1 FRUCHTMAN & ASSOCIATES CONSULTING MECHANICAL ENGINEERS September 27, 2018 Ocean Towers Housing Corporation 201 Ocean Avenue Santa Monica, CA Attn: Mr. Gerry Suenram General Manager Re: Ocean Towers 201 Ocean Avenue Santa Monica, CA Report on Condition of HVAC and Plumbing Systems On September 11, 2018 we were retained to perform a cursory evaluation of the common area heating, ventilation, air conditioning (HVAC); and plumbing systems serving the building. Plans of these systems were requested, but are apparently not available. As part of our work we conducted one site visit. This visit was limited to an observation of piping and equipment which is readily visible. No destructive testing was performed to examine piping and equipment within walls or above ceilings. This report summarizes our preliminary findings and recommendations for moving forward. In formulating the opinions stated in this report, we relied upon the following: A cursory site visit on September 26, 2018, with Adam King of Wolf Plumbing. Conversations with Mr. Gerry Surenam General Manger Conversations with Mr. Adam King of Wolf Plumbing. Correspondence with manufacturers representatives for Baltimore Air Coil (cooling tower manufacturer) and Raypak (heating hot water and domestic hot water boiler manufacturer). Building and Systems Description Ocean Towers is a high-rise residential complex consisting of approximately 317 dwelling units in two high-rise towers. Each high-rise tower has 17 floors. The towers sit on a podium structure which includes three levels of parking - one subterranean level, one ground level, and one above grade parking level. There are also common area spaces including a large lobby area, fitness center and various support spaces. The complex was constructed in The sanitary waste and vent piping and storm drainage systems are cast iron with no-hub couplings. The domestic water piping systems are predominately copper. However, some active sections of galvanized steel piping were also noted. One domestic water service supplies water to the entire building. This service is piped to a triplex booster pumping system. Water is pumped from the pumping system to both residential towers, and to a mechanical room, which houses two domestic hot water boilers and a vertical storage tank. Hot water is distributed from this system to the building. The hot water distribution WASHINGTON PLACE PHONE: LOS ANGELES, CALIFORNIA FAX: w w w. f r u c h t m a n e n g. c o m W:\Project Folders\o\otsm2345\otsm M&P report.doc

2 Ocean Towers Santa Monica, CA M & P Report page 2 system includes pressure reducing valves on the lower 14 floors of the building, and a series of recirculating pumps which are intended to recirculate hot water through the building back to the hot water system. Each of the two residential towers in the building are supplied with condenser water from two separate HVAC central plants. Each central plant consists of a closed circuit cooling tower, a heating hot water boiler, and two condenser water pumps. The heating hot water boilers are located in the same room as the domestic hot water heaters. The condenser water pumps and piping systems distribute condenser water throughout each building. 201 Ocean Avenue

3 Ocean Towers Santa Monica, CA M & P Report page 3 Observations/Comments A. Sanitary waste piping system Sanitary waste piping from the residential dwelling units and other plumbing fixtures throughout the complex collect together within the parking garage, and exit the building, where it connects to the municipal sewer system. There is an extensive network of cast iron piping which is visible within the parking garage areas. Many sections of this piping have been replaced. Where piping has not been replaced, we observed many segments of piping which are corroding and exhibiting evidence of leaks (present and imminent), and cracking. In older cast iron piping systems such as this we often recommend that random sections of piping be removed for analysis at a laboratory. This is used to assist in determining how much life remains in the piping. However, based upon our observations, and the history of pipe leakage within the garage, we recommend that all of the sanitary waste piping within the garage be replaced as soon as possible. We did not see any of the cast iron piping within the residential towers, as it is concealed behind ceilings and walls. It is likely in similar condition as that which was observed in the garage. However, if there is not an extensive history of leakage, it may be possible to defer replacement of this piping for a while if necessary. Random removal of segments of piping and laboratory testing could assist in determining the expected remaining life of this piping, but regardless, periodic piping failures should be expected until the piping is replaced. B. Sanitary vent piping system Sanitary vent piping in the building is not under pressure, and is not typically exposed to water flow. Accordingly, water leakage is not generally an issue with this piping. However, leakage from cracks in the piping, or separations of the couplings or joints could cause odors to discharge from the piping. As with any 50 year old piping system, problems could arise at any time, so ideally, replacement would be prudent. This could be done most cost effectively if done in conjunction with the sanitary waste piping replacement. However, if the homeowners choose not to invest in replacement, at a minimum we would recommend that the piping be visually examined and repaired or replaced where problems are evident. C. Storm water piping system This piping system is nearly 50 years old, and consequently, leaks could occur at any time. We understand that there has not been an extensive history of leakage in this system, accordingly, it may be possible to defer replacement of this piping for a while if necessary. Random removal of segments of piping and laboratory testing could assist in determining the expected remaining life of this piping, but regardless, periodic piping failures should be expected until the piping is replaced. D. Domestic cold water piping system At some point in the past, most of the domestic water piping in the building was repiped in copper, from galvanized steel. Major work to the copper piping system does not appear to be necessary at this time. However, there is still an active section of 6 diameter galvanized

