1 Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0188 ISBN: Dispersion of pollutants released at floor level under three types of heating systems: A CFD study. Laura Stasiuliene,*, Andrius Jurelionis 1 1 Kaunas University of Technology (KTU), Kaunas, Lithuania * Corresponding laura.stasiuliene@ktu.lt SUMMARY Floor heating and hot water radiator heating, as well as air heating in combination with heat recovery ventilation are most frequently used systems in modern buildings. These three systems are different from perspective of air temperature distribution and ventilation effectiveness. The aim of this study was to evaluate personal exposure of the occupants to airborne pollutants emitted at the floor level in rooms with three different heating systems combined with mixing ventilation. A three-dimensional steady-state numerical analysis was performed in a room heated by three different heating systems combined with two air distribution methods at the air change rate of 2 h-. The pollution source was simulated as benzene in the centre of the chamber. Heated dummy was used to estimate the effects of convection generated by the occupant as well as personal exposure. The results indicate that inhaled-to ambient pollutant concentration is higher in air heating and radiator heating. Positive effect of floor heating on ventilation effectiveness and personal exposure was observed. KEYWORDS Floor heating, air heating, radiator heating, personal exposure, ventilation effectiveness 1 INTRODUCTION A variety of technologies are used for heating buildings. Floor heating, radiator heating and air heating combined with mechanical ventilation are most frequently used systems in buildings nowadays. The performance of these three systems are significantly different. Floor heating provides consistent air temperature and low level air velocities in rooms. Radiator heating and air heating systems create uneven pools of warmth and vertical air temperature gradient is present. Higher temperatures and air velocities occurs above radiators compared to other parts of the room in radiator heating systems (Gökhan et al, 2010). A layer of warm air in the upper part of the room can be formed in air heating systems. Air heating is also sensitive to the air distribution equipment used (Krajčík et al, 2012; Feist et al, 2005). Dispersion of pollutants is influenced by location of pollutant source, supplied air flow, contaminant density (Heiselberg, 1996; Mundt, 2001). The results of the study on ventilation
2 effectiveness and thermal comfort in rooms with floor heating and warm air heating performed by Krajčik et al (2012) showed that ventilation effectiveness depends on the position of the air terminal devices. The study of Golkarfard and Telibizadeh (2014) showed that the deposition ratio of particles and the percentage of suspended particles in rooms with radiator heating system were higher in comparison to the floor heating. The isothermal pollutants released at floor level can be transported to breathing level by human convective boundary layer (CBL) (Licina et al, 2014). The most frequent sources of such pollutants are floor coverings, cleaning products, varnishes and others that emit volatile organic compounds (Kim, 2010; Katsoyiannis et al, 2008). Ventilation effectiveness and personal exposure to pollutants released at floor level in rooms with air heating and floor heating combined with mechanical ventilation was evaluated by our previous studies (Jurelionis et al, 2016). The aim of this study was to evaluate and compare personal exposure of the occupants to airborne pollutants emitted at the floor level in rooms with three different heating systems combined with mixing ventilation. 2 METHODS Computational fluid dynamics (CFD) software Flovent (Mentor Graphics, USA, 2015) was used to predict contaminant dispersion in the three-dimensional room with dimensions of m and ambient conditions of +20 C (Figure 1). Six cases of air heating, radiator heating and floor heating combined with two types of mixing ventilation were created for the numerical analysis. Low Reynolds number LVEL K-epsilon turbulence model with Double Precision Solver (DPS) was selected for steady-state numerical simulations. Figure 1. Room geometry used in the CFD simulation with air exhaust and two air supply systems, pollution source, and heated dummy.
