Oil Circulation-Its Effects on Compressor Capacity, Theory and Experiment

Size: px
Start display at page:

Download "Oil Circulation-Its Effects on Compressor Capacity, Theory and Experiment"

Transcription

1 Prde University Prde e-pbs International Compressor Engineering Conference School of Mechanical Engineering 1972 Oil Circlation-Its Effects on Compressor Capacity, Theory and Experiment K. W. Cooper Borg-Warner Corporation A. G. Mont York Division Follow this and additional works at: Cooper, K. W. and Mont, A. G., "Oil Circlation-Its Effects on Compressor Capacity, Theory and Experiment" (1972). International Compressor Engineering Conference. Paper 9. This docment has been made available throgh Prde e-pbs, a service of the Prde University Libraries. Please contact epbs@prde.ed for additional information. Complete proceedings may be acqired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at Herrick/Events/orderlit.html

2 OIL CIRCULATION - ITS EFFECT ON COMPRESSOR CAPACITY, THEORY AND EXPERIMENT K. W. Cooper, Principal Engineer York Division, Borg-Warner Corporation York, Pennsylvania A. G. Mont, Principal Engineer York Division, Borg-Warner Corporation York, Pennsylvania INTRODUCTION This paper is an otgrowth of atomotive air conditioning system analysis done at the York Division of Borg-Warner Corporation. One of the conditions for an acceptable atomobile air conditioner is that it be able to qickly cool the car interior after a period of standing in the sn. To simlate this condition, the atomotive indstry ses a so-called "plldown test". This test consists of "soaking" a car with a simlated sn load and at an elevated temperatre ntil a given inside temperatre is reached. The car is then started and the air conditioner engaged. Selected temperatres are monitored as a fnction of time. It has been fond that the performance of the compressor with a given system is important for the initial minte or two of the plldown. If for some reason there is a deterioration of performance at this time, the system cannot seem to catch p to an initially better performing compressor even thogh the capacities of the two are the same after several mintes. Dring one of the plldown tests, this phenomenon was apparent. In attempting to analyze the test, selected calorimeter tests were performed. It was fond that the system had inadvertently been overcharged with oil casing a high oil circlation rate. When these conditions were dplicated on the calorimeter, a difference in capacity of nearly 3% was noted. In order to explain this difference, the thermodynamics of Rl2-oil mixtres was investigated. This paper presents the reslts of that stdy. THERMODYNAMICS A positive displacement compressor will indct a given volme of flid at a given speed and pressre ratio. Figre 1 is a sketch of the refrigeration system. The capacity of the evaporator will be given by; If there is only refrigerant flowing, the capacity will be; Or == fs VD(hz - h1 )"'1 r r r /Vr (2) and if there is an oil-refrigerant mixtre (3) Experience has indicated that volmetric efficiency may be somewhat affected by oil circlation de to the cooling and expansion effect. However, for the first approximation, we will assme that it is not changed. Ths; Taking the ratio of (3) to (2) and sing ( 4) ; It is known that (hz - h 1 ) is less than m r (hz - h1 ) and thatf s is greater than r r m fs ; ths it cannot be told how mch r redction will occr withot some actal calclations. When the liqid mixtre enters the evaporator, it contains circlating oil (x lbs. of oil per lb. of mixtre). As it leaves the evaporator, some of the refrigerant (w lbs. of refrigerant per lb. liqid mixtre) remains in the oil as a liqid. This redces the amont of refrigerant (4) 52

