Refrigeration/Troubleshooting Manual

Size: px
Start display at page:

Download "Refrigeration/Troubleshooting Manual"

Transcription

1 Refrigeration/Troubleshooting Manual P.O. Box 245 Syracuse, NY P/N: Table of Contents: Section 1: Geothermal Refrigeration Circuits Overview... 2 Water-to-Air Refrigerant Circuit... 3 Refrig. Ckt. Component Operation... 3 Water-to-Water Refrigerant Circuit... 5 Heating Operation... 6 Cooling Operation... 6 Summary... 8 Guide Revision Table: Date By Page Note KT All First published Section 2: Heat of Extraction/Heat of Rejection Overview... 9 Performance Data... 9 Formulas Examples Section 3: Superheat/Subcooling Overview Definitions Checking Superheat and Subcooling Putting It All Together Pressure/Temperature Chart R-410A Pressure/Temperature Chart R Superheat/Subcooling Measurements Superheat/Subcooling Tables Examples Section 4: Desuperheater Operation Overview Desuperheater Cut-Away Appendix A: Troubleshooting Form

2 Section 1: Geothermal Refrigeration Circuits Overview Geothermal heat pumps are available in a variety of configurations to provide flexibility for installation in new construction or retrofit applications. Most common in North America are packaged water-to-air heat pumps, which provide forced air heating and cooling. Packaged units (see figure 1) have the compressor section and the air handler section in the same cabinet. There are also other types of geothermal heat pumps, such as water-to-water, which are used for radiant floor heating. exchanger (water-to-water and waterto-air units) is connected to the ground loop or open loop (well water) system. The load heat exchanger is connected to the hydronic load (for example, radiant floor heating) for water-to-water units. The load heat exchanger in a water-to-air unit is the air coil, which is connected to duct work. Water-to-water heat pumps heat or chill water instead of heating or cooling the air (see figure 5). The difference between a water-to-air and water-to-water heat pump is the load heat exchanger. A second water-to-refrigerant coil is substituted for the air to refrigerant coil. The source heat Figure 1: Water-to-Air Refrigeration Circuit Condenser (heating) Evaporator (cooling) 5 To suction line Heating Cooling Optional desuperheater installed in discharge line (always disconnect during troubleshooting) 1 3 Condenser (cooling) Evaporator (heating) 2 Refrigeration/Troubleshooting Guide,

3 Section 1: Geothermal Refrigeration Circuits Water-to-Air Refrigerant Circuit The water-to-air geothermal heat pump refrigerant circuit is very simple compared to air source heat pumps. Defrost cycle is not required, and all components are indoors in a single cabinet. The main components shown in figure 1 are the compressor (1), the air coil (2), the coaxial heat exchanger (3), the reversing valve (4), the or thermal expansion valve (5), and the filter drier (6). Compressor: The compressor (1) is the heart of the system. The compressor pumps refrigerant through the circuit, and increases the pressure of the refrigerant. Since pressure and temperature are directly related, when the pressure is increased, the temperature is also increased. When the temperature of the refrigerant is raised to a higher temperature than the temperature of the air flowing through the air coil (2) in heating, heat is released to the air to heat the building. Likewise, when the refrigerant temperature is raised to a higher temperature than the water flowing through the coaxial heat exchanger (3) in cooling, heat is released to the water. uses Copeland Scroll compressors. A scroll is an involute spiral which, when matched with a mating spiral scroll form as shown in figure 2, generates a series of crescent-shaped gas pockets between the two members. Scroll compressors work by moving one spiral element inside another stationary spiral to create a series of gas pockets that become smaller and increase the pressure of the gas. The largest openings are at the outside of the scroll where the gas enters on the suction side. As these gas pockets are closed off by the moving spiral they move towards the center of the spirals and become smaller and smaller. This increases the pressure on the gas until it reaches the center of the spiral and is discharged through a port near the center of the scroll. Both the suction process (outer portion of the scroll members) and the discharge process (inner portion) are continuous. The moving scroll moves in an orbiting path within the stationary (fixed) scroll as it creates the series of gas pockets. During compression, several pockets are being compressed simultaneously, resulting in Figure 2: Scroll Operation Compression in the scroll is created by the interaction of an orbiting spiral and a stationary spiral. Gas enters the outer openings as one of the spirals orbits. The open passages are sealed off as gas is drawn into the spiral. As the spiral continues to orbit, the gas is compressed into two increasingly smaller pockets. By the time the gas arrives at the center port, discharge pressure has been reached. Actually, during operation, all six gas passages are in various stages of compression at all times, resulting in nearly continuous suction and discharge. Refrigeration/Troubleshooting Guide 3

