REMKO CLK Mobile automatic heater

Size: px
Start display at page:

Download "REMKO CLK Mobile automatic heater"

Transcription

1 REMKO CLK Mobile automatic heater Operation Technology Spare Parts Edition GB M04 REMKO - powerful like a bear.

2

3 Operating Instructions Read these instructions carefully before setting up/operating the unit! Our guarantee becomes null and void if the unit is used, set up or maintained improperly, or if modifications are made to the supplied unit without our prior consent. Subject to alterations! Mobile automatic heater REMKO CLK Contents Page Contents Page Safety Instructions 4 Description of Device 4 Installation Requirements 6 Safety Device 6 Waste Gas Pipes 6 Before Starting 7 Starting 7 Unit Shut Down 8 Maintenance and Service 8 Troubleshooting 10 Service and Guarantee 11 Technical Data 12 Wiring Diagram 13 Exploded View 14 Spare Part List 15 Initial Operation of the Forced-Air Burner 16 Maintenance Log 18 Always keep these operating instructions near or on the unit! 3

4 Safety Instructions Make sure to observe relevant local building and fire protection codes and abide by professional association regulations when the units are in operation. The unit may only be operated by persons who have received proper training in the operation of the unit. The unit is to be installed and operated in such a way as to ensure that people are not endangered by waste gases and radiation heat and fires cannot occur. The unit may only be installed and operated in rooms, when the air-rate fed to the unit is sufficient for combustion. Units without an exhaust system may be operated only in well-ventilated rooms. Persons may not remain permanently in the room where the unit has been installed. Warning signs are to be posted at the entrances. A safety zone of 1.5 m around the unit is to be maintained even for non-flammable objects. The unit is to be installed only on a non-combustible ground. The unit may not be set up or operated in surroundings susceptible to fire or explosions. Mobile fuel containers may only be installed in compliance with technical regulations for flammable liquids. The protective air suction grille must always be kept free of dirt and loose objects. Do not insert foreign objects into the unit at any time. Do not expose the unit to a direct stream of water. All electrical cables outside the unit are to be protected from damage (e.g. caused by animals, etc.). Make sure always to pull the mains plug out of the mains socket when maintenance and repairs are carried out. While the unit is in operation, the safety mechanisms may not be bypassed or blocked! Before doing any maintenance or repair work, make sure to unplug the unit from the power supply. Never interrupt the power supply (except in emergency situations) before the unit has reached the end of the cool-down phase. Use prototype-tested WLE-type oil burners only. Description of Device The units are mobile, warm air heaters with heatexchangers and an exhaust connection for commercial use. The unit is fired directly with heating oil or diesel. It is designed for fully-automatic, universal and reliable use. The units are only operated with separate forced-air burners. The unit is equipped with a quiet, high-performance axial ventilator requiring little maintenance, a connection cable with plug and a room thermostat socket. The standard units with forced-air burners supplied directly from the factory are equipped with a fitting for an oil reservoir and an electric oil preheater. Up to CLK 70: preheater in nozzle stock. CLK 120 and higher: REMKO multifilex oil preheater. The unit complies with the basic safety and health requirements of the relevant EU regulations and is reliable and simple to operate. Areas of application The units are mobile, warm air heaters that supply instantaneous heat. They are only used for commercial purposes. The unit can be used e.g. in the following areas: for drying new buildings for point heating of outdoor workplaces for point heating of workplaces in open, non firehazard fabrication rooms and halls for heating closed and open rooms, on a permanent or temporary basis to de-ice machines, vehicles and non-flammable storage goods to maintain the temperature of components susceptible to frost as well as greenhouses Device functionality If the unit is switched to heating mode, the forced-air burner starts automatically. In fully-automatic heating mode, the forced-air burner starts only when the room thermostats determined that heat is necessary. After the burner has run for a short time, the temperature control thermostat TR (rated temperature 35 to 40 C) automatically switches the air supply fan on. Warm air is blown out. When the room thermostat is in operation, the process above is automatically repeated depending on the amount of heat required. The temperature monitor TW (rated temperature 80 to 85 C) monitors the internal temperature of the unit. After the device is switched off with the operating switch or the room thermostat, the air supply fan runs for a certain amount of time to cool the combustion chamber with heat-exchanger and then switches off. This process can be repeated several times. 4

5 Monitoring operation of device All functions of the unit are fully automatic and monitored for safety by the safety facility and the automatic burner relay (part of the forced-air burner). If the flame burns irregularly or goes out, the unit is switched off by the automatic burner relay. The control lamp on the control panel and the malfunction lamp of the automatic burner relay light up. Before the unit can be restarted, the automatic burner relay must be released by pressing the external reset button on the operating panel or the reset button on the automatic burner relay. The fan control (TR) regulates operation of the fan. The temperature monitor (TW) limits or regulates the temperature of the unit in heating mode. The safety temperature limiter (STB) interrupts heating mode when extreme overheating occurs or if the temperature monitor (TW) stops working or is defective. The STB can only be manually released after the unit has cooled down. Before the STB is released to begin operation again, the reason the STB was activated must be determined. While the unit is in operation, the safety features may not be bypassed or blocked! Installation in closed, well aerated rooms without connection to a chimney The units may only be operated when the minimum amount of air required for combustion is supplied. A safe exhaustion of the waste gases is to be ensured to exclude inadmissible pollution. - Fresh air is supplied from below. - Waste gases are expelled upwards. Outside installation Operation of the unit may not have any harmful effects or cause any unreasonable problems. The unit operator must ensure that unauthorised persons are prevented from manipulating the unit or its power supply. Because rain and snow can be sucked in by the air supply fan, a suitable protective covering should be used. Heating Rooms Warm air generators may only be operated with a room thermostat when heating rooms. Accessories. Make sure that there is enough fresh air to ensure optimum combustion. Installation Requirements The heaters may only be installed in compliance with the relevant regulations, in particular, regulations governing the installation and operation of fireplaces and furnaces. Any national/regional emission control laws or regulations must also be observed. Avoid under- or overpressure in the room where the unit is installed, as this would result in combustion troubles. Make absolutely sure that the opening for air intake and output is adjusted to the fan power (see model plate). If this is not possible, the burner has to be equipped with a separate air supply device to ensure optimum combustion. Electrical Connection The units are operated with 400 V / 3~N / 50 Hz. The unit must be connected to the power source at a special terminal equipped with a switch to protect against faulty currents. Extension cable may only be laid by authorised electricians based on the capacity of a unit, the length of the cable and in accordance with local requirements. All extension cable may only be used once they have been unrolled. Safety zones To ensure safe operation and guarantee unhindered access to the unit for maintenance work, a safety zone of 1.5 m should be maintained around the unit. Floors and ceilings must be fire-resistant. 5

