1 Research and Development of Residential Heat Pump Midterm Report: Performance Analysis and Design Crosby Laboratory Department of Mechanical Engineering University of Maine Orono, Maine Team Members: Donald S. Jarvi Adam Koppel Kyle Knowlton Eric Bragdon Advisor: Jim LaBrecque
2 Abstract: The following will include detailed information relating to the progress of development on the residential heat pump unit. Information will include performance test data of the fans, compressors, and heat exchangers as well as public relations progress and goals to be accomplished the following semester. Objective: The heat pump unit was assembled and partially designed by a previous team of mechanical engineering technology students. The unit was in operating condition and took little preparation in getting the unit to operate. Our main goal for this semester was to improve, enhance, and optimize the features of the heat pump making the unit have higher performance and operate more efficiently. Just by inspection, without the unit running, we noticed several areas improvement such as fan positioning, aesthetics, and controls. Currently, the controls system is in crude shape and takes up an unnecessary volume. The aesthetics of the unit resemble a prototype, which is in fact what the unit is, and also has loose structure. By the end of this project, we hope to have a unit that will closely resemble that of one that would be sold by retailers. Performance: Upper Heat Exchanger Fan: After the unit was up and operating, performance data was taken on the compressor, fans, and heat exchangers. Using the fans performance data provided by the manufacturer, we immediately saw that the upper coil fan (condenser in the winter evaporator in the summer) was oversized. But due to the complex positioning of the upper heat exchanger, various pressure drops would cause this data to be different than the actual capacity of the fan in our setting. So, an air velocity meter was used to gather a velocity profile of both upper and lower fans.
3 Figure 1: A velocity profile as a function of height on upper heat exchanger. Integrating the velocity profile gives an average velocity of ft/min. Using the exposed heat exchanger area of 1.02 ft 2, the air volumetric flow can be computed using Q=VA, giving an air flow of 810 CFM. From the manufacturer s fan curve, we should be achieving about 1200 CFM. This makes the fan less efficient than if a properly sized fan was used due to unnecessary pressure drops across the awkwardly positioned heat exchanger. Lower Heat Exchanger Fan: For the lower heat exchanger, a radial orientation was used to gather the velocity profile. Figure 2: A velocity profile as a function of radius for the lower heat exchanger.
4 Integrating the velocity profile gave an average velocity of 857 ft/min. For the lower heat exchanger, an area of ft 2 was used giving a flow rate of CFM. However, this fan is not oversized where the desired capacity is higher than that of the upper fan. Compressor: Compressor performance data was computed after collecting air temperatures off of the heat exchangers, subcooling temperatures, and subcooling pressures. Temperatures were collected using a handheld air temperature gage thermocouples attached to subcooling pipes. Pressure readings were taken using a Texas Instruments pressure transducer. Heat Energy and Electrical Input vs. Outside Temperature Heat Energy (tons) Electrical Input (watts) Heat Energy (tons) Electrical Energy (watts) Outside Temperature (F) Figure 3: Graphical display of heat energy received and electrical energy put in as a function of outdoor air temperature.
5 Figure 4: Plot of coefficient of performance represented in terms of Carnot and refrigerant performance as a function of outdoor air temperature. As seen in figures 3 and 4, the compressor delivers a reasonable amount of thermal energy while reaching COP s in the range of 3.5 on mild days. NOTE: much of the
6 thermodynamic analysis of the compressor depends on the isentropic efficiency of the comressor which we assumed to be n =.9. Upper Heat Exchanger: During test analysis, quick temperature readings were taken at various points on both heat exchangers using an infrared temperature gage. With the compressor running at about 60%, the temperatures on the upper heat exchanger were 110 F where the desired temperature is about 95 F. The group concluded that this is a poor configuration of fan size and heat exchanger size combination. Lower Heat Exchanger: The lower heat exchanger configuration with its fan seems to be performing to our desired standards. The group decided to keep this configuration. Design: After test analysis was completed, areas for improvement were exposed mainly in the upper heat exchanger. A new fan was sized based on air flow capacity, sound pressure level, and positioning. The group decided on the EBM Papst R4E310-AR This fan is different than the axial fan currently installed on the unit. It features a motorized impeller design that delivers the same capacity, but with lower sound pressure level and more capable of overcoming such static pressure over the upper heat exchanger. The new fan was sized for the following specifications provided to us by the manufacturer. Figure 5: Fan performance curves provided by the manufacturer. Curve numbers represent model numbers provided in Figure 6. Source: EBM Papst.
