1 Welcome to the Ice-O-Matic on-line training modules. Ice. Pure and Simple
2 DIAGSING FREEZE-UP ISSUES This module will help in diagnosis of a freeze up should it occur on various models of ICE Series Cubers. This module defines a freeze up as the unit never entering defrost, stays too long in the freeze cycle creating blocks of ice or enters defrost then leaves without harvesting the ice.
3 R-1 Relay Coil Timer Initiate Control Solid State Timer Delay First, let s do a brief review of the sequence of operation for the 150 pound through 1000 pound production units. The Low Pressure Timer Initiate controls the untimed portion of the freeze cycle. The LPTI closes on pressure drop, energizing the Timer. The Timer will continue the freeze cycle for the length of time it is set for, controlling the bridge thickness, then closes. This energizes the Relay, sending the unit into a defrost cycle.
4 In the under counter units, there is only one relay. In modular units there are 2 relays, the top of which ( Relay 1) energizes the defrost components.
5 Once the relay energizes the defrost components, the Harvest Assist Assembly controls the length of the defrost cycle. The assembly pushes the ice off of the Evaporator, then retracts to it s original position, terminating the defrost cycle and the unit re-enters freeze.
6 When diagnosing a freeze-up, it is best to start the diagnosis while the unit is still having the issue. By clearing the Evaporator, you may be hiding one of the symptoms of the problem, thereby delaying the diagnosis.
7 How to check LP Control with Ice on the Evaporator Ice. Pure and Simple The diagnosis would start by checking the status of the LPTI. The LPTI can be checked while the unit is in freeze by placing your meter across the terminals of the control. If line voltage is displayed on your meter, the control is open. If no voltage is displayed, the control is closed or no voltage is applied to it. The Timer can also be checked in the same manner once the LPTI closes.
8 How to check LP Control with No Ice on the Evaporator Ice. Pure and Simple To check the set point of the LPTI, start by turning the unit off after a harvest. Unplug the Water Pump and set the Timer to 1 second. Now turn the selector switch to ICE. With no load on the Evaporator the suction pressure will drop quickly. Watch your suction gauge. When the LPTI reaches it s set point, it will close, energizing the Timer for only one second. The Timer will then close, starting the defrost. With the opening of the Hot Gas Valve the suction pressure will begin to rise. The lowest pressure shown on your gauge before the suction rises IS the set point of the LPTI. Verify this set point with the chart in the Technical Service Manual.
9 The following slides will examine freeze up issues related to the control circuit.
10 1 Evap Modular Units LPTI WON T CLOSE The unit is unable to enter defrost. Relay 2 Coil WASH Water Pump ICE Cam SW Relay 1-A Purge Valve Contactor Harvest Motor Purge SW Hot Gas Relay 1-B LP Control Timer Relay 1 Coil Relay 1-B Fan Bin Fill Switch ICE Fan Cycle Control Relay-2 HP Control High Temperature Safety Contactor Coil POWER SUPPLY
11 1 Evap Modular Units TIMER WON T CLOSE The unit is unable to enter defrost. Relay 2 Coil WASH Water Pump ICE Cam SW Relay 1-A Purge Valve Contactor Harvest Motor Purge SW Hot Gas Relay 1-B LP Control Timer Relay 1 Coil Relay 1-B Fan Bin Fill Switch ICE Fan Cycle Control Relay-2 HP Control High Temperature Safety Contactor Coil POWER SUPPLY
12 1 Evap Modular Units OPEN COIL ON RELAY 1 Relay 2 Coil The Purge Valve will open, but the unit will not energize the Hot Gas Valve or the Harvest Assist Assembly. The unit will not harvest the ice. WASH ICE Cam SW Water Pump Relay 1-A Purge Valve Contactor Harvest Motor Purge SW Hot Gas Relay 1-B LP Control Timer Relay 1 Coil Relay 1-B Fan Bin Fill Switch ICE Fan Cycle Control Relay-2 HP Control High Temperature Safety Contactor Coil POWER SUPPLY
13 1 Evap Modular Units OPEN COIL ON HOT GAS VALVE The Hot Gas Valve will not open and with the opening of the contacts of Relay 1, the Fan Motor will shut off. The unit will eventually go off on high head pressure without harvesting the ice. WASH ICE Cam SW Relay 2 Coil Water Pump Relay 1-A Purge Valve Contactor Harvest Motor Purge SW Hot Relay 1-B Gas LP Control Timer Relay 1 Coil Relay 1-B Fan Bin Fill Switch ICE Fan Cycle Control Relay-2 HP Control High Temperature Safety Contactor Coil POWER SUPPLY
14 1 Evap Modular Units Contacts of Purge Sw. OPEN Relay 2 Coil If the Contacts of the Purge Sw. are opened during defrost, Relay 1 will lose power as soon as the LPTI opens, sending the unit back to freeze without harvesting. WASH ICE Cam SW Water Pump Relay 1-A Purge Valve Contactor Harvest Motor Purge SW Hot Gas Relay 1-B LP Control Timer Relay 1 Coil Relay 1-B Fan Bin Fill Switch ICE Fan Cycle Control Relay-2 HP Control High Temperature Safety Contactor Coil POWER SUPPLY
15 Intermittent Freeze Ups A possible cause of intermittent freeze ups can be the Harvest Assist Assembly motor Bumping. Inside the small motor is a ratchet that should allow the motor to turn clockwise only. If this ratchet wears or becomes displaced, the motor can turn either clockwise or counterclockwise at any time.
