EEDEN technical data. air conditioning systems RZQ-DV1. Split Sky Air

Size: px
Start display at page:

Download "EEDEN technical data. air conditioning systems RZQ-DV1. Split Sky Air"

Transcription

1 EEDEN09-00 technical data RZQ-DV air conditioning systems Split Sky Air

2 Split - Sky Air Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste. Het ISO400 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment. Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO900 standard. ISO900 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product. The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V.. Daikin units comply with the European regulations that guarantee the safety of the product. Naamloze Vennootschap Zandvoordestraat 300 B-8400 Ostend, Belgium BTW: BE RPR Oostende Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory. EEDEN09-00 EEDEN /2009 Printed in Belgium by Goekint Graphics Copyright Daikin

3 EEDEN09-00 technical data RZQ-DV air conditioning systems Split Sky Air

4 Outdoor Units R-40A RZQ-DV TABLE OF CONTENTS RZQ-DV Features Specifications Nominal Capacity and Nominal Input Technical Specifications Electrical Specifications Electrical data Options Capacity tables Combination table Cooling capacity tables Heating capacity tables Dimensional drawing & centre of gravity Dimensional drawing Centre of gravity Piping diagram Wiring diagram Wiring diagram Sound data Sound pressure spectrum Sound power spectrum Installation Installation method Operation range Split Sky Air Outdoor Units 4

5 i n y k r o t o 0 i d - l t 4 puz - Outdoor Units R-40A RZQ-DV Features U S A V D Q R SO Outdoor units for pair, twin, triple, double twin application The Sky Air Inverter is developed for use in shops, restaurants and small offices. This innovative Daikin unit provides a more comfortable environment and offers great savings in energy consumption to shop and office owners. The use of inverter type outdoor units results in an air conditioning system with a high energy efficiency and very low sound level An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures. During start up, the room can be cooled down or heated very quickly. Once the temperature in the room has reached its set point, the low power operation starts to save energy. Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall. Outdoor units are fitted with either a swing or scroll compressor, renowned for low noise and high energy efficiency A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions 5 Split Sky Air Outdoor Units

6 2 Specifications Outdoor Units R-40A RZQ-DV 2- NOMINAL CAPACITY AND NOMINAL INPUT RZQ7D7VB RZQ00D7VB RZQ25D7VB RZQ40D7VB For combination indoor units + outdoor units Indoor Units FCQH7D7VEB FCQH00D7VEB FCQH25D7VEB FCQH40D7VEB Cooling capacity Standard kw Heating capacity Standard kw Power Input Cooling Standard kw Heating Standard kw For combination EER Nominal indoor units + outdoor COP Nominal units Energy Label Cooling A Heating A Annual energy consumption kwh 940,250,740 2,80 Indoor Units FBQ7C7VEB FBQ00C7VEB FBQ25C7VEB FBQ40C7VEB Cooling capacity Standard kw Heating capacity Standard kw Power Input Cooling Standard kw Heating Standard kw For combination EER Nominal indoor units + outdoor COP Nominal units Energy Label Cooling A A A B Heating A A A B Annual energy consumption kwh,047,35,796 2,226 Indoor Units FCQ7C7VEB FCQ00C7VEB FCQ25C7VEB FCQ40C7VEB Cooling capacity Standard kw Heating capacity Standard kw Power Input Cooling Standard kw Heating Standard kw For combination EER Nominal indoor units + outdoor COP Nominal units Energy Label Cooling A A A D Heating A A A C Annual energy consumption kwh,055,39,849 2,555 Indoor Units FHQ7BVVB FHQ00BVVB FHQ25BVVB Cooling capacity Standard kw Heating capacity Standard kw Power Input Cooling Standard kw Heating Standard kw For combination EER Nominal indoor units + outdoor COP Nominal units Energy Label Cooling B B C Heating D C C Annual energy consumption kwh,72,572 2,9 Indoor Units FAQ7BVVB FAQ00BVVB FDQ25B8V3B9 Cooling capacity Standard kw Heating capacity Standard kw Power Input Cooling Standard kw Heating Standard kw For combination EER Nominal indoor units + outdoor COP Nominal units Energy Label Cooling B B B Heating B B A Annual energy consumption kwh,4,645,978 Indoor Units FUQ7BVVB FUQ00BVVB FUQ25BVVB Cooling capacity Standard kw Heating capacity Standard kw Power Input Cooling Standard kw Heating Standard kw Split Sky Air Outdoor Units 6

7 2 Specifications Outdoor Units R-40A RZQ-DV 2 2- NOMINAL CAPACITY AND NOMINAL INPUT RZQ7D7VB RZQ00D7VB RZQ25D7VB RZQ40D7VB For combination indoor units + outdoor units EER Nominal COP Nominal Energy Label Cooling A A B Heating B C C Annual energy consumption kwh,05,484, TECHNICAL SPECIFICATIONS RZQ7D7VB RZQ00D7VB RZQ25D7VB RZQ40D7VB Casing Colour Ivory White Material Painted galvanised steel Dimensions Unit Height mm 770,345,345,345 Width mm Depth mm Packing Height mm 900,524,524,524 Width mm Depth mm Weight Unit kg Packed Unit kg Heat Exchanger Dimensions Length mm Nr of Rows Fin Pitch mm Nr of Passes Face Area m² Nr of Stages Tube type Hi-XSS(8) Fin Type WF fin Treatment Anti-corrosion treatment (PE) Fan Type Propeller Discharge direction Horizontal Quantity Air Flow Rate Cooling m³/min (nominal at 230V) Heating m³/min Motor Quantity Model KFD A Brushless DC Motor Motor Speed (nominal) Steps Cooling rpm (Standard) Heating rpm (Standard) Fan Motor Output W Drive Direct drive Compressor Quantity Motor Model 2YC63DXD JT00G-VD JT00G-VD JT00G-VD Type Hermetically sealed Hermetically sealed scroll compressor swing compressor Motor Output W,700 2,200 2,200 2,200 Crankcase W Heater Starting Method Inverter driven Operation Range Cooling Min CDB Max CDB Heating Min CWB Max CWB Sound Level (nominal) Sound Level (Night quiet) Cooling Sound Power dba Sound Pressure dba (Standard) Heating Sound Pressure (Standard) dba Sound Pressure dba Split Sky Air Outdoor Units

8 2 Specifications Outdoor Units R-40A RZQ-DV 2-2 TECHNICAL SPECIFICATIONS RZQ7D7VB RZQ00D7VB RZQ25D7VB RZQ40D7VB Refrigerant Type R-40A Charge kg Control Expansion valve (electronic type) Nr of Circuits Refrigerant Oil Type FVC50K Daphne FVC68D Charged Volume l Piping connections Liquid (OD) Quantity Type Flare connection Diameter (OD) mm Gas Quantity Type Flare connection Diameter (OD) mm Drain Quantity Type Hole Diameter (OD) mm Piping Length Minimum m Maximum m Equivalent m Chargeless m Additional Refrigerant Charge kg/m See installation manual 4PW Installation height difference Maximum m Max. internunit level difference m Heat Insulation Both liquid and gas pipes Defrost Method Pressure equalising Defrost Control Temperature Capacity Control Method Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Standard Item Tie-wraps Accessories Quantity Item Installation manual Quantity Notes Nominal cooling capacities are based on : indoor temperature : 27 CDB, 9 CWB, outdoor temperature : 35 CDB, equivalent refrigerant piping : 5m, level difference : 0m. Nominal heating capacities are based on: indoor temperature: 20 CDB; outdoor temperature: 7 CDB, 6 CWB; equivalent refrigerant piping length: 5m; level difference: 0m ELECTRICAL SPECIFICATIONS RZQ7D7VB RZQ00D7VB RZQ25D7VB RZQ40D7VB Power Supply Name V Phase ~ Frequency Hz Voltage V Voltage range Minimum V Maximum V Current Recomended fuses A Wiring connections Power Supply Intake Notes For Power Supply For connection with indoor Remark Remark See installation manual 4PW See installation manual 4PW Outdoor unit only See separate drawings for electrical data () European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 6A smaller than or equal to 75A per phase. (2) Short-circuit power Power supply to the FDQ indoor unit is separate Split Sky Air Outdoor Units 8

9 Outdoor Units R-40A RZQ-DV 3 Electrical data RZQ7-40DV 3 Unit combination Power supply Comp. OFM IFM Indoor unit Outdoor unit Hz-volts Voltage range MCA TOCA MFA MSC RLA kw FLA kw FLA RLA is based on the following conditions: Power supply: 50Hz - 230V Cooling Indoor temperature 27 CDB/9 CWB Outdoor temperature 35 CDB Heating Indoor temperature 20.0 CDB Outdoor temperature 7.0 CDB/6.0 CWB 2 TOCA means the total value of each OC set 3 Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits 4 Maximum allowable voltage unbalance between phases is 2% 5 MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.5a) 6 Select wire size based on the larger value of MCA or TOCA 7 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) SYMBOLS MCA : Min. Circuit Amps (A) TOCA : Total Over Current Amps (A) MFA : Max. Fuse Amps (A) (See note 7) MSC : MSC means the max. current during the starting of compressor. (A) RLA : Rated Load Amps (A) OFM : Outdoor Fan Motor (A) IFM : Indoor Fan Motor FLA : Full Load Amps kw : Fan Motor Rated Output (kw) 3D Split Sky Air Outdoor Units

10 Outdoor Units R-40A RZQ-DV 4 Options RZQ(S)7-40DV Name of option Central drain plug Refrigerant branch piping Demand adapter kit Kit name RZQ7D7VB RZQ00D7VB RZQ25D7VB RZQ40D7VB RZQS7D7VB RZQS00D7VB RZQS25D7VB RZQS40D7VB - RZQ00B8WB RZQ25B8WB RZQ40B8WB EKDK04 Twin KHRQ22M20TA (KHRQ58T): see note Triple - KHRQ27H (KHRQ58H): see note Double-twin - - KHRQ22M20TA (KHRQ58T): see note (3x) KRP58M5 3 4 NOTE For RZQ00-40B8WB in combination with FCQ35-7C, FCQH7C or FCQH7D use the refrigerant branch piping mentioned between brackets. 3TW26739-F Split Sky Air Outdoor Units 0

