INSTALLATION AND MAINTENANCE INSTRUCTIONS EVP EVP 500 LEK

Size: px
Start display at page:

Download "INSTALLATION AND MAINTENANCE INSTRUCTIONS EVP EVP 500 LEK"

Transcription

1 MOS GB INSTALLATION AND MAINTENANCE INSTRUCTIONS LEK

2 LEK LEK LEK LEK LEK LEK

3 Table of Contents For Home Owners General System description Principle of operation 3 Abbreviations 3 System diagram 3 Front panel Visible part of front panel 4 Functions on the front panel 4 Room temperature Heating control system 6 Default setting 6 Changing the room temperature manually 6 Hot water temp. Maintenance routines 7 For the Installer General information for the installer Transport and storage 8 Assembly 8 Inspection of the installation 8 Connection 8 Extra electric hot water heater 9 Electrical connections Folding down the front panel 10 Connection 11 Internal fuse protection 11 Resetting the temperature limiter 11 Power rating as set at the factory 12 Max phase current 12 Connecting the outside sensor 13 Input for external power monitor 13 Centralised load control/tariff 13 Quick start boiler mode 13 Blocking room heating during tariff control 13 Input for external charge pump feed 14 External additional relay 14 Temperature sensor data 14 Docking General 15 Pipe connection to NIBE FIGHTER outdoor air heat pump 15 Communication between and F20XX 16 Pipe connection to other outdoor air heat pump 17 Extra docking connections 17 Electric boiler mode 17 Electrical connection 17, F20XX and solar panel 18 Abbreviations 18, F20XX and oil/pellet/gas boiler 19, F20XX and combi/wood boiler 20, wood boiler, accumulator tank and solar panel 21 Commissioning and adjusting Preparations 22 Addition 22 Venting the heating system 22 Start-up and inspection 22 Setting of temperature levels 23 Adjustment, charge flow F20XX 24 Charge pump diagram 25 Readjustment 25 Draining the heating system 25 Setting of flow temperature 26 Miscellaneous Dealing with malfunctions Low hot water temperature or no hot water 27 High hot water temperature 27 Low room temperature 27 High room temperature 27 Electric boiler operation due to blocked heat pump 27 Switch position 28 Resetting the miniature circuit breakers 29 Alarm 29 Fine wire fuse 29 Electrical circuit diagram Dimensions Technical specifications Component positions 34 List of components 35 Technical specifications 36 Accessories 37 Enclosed kit 37 1

4 For Home Owners General General In order to get the ultimate benefit from your indoor module, you should read through the For Home Owners section in this Installation and Maintenance Instruction. is intended for houses/properties with waterborne heating. A climate controlled automatic bypass ensures that the indoor module is always working as efficiently as possible. is a Swedish-made quality product offering a long life span and reliable operation. The serial number* (95) must always be stated in all correspondence with NIBE. 089 Installation date Installation engineers Setting, "VP connection difference" (2 ºC at delivery) Setting "Max electrical output" (9 kw at delivery) Setting "Max flow line" (55 ºC at delivery) Setting "Heat pump operating mode" (NORM at time of delivery) Setting, "Immersion heater thermostat" (60 ºC at delivery) Setting "Option, heating curve" (10 at delivery) Setting "Offset heating curve" (-2 at delivery) Any changes to default values are made here. Datum Sign *Serial numbers are on the left of the top cover. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance. Rights to make any design or technical modifications are reserved. NIBE

5 For Home Owners System description System description Principle of operation is an indoor module designed for houses/smaller properties with waterborne heating. The indoor module consists of a pressure vessel, two immersion heater, charge pump as well s intelligent control and is suitable for docking with NIBE's air/water heat pumps. Hot water heating occurs via a cam pipe coil. The low internal volume and high circulation rate of the water in the coil prevents bacterial growth. In the event of a domestic water flow greater than 12 l/min, supplementing with a core water heater is recommended. The immersion heaters have a max output of 18 kw withoption of setting lower outputs. The supplied output is 9 kw. The indoor module and heat pump work optimally towards a heat distribution system of up to 55/45 C at dimensioned outdoor temperature. At higher flow line temperatures (maximum 65 C) heat pump operation can be limited. If the heat pump operation is limited the installation only works with the addition. The heat pump starts when temperatures permit operation again. For further information about system limitation, see the heat pump manual. The total boiler water volume is 500 litres. System diagram The supply temperature is determined by the current outdoor temperature and selected settings. Abbreviations OFF* Shut-off valve BL* Mixer valve CP* Circulation pump DG Docking sensor EXP* Expansion vessel FG Temperature sensor, flow line PG Boiler sensor RC Control box SV Shunt valve SÄV1* Safety valve, boiler SÄV2* Safety valve, water heater SÄV3* Safety valve, heat pump TV Drain valve OS** Temperature sensor, outdoor BV** Non-return valve SN Charge pump SF* Particle filter EXP* CP* SÄV1* SÄV2* BL* FG RC SV PG UG** SÄV3* AV* BV** DG SF* AV* LP TV F20XX F20XX * Not included in the consignment NOTE: This is an outline diagram. Actual installations must be planned according to applicable standards. ** Enclosed 3

6 For Home Owners Front panel Front panel Visible part of front panel Boiler temperature gauge Heat pump operating mode Immersion heater thermostat A B C D E F G H In Switch Operating mode, immersion heater Operating mode indicator Alarm indication Curve coefficient Offset heating curve Functions on the front panel A Boiler temperature gauge Current boiler temperature is displayed here. B Heat pump operating mode This knob can be set in five positions. ECO Economy mode --- NORM minus NORM Normal mode --- NORM plus COMF Comfort mode C Immersion heater thermostat Displays the selected setting on the immersion heater thermostat. D Switch with three modes 1-0- : 1 Normal mode. All control functions connected. 0 The indoor module is completely switched off. Standby mode. This mode is used in the event of operating disturbances. 4

7 For Home Owners Front panel E F G H Operating mode, immersion heater with 2 modes: ON and OFF ON An immersion heater is permitted if so required (Normal mode) OFF Immersion heater is completely blocked. Operating mode indicator This is a green lamp which can either light continuously or flash once, twice or three times every 5 seconds. Constantly on Shows that is operational and that no heating is required. One flash Two flashes Three flashes emits signals to the heat pump (F20XX), indicating that heating is required. emits signals to both the heat pump (F20XX) and the additional heat output, indicating that heating is required. emits a signal to the additional heat output, indicating that heating is required (F20XX blocked). Alarm indication This is a red lamp which may be on, flashing or off. On Existing alarms in the heat pump or sensor alarms in. Flashing* Communication error between heat pump and. Off Normal operation Curve coefficient Knob "Curve coefficient" is used to set the automatic heating control system, see section "Default setting" on page 6. In Offset, heating curve With the knob "Offset heating curve", you can change the heating curve offset and hence the room temperature; see section "Default setting" on page 6 and "Setting of flow temperature" on page 26. * If the heat pump is made by a manufacturer other than NIBE, see section "Electrical connection" on page 17. 5

8 For Home Owners Room temperature Room temperature Heating control system The indoor temperature depends on several factors. During the hot season, solar radiation and heat given off by people and equipment are sufficient to keep the house warm. When it gets colder outside, the heating system must be started. The colder its gets, the hotter the radiators must be. This adjustment is made automatically, however the basic settings must first be made on the indoor module, see the section Default setting on page 6. Default setting For optimum operational economy, make settings first on the indoor module with any room thermostats fully open. When the correct "Heating curve selection" and "Offset, heat curve" have been selected, the thermostats can be controlled to compensate for solar radiation etc. For basic setting, use the knob "Option, heating curve" and the knob "Offset heating curve". If the required room temperature is not obtained, readjustment may be necessary. Readjustment the default settings Cold weather conditions If the room temperature is too low, increase the curve offset setting by one step. If the room temperature is too high, reduce the heating curve setting by one step. Warm weather conditions If the room temperature is too low, increase the curve offset setting by one step. If the room temperature is too high, reduce the curve offset" setting by one step. heating Option, heating "Heating NOTE Wait one day between settings so that the temperatures have time to stabilise. Changing the room temperature manually If you want to temporarily or permanently lower or raise the indoor temperature relative to the previously set temperature, turn the "Heating curve offset" knob anticlockwise or clockwise. One line approximately represents a 1 degree change in room temperature. NOTE: An increase in the room temperature may be limited by the radiator or underfloor heating thermostats, if so these must be turned up. 6

9 For Home Owners Hot water temp. Hot water temp. Upon delivery, the indoor module is set to normal mode on the knob and 60 C on the knob. This usually gives a good combination of optimal savings and comfort. To increase the hot water capacity (the comfort): In cold weather Turn the knobs and one step clockwise. In hot weather Turn the knob, one step clockwise. If the hot water capacity is sufficient, both knobs and can be turned one step counterclockwise. This results in less comfort but greater savings. Tappvarmvattenvolym (litres) 40 ºC [liter] 400 Domestic hot water volume 40 C Supreme comfort 1. Normal drain flow (8 l / min) 2. High drain flow (12 l / min) 1 Hög komfort Normal komfort 100 Normal comfort 0 ECO NORM COMF Hög High besparing savings Normal Normal besparing saving Maintenance routines Checking the safety valves,must be provided with two safety valves when installed; one for the heating system and one for the water heater. The heating system s safety valve must be completely tight, but the water heater s safety valve may occasionally release some water after hot water has been used. This is because the cold water, which enters the water heater to replace the hot water, expands when heated causing the pressure to rise and the safety valve to open. The safety valves must be checked regularly. Check as follows: Open the valve. Check that water flows through the valve. Close the valve again. Check the pressure. If the pressure is too low, top up the boiler water. NOTE In the event of a domestic water flow greater than 12 l/min, it is recommended to supplement with a core water heater. 7

