1 MCAC-UTSM Contents Part 1 General Information... 1 Part 2 Indoor Units... 7 Part 3 Outdoor Units Part 4 Installation Part 5 Control The specifications, designs, and information in this book are subject to change without notice for product improvement. Contents i

2

3 MCAC-UTSM General Information Part 1 General Information 1. Model Names of Indoor/Outdoor Units External Appearance Indoor Units Outdoor Units Nomenclature Features... 6 General Information 1

4 Model Names of Indoor/Outdoor Units 1. Model Names of Indoor/Outdoor Units MCAC-UTSM Outdoor unit model Power supply (V-ph-Hz) Compressor type Compressor brand Matched indoor units model MOU-12HN1 220~ ROTARY MIDEA-TOSHIBA MCA-12HRN1 MUB-12HRN1 MOUA-18HN1 220~ ROTARY MIDEA-TOSHIBA MCA-18HRN1 MUB-18HRN1 MOUA-24HN1 220~ ROTARY MIDEA-TOSHIBA MCC-24HRN1 MUB-24HRN1 MOU-30HN1 220~ SCROLL SANYO MCC-30HRN1 MUB-30HRN1 MOU-30HN1-R 380~ SCROLL SANYO MCC-30HRN1-R MUB-30HRN1 MOU-36HN1 220~ SCROLL SANYO MCC-36HRN1 MUB-36HRN1 MOU-36HN1-R 380~ SCROLL SANYO MCC-36HRN1-R MUB-36HRN1 MOUA-48HN1-R 380~ SCROLL DAIKIN MCC-48HRN1-R MUB-48HRN1-R MOUA-60HN1-R 380~ SCROLL SANYO MUB-60HRN1-R 2 General Information

5 MCAC-UTSM External Appearance 2. External Appearance 2.1 Indoor Units Four-way cassette type (compact) Four-way cassette type Ceiling & floor type Ceiling & floor type General Information 3

6 External Appearance MCAC-UTSM Outdoor Units 12,000Btu/h 18,000Btu/h 24,000Btu/h 30,000~36,000Btu/h 48,000Btu/h 60,000Btu/h 4 General Information

7 MCAC-UTSM Nomenclature 3.1 Indoor Unit M C C - 48 H R N1 - R Nomenclature Power Supply R 380~415V, 3N, 50Hz ~240V, 1N, 50Hz Refrigerant Type N1 R410A Control Mode W Wired Control R Remote Control Function Code C Cooling Only H Cooling & Heating Capacity ( 1000Btu/h) Product Series A Time A Designed C Time C Designed B Time B Designed Indoor Unit Type T Duct H High Static Pressure Duct C Cassette U Ceiling & Floor Midea 3.2 Outdoor Unit M O U A - 48 H N1 - R Power Supply R 380V~415V, 3N, 50Hz ~240V, 1N, 50Hz Refrigerant Type N1 R410A Function Code C Cooling Only H Cooling & Heating Capacity ( 1000Btu/h) Product Series A Time A Designed B Time B Designed Universal Outdoor Unit O Outdoor unit U Universal Midea General Information 5

8 Features MCAC-UTSM Features 1. High quality coils: The coil is constructed of advanced inner grooved copper tube and aluminum fins. 2. Anti-rust, 500 hours salt spray test. 3. Low operation sound level: Well-known stable and quiet running fan motor. 4. Well-known compressor. 5. Compact design: Smaller dimension and larger stuffing capacity. 6. Universal outdoor unit design. 7. Optional air outlet grille: plastic type and wire type. Metal grille Plastic type Plastic type 8. Optional low temperature cooling module. 9. R410A environment friendly refrigerant. 6 General Information

9 MCAC-UTSM Indoor Units Part 2 Indoor Units Four-way Cassette Type (Compact)... 8 Four-way Cassette Type Ceiling & Floor Type Indoor Units 7

10 Four-way Cassette Type (Compact) MCAC-UTSM Four-way Cassette Type (Compact) 1. Features Specifications Dimensions Service Space Wiring Diagram Air Velocity and Temperature Distributions Capacity Tables Electric Characteristics Sound Levels Exploded View Accessories The Specification of Power Field Wiring Indoor Units

11 MCAC-UTSM Features (1) Low operation noise ---Streamline plate ensures quietness ---Creates natural and comfortable environment Features (2) Efficient cooling ---Equal, fast and wide range cooling (3) The adoption of the most advanced 3-Dimensional Screw Fan ---Reduces the air resistance passing through ---Smoothes the air flow ---Makes air speed distribution to the heat exchange uniform (4) Improvement for easy installation and maintenance ---Little space is required for installation into a shallow ceiling ---Because of the compactness and weight reduction of the main unit and panel, all models can be installed without a hoist Indoor Units 9

12 Specifications MCAC-UTSM Specifications Model MCA-12HRN1 MCA-18HRN1 Code Power supply V-ph-Hz 220~ ~ Cooling Heating Indoor fan motor Indoor coil Capacity kw Input W Capacity kw 4 6 Input W Model YDK45-4F YDK45-4F Brand Welling Welling Input W 56.7/51.5/ /51.5/44.4 Capacitor uf 1.5uF/450V 2.5uF/450V Speed(Hi/Mi/Lo) r/min 930/845/ /845/680 Number of rows 2 2 Tube pitch(a) row pitch(b) mm Fin spacing mm Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Tube outside dia.and type mm φ7 Inner grooved copper tube φ7 Inner grooved copper tube Coil length height width mm Number of circuits 5 5 Indoor air flow (Hi/Mi/Lo) m 3 /h 680/600/ /760/500 Indoor noise level (sound pressure) db(a) 41/38/ /39.4/35.8 Indoor unit Dimension (W H D)(body) mm Packing (W H D)(body) mm Dimension (W H D)(panel) mm Packing (W H D)(panel) mm Net/Gross weight(body) kg 21/28 21/27 Net/Gross weight(panel) kg 3/5 3/5 Refrigerant type R410A R410A Design pressure MPa 4.4/ /2.6 Refrigerant piping Liquid side/ Gas side mm φ6.4/φ12.7 φ6.4/φ12.7 Drainage water pipe diameter mm ODφ25 ODφ25 Connection wiring Power wiring mm Strong electric signal wiring mm Weak electric signal wiring mm 2 1-core shield wire core shield wire Controller R11HG/E(standard) R11HG/E(standard) Operation temperature Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27 CDB, 19 CWB; Outdoor temp: 35 CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20 CDB; Outdoor temp: 7 CDB, 6 CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. 10 Indoor Units

13 MCAC-UTSM Dimensions Dimensions 4. Service Space Indoor Units 11

14 Wiring Diagram 5. Wiring Diagram MCAC-UTSM Indoor Units

15 MCAC-UTSM Air Velocity and Temperature Distributions Air Velocity and Temperature Distributions Airflow velocity Temperature Indoor Units 13

16 Capacity Tables MCAC-UTSM Capacity Tables 7.1 Cooling Capacity MCA-12HRN1 Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC TC /15ºC DB/WB SC Input /17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB MCA-18HRN1 Cooling TC SC Input TC SC Input TC SC Input Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC 21/15ºC DB/WB 24/17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB TC SC Input TC SC Input TC SC Input TC SC Input Indoor Units

17 MCAC-UTSM Capacity Tables 7.2 Heating Capacity MCA-12HRN1 Heating Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB TC ºC Input ºC 27ºC MCA-18HRN1 Heating TC Input TC Input Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB TC ºC Input ºC 27ºC Remark: TC: Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw TC Input TC Input Indoor Units 15

18 Electric Characteristics MCAC-UTSM Electric Characteristics Model Indoor Units Power Supply Indoor Fan Motor Hz Voltage Min. Max. MCA MFA kw FLA MCA-12HRN V 198V 254V MCA-18HRN V 198V 254V Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) KW: Fan Motor Rated Output (kw) FLA: Full Load Amps. (A) 9. Sound Levels FOUR-WAY CASSETTE TYPE 1.0m Microphone Model Noise level db(a) H M L MCA-12HRN MCA-18HRN Indoor Units

19 MCAC-UTSM Exploded View MCA-12HRN1 MCA-18HRN1 Exploded View 10.5 No. Part Name Quantity No. Part Name Quantity 1 Drainage pan ass'y 1 11 E-Part box cover 1 2 Centrifugal fan 1 12 Drain pump Holder 1 3 Installation bracket 4 13 Drain pump 1 4 Evaporator fixing hanger 1 14 Right clapboard ass'y 1 5 Motor 1 15 Partition board 1 6 Motor base 1 16 Evaporator fixing board ass'y 1 7 Base ass'y 1 17 Evaporator ass'y 1 8 Board 1 18 Evaporator temp. sensor ass'y 1 9 Sealed board ass'y 1 19 Room temp. sensor ass'y 1 10 E-part box ass'y 1 20 Remote controller Main controller ass'y 1 21 Remote controller holder Motor capacitor 1 22 Panel ass'y Wire joint, 7p Swing motor Wire joint Display board Transformer 1 Indoor Units 17

20 Accessories 11. Accessories Installation fittings MCAC-UTSM Name Shape Quantity 1. Expansible hook 4 2. Installation hook 4 3. Installation paper board 1 4. Out-let pipe sheath 1 Drainpipe Fittings 5. Out-let pipe clasp 1 6. Tightening band Drain joint 1 8. Remote controller 1 Remote controller & Its holder 9. Remote controller holder Mounting screw(st C-H) Alkaline dry batteries (AM4) 2 Others 12. Owner's manual Installation manual The Specification of Power Type MCA-12HRN1 MCA-18HRN1 Power Phase 1-phase 1-phase Frequency and Voltage V, 50Hz V, 50Hz Circuit Breaker/ Fuse (A) 40/25 40/25 Indoor Unit Power Wiring (mm 2 ) Indoor/Outdoor Connecting Wiring Outdoor Unit Power Wiring Strong Electric Signal Weak Electric Signal 1-core shield wire core shield wire Indoor Units

21 MCAC-UTSM Field Wiring Field Wiring MCA-12HRN1 Indoor Units 19

22 Field Wiring MCAC-UTSM MCA-18HRN1 20 Indoor Units

23 MCAC-UTSM Four-way Cassette Type Four-way Cassette Type 1. Features Specifications Dimensions Service Space Wiring Diagrams Air Velocity and Temperature Distributions Capacity Tables Electric Characteristics Sound Levels Exploded View Accessories The Specification of Power Field Wiring Indoor Units 21

24 Features 1. Features (1) Ultra thin machine body to easy installation and maintenance. 24K:230mm, 30-48K:300mm. MCAC-UTSM (2) Different color panels to choose: White, Gray, Blue, Black (3) The swing angle of the first louver are 40~42 degrees and the second louver are 37~38 degrees. (4) 4 speeds available, optional super high fan speed design, suitable for the large building over 3m high. (5) Adding digital tube displaying on the display board. LED can display the Error Code to make the malfunction checking easier. (6) Reserve spaces for air side-outlet, it is available to connect duct pipe hence Air supplying from the four sides to nearby small room. 22 Indoor Units

25 MCAC-UTSM Features (7) Stylish design is harmonious with any interior decoration and creates and elegant environment. (8) Built-in water pump with 750mm pumping head. (9) Fresh air makes life more healthy and comfortable. Indoor Units 23

26 Specifications MCAC-UTSM Specifications Model MCC-24HRN1 MCC-30HRN1 Code Power supply V-ph-Hz 220~ ~ Cooling Heating Indoor fan motor Indoor coil Capacity kw Input W Capacity kw Input W Model YDK80-6E YDK90-6E Brand Welling Welling Input W 120/110/100/90 165/143/116/100 Capacitor uf 3.5uF/450V 3.5uF/450V Speed(Hi/Mi/Lo) r/min 800/670/550/ /770/640/550 Number of rows 2 2 Tube pitch(a) row pitch(b) mm Fin spacing mm Fin type (code) Hydrophilic aluminum Hydrophilic aluminium Tube outside dia.and type mm φ7 Inner grooved copper tube φ7 Inner grooved copper tube Coil length height width mm Number of circuits Indoor air flow (Hi/Mi/Lo) m 3 /h 1220/1010/ /1296/1124 Indoor noise level (sound pressure) db(a) 48/44/40 50/46//42 Indoor unit Dimension (W H D)(body) mm Packing (W H D)(body) mm Dimension (W H D)(panel) mm Packing (W H D)(panel) mm Net/Gross weight(body) kg 29/36 35/42 Net/Gross weight(panel) kg 6/9 6/9 Refrigerant type R410A R410A Design pressure MPa 4.4/ /2.6 Refrigerant piping Liquid side/gas side mm φ9.5/φ15.9 φ12.7/φ19 Drainage water pipe diameter mm ODφ32 ODφ32 Connection wiring Power wiring mm Strong electric signal wiring mm Weak electric signal wiring mm 2 1-core shield wire core shield wire Controller R05/BGE(standard) R05/BGE(standard) Operation temperature Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27 CDB, 19 CWB; Outdoor temp: 35 CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20 CDB; Outdoor temp: 7 CDB, 6 CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. 24 Indoor Units

27 MCAC-UTSM Specifications Model MCC-30HRN1-R MCC-36HRN1 Code Power supply V-ph-Hz 380~ ~ Cooling Heating Indoor fan motor Indoor coil Capacity kw Input W Capacity kw Input W Model YDK90-6E YDK90-6E Brand Welling Welling Input W 165/143/116/ /143/116/100 Capacitor uf 3.5uF/450V 3.5uF/450V Speed(Hi/Mi/Lo) r/min 840/770/640/ /770/640/550 Number of rows 2 2 Tube pitch(a) row pitch(b) mm Fin spacing mm Fin type (code) Hydrophilic aluminum Hydrophilic aluminum Tube outside dia.and type mm φ7 Inner grooved copper tube φ7 Inner grooved copper tube Coil length height width mm Number of circuits Indoor air flow (Hi/Mi/Lo) m 3 /h 1538/1296/ /1296/1124 Indoor noise level (sound pressure) db(a) 50/46//42 50/46//42 Indoor unit Dimension (W H D)(body) mm Packing (W H D)(body) mm Dimension (W H D)(panel) mm Packing (W H D)(panel) mm Net/Gross weight(body) kg 35/42 35/42 Net/Gross weight(panel) kg 6/9 6/9 Refrigerant type R410A R410A Design pressure MPa 4.4/ /2.6 Refrigerant piping Liquid side/gas side mm φ12.7/φ19 φ12.7/φ19 Drainage water pipe diameter mm ODφ32 ODφ32 Connection wiring Power wiring mm Strong electric signal wiring mm Weak electric signal wiring mm 2 1-core shield wire Controller R05/BGE(standard) R05/BGE(standard) Operation temperature Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27 CDB, 19 CWB; Outdoor temp: 35 CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20 CDB; Outdoor temp: 7 CDB, 6 CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. Indoor Units 25

28 Specifications MCAC-UTSM Model MCC-36HRN1-R MCC-48HRN1-R Code Power supply V-ph-Hz 380~ ~ Cooling Heating Indoor fan motor Indoor coil Capacity kw Input W Capacity kw Input W Model YDK90-6E YDK90-6E Brand Welling Welling Input W 165/143/116/ /143/116/100 Capacitor uf 3.5uF/450V 3.5uF/450V Speed(Hi/Mi/Lo) r/min 840/770/640/ /770/640/550 Number of rows 2 2 Tube pitch(a) row pitch(b) mm Fin spacing mm Fin type (code) Hydrophilic aluminum Hydrophilic aluminum Tube outside dia.and type mm φ7 Inner grooved copper tube φ7 Inner grooved copper tube Coil length height width mm Number of circuits Indoor air flow (Hi/Mi/Lo) m 3 /h 1538/1296/ /1296/1124 Indoor noise level (sound pressure) db(a) 50/46//42 50/46//42 Indoor unit Dimension (W H D)(body) mm Packing (W H D)(body) mm Dimension (W H D)(panel) mm Packing (W H D)(panel) mm Net/Gross weight(body) kg 35/42 35/42 Net/Gross weight(panel) kg 6/9 6/9 Refrigerant type R410A R410A Design pressure MPa 4.4/ /2.6 Refrigerant piping Liquid side/gas side mm φ12.7/φ19 φ12.7/φ19 Drainage water pipe diameter mm ODφ32 ODφ32 Connection wiring Power wiring mm Strong electric signal wiring mm Weak electric signal wiring mm 2 Controller R05/BGE(standard) R05/BGE(standard) Operation temperature Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27 CDB, 19 CWB; Outdoor temp: 35 CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20 CDB; Outdoor temp: 7 CDB, 6 CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. 26 Indoor Units

29 MCAC-UTSM Dimensions 3.1 MCC-24HRN1 Dimensions 3.2 MCC-30HRN1 MCC-30HRN1-R MCC-36HRN1 MCC-36HRN1-R MCC-48HRN1-R Indoor Units 27

30 Service Space 4. Service Space The indoor unit should be installed in a location that meets the following requirements: There is enough room for installation and maintenance. The ceiling is horizontal, and its structure can endure the weight of the indoor unit. The outlet and the inlet are not impeded, and the influence of external air is the least. The air flow can reach throughout the room. The connecting pipe and drainpipe could be extracted out easily. There is no direct radiation from heaters. MCAC-UTSM Indoor Units