11 9 9 5 Capacity tables 5 - Combination table Outdoor Units R-40A RZQ-DV 5 Multi Combination Possibilities P = Pair 2=Twin 3 = Triple 4 = Double twin SKY-AIR Hi casette Thin cassette 2x2 cassette Duct (medium ESP) Ceiling suspended 4way ceiling Wall mounted High ESP duct Floor standing Model name SKY-AIR Hi casette Thin cassette 2x2 cassette Duct (medium ESP) Ceiling suspended 4way ceiling Wall mounted High ESP duct Floor standing Model name Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room). 2 When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the main unit. 3 Refnet kits that are necessary to install the combinations: Twin: KHRQ22M20TA Triple: KHRQ27H Double twin: KHRQ22M20TA 3TW E Split Sky Air Outdoor Units

12 9 Outdoor Units R-40A RZQ-DV 5 Capacity tables 5 - Combination table EDP Room Specifications Possible combinations and standard capacity for twin, triple and double twin operation SKY-AIR Hi casette Thin cassette 2x2 cassette Duct (medium ESP) Ceiling suspended 4way ceiling Wall mounted High ESP duct 3 5 Multi Combination Possibilities 3TW3679-3A Most popular for EDP Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room). 2 When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the main unit. In table above the indoor units are mentioned in order of the possible function (most funcitions are on FCQ, less functions are on FAQ). 3 Refnet kits that are necessary to install the combinations: Twin: KHRQ22M20TA Triple: KHRQ27H Double twin: KHRQ22M20TA Split Sky Air Outdoor Units 2

13 5 Capacity tables 5-2 Cooling capacity tables RZQ7DV Outdoor Units R-40A RZQ-DV 5 Cooling Coefficient of power input. (-) Cooling capacity Cooling capacity (kw) Capacity range Rated point Indoor Outdoor temp. ( CDB) EWB EDB TC SHC CPI TC SHC CPI TC SHC CPI TC SHC ( C) ( C) (kw) (kw) (-) (kw) (kw) (-) (kw) (kw) (-) (kw) (kw) CPI (-). Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m 3 /min.) x ( BF) x (DB* EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference : 0 m 5. Coefficient of power input is the percentage when the rated valve is defined as The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Multi) Model FCQH7D FCQ7C FBQ7 FHQ7 FAQ7 FUQ7 AFR (BF) (0.7) (0.9) (0.08) (0.0) (0.08) (0.07) Model FCQ35Cx2 FFQ35x2 FBQ35Cx2 FHQ35x2 AFR 0.5x2 0x2 5x2 3x2 (BF) (0.28x2) (0.25x2) (0.5x2) (0.2x2) SYMBOLS 3D AFR: Air flow rate (m 3 /min) BF: Bypass factor EWB: Entering wet bulb temp. ( CWB) EDB: Entering dry bulb temp. ( CDB) TC: Total cooling capacity (kw) SHC: Sensible heating capacity (kw) PI: Power input (kw) (comp.+indoor+outdoor fan motor) CPI: Coefficient of power input. (-) Caution: TC and SHC are shown by kw 8. Rated power input of each model is tabulated below. Model FCQH7D FCQ7C FBQ7C FHQ7 FAQ7 FUQ7 Cooling (Multi) Model FCQ35Cx2 FFQ35x2 FBQ35x2 FHQ35x2 Cooling Split Sky Air Outdoor Units

14 Outdoor Units R-40A RZQ-DV 5 Capacity tables 5-2 Cooling capacity tables RZQ00DV Cooling Coefficient of power input. (-) 3 5 Cooling capacity Capacity range Cooling capacity (kw) Rated point Indoor Outdoor temp. ( CDB) EWB EDB TC SHC CPI TC SHC CPI TC SHC CPI TC SHC ( C) ( C) (kw) (kw) (-) (kw) (kw) (-) (kw) (kw) (-) (kw) (kw) CPI (-). Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m 3 /min.) x ( BF) x (DB* EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference : 0 m 5. Coefficient of power input is the percentage when the rated valve is defined as The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Twin) (Triple) Model FCQH00D FCQ00C FBQ00C FHQ00 FAQ00 FUQ00 AFR (BF) (0.7) (0.6) (0.3) (0.4) (0.0) (0.07) Model FCQ50Cx2 FFQ50x2 FBQ50Cx2 FHQ50x2 AFR 2.5x2 2x2 6x2 3x2 (BF) (0.28x2) (0.6x2) (0.6x2) (0.x2) Model FCQ35Cx3 FFQ35x3 FBQ35Cx3 FHQ35x3 AFR 0.5x3 0x3 6x3 3x3 (BF) (0.28x3) (0.25x3) (0.5x3) (0.2x3) SYMBOLS 3D AFR: Air flow rate (m 3 /min) BF: Bypass factor EWB: Entering wet bulb temp. ( CWB) EDB: Entering dry bulb temp. ( CDB) TC: Total cooling capacity (kw) SHC: Sensible heating capacity (kw) PI: Power input (kw) (comp.+indoor+outdoor fan motor) CPI: Coefficient of power input. (-) Caution: TC and SHC are shown by kw 8. Rated power input of each model is tabulated below. Model FCQH00D FCQ00C FBQ00C FHQ00 FAQ00 FUQ00 Cooling (Twin) Model FCQ50Cx2 FFQ50x2 FBQ50x2 FHQ50x2 Cooling (Triple) Model FCQ35Cx3 FFQ35x3 FBQ35x3 FHQ35x3 Cooling Split Sky Air Outdoor Units 4

15 5 Capacity tables 5-2 Cooling capacity tables RZQ25DV Outdoor Units R-40A RZQ-DV 5 Cooling Coefficient of power input. (-) Cooling capacity Capacity range Cooling capacity (kw) Rated point Indoor Outdoor temp. ( CDB) EWB EDB TC SHC CPI TC SHC CPI TC SHC CPI TC SHC ( C) ( C) (kw) (kw) (-) (kw) (kw) (-) (kw) (kw) (-) (kw) (kw) CPI (-). Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m 3 /min.) x ( BF) x (DB* EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference : 0 m 5. Coefficient of power input is the percentage when the rated valve is defined as The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Twin) (Triple) Model FCQH25D FCQ25C FBQ25C FHQ25 FAQ25 FUQ25 AFR (BF) (0.9) (0.9) (0.6) (0.3) (0.3) (0.25) Model FCQ60Cx2 FFQ60x2 FBQ60Cx2 FHQ60x2 AFR 3.5x2 5x2 8x2 7x2 (BF) (0.2x2) (0.x2) (0.5x2) (0.2x2) Model FCQ50Cx3 FFQ50x3 FBQ50Cx3 FHQ50x3 AFR 2.5x3 2x3 6x3 3x3 (BF) (0.2x3) (0.6x3) (0.6x3) (0.x3) 8. Rated power input of each model is tabulated below. Model FCQH25D FCQ25C FBQ25C FHQ25 FAQ25 FUQ25 Cooling (Twin) Model FCQ60Cx2 FFQ60x2 FBQ60x2 FHQ60x2 Cooling (Triple) Model FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 Cooling (Double Twin) SYMBOLS 3D AFR: Air flow rate (m 3 /min) BF: Bypass factor EWB: Entering wet bulb temp. ( CWB) EDB: Entering dry bulb temp. ( CDB) TC: Total cooling capacity (kw) SHC: Sensible heating capacity (kw) PI: Power input (kw) (comp.+indoor+outdoor fan motor) CPI: Coefficient of power input. (-) Caution: TC and SHC are shown by kw Model FCQ35Cx4 FFQ35x4 FBQ35Cx4 FHQ35x4 AFR 0.5x4 0x4 6x4 3x4 (BF) (0.28x4) (0.25x4) (0.5x4) (0.2x4) (Double Twin) Model FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4 Cooling Split Sky Air Outdoor Units

16 Outdoor Units R-40A RZQ-DV 5 Capacity tables 5-2 Cooling capacity tables RZQ40DV Cooling Coefficient of power input. (-) 3 5 Cooling capacity Cooling capacity (kw) Capacity range Rated point Indoor Outdoor temp. ( CDB) EWB EDB TC SHC CPI TC SHC CPI TC SHC CPI TC SHC ( C) ( C) (kw) (kw) (-) (kw) (kw) (-) (kw) (kw) (-) (kw) (kw) CPI (-). Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m 3 /min.) x ( BF) x (DB* EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference : 0 m 5. Coefficient of power input is the percentage when the rated valve is defined as The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Twin) (Triple) Model FCQH40D FCQ40C AFR (BF) (0.20) (0.22) Model FCQH7Dx2 FCQ7Cx2 FBQ7Cx2 FHQ7x2 FUQ7x2 FAQ7x2 AFR 2x2 5.5x2 8x2 7x2 9x2 9x2 (BF) (0.7x2) (0.9x2) (0.08x2) (0.x2) (0.07x2) (0.08x2) Model FCQ50Cx3 FFQ50x3 FBQ50Cx3 FHQ50x3 AFR 2.5x3 2x3 6x3 3x3 (BF) (0.2x3) (0.6x3) (0.6x3) (0.x3) 8. Rated power input of each model is tabulated below. Model FCQH40D FCQ40C Cooling (Twin) Model FCQH7Dx2 FCQ7Cx2 FBQ7Cx2 FHQ7x2 FUQ7x2 FAQ7x2 Cooling (Triple) Model FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 Cooling (Double Twin) SYMBOLS 3D AFR: Air flow rate (m 3 /min) BF: Bypass factor EWB: Entering wet bulb temp. ( CWB) EDB: Entering dry bulb temp. ( CDB) TC: Total cooling capacity (kw) SHC: Sensible heating capacity (kw) PI: Power input (kw) (comp.+indoor+outdoor fan motor) CPI: Coefficient of power input. (-) Caution: TC and SHC are shown by kw Model FCQ35Cx4 FFQ35x4 FBQ35Cx4 FHQ35x4 AFR 0.5x4 0x4 6x4 3x4 (BF) (0.28x4) (0.25x4) (0.5x4) (0.2x4) (Double Twin) Model FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4 Cooling Split Sky Air Outdoor Units 6

