Implications of GHP Fan Control Strategies on Humidity Control in Commercial Applications
|
|
- Betty Glenn
- 5 years ago
- Views:
Transcription
1 Implications of GHP Fan Control Strategies on Humidity Control in Commercial Applications ASHRAE Winter Meeting February 9, 2005 Hugh I. Henderson, Jr., P.E. CDH Energy Corp. Cazenovia, NY DOE/NETL Project #DE-FC26-01NT41253
2 Fan Control Affects Latent Performance How is ventilation air supplied? Provided directly to heat pump inlet Provided directly to space If supply fan operates continuously, then latent capacity degrades at part load
3 Steady-State Cooling Coil Performance AC coil performance is well understood at steady-state conditions GHP is similar to conventional AC Coils provide both sensible cooling and moisture removal (latent cooling) SHR: sensible heat ratio..fraction of total cooling that is sensible Colder coil surfaces remove more moisture Reduced air flow provides more moisture removal (for DX coils) Higher condenser temperatures increase SHR i.e., high ground loop temperatures
4 Occurences Occurences Equipment Survey Reviewed specifications for 500 commercial and residential AC units Goal was to determine range of common coil geometries Variation by equipment type Typical DX AC coil is 3-rows, 15 fpi Packaged Air Handlers Evap Coils Number of Rows Packaged Air Handlers Evap Coils Fin Spacing (fpi)
5 Sat. Temp = 42.4 Absolute Humidity Ratio (lb/lb) Typical AC Coil Performance Total: 2.0 tons (coil) Power: 2.5 kw EER: 9.6 Btu/Wh Sweetser - Upstairs Unit SHR: Dry Bulb Temperature (F) 0.000
6 Part Load Performance GHP cycles compressor ON and OFF based on a space thermostat The portion of time the coil operates (i.e., the runtime fraction) is longer when cooling loads are greater RTF = ON (ON + OFF) How do sensible and latent capacity vary under cyclic conditions?
7 Capacity (MBtu/h) Sensible and Latent Capacity With Continuous Supply Air Fan Operation 30 COIL1_TEST_4B_10B_16B_22B 08/30/02 07:42:04 Cycle #1 (Comp ON time: 45.0 minutes) Sensible 20 Transition pt Off-Cycle Evaporation is Adiabatic Process: Sensible Latent 10 0 Latent Removal -10 Compressor Latent Addition time (minutes)
8 Latent Capacity Latent Degradation Concepts t wet = M o /Q L M o Useful Moisture Removal Q L = Q e /Q L Q e Evaporation Delay Time (t o ) time for first condensate to fall from pan M o Evaporation TIME (minutes)
9 LHR Degradation Model Borrowed approaches used to develop partload efficiency degradation function for SEER test procedure Used same part-load assumptions (C d ): AC at startup described by a time constant Cycling rate driven by thermostat curve Additional latent assumptions: Coil surfaces hold a fixed amount of moisture (M o ) Off-cycle coil is like an evaporative cooler
10 SHR Comparing LHR Model to Field Tests Henderson (1998) compared the model results to field data collected on a 3-ton residential geothermal heat pump Continuous supply air fan operation Measured Data: averaged into 4 hour intervals entering RH: 57% to 63% entering air temp: 68F to 72F loop temps: 65F to 90F Runtime Fraction (-) Latent Degradation Model with: t wet = 720 sec = 1.07 N max = 3.6 cyc/h = 75 sec linear decay Steady State SHR = 0.76
11 Capacity (MBtu/h) Actual Laboratory Results COIL2_TEST_4B_10B_16B_22B_25B 11/14/02 10:07:57 Cycle #2 (Comp ON time: 45.0 minutes) Sensible Integrated Moist (delay of 1.0 min) Mass twet QS= 21.8 Sens (lb & min): Lat (lb & min): (+) Latent (psych) Condensate 11.9 (gamma = 1.60) 5 QL= 7.4 QC= 6.7 (-) Latent (psych) Integration Pt min F, 60.4 F dp, 51.5 % Run hz, 76.6 psi, 967 cfm, in Hg time (minutes)
12 Sensible Heat Ratio (-) Laboratory Testing SHR Degradation LHR Model matches measured data at nominal entering conditions (80F db, 60.4F dp) 1.0 Constant Fan Cyclic Tests for COIL2 (80db, 60dp) Constant Fan Mode 1st Cycle 2nd Cycle 3rd Cycle 0.8 twet= 17.3, gamma= 1.50, exp Steady State SHR = (based on condensate) Runtime Fraction (-)
