SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

Size: px
Start display at page:

Download "SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A"

Transcription

1 Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. Please void OBH733 REVISED EDITION-A. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH733 REVISED EDITION-B Models MUZ-GL09NA - U8 MUZ-GL09NAH - U8 MUY-GL09NA - U1 MUZ-GL12NA - U1 MUZ-GL12NAH - U1 MUY-GL12NA - U1 MUZ-GL15NA - U1 MUZ-GL15NAH - U1 MUY-GL15NA - U1 MUZ-GL18NA - U1 MUZ-GL18NAH - U1 MUY-GL18NA - U1 MUZ-GL24NA - U1 MUY-GL24NA - U1 Indoor unit service manual MSZ-GL NA, MSY-GL NA Series (OBH732) MUZ-GL18/24NA MUZ-GL18NAH MUY-GL18/24NA CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES AND FUNCTIONS 3 3. SPECIFICATION 4 4. OUTLINES AND DIMENSIONS 7 5. WIRING DIAGRAM 9 6. REFRIGERANT SYSTEM DIAGRAM DATA ACTUATOR CONTROL SERVICE FUNCTIONS TROUBLESHOOTING DISASSEMBLY INSTRUCTIONS 62 PARTS CATALOG (OBB733) NOTE: RoHS compliant products have <G> mark on the spec name plate.

2 Use the specified refrigerant only Never use any refrigerant other than that specified. Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions. Revision A: MUZ-GL12/15NA- U1, MUZ-GL12/15NAH- U1 and MUY-GL09/12/15NA- U1 have been added. Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. 1 TECHNICAL CHANGES MUZ-GL18NA - U1 MUZ-GL18NAH - U1 MUY-GL18NA - U1 MUZ-GL24NA - U1 MUY-GL24NA - U1 1. New model MUZ-GL09NA - U8 MUZ-GL09NAH - U8 MUY-GL09NA - U1 MUZ-GL12NA - U1 MUZ-GL12NAH - U1 MUY-GL12NA - U1 MUZ-GL15NA - U1 MUZ-GL15NAH - U1 MUY-GL15NA - U1 1. New model 2

3 2 PART NAMES AND FUNCTIONS MUZ-GL09NA MUZ-GL12NA MUZ-GL15NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NAH MUY-GL15NA Air inlet (back and side) Piping Air outlet Drain hose Drain outlet MUZ-GL18NA MUZ-GL24NA MUZ-GL18NAH MUY-GL18NA MUY-GL24NA Air inlet (back and side) Piping Drain hose Air outlet Drain outlet 3

4 3 SPECIFICATION Outdoor unit model Capacity Rated (Minimum~Maximum) MUZ- GL09NA MUZ- GL09NAH 4 MUY- GL09NA MUZ- GL12NA MUZ- GL12NAH MUY- GL12NA MUZ- GL15NA MUZ- GL15NAH MUY- GL15NA Cooling 1 Btu/h 9,000 (3,600-12,200) 12,000 (1,500-13,600) 14,000 (3,100-18,200) 10,900 14,400 18,000 Heating 47 1 (MUZ) Btu/h (4,500-14,100) (2,000-18,100) (4,800-20,900) Capacity 6,900 9,200 12,200 Heating 17 2 (MUZ) Btu/h Rated (Maximum) (10,800) (12,000) (16,400) Cooling 1 W 585 (240-1,050) 920 (100-1,300) 1,080 (210-2,000) Power consumption 720 1,100 1,600 Rated (Minimum~Maximum) Heating 47 1 (MUZ) W (230-1,350) (110-1,620) (2,010) Power consumption ,190 Heating 17 2 (MUZ) W Rated (Maximum) (1,060) (1,240) (1,850) EER 1 [SEER] 3 Cooling 15.4 [24.6] 13.0 [23.1] 13.0 [21.6] NA: NA: NA: HSPF IV 4 Heating (MUZ) NAH: NAH: NAH: COP Heating 1 (MUZ) Power factor Cooling (208/230) % 92/92 87/87 95/95 97/97 Heating (MUZ) (208/230) % 95/95-96/96 98/98 Power supply V, phase, Hz 208/230, 1, 60 Max. fuse size (time delay) A 15 Min. circuit ampacity A Fan motor F.L.A A 0.50 Model SNB092FQAMT KNB073FRVMC SNB092FQAMT SNB130FQBMT Compressor R.L.A A L.R.A A Refrigeration oil L (Model) 0.35 (FV50S) 0.27 (FV50S) 0.35 (FV50S) 0.35 (FV50S) Refrigerant control Linear expansion valve Sound level 1 Cooling db(a) Heating (MUZ) db(a) Airfl ow Cooling CFM 1, High - Med. - Low Heating (MUZ) CFM 1,186-1,116-1,045-1,186-1,116-1,045-1,186-1,045-1,045 - Fan speed Cooling rpm High - Med. - Low Heating (MUZ) rpm Defrost method Reverse cycle W in. 31-1/2 Dimensions D in. 11-1/4 H in. 21-5/8 Weight Ib. 81 External fi nish Munsell 3Y 7.8/1.1 Remote controller Wireless type Control voltage (by built-in transformer) VDC Refrigerant piping t supplied Refrigerant pipe size Liquid in. 1/4 (0.0315) (Min. wall thickness) Gas in. 3/8 (0.0315) 1/2 (0.0315) Connection method Indoor Flared Outdoor Flared Between the indoor Height difference ft. 40 & outdoor units Piping length ft. 65 Refrigerant charge (R410A) 2 lb. 9 oz. NOTE: Test conditions are based on AHRI 210/240. 1: Rating conditions (Cooling) Indoor: 80 FDB, 67 FWB, Outdoor: 95 FDB, (75 FWB) (Heating) Indoor: 70 FDB, 60 FWB, Outdoor: 47 FDB, 43 FWB 2: (Heating) Indoor: 70 FDB, 60 FWB, Outdoor: 17 FDB, 15 FWB 3: Test condition (Refer to page 6.) 4: Test condition (Refer to page 6.)

5 Outdoor unit model Capacity Rated (Minimum~Maximum) Capacity Rated (Maximum) Power consumption Rated (Minimum~Maximum) MUZ-GL18NA MUY-GL18NA MUZ-GL24NA MUY-GL24NA MUZ-GL18NAH Cooling 1 Btu/h 18,000 (5,800 ~ 22,000) 22,500 (8,200 ~ 31,400) Heating 47 1 (MUZ) Btu/h 21,600 (5,400 ~ 25,000) - 27,600 (7,500 ~ 36,900) - Heating 17 2 (MUZ) Btu/h 13,800 (18,200) - 16,000 (24,600) - Cooling 1 W 1,295 (285 ~ 2,105) 1,742 (560 ~ 3,522) Heating 47 1 (MUZ) W 1,635 (275 ~ 2,455) 2,282 (508 ~ 3,592) Power consumption Rated (Maximum) Heating 17 2 (MUZ) W 1,435 (2,105) - 1,712 (3,232) - EER 1 [SEER] 3 Cooling 13.4 [20.5] 12.5 [20.5] HSPF IV 4 Heating (MUZ) NA: NA: 10.0 NAH: COP Heating 1 (MUZ) Power factor Cooling (208/230) % 99/99 99/99 Heating (MUZ) (208/230) % 99/99-99/99 - Power supply V, phase, Hz 208/230, 1, 60 Max. fuse size (time delay) A Min. circuit ampacity A Fan motor F.L.A A Model SNB130FQBMT SNB172FQKMT Compressor R.L.A A L.R.A A Refrigeration oil L (Model) 0.35 (FV50S) 0.35 (FV50S) 0.40 (FV50S) Refrigerant control Linear expansion valve Sound level 1 Cooling db(a) Heating (MUZ) db(a) Airfl ow High - Med. - Low Fan speed High - Med. - Low Defrost method Dimensions Cooling CFM 1, ,016-1, Heating (MUZ) CFM 1,689-1,689-1,372-1,701-1,701-1,341 - Cooling rpm Heating (MUZ) rpm Reverse cycle W in. 33-1/16 D in. 13 H in. 34-5/8 Weight Ib External fi nish Munsell 3Y 7.8/1.1 Remote controller Wireless type Control voltage (by built-in transformer) VDC Refrigerant piping t supplied Refrigerant pipe size (Min. wall thickness) Connection method Between the indoor & outdoor units Liquid in. 1/4 (0.0315) 3/8 (0.0315) Gas in. 1/2 (0.0315) 5/8 (0.0315) Indoor Flared Outdoor Flared Height difference ft. 50 Piping length ft. 100 Refrigerant charge (R410A) 3 lb. 9 oz. 4 lb. 3 oz. NOTE: Test conditions are based on AHRI 210/240. 1: Rating conditions (Cooling) Indoor: 80 FDB, 67 FWB, Outdoor: 95 FDB, (75 FWB) (Heating) Indoor: 70 FDB, 60 FWB, Outdoor: 47 FDB, 43 FWB 2: (Heating) Indoor: 70 FDB, 60 FWB, Outdoor: 17 FDB, 15 FWB 3: Test condition (Refer to page 6.) 4: Test condition (Refer to page 6.) 5

6 Test condition 3, 4 ARI Mode Test SEER (Cooling) HSPF (Heating) "A-2" Cooling Steady State at rated compressor Speed "B-2" Cooling Steady State at rated compressor Speed "B-1" Cooling Steady State at minimum compressor Speed "F-1" Cooling Steady State at minimum compressor Speed "E-V" Cooling Steady State at Intermediate compressor Speed 5 "H1-2" Heating Steady State at rated compressor Speed "H3-2" Heating at rated compressor Speed "H0-1" Heating Steady State at minimum compressor Speed "H1-1" Heating Steady State at minimum compressor Speed "H2-V" Heating at Intermediate compressor Speed 5 Indoor air condition ( F) Outdoor air condition ( F) Dry bulb Wet bulb Dry bulb Wet bulb (75) (65) (65) (53.5) (69) NOTE: 5: At Intermediate compressor Speed = ("Rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed". OPERATING RANGE (1) POWER SUPPLY Rated voltage Guaranteed voltage (V) Outdoor unit 208/230 V 1 phase 60 Hz Min Max. 253 (2) OPERATION Intake air temperature ( F) Mode Condition Indoor Outdoor DB WB DB WB Standard temperature Cooling Maximum temperature Minimum temperature Maximum humidity 78 % Standard temperature Heating Maximum temperature Minimum temperature

7 4 OUTLINES AND DIMENSIONS MUZ-GL09NA MUZ-GL12NA MUZ-GL15NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NAH MUY-GL15NA Unit: inch REQUIRED SPACE *1 4 in. (100 mm) or more when front and sides of the unit are clear 4 in. (100 mm) or more clear *1 4 in. (100 mm) or more (GL09/12/15NA) (GL12/15NAH) 8 in. (200 mm) or more *2 14 in. (350 mm) or more *2 When any 2 sides of left, right and rear of the unit are clear holes Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 1/4 Gas refrigerant pipe joint Refrigerant pipe (flared) Ø 3/8 (GL09/12) Ø 1/2 (GL15) 7

8 MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA MUZ-GL24NA MUY-GL24NA Unit: inch REQUIRED SPACE *1 20 in. (500 mm) or more when front and sides of the unit are clear Clear *1 16-7/16 Air in Drain hole 1-9/16 1-5/8 4 in. (100 mm) or more 4 in. (100 mm) or more 13 2 Air in 14-3/16 Air out 6-7/ / /16 4-5/16 2-holes 13/32 13/16 3-3/16 20 in. (500 mm) or more *2 Service panel 14 in. (350 mm) or more *2 When any 2 sides of left, right and rear of the unit are clear Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 1/4 (GL18) Refrigerant pipe (flared) Ø 3/8 (GL24) 17-25/ / /2 3-29/ /16 Gas refrigerant pipe joint Refrigerant pipe (flared) Ø 1/2 (GL18) Refrigerant pipe (flared) Ø 5/8 (GL24) 8

9 5 WIRING DIAGRAM MUZ-GL09NA MUZ-GL12NA 9

10 MUZ-GL09NAH MUZ-GL12NAH 10

11 MUY-GL09NA MUY-GL12NA 11

12 MUZ-GL15NA 12

13 MUZ-GL15NAH 13

14 MUY-GL15NA 14

15 MUZ-GL18NA 15

16 MUZ-GL18NAH 16

17 MUY-GL18NA 17

18 MUZ-GL24NA 18

19 MUY-GL24NA 19

20 6 REFRIGERANT SYSTEM DIAGRAM MUZ-GL09NA MUZ-GL12NA MUZ-GL15NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NAH MUY-GL15NA Unit: Inch (mm) Refrigerant pipe ø3/8 (ø9.52) (GL09/12) ø1/2 (ø12.7) (GL15) 4-way valve (with heat insulator) Flared connection Muffler Stop valve (with service port) Service port Discharge temperature thermistor RT62 Muffler Service port Compressor Defrost thermistor RT61 (MUZ) Outdoor heat exchanger Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Flared connection Stop valve (with strainar) Refrigerant pipe ø1/4 (ø6.35) (with heat insulator) MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA Refrigerant pipe ø1/2 (ø12.7) (with heat insulator) Capillary tube O.D I.D /16 (ø4.0 ø ) 4-way valve LEV Capillary tube O.D I.D /32 (ø3.0 ø ) Refrigerant flow in cooling Refrigerant flow in heating (MUZ) Muffler with #100 mesh strainer Strainer #100 R.V. coil (MUZ) heating ON cooling OFF Service port Flared connection Stop valve (with service port) Service port Discharge temperature thermistor RT62 Defrost thermistor RT61 (MUZ) Outdoor heat exchanger Flared connection Stop valve Refrigerant pipe ø1/4 (ø6.35) (with heat insulator) Strainer #100 Muffler Compressor Capillary tube O.D I.D /16 (ø4.0 ø ) Capillary tube O.D I.D /8 (ø3.0 ø ( 4)) LEV Strainer # Capillary tube O.D I.D /8 (ø4.0 ø ) Outdoor heat exchanger temperature thermistor RT68 R.V. coil (MUZ) heating ON cooling OFF Refrigerant flow in cooling Refrigerant flow in heating (MUZ)