4 Section 1: Geothermal Refrigeration Circuits a very smooth process. By maintaining an even number (six in a Copeland Scroll compressor) of balanced gas pockets on opposite sides, the compression forces inside the scroll work to balance each other and reduce vibration inside the compressor. Single speed and two-stage (UltraTech) scroll compressors are used in s product line. The two-stage scroll works exactly like the single speed scroll shown in figure 2, but it has additional components, a solenoid valve, and bypass ports in the scroll mechanism. When the solenoid valve opens the bypass ports as shown in figure 3, the capacity is reduced to 67%, since part of the scroll is bypassed. Figure 3: UltraTech Operation 67% - Ports Open 100% Ports Closed : The air coil (2), a refrigerant-to-air heat exchanger servers as the condenser in heating, and the evaporator in cooling. ial Heat Exchanger: The coaxial heat exchanger (3), a water-to-refrigerant heat exchanger, serves as the evaporator in heating, and the condenser in cooling. pump to switch from heating to cooling. The normal (non-energized) mode is heating. Therefore, the discharge gas from the compressor flows to the air coil in the non-energized mode. When the reversing valve solenoid is energized in cooling, the valve switches to allow the discharge gas from the compressor to flow to the coaxial heat exchanger. The reversing valve is a pilot-operated valve, which means that the solenoid opens a small port, connecting the copper tubing from the bottom port (discharge line from the compressor) to the valve chamber. The high pressure of the discharge line forces the valve to switch from one mode to the other. Thermal Expansion (): The (5) meters refrigerant to make sure that the proper amount of refrigerant is being fed to the heat exchangers in order to maximize the condensing and evaporating functions. The is also important in keeping liquid refrigerant from reaching the suction line of the compressor, which could damage the compressor. The is designed to operate bi-directionally in packaged water-to-air and water-to-water heat pumps. Figure 4: Operation Diaphram : The reversing valve (4) provides the ability to switch functions of the two heat exchangers, above. As shown in figure 1, the discharge line from the compressor is always connected to the bottom of the reversing valve. The center connection at the top is always connected to the suction line from the compressor. The other two connections allow the heat Seat Pin 4 4 = Liquid Pressure (opening force) 4 Refrigeration/Troubleshooting Guide,

5 Section 1: Geothermal Refrigeration Circuits Figure 4 shows the operation of the, and the four forces that affect the operation. The has two copper fittings for connection to the air coil and coaxial heat exchanger, as well as two smaller copper lines that are used for metering. One line is connected to a bulb that is attached to the suction line of the compressor. The bulb is filled with refrigerant. As the suction line temperature changes, the bulb pressure changes. The other line is connected directly to the suction line. The bulb pressure (force 1) pushes down on the diaphragm as the bulb pressure increases (suction line temperature increases). When the pressure pushes down on the diaphragm, the pin (which is attached to the diaphragm) is pushed away from the valve seat, which opens the valve. The other line, connected directly to the suction line uses suction pressure (force 2) to push up on the diaphragm as the pressure increases. As the diaphragm is pushed up, the pin is pushed into the valve seat, closing the valve. This relationship of temperature (bulb pressure) and pressure (suction line) creates a balancing effect, which causes the valve to meter at 0 superheat (see section 3 for explanation of superheat). Since it is important to make sure that liquid is not returning to the compressor, the valve spring (force 3) is adjusted to fool the valve into balancing at a higher superheat (usually 10 to 12). Force 4 (liquid pressure) is an opening force. : The filter drier (6) functions exactly as its name implies. It filters any particles from the refrigerant system, and it pulls moisture from the system. It is extremely important that the filter drier is changed any time the refrigerant circuit is open for a component replacement or repair, especially for systems with R-410A refrigerant. R-410A uses P.O.E. oil, which is hygroscopic (tendency of a material to absorb moisture from the air). Moisture contaminates the refrigerant circuit over time, and must be avoided. Figure 5: Water-to-Water Refrigerant Circuit Condenser (heating) Evaporator (cooling) To suction line Load Heating Load Load Cooling Optional desuperheater installed in discharge line (always disconnect during troubleshooting) Condenser (cooling) Evaporator (heating) Refrigeration/Troubleshooting Guide 5