13 Sensible Heat Ratio (-) Laboratory Testing SHR Degradation (cont.) Model also matched measured data at other entering conditions! Constant Fan Cyclic Tests for COIL2 (75db, 64dp) Constant Fan Mode (75F db, 64F dp) st Cycle 2nd Cycle 3rd Cycle Steady State SHR = (based on condensate) twet= 11.2, gamma= 0.49, exp Runtime Fraction (-)
14 Sensible Heat Ratio (-) Laboratory Testing SHR Degradation (cont.) Coil 5 showed impact in AUTO Fan Mode! 1.0 AUTO Fan Mode Auto Fan Cyclic Tests for COIL st Cycle 2nd Cycle 3rd Cycle 4th Cycle 5th Cycle Steady State SHR = (based on condensate) Runtime Fraction (-)
15 Sensible Heat Ratio (-) Field Testing SHR Degradation Significant AUTO fan degradation! 1.0 Sweetser - Downstairs AC Unit Steady State SHR = Auto Fan Mode Constant Fan Mode (08/18/02 to 09/04/02) (Model: twet=15 min, gamma=2.2, Nmax=3) Runtime Fraction
16 Measured Performance Parameters Coil 1 (Slanted slab, 3 row, 13 fpi, plain fins, orifice) Coil 2 Normal Flow (A-coil, 3 rows, 15.5 fpi, lanced sine-wave fins, TXV) Coil 2 Low Flow (A-coil, 3 rows, 15.5 fpi, lanced sine-wave fins, TXV) Coil 4 (vert. slab, 2 rows, 14 fpi, wavy fins, orifice) Coil 5 (slanted slab, 4 rows, 12 fpi, wavy fins, orifice) Coil 6 (A-coil, 3 rows, 13 fpi, wavy fins,txv) Coil 6 High Flow (A-coil, 3 rows, 13 fpi, wavy fins,txv) Coil 8 Chilled Water (vert. slab, 4 rows, 10 fpi, wavy fins,46f CHW) Notes: Size Fin Surface Area Retained Moisture Mass Cond Delay Time t wet (tons) (ft 2 ) (lb) (lb/kft 2 ) (min) (min) Cooling capacity includes sensible and latent cooling at nominal conditions. Nominal conditions correspond to ASHRAE Test A test point. Surface area is gross fin area (coil face area x coil depth x fin spacing x 2). Condensate delay time and t wet are at nominal conditions.
17 Lab + Field: Retained Moisture Henderson (1998) Estimated in Field CHW Coil 2.9 ton Rooftop 10 tons Residential 3.5 ton Lab - Coil 8 Lab - Coil 7 Lab - Coil 6 Lab Measurements Lab - Coil 5 Lab - Coil 4 Lab - Coil 3 Lab - Coil 2 Lab - Coil 1 Korte & Jacobi (1997) Coil Moisture Retention (lb per 1000 ft2) Moisture per total gross fin area (gross area = face area x depth x fin spacing x 2)
18 Indoor Humidity (gr/lbm) Field Testing Impact of Constant Fan Large penalty for constant fan operation Heink - Humidity Inside vs. Outside 60 Even for a dual-capacity AC unit Auto Fan Mode Constant Fan Mode Outdoor Humidity (gr/lbm)
19 Space Humidty (%RH) Impact on Space Humidity Levels Room Humidity - July 13 Constant Fan AUTO Fan Hour of Day TRNSYS Model of Hotel Room DX AC cycling in Hawaii DX AC
20 What Control Strategies Help? Do fan delay strategies help? No not until about a 10 minute delay Two-speed or staged capacity heat pumps? Yes increases runtime fraction (depends on coil split & fan control) Reduced airflow during off cycle? Yes would minimize off cycle evaporation Cycle the fan with the compressor? Yes whenever possible
21 Summary GHPs are like Air Conditioners, only they re geothermal Follow same steady state latent/sensible trends as conventional DX coil Subject to the same part load effects With constant fan, latent removal disappears below half load To maintain latent capacity Cycle fan with the compressor (when possible) Slow the fan down during off cycle Add more capacity stages
Dehumidification at Part Load
Dehumidification at Part Load Authors Shirey III, Don Henderson Jr., Hugh Original Publication Don Shirey III, Hugh Henderson Jr., Dehumidification at Part Load, ASHRAE Journal, April 2004. This article
More informationAir Conditioning for and-humid Climates:
Air Conditioning for Hot-and and-humid Climates: Commercial Technologies ACEEE Market Transformation Conference Emerging Technologies March 21, 2007 Hugh I Henderson, Jr., P.E. CDH Energy Corp. Cazenovia,
