1 Installation Operation Maintenance DUCTABLE WATER UNIT FWD

2 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice in the installation, putting into service, operation and periodic maintenance by the user of FWD units. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified service technician should be employed through the medium of a maintenance contract with a reputable service company. Warranty Warranty is based on the general terms and conditions of the constructor. The warranty is void if the equipment is modified or repaired without the written approval of the constructor, if the operating limits are exceeded, or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance, or failure to comply with the manufacturer's instructions, is not covered by the warranty obligation. If the user does not conform to the rules of chapter "Maintenance", it may entail cancellation of warranty and liabilities by the constructor. Reception When the unit arrives on site, check it has not been damaged in any way during transport. If damage is observed, or even merely suspected, notify the carrier within 24 hours by registered letter. Notify the local Trane Sales office at the same time. The unit should be totally inspected within 3 days of delivery. If damage is observed, notify the last carrier by registered letter and notify the local sales office. General information About this manual Warnings and Cautions appear at appropriate places in this instruction manual. Your personal safety and the proper operation of this machine require that you follow them carefully. Société Trane assumes no liability for installations or servicing performed by unqualified personnel. About this unit These FWD units are assembled, pressure tested, dehydrated, charged with refrigerant and oil, and factory tested, before shipment. The information contained in this manual concerns FWD units. American Standard Inc

3 Contents General Information 2 Foreword 2 Warranty 2 Reception 2 Introduction 2 Installation 4 Ceiling installation 6 Installation on the ground 6 Condensate drainage 7 Electrical connections 7 Duct connections 8 Operation / Maintenance 9 Choice of fan speed 9 Initial checks 9 Maintenance recommendations 9 Maintenance 10 Removal of the fan motor unit 10 3

4 Installation Introduction Caution. Read this manual carefully before starting to install the system. Components supplied with the unit - 2 corner brackets to suspend the unit from the ceiling Electrical connections - The electrical wiring and connections must comply with local electricity legislation. - Check the electrical characteristics on the name plate correspond to the grid s characteristics. Warning. Never open the electrical panel without first disconnecting the power supply. There is a risk of electrocution! Description of the unit The FWD unit is a slim discharge cabinet unit for installation in false ceilings, lofts and ventilation spaces. It is designed for horizontal installation with discharge via a duct (see selection catalogue for the available static pressure). The unit s structure consists of unpainted completely insulated galvanised steel panels. Figure 1 : Description ➀ ➁ ➂ 1 Hot water coil 2 Fan unit 3 Control / power cabinet 4Water inlet and outlet screw-in connections ➃ 4

5 Installation TECHNICAL DATA FWD Power supply (V/Ph/Hz) 230/1/50 Capacities Cooling capacity on water (1) (kw) 5,2 8, ,8 30,1 Heating capacity on water (2) (kw) 6,3 11,9 18,9 20,9 38,2 Fan motor (type) 2 x direct drive centrifugal Fan power input (3) (kw) 0,23 0,46 0,65 1,04 1,51 Current amps(3) (A) 1,1 2,2 3,1 4,7 5,5 Start-up amps (A) 3,2 5,5 9,3 14,1 16,5 air flow minimum (m3/h) nominal (m3/h) maximum (m3/h) Main coil Water entering/leaving connections (type) ISO R7 rotating female (Dia) 3/4" 3/4" 1"1/2 1"1/2 1"1/2 Electric heater (accessory for blower only) Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50 Heating capacity (kw) 2/ Hot water coil (accessory for blower only) Heating capacity (4) (kw) 6, ,4 22,4 34,5 G2 filter (filter box accessory) Quantity Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586x421x8 586x621x8 G4 filter (filter box accessory) Quantity Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586x414x48 586x614x48 Condensate pump (accessory) (type) Centrifugal Water flow - lift height (l/h - mm) Not available for FWD30 and FWD45 Sound level (L/M/H speed) Sound pressure level (5) (db(a)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58 Sound power level (5) (db(a)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68 Unit dimensions Width x Depth (mm) 890 x x x x x 1090 Height (mm) Shipped unit dimensions Width x Depth (mm) 933 x x x x *1133 Height (mm) Weight (kg) Colour galvanised steel Recommended fuse size Unit alone (am/gi) (A) 8/16 8/16 8/16 8/25 8/25 Unit with electric heater (gi) (A) 16 (2kW), 25 (4kW) 40 (230V), 3*16 (400V) 3*20 3*25 3*25 (1) Conditions: Water entering/leaving temperature: 7/12 C, Air inlet temperature 27/19 C DB/WB - Nominal air flow (2) Conditions: Water entering/leaving temperature: 50/45 C,,Air inlet temperature 20 C DB - Nominal air flow (3) At high speed with nominal air flow. (4) Water entering/leaving temperature 90/70 C, air inlet temperature 20 C DB, Nominal air flow. (5) A rectangular glass wool duct 1m50 long is placed on the blower.the measurement is taken in the room containing the blower unit. Heat exchanger operating limits: FWD : "water temperature: max 100 C "absolute service pressure: min 1 bar / max 11 bars Accessories - Hot water coil: "water temperature: min. +2 C / max. 100 C "absolute service pressure: min 1 bar / max 11 bars 5

