Existing Conditions Assessment November 14, 2006 NORTH MIDDLESEX REGIONAL HIGH SCHOOL Townsend, MA L21366/ /Page 1

Size: px
Start display at page:

Download "Existing Conditions Assessment November 14, 2006 NORTH MIDDLESEX REGIONAL HIGH SCHOOL Townsend, MA L21366/ /Page 1"

Transcription

1 L21366/ /Page 1 HVAC EXECUTIVE SUMMARY The North Middlesex Regional High School has received average maintenance of the HVAC systems over its occupied years. Even with adequate maintenance, through normal operation systems do gradually deteriorate due to scale, poor water conditions, and lack of preventive maintenance. Systems will gradually deteriorate to a point of exceeding their maximum serviceable life. This building is a typical example of one such project. While generally speaking, most systems are operating and maintaining reasonable space temperature control, but due to the antiquated nature of the mechanical systems and their gradual scaling of the various piping systems, heat transfer rates have become reduced and the overall system is taxed to a point of inefficiency being created by the slowly depreciating system. In addition automatic temperature control appears compromised due to failed controls and equipment, and ventilation rates and acceptable air-quality are compromised due to the progressing surface contamination on many systems as well as mis-adjusted and closed outside ventilation dampers. While there are no catastrophic failures obvious with the present equipment, the piping systems are suggesting a developing condition which could present itself as a major failure due to poor return water flow in the condensate system. The systems could continuously be repaired and modified on a sectional basis that will keep the systems operating maintaining space temperature control however, continued operation will be at the expense of increased operating costs due to inefficiency in heat transfer and through the generally antiquated nature of the systems themselves. All systems installed within this building have exceeded their maximum serviceable life and are in need of replacement. With overall repair, maintenance, cleaning and calibrating of the system, a continued limited service could be achieved however, unpredictable at best. Mechanical System Condition Survey Boiler Room The boiler room is provided with three (3) H.B. Smith 650 mills cast iron sectional boilers. Each boiler generates low pressure steam which is distributed to the various heating apparatus at a pressure of between 5 and 10 psi. Two burners are provided with dual fuel and the third is provided with a gas only burner. As it presently exists, a gas service is installed to the boiler room however, the power plant generally operates utilizing number two fuel oil with the gas only boiler very rarely used. As we understand it the burners for the dual fuel applications are configured to operate as oil only. Each boiler is provided with dual low water cut offs and all operating and safety controls which do meet current building code requirements. It is our understanding that one single boiler is capable of maintaining the entire facility on typical winter days with a second the boiler operating only during the coldest times of winter. Boiler No. 3 was installed approximately 35 years ago and is considered to be in poor condition at this time with various nipple leaks and shell corrosion indicated throughout. Boiler No. 2 is an original boiler when the power plant was built in 1960.

2 L21366/ /Page 2 This boiler is showing severe signs of wear and near failure as evidenced by multiple water stains around the base of the boiler, multiple nipple leaks at each of mud drum, rupture stains around access doors to the fire box, and overall deterioration on and around the boiler itself. Boiler No.1 is an original boiler when the power plant was built in This boiler is noted to be in very good condition on the exterior showing no signs of leakage or general deterioration as indicated above in boiler number 2. As we understand it this boiler is rarely used for reasons we are unclear on. The two (2) boilers installed during the original construction combine to a single common header located over the boilers where various zones originate and run out to various heating points within the original building. During the 1970 addition, a secondary header was installed over boiler number three which back feeds into the original header essentially creating a common distribution header feeding all points of the entire building. Breeching from boilers is through a welded black steel ducting system which appears to be covered with either calcium silicate or asbestos insulation with a canvas jacket. The boilers are provided with induced draft fans which assist in the flow of combustion gases from the boiler to the chimney, as well as barometric dampers to adjust for atmospheric conditions on the chimney. It was noted that there was excessive surface contamination on each draft fan. The breeching discharges into a masonry chimney which is vented vertically through the building to the exterior. There was no water staining or cracks on the surface of the chimney and the chimney was provided with a clean-out door. We could not determine if a flue liner was in place however, the overall size and height of the chimney appears adequate for the combustion gases discharged. All steam piping throughout the entire boiler room appears to be schedule 40 black steel with the laterals insulated with fiberglass insulation however the valves and fittings appeared to be insulated with asbestos. There was no evidence of leakage on the piping with only minor leakage noted on valve bodies. The condensate piping also appears to be schedule 40 black steel insulated with fiberglass insulation on the laterals and the valves and fittings appeared to contain asbestos. Many sections of piping at the rear of the boilers as well as around the boiler feed water system have had their insulation removed. Discussions with maintenance personnel has indicated that although the piping has not been a major source of concern over the years there could be evidence that various sections of the piping are beginning to leak as evidenced by lack of condensate flow back to the feed water system. It also appears that the condensate system could be blocked with sediment also interfering with adequate condensate flow back. It was not possible to determine an exact condition of the existing piping at this time. In order to maintain an exact interior pipe condition various sections of pipe should be removed and examined for interior erosion or sludge. Considering the light weight piping used in the condensate piping system, we have serious concerns as to the actual integrity of this piping system and more than likely it has reached its maximum serviceable life. In recent years the traps on the heating equipment have been replaced throughout the building which has reduced energy consumption however, in a number of applications particularly around the air handling equipment and end of main drips, a fixed orifice non-mechanical trap was installed which also could be preventing adequate condensate flow back to the feed water system as well as contributing to the indicated steam discharge from various vents throughout the building.

3 L21366/ /Page 3 No. 4 fuel oil was originally installed for the power plant however, approximately 10 years ago the entire system was converted to number 2 fuel oil at which time a new double wall 12,000 gallon buried fuel oil storage tank was installed along with all supply and return piping installed in a secondary containment conduit. Two (2) individual gear pumps installed during the original construction transfer the fuel from the oil tank through duplex strainers and heat exchanger to where the oil is heated and distributed to the individual burners. What the burners do not fire is returned back to the fuel oil tank for redistribution. The heat exchangers located at the fuel oil transfer set are no longer used. Minor leakage was evident around the fuel oil transfer area, however; there were no signs of near failure. Distribution piping between the transfer set and the burners is through a schedule 40 uninsulated system located overhead. Minor leakage was indicated around the boiler burner unit, however; a system failure is not indicated. With the exception of the tank and buried piping the overall condition of the fuel oil transfer system would be considered poor. Condensate which is returned from the general building heating apparatus is collected in a floor mounted condensate receiver boiler feed water unit. Located under this storage tank are centrifugal pumps which provide feed water to the individual boilers through a feed water control valve on each boiler on a signal from the low water cut off switch in the boiler operating controls. We did confirm that this feed water system does operate adequately. The level controls located within the boiler feed water unit indicated a very low water level suggesting inadequate condensate flow back from the building. It would also indicate with his low water condition city water is introduced to maintain adequate feed water levels to each boiler. We understand that the city water is not chemically treated before its introduction into the heating system and if this is the case, the excess oxygen suspended within the city water could potentially be eroding away the interior of the piping systems. We were also advised that at the beginning of each day after the buildings have started water must be drained from the boilers to maintain adequate water levels. It is our understanding through maintenance personnel that this condition has existed for a long period of time which would give strong indications that the piping systems are more than likely near complete failure. The power plant is provided with a blowdown system which connects to each mud drum of each boiler and distributes to a floor mounted receiver tank which appears to be insulated with asbestos with a canvas jacket. As the condensate is transferred city water is mixed with the high temperature condensate where it is cooled and then removed from the power plant to drain. It appears that the city water cooling system in this condensate blowdown circuit is not operating. If this is the case, higher than allowed condensate temperature is discharging from the building to the sanitary sewer.