4 Ocean Towers Santa Monica, CA M & P Report page 4 steel pipe which extends from where the water service enters the building, to the suction of the domestic water booster pumping system. Parallel to this is a 6 diameter copper pipe, which was apparently installed within the past couple of years, but for some reason was never placed on line. The copper line work should be completed, pressure tested, and placed on line as soon as possible so that the galvanized system can be removed from the system. All fittings and couplings should be checked to ensure that they are suitable for domestic water systems. Any other segments of galvanized piping which remain should also be removed and replaced with copper. E. Domestic hot water piping system We understand that the domestic hot water piping system was re-designed and re-piped in copper sometime in the mid to late 90 s. We have also been advised that the building is experiencing water pressure problems, recirculation problems, and mixing of hot and cold water. These symptoms are characteristic of an improperly designed hot water recirculating system. We recommend that the building retain the services of a qualified firm to create asbuilt drawings of the entire domestic water piping system. Once these drawings are available, they should be provided to an engineering firm for review and repair recommendations. F. Domestic water booster pumping system Water pressure for the entire complex is generated at a triplex domestic water booster pumping system. However, at the time of our visit, two of the three pumps were off line, and valved off. Only a single pump is currently operational. We do not know why this is the case. The entire pumping system (all three pumps) should be placed in operation as soon as possible. This is urgent as there is currently no redundancy in the system, so should the one active pump be lost, the upper floors and possibly the entire complex will be without water. G. Domestic hot water heating systems The building has two domestic hot water heaters serving a single vertical storage tank. The heaters were manufactured by Raypak in 2008, and should, if properly serviced and maintained, have 10 or more years of life remaining. While at the site it was noted that the air filters which serve these heaters were loaded up with dirt. These filters should be washed, at least quarterly. Failure to do so could result in heater failure. The hot water storage tank was manufactured in This is very old for a storage tank. For it to have lasted this long, it has likely been serviced and re-lined, perhaps several times. The access cover should be pulled and the inside of the tank should be examined by a qualified service company. If the tank has not been regularly serviced and maintained, then there could be sufficient loss of metal to warrant a new tank. There is an existing expansion tank adjacent to the hot water heater. Expansion tanks are required to help regulate pressure in the system when there is no hot water demand. The installed expansion tank appears to be too small for the size of the hot water system in the complex, and may be partially responsible for some of the pressure problems that the

5 Ocean Towers Santa Monica, CA M & P Report page 5 building has been experiencing. We recommend that the sizing be checked, and the expansion tank be upsized as needed. H. Sewage ejection pit covers There are a series of sewage ejection and sump pits in the lower parking level of the building. The covers of the sewage ejection pits are not properly sealed, allowing sewer gases to escape into the room. Foam spray has been applied to the joints around the various openings around the sump pit cover. We recommend that the covers be modified or replaced with suitable tight fitting sealed and gasketed covers to prevent sewer gases from escaping into the room. I. Cooling towers Each building has a cooling tower. The towers were manufactured in 1999, and are therefore nearly 20 years old. The towers have galvanized steel basins. If well maintained, these types of towers generally have a 20 to 25 year expected useful life. We were unable to examine the inside of the tower basins, which are one of the most critical parts of the tower. The external portions of the basins which we were able to see did not appear to have any surface corrosion. However, pipe connections and other parts were corroded. The fan shafts have heavy corrosion. The bearings on one of the towers sound like they have failed, and have caused the fan wheel to spin improperly. Replacement of the towers should be planned for the very near future. The tower which has the bad bearings should be attended to as soon as possible. In lieu of replacement, the towers could be refurbished. A comprehensive refurbishment would include grinding the interior of the basin and other wetted surfaces to bare metal, and re-coating; replacing the shafts and fan wheels with new; replacing the bearings with new; replacing the belts with new; replacing the fill material; etc. While less expensive than a replacement, a refurbishment will increase the remaining life of the tower, but it will not provide the longevity, reliability, and efficiency of a new tower. J. Condenser water piping system One of the two condenser water piping systems observed in the cooling tower room appears to have been fairly recently replaced. The other condenser water piping system observed appears to have an older, and possibly original piping system. We recommend that samples of the remaining older condenser water piping be removed and evaluated in a laboratory to determine the condition and remaining useful life. Replacement of this piping may very well be recommended. K. Miscellaneous Drains While walking the site, Adam King noted that the drains in the heater room, the fire pump room, and other mechanical spaces no longer function. Since these rooms are vulnerable to pipe leaks and water discharge, it is important that these drains function properly. Suitable troubleshooting and repairs should be made to minimize damage in the event that water is discharged into these rooms.

