization of the intervened alarms. - Additional module with the following inlets / outlets: INLETS o External alarm 1 o External alarm 2 o Line current indication. o Line voltage indication / Compensation o Ambient air temperature OUTLETS o External alarm 1 o External alarm 2 o General alarm 2 o General alarm 3 - Driver for the additional module. WARNING It is mandatory to install a water filter on evaporator water inlet (not supplied with the machine). RC GROUP reserves the right to accept the matching of the optional installed on the unit. RC GROUP S.p.A. T_MLTPF_0413_GB R410A 11

12 TECHNICAL DATA MODEL 22 P1 24 P1 28 P1 32 P1 36 P1 42 P1 S S S S S S SIZE C1 C1 C1 C1 C1 C1 COOLING ONLY (1) COOLING CAPACITY kw 21,8 24,8 29,0 32,9 36,7 42,4 Compressors power input kw 6,3 7,3 8,5 9,6 10,9 13,1 Compressors operating current [OA] A 11,3 13,4 15,6 17,1 19,7 24,5 Evaporator water flow rate m³/h 3,8 4,3 5,0 5,7 6,3 7,3 Evaporator pressure drop kpa HEATING ONLY (2) HEATING CAPACITY kw 25,2 28,8 30,0 37,9 42,4 43,7 Compressors power input kw 5,9 6,8 7,8 8,9 9,9 11,6 Compressors operating current [OA] A 10,8 12,7 14,7 15,9 18,2 22,3 Condenser water flow rate m³/h 4,4 5,0 5,2 6,6 7,4 7,6 Condenser pressure drop kpa COOLING + HEATING (3) COOLING CAPACITY kw 22,7 26,1 30,6 34,9 39,0 45,4 HEATING CAPACITY kw 28,7 32,9 38,5 43,8 49,0 57,2 Compressors power input kw 6,0 6,8 7,9 8,9 10,0 11,8 Compressors operating current [OA] A 10,9 12,7 14,7 15,9 18,4 22,7 COMPRESSORS Quantity n Maximum current A Starting current A Capacity steps EVAPORATOR n Water volume l 1,9 1,9 2,1 2,8 2,9 3,3 Max water flow rate m³/h 4,6 5,2 6,0 6,9 7,8 9,0 CONDENSER n Water volume l 1,9 1,9 2,1 2,8 2,9 3,3 Max water flow rate m³/h 5,5 6,3 7,3 8,3 9,3 10,8 CENTRIFUGAL FANS n Total air flow m³/h External static pressure Pa Max external static pressure Pa Power input kw 0,6 0,7 1,1 1,2 1,6 2,1 Plate current [FLA] A 4,3 4,3 4,3 4,9 4,9 4,9 REFRIGERANT Total refrigerant charge (optional excluded) kg R410A R410A R410A R410A R410A R410A Gas circuits n POWER SUPPLY V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 ENERGY EFFICIENCY INDEXES EER Energy Efficiency Ratio kw/kw 3,20 3,12 3,01 3,03 2,93 2,80 COP Coefficient of performance kw/kw 3,90 3,87 3,35 3,75 3,68 3,20 ESEER - Eurovent Standard 4,01 3,93 3,62 3,66 3,46 3,19 IPLV - ARI Standard 550/590 4,45 4,36 4,01 4,06 3,84 3,54 SOUND LEVEL Average sound pressure level [Lp] (4) db(a) 70,6 72,1 76,3 75,6 77,6 79,4 Sound power level [Lw] (5) db(a) 87,1 88,7 92,9 92,1 94,2 96,0 PUMPING GROUP Pump for chilled water 1 centrifugal pump 2 poles motor D PPF-AR MUL 1/1 1/1 1/1 1/1 1/1 1/1 2 centrifugal pumps 2 poles motor D PPF-AR MUL 1/2(*) 1/2(*) 1/2(*) 1/2(*) 1/2(*) 1/2(*) Pump for hot water 1 centrifugal pump 2 poles motor D PPF-AC MUL 1/1(*) 1/1(*) 1/1(*) 1/1(*) 1/1(*) 1/1(*) 2 centrifugal pumps 2 poles motor D PPF-AC MUL 1/2(*) 1/2(*) 1/2(*) 1/2(*) 1/2(*) 1/2(*) Chilled water tank l Chilled and hot water tanks ll DIMENSIONS Length mm Width mm Height mm NET WEIGHT kg HYDRAULIC CONNECTIONS PLANT CHILLED AND HOT WATER Inlet / Outlet (ISO 7/1 - R) Ø 1 1/2" 1 1/2" 1 1/2" 1 1/2" 1 1/2" 1 1/2" Inlet / Outlet Flexible joint - OD Ø mm CONDENSATE DISCHARGE Inlet / Outlet (ISO 7/1 - R) Ø 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 1. Gross value - Referred to chilled water temperature 12/7 C; 35 C ambient temperature. 2. Gross value - Referred to hot water temperature 40/45 C; 7 C ambient temperature. 3. Gross value - Referred to chilled water outlet temperature 7 C; hot water outlet temperature 45 C. 4. Average sound pressure level [Lp] 1m far according to ISO EN Sound power level [Lw] according to ISO EN (*) Pumping group provided as separate kit. Contact RC GROUP Commercial Office. 12 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