17 5 Capacity tables 5-2 Cooling capacity tables RZQ40DV Outdoor Units R-40A RZQ-DV 5 Cooling Coefficient of power input. (-) Cooling capacity Cooling capacity (kw) Capacity range Rated point Indoor Outdoor temp. ( CDB) EWB EDB TC SHC CPI TC SHC CPI TC SHC CPI TC SHC ( C) ( C) (kw) (kw) (-) (kw) (kw) (-) (kw) (kw) (-) (kw) (kw) CPI (-). Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m 3 /min.) x ( BF) x (DB* EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference : 0 m 5. Coefficient of power input is the percentage when the rated valve is defined as The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. Model AFR (BF) FBQ40C 39 (0.4) SYMBOLS 3D AFR: Air flow rate (m 3 /min) BF: Bypass factor EWB: Entering wet bulb temp. ( CWB) EDB: Entering dry bulb temp. ( CDB) TC: Total cooling capacity (kw) SHC: Sensible heating capacity (kw) PI: Power input (kw) (comp.+indoor+outdoor fan motor) CPI: Coefficient of power input. (-) Caution: TC and SHC are shown by kw 8. Rated power input of each model is tabulated below. Model FBQ40C Cooling Split Sky Air Outdoor Units

18 Outdoor Units R-40A RZQ-DV 5 Capacity tables 5-2 Cooling capacity tables RZQ7-40DV Capacity in function of field piping length for non-inverter 3 5 Capacity (%) length (m) Cooling Heating 3TW Split Sky Air Outdoor Units 8

19 5 Capacity tables 5-3 Heating capacity tables RZQ7DV Outdoor Units R-40A RZQ-DV 5 Heating Coefficient of power input. (-) Heating capacity Capacity range Heating capacity (kw) Rated point Indoor Outdoor temp. ( CDB) EDB TC CPI TC CPI TC CPI TC CPI TC CPI TC ( C) (kw) (-) (kw) (-) (kw) (-) (kw) (-) (kw) (-) (-) CPI (-). Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m 3 /min.) x ( BF) x (DB* EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference : 0 m 6. Coefficient of power input is the percentage when the rated valve is defined as The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Multi) Model FCQH7C FCQ7C FBQ7 FHQ7 FAQ7 FVQ7 AFR (BF) (0.7) (0.9) (0.08) (0.0) (0.08) (0.07) Model FCQ35Cx2 FFQ35x2 FBQ35Cx2 FHQ35x2 AFR 0.5x2 0x2 6x2 3x2 (BF) (0.28x2) (0.25x2) (0.5x2) (0.2x2) SYMBOLS 3D AFR: Air flow rate (m 3 /min) BF: Bypass factor EWB: Entering wet bulb temp. ( CWB) EDB: Entering dry bulb temp. ( CDB) TC: Total heating capacity (kw) SHC: Sensible heating capacity (kw) PI: Power input (kw) (comp.+indoor+outdoor fan motor) CPI: Coefficient of power input. (-) Caution: TC and SHC are shown by kw 0. Rated power input of each model is tabulated below. Model FCQH7D FCQ7C FBQ7 FHQ7 FAQ7 FUQ7 Heating (Multi) Model FCQ35Cx2 FFQ35x2 FBQ35Cx2 FHQ35x2 Heating Split Sky Air Outdoor Units

20 Outdoor Units R-40A RZQ-DV 5 Capacity tables 5-3 Heating capacity tables RZQ00DV Heating Coefficient of power input. (-) 3 5 Heating capacity Capacity range Heating capacity (kw) Rated point Indoor Outdoor temp. ( CDB) EDB TC CPI TC CPI TC CPI TC CPI TC CPI TC ( C) (kw) (-) (kw) (-) (kw) (-) (kw) (-) (kw) (-) (-) CPI (-). Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m 3 /min.) x ( BF) x (DB* EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference : 0 m 6. Coefficient of power input is the percentage when the rated valve is defined as The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Twin) (Triple) Model FCQH00D FCQ00C FBQ00C FHQ00 FAQ00 FUQ00 AFR (BF) (0.7) (0.6) (0.3) (0.4) (0.0) (0.07) Model FCQ50Cx2 FFQ50x2 FBQ50Cx2 FHQ50x2 AFR 2.5x2 2x2 6x2 3x2 (BF) (0.28x2) (0.6x2) (0.6x2) (0.x2) Model FCQ35Cx3 FFQ35x3 FBQ35Cx3 FHQ35x3 AFR 0.5x3 0x3 6x3 3x3 (BF) (0.28x3) (0.25x3) (0.5x3) (0.2x3) SYMBOLS 3D AFR: Air flow rate (m 3 /min) BF: Bypass factor EWB: Entering wet bulb temp. ( CWB) EDB: Entering dry bulb temp. ( CDB) TC: Total heating capacity (kw) SHC: Sensible heating capacity (kw) PI: Power input (kw) (comp.+indoor+outdoor fan motor) CPI: Coefficient of power input. (-) Caution: TC and SHC are shown by kw 0. Rated power input of each model is tabulated below. Model FCQH00D FCQ00C FBQ00C FHQ00 FAQ00 FUQ00 Heating (Twin) Model FCQ50Cx2 FFQ50x2 FBQ50x2 FHQ50x2 Heating (Triple) Model FCQ35Cx3 FFQ35x3 FBQ35x3 FHQ35x3 Heating Split Sky Air Outdoor Units 20

21 5 Capacity tables 5-3 Heating capacity tables RZQ25DV Outdoor Units R-40A RZQ-DV 5 Heating Coefficient of power input. (-) Heating capacity Heating capacity (kw) Capacity range Rated point Indoor Outdoor temp. ( CDB) EDB TC CPI TC CPI TC CPI TC CPI TC CPI TC ( C) (kw) (-) (kw) (-) (kw) (-) (kw) (-) (kw) (-) (-) CPI (-). Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m 3 /min.) x ( BF) x (DB* EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference : 0 m 6. Coefficient of power input is the percentage when the rated valve is defined as The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Twin) (Triple) Model FCQH25D FCQ25C FBQ25C FHQ25 FAQ25 FUQ25 AFR (BF) (0.9) (0.9) (0.6) (0.3) (0.3) (0.25) Model FCQ60Cx2 FFQ60x2 FBQ60Cx2 FHQ60x2 AFR 3.5x2 5x2 8x2 7x2 (BF) (0.2x2) (0.x2) (0.5x2) (0.2x2) Model FCQ50Cx3 FFQ50x3 FBQ50Cx3 FHQ50x3 AFR 2.5x3 2x3 6x3 3x3 (BF) (0.2x3) (0.6x3) (0.6x3) (0.x3) 0. Rated power input of each model is tabulated below. Model FCQH25D FCQ25C FBQ25C FHQ25 FAQ25 FUQ25 Heating (Twin) Model FCQ60Cx2 FFQ60x2 FBQ60x2 FHQ60x2 Heating (Triple) Model FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 Heating (Double Twin) SYMBOLS 3D AFR: Air flow rate (m 3 /min) BF: Bypass factor EWB: Entering wet bulb temp. ( CWB) EDB: Entering dry bulb temp. ( CDB) TC: Total heating capacity (kw) SHC: Sensible heating capacity (kw) PI: Power input (kw) (comp.+indoor+outdoor fan motor) CPI: Coefficient of power input. (-) Caution: TC and SHC are shown by kw Model FCQ35Cx4 FFQ35x4 FBQ35Cx4 FHQ35x4 AFR 0.5x4 0x4 6x4 3x4 (BF) (0.28x4) (0.25x4) (0.5x4) (0.2x4) (Double Twin) Model FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4 Heating Split Sky Air Outdoor Units

22 Outdoor Units R-40A RZQ-DV 5 Capacity tables 5-3 Heating capacity tables RZQ40DV Heating Coefficient of power input. (-) 3 5 Heating capacity Heating capacity (kw) Capacity range Rated point Indoor Outdoor temp. ( CDB) EDB TC CPI TC CPI TC CPI TC CPI TC CPI TC ( C) (kw) (-) (kw) (-) (kw) (-) (kw) (-) (kw) (-) (-) CPI (-). Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m 3 /min.) x ( BF) x (DB* EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference : 0 m 6. Coefficient of power input is the percentage when the rated valve is defined as The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Twin) (Triple) Model FCQH40D FCQ40C AFR (BF) (0.20) (0.22) Model FCQH7Dx2 FCQ7Cx2 FBQ7Cx2 FHQ7x2 FUQ7x2 FAQ7x2 AFR 2x2 5.5x2 8x2 7x2 9x2 9x2 (BF) (0.7x2) (0.9x2) (0.08x2) (0.x2) (0.07x2) (0.08x2) Model FCQ50Cx3 FFQ50x3 FBQ50Cx3 FHQ50x3 AFR 2.5x3 2x3 6x3 3x3 (BF) (0.2x3) (0.6x3) (0.6x3) (0.x3) 0. Rated power input of each model is tabulated below. Model FCQH40D FCQ40C Heating (Twin) Model FCQH7Dx2 FCQ7Cx2 FBQ7Cx2 FHQ7x2 FUQ7x2 FAQ7x2 Heating (Triple) Model FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 Heating (Double Twin) SYMBOLS 3D AFR: Air flow rate (m 3 /min) BF: Bypass factor EWB: Entering wet bulb temp. ( CWB) EDB: Entering dry bulb temp. ( CDB) TC: Total heating capacity (kw) SHC: Sensible heating capacity (kw) PI: Power input (kw) (comp.+indoor+outdoor fan motor) CPI: Coefficient of power input. (-) Caution: TC and SHC are shown by kw Model FCQ35Cx4 FFQ35x4 FBQ35Cx4 FHQ35x4 AFR 0.5x4 0x4 6x4 3x4 (BF) (0.28x4) (0.25x4) (0.5x4) (0.2x4) (Double Twin) Model FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4 Heating Split Sky Air Outdoor Units 22