21 MUZ-GL24NA MUY-GL24NA Refrigerant pipe ø5/8 (ø15.88) (with heat insulator) 4-way valve Muffler with #100 mesh strainer Service port Flared connection Stop valve (with service port) Service port Discharge temperature thermistor RT62 Defrost thermistor RT61 (MUZ) Outdoor heat exchanger Ambient temperature thermistor RT65 Compressor Outdoor heat exchanger temperature thermistor RT68 Flared connection Stop valve Refrigerant pipe ø3/8 (ø9.52) (with heat insulator) Strainer #100 LEV Capillary tube O.D I.D /16 (ø4.0 ø ) Strainer #100 R.V. coil (MUZ) heating ON cooling OFF Refrigerant flow in cooling Refrigerant flow in heating (MUZ) 21

22 MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE Model MUZ-GL09NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NA MUZ-GL15NAH MUY-GL15NA MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA MUZ-GL24NA MUY-GL24NA Max. Length A Refrigerant piping: ft. Max. Height difference B Gas 3/8 1/2 Piping size O.D: in. Liquid 1/4 5/8 3/8 Indoor unit Max. Height difference B Max. Length A Outdoor unit ADDITIONAL REFRIGERANT CHARGE (R410A: oz.) NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation. Model MUZ-GL09NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NA MUZ-GL15NAH MUY-GL15NA Outdoor unit precharged Refrigerant piping length (one way): ft lb. 9 oz Calculation: X oz. = 1.08/5 oz./ft. (Refrigerant piping length (ft.) - 25) 22

23 NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation. Model MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA Outdoor unit precharged Refrigerant piping length (one way): ft lb. 9 oz Calculation: X oz. = 1.08/5 oz./ft. (Refrigerant piping length (ft.) - 25) NOTE: Refrigerant piping exceeding 33 ft. requires additional refrigerant charge according to the calculation. Model MUZ-GL24NA MUY-GL24NA Outdoor unit precharged Refrigerant piping length (one way): ft lb. 3 oz Calculation: X oz. = 2.96/5 oz./ft. (Refrigerant piping length (ft.) - 33) 23

24 7 DATA MUZ-GL09NA MUZ-GL12NA MUZ-GL15NA MUZ-GL18NA MUZ-GL24NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NAH MUY-GL15NA MUZ-GL18NAH MUY-GL18NA MUY-GL24NA 7-1. PERFORMANCE DATA 1) COOLING CAPACITY Indoor air Model IWB ( F) MUZ-GL09NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NA MUZ-GL15NAH MUY-GL15NA MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA MUZ-GL24NA MUY-GL24NA Outdoor intake air DB temperature ( F) TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC NOTE: 1. IWB : Intake air wet-bulb temperature TC : Total Capacity (x10 3 Btu/h) SHC : Sensible Heat Capacity (x10 3 Btu/h) TPC : Total Power Consumption (kw) 2. SHC is based on 80 F of indoor Intake air DB temperature. 2) COOLING CAPACITY CORRECTIONS MUZ-GL09NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NA MUZ-GL15NAH MUY-GL15NA MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA MUZ-GL24NA MUY-GL24NA Refrigerant piping length (one way: ft.) 25 (std.)

25 3) HEATING CAPACITY (MUZ) Indoor air Outdoor intake air WB temperature ( F) Model IDB ( F) TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC MUZ-GL09NA MUZ-GL12NA MUZ-GL09NAH MUZ-GL12NAH MUZ-GL15NA MUZ-GL15NAH MUZ-GL18NA MUZ-GL18NAH MUZ-GL24NA NOTE: 1. IDB : Intake air dry-bulb temperature TC : Total Capacity (x10 3 Btu/h) TPC : Total Power Consumption (kw) 2. Above data is for heating operation without any frost. How to operate with fixed operational frequency of the compressor. 1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL mode or EMERGENCY HEAT mode before starting to operate the air conditioner. 2. The compressor starts with operational frequency. 3. The fan speed of the indoor unit is High. 4. This operation continues for 30 minutes. 5. In order to release this operation, press the EMERGENCY OPERATION switch or press any button on the remote controller. 25

26 7-2. PERFORMANCE CURVE Cooling Capacity correction factors Cooling capacity (at Rated frequency) Outdoor intake air DB temperature( F) Indoor intake air Wet-bulb temperature( F) MUZ-GL09NA MUZ-GL09NAH MUY-GL09NA Total power consumption (kw) SHF at rating condition = 0.82 Airflow = 399 CFM Indoor intake air WB temperature ( F) Outdoor intake air DB temperature ( F) MUZ-GL12NA MUZ-GL12NAH MUY-GL12NA Total power consumption (kw) SHF at rating condition = 0.77 Airflow = 399 CFM Indoor intake air WB temperature ( F) Outdoor intake air DB temperature ( F) MUZ-GL15NA MUZ-GL15NAH MUY-GL15NA Total power consumption (kw) SHF at rating condition = 0.78 Airflow = 533 CFM Outdoor intake air DB temperature ( F) Indoor intake air WB temperature ( F) MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA Total power consumption (kw) SHF at rating condition = 0.87 Airflow = 646 CFM Indoor intake air WB temperature ( F) Outdoor intake air DB temperature ( F) MUZ-GL24NA MUY-GL24NA Total power consumption (kw) SHF at rating condition = 0.75 Airflow = 634 CFM Indoor intake air WB temperature ( F) Outdoor intake air DB temperature ( F) This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity. 26

27 Heating Capacity correction factor Heating capacity (at Rated frequency) Indoor intake air Dry-bulb temperature ( F) Outdoor intake air WB temperature ( F) MUZ-GL09NA Total power consumption (kw) Indoor intake air DB temperature ( F) Airflow = 406 CFM Outdoor intake air WB temperature ( F) MUZ-GL09NAH Total power consumption (kw) Indoor intake air DB temperature ( F) Airflow = 406 CFM Outdoor intake air WB temperature ( F) MUZ-GL12NA Total power consumption (kw) MUZ-GL15NA Total power consumption (kw) Indoor intake air DB temperature ( F) Airflow = 406 CFM Outdoor intake air WB temperature ( F) Indoor intake air DB temperature ( F) Airflow = 463 CFM Outdoor intake air WB temperature ( F) MUZ-GL12NAH Total power consumption (kw) Outdoor intake air WB temperature ( F) MUZ-GL15NAH Total power consumption (kw) Indoor intake air DB temperature ( F) Indoor intake air DB temperature ( F) Airflow = 406 CFM Airflow = 463 CFM Outdoor intake air WB temperature ( F)

28 MUZ-GL18NA Total power consumption (kw) Indoor intake air DB temperature ( F) Airflow = 646 CFM Outdoor intake air WB temperature ( F) MUZ-GL18NAH Total power consumption (kw) Indoor intake air DB temperature ( F) Airflow = 646 CFM Outdoor intake air WB temperature ( F) MUZ-GL24NA Total power consumption (kw) Indoor intake air DB temperature ( F) Airflow = 738 CFM Outdoor intake air WB temperature ( F) This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity. 28

29 7-3. CONDENSING PRESSURE Cooling Data are based on the condition of indoor humidity 50 %. Air flow should be set to High speed. MUZ-GL09NA MUZ-GL09NAH MUY-GL09NA (PSIG) 450 Condensing pressure Indoor DB temperature ( F) ( F) Outdoor ambient temperature MUZ-GL12NA MUZ-GL12NAH MUY-GL12NA (PSIG) 500 Condensing pressure MUZ-GL15NA MUZ-GL15NAH MUY-GL15NA ( F) Outdoor ambient temperature (PSIG) 500 Condensing pressure Indoor DB temperature ( F) Indoor DB temperature ( F) ( F) Outdoor ambient temperature (PSIG) 180 Suction pressure Indoor DB temperature ( F) Outdoor ambient temperature (PSIG) 180 Suction pressure Indoor DB temperature ( F) Outdoor ambient temperature (PSIG) 180 Suction pressure Indoor DB temperature ( F) Outdoor ambient temperature ( F) ( F) ( F) 29

30 MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA (PSIG) 500 Condensing pressure Indoor DB temperature ( F) (PSIG) 180 Suction pressure Indoor DB temperature ( F) ( F) Outdoor ambient temperature Outdoor ambient temperature ( F) MUZ-GL24NA MUY-GL24NA Condensing pressure (PSIG) Indoor DB temperature ( F) Suction pressure (PSIG) Indoor DB temperature ( F) ( F) Outdoor ambient temperature ( F) Outdoor ambient temperature 30

31 Heating Data are based on the condition of outdoor humidity 75%. Air flow should be set to High speed. Data are for heating operation without any frost. MUZ-GL09NA MUZ-GL09NAH Condensing pressure (PSIG) Indoor DB temperature ( F) 58Hz (PSIG) Suction pressure Indoor DB temperature ( F) 58Hz ( F) Outdoor ambient temperature ( F) Outdoor ambient temperature MUZ-GL12NA MUZ-GL12NAH (PSIG) (PSIG) Condensing pressure Indoor DB temperature ( F) Suction pressure Indoor DB temperature ( F) Hz 65 58Hz ( F) Outdoor ambient temperature ( F) Outdoor ambient temperature MUZ-GL15NA MUZ-GL15NAH Condensing pressure (PSIG) Indoor DB temperature ( F) (PSIG) 190 Suction pressure Indoor DB temperature ( F) Hz 65 58Hz ( F) Outdoor ambient temperature ( F) Outdoor ambient temperature 31

32 MUZ-GL18NA MUZ-GL18NAH Condensing pressure (PSIG) Indoor DB temperature ( F) (PSIG) 200 Suction pressure Indoor DB temperature ( F) Hz 75 81Hz ( F) Outdoor ambient temperature ( F) Outdoor ambient temperature MUZ-GL24NA Condensing pressure (PSIG) Indoor DB temperature ( F) Suction pressure (PSIG) Indoor DB temperature ( F) Hz Hz ( F) ( F) Outdoor ambient temperature Outdoor ambient temperature 32

33 7-4. STANDARD OPERATION DATA Total Electrical circuit Refrigerant circuit Indoor unit Outdoor unit Model MSZ-GL09NA MSY-GL09NA MSZ-GL12NA MSY-GL12NA MSZ-GL15NA MSY-GL15NA Item Unit Cooling Heating Cooling Cooling Heating Cooling Heating Capacity Btu/h 9,000 10,900 9,000 12,000 14,400 14,000 18,000 SHF Input kw Rated frequency Hz Indoor unit MSZ-GL09NA MSY-GL09NA Power supply V, phase, Hz 208/230, 1, 60 MSZ-GL12NA MSY-GL12NA MSZ-GL15NA MSY-GL15NA Input kw Fan motor current A 0.24/ / / / / / /0.31 Outdoor unit MUZ-GL09NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NA MUZ-GL15NAH MUY-GL15NA Power supply V, phase, 208/230, 1, 60 Hz Input kw Comp. current A 2.45/ / / / / / /6.43 Fan motor current A 0.36/ / / / / / /0.36 Condensing pressure PSIG Suction pressure PSIG Discharge temperature F Condensing temperature F Suction temperature F Comp. shell bottom temperature F Ref. pipe length ft. 25 Refrigerant charge (R410A) 2 lb 9 oz. Intake air temperature DB F WB F Discharge air temperature DB F WB F Fan speed (High) rpm 1,020 1,040 1,020 1,020 1,040 1,280 1,140 Airfl ow (High) CFM 367 (Wet) (Wet) 367 (Wet) (Wet) 463 Intake air temperature DB F WB F Fan speed rpm Airfl ow CFM 1,229 1,172 1,229 1,229 1,172 1,243 1,229 33

34 Outdoor unit Indoor unit Refrigerant circuit Electrical circuit Total Model MSZ-GL18NA MSY-GL18NA MSZ-GL24NA MSY-GL24NA Item Unit Cooling Heating Cooling Heating Capacity Btu/h 18,000 21,600 22,500 27,600 SHF Input kw Rated frequency Hz Indoor unit Power supply V, phase, Hz MSZ-GL18NA MSY-GL18NA 208/230, 1, 60 MSZ-GL24NA MSY-GL24NA Input kw Fan motor current A 0.46/ /0.51 Outdoor unit Power supply V, phase, Hz MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA 208/230, 1, 60 MUZ-GL24NA MUY-GL24NA Input kw Comp. current A 5.01/ / / /8.67 Fan motor current A 1.05/ / / /1.02 Condensing pressure PSIG Suction pressure PSIG Discharge temperature F Condensing temperature F Suction temperature F Comp. shell bottom temperature F Ref. pipe length ft. 25 Refrigerant charge (R410A) 3 lb 9 oz. 4 lb 3 oz. Intake air temperature Discharge air temperature DB F WB F DB F WB F Fan speed (High) rpm 1,170 1,170 1,300 1,300 Airfl ow (High) CFM 581 (Wet) (Wet) 738 Intake air temperature DB F WB F Fan speed rpm Airfl ow CFM 1,691 1,691 1,769 1,701 34

35 7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY MUY-GL09NA 2.0 Correction of Cooling capacity Correction of Cooling total input 2.0 Capacity correction factors Input correction factors (Hz) (Hz) The operational frequency of compressor The operational frequency of compressor MUZ-GL09NA MUZ-GL09NAH Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity Correction of Heating total input 2.0 Capacity correction factors Input correction factors Capacity correction factors Input correction factors (Hz) (Hz) (Hz) (Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor MUZ-GL12NA MUZ-GL12NAH MUY-GL12NA Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity Correction of Heating total input Capacity correction factors Input correction factors Capacity correction factors Input correction factors (Hz) (Hz) (Hz) (Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor MUZ-GL15NA MUZ-GL15NAH MUY-GL15NA Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity Correction of Heating total input Capacity correction factors Input correction factors Capacity correction factors Input correction factors (Hz) (Hz) (Hz) (Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor 35

36 MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA 2.0 Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity Correction of Heating total input 2.0 Capacity correction factors Capacity correction factors (Hz) (Hz) (Hz) (Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor MUZ-GL24NA MUY-GL24NA Correction of Cooling capacity Input correction factors Input correction factors Correction of Cooling total input Capacity correction factors Capacity correction factors Correction of Heating capacity Input correction factors Input correction factors Correction of Heating total input (Hz) The operational frequency of compressor (Hz) The operational frequency of compressor (Hz) The operational frequency of compressor (Hz) The operational frequency of compressor 7-6. HOW TO OPERATE FIXED-FREQUENCY OPERATION (Test run operation) 1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice). 2. Test run operation starts and continues to operate for 30 minutes. 3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode. 4. Indoor fan operates at High speed. 5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies). 6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on the remote controller. 36