13 TECHNICAL DATA MODEL 53 P1 55 P2 62 P2 67 P1 71 P2 85 P2 S S S S S S SIZE C2 C2 C2 C2 C2 C3 COOLING ONLY (1) COOLING CAPACITY kw 53,9 56,9 63,9 67,8 72,1 85,8 Compressors power input kw 16,2 16,7 19,1 20,7 21,6 24,8 Compressors operating current [OA] A 28,2 30,8 33,9 35,3 39,0 47,0 Evaporator water flow rate m³/h 9,3 9,8 11,0 11,7 12,4 14,8 Evaporator pressure drop kpa HEATING ONLY (2) HEATING CAPACITY kw 56,6 59,7 67,1 70,9 75,5 90,0 Compressors power input kw 15,2 16,3 18,4 19,3 20,2 23,7 Compressors operating current [OA] A 26,9 30,2 32,8 33,6 36,9 45,3 Condenser water flow rate m³/h 9,8 10,4 11,7 11,8 13,1 15,6 Condenser pressure drop kpa COOLING + HEATING (3) COOLING CAPACITY kw 55,5 58,2 65,7 69,7 75,0 88,5 HEATING CAPACITY kw 71,2 74,6 84,2 89,4 95,6 112,0 Compressors power input kw 15,7 16,4 18,5 19,8 20,6 24,0 Compressors operating current [OA] A 27,4 30,3 33,0 34,1 37,5 45,7 COMPRESSORS Quantity n Maximum current A Starting current A Capacity steps EVAPORATOR n Water volume l 4,2 4,8 5,7 4,2 5,5 6,3 Max water flow rate m³/h 11,4 13,4 14,4 11,8 15,3 18,2 CONDENSER n Water volume l 4,2 4,8 5,7 4,2 5,5 6,3 Max water flow rate m³/h 13,8 16,2 17,2 14,4 18,3 21,8 CENTRIFUGAL FANS n Total air flow m³/h External static pressure Pa Max external static pressure Pa Power input kw 2,0 2,0 2,2 2,3 2,9 2,7 Plate current [FLA] A 8,6 9,8 8,4 8,4 8,4 14,7 REFRIGERANT Total refrigerant charge (optional excluded) kg R410A R410A R410A R410A R410A R410A Gas circuits n POWER SUPPLY V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 ENERGY EFFICIENCY INDEXES EER Energy Efficiency Ratio kw/kw 2,96 3,04 3,01 2,95 2,94 3,12 COP Coefficient of performance kw/kw 3,29 3,26 3,27 3,28 3,27 3,41 ESEER - Eurovent Standard 3,51 3,85 3,69 3,70 3,61 3,94 IPLV - ARI Standard 550/590 3,89 4,35 4,09 4,08 4,00 4,37 SOUND LEVEL Average sound pressure level [LPm] (4) db(a) 77,6 69,6 79,5 75,9 72,0 76,0 Sound power level [Lw] (5) db(a) 94,8 86,8 96,7 93,1 89,2 93,9 PUMPING GROUP Pump for chilled water 1 centrifugal pump 2 poles motor D PPF-AR MUL 2/1 2/1 2/1 2/1 2/1 3/1 2 centrifugal pumps 2 poles motor D PPF-AR MUL 2/2(*) 2/2(*) 2/2(*) 2/2(*) 2/2(*) 3/2(*) Pump for hot water 1 centrifugal pump 2 poles motor D PPF-AC MUL 2/1(*) 2/1(*) 2/1(*) 2/1(*) 2/1(*) 3/1(*) 2 centrifugal pumps 2 poles motor D PPF-AC MUL 2/2(*) 2/2(*) 2/2(*) 2/2(*) 2/2(*) 3/2(*) Chilled water tank l Chilled and hot water tanks ll DIMENSIONS Length mm Width mm Height mm NET WEIGHT kg HYDRAULIC CONNECTIONS PLANT CHILLED AND HOT WATER Inlet / Outlet (ISO 7/1 - R) Ø 2" 2" 2" 2" 2" - Inlet / Outlet Flexible joint - OD Ø mm ,0 CONDENSATE DISCHARGE Inlet / Outlet (ISO 7/1 - R) Ø 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 1. Gross value - Referred to chilled water temperature 12/7 C; 35 C ambient temperature. 2. Gross value - Referred to hot water temperature 40/45 C; 7 C ambient temperature. 3. Gross value - Referred to chilled water outlet temperature 7 C; hot water outlet temperature 45 C. 4. Average sound pressure level [LPm] 1m far according to ISO EN Sound power level [Lw] according to ISO EN (*) Pumping group provided as separate kit. Contact RC GROUP Commercial Office. RC GROUP S.p.A. T_MLTPF_0413_GB R410A 13

14 TECHNICAL DATA MODEL 107 P2 135 P2 170 P2 195 P2 220 P2 S S S S S SIZE C3 C4 C4 C4 C5 COOLING ONLY (1) COOLING CAPACITY kw 109,0 134,0 175,0 194,0 222,0 Compressors power input kw 31,9 41,1 51,8 60,6 65,4 Compressors operating current [OA] A 55,6 70,3 88,5 103,0 112,0 Evaporator water flow rate m³/h 18,7 23,1 30,1 33,4 38,2 Evaporator pressure drop kpa HEATING ONLY (2) HEATING CAPACITY kw 114,0 143,0 185,0 208,0 236,0 Compressors power input kw 30,5 38,6 49,1 55,2 61,8 Compressors operating current [OA] A 53,8 67,1 84,7 95,6 107,0 Condenser water flow rate m³/h 19,8 24,8 32,1 36,1 41,0 Condenser pressure drop kpa COOLING + HEATING (3) COOLING CAPACITY kw 111,0 139,0 180,0 204,0 229,0 HEATING CAPACITY kw 142,0 179,0 231,0 261,0 293,0 Compressors power input kw 31,3 39,5 50,3 56,7 63,2 Compressors operating current [OA] A 54,8 68,3 86,3 97,7 109,0 COMPRESSORS Quantity n Maximum current A Starting current A Capacity steps EVAPORATOR n Water volume l 8,4 10,5 14, Max water flow rate m³/h 23,0 28,6 37,0 41,0 47,0 CONDENSER n Water volume l 8,4 10,5 14,7 14,0 16,0 Max water flow rate m³/h 27,5 34,5 44,6 49,8 56,7 CENTRIFUGAL FANS n Total air flow m³/h External static pressure Pa Max external static pressure Pa Power input kw 5,0 3,6 7,6 8,5 8,2 Plate current [FLA] A 14,7 16,8 16,8 16,8 21,0 REFRIGERANT Total refrigerant charge (optional excluded) kg R410A R410A R410A R410A R410A Gas circuits n POWER SUPPLY V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 ENERGY EFFICIENCY INDEXES EER Energy Efficiency Ratio kw/kw 2,96 3,00 2,94 2,81 3,02 COP Coefficient of performance kw/kw 3,22 3,39 3,26 3,27 3,37 ESEER - Eurovent Standard 3,47 3,97 3,49 3,38 3,69 IPLV - ARI Standard 550/590 3,85 4,40 3,87 3,75 4,09 SOUND LEVEL Average sound pressure level [LPm] (4) db(a) 80,8 74,0 77,3 78,0 77,3 Sound power level [Lw] (5) db(a) 98,7 92,6 95,9 96,6 96,6 PUMPING GROUP Pump for chilled water 1 centrifugal pump 2 poles motor D PPF-AR MUL 3/1 4/1 4/1 4/1 5/1 2 centrifugal pumps 2 poles motor D PPF-AR MUL 3/2(*) 4/2 4/2 4/2 5/2 Pump for hot water 1 centrifugal pump 2 poles motor D PPF-AC MUL 3/1(*) 4/1 4/1 4/1 5/1 2 centrifugal pumps 2 poles motor D PPF-AC MUL 3/2(*) 4/2 4/2 4/2 5/2 Chilled water tank l Chilled and hot water tanks ll DIMENSIONS Length mm Width mm Height mm NET WEIGHT kg HYDRAULIC CONNECTIONS PLANT CHILLED AND HOT WATER Inlet / Outlet (ISO 7/1 - R) Ø Inlet / Outlet Flexible joint - OD Ø mm 73,0 88,9 88,9 88,9 88,9 CONDENSATE DISCHARGE Inlet / Outlet (ISO 7/1 - R) Ø 3/4" 3/4" 3/4" 3/4" 3/4" 1. Gross value - Referred to chilled water temperature 12/7 C; 35 C ambient temperature. 2. Gross value - Referred to hot water temperature 40/45 C; 7 C ambient temperature. 3. Gross value - Referred to chilled water outlet temperature 7 C; hot water outlet temperature 45 C. 4. Average sound pressure level [LPm] 1m far according to ISO EN Sound power level [Lw] according to ISO EN (*) Pumping group provided as separate kit. Contact RC GROUP Commercial Office. 14 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

15 ACOUSTIC DATA MODEL 22 P1 24 P1 28 P1 32 P1 36 P1 42 P1 53 P1 55 P2 62 P2 S S S S S S S S S SIZE C1 C1 C1 C1 C1 C1 C2 C2 C2 Sound power level [Lw] (1) db(a) 87,1 88,7 92,9 92,1 94,2 96,0 94,8 86,8 96,7 Average sound pressure level [LPm] at 1m (2) db(a) 70,6 72,1 76,3 75,6 77,6 79,4 77,6 69,6 79,5 [LPm] at 5m (2) db(a) 60,8 62,4 66,5 65,8 67,8 69,7 68,3 60,3 70,1 [LPm] at 10m (2) db(a) 55,5 57,1 61,2 60,5 62,5 64,4 63,1 55,1 65,0 MODEL 67 P1 71 P2 85 P2 107 P2 135 P2 170 P2 195 P2 220 P2 S S S S S S S S SIZE C2 C2 C3 C3 C4 C4 C4 C5 Sound power level [Lw] (1) db(a) 93,1 89,2 93,9 98,7 92,6 95,9 96,6 96,6 Average sound pressure level [LPm] at 1m (2) db(a) 75,9 72,0 76,0 80,8 74,0 77,3 78,0 77,3 [LPm] at 5m (2) db(a) 66,6 62,6 67,1 71,9 65,5 68,9 69,5 69,3 [LPm] at 10m (2) db(a) 61,4 57,5 62,0 66,8 60,6 63,9 64,6 64,4 1. Sound power level [Lw] according to ISO EN Average sound pressure level [LPm] according to ISO EN 3744 IMPORTANT For further information about units acoustic data, please refer to The Noise bulletin of RC GROUP technical literature. RC GROUP S.p.A. T_MLTPF_0413_GB R410A 15