6 Installation Ceiling installation Preparation of the ceiling and installation of the unit A template for drilling into the ceiling to fix the threaded rods is printed on the cover of the unit s packaging. The angle brackets can also be used to determine the drilling hole distances. Access must be provided on the water connection end to facilitate installation, maintenance and access to the cabinet. Four 8 mm diam. threaded rods must be securely fixed into the building s slab or structure. Screw a nut A (Figure 2) sufficiently high onto each threaded rod. Put the angle brackets B in place by holding them using a second nut C. Make sure the angle brackets are level in both directions using the bottom nuts C. Once they are perfectly level insert the FWD unit and let the angle brackets support it. Use the top nuts A to tighten the unit against the corner brackets. It is possible to avoid using the 2 angle brackets B supplied with the unit and mount it using just the threaded rods D and the 2 shaped bars E. In both cases isolators can be installed between the nuts C and the angle brackets B or shaped bars E, to reduce transmission of vibrations to the building s structure. Warning. Since the condensate tray is sloped to facilitate flow of condensates, the unit must be positioned absolutely level in both directions. Installation on the ground The unit can be installed on the ground, but make sure the condensate can be drained properly. Ensure it is installed on vibration isolators and that it is level in both directions. Hydraulic connections It is easy to remove the electric cabinet to facilitate access to the hydraulic connections. Installation procedure - Define the layout of the lines so that they are as short as possible. - Limit pressure losses in the lines caused by pinching, too many bends and bending radii that are too small. - Connection of water inlet and outlet lines: The coil is connected by means of 3/4 female ISO R7 connectors. Warning. Limit the tightening torque applied to the connector nuts to prevent deformation of the piping and seals (risk of leaks). Figure 2 : Angle brackets B A 6

7 Installation Condensate drainage The unit must be perfectly horizontal in both directions. Connect the condensate tray outlet (outer diam. 20 mm). To ensure satisfactory condensate drainage, the drainage tube must be sloped 10. There must not be a condensate trap anywhere on the line. However a siphon can be provided to prevent outside air being drawn in by the indoor unit. If the pipe passes through a room, insulate it to prevent damage caused by condensation. We recommend polyethylene foam (6 mm thick). Condensate pump (accessory) If it is not possible to drain the condensates by gravity, a condensate pump can be installed as an accessory. Figure 3 : Connection of the condensate drain It can lift the condensates a maximum of 500 mm. For installation and connection of the condensate pump, refer to the submittals supplied with this accessory. Electrical connections If access to the electric cabinet is problematic, it can be moved a maximum distance of 500 mm. All wiring and earthing must comply with local standards. Caution a) Check the electrical characteristics on the unit s name plate. Make sure the wiring corresponds to the manufacturer s electrical diagram and local standards. b) Power up the units using one or more lines protected by a disconnect switch and fuses. c) Earth each unit. d) The wires must not touch the refrigerant lines, the motors or other moving parts. e) The manufacturer does not asuume any liability for problems caused by modifications to the unit s internal wiring. f) Tighten the terminals securely. Figure 4 : Moving the electric cabinet g) For the electrical connections, refer to the interconnection diagrams supplied with the device. 7

8 Installation Duct connections FWD units can be fitted directly with rectangular discharge and intake ducts. DIMENSIONS OF DUCT CONNECTIONS (INTAKE AND DISCHARGE) Sizes Length Width Warning.The pressure loss caused by the duct network and accessories must not exceed the unit s available static pressure (see selection chart). The air intake can be located at the back of the unit or underneath it. Filtering: vital to ensure the unit runs smoothly. No filters are supplied with the unit, but they can be ordered as accessories: - Filter box with EU2 filters to fix to the unit s intake. (behind or underneath). Figure 5 : Connection of ducts 8

9 Operation / Maintenance Choice of fan speed The FWD unit is delivered from the factory unwired. Please refer to the selection chart to select the static pressure according to the flowrate. Once the fan rotation speed has been determined, wire up the fan motor to the required speed using the supplied electrical diagrams. For use of temperature control, refer to the guide supplied with the thermostat. Initial checks - Check the electrical connections and water pipes are fixed securely. - Rotate the fan blades by hand to make sure it rotates freely. - Check that all nuts and bolts are tightened correctly. - Make sure the chilled water piping and the condensate drainage tube are properly insulated to avoid problems with condensation water flow. Maintenance recommendations (regular use) Failure to follow these instructions may cause damage to the unit. The frequency of maintenance will depend on the conditions of use of the unit and will be determined by regular inspections. When servicing the units, make sure also that the air passage through the coils (both internal and external) is clean, and free of dirt or debris. a) Clean the air filter by beating it and drawing air through it in the opposite direction to the passage of air. b) Check the condensate tubes are not obstructed. c) Rotate the fan blades and make sure they are not damaged. Clean them if necessary and check they are correctly aligned. d) Motor - check the wiring, and make sure the switches operate correctly. Replace any damaged components. e) Safety disconnection and electrical components - check they operate correctly. f) Water circuit - check there are no leaks. g) Tighten all the nuts and bolts. 9

