INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WFERV. Bard Manufacturing Company, Inc.

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WFERV. Bard Manufacturing Company, Inc."

Transcription

1 INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WFERV Bard Manufacturing Company, Inc. Bryan, Ohio 4356 Since Moving ahead, just as planned. Manual: Supersedes: NEW File: Volume III, Tab 19 Date: Manual Page 1 of 21

2 CONTENTS Model Nomenclature Legend... 3 Electrical Specifications... 3 General Description... 3 General Information... 3 Unpacking... 3 Performance and Application Data - WFERV... 4 Basic Installation (Field Installation)... 5 & 6 Basic Installation (Factory Installed Versions) Control Wiring Control Requirements Recommended Control Sequences Ventilation Airflow Energy Recovery Ventilator Maintenance Maintenance Procedures Quarterly & Annual Maintenance Wiring Diagram Figures Figure 1 Intake Hood Assembly... 6 Figure 2 Remove Vent Option Door... 7 Figure 3 Filter & Exhaust Plate Location... 8 Figure 4 Installation of Exhaust Blower Assembly... 9 Figure 5 Installation of WFERV... 1 Figure 6 WFERV Assembly...11 Figure 7 Wiring - 23 Volt Figure 8 Installation of Fresh Air Intake Hood Assembly Figure 9 Operation of Unit with WFERV Figure 1 Thermostat Wiring Figure 11 Terminal Block Location Diagram Figure 12 Hub Assembly with Ball Bearings... 2 Tables Table 1 Ventilation Air (CFM) COPYRIGHT SEPTEMBER 27 BARD MANUFACTURING COMPANY, INC. BRYAN, OHIO USA 4356 Manufactured under the following U.S. patent numbers: 5,485,878; 5,23,116; 4,924,934; 4,875,52; 4,825,936 Manual Page 2 of 21

3 MODEL NOMENCLATURE LEGEND WF ERV A WF = Wall Mount Gas Furnace Energy Recovery Ventilator Electrical A = 23/28 Volt ELECTRICAL SPECIFICATIONS Model Voltage Amps Control Voltage WFERV 23/ V GENERAL DESCRIPTION The Energy Recovery Ventilator was designed to provide energy efficient, cost effective ventilation to meet I.A.Q. (Indoor Air Quality) requirements while still maintaining good indoor comfort and humidity control for a variety of applications such as schools, classrooms, lounges, conference rooms, beauty salons and others. It provides a constant supply of fresh air for control of airborne pollutants including CO 2, smoke, radon, formaldehyde, excess moisture, virus and bacteria. The ventilator incorporates patented rotary heat exchanger technology to remove both heat and moisture. It is designed as a single package, which can be easily factory or field installed for new installations or retrofit to Bard WF wall mounted units. The package consists of a unique rotary Energy Recovery Cassette that can be easily removed for cleaning or maintenance. The cassette has a 21-inch diameter heat transfer wheel for efficient heat transfer. The heat transfer wheel uses a permanently bonded dry desiccant coating for total heat recovery. Ventilation is accomplished with two (2) blower/motor assemblies each consisting of a drive motor and dual blowers for maximum ventilation at low sound levels. On non-independent motor control models, the air is exhausted at the same rate that fresh air is brought into the structure, thus not impacting building pressure. On independent motor control models, the air can be exhausted at a different rate than the intake or fresh air. Never operate the fresh air at a lower speed than the exhaust air. Operating the fresh air at a higher speed than the exhaust air will help maintain a slight positive pressure in the building. The rotating energy wheel provides the heat transfer effectively during both summer and winter conditions. Provides required ventilation to meet the requirements of ASHRAE standard. NOTE: Never set intake blower at a lower speed than the exhaust blower, as it will create a negative pressure in the room. During operation below 5 degrees F outdoor temperature, freezing of moisture in the heat transfer wheel can occur. Consult the factory if this possibility exists. GENERAL INFORMATION The ventilator should only be installed by a trained heating and air conditioning technician. These instructions serve as a guide to the technician installing the ventilator package. They are not intended as a stepby-step procedure with which the mechanically-inclined owner can install the package. The ventilator housing is shipped in one carton, which contains the following: 1. Energy Recovery Ventilator 2. Service Door 3. Rain Hood and Mist Eliminator 4. Installation Instructions UNPACKING Upon receipt of the equipment, be sure to compare the model number found on the shipping label with the accessory identification information on the ordering and shipping document to verify that the correct accessory has been shipped. Inspect the carton housing of each ventilator as it is received, and before signing the freight bill, verify that all items have been received and that there is no visible damage. Note any shortages or damage on all copies of the freight bill. The receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier s agent. Concealed damage not discovered until after loading must be reported to the carrier within 15 days of its receipt. Manual Page 3 of 21

4 Ambient O.D. DB/ WB F VLT VENTILATION RATE 45 CFM High Speed (Black) 72% EFFICIENCY VLS VLL HRT APPLICATION DATA WFERV SUMMER COOLING PERFORMANCE (INDOOR DESIGN CONDITIONS 75 DB/63 WB) HRS HRL VLT VENTILATION RATE 37 CFM Medium Speed (Blue) 73% EFFICIENCY VLS VLL HRT HRS HRL VLT VENTILATION RATE 28 CFM Low Speed (Red) 74% EFFICIENCY VLS VLL HRT HRS HRL WINTER HEATING PERFORMANCE (INDOOR DESIGN CONDITIONS 7 F DB) VENTILATION RATE Ambient O.D. DB F 45 CFM 76% EFF. WVL WHR 37 CFM 78% EFF. WVL WHR 28 CFM 8% EFF. WVL WHR LEGEND: VLT = Ventilation Load Total VLS = Ventilation Load Sensible VLL = Ventilation Load Latent HRT = Heat Recover Total HRS = Heat Recovery Sensible HRL = Heat Recovery Latent WVL = Winter Ventilation Load WHR = Winter Heat Recovery NOTE: Sensible performance only is shown for winter application Manual Page 4 of 21