23 5 Capacity tables 5-3 Heating capacity tables RZQ40DV Outdoor Units R-40A RZQ-DV 5 Heating Coefficient of power input. (-) Heating capacity Heating capacity (kw) Capacity range Rated point Indoor Outdoor temp. ( CDB) EDB TC CPI TC CPI TC CPI TC CPI TC CPI TC ( C) (kw) (-) (kw) (-) (kw) (-) (kw) (-) (kw) (-) (-) CPI (-). Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m 3 /min.) x ( BF) x (DB* EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference : 0 m 6. Coefficient of power input is the percentage when the rated valve is defined as The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Model AFR (BF) FBQ40C 39 (0.4) SYMBOLS 3D AFR: Air flow rate (m 3 /min) BF: Bypass factor EWB: Entering wet bulb temp. ( CWB) EDB: Entering dry bulb temp. ( CDB) TC: Total heating capacity (kw) SHC: Sensible heating capacity (kw) PI: Power input (kw) (comp.+indoor+outdoor fan motor) CPI: Coefficient of power input. (-) Caution: TC and SHC are shown by kw 0. Rated power input of each model is tabulated below. Model FBQ40C Heating Split Sky Air Outdoor Units

24 Outdoor Units R-40A RZQ-DV 6 Dimensional drawing & centre of gravity 6 - Dimensional drawing RZQ7DV unit (mm) 3 Hole for anchor bolt 4-M2 Gas pipe connection J5.9 flare 2 Liquid pipe connection - J9.5 flare 3 Service port (in the unit) 4 Grounding terminal M5 (in switch box) 5 Refrigerant piping intake 6 Power supply wiring intake (knock out hole J34) 7 Control wiring intake (Knock out hole J27) 8 Drain outlet 6 3TW2544-A RZQ00,25,40DV Hole for anchor bolt 4-M2 Gas pipe connection J5.9 flare 2 Liquid pipe connection - J9.5 flare 3 Service port (in the unit) (2x) 4 Grounding terminal M5 (in switch box) 5 Refrigerant piping intake 6 Power supply wiring intake (knock hole J34) 7 Control wiring intake (knock hole J27) 8 Drain outlet unit (mm) 3TW2607- Split Sky Air Outdoor Units 24

25 Outdoor Units R-40A RZQ-DV 6 Dimensional drawing & centre of gravity 6-2 Centre of gravity RZQ7DV 6 4TW RZQ00-40DV 4TW Split Sky Air Outdoor Units

26 Outdoor Units R-40A RZQ-DV 7 Piping diagram RZQ7-40DV 3 Electronic expansion valve 7 Heat exchanger 4-way valve Heat exchanger Low pressure sensor High pressure switch J9.5 C220T-0 J5.9 C220T-0 Compressor Service port 5/6 Accumulator Indoor unit Stop valve (with service port 5/6 flare) Outdoor unit Heating Cooling O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe 3TW2965- RZQ7-40DV (Twin) Heat exchanger Electronic expansion valve Heat exchanger 4-way valve Indoor unit Low pressure sensor High pressure switch Heat exchanger Branch duct connection Option J9.5 Compressor Service port 5/6 J5.9 Accumulator Outdoor unit Heating Cooling Indoor unit Stop valve (with service port 5/6 flare) Note:. The pipes between the branch and the indoor units should have the same size as the indoor connections. O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe 3TW Split Sky Air Outdoor Units 26

27 7 Piping diagram Outdoor Units R-40A RZQ-DV RZQ00,25,40DV (Triple) Indoor unit 7 Heat exchanger Stop valve (with service port 5/6 flare) Electronic expansion valve Heat exchanger Heat exchanger Indoor unit 4-way valve J9.5 Low pressure sensor High pressure switch J5.9 Heat exchanger Indoor unit Branch duct connection Compressor Service port 5/6 Option Accumulator Note:. The pipes between the branch and the indoor units should have the same size as the indoor connections. Outdoor unit Heating Cooling O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe 3TW RZQ25-40DV (Double twin) Heat exchanger Indoor unit Electronic expansion valve Heat exchanger Heat exchanger Indoor unit J9.5 J5.9 4-way valve Low pressure High pressure sensor switch Heat exchanger Indoor unit Branch duct connection Option J9.5 J5.9 Compressor Service port 5/6 Accumulator Heat exchanger J9.5 Stop valve (with service port 5/6 flare) Outdoor unit Heating Cooling J5.9 O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe Note:. The pipes between the branch and the indoor units should have the same size as the indoor connections. 3TW Split Sky Air Outdoor Units

28 Outdoor Units R-40A RZQ-DV 8 Wiring diagram 8 - Wiring diagram RZQ7DV 3 Indoor ON OFF Outdoor (Note 4) AP : Printed circuit board (Main) A2P : Printed circuit board (Inverter) BS BS4 : Push button switch C C3 : Capacitor DS : Dip switch FU : Fuse (T 6.3A / 250V) F6U : Fuse (T 3.5A / 250V) HP 7P (A2P) : Light emitting diode (service monitor orange) HAP (AP) : Light emitting diode (service monitor green) KR : Magnetic relay (YS) K0R : Magnetic relay KR : Magnetic relay LR : Reactor MC : Motor (compressor) MF : Motor (fan) PS : Switching power supply QDI : Field earth leakage breaker (30mA) R : Resistor R2 : Resistor RT : Thermistor (air) R2T : Thermistor (discharge) R3T : Thermistor (Suction) R4T : Thermistor (Heat exchanger) R5T : Thermistor (Thermistor (heat exchanger middle)) R6T : Thermistor (liquid) R0T : Thermistor (fin) RC : Signal receiver circuit SNPH : Pressure sensor SPH : Pressure switch (High) TC : Signal transmission circuit VR : Power module V2R,V3R : Diode module VT : IGBT XM : Terminal strip (Power supply) YE : Electronic expansion valve YS : Solenoid valve (4 way valve) ZC : Noise filter (ferrite core) ZF Z4F : Noise filter 8 Position of compressor terminal El. comp. Assy Position of elements (Back) (Front) Notes:. This wiring diagram only applies to the outdoor unit 2. L: Live, N: Neutral, : Field wiring 3. : Terminal strip : Connector : Connection : Protective earth (screw) : Relay connector : Noiseless earth : Terminal 4. Refer to the option manual, for connecting wiring to x6a. 5. Refer to the Wiring diagram sticker (on back of front plate) on how to use BS BS4 and DS switch. 6. Do not operate the unit by short-circuiting protection device SPH 7. Colours: WHT: White / RED: Red / BLU: Blue / ORG: Orange BRN: Brown / GRN: Green / YLW: Yellow 8. Confirm the method of setting the selector switches (DS) by service manual. Factory setting of all switches: OFF. 2TW30466-B RZQ00-40DV Indoor ON OFF Outdoor (Note 4) AP : Printed circuit board (Main) A2P : Printed circuit board (Inverter) A3P : Printed circuit board (Noise filter) A4P : Printed circuit board BS BS4 : Push button switch C C4 : Capacitor DS : Dip switch EHC : Crankcase heater FU, F3U, F4U : Fuse (T 6.3A / 250V) F6U : Fuse (T 5,0A / 250V) HP 7P (A2P) : Light emitting diode (service monitor orange) (H2P) Prepare, Test Flickering Malfunction Detection -- Light up HAP (AP) : Light emitting diode (service monitor green) KR : Magnetic relay (YS) K4R : Magnetic relay (EHC) K0R : Magnetic relay KR : Magnetic relay LR : Reactor MC : Motor (compressor) MF : Motor (fan) (upper) M2F : Motor (fan) (lower) PS : Switching power supply QDI : Field earth leakage breaker (30mA) R : Resistor R2 : Resistor RT : Thermistor (air) R2T : Thermistor (discharge) R3T : Thermistor (Suction) R4T : Thermistor (Heat exchanger) R5T : Thermistor (Thermistor (heat exchanger middle)) R6T : Thermistor (liquid) R0T : Thermistor (fin) RC : Signal receiver circuit SNPH : Pressure sensor SPH : Pressure switch (High) TC : Signal transmission circuit VR : Power module V2R,V3R : Diode module VT : IGBT XM : Terminal strip (Power supply) YE : Electronic expansion valve YS : Solenoid valve (4 way valve) ZC : Noise filter (ferrite core) ZF Z4F : Noise filter Position of compressor terminal Wire entrance El. comp. Assy Position of elements (Back) (Front) Notes:. This wiring diagram only applies to the outdoor unit 2. L: Live, N: Neutral, : Field wiring 3. : Terminal strip : Connector : Connection : Protective earth (screw) : Relay connector : Noiseless earth : Terminal 4. Refer to the option manual, for connecting wiring to x6a. 5. Refer to the Wiring diagram sticker (on back of front plate) on how to use BS BS4 and DS switch. 6. Do not operate the unit by short-circuiting protection device SPH 7. Colours: WHT: White / RED: Red / BLU: Blue / ORG: Orange BRN: Brown / GRN: Green / YLW: Yellow 8. Confirm the method of setting the selector switches (DS) by service manual. Factory setting of all switches: OFF. 2TW Split Sky Air Outdoor Units 28