4 L21366/ /Page 4 Combustion air for the boiler room also appears to be inadequate. Located at the ceiling of the original boiler room is an air handling unit which is completely taken out of service. Located in the boiler room addition are two individual combustion air ducts one located high within the room and the other discharging to the floor each of which are provided with motor operated dampers. It does not appear that the motor operated dampers are operating. The overall size of the combustion air openings is inadequate for the total connected powerplant rating. The automatic temperature control is of the pneumatic design. Located within the boiler room is a single air storage tank with dual tank mounted compressors and motors which generates compressed air for distribution through a dual pressure day night control system. Located adjacent to the air storage tank is a refrigerated air dryer with oil water separators as well as pressure regulators. Compressed air circulates throughout the boiler room and the building thru a combination of copper tubing and polyvinyl tubing to the individual control devices. Located on an adjacent wall are automatic temperature control panels all of which was noted to be extremely antiquated and do not appear to operate. It does appear that this automatic temperature control system is original to the building and it was noted that the compressed air tank does have surface contamination and slight leaking, as does the adjacent control devices. Considering the age and antiquated nature consideration should be given to upgrading. Addition Building Mechanical Room Steam is distributed to the addition building through an underground trench system which appears to run throughout the existing building and into the new addition. Located within the mechanical room is a depressed mechanical pit adjacent to the incoming trench which allows steam piping to rise to the ceiling to feed various pieces of equipment as well as contains a condensate receiver tank with pumps to return condensate back to the boiler room. The tank is of the steel wall design insulated with what appears to be either calcium silicate or asbestos with a canvas jacket. The system is provided with a primary and standby discharge pump which discharges within the trench through a fiberglass insulated schedule 40 black steel condensate return pipe which terminates in the original boiler room. The tank and its associated pumps and controls was noted to be an average condition with slight surface soiling. It was noted that the vent pipe was discharging condensate which could be the result of bypassed steam from either failed steam traps or the incorrectly installed orifice traps. A direct source of low-pressure steam is provided to a floor mounted domestic hot water heater which is utilized year-round for domestic hot water distribution.

5 L21366/ /Page 5 Student Center The student center, which is the former cafeteria of the original building, is provided with six vertical discharge classroom unit ventilators located along the exterior of the space. Each classroom unit ventilator appears to have been recently installed and is provided with a lowpressure steam heating coil with valve control which ties into the existing steam distribution system located in a floor mounted trench, supply air through a vertical discharge grill, return air drawn at the base of the unit, filters, a direct expansion cooling coil which is circuited to an internal compressor and condensing cycle, and a direct source of outside ventilation air drawn through a wall mounted louver. Condenser air for air-conditioning cycles are also drawn through the same wall mounted louver. The overall condition of the equipment was noted to be very good however, the units were very noisy when they operate but are providing adequate total air circulation. Automatic temperature control for these unit ventilators are through equipment installed standalone electronic sensors installed at the time the unit ventilators were installed. All systems were operating satisfactorily. There were no central exhaust systems installed to facilitate the flow of ventilation air and as a result could be compromising be code required outside air requirement of the building code. Administration Area The administration area which is located in the original building is provided with a continuous length of fin tube radiation located along the entire exterior wall and is controlled by various wall mounted pneumatic thermostats in the individual offices. All of the radiation is fed from the overhead steam distribution system and the condensate piping runs at the rear of the fin cover and discharges to a mechanical pit in an adjacent mechanical room. A condensate receiver a located within this mechanical pit discharges condensate back to the boiler room. The overall condition of the fin tube radiation was noted to be very poor and was noted to have surface damage in surface soiling all of which was original and in general need of replacement. All thermostats were original and were extremely antiquated and questionable if any operate. The condensate receiver is extremely antiquated with excessive surface soiling and contamination also in need of replacement.

6 L21366/ /Page 6 Ventilation air for the entire administration area is through the use of operable windows located along the exterior wall. A central exhaust system which includes a roof mounted exhaust fan is provided to facilitate the flow of ventilation air through the windows, however; it is generally undersized for the area served as well has noted to be soiled. Although the percentage of openable area is adequate to meet the natural ventilation requirement of the building code it is not a recommended application and should be upgraded. The administration area is also provided with two vertical discharge 100% recirculation air-conditioning units one of which is located in the nurses area and the second located in the vault. Each unit is provided with a length of horizontal supply duct work which is uninsulated and serves at various wall and ceiling diffusers in the individual areas. Each unit is provided with a roof mounted air cooled condensing unit and is controlled by two individual electric wall mounted thermostats. Both systems were noted to be extremely antiquated, soiled, and the unit located within the nurses area was in a general state of disrepair as well as exposed to the general public. Both systems have reached their maximum serviceable life and are in need of replacement. Auditorium The auditorium is provided with a single heating and ventilating air handling unit, which is located above the ceiling of the auditorium at the rear adjacent to the projection room. The air handling unit is provided with a supply fan, filters, steam heating coil which ties into the overhead steam distribution system, return air which is drawn from two individual return air registers located approximately 8 inches above the floor under the air handling unit, and a direct source of outside air through a wall mounted intake louver. Supply air is provided to the space through an insulated galvanized sheet-metal distribution system to series of ceiling diffusers. It does appear that the amount of air provided to the space is adequate for the overall population. All grilles were noted to be slightly soiled, and original to the building approximately 35 years old. Considering the general antiquated nature of the supply system, as well as its age all systems appear to have reached their maximum serviceable life and generally in need of replacing.