5 BASIC INSTALLATION (Field Installation) 1. Unpack the ventilator assembly, which includes the integral ventilator with attached electrical harness and miscellaneous hardware. Model WARNING Open breaker switch before installing this accessory to prevent injury or death due to electrical shock or contact with moving parts. Turn thermostat to OFF. For Use With Following Units WFERV WF5-125 Electrical 23/28-1 or 3 phase 2. Remove intake hood assembly from back of ventilator. (See Figure 1.) 3. Remove the existing exterior vent option door on the unit. (See Figure 2.) 4. Remove and save existing unit air filter. Remove and discard the rear exhaust cover plate and remove center screw from condenser grille. (See Figure 3.) 5. Install exhaust blower assembly in rear exhaust opening and secure with four (4) screws. Position 4 pin connector so it is accessible. (See Figure 4.) 6. Install ventilator into the unit. (See Figure 5.) IMPORTANT NOTE: Position front lip of ventilator over front grille and on top of condenser partition. (See Figure 5.) This is important to insure proper drainage of any water entering damper assembly. 7. Remove cassette and plug in exhaust blower. Replace cassette. (See Figure 6.) 8. Open control panel to gain access to unit low voltage terminal block. (Insure all power is OFF prior to opening the control panel.) 9. Remove female plug of low voltage wiring harness from the heat recovery assembly and snap into filter rack. Route electrical harness leads through the 7/8" bushing into the low voltage box. (See Figure 5.) 1. Connect leads C (black), W (blue), and G (orange) with fork terminal to corresponding points on terminal strip. (See Figure 7 for 23V units.) NOTE: These 24 volt control wires control the starting and stopping of the Energy Recovery Ventilator and can be independently controlled by an energy management control or timer. See separate section on Control Wiring for suggested control schemes. 11. Remove female plug of high voltage wiring harness from the heat recover assembly and snap into filter rack. Wire to terminal block. (See Figure 7 for 23V units.) 12. Plug male plug from female at filter rack. (See Figure 5.) 13. Close control panel cover. 14. Replace filter and one (1) screw in condenser grille. (See Figure 3) 15. Ventilator checkout A. Resupply power to unit. B. Energize the evaporator blower by switching thermostat to the manual fan position with Heat/Cool in OFF position. C. Ventilator heat transfer wheels should rotate slowly (49 RPM). Intake and exhaust blowers should run. (See Figure 9.) D. De-energize the evaporator blower. Energy Recovery wheels, and fresh air and exhaust air blowers should stop. E. This completes ventilator checkout. Manual Page 5 of 21

6 16. Disconnect the wires connected in Step 1 if other control options are to be used. 17. Replace the lower service access panel with the new panel provided. Attach air intake hood with screws provided. (See Figure 9.) Be sure to insert the top flange of the air intake hood into and through the slot in the service door and between the door and insulation to prevent bowing of the door. 18. Close front door. 19. Apply Certification label, included with Installation Instructions, next to unit Serial Plate. 19. Ventilator is now ready for operation. FIGURE 1 INTAKE HOOD ASSEMBLY Manual Page 6 of 21

7 FIGURE 2 REMOVE VENT OPTION DOOR FRONT DOOR VENT OPTION DOOR EXHAUST COVER PLATES MIS-235 Manual Page 7 of 21

8 FIGURE 3 FILTER AND EXHAUST PLATE LOCATION FRONT DOOR REAR EXHAUST FILL PLATE FRONT EXHAUST FILL PLATE FILTER SCREW MIS-2345 Manual Page 8 of 21

9 FIGURE 4 INSTALLATION OF EXHAUST BLOWER ASSEMBLY FASTEN ASSEMBLY TO CONDENSER PARTITION WITH (4) SCREWS DO NOT REMOVE FRONT PLATE LOWER WFERV ASSEMBLY LOCATING HOLES RIGHT SIDE ATTATCH EXHAUST BLOWER ENCLOSER WITH SCREWS PROVIDED AS SHOWN. MIS-2353 Manual Page 9 of 21

10 Manual Page 1 of 21 FIGURE 5 INSTALLATION OF WFERV

11 FIGURE 6 WFERV ASSEMBLY Manual Page 11 of 21

12 FIGURE 7 WIRING 23 VOLT 23 VOLT WIRES INSERTED WITH BLOWER WIRES, CONNECT WIRES TO "L1" AND "L2" ON CONTROL BOARD AS SHOWN ON WIRING DIAGRAM GROUND WIRE CONNECT LOW VOLTAGE WIRES TO "C", "W1", AND "G" AS SHOWN ON WIRING DIAGRAM MIS-2356 Manual Page 12 of 21

13 FIGURE 8 INSTALLATION OF FRESH AIR INTAKE HOOD ASSEMBLY Manual Page 13 of 21

14 FIGURE 9 OPERATION OF UNIT WITH WFERV INSTALLED GAS MANIFOLD TOP BURNER BOX INDUCER DRAFT BLOWER SUPPLY AIR EXHAUST HOOD EXHAUST AIR GAS VALVE INDOOR (COMFORT AIR) BLOWER INTAKE AIR HOOD INTAKE AIR FILTER INTAKE BLOWER WFERV HOOD RETURN AIR FRESH AIR WERV CASSETTE EXHAUST BLOWER MIS-2369 Manual Page 14 of 21

15 BASIC INSTALLATION (FACTORY INSTALLED VERSIONS) 1. Remove air intake hood from return air area of unit. (See Figure 1.) 2. Install air intake hood. Refer to Item 17 of Basic Installation (Field Installation). 3. Refer to Control Wiring section for suggested control schemes for the WFERV. 4. After wiring, replace all panels. CONTROL WIRING The WFERV comes from the factory with the low voltage control wires wired into the wall mount low voltage terminal strip (see wiring diagrams). Care must be taken when deciding how to control the operation of the ventilator. When designing the control circuit for the ventilator, the following requirements must be met. CONTROL REQUIREMENTS 1. Indoor blower motor must be run whenever the WFERV is run. 2. Select the correct motor speed tap in the WFERV. Using Table 1 of the WFERV Installation Instructions, determine the motor speed needed to get the desired amount of ventilation air needed. For instance, do not use the high speed tap on a WFERV if only 2 CFM of ventilation air is needed. Use the low speed tap. Using the high speed tap would serve no useful purpose and significantly affect the overall efficiency of the system. System operating cost would also increase. 3. Run the WFERV only during periods when the conditioned space is occupied. Running the WFERV during unoccupied periods wastes energy, decreases the expected life of the WFERV, and can result in a large moisture buildup in the structure. The WFERV removes 6 to 7% of the moisture in the incoming air, not 1% of it. Running the WFERV when the structure is unoccupied allows moisture to build up in the structure because there is little or no load. Use a control system that in some way can control the system based on occupancy. * * IMPORTANT * * Operating the WFERV during unoccupied periods can result in a build up of moisture in the structure. RECOMMENDED CONTROL SEQUENCES Several possible control scenarios are listed below: 1. Use a programmable electronic thermostat with auxiliary terminal to control the WFERV based on daily programmed occupance periods. 2. Use a motion sensor in conjunction with a mechanical thermostat to determine occupancy in the structure. Bard markets the CS2 for this use. 3. Use a DDC control system to control the WFERV based on a room occupancy schedule to control the WFERV. 4. Tie the operation of the WFERV into the light switch. The lights in a room are usually on only when occupied. 5. Use a manual timer that the occupants turn to energize the WFERV for a specific number of hours. 6. Use a programmable mechanical timer to energize the WFERV and indoor blower during occupied periods of the day. VENTILATION AIRFLOW The 24 volt WFERV is equipped with a 3-speed motor to provide the capability of adjusting the ventilation rates to the requirements of the specific application by simply changing motor speeds. Manual Page 15 of 21