6 Safety Device The device has 3 safety functions: Information on the Safety Device The device is equipped with a sensor monitoring feature and is resistant to cool down to temperatures of -20 C; below -20 C the device switches off; when the temperature rises above this temperature, it switches on again. When the sensor or capillary tube is damaged, or when an excess temperature of approximately 220 C is reached, the liquid contained in the thermostat is emptied and the device switches off for safety purposes. The device is no longer operable and must be replaced If it is necessary to replace the STB, only the original REMKO part may be used. Fan control (TR) Temperature monitor (TW) Safety temperature limiter (STB) Fan control (TR) The fan control switches the circulating air fan off and on. The point at which the device is switched on or off is set in the control box via the temperature control thermostat Scale Rated value approx. 35 to 40 C. Temperature Monitor (TW) When the unit is in heating mode, the temperature monitor limits both the temperature of the unit and the air being blown out. The switching point is set via the temperature control thermostat Scale in the control box. Rated value approx. 80 to 85 C. Safety Temperature Limiter (STB) The STB controls the temperature monitor. The switching point is fixed. The burner is prevented from being restarted if the STB is activated. After the cover next to the control panel is removed, the reset button must be pressed from the outside. After the STB has been reset, the cover must be replaced. Before a STB reset, check the operating conditions to ensure that the STB temperature is not exceeded again. Make sure to install and mounting the device carefully. Do not bend the capillary tubes near to solder points. When installing the capillary tubes, be careful not to damage or bend them too sharply. The sensors may only be mounted in the mounting brackets supplied by the manufacturer. The sensors must always be free from dust and dirt. Waste Gas Pipes When the units are operated outside or in open rooms you do not need a waste gas pipe. However, we recommend using a waste gas pipe 1 m long (see example 2) with a rain cover on top to prevent the penetration of rainwater and dirt. If the units are used as room heaters, it is necessary to route the waste gases to the outside. Make absolutely sure that counter pressure is not created by improperly laid waste gas pipes. The unit generally operates properly when the waste gas pipes have been laid at an incline and assembled with vertical end pipes. The waste gas pipes must reach at least beyond the gutters but preferably above the top of the roof to prevent counter pressure caused by weather conditions (e.g. wind). All waste gas pipe components must be securely fastened. They may not be smaller in diameter than the waste gas connection. A minimum distance of 0.6 m must be maintained from flammable objects. Waste gas components incl. fasteners can be purchased as accessories. When using an waste gas connection, the burner must be adjusted accordingly. Example 1 Example 2 Example 3 Operation with exhaust gas pipe extended. Requires condensation trap max.1 m. Operation without exhaust gas pipe extended. max. 1 meter Inadmissible installation. Important Information. To prevent damage to the combustion chamber caused by moisture build-up (condensation) (see example 3), make sure that the waste gas pipes have a properly installed condensation trap (see example 1). more than 1 m. 6

7 Before Starting Prior to initial operation, check the unit for any visual defects on the control and safety devices, that the unit has been installed correctly and that it has been properly connected to the mains. Observe the following points: Install the unit in a stable position. Make sure that air is supplied for combustion. Make sure that the air can be sucked in and be exhausted freely. Avoid overpressure and underpressure in the room where the unit has been installed. Make sure that enough fuel is supplied. Please note: the multifilex oil preheater will only function properly if voltage is supplied to the unit for a longer time prior to initial operation. Use only clean heating oil or diesel. Do not use bio diesel. Flexible fuel tubes must be protected from being damaged, e.g. from forklifts, animals, etc. Paraffin accumulation at low outside temperatures A sufficient amount of heating oil must be able to flow freely even when temperatures are low. Paraffin can accumulate even at temperatures below 5 C. Appropriate measures must be taken to prevent this. Use winterised heating oil or winter diesel. Connection to the power supply The units are operated with 400 V / 3~N / 50 Hz. The unit is connected to the power supply by an attached power cable with a grounded contact plug. The unit must be connected to the power supply at a special terminal equipped with a switch to protect against faulty currents. Extension cables may only be laid by authorised electricians based on the capacity of a unit, the length of the cable and in accordance with the intended use. Extension cables may only be used once they are unrolled. Additional information The waste gas values of the oil-burner are to be checked and properly adjusted by authorised personnel to ensure compliance with local requirements. Starting Only those persons who have been trained in operation of the unit may be responsible for operating and monitoring it. Important information about starting the cold unit The preheating of the nozzle stock delays the temperature depending start of the CLK 30 to CLK 70 units delivered with forced-air burners. Control Panel safety temperature limiter operating switch bridge circuit plug thermostat socket reset button (burner) control lamp, red (burner malfunction) control lamp, green (in operation) Note about the green control lamp (in operation). The control lamp indicates that the unit is in heating mode. When the unit is in ventilation mode, nothing is displayed if the room thermostat is switched off or if the STB was activated. Connecting the unit to the power supply 1. Set the operating switch to 0 (OFF). 2. Connect the unit plug to a properly connected power socket. 3. Open all shut-off fittings in the oil supply. When operating the unit for the first time, air in the oil supply can cause the burner to malfunction. Heating without a room thermostat The unit runs in continuous operation Plug the supplied bridge circuit plug 2 into the thermostat socket 1 of the control panel. 2. Set the operating switch to I heating. Ventilation In this position only the supply air fan runs and the unit can be used for air circulation. 1. Set operating switch to II (ventilation). 2. Please note: in this mode, it is not possible to use the thermostat nor can the unit be operated in heating mode. 7

8 Fully automatic heating with room thermostat The unit runs fully automatically with the temperature which has been pre-selected on the room thermostat Remove the bridge circuit plug Plug the thermostat plug 3 of the room thermostat (accessories) into the thermostat socket Put room thermostat 4 in a suitable place. The thermostat sensor may not be placed directly in the warm air stream or attached to a cold surface. 4. Pre-select desired room temperature on the room thermostat. 5. Set the operating switch to I. When heat is required, the forcedair burner switches on automatically; operation of the unit is fullyautomatic. Hot air distribution The units are equipped with a high-performance axial fan. This fan has been designed to transport the hot air directly and effectively. It is preferable to distribute air by means of pipes or special hot air hoses. Warm air may only be distributed in accordance with the fan capacity of the unit in operation. Please follow these instructions when attaching warm air hoses: Use only warm air hoses (accessories) approved by our company. Make sure that the hoses and/or pipes are securely attached to the unit s air outlet connection. To prevent heat from building up, the pipes and hoses may not have sharp kinks and bends. Counter pressure may not be allowed to build up when using hoses to heat closed rooms. If suction temperatures increase or if there is resistance on the air output opening, the forced-air burner can be switched off at short notice by the temperature monitor (TW) in heating mode. When the temperature falls, the burner restarts automatically. If the intervals are too short, the length of the warm air hoses should be checked. Avoid starting the burner in frequent cycles (under 5 min.). When the temperature is too high on the unit s outgoing air side, the heating-operation is interrupted automatically by the STB! Unit Shut Down 1. Set the operating switch to 0 OFF. 2. Shut off the fuel supply. Important information about the unit s cool-down phase The air supply fan continues running to cool down the combustion chamber and then stops at a later time. The fan can run several times before the unit is finally switched off. Never interrupt (except in emergency situations) the power supply until the cool-down phase is completely finished. Our guarantee does not cover damages caused to the unit by overheating. Maintenance and Service Regular maintenance and observance of some basic principles are required to ensure a long service life and to keep the unit functioning properly. Prior to doing any work on the unit, make sure to unplug it from the power source! The unit must be maintained and cleaned at regular intervals. The unit must be kept free of dust and other deposits and may only the cleaned using a dry or damp cloth. Do not use a direct stream of water Do not use any aggressive cleaning agents or those which are harmful to the environment. Do not use cleaning agents which contain solvents. Use only clean heating oil or diesel. Make sure to keep paraffin from accumulating. Check oil filters regularly and replace dirty ones. Check the unit for mechanical damage; replace defective parts when necessary. Check fan blades and combustion chamber with heat-exchanger at regular intervals and clean when dirty. Check oil tanks regularly for dirt and foreign objects and clean when necessary. Make sure that the waste gas and combustion air can always be properly expelled. Regularly check safety devices to ensure that they are working properly. Always keep safety devices free of dust and dirt. Have the waste gas values of the burner checked regularly by authorized personnel. For safety purposes, we recommend entering into a maintenance contract! 8