10 For the Installer General information for the installer General information for the installer Transport and storage The inside module should be transported and stored vertically in a dry place. If the inside module has to be transported horizontally, this should be done with care. Assembly The indoor module is ideally located in a utility room or boiler room. The unit can be aligned using the adjustable feet. The inside module's factory-fitted lifting eye can be removed after installation and the insulation plug enclosed is pressed into place in order to reduce heat losses. If pipes are to be routed on an internal wall that backs on to a bedroom or living room, this must take place without clamping. Inspection of the installation Current regulations require the system to be inspected before it is commissioned. The inspection must be carried out by a suitably qualified person and should be documented. The above applies to closed heating systems. Therefore, the boiler must not be replaced without reinspection. Connection Pipe installation must take place in accordance with applicable heating and hot water standards. Internal support bushes should be fitted when an annealed copper or steel pipe is used. Overflow pipes from safety valves must be passed to floor drains so that hot water cannot splash when the valves have to checked or the indoor module vented. The overflow pipe must be routed enclosed along its entire length to prevent water pockets and be frost proof. The outlet of the pipe must be clearly visible. The hot water circuit must be provided with a mixing valve as the boiler temperature can exceed 60 C and there is a risk of scalding. can be connected to both an open and a closed expansion tank. If the heating system is provided with an open expansion tank, the distance between the highest radiator and the expansion tank must be no less than 2.5 m. Min 2,5 m 8

11 ARMATUR For the Installer General information for the installer Extra electric hot water heater The facility should be supplemented with an electric water heater, if a hot tub or other significant consumer of hot water is installed. If the heater is equipped with a valve connector Ø 15 mm this should be replaced with a corresponding one (separable) Ø22mm. Appropriate heater is COMPACT for floor mounting and EMINENT for wall mounting. 1. Separate the valve connector. 2. Install the valve connector part on incoming cold water to the heater. 3. Install the mixing valve part on outgoing hot water from the heater. 4. Plug the part on the valve connector part. VALVE CONNECTION-SPLIT Ventilkoppel-del HW Vv OFF från EVP värmepump 500 CW Kv NON-RETURN VALVE Backventil MIXING Blandningsventil-del VALVE-SPLIT PLUGGING Proppas HW Vv VALVE CONNECTION-SPLIT MIXING VALVE-SPLIT LEK NOTE The pipe work must be flushed before the indoor module is connected, so that any contaminants do not damage the component parts. 9

12 For the Installer Electrical connections Electrical connections Folding down the front panel The front panel folds down by undoing the two screws at the top of the panel. The panel can then be folded down into a horizontal position (against stop lugs on either side of the front panel). Rear of front panel 33 LEK 34 Strain relief device When connecting an electrical output greater than 9 kw, the strain relief device for the supply cable needs to be replaced with an enclosed strain relief device. For cables up to 2.5 mm 2, the small one can ideally the factory fitted strain relief device be used. The one included is fitted for thicker cables. 10

13 LEK For the Installer Electrical connections X9 X12 X10 X11 Connection Disconnect the indoor module before insulation testing the house wiring. must be installed via an isolator switch with a minimum breaking gap of 3 mm. When the building is equipped with an earth-fault breaker, should be equipped with a separate one. Remove the upper cover. The connection cable must be connected to the terminal block (X9) according to the terminal block's markings and installed in one of the strain reliefs for the cable. 0 N L L1 L2 L3 X9 Resetting the temperature limiter The temperature limiters (6) 1 and 2 interrupt the power supply to the immersion heaters and the boiler temperature is between 90 C and 100 C, these can be reset by pressing the button on the relevant temperature sensor. The temperature limiters (6) 1 and 2 can be accessed behind the lower cover, where they are positioned on top of the panel. These can be reset by pressing the buttons on the respective temperature limiters. NOTE Reset the temperature limiters, they may have tripped during transport. NOTE Electrical installation and service must be carried out under the supervision of a qualified electrician. Electrical installation and wiring must be carried out in accordance with the stipulations in force. 6 6 NOTE The switch (8) must not be moved from "0" until the boiler has been filled with water. Otherwise the temperature limiter, thermostat and immersion heater may be damaged. Internal fuse protection Automatic elements, charge pump (17) and its cabling are fuse-protected internally with a miniature circuit breaker (7), plus a fine-wire fuse (33) on the relay card (34). 11

14 For the Installer Electrical connections Power rating as set at the factory The two immersion heaters have a total max. output of 18 kw. The power rating as set at the factory is 9 kw. Max phase current Immersion heater, output (kw) Max load phase (A) Different max outputs are set using the knob "Max electrical output" (61) on the relay card (34) LEK 12

15 For the Installer Electrical connections Connecting the outside sensor The outside sensor (15) must be installed in a shaded location on a wall facing north or north-west, where it will not be affected by the morning sun, for example. This sensor is connected by twin cables to terminal (X12), positions "7" and "8". The minimum cable cross section should be 0.4mm 2 up to lengths of 50 metres, for example, EKKX or LiYY. External Externt UG X12 Input for external power monitor The indoor module is provided with a control input for an external output monitor. The output (potential free) of the external output monitor is connected to terminal (X12), positions "5" and "6". If positions "5" and "6" are closed, any connected electrical steps are gradually disconnected at 10 second intervals until the current does not exceed the permissible value. Reconnection of the additional electricity then occurs automatically. X12 Quick start boiler mode During normal operation, it takes one hour from boiler operation activation until the first electrical step cuts in, and then one hour between each electrical step. To shorten the time until the first electrical step cuts in, it is possible to quick start by: 1. Bridge both tariff A (electrical tariff) and tariff B (compressor tariff), terminal block X12 terminal 1 and 2 as well as 3 and Remove tariff A terminals 1 and 2. This means that the first electrical step cuts in after only 5 seconds. 3. When the first electrical step is activated, tariff B, terminal block 12, terminals 3 and 4 are also removed to allow the compressor in the heat pump to produce heat. Blocking room heating during tariff control The supplied bridge is used to save the stored heat energy in for hot water production, when both tariff A and B are activated. Connect the bridge on the microprocessor board (41), terminal block X3 between terminals 31 and 32. With the bridge installed, the shunt valve closes completely as tariffs A and B are activated at the same time. This means that no heat is retrieved from. During the time that tariff A and B are activated, no new hot water is produced, only access to existing hot water is available. LEK Centralised load control/tariff If tariff control is use, it can be connected to terminal (X12). If positions 1 and 2 are closed, all electric addition will be blocked. If positions 3 and 4 are closed, heat pump operation will be blocked. However, this assumes that the docked heat pump is F20XX. X12 13

16 For the Installer Electrical connections Input for external charge pump feed If does not have to be docked with F20XX but with some other external heat source, the charge pump can still be used. This is achieved by manually supplying the charge pump externally via terminal (X10) positions 1 and 2 in accordance with the required operating conditions. In addition, the connector (13) must be moved from an internal socket to an external one as shown in the diagram below. External additional relay When is to be docked to an external heat source designed to replace the additional heater, terminal (X11) may be used to control switching this on and off. When the additional heater is to be activated, contact is achieved between terminal (X11) position "1" and position "3". This contact is potential free and activated according to the same conditions as the additional heater. 13 Temperature sensor data Temperature ( C) Resistance (k ) , , , , , , , ,17 0 9,81 5 7, , , , , , , , , , , ,525 Voltage (V) 3,16 3,10 3,04 2,95 2,85 2,72 2,57 2,41 2,23 2,04 1,85 1,65 1,47 1,29 1,12 0,97 0,84 0,72 0,62 0,46 0,34 X11 NOTE Supply for external ciculation pump in the heating system is not available in 14

17 Typ: Fighter /8kW Art.nr. : Tillv.nr. och tillv.år: se separat skylt Spänning: 400V 3N+PE 50Hz Märkström (A): 8.4 A Inställningar av motorskydd: 7 A Värmebärardel -Volym: 1.5 l -Beräkningstryck: 3 bar (0.3 MPa) -Provtryck: 3,9 bar (0,39 MPa) -Beräkningstemp: 100 C Köldmediemängd: 2,2 kg Köldtyp: R407C Provtryck, kylsystem: 26 bar (2,6 MPa) Made by NIBE AB, SE Markaryd, SWEDEN For the Installer Docking Docking General can be installed in a number of different ways. For all docking options, the necessary safety equipment must be fitted in accordance with applicable rules. must be docked to an outdoor air heat pump with a maximum output of 15 kw. Pipe connection to NIBE FIGHTER outdoor air heat pump Connect the heat pump's supply (70) to the EVP's "Supply HP." (76). The heat pump's return line (71) must be connected to the EVP's "Return line HP" (75). The heat pump's supplied particle filter must be installed on the heat pump's return line. Flow line (from the heat pump) 70 Flow line (to ) 76 Return line (to heat pump) 71 Return line (from ) 75 LEK NOTE: This is an outline diagram. Actual installations must be planned according to applicable standards. * Not included in boiler delivery ** Enclosed EXP* CP* SÄV1* SÄV2* BL* FG UG** RC SV PG SÄV3* AV* BV** DG SF* AV* LP TV F20XX F20XX 15