6 Ocean Towers Santa Monica, CA M & P Report page 6 L. Heating hot water boilers The two heating hot water boilers were manufactured in 2001 and in They are therefore approximately 17 years old. Copper fin tube boilers such as this typically have a 20 to 25 year life, if maintained well, and the building has maintained a good water treatment program. Funds should be set aside for replacement in the next couple of years. M. Fire sprinkler heads We did not evaluate the fire sprinkler system as part of our work. However, it was noted that many of the fire sprinkler heads in the parking garage appear to be original, and are therefore nearing 50 years of age. According to the National Fire Protection Association (NFPA) Pamphlet 25, and local requirements, heads which are 50 years old must be either replaced, or tested to ensure that they will function if needed. If the heads are able to be retained, then this procedure needs to be repeated every 10 years until the heads are replaced. Accordingly, funds should be set aside for possible replacement. Longitudinal Crack in Sanitary Waste Pipe

7 Ocean Towers Santa Monica, CA M & P Report page 7 Corrosion and Leak in Sanitary Waste Pipe Corrosion and Leak in Sanitary Waste Pipe

8 Ocean Towers Santa Monica, CA M & P Report page 8 Foam Spray Used in an Effort to Seal Sewage Ejection Pit Vapor Leaks Severely Corroded Cooling Tower Fan Shaft

9 Ocean Towers Santa Monica, CA M & P Report page 9 Condenser Water Piping Surface Corrosion This report is just a brief overview of the issues observed during our single site visit, and was limited to a cursory evaluation of readily visible piping and equipment in the lower portion of the building. As noted, significant work is needed to restore these systems to a reliable condition. Further testing and evaluation is needed to have a full understanding of all the potential issues in the complex. Please review and contact me with any questions you may have. Very truly yours, FRUCHTMAN & ASSOCIATES David J. Fruchtman, P.E., CEM, IAPMO Certified Plumbing Inspector, IAPMO Certified Mechanical Inspector President

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance Groton Heights School Mechanical Evaluation TO: FROM: Amy Vaillancourt, Project Manager Harley Langford, Project Manger Jason Curtis, P.E. DATE: February 24, 2016; Revised May 31, 2016 On Monday, December

More information

Villas I at Snowden Overlook Condominium Suggested Home Maintenance Checklist July 27, 2018

Villas I at Snowden Overlook Condominium Suggested Home Maintenance Checklist July 27, 2018 Villas I at Snowden Overlook Condominium Suggested Home Maintenance Checklist July 27, 2018 Introduction As unit owners we are responsible for many aspects of our homes. Periodic maintenance can avoid

More information

Village of Sloan Smoke Testing September 2017

Village of Sloan Smoke Testing September 2017 Village of Sloan Smoke Testing September 2017 What is Smoke Testing? Smoke testing is used to detect any water other than wastewater entering the sanitary sewer system. This water could be coming from

More information

Top of the World Tower

Top of the World Tower Workplace Building Preventive Maintenance Checklist conducted for Top of the World Tower Conducted on 22 Oct 2018 11:00 AM Prepared by Greg Langley Location 1247 Dartmouth St, Albany, CA 94706, USA Completed

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

Plumber Level 3 Rev. May 2011

Plumber Level 3 Rev. May 2011 Level 3 C1 Commercial Sanitary Drainage Systems Duration: 16 hours 10 hours 6 hours This unit of instruction is designed to provide the Plumber apprentice with the basic knowledge and understanding of

More information

Eveready Flood Control Frequently Asked Questions

Eveready Flood Control Frequently Asked Questions Eveready Flood Control 773 533 4800 Frequently Asked Questions 1. Why do I flood? Flooding can be caused by either a problem in your sewer line or an overloaded municipal sewer system. If you flush toilets,

More information

SCOPE OF INSPECTION THE FOLLOWING SYSTEMS AND COMPONENTS, IF APPLICABLE, ARE INSPECTED DURING OUR STANDARD HOME INSPECTION.

SCOPE OF INSPECTION THE FOLLOWING SYSTEMS AND COMPONENTS, IF APPLICABLE, ARE INSPECTED DURING OUR STANDARD HOME INSPECTION. SCOPE OF INSPECTION THE FOLLOWING SYSTEMS AND COMPONENTS, IF APPLICABLE, ARE INSPECTED DURING OUR STANDARD HOME INSPECTION. Important Note: IF THE SYSTEMS AND COMPONENTS LISTED BELOW ARE NOT SPECIFICALLY

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#58619/Page 1/November 1, 2017 PLUMBING Executive Summary: Presently, the Plumbing Systems serving the building are cold water, hot water, sanitary, waste and vent system, storm drain piping, and natural

More information

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers. SECTION 22 10 00 PLUMBING PIPING AND PUMPS PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS PITTSBURG STATE UNIVERSITY HVAC and BUILDING AUTOMATION SYSTEM STANDARDS CHILLERS In new construction, liquid-cooled models are preferred for systems larger than 100 ton. o Trane, York and McQuay brands

More information

VSA SEWAGE PUMP. Capacities to 1600 gpm, Heads to 120, Horsepower range 3/4 thru 40, 3 thru 6 discharge, 1750 and 1150 operation.

VSA SEWAGE PUMP. Capacities to 1600 gpm, Heads to 120, Horsepower range 3/4 thru 40, 3 thru 6 discharge, 1750 and 1150 operation. Brochure# 228E 122011 TYPE VSA SEWAGE PUMP Capacities to 100 gpm, Heads to 120, Horsepower range 3/ thru 0, 3 thru discharge, 1750 and 1150 operation. HIGHLIGHTS Wet-Pit Installations Pumps Suspend From

More information

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc.