31 MCAC-UTSM Wiring Diagrams 5.1 MCC-24HRN1 MCC-30HRN1 MCC-36HRN1 Wiring Diagrams Indoor Units 29

32 Wiring Diagrams MCAC-UTSM MCC-30HRN1-R MCC-36HRN1-R MCC-48HRN1-R 30 Indoor Units

33 MCAC-UTSM Air Velocity and Temperature Distributions Air Velocity and Temperature Distributions Airflow velocity Temperature Indoor Units 31

34 Capacity Tables 7. Capacity Tables MCC-24HRN1 Cooling Cooling Outdoor conditions (DB) MCAC-UTSM Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC 21/15ºC DB/WB 24/17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB TC SC Input TC SC Input TC SC Input TC SC Input Heating Heating Indoor Conditions (DB) 15ºC 20ºC 27ºC Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw Outdoor conditions (kw) 24/18ºC 7/6ºC 2/1ºC -5/-6ºC DB/WB DB/WB DB/WB DB/WB TC Input TC Input TC Input Indoor Units

35 MCAC-UTSM Capacity Tables MCC-30HRN1 Cooling Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC TC /15ºC DB/WB SC /17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Input TC SC Input TC SC Input TC SC Input Heating Heating Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB TC ºC Input ºC TC Input TC ºC Input Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw Indoor Units 33

36 Capacity Tables MCAC-UTSM MCC-30HRN1-R Cooling Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC TC /15ºC DB/WB SC /17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Input TC SC Input TC SC Input TC SC Input Heating Heating Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB TC ºC Input ºC TC Input TC ºC Input Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw 34 Indoor Units

37 MCAC-UTSM Capacity Tables MCC-36HRN1 Cooling Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC TC /15ºC DB/WB SC /17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Input TC SC Input TC SC Input TC SC Input Heating Heating Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB TC ºC Input ºC TC Input TC ºC Input Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw Indoor Units 35

38 Capacity Tables MCAC-UTSM MCC-36HRN1-R Cooling Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC TC /15ºC DB/WB SC /17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Input TC SC Input TC SC Input TC SC Input Heating Heating Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB TC ºC Input ºC TC Input TC ºC Input Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw 36 Indoor Units

39 MCAC-UTSM Capacity Tables MCC-48HRN1-R Cooling Heating Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC 21/15ºC DB/WB 24/17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Heating TC SC Input TC SC Input TC SC Input TC SC Input Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB 15ºC 20ºC 27ºC Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw TC Input TC Input TC Input Indoor Units 37

40 Electric Characteristics MCAC-UTSM Electric Characteristics Model Indoor Units Power Supply Indoor Fan Motor Hz Voltage Min. Max. MCA MFA kw FLA MCC-24HRN V 198V 254V MCC-30HRN V 198V 254V MCC-30HRN1-R V 342V 418V MCC-36HRN V 198V 254V MCC-36HRN1-R V 342V 418V MCC-48HRN1-R V 342V 418V Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) KW: Fan Motor Rated Output (kw) FLA: Full Load Amps. (A) 9. Sound Levels FOUR-WAY CASSETTE TYPE 1.0m Microphone Model Noise level db(a) H M L MCC-24HRN MCC-30HRN1/MCC-30HRN1-R MCC-36HRN1/MCC-36HRN1-R MCC-48HRN1-R Indoor Units

41 MCAC-UTSM Exploded View 10.1 MCC-24HRN1 Exploded View 33 Indoor Units 39

42 Exploded View MCAC-UTSM No. Part Name Quantity No. Part Name Quantity 1 Electricity control box coping I 1 12 Motor 1 2 Electricity control box coping II 1 13 Base 1 3 E-part box ass'y 1 14 Wire clamp E-part box 1 15 Panel Transformer 1 16 Wire clamp Room temp. sensor ass'y 1 17 Wire clip Motor capacitor 1 18 Evaporator fixing hanger Main controller 1 19 Water pump board Wire joint 1 20 Drain pump Wire joint, 3p 1 21 Installation bracket ass'y 1 4 Air guide ring ass'y 1 22 Board ass'y 1 5 Foam ass'y 1 23 Water pipe clamp 1 6 Fan ass'y 1 24 Fan clip 1 7 Evaporator fixing board 1 25 Water cover ass'y 1 8 Evaporator ass'y 1 26 Board ass'y Evaporator Hook Evaporator output pipe ass'y 1 27 Water pipe Evaporator input pipe ass'y 1 28 Sealed board ass'y Sleeve 1 29 Pump rubber washer 3 9 Board ass'y 1 30 Remote controller Hook 2 31 Installation bracket 1 10 Foam ass'y 1 32 Evaporator temp. sensor 1 11 Board ass'y 1 33 Water-level sensor ass y 1 40 Indoor Units

43 MCAC-UTSM Exploded View 10.2 MCC-30HRN1 Indoor Units 41

44 Exploded View MCAC-UTSM No. Part Name Quantity No. Part Name Quantity 1 Electric control box head cover I 1 13 Base pan seat 1 2 Electric control box head cover II 1 14 Base pan welded assembly 1 3 Electric control box assembly of indoor unit 1 15 Plate, wire Electric control box welded assembly 1 16 Tandem, wire Voltage transformer 1 17 Bipitch wire clip Indoor temp. sensor subassembly 1 18 Evaporator fixing hook Capacitor 1 19 Water pump baffle plate Four sides air outlet indoor main control plate 1 20 Water drain pump subassembly 1 4 Air inducting coils subassembly 1 21 Water pump installation bracket subassembly 1 5 Foam subassembly,drip tray 1 22 Front barrier IV subassembly 1 6 Fan assembly 1 23 Water pump pumping pipe grommet 1 7 Evaporator fixing board 1 24 Fan fins 1 8 Evaporator assembly 1 25 Install lifting lug Evaporator 1 26 Water finder cover subassembly Evaporator output tube assembly 1 27 Front barrier III subassembly Evaporator filter assembly 1 28 Water pumping connect pipe Barrel 1 29 Exhalant tube seal plate subassembly 1 9 Front barrier I subassembly 1 30 Water pump's rubber pad 1 10 Foam seat subassembly 1 31 Remote controller 1 11 Front barrier II subassembly 1 32 Bracket, remote controller 1 12 Asynchronous dynamo 1 33 Front panel 1 42 Indoor Units

45 MCAC-UTSM Exploded View 10.3 MCC-30HRN1 -R Indoor Units 43

46 Exploded View MCAC-UTSM No. Part Name Quantity No. Part Name Quantity 1 Electric control box head cover I 1 13 Base pan seat 1 2 Electric control box head cover II 1 14 Base pan welded assembly 1 3 Electric control box assembly of indoor unit 1 15 Plate, wire Electric control box welded assembly 1 16 Tandem, wire Voltage transformer 1 17 Bipitch wire clip Indoor temp. sensor subassembly 1 18 Evaporator fixing hook Capacitor 1 19 Water pump baffle plate Four sides air outlet indoor main control plate 1 20 Water drain pump subassembly 1 4 Air inducting coils subassembly 1 21 Water pump installation bracket subassembly 1 5 Foam subassembly,drip tray 1 22 Front barrier IV subassembly 1 6 Fan assembly 1 23 Water pump pumping pipe grommet 1 7 Evaporator fixing board 1 24 Fan fins 1 8 Evaporator assembly 1 25 Install lifting lug Evaporator 1 26 Water finder cover subassembly Evaporator output tube assembly 1 27 Front barrier III subassembly Evaporator filter assembly 1 28 Water pumping connect pipe Barrel 1 29 Exhalant tube seal plate subassembly 1 9 Front barrier I subassembly 1 30 water pump's rubber pad 1 10 Foam seat subassembly 1 31 Remote controller 1 11 Front barrier II subassembly 1 32 Bracket, remote controller 1 12 Asynchronous dynamo 1 33 Front panel 1 44 Indoor Units

47 MCAC-UTSM Exploded View 10.4 MCC-36HRN1 Indoor Units 45

48 Exploded View MCAC-UTSM No. Part Name Quantity No. Part Name Quantity 1 Electric control box head cover I 1 13 Base pan seat 1 2 Electric control box head cover II 1 14 Base pan welded assembly 1 3 Electric control box assembly of indoor unit 1 15 Plate, wire Electric control box welded assembly 1 16 Tandem, wire Voltage transformer 1 17 Bipitch wire clip Indoor temp. sensor subassembly 1 18 Evaporator fixing hook Capacitor 1 19 Water pump baffle plate Four sides air outlet indoor main control plate 1 20 Water drain pump subassembly 1 4 Air inducting coils subassembly 1 21 Water pump installation bracket subassembly 1 5 Foam subassembly,drip tray 1 22 Front barrier IV subassembly 1 6 Fan assembly 1 23 Water pump pumping pipe grommet 1 7 Evaporator fixing board 1 24 fan fins 1 8 Evaporator assembly 1 25 Install lifting lug Evaporator 1 26 Water finder cover subassembly Evaporator output tube assembly 1 27 Front barrier III subassembly Evaporator filter assembly 1 28 Water pumping connect pipe Barrel 1 29 Exhalant tube seal plate subassembly 1 9 Front barrier I subassembly 1 30 Water pump's rubber pad 1 10 Foam seat subassembly 1 31 Remote controller 1 11 Front barrier II subassembly 1 32 Bracket, remote controller 1 12 Asynchronous dynamo 1 33 Front panel 1 46 Indoor Units

49 MCAC-UTSM Exploded View 10.5 MCC-36HRN1-R Indoor Units 47

50 Exploded View MCAC-UTSM No. Part Name Quantity No. Part Name Quantity 1 Electric control box head cover I 1 13 Base pan seat 1 2 Electric control box head cover II 1 14 Base pan welded assembly 1 3 Electric control box assembly of indoor unit 1 15 Plate, wire Electric control box welded assembly 1 16 Tandem, wire Voltage transformer 1 17 Bipitch wire clip Indoor temp. sensor subassembly 1 18 Evaporator fixing hook Capacitor 1 19 Water pump baffle plate Four sides air outlet indoor main control plate 1 20 Water drain pump subassembly 1 4 Air inducting coils subassembly 1 21 Water pump installation bracket subassembly 1 5 Foam subassembly,drip tray 1 22 Front barrier IV subassembly 1 6 Fan assembly 1 23 Water pump pumping pipe grommet 1 7 Evaporator fixing board 1 24 Fan fins 1 8 Evaporator assembly 1 25 Install lifting lug Evaporator 1 26 Water finder cover subassembly Evaporator output tube assembly 1 27 Front barrier III subassembly Evaporator filter assembly 1 28 Water pumping connect pipe Barrel 1 29 Exhalant tube seal plate subassembly 1 9 Front barrier I subassembly 1 30 Water pump's rubber pad 1 10 Foam seat subassembly 1 31 Remote controller 1 11 Front barrier II subassembly 1 32 Bracket, remote controller 1 12 Asynchronous dynamo 1 33 Front panel 1 48 Indoor Units

51 MCAC-UTSM Exploded View 10.6 MCC-48HRN1-R 3/3.2/3.3/3.4/3.5/3.6/ Indoor Units 49

52 Exploded View MCAC-UTSM No. Part Name Quantity No. Part Name Quantity 1 Electricity control box coping I 1 13 Chassis pillow 1 2 Electricity control box coping II 1 14 Chassis Ass'y 1 3 Electric control assy subassembly 1 15 Plate, wire E-part box 1 16 Panel Transformer 1 17 Plate, wire Indoor temp. sensor subassembly 1 18 Bipitch wire clip Motor capacitor 1 19 Fixing hanger, evaporator Main controller subassembly 1 20 Water pump baffle Wire joint, 6p 1 21 Drain pump Wire joint, 6p 1 22 Water Pump installation subassembly 1 4 Guide wind circle subassembiy 1 23 Boarding subassembly Ⅳ 1 5 Foam subassembly,drip tray 1 24 Water pipe clamp 1 6 Wind wheel assembly 1 25 Clip, wind wheel 1 7 Fixing board, Evaporator 1 26 water finder cover subassembly 1 8 Evaporator assembly 1 27 Boarding subassembly Ⅲ Evaporator Installation hanger Gas output pipe, evaporator, assembly 1 28 Extended water pipe Eva filter, assmy assembly 1 29 Sealing board for pipe tie-in subassembly Sleeve 1 30 Rubber washer, pump 1 9 Boarding subassembly I 1 31 Remote controller Installation hanger 2 32 Holder 1 10 Foam subassembly, Base 1 33 Evaporator temp. sensor 1 11 boarding subassembly II 1 34 Water-level sensor ass y 1 12 Asynchronism motor 1 50 Indoor Units

53 MCAC-UTSM Accessories Installation Fittings Tubing & Fittings Drainpipe Fittings Protect Pipe Fittings Accessories Name Shape Quantity 1. Expansible hook 4 2. Installation hook 4 3. Installation paper board 1 4. Bolt M Connecting pipe group 1 6. Binding tape 6 7.Soundproof/insulation sheath 2 8. Out-let pipe sheath 1 9. Out-let pipe clasp Tightening band Drain joint Seal ring Wall conduit Wall conduit cover Remote controller 1 Remote controller & Its Frame Others 16. Frame Mounting screw(st C-H) Alkaline dry batteries (AM4) Owner's manual Installation manual The Specification of Power Type MCC-24HRN1 MCC-30HRN1 MCC-30HRN1-R Phase 1-phase 1-phase 3-phase Power Frequency and Voltage V, 50Hz V, 50Hz V, 50Hz Circuit Breaker/ Fuse (A) 40/25 40/25 25/15 Indoor Unit Power Wiring (mm 2 ) Ground Wiring Outdoor Unit Power Wiring Strong Electric Signal Indoor/Outdoor Connecting Wiring (mm 2 ) Weak Electric Signal 1-core shield wire core shield wire Type MCC-36HRN1 MCC-36HRN1-R MCC-48HRN1-R Power Phase 1-phase 3-phase 3-phase Frequency and Voltage V, 50Hz V, 50Hz V, 50Hz Circuit Breaker/ Fuse (A) 40/25 25/15 25/15 Indoor Unit Power Wiring (mm 2 ) Outdoor Unit Power Indoor/Outdoor Connecting Wiring Wiring (mm 2 ) Strong Electric Signal Weak Electric Signal 1-core shield wire Indoor Units 51

54 Field Wiring 13. Field Wiring MCAC-UTSM Indoor Units

55 MCAC-UTSM Ceiling & Floor Type Ceiling & Floor Type 1. Features Specifications Dimensions Service Space Wiring Diagrams Air Velocity and Temperature Distributions Capacity Tables Electric Characteristics Sound Levels Exploded View Accessories The Specification of Power Field Wiring Indoor Units 53

56 Features MCAC-UTSM Features 1.1. New design, more modern and elegant appearance Convenient installation --The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrow --It is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as one lighting 1.3. Two direction auto swing (vertical & horizontal) and wide angle air flow --Air flow directional control minimizes the air resistance and produces wilder air flow to vertical direction. --The range of horizontal air discharge is widened which secures wider air flow distribution to provide more comfortable air circulation no matter where the unit is set up 1.4. Three level fan speed, more humanism design, meets different air-supply requirement Water proof by utilizing the absorbing plastic film on water collector Easy operation. Auto-restart function, remote control and optional wire control method Low noise level plus compact size --Shape of the blades has been improved to prevent noise caused by turbulence. 54 Indoor Units

57 MCAC-UTSM Specifications 2. Specifications Model MUB-12HRN1 MUB-18HRN1 Code Power supply V-ph-Hz 220~ ~ Cooling Heating Indoor fan motor Capacity kw Input W Capacity kw 4 6 Input W Model YSK25-6L YSK55-4L Brand Welling Welling Input W 33.4/31.1/ /105/85 Capacitor uf 1.2uF/450V 2.5uF/450V Indoor coil Speed(Hi/Mi/Lo) r/min 756/666/ /1190/1040 Number of rows 2 3 Tube pitch(a) row pitch(b) mm Fin spacing mm Fin type (code) Hydrophilic aluminum Hydrophilic aluminium Tube outside dia.and type mm φ9.53 Inner grooved copper tube φ9.53 Inner grooved copper Coil length height width mm Number of circuits 3 3 Indoor air flow(hi/mi/lo) m 3 /h 600/480/ /792/700 Indoor noise level (sound pressure) db(a) 43/41/38 43/41/38 Indoor unit Dimension (W H D) mm Packing (W H D) mm Net/Gross weight kg 27/33 27/33 Refrigerant type R410A R410A Design pressure MPa 4.4/ /2.6 Refrigerant piping Liquid side/gas side mm φ6.4/φ12.7 φ6.4/φ12.7 Drainage water pipe diameter mm ODφ25 ODφ25 Connection wiring Power wiring mm Strong electric signal wiring tube mm Weak electric signal wiring mm 2 1-core shield wire core shield wire Controller R05/BGE(standard) R05/BGE(standard) Operation temperature Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27 CDB, 19 CWB; Outdoor temp: 35 CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20 CDB; Outdoor temp: 7 CDB, 6 CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. Indoor Units 55