29 9 Sound data Outdoor Units R-40A RZQ-DV 9 - Sound pressure spectrum RZQ7DV - Cooling RZQ7DV - Heating 9 Sound pressure level (db) Sound pressure level (db) 3TW Octave band center frequency (Hz) 3TW Octave band center frequency (Hz) M High-tap M High-tap Data is valid at free field condition 2 Data is valid at nominal conditions. 3 db(a) = A-weighted sound pressure level (A-scale according to IEC) 4 Reference acoustic pressure 0dB = 20μPa Measuring location (discharge side) Data is valid at free field condition 2 Data is valid at nominal conditions. 3 db(a) = A-weighted sound pressure level (A-scale according to IEC) 4 Reference acoustic pressure 0dB = 20μPa Measuring location (discharge side) RZQ00DV - Cooling RZQ00DV - Heating Sound pressure level (db) Sound pressure level (db) 3TW Octave band center frequency (Hz) 3TW Octave band center frequency (Hz) M High-tap M High-tap Data is valid at free field condition 2 Data is valid at nominal conditions. 3 db(a) = A-weighted sound pressure level (A-scale according to IEC) 4 Reference acoustic pressure 0dB = 20μPa Measuring location (discharge side) Data is valid at free field condition 2 Data is valid at nominal conditions. 3 db(a) = A-weighted sound pressure level (A-scale according to IEC) 4 Reference acoustic pressure 0dB = 20μPa Measuring location (discharge side) 29 Split Sky Air Outdoor Units

30 9 Sound data Outdoor Units R-40A RZQ-DV 9 - Sound pressure spectrum RZQ25DV - Cooling RZQ25DV - Heating 3 Sound pressure level (db) Sound pressure level (db) 9 3TW Octave band center frequency (Hz) 3TW Octave band center frequency (Hz) M High-tap M High-tap Data is valid at free field condition 2 Data is valid at nominal conditions. 3 db(a) = A-weighted sound pressure level (A-scale according to IEC) 4 Reference acoustic pressure 0dB = 20μPa Measuring location (discharge side) Data is valid at free field condition 2 Data is valid at nominal conditions. 3 db(a) = A-weighted sound pressure level (A-scale according to IEC) 4 Reference acoustic pressure 0dB = 20μPa Measuring location (discharge side) RZQ40DV - Cooling RZQ40DV - Heating Sound pressure level (db) Sound pressure level (db) 3TW Octave band center frequency (Hz) 3TW Octave band center frequency (Hz) M High-tap M High-tap Data is valid at free field condition 2 Data is valid at nominal conditions. 3 db(a) = A-weighted sound pressure level (A-scale according to IEC) 4 Reference acoustic pressure 0dB = 20μPa Measuring location (discharge side) Data is valid at free field condition 2 Data is valid at nominal conditions. 3 db(a) = A-weighted sound pressure level (A-scale according to IEC) 4 Reference acoustic pressure 0dB = 20μPa Measuring location (discharge side) Split Sky Air Outdoor Units 30

31 Outdoor Units R-40A RZQ-DV 9 Sound data 9-2 Sound power spectrum RZQ7DV RZQ00DV 9 Sound power level (db) Sound power level (db) 3TW3677- Octave band center frequency (Hz) 3TW3687- Octave band center frequency (Hz) M High-tap M High-tap db(a) = A-weighted sound pressure level (A-scale according to IEC) 2 Reference acoustic intensity 0dB = 0E-6μW/m 2 3 Measured according to ISO 3744 db(a) = A-weighted sound pressure level (A-scale according to IEC) 2 Reference acoustic intensity 0dB = 0E-6μW/m 2 3 Measured according to ISO 3744 RZQ25DV RZQ40DV Sound power level (db) Sound power level (db) 3TW3697- Octave band center frequency (Hz) 3TW3707- Octave band center frequency (Hz) M High-tap M High-tap db(a) = A-weighted sound pressure level (A-scale according to IEC) 2 Reference acoustic intensity 0dB = 0E-6μW/m 2 3 Measured according to ISO 3744 db(a) = A-weighted sound pressure level (A-scale according to IEC) 2 Reference acoustic intensity 0dB = 0E-6μW/m 2 3 Measured according to ISO Split Sky Air Outdoor Units

32 Outdoor Units R-40A RZQ-DV 0 Installation 0 - Installation method RZQ7-40DV 3 A. Non stacked installation Legend Suction side obstacle Discharge side obstacle 0 Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. B. Stacked installation Figures between ( ) indicate the dimensions only for the class models.. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet Do not stack more than one unit. About 00mm is required as the dimension for laying the upper outdoor unit s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L H H < L L A 0<L /2 H 50 (250) /2 H < L 200 (300) Installation impossible 3TW Split Sky Air Outdoor Units 32

33 Operation range Outdoor Units R-40A RZQ-DV RZQ7-40DV (Cooling) Outdoor temp. ( CDB) Operation range Allowable range of operation (pull-down) Outdoor temp. ( CWB) Allowable range of operation (warming-up) (Heating) Operation range Indoor temp. ( CWB) Indoor temp. ( CDB) NOTE Depending on operation and istallation conditions. The indoor unit can change over to freeze-up operation (indoor de-icing) 2 To reduce the freeze-up operation (indoor de-icing) frequency it is recommended to install the outdoor unit in a location not exposed to wind. 3TW26733-B RZQ7-40DV (EDP ROOM) (Cooling) Outdoor temp. ( CDB) Operation range Allowable range of operation (pull-down) Outdoor temp. ( CWB) Allowable range of operation (warming-up) (Heating) Operation range Indoor temp. ( CWB) Indoor temp. ( CDB) NOTE Depending on operation and istallation conditions. The indoor unit can change over to freeze-up operation (indoor de-icing) 2 To reduce the freeze-up operation (indoor de-icing) frequency it is recommended to install the outdoor unit in a location not exposed to wind. 3TW2963-2A 33 Split Sky Air Outdoor Units

EEDEN technical data. air conditioning systems RZQS-DV1. Split Sky Air

EEDEN technical data. air conditioning systems RZQS-DV1. Split Sky Air EEDEN09-00 technical data RZQS-DV air conditioning systems Split Sky Air Split - Sky Air Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to

More information

EEDEN technical data. air conditioning systems RZQS71-140C7V1B. Split Sky Air

EEDEN technical data. air conditioning systems RZQS71-140C7V1B. Split Sky Air EEDEN08-00 technical data RZQS7-40C7VB air conditioning systems Split Sky Air Split - Sky Air Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has

More information

technical data air conditioning systems RZQ-B Pair/Twin/Triple/Double Twin Application, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems RZQ-B Pair/Twin/Triple/Double Twin Application, Inverter Controlled Unit Split Sky Air technical data RZQ-B ///Double Application, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO14001 assures an effective environmental management system in order to help

More information

technical data air conditioning systems RZQ B8W1B Split Sky Air

technical data air conditioning systems RZQ B8W1B Split Sky Air technical data RZQ00-25-40B8WB air conditioning systems Split Sky Air Split - Sky Air Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its

More information

technical data air conditioning systems RZQ-B9V3B_RZQ-B8W1B Pair, Twin, Triple, Double Twin, Application, Inverter Controlled Split Sky Air

technical data air conditioning systems RZQ-B9V3B_RZQ-B8W1B Pair, Twin, Triple, Double Twin, Application, Inverter Controlled Split Sky Air technical data RZQ-B9V3B_RZQ-B8W1B,, Triple, Double, Application, Inverter Controlled air conditioning systems Split Sky Air TABLE OF CONTENTS RZQ-B9V3B_RZQ-B8W1B 1 Features.............................................................

More information

technical data air conditioning systems RR-B8V3B_RR-B8W1B Pair, Twin, Triple Application Split Sky Air

technical data air conditioning systems RR-B8V3B_RR-B8W1B Pair, Twin, Triple Application Split Sky Air technical data RR-B8V3B_RR-B8WB Pair, Twin, Triple Application air conditioning systems Split Sky Air Split - Sky Air Daikin s unique position as a manufacturer of air conditioning equipment, compressors

More information

Air Conditioners. Technical Data RZQG-L

Air Conditioners. Technical Data RZQG-L Air Conditioners Technical Data O u t d o o r u n i t s o p t i m i z e d f o r s e a s o n a l e f f i c i e n c y w w w. d a i k i n. e u RZQG-L Air Conditioners Technical Data O u t d o o r u n i t

More information

technical data air conditioning systems RZQ C7Y1B Split Sky Air

technical data air conditioning systems RZQ C7Y1B Split Sky Air technical data RZQ200-250C7YB air conditioning systems Split Sky Air Split - Sky Air The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin

More information

TABLE OF CONTENTS RMXS-E8V1B

TABLE OF CONTENTS RMXS-E8V1B Outdoor Units R-410A RMXS-E8V1B TABLE OF CONTENTS RMXS-E8V1B! 1 Features........................................................... 814 2 Specifications.....................................................

More information

EEDEN technical data ERHQ AA. Altherma. Altherma

EEDEN technical data ERHQ AA. Altherma. Altherma EEDEN08-720 technical data ERHQ0-06AA Altherma Altherma Altherma Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement

More information

technical data air conditioning systems RMXS-E7V3B1 Super multi plus Split Sky Air

technical data air conditioning systems RMXS-E7V3B1 Super multi plus Split Sky Air technical data RMXS-E7V3B1 Super multi plus air conditioning systems Split Sky Air Outdoor Units R-410A RMXS-E7V3B1 TABLE OF CONTENTS RMXS-E7V3B1 1 Features.............................................................

More information

Air Conditioning Technical Data RZASG-MV1

Air Conditioning Technical Data RZASG-MV1 Air Conditioning Technical Data RZASG-MV1 Outdoor Unit RZASG-MV1 TABLE OF CONTENTS RZASG-MV1 1 Features............................................................. 2 2 Specifications.......................................................

More information

TABLE OF CONTENTS ERSQ-AAY1

TABLE OF CONTENTS ERSQ-AAY1 Daikin Altherma High Temperature Outdoor units ERSQ-AAY1 TABLE OF CONTENTS ERSQ-AAY1 1 Features............................................................ 6 2 Specifications......................................................

More information

Air Conditioning Technical Data RZAG-MV1

Air Conditioning Technical Data RZAG-MV1 Air Conditioning Technical Data RZAG-MV1 TABLE OF CONTENTS RZAG-MV1 1 Features............................................................. 2 2 Specifications.......................................................

More information

technical data air conditioning systems Indoor Units FBQ-C7VEB

technical data air conditioning systems Indoor Units FBQ-C7VEB technical data Indoor Units FBQ-C7VEB air conditioning systems technical data Indoor Units FBQ-C7VEB air conditioning systems Indoor Units R-40A FBQ-C7VEB TABLE OF CONTENTS FBQ-C7VEB Features.............................................................

