Operating Manual, Model K/348012K Recovery/Recycling/Recharging Unit For R-12 and R-134a Refrigerants...1

Size: px
Start display at page:

Download "Operating Manual, Model K/348012K Recovery/Recycling/Recharging Unit For R-12 and R-134a Refrigerants...1"

Transcription

1 Operating Manual, Model K/348012K Recovery/Recycling/Recharging Unit For R-12 and R-134a Refrigerants...1

2 Refrigerant Recovery, Recycling and Recharging Station Series: K/348012K Refrigerants: R-12 and R-134a WARNING PRESSURIZED TANK CONTAINS LIQUID REFRIGERANT. OVERFILLING OF THE TANK MAY CAUSE VIOLENT EXPLOSION AND POSSIBLE INJURY OR DEATH. Refer to the instruction manual for tank specifications and ordering information. Do not recover refrigerants into a non-refillable storage container! Federal regulations require refrigerant to be transported only in containers meeting DOT spec. 4BW or DOT spec. 4BA. ALL HOSES MAY CONTAIN LIQUID REFRIGERANT UNDER PRESSURE. Contact with refrigerant may cause injury. Wear proper protective equipment, including safety goggles. Disconnect hoses with extreme caution. HIGH VOLTAGE ELECTRICITY INSIDE PANELS. RISK OF ELECTRICAL SHOCK. Disconnect power before servicing unit. Refer to the instruction manual. TO REDUCE THE RISK OF FIRE, avoid the use of an extension cord because the extension cord may overheat. However, if you must use an extension cord, use No. 14 AWG at the minimum and as short as possible. Do not use this equipment in the vicinity of spilled or open containers of gasoline or other flammable substances. Use this equipment in locations with mechanical ventilation that provides at least four air changes per hour or locate the equipment at least 18 inches above the floor. Make certain all safety devices are functioning properly before operating the unit. Before operating, read and follow the instructions and warnings in this manual. CAUTION: SHOULD BE OPERATED BY QUALIFIED PERSONNEL. Operator must be familiar with air conditioning and refrigeration systems, refrigerants and the dangers of pressurized components. Use only with R-12 or R-134a. This equipment is not designed for any other purpose than recovering, recycling or recharging refrigerants! Do not mix refrigerant types! ATTENTION! Ce réservoir sous pression contient du frigorigène liquide. S il est surchargé, ce réservoir peut exploser et causer des blessures ou la mort. ATTENTION. Débrancher avant la maintenance. ATTENTION. Pour réduire les risques d incendie, ne pas utiliser de cordon prolongateur de section inférieure à 14 AWG de facon à éviter la surchauffe du cordon. ATTENTION. Utiliser seulement du frigorigène R-134a. OPERATING NOTES At temperatures exceeding 120 o F / 49 o C, wait 10 minutes between recovery jobs. R-12 and R-134a WARNINGS! Use the Series K/348012K only with R-12 or R-134a! Cross-contamination with other refrigerant types will cause severe damage to the A/C system and to service tools and equipment. Do not mix refrigerant types through a system or in the same container! Avoid breathing A/C refrigerant and lubricant vapor or mist. Exposure may irritate eyes, nose and throat. To remove R-12 or R-134a from the A/C system, use service equipment certified to meet the requirements of SAE-J2210 (R-12 or R-134a recycling equipment). If accidental system discharge occurs, ventilate work area before resuming service. R-12 or HFC-134a service equipment or vehicle A/C systems should not be pressure tested or leak tested with compressed air. Some mixtures of air/hfc-r-12 /R-134a have been shown to be combustible at elevated pressures. These mixtures are potentially dangerous and may result in fire or explosion causing injury or property damage. Additional health and safety information may be obtained from refrigerant and lubricant manufacturers.

3 Table of Contents Introduction... 2 Glossary of Terms... 2 Set-Up Instructions... 4 Initial Set-Up... 4 Preparing the Vacuum Pump... 5 Operating Guidelines... 6 Using the Selection Menu... 6 Change Filter... 6 Recycle... 6 External Storage Vessel (ESV) Refill... 7 Vacuum Pump Hours... 8 Drier Recovered Lbs Basic/Advanced Prompts... 9 Auto Restart ON/OFF... 9 Selecting a Unit (Metric/English) Language Select Installation Routine/First Fill Using the Control Panel Keypad Functions Operating Instructions Operating Tips Recovering Refrigerant Evacuating the A/C System Replenishing A/C System Oil Recharging the A/C System Maintenance Instructions Replacing the Filter-Drier Changing the Vacuum Pump Oil Checking for Leaks Electrical Protection General Maintenance Replacement Parts List (348002K) Replacement Parts List (348012K) Flow Diagram Wiring Diagram Limited Warranty U.S. Patents: 4,523,897; 4,688,388 Re 33,212; 4,768,347; 4,805,416; 4,809,520; 4,878,356; 4,938,031; 5,005,369; 5,005,375; 5,038,578; 5,042,271; 5,209,653; 5,248,125 Australian Patent: 613,058 Canadian Patents: 1,311,621; 1,311,622; 2,012,620; 2,026,348 European Patent: Bl German Patent: Mexican Patent: OTHER U.S. AND FOREIGN PATENTS PENDING. Mfd. by Robinair, SPX Corporation, Montpelier, OH K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 1

4 Introduction This manual contains important safety procedures concerning the operation, use, and maintenance of this product. Failure to follow the instructions contained in this manual may result in serious injury. If you are unable to understand any of the contents of this manual, please bring it to the attention of your supervisor. Do not operate this equipment unless you have read and understood the contents of this manual. The K and K models are designed to be used on R-12 and R-134a vehicles. They are compatible with existing service equipment and standard service procedures. The K model is UL-listed. The K is CE approved. Both are single pass systems that meet the SAE specifications for recycled refrigerant. To validate your warranty, complete the warranty card attached to your unit and return it within ten days from date of purchase. GLOSSARY OF TERMS A/C System Unit External Storage Vessel Source Tank The air conditioning system being serviced. The refrigerant recovery/recycling/recharging unit. The refillable refrigerant storage vessel designed specifically for this unit. A disposable tank of new refrigerant used to refill the external storage vessel. Low Side Gauge High Side Gauge Low Side Gauge High Side Gauge Low Side Valve Low Side Valve High Side Valve Main Power Switch High Side Valve Selector Switch Keypad Diagram of the K Control Panel INST Robinair, SPX Corporation

5 Set-Up Instructions Diagram of Unit s Components External View Oil Injection Valves 2. R-134a Hoses Scales 4. Oil Injection Bottles Amp Breaker 6. 3 Amp Breaker Hose Holders 8. RJ45 Upgrade Port 9. Power Cord Receptacle 10. Quick Couplers R-12 Hoses 12. External Storage Vessel (ESV) 12 INST Diagram of Unit s Components Internal View 1. Relays 2. Compressor 3. Vacuum Pump 4. Filter 5. Manifold Block 6. Air Purge Assembly 7. Vacuum Pump Receptacle 8. Transformer 9. Fan 10. Oil Drain Bottle 11. Accummulator INST K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 3

6 Set-Up Instructions INITIAL SET-UP CAUTION! R-134a systems have special fittings (per SAE specifications) to avoid cross-contamination with R-12 systems. Do not attempt to adapt your unit for another refrigerant system failure will result! Read and follow all warnings at the beginning of this manual before operating the unit. CAUTION! Avoid the use of an extension cord because the extension cord may overheat. However, if you must use an extension cord, use a No. 14 AWG minimum and keep the cord as short as possible. IMPORTANT! You must press the MENU key to access all the functions. 1. Lock both front casters of the unit by stepping on the cam brake levers, plug the power cord into the power cord receptacle (Item 9 in the INST 0707 drawing on page 3). Turn on the MAIN POWER switch. 2. Press MENU. 3. Use the UP and DOWN arrows to select LANGUAGE SELECTION. Press ENTER. 4. Use the UP and DOWN arrows to scroll through the language options and press ENTER to select a language and exit LANGUAGE SELECTION. 5. Press MENU. Use the ARROW keys to go to SELECT AUTO RESTART. Press ENTER. 6. Use the UP and DOWN arrows to toggle between AUTO RESTART ON and AUTO RESTART OFF. Press ENTER to select. NOTE: See the Operating Guidelines section of this manual for a description of these functions. 7. Press MENU. Use ARROW keys to go to SELECT PROMPT. Press ENTER. 8. Use the UP and DOWN arrows to toggle between BASIC PROMPTS and ADVANCED PROMPTS. Press ENTER to select. NOTE: See the Operating Guidelines section of this manual for a description of these functions Robinair, SPX Corporation