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc. FAARM-Underground Facility Conceptual Design Review Mechanical Systems Prepared by: Dunham Associates, Inc. April 17, 2012 Dunham Project Number: 0412145-000-00 Dunham Associates Inc. Page 1 of 8 Mechanical

More information

Induction Furnace Cooling Systems

Induction Furnace Cooling Systems Induction Furnace Cooling Systems One Foundry s Experiences By David Havel, P.E. Columbia Steel Casting Co., Inc. September 2016 Induction Furnace Cooling Systems 1 Induction Furnace Cooling Systems One

More information

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Design and Construction Standards SECTION PLUMBING EQUIPMENT SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES

More information

Mechanical System Description

Mechanical System Description 1. Building Description: Mechanical System Description The building is a Type-1B construction, 9-levels, non-high rise building with 67 affordable family housing units. The first level of the structure

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT

More information

PLUMBING CURRICULA OUTLINE

PLUMBING CURRICULA OUTLINE PLUMBING CURRICULA OUTLINE CORE CURRICULUM 2015 Basic Safety (Construction Site Safety Orientation) (12.5 Hours) (Module ID 00101-15) Presents basic jobsite safety information to prepare workers for the

More information

PLUMBING INSTALLATIONS

PLUMBING INSTALLATIONS PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT PLUMBING INSTALLATIONS A homeowner guide to plumbing requirements for single-family dwellings November 2017 contents Permit Requirements... 3 Inspection Requirements...

More information

4. Plumbing fixtures. a) The plumbing fixtures are from the original building. They are appear old and not to comply with ADA requirements.

4. Plumbing fixtures. a) The plumbing fixtures are from the original building. They are appear old and not to comply with ADA requirements. From: Jian Zhang Sheet: 1 of 8 Date of Visit: 12/7/10 Coach House: Plumbing Systems b) All original building storm piping shows significant signs of aging. b) All original building sanitary piping shows

More information

Read Only Document Not For Distribution

Read Only Document Not For Distribution Chapter 9 Indirect Waste Piping and Special Wastes 9.1 INDIRECT WASTES 9.1.1 General Drains from fixtures, fixture compartments, equipment, appliances, appurtenances, and other devices requiring protection

More information

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES 2.05 PLUMBING GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.05 It is expected that the plumbing design professional will conform to accepted good engineering design practices.

More information

Mechanical Inspection Plumbing

Mechanical Inspection Plumbing 0811 Fixtures Sinks, drinking fountains, water closets, showers, etc. Classroom Sinks. Classroom sinks (19) are enameled cast iron self rimming side ledge with gooseneck faucet trim with index handles,

More information

TANKLESS PRODUCT GUIDE CANADA TANKLESS PRODUCT GUIDE. A. O. Smith

TANKLESS PRODUCT GUIDE CANADA TANKLESS PRODUCT GUIDE. A. O. Smith TANKLESS PRODUCT GUIDE CANADA TANKLESS PRODUCT GUIDE A. O. Smith www.hotwater.com A. O. Smith Tankless Advantage ENDLESS HOT WATER * Heating water only as it s being used means you will never run out of

More information

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS Presented to: Presented by: Sargon Ishaya, PE www.pragmaticprofessionalengineers.com Introduction Today s Agenda Overview Review

More information

Choosing the Right Pump

Choosing the Right Pump Choosing the Right Pump Pumps are used to move fluid from one destination to another. They come in many different shapes, sizes, and operated by either electric motor, engine, by hand or solar power. They

More information

RESIDENTIAL FIRE SPRINKLER SYSTEMS POLICY

RESIDENTIAL FIRE SPRINKLER SYSTEMS POLICY RESIDENTIAL FIRE SPRINKLER SYSTEMS POLICY Plan Submittal and Inspection Requirements Revised 01/18/18 All residential fire sprinkler systems within the jurisdiction of the Fire Department shall meet all

More information

HYBRID ADIABATIC Cooling System

HYBRID ADIABATIC Cooling System Blending Conveying Drying Process Cooling Heat Transfer Size Reduction HYBRID ADIABATIC Cooling System Water & Energy Savings Low Maintenance Improved Health & Safety Hybrid design combines dry cooler

More information

How about Savings in Time, Money, Energy and Longer Life?