58 Specifications MCAC-UTSM Model MUB-24HRN1 MUB-30HRN1 Code Power supply V-ph-Hz 220~ ~ Cooling Heating Indoor fan motor Capacity kw Input W Capacity kw Input W Model YSK55-4L YSK80-4A Brand Welling Welling Input W 125/105/85 143/122/110 Capacitor uf 2.5uF/450V 3.5uF/450V Indoor coil Speed(Hi/Mi/Lo) r/min 1310/1190/ /1210/1115 Number of rows 3 3 Tube pitch(a) row pitch(b) mm Fin spacing mm Fin type (code) Hydrophilic aluminium Hydrophilic aluminum Tube outside dia.and type mm φ9.53 Inner grooved copper tube φ9.53 Inner grooved copper Coil length height width mm Number of circuits 3 5 Indoor air flow(hi/mi/lo) m 3 /h 1200/900/ /1200/1000 Indoor noise level (sound pressure) db(a) 45/43/40 45/43/40 Indoor unit Dimension (W H D) mm Packing (W H D) mm Net/Gross weight kg 27/33 35/40 Refrigerant type R410A R410A Design pressure MPa 4.4/ /2.6 Refrigerant piping Liquid side/gas side mm φ9.5/φ15.9 φ12.7/φ19 Drainage water pipe diameter mm ODφ25 ODφ25 Connection wiring Power wiring mm Strong electric signal wiring tube mm Weak electric signal wiring mm 2 1-core shield wire core shield wire Controller R05/BGE(standard) R05/BGE(standard) Operation temperature Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27 CDB, 19 CWB; Outdoor temp: 35 CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20 CDB; Outdoor temp: 7 CDB, 6 CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. 56 Indoor Units

59 MCAC-UTSM Specifications Model MUB-30HRN1 MUB-36HRN1 Code Power supply V-ph-Hz 380~ ~ Cooling Heating Capacity kw Input W Capacity kw Input W Model YSK80-4A YSK80-4A Brand Welling Welling Indoor fan motor Indoor coil Input W 143/122/ /122/110 Capacitor uf 3.5uF/450V 3.5uF/450V Speed(Hi/Mi/Lo) r/min 1310/1210/ /1210/1115 Number of rows 3 3 Tube pitch(a) row pitch(b) mm Fin spacing mm Fin type (code) Hydrophilic aluminum Hydrophilic aluminum Tube outside dia.and type mm φ9.53 Inner grooved copper φ9.53 Inner grooved copper tube tube Coil length height width mm Number of circuits 5 5 Indoor air flow(hi/mi/lo) m 3 /h 1400/1200/ /1200/1000 Indoor noise level (sound pressure) db(a) 45/43/40 45/43/40 Indoor unit Dimension (W H D) mm Packing (W H D) mm Net/Gross weight kg 35/40 35/40 Refrigerant type R410A R410A Design pressure MPa 4.4/ /2.6 Refrigerant piping Liquid side/gas side mm φ12.7/φ19 φ12.7/φ19 Drainage water pipe diameter mm ODφ25 ODφ25 Connection wiring Power wiring mm Strong electric signal wiring mm Weak electric signal wiring mm 2 1-core shield wire Controller R05/BGE(standard) R05/BGE(standard) Operation temperature Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27 CDB, 19 CWB; Outdoor temp: 35 CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20 CDB; Outdoor temp: 7 CDB, 6 CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. Indoor Units 57

60 Specifications MCAC-UTSM Model MUB-36HRN1 MUB-48HRN1-R MUB-60HRN1-R Code Power supply V-ph-Hz 380~ ~ ~ Cooling Heating Capacity kw Input W Capacity kw Input W Model YSK80-4A YSK59-4D( 2) YSK59-4D( 2) Indoor fan motor Indoor coil Brand Welling Welling Welling Input W 143/122/ /81.5/ /81.5/77.5 Capacitor uf 3.5uF/450V 2.5uF/450V 2.5uF/450V Speed(Hi/Mi/Lo) r/min 1310/1210/ /1070/ /1070/995 Number of rows Tube pitch(a) row pitch(b) mm Fin spacing mm Fin type (code) Hydrophilic aluminum Hydrophilic aluminium Hydrophilic aluminium Tube outside dia.and φ9.53 Inner grooved φ9.53 Inner grooved φ9.53 Inner grooved mm type copper tube copper tube copper tube Coil length height width mm Number of circuits Indoor air flow(hi/mi/lo) m 3 /h 1400/1200/ /1985/ /2085/1736 Indoor noise level (sound pressure) db(a) 45/43/40 47/45/42 49/47/44 Indoor unit Dimension (W H D) mm Packing (W H D) mm Net/Gross weight kg 35/40 52/59 52/59 Refrigerant type R410A R410A R410A Design pressure MPa 4.4/ / /2.6 Refrigerant piping Liquid side/gas side mm φ12.7/φ19 φ12.7/φ19 φ12.7/φ19 Drainage water pipe diameter mm ODφ25 ODφ25 ODφ25 Connection wiring Power wiring mm Strong electric signal wiring Weak electric signal wiring mm mm 2 Controller R05/BGE(standard) R05/BGE(standard) R05/BGE(standard) Operation temperature Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27 CDB, 19 CWB; Outdoor temp: 35 CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20 CDB; Outdoor temp: 7 CDB, 6 CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. 58 Indoor Units

61 MCAC-UTSM Dimensions 3. Dimensions a. Wall mounting installation b. Ceiling installation Capacity (Btu/h) A B C D E F G Note: The dimension of 12000Btu/h, 18000Btu/h and 24000Btu/h are the same. The dimension of 30000Btu/h and 36000Btu/h are the same. The dimension of 48000Btu/h and 60000Btu/h are the same. Indoor Units 59

62 Service Space MCAC-UTSM Service Space 60 Indoor Units

63 MCAC-UTSM Wiring Diagrams 5. Wiring Diagrams 5.1 MUB-12HRN1 MUB-18HRN1 Indoor Units 61

64 Wiring Diagrams MCAC-UTSM MUB-24HRN1 MUB-30HRN1(1 phase) MUB-36HRN1(1 phase) 62 Indoor Units

65 MCAC-UTSM Wiring Diagrams 5.3 MUB-30HRN1(3 phase) MUB-36HRN1(3 phase) Indoor Units 63

66 Wiring Diagrams MCAC-UTSM MUB-48HRN1-R MUB-60HRN1-R 64 Indoor Units

67 MCAC-UTSM Air Velocity and Temperature Distributions 6. Air Velocity and Temperature Distributions Discharge angle 60 (CEILING) Airflow velocity Temperature Indoor Units 65

68 Air Velocity and Temperature Distributions MCAC-UTSM Discharge angle 60 (FLOOR) Temperature Airflow velocity 66 Indoor Units

69 MCAC-UTSM Capacity Tables 7. Capacity Tables MUB-12HRN1 Cooling Heating Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC 21/15ºC DB/WB 24/17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Heating TC SC Input TC SC Input TC SC Input TC SC Input Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB 15ºC 20ºC 27ºC Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw TC Input TC Input TC Input Indoor Units 67

70 Capacity Tables MCAC-UTSM MUB-18HRN1 Cooling Heating Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC 21/15ºC DB/WB 24/17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Heating TC SC Input TC SC Input TC SC Input TC SC Input Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB 15ºC 20ºC 27ºC Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw TC Input TC Input TC Input Indoor Units

71 MCAC-UTSM Capacity Tables MUB-24HRN1 Cooling Heating Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC 21/15ºC DB/WB 24/17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Heating TC SC Input TC SC Input TC SC Input TC SC Input Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB 15ºC 20ºC 27ºC Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw TC Input TC Input TC Input Indoor Units 69

72 Capacity Tables MCAC-UTSM MUB-30HRN1 (1 phase) Cooling Heating Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC 21/15ºC DB/WB 24/17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Heating TC SC Input TC SC Input TC SC Input TC SC Input Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB 15ºC 20ºC 27ºC Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw TC Input TC Input TC Input Indoor Units

73 MCAC-UTSM Capacity Tables MUB-30HRN1 (3 phase) Cooling Heating Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC 21/15ºC DB/WB 24/17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Heating TC SC Input TC SC Input TC SC Input TC SC Input Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB 15ºC 20ºC 27ºC Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw TC Input TC Input TC Input Indoor Units 71

74 Capacity Tables MCAC-UTSM MUB-36HRN1 (1 phase) Cooling Heating Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC 21/15ºC DB/WB 24/17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Heating TC SC Input TC SC Input TC SC Input TC SC Input Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB 15ºC 20ºC 27ºC Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw TC Input TC Input TC Input Indoor Units

75 MCAC-UTSM Capacity Tables MUB-36HRN1 (3 phase) Cooling Heating Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC 21/15ºC DB/WB 24/17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Heating TC SC Input TC SC Input TC SC Input TC SC Input Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB 15ºC 20ºC 27ºC Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw TC Input TC Input TC Input Indoor Units 73

76 Capacity Tables MCAC-UTSM MUB-48HRN1-R Cooling Heating Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC 21/15ºC DB/WB 24/17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Heating TC SC Input TC SC Input TC SC Input TC SC Input Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB 15ºC 20ºC 27ºC Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw TC Input TC Input TC Input Indoor Units

77 MCAC-UTSM Capacity Tables MUB-60HRN1-R Cooling Heating Cooling Outdoor conditions (DB) Indoor Conditions (kw) 21ºC 28ºC 35ºC 43ºC 21/15ºC DB/WB 24/17ºC DB/WB 27/19ºC DB/WB 32/23ºC DB/WB Heating TC SC Input TC SC Input TC SC Input TC SC Input Outdoor conditions Indoor Conditions (DB) (kw) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB 15ºC 20ºC 27ºC Remark: TC : Total capacity ; kw SC: Sensible heat capacity ; kw Input: Input power ; kw TC Input TC Input TC Input Indoor Units 75

78 Electric Characteristics MCAC-UTSM Electric Characteristics Model Indoor Units Power Supply Indoor Fan Motor Hz Voltage Min. Max. MCA MFA kw FLA MUB-12HRN V 198V 254V MUB-18HRN V 198V 254V MUB-24HRN V 198V 254V MUB-30HRN V 198V 254V MUB-30HRN V 342V 418V MUB-36HRN V 198V 254V MUB-36HRN V 342V 418V MUB-48HRN1-R V 342V 418V ( 2) MUB-60HRN1-R V 342V 418V ( 2) Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) KW: Fan Motor Rated Output (kw) FLA: Full Load Amps. (A) 9. Sound Levels Ceiling Floor Model Noise level H M L MUB-12HRN MUB-18HRN MUB-24HRN MUB-30HRN1 (1 phase) MUB-30HRN1 (3 phase) MUB-36HRN1 (1 phase) MUB-36HRN1 (3 phase) MUB-48HRN1-R MUB-60HRN1-R Indoor Units

79 MCAC-UTSM Exploded View 10. Exploded View 10.1 MUB-12HRN1 No. Part Name Quantity No. Part Name Quantity 1 Filter 2 20 Evaporator ass'y 1 2 Grille clamp 2 21 Installation board 1 3 Grille 1 22 Foam ass'y 1 4 Grille clamp 2 23 Foam ass'y 1 5 Grille strengthening rib 1 24 Evaporator Left support 1 6 Volute shell 2 25 Foam ass'y 1 7 Grille lock 1 26 Support board 1 8 Plastic fan 2 27 Evaporator right clapboard 1 9 Motor clamp 1 28 Evaporator left clapboard 1 10 Motor clamp 1 29 Cover 1 11 Volute shell 2 30 Display panel box 1 12 Board 1 31 Display board ass'y 1 13 Middle beam 1 32 Manual button 1 14 E-part box cover 1 33 Air outlet ass'y 1 15 E-part box ass'y 1 34 Foam Main controller ass'y 1 35 Drainage pan holder Motor capacitor 1 36 Drainage pan ass'y Wire joint 1 37 Plastic cover Wire joint 1 38 Motor Transformer 1 39 Panel ass'y 1 16 Left cover 1 40 Remote controller 1 17 Installation board 1 41 Installation bracket 1 18 Base ass'y 1 42 Room temp sensor ass'y 1 19 Rear cover 1 43 Temp.sensor ass'y 1 Indoor Units 77

80 Exploded View MCAC-UTSM MUB-18HRN1 No. Part Name Quantity No. Part Name Quantity 1 Filter 2 20 Evaporator ass'y 1 2 Grille clamp 2 21 Installation board 1 3 Grille 1 22 Foam ass'y 1 4 Grille hang 2 23 Foam ass'y 1 5 Grille strengthening rib 1 24 Evaporator Left support 1 6 Volute shell 2 25 Foam ass'y 1 7 Grille lock 1 26 Support board 1 8 Plastic fan 2 27 Evaporator right clapboard 1 9 Motor clamp 1 28 Evaporator left clapboard 1 10 Motor clamp 1 29 Cover 1 11 Volute shell 2 30 Display panel box 1 12 Board 1 31 Display board ass'y 1 13 Middle beam 1 32 Manual button 1 14 E-part box cover 1 33 Air outlet frame mount ass'y 1 15 E-part box ass'y 1 34 Foam Main controller ass'y 1 35 Drainage pan holder Motor capacitor 1 36 Drainage pan ass'y Wire joint 1 37 Plastic cover Wire joint 1 38 Motor Transformer 1 39 Panel ass'y 1 16 Left cover 1 40 Remote controller 1 17 Installation board 1 41 Installation bracket 1 18 Base ass'y 1 42 Room temp. sensor ass'y 1 19 Rear cover 1 43 Evaporator temp. sensor ass'y 1 78 Indoor Units

81 MCAC-UTSM Exploded View 10.3 MUB-24HRN1 No. Part Name Quantity No. Part Name Quantity 1 Filter 2 20 Evaporator ass'y 1 2 Grille clamp 2 21 Installation board 1 3 Grille 1 22 Foam ass'y 1 4 Grille hang 2 23 Foam ass'y 1 5 Grille strengthening rib 1 24 Evaporator Left support 1 6 Volute shell 2 25 Foam ass'y 1 7 Grille lock 1 26 Support board 1 8 Plastic fan 2 27 Evaporator right clapboard 1 9 Motor clamp 1 28 Evaporator left clapboard 1 10 Motor clamp 1 29 Cover 1 11 Volute shell 2 30 Display panel box 1 12 Board 1 31 Display board ass'y 1 13 Middle beam 1 32 Manual button 1 14 E-part box cover 1 33 Air outlet frame mount ass'y 1 15 E-part box ass'y 1 34 Foam Main controller ass'y 1 35 Drainage pan holder Motor capacitor 1 36 Drainage pan ass'y Wire joint 1 37 Plastic cover Wire joint 1 38 Motor Transformer 1 39 Panel ass'y 1 16 Left cover 1 40 Remote controller 1 17 Installation board 1 41 Installation bracket 1 18 Base ass'y 1 42 Room temp. sensor ass'y 1 19 Rear cover 1 43 Evaporator temp. sensor ass'y 1 Indoor Units 79

82 Exploded View MCAC-UTSM MUB-30HRN1 MUB-36HRN1(1 phase) No. Part Name Quantity No. Part Name Quantity 1 Filter 3 20 Evaporator ass'y 1 2 Grille clamp 2 21 Installation board 1 3 Grille 1 22 Foam ass'y 1 4 Grille clamp 2 23 Foam ass'y 1 5 Grille strengthening rib 1 24 Evaporator Left support 1 6 Volute shell 3 25 Foam ass'y 1 7 Grille lock 2 26 Support board 1 8 Plastic fan 3 27 Evaporator right clapboard 1 9 Motor clamp 1 28 Evaporator left clapboard 1 10 Motor clamp 1 29 Cover 1 11 Volute shell 3 30 Display panel box 1 12 Board 1 31 Display board ass'y 1 13 Middle beam 1 32 Manual button 1 14 E-part box cover 1 33 Air outlet ass'y 1 15 E-part box ass'y 1 34 Foam Main controller ass'y 1 35 Drainage pan holder Motor capacitor 1 36 Drainage pan ass'y Wire joint 1 37 Plastic cover Wire joint 1 38 Motor Transformer 1 39 Panel ass'y 1 16 Left cover 1 40 Remote controller 1 17 Installation board 1 41 Installation bracket 1 18 Base ass'y 1 42 Room temp sensor ass'y 1 19 Rear cover 1 43 Temp.sensor ass'y 1 80 Indoor Units