More information

Air Conditioning. Technical Data EEDEN AZQS-BV1

Air Conditioning. Technical Data EEDEN AZQS-BV1 Air Conditioning Technical Data EEDEN14-131 AZQS-BV1 TABLE OF CONTENTS AZQS-BV1 1 Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioners. Technical Data FBQ-C

Air Conditioners. Technical Data FBQ-C Air Conditioners Technical Data C o n c e a l e d C e i l i n g U n i t E E D E N 1 0-1 0 0 FBQ-C Air Conditioners Technical Data C o n c e a l e d C e i l i n g U n i t E E D E N 1 0-1 0 0 FBQ-C Indoor

More information

TABLE OF CONTENTS ERHQ BAV3

TABLE OF CONTENTS ERHQ BAV3 TABLE OF CONTENTS ERHQ006-016BAV3 1 Features........................................................... 134 2 Specifications..................................................... 135 Nominal Capacity and

More information

Air Conditioning. Technical Data. Pair, Twin, triple, double twin EEDEN RZQ-C

Air Conditioning. Technical Data. Pair, Twin, triple, double twin EEDEN RZQ-C Air Conditioning Technical Data Pair, Twin, triple, double twin EEDEN-00 RZQ-C TABLE OF CONTENTS RZQ-C Features............................................................. 2 2 Specifications.......................................................

More information

1 Features. Outdoor Units R-410A RYN-E3V1B. Split Sky Air Outdoor Units

1 Features. Outdoor Units R-410A RYN-E3V1B. Split Sky Air Outdoor Units Features O u t d o o r U n i S p l i t S k y R Y N - E V B R - 4 0 a Outdoor units for pair application Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply

More information

EEDEN technical data ERHQ AA

EEDEN technical data ERHQ AA EEDEN08-70 technical data Altherma Outdoor units R-410A Altherma Outdoor units 34 1 Features 1 O u t d o o r u n i A l t h e r m a E R H Q 0 1 1-0 1 6 A A R - 4 1 0 A Cost effective alternative to a fossil

More information

Air Conditioning. Technical Data EEDEN RZQG-L8/7V1

Air Conditioning. Technical Data EEDEN RZQG-L8/7V1 Air Conditioning Technical Data EEDEN14-100 RZQG-L8/7V1 Outdoor Unit RZQG-L8/7V1 TABLE OF CONTENTS RZQG-L8/7V1 1 Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioning. Technical Data EEDEN RZQSG-L(3/8)V1

Air Conditioning. Technical Data EEDEN RZQSG-L(3/8)V1 Air Conditioning Technical Data EEDEN-00 RZQSG-L(/8)V Outdoor Unit RZQSG-L(/8)V TABLE OF CONTENTS RZQSG-L(/8)V Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioning. Technical Data. Multi model application EEDEN MXS-E

Air Conditioning. Technical Data. Multi model application EEDEN MXS-E Air Conditioning Technical Data Multi model application EEDEN1-100 MXS-E TABLE OF CONTENTS MXS-E 1 Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioning. Technical Data EEDEN RZQSG-L(8)Y1

Air Conditioning. Technical Data EEDEN RZQSG-L(8)Y1 Air Conditioning Technical Data EEDEN3-00 RZQSG-L(8)Y Outdoor Unit RZQSG-L(8)Y TABLE OF CONTENTS RZQSG-L(8)Y Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioning. Technical Data EEDEN RXS-F8

Air Conditioning. Technical Data EEDEN RXS-F8 Air Conditioning Technical Data EEDEN15-100 RXS-F8 Outdoor Unit RXS-F8 TABLE OF CONTENTS RXS-F8 1 Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioning Technical Data AZAS-MY1

Air Conditioning Technical Data AZAS-MY1 Air Conditioning Technical Data AZAS-MY1 Outdoor Unit AZAS-MY1 TABLE OF CONTENTS AZAS-MY1 1 Features............................................................. 2 2 Specifications.......................................................

More information

Air conditioners, heating & cooling for shops,restaurants and offices

Air conditioners, heating & cooling for shops,restaurants and offices Air conditioners, heating & cooling for shops,restaurants and offices 4-way blow ceiling suspended unit air to air heat pumps www.daikin.eu FUQ-B made by daikin : WORLD-FAMOUS FOR EFFICIENCY By purchasing

More information

Heating. Technical Data EEDEN ERRQ-AY1

Heating. Technical Data EEDEN ERRQ-AY1 Heating Technical Data EEDEN3-726 ERRQ-AY Daikin Altherma high temperature split ERRQ-AY TABLE OF CONTENTS ERRQ-AY Features............................................................. 2 2 Specifications.......................................................

More information

EEDEN technical data EKRTR. Altherma. Altherma

EEDEN technical data EKRTR. Altherma. Altherma EEDEN08-720 technical data EKRTR Altherma Altherma Altherma Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental

More information

Heating. Technical Data. Daikin Altherma low temperature monobloc EEDEN EDHQ-BB6V3

Heating. Technical Data. Daikin Altherma low temperature monobloc EEDEN EDHQ-BB6V3 Heating Technical Data Daikin Altherma low temperature monobloc EEDEN3-725 EDHQ-BB6V3 Monobloc without bottom plate heater EDHQ-BB6V3 TABLE OF CONTENTS EDHQ-BB6V3 Features.............................................................

More information

Air conditioners, heating & cooling. for large spaces. air to air heat pumps. FDQ-B

Air conditioners, heating & cooling. for large spaces. air to air heat pumps.   FDQ-B Air conditioners, heating & cooling for large spaces CONCEALED CEILING UNIT air to air heat pumps www.daikin.eu FDQ-B THE MOST ADVANCED CLIMATE CONTROL FOR LARGE SPACES The quality air conditoning of Daikin

More information

Heating. Technical Data. Daikin Altherma low temperature monobloc EEDEN EBLQ-BB6W1

Heating. Technical Data. Daikin Altherma low temperature monobloc EEDEN EBLQ-BB6W1 Heating Technical Data Daikin Altherma low temperature monobloc EEDEN3-725 EBLQ-BB6W Monobloc with bottom plate heater EBLQ-BB6W TABLE OF CONTENTS EBLQ-BB6W Features.............................................................

More information

technical data air conditioning systems FDKS-CVMB Concealed ceiling, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems FDKS-CVMB Concealed ceiling, Inverter Controlled Unit Split Sky Air technical data FDKS-CVMB Concealed ceiling, Inverter Controlled Unit air conditioning systems Split Sky Air Indoor Units R410A FDKS-CVMB TABLE OF CONTENTS FDKS-CVMB 1 Features.............................................................

More information

Heating. Technical Data. Daikin Altherma low temperature split EEDEN ERLQ-CW1

Heating. Technical Data. Daikin Altherma low temperature split EEDEN ERLQ-CW1 Heating Technical Data Daikin Altherma low temperature split EEDEN2-725 ERLQ-CW Daikin Altherma low temperature split ERLQ-CW TABLE OF CONTENTS ERLQ-CW Features.............................................................

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data O u t d o o r u n i t - m u l t i m o d e l E E D E N 2-0 0 MXS-K TABLE OF CONTENTS MXS-K Features............................................................. 2 2 Specifications.......................................................

More information

technical data air conditioning systems FDXS-CVMB Concealed Ceiling, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems FDXS-CVMB Concealed Ceiling, Inverter Controlled Unit Split Sky Air technical data FDXS-CVMB Concealed Ceiling, Inverter Controlled Unit air conditioning systems Split Sky Air Indoor Units R410A FDXS-CVMB TABLE OF CONTENTS FDXS-CVMB 1 Features.............................................................

More information

technical data air conditioning systems FVXS-FV1B R-410A Split Sky Air

technical data air conditioning systems FVXS-FV1B R-410A Split Sky Air technical data FVXS-FV1B R-410A air conditioning systems Split Sky Air Indoor Units R-410A FVXS-FV1B TABLE OF CONTENTS FVXS-FV1B 1 Features.............................................................

More information

for the retail market, hotels, restaurants and offices

for the retail market, hotels, restaurants and offices Air conditioners, HEATING & COOLING for the retail market, hotels, restaurants and offices INVERTER DRIVEN CONCEALED CEILING UNIT air to air heat pumps www.daikin.eu FBQ-C INtelligent unit, neatly concealed

More information

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FXMQ-MB

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FXMQ-MB Air Conditioning Technical Data Concealed ceiling unit with high ESP EEDEN15-204 FXMQ-MB Indoor Unit FXMQ-MB TABLE OF CONTENTS FXMQ-MB 1 Features.............................................................

More information

Air conditioners, heating & cooling for the retailmarket and offices

Air conditioners, heating & cooling for the retailmarket and offices Air conditioners, heating & cooling for the retailmarket and offices floor standing unit air to air heat pumps www.daikin.eu FVQ-B MAXIMUM RELIABILITY, MINIMUM ENERGY USE Advanced climate systems in modern

More information

Ventilation. Technical Data. Outdoor air processing unit, ventilation and air processing EEDEN FXMQ-MF

Ventilation. Technical Data. Outdoor air processing unit, ventilation and air processing EEDEN FXMQ-MF Ventilation Technical Data Outdoor air processing unit, ventilation and air processing EEDEN13-205 FXMQ-MF TABLE OF CONTENTS FXMQ-MF 1 Features.............................................................

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data F l o o r s t a n d i n g u n i t E E D E N 2-0 0 FVQ-C Indoor Unit Floor standing unit FVQ-C TABLE OF CONTENTS FVQ-C Features.............................................................