7 Set-Up Instructions VACUUM PUMP INITIAL FILL 1. Press VACUUM to get to the VACUUM mode. Press START to go into VACUUM. Set Up Instructions NOTE: The vacuum pump is shipped without oil in the reservoir. Before starting the pump, oil must be added to the pump or damage may occur. 2. Close all manifold valves on the control panel. 3. Remove bolts holding the door closed and open the door. 4. Remove the black plastic plug from the fill port on the top of the vacuum pump. 5. Attach the oil fill tube to the 16 oz. bottle of vacuum pump oil provided in the accessory kit. IMPORTANT! For maximum performance, be sure to change the vacuum pump oil frequently. IMPORTANT! Be sure the pump is running when adding oil. 6. While the vacuum pump is running, add oil until it reaches the center of the sight glass. Press STOP. The vacuum pump is now filled to the proper level with oil. 7. Pour oil (approximately 12 oz.) into the fill port of the vacuum pump until the oil appears at the bottom of the sight glass. Press ENTER. 8. Replace the plug in the fill port. 9. Press STOP to exit. 1. Oil Fill Port 2. Sight Glass 3. Oil Drain 10. Close the door and replace the bolts holding the door shut INSTALLATION ROUTINE 1. Press MENU. Use the ARROW keys to go to the INSTALLATION ROUTINE. INST Press ENTER. The display toggles between CONNECT LS RXX HOSE TO SOURCE TANK and TURN ALL VALVES TO VACUUM/RECOVER AND PRESS START TO BEGIN. Follow the on-screen prompts. 3. Remove the service hoses from the accessory kit and remove the plugs from the hoses using a pair of pliers. 4. Attach the service hoses to the high and low side bulkheads on the rear of the unit. Attach the R-134a hoses to the left rear. Attach the R-12 hoses to the right rear. Attach the RED hoses to the bulkheads labeled HIGH and the BLUE hoses to the bulkheads labeled LOW K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 5

8 Operating Guidelines 5. Press START. The unit automatically evacuates the system for 5:00 minutes to remove any air from the external storage vessel (Ensure that all tank valves are open). IF THE SELECTOR SWITCH IS SET TO R-134A: 6. Connect the lowside service coupler to the source tank valve, using the adapter supplied with the unit, when the 5:00 minute evacuation is complete. Open the service coupler and turn manifold valves to RECOVER/VACUUM. IF THE SELECTOR SWITCH IS SET TO R-12: 7. When the 5:00 minutes evacuation is complete, connect the low side hoses the hose adapter supplied with the unit. Attach the adapter to the source tank. USING THE SELECTION MENU 1. Press MENU. The top line of the display reads LANGUAGE SELECTION. 2. Use the UP and DOWN arrows to scroll through the menu choices. The menu choices are (in order of appearance): 3. Press ENTER to make a choice from the menu. Press STOP to terminate any process. 1. LANGUAGE SELECT 2. CHANGE FILTER 3. FILTER WEIGHT 4. SELECT AUTO RESTART 5. MEASUREMENT UNITS 6. CHANGE VACUUM PUMP OIL 7. TANK FILL 8. VACUUM OIL TIME 9. INSTALLATION ROUTINE 10. SELECT PROMPTS 11. CHANGE DEFAULT (Password Protected) CHANGE FILTER The filter-drier removes acid, particulates and water from the refrigerant. Change the filter-drier after 150 pounds of refrigerant has been filtered. See the DRIER RECOVERED LBS. section on the following page as well as the Maintenance Section on page 20 for instructions Robinair, SPX Corporation

9 Operating Guidelines USING THE SELECTION MENU (continued) 4-a. TANK FILL (R-12 Users) NOTE: If using a refillable tank, place the tank upside down and connect the lowside service hose to the vapor valve. Set SELECTOR switch to R-12: 1. Connect the 6" yellow adapter to the end of the low side service hose. 2. Connect the low side service hose to the source tank and open valve. 3. Select TANK FILL from the Selection Menu. 4. Press ENTER. Then press START and the tank automatically refills. The unit stops when a sufficient amount of refrigerant has been transferred to the ESV- or - the source tank is empty. NOTE: Press STOP if you wish to stop fill before it completes. 5. Close the valve on the source tank. 6. Disconnect the 96" blue service hose from the adapter, then disconnect the 6" yellow adapter from the source tank. 7. Press STOP to exit. R-12 Low Side Service Hose Source Tank ESV INST K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 7

10 Operating Guidelines USING THE SELECTION MENU (continued) 4-b. TANK FILL (R-134a Users) NOTE: If using a refillable tank, place the tank upside down and connect the lowside service hose to the vapor valve. Set the SELECTOR switch to R-134a: 1. Connect the tank to quick-coupler adapter (supplied with the unit) to the low side service hose. 2. Connect the low side service hose to the source tank and open valve. 3. Select TANK FILL from the Selection Menu. 4. Press ENTER. Then press START and the tank automatically refills. The unit stops when a sufficient amount of refrigerant has been transferred to the ESV- or - the source tank is empty. NOTE: Press STOP if you wish to stop fill before it completes. 5. Close the valve on the source tank. 6. Disconnect the 96" blue service hose from the adapter, then disconnect the adapter from the source tank. 7. Press STOP to exit. VACUUM OIL TIME This feature displays the number of hours the vacuum pump has been used since the last oil change and needs reset after an oil change. Change the vacuum pump oil after every 10 hours of operation. See the Maintenance section on page 20 of this manual for instructions Robinair, SPX Corporation

11 Operating Guidelines USING THE SELECTION MENU (continued) FILTER WEIGHT This function is used to show the operator how many pounds of refrigerant have been recovered since the last filter change. 1. Select FILTER WEIGHT from the menu. Press ENTER. 2. The display shows amount of refrigerant recovered since last filter change. 3. If display reads greater than 300 lbs., go to MENU/CHANGE FILTER 4. Press STOP to exit. SELECT PROMPT Use the BASIC PROMPT option to receive step-by-step, on-screen prompting through any procedure. Use ADVANCED PROMPT once you know the procedure and no longer need the step-by-step routine. 1. Choose SELECT PROMPTS from the menu. Press ENTER. 2. Toggle between BASIC/ADVANCED using the ARROW keys. 3. Press ENTER to select the current choice. SELECT AUTO RESTART The AUTO RESTART ON option is used to automatically restart the unit if a pressure rise is detected by the unit during the five minute waiting period after recovering refrigerant. If AUTO RESTART OFF is selected, the operator must watch the gauges for a pressure rise and manually restart the recovery process if a pressure rise is detected. 1. Select AUTO RESTART. Press ENTER. 2. Use ARROW keys to toggle between the two options. 3. Press ENTER to select the current choice K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 9

12 Operating Guidelines USING THE SELECTION MENU (continued) MEASUREMENT UNITS 1. Select MEASUREMENT UNITS from the menu. Press ENTER. 2. Toggle between UNITS ENGLISH and UNITS METRIC using the ARROW keys. 3. Press ENTER to select the current choice. LANGUAGE SELECTION The operator can choose between English, Spanish, French, or German. 1. Scroll through the selection menu to LANGUAGE SELECTION and press ENTER. 2. Use the UP and DOWN arrows to scroll through the languages and then press ENTER to save the current choice. INSTALLATION ROUTINE and FIRST FILL The INSTALLATION ROUTINE is an automatic function that is used only for initial set-up. See the Initial Set-Up section of this manual for details Robinair, SPX Corporation

13 Operating Guidelines USING THE CONTROL PANEL The control panel has various components that control specific operating functions. MAIN POWER SWITCH Supplies electrical power to the control panel. DIGITAL DISPLAY Used on the visual interface between the operator and the machine. LOW SIDE MANIFOLD GAUGE Connects to an A/C system and shows the system s low side pressure. HIGH SIDE MANIFOLD GAUGE Connects to an A/C system and shows the system s high side pressure. LOW SIDE VALVE Controls the low side flow from the A/C system through the unit. It has two positions: 1) Vacuum/Recover, and 2) Closed. HIGH SIDE VALVE Controls the high side flow from the A/C system through the unit. It has three positions: 1) Vacuum/Recover, 2) Closed, 3) Oil Inject/Charge INST Diagram of Control Panel 1. Main Power Switch 2. Display 3. Low Side Gauge 4. High Side Gauge 5. High Side Valve 6. Low Side Valve 7. Keypad 8. Selector Switch K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 11

14 Operating Guidelines KEYPAD FUNCTIONS In addition to the number keys, the keypad contains special keys that accomplish specific operating functions. CHARGE Automatically charges the A/C system with the programmed amount of refrigerant. CLEAR Clears indicated data from the unit's memory. ENTER Enters programmed data into the unit s memory. MENU Enters the selection menu. RECOVER Activates the recovery sequence. START Begins a function. STOP Terminates a function. UP/DOWN ARROWS Used for scrolling through the menu items. VACUUM Activates the vacuum and automatic recycling sequence. Diagram of Keypad INST Robinair, SPX Corporation

15 Operating Instructions OPERATING TIPS Follow the recommended service procedure for the containment of R-12 and R-134a. The recovery compressor is not a vacuum pump. The compressor pulls the A/C system to a partial vacuum only. You must use the unit s vacuum cycle to remove moisture from the A/C system. We recommend a minimum 15-minute vacuum with more time as required by the system manufacturer. This unit is designed to be used with the manifold gauge set built into the control panel. It includes a 6 cfm (142 l/m) vacuum pump for fast, thorough evacuation. Be sure to change the vacuum pump oil after 10 hours of vacuum pump use. R-12 and R-134a systems require special oils. Refer to the A/C system manufacturer s service manuals for oil specifications. NOTE: The following operating instructions are written to be used with the BASIC PROMPTS mode of operation. It is recommended that the BASIC PROMPTS mode is used until the operator becomes very familiar with the operation of the unit. See the OPERATING GUIDELINES section of this manual for instructions on how to select between BASIC PROMPTS and ADVANCED PROMPTS K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 13