7 L21366/ /Page 7 The stage area was not provided with any direct supply or exhaust ventilation air all of which is non code compliant. Located at the front of the stage in the auditorium area are two wall mounted exhaust registers which communicate to individual roof mounted exhaust fans through a galvanized exhaust system. As we understand it the exhaust fans were upgraded recently during a roofing upgrade project and do appear to operate however, we could not confirm if they were balanced to code conditions. Entrances, Vestibules, Corridors The individual communicating corridors were not provided with any supply or exhaust ventilation air all of which is non code compliant and should be improved upon. The primary and secondary entrances and exits throughout the building were not provided with vestibule interlocks to prevent infiltration of cold air during frequent use. This present condition is not code compliant under the current building code and is extremely energy wasteful allowing the large amount of cold air to enter the building which must be heated. Vestibule interlocks at all entrances and exits are highly recommended. The primary and secondary entrances were provided with convection heating which are extremely undersized. This condition is allowing cold air to filter throughout the corridor areas and affect overall building temperature control. Convection heaters were also provided throughout the communicating corridors and once the exterior doors are closed are adequate for overall space heating. The overall condition of all heating equipment in their associated thermostats is extremely antiquated, some of which are damaged, all of which are recommended for replacement. Classrooms The original building classrooms are provided with a vertical discharge classroom unit ventilator located along the exterior wall of the building. Each unit is provided with a supply fan which discharge is vertically into the space, steam heating coil with valve control which ties into a main steam line which travels at the rear of the classroom unit ventilator, return air drawn at the base of the unit, filters, and outside air drawn directly at the rear of the unit through a wall mounted louver. Each unit is controlled by a wall mounted pneumatic thermostat. The classroom unit ventilator and the thermostat are original to the building and were noted to be extremely antiquated, the unit ventilators were damaged and had severe surface soiling, the interior areas of the cabinets were extremely soiled, and it does not appear that the outside intake louvers are operating and therefore ventilation air is compromised below building code requirements. All equipment has reached its maximum serviceable life and is in need of replacement.

8 L21366/ /Page 8 Located on the interior wall of each classroom is a wall mounted exhaust register which communicates to a roof mounted exhaust fan through a series of galvanized sheetmetal exhaust ductwork. The interior of all registers were extremely soiled and all grilles were antiquated. It does appear that all roof exhaust fans were replaced during a recent re-roofing project and do appear to operate however, we have no assurance that code required amounts of ventilation air are being exhausted at this time. With the exception of the roof mounted exhaust fans all systems are extremely antiquated and are need replacement. Condensate is returned to a common condensate return line generally located above the floor at the rear of the unit ventilators in a wall mounted enclosure. As we understand it in recent years various sections of the condensate piping has been failing indicating corrosion and that the system is nearing its maximum serviceable life. The condensate collects at common points throughout the building and discharges into mechanical pits containing condensate receivers where it is discharged through a pressurized system back to the boiler room. All condensate piping is original and approximately 45 years old and with the apparent recent failures indicates the system has reached its maximum serviceable life and is in need replacement. The condensate receivers are provided with a primary and standby distribution pump however, all systems were antiquated and in need of replacement. The computer classrooms are provided with vertical discharge classroom unit ventilators located along the exterior of the space. Each classroom unit ventilator appears to have been recently installed and is provided with a low-pressure steam heating coil with valve control which ties into the existing steam distribution system located behind the unit ventilators in a wall mounted enclosure, supply air through a vertical discharge grill, return air drawn at the base of the unit, filters, a direct expansion cooling coil which is circuited to a grade mounted air cooled condensing unit, and a direct source of outside ventilation air drawn through a wall mounted louver. The overall condition of the equipment was noted to be very good however, the units were very noisy when they operate but are providing adequate total air circulation. Automatic temperature control for these unit ventilators are through equipment installed standalone electronic sensors installed at the time the unit ventilators were installed. All systems were operating satisfactorily, were clean, and in very good condition. The addition building classrooms are provided with a vertical discharge classroom unit ventilator located along the exterior wall of the building. Each unit is provided with a supply fan which discharge is vertically into the space, steam heating coil with valve control which ties into a main steam line located below the floor, return air drawn at the base of the unit, filters, and outside air drawn directly at the rear of the unit through a wall mounted louver. Each unit is controlled by a wall mounted pneumatic thermostat. The classroom unit ventilator and the thermostat are original to the building and were noted to be extremely antiquated, the unit ventilators were damaged and had severe surface soiling, the interior areas of the cabinets were extremely soiled, and it does not appear that the outside intake louvers are operating and therefore ventilation air is compromised below building code requirements. All equipment has reached its maximum serviceable life and is in need of replacement.

9 L21366/ /Page 9 The addition building classrooms were also provided with a cabinet exhaust fans located adjacent to the classroom unit ventilator which is designed to remove the code required amount of ventilation air. Each cabinet fan was noted to be soiled, some of which were damaged and it did not appear that any of these fans were operating. With the non operating condition of these exhaust fans the code required amount of ventilation air is not being provided at this time. The steam piping feeding the addition building is located throughout a series of floor trenches beneath the first floor level and feeds all equipment from this trench. All steam piping is schedule 40 black steel and appears to be insulated with fiberglass insulation. The condensate piping is also located in the same floor trench and returns by gravity to a central condensate receiver located in the addition building mechanical room where it is returned to the existing boiler room. All piping is nearing its maximum serviceable life and generally should be upgraded. Gymnasiums The original building gymnasium is provided with two horizontal discharge air handling units located at the ceiling. Each air handling unit is provided with a supply fan, steam heating coil which ties into the overhead steam distribution system, filters, return air drawn at the base of the unit, and outside air drawn in through a wall mounted louver. Each air handling unit discharges into a soffit area located over the dividing curtain, and through a series of wall mounted registers provides ventilation air to the entire space. It does appear that the amount of ventilation provided for the space is undersized by current building code requirements. With the return air opening drawn directly at the base of the air handling unit the close proximity of the supply and return is short-circuiting a percentage of the total air therefore compromising overall air quality and air volume distributed. Each air handling unit is noted to be original and does contain surface contamination. It does not appear that the outside air dampers are operable and therefore outside ventilation air could be compromised below building code requirements. All systems are extremely antiquated and have reached their maximum serviceable life and air and general need of replacement.

10 L21366/ /Page 10 Each side of the gymnasium associated with each air handling unit is a wall mounted exhaust register located approximately 8 inches above the floor. Each register is connected to a roof mounted exhaust fan through a galvanized sheetmetal exhaust system. The interior condition of each register was severely contaminated with dirt and debris. The exhaust fan is designed to remove the minimal amount of code required ventilation air. It does appear that the exhaust fan was recently replaced during a roofing modification however we cannot be certain of code required amounts of ventilation air are being controlled. The space was not provided with economizer relief to allow for higher amounts of outside air when outside temperature permits. The addition building gymnasium is provided with four separate air handling units located in mechanical mezzanines at four corners of the space. Each air handling unit is of the vertical discharge design and is provided with a steam heating coil which ties into the overhead steam distribution system, filters, return air, and outside air drawn into a wall mounted louver. It does appear based on the size of the equipment that the amount of the air is undersized and is not compliant with building code requirements. The supply registers of each unit were noted to have slight surface soiling and with the close proximity of the supply and the return a percentage of the overall volume of air is short-circuiting and therefore limiting overall distribution to the space which is further compromising overall air quality. It does not appear that the outside air dampers are operable and therefore ventilation air is not compliant with building code requirements. Based on condition and overall age of equipment, and the questionable design of the individual systems all systems should be considered to upgrading at this time The space was provided with exhaust air to provide minimum ventilation air requirements which is through four individual wall mounted registers located approximately 8 inches above the floor which communicate to roof mounted exhaust fans through a galvanized sheetmetal exhaust system. Each exhaust fan is sized to provide a minimum amount of code required ventilation air and as we understand it each fan was replaced recently during a roofing modification however we have no confirmation that the fans are balanced to allow building code required air volumes. The space was not provided with any means of economizer relief to allow higher amounts of outside air when outside air temperature permits.