16 ELECTRIC DATA MAXIMUM ELECTRIC ABSORPTION CALCULATION [FLA] This chapter is showing the maximum electrical absorption calculation of unit (A), corresponding to extreme working conditions. The involved components are the following: - Compressors electric motor - Condensers fans electric motors - Water pump electric motor (if present) The electrical data of the various components are indicated in the relative technical data sheets. EXAMPLE 1: Calculation for MULTIPLO PF 55 P2 S C2: MAXIMUM ELECTRIC ABSORPTION [FLA] - Compressors A 50,0 + - Condenser fans A 9,8 = Maximum electric absorption A 59,8 EXAMPLE 2: Calculation for MULTIPLO PF 55 P2 S C2 equipped with PPF UNI 1/1 pumping group: MAXIMUM ELECTRIC ABSORPTION [FLA] - Compressors A 50,0 + - Condenser fans A 9,8 = - Water pump A 3,5 = Maximum electric absorption A 63,3 16 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

17 MP.COM: MICROPROCESSOR CONTROL SYSTEM The MP.COM microprocessor control system is equipped with 8 keys terminal and back lighted graphic display on which all information in different languages or easily identifiable symbols are displayed. The system disposes of a flash memory that preserves the information even in absence of power supply. KEYBOARD FUNCTIONS KEY 1 KEY 2 KEY 3 KEY 4 KEY 5 KEY 6 KEY 7 KEY 8 Switches on/off the unit. Stops the alarm acoustical signal and displays the intervened alarm. Accedes to the parameters of possible units connected in LAN network. LAN connection with 3 wires without additional accessories. It is possible to connect in network different capacity units and with different number of compressors. Home key displays the main screen. Accedes to control and visualization menus as: - Unit working status - Set-points - Alarms reset (protected by password) - Service parameters setting (protected by password) - Intervened alarms history - Setting for main components manual operation (protected by password) - Date and time setting - Setting of communication system for SMS messages dispatch Scroll the pages inside each menu and decreases the displayed value Scroll the pages inside each menu and increases the displayed value Shift the cursor inside each menu and confirm a parameter insertion REMOTE CONTROLS/ALARMS INLETS 1 External enabling 2 Cooling set-point changing 3 Cooling enabling 4 Heating enabling 5 Set-point compensation OUTLETS 1 General alarm 1 deviating contact 2 General alarm 2 remote controls/alarms voltage free controls/alarms IMPORTANT To obtain more information, please refer to the software catalogue of the unit. RC GROUP S.p.A. T_MLTPF_0413_GB R410A 17

18 IDEA : DYNAMIC CONTROL SYSTEM OF DEFROSTING CYCLES RC GROUP PATENTED the dynamic control system of defrosting cycles which is called IDEA (Intelligent Defrosting system for Energy-saving Applications). Unlike the traditional defrosting systems (fixed time or pressostatic at static reading), IDEA is able to identify the actual ice presence on the evaporating coil in order to start the defrosting cycle only when it is necessary. This allows an yearly energy saving ranging from 15% to 20%. Moreover, the system is totally automatic, it does not demand the introduction of any limit control parameter and it conforms to all climatic conditions. The advantages of the dynamic system can be easily summarised. First of all, the heat pump starts defrosting cycles only when they are really necessary. In this way undesired defrosting cycles are avoided and the temporal sequence is optimized, reducing or increasing it according to the thermo-hygrometric conditions of the outdoor air. Another system s advantage is that it does not demand human intervention. The other systems demand the definition of limit values: as everyone knows, not always those who handle a chillers have the necessary skill to do it, therefore they can often make serious planning mistakes or they can tamper with the system while it is working. Moreover, during plant working, the conditions of the evaporating coil can change because of the dirt which has formed: IDEA dynamic system is able to conform to the changing conditions. The IDEA system does not demand any human intervention because it is only based on the dynamic reading of working parameters, which are absolutely objective data that are not subject to mistakes. In short, the advantages are the following: the optimized heat pump working the optimized plant working the yearly working saving which ranges between 15% and 20%. the total absence of planning mistakes the reduced compressor wear, therefore an higher duration of the heat pump 18 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

19 OPTIONAL ACCESSORIES PUMPING GROUP Factory assembled pumping group that doesn't modify the machine dimensions. When indicated the optional accessories is provide as separate kit. In the chillers technical data tables are showed the pumping group type for each machine. The system includes: SINGLE PUMP VERSION: /1-AR-MUL Chilled water; /1-AC-MUL Hot water Pumping group with one in-line pump: Control and working electric equipment built in the water chiller electric board and directly managed by the microprocessor control. Pump with 2 poles electric motor (PPF MUL series). Insulated piping. Expansion tank. Safety valve. Safety flow switch. Pressure gauge on water suction and discharge. Valve for water filling/discharge. TWO PUMPS VERSION: /2-AR-MUL Chilled water; /2-AC-MUL Hot water Pumping group with twin head in-line pumps. Control and working electric equipment built in the water chiller electric board and directly managed by the microprocessor control. Pump with 2 poles electric motor (PPF MUL model). Insulated piping. Expansion tank. Safety valve. Safety flow switch. Pressure gauge on water suction and discharge. Valve for water filling/discharge. One pump is working and the other is in stand-by. Automatic changeover in case of failure. PUMPING GROUP D-PPF.../1-AR-MUL D-PPF /1-AC-MUL D-PPF.../2-AR-MUL D-PPF /2-AC-MUL VE YS MA RU P FL MA RU VE YS MA RU P FL MA RU RC RC RC Valve for water filling / discharge VE Expansion tank YS Safety valve RU Service valve MA Pressure gauge P Water pump FL Water flow switch RC GROUP S.p.A. T_MLTPF_0413_GB R410A 19