More informationAn Hourly Building Simulation Tool to Evaluate Hybrid Desiccant System Configuration Options
An Hourly Building Simulation Tool to Evaluate Hybrid Desiccant System Configuration Options ASHRAE Summer Meeting June 29, 2003 Hugh I Henderson, Jr. P.E. CDH Energy Corp. Cazenovia, NY James R. Sand,
More informationClosing the Gap: Getting Full Performance from Residential Central Air Conditioners. Task 4 - Develop New Climate-Sensitive Air Conditioner
Closing the Gap: Getting Full Performance from Residential Central Air Conditioners Task 4 - Develop New Climate-Sensitive Air Conditioner Simulation Results and Cost Benefit Analysis April 27, 27 Prepared
More informationTechnical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler
Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS FOR COMBINATION HEATING AND COOLING ROOFTOP UNITS RKKB SERIES 7.5, 8.5, 10, 12.5 & 15 TON [26.4, 29.9, 35.2 44 & 52.8 kw] RKMB SERIES 7.5, 8.5, 10 & 12.5 TON [26.4, 29.9, 35.2
More informationPC SERIES 50 Hertz PRODUCT SPECIFICATIONS. Self-Contained Packaged Air Conditioners. 4 and 5 Ton [14.1 kw to 17.6 kw]
PC SERIES 50 Hertz Self-Contained Packaged Air Conditioners 4 and 5 Ton [14.1 kw to 17.6 kw] Nominal Cooling Capacity: 48,000 to 60,000 BTUH The PC 50 Hz self-contained packaged air conditioners are designed
More informationRelative Humidity in Schools Jim Cummings and Chuck Withers
to Co n tr o l Relative Humidity in Schools Jim Cummings and Chuck Withers SEEC Southern Energy-Efficiency Center Energy Efficient Strategies to Control Relative Humidity in Schools James Cummings and
More informationDesigning Energy Efficient Outdoor Air Systems
Designing Energy Efficient Outdoor Air Systems Joseph Thorndal Applied Products Sales Manager Greenheck, Schofield, Wisconsin 1 Joseph Thorndal BS Industrial Engineering North Dakota State University Work
More informationSession: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island
Session: HVAC 101 HVAC 101 Steve Sain Sain Engineering Associates, Inc. August 9, 2016 Rhode Island Convention Center Providence, Rhode Island Why? 2 Acknowledgements 3 Disclaimer I m gonna shoot down
More informationFALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)
FALCON Rooftop Units ACPSE 50/60Hz Cooling : 36 to 1388 MBH (11 to 407 ) Heating : 40 to 1298 MBH (12 to 380 ) R Products that perform...by people who care NOMENCLATURE 6 AC P S E 435 P - HP G Q 6-60 Hz
More informationTECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36
TECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36 Due to continuous product improvement, specifications are
More informationProduct Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw)
Product Data 38AH024-134 Commercial Air-Cooled Condensing Units 50/60 Hz 20 to 130 Nominal Tons (63 to 390 Nominal kw) a38-4143ef 38AH044-134 These dependable split systems match Carrier s 40RM or 39 Series
More informationDehumidification: Energy Efficiency Comparisons
Fourth Annual Energy Management Workshop Cocoa, Florida February 10-11, 2003 Dehumidification: Energy Efficiency Comparisons Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting,
More informationEvaporative Cooling in a Hot-Dry Climate
Evaporative Cooling in a Hot-Dry Climate David Springer Davis Energy Group SWEEP Workshop July 10, 2007 Sponsors: Clarum Homes California Energy Commission U.S.Department of Energy Issues for Discussion
More informationproduct application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM
product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM 551B 581B DuraPac Plus Series Sizes 036-150 3to12 1 / 2 Tons Cancels: New PAD 551B.36.2 10/1/04 CONTENTS Page INTRODUCTION.................................