16 Operating Instructions RECOVERING REFRIGERANT WARNING Always wear safety goggles when working with refrigerant. Read and follow all warnings at the beginning of this manual before operating the unit. 1. Connect the power cord to the back of the unit and plug into the proper voltage outlet. 2. Turn on the MAIN POWER and empty the oil drain bottle located on the right hand side of the unit. 3. Press RECOVER. 4. If 300 or more pounds of refrigerant has been recovered since the last filterdrier change, the display reads REPLACE FILTER. 5. Connect the high and low side hoses to the A/C system service ports. For R-134a, open the coupler valves. 6. Place both High and Low Side manifold valves in the Recover/Vacuum position on the control panel. 7. If the system pressure is below 25 psi, the display reads LOW SYSTEM PRESSURE until the pressure increases or the START button is pressed. 8. If the unit has refrigerant in the low-side plumbing, it begins the clearing process and displays CLEARING. If you wish to skip the clearing operation or stop the clearing prematurely, press START. NOTE: An inaccurate recovery weight may result if the clearing operation is not completed. 9. When the system has recovered to a vacuum level of approximately 13 in. Hg., the compressor automatically shuts off. Manifold Gauges Manifold Gauges Valves Open Recover INST Diagram of Control Panel During Recovery 2000 Robinair, SPX Corporation

17 Operating Instructions 10. The unit then goes into automatic oil drain and the display reads OIL DRAINING. Oil draining can require up to 90 seconds to complete. 11. After the oil drain is complete, the display alternates between: RECOVERY COMPLETE CHECK OIL BOTTLE. RECOVERED XXX.XX lbs. RECOVERED XXX.X lbs. 12. Check the oil drain bottle and note the amount of oil that was removed from the A/C system. This is the amount of oil that must be charged into the A/C system after evacuation is complete. 13. To ensure complete recovery of refrigerant, wait 5 minutes and watch the manifold gauges for a rise in pressure above 0 in. Hg. A pressure rise may occur if there was freezing in the A/C system during recovery. If a rise occurs, press START to repeat the recovery process. Repeat as needed until the system pressure holds for two minutes, then press STOP. The AUTO RESTART ON option can be used to automatically restart the recycling process if the unit detects a pressure rise after five minutes. See the Selection MENU section for details. This process meets SAE Spec J Press STOP to exit. Recovery is now complete. You are now ready to make any repairs to the A/C system, if necessary, or advance to the Evacuation Process. Diagram of the Oil Injection System Oil Injector Bottle Oil Drain Bottle INST K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 15

18 Operating Instructions EVACUATING THE A/C SYSTEM WARNING Always wear safety goggles when working with refrigerant. Use only authorized refillable refrigerant tanks. Read and follow all warnings at the beginning of this manual before operating the unit. In addition to the number keys, the keypad contains special keys that accomplish specific operating functions. IMPORTANT! You should evacuate for at least 15 minutes to ensure adequate moisture and contaminant removal. IMPORTANT! If the vacuum pump has run for 10 or more hours without an oil change, the message VACUUM OIL TIME = Xhr. Xmin Xsec appears on the display. Change the pump oil following the procedures in the MAINTENANCE INSTRUCTIONS. 1. Connect the service hoses to the vehicle. R-134a users: Open the coupler valves. 2. Place both High and Low Side manifold valves in Recover/Vacuum. 3. Turn the unit on and press VACUUM. 4. If the vacuum pump has been run more than 10 hours since the last oil change, the display reads: VACUUM OIL TIME= X hr. Xmin. Xsec. Press STOP to change the vacuum pump oil or press START to continue. Instructions for changing the vacuum pump oil are located in the maintenance section of this manual. NOTE: Vacuum Pump oil should be changed after 10 hours of use to maintain maximum performance and endurance levels. 5. If the system being evacuated contains a pressure over 25 psi at any point during the evacuation, the display reads HIGH SYSTEM PRESSURE. This message indicates that the A/C system contains refrigerant. Press RECOVER to continue. After recovery is complete, return to Step 1 to evacuate the A/C system. 6. If the pressure is below 25 psi, the user is prompted to press START to VACUUM or press CHARGE to use the VACUUM-CHARGE (VAC-CHG) feature. If VACUUM is selected, the unit vacuums the system only and user interaction is required to enter the CHARGE mode. If the VACUUM- CHARGE feature is chosen, the unit automatically charges the system after evacuation is complete. Valves Open Vacuum 16 The Control Panel During Evacuation INST Robinair, SPX Corporation

19 Operating Instructions NOTE: If any oil was drained from the system during recovery, DO NOT use the VAC-CHG feature. The oil must be replenished into the A/C system, which is not possible when the VAC-CHG function is used. VACUUM 1. Press ENTER to accept the default evacuation time of 15:00 minutes or enter the desired vacuum time by using the number keys (To enter 10 minutes, press 1 and 10:00 should appear on the display. To enter 1 minute, press 0 then press 1, and 1:00 should appear on the display). 2. Press ENTER. The unit evacuates the A/C system and stops when the specified time has elapsed. 3. You are now ready to replenish the A/C system oil (if necessary) or to recharge the system with refrigerant. 4. Press STOP to exit. IMPORTANT! You should evacuate the A/C system for at least 15 minutes to ensure adequate moisture and contaminant removal. VAC-CHG 1. Press CHARGE to select the VAC-CHG feature. 2. Press START to charge the default amount of refrigerant (2.00lb) or use the number keys to enter the desired charge weight. Then press ENTER. 3. If the weight entered leaves less than 5 lbs. of refrigerant in the external storage vessel, the VAC-CHG process does not begin and the display reads LOW REFRIGERANT. At this point, refrigerant must be added to the external storage vessel. See the OPERATING GUIDELINES section of this manual for external storage vessel refill instructions and then return to Step 1 of EVACUATING THE A/C SYSTEM. 4. If the external storage vessel contains a sufficient amount of refrigerant, press ENTER to accept the default evacuation time of 15:00 minutes or enter the desired vacuum time by using the number keys. Then press ENTER. 5. The unit automatically charges the A/C system after the specified vacuum time has elapsed. 6. Advance to Step 6 of RECHARGING THE A/C SYSTEM in this manual to complete the charging process K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 17

20 Operating Instructions REPLENISHING A/C SYSTEM OIL Before charging the A/C system, you must replenish any oil removed from the A/C system during the recovery process. IMPORTANT! You can charge oil through either the low side or high side, or both, depending on the vehicle manufacturer s recommendation. Just open the appropriate manifold valve or valves. 1. Select the correct oil for the A/C system being serviced. Refer to the vehicle manufacturer's service manual. CAUTION! To prevent air from entering the A/C system, never let the oil level drop below the pick-up tube while charging or replenishing. 2. Adjust the O-ring around the oil injector bottle to the required oil charge level. For example, if the bottle's oil level is at 4 ounces and you need 1/2 ounce of oil to replenish the A/C system, place the o-ring at the 3 1/2 ounce level. 3. Install the bottle on the oil injection assembly on the back of the unit. CAUTION! Never open the oil injection valve while there is positive pressure in the A/C system. This action could blow oil back through the bottle vent. 4. Place the Low Side valve in the Closed position. Place the High Side valve in the Oil Inject/Charge position. 5. Turn the oil injection valve at the top of the bottle and watch the level of oil being drawn into the A/C system. This process takes only seconds watch carefully! 6. Turn OFF the valve when the required oil charge has been pulled into the system. Oil Injector Bottle Closed Oil Inject/Charge Oil Drain Bottle INST 0770 INST Robinair, SPX Corporation

21 Operating Instructions RECHARGING THE A/C SYSTEM WARNING Always wear safety goggles when working with refrigerant. Use only authorized refillable refrigerant tanks. Disconnect hoses with extreme caution! All hoses may contain liquid refrigerant under pressure. Read and follow all warnings at the beginning of this manual before operating the unit. 1. Press CHARGE. 2. Accept either the default weight by pressing START or type in a weight with the number keys and press START (For example, to program 3 lbs, press 3 and 3.00 lbs will appear on the display. To program 3.25 lbs, press 3-2-5, in that order, and 3.25 lbs will appear on the display). 3. If the weight entered will leave less than 5 lbs. of refrigerant in the refrigerant tank, the charge function will not start and the display will read: LOW REFRIGERANT Refrigerant XX.XX lbs. See the Operating Guidelines section of the manual for refill instructions. 4. Close the Low Side valve. Place the High Side valve in the Oil Inject/Charge position (Note: Use the valves corresponding with the refrigerant you are working with). 5. Upon entering a valid charge weight, the display shows: CHARGE MODE Closed AMT. CHARGED XX.XX lbs. Press START to continue. 6. The display will say "Charge complete. Amt. charged XX.XX". 7. Close the high and low side coupler valves and remove the service hoses from the A/C system. 8. Turn off the MAIN POWER switch. The A/C system is now ready for use. Oil Inject/Charge Note: To add less than 1 pound of refrigerant, such as 0.25, press 0-2-5, in that order. IMPORTANT! You should evacuate the A/C system for at least 15 minutes for adequate moisture and contaminant removal. INST 0770 CORRECTING AN INCOMPLETE CHARGE On ocassions the AMT. CHARGED will not finish. The reason for this is that the pressures in the ESV and the A/C system have equaled. To finish the charge, you should: 1. Turn high side valve on the control panel to the closed position. 2. Turn low side valve on the control panel to recover/vacuum position. 3. Start the vehicle and turn on the A/C. 4. The remainder of the charge will be pulled into the A/C system and display will read CHARGE COMPLETE K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 19