16 Model TABLE 1 VENTILATION AIR (CFM) VENTILATION AIR High Speed (Black) (CFM) Med. Speed (Blue) Low Speed (Red) WFERV All units are factory set on High speed and can be field adjusted for lower speeds if required. 24-Volt Units (Single switch models): The speed of both blowers (intake and exhaust) can be controlled by a switch located on the left side of the control panel, behind the WFERV front door. 24-Volt Units (Dual switch models): The speed of each blower (intake and exhaust) can be controlled independently by two (2) switches located on the left side of the control panel, behind the WFERV front door. The switch located on the upper part of the control panel controls the intake blower located in the upper assembly. The switch located on the lower part of the control panel controls the exhaust blower located in the lower assembly. See Figure 6. If desired, the intake blower can be set up for one speed and the exhaust blower set up for another speed if needed for the specific application. WARNING Open circuit breaker to shut all power OFF before doing this. Failure to do so could result in injury or death due to electrical shock. ENERGY RECOVERY VENTILATOR MAINTENANCE GENERAL INFORMATION The ability to clean exposed surfaces within air moving systems is an important design consideration for the maintenance of system performance and air quality. The need for periodic cleaning will be a function of operating schedule, climate, and contaminants in the indoor air being exhausted and in the outdoor air being supplied to the building. All components exposed to the airstream, including energy recovery wheels, may require cleaning in most applications. Rotary counterflow heat exchanges (heat wheels) with laminar airflow are self-cleaning with respect to dry particles. Smaller particles pass through; larger particles land on the surface and are blown clear as the flow direction is reversed. For this reason, the primary need for cleaning is to remove films of oil-based aerosols that have condensed on energy transfer surfaces. Buildup of material over time may eventually reduce airflow. Most importantly, in the case of desiccant coated (enthalpy) wheels, such films can close off micron sized pores at the surface of the desiccant material, reducing the efficiency with which the desiccant can absorb and desorb moisture. FREQUENCY In a reasonably clean indoor environment such as a school, office building, or home, experience shows that reductions of airflow or loss of sensible (temperature) effectiveness may not occur for ten or more years. However, experience also shows that measurable changes in latent energy (water vapor) transfer can occur in shorter periods of time in commercial, institutional and residential applications experiencing moderate occupant smoking or with cooking facilities. In applications experiencing unusually high levels of occupant smoking, such as smoking lounges, nightclubs, bars and restaurants, washing of energy transfer surfaces, as frequently as every six months, may be necessary to maintain latent transfer efficiency. Similar washing cycles may also be appropriate for industrial applications involving the ventilation of high levels of smoke or oilbased aerosols such as those found in welding or machining operations, for example. In these applications, latent efficiency losses of as much as 4% or more may develop over a period of one to three years. CLEANABILITY AND PERFORMANCE In order to maintain energy recovery ventilation systems, energy transfer surfaces must be accessible for washing to remove oils, grease, tars and dirt that can impede performance or generate odors. Washing of the desiccant surfaces is required to remove contaminate buildups that can reduce adsorption of water molecules. The continued ability of an enthalpy wheel to transfer latent energy depends upon the permanence of the bond between the desiccant and the energy transfer surfaces. Bard wheels feature silica gel desiccant permanently bonded to the heat exchange surface without adhesives; the desiccant will not be lost in the washing process. Proper cleaning of the Bard energy recovery wheel will restore latent effectiveness to near original performance. MAINTENANCE PROCEDURES NOTE: Local conditions can vary and affect the required time between routine maintenance procedures, therefore all sites (or specific units at a site) may not have the same schedule to maintain acceptable performance. The following timetables are recommended and can be altered based on local experience. Manual Page 16 of 21

17 QUARTERLY MAINTENANCE 1. Inspect mist eliminator/prefilter and clean if necessary. This filter is located in the fresh air intake hood on the front of the unit. This is an aluminum mesh filter and can be cleaned with water and any detergent not harmful to aluminum. 2. Inspect wall mount unit filter and clean or replace as necessary. This filter is located either in the unit, in a return air filter grille assembly, or both. If in the unit it can be accessed by removing the lower service door on the front of the unit. If in a return air filter grille, by hinging the grille open to gain access. 3. Inspect energy recovery ventilator for proper wheel rotation and dirt buildup. This can be done in conjunction with Item 2 above. Energize the energy recovery ventilator after inspecting the filter and observe for proper rotation and/or dirt buildup. 4. Recommended energy recovery wheel cleaning procedures follow: Disconnect all power to unit. Remove the lower service door of the wall mount unit to gain access to the energy recovery ventilator. 5. Remove the front access panel on the ventilator. Unplug amp connectors to cassette motors. Slide energy recovery cassette out of ventilator. 6. Use a shop vacuum with brush attachment to clean both sides of the energy recovery wheels. 7. Reverse shop vacuum to use as a blower and blow out any residual dry debris from the wheel. NOTE: Discoloration and staining of the wheel does not affect its performance. Only excessive buildup of foreign material needs to be removed. 8. If any belt chirping or squealing noise is present, apply a small amount of LPS-1 or equivalent dry film lubricant to the belt. ANNUAL MAINTENANCE 1. Inspect and conduct the same procedures as outlined under Quarterly Maintenance. 2. To maintain peak latent (moisture) removal capacity, it is recommended that the energy recovery wheels be sprayed with a diluted nonacid based evaporator coil cleaner or alkaline detergent solution such as 49. NOTE: Do not use acid based cleaners, aromatic solvents, temperatures in excess of 17 F or steam. Damage to the wheel may result. Do not disassemble and immerse the entire heat wheel in a soaking solution, as bearing and other damage may result. 3. Rinse wheel thoroughly after application of the cleaning solution, and allow to drain before reinstalling. 4. No re-lubrication is required to heat wheel bearings of the drive motor, or to the intake and exhaust blower motors. 5. If any belt chirping or squealing noise is present, apply a small amount of LPS-1 or equivalent dry film lubricant to the belt. Manual Page 17 of 21