37 8 ACTUATOR CONTROL MUZ-GL09NA MUZ-GL12NA MUZ-GL15NA MUZ-GL18NA MUZ-GL24NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NAH MUY-GL15NA MUZ-GL18NAH MUY-GL18NA MUY-GL24NA 8-1. OUTDOOR FAN MOTOR CONTROL The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running. Compressor Outdoor fan motor ON OFF ON 5 seconds 15 seconds OFF 8-2. R.V. COIL CONTROL (MUZ) Heating ON Cooling OFF Dry OFF NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor. <COOL> <HEAT> 5 seconds 5 seconds ON Compressor OFF R.V.coil ON OFF Outdoor fan ON motor OFF 8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR Sensor Purpose Compressor 37 LEV Actuator Outdoor fan motor R.V.coil Indoor fan motor Discharge temperature Protection thermistor Cooling: Coil frost prevention Indoor coil temperature thermistor Heating: High pressure protection Defrost thermistor (MUZ) Heating: Defrosting Fin temperature thermistor Protection Cooling: Low ambient temperature operation Ambient temperature thermistor Outdoor heat exchanger temperature thermistor *. MUZ-GL NAH only. Heating: Defrosting (Heater) Cooling: Low ambient temperature operation Cooling: High pressure protection Defrost heater *

38 9 SERVICE FUNCTIONS MUZ-GL09NA MUZ-GL12NA MUZ-GL15NA MUZ-GL18NA MUZ-GL24NA 9-1. CHANGE IN DEFROST SETTING (MUZ) Changing defrost finish temperature <JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board (Refer to ). Defrost finish temperature Jumper MUZ-GL09NAH MUY-GL09NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NAH MUY-GL15NA MUZ-GL18NAH MUY-GL18NA MUY-GL24NA MUZ-GL09/12/15NA MUZ-GL09/12/15NAH MUZ-GL18/24NA MUZ-GL18NAH JS Soldered (Initial setting) ne (Cut) 41 F (5 C) 50 F (10 C) 50 F (10 C) 64 F (18 C) 9-2. PRE-HEAT CONTROL SETTING (MUZ) MUZ-GL09/12/15/18 When moisture gets into the refrigerant cycle, it may interfere with the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature thermistor is 68 F (20 C) or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W) MUZ-GL24 Prolonged low load operation, in which the thermostat is OFF for a long time, at low outside temperature [32 F (0 C) or less] may cause the following troubles. To prevent those troubles, activate the pre-heat control. 1) If moisture gets into the refrigerant cycle and freezes, it may interfere the start-up of the compressor. 2) If liquid refrigerant collects in the compressor, a failure in the compressor may occur. The pre-heat control turns ON when the compressor temperature is 68 F (20 C) or below. When the pre-heat control turns ON, the compressor is energized. (About 70 W) Pre-heat control setting <JK> ON: To activate the pre-heat control, cut JK wire of the inverter P.C. board. OFF: To deactivate the pre-heat control, solder JK wire of the inverter P.C. board. (Refer to ) JK Jumper Soldered Cut MUZ-GL09/12/15/18NA MUZ-GL09/12/15/18NAH Deactivated (Factory setting) Activated Pre-heat control setting MUZ-GL24NA Deactivated Activated (Factory setting) NOTE: When the inverter P.C. board is replaced, check the jumper wires, and cut/solder them if necessary. 38

39 10 TROUBLESHOOTING MUZ-GL09NA MUZ-GL12NA MUZ-GL15NA MUZ-GL18NA MUZ-GL24NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NAH MUY-GL15NA MUZ-GL18NAH MUY-GL18NA MUY-GL24NA CAUTIONS ON TROUBLESHOOTING 1. Before troubleshooting, check the following 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for miswiring. 2. Take care of the following during servicing 1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after confirming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug. 2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board. 3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor. 4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components. 5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires. <Incorrect> <Correct> Lead wiring Connector housing 3. Troubleshooting procedure 1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service work. (See the service manual of the indoor unit for a description of those failure codes.) 2) Before servicing, check that the connector and terminal are connected properly. 3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration. 4) Refer to 10-2 and

40 10-2. FAILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled. 1. Flow chart of failure mode recall function for the indoor/outdoor unit Operational procedure The cause of abnormality cannot be found because the abnormality does not recur. Setting up the failure mode recall function Turn ON the power supply. <Preparation of the remote controller> While pressing OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button. Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then release the buttons. MSZ-GL06/09/12/15NA MSY-GL09/12/15NA MSZ-GL18NA MSY-GL18NA MSZ-GL24NA MSY-GL24NA Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit Regardless of normal or abnormal condition, a short beep is emitted once the signal is received. Does the upper lamp of the OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the upper lamp of the OPERATION INDICATOR lamp. 2 Judgment of indoor/outdoor abnormality (Blinks) Before blinking, does the upper lamp of the OPERATION INDICATOR lamp stay ON for 3 seconds? When it stays ON for 3 seconds (without beep): The outdoor unit is abnormal. (OFF) Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnormalities that cannot be recalled with this way. Check if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to ) E.g.: MSZ type The indoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least 2 consecutive blinking cycles. 2 The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the outdoor unit failure mode table. (Refer to ) Make sure to check at least 2 consecutive blinking cycles. 3 Releasing the failure mode recall function Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller. Repair the failure parts. Deleting the memorized abnormal condition After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above. Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above. NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized. 2. Blinking pattern when the indoor unit is abnormal: 2.5-second OFF Blinking at 0.5- second interval 2.5-second OFF Blinking at 0.5- second interval ON OFF Beeps Repeated cycle Beeps Repeated cycle Beeps Repeated cycle 3.Blinking pattern when the outdoor unit is abnormal: Blinking at second OFF 3-second ON second interval 2.5-second OFF 3-second ON Blinking at 0.5- second interval ON OFF beep Repeated cycle Beeps 40 beep Repeated cycle Beeps Repeated cycle

41 2. Flow chart of the detailed outdoor unit failure mode recall function Operational procedure The outdoor unit might be abnormal. Check if outdoor unit is abnormal according to the following procedures. Make sure that the remote controller is set to the failure mode recall function. With the remote controller headed towards the indoor unit, press TOO COOL button to adjust the set temperature to 77 F (25 C) Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received. Does the upper lamp of the OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the upper lamp of the OPERATION INDICATOR lamp. 2 (OFF) (Blinks) The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the outdoor unit failure mode table ( ). Make sure to check at least 2 consecutive blinking cycles. 2 The outdoor unit is normal. Releasing the failure mode recall function Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller. Release the failure mode recall function according to the left mentioned procedure. Repair the failure parts. Deleting the memorized abnormal condition After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" ( ). Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above. NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized. 2.Blinking pattern when outdoor unit is abnormal: 2.5-second OFF 3-second ON Blinking at 0.5- second interval 2.5-second OFF 3-second ON Blinking at 0.5- second interval ON OFF beep Repeated cycle Beeps beep Repeated cycle Beeps Repeated cycle 41

42 3. Outdoor unit failure recall mode table The upper lamp of the OPERATION INDICATOR lamp (Indoor unit) Abnormal point (Failure mode/protection) LED indication (Outdoor P.C. board) Condition Remedy Indoor/outdoor unit failure mode recall function Outdoor unit failure mode recall function OFF ne (rmal) 1-time fl ash Indoor/outdoor Any signals from the inverter P.C. Refer to How 2.5 seconds OFF communication, receiving error board cannot be received normally for 3 minutes. to check miswiring and serial signal error. 2-time fl ash 2.5 seconds OFF 3-time fl ash 2.5 seconds OFF 4-time fl ash 2.5 seconds OFF 5-time fl ash 2.5 seconds OFF 6-time fl ash 2.5 seconds OFF 7-time fl ash 2.5 seconds OFF 8-time fl ash 2.5 seconds OFF 9-time fl ash 2.5 seconds OFF Indoor/outdoor communication, receiving error Outdoor power system Discharge temperature thermistor Defrost thermistor Fin temperature thermistor P.C. board temperature thermistor Ambient temperature thermistor Outdoor heat exchanger temperature thermistor Overcurrent Compressor synchronous abnormality (Compressor start-up failure protection) Discharge temperature High pressure Fin temperature/ P.C. board temperature Outdoor fan motor n-volatile memory data Power module (IC700) (MUZ-GL09/12/15/18, MUY- GL09/12/15/18) IGBT module (IC700) (MUZ-GL24, MUY-GL24) 1-time fl ash every 2.5 seconds 3-time fl ash 2.5 seconds OFF 4-time fl ash 2.5 seconds OFF 2-time fl ash 2.5 seconds OFF 11-time fl ash 2.5 seconds OFF 12-time fl ash 2.5 seconds OFF 7-time fl ash 2.5 seconds OFF 5-time fl ash 2.5 seconds OFF 6-time fl ash 2.5 seconds OFF Although the inverter P.C. board sends signal "0", signal "1" has been received 30 consecutive times. Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started. Thermistor shorts or opens during compressor running. Large current fl ows into the power module (IC700) (MUZ-GL09/12/15/18, MUY-GL09/12/15/18)/ IGBT module (IC700) (MUZ-GL24, MUY-GL24). Waveform of compressor current is distorted. Temperature of discharge temperature thermistor exceeds 241 F (116 C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212 F (100 C) or less 3 minutes later. Temperature indoor coil thermistor exceeds 158 F (70 C) in HEAT mode. Temperature defrost thermistor exceeds 158 F (70 C) in COOL mode. Temperature of the fin temperature thermistor on the inverter P.C. board exceeds F (75-86 C) (MUZ- GL09/12/15/18, MUY-GL09/12/15/18)/ F (75-80 C) (MUZ-GL24, MUY- GL24), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds F (72-85 C) (MUZ-GL09/12/15/18, MUY- GL09/12/15/18)/ F (70-75 C) (MUZ-GL24, MUY-GL24). Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up. n-volatile memory data cannot be read properly. The interface short circuit occurs in the output of the power module (IC700) (MUZ-GL09/12/15/18, MUY- GL09/12/15/18)/IGBT module (IC700) (MUZ-GL24, MUY-GL24). The compressor winding shorts circuit. Refer to How to check miswiring and serial signal error. Reconnect connectors. Refer to "How to check inverter/ compressor". Check stop valve. Refer to "Check of outdoor thermistors". Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED. Reconnect compressor connector. Refer to "How to check inverter/ compressor". Check stop valve. Reconnect compressor connector. Refer to "How to check inverter/ compressor". Check refrigerant circuit and refrigerant amount. Refer to "Check of LEV". Check refrigerant circuit and refrigerant amount. Check stop valve. Check around outdoor unit. Check outdoor unit air passage. Refer to "Check of outdoor fan motor". Refer to "Check of outdoor fan motor". Refer to "Check of inverter P.C. board". Replace the inverter P.C. board. Refer to "How to check inverter/ compressor". NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.). 42

43 The upper lamp of the OPERATION INDICATOR lamp (Indoor unit) 10-time fl ash 2.5 seconds OFF 11-time fl ash 2.5 seconds OFF 14-time fl ash or more 2.5 seconds OFF Abnormal point (Failure mode/protection) Discharge temperature DC voltage Each phase current of compressor Stop valve (Closed valve) 4-way valve/ Pipe temperature Outdoor refrigerant system abnormality LED indication (Outdoor P.C. board) 8-time fl ash 2.5 seconds OFF 9-time fl ash 2.5 seconds OFF 14-time fl ash 2.5 seconds OFF 16-time fl ash 2.5 seconds OFF 17-time fl ash 2.5 seconds OFF Condition Temperature of discharge temperature thermistor has been 122 F (50 C) or less for 20 minutes. DC voltage of inverter cannot be detected normally. Each phase current of compressor cannot be detected normally. Closed valve is detected by compressor current. The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature. Remedy Indoor/outdoor unit failure mode recall function Outdoor unit failure mode recall function Refer to "Check of LEV". Check refrigerant circuit and refrigerant amount. Refer to "How to check inverter/ compressor". Check stop valve. Check the 4-way valve. Replace the inverter P.C. board. A closed valve and air trapped in the Check for a gas leak refrigerant circuit are detected based in a connecting piping on the temperature sensed by the etc. indoor and outdoor thermistors and the Check the stop valve. current of the compressor. Refer to Check of outdoor refrigerant circuit. NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.). 43