83 MCAC-UTSM Exploded View 10.5 MUB-30HRN1 MUB-36HRN1(3 phase) No. Part Name Quantity No. Part Name Quantity 1 Filter 3 20 Evaporator ass'y 1 2 Grille clamp 2 21 Installation board 1 3 Grille 1 22 Foam ass'y 1 4 Grille clamp 2 23 Foam ass'y 1 5 Grille strengthening rib 1 24 Evaporator Left support 1 6 Volute shell 3 25 Foam ass'y 1 7 Grille lock 2 26 Support board 1 8 Plastic fan 3 27 Evaporator right clapboard 1 9 Motor clamp 1 28 Evaporator left clapboard 1 10 Motor clamp 1 29 Cover 1 11 Volute shell 3 30 Display panel box 1 12 Board 1 31 Display board ass'y 1 13 Middle beam 1 32 Manual button 1 14 E-part box cover 1 33 Air outlet ass'y 1 15 E-part box ass'y 1 34 Foam Main controller ass'y 1 35 Drainage pan holder Motor capacitor 1 36 Drainage pan ass'y Wire joint 1 37 Plastic cover Wire joint 1 38 Motor Transformer 1 39 Panel ass'y 1 16 Left cover 1 40 Remote controller 1 17 Installation board 1 41 Installation bracket 1 18 Base ass'y 1 42 Room temp sensor ass'y 1 19 Rear cover 1 43 Temp.sensor ass'y 1 Indoor Units 81

84 Exploded View MCAC-UTSM MUB-48HRN1-R 31.1 No. Part Name Quantity No. Part Name Quantity 1 Grille ass'y 2 21 Volute shell 4 2 Motor clamp 2 22 Middle beam 1 3 Motor clamp 2 23 E-part box cover 1 4 Filter bracket 2 24 E-part box ass'y 1 5 Installation board Main controller ass'y 1 6 Installation board Motor capacitor 2 7 Filter bracket Wire joint 1 8 Right sealed board Wire joint 1 9 left sealed board Transformer 1 10 Pipe clamp board 1 25 Foam 2 11 Cover 1 26 Top cover ass'y 1 12 Left cover 1 27 Drainage pan ass'y 1 13 Display board ass'y 1 28 Plastic cover 1 14 Display installation box 1 29 Foam 2 15 Air outlet ass'y 1 30 Filter Display board ass'y 1 31 Evaporator ass'y 1 16 Base ass'y Temp. sensor ass'y 1 17 Plastic fan 4 32 Remote controller 1 18 Volute shell 4 33 Installation bracket 1 19 Motor 2 34 Room temp. sensor ass'y 1 20 Motor bracket 2 82 Indoor Units

85 MCAC-UTSM Exploded View 10.7 MUB-60HRN1-R No. Part Name Quantity No. Part Name Quantity 1 Grille ass'y 2 21 Volute shell 4 2 Motor clamp 2 22 Middle beam 1 3 Motor clamp 2 23 E-part box cover 1 4 Filter bracket 2 24 E-part box ass'y 1 5 Installation board Main controller ass'y 1 6 Installation board Motor capacitor 2 7 Filter bracket Wire joint 1 8 Right sealed board Wire joint 1 9 Left sealed board Transformer 1 10 Pipe clamp board 1 25 Foam 2 11 Cover 1 26 Top cover ass'y 1 12 Left cover 1 27 Drainage pan ass'y 1 13 Display board ass'y 1 28 Plastic cover 1 14 Display installation box 1 29 Foam 2 15 Air outlet frame ass'y 1 30 Filter Display board ass'y 1 31 Evaporator ass'y 1 16 Base ass'y Temp. sensor ass'y 1 17 Plastic fan 4 32 Remote controller 1 18 Volute shell 4 33 Installation bracket 1 19 Motor 2 34 Room temp. sensor ass'y 1 20 Motor bracket 2 Indoor Units 83

86 Accessories MCAC-UTSM Accessories Name Shape Quantity Installation fittings 1.Hook 2 2.Hanging arm 2 3. Remote controller 1 Remote controller & Its Holder 4. Remote controller holder 1 5. Mounting screw(st C-H) 2 6. Alkaline dry batteries (AM4) 2 Others 7. Owner's manual 1 8. Installation manual 1 9. Remote controller manual The Specification of Power Power Type Btu/h Btu/ h Btu/ h Phase 1-phase 1-phase 3-phase Frequency and Voltage V, 50Hz V, 50Hz V, 50Hz Circuit Breaker/ Fuse (A) 20/16 40/25 40/20 Indoor Unit Power Wiring (mm 2 ) Indoor/Outdoor Connecting Wiring (mm 2 ) Ground Wiring Outdoor Unit Power Wiring Strong Electric Signal core shield wire 1-core shield wire Weak Electric Signal mm mm 2 84 Indoor Units

87 MCAC-UTSM Field Wiring 13. Field Wiring MUB-12HRN1 MUB-18HRN1 Indoor Units 85

88 Field Wiring MCAC-UTSM MUB-24HRN1 MUB-30HRN1 MUB-36HRN1(1 phase) 86 Indoor Units

89 MCAC-UTSM Field Wiring MUB-30HRN1 MUB-36HRN1(3 phase) MUB-48HRN1-R MUB-60HRN1-R Indoor Units 87

90 Outdoor Units MCAC-UTSM Part 3 Outdoor Units 1. Specifications Dimensions Service Space Piping Diagrams Wiring Diagrams Electric Characteristics Operation Limits Sound Levels Exploded View Troubleshooting Outdoor Units

91 MCAC-UTSM Specifications 1. Specifications Model MOU-12HN1 MOUA-18HN1 Code Power supply V-ph-Hz 220~ ~ Max. input consumption W Max. input current A Starting current A Compressor Outdoor fan motor Outdoor coil Model PA140X2C-4FT PA225X2CS-4KU1 Type ROTARY ROTARY Brand MIDEA-TOSHIBA MIDEA-TOSHIBA Supplier MIDEA-TOSHIBA MIDEA-TOSHIBA Capacity Btu/h Input W Rated current(rla) A Locked rotor Amp(LRA) A Thermal protector Internal Internal Capacitor μf 35μF/ V 50μF/440V-450V Refrigerant oil ml ESTEL OIL VG74, 480 ESTER OIL VG74, 750 Model YDK24-6F YDK48-6H(A) Type AC motor AC motor Brand Welling Welling Input W Capacitor μf 2.5uF/450V 3μF/450V Speed r/min Number of rows 2 2 Tube pitch(a) row pitch(b) mm Fin spacing mm Fin type Hydrophilic aluminium Hydrophilic aluminium Tube outside dia.and type mm φ7 Inner grooved copper φ7.94 Inner grooved copper tube tube Coil length height mm width Number of circuits 2 5 Outdoor air flow m 3 /h Outdoor noise level (sound pressure) db(a) Outdoor unit Refrigerant Dimension(W H D) mm 838(780) (762) Packing (W H D) mm Net/Gross weight kg 37/39 41/44 Type R410A R410A Charged volume g Design pressure MPa 4.4/ /2.6 Refrigerant piping Liquid side/ Gas side mm φ6.4/φ12.7 φ6.4/φ12.7 Max. pipe length m Max. difference in level m Ambient temp. cooling:18~43; heating:-7~24 cooling: 18~43; heating:-7~24 Outdoor Units 89

92 Specifications MCAC-UTSM Model MOUA-24HN1 MOU-30HN1 Code Power supply V-ph-Hz 220~ ~ Max. input consumption W Max. input current A Starting current A Compressor Outdoor fan motor Outdoor coil Model PA290X3CS-4MU1 C-SBN301H5D Type ROTARY SCROLL Brand MIDEA-TOSHIBA SANYO Supplier MIDEA-TOSHIBA SANYO Capacity Btu/h Input W Rated current(rla) A Locked rotor Amp(LRA) A Thermal protector Internal Internal Capacitor μf 50μF/440V-450V 60uF/450V Refrigerant oil ml ESTER OIL VG74, 950 FV68S, 1700 Model YDK53-6Q YDK250-6D Type AC motor AC motor Brand Welling Welling Input W Capacitor μf 3μF/450V 10uF±5% 450V Speed r/min Number of rows Tube pitch(a) row pitch(b) mm Fin spacing mm Fin type Hydrophilic aluminium Hydrophilic aluminium Tube outside dia.and type mm φ7.94 Inner grooved copper φ7.94 Inner grooved copper tube tube Coil length height mm width Number of circuits 6 7 Outdoor air flow m 3 /h Outdoor noise level (sound pressure) db(a) Outdoor unit Refrigerant Dimension(W H D) mm 932(852) (990) Packing (W H D) mm Net/Gross weight kg 56/61 94/104 Type R410A R410A Charged volume g Design pressure MPa 4.4/ /2.6 Refrigerant piping Liquid side/ Gas side mm φ9.5/φ15.9 φ12.7/φ19 Max. pipe length m Max. difference in level m Ambient temp. cooling: 18~43; heating:-7~24 cooling: 18~43; heating:-7~24 90 Outdoor Units

93 MCAC-UTSM Specifications Model MOU-30HN1-R MOU-36HN1 Code Power supply V-ph-Hz 380~ ~ Max. input consumption W Max. input current A Starting current A Compressor Outdoor fan motor Outdoor coil Model C-SBN303H8D C-SBN301H5D Type SCROLL SCROLL Brand SANYO SANYO Supplier SANYO(Dalian) SANYO Capacity Btu/h Input W Rated current(rla) A Locked rotor Amp(LRA) A Thermal protector Internal Internal Capacitor μf / 60uF/450V Refrigerant oil ml DAPHNE FV68S, 1700 FV68S 1700 Model YDK250-6D YDK250-6D Type AC motor AC motor Brand Welling Welling Input W Capacitor μf 10uF±5% 450V 10uF±5% 450V Speed r/min Number of rows Tube pitch(a) row pitch(b) mm Fin spacing mm Fin type Hydrophilic aluminium Hydrophilic aluminium Tube outside dia.and type mm φ7.94 Inner grooved copper φ7.94 Inner grooved copper tube tube Coil length height mm width Number of circuits 7 7 Outdoor air flow m 3 /h Outdoor noise level (sound pressure) db(a) Outdoor unit Refrigerant Dimension(W H D) mm 1075(990) (990) Packing (W H D) mm Net/Gross weight kg 99/104 99/104 Type R410A R410A Charged volume g Design pressure MPa 4.4/ /2.6 Refrigerant piping Liquid side/ Gas side mm φ12.7/φ19 φ12.7/φ19 Max. pipe length m Max. difference in level m Ambient temp. cooling: 18~43; heating:-7~24 cooling: 18~43; heating:-7~24 Outdoor Units 91

94 Specifications MCAC-UTSM Model MOU-36HN1-R MOUA-48HN1-R Code Power supply V-ph-Hz 380~ ~ Max. input consumption W Max. input current A Starting current A Compressor Outdoor fan motor Outdoor coil Model C-SBN303H8D JT160G-P8Y1 Type SCROLL SCROLL Brand SANYO DAIKIN Supplier SANYO(Dalian) DAIKIN Capacity Btu/h Input W Rated current(rla) A Locked rotor Amp(LRA) A Thermal protector Internal Internal Capacitor μf / / Refrigerant oil ml DAPHNE FV68S, 1700 DAPHNE FVC68D, 1500 Model YDK250-6D YDK YDK65-6F-1 Type AC motor AC motor Brand Welling Welling Input W Capacitor μf 10uF±5% 450V 4μF/450V 2 Speed r/min Number of rows Tube pitch(a) row pitch(b) mm Fin spacing mm Fin type Hydrophilic aluminium Hydrophilic aluminium Tube outside dia.and type mm φ7.94 Inner grooved copper φ7.94 Inner grooved copper tube tube Coil length height mm width Number of circuits 7 8 Outdoor air flow m 3 /h Outdoor noise level (sound pressure) db(a) Outdoor unit Refrigerant Dimension(W H D) mm 1075(990) (900) Packing (W H D) mm Net/Gross weight kg 99/104 93/99 Type R410A R410A Charged volume g Design pressure MPa 4.4/ /2.6 Refrigerant piping Liquid side/ Gas side mm φ12.7/φ19 φ12.7/φ19 Max. pipe length m Max. difference in level m Ambient temp. cooling: 18~43; heating:-7~24 cooling: 18~43; heating:-7~24 92 Outdoor Units

95 MCAC-UTSM Specifications Model MOUA-60HN1-R Code Power supply V-ph-Hz 380~ Max. input consumption W 7500 Max. input current A 12.8 Starting current A 52 Model C-SBN453H8D Type SCROLL Brand SANYO Supplier Dalian SANYO Compressor Co., Ltd. Capacity Btu/h Compressor Input W 5750 Rated current(rla) A 9.77 Locked rotor Amp(LRA) A 67 Thermal protector Internal Capacitor μf / Refrigerant oil ml FV68S, 1700 Model YDK YDK65-6F-1 Type AC motor Outdoor fan motor Brand Welling Input W Capacitor μf 4μF/450V Speed r/min 825 Number of rows 2 Tube pitch(a) row pitch(b) mm Fin spacing mm 1.6 Outdoor coil Fin type Hydrophilic aluminium Tube outside dia.and type mm φ7.94 Inner grooved copper tube Coil length height width mm Number of circuits 8 Outdoor air flow m 3 /h 6850 Outdoor noise level (sound pressure) db(a) 59.3 Dimension(W H D) mm 986(900) Outdoor unit Packing (W H D) mm Net/Gross weight kg 93/99 Refrigerant Type R410A Charged volume g 3200 Design pressure MPa 4.4/2.6 Liquid side/ Gas side mm φ12.7/φ19 Refrigerant piping Max. pipe length m 30 Max. difference in level m 20 Ambient temp. cooling: 18~43; heating:-7~24 Outdoor Units 93

96 Dimensions MCAC-UTSM Dimensions 2.1 MOU-12HN1 94 Outdoor Units

97 MCAC-UTSM Dimensions 2.2 MOUA-18HN1 Outdoor Units 95

98 Dimensions MCAC-UTSM MOUA-24HN1 96 Outdoor Units

99 MCAC-UTSM Dimensions 2.4 MOU-30HN1 MOU-30HN1-R MOU-36HN1 MOU-36HN1-R Outdoor Units 97

100 Dimensions MCAC-UTSM MOUA-48HN1-R MOUA-60HN1-R 98 Outdoor Units

101 >200cm >60cm MCAC-UTSM Service Space 3. Service Space (Wall or obstacle) Obstacle >30cm Air inlet >30cm Air inlet Maintain channel >60cm Fix with bolt Air outlet Necessary width Deep foundation 600mm is necessary between 2 outdoor units Outdoor Units 99

102 Piping Diagrams MCAC-UTSM Piping Diagrams 4.1 MOU-12HN1 Outdoor unit Indoor units condenser temp. sensor 4-way valve T3 Check valve filter Throttle capiliary stop valve T2 evaporator temp. sensor T1 room temp. sensor stop valve compressor 4.2 MOUA-18HN1 Outdoor unit Indoor units condenser temp. sensor 4-way valve T3 filter Throttle capiliary stop valve T2 evaporator temp. sensor T1 room temp. sensor stop valve compressor 100 Outdoor Units

103 MCAC-UTSM Piping Diagrams 4.3 MOUA-24HN1 Outdoor unit Indoor units condenser temp. sensor 4-way valve T3 filter Throttle capiliary stop valve T2 evaporator temp. sensor T1 room temp. sensor stop valve compressor 4.4 MOU-30HN1 MOU-36HN1 MOU-30HN1-R MOU-36HN1-R Outdoor unit Indoor units condenser temp. sensor Muffle 4-way valve T3 T4 ambient temp. sensor Check valve filter Throttle capiliary stop valve T2 evaporator temp. sensor T1 room temp. sensor T5 Discharge temp. sensor High pressure switch stop valve compressor low-pressure accumulator Remark: For MOU-30HN1, MOU-36HN1, the T4 ambient temp. sensor is not included. Outdoor Units 101

104 Piping Diagrams MCAC-UTSM MOUA-48HN1-R Outdoor unit Indoor units condenser temp. sensor 4-way valve T3 filter T2 evaporator temp. sensor High pressure switch T4 ambient temp. sensor Throttle capiliary stop valve T1 room temp. sensor stop valve Discharge temp.sensor Low pressure switch compressor low pressure receiver 4.6 MOUA-60HN1-R Outdoor unit Indoor units condenser temp. sensor 4-way valve high pressure switch T3 T4 ambient temp. sensor filter Throttle capiliary stop valve T2 evaporator temp. sensor T1 room temp. sensor muffle discharge temp.sensor low pressure switch stop valve compressor low pressure receiver 102 Outdoor Units