22 Maintenance Instructions REPLACING THE FILTER-DRIER Order part #34724 for a replacement filter-drier. The filterdrier on this unit is designed to trap acid and particulates and is formulated to remove water from the refrigerant. You must change the filter-drier to assure adequate moisture and contaminant removal. Typically, you can recycle up to 300 pounds (136 kilograms) of refrigerant between filter changes. CAUTION! For best results, use Robinair filter-driers (part no ). All performance tests and claims are based on using this specially-blended filter-drier. Use of another may affect performance results. Filter Filter-Drier INST0477 Filter 1. Press MENU. 2. Scroll through the menu to CHANGE FILTER and press ENTER. Display reads: RXX Filter Weight X.XX lbs. 3. Press START to begin. 4. Wait for the unit to self clear. 5. When clearing is complete, the display reads DISCONNECT POWER. Replace RXX filter. 6. Turn off the main power and unplug the machine. 7. Open the unit door and replace the old filter with the new filter. 8. Close the unit door, plug in the machine, and turn on the Main Power. 9. Close the door to the unit. 10. The filter change is now complete. Location of the Filter-Drier INST Robinair, SPX Corporation

23 CHANGING THE VACUUM PUMP OIL For maximum vacuum pump performance, change the vacuum pump oil every 10 hours of operation. 1. Press MENU. 2. Use the ARROW keys to select CHANGE VAC PUMP OIL. 3. Press ENTER. NOTE: Do not connect the service hoses to a vehicle. 4. Ensure that the high side and low side manifold valves are closed and press START. 5. Screen displays OIL CHANGE. 6. Allow the vacuum pump to run until it automatically stops (2 minutes). 7. Remove the black plastic plug on the oil fill port of the vacuum pump. 8. Remove the oil drain cap from the vacuum pump and drain the oil into a suitable container for proper disposal. 9. Replace the oil drain cap and press START. Maintenance Instructions 10. Screen now toggles between ADD 5 oz. OF OIL TO VACUUM PUMP and PRESS START TO CONTINUE. 11. Attach the flexible tube and cap to the oil bottle and pour five ounces of vacuum pump oil into the fill port. 12. Press START and while the vacuum pump is running, slowly add oil until the level is even with the line on the reservoir's sight glass. 13. Press STOP and replace the black plastic plug on the fill port. 14. The unit is now ready to operate K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 21

24 Maintenance Instructions Diagram of Vacuum Pump INST Oil Filler Tube 2. Pump Exhaust 3. Oil Fill Port 4. Sight Glass 5. Oil Drain Fitting 6. Inlet INST Oil Fill Port 2. Sight Glass 3. Oil Drain IMPORTANT! Inspect the unit periodically for leaks. The manufacturer does not reimburse for lost refrigerant. CHECKING FOR LEAKS Every three months, or as specified by local or state laws, you should check the unit for leaks. 1. Turn off the MAIN POWER switch, and disconnect the power cord from the outlet. 2. Open door. 3. Use a leak detector to probe all connections for refrigerant leaks. Tighten fittings if a leak is indicated. 4. Close door Robinair, SPX Corporation

25 Maintenance Instructions ELECTRICAL PROTECTION If the circuit breaker trips, all power to the unit is lost. Press the circuit breaker button to reset. The circuit breaker is located near the fuse on the back of the unit. GENERAL MAINTENANCE 1. On a regular basis, wipe off the unit with a clean cloth to remove grease, dust or other dirt. 2. Periodically check the internal components for leaks over time, fittings can loosen as the unit is moved. Open the unit door panel and trace lines with a leak detector. Also, check connections on the back of the unit. Tighten any loose fittings or connections you may find K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 23

26 Replacement Parts The following is a list of replacement parts and accessories you may need to service or maintain your unit. We suggest you keep several filter-driers on hand so you will always be able to change them and complete any recycling job that is in progress. Premium High Vacuum Pump Oil is also available in handy quart containers or in convenient gallon containers: Quart (shipped 12 quarts per case) Gallon (shipped 4 gallons per case) Because of ongoing product improvements, we reserve the right to change design, specifications, and materials without notice Robinair, SPX Corporation

27 Replacement Parts List K Replacement Parts R-12 R-134a Replacement Replacement Component Part Number Part Number 96" Red Hose 68396A " Blue Hose 68296A Fan RA17516 RA19409 Filter-Drier Compressor RA19735 RA19735 Vacuum Pump RA15425 RA15425 High Pressure Switch RA19427 RA19427 Main Power Switch RA19344 RA19343 Vacuum Switch RA19428 RA19428 Pump Protection Switch RA19429 RA19429 Automatic Expansion Valve RA19592 RA19592 Scale Assembly RA19603 RA19603 Main Circuit Board RA19594 RA19740 High Side Gauge RA19742 RA19613 Low Side Gauge RA19741 RA19614 Low Side Coupler N/A 18190A High Side Coupler N/A 18191A Automatic Air Purge RA19476 RA19595 Relays RA17459 RA17459 Transformer RA19596 RA19596 Solenoid Rebuild Kit RA19258 RA19258 UL Circuit RA19673 RA K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 25

28 Replacement Parts List K Replacement Parts Component R-12 R-134a Replacement Replacement Part Number Part Number 96" Red Hose 68396A " Blue Hose 68296A Fan RA17516 RA19409 Filter-Drier Compressor RA19736 RA19736 Vacuum Pump RA15428 RA15428 High Pressure Switch RA19427 RA19427 Main Power Switch RA19344 RA19343 Vacuum Switch RA19428 RA19428 Pump Protection Switch RA19429 RA19429 Automatic Expansion Valve RA19592 RA19592 Scale Assembly RA19603 RA19603 Main Circuit Board RA19740 RA19740 High Side Gauge RA19742 RA19613 Low Side Gauge RA19741 RA19614 Low Side Coupler N/A 18190A High Side Coupler N/A 18191A Automatic Air Purge RA19476 RA19595 Relays RA17324 RA17324 Transformer RA19596 RA19596 Solenoid Rebuild Kit RA19258 RA19258 UL Circuit RA19673 RA Robinair, SPX Corporation

29 INST 0717 Flow Diagram K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 27

30 Wiring Diagram Inst Robinair, SPX Corporation

31 Limited Warranty This product is warranted to be free from defects in workmanship, materials and components for a period of one year from date of purchase. All parts and labor required to repair defective products covered under the warranty will be at no charge. The following restrictions apply: 1. The limited warranty applies to the original purchaser only. 2. The warranty applies to the product in normal usage situations only, as described in the Operating Manual. The product must also be serviced and maintained as specified. 3. If the product fails, it will be repaired or replaced at the option of the manufacturer. 4. Transportation charges for warranty service will be reimbursed by the factory upon verification of the warranty claim and submission of a freight bill for normal ground service. Approval from Robinair must be obtained prior to shipping to either an authorized service center or the factory. 5. Warranty service claims are subject to factory inspection for product defect(s). 6. Robinair shall not be responsible for any additional costs associated with a product failure including, but not limited to, loss of work time, loss of refrigerant, and unauthorized shipping and/or labor charges. 7. All warranty service claims must be made within the specified warranty period. Proof-of-purchase date must be supplied to the manufacturer. 8. Use of Robinair recovery/recycling equipment with unauthorized refrigerants will void our warranty. Authorized refrigerants are listed on the equipment or are available through our Technical Service Department. This Limited Warranty does not apply if: The product, or product part, is broken by accident. The product is misused, tampered with, or modified. The product is used for recovering or recycling any substance other than the specified refrigerant type K/348012K Cool-Tech Recovery/Recycling/Recharging Unit 29

32 CONVERSION TABLE OZ. LBS lb. Visit our web site at or call our Toll-Free Technical Support Line at in the continental U.S. or Canada. In all other locations, contact your local distributor. To help us serve you better, please be prepared to provide the model number, serial number, and date of purchase. To validate your warranty, you must complete the warranty card attached to your unit and return it within ten days from date of purchase. NATIONWIDE NETWORK OF AUTHORIZED SERVICE CENTERS If your unit needs repairs or replacement parts, you should contact the service center in your area. For help in locating a service center, call the toll free technical support line. Due to ongoing product improvements, we reserve the right to change design, specifications and materials without notice. The K and K are designed to meet all applicable agency certifications including Underwriter's Laboratories, Inc., SAE Standards and CUL. Proper maintenance of this equipment will provide accurate A/C service for many years. Certain state and local jurisdictions dictate that using this equipment to sell refrigerant by weight may not be permitted. We recommend charging for any A/C service by the job performed. This weight scale provides a means of metering the amount of refrigerant needed for optimum A/C system performance as recommended by OEM manufacturers. SPX ROBINAIR SPX Corporation 1224 Robinair Way, Box 193 Montpelier, OH Phone: Fax: Web site: (Rev. 05/00) K/348012K Operating Manual Printed In USA