7 Figure 6: Fan performance data provided by manufacturer. Selected fan is highlighted in yellow. Source: EBM Papst. New Features: Several new features that the group plans to add to the unit include air filters, sterile UV lighting, humidification nozzles, and domestic hot water heat exchanger. Air Filters: The group decided to use the AspenAire FG which measures 14 x14 and has a power usage of less than 2 W at 24 VAC. Domestic Hot Water Heat Exchanger: The group chose the Turbotec Turbo-Flow BTSSN-12 air to water heat exchanger. This new technology features an inner coil that creates turbulance in the fluid being heated/cooled. This drastically increases the COP of the unit in the summer where the unit is being an as an air conditioner as well as a water heater simultaneously. All other new features have not been precisely sized and have not yet decided on a manufacturer at this time. Conclusion: Our team has learned a lot this semester about heat pump technology and the refrigeration cycle. Our advisor Jim LaBrecque has been a great help with teaching us how to solve real-world issues associated with refrigeration equipment, and has helped us to get funding for next semester. Another part of our project has been raising awareness about heat pump technology and the energy savings associated with it. Our public relation work included attending a climate change expo, a winter energy and heating expo, and a news interview with channel 2 WLBZ, all of which showcased our senior project. Our milestones changed from our initial list to incorporate our PR work. Our design also changed to allow for a new top fan on the unit. Our milestone list for next semester includes rebuilding the unit and changing the layout, using most of the parts we already have. Once our new parts are ordered and arrive, we will use our SolidWorks drawings to help fabricate a new case and we will begin construction.
8 Parts List: Compressor Panasonic Rotary model 5KD240XAC21 Spec. No. SC A Capacity: 2 Ton Electronic Expansion Valve Parker Electronically Controlled type with 650 steps of resolution Inlet: 1/4" Outlet: 3/8" Coils AlumiCool Micro-channel Top coil dimensions: 15.55" x 10.2" Bottom coil dimensions: 15.55" x 30.2" Filter Dryer Parker Size: 4.5" long x 3" diameter Top Fan EBM Papst EC centrifugal fan model R3G 310-AP52-01, motor M3G074-CF Inlet ring: model Size: 310mm diameter Blade style: backward-curved Bottom Fan EBM Papst EC Axial fan model A3G300- AB56-02 Size: 300mm Blade style: sickled Ventilation Fan EBM Papst VarioPro model 6248N12P Desuperheater Coil For DHW Production TurboTec model BTSSN-12
9 Appendix A: Test data collected for compressor performance analysis. Done by Adam Koppel 12/14/2008 Fixed Indoor Condensing psia Comp. Displacement 24 cm^3 / rev. Supply Temp ft^3 / rev Sub-cool 5 Superheat 10 n compressor 0.9 changable BTU / lbm BTU / lbm-r Ft^3 / lbm Changeable lbm / hr Enthalpy Entering Entropy Entering Outside Temp. Evaporator Temp. ρ Vapor Entering rpm Compressor Mass flow rate Compreesor Compressor
10 fixed Assuming Coil can handle load Isentropic Isentropic Enthalpy taking Temp. Exiting Enthalpy Exiting isentropic n into Actual Comp. Enthalpy Exiting Compressor Compressor Account Exiting Temp. Condenser
11 TU/ hr Tons BTU / lbm BTU/ hr BTU / lbm BTU/ hr Watts dot high Tons of Heating Q low Q dot low W Compressor W dot Compresser W dot Compresser COP Carnot 9.25 COP Refirgerant
12
Refrigeration Systems
Refrigeration Systems COP COP = coefficient of performance Air conditioners, refrigerators: COP=QL/Wnet Heat pumps: COP=QH/Wnet Energy balance: Wnet+QL=QH From Cengel, Thermodynamics: An Engineering Approach,
More informationMechanical Engineering Laboratory
Mechanical Engineering Laboratory MEE 416 Professor H. Ezzat Khalifa Syracuse University http://lcs.syr.edu/faculty/khalifa/mee416/ MEE416 1 A. Experiment 1 Air-Conditioning: Air-side Experiment 0031 Link
More information3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?