3 One wall of the solution domain was imitating outside wall of the room. Temperature difference between cold wall and other walls of the solution domain was 3 C. Floor surface temperature was set to +24 C in cases with floor heating. The boundaries for cold wall and warm floor were defined as fixed temperature surfaces, and therefore radiation from these surfaces was estimated without the change of the surface temperatures due to absorbed radiation. Two types of mixing ventilation patterns (four-way air supply and high level wall grille air supply) was chosen for the numerical simulation as commonly used in modern buildings. Air change rate was set to 2 ach. Air supply diffusers ( m) were simulated as the uniform air jets by using the Box method (Nielsen PV, 1992). High level wall grille ( m) was simulated as a fixed flow opening with the free area ratio of Air exhaust diffuser ( m) was simulated as in-ceiling openings with the free area ratio of 0.5. Supply air temperature was set 5 C higher than the set-point room air temperature in cases when air heating was used. Supply air temperature was set as equal to room air temperature in cases with floor heating and radiator heating. Simplified geometry of heated dummy (1.7 m 2 surface area) was used to simulate convective and radiative heat flux from the dummy. The distance between the dummy and the wall was 0.2 m. Heated dummy located in the supply air side was used to estimate the effects of convection generated by the occupant as well as personal exposure. The pollution source was simulated as floor air inlet with very low air velocity equal to 0.01 m/s in the middle of the room. Properties of the pollution source were selected similar to benzene: molecular weight 78 g/mol, diffusivity in primary fluid 8.8e 06 m 2 /s, viscosity 7.43e 06 Ns/m 2. It was considered that pollution generation at the floor level was the mixture of air and benzene at 80,000 ppm concentration at air flow rate of 0.01 l/s. Pollution concentration in the supply air was set to 0 ppm. Cartesian grid was used with the number of grid cells varying in the range from 100,000 to 150,000 depending on the air distribution scheme. The density of the grid was increased close to the air supply equipment and localized close to the heated dummy. 3 RESULTS CFD simulations were performed for 6 overall cases. In Figures 2 and 3, the sections of the model at the height of 0.1 m above the floor and through the heated dummy are presented for each case with different heating types and different air supply patterns. Vertical air temperature gradient in cases with radiator heating, air heating and floor heating was 0.69, 0.85 and 0.06 C/m respectively. Air temperature simulation results are not presented due to limitations on the length of the article. CFD simulations showed that dispersion of near floor pollutants in the room in cases with radiator heating and air heating are influenced by convective flows generated by the occupant. In these cases pollutants were transported towards thermal dummy and this means that personal exposure was higher. In cases with floor heating pollutant flow was directed to the opposite side to the cold wall. This affect influenced personal exposure of the dummy and it was lower.
4 A B Radiator heating Air heating Floor heating Figure 2. CFD prediction results of floor released contaminant dispersion in the room (high level wall grille air supply); A the section of the model at the height of 0.1 m above the floor; B the section of the model through the heated dummy
5 A B Radiator heating Air heating Floor heating Figure 3. CFD prediction results of floor released contaminant dispersion in the room (inceiling four-way air supply diffuser); A the section of the model at the height of 0.1 m above the floor; B the section of the model through the heated dummy 4 DISCUSSION In this study human respiration was not considered, in order to compare the results with experiment which were carried previously. The point source of pollutants was selected for this study. The patterns of pollutant dispersion between the cases with pollutants generated by larger surfaces and single small pollution sources were tested and were similar in both cases.