10 Maintenance Figure 6 : Removal of the fan motor Unscrew the 4 screws fixing the panel and remove the panel. Unscrew the 4 screws fixing the intake support bracket and remove it. Unscrew the 4 screws fixing the base of the electrical cabinet by one turn. N.B.. The motor cables must be disconnected in the electrical cabinet. Push the cabinet upwards and move it enough to access the screws fixing the fan motor. Loosen the 4 screws fixing the condensate tray by a few turns. Unscrew the 2 x 2 screws (08) or 2 x 3 screws ( ) fixing the fan motor while holding it up. Take out the fan motor assembly, by pushing outwards on the bottom of the 2 side panels, taking care not to damage the insulation material. 10

11 Maintenance Symptom The unit is not powered up. The unit does not operate The fan motors do not operate. Room temperature too high Room temperature too low No air flow Heater limit thermostats activated (option). Possible cause A)The electric cabinet is not connected. B) The control circuit is not powered up. A) The thermostat is not controlling the unit. A) The electric motors are not powered up. B)The thermal protection of the motors has been cut. A) The unit is not operating. B) The thermostat settings are incorrect. C) Insufficient air flow D) Insufficient chilled water flow E) Chilled water temperature too high. F) The thermostat is not operating correctly. G) Heat load is greater than expected. A) The thermostat settings are incorrect. B) Electric heating is not operating (option). C) The hot water coil is not operating (option). D) Heat evacuation is greater than expected. A) Clogged filters. B) The fans are rotating the wrong way C) The air flow is obstructed. A) Air flow problem B) Thermostat incorrectly wired. C) Defective thermostat. Solution Check the unit s general disconnect switch is closed. Check the control circuit s fuse. Check the thermostat is plugged in (also refer to the thermostat s instruction manual). Check the fan motors are powered up and the fan circuit-breakers are reset. Check the motor winding resistance after resetting. Check the power supply voltage and the input current. See The unit is not operating. Check the set point. See No air flow Checked the chilled water flow. Check the gate valves and the water circuit. Check the unit s chilled water production. Refer to the thermostat s instruction manual. Check the zone s heat load (too much fresh air). Refer to the thermostat s instruction manual. 1) Check the heating elements. 2) Check the electrical power supplies. 3) In the event of an electric heater alarm, remove the cause and reset the heater limit thermostat. Check hot water is available. Check the surrounding heat evacuation points. Check the extent of infiltration of outside air. Clean or replace the recycling filters. Check and correct See No air flow. Check the heater limit thermostat connections. Replace the heater limit thermostat. 11

12 Safety recommendations To avoid accidents and damage, the following recommendations should be observed during maintenance and service visits: 1. The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter Installation. Always provide a pressure regulator. 2. Disconnect the main supply before any servicing on the unit. 3. Service work on the refrigeration system and the electrical system should be carried out only by qualified and experienced personnel. Maintenance contract It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty. Training The equipment described in this manual is the result of many years of research and continuous development. To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown. The manufacturer has a policy of continuous product improvement, and reserves the right to alter any details of the products at any time without notice. This publication is a general guide to install, use and properly maintain our products. The information given may be different from the specification for a particular country or for a specific order. In this event, please refer to your nearest office. For additional information, contact: Distributor / Installer stamp The Trane Company An American Standard Company For more information contact your local sales office or us at comfort@trane.com Literature Order Number Date 0201 Subersedes N40 IM 009 E Stocking Location Europe Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specifications without notice. Société Trane Société Anonyme au capital de Euros Siege Social: 1 rue des Amériques Golbey France Siret RSC Epinal B Numéro d identification taxe intracommunanutaire: FR

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4 Installation Operation Maintenance Ductable water unit FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Series R Air-Cooled Helical Rotary Liquid Chiller RTAD 085-180 (50Hz) Standard, Free Cooling and Heat Recovery models RTAD-SVX01F-E4 General information Foreword These

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance CGCL Air Cooled Water Chiller With Centrifugal Fans Sizes 200-250 - 300-350 - 400-450 - 500-600 To be used with the manual of SMM Module Reference L80IM022E CGCL-SVX01A-E4

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Voyager I Rooftop Units Cooling-only TSD/TSH 060 072 102 120 Reversible WSD/WSH 060 072 090 Gas-fired YSD/YSH 060 072 090 102 120 RT-SVX20D-E4 Original instruction Table

More information

AQUASTYLUS Chilled Water Fan Coil Convertible Type CFEA Series 50/60 Hz

AQUASTYLUS Chilled Water Fan Coil Convertible Type CFEA Series 50/60 Hz Installation Manual AQUASTYLUS Chilled Water Fan Coil Convertible Type CFEA Series 50/60 Hz 50 Hz Models Cooling Only CFEA 04 C0M1 CFEA 06 C0M1 CFEA 08 C0M1 CFEA 10 C0M1 CFEA 12 C0M1 CFEA 14 C0M1 CFEA