20 OPTIONAL ACCESSORIES PUMPING GROUP TECHNICAL DATA PUMPING GROUP FOR CHILLED WATER 2 POLES ELECTRIC MOTOR SINGLE PUMP MODEL MODEL D-PPF -AR-MUL 1/1 2/1 3/1 4/1 5/1 WATER FLOW RATE Minimum water flow rate m 3 /h Maximum water flow rate m 3 /h DISCHARGE HEAD At minimum water flow kpa At maximum water flow kpa WATER PUMP (1) Plate power input kw 0,75 1,5 2,2 2,2 2,2 Plate current [FLA] A 1,9 3,5 4,6 4,6 4,6 WEIGHT (2) Empty weight kg 31,5 34,5 55,0 66,0 66,0 POWER SUPPLY V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 2 POLES ELECTRIC MOTOR TWIN PUMP MODEL MODEL D-PPF -AR-MUL 1/2 (*) 2/2 (*) 3/2 (*) 4/2 5/2 WATER FLOW RATE Minimum water flow rate m 3 /h Maximum water flow rate m 3 /h DISCHARGE HEAD At minimum water flow kpa At maximum water flow kpa WATER PUMP (1) Plate power input kw 0,75 1,5 2,2 3,0 3,0 Plate current [FLA] A 1,9 3,5 4,6 6,1 6,1 WEIGHT (2) Empty weight kg 59,0 65,0 104, POWER SUPPLY V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 TECHNICAL DATA PUMPING GROUP FOR HOT WATER 2 POLES ELECTRIC MOTOR SINGLE PUMP MODEL MODEL D-PPF -AC-MUL 1/1 (*) 2/1 (*) 3/1 (*) 4/1 5/1 WATER FLOW RATE Minimum water flow rate m 3 /h Maximum water flow rate m 3 /h DISCHARGE HEAD At minimum water flow kpa At maximum water flow kpa WATER PUMP (1) Plate power input kw 0,75 1,5 2,2 3,0 4,0 Plate current [FLA] A 1,9 3,5 4,6 6,1 7,8 WEIGHT (2) Empty weight kg 31,5 34,5 55,0 68,0 66,0 POWER SUPPLY V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 2 POLES ELECTRIC MOTOR TWIN PUMP MODEL MODEL D-PPF -AC-MUL 1/2 (*) 2/2 (*) 3/2 (*) 4/2 5/2 WATER FLOW RATE Minimum water flow rate m 3 /h Maximum water flow rate m 3 /h DISCHARGE HEAD At minimum water flow kpa At maximum water flow kpa WATER PUMP (1) Plate power input kw 0,75 1,5 2,2 3,0 4,0 Plate current [FLA] A 1,9 3,5 4,6 6,1 7,8 WEIGHT (2) Empty weight kg 59,0 65,0 104, POWER SUPPLY V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 1 The given value is referred to the working pump only. 2 Add this value to the chiller weight. (*) Provided in kit. Contact RC GROUP Commercial Office. WARNING: The noise generated by the pumps does not increase the chiller overall noise pressure level. 20 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

21 Discharge head (kpa) Discharge head (kpa) OPTIONAL ACCESSORIES PUMPING GROUP PUMP PERFORMANCE MODELS WITH SINGLE PUMP Discharge head (kpa) Discharge head (kpa) D-PPF1/1-AR-MUL, D-PPF1/1-AC-MUL D-PPF2/1-AR-MUL, D-PPF2/1-AC-MUL Water flow (m 3 /h) D-PPF3/1-AR-MUL, D-PPF3/1-AC-MUL Discharge head (kpa) Discharge head (kpa) Water flow (m 3 /h) D-PPF4/1-AR-MUL, D-PPF5/1-AR-MUL Water flow (m 3 /h) Water flow (m 3 /h) D-PPF4/1-AC-MUL D-PPF5/1-AC-MUL Water flow (m 3 /h) Water flow (m 3 /h) The graph is referred to performances values of the pump. To obtain the pressure available for the plant, deduct the pressure drop of the relative heat exchanger as indicated in unit technical data. RC GROUP S.p.A. T_MLTPF_0413_GB R410A 21

22 Discharge head (kpa) Discharge head (kpa) Discharge head (kpa) Discharge head (kpa) Discharge head (kpa) Discharge head (kpa) OPTIONAL ACCESSORIES PUMPING GROUP PUMP PERFORMANCE MODELS WITH TWIN HEAD PUMP D-PPF1/2-AR-MUL, D-PPF1/2-AC-MUL D-PPF2/2-AR-MUL, D-PPF2/2-AC-MUL Water flow (m 3 /h) Water flow (m 3 /h) D-PPF3/2-AR-MUL, D-PPF3/2-AC-MUL D-PPF4/2-AR-MUL, D-PPF4/2-AC-MUL Water flow (m 3 /h) Water flow (m 3 /h) D-PPF5/2-AR-MUL D-PPF5/2-AC-MUL Water flow (m 3 /h) Water flow (m 3 /h) The graph is referred to performances values of the pump. To obtain the pressure available for the plant, deduct the pressure drop of the relative heat exchanger as indicated in unit technical data. 22 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

23 OPTIONAL ACCESSORIES - WATER TANKS The tank or the tanks are supplied assembled under the unit, ready to work. In the chiller technical data sheet are showed the tank type for each unit. Each tank includes: Base and self supporting frame in steel plate with protective surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with epoxy powders. Colour: RAL water tanks with anticondensate insulation. Antifreeze heater Piping with anticondensate insulation for connection with the machine. MODEL C1 C2 C3 C4 C5 Water volume l Empty weight (1) kg Chilled water / hot water hydraulic connections Inlet/outlet (ISO 7/1 R) Ø 1 1/2" Inlet/outlet Flexible joint DN Water discharge (ISO 7/1-R) Ø 1/2 1/2 1/2 1/2 1/2 Air vent (ISO 7/1-R) Ø 1/2 1/2 1/2 1/2 1/2 (1) Add this value to the machine weight, single tank weight. CHILLED WATER TANK Chilled water tank Chilled water tank HOT WATER TANK Hot water tank Hot water tank 1. Chilled water inlet. 2. Chilled water outlet.. 3. Hot water inlet. 4. Hot water outlet. 5. Water tank water charge. 6. Water tank air discharge. RC GROUP S.p.A. T_MLTPF_0413_GB R410A 23

24 CHILLED WATER TANK + HOT WATER TANK Hot water tank Hot water tank Chilled water tank Chilled water tank 1. Chilled water inlet. 2. Chilled water outlet.. 3. Hot water inlet. 4. Hot water outlet. 5. Water tank water charge. 6. Water tank air discharge. IMPORTANT To obtain more information about the hydraulic connection of the units, please refer to the technical drawings. 24 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

25 OPTIONAL ACCESSORIES SILENCING PLENUM ON CONDENSER AIR DISCHARGE The plenum is supplied as separate accessory for installation on site. The system includes: Aluminium profile frame jointed with reinforced PVC corners. Panelling in steel plate with protective surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with epoxy powders. Colour: RAL 9002 Noise absorption partitions. The plenum is supplied with built-in weatherproof noise absorption partitions allowing outdoor installation. Air discharge on the upper side of the machine (vertical air discharge) Predisposition for an eventual air duct connection The use of the silencing plenum allows to reach a level of sound pressure 1m far on fans air discharge side equal to the chiller average sound pressure level reduced of 3dB(A). The silencing plenum doesn t modify the declared average noise level. SIZE C1 C2 C3 C4 C5 Weight kg SILENCING PLENUM ON CONDENSER AIR DISCHARGE A. EXAMPLE 1: Calculation for MULTIPLO PF 55 P2 S C2: Sound pressure level [Lp] 1m far according to ISO EN 3744= 69,6 db(a) Sound pressure level [Lp] 1m far, fans air discharge side (A.) = 69,6-3=66,6 db(a) RC GROUP S.p.A. T_MLTPF_0413_GB R410A 25

26 OPTIONAL ACCESSORIES KIT FOR OUTDOOR INSTALLATION For outdoor installation the use of the dedicated optional kit is mandatory. The machine must be installed under a cover or anyway protected against atmospherics agent. The dimensions of the cover must consider the possibility of transversal rain, characterized by an higher inclination of the rainfall caused by the wind. Only the installations with horizontal air discharge flow are permitted without ducting. To avoid air recirculation, ducting is suggested for horizontal air discharge on coil side. OUTDOOR INSTALLATION HORIZONTAL AIR DISCHARGE Cover Possible presence of a wall or an obstruction to the air flow Net Ducting (air discharge) (not supplied) 26 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