3 vapor. The amont of oil and refrigerant liqid (z lbs. oil and refrigerant liqid per lb. mixtre) is given by; z = x (6) 1 - w The amont of refrigerant vapor is (1 - z). In order to find the amont of refrigerant liqid in the oil leaving the evaporator (w), it is necessary to have an eqation of oil-refrigerant solbility. This stdy is concifned with Rl2-oil mixtres. G. Bambach has developed the following eqations to represent paraffin base Rl2- oil solbility. These eqations are written in the MKS system of nits following Eropean cstom. No attempt has been made to convert to English nits, as it is a simple matter to make the reqired conversions for pressre and temperatre. For temperatres below C. (32 F.): LoglO (P') "" w-j, T' w-l.o and for temperatres above C. (32 F.): Log 1 CP') = w-~ _ w-~ T' (7) (8) -(.2338(w -.6) ) (T' ) Where; P' pressre--kg/cm 2 =.73l(Psia) T' temperatre--kelvin For oil the enthalpy to the same base as Rl2, i.e., liqid at -4 F., is fond by considering the definition; dh = c dt P Now for a typical r,ef,rigerant oil, Ths; or; cp =.43 + o.ooos (Tl J d'h = J C dt ~ T -4 p h = JrT ( (T) ) dt -4 Integrating and sbstitting the limits: (9) (1) (11) (12) h..,.43(t) +.25 T (13) * sperscripts refer to references in the bibliography. The enthalpy of the liqid leaving the evaporator is; h 2 = ( 1 - w) h 2 + w h 2 o rl where, h2 rl liqid Rl2 enthalpy at T 2. Then the enthalpy of the total mixtre leaving the evaporator is; where, (14) h 2.., z h 2 + (1 - z) h 2 (15) m rv h2rv = enthalpy of Rl2 vapor at P 2 and T 2. Reference to Bambach 1 indicates that the heat of mixing for Rl2-oil mixtres is small and ths has been neglected in eqation (15). The enthalpy of the liqid mixtre entering the evaporator is; where, hl.., X hl + (1 - x) hl (16) m rl hlrl =enthalpy of Rl2 liqid at T 1. The mixtre density at the compressor is fond in a similar manner. For the liqid portion of the mixtre; where, 1 fz w -r;;: density of refrigerant liqid at Ts density of oil at Ts. For a common refrigeration oil; /' = ( (T- 6)) 62.4 The mixtre density is then fond by a second application of eqation (17); r where, 1 z 1 - z sm.., r;. + r srv fs '"' density of refrigerant rv vapor at Ps and Ts. Again, reference to Bambach 1 indicates that the volme contraction for Rl2-oil mixtres is small and therefore has been neglected in eqation (19). (17) Eqations (6) throgh (19) may be sed to find the nmerator of eqation (5) The (18) (19) denominator is composed of the pre refrigerant properties at the indicated conditions. It shold be noted that the density ratio calclation is based on the properties at the compressor sction while the enthalpy ratio is calclated sing 53

4 properties entering and leaving the evaporator. The next section presents some of these calclations in parametric form. RESULTS In order to obtain a feeling for the magnitde of the compressor capacity correction, Figres 2, 3 and 4 have been drawn assming no change in pressre and temperatre between the evaporator otlet and compressor sction. These crves have been calclated for a range of conditions typical of atomotive air conditioning system operation. Figre 2 indicates that the capacity correction is not a strong fnction of liqid temperatre. However, the correction factor becomes sizeable.with increased oil circlation when evaporating temperatre and sperheat are held constant. As the evaporating temperatre increases, the capacity correction factor increases. Figre 3, for constant liqid temperatre and sperheat, shows that the capacity correction does not change greatly with evaporating temperatres. The dependance on oil circlation is abot the same as exhibited by Figre 2. Figre 4 shows that sperheat has by far the greatest inflence on capacity redction for a given oil circlation rate. E.g., for a 5% oil circlation the capacity correction factor decreases from.956 to.81 as the sperheat is redced from 3 F. to 3 F. The reason for this is that the solbility of Rl2 in oil is mch greater at low sperheats. Therefore, less refrigerant is available for evaporation. In an actal system, the conditions leaving the evaporator are different than those entering the compressor. This means that the compressor capacity correction mst be broken p into a density correction and an enthalpy correction as indicated in eqation (5). The density correction is calclated sing the pressre and temperatre at the compressor sction, whereas, the enthalpy correction ses the liqid temperatre before expansion and the pressre and temperatre leaving the evaporator. The two factors shold be mltiplied to obtain the compressor capacity correction. Similarly, Figre 6 shows the enthalpy correction as a fnction of oil circlation, liqid te~peratre entering the expansion valve, sperheat and satrated temperatre leaving the evaporator. To facilitate constrction of Figres 5 and 6, some minor approximations have been made. This has been done for illstrative prposes only. For best accracy, the eqations presented above along with refrigerant property sbrotines may be easily solved sing a digital compter. The example lines in Figres 5 and 6 represent the conditions of an actal test. For 7% oil circlation, the density correction is 1.3 and enthalpy correction is.54 reslting in a compressor capacity correction of.72. When the same compressor was retested with the correct oil charge, the oil circlation rate was nearly zero. The measred capacity ratio between the tests was.715. This compares favorably with the calclated correction. A second test with an oil circlation of 2% gave a calclated capacity correction of.934 and a measred correction of.92. CONCLUSION This paper has shown that the thermodynamic effects of Rl2-oil mixtres are important when measring compressor capacity or when designing systems. This is indicated by the agreement between test and calclation. It has been seen that low sperheat has a large effect on performance when there is a significant oil circlation rate. The evaporating temperatre and liqid temperatre exhibit a lesser inflence. This points ot the need for carefl monitoring of oil circlation rates. It shold be noted that this is independent of the effect of oil circlation on heat transfer. ACKNOWLEDGMENT We wold like to express or appreciation to the York Division of Borg-Warner Corporation for the se of their facilities and data. We are gratefl for the help and cooperation of all the people involved in the testing and preparation of this paper. Figre 5 is a graph of the density correction. Enter the graph with the oil circlation, draw a line vertically ntil it intersects the compressor sperheat. From this point, draw a horizontal line to intersect with the compressor satrated temperatre and then down to determine the density correction factor. NOMENCLATURE cp Specific h Enthalpy m Mass flow P' Pressre p Pressre heat of oil rate Bt/lb-F Bt/lb lb/hr Kg/sq em lb/sq in 54