More informationC13-Series Engineering Guide
Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................
More informationA/C Cooling Load calculation and measurement
Testo Inc. 40 White Lake Rd. Sparta NJ 07871 (800) 227-0729 A/C Cooling Load calculation and measurement When we talk about sizing an air conditioning appliance (tons of cooling, BTU/h or KW), we are specifying
More informationCARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.
Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using
More informationEnergy Use in Refrigeration Systems
2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is
More information1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series
1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series Rated in accordance with ARI Standard 210. Certification applies only when used with proper components as listed with ARI. FEATURES Designed as an upflow indoor
More informationPACKAGE AIR CONDITIONER
PACKAGE AIR CONDITIONER FORM NO. ATZ-206 TZAA- HIGH EFFICIENCY SERIES NOMINAL SIZE 10 TON [35.2 kw] 10 TON MODEL [35.2 kw] This product is shipped with a nitrogen holding charge that must be vented prior
More informationTechnical Development Program
Technical Development Program PRESENTED BY: James Parker Insert your logo here AIR HANDLERS Coils: Direct Expansion Chilled Water and Heating Menu Section 1 Introduction Section 2 Typical Coil Applications
More informationK*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*
TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS K*ES120 10 NOMINAL TONS EER 8.5 DESCRIPTION These completely assembled dual circuit evaporator blower units include a well-insulated cabinet, a DX cooling
More informationTECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)
DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage
More informationTEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat
More informationPresented By: John Dolan, P.E.
Variable Speed Compressor Technologies Presented By: John Dolan, P.E. President - Thermosystems, Inc. BS in Mechanical Engineering from UIUC 29 years HVAC Equipment Application Experience jdolan@thermohvac.com
More informationVertiCool Aurora Engineering Guide
Engineering Guide Effective August 2016 Air-Cooled, Water-Cooled and Water Source Heat Pump Contents Product Features... 3 Options... 4 Physical Data...5-6 Air-Cooled Performance Data (a) (b) (c)...7-8
More information15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON
7D- -A EVOLUTIONr 15 SEER SINGLE-PACKAGED HEAT PUMP SYSTEM WITH PURONr (R-410A) REFRIGERANT SINGLE PHASE 2-5 NOMINAL TONS (SIZES 24-) Fig. 1 - Unit 7D - -A Product Data A09032 Single-Packaged Products
More informationProduct Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons
0TJ06-03S Side Discharge Single-Package Rooftop Units 0/ Hz to 30 Nominal Tons Product Data The 0TJ-S series is a special side discharge version packaged unit with capacities of -30 Tons. This unit can
More informationPAJ3. Product Specifications
13 SEER, R 410A PACKAGE AIR CONDITIONER FOR MANUFACTURED HOUSING, RESIDENTIAL, AND LIGHT COMMERCIAL APPLICATIONS 2 5 TONS Single Phase, 208/230 V, 60 Hz BUILT TO LAST, EASY TO INSTALL AND SERVICE Compact,
More informationFF1DNA, FF1DNE FAN COIL UNITS. Sizes 018, 024, 030. Form No. PDS FF1D.18.3 FEATURES FF1D
FAN COIL UNITS FF1DNA, FF1DNE Sizes 018, 024, 030 FF1D FEATURES The FF1DNA and FF1DNE Fan Coil units are designed as upflow indoor air handlers for split-system heat pumps and air conditioners. They are
More informationIntroduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN
Introduction to HVAC Agenda Psychrometrics Human Comfort Heat Transfer Refrigeration Cycle HVAC Terminology HVAC Systems Introduction to HVAC Psychrometrics 2000 TRG-TRC002-EN Properties of Air Dry-bulb
More informationRuud Commercial Achiever Series Package Gas Electric Unit featuring HumidiDry Technology
Package Gas Electric Ruud Commercial Achiever Series Package Gas Electric Unit featuring HumidiDry Technology RKNL-G 13 SEER Series With ClearControl Nominal Sizes 3-5 Tons [10.6-17.6 kw] SINGLE PHASE
More informationMANUAL J/S Summary One summary sheet for each system
MANUAL J/S Summary One summary sheet for each system NOTE: The load calculation must be calculated on a room basis. Room loads are a mandatory requirement for making Manual D duct sizing calculations.
More informationCAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE
COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE CAS Product Specifications Single stage cooling capacity control on all models with Micro channel
More informationCompact, Self-Contained unit that offer low installation cost plus dependable performance.
0 Compact, Self-Contained unit that offer low installation cost plus dependable performance. From carrier s excellence in engineering come a new, compact of single package horizontal and vertical water
More informationComparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Comparison of Performance of a Residential Air- Conditioning System Using
More informationTECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811
Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage
More informationSteady and Cyclic Performance Testing of Packaged R-410A Units
Prepared by: Bo Shen, James E. Braun, and Eckhard A. Groll Ray W. Herrick Laboratories The School of Mechanical Engineering Purdue University Steady and Cyclic Performance Testing of Packaged R-410A Units
More informationEFFECT OF REFRIGERANT CHARGE, DUCT LEAKAGE, AND. EVAPORATOR Am FLOW ON THE HIGH TEMPERATURE PERFORMANCE OF AIR CONDITIONERS AND HEAT PUMPS.
EFFECT OF REFRIGERANT CHARGE, DUCT LEAKAGE, AND EVAPORATOR Am FLOW ON THE HIGH TEMPERATURE PERFORMANCE OF AIR CONDITIONERS AND HEAT PUMPS A Thesis by ANGEL GERARDO RODRIGUEZ Submitted to the Office of
More informationR4H4. Product Specifications
R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY BALANCED REFRIGERANT 1-1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Scroll compressors on
More informationSUBMITTAL. Project. CLU Swenson Center. Date 01/07/2010. Mechanical Contractor. West Coast Air Conditioning. Mechanical Engineer
SUBMITTAL Project CLU Swenson Center Date 01/07/2010 Mechanical Contractor West Coast Air Conditioning Mechanical Engineer J & S Consulting Engineers, Inc. Revision Notes RTU-101, 102, 103, 201, 202, 203,
More informationFundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer
Fundamentals of Psychrometrics By James L. Murphy, Colorado Building Environments Sales Engineer Let s s Start with Air Air is Made up of Two Main Gases Nitrogen (77%) Oxygen (23%) If that is all there
More informationPAR5. Product Specifications
TM PAR5 Product Specifications UP to 16 SEER, UP to 12.5 EER, PACKAGE AIR CONDITIONING UNITS, 2 5 TONS 208/230 Volt, 1 phase, 60 Hz 208/230 Volt, 3 phase, 60 Hz REFRIGERATION CIRCUIT Environmentally balanced
More informationTECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) DESCRIPTION
TECHNICAL GUIDE SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) LISTED ISO 9001 Certified Quality Management System Due to continuous product
More informationThe Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc.
The Basics - B Practical Psychrometrics Jerry Cohen President Jacco & Assoc. Who is Jacco Established 1968 Hudson, Ohio Columbus, Ohio Toledo, Ohio Focused on the Engineered Environment Systems Knowledgeable
More informationR4H4. Product Specifications
ENVIRONMENTALLY SOUND REFRIGERANT R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION
More informationCOMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal
By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal Summary Refrigeration air coolers (evaporators) are widely
More informationSummary Comparison of Simulation Program Features
Summary Comparison of Simulation Program Features FEATURE DOE2.2 equest TRACE 700 HAP Public/Proprietary Public Domain Proprietary Proprietary Proprietary Simulation Method 8760 hours 8760 hours 8760 hours
More informationField Installed Options: * Louvered or non-louvered ceiling access panels. * Time delay relay.
Description: These air handlers are designed for horizontal mounting into a furred down ceiling, and will handle up to 1150 CFM and up to 3 ton of cooling with a DX cooling or heat pump coil, or Chilled
More informationCommercial High-Efficiency Condensing Units
FORM NO. A22-194 REV. 2 Supersedes Form No. A22-194 Rev. 1 Commercial High-Efficiency Condensing Units RAWL High Efficiency 6.5 & 7.5 TON MODEL [22.86 & 26.38 kw] TABLE OF CONTENTS Model Number Designation...2
More informationRheem Commercial Classic Series Package Air Conditioner
13.0 Air Package Air Conditioner Rheem Commercial Classic Series Package Air Conditioner RLPN-C 14 SEER Series With ClearControl Nominal Sizes 3-5 Tons [10.6-17.6 kw] RLQN-C 15 SEER Series With ClearControl
More informationTECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) DESCRIPTION
TECHNICAL GUIDE SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) LISTED MODELS: 018-060 (3 PH) MODELS: 076 (3 PH) ISO 9001 Certified Quality
More informationVertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump
VertiCool CLASSIC Engineering Guide Effective March 2018 Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump Contents Product Features... 3 UNIT FEATURES... 3 OPTIONS:... 3 Physical Data...