18 For the Installer Docking Communication between and F20XX Electrical connection F20XX switches the compressor on and off in F20XX. Connect according to the following image with screened cable. Connect the screen to. Suitable cable is 3 x 0,22-0,25, LiYCY Note! The communication cables must be kept a distance ofat least 20 cm from high voltage cables during cable routing. 1 F20XX X12 44 A+ 44 B- X12 GND 9 F20XX FIGHTER

19 For the Installer Docking Pipe connection to other outdoor air heat pump Connect the heat pump's supply to the indoor module's Supply HP. (76). The heat pump's return line must be connected to the EVP's Return line HP (75). Flow line (to ) Return line (from ) Extra docking connections Route any pipes from the docked option that are to be connected to the docking terminal on EVP through the underneath of the front cover. Cut the plastic cover according to the punched pattern. Electric boiler mode If is to be used without a heat pump, e.g. if a fault has occurred in the heat pump or if the heat pump has not yet been installed, a jumper must be placed between positions 3 and 4 on terminal (X12). This stops the boiler signalling a communications alarm when communication with F20XX is not found. then functions as a purely electric boiler with automatic heating controls, although without freeze protection. X12 Electrical connection When connecting an air/water heat pump other than F20XX, it will not be possible to utilise parts of the intelligence in the controls of. It is best to place a suitable thermostat which operates the heat pump's on and off control in the s submersible tube to the heat pump sensor. To use the integral charge pump, an external supply is required at terminal (X10), positions 1 and 2 according to the operating conditions required (e.g. frost protection circulation). In addition, the connector (13) must be moved from an internal socket to an external one. The electric boiler temperature is set using the knob to a suitable temperature (lowest reference value supply line at DOT). Place a jumper between positions 3 and 4 on terminal (X12). This ensures that the boiler does not signal a communications alarm when communication with F20XX is not found. There are three options for blocking immersion heater operation as the heat pump alone is able to cover the heating requirements in the building. It is most appropriate to use a relay which bridges positions "1" and "2", i.e. the tariff electricity supplement is activated when the heat pump has full coverage, output-wise. The other alternative is to manually block the additional heater, as the heat pump alone is able to meet the heat requirements by setting the change-over switch on the control panel to "OFF". When the heat requirement is then not met by the heat pump alone, the change-over switch is set back to "ON". The third alternative is to set potentiometer (61) to 0 kw. NOTE X12 X12 There is a risk of freezing if immersion heater operation is blocked. 17

20 For the Installer Docking, F20XX and solar panel NOTE: This is an outline diagram. Actual installations must be planned according to applicable standards. EXP* CP* SÄV1* SÄV2* BL* RC P FG UG** RC SV PG SÄV3* AV* BV** DG SF* AV* LP TV BV F20XX F20XX General The heat from the solar panels is transferred to via a plate heat exchanger, which is connected to 's extra docking connections (77) and (78). A temperature sensor from the solar heating systems control box is located in "submerged tube extra docking connection" (86). A non-return valve with opening pressure is installed on the indoor module s side of the plate heat exchanger, to prevent self-circulation. NOTE To prevent interference, sensor cables and communication cables must be separated (min 20 cm) from high voltage cable when cable routing. NOTE Max 85 C to from connected units. Abbreviations OFF* Shut-off valve BL* Mixer valve CP* Circulation pump DG Docking sensor EXP* Expansion vessel FG Temperature sensor, flow line PG Boiler sensor RC Control box SV Shunt valve SÄV1* Safety valve, boiler SÄV2* Safety valve, water heater SÄV3* Safety valve, heat pump TV Drain valve OS** Temperature sensor, outdoor BV** Non-return valve SN Charge pump SF* Particle filter Install a non-return valve or a gravity brake towards the heating system to prevent self ciculation and therefore a reduced energy loss. * ** Not included in the consignment Enclosed 18

21 For the Installer Docking, F20XX and oil/pellet/gas boiler NOTE: This is an outline diagram. Actual installations must be planned according to applicable standards. EXP* CP* SÄV1* SÄV2* BL* FG UG** RC SV PG SÄV3* AV* BV** DG SF* AV* LP TV BV FIGHTER F20XX 20XX Oljepanna Oil/pellets/gas boiler. General Oil/Pellets/Gas boiler pipe connections are connected to EVP 500's extra docking connections (77) and (78). The charge pump for Oil/Pellets/Gas boiler is supplied via the external addition relay terminal block (X11) terminal 1 and 3. Max power output is set to 0 kw. A non-return valve with opening pressure must be installed to prevent self-circulation. F20XX's addition relay blocks the external addition until there is a demand. NOTE Max 85 C to from connected units. Install a non-return valve or a gravity brake towards the heating system to prevent self ciculation and therefore a reduced energy loss. NOTE To prevent interference, sensor cables and communication cables must be separated (min 20 cm) from high voltage cables when cable routing. * ** Not included in the consignment Enclosed 19

22 For the Installer Docking, F20XX and combi/wood boiler NOTE: This is an outline diagram. Actual installations must be planned according to applicable standards. EXP* CP* SÄV1* SÄV2* BL* UG** FG SV RC PG BL* SÄV3* AV* BV** DG SF* AV* LP TV BV BV FIGHTER F20XX20XX ACCU ACCU Combi/wood Kombipanna boiler/ General The accumulator tank's pipe connections are connected to 's extra docking connections (77) and (78). The charge pump to the multi-fuel heating boiler is supplied via an appropriate thermostat. A non-return valve with opening pressure is fitted so as to prevent self-circulation. The thermostat that is to be installed in the accumulator tank to start heating, should have a starting temperature of approx C. A thermal mixing valve. e.g. Laddomat type N, is installed to limit the incoming temperature for EVP 500 to 65 C. This is to prevent HP alarms at F20XX when its frost protection circulation is activated. NOTE To prevent interference, sensor cables and communication cables must be separated (min 20 cm) from high voltage cables when cable routing. NOTE The charge circuits between and the accumulator tank must be supplied with thermal mixing valves (max 65 C). Install a non-return valve or a gravity brake towards the heating system to prevent self ciculation and therefore a reduced energy loss. * ** Not included in the consignment Enclosed 20

23 For the Installer Docking, wood boiler, accumulator tank and solar panel NOTE: This is an outline diagram. Actual installations must be planned according to applicable standards. EXP* CP* SÄV1* SÄV2* BL* RC P FG RC SV PG DG BV** BV LP TV BV Wood-fired Vedpanna ACCU General The accumulator tank's pipe connections are connected to 's extra docking connections (75) and (76). To transfer heat from the accumulator tank to, the indoor module's internal charge pump is used. The charge pump is controlled by an appropriate thermostat located in the accumulator tank and supplied via terminal block (X10) terminal 1 and 2. In addition, connector (13) must be reconnected externally from internally. A non-return valve with opening pressure are fitted to both the circuit for the wood boiler and the sun circuit in order to prevent self-circulation. Twin thermometers that are to be installed in the accumulator tank must cut charging at max 85 C and a suitable start temperature should be approx. 60 C. NOTE Max 85 C to from connected units. Install a non-return valve or a gravity brake towards the heating system to prevent self ciculation and therefore a reduced energy loss. NOTE To prevent interference, sensor cables and communication cables must be separated (min 20 cm) from high voltage cables when cable routing. * ** Not included in the consignment Enclosed 21

24 For the Installer Commissioning and adjusting Commissioning and adjusting Preparations Check that the switch (8) is set to "ON" and that the temperature limiters (6) have not tripped (press the button hard to reset). Addition It is best to top up the indoor module by means of a fixed filler pipe to the radiator return. Venting the heating system Bleed the indoor module via the bleeder nipple (81) and the rest of the heating system through the relevant venting valves. Keep topping up and venting until all air has been removed and the pressure is correct. Start-up and inspection 1. Check that the water is full and vented. 2. Turn on the main circuit breaker. 3. Check that all incoming phases are powered. 4. Check that the miniature circuit-breaker (7) is on. 5. Check that the temperature limiters (6) have not tripped during transit. 6. Turn on the switch (8). 7. Adjust the curve coefficient and heating curve offset according to the requirements of the property using the knobs and. 8. If F20XX is not to be connected, bridge positions 3 and 4 on terminal (X12). Continue with the following points if is to be docked to NIBE's air/water heat pump. 1. Connect a shielded communications cable between F20XX and as per "Communication between and F20XX" on page Follow the start-up and inspection instruction for the respective heat pumps. 3. Check that the value is 1 in channel A1 in F2020/F2025 (in F2005/2010 channel 13 must be set to 2). 4. Set the heating system's balance temperature (according to dimensioning) in channel A5 in F2020/F2025 or channel 17 in F2005/F Adjust the charge flow between the heat pump and EVP 500 using the mode switch on the charge pump. Guideline value balance temperature The table applies at DOT and with an approximate hot water demand of 5000 kwh/year and a heat distribution system with a maximum supply/return temperature of 55/45 C. Where the table only contains guideline values, it is important that the heating system's balance temperature is dimensioned, preferably with the dimensioning tool VPDIM. Heat pump F kw F kw Previous annual consumption (kwh/m 3 oil) 20000/ C -15 C 25000/3.3-8 C -13 C 30000/4-5 C -10 C 35000/4.7-2 C -7 C 40000/5.3-1 C -5 C 45000/6 1 C -3 C 50000/6.7 2 C -2 C NOTE It is of the utmost importance that the balance temperature is adjusted to suit the independent heating system, so that the additional heat is not engaged earlier than necessary. 22