More information

Air Conditioners. Technical Data FTXS-G

Air Conditioners. Technical Data FTXS-G Air Conditioners Technical Data I n d o o r u n i t s w w w. d a i k i n. e u FTXS-G Air Conditioners Technical Data I n d o o r u n i t s w w w. d a i k i n. e u FTXS-G Indoor Units R-410A FTXS-G TABLE

More information

EEDEN technical data. air conditioning systems FTXS-G2V1B. Indoor units. Split - Sky Air

EEDEN technical data. air conditioning systems FTXS-G2V1B. Indoor units. Split - Sky Air EEDEN08-00 technical data FTXS-G2VB Indoor units air conditioning systems Split - Sky Air EEDEN08-00 technical data FTXS-G2VB Indoor units air conditioning systems Split - Sky Air Indoor Units R-40A FTXS-G2VB

More information

technical data air conditioning systems Indoor Units FCQ-C8VEB

technical data air conditioning systems Indoor Units FCQ-C8VEB technical data Indoor Units FCQ-C8VEB air conditioning systems technical data Indoor Units FCQ-C8VEB air conditioning systems TABLE OF CONTENTS FCQ-C8VEB! 1 Features.............................................................

More information

Air Conditioners. Technical Data. Heating only hydrobox for VR V HXHD-A

Air Conditioners. Technical Data. Heating only hydrobox for VR V HXHD-A Air Conditioners Technical Data Heating only hydrobox for VR V E E D E N 1 1-2 0 4 HXHD-A Air Conditioners Technical Data Heating only hydrobox for VR V E E D E N 1 1-2 0 4 HXHD-A TABLE OF CONTENTS HXHD-A

More information

technical data air conditioning systems FTXG-C Wall Mounted, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems FTXG-C Wall Mounted, Inverter Controlled Unit Split Sky Air technical data FTXG-C Wall Mounted, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO14001 assures an effective environmental management system in order to help protect

More information

Daikin air conditioners for your home, shops, restaurants and offices

Daikin air conditioners for your home, shops, restaurants and offices Daikin air conditioners for your home, shops, restaurants and offices CONCEALED CE ILING UN IT www.daikineurope.com FDEQ-B7 Concealed ceiling units are built into the false ceiling, leaving only the suction

More information

technical data air conditioning systems FHYKP-B Ceiling Mounted Corner Cassette Split Sky Air

technical data air conditioning systems FHYKP-B Ceiling Mounted Corner Cassette Split Sky Air technical data FHYKP-B Ceiling Mounted Corner Cassette air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human

More information

for small rooms in multi application

for small rooms in multi application Air conditioners, heating & cooling for small rooms in multi application concealed ceiling unit air to air heat pumps www.daikin.eu FDbq-b HOSPITALITY STARTS WITH A STABLE AND DRAUGHT-FREE INDOOR CLIMATE

More information

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FDQ-C

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FDQ-C Air Conditioning Technical Data Concealed ceiling unit with high ESP EEDEN15-100 FDQ-C TABLE OF CONTENTS FDQ-C 1 Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioners Heating & Cooling

Air Conditioners Heating & Cooling Air Conditioners Heating & Cooling C o n c e a l e d C e i l i n g U n i t Energy label:» Up to class A Heat pump system Seasonal inverter technology Flexible duct system for large areas Neatly concealed»

More information

technical data air conditioning systems FHYCP-B7 4-way Blow Ceiling Mounted Cassette (950x950) Split Sky Air

technical data air conditioning systems FHYCP-B7 4-way Blow Ceiling Mounted Cassette (950x950) Split Sky Air technical data FHYCP-B7 4-way Blow Ceiling Mounted Cassette (950x950) air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data I n d o o r u n i t E E D E N - 3 ABQ-A Indoor Unit Concealed ceiling unit ABQ-A TABLE OF CONTENTS ABQ-A Features.............................................................

More information

Daikin air conditioners for shops, restaurant and offices

Daikin air conditioners for shops, restaurant and offices Daikin air conditioners for shops, restaurant and offices ROUNDFLOW CEILING MOUNTED CASSETTE w w w. d a i k i n. e u FCQH-C The new Daikin Sky Air Roundflow Cassette: Daikin has renewed its Sky Air ceiling

More information

Air Conditioning. Technical Data. High temperature hydrobox for VRV EEDEN HXHD-A8

Air Conditioning. Technical Data. High temperature hydrobox for VRV EEDEN HXHD-A8 Air Conditioning Technical Data High temperature hydrobox for VRV EEDEN15-204 Indoor Unit TABLE OF CONTENTS 1 Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data W a l l m o u n t e d u n i t E E D E N 2-0 0 CTXS-K Indoor Unit Wall mounted unit CTXS-K TABLE OF CONTENTS CTXS-K Features.............................................................

More information

Air Conditioners Heating & Cooling

Air Conditioners Heating & Cooling Air Conditioners Heating & Cooling C o n c e a l e d C e i l i n g U n i t Energy label:» Up to class A Heat pump system Seasonal inverter technology Flexible duct system for large areas Neatly concealed»

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data W a l l m o u n t e d u n i t E E D E N 2-0 0 4 FTXN-L Indoor Unit Wall mounted unit FTXN-L TABLE OF CONTENTS FTXN-L Features.............................................................

More information

Air Conditioners Heating & Cooling

Air Conditioners Heating & Cooling Air Conditioners Heating & Cooling C o n c e a l e d C e i l i n g U n i t Energy label:» Up to class A Heat pump system Seasonal inverter technology Reduced power consumption thanks to DC inverter fan

More information

Air Conditioners Heating & Cooling

Air Conditioners Heating & Cooling Air Conditioners Heating & Cooling Ceiling Suspended Cassette»» Energy label:» Up to class A»» Heat pump system»» Seasonal inverter technology»» The ideal solution» for larger rooms»» Can be installed

More information

technical data air conditioning systems FHYP-B Ceiling Suspended Unit Split Sky Air

technical data air conditioning systems FHYP-B Ceiling Suspended Unit Split Sky Air technical data FHYP-B Ceiling Suspended Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human health and

More information

Air Conditioning. Technical Data. Ceiling suspended unit EEDEN AHQ-C

Air Conditioning. Technical Data. Ceiling suspended unit EEDEN AHQ-C Air Conditioning Technical Data Ceiling suspended unit EEDEN13-131 AHQ-C Indoor Unit AHQ-C TABLE OF CONTENTS AHQ-C 1 Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioning. Technical Data. Flexi type unit EEDEN FLXS-B(9)

Air Conditioning. Technical Data. Flexi type unit EEDEN FLXS-B(9) Air Conditioning Technical Data Flexi type unit EEDEN14-100 FLXS-B(9) Indoor Unit FLXS-B(9) TABLE OF CONTENTS FLXS-B(9) 1 Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioning. Technical Data. Concealed ceiling unit EEDEN FDXM-F

Air Conditioning. Technical Data. Concealed ceiling unit EEDEN FDXM-F Air Conditioning Technical Data Concealed ceiling unit EEDEN16-100 FDXM-F Indoor Unit FDXM-F TABLE OF CONTENTS FDXM-F 1 Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioning. Technical Data. VRV IV heat recovery EEDEN14-200_4 REYQ-T

Air Conditioning. Technical Data. VRV IV heat recovery EEDEN14-200_4 REYQ-T Air Conditioning echnical Data VRV IV heat recovery EEDEN14-0_4 REYQ- ABLE OF CONENS REYQ- 1 Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioning. Technical Data. VRV IV S-series heat pump EEDEN16-200_2 RXYSQ-TV1

Air Conditioning. Technical Data. VRV IV S-series heat pump EEDEN16-200_2 RXYSQ-TV1 Air Conditioning Technical Data VRV IV S-series heat pump EEDEN16-0_2 RXYSQ-TV1 Outdoor Unit RXYSQ-TV1 TABLE OF CONTENTS RXYSQ-TV1 1 Features.............................................................

More information

Air Conditioning. Technical Data. VRV IV S-series compact heat pump EEDEN RXYSCQ-TV1

Air Conditioning. Technical Data. VRV IV S-series compact heat pump EEDEN RXYSCQ-TV1 Air Conditioning Technical Data VRV IV S-series compact heat pump EEDEN16-100 RXYSCQ-TV1 TABLE OF CONTENTS RXYSCQ-TV1 1 Features............................................................. 2 2 Specifications.......................................................

More information

for your home FLXS-B Flexi type unit air to air heat pumps

for your home FLXS-B Flexi type unit   air to air heat pumps Air conditioners, HEATING & COOLING for your home Flexi type unit air to air heat pumps www.daikin.eu FLXS-B TOP CLASS, MADE FOR A LONG FUTURE The importance of well-being and pleasure is increasing in

More information

Remote control infrared ARC433B76 ARC433A8 ARC433B69

Remote control infrared ARC433B76 ARC433A8 ARC433B69 Cooling Only INDOOR UNITS FDKS25E FDKS35E FDKS50C FDKS60C Capacity cooling min~nom~max kw 1.3~2.4~3.0 1.4~3.4~3.8 1.7~5.0~5.3 1.7~6.0~6.5 Power input cooling min~nom~max kw -~0.69~- - ~1.09~- -~1.65~-

More information

w w w. d a i k i n. e u ATXS-E

w w w. d a i k i n. e u ATXS-E Daikin air conditioners for your home WALL MOUNTED UNIT ATXS-E w w w. d a i k i n. e u Daikin s stylishly elegant wall mounted Siesta unit will grace the dining, living or bedroom of any home. Siesta will

More information

Fan Coil Units. Technical Data FWC-BT/BF

Fan Coil Units. Technical Data FWC-BT/BF Fan Coil Units Technical Data R o u n d f l o w c a s s e t t e E C D E N 1 2-4 0 0 FWC-BT/BF Fan Coil Units Technical Data R o u n d f l o w c a s s e t t e E C D E N 1 2-4 0 0 FWC-BT/BF Table of Contents

More information

Air Conditioning. Technical Data. 4-way blow ceiling mounted cassette EEDEN ACQ-C

Air Conditioning. Technical Data. 4-way blow ceiling mounted cassette EEDEN ACQ-C Air Conditioning Technical Data 4-way blow ceiling mounted cassette EEDEN14-131 ACQ-C Indoor Unit ACQ-C TABLE OF CONTENTS ACQ-C 1 Features.............................................................