27 In case of vertical air discharge, ducting is mandatory. OUTDOOR INSTALLATION VERTICAL AIR DISCHARGE Cover Ducting (air discharge) (not supplied) Net Possible presence of a wall or an obstruction to the air flow WARNING: Plug fan must be protected from direct rain and atmospherics agents. RC GROUP S.p.A. T_MLTPF_0413_GB R410A 27

28 UNIT DRAWINGS Dimensions in mm MULTIPLO PF C1 28 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

29 UNIT DRAWINGS Dimensions in mm MULTIPLO PF C2 RC GROUP S.p.A. T_MLTPF_0413_GB R410A 29

30 UNIT DRAWINGS Dimensions in mm MULTIPLO PF C3 30 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

31 UNIT DRAWINGS Dimensions in mm MULTIPLO PF C4 RC GROUP S.p.A. T_MLTPF_0413_GB R410A 31

32 UNIT DRAWINGS Dimensions in mm MULTIPLO PF C5 32 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

33 RC GROUP S.p.A. T_MLTPF_0413_GB R410A 33

34 34 RC GROUP S.p.A. T_MLTPF_0413_GB R410A

35 RC GROUP S.p.A. T_MLTPF_0413_GB R410A 35

36 The continuous improvement of products may imply changes in the data shown in this catalogue. RC GROUP S.p.A. Via Roma, Valle Salimbene (PV), Italy Tel. +39 (0) Fax +39 (0) T_MLTPF _0413_GB RC Group S.p.A. is a company of

kw COOLING kw HEATING

kw COOLING kw HEATING Heat pump water/water liquid chillers for indoor installation. Inversion on hydraulic circuit. 394 1505 kw COOLING 477 1976 kw HEATING technicalcatalogue T_FRGSCRWP_0913_GB INDEX GENERAL CHARACTERISTICS...

More information

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw Multifunction chillers for indoor installation. Cooling Capacity: 22 222 Heating Capacity: 25 236 Scroll compressors EC Plug Fans Plate type heat exchangers EER up to 3,12 COP up to 3,84 ESEER up to 4,01

More information

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB Packaged air cooled liquid chillers for outdoor installation 42 574 kw technicalcatalogue T_EGL_1012_GB INDEX EUROVENT CERTIFICATION... 3 GENERAL CHARACTERISTICS... 3 SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION...

More information

44,9 202,0 kw. technicalcatalogue

44,9 202,0 kw. technicalcatalogue Packaged air cooled liquid chillers for outdoor installation equipped with scroll compressor and microchannel condensing coils 44,9 202,0 kw technicalcatalogue T_PYXU_0413_GB INDEX EUROVENT CERTIFICATION...

More information

kw. technicalcatalogue

kw. technicalcatalogue Packaged air cooled liquid chillers in A class energy efficiency for outdoor installation equipped with scroll compressor and microchannel condensing coils 108 876 kw technicalcatalogue T_PYXCLA_0413_GB

More information

EQUH PF PACKAGED HEAT PUMP AIR/ WATER LIQUID CHILLER FOR INDOOR INSTALLATION

EQUH PF PACKAGED HEAT PUMP AIR/ WATER LIQUID CHILLER FOR INDOOR INSTALLATION TECHNICAL CATALOGE EQUH PF PACKAGED HEAT PUMP AIR/ WATER LIQUID CHILLER FOR INDOOR INSTALLATION Cooling capacity 19,1 to 225 kw Heating capacity 23,7 to 324 kw Thank you for trust in Hitecsa Product. From

More information

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB T_SMT_0609_GB 4,9 49,5 kw Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans INDEX SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3 CE CONFORMITY... 3 WORKING

More information

unico pf unico pf rcgroupairconditioning

unico pf unico pf rcgroupairconditioning : ckaged air cooled liquid chillers for indoor installation, equipped with scroll compressors and plug fan Cooling Capacity: 19,6 264 unico pf PLTE rcgroupairconditioning R410 E C MIN FETURES ir cooled

More information

EQEF TECHNICAL CATALOGUE AIR COOLED WATER CHILLERS AXIAL FANS WITH FREE-COOLING SYSTEM

EQEF TECHNICAL CATALOGUE AIR COOLED WATER CHILLERS AXIAL FANS WITH FREE-COOLING SYSTEM TECHNICAL CATALOGUE EQEF Water Chillers with Free Cooling System Models:60.1 60.2 70.1 70.2 90.1 90.2 120.1 120.2 135.1 150.1 190.2 200.1 200.2 240.2 270.2 300.2 Cooling capacities: 69,7 to 331 KW 02.16

More information

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB R407C EASY_R Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans 5,2 41,5 kw T_ESY_R_0508_GB EASY_R R407C INDEX WORKING LIMITS... 3 SERIES IDENTIFICATION... 4 MODEL

More information

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB Next P 6 112 kw COOLING 5 93 kw HEATING Heat pump air conditioners with upflow air delivery technicalcatalogue T_NXTP_0411_GB INDEX GENERAL CHARACTERISTICS... 3 SERIES IDENTIFICATION... 4 MODEL IDENTIFICATION...

More information

pyxis hp "u" pyxis hp "u" IDEA NEW rcgroupairconditioning

pyxis hp u pyxis hp u IDEA NEW rcgroupairconditioning Comfort PYXIS HP U : ir / water reversible heat pumps for outdoor installation, equipped with scroll compressors and axial fans Cooling Capacity: 42,3 195,0 Heating Capacity: 47,1 222,0 NEW IDE R410 rcgroupairconditioning

More information

kw. technicalcatalogue

kw. technicalcatalogue Packaged air cooled liquid chillers for outdoor installation equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded evaporator and microchannel condensing coils. 280

More information

EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW

EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW TECHNICAL CATALOGUE EQSL Air Cooled Water Chillers Models: 300 V2 F06 1310 V2 F16 Cooling capacity: 299 to 1310 KW 02.16 ref. 207598 Rev.100 Thank you for trusting in Hitecsa Products. Our company has

More information

pyxis u pyxis ua NEW rcgroupairconditioning

pyxis u pyxis ua NEW rcgroupairconditioning Industrial : Packaged air cooled liquid chillers for outdoor installation equipped with scroll compressors and microchannel condensing coils Cooling capacity: 44,9 200,0 rcgroupairconditioning R410 C PLTE

More information

Next MTR kw. technicalcatalogue. Air conditioners for Metrology Labs with upflow air delivery T_NXTMTR_0511_GB

Next MTR kw. technicalcatalogue. Air conditioners for Metrology Labs with upflow air delivery T_NXTMTR_0511_GB 6 15 kw Next MTR Air conditioners for Metrology Labs with upflow air delivery technicalcatalogue T_NXTMTR_0511_GB INDEX GENERAL CHARACTERISTICS... 3 SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3

More information

4,5 22,5 kw. technicalcatalogue. Air-conditioned server-racks for direct installation into the room T_CLSEVO_0113_GB

4,5 22,5 kw. technicalcatalogue. Air-conditioned server-racks for direct installation into the room T_CLSEVO_0113_GB 4,5 22,5 kw Air-conditioned server-racks for direct installation into the room technicalcatalogue T_CLSEVO_0113_GB INDEX HIGHLIGHTS... 3 PLANT TYPE... 3 GENERAL CHARACTERISTICS... 5 SERIES IDENTIFICATION...