44 10-3. TROUBLESHOOTING CHECK TABLE. Symptom LED indication Outdoor unit does not operate. 'Outdoor unit stops and restarts 3 minutes later' is repeated. 1-time fl ash every 2.5 seconds 6-time fl ash 2.5 seconds OFF 11-time fl ash 2.5 seconds OFF 16-time fl ash 2.5 seconds OFF 17-time fl ash 2.5 seconds OFF 2-time fl ash 2.5 seconds OFF 3-time fl ash 2.5 seconds OFF 4-time fl ash 2.5 seconds OFF 5-time fl ash 2.5 seconds OFF 8-time fl ash 2.5 seconds OFF 10-time fl ash 2.5 seconds OFF Abnormal point/ Condition Outdoor power system Condition Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started. Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor, defrost thermistor, P.C. board temperature thermistor, outdoor heat exchanger temperature thermistor or ambient temperature thermistor shorts or opens during compressor running. Outdoor control system nvolatile memory data cannot be read properly. (The upper lamp of the OPERATION INDICATOR lamp on the indoor unit lights up or fl ashes 7-time.) Serial signal The communication fails between the indoor and outdoor unit for 3 minutes. Stop valve/ Closed valve is detected by compressor current. Closed valve 4-way valve/ Pipe temperature Outdoor refrigerant system abnormality Overcurrent protection Discharge temperature overheat protection Fin temperature /P.C. board temperature thermistor overheat protection High pressure protection The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature. A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor. Large current fl ows into the power module (IC700) (MUZ- GL09/12/15/18, MUY-GL09/12/15/18)/ IGBT module (IC700) (MUZ-GL24, MUY-GL24). Remedy Reconnect connector of compressor. Refer to "How to check inverter/compressor". Check stop valve. Refer to "Check of outdoor thermistors". Replace inverter P.C. board. Refer to "How to check miswiring and serial signal error. Check stop valve. Refer to "Check of R.V. coil". Replace the inverter P.C. board. Check for a gas leak in a connecting piping etc. Check the stop valve. Refer to Check of outdoor refrigerant circuit. Reconnect connector of compressor. Refer to "How to check inverter/compressor". Check stop valve. Temperature of discharge temperature thermistor exceeds Check refrigerant circuit and refrigerant amount. 241 F (116 C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212 F (100 C) or less Refer to "Check of LEV". 3 minutes later. Temperature of the fin temperature thermistor on the heat sink Check around outdoor unit. exceeds F (75-86 C) (MUZ-GL09/12/15/18, MUY- Check outdoor unit air passage. GL09/12/15/18)/ F (75-80 C) (MUZ-GL24, MUY- Refer to "Check of outdoor GL24) or temperature of P.C. board temperature thermistor on fan motor". the inverter P.C.board exceeds F (72-85 C) (MUZ- GL09/12/15/18, MUY-GL09/12/15/18)/ F (70-75 C) (MUZ-GL24, MUY-GL24). Indoor coil thermistor exceeds 158 F (70 C) in HEAT mode. Defrost thermistor exceeds 158 F (70 C) in COOL mode. Compressor synchronous abnormal- The waveform of compressor current is distorted. ity Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up. 12-time fl ash Each phase current 2.5 seconds OFF of compressor 13-time fl ash 2.5 seconds OFF Check refrigerant circuit and refrigerant amount. Check stop valve. Reconnect connector of compressor. Refer to "How to check inverter/compressor". Refer to "Check of outdoor fan motor. Refer to "Check of inverter P.C. board. Refer to "How to check inverter/compressor". Each phase current of compressor cannot be detected normally. DC voltage DC voltage of inverter cannot be detected normally. It occurs with following case. Instantaneous power voltage drop. (Short time power failure) (MUZ- GL24, MUY-GL24) NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to LED is lighted during normal operation. 3. Blinking patterns of this mode differ from the ones of the failure recall mode. The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the fl ashing frequency is second ON 0.5-second ON Inverter P.C. board MUZ-GL09/12/15/18NA(H) MUY-GL09/12/15/18NA Flashing LED Refer to "Check of power supply". (MUZ-GL24, MUY-GL24) Refer to "How to check inverter/compressor". MUZ-GL24NA MUY-GL24NA Flashing LED ON OFF 2.5-second OFF 2.5-second OFF 44

45 . Symptom LED indication Outdoor unit operates. Outdoor unit operates. 1-time fl ash 2.5 seconds OFF 3-time fl ash 2.5 seconds OFF 4-time fl ash 2.5 seconds OFF MUZ-GL09/12/15/18 MUY-GL09/12/15/18 5-time fl ash 2.5 seconds OFF 7-time fl ash 2.5 seconds OFF 8-time fl ash 2.5 seconds OFF 9-time fl ash 2.5 seconds OFF Abnormal point/ Condition Frequency drop by current protection Frequency drop by high pressure protection Frequency drop by defrosting in COOL mode Frequency drop by discharge temperature protection Outside temperature thermistor protection Low discharge temperature protection MUZ-GL09/12/15/18 MUY-GL09/12/15/18 PAM protection PAM: Pulse Amplitude Modulation MUZ-GL24 MUY-GL24 Zero cross detecting circuit Inverter check mode MUZ-GL09/12/15/18 MUY-GL09/12/15/18 MUZ-GL24 MUY-GL24 Condition When the input current exceeds approximately 10.5A, compressor frequency lowers. Current from power outlet is nearing breaker capacity. Temperature of indoor coil thermistor exceeds 131 F (55 C) in HEAT mode, compressor frequency lowers. Indoor coil thermistor reads 46 F (8 C) or less in COOL mode, compressor frequency lowers. Temperature of discharge temperature thermistor exceeds 232 F (111 C), compressor frequency lowers. When the outside temperature thermistor shorts or opens, protective operation without that thermistor is performed. Temperature of discharge temperature thermistor has been 122 F (50 C) or less for 20 minutes. The overcurrent flows into PFC (Power factor correction :IC820) or the DC voltage reaches 394 V or more, PAM stops and restarts. Zero cross signal cannot be detected. NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to LED is lighted during normal operation. 3. Blinking patterns of this mode differ from the ones of the failure recall mode. The connector of compressor is disconnected, inverter check mode starts. Remedy The unit is normal, but check the following. Check if indoor fi lters are clogged. Check if refrigerant is short. Check if indoor/outdoor unit air circulation is short cycled. Check refrigerant circuit and refrigerant amount. Refer to "Check of LEV". Refer to "Check of outdoor thermistors". Refer to Check of outdoor thermistors. Refer to "Check of LEV". Check refrigerant circuit and refrigerant amount. This is not malfunction. PAM protection will be activated in the following cases: 1 Instantaneous power voltage drop. (Short time power failure) 2 When the power supply voltage is high. It occurs with following cases. 1 Instantaneous power voltage drop. (Short time power failure) 2 Distortion of primary voltage Refer to "Check of power supply". Check if the connector of the compressor is correctly connected. Refer to "How to check inverter/compressor". The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the fl ashing frequency is 2. Inverter P.C. board MUZ-GL09/12/15/18(H) MUY-GL09/12/15/18NA MUZ-GL24NA MUY-GL24NA ON OFF 2.5-second OFF 0.5-second ON 2.5-second OFF 0.5-second ON Flashing LED Flashing LED 45

46 10-4. TROUBLE CRITERION OF MAIN PARTS MUZ-GL09NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NA MUZ-GL15NAH MUY-GL15NA MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA MUZ-GL24NA MUY-GL24NA Part name Check method and criterion Figure Defrost thermistor (RT61) (MUZ) Fin temperature thermistor (RT64) Ambient temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68) Discharge temperature thermistor (RT62) Measure the resistance with a tester. Refer to Test point diagram and voltage, 1. Inverter P.C. board, for the chart of thermistor. Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up. Refer to Test point diagram and voltage, 1. Inverter P.C. board, for the chart of thermistor. Compressor Measure the resistance between terminals using a tester. [Temperature: F ( C)] rmal (Ω) U-V U-W V-W MUY-GL09 MUZ-GL09/12 MUY-GL12 MUZ-GL15/18 MUY-GL15/18 MUZ-GL24 MUY-GL WHT V RED BLK W U Outdoor fan motor Measure the resistance between lead wires using a tester. [Temperature: F ( C)] rmal (Ω) Color of lead wire RED BLK BLK WHT WHT RED MUZ-GL09/12/15 MUY-GL09/12/15 MUZ-GL18/24 MUY-GL18/ WHT V RED BLK W U R. V. coil (21S4) Measure the resistance using a tester. [Temperature: F ( C)] rmal (kω) Expansion valve coil (LEV) Measure the resistance using a tester. [Temperature: F ( C)] Color of lead wire rmal (Ω) RED ORN RED WHT RED BLU RED YLW WHT ORN RED (+12V) LEV YLW BLU Defrost heater (MUZ-GL NAH) Measure the resistance using a tester. [Temperature: F ( C)] rmal (Ω)

47 10-5. TROUBLESHOOTING FLOW A How to check inverter/compressor Disconnect the connector between the compressor and the power module (IC700) (MUZ-GL09/12/15/18, MUY-GL09/12/15/18)/IGBT module (IC700) (MUZ- GL24, MUY-GL24). Check the voltage between terminals. See Check of open phase. Are the voltages balanced? Replace the inverter P.C. board. Check the compressor. See Check of compressor. B Check of open phase With the connector between the compressor and the power module (IC700) (MUZ-GL09/12/15/18, MUY-GL09/12/15/18)/IGBT module (IC700) (MUZ-GL24, MUY-GL24) disconnected, activate the inverter and check if the inverter is normal by measuring the voltage balance between the terminals. Output voltage is V. (The voltage may differ according to the tester.) << Operation method>> Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA- TION: Refer to 7-6.) <<Measurement point>> At 3 points BLK (U)-WHT (V) Measure AC voltage between the lead wires at 3 points. BLK (U)-RED (W) WHT(V)-RED (W) NOTE: 1. Output voltage varies according to power supply voltage. 2. Measure the voltage by analog type tester. 3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to ) C Check of compressor Refer to Check of compressor winding. Is the compressor normal? Refer to Check of compressor operation time. Does the compressor operate continuously? OK Replace the compressor. Refer to Check of compressor start failure. 47

48 D Check of compressor winding Disconnect the connector between the compressor and the power module (IC700) (MUZ-GL09/12/15/18, MUY-GL09/12/15/18)/ IGBT module (IC700) (MUZ-GL24, MUY-GL24), and measure the resistance between the compressor terminals. <<Measurement point>> At 3 points BLK-WHT Measure the resistance between the lead wires at 3 points. BLK-RED WHT-RED <<Judgement>> Refer to [Ω] Abnormal [short] Infinite [Ω] Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement. E Check of compressor operation time Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to overcurrent. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 7-6.) <<Measurement>> Measure the time from the start of compressor to the stop of compressor due to overcurrent. F Check of compressor start failure <<Judgement>> 0 second 1 second 2 seconds 10 seconds 10 minutes Compressor starts Abnormal (IC700 failure) (Compressor winding short) Abnormal (Compressor lock out) (Starting defect) Abnormal (Poor contact) (Inverter P.C. board defect) (Disconnected connector) Abnormal (Refrigerant circuit defect) (Closed valve) rmal Confi rm that ~ is normal. Electrical circuit check. Contact of the compressor connector. Output voltage of inverter P.C. board and balance of them (See ). Direct current voltage between DB61(+) and (-) (MUZ-GL09/12/15/18, MUY-GL09/12/15/18)/JP715(+) and JP30(-) (MUZ-GL24, MUY-GL24) on the inverter P.C. board. Voltage between outdoor terminal block S1-S2 Does the compressor run for 10 seconds or more after it starts? Check the refrigerant circuit. Check the stop valve. After the compressor is heated with a drier, does the compressor start? 1 Compressor start failure. Activate pre-heat control. (Refer to 9-2. "PRE-HEAT CONTROL SETTING") Replace the compressor. 1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating. 48 Heating part

49 G Check of outdoor thermistors Disconnect the connector of thermistor in the inverter P.C. board (see below table), and measure the resistance of thermistor. Is the resistance of thermistor normal? (Refer to ) Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch. Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board. Does the unit operate for 10 minutes or more without showing thermistor abnormality? OK (Cause is poor contact.) Replace the inverter P.C. board. MUZ-GL09/12/15/18, MUY-GL09/12/15/18 Thermistor Symbol Connector, Pin. Board Defrost (MUZ) RT61 Between CN641 pin1 and pin2 Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Inverter P.C. board Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3 MUZ-GL24, MUY-GL24 Thermistor Symbol Connector, Pin. Board Defrost (MUZ) RT61 Between CN671 pin1 and pin2 Discharge temperature RT62 Between CN671 pin3 and pin4 Fin temperature RT64 Between CN673 pin1 and pin2 Inverter P.C. board Ambient temperature RT65 Between CN672 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN671 pin5 and pin6 49

50 H Check of R.V. coil (MUZ) MUZ-GL09/12/15/18NA MUZ-GL09/12/15/18NAH First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector although no signal is being transmitted to R.V. coil. Check if CN721 is connected. Unit operates COOL mode even if it is set to HEAT mode. Disconnect connector between the compressor and the power module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode). Is there 208/230 VAC between CN721 and on the inverter P.C. board 3 minutes after the power supply is turned ON? Replace the 4-way valve. Replace the inverter P.C. board. Unit operates HEAT mode even if it is set to COOL mode. Disconnect connector between the compressor and the power module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode). Is there 208/230 VAC between CN721 and on the inverter P.C. board 3 minutes after the power supply is turned ON? Replace the 4-way valve. Replace the inverter P.C. board. MUZ-GL24NA First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to In case CN602 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector although no signal is being transmitted to R.V. coil. Check if CN602 is connected. Unit operates COOL mode even if it is set to HEAT mode. Disconnect connector between the compressor and the IGBT module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode). Is there 208/230 VAC between CN602 and on the inverter P.C. board 3 minutes after the power supply is turned ON? Replace the 4-way valve. Replace the inverter P.C. board. Unit operates HEAT mode even if it is set to COOL mode. Disconnect connector between the compressor and the IGBT module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode). Is there 208/230 VAC between CN602 and on the inverter P.C. board 3 minutes after the power supply is turned ON? Replace the 4-way valve. Replace the inverter P.C. board. 50

51 I Check of outdoor fan motor Check the connection between the connector CN931 and CN932. Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Is the resistance between each terminal of outdoor fan motor normal? (Refer to 10-4.) Disconnect CN932 from the inverter P.C. board, and turn on the power supply. Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-) Replace the outdoor fan motor. (Fixed to either 5 or 0 VDC) Does the voltage between each terminal become 5 and 0 VDC repeatedly? Does the outdoor fan motor rotate smoothly? Replace the inverter P.C. board. 51

52 J Check of power supply Disconnect the connector between the compressor and the power module (IC700) (MUZ-GL09/12/15/18, MUY- GL09/12/15/18)/IGBT module (IC700) (MUZ-GL24, MUY-GL24). Turn ON power supply and press EMERGENCY OPERATION switch. Rectify indoor/outdoor connecting wire. Does the upper lamp of the OPERATION INDICATOR lamp on the indoor unit light up? Is there voltage 208/230 VAC between the indoor terminal block S1 and S2? Replace the indoor electronic control P.C. board. Is there DC voltage VDC between DB61 (+) and DB61 ( ) (MUZ-GL09/12/15/18, MUY- GL09/12/15/18)/ VDC between JP715 (+) and JP30 ( ) (MUZ-GL24, MUY-GL24) on the inverter P.C. board? (Refer to ) Does LED on the inverter P.C. board light up or fl ash? (Refer to ) Replace the inverter P.C. board. Check the electric parts in main circuit. If lights up, OK. If fl ashes, refer to VDC DB61 Inverter P.C. board (Solder side) MUZ-GL09/12/15/18NA MUZ-GL09/12/15/18NAH MUY-GL09/12/15/18NA VDC JP715 JP30 MUZ-GL24NA MUY-GL24NA 52