9 Cleaning The complete unit including heat exchanger, combustion chamber and forced-air burner, is to be cleaned from dust and dirt after every heating period, or before if necessary, depending on the operating conditions. Parts subject to wear and tear, such as waste gas suppressors, gaskets, oil filter inserts, and oil nozzles are to be checked and replaced if necessary. Adjustments and maintenance work may only be performed by authorised personnel. Cleaning the heat-exchanger 1. Unplug the unit. 2. Unscrew the 4 fixing screws and remove the blow-out cone 1. If there are warm air hoses, they do not have to be removed. 3. Remove revision cover 2 and take the waste gas suppressor 4 out of unit. 4. Clean waste gas passes 5. A special cleaning brush (Ref. No ) can be purchased as an accessory Cleaning the combustion chamber 1. Unplug unit from the power source. 2. Remove the burner cover 1 after opening the two quick release fasteners. 3. Unscrew the fuel filter 2 including the fuel tubes from the mount and pull the plug 3 from the burner Loosen the tightening bolt on the burner flange 5 and remove the burner by pulling it towards you. 5. Place the burner and the fuel filter next to the unit. 6. Disassemble the burner flange. 7. Do not damage the flange gasket. Damaged flange gasket can cause air to be suctioned in incorrectly Clean waste gas suppressors or replace them if necessary. 6. Check gaskets 3 and revision cover 2 and replace them if necessary. 7. Reassemble the unit in the reverse order. Important information about the revision cover Make sure that the gaskets and the revision covers are placed correctly. During assembling take care of uniform tightening of the fixing nuts for clamping of the revision cover. Uneven tightening may result in leakages of waste gas. 8. Clean combustion chamber through the burner opening using a vacuum cleaner. Special cleaning sets can be purchased as accessories for the REMKO industrial vacuum cleaner. 9. Assemble the burner flange and burner as described in the following section. 9

10 Assembling the burner flange and the burner. 1. Check the flange gasket 6 and replace it if necessary. 2. Attach the burner flange to the unit housing with the four bolts. Pay attention to the UP (UP, HAUT) label! 3. Tighten the upper bolts. 4. Turn the lower bolts but do not tighten them so that the burner flange can still be put together. 5. Slide the flame tube of the burner into the burner flange. Take note of measurement X in the diagram. Burners up to size 33: X = 20 mm Burners larger than 44: X = 30 mm 6. Attach the flame tube to the flange by lifting the burner slightly (3 incline). Use a hexagon socket screw key. 7. Finally, tighten the lower bolts. 8. Replace the burner cover and attach securely with the quick release fasteners. X Troubleshooting Prior to doing any work on the unit, unplug it from the power supply! Unit does not start: 1. Check power supply. 1~ 230 V. 2. Set operating switch to I. 3. Ensure that the operation lamp on the control panel is illuminated. It must indicate that the unit is in heating mode. 4. Check that the bridge circuit plug or the thermostat plug has been plugged in correctly. 5. Check the room thermostat setting. The temperature set on the room thermostat must be higher than the room temperature. 6. Check whether the safety temperature limiter (STB) was activated. You must remove the protective cover next to the control panel. 7. Before resetting the STB, it is absolutely necessary to determine the reason it was activated and take appropriate measures. The following are possible reasons: Unit could not cool down because the power supply was interrupted. Temperature of air being blown out is too high because hoses are not directing air properly. Air intakes and outlets are blocked. 8. Check whether the burner malfunction control lamp on the control panel is illuminated. If so, release the automatic burner relay by pressing the reset button. 9. Set operating switch to II If the fan now starts running, look for the malfunction in the burner. Additional maintenance information. Maintenance work on the burner may only be done by authorised personnel. Make sure to comply with waste gas emission limits in accordance with regulations. After maintenance work is complete, conduct an electrical safety test. Forced-air burner and power supply 1. Check whether fuel filter is dirty. Replace dirty filters. 2. Check that all shut-off fittings in the oil supply are open. 3. Check that there is enough fuel in the fuel container. 4. Check whether paraffin has accumulated in the heating oil. This can occur even at 5 C. 5. Check oil tubes for damage. 6. Check the sensors and capillary pipes of the safety devices for damage or dirt. 7. Check that the temperature monitor (TW) is working properly. 8. Check the forced-air burner for any dirt in the nozzle, air flow plate, filters, etc. 10

11 Fan does not start: 1. Check whether fan blade is running smoothly. 2. Check the power cord on the air supply fan for damage. 3. Check the fan s operating capacitor for damage. It is located in the unit s control panel box. 4. Check that the fan control thermostat (TR) is working properly. For safety purposes, repair work on the electrical components and the burner may only be performed by authorised personnel. Important information about resetting the burner If, during the start phase, the unit is switched off again due to a malfunction, it may only be restarted after 5 minutes have elapsed. Take any steps necessary to prevent another reset. Danger of deflagration. After working on the unit, conduct an electrical safety test. Service and Guarantee For the guarantee to be valid, the customer must completely fill out the guarantee certificate enclosed with all heating units and send it back to REMKO GmbH & Co. KG in a timely manner after purchasing of the unit and putting it into operation. The units have undergone several tests to ensure proper functioning at the factory. If there are still malfunctions that cannot be fixed by the operator using the troubleshooting instructions, please contact your dealer or contract partner. An operation/use other than indicated in these instructions is prohibited! In the case of non-compliance, we assume no liability and our guarantee becomes null and void. Proper Use These units have been designed and equipped exclusively to be used for heating and ventilation for industrial and commercial purposes. The manufacturer is not liable for any damage resulting from non-adherence to manufacturer specifications, legal requirements or any modifications to the units. 11

12 Technical Data Model CLK 30 CLK 50 CLK 70 CLK 120 CLK 150 rated heat power max. kw rated heat output kw rated air output 1) m³/h 1,760 2,780 4,920 7,350 8,920 pressure, max. complete Pa fuel heating oil or diesel (DIN 51603) fuel consumption, max. L/h oil nozzle (Danfoss) 2) USG 0.6 / 60 S 1.00 / 60 S 1.35 / 60 S 2.25 / 80 S 2.75 / 80 S pump pressure, approx. 2) bar waste gas emissions, max. % 9 waste gas volume, approx. kg/h furnace resistance, approx. (start/operation) Pa 145 / / / / / 120 required chimney draught Pa 0 electrical connection V/Hz 1~ 230/50 power consumption max. (total unit) W ,300 1,900 rated current max. (total unit) A power consumption max. (fan) W ,500 rated current max. (fan) A capacitor (fan) µf power consumption (oil preheater ) W fuse protection (supplied) A increase of temperature ( t ) K sound pressure level L pa 1m 3) db (A) air outlet Ø mm waste gas connection Ø mm dimensions: length, total mm 1,450 1,450 1,610 2,100 2,100 width, total mm height, total mm 1,000 1,000 1,120 1,350 1,350 weight without burner kg weight with burner kg ) t 45K / 1.2 kg/m³ 2) The mentioned nozzle-sizes and pump pressures were determined on the basis of adjustment tests on test units. The oil throughput had been measured out. The specifications serve only as guidelines due to product-specific differences in nozzle and pressure tolerances and oil temperature. 3) Noise measuring without burner. We reserve the right to make changes to dimensions and design in the interest of technical progress. 12

13 Wiring Diagram TR TW STB RT S A 4B 2A 3A 5B 6B H2 H1 KL I B4 0 II C S2 N N M brown braun orange black schwarz blue blau #2 S3 T2 T1 N L1 5 #3 #4 N L1 PE WS ÖV oil preheater Optional: with CLK 30 / 50 / 70. Standard: with CLK 120 / 150 (only if burner has been installed at our factory) HW C = capacitor S2 = external reset button (burner) H1 = control lamp, green STB = safety temperature limiter H2 = control lamp, red TR = fan control thermostat KL = terminal strip TW = temperature monitor thermostat M = fan motor WS = plug to burner, 7-pole (only if burner has been installed at our factory) RT = room thermostat socket ÖV = oil preheater S1 = operating switch 13

14 Exploded View sensor STB sensor TW sensor TR view control panel oil preheater for CLK 120 and higher shown CLK 70 We reserve the right to make changes to dimensions and design in the interest of technical progress. 14