105 MCAC-UTSM Wiring Diagrams 5. Wiring Diagrams 5.1 MOU-12HN1 Outdoor Units 103

106 Wiring Diagrams MCAC-UTSM MOUA-18HN1 104 Outdoor Units

107 MCAC-UTSM Wiring Diagrams 5.3 MOUA-24HN1 Outdoor Units 105

108 Wiring Diagrams MCAC-UTSM MOU-30HN1 MOU-36HN1 106 Outdoor Units

109 MCAC-UTSM Wiring Diagrams 5.5 MOU-30HN1-R MOU-36HN1-R Outdoor Units 107

110 Wiring Diagrams MCAC-UTSM MOUA-48HN1-R MOUA-60HN1-R 108 Outdoor Units

111 MCAC-UTSM Electric Characteristics 6. Electric Characteristics Model Outdoor Unit Compressor OFM Hz Voltage Min. Max. MSC RLA KW FLA MOU-12HN ~240V 198V 254V MOUA-18HN ~240V 198V 254V MOUA-24HN ~240V 198V 254V MOU-30HN ~240V 198V 254V MOU-30HN1-R ~415V 342V 418V MOU-36HN ~240V 198V 254V MOU-36HN1-R ~415V 342V 418V MOUA-48HN1-R ~415V 342V 418V MOUA-60HN1-R ~415V 342V 418V Remark: MSC: Max. Starting Amps. (A) RLA: Rated Locked Amps. (A) OFM: Outdoor Fan Motor. FLA: Full Load Amps. (A) KW: Rated Motor Output (kw) 7. Operation Limits Operation mode Outdoor temperature( ) Room temperature( ) Cooling operation 18~43 17~30 Heating operation -7~24 17~30 Cooling Heating Outdoor temperature( DB) STD Outdoor temperature( WB) STD Indoor temperature( WB) Indoor temperature( DB) Outdoor Units 109

112 Sound Levels MCAC-UTSM Sound Levels For 12000~36000Btu/h For 48000,60000Btu/h Outdoor Unit Microphone H 1.0m Note: H= 0.5 height of outdoor unit Note: The point A is in the middle of the whole outdoor panel. Model Noise level db(a) MOU-12HN1 43 MOUA-18HN1 48 MOUA-24HN1 55 MOU-30HN1 57 MOU-30HN1-R 57 MOU-36HN1 57 MOU-36HN1-R 57 MOUA-48HN1-R 59 MOUA-60HN1-R Outdoor Units

113 MCAC-UTSM Exploded View 9. Exploded View 9.1 MOU-12HN1 No. Part Name Quantity No. Part Name Quantity 1 Fan motor 1 10 High pressure valve ass'y 1 2 Motor bracket ass'y High pressure valve 1 3 Rear net Filter ass'y 1 4 Condenser ass'y 1 11 Base ass'y 1 5 E-part box ass'y 1 12 Grille Wire joint,2p 1 13 Front panel Wire joint,5p 1 14 Compressor Compressor capacitor 1 15 Net Clamp Motor capacitor 1 16 Right clapboard way valve ass'y 1 17 Partition board ass'y way valve 1 18 Left supporter Low pressure valve 1 19 Motor bracket 1 7 Big handle 1 20 Top cover 1 8 Suction pipe 1 21 Axial flow fan 1 9 Valve plate 1 22 Temp.sensor ass'y 1 Outdoor Units 111

114 Exploded View MCAC-UTSM MOUA-18HN1 5.1/ 5.2 No. Part Name Quantity No. Part Name Quantity 1 Motor 1 12 Grille 1 2 Motor bracket ass'y 1 13 Front panel ass'y 1 3 Rear net 1 14 Valve plate 1 4 Condenser ass'y 1 15 Partition board ass'y 1 5 High pressure valve ass'y 1 16 Left supporter High pressure valve 1 17 Big handle Capillary 1 18 E-part box ass'y 1 6 Temp. sensor ass'y Compressor capacitor way valve ass'y Motor capacitor Low pressure valve Wire joint,2p way valve Wire joint Solenoid Electric installation board 1 8 Right cover ass'y 1 19 Rear Supporter 1 9 Drainage pan 1 20 Top cover 1 10 Base ass'y 1 21 Axial flow fan 1 11 Compressor 1 23 R410A 112 Outdoor Units

115 MCAC-UTSM Exploded View 9.3 MOUA-24HN1 26 No. Part Name Quantity No. Part Name Quantity 1 Motor 1 13 Front panel ass'y 1 2 Motor bracket ass'y 1 14 Partition board ass'y 1 3 Rear net 1 15 Drainage cover 1 4 Condenser ass'y 1 16 E-part box ass'y 1 5 Condenser temp. sensor ass'y Compressor capacitor 1 6 High pressure valve ass'y Wire joint High pressure valve Wire joint,2p Capillary Wire joint way valve ass'y Contactor Solenoid Motor capacitor way valve 1 17 Left supporter Accumulator cylinder 1 18 Big handle Low pressure valve 1 19 Handle 1 8 Right cover ass'y 1 20 Rear Supporter 1 9 Compressor 1 21 Top cover 1 10 Base ass'y 1 22 Axial flow fan 1 11 Valve plate 1 24 R410A 12 Grille 1 Outdoor Units 113

116 Exploded View MCAC-UTSM MOU-30HN1 MOU-36HN1 No. Part Name Quantity No. Part Name Quantity 1 Top cover ass'y 1 17 Copper nut 1 2 Rear Supporter 1 18 Copper nut 1 3 Motor bracket ass'y 1 19 Sphere pad 1 4 Fixing ring 1 20 Sphere pad 1 5 Accumulator cylinder 1 21 Temp. sensor ass'y 1 6 Motor 1 22 Discharge temp sensor 1 7 Suction pipe 1 23 Compressor electric heater 1 8 Condenser ass'y 1 24 Front panel Condenser ass'y 1 25 Front net ass'y Input pipe ass'y 1 26 Axial flow fan Fluted pipe ass'y 1 27 Partition board ass'y 1 9 Rear right clapboard ass'y 1 28 Rear net 1 10 Front right clapboard ass'y 1 29 Left holder way valve ass'y 1 30 E-part box ass'y Low pressure valve Wire joint way valve Wire joint Solenoid Electric installation board 1 12 High pressure valve ass'y AC contactor High pressure valve Compressor capacitor One way valve Compressor capacitor 1 13 Valve plate Resistance ass'y 1 14 Base ass'y Capacitor 1 15 Compressor Wire joint 2 16 Discharge pipe ass'y Compressor relay Muffler 1 31 Drainage cover Pipe joint 1 32 Big handle Pressure controller Outdoor Units

117 MCAC-UTSM Exploded View 9.5 MOU-30HN1-R MOU-36HN1-R No. Part Name Quantity No. Part Name Quantity 1 Top cover ass'y 1 17 Temp sensor 1 2 Rear Supporter 1 18 Copper nut 1 3 Motor bracket ass'y 1 19 Copper nut 1 4 Fixing ring 1 20 Sphere pad 1 5 Accumulator cylinder 1 21 Sphere pad 1 6 Motor 1 22 Temp.sensor ass'y 1 7 Suction pipe 1 23 Discharge temp sensor 1 8 Condenser ass'y 1 24 Compressor electric heater Condenser ass'y 1 25 Front panel Input pipe ass'y 1 26 Front net ass'y Fluted pipe ass'y 1 27 Axial flow fan 1 9 Rear right clapboard ass'y 1 28 Partition board ass'y 1 10 Front right clapboard ass'y 1 29 Rear net way valve ass'y 1 30 Left holder Low pressure valve 1 31 E-part box ass'y way valve Electric installation board Solenoid E-Part box 1 12 High pressure valve ass'y Main control board ass'y High pressure valve Wire joint One way valve Transformer 1 13 Valve plate Capacitor 1 14 Base ass'y AC contactor 1 15 Compressor Wire joint,4p 1 16 Discharge pipe ass'y Wire joint, 5p Muffler 1 32 Drainage cover Pipe joint 1 33 Big handle Pressure controller 1 Outdoor Units 115

118 Exploded View MCAC-UTSM MOUA-48HN1-R No. Part Name Quantity No. Part Name Quantity 1 Rear supporter 1 16 Front-right panel ass'y 1 2 Motor bracket ass'y 1 17 Front net ass'y 2 3 Condenser ass'y 1 18 Front panel Input pipe ass'y 1 19 Rear-left supporting board Output pipe ass'y 1 20 E-part box ass'y 1 4 Top cover E-Part box 1 5 Partition board ass'y Wire joint 3 6 Big handle ass'y Wire joint, 5p 1 7 Rear-right panel AC contactor 1 8 Low pressure valve ass'y Main control board ass'y way valve Wire joint,4p Solenoid Transformer Low pressure valve Electric installation board 1 9 Valve plate Motor capacitor 2 10 High pressure valve ass'y 1 21 Base Strainer 1 22 Motor High pressure valve 1 23 Motor 1 11 Discharge pipe ass'y 1 24 Axial flow fan Pressure controller 1 25 Discharge temp sensor 1 12 Suction pipe ass'y 1 26 Temp sensor ass'y Pressure controller 1 27 Room temp sensor ass'y 1 13 Compressor 1 28 Compressor electric heater 1 14 Separator 1 29 Compressor wire joint ass'y 1 15 Handle Outdoor Units

119 MCAC-UTSM Exploded View 9.7 MOUA-60HN1-R No. Part Name Quantity No. Part Name Quantity 1 Rear supporter 1 16 Front-right panel ass'y 1 2 Motor bracket ass'y 1 17 Front net ass'y 2 3 Condenser ass'y 1 18 Front panel Input pipe ass'y 1 19 Rear-left supporting board Output pipe ass'y 1 20 E-part box ass'y 1 4 Top cover E-Part box 1 5 Partition board ass'y Wire joint 3 6 Big handle ass'y Wire joint, 5p 1 7 Rear-right panel AC contactor 1 8 Low pressure valve ass'y Main control board ass'y way valve Wire joint,4p Solenoid Transformer Low pressure valve Electric installation board 1 9 Valve plate Motor capacitor 2 10 High pressure valve ass'y 1 21 Base Strainer 1 22 Motor High pressure valve 1 23 Motor 1 11 Discharge pipe ass'y 1 24 Axial flow fan Pressure controller 1 25 Discharge temp sensor 1 12 Suction pipe ass'y 1 26 Temp sensor ass'y Pressure controller 1 27 Room temp sensor ass'y 1 13 Compressor 1 28 Compressor electric heater 1 14 Separator 1 29 Compressor wire joint ass'y 1 15 Handle 2 Outdoor Units 117

120 Troubleshooting MCAC-UTSM Troubleshooting Self-diagnosis Indoor unit s LED indication (1) For the Four-way cassette During malfunction protection, digital pipe displays as follow: No Displaying contents Malfunction or protection 1 E2 Indoor temperature sensor is abnormal 2 E3 Evaporator temperature sensor is abnormal 3 E4 Condenser temperature sensor is abnormal 4 E5 Temperature sensor error of water pump 5 E6 Outdoor unit malfunction 6 E7 EEPROM malfunction 7 E8 Full-water malfunction (2) For the other types indoor unit No. Type Contents LED Flashing Remark 1 Normal Standing-by Operation lamp flashes at 0.5Hz 2 Normal System Off All lamps are off Nothing wrong with the 3 Normal System startup Operation lamp on unit when LED indicate 4 Normal Forced cooling Operation lamp flashes at 5Hz, these contents. Timer lamp on 5 Protection Lamps of operation, timer, Whole unit is shut Over current protection of the compressor defrosting (only fan) flashing down. It cannot recover occurs 4 times in 1h simultaneously at 5Hz. unless power is cut off 6 Protection Outdoor protection (lack of phase, phase sequence and temperature protection) All lamps flashing at 5Hz Room temperature sensor checking 7 Error 8 Error 9 Error channel is abnormal Evaporator sensor checking channel is abnormal Condenser sensor checking channel is abnormal 10 Error Communication of EEPROM malfunction 11 Error Water level alarm/pump sensor malfunction Timer lamp flashing at 5Hz Operation lamp flashing at 5Hz Defrosting lamp flashing at 5Hz Operation lamp and timer lamp flashing at 5Hz Alarm lamp flashes at 5Hz Recover automatically after errors are eliminated (For T3 malfunction of 5HP, can t recover automatically) (3) LEDs for the indication of outdoor trouble (3 phase type, 14, 16kW) Type Contents LED1 LED2 LED3 Trouble Phase sequence Flash Off Off Trouble Lack of phase(a,b) Flash Off Off Trouble Lack of phase(c) Off Off Off Trouble Protection of Low pressure Flash Flash Off Trouble Overload of current Off Off Flash Trouble Communication malfunction Flash Off Flash Trouble Open-circuit and short-circuit trouble of T3 Off Flash Flash Trouble Open-circuit and short-circuit trouble of T4(High discharge temperature protection) Off Flash Off Trouble High temperature protection of condenser Flash Flash Flash 118 Outdoor Units

121 MCAC-UTSM Troubleshooting 10.2 Solving steps for typical malfunction (1) For the new four-way cassette E2: Indoor temperature sensor is abnormal E2 Whether the resistance of the room temp. sensor is 10K No Replace temp. sensor Yes Replace the PCB E3: Evaporator temperature sensor is abnormal E3 Whether the resistance of the evaporator temp. sensor is 10K Yes No Replace evaporator temp. sensor Replace the PCB E4: Condenser temperature sensor is abnormal E4 Whether the resistance of the condenser temp. sensor is 10K No Replace condenser temp. sensor Yes Replace the PCB Outdoor Units 119

122 Troubleshooting MCAC-UTSM E5: Temperature sensor error of water pump E5 Whether the resistance of the temp. sensor is 10K No Replace temp. sensor Yes Replace the PCB E6: Outdoor unit malfunction E6 Whether the outdoor unit is power on No Check when the power is on Yes Measure whether the voltage of the communication line s red and black end between the indoor and outdoor unit is +5V No Replace the outdoor unit board Yes Check the indoor unit main board CN5 or replace the main control board Yes Replace the PCB 120 Outdoor Units

123 MCAC-UTSM Troubleshooting E7: EEPROM malfunction E7 EEPROM chip is broken Yes Replace EEPROM No Check whether the main control chip 9177 is broken Yes Replace 9177 chip No Check PCB board or replace the main control board E8: Full-water malfunction E8 Check whether the water-level switch is inserted well No Insert the water-level switch well Yes Check whether the water-level switch is broken Yes Replace the water-level switch No Check whether the water pump is normal No Replace the water pump Yes Check PCB board or replace the main control board Outdoor Units 121

124 Troubleshooting MCAC-UTSM (2) For the outdoor unit a. Phase sequence error: Phase sequence error Change the order of two of the wires to power supply. Switch on the unit again. If the problem can not be solved, the outdoor PCB is defective b. Overload of current Overload of current Check the current, normally Is the current in rated range? Yes The outdoor PCB is defective No Possible reason 1. Outdoor fan is defective 2. The compressor is defective 3. Refrigerant is over charged 4. Air enter the refrigerant system 5. Heat exchanger is too dirty c. Lack of phase Lack of phase Check the power supply, is it 3 phase, V? Yes Check the connection between power supply and terminal, is the voltage in outdoor terminal is 3 phase, V? Yes Outdoor PCB is defective 122 Outdoor Units

125 MCAC-UTSM Troubleshooting d. Protection of pressure or temp. Protection of pressure or temp. Yes Is it k1 or K2 open? Is temp. protective switch K1 open Is pressure protective switch K2 open Yes Yes Possible reason 1. The wires is loose to K1 2. Air or other gas in the refrigerant. 3. Heat exchanger is dirty 4. Outdoor fan or fan blade is defective 5. Outdoor unit is bad ventilation 6. Refrigerant is leakage 7. K1 switch is defective Possible reason 1. The wires is loose to K2 2. Air or other gas in the refrigerant. 3. Heat exchanger is dirty 4. Outdoor fan or fan blade is defective 5. Outdoor unit is bad ventilation 6. Refrigerant is two much 7. K2 switch is defective e. Open-circuit and short-circuit trouble of T3 Is connection to connector of temp. sensor good? No Yes Repair connector Check the resistance of the temp. sensor according to Annex 1 Is it the resistance is normal? Yes No Indoor PCB is defective. Replace the sensor Outdoor Units 123

126 Troubleshooting MCAC-UTSM f. Open-circuit and short-circuit trouble of T4 Is connection to connector of temp. sensor good? Yes No Check the resistance of the temp. sensor according to Annex 1 Repair connector Is it the resistance is normal? Yes No Indoor PCB is defective. Replace the sensor g. High temperature protection of condenser High temperature protection of condenser Check the resistance of the temp. sensor according to Annex 1, is it normal? Yes No Possible reason 1. Air or other gas in the refrigerant. 2. Heat exchanger is dirty 3. Outdoor fan or fan blade is defective 4. Outdoor unit is bad ventilation 5. Refrigerant is leakage 6. Outdoor PCB is defective Replace the sensor 124 Outdoor Units

127 MCAC-UTSM Troubleshooting Appendix Indoor Temp. and Pipe Temp. Sensor Resistance Value Table ( --K) K Ohm K Ohm K Ohm K Ohm Outdoor Units 125

128

129 MCAC-UTSM Installation Part 4 Installation 1. Precaution on Installation Vacuum Dry and Leakage Checking Additional Charge Water Drainage Insulation Work Wiring Test Operation Installation 127