18 Manual Page 18 of 21 FIGURE 1 THERMOSTAT WIRING DIAGRAM

19 FIGURE 11 TERMINAL BLOCK LOCATION Manual Page 19 of 21

20 Manual Page 2 of 21 FIGURE 12 HUB ASSEMBLY WITH BALL BEARING

21 Manual Page 21 of 21

INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WGERV-A3A WGERV-C3A WGERV-A5A WGERV-C5A WGSERV-A5 WGSERV-C5

INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WGERV-A3A WGERV-C3A WGERV-A5A WGERV-C5A WGSERV-A5 WGSERV-C5 INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WGERV-A3A WGERV-C3A WGERV-A5A WGERV-C5A WGSERV-A5 WGSERV-C5 Bard Manufacturing Company, Inc. Bryan, Ohio 4356 Since 1914...Moving

More information

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST Models: WERV-A2B WERV-A3C WERV-C2B WERV-C3C For Use With Bard 1-1/2 Through 3 Ton Wall Mount Air Conditioners and Heat Pumps

More information

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST Models: ERVF-A3 ERVF-C3 For Use With Bard 2-1/2 through 3 Ton Wall Mount Air Conditioners and Heat Pumps Bard Manufacturing

More information

Q-TEC QC-Series Chilled Water Air Conditioner

Q-TEC QC-Series Chilled Water Air Conditioner Cooling Capacities: 13,3 to 49,3 BTUH (Based on EWT, GPM & CFM) Q-TEC QC-Series Chilled Water Air Conditioner The Q-TEC Series self-contained packaged chilled water air conditioner is designed to be installed

More information

THE WALL-MOUNT TM SIX TON AIR CONDITIONER

THE WALL-MOUNT TM SIX TON AIR CONDITIONER The Bard Wall-Mount Six Ton Air Conditioner is a self contained energy efficient system, which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or

More information

Green Refrigerant. THE WALL-MOUNT STEP CAPACITY AIR CONDITIONERS Integrated Part Load Value (IPLV) Efficiency Up To 15.3 BTU/WATT. Engineered Features

Green Refrigerant. THE WALL-MOUNT STEP CAPACITY AIR CONDITIONERS Integrated Part Load Value (IPLV) Efficiency Up To 15.3 BTU/WATT. Engineered Features THE WALL-MOUNT STEP CAPACITY AIR CONDITIONERS Integrated Part Load Value (IPLV) Efficiency Up To 5.3 BTU/WATT WA3S WA5S Right Side Control Panel WL3S WL5S Left Side Control Panel 3 to 5 Ton (35,2 to 5,5

More information

Q-TEC Q24A-Q60A Air Conditioners

Q-TEC Q24A-Q60A Air Conditioners The Q-TEC Series self contained packaged air conditioner is designed to be installed inside a building structure against an exterior exposed wall. Q-TEC s design provides whisper quiet operation with total

More information

THE WALL-MOUNT Quiet Climate A/C 10.0 EER

THE WALL-MOUNT Quiet Climate A/C 10.0 EER THE WALL-MOUNT Quiet Climate A/C. EER Models WA, W9A, WA to Ton (, to, Btuh) Right Side Control Panel Hz GREEN REFRIGERANT R-A The Bard Wall-Mount Air Conditioner is a self contained energy efficient system,

More information

THE WALL-MOUNT HEAT PUMPS EER, (60HZ)

THE WALL-MOUNT HEAT PUMPS EER, (60HZ) THE WALL-MOUNT HEAT PUMPS -. EER, (HZ) Models: Heating Capacities: Cooling Capacities: Engineered Features WHA to WHA Hz (,5 to 5,5 Btuh) (7, to 5, Btuh) The Bard Wall-Mount Heat Pump is a self contained

More information

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121 INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS Model: WA121 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. Manual : 2100-234 G Supersedes: 2100-234

More information

SAFETY AND INSTALLATION MANUAL MODEL 8100

SAFETY AND INSTALLATION MANUAL MODEL 8100 SAFETY AND INSTALLATION MANUAL ENERGY RECOVERY VENTILATORS MODEL 8100 Provides year-round fresh air Recovers 77% of the apparent heating or cooling energy from the exhausted air See Warnings Page 3 Table

More information

Heat Recovery Ventilators models:

Heat Recovery Ventilators models: User s Manual Read and save these instructions. Heat Recovery Ventilators models: 1000 HE 2000 HE 3000 HE 3055 Compact HE 1.3 HE 1.8 HE 2.6 5585 Compact VB0021 VVI, 550 Lemire Blvd., Drummondville, Qc,

More information

INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER

INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER BARD MANUFACTURING COMPANY Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual: 2100-393C Supersedes: 2100-393B File: Volume III Tab

More information

Energy Recovery with Cooling and Heating Model ERCH

Energy Recovery with Cooling and Heating Model ERCH Energy Recovery with Cooling and Heating Model ERCH 100% Outdoor Air System Dedicated Outdoor Air System 1,000-10,000 cfm 1.75 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating,

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS.......................... 2 INTERMITTENT IGNITION DEVICE...........

More information

USER S GUIDE. For all Packaged Systems (Air Conditioners and Heat Pumps)

USER S GUIDE. For all Packaged Systems (Air Conditioners and Heat Pumps) USER S GUIDE For all Packaged Systems (Air Conditioners and Heat Pumps) WA & WL - Series Air Conditioners WH & SH - Series Air Source Heat Pumps QA - Series Air Conditioners QH - Series Air Source Heat

More information

CATALOG. SKYPAK Self-Contained Heating/Cooling Units

CATALOG. SKYPAK Self-Contained Heating/Cooling Units CATALOG SKYPAK Self-Contained Heating/Cooling Units FORM SK145.00-EG6 (1211) TABLE OF CONTENTS SKYPAK Self-Contained Heating/Cooling Units Introduction...3 Product Overview...3 Nomenclature...4 SKYPAK

More information

SKYPAK II, 3 Ton Series, gives you a

SKYPAK II, 3 Ton Series, gives you a SKYPAK II 3 ton Heating And Cooling self-contained Package SKYPAK II, 3 Ton Series, gives you a complete air-conditioning and heating system as an all in one package unit. Designed for convenient through-the-wall

More information

I-TEC I30A1D-I60A1D 2-Stage Compressor High Efficiency Air Source Air Conditioners w/dehumidification

I-TEC I30A1D-I60A1D 2-Stage Compressor High Efficiency Air Source Air Conditioners w/dehumidification I-TEC I30AD-IAD 2-Stage Compressor High Efficiency Air Source Air Conditioners w/dehumidification Cooling Capacities: 20,0 to 54,000 Btuh The Bard I-TEC Air Conditioner system is designed for classrooms