More informationUP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT
SOUND REFRIGERANT ENVIRONMENTALLY PAJ4 Product Specifications UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT Environmentally sound R-410A
More informationN4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz
ENVIRONMENTALLY SOUND REFRIGERANT N4H4 Performance Series Product Specifications 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION
More informationProduct Data. 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons INDUSTRY LEADING FEATURES / BENEFITS
24AHA4 Performance Series Air Conditioner with Refrigerant 1-1/2 to 5 Nominal Tons Product Data Carrier air conditioners with refrigerant provide a collection of features unmatched by any other family
More informationRuud Achiever Series Dedicated Horizontal Package Heat Pump
Package Heat Pump Ruud Achiever Series Dedicated Horizontal Package Heat Pump RQPM- -SEER Series Nominal Sizes 2-5 Tons [7-7.6 kw] RQRM- 5/6-SEER Series Nominal Sizes 2-5 Tons [7-7.6 kw] (5 SEER/2.0 EER
More informationRuud Achiever Series Dedicated Horizontal Package Heat Pump
Package Heat Pump Ruud Achiever Series Dedicated Horizontal Package Heat Pump RQPM- 4-SEER Series Nominal Sizes 2-5 Tons [7-7.6 kw] RQRM- 5/6-SEER Series Nominal Sizes 2-5 Tons [7-7.6 kw] (5 SEER/2.0 EER
More informationCommercial High-Efficiency Condensing Units
FORM NO. A22-193 REV. 3 Supersedes Form No. A22-193 Rev. 2 Commercial High-Efficiency Condensing Units 15 & 20 TON MODEL [52.8 & 70.3 kw] 10 & 12.5 TON MODEL [35.2 & 44.0 kw] 10 THROUGH 20 NOMINAL TON
More informationUP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM
EFFICIENT UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase REFRIGERATION CIRCUIT S 2- stage scroll compressors
More informationRHEEM Split Systems Condensers All submitted condensers meet the 15 SEER minimum All submitted condensers meet the 208/230V specification All submitted condensers contain enhanced mufflers to help dissipate
More informationProduct Data PF1MNC DIRECT EXPANSION FAN COIL SIZES 018 THRU 061 FEATURES/BENEFITS AVAILABLE SIZES: 18,000 to 61,000 BTU unit ELECTRICAL RANGE:
DIRECT EXPANSION FAN COIL SIZES 018 THRU 061 Product Data FEATURES/BENEFITS AVAILABLE SIZES: 18,000 to 61,000 BTU unit ELECTRICAL RANGE: 40 -va, 208/230 -v transformer, 60 Hz, 1 Phase. FAN MOTOR: 2 -speed
More informationSystem Modeling of Gas Engine Driven Heat Pump
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 01 System Modeling of Gas Engine Driven Heat Pump Isaac Mahderekal shenb@ornl.gov
More informationCOMMERCIAL HVAC PACKAGED EQUIPMENT. Split Systems
COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They are
More informationPsychrometric Engineering Applications
Psychrometric Engineering Applications Course No: M01-014 Credit: 1 PDH Klas Haglid, P.E., R.A. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800
More informationProduct Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons
Product Data OMNIZONE 50BRN,BZN006-024 Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems 5 to 20 Nominal Tons The 50BRN,BZN water-cooled and remote air-cooled indoor, self-contained units
More informationProduct Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons
007-014 Single- Package Rooftop Units - 50 Hz 6 to 12 Nominal Tons Product Data Single package rooftop cooling units with electric heat option. Compact, horizontal discharge units (vertical discharge option),
More informationOptimisation of cooling coil performance during operation stage for improved humidity control
Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 741 Optimisation of cooling coil performance during operation stage for improved humidity control S.C. Sekhar * and L.T. Tan National
More informationSERVICE ASSISTANT OVERVIEW FDSI Online Training
Author: Dale T. Rossi Online Editor: Zachary Williams SERVICE ASSISTANT OVERVIEW FDSI Online Training May 5, 2009 Table Service Assistant Description... 2 Installing the Main Unit... 3 Ambient Temperature...