6 Section 1: Geothermal Refrigeration Circuits Water-to-Water Refrigerant Circuit The water-to-water heat pump refrigerant circuit, as shown in figure 5, functions exactly the same as the the water-to-air refrigerant circuit with one exception. The air coil is replaced by a second coaxial heat exchanger. The source coax is the same as the water-to-air unit coax. However, the load coax heats or chills water instead of heating or cooling the air. Heating Operation For the purposes of discussing the refrigerant circuit operation in heating and cooling modes, the water-to-air circuit will be used. The other configurations directly apply with minor terminology/component changes. In heating mode (see figure 7), the reversing valve is not energized. The high temperature, high pressure refrigerant gas from the compressor flows to the air coil. As the air moves through the air coil, the cool (typically 70) air causes the hot refrigerant (typically 130 to 180) to condense into a liquid. Thus, the air coil is the condenser in the heating mode. After leaving the air coil (condenser), the refrigerant is approximately the temperature of the leaving air. The refrigerant is within a few of being at the same pressure as it was at the compressor discharge line. This is the heating liquid line. The liquid line of a packaged unit changes location, depending upon the mode of operation. It is always located between the and the condenser. However, since a geothermal unit is a heat pump, the condenser can either be the air coil (heating) or coaxial water coil (cooling). At the, the refrigerant is forced through a very small opening, which causes a large pressure drop. As mentioned earlier, pressure and temperature are directly related, so the temperature also drops after the. At this point, the refrigerant is a low temperature liquid (typically 15 to 50, depending upon loop temperature). The warm water (or water/antifreeze solution) flowing through the coaxial heat exchanger (typically 30 to 60) causes the cold refrigerant to boil off (evaporate) into a gas or vapor. Thus, the coax is the evaporator in heating. After leaving the coax (evaporator), the refrigerant is now approximately the same temperature as the water entering the heat pump. This low pressure gas enters the compressor, and the cycle starts all over again. Proper refrigerant metering will insure that no liquid is returned to the compressor. Section 3 discusses superheat and subcooling, which allow the technician to evaluate how well the condenser and evaporator are operating. Cooling Operation In cooling mode (see figure 8), the reversing valve must be energized. The high temperature, high pressure refrigerant gas from the compressor flows to the coaxial heat exchanger. As the water (or water/ antifreeze solution) flows through the coax, the cool (typically 50 to 100) water causes the hot refrigerant (typically 130 to 180) to condense into a liquid. Thus, the coax is the condenser in the cooling mode. After leaving the coax (condenser), the refrigerant is approximately the temperature of the water leaving the coax. The refrigerant is within a few of the compressor discharge line pressure. This is the cooling liquid line. The liquid line of a packaged unit changes location, 6 Refrigeration/Troubleshooting Guide,

7 Section 1: Geothermal Refrigeration Circuits Figure 7: Heating Condenser (heating) Evaporator (cooling) To suction line Optional desuperheater installed in discharge line (always disconnect during troubleshooting) Condenser (cooling) Evaporator (heating) Figure 8: Cooling Condenser (heating) Evaporator (cooling) To suction line Optional desuperheater installed in discharge line (always disconnect during troubleshooting) Condenser (cooling) Evaporator (heating) Refrigeration/Troubleshooting Guide 7