6 5 CONCLUSIONS CFD simulations showed that personal exposure to pollutants released at floor level depends on heating type and is higher in cases with radiator heating and air heating. Positive effect of floor heating on personal exposure was observed. 6 ACKNOWLEDGEMENT This work was supported by the European Social Fund under the Global Grant Scheme (Project No. VP1-3.1-ŠMM-07-K ). 7 REFERENCES Feist W., Schnieders J., Dorer V., and Haas A Re-inventing air heating: Convenient and comfortable within the frame of the Passive House concept. Energy Build, 37, Golkarfard V. and Talebizadeh P Numerical comparison of airborne particles deposition and dispersion in radiator and floor heating systems. Advanced Powder Technology, 1; 25(1): Gökhan S., Nuhsin K Numerical analysis of air flow, heat transfer, moisture transport and thermal comfort in a room heated by two-panel radiators. Energy and Buildings, 43, Heiselberg P Room air and contaminant distribution in mixing ventilation. ASHRAE Transactions, 102 (2) Jurelionis A., Gagytė, L., Šeduikytė L., Prasauskas T., Čiužas D. and Martuzevičius D Combined air heating and ventilation increases risk of personal exposure to airborne pollutants released at the floor level. Energy Build, doi: /j.enbuild Jurelionis A., Stasiuliene, L., Prasauskas T. and Martuzevičius D Dispersion of indoor air pollutants emitted at nea-floor levels in rooms with floor heating and mixing ventilation. Indoor and Build Environment, doi: / X Katsoyiannis A, Leva P, and Kotzias D VOC and carbonyl emissions from carpets: A comparative study using four types of environmental chambers. J Hazard Mater, 4/1; 152(2): Kim S Control of formaldehyde and TVOC emission from wood-based flooring composites at various manufacturing processes by surface finishing. J Hazard Mater, 4/15; 176(1 3): Krajčík M., Simone A., and Olesen B.W Air distribution and ventilation effectiveness in an occupied room heated by warm air. Energy Build, 55, Licina D, Melikov A, Pantelic J, Sekhar C, and Tham KW Human convection flow in spaces with and without ventilation: personal exposure to floor-released particles and cough-released droplets. Indoor Air, doi: /ina Mundt E Non-buoyant pollutant sources and particles in displacement ventilation. Build. Environ, Nielsen PV. Description of supply openings in numerical models for room air distribution. ASHRAE Transact 1992,
The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa
Aalborg Universitet The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa Published in: COLD CLIMATE HVAC 2009 Publication date: 2009
More informationShuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan
INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon
More informationTHE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS
THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS Panu Mustakallio 1, Arsen Melikov 2, Marcin Duszyk 2, Risto Kosonen 1 1 Oy Halton Group Ltd., Helsinki, Finland. 2 International
More informationAir Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation
Downloaded from orbit.dtu.dk on: Mar 02, 2018 Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation Wu, Xiaozhou; Fang, Lei; Olesen, Bjarne
More informationThe Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *
Journal of Environmental Protection, 2013, 4, 638-646 http://dx.doi.org/10.4236/jep.2013.46073 Published Online June 2013 (http://www.scirp.org/journal/jep) The Research of Performance Comparison of Displacement
More informationHealthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland
Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0141 ISBN: 978-83-7947-232-1 Prediction of exhaust gas stagnation in common corridor of apartments with gas water heater Takuro Nakamura
More informationImpact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams
Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Risto Kosonen 1, Arsen Melikov 2, Boryana Yordanova 2 and Lyuben Bozkhov 2 1 Halton Oy 2 International
More informationNumerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China
Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room Yanli Ren 1 ; Deying Li 2 ; Yufeng Zhang 1 1 School of Environment Science and Engineering, Tianjin University, Tianjin 300072,
More informationTo describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June
Thermal comfort with radiant and convective cooling systems Risto Kosonen Halton Oy and Aalto University risto.kosonen@halton.com Panu Mustakallio Halton Oy The difference in thermal conditions between
More informationMODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic
Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING Vladimír Zmrhal 1, Jan Hensen 2 and František Drkal 1 1
More informationModeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room
Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Y. Momoi 1, K. Sagara 1, T. Yamanaka 1 and H. Kotani 1 1 Osaka University, Graduate School of Eng., Dept.
More informationAalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li
Aalborg Universitet Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li Published in: Clima 2010 : 10th Rehva World Congress Publication date:
More informationAIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY
Proceedings of BS5: 4th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 5. AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN
More informationEXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION
Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Liu Jing 1, Yoshihiro Aizawa 2, Hiroshi Yoshino 3 1 School of Municipal
More informationNumerical Simulation of Ventilation Efficiency in Commercial Kitchen
Numerical Simulation of Ventilation Efficiency in Commercial Kitchen Yasushi Kondo 1, Shin-ichi Akabayashi 2, Osamu Nagase 3 and Akihiko Matsuda 4 1 Dept of Architecture, Musashi Institute of Technology,
More informationAmerican Society of Heating, Refrigerating and Air-Conditioning Engineers
Flow Pattern and Thermal Comfort in Office Environment with Active Chilled Beams Journal: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Manuscript ID: Draft Publication:
More informationHealthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland
Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0237 ISBN: 978-83-7947-232-1 Evaluation of the Thermal Microenvironment, Generated in a Hospital Bed with Localized Ventilation System
More informationResidential ventilation concepts based on the idea of displacement airflow distribution
A strategy for reducing energy demand Student: Aris Gkitzias (I.D:4180380) Mentors: Dr. Regina Bokel, Ir. John van der Vliet MSc graduation project Department of Building Technology, faculty of architecture
More informationOptimisation of cooling coil performance during operation stage for improved humidity control
Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 741 Optimisation of cooling coil performance during operation stage for improved humidity control S.C. Sekhar * and L.T. Tan National
More informationThermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia
IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia To cite this article: N A Malek
More informationSpace Air Diffusion II
MEBS6008 Environmental Services II http://me.hku.hk/bse/mebs6008/ Space Air Diffusion II Ir. Dr. Sam C. M. Hui Visiting Assistant Professor Department of Mechanical Engineering The University of Hong Kong
More informationSandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2
A CFD Analysis of Smoke Movement in Steel Industry Sheds Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2 Mechanical Dept. Dr.Babasaheb Ambedkar College of Engineering and Research,
More informationpower-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect
A Numerical Investigation on the Effect of Operation Control of a Multi-Split Air-Conditioning System on Indoor Thermal Environment H. Matsunaga 1,*, S. Iizuka 1, M. Okumiya 1, G. Yoon 2, and H. Niwa 3
More informationCOMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS
COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS Risto Kosonen, Panu Mustakallio Arsen Melikov 2, Marcin Duszyk 2 Oy Halton Group Ltd., Helsinki, Finland. 2 International
More informationSTUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER
STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER WULANDANI, D., K. ABDULLAH, E. HARTULISTIYOSO Department of Agricultural Engineering, Faculty of Agricultural
More informationCHAM Case Study Numerical Simulation of a Air-to-air Cross-flow Heat Exchanger
CHAM Limited Pioneering CFD Software for Education & Industry CHAM Case Study Numerical Simulation of a Air-to-air Cross-flow Heat Exchanger PHOENICS demonstration case A CFD model of a cross-flow heat
More informationNumerical study of heat pipe application in heat recovery systems
Numerical study of heat pipe application in heat recovery systems *Song Lin, John Broadbent, Ryan McGlen Thermacore Europe, 12 Wansbeck Business Park Ashington, Northumberland NE3 QW, UK E-mail: song.lin@thermacore.com
More informationDESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background
DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS By Yuguo Li and SARS Busters * Background The hospital care workers (HCWs) have been the most severely affected professions during the SARS epidemics in
More informationDisplacement Ventilation
Displacement Ventilation Displacement Ventilation Displacement Ventilation vs. Dilution Ventilation Characteristics Design Considerations Layout and Selection Product Overview Casino Case Study Dilution
More informationA Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space
Available online at www.sciencedirect.com Procedia Engineering 31 (2012) 734 738 International Conference on Advances in Computational Modeling and Simulation A Numerical study of the Fire-extinguishing
More informationComparison of Thermal Comfort by Radiant Heating and Convective Heating
Journal of Engineering, Project, and Production Management 2015, 5(1), 26-35 Comparison of Thermal Comfort by Radiant Heating and Convective Heating Shigeru Imai 1 and Shoichi Kojima 2 1 MSc Student, Department
More informationThe impact of thermal loads on indoor air flow