53 K Check of LEV (Expansion valve) Turn ON the power supply. <Preparation of the remote controller> While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button. Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then release the buttons. MSZ-GL06/09/12/15NA MSY-GL09/12/15NA MSZ-GL18NA MSY-GL18NA MSZ-GL24NA MSY-GL24NA Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 Expansion valve operates in full-opening direction. E.g.: MSZ type Do you hear the expansion valve "click, click "? Do you feel the expansion valve vibrates when touching it? OK 1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received. Is LEV coil properly fi xed to the expansion valve? Does the resistance of LEV coil have the characteristics? (Refer to 10-4.) Replace the LEV coil. Properly fi x the LEV coil to the expansion valve. Measure each voltage between connector pins of CN724 on the inverter P.C. board. 1. Pin (-) Pin (+) 2. Pin (-) Pin (+) 3. Pin (-) Pin (+) 4. Pin (-) Pin (+) Is there about 3-5 VAC between each? NOTE: Measure the voltage by an analog tester. Replace the inverter P.C. board. Replace the expansion valve. NOTE: After check of LEV, do the undermentioned operations. 1. Turn OFF the power supply and turn it ON again. 2. Press RESET button on the remote controller. 53

54 L Check of inverter P.C. board Check the outdoor fan motor. (Refer to ) Is the fuse (F901) blown on the inverter P.C. board? Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct. Operate the outdoor unit by starting EMERGENCY OPERATION. Check the LED indication on the inverter P.C. board. Does the LED flash 10 times? (10-time fl ash) Check the corresponding parts following LED indication. (Refer to 10-3.) Replace the inverter P.C. board. 54

55 M How to check miswiring and serial signal error MUZ-GL09/12/15NA MUZ-GL09/12/15NAH MUY-GL09/12/15NA Turn OFF the power supply. Is there rated voltage in the power supply? NOTE: Refer to the indoor unit service manual. Check the power supply. Turn ON the power supply. Is there rated voltage between the outdoor terminal block S1 and S2? Press EMERGENCY OPERATION switch once. Check the wiring. Does the left lamp of OPERATION INDICATOR lamp light up? <Confi rmation of the power to the indoor unit> Is serial signal error indicated 6 minutes later? Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire? Correct them. B A Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not miswiring. Bridge the outdoor terminal block S2 and S Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confi rm the wiring is correct before the operation starts. 3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board is normal, LED blinks 6 times after 3 minutes. Turn ON the power supply. Is the bus-bar voltage of the inverter P.C. board normal? (Refer to "TEST POINT DIAGRAM AND VOLTAGE" in the outdoor service manual.) Check of power supply. Does the LED on the inverter P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"? 3 Turn OFF the power supply. Remove the bridge between the outdoor terminal block S2 and S3. Turn ON the power supply. (Lighted or not lighted) Replace the inverter P.C. board Be careful of the residual voltage of smoothing capacitor. Is there rated voltage between the indoor terminal block S1 and S2? <Confi rmation of power voltage> Check the wiring If there are any error of the indoor/outdoor connecting wire: such as the damage of the wire, intermediate connection, and/or poor contact to the terminal block, replace the indoor/ outdoor connecting wire. A Turn OFF inverter-controlled lighting equipment. Turn OFF the power supply and then turn ON again. Press EMERGENCY OPERATION switch. Is serial signal error indicated 6 minutes later? B Is there amplitude of 10 to 20 VDC between the indoor terminal block S2 and S3? <Confi rmation of serial signal> Reinstall either the unit or the light away from each other. Attach a fi lter on remote control receiving section of the indoor unit. Is there 2 VDC or less between CN202 (+) and JPG (GND)(-) on the indoor electronic control P.C. board? Is there 2 VDC or less between Is there 2 VDC or less between CN202A (+) and JPG (GND)(-) CN202 (+) and JPG (GND)(-) on on the indoor electronic control P.C. the indoor electronic control P.C. board? board? Replace the indoor power P.C. board. 55 Replace the indoor electronic control P.C. board.

56 MUZ-GL18/24NA MUZ-GL18NAH MUY-GL18/24NA Turn OFF the power supply. NOTE: Refer to the indoor unit service manual. Is there rated voltage in the power supply? Turn ON the power supply. Check the power supply. Is there rated voltage between outdoor terminal block S1 and S2? Press EMERGENCY OPERATION switch once. Check the wiring. Does the OPERATION INDICATOR lamp light up? <Confi rmation of the power to the indoor unit> Is serial signal error indicated 6 minutes later? Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire? Correct them. B A Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not miswiring. Bridge the outdoor terminal block S2 and S3. 1 Turn ON the power supply. 1. Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confi rm the wiring is correct before the operation starts. 3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes. (Except for outdoor unit of multi system type) Is the bus-bar voltage of the inverter P.C. board or the outdoor electronic control P.C. board normal? (Refer to "TEST POINT DIAGRAM AND VOLTAGE" in the outdoor service manual.) Does the LED on the inverter P.C. board or the outdoor electronic control P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"? 3 Turn OFF the power supply. Remove the bridge between outdoor terminal block S2 and S3. GL18 Turn on the power supply. (Lighted or not lighted) Replace the inverter P.C. board or the outdoor electronic control P.C. board Be careful of the residual voltage of smoothing capacitor. GL24 Replace the indoor electronic control P.C. board. Turn OFF inverter-controlled lighting equipment. Turn OFF the power supply and then turn ON again. Press EMERGENCY OPERATION switch. Is serial signal error indicated 6 minutes later? B Is there amplitude of 10 to 20 VDC between the indoor terminal block S2 and S3? <Confi rmation of serial signal> A Reinstall either the unit or the light away from each other. Attach a fi lter on remote control receiving section of the indoor unit. Is there 2 VDC or less between CN10A (+) and GND (-) on the indoor electronic control P.C. board? Is there 2 VDC or less between Is there 2 VDC or less between CN10A (+) and GND (-) on CN10A (+) and GND (-) on the indoor electronic control P.C. board? the indoor electronic control P.C. board? Replace the indoor power P.C. board. Replace the indoor electronic control P.C. board. 56

57 N Check of defrost heater (MUZ-GL NAH) MUZ-GL09/12/15/18NAH Check the following points before checking electric continuity. 1. Does the resistance of ambient temperature thermistor have the characteristics? Refer to Is the resistance of defrost heater normal? Refer to Does the heater protector remain conducted (not open)? 4. Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors? In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 32 F (0 C) or below, and let the defrost thermistor continue to read 30 F (-1 C) or below. NOTE: In case both thermistors are more than the above temperature, cool them with cold water etc... Is there 208/230 VAC between CN722 and on the inverter P.C. board? Refer to t the problem of the inverter P.C. board. Replace the inverter P.C. board. O Check of outdoor refrigerant circuit Has the operation stopped during pump down? Was the operation started with the stop valve closed, and was it opened during operation? The unit occasionally stops when the stop valve is opened or closed during operation. Open the stop valve and start the cooling operation again. The operation has stopped to prevent the diesel explosion caused by air trapped in the refrigerant circuit. Close the stop valve, and disconnect the power plug or turn the breaker OFF. The refrigerant gas amount may be 60% or less than the normal amount. Identify where the gas is leaking from, and fi x the leak. CAUTION : Do not start the operation again to prevent hazards. 57

58 P Electromagnetic noise enters into TV sets or radios Is the unit grounded? Ground the unit. Is the distance between the antennas and the indoor unit within 9.91 ft. (3m), or is the distance between the antennas and the outdoor unit within 9.91 ft. (3m)? Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit. Is the distance between the TV sets or radios and the indoor unit within 3.28 ft. (1m), or is the distance between the TV sets or radios and the outdoor unit within 9.91 ft. (3m)? Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit. Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the antenna wiring? Replace or repair the antenna. Replace or repair the coaxial cable. Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close? Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas. Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service. 1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave) 2. Channel, frequency, broadcast station affected by the electromagnetic noise 3. Channel, frequency, broadcast station unaffected by the electromagnetic noise 4. Layout of: indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, ground wire, antennas, wiring from antennas, receiver 5. Electric field intensity of the broadcast station affected by the electromagnetic noise 6. Presence or absence of amplifi er such as booster 7. Operation condition of air conditioner when the electromagnetic noise enters in 1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise. 2) Within 3 minutes after turning ON the power supply, press STOP/OPERATE (OFF/ON) button on the remote controller for power ON, and check for the electromagnetic noise. 3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise. 4) Press STOP/OPERATE (OFF/ON) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise. 58

59 10-6. TEST POINT DIAGRAM AND VOLTAGE 1. Inverter P.C. board MUZ-GL09/12/15NA MUZ-GL09/12/15NAH MUY-GL09/12/15NA Smoothing capacitor (C63) DB VDC (-) (+) Back side of unit Smoothing capacitor (C62) R.V.coil Heater connector (CN721) (CN722) (MUZ) Smoothing (MUZ-GL09/ capacitor (C61) 208/230 VAC 12/15NAH) Fuse (F701) T3.15AL250V Fuse (F801) T3.15AL250V 208/230 VAC Fuse (F901) T3.15AL250V Output to drive outdoor fan motor (CN932) 208/230 VAC Jumper wire for preheat control setting (JK) LEV connector (CN724) Outdoor heat exchanger temperature thermistor /RT68 (CN644) Discharge temperature thermistor/rt62 (CN641) Defrost thermistor /RT61(CN641)(MUZ) Ambient temperature thermistor/rt65 (CN643) Front side of unit Signal of outdoor fan motor (CN931) LED Fin temperature thermistor/rt64 (CN642) Output to drive compressor (LDU, LDV, LDW) Defrost thermistor(rt61) Ambient temperature thermistor(rt65) Outdoor heat exchanger temperature thermistor(rt68) Temperature( F) HVLVWDQFH N 5HVLVWDQFH N 5HVLVWDQFH N Temperature ( F) 59 Fin temperature thermistor(rt64) 160 Discharge temperature thermistor (RT62) Jumper wire for changing defrost setting (JS) Temperature( F)

60 MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA Back side of unit Smoothing capacitor (C63) Smoothing capacitor (C62) DB VDC (-) (+) R.V.coil (CN721) (MUZ) 208/230 VAC Heater connector (CN722) (MUZ-GL18NAH) Fuse (F701) T3.15AL250V Smoothing capacitor (C61) Fuse (F801) T3.15AL250V 208/230 VAC Fuse (F901) T3.15AL250V Output to drive outdoor fan motor (CN932) 208/230 VAC Output to drive compressor (LDU, LDV, LDW) Jumper wire for changing defrost setting (JS) LEV connector (CN724) Outdoor heat exchanger temperature thermistor /RT68 (CN644) Discharge temperature thermistor/rt62 (CN641) Defrost thermistor /RT61(CN641) (MUZ) Ambient temperature thermistor/rt65 (CN643) Signal of outdoor fan motor (CN931) Front side of unit Fin temperature thermistor/rt64 (CN642) LED Defrost thermistor(rt61) Ambient temperature thermistor(rt65) Outdoor heat exchanger temperature thermistor(rt68) Temperature( F) HVLVWDQFH N 5HVLVWDQFH N 5HVLVWDQFH N Temperature ( F) 60 Fin temperature thermistor(rt64) 160 Discharge temperature thermistor (RT62) Jumper wire for pre-heat control setting (JK) Temperature( F)

61 MUZ-GL24NA MUY-GL24NA Fuse (F601) T3.15AL250V R.V. coil (CN602) 208/230 VAC (MUZ) Signal of outdoor fan motor (CN931) LEV connector (CN724) Fuse (F901) T3.15AL250V Output to drive outdoor fan motor (CN932) Fuse (F880) T3.15AL250V JP715 (+) VDC JP30 (-) LED Defrost thermistor /RT61 (CN671) (MUZ) Discharge temperature thermistor/rt62 (CN671) Outdoor heat exchanger temperature thermistor /RT68 (CN671) Ambient temperature thermistor/rt65 (CN672) Fin temperature thermistor/rt64 (CN673) Jumper wire for changing defrost setting (JS) Jumper wire for pre-heat control setting (JK) Resistance(k ) Defrost thermistor(rt61) (MUZ) Ambient temperature thermistor(rt65) Outdoor heat exchanger temperature thermistor(rt68) Temperature( F) Discharge temperature thermistor (RT62) Temperature ( F) 61 Resistance(k ) Fin temperature thermistor(rt64) Temperature( F)

62 11 DISASSEMBLY INSTRUCTIONS <"Terminal with locking mechanism" Detaching points> The terminal which has the locking mechanism can be detached as shown below. There are 2 types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching. (1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism. Sleeve Locking lever Slide the sleeve. Pull the terminal while pushing the locking lever MUZ-GL09NA MUZ-GL09NAH MUY-GL09NA MUZ-GL12NA MUZ-GL12NAH MUY-GL12NA MUZ-GL15NA MUZ-GL15NAH MUY-GL15NA NOTE: Turn OFF the power supply before disassembly. OPERATING PROCEDURE PHOTOS 1. Removing the cabinet (1) Remove the screw fixing the service panel. (2) Pull down the service panel and remove it. (3) Remove the screws fixing the conduit cover. (4) Remove the conduit cover. (Photo 4) (5) Remove the screw fixing the conduit plate. (Photo 5) (6) Remove the conduit plate. (7) Disconnect the power supply wire and indoor/outdoor connecting wire. (8) Remove the screws fixing the top panel. (9) Remove the top panel. (10) Remove the screws fixing the cabinet. (11) Remove the cabinet. (12) Remove the screws fixing the back panel. (13) Remove the back panel. Photo 1 Connector Hold the sleeve, and pull out the terminal slowly. Screws of the top panel Back panel Screws of the back panel Photo 2 Screws of the top panel Photo 3 Screws of the cabinet Screw of the cabinet Service panel Screws of the terminal block support and the back panel Direction to remove Screws of the cabinet Screws of the cabinet Hooks 62

63 OPERATING PROCEDURE Photo 4 Photo 5 Screws of the conduit cover PHOTOS Screw of the conduit plate 2. Removing the inverter assembly, inverter P.C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN721 (R.V. coil) (MUZ) CN722 (Defrost heater and heater protector) (MUZ- GL09/12/15NAH) CN931, CN932 (Fan motor) CN641 (Defrost thermistor (MUZ) and discharge temperature thermistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV) (3) Remove the compressor connector (CN61). (4) Remove the screws fixing the heat sink support and the separator. (5) Remove the fixing screws of the terminal block support and the back panel. (6) Remove the inverter assembly. (7) Remove the screw of the ground wire and screw of the terminal block support. (8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and remove the inverter P.C. board from the P.C. board support. 3. Removing R.V. coil (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board> CN721 (R.V. coil) (MUZ) (3) Remove the R.V. coil. Photo 6 Screws of the heat sink support and the separator Photo 7 Heat sink Heat sink support P.C. board support Screws of the terminal block support and the back panel Screw of the Terminal block support Terminal block support 63 Screw of the inverter P.C. board Screw of the ground wire