5 Q Capacity Bt/hr T Temperatre F T' Temperatre K Compressor displacement c ft/hr w x z Liqid refrigerant fraction Oil circlation rate Liqid mixtre fraction Density Volmetric Efficiency Sbscripts lb/c ft CONDENSER 1 1 entering evaporator 2 leaving evaporator L liqid 2 EVAPORATOR m mixtre oil r refrigerant s v compressor sction vapor Figre 1. Refrigeration system z liqid mixtre in total mixtre BIBLIOGRAPHY 1. G. Bambach, "Das Verhalten von Mineralol-Fl2-Gemischen in Kaltemaschinen", c. F. Mller, Karlsrhe,

6 15.8 H E-< E;J,.:; :><.7 E-o H ~..: ~.6{) "' "' gz!.5 SATURATED TE!l.PERATURE SUPERHEAT ~ 2 F PERCENT OIL CIRCULATION Figre 2. Compressor Capacity Correction. Liqid Temperatre, R12-i1 Mixtres 1..9 :>: t;. 8 H r:.l,.:; [:: tl. 7..: ~ ~ "' ~.6 "' 15 LIQUID TEHPERATURE = 13 F SUPERHEAT ~ 2 F PERCENT OIL CIRCULATION Figre 3. Compressor Capacity Correction, Satrated Temperatre, 1U2-il l1ixtres 56

7 .9 LIQUID TEMPERATURE ~ 13 F SATURATED TE~IPERATUR.E ~ 3Q F o.so PERCENT OIL CIRCULATION 9 1 Figre 4. Compressor Capacity Correction, Sperheat, Rl2-il Mixtres 57

8 6 4 2pSATURATED TEMPERATURE DENSITY CORRECTION PERCENT OIL CIRCULATION Figre 5. Density Correction, R12-i1 Mixtres 58

9 3 F SUPERHEAT LIQUID TEMPERATU~ 15 F PERCENT OIL CIRCULATION z ><H..8 ~~ E-<P::: zo r.:iu SATURATED TEMPERATURE.5 Figre 6. Enthalpy Correction, Rl2-il Mixtres 59

Experimental Comparison of the Performance of Refrigerants R134a and R32/R134a in Dry Expansion and Liquid Recirculation Refrigerating Systems

Experimental Comparison of the Performance of Refrigerants R134a and R32/R134a in Dry Expansion and Liquid Recirculation Refrigerating Systems Prde University Prde e-pbs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1998 Experimental Comparison of the Performance of Refrigerants R134a and R32/R134a

More information

Two Time Constant Modeling Approach for Residential Heat Pumps

Two Time Constant Modeling Approach for Residential Heat Pumps Prde University Prde e-pbs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1986 To Time Constant Modeling Approach for Residential Heat Pmps D. R. Tree B. W.