15 Spare Part List No. Description CLK 30 Ref. No. CLK 50 Ref. No. CLK 70 Ref. No. CLK 120 Ref. No. CLK 150 Ref. No. 1 cover plate insulation, top insulation, right side cover, right top side cover, right bottom base plate insulation, bottom side cover, left top side cover, left bottom insulation, left rear panel, cpl insulation air baffle control panel, cpl rubber seal, control panel front panel insulation, front panel guide angle angle support, oil filter oil-preheater rubber seal, O-ring filter insert oil filter cup lead-through, tube blow-out cone burner cover support base axle wheel wheel cap wheel lock ring combustion chamber, cpl lock cap waste gas suppressor (set) inspection cover gasket for inspection cover rosette for waste gas connection transport handle, front transport handle, rear transport handle, centre crane eye fan, cpl capacitor (fan) safety temperature limiter (STB) fan control thermostat (TR) temperature monitor (TW) operating switch control lamp, green (in operation) control lamp, red (burner malfunction) external reset button (burner) thermostat socket bridge circuit plug connecting cable with plug not plug to burner, 7-pole shown fitting for oil reservoir, cpl cleaning brush, cpl When ordering spare parts please indicate ref. no. and machine no. (see model plate)! 15

16 Initial Operation of the Forced Air Burner Preparation After loosening the 4 housing bolts, remove the mounting base plate of the housing so that it is suspended to the side. There are 6 housing bolts to disassemble for the SL 44 model (look for the arrows). The operating parts are immediately accessible and can now be serviced. Setting ignition electrode and device A D C B size \ dimension A B C D SLV 11 und ,5 SL All measurements are approx. values in mm. The optimum setting must be adjusted to local and structural requirements. To service, insert or replace the nozzle, the base plate must be suspended horizontally by hooks. Proceed as follows: 1. Hold base plate horizontally. 2. Push right-hand mounting laterally into hook device. 3. Hook left-hand side into the lug. Air slide plate The adjustable air slide plate is used to adjust the burner pressure to the amount of resistance in the combustion chamber and the chimney draught without having to make changes to the original cross-section. 1. Loosen socket screw. 2. Turn air slide plate to desired setting. Pay attention to the arrows. Turn to min Turn to max =reduced burner pressure =increased burner pressure Required nozzle sizes Selecting the required oil nozzle depends on the pump pressure and the unit capacity. You may only use an oil nozzle that is suitable for the shape of the respective burner chamber with a corresponding spray angle, cone properties and throughput. You can find the required oil nozzle sizes under Technical Data. Base plate After changing the nozzle and setting the air slide plate, reassemble the base plate in the reverse order. 16

17 Secondary air setting (Setting the nozzle stock) 1 2 Adjusting the air flap Proceed as follows to adjust the air flap: 1. Loosen the knurled nut Rotate the adjustment screw 3 accordingly. 3. Keep the following in mind: Right rotation = less air Left rotation = more air 4. After the adjustment is completed, retighten the adjustment screw with the knurled nut. Proceed as follows to preset the secondary air: Use the adjusting screw 1 to adjust the nozzle 2 to the value you want. SLV 11 und SLV 33 SL 44 Air flap Counter clockwise (-) = lower scale values increased pressure behind the air flow plate lower performance range Clockwise (+) = higher scale values lower pressure behind the air flow plate upper performance range. Counter clockwise (+) = higher scale values reduced pressure behind the air flow plate upper performance range Counter clockwise (-) = lower scale values increased pressure behind the air flow plate lower performance range. The adjustment screw 3 is used to set the required quantity of air. The air flap is opened or closed until the soot profile displays an oil-free colour 0-1. Additional Information If the air flap is completely open and the flame emits smoke or flickers, use the secondary air setting to lower the pressure behind the air flow plate. It might be necessary to open the air slide plate even further. Setting the pump pressure For initial burner operation and after each time the burner is serviced, the oil pressure must be adjusted and/or checked. Never operate the pump without fuel! Proceed as follows to adjust the pump pressure 1. Remove the stopper on the P measuring connection. 2. Mount the oil manometer. 3. Open all shut-off fittings in the oil supply. 4. Switch the burner on. 5. Set the required oil pressure in accordance with the size of the nozzle and the unit performance. 6. Switch the burner off. 7. Disassemble the oil manometer. 8. Replace the stopper and its seal. 3 4 Important Information The forced-air burner may only be put into operation by trained personnel. All specifications only serve as presets and must be set or adjusted after the waste gas has been analysed. Exhaust emissions must be restricted in accordance with the ordinance on small furnace systems. 17

18 Maintenance Log Model: :... Model No.: :... Burner :... Burner No.: : Clean unit -surface- Clean unit -interior- Clean fan Clean combustion chamber Clean heat exchanger Clean/replace waste gas suppressor Replace seals -inspection cover- Replace seals burner- Clean/replace filter -fuel- Check safety mechanisms Electric safety inspections Check protective mechanisms Check unit for damage Maintenance burner Test run Remarks: Date: Date: Date: Date: Date: Signature Signature Signature Signature Signature 6. Date: Date: Date: Date: Date: Signature Signature Signature Signature Signature 11. Date: Date: Date: Date: Date: Signature Signature Signature Signature Signature 16. Date: Date: Date: Date: Date: Signature Signature Signature Signature Signature Maintenance work may only be performed by authorised personnel; settings must comply with legal specifications. A corresponding test log must be kept. 18

19

20 REMKO GmbH & Co. KG Klima- und Wärmetechnik D Lage Im Seelenkamp 12 D Lage PO Box 1827 Phone +49 (5232) Fax +49 (5232)

REMKO CLK 20 Mobile Heaters

REMKO CLK 20 Mobile Heaters REMKO CLK 20 Mobile Heaters Operation Technology Spare Parts Edition GB M08 REMKO powerful like a bear Operating Instructions Before commissioning/use of the equipment, these operating instructions must

More information

Oper at ion Technology

Oper at ion Technology CLA 25-100 Aut omat i c Oil/ Gas Heat er s Edit ion GB- 709 Oper at ion Technology Or iginal REM KO Spar e Par ts REM KO - alles bär enst ar k. Oper at ing inst r uct ions Make sure to read these instructions

More information

Propane Heater REMKO PGM 30 REMKO PGM 60

Propane Heater REMKO PGM 30 REMKO PGM 60 Propane Heater REMKO PGM 30 REMKO PGM 60 Operation Technology Spare Parts Edition GB L07 REMKO strong as a bear. Operating instructions Make sure to read these instructions carefully before starting/using

More information

REMKO CLK CLK 30, CLK 50, CLK 70, CLK 120, CLK 150

REMKO CLK CLK 30, CLK 50, CLK 70, CLK 120, CLK 150 REMKO CLK CLK 30, CLK 50, CLK 70, CLK 120, CLK 150 Automatic oil/gas heaters Operation Technology Spare parts Edition GB I12 Contents Safety notes 4 Unit description 4 Specifications for fan-assisted

More information

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80 IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80 EN OPERATING MANUAL OIL HEATER TRT-BA-IDE20-30-50-60-80-TC-001-EN Table of contents Information on the use of this manual... 1 Scope of delivery... 1 General safety...