Code No: RR410305 Set No. 1 IV B.Tech I Semester Regular Examinations, November 2006 REFRIGERATION & AIR CONDITIONING (Mechanical Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions All
More information"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"
"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger" 1 Prof.Gaffar G.Momin, 2 Sagar B. Tupe, 2 Swapnil A. Parate 2 Omkar G. Yewale 2 Aakash P.
More informationThermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler
Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler Author: Volodymyr Voloshchuk Vl.volodya@gmail.com Introduction In
More informationTEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #32 System Soft-Optimized Test of Refrigerant D2Y60 in Air Source
More informationDevelopment of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering
Session 2633 Development of a Psychrometric Test Chamber Michael J. Swedish Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Acknowledgments The design of the Psychrometric
More informationMechanical Heat Pump R515
P.A.Hilton Ltd Mechanical Heat Pump R515 Above: R515 shown fitted with standard wattmeter Stabilises in minutes allowing many tests to be conducted in a typical laboratory period. Allows a complete refrigerant
More informationCombination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer
Paper ID #6647 Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer Dr. Lin Lin, University of Southern Maine Dr. Lin joined Department of Engineering at University
More informationDhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK
St.MARTIN S ENGINEERING COLLEGE Dhulapally, Secunderabad-500 014 Subject: REFRIGERATION AND AIR CONDITIONING Class : ECE III 1 Define Unit of refrigeration. 2 Define C.O.P. QUESTION BANK 3 What is the
More informationDesign of a Low capacity Evaporator of a Refrigeration Unit
Session 3666 Design of a Low capacity Evaporator of a Refrigeration Unit Alireza Mohammadzadeh Padnos School of Engineering Grand Valley State University Overview This project has been assigned to students
More informationLow GWP Refrigerants for Air Conditioning Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta
More informationME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3
ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes
More informationChapter 9. Refrigeration and Liquefaction
Chapter 9 Refrigeration and Liquefaction Refrigeration is best known for its use in the air conditioning of buildings and in the treatment, transportation, and preservation of foods and beverages. It also
More informationEnergy Use in Refrigeration Systems
2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is
More informationII. OBJECTIVE OF RESEARCH
Enhancement of Coefficient of Performance of Vapor Compression Refrigeration System Using Diffuser at let of Condenser Mr. Nurul Seraj 1, Dr. S. C. Roy 2 1 Student, 2 Head of Department, Department of
More informationINSTITUTE OF AERONAUTICAL ENGINEERING
1 P a g e INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad -00 043 MECHANICAL ENGINEERING QUESTION BANK Name : REFRIGERATION AND AIR CONDITIONING Code : A60334 Class : III B. Tech
More informationTranscritical CO2 Bottle Cooler Development
Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains
More informationMath. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.
HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +
More informationPressure Enthalpy Charts
Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance
More informationRotodynamic Pumps INTRODUCTION:
Rotodynamic Pumps INTRODUCTION: Liquids have to be moved from one location to another and one level to another in domestic, agricultural and industrial spheres. The liquid is more often water in the domestic
More informationThe Refrigeration Cycle
Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.
More informationTEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)
More informationThe Refrigeration Cycle
Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.
More informationTEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A
More information(Refer Slide Time: 00:00:40 min)
Refrigeration and Air Conditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 10 Vapour Compression Refrigeration Systems (Refer Slide
More informationSubscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid
Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance
More informationExperimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract
Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant M. Honma, T. Tamura, Y. Yakumaru and F. Nishiwaki Matsushita Electric Industrial Co., Ltd. Living Environment
More informationBehavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32
More informations. Properties for R134a are as follows : Saturated R-134a Superheated R-134a
CHAPTER 9 REFRIGERATION & AIR-CONDITIONING YEAR 2012 ONE MARK Common Data For Q. 1 and Q.2 A refrigerator operates between 120 kpa and 800 kpa in an ideal vapour compression cycle with R-134a as the refrigerant.
More informationTEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #47 System Drop-in Test of R-32 and Refrigerant Blends ARM-71a,
More informationENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER
Poster P.4.2 - - ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER Jan Sedlar, University Centre for Energy Efficient Buildings and Faculty of Mechanical Engineering, Czech Technical University in Prague, Czech
More informationPerformance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in
More informationpdfmachine trial version
HVAC PROBLEM SHEET # 02(REVERSED BRAYTON CYCLE) 1. 500 kg of atmospheric air is circulated per hour in an open type of refrigeration installation. The air is drawn from the cold chamber at temperature
More informationME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY
ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY MASS & E ERGY BALA CES I PSYCHROMETRIC PROCESSES EXPERIME T 3 1. OBJECTIVE The object of this experiment is to observe four basic psychrometric processes
More informationTEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled
More informationR10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)
Set No. 1 IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec - 2014 REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering) Time: 3 hours Max. Marks: 75 Answer any FIVE Questions All Questions
More informationREFRIGERATION CYCLES
REFRIGERATION CYCLES Carnot Cycle We start discussing the well-known Carnot cycle in its refrigeration mode. Figure 1: Carnot Cycle In this cycle we define the coefficient of performance as follows: COP
More informationRefrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 26 Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants Jit Guan
More informationR07. Answer any FIVE Questions All Questions carry equal marks *****
Set No: 1 III B.Tech. II Semester Supplementary Examinations, April/May 2013 REFRIGERATION AND AIR CONDITIONING (Mechanical Engineering) Time: 3 Hours Max Marks: 80 Answer any FIVE Questions All Questions
More informationTechnical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler
Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System
More informationMASS. MARITIME ACADEMY
MASS. MARITIME ACADEMY REFRIGERATION LAB OUTLINE Rev.3 Fall 2015 Table of Content Page Lab #1: Introduction to refrigeration system components, tools and procedures 1 Lab #2: Familiarization, operation,
More informationU.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India
DESIGN OF HYBRID AIR COOLER USING VAPOUR COMPRESSION REFRIGERATION SYSTEM Vimalkirti Shende 1, Sushil Borkar 2, Touseef Iqbal Qureshi 3 Asst. Prof. Nikhil Bhende 1 1,2,3 U.G. Student, Department of Mechanical
More informationCHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM
111 CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 7.1 INTRODUCTION Energy is the primary component to run any system in the world. According to
More informationWeek 9. Refrigeration Cycles I. GENESYS Laboratory
Week 9. Refrigeration Cycles I Objectives 1. Introduce the concepts of refrigerators and heat pumps and the measure of their performance. 2. Analyze the ideal vapor-compression refrigeration cycle. 3.