16 Harvest Assist Should the ratchet be worn, the motor could turn counterclockwise for a split second. The Cam Switch will ride out of the depression of the Clutch the wrong direction, closing the Normally Open contacts of the Cam Switch. The Water Pump and the Purge Valve will shut down with out purging the water. Then the ratchet could catch, forcing the motor to turn back clockwise.
17 Harvest Assist The motor will turn the Clutch back clockwise. The result will be the Cam Switch dropping back into the low side of the Clutch, re-opening the Normally Open contacts of the Cam Switch. The unit will return to the freeze cycle without harvesting the ice. The following cycles may harvest as normal. Should your unit occasionally create thick slabs of ice, replacing the Probe Motor may be in order.
18 Should the Harvest Assist Assembly become dislodged from its mounts or the Probe Shaft become disconnected from the swivel, the unit will go through a short defrost (about 30 seconds) while the Probe Motor rotates 360 degrees, then returns the unit to the freeze cycle without harvesting the ice slab.
19 The following slides will examine freeze up issues related to the refrigeration system.
20 Should a TXV fail to meter properly and is over feeding refrigerant, the suction pressure will remain elevated. This may cause the LPTI not to close if the set point can not be reached, causing a freeze up. The suction pressure should slowly, continuously and steadily drop during the freeze cycle as ice is formed on the Evaporator.
21 The same issue will be encountered if the is inefficient. The suction pressure may remain high enough that the LPTI can t close, but low enough to form ice, resulting in a freeze up. Check the s amp draw against the RLA listed on the data tag. Five minutes into the freeze cycle the amp draw should be within 10% of the RLA listed to be considered efficient.
22 A dirty or clogged Condenser or an inefficient Fan Motor can also contribute to freeze up issues by not allowing the heat exchange from the unit. Fan Motor amp draw should be verified to assure efficiency. Lack of liquid feeding the TXV can cause a freeze up. This can also be the case in an over charged system.
23 A dirty or damaged Evaporator can cause a freeze up by not allowing all the ice to be harvested from the plate. Examine the Evaporator for pitting or loose horizontal dividers, either of which can cause ice to remain on the plate. If part of the ice slab remains on the Evaporator when the unit re-enters the freeze cycle, a freeze up can be the result.
24 Should the Hot Gas Valve start leaking by, the result would be a higher suction pressure. Depending on the degree the valve is leaking, it can result in either no production of ice to slow production. If the leak is slight, it may keep the suction pressure above the set point of the LPTI, resulting in a freeze up. There should always be a marked temperature difference between the inlet and outlet of the Hot Gas Valve.
25 Diagnosing Freeze-ups Quiz
Technical Training Prodigy Undercounter Cubers. Models CU1526, CU2026 and CU3030
Technical Training Prodigy Undercounter Cubers Models CU1526, CU2026 and CU3030 List of Major Topics Introduction Installation Operation Maintenance Diagnosis Service Prodigy with a Bin 3 models CU1526
More informationProdigy Eclipse Cuber Technical Training
Prodigy Eclipse Cuber Technical Training 600 800 1000 1200 1400 1800 2000 In This Presentation What Eclipse is Components and their functions Installation Operation Maintenance Service Diagnosis The Prodigy
More informationProdigy Plus - D Series Cuber Technical Review
Prodigy Plus - D Series Cuber Technical Review Water Distributor Control Panel Air Filter ice Thickness Sensor Lower Light and Switch Panel Water Pump Water Level Sensor & Guard Curtain Switch and Magnet
More informationWarm Case Troubleshooting Guide 9/18/2014
Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last
More informationElectrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)
Electrical Problems Fuse(s) blow or circuit breaker trips Does the unit use circuit breakers or fuses? Fuse(s) Circuit breakers Are the fuses dual element time delay? Is the circuit breaker HACR rated?
More informationIMPORTANT. HOSHIZAKI provides this manual primarily to assist qualified service technicians in the service and maintenance of the icemaker.