11 L21366/ /Page 11 Locker Rooms The boys and girls locker rooms are similar and are each provided with two horizontal discharge classroom unit ventilators located at the ceiling of the space. Each unit is provided with a supply fan, steam heating coil which ties into the overhead steam distribution system, return air drawn at the base of the unit, filters, and outside air from a roof mounted intake hood. It does not appear that the outside air dampers are operating and therefore ventilation air is not in compliance with building code requirements. Each unit free blows into the space and with the close proximity of the return air to supply air, is short-circuiting a percentage of the total air therefore compromising overall air quality and ventilation air provided to the space. All units were noted to have surface soiling and contamination and some units were damaged. Based on overall condition and age all systems have reached their maximum serviceable life and are need of replacement The entire locker area is also provided with a central exhaust system which includes ceiling exhaust registers generally located over the shower and toilet areas which communicates to roof mounted exhaust fans through a galvanized sheetmetal exhaust system. All systems were noted to have surface soiling and contamination and all systems were extremely antiquated. Many systems located within the boys locker area were also damaged. It does appear that the roof mounted exhaust fans were replaced during a recent reroofing project and do appear to operate however, it does appear that the systems are undersized and are not in compliance with current building code ventilation requirements. With the exception of the exhaust fans, based on overall condition and age all systems have reached their maximum serviceable life and are need of replacement. Cafeteria Each cafeteria area is provided with three vertical discharge classroom unit ventilators to of which are located along the exterior wall of the building and one is located on interior wall. The combined volume of each unit ventilator does appear adequate to meet building code ventilation requirements. Each unit is provided with a supply fan which discharges vertically into the space, steam heating coil with valve control which ties into a main steam line which travels in a trench beneath the classroom unit ventilator, return air drawn at the base of the unit, filters, and outside air drawn directly at the rear of the unit through a wall mounted louver. Each unit is controlled by a wall mounted pneumatic thermostat. The classroom unit ventilators and the thermostat are original to the building and were noted to be extremely antiquated, the unit ventilators were damaged and had severe surface soiling, the interior areas of the cabinets were extremely soiled, and it does not appear that the outside intake louvers are operating and therefore ventilation air is compromised below building code requirements. All equipment has reached its maximum serviceable life and is in need of replacement.

12 L21366/ /Page 12 Located on the interior wall adjacent to the classroom unit ventilator are two wall mounted exhaust registers which communicates to a roof mounted exhaust fan through a series of galvanized sheetmetal exhaust ductwork. The interior of all registers were soiled and all grilles were slightly damaged. It does appear that all roof exhaust fans were replaced during a recent reroofing project and do appear to operate however, we have no assurance that code required amounts of ventilation air are being exhausted at this time. With the exception of the roof mounted exhaust fans all systems have reached a maximum serviceable life and should be replaced. Kitchen The kitchen is provided with a single canopy hood located over the entire cooking area. The hood discharges vertically to a roof mounted exhaust fan and is controlled manually by a wall mounted switch. The hood is provided with removable cleanable cartridge filters, vaportight incandescent lighting, and fire protection. The entire hood is of the single wall stainless steel design and is of the proper height and size to completely cover all cooking equipment. The hood was noted to be very clean and in very good condition. It was not possible to determine if the proper air volume is being exhausted through the hood however, we did note that there was no mechanical make up air provided and is could compromise adequate air volumes. It does appear that make up air was intended to come from the adjacent cafeteria areas however the amount of outside air provided in each cafeteria is in adequate to maintain code required make up air. Although no recommendations are made for the exhaust hood make up air should be provided to maintain code volumes of exhaust air. The kitchen area was provided with a horizontal discharge classroom unit ventilator located at the ceiling of the space. The unit is provided with a supply fan, steam heating coil which ties into the overhead steam distribution system, return air drawn at the base of the unit, filters, and outside air from a roof mounted intake hood. It does not appear that the outside air dampers are operating and therefore ventilation air is not in compliance with building code requirements. The unit free blows into the space and with the close proximity of the return air to supply air, is shortcircuiting a percentage of the total air therefore compromising overall air quality and ventilation air provided to the space. The unit were noted to have surface soiling and contamination and slightly damaged. Based on overall condition the unit has reached its maximum serviceable life and is in need of replacement.

13 L21366/ /Page 13 Woodworking Shop The woodworking shop is provided with a horizontal discharge classroom unit ventilator located at the ceiling of the space. The unit is provided with a supply fan, steam heating coil which ties into the overhead steam distribution system, return air drawn at the base of the unit, filters, and outside air from a wall mounted intake louver. It does not appear that the outside air dampers are operating and therefore ventilation air is not in compliance with building code requirements. The unit free blows into the space and with the close proximity of the return air to supply air, is short-circuiting a percentage of the total air therefore compromising overall air quality and ventilation air provided to the space. The unit were noted to have surface soiling and contamination and extensive damage. Based on overall condition the unit has reached its maximum serviceable life and is in need of replacement. The space is also provided with an overhead dust collection system which is made up of a galvanized sheetmetal exhaust system which connects to various woodworking appliances which is ducted to an exterior mounted duct collection system. The dust collection system is of the 100% recirculation design and is located directly outside of the building. The recirculation air defuses back to a storage room through a secondary filter where it is recycled back to the space. When the system does operate it is extremely noisy. Although antiquated and dirty the entire system does appear to operate and maintain reasonable dust control. RECOMMENDATIONS When considering the overall age and poor performance of the HVAC systems, their general state of disrepair, and for the most part a non operating automatic temperature control system, all mechanical systems should be replaced. We do not recommend upgrading the components of the systems on a sectional basis since the mechanical systems and their components work together as a single system and, as an example, changing the boilers without the piping systems, or the classroom unit ventilators without changing the automatic controls and the piping, would not experience the benefits of the investment of upgrading the components since a failure is eminent at any point within the existing components. Any interruption at any point in the system would essentially render the entire system inoperative, or poorly performing at best. As the building presently exists, there are no life safety concerns associated with the HVAC systems however, the building code has specific requirements relating to ventilation air of which is severely compromised within this building. It would be possible to manipulate the existing control system and air handling equipment to provide a limited amount of ventilation air possibly to meet minimum building code requirements however, we would not recommend this condition as a "fix" to the problem and only endorse this as a temporary repair.