64 OPERATING PROCEDURE 4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN641 (Defrost thermistor (MUZ) and discharge temperature thermistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) (3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor from its holder. (6) Pull out the ambient temperature thermistor from its holder. Photo 8 PHOTOS Screw of the R.V. coil (MUZ) Discharge temperature thermistor Photo 9 Ambient temperature thermistor Outdoor heat exchanger temperature thermistor Defrost thermistor (MUZ) 64

65 OPERATING PROCEDURE 5. Removing outdoor fan motor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board> CN931, CN932 (Fan motor) (3) Remove the propeller fan nut. (4) Remove the propeller fan. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor. NOTE: The propeller fan nut is a revers thread. Photo 10 PHOTOS Screws of the outdoor fan motor Propeller fan Propeller fan nut 6. Removing the compressor and 4-way valve (1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Remove the screws fixing the reactor. (4) Remove the reactor. (5) Remove the soundproof felt. (6) Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 PSIG. (7) Detach the brazed part of the suction and the discharge pipe connected with compressor. (8) Remove the nuts fixing the compressor. (9) Remove the compressor. (10) Detach the brazed part of pipes connected with 4-way valve. Photo 11 Screws of the reactor Photo 12 Soundproof felt Suction pipe brazed part Discharge pipe brazed part Brazed parts of 4-way valve 65

66 11-2. MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA NOTE: Turn OFF the power supply before disassembly. OPERATING PROCEDURE PHOTOS 1. Removing the cabinet (1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the screws fixing the conduit cover. (6) Remove the conduit cover. (7) Remove the screw of fixing the conduit plate. (8) Remove the conduit plate. (9) Remove the top panel. (10) Remove the valve cover. (11) Disconnect the power supply and indoor/outdoor connecting wire. (12) Remove the screws of the cabinet. (13) Remove the cabinet. (14) Remove the screws of the back panel. (15) Remove the back panel. Photo 1 Screws of the cabinet Screws of the top panel Photo 3 Screws of the conduit cover Screws of the cabinet Screws of the cabinet Photo 2 Screw of the back panel Screws of the cabinet Screws of the top panel Screw of the valve cover Photo 4 Screw of the conduit plate Screws of the back panel Screws of the cabinet Screws of the service panel 66

67 OPERATING PROCEDURE 2. Removing the inverter assembly, inverter P.C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN721 (R.V. coil) (MUZ) CN722 (Defrost heater) (MUZ-GL18NAH) CN931, CN932 (Fan motor) CN641 (Defrost thermistor (MUZ) and discharge temperature thermistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV) (3) Remove the compressor connector. (4) Remove the screw fixing the heat sink support and the separator. (5) Remove the fixing screws of the terminal block support and the back panel. (6) Remove the inverter assembly. (7) Remove the screw of the ground wire, screw of the P.C. board cover and screws of the terminal block support. (8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and the inverter P.C. board from the P.C. board support. 3. Removing R.V. coil (MUZ) (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connector: <Inverter P.C. board> CN721 (R.V. coil) (MUZ) (3) Remove the R.V. coil. Photo 7 Photo 5 Screw of the heat sink support and the separator Photo 6 P.C. board support Screw of the inverter P.C. board Heat sink PHOTOS Heat sink support Screws of the terminal block support and the back panel Screw of the P.C. board cover Screw of the R.V. coil (MUZ) Screw of the ground wire Screws of the terminal block support Brazed parts of 4-way valve 67

68 OPERATING PROCEDURE PHOTOS 4. Removing the discharge temperature thermistor, defrost thermistor (MUZ), outdoor heat exchanger temperature thermistor and ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN641 (Defrost thermistor (MUZ) and discharge temperature thermistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) (3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor from its holder. (6) Pull out the ambient temperature thermistor from its holder. Photo 8 Outdoor heat exchanger temperature thermistor Ambient temperature thermistor 5. Removing outdoor fan motor (1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board> CN931 and CN932 (Fan motor) (3) Remove the propeller fan nut. (4) Remove the propeller fan. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor. NOTE: The propeller fan nut is a revers thread. Photo 9 Defrost thermistor (MUZ) Propeller fan nut 6. Removing the compressor and 4-way valve (1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 PSIG. (5) Detach the brazed part of the suction and the discharge pipe connected with compressor. (6) Remove the compressor nuts. (7) Remove the compressor. (8) Detach the brazed part of 4-way valve and pipe. (Photo 7) Photo 10 Brazed part of the discharge pipe Screws of the outdoor fan motor Discharge temperature thermistor Brazed part of the suction pipe 68

69 11-3. MUZ-GL24NA MUY-GL24NA OPERATING PROCEDURE 1. Removing the cabinet (1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the screws fixing the conduit cover. (6) Remove the conduit cover. (7) Remove the top panel. (8) Remove the valve cover. (9) Disconnect the power supply and indoor/outdoor connecting wire. (10) Remove the screws of the cabinet. (11) Remove the cabinet. (12) Remove the screws of the back panel. (13) Remove the back panel. Photo 1 NOTE: Turn OFF the power supply before disassembly. Screws of the cabinet PHOTOS Screws of the top panel Photo 2 Screws of the back panel Screws of the top panel Screws of the back panel Screws of the back panel Photo 3 Screws of the cabinet Screws of the conduit cover Screws of the cabinet Photo 4 Screw of the conduit plate Screws of the cabinet Screws of the back panel Screws of the back panel Screws of the service panel Screw of the valve cover 69

70 OPERATING PROCEDURE PHOTOS 2. Removing the inverter assembly, inverter P.C. board and relay P.C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN602 (R.V. coil) (MUZ) CN931, CN932 (Fan motor) CN671 (Defrost thermistor (MUZ), discharge temperature thermistor and outdoor heat exchanger temperature thermistor) CN672 (Ambient temperature thermistor) CN724 (LEV) Photo 5 Inverter P.C. board Screw of the relay panel Ground wires Screws of the P.B. support (3) Remove the compressor connector. (4) Remove the screws fixing the relay panel. (5) Remove the relay panel. (6) Remove the ground wires and the lead wires of the inverter P.C. board. (7) Remove the screws of the P.B. support. (8) Remove the inverter P.C. board from the P.B. support. Screws of the P.B. support Screw of the relay panel Screw of the relay panel 3. Removing R.V. coil (MUZ) (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connector: <Inverter P.C. board> CN602 (R.V. coil) (MUZ) (3) Remove the R.V. coil. Photo 6 Screw of the R.V. coil (MUZ) Brazed parts of 4-way valve 70

71 OPERATING PROCEDURE PHOTOS 4. Removing the discharge temperature thermistor, defrost thermistor (MUZ), outdoor heat exchanger temperature thermistor and ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN671 (Defrost thermistor (MUZ), discharge temperature thermistor and outdoor heart exchanger temperature thermistor) CN672 (Ambient temperature thermistor) (3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor from its holder. (6) Pull out the ambient temperature thermistor from its holder. Photo 7 Outdoor heat exchanger temperature thermistor Ambient temperature thermistor 5. Removing outdoor fan motor (1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board> CN931 and CN932 (Fan motor) (3) Remove the propeller. (4) Remove the screws fixing the fan motor. (5) Remove the fan motor. NOTE: The propeller fan nut is a revers thread. Photo 8 Defrost thermistor (MUZ) Screws of the outdoor fan motor 6. Removing the compressor and 4-way valve (1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 PSIG. (5) Detach the brazed part of the suction and the discharge pipes connected with compressor. (6) Remove the compressor nuts. (7) Remove the compressor. (8) Detach the brazed parts of 4-way valve and pipes. (Photo 6) Photo 9 Brazed part of the discharge pipe Discharge temperature thermistor Brazed part of the suction pipe 71

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC Revision A: MUZ-HM09/12NA- U8, MUZ-HM09/12NA2- U8, MUZ-HM15/18NA- U1, MUZ-HM15/18NA2- U1 and MUZ-HM24NA2- U1 have been added. Please void OBH747. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A.

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH Revision D: Capacity corrections have been corrected [7-1. 2), 3)]. OBH684 REVISED EDITION-C is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH684 REVISED EDITION-D Models MUZ-FH06NA MUZ-FH09NA

More information

SERVICE MANUAL MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-F.

SERVICE MANUAL MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-F. Revision F: The descriptions of the expansion valve coil have been corrected. (10-4.) Some descriptions have been modified. Please void OBH543 REVISED EDITION-E. OUTDOOR UNIT SERVICE MANUAL HFC utilized

More information

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A Revision E: Capacity corrections have been corrected [7-1. 2), 3)]. OBH502 REVISED EDITION-D is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH502 REVISED EDITION-E Models MUZ-D30NA / - 1 / -

More information

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 Indoor unit service manual MSZ-DM VA Series (OBH750) CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES

More information

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH502 Wireless type Models MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA Indoor unit service manual MSZ-D NA Series (OBH501) MSY-D

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA OUTDOOR UNIT. No. OBH543. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA OUTDOOR UNIT. No. OBH543. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 Models MUZ-FE09NA MUZ-FE12NA Indoor unit service manual MSZ-FE NA Series (OBH542) CONTENTS 1. TECHNICAL CHANGES 2 2. PART

More information

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467. SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-HC35VA- E2 and MUZ-HC35VAB- E2 have been added. Please void OBH467 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH467 REVISED EDITION-B

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC Revision E: MUZ-FH25VE- E4, ER4, ET3, MUZ- FH35VE- E3, ER3, ET3 and MUZ- FH50VE- E2, ER2, ET2 have been added. Please void OBH624 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624

More information

SERVICE MANUAL MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA - U1 MSZ-GL18NA - U1 MSZ-GL24NA - U1

SERVICE MANUAL MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA - U1 MSZ-GL18NA - U1 MSZ-GL24NA - U1 Revision B: 3. SPECIFICATION has been corrected. Please void OBH732 REVISED EDITION-A. INDOOR UNIT SERVICE MANUAL. OBH732 REVISED EDITION-B Models MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA

More information

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E Revision E: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH629 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-E Models

More information

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC Revision F: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH590 REVISED EDITION-E. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED EDITION-F

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629.

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-A Models MUZ-SF25VE - E1 MUZ-SF42VE

More information

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Models HFC

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Models HFC Revision G: Errors in TROUBLESHOOTING have been corrected. Please void OB455 REVISED EDITION-F. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB455 REVISED EDITION-G Models MUZ-GB50VA - E1 MUZ-GB50VA

More information

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2 Revision F: "How to check miswiring and serial signal error" has been corrected (11-5. M ). OBH648 REVISED EDITION-E is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH648 REVISED EDITION-F Models

More information

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1 SPLIT-TYPE AIR CONDITIONERS Revision D: Changing defrost finish temperature has been corrected (10-1.). Please void OBH516 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED

More information

1 TECHNICAL CHANGES. MUZ-A09NA MUZ-A09NA - 1 MUZ-A09NA - U1 MUZ-A09NA - U2 1. Refrigerant system diagram has been changed.

1 TECHNICAL CHANGES. MUZ-A09NA MUZ-A09NA - 1 MUZ-A09NA - U1 MUZ-A09NA - U2 1. Refrigerant system diagram has been changed. 1 TECHNICAL CHANGES MUZ09UN MUZ-A09NA MUZ12UN MUZ-A12NA MUH15TN MUZ-A15NA MUH17TN MUZ-A17NA MUH24WN MUZ-A24NA MU15TN MUY-A15NA MU17TN MUY-A17NA MU24WN MUY-A24NA 1. Outdoor unit model has been changed.

More information

MUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service manual MSZ-EF VE Series (OBH589)

MUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service manual MSZ-EF VE Series (OBH589) SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 Models MUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service

More information

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Wireless type Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Wireless type Models HFC. Revision E: REVISED EDITION-E R410A Revision E: MUZ-GB50VA- E3 has been added. Please void OB455 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB455 REVISED EDITION-E Wireless type Models MUZ-GB50VA - E1 MUZ-GB50VA -

More information

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1 SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH

More information

1. INDOOR UNITS... MSZ-FH-3 2. OUTDOOR UNITS... MSZ-FH-4 3. SYSTEM... MSZ-FH-5

1. INDOOR UNITS... MSZ-FH-3 2. OUTDOOR UNITS... MSZ-FH-4 3. SYSTEM... MSZ-FH-5 M-SERIES SINGLE ZONE SYSTEMS MSZ-FH High Performance Wall-Mount Heat Pump Systems 1. INDOOR UNITS... MSZ-FH-3 2. OUTDOOR UNITS... MSZ-FH-4 3. SYSTEM... MSZ-FH-5 3-1. SPECIFICATIONS... MSZ-FH-6 MSZ-FH09NA

More information

MSZ-GE06NA- 8, 9 MSZ-GE09NA- 8, 9 MSZ-GE12NA- 8, 9 MSZ-GE15NA- 8, 9 MSZ-GE18NA- 8, 9

MSZ-GE06NA- 8, 9 MSZ-GE09NA- 8, 9 MSZ-GE12NA- 8, 9 MSZ-GE15NA- 8, 9 MSZ-GE18NA- 8, 9 SPLIT-TYPE AIR CONDITIONERS Revision D: MSZ-GE06/09/12/15/18NA- 9 and MSY- GE09/12/15/18NA- 9 have been added. Please void OBH548 REVISED EDITION-C INDOOR UNIT SERVICE MANUAL. OBH548 REVISED EDITION-D

More information

SERVICE MANUAL MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA INDOOR UNIT. No. OBH746 REVISED EDITION-B. Models

SERVICE MANUAL MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA INDOOR UNIT. No. OBH746 REVISED EDITION-B. Models Revision B: 3-1. OPERATING RANGE has been modified. Please void OBH746 REVISED EDITION-A. INDOOR UNIT SERVICE MANUAL. OBH746 REVISED EDITION-B Models MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH530 Models MU-GE50VB- E1 - E1 Indoor unit service manual MS/MSH-GE VB Series (OBH529) CONTENTS 1. TECHNICAL CHANGES 2 2. PART

More information

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 MSZ-GE60VA - E1 MSZ-GE71VA - E1 INDOOR UNIT. No.