73105 IMPORTANT Only qualified service technicians should attempt to service or maintain this icemaker. No service or maintenance should be undertaken until the technician has thoroughly read this Service
More informationEclipse Technical Training CME686 CME810 CP686 CP886 CP1086
Eclipse Technical Training CME686 CME810 CP686 CP886 CP1086 In This Presentation What Eclipse is Components and their functions Installation Operation Maintenance Service Diagnosis The Eclipse System The
More informationSERVICE PARTS MANUAL ICE SERIES CUBERS MODEL-ICE0250, ICE0400, ICE0500, ICE0606
MODEL-ICE0250, ICE0400, ICE0500, ICE0606 ICE SERIES CUBERS SERVICE PARTS MANUAL Includes 50HZ units Mile High Equipment 11100 East 45th Ave Denver, Colorado 80239 Print Date 03/03 * This parts list contains
More informationHOSHIZAKI AMERICA, INC. SERVICE BULLETIN
HOSHIZAKI AMERICA, INC. SERVICE BULLETIN Subject: E SERIES CONTROL BOARD Page 1 of 4 Beginning in February, the KM Universal Alpine replacement control board part number 2U0139-01, will sub to a new Control
More informationFLAKER/DCM SEQUENCE OF OPERATION
FLAKER/DCM SEQUENCE OF OPERATION H O S H I Z A K I A M E R I C A The Flaker and DCM series of ice machines use a completely different ice making process than the cuber style of icemaker. The Flaker has
More informationKM-630MAH KM-630MWH KM-630MRH
NO.: ISSUED: 73114 JUNE 23, 2004 HOSHIZAKI MODULAR CRESCENT CUBER MODEL KM-630MAH KM-630MWH KM-630MRH SERVICE MANUAL IMPORTANT Only qualified service technicians should attempt to service or maintain this
More informationSERVICE PARTS MANUAL ICE SERIES CUBERS MODEL-ICE0250, ICE0400, ICE0500, ICE0606 Includes 50Hz. Units
SERVICE PARTS MANUAL ICE SERIES CUBERS MODEL-ICE0250, ICE0400, ICE0500, ICE0606 Includes 50Hz. Units ICE-O-Matic 11100 East 45th Ave Denver, Colorado 80239 Part Number 9081299-01 Rev 8/08 # This parts
More informationEC Series Ice Machines
EC Series Ice Machines This manual is updated as new information and models are released. Visit our website for the latest manual. www.manitowocice.com Manitowoc Ice, Inc. P/N 80-1520-3 10/07 Safety Notices
More informationAutomatic Ice maker. Service manual MIM250
Automatic Ice maker Service manual MIM250 1 Table of contents Installation Guidelines ---------------------------------------------------------3 How the Ice Maker Works ----------------------------------------------------4
More informationCM 3 Control System Update. Prodigy Cuber. Technical Review
CM 3 Control System Update Prodigy Cuber Technical Review Prodigy Cuber - Control System The control system of this ice machine consists of a central controller, an ice thickness sensor, a water level
More informationFull Range Systems. Mokon Troubleshooting Guide Model 311. Process/Water Loop. Problem Possible Cause Corrective Measure. Process pump will not start
Mokon Troubleshooting Guide Model 311 Process pump will not start Process pump shuts down during operation Pump seal leak Tank overflows or will not fill on systems with autofill option (water makeup valve)
More informationService Manual. Modular Crescent Cuber with G Control Board
Service Manual Modular Crescent Cuber with G Control Board Model KMD-460MAH, MWH KMD-530MAH, MWH, MRH KML-250MAH, MWH KML-351MAH, MWH KML-451MAH, MWH KML-631MAH, MWH, MRH hoshizakiamerica.com Number: 73205
More informationICEMAKER FAMILIARIZTION AND TROUBLESHOOTING
CONSUMER SERVICES TECHNICAL EDUCATION GROUP PRESENTS R-106 ICEMAKER FAMILIARIZTION AND TROUBLESHOOTING TRAINING MANUAL Part No. 8178689 FORWARD The following training manual information is provided to
More informationKM-61BAH KM-101BAH KM-151BAH
NO. M006-749 ISSUED: FEB. 18, 2008 REVISED: JUN. 12, 2008 HOSHIZAKI SELF-CONTAINED CRESCENT CUBER MODEL KM-61BAH KM-101BAH KM-151BAH SERVICE MANUAL IMPORTANT Only qualified service technicians should attempt