More information

R32 As a Solution for Energy Conservation and Low Emission

R32 As a Solution for Energy Conservation and Low Emission Prde University Prde e-pbs nternational Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2 R32 As a Soltion for Energy Conservation and Low Emission R. Yajima Daikin ndstries

More information

* How much fresh intake air reaches the box cut face

* How much fresh intake air reaches the box cut face 157 Ventilating the Box Ct of a Two-Pass 4-ft xtended Ct dward D. Thimons, Charles D. Taylor, and Jeanne A. Zimmer NIOSH Pittsbrgh Research Laboratory Pittsbrgh, PA 15236 ABSTRACT On a continos miner coal

More information

Auto Drain Valve. Longer life & Higher resistance to foreign matter. AD402-A Series CAT.ES40-65A. Improved foreign matter resistance

Auto Drain Valve. Longer life & Higher resistance to foreign matter. AD402-A Series CAT.ES40-65A. Improved foreign matter resistance Ato Drain Valve RoHS Longer life & Higher resistance to foreign matter Improved foreign matter resistance Catching of foreign matter is redced with no sliding part. Diaphragm type Poppet type Shape prevents

More information

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Conceptual Design of a Better Heat Pump Compressor for Northern Climates Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1976 Conceptual Design of a Better Heat Pump Compressor for Northern Climates D. Squarer

More information

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential

More information

Buderus Oil Boilers. Buderus G115 & G215.

Buderus Oil Boilers. Buderus G115 & G215. Bders Oil Boilers Bders G115 & G215 Bders residential oil boilers are designed to extract and deliver more heat from every fel dollar, and are available in higher otpts at less cost per BTU. www.boschheatingandcooling.com

More information

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 004 Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow

More information

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Investigation of Refrigerant Vapor- Injection Technique for

More information

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle

More information

V liquid fromopen width textile material

V liquid fromopen width textile material Textile Chemist and Colorist Agst 199O/Vol. 22, No. 8 Basic Principles of Vacm Slot xtraction By ARTHUR D. BROADBNT. University of Sherbrooke, Sherbrooke. Qebec, Canada acm extraction removes excess V

More information

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube

More information

Asphalt. Tel: +44 (0) u Fax: +44 (0) u

Asphalt. Tel: +44 (0) u Fax: +44 (0) u Asphalt 45 Analysis and Binder Recovery 45 Design and Testing of Bitminos Mixtres 45 Specific Gravity 46 Bitmen and Tar 47 Temperatre and Density 47 Core Drilling 47 Pavement The main engineering se of

More information

Purdue e-pubs. Purdue University

Purdue e-pubs. Purdue University Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 206 Experimental Investigation of the Refrigerant Flow Distribution Characteristic

More information

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Control Method Of Circulating Refrigerant Amount For Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Control Method Of Circulating Refrigerant Amount For Heat Pump System Jin

More information

ASFP On-site guide to installing fire-stopping

ASFP On-site guide to installing fire-stopping ASFP On-site gide to installing fire-stopping ASFP On-site gide to installing fire-stopping In this gide fire-stopping incldes cavity barriers, penetration seals for services and linear joint seals. The

More information

UNDRAINED BEARING CAPACITY OF EMBEDDED STRIP FOOTINGS UNDER VERTICAL AND HORIZONTAL LOADS

UNDRAINED BEARING CAPACITY OF EMBEDDED STRIP FOOTINGS UNDER VERTICAL AND HORIZONTAL LOADS Corrier d Savoir N 8, Mars 4, pp.-5 UNDRAINED BEARING CAPACITY OF EMBEDDED STRIP FOOTINGS UNDER VERTICAL AND ORIZONTAL LOADS D. BENMEDDOUR,. YAIA-CERIF, M. MELLAS Department of Civil and ydralic Engineering,

More information

LA1 UMx0E Metal Column Loudspeakers

LA1 UMx0E Metal Column Loudspeakers Commnications Systems LA1 UMxE Metal Colmn Lodspeakers LA1 UMxE Metal Colmn Lodspeakers www.boschsecrity.com Good speech intelligibility and backgrond msic reprodction For applications where directivity

More information

Study of R161 Refrigerant for Residential Airconditioning

Study of R161 Refrigerant for Residential Airconditioning Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Study of Refrigerant for Residential Airconditioning Applications Yingwen

More information

(Refer Slide Time: 00:00:40 min)