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 MSZ-GE60VA - E1 MSZ-GE71VA - E1 INDOOR UNIT. No. SPLIT-TYPE AIR CONDITIONERS Revision E: Detail of the indoor fan speed control in COOL or DRY operation has been added (9-1.3, 9-2.3). Please void OBH515 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL.

More information

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE MSZ-FH25VE2 MSZ-FH35VE2 MSZ-FH50VE2 INDOOR UNIT. No. OBH623. Models

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE MSZ-FH25VE2 MSZ-FH35VE2 MSZ-FH50VE2 INDOOR UNIT. No. OBH623. Models Revision D: MSZ-FH25VE2- E1, ER1, MSZ- FH35VE2- E1, ER1 and MSZ- FH50VE2- E1, ER1 have been added. Please void OBH623 REVISED EDITION-C. INDOOR UNIT SERVICE MANUAL. OBH623 REVISED EDITION-D Models MSZ-FH25VE

More information

SERVICE MANUAL INDOOR UNIT. No. OBH788

SERVICE MANUAL INDOOR UNIT. No. OBH788 INDOOR UNIT SERVICE MANUAL. Models MSZ-AP25VG - E1, EN1 MSZ-AP35VG - E1, EN1 MSZ-AP42VG - E1, EN1 MSZ-AP50VG - E1, EN1 MSZ-AP25VGK - E1, EN1 MSZ-AP35VGK - E1, EN1 MSZ-AP42VGK - E1, EN1 MSZ-AP50VGK - E1,

More information

SERVICE MANUAL INDOOR UNIT

SERVICE MANUAL INDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision A: MSZ-SF25/35/42/50VE- E2 and MSZ-SF25/35/ 42/50VE- EN2 have been added. Please void OBH600. INDOOR UNIT SERVICE MANUAL. OBH600 REVISED EDITION-A Models MSZ-SF25VE

More information

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy SPLIT-TYPE AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL. OBH589 Models MSZ-EF22VEW - MSZ-EF22VEW - E1 MSZ-EF25VEW - E1 MSZ-EF22VEB - E1 MSZ-EF35VEW - E1 MSZ-EF22VES E1 - MSZ-EF42VEW - E1 MSZ-EF25VEW - E1

More information

SERVICE MANUAL MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA INDOOR UNIT. No. OBH501. Wireless type Models

SERVICE MANUAL MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA INDOOR UNIT. No. OBH501. Wireless type Models INDOOR UNIT SERVICE MANUAL. OBH501 Wireless type Models MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA CONTENTS Outdoor unit service manual MUZ-D NA Series (OBH502) MUY-D NA Series (OBH502) 1. TECHNICAL CHANGES

More information

SERVICE MANUAL MSZ-DM25VA - E1, ER1 MSZ-DM35VA - E1, ER1 INDOOR UNIT. No. OBH750. Models

SERVICE MANUAL MSZ-DM25VA - E1, ER1 MSZ-DM35VA - E1, ER1 INDOOR UNIT. No. OBH750. Models INDOOR UNIT SERVICE MANUAL. Models MSZ-DM25VA - E1, ER1 MSZ-DM35VA - E1, ER1 Outdoor unit service manual MUZ-DM VA Series (OBH751) MXZ-DM VA Series (OBH739) MSZ-DM25VA MSZ-DM35VA CONTENTS 1. TECHNICAL

More information

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E SPLIT-TYPE AIR CONDITIONERS Revision E: MFZ-KA5VA- E5, MFZ-KA35VA- E5 and MFZ-KA50VA- E5 have been added. Please void OB409 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OB409 REVISED EDITION-E Models

More information

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE INDOOR UNIT. No. OBH623. Models SPLIT-TYPE AIR CONDITIONERS

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE INDOOR UNIT. No. OBH623. Models SPLIT-TYPE AIR CONDITIONERS SPLIT-TYPE AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL. Models MSZ-FH25VE MSZ-FH35VE - E1 - E1 Outdoor unit service manual MUZ-FH VEHZ Series (OBH625) MUZ-FH VE Series MXZ-D VA Series CONTENTS 1. TECHNICAL

More information

SERVICE MANUAL MUZ-GB50VA - MUZ-GB50VA - E2 OUTDOOR UNIT. No. OB455 REVISED EDITION-D. Wireless type Models HFC

SERVICE MANUAL MUZ-GB50VA - MUZ-GB50VA - E2 OUTDOOR UNIT. No. OB455 REVISED EDITION-D. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Revision D: RoHS PARTS LIST has been changed. Please void OB455 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A. OB455 REVISED EDITION-D Wireless

More information

SERVICE MANUAL MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG OUTDOOR UNIT. No. OBH767. Models HFC R32

SERVICE MANUAL MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG OUTDOOR UNIT. No. OBH767. Models HFC R32 OUTDOOR UNIT SERVICE MANUAL HFC utilized R32. Models MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG - E1, ER1, ET1 - E1, ER1, ET1 - E1, ER1, ET1 - E1, ER1, ET1 Indoor unit service manual MSZ-LN VGW/V/B/R

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH789

SERVICE MANUAL OUTDOOR UNIT. No. OBH789 OUTDOOR UNIT SERVICE MANUAL HFC utilized R32. Models MUZ-AP25VG - E1, ET1 MUZ-AP25VGH - E1 MUZ-AP35VG - E1, ET1 MUZ-AP35VGH - E1 MUZ-AP42VG - E1, ET1 MUZ-AP42VGH - E1 MUZ-AP50VG - E1, ET1 MUZ-AP50VGH -

More information

Revision C: Specification has been corrected. The value of "Moisture removal" for MSZ-GE24NA and MSY-GE24NA has been corrected. [2.7 pt.

Revision C: Specification has been corrected. The value of Moisture removal for MSZ-GE24NA and MSY-GE24NA has been corrected. [2.7 pt. Use the speciþed refrigerant only Never use any refrigerant other than that specified. Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant

More information

SERVICE MANUAL MFZ-KA25VA - MFZ-KA35VA - MFZ-KA35VA - E1. Wireless type Models FLOOR-TYPE, HEAT PUMP AIR CONDITIONERS. No.

SERVICE MANUAL MFZ-KA25VA - MFZ-KA35VA - MFZ-KA35VA - E1. Wireless type Models FLOOR-TYPE, HEAT PUMP AIR CONDITIONERS. No. FLOOR-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models MFZ-KAVA - MFZ-KA3VA - E E. OB409 MFZ-KA0VA - E Indication of model name MFZ-KAVA - E MFZ-KA3VA - E MFZ-KA0VA - E NOTE: This service

More information

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System Submittal Data: Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES

More information

Submittal Data: VIR12HP230V1B. Job Name Location Date. Submitted To

Submittal Data: VIR12HP230V1B. Job Name Location Date. Submitted To Submittal Data: Innovative Ductless solutions 12,000 BTU/H (208/230V) Wall Mounted Heat Pump System Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES

More information

Submittal Data: VIR09HP115V1B Job Name Location Date. Submitted To. Innovative Ductless solutions 9,000 BTU/H (115V) Wall Mounted Heat Pump System

Submittal Data: VIR09HP115V1B Job Name Location Date. Submitted To. Innovative Ductless solutions 9,000 BTU/H (115V) Wall Mounted Heat Pump System Submittal Data: Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES -Compact and Quiet Design -High Efficiency DC Inverter Technology -Wireless Remote

More information

SERVICE MANUAL MS-GF20VA MS-GF25VA MS-GF35VA MS-GF50VA MS-GF60VA MS-GF80VA INDOOR UNIT. No. OBH621 REVISED EDITION-A. Models

SERVICE MANUAL MS-GF20VA MS-GF25VA MS-GF35VA MS-GF50VA MS-GF60VA MS-GF80VA INDOOR UNIT. No. OBH621 REVISED EDITION-A. Models SPLIT-TYPE AIR CONDITIONERS Revision A: MS-GF50VA- E1, MS-GF60VA- E1 and MS-GF80VA- E1 have been added. Please void OBH621. INDOOR UNIT SERVICE MANUAL. OBH621 REVISED EDITION-A Models MS-GF20VA MS-GF25VA

More information

Submittal Data: VIR24HP230V1B. Job Name Location Date. Submitted To

Submittal Data: VIR24HP230V1B. Job Name Location Date. Submitted To Submittal Data: Innovative Ductless solutions 24,000 BTU/H (208/230V) Wall Mounted Heat Pump System Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG18KLCA ASYG24KLCA OUTDOOR AOYG18KLTA AOYG24KLTA DR_AS069EF_01 2018.03.16 Notices: Product specifications and design are subject to

More information

SERVICE MANUAL MLZ-KA25VA - MLZ-KA35VA - MLZ-KA50VA - E1 INDOOR UNIT. No. OBH483. Ceiling cassette type Models

SERVICE MANUAL MLZ-KA25VA - MLZ-KA35VA - MLZ-KA50VA - E1 INDOOR UNIT. No. OBH483. Ceiling cassette type Models CEILING CASSETTE TYPE, HEAT PUMP AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL. OBH483 Ceiling cassette type Models E1 MLZ-KA25VA - E1 MLZ-KA35VA - MLZ-KA50VA - E1 Outdoor unit service manual MXZ-A VA Series

More information

SERVICE MANUAL MSZ-HC25VA - E1 MSZ-HC35VA - E1 MSZ-HC35VA - E2 MSZ-HC35VAB - E1 MSZ-HC35VAB - E2 INDOOR UNIT. No. OBH466. Models

SERVICE MANUAL MSZ-HC25VA - E1 MSZ-HC35VA - E1 MSZ-HC35VA - E2 MSZ-HC35VAB - E1 MSZ-HC35VAB - E2 INDOOR UNIT. No. OBH466. Models SPLIT-TYPE AIR CONDITIONERS Revision B: MSZ-HC35VA- E2 and MSZ-HC35VAB- E2 have been added. Please void OBH466 REVISED EDITION-A. INDOOR UNIT SERVICE MANUAL. OBH466 REVISED EDITION-B Models MSZ-HC25VA

More information

Power Input (Max) 1,500 W Dehumidification 1.7 pt/hr HSPF 10.5 COP 4.2 Compressor Type DC Inverter Driven 2-Stage Rotary Heating at 17 F FLA 8.

Power Input (Max) 1,500 W Dehumidification 1.7 pt/hr HSPF 10.5 COP 4.2 Compressor Type DC Inverter Driven 2-Stage Rotary Heating at 17 F FLA 8. Submittal Data: CROWN09HP230V1B Superior Performance in Extreme Temperature 9,000 BTU/H Wall Mounted Heat- Pump System Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR ASU9RL2 ASU12RL2 OUTDOOR AOU9RL2 AOU12RL2 1.INDOOR UNIT : ASU9RL2 ASU12RL2 DTR_AS072E_01 2012.11.02 1. INDOOR UNIT CONTENTS 1. FEATURE...

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL For Extra Cold Climate Area INDOOR ASU18RLF ASU24RLF OUTDOOR AOU18RLXFWH AOU24RLXFWH DR_AS014EF_04 2017.03.10 Notices: Product specifications

More information

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy MUZ-GA35VAH - E1

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy MUZ-GA35VAH - E1 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MUZ-GA5VA - E MUZ-GA35VA - E MUZ-GA5VAH - MUZ-GA35VAH - E HFC utilized R40A. OB379 Indication of model name MUZ-GA5VA - E MUZ-GA35VA

More information

SUBMITTAL DATA: MSY-GL12NA & MUY-GL12NA 12,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM. System Reference:

SUBMITTAL DATA: MSY-GL12NA & MUY-GL12NA 12,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM. System Reference: M-SERIES SUBMITTAL DATA: MSY-GL12NA & MUY-GL12NA 12,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM Job Name: System Reference: Date: Indoor Unit: MSY-GL12NA Outdoor Unit: MUY-GL12NA Wireless Remote Controller

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LLCC AS G09LLCC AS G12LLCC OUTDOOR AO G07LLCC AO G09LLCC AO G12LLCC 1.INDOOR UNIT : AS G07LLCC AS G09LLCC AS G12LLCC DTR_AS087E_02

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 19,100 BTU/h,200 BTU/h 30,600 BTU/h Outdoor Model No. CU-3KE19NBU CU-4KE24NBU

More information

SUBMITTAL DATA: MSY-GL24NA & MUY-GL24NA 24,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM. System Reference:

SUBMITTAL DATA: MSY-GL24NA & MUY-GL24NA 24,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM. System Reference: M-SERIES SUBMITTAL DATA: MSY-GL24NA & MUY-GL24NA 24,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM Job Name: System Reference: Date: Indoor Unit: MSY-GL24NA Outdoor Unit: MUY-GL24NA Wireless Remote Controller

More information

SUBMITTAL DATA: MSZ-FH06NA & MUZ-FH06NA 6,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM. Electrical Power Requirements. Indoor / Outdoor A 1 / 11

SUBMITTAL DATA: MSZ-FH06NA & MUZ-FH06NA 6,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM. Electrical Power Requirements. Indoor / Outdoor A 1 / 11 M-SERIES SUBMITTAL DATA: MSZ-FH0NA & MUZ-FH0NA,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM Job Name: System Reference: Date: Electrical Power Requirements 08 / 30V, -Phase, 0 Hz ACCESSORIES: Unit Unit: MSZ-FH0NA

More information

SERVICE MANUAL MLZ-KP25VF MLZ-KP35VF MLZ-KP50VF INDOOR UNIT. No. OBH801. Models

SERVICE MANUAL MLZ-KP25VF MLZ-KP35VF MLZ-KP50VF INDOOR UNIT. No. OBH801. Models INDOOR UNIT SERVICE MANUAL. Models MLZ-KP25VF MLZ-KP35VF MLZ-KP50VF - E1, ER1 - E1, ER1 - E1, ER1 Outdoor unit service manual MXZ-D VA Series (OBH626) MXZ-E VA Series (OBH723) MXZ-F VF Series (OBH790)

More information

SUZ-KA25VA2.TH SUZ-KA35VA2.TH SUZ-KA50VA2.TH SUZ-KA60VA2.TH SUZ-KA71VA2.TH

SUZ-KA25VA2.TH SUZ-KA35VA2.TH SUZ-KA50VA2.TH SUZ-KA60VA2.TH SUZ-KA71VA2.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS September 2011.OCH472 REVISED EDITION-A TECHNICAL & SERVICE MANUAL R410A Outdoor unit [Model names] SUZ-KA25VA2 SUZ-KA35VA2 SUZ-KA50VA2 SUZ-KA60VA2 SUZ-KA71VA2 [Service

More information

TECHNICAL & SERVICE MANUAL SUZ-SA71VA.TH. R410A Outdoor unit SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. May 2014 HFC. No.OCH561 R410A CONTENTS

TECHNICAL & SERVICE MANUAL SUZ-SA71VA.TH. R410A Outdoor unit SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. May 2014 HFC. No.OCH561 R410A CONTENTS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS May 2014. TECHNICAL & SERVICE MANUAL R410A Outdoor unit [Model Name] SUZ-SA71VA [Service Ref.] HFC utilized R410A te: This service manual describes technical data

More information

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1. Wireless type Models HFC FLOOR AND CEILING TYPE AIR CONDITIONERS. No.