14 L21366/ /Page 14 Because of the poorly performing automatic controls, more than likely energy consumption within the building is well above average when compared to similar buildings, and considering the general state of disrepair, maintenance costs and repair costs would also be considered above average. The only alternative to correct on a long-term basis the ventilation code deficiency, high operating costs, and high maintenance and repair costs, would be in overall system replacement utilizing energy conservation design techniques. Considering normal air-conditioning areas to include administration, cafeteria, media center, and auditorium would have an associated construction cost based on present day dollars to be approximately $ per square foot.

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance Groton Heights School Mechanical Evaluation TO: FROM: Amy Vaillancourt, Project Manager Harley Langford, Project Manger Jason Curtis, P.E. DATE: February 24, 2016; Revised May 31, 2016 On Monday, December

More information

Siemens Building Technology MEP Existing Conditions

Siemens Building Technology MEP Existing Conditions Electrical Existing Conditions Report Executive Summary: The electrical systems for the are generally of the original vintage. The site is primary metered with the meter located in the main Electric Room.

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#56566/Page 1/May 23, 2017 HVAC Heating Plant The original Town Hall building and Addition building are primarily heated by a gas fired hot water plant that is located in the basement. The boiler plant

More information

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

Florence High School / Middle School Page 1 of 3 Florence, WI

Florence High School / Middle School Page 1 of 3 Florence, WI Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October

More information

S AGE E NGINEERING A SSOCIATES, LLP

S AGE E NGINEERING A SSOCIATES, LLP S AGE E NGINEERING A SSOCIATES, LLP 1211 Western Avenue Albany, NY (518) 453 6091 F (518) 453 6092 Kingston Library Mechanical and Electrical Systems Field Report Date of Visits: Mechanical - September

More information

Series 300 VTB. Installation Instructions

Series 300 VTB. Installation Instructions Series 300 VTB Installation Instructions Sizes 7 12 16 20 30 HP #2 Fuel Oil Gas (500 to 2500 BTU) Gas Light Oil Combination High Pressure Steam Sizes 7 thru 16 HP (125 PSI) Sizes 20 and 30 HP (150 PSI)

More information

Cook - Wissahickon Elementary School

Cook - Wissahickon Elementary School Cook - Wissahickon Elementary School 201 E. Salaignac St., Philadelphia, PA 19128 HVAC Replacement Project Scope Determination Report May 10, 2018 Prepared by: G.P. Lamina, Jr., P.E., MBA School District

More information

DOCUMENT TABLE OF CONTENTS

DOCUMENT TABLE OF CONTENTS DOCUMENT 00003 June 16, 2005 TABLE OF CONTENTS DOCUMENT NO. INTRODUCTORY INFORMATION DOCUMENT 00003 TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS SECTION 01011 SECTION 01025 SSP21.1-1 SECTION 01026

More information

Facility Improvements

Facility Improvements AP-SI-03 BICYCLE RACK ADDITION AP-SI-05 EXTERIOR BENCH ADDITIONS Installation of bike rack will allow for designated and secure storage of bicycles. Installation of exterior benches will provide an outdoor

More information

Massachusetts School Building Authority

Massachusetts School Building Authority Massachusetts School Building Authority School District Revere District Contact Paul Dakin TEL: (781) 286-8226 Name of School Submission Date 3/6/2007 The following Priorities have been included in the

More information

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN September 30, 2015 PBA Project No. 2015.0140.00 PETER BASSO ASSOCIATES INC. CONSULTING ENGINEERS 5145 LIVERNOIS ROAD,

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION SECTIONS 23.20.100 Local Amendments To The International Mechanical Code, 2000 Edition 23.20.202 Definitions 23.20.301.14

More information

Evaluation. ems. Prepared By: Martha. a s Vineyard. Box P.O. Box June 2015

Evaluation. ems. Prepared By: Martha. a s Vineyard. Box P.O. Box June 2015 Martha a s Vineyard Regional High School Vineyard Haven, MA 2 2015 HVAC Syste ems Evaluation Prepared For: Martha s Vineyard Regional School District Box 1385 Oaks Bluff, MA 02557 Prepared By: BLW Engineers,

More information

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW... SECTION 230001 TABLE OF CONTENTS SECTION 230001 PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS... 1 1.00 FILED SUB BID... 1 1.01 PROJECT OVERVIEW... 2 1.02 DESIGN CRITERIA... 4 1.03 CODE ISSUES...

More information

Wappingers Central School District Energy Performance Contract. 01/29/2013 7:00am 9:00am

Wappingers Central School District Energy Performance Contract. 01/29/2013 7:00am 9:00am ECG ENGINEERING, P.C. Inspection Report #3 ECG 2685 Wappingers Central School District Energy Performance Contract Inspection Dates: Inspector: 01/25/2013 10:30am 1:00pm 01/29/2013 7:00am 9:00am Harold

More information

PART 5: HVAC & DHW SYSTEMS

PART 5: HVAC & DHW SYSTEMS PART 5: HVAC & DHW SYSTEMS Building Science Review Building Science Review: HVAC & DHW Systems This document will help you: Correctly answer all parts of the HVAC Systems section in the Home Energy Score

More information

RECOMMENDED PROCEDURES FOR THIRD-PARTY PREVENTATIVE MAINTENANCE PROVIDERS

RECOMMENDED PROCEDURES FOR THIRD-PARTY PREVENTATIVE MAINTENANCE PROVIDERS RECOMMENDED PROCEDURES FOR THIRD-PARTY PREVENTATIVE MAINTENANCE PROVIDERS 1 Contents Introduction... 3 Portfolio Energy Goals... 3 Purpose of This Document... 3 Gas Furnaces... 4 Electric Furnaces... 7

More information

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings)

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings) 1. Ground Level Indoor Inspection a. Univents are on and air discharge grills are free of obstructions. If false, send email to building principal and facilities director asking staff to be instructed

More information

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV ClearFire Economizer Model ECF Integral or External Addendum to manuals 750-295 CFH and 750-269 CFV CB-8466 08/2011 1-GENERAL The Model ECF economizer is a stainless steel coil tube arrangement using

More information

2012 INTERNATIONAL FUEL GAS CODE VENTS

2012 INTERNATIONAL FUEL GAS CODE VENTS 2012 INTERNATIONAL FUEL GAS CODE SECTION 502 (IFGC) VENTS 502.1 General. All vents, except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accordance with

More information

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO.