More informationSERVICE PARTS MANUAL ICE SERIES CUBERS MODEL-ICE0806, ICE1006 Includes 50Hz. and 3 Phase Units
SERVICE PARTS MANUAL ICE SERIES CUBERS MODEL-ICE0806, ICE1006 Includes 50Hz. and 3 Phase Units ICE-O-Matic 11100 East 45th Ave Denver, Colorado 80239 Part Number 9081307-01 Rev 3/06 * This parts list contains
More informationFOR SERVICE TECHNICIAN S USE ONLY
FOR SERVICE TECHNICIAN S USE ONLY NOTE: This sheet contains important Technical Service Data. Tech Sheet Do Not Remove Or Destroy DANGER Electrical Shock Hazard Only authorized technicians should perform
More informationKM-900MAF KM-900MWF KM-900MRF KM-900MRF3
NO.: ISSUED: REVISED: 73083 MAR. 19, 1999 DEC. 15, 2003 HOSHIZAKI MODULAR CRESCENT CUBER MODELS KM-900MAF KM-900MWF KM-900MRF KM-900MRF3 SERVICE MANUAL IMPORTANT Only qualified service technicians should
More informationKML F SERIES KML H SERIES
NO.: ISSUED: REVISED: 73085 AUG. 18, 1999 JAN. 13, 2004 HOSHIZAKI MODULAR CRESCENT CUBER MODELS KML F SERIES KML H SERIES SERVICE MANUAL IMPORTANT Only qualified service technicians should attempt to service
More informationNO. F ISSUED: JUN. 18, 2008 REVISED: JUN. 17, 2011 HOSHIZAKI SELF-CONTAINED CRESCENT CUBER KM-100A KM-125A MODEL SERVICE MANUAL
NO. F003-756 ISSUED: JUN. 18, 2008 REVISED: JUN. 17, 2011 HOSHIZAKI SELF-CTAINED CRESCENT CUBER MODEL KM-100A KM-125A SERVICE MANUAL IMPORTANT This manual should be read carefully before the icemaker is
More informationService Manual. Commercial Series Refrigerated Kitchen Equipment Models Undercounter Worktop Prep Table. hoshizakiamerica.com
Service Manual Commercial Series Refrigerated Kitchen Equipment Models Undercounter Worktop Prep Table hoshizakiamerica.com Number: 73191 Issued: 9-29-2011 Revised: 9-7-2017 WARNING Only qualified service
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Modular Crescent Cuber Models KM-320MAH, MWH KM-340MAH, MWH KM-515MAH, MWH, MRH KM-600MAH KM-650MAH, MWH, MRH KM-901MAH, MWH, MRH/3 KM-1340MAH, MWH, MRH KM-1601MRH/3 A Superior
More informationHOSHIZAKI MODULAR CRESCENT CUBER MODEL KM-280MAH KM-280MWH SERVICE MANUAL
NO. 73117 ISSUED: AUG. 15, 2004 REVISED: HOSHIZAKI MODULAR CRESCENT CUBER MODEL KM-280MAH KM-280MWH SERVICE MANUAL IMPORTANT Only qualified service technicians should attempt to service or maintain this
More informationService Manual. Modular Crescent Cuber Models KM-901MAJ, MWJ, MRJ/3 KM-1100MAJ, MWJ, MRJ KM-1340MAJ, MWJ, MRJ/3 KM-1601MRJ/3. hoshizakiamerica.
Service Manual Modular Crescent Cuber Models KM-901MAJ, MWJ, MRJ/3 KM-1100MAJ, MWJ, MRJ KM-1340MAJ, MWJ, MRJ/3 KM-1601MRJ/3 hoshizakiamerica.com Number: 73213 Issued: 1-30-2018 Revision: 3-13-2018 WARNING
More informationNUMBER: ISSUED: JULY 13, /336 73/23 STACKABLE CRESCENT CUBER KM-1300SWH-E SERVICE MANUAL FOR QUALIFIED SERVICE PERSON HOSHIZAKI
89/336 73/23 NUMBER: 73141 ISSUED: JULY 13, 2006 STACKABLE CRESCENT CUBER KM-1300SWH-E SERVICE MANUAL FOR QUALIFIED SERVICE PERSON HOSHIZAKI IMPORTANT Only qualified service technicians should attempt
More informationSERVICE PARTS MANUAL. The ICE Series Undercounter Cubers MODEL-ICEU300, ICEU305
SERVICE PARTS MANUAL The ICE Series Undercounter Cubers MODEL-ICEU300, ICEU305 ICE-O-Matic Print Date 04/05 11100 East 45th Ave Denver, Colorado 80239 Part Number 9081332-01 * This parts list contains
More informationTable of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)
Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High
More informationService Manual. Modular Crescent Cuber Models KM-1301SAJ-E. hoshizakiamerica.com
Service Manual Modular Crescent Cuber Models KM-1301SAJ-E hoshizakiamerica.com Number: 73233 Issued: 9-28-2018 WARNING Only qualified service technicians should install and service the icemaker. To obtain
More informationPeachtree City is home office for America located about 30 miles south of the Atlanta airport this is were all KM cubers as well as Flakers are built.