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1. Wireless type Models HFC FLOOR AND CEILING TYPE AIR CONDITIONERS. No. FLOOR AND CEILING TYPE AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MUCFH-GA35VB - E MUCFH-GA50VB - MUCFH-GA60VB - E HFC utilized R40A. OB38 CONTENTS Indication of model name MUCFH-GA50VB - E.

More information

SUZ-SA71VA3.TH SUZ-SA100VA2.TH

SUZ-SA71VA3.TH SUZ-SA100VA2.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL R410A Outdoor unit [Model Name] SUZ-SA71VA3 SUZ-SA100VA2 [Service Ref.] SUZ-SA71VA3.TH SUZ-SA100VA2.TH January 2018. HFC utilized R410A

More information

Air Conditioner CONTENTS

Air Conditioner CONTENTS ORDER NO. MAC0509068C2 Air Conditioner CS-F24DD1E5 CU-B24DBE5 CS-F28DD1E5 CU-B28DBE5 CS-F28DD1E5 CU-B28DBE8 CS-F34DD1E5 CU-B34DBE5 CS-F34DD1E5 CU-B34DBE8 CS-F43DD1E5 CU-B43DBE8 CS-F50DD1E5 CU-B50DBE8 CONTENTS

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE OUTDOOR AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE DR_AS037EF_01 2016.12.05 Notices: Product

More information

15A 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

15A 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C) Innovative Ductless Mini Split Solution Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES -Multi-Speed Fan -Medium Static Pressure Capability -Return

More information

Submittal Data: UMAT48HP230V1AF. Job Name Location Date. Submitted To

Submittal Data: UMAT48HP230V1AF. Job Name Location Date. Submitted To Innovative Ductless Mini Split Solution Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES -Multi-Speed Fan -4-way Discharge Air -Swing Louvers -Wireless

More information

15A Operating Range Communication Wire Size 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

15A Operating Range Communication Wire Size 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C) Innovative Ductless Mini Split Solution Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES -Multi-Speed Fan -4-way Discharge Air -Swing Louvers -Wireless

More information

13 SEER HEAT PUMPS. Featuring Earth-Friendly R-410A Refrigerant 13PJL SERIES. Features Coils constructed with copper tubing and enhanced aluminum

13 SEER HEAT PUMPS. Featuring Earth-Friendly R-410A Refrigerant 13PJL SERIES. Features Coils constructed with copper tubing and enhanced aluminum FORM NO. P11-774 REV. 3 Supersedes Form No. P11-774 Rev. 2 Featuring Earth-Friendly R-410A Refrigerant earth friendly refrigerant 13PJL SERIES 13 SEER HEAT PUMPS Features Coils constructed with copper

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL KS1872 + C1872 + CL1872 KS2472 + C2472 + CL2472 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KS1872 KS2472 Product

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Duct type DESIGN & TECHNICAL MANUAL INDOOR ARU9RLF ARU12RLF ARU18RLF OUTDOOR AOU9RLFC AOU12RLFC AOU18RLFC 1. INDOOR UNIT : ARU9RLF ARU12RLF ARU18RLF DTR_AR059E_01 2013.02.28 1. INDOOR UNIT

More information

18-2 AWG / 300V THHN Operating Range MCA 2.0A Cooling (Max) 118 F (48 C) MOCP/Breaker Size 15A (Min) 0 F (-18 C)

18-2 AWG / 300V THHN Operating Range MCA 2.0A Cooling (Max) 118 F (48 C) MOCP/Breaker Size 15A (Min) 0 F (-18 C) Innovative Ductless Mini Split Solution Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES -Multi-Speed Fan -4-way Discharge Air -Internal Condensate

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CLM97 CLM7 CLM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No.

More information

SERVICE MANUAL MUH-GA50VB - MUH-GA60VB - MUH-GA80VB - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. OB368 R410A CONTENTS

SERVICE MANUAL MUH-GA50VB - MUH-GA60VB - MUH-GA80VB - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. OB368 R410A CONTENTS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MUH-GA50VB - E MUH-GA60VB - MUH-GA80VB - E HFC utilized R40A. OB368 CONTENTS Indication of model name MUH-GA50VB - E. TECHNICAL

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL XHS1271 & PNR-XS1872 + CH1271 XHS1872 & PNR-XS1872 + CH1872 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) XHS1271

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LMCA AS G09LMCA AS G12LMCA AS G14LMCA OUTDOOR AO G07LMCA AO G09LMCA AO G12LMCA AO G14LMCA 1. INDOOR UNIT : AS G07LMCA AS G09LMCA

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KE30NKU + CU-KE30NKU CS-KE36NKU + CU-KE36NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KE30NKU CS-KE36NKU Product Code No. 1 852 360 88

More information

Innovative Ductless Mini Split Solution Submittal Data: GUHD24ND3FO/GKH24D3FI Job Name Location Date

Innovative Ductless Mini Split Solution Submittal Data: GUHD24ND3FO/GKH24D3FI Job Name Location Date Innovative Ductless Mini Split Solution Submittal Data: GUHD24ND3FO/GKH24D3FI 24,000 BTUH 24,000 Ceiling BTU/H Cassette Ceiling Heat Casse3e Pump Heat System Pump System Job Name Location Date Purchaser

More information

SERVICE MANUAL. Inverter Wall Mounted Single Split. MODELS Cooling Only. Heatpump SM-5WM-Y-NA-B1

SERVICE MANUAL. Inverter Wall Mounted Single Split. MODELS Cooling Only. Heatpump SM-5WM-Y-NA-B1 SERVICE MANUAL Inverter Wall Mounted Single Split MODELS Cooling Only FTKB09AXVJU FTKB12AXVJU FTKB18AXVJU FTKB24AXVJU FTKN09AXVJU FTKN12AXVJU FTKN18AXVJU FTKN24AXVJU Heatpump FTXB09AXVJU FTXB12AXVJU FTXB18AXVJU

More information

TECHNICAL & SERVICE MANUAL. Ceiling Concealed

TECHNICAL & SERVICE MANUAL. Ceiling Concealed STAND BY DEFROST CHECK CLOCK ON OFF NOT AVAILABLE FILTER CHECK MODE TEST RUN FUNCTION SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL Series SEZ Ceiling Concealed R40A.OC0 REVISED EDITION-A

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA OUTDOOR AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA DR_AS049EF_02 2017.10.11 Notices: Product

More information

13 SEER CONDENSING UNITS

13 SEER CONDENSING UNITS FORM NO. A11-182 REV. 8 Supersedes Form No. A11-182 Rev. 7 13 SEER CONDENSING UNITS Features Painted louvered steel cabinet. Easily accessible control box. Condenser coils constructed with copper tubing

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL No. OCH468 REVISED EDITI-A HFC utilized R4A June 2 [Model name] MXZ-8B48NA PAC-AKA5BC PAC-AKA3BC (Indispensable

More information

SERVICE MANUAL MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 INDOOR UNIT. No. OBH529. Models

SERVICE MANUAL MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 INDOOR UNIT. No. OBH529. Models SPLIT-TYPE AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL. OBH529 Models MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 service manual MU-GA VB Series (OB386) MUH-GA VB Series

More information

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM EFFICIENT UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase REFRIGERATION CIRCUIT S 2- stage scroll compressors

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Duct type DESIGN & TECHNICAL MANUAL INDOOR ARU9RLF ARU12RLF ARU18RLF OUTDOOR AOU9RLFC AOU12RLFC AOU18RLFC 1. INDOOR UNIT : ARU9RLF ARU12RLF ARU18RLF DTR_AR059E_05 2015.06.01 1. INDOOR UNIT

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A09LEC AS A12LEC OUTDOOR AO R09LECN AO R12LECN 1.INDOOR UNIT : AS A09LEC AS A12LEC DTR_AS047E_01 2010.10.05 1. INDOOR UNIT CONTENTS

More information

Part 3 Troubleshooting

Part 3 Troubleshooting Part Troubleshooting What is in this part? This part contains the following chapters: Chapter See page Troubleshooting 2 Error Codes: Hydro-box 7 Error Codes: Outdoor Units Error Codes: System Malfunctions

More information

TZPL SERIES. Applications Thermal Zone remote heat pumps offer comfort and dependability for single, multi-family and light commercial applications.

TZPL SERIES. Applications Thermal Zone remote heat pumps offer comfort and dependability for single, multi-family and light commercial applications. FORM NO. PTZ-786 Supersedes Form No. PTZ-765 Rev. 2 TZPL SERIES Manufactured for Thermal Zone Philadelphia, PA 13 SEER HEAT PUMPS Features Coils constructed with copper tubing and enhanced aluminum fins.

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G09LTCB AS G12LTCB AS G14LTCB OUTDOOR AO G09LTCN AO G12LTCN AO G14LTCN 1. INDOOR UNIT : AS G09LTCB AS G12LTCB AS G14LTCB DTR_AS057E_01

More information

CS-E18NKUA CS-E24NKUA CU-E18NKUA CU-E24NKUA TABLE OF CONTENTS WARNING

CS-E18NKUA CS-E24NKUA CU-E18NKUA CU-E24NKUA TABLE OF CONTENTS WARNING Order No: PAPAMY1204088CE Indoor Unit CS-E18NKUA CS-E24NKUA Outdoor Unit CU-E18NKUA CU-E24NKUA WARNING This service information is designed for experienced repair technicians only and is not designed for

More information

Single Zone Air Conditioner SVC MANUAL (Exploded View)

Single Zone Air Conditioner SVC MANUAL (Exploded View) Single Zone Air Conditioner SVC MANUAL (Exploded View) CAUTION Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel. MODEL: MR36UY3J 960-920-10

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL XS171 & PNRXS187 + C171 XS171 & PNRXS187 + CL171 XS187 & PNRXS187 + CH187 XS187 & PNRXS187 + CL187 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER

More information

Air Conditioners. Technical Data RZQG-L

Air Conditioners. Technical Data RZQG-L Air Conditioners Technical Data O u t d o o r u n i t s o p t i m i z e d f o r s e a s o n a l e f f i c i e n c y w w w. d a i k i n. e u RZQG-L Air Conditioners Technical Data O u t d o o r u n i t

More information

TECHNICAL GUIDE MODELS: DCPM/DHPM PREMIUM SERIES DUCTLESS SINGLE-SPLIT AIR CONDITIONERS AND HEAT PUMPS 22 SEER 1 PHASE 3/4 THRU 3 NOMINAL TONS

TECHNICAL GUIDE MODELS: DCPM/DHPM PREMIUM SERIES DUCTLESS SINGLE-SPLIT AIR CONDITIONERS AND HEAT PUMPS 22 SEER 1 PHASE 3/4 THRU 3 NOMINAL TONS TECHNICAL GUIDE PREMIUM SERIES DUCTLESS SINGLE-SPLIT AIR CONDITIONERS AND HEAT PUMPS 22 SEER 1 PHASE 3/4 THRU 3 NOMINAL TONS MODELS: DCPM/DHPM Due to continuous product improvement, specifications are

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR ASU18RLF ASU24RLF OUTDOOR AOU18RLXFW AOU24RLXFW 1. INDOOR UNIT : ASU18RLF ASU24RLF DTR_AS51E_1 21.12.22 1. INDOOR UNIT CONTENTS 1. FEATURE...

More information

PAJ3. Product Specifications

PAJ3. Product Specifications 13 SEER, R 410A PACKAGE AIR CONDITIONER FOR MANUFACTURED HOUSING, RESIDENTIAL, AND LIGHT COMMERCIAL APPLICATIONS 2 5 TONS Single Phase, 208/230 V, 60 Hz BUILT TO LAST, EASY TO INSTALL AND SERVICE Compact,

More information

Samsung 360 Cassette, Single Zone, Split System

Samsung 360 Cassette, Single Zone, Split System Job Name Purchaser Submitted to Unit Designation Location Engineer Reference Schedule # Approval Page 1 of 5 Construction Specifications Model Indoor Unit Model Number Outdoor Unit Model Number Nominal

More information

TAC-09CS/K TAC-12CS/K TAC-18CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-12CHS/K TAC-18CHS/K TAC-24CHS/K

TAC-09CS/K TAC-12CS/K TAC-18CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-12CHS/K TAC-18CHS/K TAC-24CHS/K TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE040427 Models TAC-07CS/K TAC-09CS/K TAC-2CS/K TAC-8CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-2CHS/K TAC-8CHS/K TAC-24CHS/K CONTENTS. IMPORTANT

More information

16 SEER TWO-STAGE AIR CONDITIONERS

16 SEER TWO-STAGE AIR CONDITIONERS FORM NO. ATZ-210 Supersedes Form No. ATZ-210 16 SEER TWO-STAGE AIR CONDITIONERS Features Outdoor air conditioner designed for ground level or rooftop installations. These units offer comfort and dependability

More information

Product Data INDUSTRY LEADING FEATURES / BENEFITS

Product Data INDUSTRY LEADING FEATURES / BENEFITS 8MGR Multi-zone Outdoor Unit Ductless System Sizes 18, 24, 0, 6 and 48 Fig. 1 18K Fig. 2 24K and 0K Product Data INDUSTRY LEADING FEATURES / BENEFITS A competitively priced and creative solution to design

More information