More information

DH-Direct Fired Poultry Farm Diesel Heater

DH-Direct Fired Poultry Farm Diesel Heater DH-Direct Fired Poultry Farm Diesel Heater Comparison of Diesel Heater to Gas Heater Diesel LPG Gas LPG Gas KW 43 70 120 Fuel consumption/hr 3 5.1 8.8 Heat output 37000 60000 100000 Cost of fuel/lit or

More information

REMKO ETF 240 Portable Air Dehumidifier

REMKO ETF 240 Portable Air Dehumidifier REMKO ETF 240 Portable Air Dehumidifier Operation Technology Spare Parts Edition GB P10 REMKO powerful like a bear. Operating Instructions Read these instructions carefully before setting up/operating

More information

REMKO AMT 60-E - 90-E Mobile Dehumidifier

REMKO AMT 60-E - 90-E Mobile Dehumidifier REMKO AMT 60-E - 90-E Mobile Dehumidifier Operation Technology Spare Parts Edition GB M02 REMKO powerful like a bear. Operating Instructions Make sure to read these instructions carefully before starting/using

More information

REMKO ETF 220 Portable Air Dehumidifier

REMKO ETF 220 Portable Air Dehumidifier REMKO ETF 220 Portable Air Dehumidifier Operation Technology Spare Parts Edition GB P04 REMKO powerful like a bear. Operating Instructions Read these instructions carefully before setting up/operating

More information

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL Heating, Air Conditioning, Ventilation Отопление-Кондиционеры-Вентиляция MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL 1. Usage MTM 8-30 universal oil heater is designed for heating commercial rooms

More information

REMKO DZH. Oil Heaters. Operation Technology Spare Parts. Edition GB D04

REMKO DZH. Oil Heaters. Operation Technology Spare Parts. Edition GB D04 REMKO DZH Oil Heaters Operation Technology Spare Parts Edition GB D04 Contents Safety Notices 4 Device Description 4 Mounting Regulations 5 Commissioning 6 Shutdown 7 Maintenance and Care 8 Trouble Shooting

More information

Parts Available from

Parts Available from Montage und Bedienungsanleitung Manuel d entretien Installation, use and maintenance instructions Installatie-, gebruiks- en onderhoudsvoorschriften Oδηγίες εγκατάστασης, χρήσης και συντήρησης D F GB NL

More information

Trotec PAC FT 2600 Portable air conditioner

Trotec PAC FT 2600 Portable air conditioner Trotec PAC FT 2600 Portable air conditioner The PAC FT 2600 portable room air conditioner comes with an infrared remote control and an air outlet hose with a flat nozzle.the unit s primary function is

More information

Light oil burners. One stage operation

Light oil burners. One stage operation Installation, use and maintenance instructions Light oil burners One stage operation CODE MODEL TYPE 3505 RDB CF 38 50 T3 350050 RDBR CF 6 50 TR 35050 RDBR CF 33 50 TR 35050 RDBR CF 38 50 T3R 350650 RDBR

More information

JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS

JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS Before using the heater, read and understand all instructions and follow them carefully. The manufacturer is not responsible for damages to goods

More information

Operating Instructions

Operating Instructions Operating Instructions BA-003 Read and understand this manual before use. Keep this manual for future reference. CONFORMS TO UL STD.No.1017 Certified to CSA STD C22.2 No.243-10 For questions or concerns

More information

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS INSTRUCTION MANUAL FOR OIL BURNER MODELS X400 Bio B10 E90-803-001-001-03 Rev 13-1 - Contents Technical specifications Technical data... 3 Working field... 3 Dimensions... 4 Head and electrode settings...

More information

TTK 75 ECO OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75ECO-TC-002-EN

TTK 75 ECO OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75ECO-TC-002-EN TTK 75 ECO EN OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75ECO-TC-002-EN Table of contents Notes regarding the operating manual... 01 Information about the device... 02 Safety... 04 Transport...05 Start-up...05

More information

Oil burners Brûleurs fioul Stookoliebranders

Oil burners Brûleurs fioul Stookoliebranders Installation, use and maintenance instructions Manuel d entretien Installatie-, gebruiks- en onderhoudsvoorschriften GB F NL Oil burners Brûleurs fioul Stookoliebranders One stage operation Fonctionnement

More information

OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25

OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25 OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25 NOT FOR DOMESTIC USE SPACE HEATING ONLY Made By: Spitwater Australia Pty Ltd 953 Metry St North Albury, NSW, Australia

More information

IDE 20 D / IDE 30 D / IDE 50 D / IDE 60 D / IDE 100 D

IDE 20 D / IDE 30 D / IDE 50 D / IDE 60 D / IDE 100 D IDE 20 D / IDE 30 D / IDE 50 D / IDE 60 D / IDE 100 D EN OPERATING MANUAL OIL HEATER TRT-BA-IDE20D-30D-50D-60D-100D-TC-001-EN Table of contents Notes regarding the operating manual... 1 Safety... 2 Information

More information

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS INSTRUCTION MANUAL FOR OIL BURNER MODELS X500 Bio B10 E90-803-001-001-00 Rev 7-1 - Contents Technical specifications Technical data... 3 Working field... 3 Dimensions... 4 Head and electrode settings...

More information

Operating Instructions

Operating Instructions Operating Instructions Varioset Standard After-sales service For after-sales service please contact the Veit representative in your country. GmbH & Co. Justus - von - Liebig - Str. 15 D - 86899 Landsberg

More information

1. GENERAL SAFETY RULES

1. GENERAL SAFETY RULES ID180 & ID290 Indirect-Fired Diesel/Oil Construction Heaters Sure Flame Products Lethbridge, Alberta, Canada Telephone: (403)328-5353 Fax: (403)328-9956 www.sureflame.ca July 12, 2006 Service and Maintenance

More information

Tornado Operations & Maintenance Manual

Tornado Operations & Maintenance Manual TORNADO INDUSTRIES 7401 W. LAWRENCE AVENUE CHICAGO, IL 60706 (708) 867-5100 FAX (708) 867-6968 www.tornadovac.com Tornado Operations & Maintenance Manual MODEL NO. 99690 BD 22/14, 99720 BD 26/14 L9722

More information

hp Dust Collector With Vacuum Attachment

hp Dust Collector With Vacuum Attachment Please dispose of packaging for the product in a responsible manner. It is suitable for recycling. Help to protect the environment, take the packaging to the local amenity tip and place into the appropriate

More information

51AKB / 51 AKC OWNER S MANUAL

51AKB / 51 AKC OWNER S MANUAL 51AKB / 51 AKC OWNER S MANUAL This manual applies to the following models 51AKB 009 51AKB 012 51AKC 009 51AKC 012 Read this instruction manual thoroughly before using the air conditioner. Control panel

More information

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL CONTENT 3 Introduction 3 General 3 Safety rules 3 Storage and transportation rules 3 Manufacturer s warranty 4 Fan design 4 Delivery set 5 Technical data

More information

Infrared Diesel Heater

Infrared Diesel Heater Infrared Diesel Heater Model No: IRD40 PART NO: 6920415 OPERATING & MAINTENANCE INSTRUCTIONS GC0812 INTRODUCTION Thank you for purchasing this CLARKE Diesel Infrared Heater. Before attempting to use the

More information

Corn Flame Energy Corn Stove Model 3000

Corn Flame Energy Corn Stove Model 3000 Corn Flame Energy Corn Stove Model 3000 Installation and Operation Guide Read thoroughly before starting installation Save this manual for future reference SAFETY NOTICE If this stove is not properly installed,

More information

model No: ir20.v2 FUSE

model No: ir20.v2 FUSE InstructioNS for: model No: ir20.v2 INFRARED PARAFfIN / KEROSENE / diesel HEATER 70000Btu 230V Thank you for purchasing a Sealey product. Manufactured to a high standard this product will, if used according

More information

DF400/DF600. Construction Heaters. Installation and Maintenance Manual

DF400/DF600. Construction Heaters. Installation and Maintenance Manual 342 N. Co. Rd. 400 East Valparaiso, IN 46383 219-464-8818 Fax 219-462-7985 www.heatwagon.com Installation and Maintenance Manual Please retain this manual for future reference. DF400/DF600 Construction

More information

INFRARED PARAFfIN / KEROSENE / model No: ir20.v2 1. SAFETY INSTRUCTIONS RECOMMENDED FUSE RATING: 5AMP

INFRARED PARAFfIN / KEROSENE / model No: ir20.v2 1. SAFETY INSTRUCTIONS RECOMMENDED FUSE RATING: 5AMP InstructioNS for: INFRARED PARAFfIN / KEROSENE / diesel HEATER model No: ir20.v2 Thank you for purchasing a Sealey product. Manufactured to a high standard this product will, if used according to these

More information

Specifications. Vacuum motor power consumption(w/hp) 1200 / 1.6. Exhaust water pump power consumption(w/hp 800 / 1.1