More information

Daikin Water Cooling, Heating, and High Capacity Booster Coils

Daikin Water Cooling, Heating, and High Capacity Booster Coils Installation and Maintenance Manual IM 900 Daikin Water Cooling, Heating, and High Capacity Booster Coils Group: Applied Air Part Number: IM 900 Date: February 2008 Types HI-F5, E-F5 2008 Daikin International

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. VARIABLE SPEED ELECTRIC FURNACE INSTALLATION INSTRUCTIONS VARIABLE SPEED ELECTRIC FURNACE SAFETY...1 INSTALLATION REQUIREMENTS...2 Tools and Parts...2 Location Requirements...2 Installation Configurations...3

More information

GreenPac & GreenPac HGR Heat Pumps & Air Conditioners Models AVP

GreenPac & GreenPac HGR Heat Pumps & Air Conditioners Models AVP MANUFACTURER CERTIFIED TO ARI AS COMPLYING WITH R EQUIPMENT ARI STANDARD 210 ARI STANDARDS GreenPac & GreenPac HGR Heat Pumps & Air Conditioners Models AVP24-30-36-42-48-60 General Description The Marvair

More information

AGITATOR V DO NOT OPERATE THE MACHINE UNTIL YOU HAVE READ ALL SECTIONS OF THESE INSTRUCTIONS IMPROPER USE OF THE MACHINE WILL VOID THE WARRANTY

AGITATOR V DO NOT OPERATE THE MACHINE UNTIL YOU HAVE READ ALL SECTIONS OF THESE INSTRUCTIONS IMPROPER USE OF THE MACHINE WILL VOID THE WARRANTY AGITATOR 20 120V INFORMATION & OPERATING INSTRUCTIONS DO NOT OPERATE THE MACHINE UNTIL YOU HAVE READ ALL SECTIONS OF THESE INSTRUCTIONS IMPROPER USE OF THE MACHINE WILL VOID THE WARRANTY 1. Always use

More information

SKYPAK II Heating & Cooling Self Contained Packages

SKYPAK II Heating & Cooling Self Contained Packages SKYPAK II Heating & Cooling Self Contained Packages SKYPAK II gives you a complete airconditioning and heating system as an all-in-one package unit. Designed for conventional through-the-wall installation

More information

GREEN REFRIGERANT R-410A

GREEN REFRIGERANT R-410A PH-SERIES PCKGED HET PUMPS Cooling Capacities: 2, to 6, Heating Capacities:, to 2, SEER:. HSPF: GREEN REFRIGERNT R-4 FRONT (INDOOR IRFLOW) END OF UNIT CK (OUTDOOR IRFLOW) END OF UNIT Standard Engineered

More information

HEAT PUMP A GUIDE TO OPERATING AND MAINTAINING YOUR RESIDENTIAL HEAT PUMP UNIT NOTE TO INSTALLER: THIS MANUAL SHOULD BE LEFT WITH THE EQUIPMENT USER.

HEAT PUMP A GUIDE TO OPERATING AND MAINTAINING YOUR RESIDENTIAL HEAT PUMP UNIT NOTE TO INSTALLER: THIS MANUAL SHOULD BE LEFT WITH THE EQUIPMENT USER. HEAT PUMP A GUIDE TO OPERATING AND MAINTAINING YOUR RESIDENTIAL HEAT PUMP UNIT NOTE TO INSTALLER: THIS MANUAL SHOULD BE LEFT WITH THE EQUIPMENT USER. WELCOME TO EFFICIENT YEAR-ROUND COMFORT Congratulations

More information

MODELS B1PA024, 030 AND 036

MODELS B1PA024, 030 AND 036 STELLAR 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.26-N1Y (892) 511.26-N1Y (893) MODELS B1PA024, 030 AND 036 035-11622 GENERAL YORK Model B1PA units are factory assembled heat

More information

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP RV Products Division INSTALLATION INSTRUCTIONS FOR 46515 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP TABLE OF CONTENTS 1. Warnings.................................................. 2 2. Component

More information

T-Series Air Conditioner T53 Model

T-Series Air Conditioner T53 Model INSTRUCTION MANUAL T-Series Air Conditioner T53 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit Packaged Gas/Electric Units Owner s Guide to Operating and Maintaining Your Gas/Electric Unit ELECTRICAL SHOCK HAZARD. FIRE OR EXPLOSION HAZARD Disconnect power at fuse box or service panel before performing

More information

62DA,DB,DC,DD,DE,DF07-38

62DA,DB,DC,DD,DE,DF07-38 62D-3SB 62DA,DB,DC,DD,DE,DF07-38 DEDICATED VERTICAL OR HORIZONTAL 100% OUTDOOR AIR UNIT PERFORMANCE DATA UNIT DIMENSION PRINTS ACCESSORY DIMENSION PRINTS Copyright 2011 Carrier Corporation Syracuse, New

More information

Energy Recovery with Cooling and Heating

Energy Recovery with Cooling and Heating Energy Recovery with Cooling and Heating VersiVent - Model VER Commercial Institutional 2,000-10,000 cfm 3.0 in. wg external static pressure Configurable September 2008 Page The VersiVent Header Model

More information

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N T-SERIES Air Conditioner T20 Model INSTRUCTION MANUAL Rev. C P/N 89114993 TABLE OF CONTENTS Warranty and Return Policy... 2 IMPORTANT NOTICE... 2 RECEIVING THE AIR CONDITIONER... 3 HANDLING AND TESTING

More information

Contents. How to choose Recovery Ventilation type?...3. How do HRV, ERV and TRV Systems work?...4. Types of installations...5. VUT 200 H mini...

Contents. How to choose Recovery Ventilation type?...3. How do HRV, ERV and TRV Systems work?...4. Types of installations...5. VUT 200 H mini... Contents How to choose Recovery Ventilation type?............................................3 How do HRV, ERV and TRV Systems work?............................................4 Types of installations..............................................................5

More information

VERTICAL HIGH OUTPUT VHC-IOM INSTALLATION AND MAINTENANCE INSTRUCTIONS VHC INSTALLER MUST BE A TRAINED, EXPERIENCED SERVICE TECHNICIAN

VERTICAL HIGH OUTPUT VHC-IOM INSTALLATION AND MAINTENANCE INSTRUCTIONS VHC INSTALLER MUST BE A TRAINED, EXPERIENCED SERVICE TECHNICIAN VHC INSTALLER MUST BE A TRAINED, EXPERIENCED SERVICE TECHNICIAN 1. PRESSURE CHECK When the valve package is factory installed, the unit is shipped with the coil and associated piping/valve package pressurized.