More information

Gas fired rooftops. Comfort all year round

Gas fired rooftops. Comfort all year round Gas fired rooftops Comfort all year round Gas fired rooftops YCD/YCH 060-075-085-100- 120-150-175-200-250 Cooling capacity 18 to 68 kw Gas heating modules : G205-G250-G350-G400- marked Voyager rooftops

More information

WINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G

WINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G WINDOW TECHNICAL GUIDE Single package Cooling only and Heat pump Models YO-YM 09-24 R407C YM 09 V6 G YM 09 V7 G YO 12-19-24 V6 G YO 12-19-24 V7 G YORK List of Contents Page 1 - Safety...2 2 - Unit packaging...2

More information

FUN I / FUN U FUN I MCP / FUN U MCP FUN V / FUN V MCP

FUN I / FUN U FUN I MCP / FUN U MCP FUN V / FUN V MCP OPERATION INSTRUCTIONS MANUAL DUCTED FAN COILS UNIT FUN I / FUN U FUN I MCP / FUN U MCP FUN V / FUN V MCP 1 CONTENTS 1. GENERAL... 3 2. INSTALLATION... 4 3. AIR CONNECTIONS... 5 4. WATER CONNECTIONS...

More information

USER S MANUAL AND INSTALLATION INSTRUCTIONS IMPORTANT

USER S MANUAL AND INSTALLATION INSTRUCTIONS IMPORTANT USER S MANUAL AND INSTALLATION INSTRUCTIONS P3BD Series 13 SEER Single Package Air Conditioner IMPORTANT Read this owner information to become familiar with the capabilities and use of your appliance.

More information

Split System, 18,000-48,000 Btu/h Underceiling Type MCC Series 50 Hz

Split System, 18,000-48,000 Btu/h Underceiling Type MCC Series 50 Hz Split System, 18,000-48,000 Btu/h Underceiling Type MCC Series 50 Hz Models Cooling Only MCC 518 ZB MCC 524 ZB MCC 530 ZB MCC 536 ZB MCC 048 ZB October 2007 General Information General Information Congratulations

More information

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1976-360 (1-02) PP TABLE OF CONTENTS 1. Warnings......................................................

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance RAUL Air Cooled Condensing Unit Sizes 190 260 300 350 400 450 500 600 700 800 To be used with the CH530 control module manual General information Foreword These instructions

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance / 015-060 Air-cooled scroll chillers and heat pumps 43-164 kw CG-SVX027B-GB Original instructions Table of Contents General Information...4 Model Number Description...6

More information

technical data Fan coil unit FWB small duct unit

technical data Fan coil unit FWB small duct unit technical data Fan coil unit FWB small duct unit TABLE OF CONTENTS FWB 1. Nomenclature ---------------------------------------------------------------------- 2 2. Features -----------------------------------------------------------------------------

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) 52" Belt Drive, Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance RTAF SE/HE/XE/HSS/HSE Air-cooled Helical-rotary chillers 300-1600 kw Sintesis chillers are part of the Ingersoll Rand EcoWise portfolio of products that are designed

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

Installation Instructions

Installation Instructions 40MBD Ducted Style Ductless System Sizes 09 to 48 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER RV Products Division INSTALLATION INSTRUCTIONS FOR 46413 SERIES PACKAGE AIR CONDITIONER 1. WARNINGS IMPORTANT NOTICE These instructions are for the use of qualified individuals specially trained and experienced

More information

Installation Instructions

Installation Instructions Split System Indoor Coils Installation Instructions! CAUTION: Read the Installation Instructions supplied with furnace/air handler and observe all safety requirements outlined in instructions and/or furnace/air

More information

LOW STATIC HYDRONIC DUCTED UNIT

LOW STATIC HYDRONIC DUCTED UNIT LOW STATIC HYDRONIC DUCTED UNIT PDWA-~AC SERIES PDWA(4R)-~-V-MEDC PDWA(4R)-~-V-MEEU PDWA(R)-~-V PDWA(R+1)-~-P Model cooling capacity( KW) at Medium Speed cooling capacity (KW) at Medium Speed cooling capacity

More information

CAR-MON DUST COLLECTORS SERIES 207, 2410, 3015

CAR-MON DUST COLLECTORS SERIES 207, 2410, 3015 INSTALLATION-OPERATION-MAINTENANCE CAR-MON DUST COLLECTORS SERIES 207, 2410, 3015 TEFC 3 phase motor Outlet duct Fan wheel housing Inlet duct connection After filter transition Optional after filter unit

More information

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer)

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) Galvanized Panel Fan IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble, install, operate

More information

INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER

INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER TABLE OF CONTENTS 1. Warnings...................................................... 3 2. Component Match-Up...........................................