130 Precaution on Installation MCAC-UTSM Precaution on Installation 1.1. Measure the necessary length of the connecting pipe, and make it by the following way. a. Connect the indoor unit at first, then the outdoor unit. Bend the tubing in proper way. Do not harm them. CAUTIONS: Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds With hands before fasten the flare nuts. Be sure to use two wrenches simultaneously when you connect or disconnect the pipes. Pipe gauge Φ6.4 Φ9.5 Φ12.7 Φ15.9 Φ19.1 Tightening torque 15~16N.m (153~163 kgf.cm) 25~26N.m (255~265kgf.cm) 35~36N.m (357~367kgf.cm) 45~47N.m (459~480 kgf.cm) 65~67N.m (663~684kgf.cm) Flare dimension A Min (mm) Max Flare shape b. The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before connection. c. Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at the repair-points Locate The Pipe a. Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall conduit and its cover. b. Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by condensation. c. Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing Connect the pipes Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit in fluent flow Be sure of no leakage by checking it with leak detector or soap water Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to prevent leakage. 128 Installation

131 MCAC-UTSM Vacuum Dry and Leakage Checking 2. Vacuum Dry and Leakage Checking 2.1. Vacuum Dry: use vacuum pump to change the moisture (liquid) into steam (gas) in the pipe and discharge it out of the pipe to make the pipe dry. Under one atmospheric pressure, the boiling point of water(steam temperature) is 100. Use vacuum pump to make the pressure in the pipe near vacuum state, the boiling point of water falls relatively. When it falls under outdoor temperature, the moisture in the pipe will be vaporized Vacuum dry procedure There are two methods of vacuum dry due to different construction environment: common vacuum dry, special vacuum dry.. Common vacuum dry procedure 1 Vacuum dry (for the first time)---connect the all-purpose detector to the inlet of liquid pipe and gas pipe, and run the vacuum pump more than two hours (the vacuum pump should be below -755mmHg) If the pump can t achieve below -755mmHg after pumping 2 hours, moisture or leakage point will still exist in the pipe. At this time, it should be pumped 1 hour more. If the pump can t achieve -755mmHg after pumping 3 hours, please check if there are some leakage points. Vacuum placement test: place 1 hour when it achieves -755mmHg, pass if the vacuum watch shows no rising. If it rises, it shows there s moisture or leakage point. Vacuuming from liquid pipe and gas pipe at the same time. Sketch map of common vacuum dry procedure. Installation 129

132 Additional Charge MCAC-UTSM Special vacuum dry procedure This vacuum dry method is used in the following conditions: There s moisture when flushing the refrigerant pipe. Rainwater may enter into the pipe. Vacuum dry for the first time 2h pumping 3. Vacuum destroy for the second time Fill nitrogen to 0.5Kgf/cm2 Because nitrogen is for drying gas, it has vacuum drying effect during vacuum destroy. But if the moisture is too much, this method can t dry thoroughly. So, please pay more attention to prevent water entering and forming condensation water. 4. Vacuum dry for the second time 1h pumping Determinant: Pass if achieving below -755mmHg. If -755mmHg can t be achieved in 2h, repeat procedure 3 and Vacuum placing test 1h 6. Sketch map of special vacuum dry procedure 3. Additional Charge Caution Refrigerant cannot be charged until field wiring has been completed. Refrigerant may only be charged after performing the leak test and the vacuum pumping. When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer. Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the appropriate refrigerant is charged. Refrigerant containers shall be opened slowly. Always use protective gloves and protect your eyes when charging refrigerant. The outdoor unit is factory charged with refrigerant. Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit/indoor unit R(g) L(m) D(mm) φ6.4 Φ9.5 Φ12.7 Less than 5m (One-way) Added Refrigerant When Over 5m(One-way) 11g/m (L-5) 30g/m (L-5) 60g/m (L-5) Remark: R(g): Additional refrigerant to be charged L(m): The length of the refrigerant pipe(one-way) D(mm): Liquid side piping diameter 130 Installation

133 MCAC-UTSM Water Drainage 4. Water Drainage 4.1. Gradient and Supporting Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short as possible and eliminate the air bubble The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the gradient of 1/100 and prevent bending. Refer to the following table for the specification of the prop stand. Diameter Hard PVC pipe 25~40mm 1.5~2m Distance between the prop stands Precautions 1 The diameter of drainpipe should meet the drainage requirement at least. 2 The drainpipe should be heat-insulated to prevent atomization. 3 Drainpipe should be installed before installing indoor unit. After powering on, there is some water in water-receiver plate. Please check if the drain pump can operate correctly. 4 All connection should be firm. 5 Wipe color on PVC pipe to note connection. 6 Climbing, horizontal and bending conditions are prohibited. 7 The dimension of drainpipe can t less than the connecting dimension of indoor drainpipe. 8 Heat-insulation should be done well to prevent condensation. 9 Indoor units with different drainage type can t share one convergent drainpipe. 4.2 Drainpipe Trap If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap Every indoor unit needs one drainpipe trap A plug should be designed to do cleaning. Plug 50cm 50cm 4.3 Upwards drainage(drain pump) For Four-way cassette(compact) Installation 131

134 Water Drainage MCAC-UTSM For Four-way cassette 4.4 Convergent drainage The number of indoor units should be as small as possible to prevent the traverse main pipe overlong Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system Selecting the diameter Number of connecting indoor units Calculate drainage volume Select the diameter Calculate allowed volume =Total cooling capacity of indoor units(hp) 2 (l/ hr) Allowed volume(lean 1/100) (l/ hr) I.D. (mm) Thick 集中排水管 Hard PVC Hard PVC 14< Hard PVC 88< Hard PVC 175< Hard PVC 334< Drainage test Drainage without drain pump After finishing drainpipe installation, pour some water into the water receiver plate to check if the water flows smoothly. 132 Installation

135 MCAC-UTSM Insulation Work 5. Insulation Work 5.1 Insulation material and thickness Insulation material Insulation material should adopt the material which is able to endure the pipe s temperature: no less than 70 in the high-pressure side, no less than 120 in the low-pressure side(for the cooling type machine, no requirements at the low-pressure side.) u Example: Heat pump type----heat-resistant Polyethylene foam (withstand above 120 ) Cooling only type----polyethylene foam (withstand above 100 ) Thickness choice for insulation material Insulation material thickness is as follows: Pipe diameter (mm) Adiabatic material thickness Φ6.4 Φ mm Refrigerant pipe Φ28.6 Φ mm Drainage pipe Inner diameterφ20 Φ32 6mm 5.2 Refrigerant pipe insulation Work Procedure 1 Before laying the pipes, the non-jointing parts and non-connection parts should be heat insulated. 2 When the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat insulated Insulation for non-jointing parts and non-connection parts wrong right Gas pipe and liquid pipe should not be put together to insulate Insulate the gas pipe (cooling only) Insulate the gas pipe and liquid pipe Installation 133

136 Wiring MCAC-UTSM For construction convenience, before laying pipes, use insulation material to insulate the pipes to be deal with, at the same time, at two ends of the pipe, remain some length not to be insulated, in order to be welded and check the leakage after laying the pipes Insulate for the jointing area, expanding area and the flange area 1 Insulate for the jointing area, expanding area and the flange area should be done after checking leakage of the pipes 2 Make sure there s no clearance in the joining part of the accessorial insulation material and local preparative insulation material. 5.3 Drainage pipe insulation The connection part should be insulated, or else water will be condensing at the non-insulation part. 5.4 Note The jointing area, expanding area and the flange area should be heat insulated after passing the pressure test The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually Use the attached heat-insulation material to insulate the pipe connections (pipes tie-in,expand nut ) of the indoor unit 6. Wiring Please refer to the Wiring Diagram. 134 Installation

137 MCAC-UTSM Test operation 7. Test operation (1) The test operation must be carried out after the entire installation has been completed. (2) Please confirm the following points before the test operation. The indoor unit and outdoor unit are installed properly. Tubing and wiring are correctly completed. The refrigerant pipe system is leakage-checked. The drainage is unimpeded. The ground wiring is connected correctly. The length of the tubing and the added stow capacity of the refrigerant have been recorded. The power voltage fits the rated voltage of the air conditioner. There is no obstacle at the outlet and inlet of the outdoor and indoor units. The gas-side and liquid-side stop values are both opened. The air conditioner is pre-heated by turning on the power. (3) According to the user's requirement, install the remote controller when the remote controller's signal can reach the indoor unit smoothly. (4) Test operation Set the air conditioner under the mode of "COOLING" with the remote controller, and check the following points. Indoor unit Whether the switch on the remote controller works well. Whether the buttons on the remote controller works well. Whether the air flow louver moves normally. Whether the room temperature is adjusted well. Whether the indicator lights normally. Whether the temporary buttons works well. Whether the drainage is normal. Whether there is vibration or abnormal noise during operation. Outdoor unit Whether there is vibration or abnormal noise during operation. Whether the generated wind, noise, or condensed of by the air conditioner have influenced your neighborhood. Whether any of the refrigerant is leaked. Installation 135

138 Control MCAC-UTSM Part 5 Control 1. Remote Controller Control

139 MCAC-UTSM Remote Controller 1.1 R11-HG/E Mode select button Each time you push the button, a mode is selected in a sequence that goes from AUTO, COOL, DRY, HEAT (cooling only type without), FAN ONLY and back to AUTO. I/O Button Push the button to start operation, push the button again to stop operation. Remote Controller Fan button Temperature Button This button is used for selecting fan speed. Each time you push the button, a fan speed is selectedinasequence that goes from AUTO, LOW, MED(Some models without, HIGH, and back to AUTO. After Sliding the cover, the button and function are as follows: Auto louver button Push this button to swing louver. Push the button again to stop. Confirmation button Push this button to confirm ON and OFF timer settings. FAN Timer button Push ON-TIME timer button to set the ON timer. Push OFF-TIME timer button to set the OFF timer. This button is used for setting the current time and OFF time. Adjust forwards Adjust backwords Clock button Push this button to set time. Push this button to cancel ON timer and OFF timer. Lock button When you push the LOCK button, all current settings are locked in and the remote controller does not accept any operation except that of the LOCK button. Use the lock mode when you want to prevent setting from being changed accidentally or play fully. Push the LOCK button again when you want to cancel the LOCK mode. RESET button When you push the RESET button, all current settings are cancelled and get into the condition of beginning. In the clock, the colon in "0:00" will flash, the mode displays "AUTO", fan speed displays "AUTO", the temperature displays "24". Control 137

140 Remote Controller MCAC-UTSM R05/BGE The below is R05/BGE wireless remote controller, for Four-way cassette type and the Ceiling& floor type. Mode setting 1 AUTO COOL DRY HEAT TEMP SET SET 2 Fan speed setting Adjust 3 FAN 4 Adjust MODE M FAN SPEED ON/OFF 5 6 Ai r dire cti on setting Horiz swing 7 9 Time setting SWING AIR DIRECTION CLOCK Vert. swing 8 SWING OK TIME ON 10 Time ON Reset 12 ECO TIME OFF 11 Time OFF Lock Confirm button Cool/heat Economic operation Visual photo 1.3 General Function for wireless remote controller: MODEL AND SPECIFICATION Model R05/BGE Rated voltage 3.0V (2 pieces of LR03 7# batteries) Min voltage for sending signal of CPU 2.4V Effective receiving distance 8m~11m Operation condition -5~ Control

R410A50Hz Universal Outdoor Series Technical Manual

R410A50Hz Universal Outdoor Series Technical Manual Outdoor Unit R410A 50Hz Universal Outdoor Series Technical Manual 2013 Version LCAC/2.0/201308 I GD Chigo Heating & Ventilation Equipment Co., Ltd. Content Content PART 1.General Information... 1 1.Nomenclature...

More information

MANUAL DE INGENIERIA. Part 1 General Information... 1 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 30

MANUAL DE INGENIERIA. Part 1 General Information... 1 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 30 MANUAL DE INGENIERIA Evaporadora Sopladora 'MVA' con Condensadora 'MOV' - Blue Star Part 1 General Information... 1 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 30 Part 1 General Information 1. Model

More information

Technical Manual. R410A 50Hz Universal Outdoor Series Inverter type. R410A50Hz Universal Outdoor Series Technical Manual LCAC/2016.

Technical Manual. R410A 50Hz Universal Outdoor Series Inverter type. R410A50Hz Universal Outdoor Series Technical Manual LCAC/2016. Outdoor Unit R410A 50Hz Universal Outdoor Series Inverter type Technical Manual LCAC/2016.1 I GD Chigo Heating & Ventilation Equipment Co., Ltd. Content Part 1. General Information... 1 1. Nomenclature...

More information

Contents. Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79

Contents. Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79 MCAC-TSM-2008-02 Contents Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79 Contents i MCAC-TSM-2008-02 Introduction Introduction Midea Mini Unitary

More information

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD.

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD. Technical Support Division 2017-4-25 New CMV System - Floor ceiling Indoor Unit 1 1. External appearance 2. Nomenclature 3. Specifications 4. Dimensions 5. Service space 6. Piping diagram 7. Wiring diagram

More information

R410A50Hz Universal Outdoor Series Technical Manual

R410A50Hz Universal Outdoor Series Technical Manual Outdoor Unit R410A 50Hz Universal Outdoor Series Service Manual 2012 Version I GD Chigo Heating & Ventilation Equipment Co., Ltd. Content Content PART 1.General Information... 1 1.Nomenclature... 2 2.Model

More information

Floor-Standing Type(E Series)

Floor-Standing Type(E Series) Floor-Standing Type(E Series) Model: MFE-60CE, MFE-60AE Part 1. Product Features With a spiral shape, the computer-aided simulation designed air passage system can efficiently reduce noise. The Soft touch

More information

Four-way Cassette Type

Four-way Cassette Type Four-way Cassette Type Part 1. Product Features 1) Low operation noise ---Streamline plate ensures quietness ---Creates natural and comfortable environment 2) Efficient cooling ---Equal, fast and wide

More information

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control...

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control... R410A Tropical Split Type AC Technical Manual Content Content Part 1 General Information... 2 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 88 Part 4 Installation... 120 Part 5 Control... 154 Indoor

More information

[U] Serie MHB / MHA Manual de Ingeniería

[U] Serie MHB / MHA Manual de Ingeniería [U] Serie MHB / MHA Evaporadoras Soplladoras de Alltta Presiión Esttáttiica 6..3,, 8 y 12..5 Ton Manual de Ingeniería. - 1 - General Information_MHB 1. Model Names of Indoor/Outdoor Units 2. External Appearance

More information

SERVICE MANUAL CONDENSING UNIT ASE-18AH, ASE-24AH, ASE-36AH, ASE-48AH, ASE-60AH

SERVICE MANUAL CONDENSING UNIT ASE-18AH, ASE-24AH, ASE-36AH, ASE-48AH, ASE-60AH SERVICE MANUAL CONDENSING UNIT ASE-18AH, ASE-24AH, ASE-36AH, ASE-48AH, ASE-60AH Outdoor Units - appearance 18,000Btu/h 30,000~36,000Btu/h 24,000Btu/h 48,000Btu/h-60,000Btu/h Model Names of Outdoor Units

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL TECHNICAL & SERVICE MANUAL CASSETTE TYPE AIR-CONDITIONER (One-way cassette) FSK-94HF FI-SM-040830 One-way Cassette Air-conditioner Table of Contants Part 1. Product Features 2 Part 2. Specification 3 Part

More information

UCV CONDENSING UNITS SPECIFICATIONS 1. Specifications

UCV CONDENSING UNITS SPECIFICATIONS 1. Specifications UCV CONDENSING UNITS SPECIFICATIONS 1. Specifications Model UCV-76C UCV-96C Code 220075900040 220075900020 Power supply V- Ph-Hz 380-415~3~50 Capacity Btu/h 76000 96000 Cooling Input W 8100 10000 Rated

More information

Technical Manual. R410A 50Hz Universal Outdoor Series Inverter type Version. R410A50Hz Universal Outdoor Series Technical Manual LCAC/1.

Technical Manual. R410A 50Hz Universal Outdoor Series Inverter type Version. R410A50Hz Universal Outdoor Series Technical Manual LCAC/1. Outdoor Unit R410A 50Hz Universal Outdoor Series Inverter type Technical Manual 2014 Version LCAC/1.0/201401 I GD Chigo Heating & Ventilation Equipment Co., Ltd. Content PART 1.General Information... 1

More information

Midea R410A Tropical ClimaCreator Series Rooftop Package 220V 3Ph 60Hz Technical Manual

Midea R410A Tropical ClimaCreator Series Rooftop Package 220V 3Ph 60Hz Technical Manual Midea R410A Tropical ClimaCreator Series Rooftop Package 220V 3Ph 60Hz Technical Manual Midea reserves the right to discontinue, or change specification or designs at any time without notices and without

More information

[U] Serie MOV. Manual de Ingeniería

[U] Serie MOV. Manual de Ingeniería [U] Serie MOV Uniidades Condensadoras (Fllujjo Verttiicall) 6..3,, 8 y 12..5 Ton Manual de Ingeniería - 112- Outdoor Units_MOV 1. Specifications.... 2. Dimension... 3. Service Space. 4. Piping Diagrams

More information

Floor-Standing Type(S2 Series)

Floor-Standing Type(S2 Series) Floor-Standing Type(S2 Series) Model: MFS2-24CR(N2), MFS2-24HR(N2), MFS2-24AR(N2), MFS2-48CR(N2), MFS2-48AR(N2) Part 1. Product Features Strong air supply. Wide angle and long distance air supply. Easy

More information

DC Inverter Multi-split System Technical Manual - 50Hz/R410a

DC Inverter Multi-split System Technical Manual - 50Hz/R410a DC Inverter Multi-split System Technical Manual - 50Hz/R410a A/1/LCAC/2/TM/2.0 General Information Contents Part 1. General Information... 4 1. Features... 4 2. Nomenclature... 6 3. Products Line-up...