More information

GLIDER EVO FREE GLIDER EVO FREE GLYCOL FREECOOLING. rcgroupairconditioning

GLIDER EVO FREE GLIDER EVO FREE GLYCOL FREECOOLING. rcgroupairconditioning : Packaged air cooled liquid chillers with free-cooling system for outdoor installation, equipped with screw compressors and axial fans Cooling Capacity: 314 1343 Free-Cooling Capacity: 308 938 GLYCOL

More information

nemo a hp rcgroupairconditioning R410A

nemo a hp rcgroupairconditioning R410A NEMO A HP: Motoevaporating heat pumps for indoor installation, equipped with scroll compressor and plate heat exchanger Cooling Capacity: 5,5 25,0 Heating Capacity: 6,4 29,3 nemo a hp PLATE rcgroupairconditioning

More information

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning : Direct expansion close control air conditioners with up-flow or down-flow air delivery. Cooling Capacity: 7 102 NEW SOFTWARE R410A rcgroupairconditioning E C A C UP FLOW DOWN FLOW MAIN FEATURES Precision

More information

NEMO A Split-system liquid chillers for indoor installation. Cooling Capacity: 5 26 kw

NEMO A Split-system liquid chillers for indoor installation. Cooling Capacity: 5 26 kw Split-system liquid chillers for indoor installation. Cooling Capacity: 5 26 Built-in pumping group Scroll compressor Plate type heat exchanger EER up to 2,88 rcgroup.it Chillers : Motoevaporating units

More information

FRIGO SCREW CLA PLUS Packaged water cooled liquid chillers in A+ class energy efficiency for indoor installation. Cooling Capacity: kw

FRIGO SCREW CLA PLUS Packaged water cooled liquid chillers in A+ class energy efficiency for indoor installation. Cooling Capacity: kw Packaged water cooled liquid chillers in + class energy efficiency for indoor installation. Cooling Capacity: 625 1179 kw Screw compressors Shell and tube heat exchangers Double refrigerant circuit EER

More information

COOLROW Close control air conditioners for In-Row installation Cooling Capacity: kw

COOLROW Close control air conditioners for In-Row installation Cooling Capacity: kw COOLROW Close control air conditioners for In-Row installation Cooling Capacity: 14 61 Available in versions equipped with: - BLDC inverter scroll compressor on board of the unit - Chilled water feeding

More information

GLIDER EVO GLIDER EVO. rcgroupairconditioning

GLIDER EVO GLIDER EVO. rcgroupairconditioning : Packaged air cooled liquid chillers for outdoor installation equipped with screw compressors and axial fans Cooling Capacity: 300 1313 rcgroupairconditioning R134a SHELL C MIN FETURES ir cooled liquid

More information

EQPHU PACKAGED HEAT PUMP AIR/ WATER LIQUID CHILLER FOR OUTDOOR INSTALLATION

EQPHU PACKAGED HEAT PUMP AIR/ WATER LIQUID CHILLER FOR OUTDOOR INSTALLATION TECHNICAL CATALOGE EQPHU PACKAGED HEAT PUMP AIR/ WATER LIQUID CHILLER FOR OUTDOOR INSTALLATION Cooling capacity 197 to 267 kw Heating capacity 219 to 301 kw 03.16 207622 Rev100 Thank you for trust in Hitecsa

More information

glider evo cla glider evo cla A-CLASS rcgroupairconditioning

glider evo cla glider evo cla A-CLASS rcgroupairconditioning Industrial GLIDER EVO CL: Packaged air cooled liquid chillers in class energy efficiency for outdoor installation, equipped with screw compressors and axial fans Cooling Capacity: 284 1513 -CLSS rcgroupairconditioning

More information

pyxis pyxisa NEW rcgroupairconditioning

pyxis pyxisa NEW rcgroupairconditioning Industrial : Packaged air cooled liquid chillers for outdoor installation equipped with scroll compressors and microchannel condensing coils Cooling capacity: 119,0 808,0 PLTE C rcgroupairconditioning

More information

PYXIS U PYXIS U. rcgroupairconditioning

PYXIS U PYXIS U. rcgroupairconditioning Industrial : Packaged air cooled liquid chillers for outdoor installation equipped with scroll compressors and microchannel condensing coils Cooling capacity: 44 284 rcgroupairconditioning MIN FETURES

More information

GLIDER EVO CLA GLIDER EVO CLA HIGHEFFICIENCY ACLASS. rcgroupairconditioning

GLIDER EVO CLA GLIDER EVO CLA HIGHEFFICIENCY ACLASS. rcgroupairconditioning GLIDER EVO CL GLIDER EVO CL: Packaged air cooled liquid chillers in class energy efficiency for outdoor installation, equipped with screw compressors and axial fans Cooling Capacity: 282 1513 HIGHEFFICIENCY

More information

pyxis cla pyxis cla A-CLASS NEW rcgroupairconditioning

pyxis cla pyxis cla A-CLASS NEW rcgroupairconditioning Industrial PYXIS CL: Packaged air cooled liquid chillers in class energy efficiency for outdoor installation, equipped with scroll compressor and microchannel condensing coils Cooling Capacity: 108 876

More information

NEXT DL NEXT DL. rcgroupairconditioning

NEXT DL NEXT DL. rcgroupairconditioning NEXT DL: Close control air conditioners with displacement air delivery with remote condenser, or built in water cooled condenser or for chilled water feeding Cooling capacity: 7,7 51,4 NEXT DL rcgroupairconditioning

More information

rcgroup.it Flooded evaporator Low noise Minimum starting current EER up to 5,25 ESEER up to 8,88

rcgroup.it Flooded evaporator Low noise Minimum starting current EER up to 5,25 ESEER up to 8,88 Packaged water cooled liquid chillers in class energy efficiency for indoor installation, equipped with turbo oil-free compressors. Cooling Capacity: 280 1840 Flooded evaporator Low noise Minimum starting

More information

UNICO TURBO FL FREE UNICO TURBO FL FREE HIGHEFFICIENCY INVERTER ACLASS FREECOOLING LOWNOISE. rcgroupairconditioning

UNICO TURBO FL FREE UNICO TURBO FL FREE HIGHEFFICIENCY INVERTER ACLASS FREECOOLING LOWNOISE. rcgroupairconditioning : Packaged air cooled liquid chillers with free-cooling system in class energy efficiency for outdoor installation, equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded

More information

unico turbo FL unico turbo FL LOW NOISE A-CLASS INVERTER rcgroupairconditioning

unico turbo FL unico turbo FL LOW NOISE A-CLASS INVERTER rcgroupairconditioning : Packaged air cooled liquid chillers in class energy efficiency for outdoor installation, equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded evaporator and microchannel

More information

rcgroup.it Flooded evaporator Refrigerant charge HFO1234ze, GWP<1 Low noise Minimum starting current EER up to 5,41 ESEER up to 9,10

rcgroup.it Flooded evaporator Refrigerant charge HFO1234ze, GWP<1 Low noise Minimum starting current EER up to 5,41 ESEER up to 9,10 Packaged water cooled liquid chillers in class energy efficiency for indoor installation, equipped with turbo oil-free compressors. Cooling Capacity: 250 1240 Flooded evaporator Refrigerant charge HFO1234ze,

More information

next p dw next p dw rcgroupairconditioning

next p dw next p dw rcgroupairconditioning NEXT P: Heat pump air conditioners with upflow air delivery with built-in water/gas exhaustion heat exchanger Cooling Capacity: 7,5 7,0 Heating Capacity: 7, 04,0 A C rcgroupairconditioning R40A PLATE E