(Refer Slide Time: 00:00:40 min) Refrigeration and Air Conditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 10 Vapour Compression Refrigeration Systems (Refer Slide

More information

Thermal performance of hydronic radiator with flow pulsation Numerical investigation Embaye, Mebrahtu; Al-Dadah, Raya; Mahmoud, Saad

Thermal performance of hydronic radiator with flow pulsation Numerical investigation Embaye, Mebrahtu; Al-Dadah, Raya; Mahmoud, Saad Thermal performance of hydronic radiator with flow plsation Nmerical investigation Embaye, Mebraht; Al-Dadah, Raya; Mahmod, Saad DOI: 10.1016/j.applthermaleng.2014.12.056 License: Other (please specify

More information

MONOTONIC BEHAVIOR OF GEOTEXTILE REINFORCED SOILS UNDER DISCRETE ROTATION OF PRINCIPAL STRESSES *

MONOTONIC BEHAVIOR OF GEOTEXTILE REINFORCED SOILS UNDER DISCRETE ROTATION OF PRINCIPAL STRESSES * IJST, Transactions of Civil Engineering, Vol. 8, No. C2, pp 25-5 Printed in The Islamic Repblic of Iran, 214 Shiraz University MONOTONIC BEHAVIOR OF GEOTEXTILE REINFORCED SOILS UNDER DISCRETE ROTATION

More information

LA1 UMx0E 1 Metal Column Loudspeakers

LA1 UMx0E 1 Metal Column Loudspeakers Commnications Systems LA UMxE Metal Colmn Lodspeakers LA UMxE Metal Colmn Lodspeakers www.boschsecrity.com Good speech intelligibility and backgrond msic reprodction For applications where directivity

More information

WARNING Important Safety Information

WARNING Important Safety Information 2 Installation Premier Series Non-Programmable Thermostats MODEL 3300 Mlti-Stage 3 Heat / 2 Cool Ato Changeover Conventional and Heat Pmp Before Installing or Operating, PLEASE READ ALL INSTRUCTIONS 1

More information

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Load Sharing Strategies in Multiple Compressor Refrigeration Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2 Load Sharing Strategies in Multiple Compressor Refrigeration Systems K. A.

More information

Heat Transfer of R-22 and Alternatives in a Plate- Type Evaporator

Heat Transfer of R-22 and Alternatives in a Plate- Type Evaporator Purdue University Purdue e-pubs nternational Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Heat Transfer of R-22 and Alternatives in a Plate- Type Evaporator S. Wellsandt

More information

High Efficiency R-134a Compressor for Domestic Refrigerator

High Efficiency R-134a Compressor for Domestic Refrigerator Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1996 High Efficiency R-134a Compressor for Domestic Refrigerator D. S. Kim Samsung Electronics

More information

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2016 Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent

More information

GEC Low-frequency Horn Strobes

GEC Low-frequency Horn Strobes Fire Alarm Systems GEC Low-freqency Horn Strobes GEC Low-freqency Horn Strobes Silence the horn while strobes flash Evacation tone Use the SperSlide featre for easy testing Wide voltage range; 16 to 33

More information

Air-Cooled Heat Exchanger Performance for R410A

Air-Cooled Heat Exchanger Performance for R410A Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1996 Air-Cooled Heat Exchanger Performance for R41A T. Ebisu Daikin Industries

More information

Low GWP Refrigerants for Air Conditioning Applications

Low GWP Refrigerants for Air Conditioning Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta

More information

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

More information

MODEL FTGF2P (240 VAC)

MODEL FTGF2P (240 VAC) SUMMARY MODEL FTGF2P (240 VAC) OPTIONS SELECTION At the back of the thermostat, there are two selection switches to set yor preference. 1 2 Temperatre in C or F. Time in 12 or 24 hors. TO SET TIME AND

More information

Design of Compressors to Meet the Performance Ranges Required for Residential Air Conditioning

Design of Compressors to Meet the Performance Ranges Required for Residential Air Conditioning Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1984 Design of Compressors to Meet the Performance Ranges Required for Residential Air Conditioning

More information

Compressor Capacity Control

Compressor Capacity Control Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1996 Compressor Capacity Control N. B. Alyokhin Odessa Polytechnic University V. P. Malakhov