The following slides are designed to give you good understanding of the KM sequence of operation. You will find the sequence explained in two ways the first is a basic explanation that goes along with
More informationSERVICE MANUAL ICEU 125 ICEU 175. Electronic cubers with storage. Version: 2010/2
SERVICE MANUAL ICEU 125 ICEU 175 Electronic cubers with storage Version: 2010/2 Page 2 Table of contents page 2 Specifications ICEU125 3 Specifications ICEU175 5 GENERAL INFORMATION AND INSTALLATION Introduction
More informationUPM I. Unit Protection Module. Installation and Operation Manual (2015/06)
UPM I Unit Protection Module Installation and Operation Manual 6 720 220 321(2015/06) 2 Key to Symbols Contents Key To Symbols...2 Warnings...2 Specifications... 3 Unit Protection Module (UPM)....3 Power
More informationReliability is a beautiful thing TM MODULAR CRESCENT CUBER KM-500MAH KM-500MWH KM-500MRH SERVICE MANUAL
Reliability is a beautiful thing TM MODULAR CRESCENT CUBER KM-500MAH KM-500MWH KM-500MRH SERVICE MANUAL NUMBER: 73104 ISSUED: NOV. 7, 2002 REVISED: DEC. 16, 2003 IMPORTANT Only qualified service technicians
More informationSERVICE MANUAL FOR QUALIFIED SERVICE PERSON HOSHIZAKI 89/336 73/23 SELF-CONTAINED CRESCENT CUBER KM-150BAF-E KM-150BWF-E
89/336 73/23 NUMBER: 73108 ISSUED: APRIL 19, 2000 REVISED: JAN. 13, 2004 SELF-CONTAINED CRESCENT CUBER KM-150BAF-E KM-150BWF-E SERVICE MANUAL FOR QUALIFIED SERVICE PERSON HOSHIZAKI IMPORTANT Only qualified
More informationFOR SERVICE TECHNICIAN S USE ONLY
F SERVICE TECHNICIAN S USE ONLY NOTE: This sheet contains important Technical Service Data. Tech Sheet Do Not Remove Or Destroy DANGER Electrical Shock Hazard Only authorized technicians should perform
More informationCondensing Unit Installation and Operating Instructions
Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.
More informationKM-630MAF KM-630MWF KM-630MRF
NO.: 73082 ISSUED: MAR. 19, 1999 REVISED: DEC. 15, 2003 HOSHIZAKI MODULAR CRESCENT CUBER MODEL KM-630MAF KM-630MWF KM-630MRF SERVICE MANUAL IMPORTANT Only qualified service technicians should attempt to
More informationMotor Vehicle Air Conditioning (MVAC) System operation and the refrigerant cycle
Motor Vehicle Air Conditioning (MVAC) System operation and the refrigerant cycle At Sea level water boils at 212⁰ F R 134a boils at 15⁰ F At Sea level R 134a boils at 15⁰ F At 30 psig R 134a boils at 35⁰
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Stackable Crescent Cuber Models KM-1301SAH/3, SWH/3, SRH/3 KM-1400SWH-M, SWH3-M KM-1601SAH/3, SWH/3, SRH/3 KM-1900SAH/3, SWH/3, SRH/3 KM-2100SWH3, SRH3 KM-2500SWH3, SRH3 KMH-2000SWH/3,
More informationA/C-HEATER SYSTEM - MANUAL
A/C-HEATER SYSTEM - MANUAL 1986 Isuzu Trooper II 1986 A/C-HEATER SYSTEM Isuzu A/C-Heater Systems - Manual P UP, Trooper II * PLEASE READ THIS FIRST * CAUTION: When discharging air conditioning system,
More informationService Manual for Cuber Model CS0415
for Cuber Model Introduction This is the service manual for the ice machine. Note and heed any warning symbols where they appear. Basic installation information is provided, however the installation manual
More informationTrouble Shooting Guide FAA, 3-phase (D3631)
Trouble Shooting Guide FAA, 3-phase (D3631) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage tripped Loose
More informationNO. 15FD-742 ISSUED: AUG. 10, 2007 REVISED: SEP. 30, 2013 HOSHIZAKI SELF-CONTAINED CRESCENT CUBER KM-30A KM-35A KM-50A KM-75A MODEL SERVICE MANUAL
NO. 15FD-742 ISSUED: AUG. 10, 2007 REVISED: SEP. 30, 2013 HOSHIZAKI SELF-CONTAINED CRESCENT CUBER MODEL KM-30A KM-35A KM-50A KM-75A SERVICE MANUAL CONTENTS PAGE I. SPECIFICATIONS--------------------------------------------------------------------------------------1
More informationTable of Contents SPECIFICATIONS Page 2. FOR THE INSTALLER Page 3. FOR THE PLUMBER Page 4. INSTALLATION Page 5. INITIAL START UP Page 6
INTRODUCTION This service manual covers the installation, operation, maintenance and service of this ice machine. Table of Contents SPECIFICATIONS Page 2 FOR THE INSTALLER Page 3 FOR THE PLUMBER Page 4
More informationNO. F ISSUED: JUN. 15, 2009 REVISED: HOSHIZAKI MODULAR CRESCENT CUBER KMD-201AA KMD-201AWA MODEL SERVICE MANUAL