More information

Air Conditioners Heating & Cooling

Air Conditioners Heating & Cooling Air Conditioners & Cooling Concealed ceiling unit with inverter driven fan Seasonal efficiency, optimized for all seasons Discretely concealed in ceiling Reduced power consumption thanks to DC inverter

More information

Air Conditioners Heating & Cooling

Air Conditioners Heating & Cooling Air Conditioners Heating & Cooling 4 - W a y B l o w C e i l i n g M o u n t e d C a s s e t t e Energy label:» Up to class A Heat pump system Inverter technology Fits precisely» in standard modules» of

More information

Air Conditioning Technical Data FAA-A > FAA71AUVEB > FAA100AUVEB

Air Conditioning Technical Data FAA-A > FAA71AUVEB > FAA100AUVEB Air Conditioning Technical Data FAA-A > FAA71AUVEB > FAA0AUVEB Indoor Unit FAA-A TABLE OF CONTENTS FAA-A 1 Features............................................................. 2 2 Specifications.......................................................

More information

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FDQ-B

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FDQ-B Air Conditioning Technical Data Concealed ceiling unit with high ESP EEDEN15-100 FDQ-B Indoor Unit FDQ-B TABLE OF CONTENTS FDQ-B 1 Features.............................................................

More information

Air Conditioners. Technical Data FTY-H

Air Conditioners. Technical Data FTY-H Air Conditioners Technical Data W a l l M o u n t e d U n i t E E D E N 1 0-1 1 0 FTY-H Air Conditioners Technical Data W a l l M o u n t e d U n i t E E D E N 1 0-1 1 0 FTY-H Indoor Unit Wall mounted

More information

AIR CONDITIONERS, HEATING & COOLING for your home

AIR CONDITIONERS, HEATING & COOLING for your home AIR CONDITIONERS, HEATING & COOLING for your home SLIM CONCEALED CEILING UNIT air to air heat pumps www.daikin.eu FDXS-E FDXS-C COMFORTABLE AIR, THE WHOLE YEAR THROUGH A comfortable living space provides

More information

Air Conditioning. Technical Data. Wall mounted unit EEDEN FTXG-JW

Air Conditioning. Technical Data. Wall mounted unit EEDEN FTXG-JW Air Conditioning Technical Data Wall mounted unit EEDEN2-00 FTXG-JW Indoor Unit Wall mounted unit FTXG-JW TABLE OF CONTENTS FTXG-JW Features.............................................................

More information

Air Conditioners Heating & Cooling

Air Conditioners Heating & Cooling Air Conditioners Heating & Cooling Ceiling suspended unit Energy label:» Up to class A Seasonal efficiency, optimized for all seasons Heat pump system Installation possible in new and existing buildings

More information

FWV 04 FWL 05 FWM 06 FWB 07 FWD 08. Control 09. Accessories 10. Daikin Europe N.V.

FWV 04 FWL 05 FWM 06 FWB 07 FWD 08. Control 09. Accessories 10. Daikin Europe N.V. Daikin has a worldwide reputation based on over 80 years experience in the successful manufacture of high quality air conditioning equipment for industrial, commercial and residential use. Daikin Europe

More information

Air Conditioners Heating & Cooling

Air Conditioners Heating & Cooling Air Conditioners Heating & Cooling R o u n d F l o w C a s s e t t e F U L L R A N G E A C L A S S E N E R G Y L A B E L Seasonal efficiency, optimized for all seasons Heat pump system Round flow principle:

More information

FTXS20G FTXS25G FTXS35G FTXS42G FTXS50G FTXS60G FTXS71G

FTXS20G FTXS25G FTXS35G FTXS42G FTXS50G FTXS60G FTXS71G Cooling only INDOOR UNITS FTXS20G FTXS25G FTXS35G FTXS42G FTXS50G FTXS60G FTXS71G Capacity cooling min~nom~max kw 1.3~2.0~2.8 1.3~2.5~3.2 1.4~3.5~4.0 1.7~4.2~5.0 1.7~5.0~5.3 1.7~6.0~6.7 2.3~7.1~8.5 Power

More information

Daikin leads the way:

Daikin leads the way: Daikin leads the way: Offering a full range of light commercial products optimised for seasonal efficiency All Seasons Climate comfort Heating Air Conditioning Applied Systems Refrigeration Daikin leads

More information

EDUS D Engineering Data RXYQ-TAYCU, 575 V. Heat Pump 60 Hz

EDUS D Engineering Data RXYQ-TAYCU, 575 V. Heat Pump 60 Hz 201806 Engineering Data RXYQ-TAYCU, 575 V Heat Pump 60 Hz RXYQ-TAYCU (575 V, 60 Hz) 1. Features and Benefits...3 2. Nomenclature...4 3. Model Names of Indoor Unit and Outdoor Unit...7 3.1 Outdoor Units...7

More information

Chillers. Technical Data. EWYD-BZ 250~580 kw

Chillers. Technical Data. EWYD-BZ 250~580 kw Chillers Technical Data A i r C o o l e d C h i l l e r w w w. d a i k i n. e u EWYD-BZ 250~580 kw Daikin Europe N.V. About Daikin Daikin has a worldwide reputation based on over 80 years experience in

More information

Daikin air conditioners for your home

Daikin air conditioners for your home Daikin air conditioners for your home WALL MOUNTE D UNIT w w w. d a i k i n. e u FTKS/FTXS-D Daikin has taken a further step towards achieving the ideal combination of style and efficiency. The D series

More information

BENEFIT FROM LOWER FUEL COSTS.

BENEFIT FROM LOWER FUEL COSTS. TODAY, MORE AND MORE PEOPLE ARE MAKING A VERY CONSCIOUS CHOICE TO ENJOY THE COMFORT OF AIR CONDITIONING IN THEIR HOME. IT IS WIDELY RECOGNISED THAT BALANCED AIR CONDITIONING HAS A TANGIBLE EFFECT ON THE

More information

Air Conditioning. Technical Data. Wall mounted unit EEDEN FTX-J3

Air Conditioning. Technical Data. Wall mounted unit EEDEN FTX-J3 Air Conditioning Technical Data Wall mounted unit EEDEN15-0 FTX-J3 TALE OF CONTENTS FTX-J3 1 Features............................................................. 2 2 Specifications.......................................................

More information

Daikin air conditioners for your home

Daikin air conditioners for your home Daikin air conditioners for your home WALL MOUNTED UN IT www.daikineurope.com FTKS/FTXS-D Daikin has taken a further step towards achieving the ideal combination of style and efficiency. The D series stylish

More information

EDUS Heat Pump - D-Series

EDUS Heat Pump - D-Series EDUS 04-740 - Heat Pump - D-Series Split-System Room Air Conditioners D-Series The Single Split Duct-Free System Heat Pump FTXS09DVJU FTXS12DVJU FTXS15DVJU FTXS18DVJU FTXS24DVJU RX09FVJU RX12FVJU RX15FVJU

More information

EEDE06-9. technical data. Altherma ERYQ A EKHBH007A / EKHBX007A EKSWW

EEDE06-9. technical data. Altherma ERYQ A EKHBH007A / EKHBX007A EKSWW EEDE06-9 technical data Altherma ERYQ005-007A EKHBH007A / EKHBX007A EKSWW50-300 Altherma ERYQ005-007A EKHBH007A / EKHBX007A EKSWW50-300 The present publication is drawn up by way of information only and

More information

Heating High/Nom./Low dba 36/33/29 44/39/33 45/41/35 45/41/37 Refrigerant Type R-410A Piping

Heating High/Nom./Low dba 36/33/29 44/39/33 45/41/35 45/41/37 Refrigerant Type R-410A Piping Heating & Cooling OPTIMIZED FOR SEASONAL EFFICIENCY INDOOR UNIT FCQG71E FCQG100E FCQG125E FCQG140E Cooling capacity Nom. kw 7.1 3 10.0 3 12.0 14.0 3 Heating capacity Nom. kw 8.0 4 11.2 4-16 4 Power input

More information

High temperature heating system AIR TO WATER HEAT PUMPS. Renovation - Heating - Domestic hot water

High temperature heating system AIR TO WATER HEAT PUMPS. Renovation - Heating - Domestic hot water High temperature heating system AIR TO WATER HEAT PUMPS Renovation - Heating - Domestic hot water Daikin Altherma Heat pumps The solution with an eye to the future Renovating your heating system and wanting

More information

Air Conditioning. Technical Data. Small concealed ceiling unit EEDEN FDBQ-B

Air Conditioning. Technical Data. Small concealed ceiling unit EEDEN FDBQ-B Air Conditioning Technical Data Small concealed ceiling unit EEDEN15-100 FDBQ-B Indoor Unit FDBQ-B TABLE OF CONTENTS FDBQ-B 1 Features............................................................. 2 2

More information

DAIKIN EMURA. FORM. FUNCTION. REDEFINED. THE NEW INDOOR AIR CONDITIONING UNIT FROM DAIKIN.

DAIKIN EMURA. FORM. FUNCTION. REDEFINED. THE NEW INDOOR AIR CONDITIONING UNIT FROM DAIKIN. emura DAIKIN EMURA. FORM. FUNCTION. REDEFINED. THE NEW INDOOR AIR CONDITIONING UNIT FROM DAIKIN. 01 D5K_M027_Product Brochure.indd 1 27/10/09 11:30:28 STYLISH DESIGN TOTAL COMFORT ALL YEAR ROUND. The new

More information

technical data air conditioning systems FT(Y)S-B Wall Mounted Unit Split Sky Air

technical data air conditioning systems FT(Y)S-B Wall Mounted Unit Split Sky Air technical data FT(Y)S-B Wall Mounted Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human health and the

More information

for your home FTYN-GX FT(Y)N-F

for your home   FTYN-GX FT(Y)N-F Air conditioners for your home W A L L M O U N T E D U N I T www.daikin.eu FTYN-GX FT(Y)N-F FOR EVERY HOME, FOR EVERY ROOM EVERY DAY, MORE AND MORE PEOPLE ARE MAKING A CONSCIOUS EFFORT TO RAISE THEIR QUALITY

More information