More information

ML180UH SERIES GAS FURNACE WARNING WARNING

ML180UH SERIES GAS FURNACE WARNING WARNING 2017 Lennox Industries Inc. Dallas, Texas, USA 506525-01 04/2017 Supersedes 10/2015 ML180UH SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property damage,

More information

DES CHAMPS PRODUCTS. Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling

DES CHAMPS PRODUCTS. Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling DES CHAMPS PRODUCTS Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling DES CHAMPS PRODUCTS Packaged Heat Recovery Systems Micro-Z

More information

REPLACEMENT PARTS MANUAL

REPLACEMENT PARTS MANUAL REPLACEMENT PARTS MANUAL WALL-MOUNTED PACKAGE AIR CONDITIONER Models: W7A W8A WA General Notes Revised and/or additional pages may be issued from time to time. A complete and current manual consists of

More information

EL195UHE SERIES GAS FURNACE WARNING WARNING

EL195UHE SERIES GAS FURNACE WARNING WARNING 2012 Lennox Industries Inc. Dallas, Texas, USA 506737-01 12/2012 Supersedes 06/2011 EL195UHE SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property

More information

Benefits Offered by Passive Dehumidification Wheel Speed Control

Benefits Offered by Passive Dehumidification Wheel Speed Control Benefits Offered by Passive Dehumidification Wheel Speed Control White paper By John Fischer Benefits Offered by Passive Dehumidification Wheel Speed Control The most significant advantage of the Pinnacle

More information

BRONZE MODELS 90H* 190H READ AND SAVE THESE INSTRUCTIONS

BRONZE MODELS 90H* 190H READ AND SAVE THESE INSTRUCTIONS USER GUIDE VB0110 BRONZE MODELS 90H* 190H READ AND SAVE THESE INSTRUCTIONS *This product earned the ENERGY STAR by meeting strict energy efficiency guidelines set by Natural Resources Canada and the US

More information

Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional

Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional 1,000-6,000 cfm 2.0 in. wg External Static Pressure Aluminum Plate Heat Exchanger April 2017 Heat Recovery Ventilators Greenheck

More information

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS* TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS K*ES120 10 NOMINAL TONS EER 8.5 DESCRIPTION These completely assembled dual circuit evaporator blower units include a well-insulated cabinet, a DX cooling

More information

Solid Door Top Mount Reach-In Freezer

Solid Door Top Mount Reach-In Freezer Solid Door Top Mount Reach-In Freezer Service, Installation and Care Manual Please read this manual completely before attempting to install or operate this equipment. Notify carrier of damage! Inspect

More information

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE CAS Product Specifications Single stage cooling capacity control on all models with Micro channel

More information

ICE CREAM TOPPING CABINETS REFRIGERATOR or FREEZER Installation, Operation and Maintenance Instructions

ICE CREAM TOPPING CABINETS REFRIGERATOR or FREEZER Installation, Operation and Maintenance Instructions ICE CREAM TOPPING CABINETS REFRIGERATOR or FREEZER Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

SLP98UH SERIES VARIABLE CAPACITY GAS FURNACE WARNING WARNING

SLP98UH SERIES VARIABLE CAPACITY GAS FURNACE WARNING WARNING 2015 Lennox Industries Inc. Dallas, Texas, USA 506443-01 01/2015 Supersedes 08/2012 SLP98UH SERIES VARIABLE CAPACITY GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can

More information

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N T-SERIES Air Conditioner T50 Model INSTRUCTION MANUAL Rev. F P/N 10-1008-203 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.

More information

EL296UHV SERIES GAS FURNACE WARNING WARNING

EL296UHV SERIES GAS FURNACE WARNING WARNING 2011 Lennox Industries Inc. Dallas, Texas, USA 506769 01 08/2012 Supersedes 10/2011 EL296UHV SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property

More information

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC! COIL Manufacturing Inc. When you want Quality, specify COLMAC! Installation, Operation, and Maintenance ENG00018621 Rev A Air Cooled Fluid Coolers Contents 1. SAFETY INSTRUCTIONS... 1 2. MODEL NOMECLATURE...

More information

RCM-77. Instruction Manual. G-Series Cooler. U.S. Patent No. 8,215,125 RECHARGE COLD MERCHANDISER

RCM-77. Instruction Manual. G-Series Cooler. U.S. Patent No. 8,215,125 RECHARGE COLD MERCHANDISER G-Series Cooler RECHARGE COLD MERCHANDISER U.S. Patent No. 8,215,125 Instruction Manual FOR YOUR FUTURE REFERENCE This easy-to-use manual will guide you in getting the best use of your cooler. Remember

More information

Energy Recovery Ventilators

Energy Recovery Ventilators Energy Recovery Ventilators Models ERM, MiniVent, ERV and ERVe Untempered Preconditioners September 2016 Energy Recovery Ventilators Greenheck offers a complete line of energy recovery ventilators to reduce

More information

Product Specifications. Vertical Floor Consoles By First Co.

Product Specifications. Vertical Floor Consoles By First Co. NOW WITH 18 GAUGE CABINET AND FACTORY INSTALLED SERVICE SWITCH Product Specifications VFB Series VSB Series VCB Series Vertical Console Fan Coils 300-00 CFM Vertical Floor Consoles By First Co. VFB Series

More information

Pocket Hardmount. Preventative Maintenance.

Pocket Hardmount. Preventative Maintenance. Pocket Hardmount Preventative Maintenance www.comlaundry.com Part No. 7-04-49 November 2005 Table of Contents Daily...2 Beginning of the Day...2 End of the Day...4 Weekly...6 Monthly...7 Quarterly...11

More information

48PGD/E/F/L/M/N PG20-28

48PGD/E/F/L/M/N PG20-28 48/50PG-10SB 48PGD/E/F/L/M/N20-28 50PG20-28 SINGLE-PACKAGE COOLING UNITS WITH FACTORY-INSTALLED GAS HEAT SINGLE-PACKAGE COOLING UNITS WITH OPTIONAL ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINTS

More information

WKS 2200 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

WKS 2200 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- 8610 Production Avenue San Diego, California 92121 (858) 566-7465 Fax (858) 566-1943 WWW.BREEZAIRE.COM WKS 2200 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- Thank you for choosing a BREEZAIRE cooling

More information

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS CROWN Boiler Co Santa-Fe Series Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS These instructions must be affixed on or adjacent to the air handler Models: SAC049A20 SAC059A25

More information

INDUCED DRAFT HIGHBOY AND COUNTERFLOW/HORIZONTAL GAS FURNACE

INDUCED DRAFT HIGHBOY AND COUNTERFLOW/HORIZONTAL GAS FURNACE INDUCED DRAFT HIGHBOY AND COUNTERFLOW/HORIZONTAL GAS FURNACE USERS INFORMATION MANUAL MODELS FOR USE WITH NATURAL GAS MHA-50N, MHA-75N, MHA-100N, MHA-125N, MDA-50N, MDA-75N, MDA-100N, MDA-125N FOR USE