25 For the Installer Commissioning and adjusting Setting of temperature levels The indoor module and, indirectly also the cam pipe coil, is, on delivery, set to normal stop temperature NORM for the heat pump and 60 C electric boiler temperature. All additional power is blocked until the heat pump can no longer manage the entire heating demand itself (below the balance temperature). This means that the electric boiler temperature is significant only below the heat pump's balance temperature. In the case of outdoor temperatures above the balance temperature, the heat pump's stop temperature is thus controlled and so all the comfort of hot water is controlled via the knob. The heat pump's stop temperature is variable and depends on the knob setting and outdoor temperature. At a higher outdoor temperature, the heat pump does not need to work as hard to get up to boiler temperature as it does when the outdoor temperature is colder, so increasing savings (see the diagram below). The temperature in the cam pipe coil increases as the boiler temperature increases. The output hot water temperature can be limited by means of a mixer valve (not included as standard). The maximum supply temperature can also be limited upwards in temperature (35 C - 65 C) to protect an underfloor heating system for example. This is done via a potentiometer (62) on circuit board (34), which is located behind the front panel. The indoor module's maximum power output is also set on the same circuit board (34) via potentiometer (61) and can be adjusted between 0-18 kw in stages of 3 kw. The power stages are connected, if necessary, at hourly intervals, on the condition that "Operating mode, immersion heater " is on position "on". The connection difference between start/stop temperature is set using potentiometer (60). At outdoor temperatures above 10 C, boiler control is automatically set to 1 C on the connection difference's setting to extend the heat pump's operating time when the given output is high. Stop temperature, heat pump Stop temperature 55,0 54,0 53,0 52,0 51,0 50,0 49,0 48,0 47,0 46,0 45, Outdoor temp. VP thermostat, stop COMF VP thermostat, stop NORM plus VP thermostat, stop NORM VP thermostat, stop NORM minus VP thermostat, stop ECO 23

26 For the Installer Commissioning and adjusting Adjustment, charge flow F20XX Adjusting the temperature difference ( T) between the heat pump's supply temperature and the heat pump's return temperature is important to maintain optimal operational economy. This is most easily done using the temperatures measured in channel T2 (supply temperature) and channel T3 (return temperature). This temperature difference ( T) is adjusted using the charge pump. Adjustment is performed with stable operation about 5 minutes after start, or about 5 minutes after defrosting in cold outdoor temperatures. NOTE The temperature difference must be within the grey marked area in the diagram below. Adjust as close to the nominal value as possible. Adjustment of charge flow for 18,0 17,0 16,0 15,0 14,0 T( C) Max Nom Min 13,0 12,0 11,0 10,0 9,0 8,0 7,0 6,0 5,0 4,0 3,0 2, Outdoor temperature ( C) 24

27 For the Installer Commissioning and adjusting Charge pump diagram The curves represent the different speeds which can be set for the charge pump. Externally accessible pressure charge circuit (particle filter and non-return valve included) Available pressure (kpa) 50,0 45,0 40,0 35, ,0 25,0 20,0 15, ,0 5,0 0, Flow (l/h) LEK Readjustment Air is initially released from the hot water and venting may be necessary. If bubbling sounds can be heard from the indoor module, the entire system requires further venting. When the system is stable (correct pressure and all air eliminated) the automatic heating control system can be set as required. See the sections "Heating control system" on page 6 and "Functions on the front panel" on page 4. Draining the heating system The power supply must be disconnected before the boiler/radiator water is drained. The boiler/radiator water can be drained via drain valve (44). Loosen the cover of the drain valve and mount the supplied hose connector to an appropriate hose. NOTE The hose must be fitted to the hose coupling supplied before being fitted to the drain valve (44). The valve opens automatically when the hose coupling is fitted to the valve. 25

28 Miscellaneous Commissioning and adjusting Setting of flow temperature Heating curve offset -2 SUPPLY TEMPERATURE FRAMLEDNINGSTEMPERATUR + 5 C FÖRSKJUTNING VÄRMEKURVA (-2) OFFSET HEAT CURVE -2 Heating curve offset 0 SUPPLY TEMPERATURE FRAMLEDNINGSTEMPERATUR + 5 C HEATING VÄRMEKURVA CURVE C UTETEMPERATUR OUTSIDE TEMPERATURE HEATING VÄRMEKURVA CURVE C - 5 FÖRSKJUTNING UTETEMPERATUR OUTSIDE OFFSET HEAT CURVE VÄRMEKURVA 0 (0) TEMPERATURE Heating curve offset +2 SUPPLY TEMPERATURE FRAMLEDNINGSTEMPERATUR + 5 C HEATING VÄRMEKURVA CURVE Setting after diagram is equipped with an outdoor temperature controlled heating control system. This means the flow temperature is regulated in relation to the current outdoor temperature. The relationship between outdoor temperature and supply temperature is set with the Heating curve selection and Heating curve offset knobs. The diagram is based on the dimensioned outdoor temperature in the area and the dimensioned flow temperature of the heating system. When these two values meet, the heating control's curve coefficient can be read. The Heating curve offset knob is then set. A suitable value for underfloor heating is -1 and for a radiator system -2. See also section "Default setting" on page 6. Relationship between set temperature and available hot water volume Domestic Tappvarmvattenvolym (litres) 40 ºC [liter] hot water volume 40 C 1. Normal drain flow (8 l / min) 2. High drain flow (12 l / min) Supreme comfort Hög komfort Normal komfort Normal comfort 0 Hög High besparing savings ECO NORM COMF 2 Normal Normal besparing saving As hot water is heated in the cam pipe coil at the same time as it is used, the hot water volume is dependent on the flow through the coil. This means that a larger quantity of hot water can be taken at a lower flow. If large hot water flows are required, the boiler temperature may be increased using the knobs and as per section "Hot water temperature" on page 7. The available hot water volume can be seen in the diagram. In the event of a hot water flow greater than 12 l/min, it is recommended to supplement with a core water heater FÖRSKJUTNING OFFSET HEAT CURVE VÄRMEKURVA +2 (+2) C UTETEMPERATUR OUTSIDE TEMPERATURE 26

29 Miscellaneous Dealing with malfunctions Dealing with malfunctions In the event of malfunction or operating disturbances first check the points below. Remember that there is an hour interval between each power stage. Low hot water temperature or no hot water Too high domestic water flow. See section Hot water temp. on page 7. Large amounts of hot water were used. Circuit or main MCB tripped. Possible earth circuit-breaker tripped. Mixer valve set too low (if mounted). Switch (8) set to 0. Tripped Miniature circuit-breaker (7) or Fine-wire fuse(33). Refer to the section "Resetting the miniature circuit breakers" on page 29. Tripped temperature limiters (6). Contact service. Check if "operating mode, immersion heater" is in mode OFF Closed or throttled shut off valve to the water heater. External output monitor may have blocked the electrical power. Hot water capacity is set too low on and/or. "Balance temperature" set too low in F20XX. Alarm indicator, see "Alarm" on page 29. High hot water temperature Mixer valve set too high. Low room temperature Circuit or main MCB tripped. Possible earth circuit-breaker tripped. Tripped Miniature circuit-breaker (7) or Fine-wire fuse(33). Refer to the section "Resetting the miniature circuit breakers" on page 29. Tripped temperature limiters (6). Contact service. Incorrectly set values for "Option, heating curve" and/or "Offset heating curve" on page 6. Circulation pump stopped. Air in the indoor module or in the system. The pressure is to low in the expansion vessel. External output monitor may have blocked the additional heater. "Balance temperature" set too low in F20XX. Alarm indicator, see "Alarm" on page 29. Electric boiler operation due to blocked heat pump The heat pump may be blocked due to a high supply or return temperature, which can depend on incorrect heat pump and/or indoor module settings. When the heat pump is blocked, this is indicated by three flashes on the operating mode indicator on. 1. Set the heating system's balance temperature in F20XX. 2. The charge flow between supply and return to the heat pump (T2 - T3) must be according to the diagram on page A high set value on the heat curve results in a high supply temperature, which in turn, results in a high return temperature. The heat pump is then outside its working range. 4. The flow in the heating system is limited by the thermostats for the radiators or underfloor heating. Instead, regulate the room temperature using "Heating curve selection" and "Offset, heat curve" on (see page 6). 5. Check that "temperature sensor, heat pump" (89) is correctly installed in the submerged tube on. 6. Adjust T above the heating system using the heating medium pump or any external valves according to the projected flow for the house. 7. In the event of docking to another heat source, the charge temperature should be limited to C. 8. The heat pump's output can be limited by the heating system. High room temperature Incorrectly set values for "Option, heating curve" and/or "Offset heating curve" on page 6. 27