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Airfinity Rooftop units Models IC - Cooling only IH - Heat pump 40-135 kw R410A Refrigerant RT-SVX056B-GB Original instructions Table of Contents General Information...4

More information

INSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP

INSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP TABLE OF CONTENTS 1. Warnings...2 2. Component Match-Up...2 3. Unit Depiction Figures...3 4. Blower Performance Data...5 5. General

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble,

More information

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP RV Products Division INSTALLATION INSTRUCTIONS FOR 46515 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP TABLE OF CONTENTS 1. Warnings.................................................. 2 2. Component

More information

Ceiling Concealed Fan-Coil Unit

Ceiling Concealed Fan-Coil Unit Installation & Maintenance Manual IM 745 Group: Fan-coil Part Number: 106333001 Date: November 2009 Ceiling Concealed Fan-Coil Unit Models: THC02, THC03, THC04, THC06, THC08, THC10, THC12 Table of Contents

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

51AKB / 51 AKC OWNER S MANUAL

51AKB / 51 AKC OWNER S MANUAL 51AKB / 51 AKC OWNER S MANUAL This manual applies to the following models 51AKB 009 51AKB 012 51AKC 009 51AKC 012 Read this instruction manual thoroughly before using the air conditioner. Control panel

More information

ARMITAGE CEILING FAN ITEM # MODEL #CC52WW5L. Español p. 17 ATTACH YOUR RECEIPT HERE. Purchase Date

ARMITAGE CEILING FAN ITEM # MODEL #CC52WW5L. Español p. 17 ATTACH YOUR RECEIPT HERE. Purchase Date ITEM #0807426 ARMITAGE CEILING FAN MODEL #CC52WW5L Harbor Breeze is a registered trademark of LF, LLC. All Rights Reserved. Español p. 17 ATTACH YOUR RECEIPT HERE Purchase Date 4009654 Questions, problems,

More information

Stainless Steel Chimney Extractor

Stainless Steel Chimney Extractor Stainless Steel Chimney Extractor User & Installation Guide LAM2404 LAMONA Appliances Dear Customer, Congratulations on your choice of a LAMONA domestic appliance which has been designed to give you excellent

More information

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL SWP (Models SWP08 through SWP20) OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

S Y D. HWP 35, 47, 58 (c/w EC Motor & UC7 Controller) Ducted Water Cooled R410A Packaged Air Conditioner. Installation & Maintenance

S Y D. HWP 35, 47, 58 (c/w EC Motor & UC7 Controller) Ducted Water Cooled R410A Packaged Air Conditioner. Installation & Maintenance HWP 35, 47, 58 (c/w EC Motor & UC7 Controller) Ducted Water Cooled R410A Packaged Air Conditioner Installation & Maintenance Fig. 1 Nomenclature Nomenclature e.g. H W P 3 5 C K Series Size Type S Y D GENERAL

More information

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES C US INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES Made in the USA by: Goodman Manufacturing Company, L.P. I0-240B 2550 North Loop West, Suite 400, Houston, TX 77092 www.goodmanmfg.com

More information

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features. Spot Cooling Systems, Inc. 120 Century Drive Suite 00 Carrollton, TX 7006 00-6-776 Operation Manual SCT1B and SCT1B Warning! Improper installation, adjustment, alteration, service, or maintenance can cause

More information

BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers

BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers Installation & Operations Manual for BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers 2 TABLE OF CONTENTS INTRODUCTION..... 4 STORE CONDITIONS........ 4 WARNING LABELS AND

More information

! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or

! The Caution Symbol (exclamation point) alerts you to a CAUTION, a safety or I&M NUMBER: 316-42-10-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

Instructions for installation and use English. More documents on: H B /09

Instructions for installation and use English. More documents on:  H B /09 TM Instructions for installation and use English EN More documents on: www.zodiac-poolcare.com H0538700.B - 2015/09 Read this manual carefully before installing, maintaining or repairing this appliance!

More information

S D HWP 77, 96. Ducted Water Cooled R410A Packaged Air Conditioner. Installation & Maintenance. Fig. 1 Nomenclature. Fig.

S D HWP 77, 96. Ducted Water Cooled R410A Packaged Air Conditioner. Installation & Maintenance. Fig. 1 Nomenclature. Fig. HWP 77, 96 Ducted Water Cooled R410A Packaged Air Conditioner Installation & Maintenance Fig. 1 Nomenclature Nomenclature e.g. H W P 7 7 C K Series Size Type S D GENERAL HWP - A general designation which

More information

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models:

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models: INSTALLATION, OPERATION AND MAINTENANCE MANUAL BHW MEDIUM STATIC PRESSURE DUCTABLE TYPE Models: 174 205 358 410 515 720 724 Cooling capacities from 3,1 to 25 KW Heating capacities from 4,5 to 55,5 KW Thank

More information

OPTIONAL SPRING MTG HANGING CENTRES WATER CONN'S: TWO BSP MALE. 19 mm (3/4") ELECTRICAL CONDUIT HOLES ACCESS PANEL OUT (WATER) IN 485 MOUNTING