More informationH EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative
A U.S. Environmental Protection Agency survey released in 2007 concluded that IT data centers consumed 61 billion kw of electricity at a total cost of $4.5 billion in 2006. As energy costs continue to
More informationExecutive Summary. Number of Low Number of High Number of Faults , Number of OK
Unit Lower limit Upper limit Air on Model no evap. F Air off evap. F dt air evap. F Executive Summary Evapo. F This is a summary chart for quick reference and view of all the systems tested. Red boxes
More informationMain Characteristics of Appliances for Transport and Compression of Air
Ing. Pavel Dostál, Ph.D., Ostrava University 1 Main Characteristics of Appliances for Transport and Compression of Air Some of the main technical characteristics of appliances for the transport and compression
More informationTEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #53 System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton
More informationPRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division
INTRODUCTION PRESSURE-ENTHALPY CHARTS AND THEIR USE The refrigerant in a refrigeration system, regardless of type, is present in two different states. It is present as liquid and as vapor (or gas). During
More informationTEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat
More information(ME-225) HEATING, VENTILATION AND AIR-CONDITIONING SYSTEM
(ME-225) HEATING, VENTILATION AND AIR-CONDITIONING SYSTEM MUHAMMAD UMER SOHAIL PhD, AEROSPACE SCHOLOR (INSTITUTE OF SPACE TECHNOLOGY) MS POWER MECHANICAL (MUST) MBA (COL) EXECUTIVE (SAARC AIOU) BSC MECHANICAL
More informationModeling And Testing Of R23/R134a Mixed Refrigerant System With Water Cooled Separator For Low Temperature Refrigeration
Marquette University e-publications@marquette Master's Theses (2009 -) Dissertations, Theses, and Professional Projects Modeling And Testing Of R23/R134a Mixed Refrigerant System With Water Cooled Separator
More informationEnhancement of COP in Vapour Compression Refrigeration System
Enhancement of COP in Vapour Compression Refrigeration System M. Krishna Prasanna #1 M.E student, Heat Transfer studies in Energy Systems Department of Mechanical Engg., Andhra University Visakhapatnam-530003,
More informationPaper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration
Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration 11.1 Introduction Preservation of foods is a vital processing step in food processing. There are
More informationSession: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island
Session: HVAC 101 HVAC 101 Steve Sain Sain Engineering Associates, Inc. August 9, 2016 Rhode Island Convention Center Providence, Rhode Island Why? 2 Acknowledgements 3 Disclaimer I m gonna shoot down
More informationTHERMAL ENGINEERING LABORATORY II. To train the students with principles and operation of thermal Engineering equipments.
AIM: THERMAL ENGINEERING LABORATORY II To train the students with principles and operation of thermal Engineering equipments. OBJECTIVES: To experimentally analyze conduction, convection and radiation.
More informationPerformance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical
More informationPerformance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Shoeb Inamdar 1, H. S. Farkade 2 P.G. Student, Department of Mechanical Engineering, Govt. College of Engg. Amravati. Maharashtra,
More informationShort Questions with Answers APPLIED THERMODYNAMICS(5 TH MECHANICAL) Chapter No-1
Short Questions with Answers APPLIED THERMODYNAMICS(5 TH MECHANICAL) Chapter No-1 1. Define mechanical efficiency in case of an IC engine? [2015w] Ans. Mechanical efficiency of an I.C. engine is defined
More information: REFRIGERATION & AIR CONDITIONING COURSE CODE : 6023 COURSE CATEGORY : A PERIODS/ WEEK : 6 PERIODS/ SEMESTER : 90 CREDIT : 6 TIME SCHEDULE
COURSE TITLE : REFRIGERATION & AIR CONDITIONING COURSE CODE : 6023 COURSE CATEGORY : A PERIODS/ WEEK : 6 PERIODS/ SEMESTER : 90 CREDIT : 6 TIME SCHEDULE MODULE TOPIC PERIODS 1 Introduction. Applications
More informationTechnical Presentation on
Technical Presentation on PID _00012345 Heating and refrigeration system using waste heat energy Photo (Author 1) Photo (Author 2) Author 1 Name Author 2 Name Restricted Circulation L&T Technology Services
More informationMECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS
MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS MASS BALANCES, PSYCHROMETRICS & HVAC 1 Copyright 2018. All rights reserved. How to use this book The exam specifications in effect since
More informationRefrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology
Refrigeration Cycles MOHAMMAD FAISAL HAIDER LECTURER Department of Mechanical Engineering Department of Mechanical Engineering Bangladesh University of Engineering and Technology Objectives Introduce the
More informationAn Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner
An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner P. Suntivarakorn, S. Satmarong, C. Benjapiyaporn, and S. Theerakulpisut Abstract This paper was to study the clothes
More informationPerformance Testing of Unitary Split-System Heat Pump with an Energy Recovery Expansion Device
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Performance Testing of Unitary Split-System Heat Pump with an Energy Recovery
More informationREFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis
REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system
More informationPerformance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a
International Journal of Research in Engineering and Science (IJRES) ISSN (Online): 2320-9364, ISSN (Print): 2320-9356 Volume 4 Issue 6 ǁ June. 2016 ǁ PP. 52-57 Performance analysis of a vapour compression
More informationKing Fahd University of Petroleum and Minerals Department of Mechanical Engineering. ME 431: Refrigeration. Laboratory Manual
King Fahd University of Petroleum and Minerals Department of Mechanical Engineering ME 431: Refrigeration Laboratory Manual February 2001 2 Table of Contents Contents Page # Safety Regulations 3 Lab Regulations
More informationCompendium DES July 2016, CARN
Compendium DES July 2016, CARN 1 Contents Contents... 2 1. Energy balance... 4 Using Energy Balance for analyzing energy systems... 4 Energy Balance definition... 4 Steady state, steady flow... 4 Methodology...
More informationPerformance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant
International Journal of Scientific and Research Publications, Volume 4, Issue 7, July 2014 1 Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170
More informationThe Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 The Development Of High Efficiency Air Conditioner With Two Compressors
More informationFig.: macroscopic kinetic energy is an organized form of energy and is much more useful
Harnessing Energy Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful Vapor Power Cycle The vast majority of electrical generating plants are variations of vapor power
More informationS.A. Klein and G.F. Nellis Cambridge University Press, 2011 = 90 F. compressor. condenser. 5 evaporator 1. evap
9.A-1 Dedicated subcooling is a novel modification for frozen food refrigeration in supermarkets. With the dedicated subcooling modification, liquid refrigerant leaving the condenser is further cooled
More informationWORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM
WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM Sachin Kumar 1, Vicky Ranga 2 1Assistant Professor, Department of Mechanical Engineering, Jagan Nath University Jhajjar, Haryana, India. 2Scholar.
More informationChapter 11. Refrigeration Cycles. Study Guide in PowerPoint
Chapter 11 Refrigeration Cycles Study Guide in PowerPoint to accompany Thermodynamics: An Engineering Approach, 7th edition by Yunus A. Çengel and Michael A. Boles The vapor compression refrigeration cycle
More informationENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS
ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS Chainarong Chaktranond *, and Peachrakha Doungsong Department of Mechanical Engineering, Faculty of Engineering,
More informationBasic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency
Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency Haiye Lou TurboMoni Applied Dynamics Lab Abstract It is often happened, when a project
More informationApplication of two hybrid control methods of expansion valves and vapor injected compression to heat pumps
AM-4249223-1 - Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps Christian K. Bach, Graduate Student, Eckhard A. Groll, Reilly Professor, James
More informationSection 1: Theory of Heat Unit 3: Refrigeration and Refrigerants
Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration.