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GBI 201-5 3C For a proper installation and in order to receive the best in operating life and efficiency from your

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 92 - BROOKLYN, 601 PARKSIDE AVENUE, New York, 11226 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-13 8:31 AM 2017-11-27 11:43 AM Asset Data Are there fuel tanks?

More information

Technical Datasheet. FHG-S Models 28, and 45. Benefits at a Glance: State Route 22 Salem, NY 12865

Technical Datasheet. FHG-S Models 28, and 45. Benefits at a Glance: State Route 22 Salem, NY 12865 FHG-S Models 28, and 45 Technical Datasheet FrÖling FHG-S The FHG-S is a patented, wood-fired gasification boiler available in two sizes with outputs from 102,500-153,500 Btu/hr. Benefits at a Glance:

More information

NYC Department of Education

NYC Department of Education Asset: I.S. 45 - BRONX, 2502 LORILLARD PLACE, New York, 10458 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-05 9:14 AM 2017-12-20 11:42 AM Asset Data Are there fuel tanks? Total

More information

CONNECTICUT. Downloaded

CONNECTICUT. Downloaded Housekeeping/Laundry/Maintenance J. Laundry. CONNECTICUT Downloaded 01.15.11 (1) This service, if provided, shall be used exclusively for laundry and shall be remote from resident and food service areas,

More information

Do not use this vent pipe or fittings for venting incinerators of any kind.

Do not use this vent pipe or fittings for venting incinerators of any kind. ! CAUTION! Do not use this vent pipe or fittings for venting incinerators of any kind. C.S.A. Certified For Natural Gas Or Propane Tested For 100 LBS. ASME Working Pressure For correct installation of

More information

VENTING CLEARANCES. BBT NORTH AMERICA Bosch Group. Bosch Water Heating 340 Mad River Park, Waitsfield, VT TWH-V-26 page 1 of 6 rev 01/06

VENTING CLEARANCES. BBT NORTH AMERICA Bosch Group. Bosch Water Heating 340 Mad River Park, Waitsfield, VT TWH-V-26 page 1 of 6 rev 01/06 page 1 of 6 VENTING CLEARANCES The vents should not be obstructed and all joints properly fitted. Floors, ceilings and walls must be cut or framed to provide necessary clearance to vents. Metal strippings

More information

Problem Cause Remedial action. Gauge glass There was excess chemical dosage The normal ph recommended was 9.5 to See photo 3 & 4.

Problem Cause Remedial action. Gauge glass There was excess chemical dosage The normal ph recommended was 9.5 to See photo 3 & 4. CASE STUDIES OF STEAM SYSTEM AUDIT IN SOME PLANTS By K.K.Parthiban, Venus Energy Audit System Introduction This article outlines the outcome of auditing of steam system conducted in process Industries.

More information

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL SECTION 15100 PART 1 GENERAL THIS IS A DESIGN GUIDE NOT A SPECIFICATION Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL HVAC SYSTEMS APPLICATIONS 1.1 SCOPE: The intent of this

More information

GENERAL BASIC INSTALLATION INSTRUCTIONS INDIRECT GAS FIRED WATER HEATERS PARKER BOILER CO.

GENERAL BASIC INSTALLATION INSTRUCTIONS INDIRECT GAS FIRED WATER HEATERS PARKER BOILER CO. GENERAL BASIC INSTALLATION INSTRUCTIONS INDIRECT GAS FIRED WATER HEATERS PARKER BOILER CO. GBI 210 3C For a proper installation and in order to receive the best in operating life and efficiency from your

More information

Diocese of Cleveland Facilities Services Corporation

Diocese of Cleveland Facilities Services Corporation Diocese of Cleveland Facilities Services Corporation BOILER MAINTENANCE and SERVICING SEASONAL MAINTENANCE - to be performed by trained boiler technician or boiler contractor only: 1. Disassemble the low

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 73 - BRONX, 1020 ANDERSON AVENUE, New York, 10452 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-16 8:29 AM 2017-11-28 10:59 AM Asset Data Are there fuel tanks? Total

More information

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems about your house CE 28 k Assessing the Comfort and Safety of Your Home s Mechanical Systems The heating, ventilating and air conditioning (HVAC) systems are a vital part of every home. These mechanical

More information

17 Interior Climate Control

17 Interior Climate Control 17 Interior Climate Control 17.1 Air is leaking through or around windows and/or exterior doors. Windows and doors shall be installed to minimize air leakage in accordance with the Alberta Building Code.

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION Sections 23.20.100 Local amendments to the International Mechanical Code, 2012 Edition.... 2 23.20.101.2 Scope.... 2 23.20.103-110

More information

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings)

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings) 1. Ground Level Indoor Inspection a. Univents are on and air discharge grills are free of obstructions. If false, send email to building principal and facilities director asking staff to be instructed

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 161 - MANHATTAN, 499 WEST 133 STREET, New York, 10027 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-15 8:26 AM 2018-06-08 1:37 PM Asset Data Are there fuel tanks?

More information

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM SUMMARY 1234 Main St.Severn 21144 Buyer Name 07/18/2018 9:00AM Henry Toman MD License 32391 1st American Home Inspection, LLC 443-685-4062 henrytoman61@gmail.com The summary is meant to organize the defects

More information

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings)

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings) 1. Ground Level Indoor Inspection a. Univents are on and air discharge grills are free of obstructions. If false, send email to building principal and facilities director asking staff to be instructed

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 86 ANNEX - BRONX, 124 EAMES PLACE, New York, 10468 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-05 1:03 PM 2018-04-27 1:35 PM Asset Data Are there fuel tanks? Total

More information

tççç= ÜÉ~íáåÖ çéíáçåë

tççç= ÜÉ~íáåÖ çéíáçåë 3. tççç= ÜÉ~íáåÖ çéíáçåë There are several different types of wood-heating appliances to choose from. Each type is intended for a particular use, and each has its own set of advantages and disadvantages.