OPTIONAL SPRING MTG HANGING CENTRES WATER CONN'S: TWO BSP MALE. 19 mm (3/4) ELECTRICAL CONDUIT HOLES ACCESS PANEL OUT (WATER) IN 485 MOUNTING HWP 117 225 Ducted Water Cooled R410A Packaged Air Conditioner Dimensions (mm) Fig. 1 HWP 117 60 1210 SPRING MOUNTING CENTRES 690 (HEIGHT = 370) FILTER BOX PROJECTION Net Weight 105 kg Installation & Maintenance

More information

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2 I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

BR342 Ducted Installation Instructions Australian Version Electronic Wall Control

BR342 Ducted Installation Instructions Australian Version Electronic Wall Control Australian Version Electronic Wall Control 1 Introduction The BR342 reverse cycle rooftop air-conditioner is designed for installation onto Recreational Vehicles (RV s) at the time of manufacture or as

More information

WATLOW ELECTRIC MFG CO. FIREBAR Screw Plug Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.

WATLOW ELECTRIC MFG CO. FIREBAR Screw Plug Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4. I&M NUMBER: 316-42-3-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to elements

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC AQB8J6WC_IM_E_25864 2006.4.4 3:29 PM Page 7 INSTALLATION MANUAL Indoor Unit AQB8J6WC AQB24J2WC Outdoor Unit UQB8J6WC UQB24J2WC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

Installer manual AG-WL10

Installer manual AG-WL10 LEK LED CLEAN TIMER OPERATION Installer manual Indoor unit air/air heat pump IHB GB 1637-1 331827 Table of Contents 1 Important information Safety information Read before starting the installation Electrical

More information

Installation Instructions

Installation Instructions Split System Indoor Coils Installation Instructions CAUTION: Read the Installation Instructions supplied with furnace/air handler and observe all safety requirements outlined in instructions and/or furnace/air

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 can be

More information

MAYFIELD CEILING FAN LISTED E ITEM # MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE.

MAYFIELD CEILING FAN LISTED E ITEM # MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE. Harbor Breeze is a registered trademark of LF, LLC. All Rights Reserved. ITEM #0331094 0331096 MAYFIELD CEILING FAN MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE Serial Number Purchase

More information

2

2 Installation Operation Commissioning Maintenance N 11.47A 2 3 1 g c e f b j d h a i 4 2 1 2 3 4 9 5 8 10 6 7 3 5 4 6 5 6 7 8 7 9 a b 10 8 11 12 9 13 14 15 2 16 1 17 a 10 18 rep.2 rep.1 rep.3 rep.4 19 11

More information

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL The Kitchen Cool by Hood Depot is a conditioned make up air unit design with flexibility, form and function kept in mind. Our unit offers a variety of configurations that allow the customer to customize

More information

ACN SMOKE INSTALLATION AND MAINTENANCE

ACN SMOKE INSTALLATION AND MAINTENANCE NovAx ACN SMOKE INSTALLATION AND MAINTENANCE 918149-0 English 918149-0 GB Installation and maintenance NovAx smoke exhaust fan type ACN smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport

More information

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance TOP ECOSMART TWINFANS (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use Installation and Maintenance The EMC Directive 2014/30/EU The Low Voltage directive 2014/35/EU INDOOR USE ONLY Introduction

More information

INSTALLATION INSTRUCTIONS Trade-Wind In-Line Blower / Ventilators

INSTALLATION INSTRUCTIONS Trade-Wind In-Line Blower / Ventilators INSTALLATION INSTRUCTIONS Trade-Wind In-Line Blower / Ventilators Models: PSX006XL PSD008XL PSD010XL CONTENTS: Part 1 - Planning The Installation Part 2 - Securing The Blower / Ventilator Part 3 - Electrical

More information

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES Bucket Fan 420 Bucket Fan 1055 Bucket Fan 1460 420 1055 1460 2 Bucket Fan CONTENT INTRODUCTION 3 USE 3 WHAT S INCLUDED IN THE BOX 3 DESIGNATION

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS C7BA & C7BH Series Split System Indoor Cased Coils INSTALLATION INSTRUCTIONS IMPORTANT It is your responsibility to know this product better than your customer. This includes being able to install the

More information

INSTALLATION, USE AND MAINTENANCE MANUAL HIGH PRESSURE FAN COIL FOR PROFESSIONAL APPLICATIONS, BUILT-IN VERSION

INSTALLATION, USE AND MAINTENANCE MANUAL HIGH PRESSURE FAN COIL FOR PROFESSIONAL APPLICATIONS, BUILT-IN VERSION INSTALLATION, USE AND MAINTENANCE MANUAL HIGH PRESSURE FAN COIL FOR PROFESSIONAL APPLICATIONS, BUILT-IN VERSION a-life2 HP 302 1202 a-life2 HP 304 1204 EN OBSERVATIONS In order to use the unit correctly

More information

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with

More information

AHU INSTALLATION & OPERATION MANUAL

AHU INSTALLATION & OPERATION MANUAL AHU INSTALLATION & OPERATION MANUAL VERSION 2 AIR HANDLING UNIT MODELS: AHU 500, AHU 900, AHU 1200, AHU 1700, AHU 2000, AHU 2500, AHU3500, AHU 4500, AHU 5000, AHU 6000, AHU 7000, AHU 8000, AHU 10000, AHU

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS C7BA Series Split System Indoor Cased Coils IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80

SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80 Installation & Maintenance Data IM 255-6 SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80 Group: Fan coil Part Number: # 106332400 Date: August 2000 Table of Contents Inspection............................................................................