More information

OIL FURNACE USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW OIL-FIRED FURNACE

OIL FURNACE USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW OIL-FIRED FURNACE 58CLA OIL FURNACE USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW OIL-FIRED FURNACE NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER. WELCOME TO A NEW GENERATION

More information

REFRIGERATED PREP TABLES Installation, Operation and Maintenance Instructions

REFRIGERATED PREP TABLES Installation, Operation and Maintenance Instructions REFRIGERATED PREP TABLES Installation, Operation and Maintenance Instructions Please read this manual completely prior to installing and operating this equipment. This manual describes how to install,

More information

DES CHAMPS PRODUCTS 85% 4,400 CFM

DES CHAMPS PRODUCTS 85% 4,400 CFM DES CHAMPS PRODUCTS Saves up to 85% of the heat from exhaust airstream Removes pollutants before they accumulate Transfers heat energy in winter/cool energy in summer Low cost Capacities up to 4,400 CFM

More information

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS W12A2-A W12A1-K

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS W12A2-A W12A1-K INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS Model: W12A2-A W12A1-K Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. Manual: 2100-509E Supersedes:

More information

DCG Commercial. Submittal Data Form

DCG Commercial. Submittal Data Form DCG Commercial Submittal Data Form 15-25 Tons Packaged Gas / Electric Units 15 Tons Cooling Capacity: 180,000 BTU/h 20 Tons Cooling Capacity: 240,000 BTU/h 25 Tons Cooling Capacity: 290,000 BTU/h 15 Tons

More information

Product Release Summary

Product Release Summary Product Release Summary 48/50HC with System March 2012 TC Benefits of EnergyX System Why Energy Recovery 1. Code requirements: ASHRAE 90.1-2004: Energy Recovery is required when design supply air capacity

More information

IMPORTANT SAFETY INFORMATION! WARNING ALWAYS keep electric cords, home furnishings, drapes, clothing, papers, or other combustibles at least 3 feet (0

IMPORTANT SAFETY INFORMATION! WARNING ALWAYS keep electric cords, home furnishings, drapes, clothing, papers, or other combustibles at least 3 feet (0 Electric Fireplace Factory Model: EF-30D CONSUMER SAFETY INFORMATION Read this manual before installing and operating this appliance Failure to follow these instructions may result in electric shock, fire

More information

40KMC KMQ

40KMC KMQ 40KMC------301 40KMQ------301 OWNER S MANUAL Split system Global cassette indoor unit IR Remote Control Room Controller Zone Manager The unit can be used with infrared Remote Control, with the Carrier

More information

SLP98UHV WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

SLP98UHV WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 1029 L7 SLP98UHV SLP98UHV SERIES UNITS SLP98UHV series units are high efficiency upflow, horizontal right and left) gas furnaces equipped with variable capacity gas valve, variable

More information

G61MPV SERIES GAS FURNACE WARNING

G61MPV SERIES GAS FURNACE WARNING 2003 Lennox Industries Inc. Dallas, Texas, USA 504,809M 03/2009 Supersedes 06/2003 G61MPV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result

More information

ROOM AIR CONDITIONER OWNER'S MANUAL

ROOM AIR CONDITIONER OWNER'S MANUAL website http://www.lgservice.com e-mail http://www.lgeservice.com/techsup.html ROOM AIR CONDITIONER OWNER'S MANUAL Please read the operating instructions and safety precautions carefully and thoroughly

More information

Sandwich/Salad Table Under-counter Refrigerator Worktop Refrigerator

Sandwich/Salad Table Under-counter Refrigerator Worktop Refrigerator Sandwich/Salad Table Under-counter Refrigerator Worktop Refrigerator Service, Installation and Care Manual Please read this manual completely before attempting to install or operate this equipment. Notify

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 10 SEER Standard Efficiency Split System These units have been designed and tested for capacity and efficiency in accordance with

More information

BOTTOM MOUNT REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

BOTTOM MOUNT REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions BOTTOM MOUNT REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the Bill of Lading

More information

Operator s Manual. IP-100 Immersion Probe Cooler

Operator s Manual. IP-100 Immersion Probe Cooler Operator s Manual IP-100 Immersion Probe Cooler 110-810 04.27.11 Table of Contents Introduction... 3 General Information... 3 General Safety Information... 3 Safety Recommendations... 4 Unpacking Your

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS GVDM-26 DOMESTIC HOT WATER DESUPERHEATER PUMP MODULE KIT BMC, Inc. Bryan, Ohio 43506 Manual: 2100-546C Supersedes: 2100-546B Date: 4-18-16 Page 1 of 11 CONTENTS General... 3 Description...

More information

PVE SERIES POWER VENTER SYSTEM MANUAL

PVE SERIES POWER VENTER SYSTEM MANUAL PVE SERIES POWER VENTER SYSTEM MANUAL Contents Page I. Typical Venting System Components 2 II. System Operation 3 III. Power Venter Sizing 3,4 IV. Installation Safety Instructions 5,6 V. Installation of

More information

Fig. 1 - Unit PGD4, PGS4, WPG4

Fig. 1 - Unit PGD4, PGS4, WPG4 OWNER S MANUAL 14 SEER Single -Package Air Conditioner and Gas Furnace System with R -410A Refrigerant Single Phase 2 to 5 Nominal Tons Three Phase 3 to 5 Nominal Tons PGD4andPGS4SeriesE,WPG4SeriesB Fig.

More information

Classic 13 Heat Pumps High Efficiency Vertical Packaged Heat Pumps Models HVPA and HVPSA

Classic 13 Heat Pumps High Efficiency Vertical Packaged Heat Pumps Models HVPA and HVPSA Classic 13 Heat Pumps High Efficiency Vertical Packaged Heat Pumps Models HVPA24-30-36-42-49-60 and HVPSA36-42-49-60 General Description HIGH EFFICIENCY - The Marvair Classic 13 High Efficiency Series

More information

Your complete source of information on Venmar AVS air exchangers. Constructo: 1.0 / 1.5 / 2.0 Solo: 1.5 / 2.0 Duo: 1.2 / 1.4 / 1.9 HE: 1.3 / 1.8 / 2.