8 Section 1: Geothermal Refrigeration Circuits depending upon the mode of operation. It is always located between the and the condenser. However, since a geothermal unit is a heat pump, the condenser can either be the air coil (heating) or coaxial water coil (cooling). condenser in cooling and the evaporator in heating. Water-to-water units use a second coax instead of the air coil. The reversing valve is energized in the cooling mode. The non-energized mode is heating. At the, the refrigerant is forced through a very small opening, which causes a large pressure drop. Once again, since pressure and temperature are directly related, the temperature also drops after the. At this point, the refrigerant is a low temperature liquid (typically 35 to 45, depending upon return air temperature and air flow). The warm air flowing through the air coil (typically 70 to 80) causes the cold refrigerant to boil off (evaporate) into a gas or vapor. Thus, the air coil is the evaporator in cooling. After leaving the air coil (evaporator), the refrigerant is now approximately the same temperature as the air entering the heat pump. This low pressure gas enters the compressor, and the cycle starts all over again. Summary To summarize, refrigerant circuits in geothermal heat pumps can be configured for packaged water-to-air, water-to-water, split systems or combination water-to-air and water-to-water units. All circuits utilize a Copeland scroll (single or two-stage) compressor, one or two water-to-refrigerant coaxial coils, an air-to-refrigerant coil, a reversing valve, a bi-directional, and a filter drier. Combination units include a direction valve and a 3-way valve to switch condenser operation. The air coil operates as the condenser in heating, and the evaporator in cooling. The source (loop) coax operates as the 8 Refrigeration/Troubleshooting Guide,

9 Section 2: Heat of Extraction/Heat of Rejection Overview As mentioned in section 1, most geothermal heat pumps are packaged water-to-air heat pumps. Therefore, the refrigerant circuit is evacuated and charged at the factory, and there is no need to connect refrigerant gauges unless the technician has verified that there is a refrigerant circuit problem. Since connecting gauges can cause a loss of charge and affect performance, recommends against connecting refrigerant gauges at startup. There are a number of checks that can be made at startup to verify performance without connecting refrigerant gauges. Heat of extraction is a calculation of the amount of heat that is being extracted or absorbed from the water or water/antifreeze solution by the evaporator (coaxial heat exchanger) in the heating mode. Heat of rejection is the amount of heat that is being rejected to the water by the condenser (coaxial heat exchanger) in the cooling mode. In addition to measuring the temperature rise or drop across the air coil, calculating heat of extraction or heat of rejection allows the technician to verify that the heat pump is performing according to specifications. If the calculation shows that the heat pump is performing poorly, then refrigeration gauges may be required to further troubleshoot the problem. Performance Data Before discussing heat of extraction (HE) / heat of rejection (HR) calculations, the technician should understand how to use the performance data in the catalog to compare the unit specifications to actual calculations. Figures 9 and 10 show performance data for a typical 3 ton geothermal water-toair heat pump. the highlighted columns indicate HE and HR. In figure 9, HE is the amount of heat that is being extracted from the water (for example, ground loop) by the refrigerant circuit. The compressor and fan power (kw column) is used to operate the refrigerant circuit. The heat delivered to the space (HC column) equals the HE from the water plus the waste heat of the power used for compressor and fan. If the kw is converted to Btuh, and added to the HE, the sum should equal HC. For example, in figure 9, at 30 EWT, 9.0 and 70 EAT, the heating capacity is 30,700 Btuh. HE is 21,800 Btuh. If the kw (2.63) is converted to Btuh (2.63 x = 8.97 MBtuh or 8,970 Btuh), and added to HE, the result is HC. Therefore, if HE is within, 10-15% of catalog performance, HC should also be within specifications. There is no need to connect refrigerant gauges if HE is within specifications. In figure 10, HR is the amount of heat that is being rejected to the water (for example, ground loop) by the refrigerant circuit. The compressor and fan power (kw column) is used to operate the refrigerant circuit. The heat rejected from the space (HR column) equals the heat from the air (TC column -- amount of cooling) plus the waste heat of the power used for compressor and fan. If the kw is converted to Btuh, and added to the TC, the sum should equal HR. For example, in figure 10, at 90 EWT, 9.0 and 75 DB/63 WB (50% RH), HR is 43,400 Btuh. TC is 34,400 Btuh. If the kw (2.73) is converted to Btuh (2.73 x = 9.31 MBtuh or 9310 Btuh), and added to TC, the result is HR. Thefore, if HR is within, 10-15% of catalog performance, TC should also be within specifications. There is no need to connect refrigerant gauges if HR is within specifications. Refrigeration/Troubleshooting Guide 9