How about Savings in Time, Money, Energy and Longer Life? Chapter 17: The Value of Maintaining Evaporative Cooling Equipment 97 The Value 17 of Maintaining Evaporative Cooling Equipment 1. Cooling Tower Maintenance and Upgrades... What s in it for You? How about

More information

The Ultimate Home Inspection Checklist

The Ultimate Home Inspection Checklist The Ultimate Home Inspection Checklist This checklist is not meant to take place of a professional home inspection and does not contain every aspect of a home inspection. Use the checklist as a guide and

More information

MONTECITO FIRE PROTECTION DISTRICT

MONTECITO FIRE PROTECTION DISTRICT Section 5a MONTECITO FIRE PROTECTION DISTRICT FIRE PROTECTION PLAN Residential Automatic Fire Sprinkler System Installations I Automatic Fire Sprinkler System Standards 1. Definition and Standard: An automatic

More information

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and Element Z for technical

More information

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Ohio Administrative Code Rule Number OPC Section IPC origin Reason for proposed 4101:3-2-01 Alternate on-site 2015 Added definition

More information

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems about your house CE 28 k Assessing the Comfort and Safety of Your Home s Mechanical Systems The heating, ventilating and air conditioning (HVAC) systems are a vital part of every home. These mechanical

More information

GEOTHERMAL STORAGE TANKS

GEOTHERMAL STORAGE TANKS GEOTHERMAL STORAGE TANKS INSTALLATION OPERATION MAINTENANCE Instruction Manual The storage tank is sold as a component part. It has been factory equipped with a booster element, and thermostat with high

More information

I. STRUCTURAL SYSTEMS

I. STRUCTURAL SYSTEMS I. STRUCTURAL SYSTEMS A. Foundations Type of Foundation(s): Pier & Beam - Crawlspace Opinion: All exposed areas of the foundation were examined visually. Examination of the foundation was limited to photographs

More information

2016 Plumbing Supplemental Plan Review List

2016 Plumbing Supplemental Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Plumbing Supplemental Plan Review List POTABLE WATER SYSTEM P1. Specify which fixtures are for private use and which are for

More information

Domestic Pump Condensate Transfer Equipment

Domestic Pump Condensate Transfer Equipment Bulletin S-944L Domestic Pump Condensate Transfer Equipment CONDENSATE RETURN UNITS BOILER FEED UNITS LOW NPSH PUMPS VACUUM HEATING UNITS INDUSTRIAL VACUUM UNITS www.domesticpump.com Condensate Return

More information

CLE SERIES Fluid heating for emergency eyewash stations

CLE SERIES Fluid heating for emergency eyewash stations Keltech Electric Tankless Water Heaters CLE SERIES Fluid heating for emergency eyewash stations Contents 2 Keltech Electric Tankless Water Heaters 3 CLE Series Overview 4 Standard Features 6 Optional Features

More information

Industrial. Solutions brands you trust. Product Overview

Industrial. Solutions brands you trust. Product Overview Industrial Solutions brands you trust. Product Overview Industrial Pump Applications Crane & Systems design s the most efficient and economical pumps to serve the large diversity of industrial applications

More information

Rental Housing Inspection Guide

Rental Housing Inspection Guide BOONE FIRE DEPARTMENT Rental Housing Division 515-432-3446 www.boonegov.com/rental BUILDING DEPARTMENT Rental Housing Inspection Guide Boone Fire Department Welcome to the Rental Housing Inspection Guide

More information

Building Utilities 1 Plumbing and Sanitary Systems

Building Utilities 1 Plumbing and Sanitary Systems Building Utilities 1 Plumbing and Sanitary Systems Taken from UST Architecture exams by Arch. Rafael Alli Recommended review material for UST Preboard Exam Prepared by: arkireviewph.multiply.com Types

More information

1 Exam Prep Plumbing State Contractors Practice Exam 2

1 Exam Prep Plumbing State Contractors Practice Exam 2 1 Exam Prep Plumbing State Contractors Practice Exam 2 1 According to Chapter 64E-6, when sizing a grease interceptor used in a restaurant, the correct formula is. A. (S) x (EW 12) x (LF) B. (S) x (GS)

More information

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM SUMMARY 1234 Main St.Severn 21144 Buyer Name 07/18/2018 9:00AM Henry Toman MD License 32391 1st American Home Inspection, LLC 443-685-4062 henrytoman61@gmail.com The summary is meant to organize the defects

More information

Manufacturers Representatives Since Industrial Systems, Inc. Computer Support, Inc

Manufacturers Representatives Since Industrial Systems, Inc. Computer Support, Inc Manufacturers Representatives Since 1974 Industrial Systems, Inc. Computer Support, Inc. www.industrialsystems.org 1-800-460-0469 210-493-4200 ENGINEERED PRODUCTS FOR THE ENGINEERED ENVIRONMENT Sewage

More information

Mr. GoodTower Service Center

Mr. GoodTower Service Center GTSC-E 0615 Mr. GoodTower Service Center Specialists in Replacement Parts and Maintenance of Evaporative Cooling Equipment Call now for a free inspection on your Evaporative Cooling equipment to: Extend

More information

WKS 2200 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

WKS 2200 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- 8610 Production Avenue San Diego, California 92121 (858) 566-7465 Fax (858) 566-1943 WWW.BREEZAIRE.COM WKS 2200 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- Thank you for choosing a BREEZAIRE cooling

More information

BALTIMORE CITY RENTAL LICENSE INSPECTION FORM RENTAL LICENSING INSPECTOR GUIDANCE

BALTIMORE CITY RENTAL LICENSE INSPECTION FORM RENTAL LICENSING INSPECTOR GUIDANCE BALTIMORE CITY RENTAL LICENSE INSPECTION FORM RENTAL LICENSING INSPECTOR GUIDANCE Checklist items A - L may receive a result of Pass or Fail A. Railing is present for interior and exterior steps with more