NO. F037-775 ISSUED: JUN. 15, 2009 REVISED: HOSHIZAKI MODULAR CRESCENT CUBER MODEL KMD-201AA KMD-201AWA SERVICE MANUAL CONTENTS PAGE I. SPECIFICATIONS ---------------------------------------------------------------------------------------
More informationInstallation Manual BCS2000/3000
Installation Manual BCS2000/3000 Supplies Needed for Installation 1. 3/8 and 5/8 copper tubing. 2. 1/4 copper water supply 3. 1/4 condensate vinyl drain tube/tube clamps 4. Provide 120v 15A circuit for
More informationProdigy and Prodigy Plus Flaked and Nugget Modular Ice Machines. and Prior
Prodigy and Prodigy Plus Flaked and Nugget Modular Ice Machines and Prior Quick Review: What is a flaker? A continuous flow ice machine Vertical, water filled, refrigerated cylinder With internal CCW 11
More informationSERVICE PARTS MANUAL MODEL-ICE1405, ICE1406 and ICE1407 Version 3 Includes 50Hz.and 3 phase Units
SERVICE PARTS MANUAL MODEL-ICE1405, ICE1406 and ICE1407 Version 3 Includes 50Hz.and 3 phase Units Ice-O-Matic 11100 East 45th Ave Denver, Colorado 80239 Part Number 9081375-01 Date 7/10 SERVICE PARTS MANUAL
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Low-Profile Modular Crescent Cuber Models KML-631MAH KML-631MWH KML-631MRH A Superior Degree of Reliability SERVICE MANUAL www.hoshizaki.com Number: 73150 Issued: 5-9-2007 Revised:
More informationTEMPERATURE & PRESSURE CONTROLS
TEMPERATURE & PRESSURE CONTROLS RANCO LUBE OIL PROTECTION CONTROLS These lube oil protection controls guard pressure-lubricated refrigeration compressors against major damage due to loss of oil pressure.
More informationInstallation Manual BCS 1000/1500
Installation Manual BCS 1000/1500 Supplies Needed for Installation 1. Double insulated refrigerant line set. 2. 1/4 copper water supply 3. 1/4 condensate vinyl drain tube/tube clamps 4. Provide 120V 15A
More informationDOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee Phone (931)
DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee 37091 Phone (931) 359-6211 1-800-251-8990 www.doleref.com PHO WATER DEFROST OPERATION & MAINTENANCE MANUAL June 2002 PHO WATER DEFROST Table
More informationSERVICE PARTS MANUAL MODELS-ICE1806 and ICE1807 Version 4-5 MODELS-ICE2106 and ICE2107 Version 4-5 Includes 3 Phase Units
SERVICE PARTS MANUAL MODELS-ICE1806 and ICE1807 Version 4-5 MODELS-ICE2106 and ICE2107 Version 4-5 Includes 3 Phase Units Ice-O-Matic 11100 East 45th Ave Denver, Colorado 80239 Part Number 9081376-02 Date
More informationFOR SERVICE TECHNICIAN S USE ONLY
F SERVICE TECHICIA S USE OY TE: This sheet contains important Technical Service Data. Tech Sheet Do ot Remove Or Destroy DAGER Electrical Shock Hazard Only authorized technicians should perform diagnostic
More informationTrouble Shooting Guide PWA, 3-phase (D10571)
Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage Loose wire
More informationF-2000MLF(-C) F-2000MWF(-C) F-2000MRF(-C) F-2000MRF3(-C)
NO: 73099 ISSUED: AUG. 29, 2001 REVISED: DEC. 16, 2003 HOSHIZAKI MODULAR FLAKER MODEL F-2000MLF(-C) F-2000MWF(-C) F-2000MRF(-C) F-2000MRF3(-C) SERVICE MANUAL IMPORTANT Only qualified service technicians
More informationPURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN
VALVES VESSELS SYSTEMS CONTROLS PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN System drawings shown in this bulletin are for illustration purposes only. Refrigeration systems
More informationCME865R & CME1002R INTRODUCTION. Table of Contents
INTRODUCTION This manual is intended as a reference for the installation and service of a Scotsman ice maker model CME865R or CME1002R. This model is a remote condenser cuber, 30" wide and should be connected
More informationItem RED=NLA-NR=No Longer Available-No Replacement Code Part Description Part Number GRP
5.0 CUBERS C136-C186 "B" SERIES AIR, WATER AND REMOTE Code Part Description Part Number GRP 136 186 AIR COOLED 5 Air Condenser 9141064-01 AC X 10 Fan Blade 10" 9131053-01 AC X 15 Fan Motor 35 watt 9161124-03
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Modular Flaker Models F-2000MWH(-C) F-2000MRH(-C) F-2000MRH3(-C) F-2000MLH(-C) A Superior Degree of Reliability SERVICE MANUAL www.hoshizaki.com Number: 73116 Issued: 7-16-2004
More informationELECTROMECHANICAL AND ELECTRONIC ICE CUBER