More informationThermodynamics I. Refrigeration and Heat Pump Cycles
Thermodynamics I Refrigeration and Heat Pump Cycles Dr.-Eng. Zayed Al-Hamamre 1 Content Introduction The Reversed Carnot Cycle The Ideal Compression Refrigeration Systems Deviation from the ICRS Selection
More informationExperimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential
More informationControl Method Of Circulating Refrigerant Amount For Heat Pump System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Control Method Of Circulating Refrigerant Amount For Heat Pump System Jin
More informationApplication Engineering
Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved
More information2016 Annual Conference
2016 Annual Conference Joe Sanchez Engineering Manager BITZER US, INC St. Louis, Missouri Engineering Chair of Compressor Section for AHRI Session 13 Advancements in Compressor Design, Testing and Performance
More informationLesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems
Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this lecture are to: 1. Importance of complete vapour compression refrigeration
More information*Corresponding author;
PERFORMANCE ANALYSIS OF AUTOMOTIVE AIR CONDITIONING SYSTEM WITH AN INTERNAL HEAT EXCHANGER USING R1234YF UNDER DIFFERENT EVAPORATION AND CONDENSATION TEMPERATURES by Mehmet DIREK a *and Alper KELESOGLU
More informationChapter 11 REFRIGERATION CYCLES. Department of Mechanical Engineering
Chapter 11 REFRIGERATION CYCLES Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University it Objectives Introduce the concepts of refrigerators and heat pumps and the measure of their performance.
More informationPerformance of an Improved Household Refrigerator/Freezer
Performance of an Improved Household Refrigerator/Freezer D. O. Ariyo Department of Mechanical Engineering, School of Engineering, Federal Polytechnic, Offa, Nigeria Y. L. Shuaib-Babata Department of Mechanical
More informationTravaglini EQUIPMENT FOR FERMENTING AND AGING OF SALAMI. Travaglini_inglese.indd 6 05/07/
Travaglini EQUIPMENT FOR FERMENTING AND AGING OF SALAMI Travaglini_inglese.indd 6 05/07/13 15.22 Since 1950, Travaglini S.p.A. has been the leading company in the manufacturing of drying, smoking, and
More informationS.A. Klein and G.F. Nellis Cambridge University Press, 2011
12.A-1 A mixture of helium and water vapor is flowing through a pipe at T= 90 C and P = 150 kpa. The mole fraction of helium is y He = 0.80. a.) What is the relative humidity of the mixture? b.) What is
More informationISSN Vol.08,Issue.21, November-2016, Pages:
ISSN 2348 2370 Vol.08,Issue.21, November-2016, Pages:4164-4170 www.ijatir.org Thermal Analysis of Vapour Compression Cycle for Different Refrigerants ALI MOHAMMED ABDOULHA MASSOUD 1, DR. MOHAMMAD TARIQ
More information4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)
4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao
More informationCase 13 Food Storage & Processing Center
Case 13 Food Storage & Processing Center Copy Right By: Thomas T.S. Wan ( ) Feb. 2, 2002 All Rights Reserved Case Background: The refrigeration system is for a food processing and storage facility. The
More information2. CURRICULUM. Sl. No.
. CURRICULUM Sl. No. Code Title No. of Lecture Hours 1 RAC 001 Fundamentals of Refrigeration and Air 60 conditioning RAC 00 Psychrometry, Heat load Estimation for 70 Air conditioning and Refrigeration
More informationEXPERIMENTAL INVESTIGATION ON VARIABLE SPEED OPERATION OF AIR CONDITIONING
HEFAT2012 9 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta EXPERIMENTAL INVESTIGATION ON VARIABLE SPEED OPERATION OF AIR CONDITIONING Grech N. and
More informationRecommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS
COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit
More informationMonitoring Pump Performance with Vibration. Mitchell Stansloski, PhD, PE
Monitoring Pump Performance with Vibration Mitchell Stansloski, PhD, PE Centrifugal Pumps Centrifugal pumps Centrifugal Pumps (Radial Flow Pumps): A pump using radial flow impellers that give their energy
More informationAir & Water Heat Pump R832
Figure 1 : R832 P.A. Hilton Ltd Air & Water Heat Pump R832 Vapour Compression Heat Pump that allows Performance Investigation from both Air and Water Sources. Rapid Stabilisation enables detailed Investigation
More informationSimscape Refrigerant Loop Product
Aims The product is an easy to use simscape simulator with simple GUI or HMI allowing to define: - the different configurations of the physical system - the different operating modes: start, stop, load
More information