The impact of thermal loads on indoor air flow Risto Kosonen 1, Maija Virta 1 and Arsen Melikov 2 1 Halton Oy 2 International Center for Indoor Environment and Energy, Department of mechanical Engineering,
More informationComputer Models For Fire and Smoke
Computer Models For Fire and Smoke Model Name: JASMINE Version: 3.1 Classification: Very Short Description: CFD or Field A CFD or field model for predicting consequences of fire to evaluate design issues
More informationCompression of Fins pipe and simple Heat pipe Using CFD
Compression of Fins pipe and simple Heat pipe Using CFD 1. Prof.Bhoodev Mudgal 2. Prof. Gaurav Bhadoriya (e-mail-devmudgal.mudgal@gmail.com) ABSTRACT The aim of this paper is to identify the advantages
More informationHealthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland
Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0320 ISBN: 978-83-7947-232-1 The Analysis of the Air Velocity Distribution above the Trench Heater with Natural Convection Mariusz
More informationStudy of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background
Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Siddharth Jain, Yogesh Deshpande, Atul Bokane, Arun Kumar Santharam, and Deepak Babar, Halliburton Abbreviations: Computational
More informationThermal Comfort with Convective and Radiant Cooling Systems
Proceedings of 9 th Windsor Conference: Making Comfort Relevant Cumberland Lodge, Windsor, UK, 7-10 April 2016. Network for Comfort and Energy Use in Buildings, http://nceub.org.uk Thermal Comfort with
More informationIMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER
2000 Elsevier Science Ltd. All rights reserved. Air Distribution in Rooms, (ROOMVENT 2000) Editor: H.B. Awbi 731 IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER
More informationNew Convection Correlations for Cooled Ceiling Panels in Room with Mixed and Stratified Airflow
2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in HVAC&R Research, Vol. 12, No. 2, April 2006. For personal use only. Additional distribution
More informationDFE T ECHNOLOGY. At Conceptronic, the design and management process for reflow soldering systems is called Dynamic Flow Engineering, or DFE.
DFE T ECHNOLOGY As components become smaller, component mixes become more diverse, and board densities continue to increase, the processes of packaging, interconnection, and assembly are challenging the
More informationNumerical analysis of diffuse ceiling ventilation and its integration with a radiant ceiling system
Zhang, C., Heiselberg, P.K., Chen, Q., and Pomianowski, M. 2017. Numerical analysis of diffuse ceiling ventilation and its integration with a radiant ceiling system, Building Simulation, 10(2): 203-218.
More informationNumerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length
Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length HEIMO WALTER Institute for Thermodynamics and Energy Conversion Vienna University
More informationComputational simulation of road tunnel fire protection by sprinklers
European Journal of Environmental and Safety Sciences 2014 2(2): 48-52 ISSN 1339-472X European Science and Research Institute (Original Research Paper) Computational simulation of road tunnel fire protection
More informationThe Experimental Validation of Numerical Modeling of the Air Distribution in the Indoor Ice Rink Arena
Proceedings of the World Congress on Mechanical, Chemical, and Material Engineering (MCM 2015) Barcelona, Spain July 20-21, 2015 Paper No. 276 The Experimental Validation of Numerical Modeling of the Air
More informationSTACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING
STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose
More informationNUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM
, Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,
More informationHeat transfer and heating rate of food stuffs in commercial shop ovens
Sādhanā Vol. 32, Part 5, October 2007, pp. 535 544. Printed in India Heat transfer and heating rate of food stuffs in commercial shop ovens P NAVANEETHAKRISHNAN,PSSSRINIVASAN and S DHANDAPANI Department
More informationSprinklers Modeling for Tunnel Road Fire Fighting
Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and
More informationInvestigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings
Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Melanie T. Fauchoux, PhD Student University of Saskatchewan http://www.engr.usask.ca/dept/mee melanie.fauchoux@usask.ca
More informationINFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS
INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS Staņislavs GENDELIS, Andris JAKOVIČS Laboratory for mathematical modelling of environmental
More informationAnalysis of ventilation system for a microwave assisted drying unit
Analysis of ventilation system for a microwave assisted drying unit ADRIAN-GABRIEL GHIAUS 1, DANIEL POPESCU 2 and CALIN CIUFUDEAN 3 1 Thermal Engineering Department Technical University of Civil Engineering
More informationCFD Analysis of Co-current Spray Dryer with Swirler at Air Inlet
CFD Analysis of Co-current Spray Dryer with Swirler at Air Inlet Bharath G Wadone #1, Dr. G Manavendra *2 # 1 PG Student: Dept. of Mechanical Engineering, *2 Associate Professor: Dept. of Mechanical Engineering,
More information,Chaojian He6, f. School of Guangxi University, Nanning , China.