More information

FAP-420/FAH-420 Automatic Fire Detectors LSN improved version

FAP-420/FAH-420 Automatic Fire Detectors LSN improved version Fire Alarm Systems FAP-420/FAH-420 Atomatic Fire Detectors LSN improved version FAP-420/FAH-420 Atomatic Fire Detectors LSN improved version www.boschsecrity.com Combination of optical, thermal and chemical

More information

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

LC4 Ceiling Loudspeaker Range

LC4 Ceiling Loudspeaker Range Commnications Systems LC4 Ceiling Lodspeaker Range LC4 Ceiling Lodspeaker Range www.boschsecrity.com Innovative CosCone fll range driver Excellent speech and msic reprodction Unrivalled opening angle for

More information

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Lars Sjoholm

More information

6 Advanced Programming

6 Advanced Programming 6 Advanced Programming 6.1 Program Codes This chapter provides the Program Codes table which smmarizes the wide variety of available programming operations, along with a description and comments. Additional

More information

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature. Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Performance Evaluation of Heat pump System using and ed Refrigerant in

More information

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition Purdue University Purdue e-pubs nternational Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2 Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

More information

FAS 420 Series Aspirating Smoke Detectors LSN improved version

FAS 420 Series Aspirating Smoke Detectors LSN improved version Fire Alarm Systems FAS 420 Series Aspirating Smoke Detectors LSN improved version FAS 420 Series Aspirating Smoke Detectors LSN improved version www.boschsecrity.com Connectable to the fire panels FPA

More information

Efficiency of Non-Azeotropic Refrigerant Cycle

Efficiency of Non-Azeotropic Refrigerant Cycle Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1998 Efficiency of Non-Azeotropic Refrigerant Cycle X. Liu Carrier Corporation

More information

Professional Series Intrusion Detector Knows when to alarm. Knows when not to. Back. Now Featuring Multi-Point Anti-Mask with Spray Detect

Professional Series Intrusion Detector Knows when to alarm. Knows when not to. Back. Now Featuring Multi-Point Anti-Mask with Spray Detect Professional Series Intrsion Detector Knows when to alarm. Knows when not to. Back Now Featring Mlti-Point Anti-Mask with Spray Detect Intelligent motion detection with nmatched versatility If yo cold

More information

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps

More information

Simulation of the Working Process of an Oil Flooded Helical Screw Compressor with Liquid Refrigerant Injection

Simulation of the Working Process of an Oil Flooded Helical Screw Compressor with Liquid Refrigerant Injection Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1992 Simulation of the Working Process of an Oil Flooded Helical Screw Compressor with Liquid

More information

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2016 Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during

More information

LBC 3200/00 Line Array Indoor Loudspeaker

LBC 3200/00 Line Array Indoor Loudspeaker Commnications Systems LBC 3200/00 Line Array Indoor Lodspeaker LBC 3200/00 Line Array Indoor Lodspeaker www.boschsecrity.com Extended listening area Excellent intelligibility of speech and msic Uniform

More information

Multi-Family Green Building Programs. Chris Johnson Johnson Environmental Subsidiary of, Integro Services Group, Inc. Engineers and Architects

Multi-Family Green Building Programs. Chris Johnson Johnson Environmental Subsidiary of, Integro Services Group, Inc. Engineers and Architects Mlti-Family Green Bilding Programs Chris Johnson Johnson Environmental Sbsidiary of, Integro Services Grop, Inc. Engineers and Architects In accordance with the Department of Labor and Indstry s statte

More information

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Effect of Height Difference on The Performance of Two-phase Thermosyphon

More information

FAP-420/FAH-420 Automatic Fire Detectors LSN improved version

FAP-420/FAH-420 Automatic Fire Detectors LSN improved version Fire Alarm Systems FAP-420/FAH-420 Atomatic Fire s LSN improved version FAP-420/FAH-420 Atomatic Fire s LSN improved version www.boschsecrity.com Combination of optical, thermal and chemical sensors with

More information

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor

More information

An Analysis of a New Type Refrigeration Cycle (MICLOSS)

An Analysis of a New Type Refrigeration Cycle (MICLOSS) Purdue University Purdue e-pubs nternational Compressor Engineering Conference School of Mechanical Engineering 1982 An Analysis of a New Type Refrigeration Cycle (MCLOSS) F. Matsuoka Follow this and additional