30 Miscellaneous Dealing with malfunctions Switch position In "Reserve mode", the indoor module's electronic control is disconnected. The immersion heater is controlled by a separate thermostat (3), and the available output in reserve mode is 9 kw. The charge pump is functional, but the automatic heating control system is not, so manual shunt operation is required. This is done by using a screwdriver to set the change-over switch on the shunt motor (19) in mode. The shunt motor can then be turned to the desired position. LEK The adjustment screw NOTE When returning to normal mode do not forget to reset the shunt motor to its original position by turning the change-over switch to "A". If the operating disturbance cannot be rectified by means of the above an installation engineer should be called. If necessary set the switch to "reserve mode" (manual shunt operation necessary). 28

31 Miscellaneous Dealing with malfunctions Resetting the miniature circuit breakers The MCB (7) is accessible behind the cover and is located to the left of the panel. Normal mode of the miniature circuitbreaker is "1" (up). Fine wire fuse Automatic elements, charge pump (17) and its cabling are fuse-protected internally with a miniature circuit breaker (7), plus a fine-wire fuse (33) on the relay card (34). The fine-wire fuse may be replaced only once the fault has been rectified. Fine-wire fuse 2 AT, 5x20mm.Adefective fine-wire fuse is indicated by the operating mode indicator being off when the switch is set to NOTE Work behind covers secured by screws may only be carried out under the supervision of a qualified installation engineer. Alarm In the event of a communications error between and F20XX, the red LED (31) flashes. This malfunction will be noted as then switches to alarm operation if the outdoor temperature is lower than +5 C. This means 35 C boiler temperature and 15 C reference temperature at the flow line. At higher outdoor temperatures, only the reference value on the flow line is set to +15 C. In the event of an internal sensor error or a constant F20XX alarm, the red LED (31) lights continuously. This malfunction will be noted as then automatically switches to alarm operation (described above). 31 Alarm indication 29

32 Miscellaneous Electrical circuit diagram Electrical circuit diagram 30

33 Miscellaneous Electrical circuit diagram 31

34 Miscellaneous Electrical circuit diagram 32

35 Miscellaneous Dimensions Dimensions Dimensions without insulation and front panel Ceiling height 1870 mm Ceiling height 1930 mm Ø m utrymme för service m free space for service 55 Dimensions with insulation and front panel Ceiling height 1900 mm Ceiling height 1980 mm Measuring principle Cu-rör pipe Ø670 Ø

36 LEK Miscellaneous Technical specifications Technical specifications Component positions LEK

37 Miscellaneous Technical specifications List of components 1 Immersion heater 9 kw 3 Thermostat, standby mode 6 Temperature limiter 7 Miniature circuit-breaker 8 Switch, position Terminal block, power supply 10 Connecting terminal, external supply charge pump 11 Connecting terminal, external additional heater 12 Terminal block, sensor, communication 13 Connector 15 Outside sensor 17 Charge pump 19 Shunt motor with handwheel 30 Switch, "Operating mode, immersion heater" 31 Indicator lamp, "Alarm indicator" 32 Indicator lamp, "Immersion heater operational" 33 Fine-wire fuse relay card 2 AT, 5x20 34 Relay card Knob, "Immersion heater thermostat" Knob, "Heat pump operating mode" Knob, "Curve coefficient" Knob, Offset heating curve Thermometer Microprocessor card Shunt valve Tapping valve Knob, setting "VP connection difference" Knob, setting "Max electrical output" Knob, setting "Max flow temperature" Relay, 3.0 kw Relay, 6.0 kw Relay, 9.0 kw Connection Flow line, heating system Ø28mm Return line, heating system Ø28mm Cold water connection Ø22mm Hot water connection Ø22mm Docking connection, supply (to another heat source) Ø28mm Docking connection, return (from another heat source) Ø28mm Extra docking equipment, front G1 int. Extra docking connection, return G1 int. Drain connection, heating system 1/2" hose coupling Venting nipple Submerged tube, extra docking connection (Ø 10.5 mm, length 160 mm) Temperature sensor, boiler Temperature sensor, submersible tube, heat pump Temperature sensor, heat system flow line Signs, serial numbers Sign, pipe connection Rating plate Lifting eye Enclosed kit 35

38 Miscellaneous Technical specifications Technical specifications IP 21 Height (excl. foot: mm) Required ceiling height Width Depth Weight Volume total Volume of vessel Volume loop Supply voltage Rated output charge pump Maximum heat pump output** Output immersion heater Enclosure class Cut-off pressure, loop Max permitted pressure in boiler Art.Nr with cam pipe coil made of copper Art.Nr with a tin coated cam pipe coil made of copper Idle loss according to EN 255-3*** 1810 mm (1760* mm) 1870 mm 750 mm (670* mm) 950 mm (905* mm) 175 kg 500 litres 495 litres 3 litres 400 V 3 NAC 50Hz 90 W 15 kw 18 kw (output on delivery 9 kw) IP 21 0,9 MPa (9 bar) 0,3 MPa (3 bar) W * Measured without insulation and covers ** Applies to outdoor air heat pump at 7/45 C (Outdoor temperature / Supply temperature) *** docked to F

39 LEK Miscellaneous Technical specifications Accessories Current limiter EBV 112 VX EBV 112 VX is a load monitor used to disconnect output that exceeds the output set on the load monitor. Part.No PLEX Plate heat exchanger for solar panel installations with MAX 10 m² solar panel surface. Part.No Laddomat type N When docking to combi/wood-fired boiler, the charge circuit must be equipped with a thermal mixing valve. Part.No LEK Enclosed kit Cable relief Outside sensor Insulation plug at the top Non-return valve LEK LEK LEK Bridge, tariff LEK 37

40 38

41 39

42 40

43

44 AT KNV Energietechnik GmbH, Gahberggasse 11, 4861 Schörfling Tel: +43 (0) Fax: +43 (0) CH NIBE Wärmetechnik AG, Winterthurerstrasse 710, CH-8247 Flurlingen Tel: (52) Fax: (52) CZ Druzstevni zavody Drazice s.r.o, Drazice 69, CZ Benatky nad Jizerou Tel: Fax: nibe@nibe.cz DE NIBE Systemtechnik GmbH, Am Reiherpfahl 3, Celle Tel: 05141/ Fax: 05141/ info@nibe.de DK Vølund Varmeteknik, Filial af NIBE AB, Brogårdsvej 7, 6920 Videbæk Tel: Fax: info@volundvt.dk FI NIBE Haato OY, Valimotie 27, Vantaa Puh: Fax: info@haato.com GB NIBE Energy Systems Ltd, 3C Broom Business Park, Bridge Way, Chesterfield S41 9QG Tel: Fax: info@nibe.co.uk NL NIBE Energietechniek B.V., Postbus 2, NL-4797 ZG WILLEMSTAD (NB) Tel: Fax: info@nibenl.nl NO NIBE AB, Fekjan 15F, 1394 Nesbru Tel: Fax: info@nibe.se PL NIBE-BIAWAR Sp. z o. o. Aleja Jana Pawła II 57, BIAŁYSTOK Tel: Fax: sekretariat@biawar.com.pl NIBE AB Sweden, Box 14, Järnvägsgatan 40, SE Markaryd Tel: +46-(0) Fax: +46-(0) info@nibe.se

INSTALLATION AND MAINTENANCE INSTRUCTIONS ELK ELK 15 LEK

INSTALLATION AND MAINTENANCE INSTRUCTIONS ELK ELK 15 LEK MOS GB 1011-3 INSTALLATION AND MAINTENANCE INSTRUCTIONS 031179 LEK Table of Contents For Home Owners General System description Principle of operation 3 Abbreviations 3 System diagram 3 Operation and

More information

ELK 26 INSTALLATION AND MAINTENANCE INSTRUCTIONS ELK 26

ELK 26 INSTALLATION AND MAINTENANCE INSTRUCTIONS ELK 26 MOS GB 38-2 INSTALLATION AND MAINTENANCE INSTRUCTIONS 2352 LEK Table of Contents For Home Owners General System description Principle of operation 3 Components 3 System diagram 3 Operation and maintenance

More information

Installer manual AHP/AHPS

Installer manual AHP/AHPS Installer manual Accumulator tank IHB GB 1415-2 231351 Table of Contents 1 Important information Safety information 2 2 AHP and AHPS Installation alternative 10 11 2 Delivery and handling Transport 5

More information

MOS GB NIBE VVM INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE VVM 300 VVM 300 LEK

MOS GB NIBE VVM INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE VVM 300 VVM 300 LEK A B I II III A B I II I II A B -2 0 +2 MOS GB 0821-4 NIBE VVM 300 511806 INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE VVM 300 VVM 300 LEK 2 1 LEK LEK 5 4 3 LEK LEK Contents User guide General Principle

More information

Installer manual AHP/AHPS

Installer manual AHP/AHPS Installer manual Accumulator tank IHB GB 1544-4 231351 Table of Contents 1 Important information 3 Installation alternative 13 Safety information 3 5 Electrical installation 15 2 Delivery and handling

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS MOS GB NIBE VVM 300 UK NIBE VVM 300 UK 230 V VVM 300 LEK