More information

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS AUTOMATIC MAKE-UP AIR DAMPER WITH READ AND SAVE THESE INSTRUCTIONS FOR RESIDENTIAL USE ONLY Page 1 WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: 1. Installation

More information

Mechanical System Description

Mechanical System Description 1. Building Description: Mechanical System Description The building is a Type-1B construction, 9-levels, non-high rise building with 67 affordable family housing units. The first level of the structure

More information

I. STRUCTURAL SYSTEMS

I. STRUCTURAL SYSTEMS I. STRUCTURAL SYSTEMS A. Foundations Type of Foundation(s): Pier & Beam - Crawlspace Opinion: All exposed areas of the foundation were examined visually. Examination of the foundation was limited to photographs

More information

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Introduction to Hydronics A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Hydronic heating systems use hot water or steam to deliver the

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

Trade of Plumbing. Module 2: Domestic Hot and Cold Water Service Unit 10: Hot Water Supply Phase 2

Trade of Plumbing. Module 2: Domestic Hot and Cold Water Service Unit 10: Hot Water Supply Phase 2 Trade of Plumbing Module 2: Domestic Hot and Cold Water Service Unit 10: Hot Water Supply Phase 2 Table of Contents List of Figures... 4 List of Tables... 5 Document Release History... 6 Module 2 Domestic

More information

2015 MECHANICAL CODE REQUIREMENTS

2015 MECHANICAL CODE REQUIREMENTS 2015 MECHANICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Mechanical requirements for residential buildings per

More information

Agustin Lara Elementary Academy

Agustin Lara Elementary Academy Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

8 5.11: Finned-Tube Coils and Heat Exchangers : Humidifiers and Water Spray Systems : Access for Inspection, Cleaning, and Maintenance

8 5.11: Finned-Tube Coils and Heat Exchangers : Humidifiers and Water Spray Systems : Access for Inspection, Cleaning, and Maintenance Table of Contents 3 Executive Summary 4 Building Overview 5 Mechanical Systems Overview 6 ASHRAE Standard 62.1 2013 Evaluation 6 Section 5: Systems and Equipment 6 5.1: Ventilation Air Distribution 6 5.2:

More information

VOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED

VOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED Ashton Elementary School 1 Masonry Repair $ 42,781.50 2 Replace HVAC $ 375,000.00 3 Replace SAT @ Various Locations $ 92,364.00 3 Recoat & Resurface Exterior Paved Play Area $ 135,978.30 3 Various Technological

More information

Notable Changes in the Mechanical Codes

Notable Changes in the Mechanical Codes Notable Changes in the Mechanical Codes July 2004 The following are some of the changes between the 1997 Uniform Mechanical Code and the 2003 International Mechanical Code(M) and the 2003 International

More information

SECTION HEATING BOILERS

SECTION HEATING BOILERS SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,

More information

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM BEST PRACTICE NO. 30 WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM Air and noncondensable gases are one of the major problems in a steam system that can cause production

More information

Richard Henry Lee Elementary School

Richard Henry Lee Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

CHURCH MUTUAL AND HARTFORD STEAM BOILER SENSOR TECHNOLOGY PROGRAM: IDENTIFYING FROZEN PIPE EXPOSURES

CHURCH MUTUAL AND HARTFORD STEAM BOILER SENSOR TECHNOLOGY PROGRAM: IDENTIFYING FROZEN PIPE EXPOSURES CHURCH MUTUAL AND HARTFORD STEAM BOILER SENSOR TECHNOLOGY PROGRAM: IDENTIFYING FROZEN PIPE EXPOSURES Where to Install Pipe Temperature Sensors for Freeze Protection 1 WHICH PIPES SHOULD I MONITOR FOR FREEZE

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 198 - BRONX, 1180 TINTON AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-24 8:14 AM 2018-01-24 9:32 PM Asset Data Are there fuel tanks? Total

More information

Home Performance Science

Home Performance Science Home Performance Science Symptoms of a Sick House Too hot/too cold rooms Respiratory problems Headaches/nausea Smoky fireplace Foggy windows Stuffy air and lingering odors Peeling paint Constant dust problems

More information

NYC Department of Education Building Condition Assessment Survey :49AM :00PM

NYC Department of Education Building Condition Assessment Survey :49AM :00PM School: InspectionId Asset Data Inspection Type Building Assessment Survey 05-06 P.S. 70 - BROOKLYN, 4 EMERSON PLACE, BROOKLYN, NY, 05 Time In Last Edited 476 MECHANICAL 05-- 08:49AM 05-- 03:00PM Have

More information

Mechanical Inspection Plumbing

Mechanical Inspection Plumbing 0811 Fixtures Sinks, drinking fountains, water closets, showers, etc. Classroom Sinks. Classroom sinks (19) are enameled cast iron self rimming side ledge with gooseneck faucet trim with index handles,

More information

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 32 - BRONX, 690 EAST 183 STREET, New York, 10458 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-13 9:25 AM 2017-11-16 5:46 PM Asset Data Are there fuel tanks? Total

More information

MUKWONAGO SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY

MUKWONAGO SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY MUKWONAGO SCHOOL DISTRICT ARCHITECTURE PARK VIEW MIDDLE SCHOOL The original school building was dedicated in 1954 as the High School, with an addition in 1959, a library addition in 1970, and an addition/renovation

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 19 - STATEN ISLAND, 780 POST AVENUE, New York, 10310 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-10-26 8:58 AM 2017-11-14 1:37 PM Asset Data Are there fuel tanks?

More information

MUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY

MUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY ARCHITECTURE ROLLING HILLS ELEMENTARY SCHOOL Rolling Hills Elementary was built in 1999 and is the newest addition to the Mukwonago Area School District. The building contains approximately 64,900 gross

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION Sections 23.20.100 Local amendments to the International Mechanical Code, 2006 Edition... 2 23.20.101.2 Scope... 2 23.20.303.4

More information

INSTALLATION AND SERVICE MANUAL

INSTALLATION AND SERVICE MANUAL INSTALLATION AND SERVICE MANUAL CHF2-i&s-02 Hot Water Heating Boilers Domestic Hot Water Supply Boilers 300,000 and 990,000 2,070,000 BTU Models Installation and service must be performed by a qualified

More information

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section. SECTION 15855 GAS FURNACE/DX COOLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of contract including General and Supplementary Conditions of Division 1 of Specification

More information

Boiler. Fire tube Boiler:

Boiler. Fire tube Boiler: Boiler What is Boiler? A closed metallic vessel in which the water is heated beyond the boiling temperature by the application of heat by the combustion of fuels to convert it into steam. The function

More information

Genevieve Melody Elementary School

Genevieve Melody Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 194 - MANHATTAN, 244 WEST 144 STREET, New York, 10030 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-12 10:48 AM 2018-01-29 10:54 AM Asset Data Are there fuel tanks?

More information

Josefa Ortiz De Dominguez Elementary School

Josefa Ortiz De Dominguez Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 111 - MANHATTAN, 440 WEST 53 STREET, New York, 10019 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-16 8:47 AM 2018-03-21 8:02 AM Asset Data Are there fuel tanks?

More information

SERIES 24. Series 24 Features. Commercial, Forced Draft, Hot Water or Steam Boiler. The right fit for any commercial job

SERIES 24. Series 24 Features. Commercial, Forced Draft, Hot Water or Steam Boiler. The right fit for any commercial job SERIES Commercial, Forced Draft, Hot Water or Steam Boiler Sizes from to,8 MBH output The right fit for any commercial job The Series is built to handle any installation - businesses, institutions, apartments,

More information

STEAM / GAS APPLICATION GUIDE

STEAM / GAS APPLICATION GUIDE WET-BASE CAST-IRON MODULAR BOILERS Guidelines for the design, purchase and installation of Slant/Fin gas-fired steam modular boiler systems. STEAM / GAS APPLICATION GUIDE CONTENTS Introduction...1 Ratings

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 104 - BROOKLYN, 9115 5TH AVENUE, New York, 11209 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-02-21 8:55 AM 2018-02-21 1:09 PM Asset Data Are there fuel tanks? Total

More information

BETTER HOME COMFORT AND PEACE OF MIND STARTS WITH THE BEST SERVICE PLANS.