More information

SeasonMaker Hi-Line Fan-coil Units Model HSS S10 & S12

SeasonMaker Hi-Line Fan-coil Units Model HSS S10 & S12 Installation & Maintenance Data IM 168-5 SeasonMaker Hi-Line Fan-coil Units Model HSS S10 & S12 Group: Fan coil Part Number: # 107132900 Date: June 1999 Table of Contents Inspection............................................................................

More information

OPERATION MANUAL U L US LISTED CM12 READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORRECT INSTALLATION AND USAGE, AND READ ALL SAFEGUARDS.

OPERATION MANUAL U L US LISTED CM12 READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORRECT INSTALLATION AND USAGE, AND READ ALL SAFEGUARDS. OPERATION MANUAL CM12 READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORRECT INSTALLATION AND USAGE, AND READ ALL SAFEGUARDS C U L US LISTED 2006 DENSO SALES CALIFORNIA, INC All rights reserved This book

More information

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 918149-0 GB Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport 3. Storage 4. Installation 4.1 Prior to attachment 4.2 Attachment

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless Split System Sizes 09 to 36 Installation Instructions NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS

More information

T-Series Air Conditioner T15 Model

T-Series Air Conditioner T15 Model INSTRUCTION MANUAL T-Series Air Conditioner T15 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

T-Series Air Conditioner T53 Model

T-Series Air Conditioner T53 Model INSTRUCTION MANUAL T-Series Air Conditioner T53 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N T-SERIES Air Conditioner T20 Model INSTRUCTION MANUAL Rev. C P/N 89114993 TABLE OF CONTENTS Warranty and Return Policy... 2 IMPORTANT NOTICE... 2 RECEIVING THE AIR CONDITIONER... 3 HANDLING AND TESTING

More information

IMPORTANT SAFETY INFORMATION:

IMPORTANT SAFETY INFORMATION: Owner s Manual Model CUH05B31T IMPORTANT SAFETY INFORMATION: Always read this manual first before attempting to install or use this heater. For your safety, always comply with all warnings and safety instructions

More information

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2 Cleaning unit for coolant :_decftez`_>r_fr] Book No.: 1271526-02 V2 Alfa Laval Separation AB Separator Manuals, dept. SKEL S-147 80 Tumba, Sweden Telephone: +46 8 53 06 50 00 Telefax: +46 8 53 03 10 40

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS FCP2400D FCP3000D FCP3600D FCP4200D FCP4800D FCP6000D FCP2400C FCX2400C FCP3000C FCP3600C FCX3600C FCP4200C FCP4800C FCX4800C FCP6000C FCX6000C Require AMF001NHA Accessory No

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET General Piping Recommendations and Refrigerant Line Length for Split-System Air Conditioners and Heat Pumps GENERAL GUIDELINES This Split-System (Air Conditioning Condensing/Heat

More information

SPA DE USO PRIVADO SPA FOR PRIVATE USE SPA POUR UN USAGE PRIVÉ SPA FÜR PRIVATE NUTZUNG SPA PER USO PRIVATO SPA PARA USO PRIVADO SPA VOOR PRIVE-GEBRUIK

SPA DE USO PRIVADO SPA FOR PRIVATE USE SPA POUR UN USAGE PRIVÉ SPA FÜR PRIVATE NUTZUNG SPA PER USO PRIVATO SPA PARA USO PRIVADO SPA VOOR PRIVE-GEBRUIK SPA DE USO PRIVADO SPA FOR PRIVATE USE SPA POUR UN USAGE PRIVÉ SPA FÜR PRIVATE NUTZUNG SPA PER USO PRIVATO SPA PARA USO PRIVADO SPA VOOR PRIVE-GEBRUIK MANUAL DE INSTALACIÓN INSTALLATION MANUAL MANUEL D

More information

T-Series Air Conditioner T20 Model

T-Series Air Conditioner T20 Model INSTRUCTION MANUAL T-Series Air Conditioner T20 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort Application guide FLATAIR - FLCK/FLHK Providing indoor climate comfort MSL60E-0701 12-2006 Congratulations you have made a wise choice and we feel sure that it will meet your expectation INDEX CONTENTS

More information

Stainless Steel Chimney Extractor

Stainless Steel Chimney Extractor Stainless Steel Chimney Extractor HJA2450-2 User & Installation Guide LAMONA Appliances Dear Customer, Congratulations on your choice of a LAMONA domestic appliance which has been designed to give you

More information

CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT. Cooling

CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT. Cooling TECHNICAL INSTRUCTIONS CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT Cooling Heating CWX 3 pipes.60 3.9 pipes + electric heating.08.96 +.5 pipes.08.5 CWX 5 pipes.70 5.70 pipes + electric heating.3 5.3 +.50