Specifications. Vacuum motor power consumption(w/hp) 1200 / 1.6. Exhaust water pump power consumption(w/hp 800 / 1.1 Specifications Rated voltage (V) AC 110-120V or 220-240V / 50-60Hz Vacuum motor power consumption(w/hp) 1200 / 1.6 Exhaust water pump power consumption(w/hp 800 / 1.1 Exhaust water pump flow (GPH/LPH)

More information

INSTRUCTIONS MANUAL FOR USE AND MAINTENANCE

INSTRUCTIONS MANUAL FOR USE AND MAINTENANCE INSTRUCTIONS MANUAL FOR USE AND MAINTENANCE Carbel models: C-60 Plus C-70 Plus C-80 Plus C-100 Plus C-70 Plus Double-sided C-80 Plus Double-sided C-100 Plus Double-sided CARBEL C/ Ciudad de Cartagena,

More information

NEPTUN I Sole cleaning unit Art.-No.:

NEPTUN I Sole cleaning unit Art.-No.: Assembly and operating instructions Please read the instruction carefully before assembling and putting into operation. Keep instruction for future reference. Contents. General 2. Function 3. Installation

More information

Installation & Maintenance Manual

Installation & Maintenance Manual Installation & Maintenance Manual MOL 200 S1L (B30A) Oil Burner 11/12 Tel: +44 (0) 1905 794331 Fax: +44 (0) 1905 794017 Email: info@nu-way.co.uk Web: www.nu-way.co.uk DESCRIPTION COMPONENTS 1. Shrouded

More information

OPERATING & MAINTENANCE MANUAL DC10 DC15 DC25 DC40 DC45

OPERATING & MAINTENANCE MANUAL DC10 DC15 DC25 DC40 DC45 OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS DC10 DC15 DC25 DC40 DC45 Made By: NOT FOR DOMESTIC USE SPACE HEATING ONLY Spitwater Australia Pty Ltd 953 Metry St., North

More information

Mobile Air Conditioner Instruction Manual Model TC-N9KM

Mobile Air Conditioner Instruction Manual Model TC-N9KM Mobile Air Conditioner Instruction Manual Model TC-N9KM Please read and retain these instructions for future reference SPECIFICATION Model no. Cooling capacity Power/Ampere consumption for cooling* Air

More information

TTV 4500 / TTV 4500 HP / TTV 7000

TTV 4500 / TTV 4500 HP / TTV 7000 TTV 4500 / TTV 4500 HP / TTV 7000 EN OPERATING MANUAL AXIAL FAN TRT-BA-TTV4500-4500HP-7000-TC-003-EN Table of contents The current version of the operating manual can be found at: Notes regarding the operating

More information

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS INSTRUCTION MANUAL FOR OIL BURNER MODELS X500-2 Low voltage 12v dc Brushed motor E90-803-001-005-01 Rev 4-1 - Contents Technical specifications Technical data...3 Working field...3 Dimensions...4 Head

More information

Combivac Operating Instructions Combivac

Combivac Operating Instructions Combivac Combivac 17-36 Operating Instructions Combivac General Table of contents General...2 Table of contents...2 Information about the operating instructions...3 Liability...3 Notices in the operating instructions...3

More information

DIESEL/PARAFFIN HEATERS

DIESEL/PARAFFIN HEATERS DIESEL/PARAFFIN HEATERS MODEL NO: XR80, XR110, XR160, XR210 PART NO: 6931004, 6931006, 6931008, 6931012 OPERATION & MAINTENANCE INSTRUCTIONS LS0814 INTRODUCTION Thank you for purchasing this CLARKE product.

More information

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20 INSTALLATION, OPERATION AND MAINTENANCE Ariterm Hybrid 20 TABLE OF CONTENTS General...3 Installation... 4-5 Dimensions - with flue gas exhauster...6 Dimensions - without flue gas exhauster...7 Pipe installations...8

More information

Kyung Dong Oil Boiler. Contents. 1. General Warnings Safety Warnings

Kyung Dong Oil Boiler. Contents. 1. General Warnings Safety Warnings Contents 1. General Warnings --------------------- 1 2. Safety Warnings ----------------------- 2 3. Parts and structure --------------------- 7 4. Safety Device ------------------------- 9 5. Checkups

More information

Light oil / kerosene burner

Light oil / kerosene burner Installation, use and maintenance instructions Light oil / kerosene burner One stage operation CODE MODEL TYPE 374445 G5 444T50 290238 (5) - 05/20 TECHNICAL DATA Thermal power output 28 60 kw 2.3 5 kg/h

More information

51AKS I S O OWNER S MANUAL

51AKS I S O OWNER S MANUAL LLOYD'S REGISTER QUALITY ASSURANCE 51AKS I S O 9 00 1 OWNER S MANUAL This manual applies to the following models Stand-alone Split 51AKS 085--- 51AKS 010--- 51AKS 185--- 51AKS 013--- 51AKS 113--- 51AKS

More information

infrared paraffin / kerosene / diesel heater

infrared paraffin / kerosene / diesel heater instructions for infrared paraffin / kerosene / diesel heater model no: IR20.V3 Thank you for purchasing a Sealey product. Manufactured to a high standard, this product will, if used according to these

More information

REMKO AMT 45-E to 115-E

REMKO AMT 45-E to 115-E REMKO AMT 45-E to 115-E Air dehumidifiers Operation Technology Spare parts Edition GB D09 Contents Air dehumidification 4 Safety notes 6 Intended use 7 Customer service and guarantee 7 Environmental protection

More information

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING FLAME115 INFRARED HEATER SERVICE MANUAL INDEX 1. CONTROLS AND COMPONENTS 2. FLAME CONTROL CYCLES 3. MAINTENANCE SCHEDULE 4. TROUBLESHOOTING GUIDE 5. REPAIR PROCEDURES 1. FAN MOTOR ASSEMBLY 2. FUEL FILTER

More information

MOBILE HOT AIR HEATING SYSTEMS

MOBILE HOT AIR HEATING SYSTEMS MOBILE HOT AIR HEATING SYSTEMS Issue 2012 Mobile hot air heating systems Mobile Heaters Heating Centers Quality with systems RAPID HEAT ADAPTED TO YOUR NEEDS Hot air heating systems for air, to feel good,

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A cod. 6272262A GENERAL DATA Heating Data Heat Output Input (Adjustable) (Adjustable) Format 34i 11.2 34KW 45 145MJ/hr Format 34e 11.2 34KW 45 145MJ/hr General Specifications FORMAT 34i 34e Main burner injectors

More information

Providing sustainable energy solutions worldwide. Installation- and maintenance instruction B 30 A

Providing sustainable energy solutions worldwide. Installation- and maintenance instruction B 30 A 178 038 51-2 2016-07-08 Providing sustainable energy solutions worldwide Installation- and maintenance instruction B 30 A DESCRIPTION Components 1. Shrouded disc 2. Nozzle 3. Ignition electrodes 4. Nozzle

More information

LS Condensate Removal Pump INSTRUCTION MANUAL REVISION A

LS Condensate Removal Pump INSTRUCTION MANUAL REVISION A LS Condensate Removal Pump INSTRUCTION MANUAL 6-71-075-115 REVISION A CAUTION: Combustible liquids may not be pumped! The condensate pump may not be run dry, as this can destroy the bearings in a very

More information

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 HG 675 X 60 HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 1 2 1. : 93/68: 90/396: 2006/95/CE: 2004/108/CE: - 1935/2004:. 2002/95/CE: RoHS 2.,.,,,,...,. (,..)..,,.,. ( ),,, ;,,.,.....,.,,,,,,...,. (..),,.,..,.,,,,

More information

Propane Flame Projector Safety instructions and operating manual

Propane Flame Projector Safety instructions and operating manual Bigflame Propane Flame Projector Safety instructions and operating manual 1 Flame projector Bigflame Safety instructions Caution The directions in this manual must be followed strictly. It is imperative