Your complete source of information on Venmar AVS air exchangers. Constructo: 1.0 / 1.5 / 2.0 Solo: 1.5 / 2.0 Duo: 1.2 / 1.4 / 1.9 HE: 1.3 / 1.8 / 2. RANGE HOODS ATTIC VENTILATORS AIR EXCHANGERS DELUXE RANGE HOODS For more than 25 years, Venmar Ventilation has been one of North America s leading manufacturers of innovative Indoor Air Quality products

More information

INSTALLATION & OPERATION MANUAL

INSTALLATION & OPERATION MANUAL CBFT SERIES CORRECTIONAL HEATED HOLDING CABINETS INSTALLATION & OPERATION MANUAL MODELS: CBFT CBFTHS ML-152028-0000Z ML-152029-0000Z VULCAN 3600 NORTH POINT BLVD. DIVISION OF ITW FOOD EQUIPMENT GROUP,

More information

EL195DFE SERIES GAS FURNACE WARNING

EL195DFE SERIES GAS FURNACE WARNING 2011 Lennox Industries Inc. Dallas, Texas, USA 506739 01 06/2011 EL195DFE SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result in serious injury,

More information

Tuning up ventilation systems

Tuning up ventilation systems MULTI-UNIT RESIDENTIAL BUILDINGS Tune-Ups for Energy and Water Efficiency This document is a tool to help reduce energy and water costs and improve comfort in a high-rise residential building through low-cost

More information

User s Information Manual

User s Information Manual 48TJD005-014 48TJE004-014 48TJF004-012 Single-Package Rooftop Heating/Cooling Units User s Information Manual NOTE TO INSTALLER This manual should be left with the equipment owner. FOR YOUR SAFETY Do not

More information

ENERVEX GSV GREASE FAN

ENERVEX GSV GREASE FAN ENERVEX GSV 200-450 GREASE FAN 3001391 12.16 Installation & Operating Manual READ AND SAVE THESE INSTRUCTIONS! ENERVEX Inc. 1685 Bluegrass Lakes Parkway Alpharetta, GA 30004 USA P: 770.587.3238 F: 770.587.4731

More information

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2012 Supersedes

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2012 Supersedes COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES 506956 01 2/2012 Supersedes 506167 01 Litho U.S.A. TAA ECONOMIZERS INSTALLATION INSTRUCTIONS FOR ECONOMIZERS (44W94, 44W95 AND 44W96) USED WITH TAA SERIES UNITS

More information

MANUAL 8/12/05. Model BKP TM 100 INSTALLATION, OPERATION & MAINTENANCE. Commercial High Efficiency Heat Pipe Dehumidifier

MANUAL 8/12/05. Model BKP TM 100 INSTALLATION, OPERATION & MAINTENANCE. Commercial High Efficiency Heat Pipe Dehumidifier MANUAL 8/12/05 INSTALLATION, OPERATION & MAINTENANCE Commercial High Efficiency Heat Pipe Dehumidifier Model BKP TM 100 Heat Pipe Technology, Inc. 6904 Parke East Blvd. Tampa FL 33610 Tel: (813) 470-4250

More information

Wax Base Heater & Dispenser

Wax Base Heater & Dispenser Wax Base Heater & Dispenser Service Manual Models: IDWB2/0900, IDWB2/0775, IDWB3/0900, IDWB3/0775, IDWB4/0900, IDWB4/0775 Introduction............................................................................

More information

installation and operation manual for Hunter Ceiling Fans

installation and operation manual for Hunter Ceiling Fans For Your Records and Warranty Assistance Model Name: Catalog/Model No.: Serial No.: Date Purchased: Where Purchased: For reference also attach your receipt or a copy of your receipt to the manual. installation

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: 1. Use this unit only in the manner intended by the manufacturer. If you

More information

Disposal Unit (BKSDU) Burger King Shortening. Operation, Service & Parts Manual BURGER KING BKSDU

Disposal Unit (BKSDU) Burger King Shortening. Operation, Service & Parts Manual BURGER KING BKSDU BURGER KING BKSDU Burger King Shortening Disposal Unit (BKSDU) Operation, Service & Parts Manual Frymaster, a member of the Commercial Food Equipment Service Association, recommends using CFESA Certified

More information

KHP Models. KHP Series. Heat Recovery Ventilator IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

KHP Models. KHP Series. Heat Recovery Ventilator IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT KHP Series Heat Recovery Ventilator IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT CAUTION - Before installation, careful consideration must be given to how this system will operate if connected

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2008 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CH33 Series Units EVAPORATOR COILS 505,264M (65484504) 05/08 Supersedes 10/07 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE

More information

VENTLESS EXHAUST HOOD OPERATORS MANUAL AND PARTS LIST REV. MAY 2016

VENTLESS EXHAUST HOOD OPERATORS MANUAL AND PARTS LIST REV. MAY 2016 VENTLESS EXHAUST HOOD OPERATORS MANUAL AND PARTS LIST REV. MAY 2016 HOODMART 172 REASER COURT ELYRIA, OH 44035 PHONE: (800)-715-1014 FAX: (800)-716-1214 1 THIS PAGE LEFT BLANK INTERNTIONALLY 2 LIMITED

More information

EL195UH SERIES GAS FURNACE WARNING

EL195UH SERIES GAS FURNACE WARNING 2010 Lennox Industries Inc. Dallas, Texas, USA 506597 01 11/2010 EL195UH SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result in serious injury,

More information

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11 SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual No.: 2100-479 Supersedes: NEW File: Volume

More information

UNDERCOUNTER REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

UNDERCOUNTER REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions UNDERCOUNTER REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions Please read this manual completely prior to installing and operating this equipment. This manual describes how

More information

CONVEYOR TOASTER MODEL QCS QCS Installation and Operation Instructions 2M-HG0657 Rev. D 6/13/05

CONVEYOR TOASTER MODEL QCS QCS Installation and Operation Instructions 2M-HG0657 Rev. D 6/13/05 CONVEYOR TOASTER MODEL QCS-2-800 QCS-3-1000 Installation and Operation Instructions 2M-HG0657 Rev. D 6/13/05 SAFETY SYMBOLS These symbols are intended to alert the user to the presence of important operating

More information

Trane CDQ Desiccant Dehumidification

Trane CDQ Desiccant Dehumidification Engineering Bulletin Trane CDQ Desiccant Dehumidification September 2004 CLCH-PRB020-EN Preface This engineering bulletin presents the Trane CDQ desiccant dehumidification system. It explains the features

More information

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- 8610 Production Avenue San Diego, California 92121 (858) 566-7465 Fax (858) 566-1943 WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- Thank you for choosing a BREEZAIRE cooling unit. We believe

More information

Central Air Conditioning System

Central Air Conditioning System Owner s Information Manual Central Air Conditioning System NOTE TO EQUIPMENT OWNER: For your convenience, please record the model and serial numbers of your new equipment in the spaces provided. This information,

More information