BETTER HOME COMFORT AND PEACE OF MIND STARTS WITH THE BEST SERVICE PLANS. BETTER HOME COMFORT AND PEACE OF MIND STARTS WITH THE BEST SERVICE PLANS. Value & Premier Oil Heating System Service Plans Choose the plan that s best for you and your home. WE PROMISE SERVICE PLANS THAT

More information

Commercial Water Heaters. Genesis. Water Heater Design Guide

Commercial Water Heaters. Genesis. Water Heater Design Guide Commercial Water Heaters Genesis Water Heater Design Guide Dear Customer, This Genesis Water Heater Design Guide is intended to explain, simplify and help in the planning and the installation of our Genesis

More information

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School MOUNT PLEASANT MIDDLE SCHOOL HVAC M-01 Heating Plant: The existing boilers have recently been upgraded. (3) steam boilers (8660 mbh each) manufactured by Weil- McLain have been installed. Newer hot water

More information

PLAN THE INSTALLATION Planning the installation first requires selecting the most appropriate installation approach. The chart below offers suggestion

PLAN THE INSTALLATION Planning the installation first requires selecting the most appropriate installation approach. The chart below offers suggestion AUTOMATIC MAKE-UP AIR DAMPER WITH To register this product visit: www.broan.com MODELS MD6T MD8T MD10T READ AND SAVE THESE INSTRUCTIONS FOR RESIDENTIAL USE ONLY Page 1 WARNING TO REDUCE THE RISK OF FIRE,

More information

GIRTON CABINET WASHER MODEL 794A

GIRTON CABINET WASHER MODEL 794A DESCRIPTION GIRTON CABINET WASHER MODEL 794A The washer shall be a Girton Model 794A Cabinet Type Pressure Washer constructed of type-304 stainless steel, utilizing a reciprocating header spray system.

More information

GASEOUS HYDROGEN SYSTEMS

GASEOUS HYDROGEN SYSTEMS CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall

More information

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

IAQ Building Education and Assessment Model (I-BEAM)

IAQ Building Education and Assessment Model (I-BEAM) Heating, Ventilation, and Airconditioning (HVAC) Text Modules IBEAM IAQ in L... http://www.epa.gov/iaq/largebldgs/ibeam/text/hvac.html Page 1 of 6 10/21/08 IAQ in Large Buildings http://www.epa.gov/iaq/largebldgs/ibeam/text/hvac.html

More information

COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES*

COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES* COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES* *Vented appliances refer to natural draft appliances equipped with a barometric draft regulator or Category I appliances equipped with a draft

More information

MODEL ANSWER FOR ELEMENTS OF MECH.ENGG.(17413) 1) steam boiler- It is a closed vessel in which steam is produced from water by combustion of fuel.

MODEL ANSWER FOR ELEMENTS OF MECH.ENGG.(17413) 1) steam boiler- It is a closed vessel in which steam is produced from water by combustion of fuel. MODEL ANSWER FOR ELEMENTS OF MECH.ENGG.(17413) Q 1. a) 1) steam boiler- It is a closed vessel in which steam is produced from water by combustion of fuel. 2) steam turbine- It is a device that extract

More information

Technical Datasheet. Solo Innova Models 30 and 50. Benefits at a Glance: Solo Innova

Technical Datasheet. Solo Innova Models 30 and 50. Benefits at a Glance: Solo Innova Solo Innova Models 30 and 50 Technical Datasheet Solo Innova Solo Innova is a patented, wood-fired gasification boiler available in two sizes with outputs from 102,500 to 170,700 Btu/hr. Benefits at a

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 146 - BRONX, 968 CAULDWELL AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-01 8:57 AM 2018-05-31 2:59 PM Asset Data Are there fuel tanks? Total

More information

WALK-AROUND INSPECTION LIST

WALK-AROUND INSPECTION LIST WALK-AROUND INSPECTION LIST Page 1 of 18 BUILDING DESCRIPTION Location of building in relation to potential sources (industry, landfills, emissions, outside renovations, etc.) Original construction date

More information

90% Efficiency without Boiler Replacement TRUE GREEN SOLUTIONS NEW. Patent Pending. EcoFlex 90 + System Modulating Fan-Powered Economizer

90% Efficiency without Boiler Replacement TRUE GREEN SOLUTIONS NEW. Patent Pending. EcoFlex 90 + System Modulating Fan-Powered Economizer without Boiler Replacement TRUE GREEN SOLUTIONS NEW Patent Pending EcoFlex + System Modulating Fan-Powered Economizer EcoFlex + System Because They Are Your Btus EcoFlex + System - a packaged modulating

More information

Packaged Semi-Instantaneous Steam Fired Water Heater

Packaged Semi-Instantaneous Steam Fired Water Heater MODEL STX Packaged Semi-Instantaneous Steam Fired Water Heater Shell and Tube Style Heater Features Reliable Only high grade materials used in construction to ensure long operating life Heat exchange pressure

More information

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District HOLUM EDUCATION CENTER Architectural The existing building has approximately 41,823 square feet and sets on a lot about 4.14 acres in size. Parking lots are located along the east and west sides of the

More information

High efficiency, cast-iron gas boiler

High efficiency, cast-iron gas boiler SENTRY High efficiency, cast-iron gas boiler LOWER PROFILE MAKES PROBLEM INSTALLATIONS EASY SENTRY High efficiency, cast-iron gas boiler A smarter choice for informed The boiler you choose for your home

More information

Chapter FUEL GAS CODE*

Chapter FUEL GAS CODE* Chapter 19.09 FUEL GAS CODE* * Editors Note: Serial No. 2004-31, 1, adopted Oct. 11, 2004 amended Title 19 in its entirety to read as herein set out. See the editor's note at Tit. 19 and also the Code

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 29 - STATEN ISLAND, 1581 VICTORY BLVD, New York, 10314 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-10 11:28 AM 2018-01-17 11:37 AM Asset Data Are there fuel tanks?

More information

Efficient Steam System Design

Efficient Steam System Design Efficient Steam System Design The word Efficient is often used to describe the general performance of a system. However it is important to distinguish between efficiency and effectiveness. Efficiency is

More information

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

EADQUARTERS. Technical Report One. Stephanie Kunkel   Mechanical Option EADQUARTERS 707 N. Calvert St. Technical Report One ASHRAE Standard 62.1 Ventilation ASHRAE Standard 90.1 Energy Design Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option

More information