Model K / K. Modelo K / K. Modèle K / K. Operating Manual

Model K / K. Modelo K / K. Modèle K / K. Operating Manual Operating Manual Model 34800-2K / 34801-2K Recovery/Recycling/Recharging Unit for R-12 and R-134a Refrigerants... English Modelo 34800-2K / 34801-2K Unidad de recuperación/reciclaje/recarga para refrigerantes

More information

Operating Manual. Model K/ K Recovery/Recycling/Recharging Unit

Operating Manual. Model K/ K Recovery/Recycling/Recharging Unit Operating Manual Model -K/-K Recovery/Recycling/Recharging Unit Model -K (for R- refrigerant) Model -K (for R-a refrigerant) Recover, Recycle, and Recharge Unit SAFETY DEFINITIONS: Follow all WARNING,

More information

Operating Manual. Series 12134B Recovery/Recycling/Recharging Unit for R-12 and R-134a

Operating Manual. Series 12134B Recovery/Recycling/Recharging Unit for R-12 and R-134a Operating Manual Series 12134B Recovery/Recycling/Recharging Unit for R-12 and R-134a LISTED 80S2 Design Certified by Underwriters Laboratories Inc., to meet SAE J1770 for recycling R-12 and R-134a using

More information

Owner s Manual. Model AC375C Refrigerant Recovery, Recycle, and Recharge Unit

Owner s Manual. Model AC375C Refrigerant Recovery, Recycle, and Recharge Unit Owner s Manual Model AC375C Refrigerant Recovery, Recycle, and Recharge Unit Model AC375C Recover, Recycle, and Recharge Unit for R-12 or R-134a Refrigerant Voltage: 220 230; 50 60 Hz SAFETY DEFINITIONS:

More information

Operating Manual. Model 34700Z / 17700Z Recovery, Recycling, Recharging Unit

Operating Manual. Model 34700Z / 17700Z Recovery, Recycling, Recharging Unit Operating Manual Model 34700Z / 17700Z Recovery, Recycling, Recharging Unit Model 34700Z / 17700Z Recovery, Recycling, & Recharging Unit SAFETY DEFINITIONS: Follow all WARNING, CAUTION, IMPORTANT, and

More information

OPERATING MANUAL. Model 34134Z. Refrigerant Unit Recover, Recycle, and Recharge

OPERATING MANUAL. Model 34134Z. Refrigerant Unit Recover, Recycle, and Recharge OPERATING MANUAL Model 34134Z Refrigerant Unit Recover, Recycle, and Recharge Recover, Recycle, and Recharge Unit Model: 34134Z Refrigerant: R-134a Voltage: 115, 60 Hz LISTED 80S2 Recycling Equipment Design

More information

P E R A T I N G A N U A L. Operating Manual for. Model Recovery, Recycling, Recharging Unit

P E R A T I N G A N U A L. Operating Manual for. Model Recovery, Recycling, Recharging Unit O P E R A T I N G M A N U A L Operating Manual for Model 34788 Recovery, Recycling, Recharging Unit Model 34788 Recovery, Recycling, & Recharging Unit SAFETY DEFINITIONS: Follow all WARNING, CAUTION, IMPORTANT,

More information

Model Operating Manual for. Recovery, Recycling, Recharging Unit P E R A T I N G A N U A L

Model Operating Manual for. Recovery, Recycling, Recharging Unit P E R A T I N G A N U A L O P E R A T I N G 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-571-8431 Visit us at www.testequipmentdepot.com M A N U A L Operating Manual for Model 34788 Recovery, Recycling,

More information

Model Operating Manual for. Recovery, Recycling, Recharging Unit P E R A T I N G A N U A L

Model Operating Manual for. Recovery, Recycling, Recharging Unit P E R A T I N G A N U A L O P E R A T I N G 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-571-8431 Visit us at www.testequipmentdepot.com M A N U A L Operating Manual for Model 34288 Recovery, Recycling,

More information

Refrigerant Recovery Machine. Model No Operating Manual

Refrigerant Recovery Machine. Model No Operating Manual Refrigerant Recovery Machine Model No. 25700 Operating Manual Safety Precautions WARNING : TO PREVENT PERSONAL INJURY AND / OR EQUIPMENT DAMAGE, CAUTION - Risk of injury. This equipment should only be

More information

347002K/177002K/34900

347002K/177002K/34900 Service Manual Models: 347002K/177002K 34900/347012K Manifold Block Style Recovery/Recycling/Recharging Unit For R-12 or R-134a Only TABLE OF CONTENTS: Theory of Operation and Safety Precautions... 2 Depressurizing

More information

Operating Manual Manual de Operación Manuel d utilisation

Operating Manual Manual de Operación Manuel d utilisation Operating Manual Manual de Operación Manuel d utilisation Model 17800B/17801B Recovery/Recycling/Recharging Unit for Multiple Refrigerants... 1 Modelo 17800B/17801B Unidad de recuperación/reciclado/recarga

More information

Operation Manual... 1 Manuel d utilisation Manual de Operación.. 60

Operation Manual... 1 Manuel d utilisation Manual de Operación.. 60 Operation Manual... 1 Manuel d utilisation... 30 Manual de Operación.. 60 SERIES: ACR2000 KENT-MOORE: J-43600 Air Conditioning and Refrigerant Service Solution WARNING Refrigerant: R134a PRESSURIZED TANK

More information

Operating Manual for. Model Recovery, Recycling, Recharging Unit

Operating Manual for. Model Recovery, Recycling, Recharging Unit Operating Manual for Model 34988 Recovery, Recycling, Recharging Unit Model 34988 Recovery, Recycling, & Recharging Unit SAFETY DEFINITIONS: Follow all WARNING, CAUTION, IMPORTANT, and NOTE messages in

More information

OPERATION & MAINTENANCE MANUAL AC860

OPERATION & MAINTENANCE MANUAL AC860 OPERATION & MAINTENANCE MANUAL AC860 Refrigerant Handling System Manual P/N 035-80913-00 TABLE OF CONTENTS Startup & Safe Operation... 1 Introduction to the AC860... 2 Control Panel... 3 Keypad Functions...

More information

OPERATION & MAINTENANCE MANUAL RHS680

OPERATION & MAINTENANCE MANUAL RHS680 OPERATION & MAINTENANCE MANUAL RHS680 Refrigerant Handling System 4075 East Market Street York, PA 17402 800-468-2321 tech@rtitech.com Manual P/N 035-80740-00 (Rev 1- May 22, 2001) TABLE OF CONTENTS Startup

More information

DiscovR R134a Refrigerant Identifier

DiscovR R134a Refrigerant Identifier Model 16009 DiscovR R134a Refrigerant Identifier Operating Manual Table of Contents Safety Precautions... 1 Description... 4 Operating Instructions.... 5 Fault Codes.... 7 Troubleshooting... 7 Replacement

More information

Operating Manual. Model Refrigerant Service Solution

Operating Manual. Model Refrigerant Service Solution Operating Manual Model 342000 Refrigerant Service Solution Series: 342000 Refrigerant: R-134a Air Conditioning and Refrigerant Service Solution SAFETY DEFINITIONS: Follow all WARNING, CAUTION, IMPORTANT,

More information

Model AC Original Instructions. Recover, Recycle, Recharge Machine for R1234yf A/C Systems

Model AC Original Instructions. Recover, Recycle, Recharge Machine for R1234yf A/C Systems Original Instructions 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Model AC1234-6 Recover, Recycle, Recharge Machine for R1234yf

More information

Operation and Maintenance Manual

Operation and Maintenance Manual Warranty Information Ritchie Engineering guarantees YELLOW JACKET products to be free of defective material and workmanship which could affect the life of the product when used for the purpose for which

More information

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual RecoverX Oil-Filled Hermetic Refrigerant Recovery System Operation and Maintenance Manual Table of Contents Page General Safety Instructions 2-3 System Overview 3 Operating Guide 4 Restart Procedure 4

More information

OWNER S MANUAL (English)

OWNER S MANUAL (English) TR600 Series Refrigerant Recovery Machines OWNER S MANUAL (English) Français, Español, Deutsch and latest updates: www.cpsproducts.com Series: TR600, TR610, TR600C, TR610C, TR600S, TR600K, TR600E TO BE

More information

RecoverX-CAR Contaminated Automotive Refrigerant Recovery System Operation and Maintenance Manual

RecoverX-CAR Contaminated Automotive Refrigerant Recovery System Operation and Maintenance Manual RecoverX-CAR Contaminated Automotive Refrigerant Recovery System Operation and Maintenance Manual (English) Table of Contents Page General Safety Instructions...2 System Overview...3 RecoverX-CAR Operation

More information

TRS21 IGNITION PROOF SERIES

TRS21 IGNITION PROOF SERIES TRS21 IGNITION PROOF SERIES 2 Cylinder Commercial Recovery Machine OWNER S MANUAL (English) Français, Español, Deutsch and latest updates: www.cpsproducts.com Series: TRS21A, TRS21E TO BE OPERATED BY QUALIFIED

More information

TRS21 IGNITION PROOF SERIES

TRS21 IGNITION PROOF SERIES TRS21 IGNITION PROOF SERIES 2 Cylinder Commercial Recovery Machine OWNER S MANUAL (English) Français, Español, Deutsch and latest updates: www.cpsproducts.com Series: TRS21, TRS21C, TRS21S Evaluated for