More information

KELVIN Clim F497. Kelvin air conditioning

KELVIN Clim F497. Kelvin air conditioning KELVIN Clim F497 Cooling Capacity: 400 ~ 1260 kw Free-Cooling Capacity: 497 ~ 1492 kw Packaged air cooled liquid chillers with free-cooling system in A class energy efficiency for outdoor installation,

More information

Kelvin air conditioning. KELVIN Clim W280. Cooling Capacity: 280 ~ 1840 kw

Kelvin air conditioning. KELVIN Clim W280. Cooling Capacity: 280 ~ 1840 kw Cooling Capacity: 280 ~ 1840 kw Water cooled liquid chillers in A class energy efficiency for indoor installation, equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded

More information

frigo turbo FL Chillers

frigo turbo FL Chillers frigo turbo FL FRIGO TURBO FL Packaged water cooled liquid chillers in A class energy efficiency for indoor installation, equipped with oil-free centrifugal compressors with magnetic levitation bearings,

More information

Kelvin air conditioning. KELVIN Clim W250. Cooling Capacity: 250 ~ 1240 kw

Kelvin air conditioning. KELVIN Clim W250. Cooling Capacity: 250 ~ 1240 kw Cooling Capacity: 250 ~ 1240 kw Water cooled liquid chillers in A class energy efficiency for indoor installation, equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 201 C K RAE 482 C K AIR R-407C Series RAE... C K from 19 to 83 kw - 1 and 2 circuits The air cooled chillers of RAE... C K series, with centrifugal fans, are designed for indoor installation and are

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 1402 C O K AIR R-407C Series RAE... C K Cooling capacity from 81 to 250 kw - 2 circuits The air cooled chillers of RAE C K series, with centrifugal fans, are designed for indoor installation and are

More information

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS RAE 1352 F.K + MV AIR R-407C FC Series RAE... F.K Cooling capacity from 77 to 289 kw - 2 circuits The air cooled chillers of RAE... F.K series, are designed for outdoor installation and are particularly

More information

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1 UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS GPE 802 Kc + CF + GP + MV + P1 130 Above picture is only indicative and is not binding. AIR R-410A

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES COOLING CAPACITY FROM 76 TO 612 Kw 1 AND 2 COOLING CIRCUITS RAE 1702 F Kc + P2 28 Above picture is only indicative

More information

next DX.U.S* 052.Z2.H6.DC

next DX.U.S* 052.Z2.H6.DC next DX.U.S* 05.Z.H6.DC GENERAL CHARACTERISTICS Air conditioning unit with remote air cooled condenser, for computer rooms, any high-tech facility and offices. Units can run non-stop at 4x65 hours a year.

More information

i-next DX kw FULL INVERTER direct expansion air conditioners for IT Cooling. To be matched with remote air-cooled condenser. rcitcooling.

i-next DX kw FULL INVERTER direct expansion air conditioners for IT Cooling. To be matched with remote air-cooled condenser. rcitcooling. CLOSE CONTROL AIR CONDITIONERS 3 140 kw FULL INVERTER direct expansion air conditioners for IT Cooling. To be matched with remote air-cooled condenser. The picture of the unit is indicative and may vary

More information

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N E S A RE F R E IG RA N T G TECHNICAL MANUAL -FRIEND Y CONDENSING UNITS FOR OUTDOOR INSTALLATION O L CMA C 2 The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual,

More information

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017 Zeta Rev LN HP 10.2 Configured unit accessories 1PS - One user-side pump with tank LN - Low noise RG - Condensation control with fan speed regulator CSP - Set point compensation depending on external air

More information

Water chillers water/water type SIGMA Technical information manual

Water chillers water/water type SIGMA Technical information manual Water chillers water/water type SIGMA Technical information manual 2 INDEX Technical features 1 Versions 3 Accessory versions 4 Technical data 7 Electrical data 11 Cooling capacity 12 Heating capacity

More information

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points Epsilon Echos+ 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Configuration /LN: Low noise unit /HP: Reversible heat pump /LE /HP: Reversible condensing unit Unique

More information

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION ECO-FRIENDLY REFRIGERANT GAS INSTALLATION AND OPERATION MANUAL Dear Customer, Thank you for having purchased a FERROLI product. It is the result of many years

More information

next NEXT EVO CW kw UP FLOW DOWN FLOW CHILLED WATER E C CLOSE CONTROL AIR CONDITIONERS FOR CHILLED WATER FEEDING,

next NEXT EVO CW kw UP FLOW DOWN FLOW CHILLED WATER E C CLOSE CONTROL AIR CONDITIONERS FOR CHILLED WATER FEEDING, next CLOSE CONTROL AIR CONDITIONERS FOR CHILLED WATER FEEDING, NEXT EVO CW WITH UPFLOW OR DOWNFLOW AIR DELIVERY 6 261 kw CHILLED WATER E C UP FLOW DOWN FLOW 2 next evo cw INTRODUCTION The NEXT EVO CW series

More information

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS RAH 602 Ka + CF + GP 62 Above picture is only indicative and is not binding.

More information

next evo cw next evo cw rcgroupairconditioning

next evo cw next evo cw rcgroupairconditioning : Close control air conditioners for chilled water feeding with upflow or downflow air delivery Cooling Capacity: 6,2 248,0 rcgroupairconditioning E C CHILLED WTER UP FLOW DOWN FLOW MIN FETURES Chilled

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS Energy saving thanks to a total recovery p Cooling Heating/DHW h Galletti multi-purpose heat pumps are total recovery units used for a simultaneous hot and

More information

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 46 Above picture is only indicative and is not binding AIR FC The packaged air cooled chillers of RAS Kp series are suitable

More information

BETA ECHOS. Air/water cooled chillers and heat pumps kw. General BETA ECHOS is a range of chillers and ductable air-water heat pumps.

BETA ECHOS. Air/water cooled chillers and heat pumps kw. General BETA ECHOS is a range of chillers and ductable air-water heat pumps. Air/water cooled chillers and heat pumps 41 303 kw General BETA ECHOS is a range of chillers and ductable air-water heat pumps. Configurations HP: Reversible heat pump LE: For connection to remote evaporator

More information

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw COMFORT CHILLERS AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw climaveneta.com COMFORT CHILLERS PERFECT COMFORT AND MAXIMUM EFFICIENCY Air-cooled liquid chiller for outside installation

More information

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz EN Technical Catalogue Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: 321-1308 kw 50 Hz EKV/BS business Air cooled water chillers for outdoor installation. Flexibility in the

More information

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors infolinia: +48 691 262 691-15 C +63 C +43 C E.V.I. HP The series of high efficiency heat pumps has been specifically designed for use with

More information

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual u Air-to-Water Reverse Cycle Heat Pumps AQH 40 to 130 40 to 131 kw 45 to 141 kw Engineering Data Manual EDM AQH-W.3GB Date : November 2007 Supersedes : TM AQH-W.2GB/03.04 Specifications The Aqu@Logic air-to-water

More information

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw Air cooled chillers with brushless oil-free compressors R-134a RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw External installation with very low sound level Cooling circuit with

More information

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata EKS/HE Refrigerant R410A GWP=2.088 Scroll Compressor Shell & Tube exchanger Axial fan Brazed plate heat exchanger MultiScroll Air-cooled liquid chillers High efficiency Solution B - Base I - Integrata

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

turb new unico turbo frigo turbo fl Liquid chiller equipped with magnetic levitation twostage centrifugal compressors RCGROUP SpA C_GNR_0711

turb new unico turbo frigo turbo fl Liquid chiller equipped with magnetic levitation twostage centrifugal compressors RCGROUP SpA C_GNR_0711 89 TURBO turb Liquid chiller equipped with magnetic levitation twostage unico new frigo fl cooling capacity 260,0 1524,0 kw compressors centrifugal refrigerant R134a fan type axial (UNICO series) microprocessor

More information

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98 Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw Scroll Compressors Series: SCAEY-FC Leaflet: DE 98 Issue: 01/16 Supersedes: 12/13 Identification code Index Index... pag. 2 Identification code...»