5th International Conference on Environment, Materials, Chemistry and Power Electronics (EMCPE 2016) The Research on Running Characteristics of A New Type of Radiant Air Conditioning Combined with Fresh
More informationComparison of radiant and convective cooling of office room: effect of workstation layout
Downloaded from orbit.dtu.dk on: Apr 27, 2018 Comparison of radiant and convective cooling of office room: effect of workstation layout Bolashikov, Zhecho Dimitrov; Melikov, Arsen Krikor; Rezgals, Lauris;
More informationCHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way
1 CHAPTER I INTRODUCTION In the modern life, electronic equipments have made their way in to practically every part, which is from electronic gadgets to high power computers. Electronic components have
More informationImproving Single-Sided Room Ventilation by Using a Ceiling Fan
Improving Single-Sided Room Ventilation by Using a Ceiling Fan Ahmed Rizk, Mustafa Elwan, Ehab Mouris To cite this version: Ahmed Rizk, Mustafa Elwan, Ehab Mouris. Improving Single-Sided Room Ventilation
More informationStudy of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan
Open Journal of Fluid Dynamics, 2017, 7, 205-218 http://www.scirp.org/journal/ojfd ISSN Online: 2165-3860 ISSN Print: 2165-3852 Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke
More informationHOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?
HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? Corresponding author: Jasmin Geppert University of Bonn Household and Appliance Technology Section Nussallee 5 D-53115 Bonn E-Mail: haushaltstechnik@uni-bonn.de
More informationTHERMAL PERFORMANCE ASSESSMENT OF GREENHOUSE SOLAR DRYER UNDER PASSIVE MODE
THERMAL PERFORMANCE ASSESSMENT OF GREENHOUSE SOLAR DRYER UNDER PASSIVE MODE Pushpendra Singh 1, Vipin Shrivastava 2 1,2 Mechanical Engineering Department, Lakshmi Narain College of Technology (India) ABSTRACT
More informationEFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING
EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING DA Hindoliya and SC Mullick * Centre for Energy Studies, Indian
More informationYan Xue 1 and Qingyan Chen 2,1* Abstract
1 2 3 4 5 6 7 8 9 1 11 12 13 14 15 16 17 18 19 2 21 22 23 24 25 26 27 28 29 3 31 32 33 34 35 36 37 38 Xue, Y. and Chen, Q. 214. Influence of floor plenum on energy performance of buildings with UFAD systems,
More informationA Study of Drying Uniformity in a New Design of Tray Dryer
52, Issue 2 (2018) 129-138 Journal of Advanced Research in Fluid Mechanics and Thermal Sciences Journal homepage: www.akademiabaru.com/arfmts.html ISSN: 2289-7879 A Study of Drying Uniformity in a New
More informationOIL AND GAS INDUSTRY
FIRED HEATER DESIGN This case study demonstrates the implementation of an API 560 fired heater compound component in Flownex. It also shows how Flownex has been used during the process design and preliminary
More informationTunnel Fire Dynamics and Evacuation Simulations
Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation
More informationAspirating Gas Detection CFD Modelling Predicts Application Performance
Aspirating Gas Detection CFD Modelling Predicts Application Performance Yun Jiang Xtralis, Bentleigh East, Australia Claudio Groppetti Xtralis, Avon, MA, USA Abstract Historically gas detection has utilized
More informationNumerical analysis of diffuse ceiling ventilation and its integration with a radiant ceiling system
Aalborg Universitet Numerical analysis of diffuse ceiling ventilation and its integration with a radiant ceiling system Zhang, Chen; Heiselberg, Per Kvols; Chen, Qingyan; Pomianowski, Michal Zbigniew Published
More informationVENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING
VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING Rebeca Barbosa 1, Martin Barták 1, Jan L. M. Hensen 1, 2, Marcel G. L. C. Loomans 2 1 Czech Technical
More informationLOW-NOX BURNER RETROFIT CHALLENGE