More information

Original Instructions Instucciones originales Consignes originales. Model: AC R-1234yf A/C Recover, Recycle, Recharge Machine

Original Instructions Instucciones originales Consignes originales. Model: AC R-1234yf A/C Recover, Recycle, Recharge Machine Original Instructions Instucciones originales Consignes originales Model: AC1234-6 R-1234yf A/C Recover, Recycle, Recharge Machine Description: Recover, recycle, and recharge machine for use with R-1234yf

More information

OPERATION & MAINTENANCE MANUAL AC880

OPERATION & MAINTENANCE MANUAL AC880 OPERATION & MAINTENANCE MANUAL AC880 Refrigerant Handling System Manual P/N 035-80749-00 TABLE OF CONTENTS AC880 Before Using the AC880... 2 Safety Precautions... 2 Using the AC880... 3 Setup... 4 Fill

More information

Pro-Set TRA21 SERIES Mobile Multiple Refrigerant Recovery / Recycle System

Pro-Set TRA21 SERIES Mobile Multiple Refrigerant Recovery / Recycle System Pro-Set TRA21 SERIES Mobile Multiple Refrigerant Recovery / Recycle System Certified by ITS to meet SAE J2810 for R-134a Designed to meet new SAE J2851 for R-1234yf MANUAL GENERAL INFORMATION Table of

More information

OPERATION & MAINTENANCE MANUAL TC670

OPERATION & MAINTENANCE MANUAL TC670 OPERATION & MAINTENANCE MANUAL TC670 Refrigerant Management Center (Convertible For Use With R12 or R134a) RTI TECHNOLOGIES, INC. 4075 East Market Street York, PA 17402 Manual P/N 035-80342-02 TC670 CONVERTIBLE

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MODEL LV8 COMMERCIAL REFRIGERANT RECOVERY UNIT NATIONAL REFRIGERATION PRODUCTS 985 WHEELER WAY LANGHORNE, PA 19047 (215) 638-8909 FAX (215) 638-9270 A01001 7/11/96 NRP-OM-LV8 7/96

More information

OWNER S MANUAL (English)

OWNER S MANUAL (English) PREMIUM RECOVERY MACHINES OWNER S MANUAL (English) Français, Español, Deutsch and latest updates: www.cpsproducts.com Series: TR700C/E /J/JUK/S; TR710C/S TO BE OPERATED BY QUALIFIED PERSONNEL ONLY Evaluated

More information

OWNER S MANUAL (English)

OWNER S MANUAL (English) TRS600 IGNITION PROOF SERIES Refrigerant Recovery Machines OWNER S MANUAL (English) Français, Español, Deutsch and latest updates: www.cpsproducts.com Series: TRS600, TRS600K, TRS600S Evaluated for performance

More information

Oilless Refrigerant Recovery System. OWNER S MANUAL (English) TO BE OPERATED BY QUALIFIED PERSONNEL ONLY

Oilless Refrigerant Recovery System. OWNER S MANUAL (English) TO BE OPERATED BY QUALIFIED PERSONNEL ONLY Pro-Set TR500 SERIES Oilless Refrigerant Recovery System OWNER S MANUAL (English) Français, Español, Deutsch and latest updates: www.cpsproducts.com Series: TR500, TR500E, TR500J, TR500S TO BE OPERATED

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MODEL LV20 LARGE CAPACITY REFRIGERANT RECOVERY UNIT NATIONAL REFRIGERATION PRODUCTS 985 WHEELER WAY LANGHORNE, PA 19047 (215) 638-8909 FAX (215) 638-9270 R01101 LV20.DOC NRP-OM-LV20

More information

OPERATION & MAINTENANCE MANUAL TX600

OPERATION & MAINTENANCE MANUAL TX600 OPERATION & MAINTENANCE MANUAL TX600 RTI TECHNOLOGIES, INC. 4075 East Market Street York, PA 17402 Manual P/N 035-80118-00 (Rev B) ! TABLE OF CONTENTS! TX600 Before Using Page 2 Safety Precautions Page

More information

Service Manual. Models 17700/17701/17703 Recovery/Recycling/Recharging Unit For R-12 Only

Service Manual. Models 17700/17701/17703 Recovery/Recycling/Recharging Unit For R-12 Only Service Manual Models 17700/17701/17703 Recovery/Recycling/Recharging Unit For R-12 Only Theory of Operation and Safety Precautions... 2 Component Descriptions... 3 Plumbing Diagram... 8 Pictorial Views...

More information

Enspeco RMS. The Enspeco Refrigerant Management. The following instructions will INSTRUCTIONS

Enspeco RMS. The Enspeco Refrigerant Management. The following instructions will INSTRUCTIONS Enspeco AUTOMOTIVE REFRIGERANT MANAGEMENT SYSTEMS RMS 5000 INSTRUCTIONS The Enspeco Refrigerant Management System 5000 provides fast and efficient recovery, recycling and charging of automotive air conditioning

More information

R100 Oil-Less Refrigerant Recovery Unit

R100 Oil-Less Refrigerant Recovery Unit R100 Oil-Less Refrigerant Recovery Unit Operation Manual 1 INTRODUCTION Welcome to simple, efficient refrigerant recovery with your new YELLOW JACKET Refrigerant Recovery Unit, R100. This unit combines

More information

User manual Flushing device VAS 6337/1a

User manual Flushing device VAS 6337/1a User manual Flushing device VAS 6337/1a 2 Content Safety warnings 3 Flushing with R134a refrigerant 4 1.0 Preparing the Vehicle AC System 4 1.1 Connecting the recovery recharge Unit 6 1.2 Flush procedure

More information

REFRIGERANT SYSTEM SERVICE WARNINGS

REFRIGERANT SYSTEM SERVICE WARNINGS 2005 HVAC Refrigerant System - MX-5 Miata REFRIGERANT SYSTEM SERVICE WARNINGS USING/HANDLING UNAPPROVED REFRIGERANT Using a flammable refrigerant, such as OZ-12, in this vehicle is dangerous. In an accident,

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MODEL RLV-700 REFRIGERANT RECOVERY / RECYCLING UNIT (PATENTED) NATIONAL REFRIGERATION PRODUCTS 985 Wheeler Way Langhorne, PA 19047 (215) 638-8909 FAX (215) 638-9270 REVISED 03-21-2018

More information

ENSPECO Recovery/ Recycle/ Evacuate/ Recharge

ENSPECO Recovery/ Recycle/ Evacuate/ Recharge ENSPECO Recovery/ Recycle/ Evacuate/ Recharge RMS 3012 RMS 3034 Approved by UL/SAE to J-1991 R12 Purity Standards Approved by UL/SAE to J-2210 R134 Purity Standards This semi-automatic machine will recover

More information

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC.

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC. Fig. 2: Blower & Evaporator Unit Specifications 2004 HVAC SYSTEMS Manual HVAC System - Sorento GENERAL SPECIFICATIONS AIR CONDITIONER Fig. 1: Air Conditioner Specifications BLOWER AND EVAPORATOR UNIT HEATER

More information

Digital Refrigerant System Analyzer. MAXMIN Psi kpa Bar MPa C F R TIME P T UNITS

Digital Refrigerant System Analyzer. MAXMIN Psi kpa Bar MPa C F R TIME P T UNITS Digital Refrigerant System Analyzer INSTRUCTION MANUAL ENGLISH LOW START PRS T-LOW SUPERHEAT MAXMIN kpa Bar MPa R TIME P T HIGH END PRS T-HIGH SUBCOOL VAC 1-800-547-5740 Fax: (503) 643-6322 www.ueitest.com

More information

99 Washington Street Melrose, MA Phone Toll Free Visit us at

99 Washington Street Melrose, MA Phone Toll Free Visit us at 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com User s Manual 1 WARNING! CAUTION! Before operating this unit, please read this

More information

OPER LV Wheeler Way

OPER LV Wheeler Way OPER RATING INSTRUCTIONS LV5 REFRIGERANT RECOVERY UNIT NATIONAL REFRIGERATION PRODUCTS 985 Wheeler Way Langhorne, PA 19047 Ph:(215) 638-8909 9 info@ @nrproducts.com LV5.DOC 9.17.2018 MODEL LV5 REFRIGERANT

More information

SERVICE PROCEDURE FOR RETROFITTED A/C SYSTEMS

SERVICE PROCEDURE FOR RETROFITTED A/C SYSTEMS Classification: Reference: Date: HA94-005 NTB94-091 September 26, 1994 SERVICE PROCEDURE FOR RETROFITTED A/C SYSTEMS APPLIED VEHICLE(S): All models except Quest equipped with a retrofitted A/C system SERVICE

More information

OPERATIONS MAINTENANCE MANUAL

OPERATIONS MAINTENANCE MANUAL OPERATIONS and MAINTENANCE MANUAL White 1090ST Refrigerant Recovery/Recycle/Recharge Unit Table of Contents Safety... 1 Introduction... 8 Refrigerant Gases... 8 Refrigerant Handling... 9 Refrigerant Safety...