More information

LH1 UC30E Music Horn Loudspeaker

LH1 UC30E Music Horn Loudspeaker Commnications Systems LH1 UC3E Msic Horn Lodspeaker LH1 UC3E Msic Horn Lodspeaker www.boschsecrity.com Excellent speech and msic reprodction Two way system Attractive ABS hosing Provisions for internal

More information

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2006 Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

More information

Comparison of Thermophysical Properties of HFC 125, 32 and 143a

Comparison of Thermophysical Properties of HFC 125, 32 and 143a Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1992 Comparison of Thermophysical Properties of HFC 125, 32 and 143a D. Arnaud

More information

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1998 Effects of Frost Formation on the External Heat Transfer Coefficient of

More information

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE Proceedings of the Asian Conference on Thermal Sciences 2017, 1st ACTS March 26-30, 2017, Jeju Island, Korea ACTS-P00385 THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK

More information

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Evaluation of a Plug-In Refrigeration System Running Under

More information

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 200 Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid Haruhisa

More information

Visualization of Magnetic Field

Visualization of Magnetic Field Visalization of Magnetic Field Neda Pekaric Nad University of Novi Sad, Faclty of technical sciences, Department of Power, electronics and telecommnications, Novi Sad Friday, September 15, 2017, ASB 10901

More information

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Improving Heating Performance of a MPS Heat Pump System With Consideration

More information

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2004 Development and Performance Measurements of a Small Compressor for Transcritical CO2

More information

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 22 Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement

More information

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2008 The Innovative Green Technology for Refrigerators Development of Innovative Linear

More information

R32 Compressor for Air conditioning and Refrigeration applications in China

R32 Compressor for Air conditioning and Refrigeration applications in China Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2012 R32 Compressor for Air conditioning and Refrigeration applications in China Weihua

More information

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length HEIMO WALTER Institute for Thermodynamics and Energy Conversion Vienna University

More information

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 26 Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants Jit Guan

More information

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to

More information

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2002 Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying

More information

Design and Test Results of a Sliding Vane Rotary Compressor for an Aircraft POD Cooling System

Design and Test Results of a Sliding Vane Rotary Compressor for an Aircraft POD Cooling System Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1986 Design and Test Results of a Sliding Vane Rotary Compressor for an Aircraft POD Cooling

More information

SBS5311 HVACR II Experiment 2: Analysis of the Combined Rankine and Vapour Compression Cycle

SBS5311 HVACR II   Experiment 2: Analysis of the Combined Rankine and Vapour Compression Cycle Introduction SBS5311 HVACR II http://ibse.hk/sbs5311/ Experiment 2: Analysis of the Combined Rankine and Vapour Compression Cycle The Rankine cycle is an idealized thermodynamic cycle of a heat engine

More information

LBC 3201/00 Line Array Indoor Loudspeaker

LBC 3201/00 Line Array Indoor Loudspeaker Commnications Systems LBC 3201/00 Line Array Indoor Lodspeaker LBC 3201/00 Line Array Indoor Lodspeaker www.boschsecrity.com Extended listening area Excellent intelligibility of speech and msic Uniform

More information

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Systematic Study of the Solution Properties of Low Global Warming Potential

More information

Superheat charging curves for technicians

Superheat charging curves for technicians This website requires certain cookies to work and uses other cookies to help you have the best experience. By visiting this website, certain cookies have already been set, which you may delete and block.

More information

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET

More information

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat

More information

Protecting Your. Waterfront. Investment. 10 Simple. Shoreland Stewardship Practices

Protecting Your. Waterfront. Investment. 10 Simple. Shoreland Stewardship Practices Protecting Yor Waterfront Investment 10 Simple Shoreland Stewardship Practices 1 HEALTHY WATERSHEDS MAKE HEALTHY LAKES and higher property vales The qality of or lakes and streams is ltimately a reflection

More information

LBC 3210/00 Line Array Indoor/Outdoor Loudspeaker

LBC 3210/00 Line Array Indoor/Outdoor Loudspeaker Commnications Systems LBC 3210/00 Line Array Indoor/Otdoor Lodspeaker LBC 3210/00 Line Array Indoor/Otdoor Lodspeaker www.boschsecrity.com Extended listening area Excellent intelligibility of speech and

More information

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant International Journal of Scientific and Research Publications, Volume 4, Issue 7, July 2014 1 Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170