LOW-NOX BURNER RETROFIT CHALLENGE By Craig Lieb Applications Engineer Zeeco, Inc. Rutland, UK Ryan Roberts Project Engineering Manager Zeeco, Inc. Broken Arrow, OK, U.S.A. Ryan Roberts has more than 20
More informationUsing FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels
Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Jack R. Mawhinney, P. Eng., FSFPE Javier J. Trelles, Ph.D. Authors & acknowledgement J. R. Mawhinney
More informationOPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE
OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE 1 RU ZHOU, 2 WEI ZHANG 1 School of Urban Construction and Safety Engineering, Nanjing University of Technology, Nanjing
More informationTHE EFFECTS OF LEAKAGES IN ROOFS WITH VENTILATED AIR LAYERS - A CFD APPROACH. Zbynek Svoboda
THE EFFECTS OF LEAKAGES IN ROOFS WITH VENTILATED AIR LAYERS - A CFD APPROACH Zbynek Svoboda Department of Building Structures, Czech Technical University, Thakurova 7, 166 29 Prague, Czech Republic, e-mail:
More informationVertical Distribution of Air Temperatures in Heated Dwelling Rooms
Vertical Distribution of Air Temperatures in Heated Dwelling Rooms Ondrej Sikula University of Technology Brno, Brno Corresponding email: sikula.o@fce.vutbr.cz SUMMARY The paper presents an experimental
More informationVariable Air Volume with Indoor Air Quality
Variable Air Volume with Indoor Air Quality and a Cure for the Spread of the Airborne Flu Virus January 11, 2017 Dinner Meeting Golden Gate ASHRAE Chapter Presented By: Thomas S. Weaver, P.E., Member ASHRAE
More informationUse of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality
Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality Arsen K. Melikov 1,*, Marcin Duszyk 1, Barbora Krejciríková 1,2, Tomonori Sakoi 3, Jan
More informationFIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability
Proceedings of the International Conference in Dubrovnik, 15-16 October 2015 FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability Johan Anderson a, Lars Boström a, Robert Jansson
More informationAN ANALYSIS OF THE ACTUAL THERMAL PLUMES OF KITCHEN APPLIANCES DURING COOKING MODE
AN ANALYSIS OF THE ACTUAL THERMAL PLUMES OF KITCHEN APPLIANCES DURING COOKING MODE R Kosonen 1,*, H Koskela 2 and P Saarinen 2 1 Halton Oy, Haltonintie 1-3, 474 Kausala, Finland 2 Finnish Institute of
More informationHealthy Buildings 2017 Europe July 2 5, 2017, Lublin, Poland. Evaluation of task air conditioning system with convection, conduction, and radiation
Healthy Buildings 2017 Europe July 2 5, 2017, Lublin, Poland Paper ID 0009 ISBN: 978-83-7947-232-1 Evaluation of task air conditioning system with convection, conduction, and radiation Misa Imazu 1,*,
More informationCFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5
IJAET International Journal of Application of Engineering and Technology ISSN: 2395-3594 Vol-1 No.-2 CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys
More informationVentilation Strategies for Healthy IEQ and Energy Efficiency
Ventilation Strategies for Healthy IEQ and Energy Efficiency Lars Ekberg Energy Management AB A Chalmers Industriteknik Company The purpose of ventilation + - Pollution Climate Heat Pollution 2 Examples
More informationA STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET
A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET I. S. Hwang and Y. L. Lee Department of Mechanical Engineering, Kongju National University, Korea E-Mail: ylee@kongju.ac.kr ABSTRACT
More informationStudy of air circulation inside the oven by computational fluid dynamics.
The 8 th International TIChE Conference (ITIChE 2018) "Designing Tomorrow Towards Sustainable Engineering and Technology" @A-ONE The Royal Cruise Hotel Pattaya, Thailand, November 8-9, 2018 Study of air
More informationConsiderations in the Design of Smoke Management Systems for Atriums
Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke
More informationShalaby Institute of Fire Protection Heyrothsberge, Germany.