More informationModels 566D 569C,576B with 524A 6to30Tons
Bryant Air Conditioning COMMERCIAL AIR-COOLED CONDENSING S WITH 524A AIR-HANDLING S Models 566D 569C,576B with 524A 6to30Tons DESCRIPTION Model 569C condensing units are available in nominal 6- to 10-ton
More informationEfficiency Vermont The American Institute of Architects Continuing Education Systems (AIA/CES) AIA/CES AIA/CES
Efficiency Vermont is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of this program will be reported to AIA/CES
More information36,000-62,000 BTUH Nominal Capacity
36,000-62,000 BTUH Nominal Capacity STANDARD EQUIPMENT 2TEE3F62A, 4TEE3F62B VARIABLE SPEED AIR HANDLER Ships horizontal - converts to vertical by standing on end. Six-way convertibility-horizontal (left
More informationENGINEERING. Edition No. 13 October 2002
Edition No. 13 October 2002 ENGINEERING S Y S T E M S O L U T I O N S W e at McQuay are very proud of our tradition of producing industry leading water source heat pumps. Our heritage stretches back more
More informationProduct Data. FF1DNA, FF1DNE Fan Coil Units. Sizes 018 thru 030 FEATURES/BENEFITS
Product Data FF1DNA, FF1DNE Fan Coil Units Sizes 018 thru 030 FF1D FEATURES/BENEFITS The FF1DNA and FF1DNE Fan Coil units are designed as upflow indoor air handlers for split-system heat pumps and air
More informationUnit Features & Benefits RQPM/RQRM Series
2 The RQPM & RQRM series of Package Heat Pumps are designed to be the most efficient, quickest to install, easiest to service, and most reliable units in the industry while still maintaining an affordable
More informationProduct Data. Fig. 1 - Unit 50VR -A
50VR---A Performancet 15 SEER 2---Stage Packaged Heat Pump tem with PuronR (R---410A) Refrigerant Single and Three Phase 2to5NominalTons(Sizes24---60) Product Data Fig. 1 - Unit 50VR -A A09033 Single-Packaged
More informationModel 655A Sizes
Bryant Air Conditioning SINGLE PACKAGE HEAT PUMP S Model 655A Sizes 018-060 1 1 2 to 5 Tons DESCRIPTION Model 655A is our latest generation of packaged heat pumps for manufactured housing, residential,
More informationProduct Data. FV4B Direct Expansion Variable Speed Fan Coil Puron Refrigerant. Sizes 002 thru 006
Product Data FV4B Direct Expansion Variable Speed Fan Coil Puron Refrigerant Sizes 002 thru 006 A02332 Premium Environmentally Sound Fan Coil The latest in technology makes the FV4B the most advanced air
More informationPrepared by: (415) With. High. Prepared for: Final Report June 27, Contributors: Tom. Me!
Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-24800 With Energy Systems Laboratory, Texas A&M University Design and Constr ruction of a Prototype High Efficiency Air Conditioner
More informationHeat Pumps COMFORT NEED IT. When You
Heat Pumps COMFORT When You NEED IT COMFORT When You NEED IT SpacePak s Solstice heat pumps are air-to-water reverse cycle heat pumps that use the comfort of Hydronics as the primary source for both heating
More informationField Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification
Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification Charles J. Cromer, PhD, P.E.; Florida Solar Energy Center, 1679 Clearlake Road, Cocoa, FL, 321-638-14,
More informationTo accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.
Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs the unwanted heat, this raises the refrigerant
More informationTrane CDQ Desiccant Dehumidification
Engineering Bulletin Trane CDQ Desiccant Dehumidification September 2004 CLCH-PRB020-EN Preface This engineering bulletin presents the Trane CDQ desiccant dehumidification system. It explains the features
More informationTECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS Model PSA4BI Series M1200 Product Line R-410A Ultra High Efficiency Air Conditioner 24.5 SEER 2-3-4 Ton 2 M1200 12 YEAR ALL PARTS LIMITED WARRANTY M1200 WITH UPGRADED WARRANTY
More informationProduct Data PF4MNA DIRECT EXPANSION FAN COIL FOR R -410A REFRIGERANT SIZES 018 THRU 061 FEATURES/BENEFITS AVAILABLE SIZES:
PF4MNA DIRECT EXPANSION FAN COIL FOR R -410A REFRIGERANT SIZES 018 THRU 061 Product Data FEATURES/BENEFITS AVAILABLE SIZES: 18,000 to 61,000 BTU unit, 1.5 to 5.0 ton unit ELECTRICAL RANGE: 40 -va, 208/230
More informationVERTICOOL TECHNICAL DATA MANUAL. Vertical Air/Water Cooled 3-25 Tons
491 East Princess Street York, PA 17403 877-905-1111 717-843-4311 Fax: 717-854-4462 uca@unitedcoolair.com www.unitedcoolair.com VERTICOOL TECHNICAL DATA MANUAL Vertical Air/Water Cooled 3-25 Tons UNITED
More informationAlpha Aire. Dedicated Outdoor Air System, VAV, Air-Source Heat Pump with Energy Recovery. Engineering Guide Effective February 2018
Alpha Aire Dedicated Outdoor Air System, VAV, Air-Source Heat Pump with Energy Recovery Engineering Guide Effective February 018 CONTENTS PRODUCT FEATURES.......................... OPTIONS.....................................
More informationSubmittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS
016---028 Single---Package Cooling Units with Factory---Installed Optional Electric Heat Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION
More informationRN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS.
RN/RQ Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS RQ Series Features: Air-cooled or water-cooled condenser, with unit capacities
More informationTechnical Papers. 37th Annual Meeting. International Institute of Ammonia Refrigeration. March 22 25, 2015
Technical Papers 37th Annual Meeting International Institute of Ammonia Refrigeration March 22 25, 2015 2015 Industrial Refrigeration Conference & Exhibition San Diego, California ACKNOWLEDGEMENT The success
More information14 SEER, 12 EER, 8.0 HSPF, PACKAGE HEAT PUMP, 2 to 5 TONS 208/ , Single Phase
SOUND REFRIGERANT ENVIRONMENTALLY PHD4 Product Specifications 14 SEER, 12 EER, 8.0 HSPF, PACKAGE HEAT PUMP, 2 to 5 TONS 208/230 1 60, Single Phase REFRIGERATION CIRCUIT Environmentally sound R-410A refrigerant
More informationRuud Commercial Value Series Package Gas Electric Unit
Package Gas Electric Ruud Commercial Value Series Package Gas Electric Unit Unit shown with optional louvered coil protection. RKKL-B Standard Efficiency Series Nominal Sizes 7.5, 0 & 2.5 Tons [26.4, 5.2
More informationTEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #47 System Drop-in Test of R-32 and Refrigerant Blends ARM-71a,
More informationRT-OA TM Rooftop Outdoor-Air (DOAS)
RT-OA TM Rooftop Outdoor-Air (DOAS) A/C s & HEAT PUMPS Dedicated Outside-Air System (DOAS) Solutions Office Buildings, Schools, Hospitals, Restaurants, Gyms & Fitness Centers, Hotels, Retail Stores...!
More informationTEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #53 System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton
More informationFLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13
Tag Data - Split System Air Conditioning Units (Large) (Qty: 6) Item Tag(s) Qty Description Model Number A1 20 ton vfd 6 6-25 Ton Unitary Split Systems ( SSC2 TTA24004H00-TWE240E404A TTA Air Condensing
More informationN4A6. Product Specifications
ENVIRONMENTALLY SOUND REFRIGERANT N4A6 Product Specifications EFFICIENT UP TO 16.5 SEER/12.2 13.0 EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt,
More informationPAD3. Product Specifications. 13 SEER PACKAGE AIR CONDITIONER, 2 to 5 TONS Single Phase, 208/230 V, 60 Hz REFRIGERATION CIRCUIT
SOUND REFRIGERANT ENVIRONMENTALLY PAD3 Product Specifications 13 SEER PACKAGE AIR CONDITIONER, 2 to 5 TONS Single Phase, 208/230 V, 60 Hz REFRIGERATION CIRCUIT Environmentally sound R 410A refrigerant
More information