More information

Sanitary Drainage Systems

Sanitary Drainage Systems 11.1 MATERIALS See Section 3.1. Sanitary Drainage Systems 11.2 BUILDING SEWERS AND BUILDING DRAINS 11.2.1 Sewer or Drain in Filled Ground Chapter 11 Building sewers or building drains that are installed

More information

plumbing for greywater

plumbing for greywater plumbing for greywater october 2015 christina bertea ~union trained journeywoman plumber (1978) ~plumbing contractor (1996) ~greywater action singingwater@jps.net plumbing for greywater basic parts of

More information

SECTION PLUMBING EQUIPMENT Piping (Plumbing). 2. Division 16 - Electrical Wiring and Connections.

SECTION PLUMBING EQUIPMENT Piping (Plumbing). 2. Division 16 - Electrical Wiring and Connections. SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15410 - Piping (Plumbing). 2. Division 16 - Electrical Wiring and Connections. 1.02 SUBMITTALS A. Submit properly identified

More information

BECAUSE TEMPERATURE MATTERS: MAINTAINING COOLING TOWERS

BECAUSE TEMPERATURE MATTERS: MAINTAINING COOLING TOWERS Service Application Manual SAM Chapter 650-013 Section 8D BECAUSE TEMPERATURE MATTERS: MAINTAINING COOLING TOWERS by Glenn A. Babcock Baltimore Aircoil Company Reprinted with permission from the Refrigerating

More information

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with

More information

1. Packaged Variable Air Volume (VAV) Rooftop Units (RTU) with Hot Water Reheat. 2. Geothermal Heat Pump VAV Rooftop Units with Hot Water Reheat

1. Packaged Variable Air Volume (VAV) Rooftop Units (RTU) with Hot Water Reheat. 2. Geothermal Heat Pump VAV Rooftop Units with Hot Water Reheat July 6, 2017 City of Countryside Attn: Mayor Sean McDermott City Hall 5550 East Avenue Countryside, IL 60525 RE: New City Hall & Police Building HVAC Options Dear Mayor McDermott, Per your request at our

More information

2009 IRC. and Fuel gas Provisions

2009 IRC. and Fuel gas Provisions 2009 IRC Q &A Plumbing, MechanICAl and Fuel gas Provisions TABLE OF CONTENTS PREFACE... vii ABOUT THE INTERNATIONAL CODE COUNCIL...viii PLUMBING PROVISIONS... 1 CHAPTER 25 PLUMBING ADMINISTRATION....3

More information

Building Department Informational Handout

Building Department Informational Handout City of Sonoma Building Department Informational Handout Residential Water Heaters Handout No: 15 Revised: 4/26/18 A water heater is an appliance designed to supply hot water and is equipped with automatic

More information

Home Set-up and Maintenance. Maintenance

Home Set-up and Maintenance. Maintenance Home Set-up and Maintenance Home Set-up and Maintenance When moving into a resale home, there are some things that you will want to take care of. This list focuses on things related to the house, rather

More information

DIVISION 15 MECHANICAL

DIVISION 15 MECHANICAL DIVISION 15 MECHANICAL A. GENERAL DESIGN CONDITIONS 1. Design occupied spaces to maintain 72 F and a space dew point temperature not to exceed 55 F. 2. Design classroom and office space buildings with

More information

C1N & C2N SERIES Fluid heating for light industrial applications

C1N & C2N SERIES Fluid heating for light industrial applications Keltech Electric Tankless Water Heaters C1N & CN SERIES Fluid heating for light industrial applications Contents Keltech Electric Tankless Water Heaters C1N & CN Series Overview Standard Features 6 Optional

More information

Full-line Product Overview

Full-line Product Overview Full-line Product Overview End Suction Centrifugal Pumps This general purpose pump can be configured in frame-mounted and close-coupled, semi-open and enclosed impeller configurations. They are available

More information

Improving Condenser Safety In Cold Chain Facilities

Improving Condenser Safety In Cold Chain Facilities Improving Condenser Safety In Cold Chain Facilities Gerald Anderson, PE Eastern Regional Sales Manager, Refrigeration 30 plus years in the refrigeration industry AGENDA Overview and Goals Basic Definitions

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

FREQUENTLY ASKED QUESTIONS

FREQUENTLY ASKED QUESTIONS FREQUENTLY ASKED QUESTIONS DRAIN WATER HEAT RECOVERY... 2 What is drain water heat recovery?... 2 Why is it important to recover heat from drain water?... 2 ZYPHO TECHNOLOGY... 2 How does ZYPHO work?...

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

John Sample. Property Address: 123 Main St. Alpharetta GA Inspector: Jason David. Residential Inspector of America, Inc.