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant

More information

Model No. Serial No. Original Purchaser. Address. City and State Zip. Dealer. Address. City and State Zip. Installation Date Name Signature

Model No. Serial No. Original Purchaser. Address. City and State Zip. Dealer. Address. City and State Zip. Installation Date Name Signature Your Warranty The manufacturer, Lanco, warrants this fan coil to the original purchaser under the following conditions: LIMITED ONE-YEAR WARRANTY 1. Any part thereof which proves to be defective in material

More information

52 SAN LUCAS CEILING FAN

52 SAN LUCAS CEILING FAN 52 SAN LUCAS CEILING FAN Owner s Manual Models #20551 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-459-3267, 9 a.m.-

More information

Vertical Concealed Fan Coil. FCVC Series MANUAL INSTALLATION, OPERATION, & MAINTENANCE

Vertical Concealed Fan Coil. FCVC Series MANUAL INSTALLATION, OPERATION, & MAINTENANCE MANUAL INSTALLATION, OPERATION, & MAINTENANCE Vertical Concealed Fan Coil FCVC Series v100 Issue Date: 12/21/15 2015 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Safety

More information

52 CEILING FAN. Owner s Manual Models #50336, 50337

52 CEILING FAN. Owner s Manual Models #50336, 50337 52 CEILING FAN Owner s Manual Models #50336, 50337 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-706-3267, 9 a.m.- 5 p.m.

More information

an ISO 9001:2015 Registered Company

an ISO 9001:2015 Registered Company an ISO 9001:2015 Registered Company Mark IV (672001-VHY) 18865 Goll St. San Antonio, TX 78266 Phone: 800-862-6658 Sales: sales@vintageair.com Tech Support: tech@vintageair.com www.vintageair.com 902001-VHY

More information

User Manual Box Exhaust Fan Series (Belt Drive)

User Manual Box Exhaust Fan Series (Belt Drive) User Manual Box Exhaust Fan Series (Belt Drive) 36" Box Exhaust Fan with Three Wing Blade Box with Aluminum Shutter 54" Box with Cone 800-779-3267 sales@schaeferfan.com www.schaeferfan.com 2013 Schaefer

More information

INSTRUCTION MANUAL (English version) Water still

INSTRUCTION MANUAL (English version) Water still INSTRUCTION MANUAL (English version) Water still Model : Brand : W4000 Merit Merit Water Still W4000 & W4000/EURO Cooling water inlet Condenser Constant level control Boiler Thermostat reset buttons To

More information

WATLOW ELECTRIC MFG CO. WATROD Duct Heater (module only) I& M Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.00

WATLOW ELECTRIC MFG CO. WATROD Duct Heater (module only) I& M Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.00 I&M NUMBER: 316-42-16-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance.

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance. ESX-X Figure 1. ESX-X units. Removable top panel A D Control module located internally External Commissioning box Table 1. ESX-X Dimensions (mm) Spigot Weight Code A B C D dia (kg) ESX1-X 705 505 355 125

More information

Galletti IWC THE HYDRONIC CASSETTE UNIT PAR EXCELLENCE A guide to choosing Create value to design better

Galletti IWC THE HYDRONIC CASSETTE UNIT PAR EXCELLENCE A guide to choosing Create value to design better www.galletti.it Galletti IWC THE HYDRONIC CASSETTE UNIT PAR EXCELLENCE A guide to choosing 2012 Create value to design better A guide to choosing The group It s 1961 and Galletti with its Jolly copper

More information

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N SPECTRACOOL Air Conditioner N21 Model INSTRUCTION MANUAL Rev. G P/N 89115088 TABLE OF CONTENTS WARRANTY AND RETURN POLICY...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

52 BERKSHIRE CEILING FAN

52 BERKSHIRE CEILING FAN 52 BERKSHIRE CEILING FAN Owner s Manual Models #20223, 20224 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-459-3267, 9

More information

installation, operation & Maintenance manual Floor-mounted Induction units acb 30/35

installation, operation & Maintenance manual Floor-mounted Induction units acb 30/35 installation, operation & Maintenance manual Floor-mounted Induction units acb 30/35 built on innovation acb 30 & 35 Active Chilled Beam Models ACB30 & ACB35 are designed for installation in the ceiling

More information

T-RECESSED RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

T-RECESSED RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS T-RECESSED RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING INSTALLATION Thermoscreens Ltd St. Mary s Road Nuneaton Warwickshire

More information

Table of Contents. What to Expect with. Mounting Options. Tools Needed. Downrod. Blades. Maintenance & Cleaning.

Table of Contents.   What to Expect with. Mounting Options. Tools Needed. Downrod. Blades. Maintenance & Cleaning. Table of Contents Tools Needed Mounting Options Ceiling Bracket 30 inches Downrod 3 4 Wiring Canopy 5 11 Ladder 2 7 feet We are proud of our work and appreciate the opportunity to supply you with the best

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information