INSTALLATION AND MAINTENANCE INSTRUCTIONS MOS GB NIBE VVM 300 UK NIBE VVM 300 UK 230 V VVM 300 LEK A B I II III A B I II I II A B -2 0 +2 MOS GB 1027-6 NIBE VVM 300 UK 031142 INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE VVM 300 UK 230 V VVM 300 2 1 5 4 3 Contents User guide General Principle of operation

More information

User and Installer manual NIBE UKV 20

User and Installer manual NIBE UKV 20 User and Installer manual 20-500, 20-750, 20-1000 Accumulator tank CHB EN 1743-1 431416 Table of Contents 1 Important information 2 For the User 3 For the Installer 4 Technical data Contact information

More information

Installation and Operating Manual

Installation and Operating Manual Installation and Operating Manual Buffer tanks: UKV 0-0 UKV 0-300 UKV 0-00 UKV 0-70 UKV 0-1000 30.0.016 617 All installation diagrams in this manual do not replace the system design; they can only be used

More information

LEK MOS UK VPA 300/200, 450/ INSTALLATION AND MAINTENANCE INSTRUCTIONS VPA 300/200, 450/300

LEK MOS UK VPA 300/200, 450/ INSTALLATION AND MAINTENANCE INSTRUCTIONS VPA 300/200, 450/300 MOS UK 1240-7 VPA 300/200, 450/300 031049 INSTALLATION AND MAINTENANCE INSTRUCTIONS VPA 300/200, 450/300 For Home Owners System description System description Unvented water heater for use with ground

More information

User manual NIBE SMO 05

User manual NIBE SMO 05 LEK User manual Accessories LEK AHB GB 1020-1 031523 A detailed explanation of the button functions can be found on page 10. How to scroll through menus and make different settings is described on page

More information

User manual NIBE F135

User manual NIBE F135 User manual Exhaust air module LEK UHB GB 1522-1 331433 Table of Contents 1 Important information Installation data Safety information Serial number Contact information F135 An excellent choice 2 The

More information

Installer manual SAM 40. Supply air module IHB GB LEK

Installer manual SAM 40. Supply air module IHB GB LEK LEK Installer manual Supply air module IHB GB 1231-2 031934 LEK LEK Table of Contents 1 Important information 2 Safety information 2 2 Delivery and handling 5 Transport 5 Assembly 5 Removing the covers

More information

MOS GB INSTALLATION AND MAINTENANCE INSTRUCTIONS VEDEX 1000 VEDEX 1000 M10527 LEK

MOS GB INSTALLATION AND MAINTENANCE INSTRUCTIONS VEDEX 1000 VEDEX 1000 M10527 LEK LEK MOS GB 0733-1 VEDEX 1000 M10527 INSTALLATION AND MAINTENANCE INSTRUCTIONS VEDEX 1000 Contents For Home Owners Installation data 2 System diagram 3 Product description 3 Area of use 3 Heating 3 Component

More information

MOS GB SMO INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10

MOS GB SMO INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10 MOS GB 1236-6 SMO 10 511882 INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10 Contents General System diagram 3 Principle of operation 3 Abbreviations 3 Front panel Display 4 Switch 5 Offset heating

More information

MOS GB SMO INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10

MOS GB SMO INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10 MOS GB 0707-3 SMO 10 511262 INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10 Contents User guide System diagram 3 Principle of operation 3 Abbreviations 3 Front panel Display 4 Switch 5 Offset heating

More information

NIBE VVM 300. Intelligent hot water NIBE VVM 300. VVM 300 is designed for connection and communication

NIBE VVM 300. Intelligent hot water NIBE VVM 300. VVM 300 is designed for connection and communication NIBE VVM 300 all in one indoor unit Intelligent hot water VVM 300 is designed for connection and communication with outdoor heat pump F20XX of 6 kw, 8 kw and 10 kw. Water volume 280 litres, of which 155

More information

Installer manual NIBE VVM 500. Indoor module APH

Installer manual NIBE VVM 500. Indoor module APH Installer manual Indoor module APH IHB GB 1216-2 031991 A detailed explanation of the button functions can be found on page 27. How to scroll through menus and make different settings is described on page

More information

User manual NIBE SMO 05. Accessories UHB GB LEK

User manual NIBE SMO 05. Accessories UHB GB LEK LEK User manual Accessories LEK UHB GB 1339-2 431198 A detailed explanation of the button functions can be found on page 10. How to scroll through menus and make different settings is described on page

More information

User manual NIBE F110

User manual NIBE F110 User manual Hot water heat pump LEK UHB GB 1434-1 231975 A detailed explanation of the button functions can be found on page 10. How to scroll through menus and make different settings is described on

More information

User manual NIBE F2016

User manual NIBE F2016 User manual Air/water heat pump LEK UHB GB 1244-2 031876 Table of Contents 1 Important information 2 Installation data 2 Safety information 4 Serial number 5 Contact information 6 F2016 - An excellent

More information

Installer manual ELK 213 Immersion heater

Installer manual ELK 213 Immersion heater Installer manual ELK 213 LEK IHB GB 1548-5 031403 Table of Contents 1 Important information Safety information 2 General 4 4 6 Output Time relay Sensors Connection of the circulation pump (GP10) 16 16

More information

Installer manual NIBE FLM. Exhaust air module IHB GB LEK

Installer manual NIBE FLM. Exhaust air module IHB GB LEK Installer manual Exhaust air module IHB GB 1414-4 031375 Table of Contents 1 Important information 2 Connections 14 Safety information 2 6 Commissioning and adjusting 19 2 Delivery and handling Transport

More information

User manual NIBE F1145

User manual NIBE F1145 User manual Ground source heat pump LEK AHB GB 1018-1 031634 A detailed explanation of the button functions can be found on page 11. How to scroll through menus and make different settings is described

More information

User manual NIBE F , 12, 16 kw Air/water heat pump UHB GB LEK LEK LEK

User manual NIBE F , 12, 16 kw Air/water heat pump UHB GB LEK LEK LEK LEK LEK LEK User manual 8, 12, 16 kw Air/water heat pump UHB GB 1335-2 231845 Table of Contents 1 Important information 2 Installation data 2 Safety information 3 Serial number 4 Contact information 7

More information

User manual NIBE F130. Hot water heat pump

User manual NIBE F130. Hot water heat pump LEK User manual Hot water heat pump UHB GB 1433-1 231985 Quick guide Navigation Ok button (confirm/select) Up/down buttons (move/increase/reduce) Back button (back/undo/exit) A detailed explanation of

More information

MOS GB SMO INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10

MOS GB SMO INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10 MOS GB 0735-3 SMO 10 511882 INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10 Contents General System diagram 3 Principle of operation 3 Abbreviations 3 Front panel Display 4 Switch 5 Offset heating

More information

User manual NIBE F2040

User manual NIBE F2040 LEK LEK LEK User manual 8, 12, 16 kw Air/water heat pump UHB GB 1512-3 231845 Table of Contents 1 Important information Installation data Safety information Serial number Contact information F2040 - An

More information

Operating manual NIBE F1345. Ground source heat pump OHB GB LEK

Operating manual NIBE F1345. Ground source heat pump OHB GB LEK Operating manual Ground source heat pump LEK OHB GB 1210-2 031838 A detailed explanation of the button functions can be found on page 6. How to scroll through menus and make different settings is described

More information

User manual NIBE F2300

User manual NIBE F2300 User manual Air/water heat pump LEK UHB GB 1138-1 031761 Table of Contents 1 Important information 2 Installation data 2 Safety information 4 Safety precautions 5 Serial number 7 Contact information 8

More information

Installer manual ELK 213 Immersion heater

Installer manual ELK 213 Immersion heater Installer manual ELK 213 LEK IHB GB 1535-3 031403 Table of Contents 1 English, IHB - ELK 213 General Component positions Pipe connections 2 2 3 5 Disturbances in comfort Accessories Technical data Electrical

More information

Installer manual NIBE VVM 310. Indoor module IHB GB

Installer manual NIBE VVM 310. Indoor module IHB GB Installer manual Indoor module APH IHB GB 1338-3 231175 A detailed explanation of the button functions can be found on page 33. How to scroll through menus and make different settings is described on page

More information

Installer manual SAM 40

Installer manual SAM 40 Installer manual Supply air module LEK IHB GB 1549-4 031934 LEK LEK Table of Contents 1 Important information 4 5 Electrical connections 17 Safety information 4 General 17 2 Delivery and handling Transport

More information

Installer manual NIBE ERS

Installer manual NIBE ERS Installer manual Ventilation heat exchanger LEK IHB GB 1622-1 331802 Table of Contents 1 Important information 4 10 Accessories 18 Safety information Serial number 4 4 11 Technical data 19 Recovery Country

More information

BA-ST FE BA-ST FE BA-ST FE BA-ST FE BA-ST FE BA-ST FE Hot Water Storage Tank with Coil

BA-ST FE BA-ST FE BA-ST FE BA-ST FE BA-ST FE BA-ST FE Hot Water Storage Tank with Coil Installation and Operating Manual BA-ST 90-1FE BA-ST 9030-1FE BA-ST 9040-1FE BA-ST 9050-1FE BA-ST 9075-1FE BA-ST 9100-1FE Hot Water Storage Tank with Coil.0.016 560 CONTENT CONTENT 1. GENERAL...3 1.1 Introduction...3