More information

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube

More information

LBB 1990/00 Plena Voice Alarm Controller

LBB 1990/00 Plena Voice Alarm Controller Commnications Systems LBB 1990/00 Plena Voice Alarm Controller LBB 1990/00 Plena Voice Alarm Controller www.boschsecrity.com Heart of the Plena Voice Alarm System EN 54 16 certified and EN 60849 compliant

More information

LBC 3011/x1 Panel Loudspeakers

LBC 3011/x1 Panel Loudspeakers Commnications Systems LBC 311/x1 Panel Lodspeakers LBC 311/x1 Panel Lodspeakers High-qality speech and msic reprodction Two-way system Simple power setting Flsh-monting in walls, ceilings, or frnitre Srface-monting

More information

Hot Water Dispenser. Important: Read and save these instructions.

Hot Water Dispenser. Important: Read and save these instructions. Part No. 3184330 nstallation nstrctions/use and Care Gide Hot Water Dispenser mportant: Read and save these instrctions. MPORTANT: nstaller: Leave nstallation nstrctions with homeowner. Homeowner: Keep

More information

Autonomic Distributed Coordinative Control "F- VPM" for Multiple Air Conditioners with Concurrent Cooling and Heating Operation

Autonomic Distributed Coordinative Control F- VPM for Multiple Air Conditioners with Concurrent Cooling and Heating Operation Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1992 Autonomic Distributed Coordinative Control "F- VPM" for Multiple Air Conditioners

More information

RSES Technical Institute Training Manual 1 70 hours, 70 NATE CEHs, 7.2 CEUs

RSES Technical Institute Training Manual 1 70 hours, 70 NATE CEHs, 7.2 CEUs Lesson 1 - Introduction to Refrigeration and Air Conditioning Define refrigeration. Identify the basic components of a refrigeration cycle. Identify the various gas laws and their importance to a basic

More information

LC4 Ceiling Loudspeaker Range

LC4 Ceiling Loudspeaker Range Commnications Systems LC4 Ceiling Lodspeaker Range LC4 Ceiling Lodspeaker Range www.boschsecrity.com Innovative CosCone fll range driver Excellent speech and msic reprodction Unrivalled opening angle for

More information

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Low Global Warming Refrigerants For Commercial Refrigeration Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Low Global Warming Refrigerants For Commercial Refrigeration Systems Samuel

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS FANMATE FEATURING EZClip TM by MAXXAIR VENTILATION SOLUTIONS SUPERIOR RAIN PROTECTION OPTIONAL BUG SCREEN ASSEMBLY AND FOR MODELS: SMOKE 755, WHITE 855, AND BLACK 955 READ AND SAVE THESE INSTRUCTIONS WARNING:

More information

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) 4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao

More information

ASFP Guide to Inspecting Passive Fire Protection for Fire Risk Assessors. Association for Specialist Fire Protection

ASFP Guide to Inspecting Passive Fire Protection for Fire Risk Assessors. Association for Specialist Fire Protection ASFP Gide to Inspecting Passive Fire Protection for Fire Risk Assessors Association for Specialist Fire Protection www.asfp.org.k Foreword I am very pleased to welcome this essential gide to inspecting

More information

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low Global Warming Potential Alternative Refrigerants Evaluation Program

More information

ENSC 388. Assignment #6

ENSC 388. Assignment #6 ENSC 388 Assignment #6 Assignment date: Wednesday Oct. 21, 2009 Due date: Wednesday Oct. 28, 2009 Problem 1 A turbine operating at steady state receives air at a pressure of 3.0 and a temperature of 390.

More information

Performance of CO2 Cycles with a Two-Stage Compressor

Performance of CO2 Cycles with a Two-Stage Compressor Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2004 Performance of CO2 Cycles with a Two-Stage Yun Hong Hwang University of

More information

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study of Fouling Performance of Air Conditioning System with

More information

LBB 1990/00 Plena Voice Alarm Controller

LBB 1990/00 Plena Voice Alarm Controller Commnications Systems LBB 1990/00 Plena Voice Alarm Controller LBB 1990/00 Plena Voice Alarm Controller www.boschsecrity.com Heart of the Plena Voice Alarm System EN 54 16 certified and EN 60849 compliant

More information

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 The Effect of the Ventilation and the Control Mode on the Performance of

More information