John Sample. Property Address: 123 Main St. Alpharetta GA Inspector: Jason David. Residential Inspector of America, Inc. John Sample Property Address: 123 Main St. Alpharetta GA 30022 Inspector: Jason David Residential Inspector of America, Inc. 3276 Buford Drive, Ste. 104-306 Buford, GA 30519 770.476.4963 ICC Certified

More information

FEATURES. Other Fed-Flush Arrangements

FEATURES. Other Fed-Flush Arrangements Brochure # 0710 TYPE TYPE... VSAF SEWAGE EJECTOR SYSTEM Flows to 600 gpm, Heads to 120, 1 thru 40 HP. Discharge size 4, 1750 and 1150 RPM, strainer in discharge pipe. HIGHLIGHTS Installations where rags

More information

CENTRAL GEORGIA TECHNICAL COLLEGE. Maintenance, Custodial & Operation Plan Facilities & Equipment

CENTRAL GEORGIA TECHNICAL COLLEGE. Maintenance, Custodial & Operation Plan Facilities & Equipment CENTRAL GEORGIA TECHNICAL COLLEGE Maintenance, Custodial & Operation Plan Facilities & Equipment Central Georgia Technical College Maintenance, Custodial and Operation Plan In order that Central Georgia

More information

Residential Water Conservation Research Brief On-Demand Hot Water Systems

Residential Water Conservation Research Brief On-Demand Hot Water Systems Overview Water heating is the second highest consumption of energy in the residential sector, accounting for 17 percent of consumed energy for the average Canadian household. Each year, residents allow

More information

Maintain. a TOWER of POWER. Part One How to. Don t let out of site, out of mind prevent you from keeping cooling towers running efficiently

Maintain. a TOWER of POWER. Part One How to. Don t let out of site, out of mind prevent you from keeping cooling towers running efficiently Part One How to Maintain a TOWER of POWER Don t let out of site, out of mind prevent you from keeping cooling towers running efficiently BY GLENN A. BABCOCK The cooling tower is often the forgotten component

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL T Edition 0 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 88 STRATFORD, CT 0665

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS 17 West Street West Hatfield, MA 01088 Phone: (413) 247-3380 * (800) 582-8423 Fax: (413) 247-3369 E-mail: info@stiebel-eltron-usa.com SB 150, SB 200 Glass Lined Indirectly Fired Water Heaters With Single

More information

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- 8610 Production Avenue San Diego, California 92121 (858) 566-7465 Fax (858) 566-1943 WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- Thank you for choosing a BREEZAIRE cooling unit. We believe

More information

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.

More information

Test Code: 8117 / Version 1

Test Code: 8117 / Version 1 Pennsylvania Customized Assessment Blueprint Plumbing Technology/Plumber PA Test Code: 8117 / Version 1 Copyright 2012. All Rights Reserved. General Assessment Information Plumbing Technology/Plumber PA

More information

TOTAL SYSTEM EFFICIENCY: AN INTRODUCTION TO CONDENSING BOILERS. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: AN INTRODUCTION TO CONDENSING BOILERS. David Grassl PE Mechanical Engineer Principal TOTAL SYSTEM EFFICIENCY: AN INTRODUCTION TO CONDENSING BOILERS David Grassl PE Mechanical Engineer Principal Boilers are closed pressure vessels that are used to heat fluids -- either water or steam. They

More information

Land Use and Environmental Service Agency (Code Enforcement) Plumbing 2010

Land Use and Environmental Service Agency (Code Enforcement) Plumbing 2010 General: 1) (Q) Who enforces the cutting and notching requirements found in the plumbing code? (A) The plumbing inspector would question the contractor initially. A building inspector would either take

More information

2015 UPC Chapter 8 Indirect Wastes RV

2015 UPC Chapter 8 Indirect Wastes RV PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.

More information

Is It Always Cost-effective

Is It Always Cost-effective Remodeling to Save Energy: Is It Always Cost-effective for a Public Library? J. Parke Randall, AIA Pecsok, Jelliffe & Randall Architects Indianapolis, IN The most energy efficient building is one where

More information

Ventilation for New Low-Rise Residential Buildings July 20, 2015

Ventilation for New Low-Rise Residential Buildings July 20, 2015 Ventilation for New Low-Rise Residential Buildings July 20, 2015 BSC Standard 01 2015 Building Science Corporation 3 Lan Drive, Suite 102 Westford, MA 01886 www.buildingscience.com Contents 1. PURPOSE...3

More information

Condensation On Windows

Condensation On Windows Condensation On Windows Window condensation is a combination of the moisture content and the temperature of the indoor air in your home. Window condensation is caused because the humid air inside your

More information

SAFETY PLUMBING PACKAGES. Quality Products & Value Packages SUSTAINABILITY. Residential Solutions ANTI-SCALE SYSTEMS FIRE PROTECTION

SAFETY PLUMBING PACKAGES. Quality Products & Value Packages SUSTAINABILITY. Residential Solutions ANTI-SCALE SYSTEMS FIRE PROTECTION Quality Products & Value Packages Residential Solutions FIRE PROTECTION COMFORTSUSTAINABILITYCONTROL PRESSURE REGULATORS TRENCH DRAINSHVAC SYSTEMS SAFETY ANTI-SCALE SYSTEMS HEATING & COOLING CONTROLS PLUMBING

More information

COHASSET, MA March 6, The following is the HVAC outline specifications, which defines the scope of work of the HVAC system.