More information

Installer manual NIBE VVM 320. Indoor module IHB GB

Installer manual NIBE VVM 320. Indoor module IHB GB Installer manual Indoor module APH IHB GB 1336-1 231357 A detailed explanation of the button functions can be found on page 32. How to scroll through menus and make different settings is described on page

More information

Installer manual NIBE VVM 310. Indoor module IHB GB

Installer manual NIBE VVM 310. Indoor module IHB GB Installer manual Indoor module APH IHB GB 1428-4 231175 A detailed explanation of the button functions can be found on page 33. How to scroll through menus and make different settings is described on page

More information

Installer manual NIBE VVM 500. Indoor module APH

Installer manual NIBE VVM 500. Indoor module APH Installer manual Indoor module APH IHB GB 1428-5 031991 A detailed explanation of the button functions can be found on page 30. How to scroll through menus and make different settings is described on page

More information

Installer manual SMO 20. Control module IHB GB LEK

Installer manual SMO 20. Control module IHB GB LEK Installer manual Control module IHB GB 1436-4 231758 A detailed explanation of the button functions can be found on page 24. How to scroll through menus and make different settings is described on page

More information

User manual NIBE SPLIT HBS 05 AMS 10-8 / / 10-16, HBS / 05-16

User manual NIBE SPLIT HBS 05 AMS 10-8 / / 10-16, HBS / 05-16 LEK LEK LEK User manual AMS 10-8 / 10-12 / 10-16, HBS 05-12 / 05-16 Air/water heat pump LEK LEK UHB GB 1622-1 331610 Table of Contents 1 Important information Installation data Safety information Contact

More information

Installer manual SMO 40. Control module IHB GB LEK

Installer manual SMO 40. Control module IHB GB LEK Installer manual Control module IHB GB 1436-2 231760 A detailed explanation of the button functions can be found on page 29. How to scroll through menus and make different settings is described on page

More information

User manual NIBE VVM 500

User manual NIBE VVM 500 User manual Indoor module APH UHB GB 1212-1 431240 A detailed explanation of the button functions can be found on page 12. How to scroll through menus and make different settings is described on page 16.

More information

Installer manual NIBE VVM 320. Indoor module IHB GB

Installer manual NIBE VVM 320. Indoor module IHB GB Installer manual Indoor module APH IHB GB 1452-3 231357 A detailed explanation of the button functions can be found on page 33. How to scroll through menus and make different settings is described on page

More information

Installer manual NIBE ERS

Installer manual NIBE ERS Installer manual Ventilation heat exchanger LEK IHB EN 1726-3 331802 Table of Contents 1 Important information 4 10 Accessories 19 Safety information Serial number 4 4 11 Technical data 20 Recovery Country

More information

Installer manual NIBE VVM 310

Installer manual NIBE VVM 310 Installer manual EMK Indoor module APH IHB GB 1524-5 231175 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of

More information

User manual NIBE F2300

User manual NIBE F2300 User manual Air/water heat pump LEK UHB GB 1508-1 231142 Table of Contents 1 Important information Installation data Safety information Safety precautions Serial number Contact information F2300 - An

More information

Installer manual NIBE ERS

Installer manual NIBE ERS Installer manual Ventilation heat exchanger LEK IHB EN 1743-4 331812 Table of Contents 1 Important information 4 9 Service 18 Safety information 4 Water seal for condensation water 18 Serial number 4

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS F F2025

INSTALLATION AND MAINTENANCE INSTRUCTIONS F F2025 MOS GB 0840-3 INSTALLATION AND MAINTENANCE INSTRUCTIONS 031185 LEK Table of Contents For Home Owners General System description Principle of operation 3 Maintenance routines General 4 For the Installer

More information

User manual NIBE VVM 310

User manual NIBE VVM 310 User manual Indoor module APH UHB GB 1308-2 231176 A detailed explanation of the button functions can be found on page 12. How to scroll through menus and make different settings is described on page 16.

More information

User manual NIBE F2120 8, 12, 16, 20

User manual NIBE F2120 8, 12, 16, 20 User manual 8, 12, 16, 20 Air/water heat pump LEK UHB GB 1631-2 331398 Table of Contents 1 Important information Installation data Safety information Contact information F2120 An excellent choice 2 The

More information

User manual AMS 10 AMS 10-6 / 10-8 / / 10-16

User manual AMS 10 AMS 10-6 / 10-8 / / 10-16 User manual -6 / 10-8 / 10-12 / 10-16 LEK LEK K LE Air/water heat pump K LE UN UHB EN 1746-1 331961 Table of Contents 1 Important information Installation data Safety information Service code and serial

More information

NIBE SPLIT ACVM 270 Air/water heat pump

NIBE SPLIT ACVM 270 Air/water heat pump NIBE SPLIT ACVM 270 Air/water heat pump NIBE SPLIT ACVM 270 system with complete indoor module NIBE SPLIT ACVM 270 is a complete modern heat pump system that offers effective technical energy saving and

More information

User manual NIBE F2120 8, 12, 16, 20

User manual NIBE F2120 8, 12, 16, 20 User manual 8, 12, 16, 20 Air/water heat pump LEK UHB GB 1648-3 331398 Table of Contents 1 Important information Installation data Safety information F2120 An excellent choice 2 The heat pump the heart

More information

Installer manual SMO 40

Installer manual SMO 40 Installer manual Control module IHB GB 1624-4 231760 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button

More information

Installer manual NIBE F2026. Air/water heat pump IHB GB LEK

Installer manual NIBE F2026. Air/water heat pump IHB GB LEK Installer manual Air/water heat pump LEK IHB GB 1132-1 031865 Table of Contents 1 Important information 2 Safety information 2 2 Delivery and handling 5 Transport and storage 5 Assembly 5 Supplied components

More information

Installer manual NIBE VVM 500

Installer manual NIBE VVM 500 Installer manual Indoor module APH IHB GB 1705-8 031991 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the

More information

MOS GB VEDEX 3300 M10528 INSTALLATION AND MAINTENANCE INSTRUCTIONS VEDEX 3300 LEK

MOS GB VEDEX 3300 M10528 INSTALLATION AND MAINTENANCE INSTRUCTIONS VEDEX 3300 LEK MOS GB 0733-1 M10528 INSALLAION AND MAINENANCE INSRUCIONS LEK Contents For Home Owners Installation data 2 System diagram 3 Area of use 3 Product description 3 Hot water heating 3 Abbreviations 3 Heating

More information

User manual NIBE F470. Exhaust air heat pump UHB GB LEK

User manual NIBE F470. Exhaust air heat pump UHB GB LEK User manual Exhaust air heat pump LEK UHB GB 1338-1 231487 A detailed explanation of the button functions can be found on page 11. How to scroll through menus and make different settings is described on

More information

User manual NIBE SMO 20

User manual NIBE SMO 20 User manual Control module LEK UHB GB 1436-3 231759 A detailed explanation of the button functions can be found on page 10. How to scroll through menus and make different settings is described on page

More information

Installer manual NIBE F135

Installer manual NIBE F135 Installer manual Exhaust air module IHB GB 1622-4 331432 Table of Contents 1 Important information 4 Index 34 Safety information 4 2 Delivery and handling 7 Transport 7 Assembly 7 Supplied components

More information

NIBE SPLIT ACVM , AMS 10

NIBE SPLIT ACVM , AMS 10 MOS GB 1252-4 INSTALLATION AND MAINTENANCE INSTRUCTIONS 431156 ACVM 10-270, AMS 10 LEK LEK LEK 2 LEK LEK LEK LEK 1 7 5 3 6 LEK LEK LEK 4 $06 K LE LE K LE K LEK LEK $06 Table of Contents For Home Owners

More information

NIBE SPLIT ACVM 270, AMS 10

NIBE SPLIT ACVM 270, AMS 10 MOS GB 0923-1 INSTALLATION AND MAINTENANCE INSTRUCTIONS 031211 ACVM 270, AMS 10 LEK LEK LEK 2 1 LEK LEK LEK LEK 5 3 6 4 LEK LEK 7 LEK LEK LEK Table of Contents For Home Owners General 3 Installation data

More information

NIBE SPLIT ACVM 270, AMS 10

NIBE SPLIT ACVM 270, AMS 10 MOS GB 1452-1 INSTALLATION AND MAINTENANCE INSTRUCTIONS 331183 ACVM 270, AMS 10 LEK LEK LEK 2 LEK LEK LEK LEK 1 7 5 3 6 LEK LEK LEK 4 AMS 10-8 K LE LE K LE K LEK LEK AMS 10-12 Table of Contents For Home

More information

Installer manual NIBE VVM 500

Installer manual NIBE VVM 500 Installer manual Indoor module APH IHB EN 1751-9 031991 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the

More information

Installer manual NIBE F1245. Ground source heat pump IHB GB

Installer manual NIBE F1245. Ground source heat pump IHB GB Installer manual Ground source heat pump LEK IHB GB 1343-2 231611 A detailed explanation of the button functions can be found on page 34. How to scroll through menus and make different settings is described

More information

User manual NIBE F1255

User manual NIBE F1255 User manual Ground source heat pump LEK UHB GB 142-231530 A detailed explanation of the button functions can be found on page 11. How to scroll through menus and make different settings is described on