More information

Light oil - kerosene burner

Light oil - kerosene burner Installation, use and maintenance instructions Light oil - kerosene burner One stage operation CODE MODEL TYPE 374374 G3B 437T 90 (4) - 05/0 TECHNICAL FEATURES TYPE 437T Thermal power output 9 35 kw.6

More information

PUREPOWER SERIES CENTRAL VACUUM POWER UNITS PP500, PP600 & PP650

PUREPOWER SERIES CENTRAL VACUUM POWER UNITS PP500, PP600 & PP650 USER GUIDE PUREPOWER SERIES CENTRAL VACUUM POWER UNITS PP500, PP600 & PP650 AB0039 FOR RESIDENTIAL USE ONLY!! MODELS SFDB-DQ, SFDB-DR AND SFDB-DS 30042509E IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

More information

Millo / Millo pro. Nr x000 / 1805-x000. Ideen für die Dentaltechnik A

Millo / Millo pro. Nr x000 / 1805-x000. Ideen für die Dentaltechnik A Millo / Millo pro Nr. 1804-x000 / 1805-x000 0609 21-6543 A Ideen für die Dentaltechnik 1 2 3 4 5 6 7 8 9 10 11 12 Millo / Millo pro No. 1804-x000 / 1805-x000 ENGLISH Content Introduction... 15 Symbols...

More information

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES Bucket Fan 420 Bucket Fan 1055 Bucket Fan 1460 420 1055 1460 2 Bucket Fan CONTENT INTRODUCTION 3 USE 3 WHAT S INCLUDED IN THE BOX 3 DESIGNATION

More information

OPERATOR S MANUAL FOR YOUR SAFETY. 4 Gallon / Liter Part No. PB408SV

OPERATOR S MANUAL FOR YOUR SAFETY. 4 Gallon / Liter Part No. PB408SV 120 VOLT WET / DRY VAC 4 Gallon / 15.14 Liter Part No. PB408SV FOR YOUR SAFETY Read and understand this manual before use. Keep this manual for future reference. OPERATOR S MANUAL TABLE OF CONTENTS SECTION

More information

HOT WASHER MODEL NO: KING150

HOT WASHER MODEL NO: KING150 WARNING: Do not use the hot washer without reading this manual HOT WASHER MODEL NO: KING150 PART NO: 7320175 OPERATION & MAINTENANCE INSTRUCTIONS LS1215 INTRODUCTION Thank you for purchasing this CLARKE

More information

FES - Series Portable Electric Heaters. YES - Series Suspended Electric Heaters CONTENTS

FES - Series Portable Electric Heaters. YES - Series Suspended Electric Heaters CONTENTS FOSTORIA INDUSTRIES, INC. A DIVISION OF FES - Series Portable Electric Heaters YES - Series Suspended Electric Heaters (FES-1524-3E shown) IMPORTANT SAFETY INFORMATION INSIDE Serious injury or death possible.

More information

Fundamental safety warnings

Fundamental safety warnings INTRODUCTION Read these instructions carefully before using the appliance. Failure to follow these instructions may result in injuries and equipment damage. The manufacturer is not liable for damages resulting

More information

THERMOFILM CONVECTIVE PANEL HEATER INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Models: CP 2400 CP 2000 CP 1500 CP 1000 TABLE OF CONTENTS

THERMOFILM CONVECTIVE PANEL HEATER INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Models: CP 2400 CP 2000 CP 1500 CP 1000 TABLE OF CONTENTS THERMOFILM CONVECTIVE PANEL HEATER Rev C JUL13 INSTALLATION, OPERATION AND MAINTENANCE MANUAL Models: CP 2400 CP 2000 CP 1500 CP 1000 TABLE OF CONTENTS 1. Important Safety Instructions 2. Specification

More information

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE 2 GLEC-6 - Installation and maintenance CONTENTS 1 Important information... 3 2 Safety notes... 3 3 Technical description...4 4 Transport... 6 5

More information

User Manual GV25 GV35 GV702. Company information: Original instructions GV12066 (1)

User Manual GV25 GV35 GV702. Company information:   Original instructions GV12066 (1) User Manual Original instructions GV25 GV35 GV702 Company information: www.vipercleaning.eu info-eu@vipercleaning.com GV12066 (1) 2012-04-10 USER MANUAL ENGLISH TABLE OF CONTENTS Introduction... 4 Manual

More information

PARAFFIN/DIESEL HEATERS

PARAFFIN/DIESEL HEATERS PARAFFIN/DIESEL HEATERS Model Nos. XR75 - XR105 - XR 155 Part Nos. 6920270-6920280 - 6920290 1200 Thank you for purchasing this CLARKE, Paraffin fired Space Heater. This range of portable heaters is designed

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

Operating manual. Wood pellet boiler. PL M 15 and PL M 25

Operating manual. Wood pellet boiler. PL M 15 and PL M 25 Operating manual Wood pellet boiler PL M 15 and PL M 25 November 29, 2007 Important! This operating manual contains important information for the operator. The boiler must be professionally installed and

More information

ST 40 Oil Burner. Installation & Maintenance Manual

ST 40 Oil Burner. Installation & Maintenance Manual ST 40 Oil Burner Installation & Maintenance Manual 178 093 13 Thank you for choosing a Nu-way burner. As you would expect from a Company who has a pedigree of more than 75 years in the heating industry,

More information

SPECIFICATIONS PART NAME

SPECIFICATIONS PART NAME SPECIFICATIONS MODEL High HEAT RATING Low FUEL TANK CAPACITY BURNING TIME DIMENSIONS(W x D x H) WEIGHT VOLTAGE / FREQUENCY ELECTRICAL CONSUMPTION LC-S27 9,900 BTU / 2.9 kw 2,900 BTU / 0.8 kw 4.0 lit. 14.2~

More information

TTK 75 E OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75E-TC-002-EN

TTK 75 E OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75E-TC-002-EN TTK 75 E EN OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75E-TC-002-EN Table of contents Notes regarding the operating manual... 01 Information about the device... 02 Safety... 04 Transport... 05 Operation...

More information

PARAFFIN/DIESEL HEATER

PARAFFIN/DIESEL HEATER PARAFFIN/DIESEL HEATER MODEL NO: XR60 PART NO: 6931002 OPERATION & MAINTENANCE INSTRUCTIONS LS0813 INTRODUCTION Thank you for purchasing this CLARKE product. Before attempting to use this product, please

More information

Air Conditioner. Instruction Manual. For Models WA-1010E, WA-1010H, WA-1010M WA-1230E, WA-1230H P O R T A B L E

Air Conditioner. Instruction Manual. For Models WA-1010E, WA-1010H, WA-1010M WA-1230E, WA-1230H P O R T A B L E R Instruction Manual For Models WA-1010E, WA-1010H, WA-1010M WA-1230E, WA-1230H P O R T A B L E Air Conditioner It is important that you read these instructions before using your new purchase and we strongly

More information

K Operating Instructions. Before first use of the unit read these operating instructions and act in accordance with them.

K Operating Instructions. Before first use of the unit read these operating instructions and act in accordance with them. K 1.100 Operating Instructions Before first use of the unit read these operating instructions and act in accordance with them. www.kaercher.com/register-and-win 59651430 (10/13) Contents General information..............