More information

RECOVERY/RECYCLE/RECHARGE

RECOVERY/RECYCLE/RECHARGE RECOVERY/RECYCLE/RECHARGE Operating Instructions 2 CONTENTS SAFETY SUMMARY 4 SAFETY INFORMATION 4 ELECTRICAL SHOCK HAZARDS 4 MOTION HAZARDS 4 FUME HAZARDS 4 HEAT/FREEZING HAZARDS 5 EXPLOSION/FLAME HAZARDS

More information

Mobile Air-Con Service Solution. AC7000 Operation Manual

Mobile Air-Con Service Solution. AC7000 Operation Manual Mobile Air-Con Service Solution AC7000 Operation Manual Cool-It Mobile HVAC Group Contents 1 About this operation manual.......................................... 2 1.1 Cool-It Hotline......................................................

More information

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL 456 Creamery Way, Exton, PA 19341, USA Phone: 610.524.8800 Fax: 610.524.8807 Email: info@refrigerantid.com www.refrigerantid.com Page

More information

RECOVERY/RECYCLE/RECHARGE

RECOVERY/RECYCLE/RECHARGE RECOVERY/RECYCLE/RECHARGE Operating Instructions WARNING!! Do not stop the recovery process. Permanent damage will occur that could void the warranty. CONTENTS INTRODUCTION 4 SAFETY SUMMARY 4 SAFETY INFORMATION

More information

APPENDIX C USER S MANUAL

APPENDIX C USER S MANUAL APPENDIX C USER S MANUAL GENERAL This appendix is for reference only. The Snap-on (ZEEAC318A) version User s Manuals is supplied for your information or can be copied for the customer. This version and

More information

RECOVERY/RECYCLE/RECHARGE

RECOVERY/RECYCLE/RECHARGE RECOVERY/RECYCLE/RECHARGE Operating Instructions WARNING!! Do not stop the recovery process. Permanent damage will occur that could void the warranty. INTRODUCTION This machine is ETL Laboratories approved,

More information

R134a RECOVERY/RECYCLE/RECHARGE Operating Instructions

R134a RECOVERY/RECYCLE/RECHARGE Operating Instructions COMMANDER1000 (-E) COMMANDER2000 (-E) COMMANDER3000 (-E) R134a RECOVERY/RECYCLE/RECHARGE Operating Instructions WARNING!! Do not stop the recovery process. Permanent damage will occur that could void the

More information

Fluid Exchange. Refrigerant Handling Systems Recovery/Recycling Systems Fluid Exchangers Flushers Fluid Exchange Accessories BUYER'S GUIDE

Fluid Exchange. Refrigerant Handling Systems Recovery/Recycling Systems Fluid Exchangers Flushers Fluid Exchange Accessories BUYER'S GUIDE Fluid Exchange Refrigerant Handling Systems Recovery/Recycling Systems Fluid Exchangers Flushers Fluid Exchange Accessories 423 ASCOT 424 Refrigerant Recovery/Recycling Systems Recovery and Recycling Systems

More information

A/C Refrigerant. Air Conditioning systems use refrigerant to move heat from air inside the car to air outside the car

A/C Refrigerant. Air Conditioning systems use refrigerant to move heat from air inside the car to air outside the car A/C Refrigerant Air Conditioning systems use refrigerant to move heat from air inside the car to air outside the car Refrigerants are HAZARDOUS to you and the environment Motor Vehicle Air Conditioning

More information

READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE OPERATING THE MACHINE

READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE OPERATING THE MACHINE XAACT Xtract 200 INFORMATION & OPERATING INSTRUCTIONS READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE OPERATING THE MACHINE 78-00018 Rev B 032912 1 CONTENTS: Machine Specifications............ 2 Record Important

More information

PRO-SET AR2700 & AR2700M SERIES REFRIGERANT RECOVERY / RECYCLING SYSTEM

PRO-SET AR2700 & AR2700M SERIES REFRIGERANT RECOVERY / RECYCLING SYSTEM PRO-SET AR2700 & AR2700M SERIES REFRIGERANT RECOVERY / RECYCLING SYSTEM This Equipment has been certified by Underwriters Laboratories Inc. to meet EPA s minimum requirements for Recovery equipment. TO

More information

EXTRACTOR Operation & Maintenance Manual

EXTRACTOR Operation & Maintenance Manual EXTRACTOR Operation & Maintenance Manual 12 Gallon Carpet Extractor Models 2-100 2-100-H 3-100 3-100-H 2-200 2-200-H 3-200 3-200-H 2-500 2-500-H 3-500 3-500-H US & Foreign Patents Pending The design features

More information

Setup and Operation Manual

Setup and Operation Manual 1645 Lemonwood Dr. Santa Paula, CA. 93060, USA Toll Free: (800) 253-2363 Tel: (805) 933-9970 rangerproducts.com CoolCharge Vehicle AC Servicer Setup and Operation Manual Manual P/N 5900968 Manual Revision

More information

36 IN. ELECTIC FIREPLACE FMI MODEL # LEF36 Mounting Base Feet and Wall Mounting Bracket Included

36 IN. ELECTIC FIREPLACE FMI MODEL # LEF36 Mounting Base Feet and Wall Mounting Bracket Included F3610G FMI PRODUCTS, LLC 36 IN. ELECTIC FIREPLACE FMI MODEL # LEF36 Mounting Base Feet and Wall Mounting Bracket Included FMI Products, LLC TABLE OF CONTENTS Safety Information... 3 Operating Instructions...

More information

Additional users operating manual

Additional users operating manual Additional users operating manual For use with A2L Refrigerants e.g. R32, 1234yf, 143a, 1234ze This additional manual is valid for the following Promax Refrigerant Recovery Units: MiniMax-E; RG 5410A-E,

More information

Whynter Portable Ice Maker 33 lb capacity - White

Whynter Portable Ice Maker 33 lb capacity - White Whynter Portable Ice Maker 33 lb capacity - White Model # : IMC-330WS INSTRUCTION MANUAL Congratulations on your new Whynter product. To ensure proper operation, please read this Instruction Manual carefully

More information

Best Practices for Mobile A/C Refrigerant System Service

Best Practices for Mobile A/C Refrigerant System Service Best Practices for Mobile A/C Refrigerant System Service Note: Refer to the vehicle manufacturer or aftermarket issued service information, the applicable SAE standards, and tool and equipment instruction

More information

K Specifications. Max. Water Volume

K Specifications. Max. Water Volume K 2.75 High Pressure Washer Operator Manual Overview... 2 Precautions... 2-4 Assembly Instructions... 4 Operating Instructions... 5 Using the Accessories... 6 Working with Detergents... 7 Shut Down and

More information

OWNER S MANUAL FOR AIR ADMIRAL VACUUM/PRESSURE STATION MODELS:

OWNER S MANUAL FOR AIR ADMIRAL VACUUM/PRESSURE STATION MODELS: OWNER S MANUAL FOR AIR ADMIRAL VACUUM/PRESSURE STATION MODELS: 79202-00 79202-05 79202-30 79202-35 Approval Agency s Model 79202-00 & 79202-05 Model 79202-30 & 79202-35 Not recommended for pumping acid,

More information

USING R-134A REFRIGERANT

USING R-134A REFRIGERANT USING R-134A REFRIGERANT HANDLING/SAFETY PRECAUTIONS 1998 GENERAL SERVICING General Servicing Procedures 1. Always work in a well-ventilated, clean area. Refrigerant is colorless and invisible as a gas.

More information

Operating Instructions

Operating Instructions Operating Instructions BA-003 Read and understand this manual before use. Keep this manual for future reference. CONFORMS TO UL STD.No.1017 Certified to CSA STD C22.2 No.243-10 For questions or concerns

More information

Quest PowerHeat HFC 100 Pro

Quest PowerHeat HFC 100 Pro Quest PowerHeat HFC 100 Pro Installation, Operation and Maintenance Instructions Read and Save These Instructions This manual is provided to acquaint you with the portable fan coil so that installation,

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

K Specifications. Max. Water Volume

K Specifications. Max. Water Volume K 2.35 High Pressure Washer Operator Manual Overview... 2 Precautions... 2-4 Assembly Instructions... 4 Operating Instructions... 5 Using the Accessories... 6 Working with Detergents... 7 Shut Down and

More information

ELECTRIC FIREPLACE CONVERTER KIT OWNERS MANUAL Model Number: EF05-23

ELECTRIC FIREPLACE CONVERTER KIT OWNERS MANUAL Model Number: EF05-23 ELECTRIC FIREPLACE CONVERTER KIT OWNERS MANUAL Model Number: EF05-23 AC 120V ~ 60Hz ~ 1400W Only use this heater as described in this manual. Any other use is not recommended by the manufacturer, and may

More information

MODEL A5-2 SOLVENT & WATER RECOVERY SYSTEMS (EXPLOSION PROOF UNITS)

MODEL A5-2 SOLVENT & WATER RECOVERY SYSTEMS (EXPLOSION PROOF UNITS) MODEL A5-2 SOLVENT & WATER RECOVERY SYSTEMS (EXPLOSION PROOF UNITS) FOR PROPER AND SAFE USE OF THIS CHEMCHAMP EQUIPMENT, PLEASE FOLLOW THIS DOCUMENT AND LOCAL AUTHORITY. KEEP THIS DOCUMENT FOR FUTURE REFERENCE.