More information

Installer manual NIBE F750. Exhaust air heat pump IHB GB LEK

Installer manual NIBE F750. Exhaust air heat pump IHB GB LEK Installer manual Exhaust air heat pump IHB GB 1437-1 231917 A detailed explanation of the button functions can be found on page 30. How to scroll through menus and make different settings is described

More information

Installer manual NIBE VVM 310

Installer manual NIBE VVM 310 Installer manual EMK Indoor module APH IHB EN 1750-8 231175 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of

More information

MOS GB VEDEX INSTALLATION AND MAINTENANCE INSTRUCTIONS VEDEX 3300 LEK

MOS GB VEDEX INSTALLATION AND MAINTENANCE INSTRUCTIONS VEDEX 3300 LEK MOS GB 1248-1 VEDEX 3300 231312 INSALLAION AND MAINENANCE INSRUCIONS VEDEX 3300 LEK Contents For Home Owners System diagram 3 Area of use 3 Product description 3 Hot water heating 3 Abbreviations 3 Heating

More information

NIBE FIGHTER 1250 A B C D E F G

NIBE FIGHTER 1250 A B C D E F G MOS GB 0844-5 031132 INSTALLATION AND MAINTENANCE INSTRUCTIONS User guide Transport / Installation Commissioning / Adjustment Accessories with quick guide Control / Alarm Technical data Item register A

More information

Installer manual NIBE F1245PC. Ground source heat pump IHB GB

Installer manual NIBE F1245PC. Ground source heat pump IHB GB Installer manual Ground source heat pump LEK IHB GB 1506-3 231810 A detailed explanation of the button functions can be found on page 34. How to scroll through menus and make different settings is described

More information

User manual NIBE VVM 320

User manual NIBE VVM 320 User manual Indoor module APH UHB GB 1336-1 231358 A detailed explanation of the button functions can be found on page 11. How to scroll through menus and make different settings is described on page 15.

More information

Installer manual AXC 30

Installer manual AXC 30 LEK Installer manual AXC 0 Accessories IHB GB - Table of Contents General Contents Component positions Common electrical connection Connecting communication Connecting the supply Shunt controlled additional

More information

User manual NIBE VVM 500

User manual NIBE VVM 500 User manual Indoor module APH UHB GB 1613-5 431240 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button

More information

User manual NIBE SMO 20

User manual NIBE SMO 20 User manual Control module LEK UHB GB 1546-4 231759 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button

More information

User manual NIBE F2026

User manual NIBE F2026 User manual Air/water heat pump LEK UHB GB 1244-2 031864 Table of Contents 1 Important information 2 Installation data 2 Safety information 4 Serial number 5 Contact information 6 F2026 - An excellent

More information

NIBE F2026 air/water heat pump. fresh air s free. NIBE F2026. Efficient scroll compressor that operates at temperatures down to -20 C.

NIBE F2026 air/water heat pump. fresh air s free. NIBE F2026. Efficient scroll compressor that operates at temperatures down to -20 C. NIBE F2026 air/water heat pump fresh air s free. Efficient scroll compressor that operates at temperatures down to -20 C. Automatic 2-step capacity regulator for the fan (not 6kW). Manufactured in three

More information

User manual NIBE SMO 40

User manual NIBE SMO 40 User manual Control module LEK UHB GB 1546-3 231761 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button

More information

Installer manual NIBE F2300. Air/water heat pump IHB GB LEK

Installer manual NIBE F2300. Air/water heat pump IHB GB LEK Installer manual Air/water heat pump LEK IHB GB 1508-1 231141 Table of Contents 1 Important information Safety information 2 Delivery and handling Transport and storage Assembly Supplied components 2

More information

Installer manual SMO 40

Installer manual SMO 40 Installer manual Accessory Card Accessories IHB GB - 0 Table of Contents General Component positions Shunt controlled additional heat General Pipe connections Outline diagram Electrical connection Program

More information

Installer manual NIBE F470

Installer manual NIBE F470 Installer manual Exhaust air heat pump LEK IHB GB 1549-2 231450 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation

More information

NIBE VVM 500 FLEXIBLE INDOOR MODULE INTELLIGENT HOT WATER NIBE VVM 500. Flexible all-in-one indoor module for heating and hot water.

NIBE VVM 500 FLEXIBLE INDOOR MODULE INTELLIGENT HOT WATER NIBE VVM 500. Flexible all-in-one indoor module for heating and hot water. NIBE VVM 500 FXIB INDOOR MODU INTELLIGENT HOT WATER Flexible all-in-one indoor module for heating and hot water. For upgrading existing heating systems or new buildings with requirements for high performance

More information

Installer manual NIBE F370

Installer manual NIBE F370 Installer manual Exhaust air heat pump LEK IHB GB 1536-2 231470 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation

More information

Installer manual SMO 40

Installer manual SMO 40 Installer manual Control module IHB EN 76-5 23760 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button

More information

NIBE F2120 Air/water heat pump

NIBE F2120 Air/water heat pump NIBE Air/water heat pump A breakthrough in efficiency NIBE is an air/water heat pump that has made a real breakthrough with a market leading SCOP. utilises the heat from the outdoor air which places big

More information

User manual NIBE F470

User manual NIBE F470 User manual Exhaust air heat pump LEK UHB GB 1544-1 231451 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the

More information

Technical Guide. Installation, Operation and Care. EP E series 7 step electric boilers 26 and 42 kw

Technical Guide. Installation, Operation and Care. EP E series 7 step electric boilers 26 and 42 kw Technical Guide Installation, Operation and Care EP E series 7 step electric boilers 26 and 42 kw Arkelstorpsvägen 88, 291 94 KRISTIANSTAD Tel +46 44-22 63 20, Telefax +46 44-22 63 58 e-mail: info@varmebaronen.se

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS FIGHTER 600P MOS GB FIGHTER 600P 1, 2,... LEK

INSTALLATION AND MAINTENANCE INSTRUCTIONS FIGHTER 600P MOS GB FIGHTER 600P 1, 2,... LEK ,,... MOS GB 04-644 R INSTALLATION AND MAINTENANCE INSTRUCTIONS General Concise product description... Setting table... System description Principle of operation... System diagram... Front panel Front

More information

Installer manual NIBE F2300. Air/water heat pump IHB GB LEK

Installer manual NIBE F2300. Air/water heat pump IHB GB LEK Installer manual Air/water heat pump IHB GB 1138-1 031741 Table of Contents 1 Important information 2 Safety information 2 2 Delivery and handling 7 Transport and storage 7 Assembly 7 Supplied components

More information

Installer manual NIBE F370

Installer manual NIBE F370 Installer manual Exhaust air heat pump LEK IHB GB 1608-4 231436 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

Installer manual NIBE VVM 325. Indoor module IHB GB APH

Installer manual NIBE VVM 325. Indoor module IHB GB APH Installer manual Indoor module APH IHB GB 1442-1 331115 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the

More information

User manual NIBE F470

User manual NIBE F470 User manual Exhaust air heat pump LEK UHB GB 1609-2 231451 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the

More information

Installer manual SMO 40

Installer manual SMO 40 Installer manual UK Control module IHB GB 1546-3 231764 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the

More information

Installer manual NIBE SPLIT HBS 05

Installer manual NIBE SPLIT HBS 05 LEK LEK LEK Installer manual AMS 10-8 / 10-12 / 10-16, HBS 05-12 / 05-16 Air/water heat pump LEK LEK IHB GB 1622-1 331592 Table of Contents 1 Important information 4 8 Disturbances in comfort 44 System

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

Installation, operation and care. Pellmax UB. Burner not included Replaces:

Installation, operation and care. Pellmax UB. Burner not included Replaces: Installation, operation and care Burner not included 2011-11-11 ver: Replaces: Contents 11.11 otes...3 General...4 Function...4 Technical data...5 System principle Pellmax with radiator and tank-in-tank

More information

NIBE F470 A + Complete heat pump unit that provides heating, hot water, ventilation, heated supply air and heat recovery. Exhaust air heat pump

NIBE F470 A + Complete heat pump unit that provides heating, hot water, ventilation, heated supply air and heat recovery. Exhaust air heat pump NIBE F470 Exhaust air heat pump Complete heat pump unit that provides heating, hot water, ventilation, heated supply air and heat recovery Display unit with easytoread colour screen. It also gives you

More information

Installer manual AG-WL10

Installer manual AG-WL10 LEK LED CLEAN TIMER OPERATION Installer manual Indoor unit air/air heat pump IHB GB 1637-1 331827 Table of Contents 1 Important information Safety information Read before starting the installation Electrical

More information

Installation, operation and care Wall-mounted electric boiler MP THL nr. - rev 02

Installation, operation and care Wall-mounted electric boiler MP THL nr. - rev 02 Installation, operation and care Wall-mounted electric boiler MP 4 150206 THL nr. - rev 02 Contents Notes... 3 Safety and handling... 4 Operation... 5 Technical data... 6 Pipe installation... 8 System

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS AMB AMB 30 LEK

INSTALLATION AND MAINTENANCE INSTRUCTIONS AMB AMB 30 LEK MOS GB 1044-1 INSTALLATION AND MAINTENANCE INSTRUCTIONS 031533 Table of Contents For the User General System description Principle of operation 3 Outdoor air operation 3 Hybrid operation 3 The control

More information