COHASSET, MA March 6, The following is the HVAC outline specifications, which defines the scope of work of the HVAC system. 23 00 00 HEATING, VENTILATING & AIR-CONDITIONING The following is the HVAC outline specifications, which defines the scope of work of the HVAC system. PART 1 GENERAL 1.1 CODES A. All work installed under

More information

MECHANICAL DESIGN. Full service Mechanical Design Professionals that can provide the full package!

MECHANICAL DESIGN. Full service Mechanical Design Professionals that can provide the full package! MECHANICAL DESIGN Full service Mechanical Design Professionals that can provide the full package! We specialize in commercial and industrial mechanical system designs that are integral to the building

More information

Progressive Cavity Sewer Systems

Progressive Cavity Sewer Systems Progressive Cavity Sewer Systems Engineered to do one job Perfectly. At the heart of the E/One Sewer System is the toughest, hardest working pump in the industry. The new standard in excellence, durability,

More information

Gulfport, Mississippi 21 May 2007

Gulfport, Mississippi 21 May 2007 G PLUMBING GENERAL REQUIREMENTS The D-BC shall design the plumbing system to comply with this criteria and the Plumbing Code. Piping shall be shown on the same plan as the fixtures being served. Pipe size

More information

S AGE E NGINEERING A SSOCIATES, LLP

S AGE E NGINEERING A SSOCIATES, LLP S AGE E NGINEERING A SSOCIATES, LLP 1211 Western Avenue Albany, NY (518) 453 6091 F (518) 453 6092 Kingston Library Mechanical and Electrical Systems Field Report Date of Visits: Mechanical - September

More information

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5 Page 1 of 5 1. SYSTEM DESCRIPTION Viking supervised, single interlocked preaction pre-primed systems utilize a Viking Deluge Valve (A.1) and a hydraulically pressurized automatic sprinkler system. The

More information

Hempcrete building and Solar thermal reincarnation

Hempcrete building and Solar thermal reincarnation Hempcrete building and Solar thermal reincarnation Dorje Denma Ling Shambala center, Tatamagouch, Nova Scotia. This is Wilber not parked on Bedford Ave. Malagash Harbor. In the woods surrounding the Shambala,

More information

FIRE/SMOKE BARRIER FUNDAMENTALS

FIRE/SMOKE BARRIER FUNDAMENTALS FIRE/SMOKE BARRIER FUNDAMENTALS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire OBJECTIVE Identify the different

More information

Lecture : Introduction to building services I - Plumbing & Drainage Services 22 September 2016

Lecture : Introduction to building services I - Plumbing & Drainage Services 22 September 2016 SBS4113 Architecture & Buildings http://ibse.hk/sbs4113/ Lecture : Introduction to building services I - Plumbing & Drainage Services 22 September 2016 Guest teacher : Ir. Eur Ing. K P Cheung Faculty of

More information

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS AUTOMATIC MAKE-UP AIR DAMPER WITH READ AND SAVE THESE INSTRUCTIONS FOR RESIDENTIAL USE ONLY Page 1 WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: 1. Installation

More information

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information Charles M. LeMaistre PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and

More information

Sprinkler Identification Number (SIN)

Sprinkler Identification Number (SIN) Worldwide Contacts www.tyco-fire.com Series DS-3 Dry-Type Sprinklers 11.2K Horizontal Sidewall Standard Response, Extended Coverage General Description TYCO Series DS-3 Dry-Type Sprinklers, 11.2K Horizontal

More information

Statutory Compliance Checklist

Statutory Compliance Checklist Date of Issue: April 2017 Statutory Compliance Checklist This document is for clergy and churchwardens to help them in the maintenance of their Churches. Refer to supplementary notes for further guidance.

More information

Charter Township of Flushing Construction Permit Fee Schedule.Construction and Development Services Department

Charter Township of Flushing Construction Permit Fee Schedule.Construction and Development Services Department Charter Township of Flushing Construction Permit Fee Schedule.Construction and Development Services Department 1. CONSTRUCTION PERMIT FEES: A. General: Fee basis/value of construction shall be determined

More information

HOME INSPECTION CHECKLIST

HOME INSPECTION CHECKLIST HOME INSPECTION CHECKLIST Date: Page 1 of 9 Client Name: Address: Tel No: Surname: Email: A WATER METER 1 Is the water meter visible YES NO 2 Water meter registers when water is drawn YES NO 3 Water meter

More information

The Evolution of. Hot Water. Generation Systems. -Ron George. Geysir at Haukadalur, Iceland ( Ron George, 2016)

The Evolution of. Hot Water. Generation Systems. -Ron George. Geysir at Haukadalur, Iceland ( Ron George, 2016) The Evolution of Hot Water Generation Systems -Ron George 18 / SEPTEMBER 2018 Geysir at Haukadalur, Iceland ( Ron George, 2016) INFOCUS Water Heater Terminology Appliances that heat water for domestic

More information