More information

Service Manual. Multi Split Type Heat Pump Air Conditioners. Applied to: HS-9U2IM_HOS-18U2IM HS-9U11IM_HS-12U11IM_HOS-21U11IM

Service Manual.   Multi Split Type Heat Pump Air Conditioners. Applied to: HS-9U2IM_HOS-18U2IM HS-9U11IM_HS-12U11IM_HOS-21U11IM Service Manual Multi Split Type Heat Pump Air Conditioners Applied to: HS-9U2IM_HOS-18U2IM HS-9U11IM_HS-12U11IM_HOS-21U11IM CONTENT 1. Product features 2. Specification 3. Dimensions 4. Refrigeration cycle

More information

Service Manual. Air Conditional

Service Manual. Air Conditional Air Conditional Service Manual Большая библиотека технической документации http://splitoff.ru/tehn-doc.html каталоги, инструкции, сервисные мануалы, схемы. -2 - MODEL: AC-FR30CM -3 - CONTENTS SPECIFICATION...

More information

Miraco MISR REFRIGERATION & AIR CONDITIONING MFG. CO.

Miraco MISR REFRIGERATION & AIR CONDITIONING MFG. CO. Miraco MISR REFRIGERATION & AIR CONDITIONING MFG. CO. High Efficiency Green Slim Line Ceiling Concealed Ducted Split Systems Cool Only Rev. August 2015 12K - 18K - 24K - 30K - 36K - 42K - 48K - 60K IAQ

More information

Engineering Data Book

Engineering Data Book 40VMF 4-Way Cassette Indoor Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without

More information

Klimaire 16 SEER CENTRAL DUCTED YEAR. Central Air Conditioning & Heat Pump Systems Multi Position Air Handling Units LIMITED GUARANTEE

Klimaire 16 SEER CENTRAL DUCTED YEAR. Central Air Conditioning & Heat Pump Systems Multi Position Air Handling Units LIMITED GUARANTEE Klimaire 16 SEER CENTRAL DUCTED Central Air Conditioning & Heat Pump Systems Multi Position Air Handling Units 10 YEAR LIMITED GUARANTEE R410A R E F R I G E R A N T CSM Condensing Units Features Condensing

More information

High Wall Split Systems Cool Only 9K - 12K - 18K - 24K. Auto. Auto. Fan Speed. Smart LCD Wireless Control. Auto Mode.

High Wall Split Systems Cool Only 9K - 12K - 18K - 24K. Auto. Auto. Fan Speed. Smart LCD Wireless Control. Auto Mode. HFC4 1 0 A 0-40V ~, 0Hz 1Ph High Wall Split Systems Cool Only 9K - 1K - 18K - 4K R-410A IAQ $ Auto Auto Fan Speed Timer s Easy Flexible Installation Smart LCD Wireless Control Auto Mode Auto Restart Easy

More information

Engineering Data Book

Engineering Data Book 40VMC Compact 4-Way Cassette Indoor Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs

More information

Window Y9USC/E 09 / 12 / 18 B5R

Window Y9USC/E 09 / 12 / 18 B5R Window Y9USC/E 09 / 12 / 18 B5R SERVICE MANUAL Y9USC-09 B5R; Y9USE-09 B5R Y9USC-12 B5R; Y9USE-12 B5R Y9USC-18 B5R; Y9USE-18 B5R SM-Y9USC-E-09-18GB 03-07 1. Precaution... 2 1.1 safety Precaution... 2 1.2

More information

V ~, 50Hz 1Ph. High Wall Split Systems Heat Pump 9K - 12K - 18K - 24K - 28K. Auto. Auto Fan Speed. Auto. Smart LCD Wireless Control.

V ~, 50Hz 1Ph. High Wall Split Systems Heat Pump 9K - 12K - 18K - 24K - 28K. Auto. Auto Fan Speed. Auto. Smart LCD Wireless Control. HFC4 1 0 A 0-40V ~, 0Hz 1Ph High Wall Split Systems Heat Pump 9K - 1K - 18K - 4K - 8K R-410A Compressor Super Quiet AMS Anti-dust Filters Auto Fan Speed Timer Functions Defrost Protection Smart LCD Wireless

More information

DC Inverter Multi-split System Technical Manual - 50Hz/R410a

DC Inverter Multi-split System Technical Manual - 50Hz/R410a DC Inverter Multi-split System Technical Manual - 50Hz/R410a A/1/LCAC/2/TM/1.0/201111 Content Contents Part 1. General Information... 1 1. Features... 1 2. Nomenclature... 3 3. Products Line-up... 5 4.

More information

Introduction Part 1 : General Information Part 2: Indoor Units Part 3: Installation Part 4: Control

Introduction Part 1 : General Information Part 2: Indoor Units Part 3: Installation Part 4: Control Introduction Part 1 : General Information Part 2: Indoor Units Part 3: Installation Part 4: Control i Introduction Fan coil unit is a kind of compound device which assemble fan and surface-type coil heating-exchanger

More information

Energy Related Products SUPER DC INVERTER SERIES

Energy Related Products SUPER DC INVERTER SERIES Energy Related Products SUPER DC INVERTER SERIES Service Manual 2013 LFIS-B-1309 Contents i Contents Part 1 General Information... 1 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 65 Part 4 Installation...

More information

MODEL: CCT 301 INV CCT 501 INV CCT 70 INV-S CCT 100 INV-S CCT 140 INV-S CCT 170 INV-S

MODEL: CCT 301 INV CCT 501 INV CCT 70 INV-S CCT 100 INV-S CCT 140 INV-S CCT 170 INV-S MODEL: CCT 301 INV CCT 501 INV CCT 70 INV-S CCT 100 INV-S CCT 140 INV-S CCT 170 INV-S Compact Four-way Cassette Type 1. Features... 2. Specification... 3. Dimension... 4. Service Space... 5. Wiring Diagram...

More information

R410 a. Air Conditioners. Residential and commercial. R410 a

R410 a. Air Conditioners. Residential and commercial. R410 a Fresh Aireasy Breathe R410 a Air Conditioners Residential and commercial R410 a Airco Branded Products The Airco brand dates back to 1949 when it was first launched into the local market. This brand has

More information

Commercial Air Conditioners. VRF 60Hz V4+S/V4+R/V4+W/Mini VRF

Commercial Air Conditioners. VRF 60Hz V4+S/V4+R/V4+W/Mini VRF 2016 Commercial Air Conditioners VRF 60Hz V4+SV4+RV4+WMini VRF OUTDOOR UNIT LINEUP INDOOR UNIT LINEUP 1.8 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 10.0 11.2 12.5 14.0 16.0 20.0 25.0 28.0 40.0 45.0 OUTDOOR UNIT

More information

All side discharge units are having high pressure switch (LP switch- Optional) and time delay relay. Compressors are scroll type, Copeland make.

All side discharge units are having high pressure switch (LP switch- Optional) and time delay relay. Compressors are scroll type, Copeland make. All outdoor units are designed to perform satisfactorily at 52 C, with the option of either top discharge condensing units, with Copeland reciprocating scroll compressors. All top discharge condensing

More information

SERVICE MANUAL UNI ON/OFF ASC-60A

SERVICE MANUAL UNI ON/OFF ASC-60A SERVICE MANUAL UNI ON/OFF ASC-60A The specifications, designs, and information in this book are subject to change without notice for product improvement. Model Power supply Cooling Heating Indoor fan motor

More information

Ceiling & Floor type Unit

Ceiling & Floor type Unit Ceiling & Floor type Unit Part 1. Product Features Quietest operation, low noise. Thin design, space-saving. Easy to operate, remote control. 16 Part 2. Specification Model MUA-18HRN2 MUA-24HRN2 MUA-24HRN2

More information

Content. The specifications, designs, and information in this book are subject to change without notice for product improvement.

Content. The specifications, designs, and information in this book are subject to change without notice for product improvement. MCAC-ATSM-2014-01 Content R410A Mini Split Chiller 50Hz 1. Model Names of Outdoor Units... 2 2. External Appearance... 2 3. menclature... 3 4. Features... 4 5. Descriptions of Standard Unit... 6 6. Specifications...

More information

Aqua Mini Full DC Inverter Unitary Chiller 50Hz. Content

Aqua Mini Full DC Inverter Unitary Chiller 50Hz. Content MCAC-ATSM-2014-09 Content 1. Outdoor units lineup... 2 2. Nomenclature... 3 3.Features... 4 4. Description of main components... 8 5. Specifications... 10 6. Dimensions... 14 7. Piping Diagram... 15 8.

More information

Cassette SERVICE MANUAL. YKHC 18 to 48 YKHC 18 YKHC 24 YKHC 30 YKHC 36 YKHC 48 SM-YKHC-18-48GB 03-07

Cassette SERVICE MANUAL. YKHC 18 to 48 YKHC 18 YKHC 24 YKHC 30 YKHC 36 YKHC 48 SM-YKHC-18-48GB 03-07 Cassette YKHC 18 to 48 SERVICE MANUAL YKHC 18 YKHC 24 YKHC 30 YKHC 36 YKHC 48 SM-YKHC-18-48GB 03-07 How to read the model? * * * Y K H C 24 F S B A A A Range: F = Floor standing H = High wall M = Master

More information

Engineering Data Book

Engineering Data Book 40VMU Under Ceiling/Floor Indoor Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs

More information

1. Product Lineup. 2. External Appearance. 3. Nomenclature M R C 36 H W N1 - R. Power supply R: 380~415V 3Ph~ 50Hz. Refrigerant type N1: R410A

1. Product Lineup. 2. External Appearance. 3. Nomenclature M R C 36 H W N1 - R. Power supply R: 380~415V 3Ph~ 50Hz. Refrigerant type N1: R410A Contents 1. Product Lineup... 1 2. External Appearance... 1 3. Nomenclature... 1 4. Features... 2 5. List of Functions... 3 6. Specifications... 6 7. Dimensional Drawings... 8 8. Wiring Diagrams... 9 9.

More information

MINI CHILLER INVERTER H4 Service manual MUENR-H4 (5, 7, 10, 12, 14, 16 kw)

MINI CHILLER INVERTER H4 Service manual MUENR-H4 (5, 7, 10, 12, 14, 16 kw) MINI CHILLER INVERTER H4 Service manual MUENR-H4 (5, 7, 10, 12, 14, 16 kw) CL25610 to CL25615 English Content 1. Outdoor units lineup... 2 2. Nomenclature... 3 3.Features... 4 4. Description of main components...

More information

Service Manual. Air Conditional

Service Manual. Air Conditional Air Conditional Service Manual Большая библиотека технической документации http://splitoff.ru/tehn-doc.html каталоги, инструкции, сервисные мануалы, схемы. -2 - MODEL: AC-FR30HM -3 - CONTENTS SPECIFICATION...

More information

SUPER DC INVERTER SERIES

SUPER DC INVERTER SERIES Energy Related Products SUPER DC INVERTER SERIES Service Manual 2016 LFIS-C1-1601 Contents i Contents Part 1 General Information... 1 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 94 Part 4 Installation...

More information

Product Data. Features/Benefits. 30RQ Air-cooled Modular Chiller R22 & R410A & R407C

Product Data. Features/Benefits. 30RQ Air-cooled Modular Chiller R22 & R410A & R407C Product Data 30RQ Air-cooled Modular Chiller R22 & R410A & R407C Introduction Air-cooled modular chiller is a kind of central airconditioning unit which adopts air as the cooling (or heating) source and

More information

Part 1 General Information... 1 Part 2 Outdoor Unit... 4 Part 3 Installation... 45

Part 1 General Information... 1 Part 2 Outdoor Unit... 4 Part 3 Installation... 45 Contents Part 1 General Information... 1 Part 2 Outdoor Unit... 4 Part 3 Installation... 45 The specifications, designs, and information in this book are subject to change without notice for product improvement.

More information

SERVICE MANUAL IOS629C2V01 IOS736C2V01 IUS0736C21 ICS0629C21 ICS0736C21 AIR CONDITIONER

SERVICE MANUAL IOS629C2V01 IOS736C2V01 IUS0736C21 ICS0629C21 ICS0736C21 AIR CONDITIONER SERVICE MANUAL IOS629C2V01 IOS736C2V01 IUS0736C21 ICS0629C21 ICS0736C21 AIR CONDITIONER i Contents CONTENTS Part 1 General Information... 1 Part 2 Indoor Units... 5 Part 3 Outdoor Units... 32 Part 4 Installation...

More information

Service manual. MIV V4+ Mini

Service manual. MIV V4+ Mini DM12-01.01.05en Service manual MIV V4+ Mini DC INVERTER R410A (~220V, 50Hz, 1Ph) MVUH80A-VA1 Contents Part 1 General Information... 1 Part 2 Outdoor Units... 6 Part 3 Installation... 44 DM12-01.01.05en

More information

1. MODELS LIST NOMENCLATURE FEATURES PRODUCT DATA FAN CHARACTERISTICS CLEARANCE DATA...

1. MODELS LIST NOMENCLATURE FEATURES PRODUCT DATA FAN CHARACTERISTICS CLEARANCE DATA... FIXED FREQUENCY U-MATCH AIR CONDITIONERS TECHNICAL SALES GUIDE Capcity Range: 18000~ 60000 Bth h T3R2250Hz CONTENTS 1. MODELS LIST... 3 2. NOMENCLATURE... 4 3. FEATURES... 5 4. PRODUCT DATA... 9 5. FAN

More information

Amendment Sheet. Nomenclature M 5 AC V 100 C R - F X AA. Code : M5ACV Date : Superceded : M5ACV

Amendment Sheet. Nomenclature M 5 AC V 100 C R - F X AA. Code : M5ACV Date : Superceded : M5ACV Amendment Sheet Code : M5ACV-2005-0002 Date : 08-05-2006 Superceded : M5ACV-2005-0001 Nomenclature Production spec variation Type of ref. connection X : Not applicable Electrical A : 220-240V/1Ph/50Hz

More information

FLUYE CON TU ESTILO DE VIDA

FLUYE CON TU ESTILO DE VIDA FLUYE CON TU ESTILO DE VIDA CatalogoFINAL ok.indd 06/04/5 :5 Air Conditioning SPLIT Elegant & Decorative Line phoenix I N V E R T E R CatalogoFINAL ok.indd 2 06/04/5 :5 50% energy saving STANDARD FEATURES

More information

Models: ACC 75D/DR ACC 100D/DR. ACC - D (Draft) Ceiling Concealed Split Systems

Models: ACC 75D/DR ACC 100D/DR. ACC - D (Draft) Ceiling Concealed Split Systems Models: ACC 75D/DR ACC 100D/DR ACC - D2-2007 (Draft) Ceiling Concealed Split Systems CONTENTS 1. NOMENECLATURE... 2 2. FEATURES... 4 3. PRODUCT LINE UP... 5 4. SPECIFICATIONS... 8 5. OPERATING RANGE...

More information

CASSETTE TYP FANCOIL UNIT SERVICE MANUAL

CASSETTE TYP FANCOIL UNIT SERVICE MANUAL CASSETTE TYP FANCOIL UNIT SERVICE MANUAL (GC201109-I) Contents PRODUCT...2 1. MODELS LIST...2 2. NOMENCLATURE OF THE UNIT...3 3. FUNCTION...3 4. PRODUCT DATA...4 CONTROL...10 1. WIRELESS REMOTE CONTROLLER...10

More information

Horizontal Water Source Heat Pumps And Cooling Only Unit

Horizontal Water Source Heat Pumps And Cooling Only Unit MWH-B-2005 Horizontal Water Source Heat Pumps And Cooling Only Unit Models: MWH MWH MWH MWH MWH 011 B/BR MWH 012 B/BR MWH 015 B/BR MWH 020 B/BR MWH 025 B/BR MWH 030 B/BR 040 B/BR 050 B/BR 060 B/BR 070

More information

Engineering Data Book

Engineering Data Book 40VMV Vertical Air Handling Indoor Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs

More information

1. Features Specification Dimensions Refrigeration cycle diagram Operation limits

1. Features Specification Dimensions Refrigeration cycle diagram Operation limits GLORY (ECO) STAR SERIES 1. Features 60 2. Specification 61 61 3. Dimensions 67 67 4. Refrigeration cycle diagram 70 70 5. Operation limits 71 6. Wiring diagram 72 7. Troubleshooting 80 8. Electronic function

More information

January Engineering Data RXSQ24-60TAVJU. Heat Pump 208/230V / 60 Hz / 1 ph. Presales Manual DAIKIN NORTH AMERICA LLC

January Engineering Data RXSQ24-60TAVJU. Heat Pump 208/230V / 60 Hz / 1 ph. Presales Manual DAIKIN NORTH AMERICA LLC January 2018 Engineering Data RXSQ24-60TAVJU Heat Pump 208/230V / 60 Hz / 1 ph Presales Manual DAIKIN NORTH AMERICA LLC DAIKIN NORTH AMERICA LLC RXSQ_TAVJU VRV LIFE TM Heat Pump Unit Contents 1. Features

More information

SKM. Air Conditioners TROPICAL

SKM. Air Conditioners TROPICAL SKM Air Conditioners TROPICAL 2 SKM Built in the Gulf for the world Foreword early 1974, SKM commissioned pilot production of air conditioning and refrigeration equipment using British and American product

More information

Engineering Data Book

Engineering Data Book 40VML Low Static Ducted Indoor Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without

More information

Air Conditioner Service Manual

Air Conditioner Service Manual Air Conditioner Service Manual Большая библиотека технической документации http://splitoff.ru/tehn-doc.html каталоги, инструкции, сервисные мануалы, схемы. 2 MODEL: AC-S13CEGL1 3 CONTENTS TECHNICAL SPECIFICATION...