International Water Mist Conference November 3-4, 2010, Prague, Czech Republic The Influence of Droplet Size of Water Mist on Extinguishment Fire Plume Dr.Hemdan Shalaby Institute of Fire Protection Heyrothsberge,
More informationComputerized Simulation of Automotive Air-Conditioning System: A Parametric Study
www.ijcsi.org 787 Computerized Simulation of Automotive Air-Conditioning System: A Parametric Study Haslinda Mohamed Kamar 1, Nazri Kamsah 2 and Mohd Yusoff Senawi 3 1 Department of Thermo-Fluid, Universiti
More informationNumerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand
Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand Mohammed Mutafi 1, Mohammad Nasif 1*, William Pao 1 and
More informationRADIATION BLOCKAGE EFFECTS BY WATER CURTAIN
, Volume 6, Number 4, p.248-254, 04 RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN C.L. Choi Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Water
More informationMinimal Invasive Ventilations Systems with Heat Recovery for Historic Buildings
Minimal Invasive Ventilations Systems with Heat Recovery for Historic Buildings Rainer Pfluger #1, Kai Längle #2 # Energy Efficient Buildings, University of Innsbruck Technikerstr. 13, 6020 Innsbruck,
More informationHeat Transfer in Evacuated Tubular Solar Collectors
Heat Transfer in Evacuated Tubular Solar Collectors Graham L. Morrison, Indra Budihardjo and Masud Behnia School of Mechanical and Manufacturing Engineering University of New South Wales Sydney 2052 Australia
More informationInternational Forum on Energy, Environment Science and Materials (IFEESM 2015)
The Comparison and Analysis of Humidity Environment between Floor and Ceiling Radiant Cooling Systems that Combined with Displacement Ventilation Kai SUN 1 a *, Chuan-hui ZHOU 1 1 College of Urban Construction,
More informationDevelopment of Rotating Tray Dryer and Study of the Hot Air Flow Pattern with Computational Fluid Dynamics
1669 A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 43, 2015 Chief Editors: Sauro Pierucci, Jiří J. Klemeš Copyright 2015, AIDIC Servizi S.r.l., ISBN 978-88-95608-34-1; ISSN 2283-9216 The Italian
More informationAR/IA/UP 241 Lecture 5: Psychrometrics
Faculty of Architecture and Planning Thammasat University AR/IA/UP 241 Lecture 5: Psychrometrics Author: Asst. Prof. Chalermwat Tantasavasdi 1. Definition of Psychrometric Chart The word psychrometry is
More informationRole of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview
International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com
More informationEngineering Simulation in Built Environment and Civil Engineering Projects
Engineering Simulation in Built Environment and Civil Engineering Projects Fluid Dynamics Simulation Mark Owens ANSYS UK Ltd 2010 ANSYS, Inc. All rights reserved. 1 ANSYS, Inc. Proprietary Fires and Smoke
More informationThermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating
Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating Vladimír Zmrhal Czech Technical University in Prague, Faculty of Mechanical Engineering Corresponding email: Vladimir.Zmrhal@fs.cvut.cz
More informationAnalysis of the influence of open door size on fire smoke diffusion law in protective engineering
Analysis of the influence of open door size on fire smoke diffusion law in protective engineering Abstract Zheli Xing a, Jinfeng Mao b, Chaofeng Li c and Jin Zhou d PLA University of Science and Technology,
More informationNUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro
Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT Z. Stevanovic 1, T. Valentina 1, N. Kadic 1, Z. Markovic 1,
More informationPART 1 THERMAL & MECHANICAL ACTIONS. DIF SEK Part 1: Thermal & Mechanical Actions 0/ 50
DIF SEK PART 1 THERMAL & MECHANICAL ACTIONS DIF SEK Part 1: Thermal & Mechanical Actions 0/ 50 Background of the RFCS Project DIFISEK+ This project is funded by the European Commission in the frame of
More information4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)
4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao
More informationModeling and Simulation of Axial Fan Using CFD Hemant Kumawat
Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat Abstract Axial flow fans, while incapable of developing high pressures, they are well suitable for handling large volumes of air at relatively
More informationRESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION
RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION DL Bohac * Center for Energy and Environment, Minneapolis, MN USA ABSTRACT Extensive
More information