More information

Flex Series Heat Pumps

Flex Series Heat Pumps Flex Series Heat Pumps Air/water heat pumps with axial or centrifugal fans; plate or shell and tube exchangers. 08/0/06 Page of 5 FLEX SERIES The patented series of modular packaged chiller and heat pump

More information

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10 Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW Compressors Scroll Serie: Series: Emissione: Issue: SCAEY Catalogo: Leaflet: Sostituisce: Supersedes: DE 88 04/11 12/10 Index

More information

Blue Box Epsilon Echos +

Blue Box Epsilon Echos + Blue Box Epsilon Echos + 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Packaged version in 5 sizes Nominal cooling capacity (A35;W7): 6 26 kw Nominal heating

More information

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw PROCESS CHILLERS AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw climaveneta.com PROCESS CHILLERS MAXIMUM EFFICIENCY IN EVERY TYPE OF PROCESS APPLICATION Air cooled liquid chiller for outdoor

More information

ERAH MC Ka. Range kw. AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line)

ERAH MC Ka. Range kw. AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line) ERAH MC Ka AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line) Range 394-1220 kw Liquid chillers air condensing unit Package external installation Screw compressors

More information

LZT High efficiency air to water heat pumps with E.V.I. compressors

LZT High efficiency air to water heat pumps with E.V.I. compressors High efficiency air to water heat pumps with E.V.I. compressors -20 C +43 C +65 C E.V.I. C.O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating

More information

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98 Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw Scroll Compressors Series: SCAEY-FC Leaflet: DE 98 Issue: 04/11 Supersedes: 12/10 Identification code Index Index... pag. 2 Identification code...»

More information

Air cooled industrial chillers

Air cooled industrial chillers Air cooled industrial chillers Main features R410A refrigerant Cooling capacity 5 175 kw Air cooled industrial chillers Models Versions HE High Efficiency Finned coil evaporators submerged in the storage

More information

LZA High efficiency air to water heat pumps with HP compressor

LZA High efficiency air to water heat pumps with HP compressor High efficiency air to water heat pumps with HP compressor -10 C +43 C +60 C HP C.O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems

More information

RC GROUP. MULTIPLO.A.STD/ELN G Multifunctions air cooled liquid chillers with Scroll compressors and axial fans R407C. SCROLL compressors kw

RC GROUP. MULTIPLO.A.STD/ELN G Multifunctions air cooled liquid chillers with Scroll compressors and axial fans R407C. SCROLL compressors kw MULTIPLO..STD/LN G Multifunctions air cooled liquid chillers with Scroll compressors and axial fans SCROLL compressors 60 110 kw RC GROUP TCHNICL DOCUMNTTION MLTSRL_G_GB407_0203 MULTIPLO..STD/LN G Multifunctions

More information

Большая библиотека технической документации каталоги, инструкции, сервисные мануалы, схемы.

Большая библиотека технической документации   каталоги, инструкции, сервисные мануалы, схемы. Большая библиотека технической документации http://splitoff.ru/tehn-doc.html каталоги, инструкции, сервисные мануалы, схемы. AIR BLUE AIR BLUE air conditioning Homes Easy to install and use, quiet, attractive,

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw COMFORT HEAT PUMPS AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw climaveneta.com COMFORT HEAT PUMPS PERFECT COMFORT AND MAXIMUM EFFICIENCY Air to water heat pump for outdoor installation,

More information

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers Self-adjusting electronic control Cooling capacity: 35 to 700 kw 410A Cooling Operation DYNACIAT - DYNACIAT POWER

More information

Multi-pipe Units with Scroll Compressors. Model CMAA Cooling capacity kw Heating capacity kw

Multi-pipe Units with Scroll Compressors. Model CMAA Cooling capacity kw Heating capacity kw Multi-pipe Units with Scroll Compressors Model CMAA Cooling capacity 45-485 kw Heating capacity 50-670 kw CMAA multi-pipe units Simultaneous heating and cooling with one product Standard versions Acoustic

More information

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS Total heat recovery multi-purpose units LCP Outdoor monobloc air-water unit LCP - kw Heating, cooling, domestic hot water one single system to meet all kinds of needs. Total heat recovery multi-purpose

More information

LDK LDK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

LDK LDK. Air to water chillers and heat pumps VERSIONS ACCESSORIES Air to water chillers and heat pumps The water chillers range is an efficient and low-noise product designed for medium to big applications. The water chillers are suitable for water outlet temperatures

More information

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:

More information

Aquaflair TRAC-TRAF-TRAH

Aquaflair TRAC-TRAF-TRAH Aquaflair TRAC-TRAF-TRAH 110 400 kw Air-cooled chillers, free-cooling chillers and heat pumps for mission critical applications Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors

More information

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw TECHNICAL INSTRUCTIONS CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw CHG 1 CHG 1 8. kw. kw.7 kw 1. kw April 7 19 - GB - 2 MARKING This product marked conforms to the essential

More information

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ SERIES: EWCBZ - Heat pump MODELS: 70, 80, 00, 0, 60, 00, 40, 00, 50 COOLING CAPACITIES from 5,9 kw to 78,5

More information

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED EQV R-407C WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED Size Cooling Heating [kw] [kw] 5 1,9 2,2 7 2,4 2,5 9 2,6 2,5 15 3,3 3,2 17 3,7 3,7 REPLACE: BT02E008GB-01 The Versatemp EQV units

More information

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW TECHNICAL INSTRUCTIONS PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER to KW PHRT PHRT PHRT PHRT For terminal units and boiler overhaul applications Heating Cooling PHRT.00 kw -. kw PHRT.0 kw /.0 kw

More information

Air-to-water scroll chillers

Air-to-water scroll chillers Air-to-water scroll chillers Model CGA 040 to 115 Cooling capacity: 14-40 kw CG-PRC031B-GB Table of Contents Technical specifications...4 Standard configuration... 4 Hydraulic version... 4 Casing... 4

More information

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES LS ir cooled water chillers with axial fans + LS The LS water chiller range has been designed for small and medium residential and commercial applications. They are suitable for generating chilled water

More information

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors -15 C +63 C E.V.I. The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems or

More information

HYDRONIC RESIDENTIAL

HYDRONIC RESIDENTIAL HYDRONIC RESIDENTIAL Chillers, reversible heat pumps and modular units for small and medium applications. Climaveneta. brand of Mitsubishi Electric Hydronics & IT Cooling Systems, presents the mini chiller

More information

GLIDER_. air cooled liquid chilled chillers / heat pumps

GLIDER_. air cooled liquid chilled chillers / heat pumps GLIDER_ cooling capacity 189,7 1613,1 heating capacity 203,1 1613,1 compressors screw refrigerant R134a fan type axial microprocessor MP.COM models 45 RC GROUP SpA C_GNR_0507 87 VERSIONS : GLIDER (R134a)

More information

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE TEcHnIcal InsTRucTIons PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE PHRIE 095 PHRIE 1 PHIE 095 PHIE 1 PHRIE 155 PHRIE 157 PHRIE 175 PHRIE 177 PHRIE 195 PHRIE 197 PHRIE 7 PHRIE

More information