More information

Refrigerant Recovery Unit, Model RRU134

Refrigerant Recovery Unit, Model RRU134 Installation, Operation & Maintenance Manual IOMM RRU134 Group: Refrigerant Effective: December 2000 Supersedes: New Refrigerant Recovery Unit, Model RRU134 1999 McQuay International Table of Contents

More information

Viking Installation Guide

Viking Installation Guide Viking Installation Guide Viking Range Corporation Front Street Greenwood, Mississippi 38930 USA (66) 455-00 For product information, visit the Viking Web site at vikingrange.com Professional Built-In

More information

High Performance Oilless Residential Light Commercial. Product Leadership Training Service Reliability

High Performance Oilless Residential Light Commercial. Product Leadership Training Service Reliability High Performance Oilless Residential Light Commercial Product Leadership Training Service Reliability User Manual 2020-9000 Rev. 1 December 2017 WARRANTY Bacharach, Inc. (Bacharach) warrants to the buyer

More information

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

Automotive Air-Conditioning Service Equipment Ariazone 5001HD OPERATOR MANUAL Ariazone 5001HD

Automotive Air-Conditioning Service Equipment Ariazone 5001HD OPERATOR MANUAL Ariazone 5001HD Automotive Air-Conditioning Service Equipment Ariazone 5001HD OPERATOR MANUAL Ariazone 5001HD - Automotive A/C Service Station 1 Contents Page 1. Introduction... 3 2. Safety firts... 4 3. Technical Features...

More information

Upholstery and Drapery Cleaner. Operator and Parts Manual. Model No.: gal Extractor. MNL32506 Rev. 00 (08-98)

Upholstery and Drapery Cleaner. Operator and Parts Manual. Model No.: gal Extractor. MNL32506 Rev. 00 (08-98) 32506 Upholstery and Drapery Cleaner Model No.: 32506 3 gal Extractor Operator and Parts Manual KLEENRITE 1122 MAPLE STREET MADERA CA 93637 U.S.A. FAX: 1-559-673-5725 CUSTOMER SERVICE: 1-800-241-4865 MNL32506

More information

ELECTRIC FIREPLACE OWNER S MANUAL

ELECTRIC FIREPLACE OWNER S MANUAL ELECTRIC FIREPLACE OWNER S MANUAL MODELS EL1346C 4001358 WARNING: If the information in this manual is not followed exactly, a fire or electrical shock may result causing property damage, personal injury

More information

ACR4 REFRIGERANT MACHINE MAINTENANCE

ACR4 REFRIGERANT MACHINE MAINTENANCE Classification: Reference: Date: HA00-001 NTB00-026 March 13, 2000 ACR4 REFRIGERANT MACHINE MAINTENANCE APPLIED VEHICLES: All Nissan Vehicles with R-134a Air Conditioning SERVICE INFORMATION To ensure

More information

INSTRUCTION MANUAL BEFORE USE, PLEASE READ AND FOLLOW ALL SAFETY RULES AND OPERATING INSTRUCTIONS.

INSTRUCTION MANUAL BEFORE USE, PLEASE READ AND FOLLOW ALL SAFETY RULES AND OPERATING INSTRUCTIONS. INSTRUCTION MANUAL MODEL NUMBER : WD31EC THERMOELECTRIC WATER DISPENSER BEFORE USE, PLEASE READ AND FOLLOW ALL SAFETY RULES AND OPERATING INSTRUCTIONS. Avanti has a policy of continuous improvement on

More information

Quest Dry 105, 155, and 205 Dual

Quest Dry 105, 155, and 205 Dual Quest Dry 105, 155, and 205 Dual Read and Save These Instructions This manual is provided to acquaint you with the dehumidifier so that installation, operation and maintenance can proceed successfully.

More information

K 2.90 M. Specifications Operating pressure, max PSI Water volume GPM Voltage V Amp draw AMPS

K 2.90 M. Specifications Operating pressure, max PSI Water volume GPM Voltage V Amp draw AMPS K 2.90 M High Pressure Washer Operator Manual Overview... 2 Important Precautions... 3-4 Assembly Instructions... 4 Operating Instructions... 5 GFCI Instructions... 6 Using the Accessories... 6 Working

More information

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N T-SERIES Air Conditioner T43 Model INSTRUCTION MANUAL Rev. I P/N 10-1008-145 TABLE OF CONTENTS Warranty and Return Policy...2 IMPORTANT NOTICE...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING

More information

CF1400 DO NOT RETURN PRODUCT TO PLACE OF PURCHASE. IF YOU HAVE ANY QUESTIONS, CALL OUR TOLL FREE HOTLINE:

CF1400 DO NOT RETURN PRODUCT TO PLACE OF PURCHASE. IF YOU HAVE ANY QUESTIONS, CALL OUR TOLL FREE HOTLINE: CF1400 DO NOT RETURN PRODUCT TO PLACE OF PURCHASE. IF YOU HAVE ANY QUESTIONS, CALL OUR TOLL FREE HOTLINE: 1-866-902-9690 8:00 am to 5:00 pm, C.S.T., Monday - Friday www.forcetoolsusa.com TABLE OF CONTENTS

More information

Quest Power Electric Heat EHS 31 Pro

Quest Power Electric Heat EHS 31 Pro Quest DRY Power 150 Electric Heat EHS 31 Pro Read and Save These Instructions The Power Electric Heat EHS 31 Pro portable, heavy duty electric heater features a built-in 50-amp twist lock receptacle designed

More information

English. Your Model Number is: HD1500 IMPORTANT

English. Your Model Number is: HD1500 IMPORTANT Your Model Number is: HD1500 IMPORTANT Attention Valued Customer: The serial number of your machine and date of purchase is necessary information to facilitate warranty claims and the ordering of replacement

More information

Quest Power Electric Heat EHS 62 Pro

Quest Power Electric Heat EHS 62 Pro Quest DRY Power 150 Electric Heat EHS 62 Pro Read and Save These Instructions The Quest Power Electric Heat EHS 62 Pro portable, heavy duty electric heater features multiple power receptacles for connection

More information

Model: LD5 Dual Mode Refrigerant Gas Leak Detector. Operating Instructions

Model: LD5 Dual Mode Refrigerant Gas Leak Detector. Operating Instructions 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Operating Instructions Model: LD5 Dual Mode Refrigerant Gas Leak Detector PAGE

More information

Cooling System Equipment

Cooling System Equipment Air Conditioning Service Centers Leak Detectors Recyclers 2007 Buyers Guide 223 Brake & Refrigerant Handling REFRIGERANT RECOVERY/RECYCLING SYSTEMS Cool-Tech R-134A Recovery, Recycling And Recharging System

More information

S1700 Electric Pressure Washer

S1700 Electric Pressure Washer S700 Electric Pressure Washer 039-8556-0 Use and Care Guide Congratulations on the purchase of your new pressure washer. In order to ensure you have the best possible experience please read through the

More information

CONVERT-ABLE FA1234 REFRIGERANT RECOVER / RECYCLE / EVACUATION AND RECHARGE UNIT

CONVERT-ABLE FA1234 REFRIGERANT RECOVER / RECYCLE / EVACUATION AND RECHARGE UNIT CONVERT-ABLE FA1234 REFRIGERANT RECOVER / RECYCLE / EVACUATION AND RECHARGE UNIT Convertible between four refrigerants: R-134a, R-1234yf, R-22 and R-407C Unit covered under US Patent 8,082,750 and other

More information

AUTOMOTIVE AIR CONDITIONER REFRIGERANT HANDLING SYSTEM

AUTOMOTIVE AIR CONDITIONER REFRIGERANT HANDLING SYSTEM Guangzhou Junliye Import&Export Co., Ltd. AUTOMOTIVE AIR CONDITIONER REFRIGERANT HANDLING SYSTEM OPERATION MANUAL 1. Cautions: Wear the glove and eye protection glass to protect the skin and eyes from

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TSA Series 6 to 20 Ton AIR CONDITIONERS 6 20 TONS 506147 01 06/11 Supersedes 3/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act

More information

K 3.97 M. Specifications or visit our website: In USA call: Part No

K 3.97 M. Specifications or visit our website:   In USA call: Part No K 3.97 M High Pressure Washer Operator Manual Overview... 2 Precautions... 2-4 Assembly Instructions... 4-5 Operating Instructions... 5-6 GFCI Instructions... 6 Using the Accessories... 6 Working with

More information

LS-JRE OPERATION & INSTRUCTION MANUAL

LS-JRE OPERATION & INSTRUCTION MANUAL SOLVENT RECYCLING SYSTEM LS-JRE OPERATION & INSTRUCTION MANUAL Now with adjustable temperature control! TABLE OF CONTENTS Description Page Introduction 1 Safety Precautions 1 Installation / Set-up 1 Supplied

More information

Water Boilers ME10EN, ME15EN. Table of Contents

Water Boilers ME10EN, ME15EN. Table of Contents Water Boilers ME10EN, ME15EN Operator Manual Model ME15EN Model ME10EN Safety Information...2 Rough-In Drawing...3 Installation...4 Priming...5 Cleaning...5 Table of Contents Adjustments...6 Maintenance...7

More information

TFC 400. OPERATOR MANUAL Clarke MODEL /09 Rev C Document Number

TFC 400. OPERATOR MANUAL Clarke MODEL /09 Rev C Document Number TFC 400 OPERATOR MANUAL Clarke MODEL 56380773 1 11/09 Rev C Document Number 56380889 IMPORTANT SAFETY INSTRUCTIONS This machine is only suitable for commercial use, for example, in hotels, schools, hospitals,

More information