More information

LOW STATIC HYDRONIC DUCTED UNIT

LOW STATIC HYDRONIC DUCTED UNIT LOW STATIC HYDRONIC DUCTED UNIT PDWA-~AC SERIES PDWA(4R)-~-V-MEDC PDWA(4R)-~-V-MEEU PDWA(R)-~-V PDWA(R+1)-~-P Model cooling capacity( KW) at Medium Speed cooling capacity (KW) at Medium Speed cooling capacity

More information

Air Conditioner Service Manual

Air Conditioner Service Manual Air Conditioner Service Manual Большая библиотека технической документации http://splitoff.ru/tehn-doc.html каталоги, инструкции, сервисные мануалы, схемы. 2 MODEL: AC-S7HGB 3 CONTENTS TECHNICAL SPECIFICATION..4

More information

Service Manual & Installation Manual

Service Manual & Installation Manual GE Consumer & Industrial Appliances Service Manual & Installation Manual Split System Air Conditioner Model numbers: GE AIR F24 GE AIR F34 GE AIR F41 1 2 3 Introduction and Features Model Remarks GE AIR

More information

Ultimate VRF System R410A, 50Hz

Ultimate VRF System R410A, 50Hz Ultimate VRF System R410A, 50Hz TVR WIZ Systems, a new leap in technology and innovation A proven solution from a trusted advisor Trane is proud to present their new line of variable refrigerant systems,

More information

Midea Ducted and Cassette Split Systems. Year round comfort, all around the house.

Midea Ducted and Cassette Split Systems. Year round comfort, all around the house. Midea Ducted and Cassette Split Systems Year round comfort, all around the house. Year round comfort, all around the house A Midea ducted inverter system puts total climate control right at your fingertips.

More information

Wall Mounted Split Systems

Wall Mounted Split Systems MWM - 2005 Wall Mounted Split Systems Models: MWM 007F/FR MWM 010F/FR MWM 015F/FR MWM 020F/FR MWM 025F/FR MWM 030F/FR Contents Features... 1 Nomenclature... 2 Specifications... 3 Performance Table... 11

More information

Blanc ON-OFF Series. Service Manual 2016

Blanc ON-OFF Series. Service Manual 2016 Blanc ON-OFF Series Service Manual 2016 MSMA1A-07HRN1 / MOAB02-07HN1 MSMA1A-09HRN1 / MOAB02-09HN1 MSMA1B-12HRN1 / MOBA01-12HN1 MSMA1C-18HRN1 / MOBA03-18HN1 MSMA1D-24HRN1 / MOCA02-24HN1 1 Blanc On-off DM16-01.01.07en

More information

Technical Guide. Split Air-Conditioners Equipment Residential COS Series

Technical Guide. Split Air-Conditioners Equipment Residential COS Series Technical Guide Split Air-Conditioners Equipment Residential COS Series TECHNICAL GUIDE SPLIT AIR-CONDITIONERS EQUIPMENT Thank you for choosing our products Note: Technical information contained in this

More information

R410A VRF Indoor Unit 50Hz AC Series

R410A VRF Indoor Unit 50Hz AC Series Commercial Air Conditioners 2016 Commercial Air Conditioner Division Midea Group R410A VRF Indoor Unit 50Hz AC Series Midea CAC After-service Application Midea CAC News Application Add.: West Region of

More information

FAN COIL USER MANUAL TC18C2DWB1 TC24C2DWB1 TC37C2DWB1 TC48C2DWB1 TC60C2DWB Innovair Corporation. All Rights Reserved.

FAN COIL USER MANUAL TC18C2DWB1 TC24C2DWB1 TC37C2DWB1 TC48C2DWB1 TC60C2DWB Innovair Corporation. All Rights Reserved. FAN COIL USER MANUAL TC18C2DWB1 TC24C2DWB1 TC37C2DWB1 TC48C2DWB1 TC60C2DWB1 Duct Type 1. Features...7 2. Dimensions...8 3. Service Space...9 4. Wiring Diagrams...10 5. Capacity Tables...11 6. Capacity

More information

Submittal Sheet AIR-CON MULTI-SPLIT II. High-Wall Cassette Duct Floor and Ceiling AMTCM4H4R18

Submittal Sheet AIR-CON MULTI-SPLIT II. High-Wall Cassette Duct Floor and Ceiling AMTCM4H4R18 Submittal Sheet Submitted for: Approval Record Job Name: Contractor: Engineer: Date: Location: Tag: AIR-CON MULTI-SPLIT II Indoor Units Outdoor Unit High-Wall Cassette Duct Floor and Ceiling AMTCM4H4R18

More information

Your Climate. We're There. TM: MDB B 2140B. Ducted Split Systems. Models: MDB 075B - MDB750B MDB 075B/B - MDB500BR. Air Conditioning REGISTERED

Your Climate. We're There. TM: MDB B 2140B. Ducted Split Systems. Models: MDB 075B - MDB750B MDB 075B/B - MDB500BR. Air Conditioning REGISTERED Your Climate. We're There. TM: MDB B 2140B Ducted Split Systems Models: MDB 075B - MDB750B MDB 075B/B - MDB500BR REGISTERED Air Conditioning Contents Nomenclature System... 2 Features... 2 General Specifications...3-5

More information

Multi Inverter Air Conditioning Condensing Units - Summary

Multi Inverter Air Conditioning Condensing Units - Summary Multi Inverter Air Conditioning Condensing Units - Summary Model Description Nominal Max of Cooling Inverter No. Heating of (kw) Fan Condensing (kw) Coils Unit ECO18MS2 Twin Multi Inverter 5kW 5.2 6.1

More information

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw) FALCON Rooftop Units ACPSE 50/60Hz Cooling : 36 to 1388 MBH (11 to 407 ) Heating : 40 to 1298 MBH (12 to 380 ) R Products that perform...by people who care NOMENCLATURE 6 AC P S E 435 P - HP G Q 6-60 Hz

More information

Hi - Wall Split Systems. Super Quiet. Auto. Mode. Wireless Control. Smart Airflow ECO ECO. Function SLEEP. Vertical Auto Swing.

Hi - Wall Split Systems. Super Quiet. Auto. Mode. Wireless Control. Smart Airflow ECO ECO. Function SLEEP. Vertical Auto Swing. R407C 220-240V ~, 50Hz Hi - Wall Split Systems Technology Tropical Compressor Super Quiet Auto Mode Auto Restart Easy Flexible Installation IAQ Anti-dust Filters AMS AMS Wireless Control Independent Dehumidification

More information

Service Manual & Installation Manual

Service Manual & Installation Manual GE Consumer & Industrial Appliances Service Manual & Installation Manual Split System Air Conditioner Model numbers: GE AIR C18 GE AIR C24 GE AIR C34 GE AIR C41 1 Introduction and Features Model Remarks

More information

SUBMITTAL M4MLW1809A-SUB-1A. Specifications 18 SERIES. Single Zone Mini-Split Inverter System M4MLW1809A1N0A M4TLS1809A11NA TAG:

SUBMITTAL M4MLW1809A-SUB-1A. Specifications 18 SERIES. Single Zone Mini-Split Inverter System M4MLW1809A1N0A M4TLS1809A11NA TAG: M4MLW1809A-SUB-1A TAG: 18 SERIES SUBMITTAL Specifications Single Zone Mini-Split Inverter System M4MLW1809A1N0A M4TLS1809A11NA MODEL - Heat Pump Only RATED Volts/PH Frequency (Hz) Rated Cooling / Heating

More information

Multi Splits Series. DKH Indoor Units DBC Indoor Units DAQ Indoor Units DCD Indoor Units Outdoor Units JOSI-DKH009-N11

Multi Splits Series. DKH Indoor Units DBC Indoor Units DAQ Indoor Units DCD Indoor Units Outdoor Units JOSI-DKH009-N11 Multi Splits Series DKH Indoor Units DBC Indoor Units DAQ Indoor Units DCD Indoor Units Outdoor Units JOSI-DKH009-N11 JOAU-ZCY218-H11 JOSI-DKH012-N11 JOSI-DBC012-N11 JOSI-DAQ012-N11 JOSI-DCD012-N11 JOAU-ZCY327-H11

More information

Split Type Air Conditioners FTNE-M Series Cooling Only [50 Hz]

Split Type Air Conditioners FTNE-M Series Cooling Only [50 Hz] PCRHK1543 Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical

More information

Midea Ducted and Cassette Split Systems. Maximum versatility, maximum value.

Midea Ducted and Cassette Split Systems. Maximum versatility, maximum value. Midea Ducted and Cassette Split Systems Maximum versatility, maximum value. Year round comfort, all around the house A Midea ducted inverter system puts total climate control right at your fingertips.

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASY9USCCW ASY9USCCW ASY12USCCW Outdoor unit AOY9USCC AOY9UFCC AOY12USCC CONTENTS SPECIFICATIONS................................... 1

More information

SUBMITTAL M4MCW1509A-SUB-1C. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG:

SUBMITTAL M4MCW1509A-SUB-1C. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG: M4MCW1509A-SUB-1C TAG: 15 SERIES SUBMITTAL Specifications Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA MODEL - Cooling Only RATED Volts/PH Frequency (Hz) Rated Cooling Capacity

More information

WORLD LARGEST Air Conditioners Manufacturer PRODUCT CATALOGUE GREE MALAYSIA SDN BHD ( M)

WORLD LARGEST Air Conditioners Manufacturer PRODUCT CATALOGUE GREE MALAYSIA SDN BHD ( M) WORLD LARGEST Air Conditioners Manufacturer PRODUCT CATALOGUE GREE MALAYSIA SDN BHD (1132718-M) WALL MOUNTED SPLIT UNIT LOMO N Series WALL MOUNTED SPLIT UNIT R410A Eco-friendly Refrigerant Quiet Fast Cooling

More information

MODEL: ACWD CEILING CONCEALED Chilled Water Fan Coils Unit

MODEL: ACWD CEILING CONCEALED Chilled Water Fan Coils Unit MODEL: ACW200D ACW300D ACW400D ACW500D ACW600D ACW800D ACW900D ACW1000D ACW1200D ACW1400D ACWD-2006 ACWD_2006_Cover.indd 1 CEILING CONCEALED Chilled Water Fan Coils Unit 2006-5-25 17:24:07 Contents Main

More information

R22 air-cooled modular chiller 50Hz unit. Content

R22 air-cooled modular chiller 50Hz unit. Content Content 1.Nomenclature... 2 2.Product Schedule... 2. External Appearance... 4.Features... 4 5.Specification... 6 6.Dimension... 10 7.Refrigeration System Sketch Drawing... 14 8.Wiring Diagrams... 16 9.Electric

More information

MVD. Cassette 4 Ways FCU DC Service manual MUCS-W7. CL04417 to CL04419 English.

MVD. Cassette 4 Ways FCU DC Service manual MUCS-W7. CL04417 to CL04419 English. MVD Cassette 4 Ways FCU DC Service manual MUCS-W7 www.mundoclima.com CL04417 to CL04419 English 4-way cassette 1. External Appearance... 2 2. Features... 2 3. Product lineup... 3 4. Accessories... 4 5.

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A09LEC AS A12LEC OUTDOOR AO R09LECN AO R12LECN 1.INDOOR UNIT : AS A09LEC AS A12LEC DTR_AS047E_01 2010.10.05 1. INDOOR UNIT CONTENTS

More information

Midea Precision Air Conditioner Technical Manual (Down delivery series)

Midea Precision Air Conditioner Technical Manual (Down delivery series) Midea Precision AC Technical Manual-Down Delivery Series MCAC-RTSM-2013-04 Midea Precision Air Conditioner Technical Manual (Down delivery series) Midea reserves the right to discontinue, or change specification

More information

MHH. 13 SEER High Efficiency R410a. SPECIFICATION sheet

MHH. 13 SEER High Efficiency R410a. SPECIFICATION sheet Air Conditioning and Heating SPECIFICATION sheet MHH 13 SEER High Efficiency R410a Split System Heat Pump Standard features: R410a system High efficiency compressor Compact design for easy installation

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG18KLCA ASYG24KLCA OUTDOOR AOYG18KLTA AOYG24KLTA DR_AS069EF_01 2018.03.16 Notices: Product specifications and design are subject to

More information

Multi Split Systems. Reverse Cycle, Inverter Air Conditioner. Exclusively distributed by

Multi Split Systems. Reverse Cycle, Inverter Air Conditioner. Exclusively distributed by Multi Split Systems Reverse Cycle, Inverter Air Conditioner Exclusively distributed by AUS 13 23 50 www.lennoxaus.com.au NZ 0800 653 330 www.lennoxnz.co.nz 1 As a global leader in comfort solutions, Lennox

More information

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw) High Ambient / High Efficiency Series R - 410a 50Hz Ducted Split Air Conditioners (5.0 kw - 17.5 kw) ISO 9001 : 2008 ISO 14001 : 2004 ISO 18001 : 2007 R - 410a 50Hz Introduction: Established in the year

More information

turn to the experts R 410A DC INVERTER LIGHT COMMERCIAL SERIES

turn to the experts R 410A DC INVERTER LIGHT COMMERCIAL SERIES turn to the experts SM R 410A DC INVERTER LIGHT COMMERCIAL SERIES DC Inverter Technology More Economical Energy Efficient Once indoor air temperatures reach your desired levels, inverter driven air-conditioners

More information

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED EQV R-407C WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED Size Cooling Heating [kw] [kw] 5 1,9 2,2 7 2,4 2,5 9 2,6 2,5 15 3,3 3,2 17 3,7 3,7 REPLACE: BT02E008GB-01 The Versatemp EQV units

More information

CASSETTE type INVERTER MULTI AIR CONDITIONER. Models AUY12LBAB AUY14LBAB AOY18LMAK2

CASSETTE type INVERTER MULTI AIR CONDITIONER. Models AUY12LBAB AUY14LBAB AOY18LMAK2 INVERTER MULTI AIR CONDITIONER CASSETTE type Models Indoor unit AUY12LBAB AUY14LBAB Outdoor unit AOY18LMAK2 CONTENTS SPECIFICATIONS..................... 1 OUTLINE AND DIMENSIONS........... 2 REFRIGERANT

More information

SUBMITTAL M4MCW1509A-SUB-1B. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG:

SUBMITTAL M4MCW1509A-SUB-1B. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG: M4MCW1509A-SUB-1B TAG: 15 SERIES SUBMITTAL Specifications Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA MODEL - Cooling Only RATED Volts/PH Frequency (Hz) Rated Cooling Capacity

More information

Midea R410A Domestic Pools & Spas Heat Pump Water Heater 50Hz A1 Series Technical Manual

Midea R410A Domestic Pools & Spas Heat Pump Water Heater 50Hz A1 Series Technical Manual Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas Heat Pump Water Heater 50Hz A1 Series Technical Manual Applicable Model: (New CE safety directive)

More information

DC INVERTER SERIES. Service Manual 2013 LIS-E-1312

DC INVERTER SERIES. Service Manual 2013 LIS-E-1312 DC INVERTER SERIES Service Manual 2013 LIS-E-1312 Contents Part 1 General Information... 1 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 65 Part 4 Installation... 74 Part 5 Electrical Control System...

More information

Commercial Air Conditioners 2017/2018. VRF 50/60Hz. V5 X Series

Commercial Air Conditioners 2017/2018. VRF 50/60Hz. V5 X Series Commercial Air Conditioners 2017/2018 VRF 50/60Hz V5 X Series Midea CAC Midea CAC is a key division of the Midea Group, a leading producer of consumer appliances and provider of heating, ventilation and

More information

SUBMITTAL M4MHW1509A-SUB-1B. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MHW1509A1N0A M4THS1509A11NA TAG:

SUBMITTAL M4MHW1509A-SUB-1B. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MHW1509A1N0A M4THS1509A11NA TAG: M4MHW1509A-SUB-1B TAG: 15 SERIES SUBMITTAL Specifications Single Zone Mini-Split Inverter System M4MHW1509A1N0A M4THS1509A11NA 2017 Ingersoll Rand All Rights Reserved MODEL - Heat Pump Only RATED Volts/PH

More information