ELECTROMECHANICAL AND ELECTRONIC ICE CUBER SERVICE MANUAL 1525 East Lake Road, Erie, PA 16511-1088 814/453-6761 FAX 814/455-6336 A Tradition of Excellence In Ice Equipment. 2004 KDIndustries, Inc., Erie,
More informationProdigy Flaked and Nugget Ice Machines Technical Review
CM 3 Control System Update Prodigy Flaked and Nugget Ice Machines Technical Review Evaporator Assembly Behind Ice Chute Assembly Fan Blade Control Panel Water Reservoir Air Filter Compressor Ice Chute
More informationService Manual. hoshizakiamerica.com
Service Manual Modular Crescent Cuber Models KM-1301SAJ/3, SWJ/3, SRJ/3 KM-1601SAJ/3, SWJ/3, SRJ/3 KM-1900SAJ/3, SWJ/3, SRJ/3 KM-2200SWJ3, SRJ3 KM-2600SWJ3, SRJ3 hoshizakiamerica.com Number: 73216 Issued:
More informationOPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER
OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001927 Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1 1.0 SCOPE: This
More informationT-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N
T-SERIES Air Conditioner T50 Model INSTRUCTION MANUAL Rev. F P/N 10-1008-203 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Low-Profile Modular Crescent Cuber Models KML-351MAH KML-351MWH A Superior Degree of Reliability SERVICE MANUAL www.hoshizaki.com Number: 73149 Issued: 6-10-2008 IMPORTANT Only
More informationService Manual. Self-Contained Crescent Cuber Models KM-230BAJ KM-300BAJ, BWJ. hoshizakiamerica.com
Service Manual Self-Contained Crescent Cuber Models KM-230BAJ KM-300BAJ, BWJ hoshizakiamerica.com Number: F111-1006 Issued: 03-15-2018 WARNING Only qualified service technicians should install and service
More informationV-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N
V-SERIES Air Conditioner VA08 Model INSTRUCTION MANUAL Rev. F P/N 90164959 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3
More informationOwners Manual Refrigerated Air Dryer MHT SERIES
Owners Manual Refrigerated Air Dryer MHT SERIES IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS IN- FORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILAR WITH THE PROPER INSTALLATION
More informationTrouble Shooting Guide RAA, 1-phase (D3627)
Trouble Shooting Guide RAA, 1-phase (D3627) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage tripped Loose
More informationTrouble Shooting Guide PAA, 1-phase (D3731)
Trouble Shooting Guide PAA, 1-phase (D3731) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage tripped Loose
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Modular Crescent Cuber Models KM-515MAH KM-515MWH KM-515MRH A Superior Degree of Reliability SERVICE MANUAL www.hoshizaki.com 1 Number: 73157 Issued: 2-1-2008 IMPORTANT Only qualified
More informationSPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N
SPECTRACOOL Air Conditioner N21 Model INSTRUCTION MANUAL Rev. G P/N 89115088 TABLE OF CONTENTS WARRANTY AND RETURN POLICY...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3
More informationLiebert InteleCool Warranty Inspection Check Sheet
The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer _ Address Owner Address Owner e-mail address Installation
More informationT-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N
T-SERIES Air Conditioner T20 Model INSTRUCTION MANUAL Rev. C P/N 89114993 TABLE OF CONTENTS Warranty and Return Policy... 2 IMPORTANT NOTICE... 2 RECEIVING THE AIR CONDITIONER... 3 HANDLING AND TESTING
More informationKM-1600MRF KM-1600MRF3
NO.: ISSUED: REVISED: 73078 FEB. 19, 1999 DEC. 13, 2003 HOSHIZAKI MODULAR CRESCENT CUBER MODEL KM-1600MRF KM-1600MRF3 SERVICE MANUAL IMPORTANT Only qualified service technicians should attempt to service
More informationENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL
ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001829 OPERATIONS AND MAINTENANCE MANUAL Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1.0 SCOPE: This Operations and Maintenance
More informationT-Series Air Conditioner T53 Model
INSTRUCTION MANUAL T-Series Air Conditioner T53 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200
More informationT-Series Air Conditioner T15 Model
INSTRUCTION MANUAL T-Series Air Conditioner T15 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200
More informationCourse ID #ICE2121. Script Notes: MKC ICE, Training Development. 1/10/2017wy