More information

Air Conditioner PORTABLE. Instruction Manual. Your Guarantee. Portable Air Conditioner / Heater. For models WA-1010E, WA-1010H, WA-1010M

Air Conditioner PORTABLE. Instruction Manual. Your Guarantee. Portable Air Conditioner / Heater. For models WA-1010E, WA-1010H, WA-1010M Portable Air Conditioner / Heater Your Guarantee If this product is found to be faulty as a result of faulty materials or workmanship within one year from date of purchase, it will be repaired or replaced

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

Operating Manual JuniorPower

Operating Manual JuniorPower To be read completely before start-up! Operating Manual JuniorPower 12/04 von Oertzen GmbH Ferdinand-Harten-Str. 10 22949 Ammersbek Tel. +49 40 604110 Fax +49 40 6041149 www.oertzen-gmbh.de info@oertzen-gmbh.de

More information

Glass and Dishwashers 402/452/502. (original instructions) (incl. Australian /502) Starting from Serial No.:

Glass and Dishwashers 402/452/502. (original instructions) (incl. Australian /502) Starting from Serial No.: Glass and Dishwashers ECOMAX 402/452/502 (incl. Australian 452-90/502) INSTALLATION AND OPERATION INSTRUCTIONS (original instructions) Starting from Serial No.: 8663 4000 REV. 05.10.2015 EN IMPORTANT NOTES

More information

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300 USER S MANUAL Heat Recovery Ventilator Vents Brig HRV 200 Vents Brig HRV 300 2 Brig HRV 200 (300) CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key... 4 Basic unit dimensions...

More information

Owner s Manual READ AND SAVE THESE INSTRUCTIONS

Owner s Manual READ AND SAVE THESE INSTRUCTIONS 16 Outdoor Misting / Oscillating Fan Model Number: AMMF16R-1 Owner s Manual READ AND SAVE THESE INSTRUCTIONS CAUTION: Before using this product, read this manual and follow all safety rules and operating

More information

PORTABLE AIR CONDITIONER (LOCAL)

PORTABLE AIR CONDITIONER (LOCAL) EN PORTABLE AIR CONDITIONER (LOCAL) OPERATING INSTRUCTIONS Read the instructions carefully before operating the appliance or carrying out maintenance work. Observe all the safety instructions; failure

More information

O P E R A T I N G I N S T R U C T I O N S

O P E R A T I N G I N S T R U C T I O N S O P E R A T I N G I N S T R U C T I O N S for Vertical Autoclave KSG 30/50-1 KSG 40/60-1 KSG 50/70-1 KSG 50/80-1 - single-walled execution - with sterilization timer and contact thermometer for sterilization

More information

ANLAGENBAU HEAT EXCHANGER w w w. a nla g enba u-b oehm er. d e Version 05/2015

ANLAGENBAU HEAT EXCHANGER w w w. a nla g enba u-b oehm er. d e Version 05/2015 ANLAGENBAU HEAT EXCHANGER Table of Contents 1.0 General Information 1.2 User Instructions 1.3 Proper Use 1.4 General Safety Rules 2.0 Design and Function 3.0 Installation 3.1 Setting up the Plate Heat

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

Supply air unit VEKA Installation & Maintenance

Supply air unit VEKA Installation & Maintenance November 2008 Safety instructions Operating the air treatment unit and accessory components WARNING Before the air treatment unit is taken into service, any free connections must be provided with protective

More information

EYS SEPARATOR EYS 01 G. USER MANUAL for EYS SCREW-PRESS SEPARATOR MODEL EYS 01 G. User Manual for EYS 01G Screw-Press Separator

EYS SEPARATOR EYS 01 G. USER MANUAL for EYS SCREW-PRESS SEPARATOR MODEL EYS 01 G. User Manual for EYS 01G Screw-Press Separator USER MANUAL for EYS SCREW-PRESS SEPARATOR MODEL EYS 01 G User Manual for EYS 01G Screw-Press Separator Table of Contents Page 1. Introduction 2 2. General Safety Instructions 3 3. Installation 5 4. Start-up

More information

Electronically controlled instantaneous water heater. MCX: 27300, and models. Installation instructions

Electronically controlled instantaneous water heater. MCX: 27300, and models. Installation instructions Electronically controlled instantaneous water heater MCX: 27300, 27400 and 27600 models Installation instructions These appliances deliver water not exceeding 50 ºC in accordance with AS3498. 1. Overview

More information

Thermo 230 / 231 / 300 / 301 / Troubleshooting

Thermo 230 / 231 / 300 / 301 / Troubleshooting Thermo 230 / 231 / 300 / 301 / 350 5 Troubleshooting 5 Troubleshooting 5.1 General This section describes troubleshooting procedures for the heaters Thermo 230, 231, 300, 301 and 350. CAUTION Troubleshooting

More information

PARAFFIN/DIESEL HEATERS

PARAFFIN/DIESEL HEATERS INSTRUCTIONS FOR: PARAFFIN/DIESEL HEATERS Models: AB602, AB902, AB801, AB80, AB100X & AB160X Thank you for purchasing a Sealey product. Manufactured to a high standard this product will, if used according

More information

DH 100 P. Always Dry dehumidifier. with. Condensation Removal System

DH 100 P. Always Dry dehumidifier. with. Condensation Removal System DH 100 P Always Dry dehumidifier with Condensation Removal System IMPORTANT SAFEGUARD Read all instructions before using this dehumidifier. To reduce the risk of fire, electric shock, or injury to persons

More information

CombiGrinder. Instruction manual. Grinder for cattle, horse and pet clipper blades. swiss made. Version/Index: CombiGrinder/A 09-16

CombiGrinder. Instruction manual. Grinder for cattle, horse and pet clipper blades. swiss made. Version/Index: CombiGrinder/A 09-16 swiss made CombiGrinder Grinder for cattle, horse and pet clipper blades Instruction manual Version/Index: CombiGrinder/A 09-16 1 Instruction manual / CombiGrinder Contents 1 Safety regulations 1.1 Symbols

More information

Operator s Manual. 6 Gallon Model No. VQ607SFD FOR YOUR SAFETY. Read and understand this manual before use Keep this manual for future reference

Operator s Manual. 6 Gallon Model No. VQ607SFD FOR YOUR SAFETY. Read and understand this manual before use Keep this manual for future reference Wet/Dry Vacuums Operator s Manual 6 Gallon Model No. VQ607SFD FOR YOUR SAFETY Read and understand this manual before use Keep this manual for future reference www.vacmaster.com Cleva North America 44 Parkway

More information

2 000W CYCLONIC BAGLESS VACUUM

2 000W CYCLONIC BAGLESS VACUUM 2 000W CYCLONIC BAGLESS VACUUM /GVAVK08 Instruction Manual Contents Guide to the Appliance Caring for the Environment Safety Information and Warnings Basic Set Up Care and Maintenance Troubleshooting 2

More information

SAFETY AND OPERATING MANUAL

SAFETY AND OPERATING MANUAL SAFETY AND OPERATING MANUAL HOT WATER ELECTRIC WATER BLASTERS Read Safety & Operating Instructions Before Commencing Operation THESE INSTRUCTIONS MUST BE READ AND ADHERED TO BEFORE OPERATING THIS MACHINE.

More information

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART # INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED

More information

Air Conditioner PORTABLE. Instruction Manual. Your Guarantee. Portable Air Conditioner / Heater. For model WA-7500M

Air Conditioner PORTABLE. Instruction Manual. Your Guarantee. Portable Air Conditioner / Heater. For model WA-7500M Portable Air Conditioner / Heater Your Guarantee If this product is found to be faulty as a result of faulty materials or workmanship within one year from date of purchase, it will be repaired or replaced

More information

PATRON CLIMAT OIL FIRED CONSTRUCTION HEATERS MODELS 40, 50 AND 130 OWNER S MANUAL. HEATER SIZES 135,000 and 195,000 and 570,000 BTU/Hr

PATRON CLIMAT OIL FIRED CONSTRUCTION HEATERS MODELS 40, 50 AND 130 OWNER S MANUAL. HEATER SIZES 135,000 and 195,000 and 570,000 BTU/Hr PATRON CLIMAT OIL FIRED CONSTRUCTION HEATERS MODELS 40, 50 AND 30 OWNER S MANUAL HEATER SIZES 35,000 and 95,000 and 570,000 BTU/Hr GENERAL HAZARD WARNING FAILURE TO COMPLY WITH THE PRECAUTIONS AND INSTRUCTIONS

More information