Course ID #ICE2121 Script Notes: MKC ICE, Training Development 1/10/2017wy Page 1 of 19 Table of Contents Lesson 1 Introduction Welcome 4 Navigation 4 Sample Spot Check 5 Equipment Overview 5 Parts ID
More informationOPERATION STARTUP TRUE
OPERATION STARTUP A. Temperature controls are factory-set to give refrigerators an approximate temperature of 35 F (1.6 C) and freezers an approximate temperature of -10 F (-23.3 C). Allow unit to function
More informationT-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N
T-SERIES Air Conditioner T43 Model INSTRUCTION MANUAL Rev. I P/N 10-1008-145 TABLE OF CONTENTS Warranty and Return Policy...2 IMPORTANT NOTICE...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING
More informationScotsman Technical Training. CU50 Cube Ice Machine
Scotsman Technical Training CU50 Cube Ice Machine Major Topics Overview Installation Start Up Sequence of Operation Maintenance Diagnostics Service Procedures Models Two Base Models Gravity Drain Pump
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Modular Crescent Cuber Model KM-600MAH A Superior Degree of Reliability SERVICE MANUAL www.hoshizaki.com 1 Number: 73167 Issued: 8-12-2008 Revised: 8-25-2008 IMPORTANT Only qualified
More informationπ H-6621 INDUSTRIAL DEHUMIDIFIER WARNINGS SPECIFICATIONS uline.com WATER REMOVAL ELECTRICAL REQUIREMENTS BUILT-IN ELECTRICAL SAFETY
π H-6621 INDUSTRIAL DEHUMIDIFIER 1-800-295-5510 uline.com WARNINGS Plug into a grounded 3 prong outlet. Do not remove ground prong. Do not use an adapter. Do not use an extension cord if possible. Failure
More informationThermoSaver TM Hot Gas Defrost System
PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin K40-THERM-PDI-15 Part # 1069130 PRODUCT SUPPORT web: k-rp.com/ts email: mdcu-lgcu@k-rp.com
More informationT-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N
T-SERIES Air Conditioner T29 Model INSTRUCTION MANUAL Rev. I P/N 89104464 TABLE OF CONTENTS Warranty and Return Policy...2 IMPORTANT NOTICE...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Low-Profile Modular Crescent Cuber Models KML-451MAH KML-451MWH A Superior Degree of Reliability SERVICE MANUAL www.hoshizaki.com Number: 73143 Issued: 3-1-2007 IMPORTANT Only qualified
More informationSWIMMING POOL & SPA HEAT PUMPS OWNERS OPERATIONAL MANUAL
SWIMMING POOL & SPA HEAT PUMPS OWNERS OPERATIONAL MANUAL MODEL AT105 AT115 AT130 with Titanium Heat Exchanger 2213 Andrea Lane Ft. Myers FL 33912 888-297-3826 941-482-0606 www.aquathermheatpumps.com DIGITAL
More informationTechnical Review. Remote Condenser Cuber. Enhanced Refrigeration and Water Systems. CM 3 Technology. of a. with. using. models included are:
Technical Review of a Remote Condenser Cuber with Enhanced Refrigeration and Water Systems using CM 3 Technology models included are: CME1356 shown on BH900 CME456, CME1056, CME1356, CME1656 and CME2006
More informationINSTALLATION and OPERATING. INSTRUCTIONS for. SMZP26 Series. elf-contained Freezers
S elf-contained Freezers INSTALLATION and OPERATING INSTRUCTIONS for Series ZERO ZONE Zero Zone, Inc. 110 N. Oakridge Dr. North Prairie, WI 53153-9792 1-800-247-4496 FAX: 1-414-392-6450 www.zero-zone.com
More informationManitowoc. Technician s Handbook. EC Models. Manitowoc Ice P/N /10
Manitowoc EC Models Technician s Handbook This manual is updated as new information and models are released. Visit our website for the latest manual. www.manitowocice.com America s #1 Selling Ice Machine
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Stackable Crescent Cuber Models KM-1800SAH/3 KM-1800SWH/3 KM-1800SRH/3 A Superior Degree of Reliability SERVICE MANUAL www.hoshizaki.com Number: 73131 Issued: 11-11-2005 Revised:
More informationWMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS
WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty
More information1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.
WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Modular Crescent Cuber Models KM-320MAH KM-320MWH A Superior Degree of Reliability SERVICE MANUAL www.hoshizaki.com Number: 73132 Issued: 1-24-2006 Revised: 11-30-2006 IMPORTANT
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Modular Crescent Cuber Serenity Series Model KMS-750MLH Including Condensing Unit Model SRK-7H A Superior Degree of Reliability SERVICE MANUAL www.hoshizaki.com Number: 73152 Issued:
More information