10 Formulas The formula is the same for HE and HR. The amount of heat being extracted or rejected can be calculated if the temperature difference between water entering and leaving the coaxial heat exchanger (TD) is known, and the water flow () is measured. The only other item needed is the type of antifreeze. A fluid factor is used to represent the specific heat of the water/antifreeze solution, as well as to convert the units ( and ) to Btuh. HE or HR (Btuh) = x TD x Fluid Factor Where: = Flow rate in U.S. gallons per minute TD = Temp. diff. (between water in & out) Fluid Factor = 500 for water; 485 for most antifreezes Figures 11 and 12 show the tools required for checking HE and HR. All technicians installing and servicing geothermal heat pumps should have at least one set of these tools. Flow rate can be determined by measuring the pressure drop across the coaxial heat exchanger. The pressure gauge and adapter should be inserted into the P/T (pressure/ temperature) port of the Water IN connection. Record the reading. Next, insert the gauge into the Water OUT port, and record the reading. The difference between the IN and OUT is the pressure drop. Once the pressure drop of the heat exchanger is known, the flow rate can be determined by consulting the performance data for the particular unit. Example: In heating mode, model 036 has EWT of 50, water pressure IN of 40, and water pressure OUT of 35. The pressure drop, therefore is 5. Figure 10 shows three water pressure drop values and three water flow rates. At 50, if the pressure drop is 1.7, the flow rate would be 5.0 ; if the pressure drop is 3.1, the flow rate would be 7.0 ; and if the pressure drop is 5.0, the flow rate would be 9.0. The flow rate in this example is 9.0. Rarely are the temperature and pressure drop exactly as shown in the tables, so there will be some interpolation required (for example, 52 EWT and 4.7 pressure drop). NOTE: A large gauge face is preferred, since it will be easier to read pressures to the nearest 0.5. ALWAYS use the same gauge in the IN and OUT connections. The use of two gauges could cause false readings, since they could both be out of calibration in opposite directions. Never force the gauge adapter into the P/T port. The gauge adapter could break off in the P/T port, or the force could cause the ring holding the P/T port bladder to become dislodged, potentially ending up in a pump impeller. Once the flow rate is determined, the pocket thermometer can be used to obtain TD. Insert the thermometer into the Water IN P/T port. Record the temperature. Insert the thermometer into the Water OUT port, and record the temperature. The difference between the IN and OUT is the TD. In heating, EWT (entering water temperature) will be warmer than LWT (leaving water temperature); in cooling it will be just the opposite. The last item needed is the type of fluid circulating through the heat pump. As mentioned earlier, 500 should be used for pure water (open loop/well water systems). Use 485 for most antifreeze solutions (see Flow Center and Loop Application Manual for details on antifreeze solutions). 10 Refrigeration/Troubleshooting Guide,

11 Section 2: Heat of Extraction/Heat of Rejection Figure 9: Typical Performance Data - Heating 036 Performance Data: 3.0 Ton, 1200 CFM, Heating EWT Entering Water Temp () Flow Rate (U.S. ) Water Press. Drop (PSI & Ft. of Head) Entering Air Temp () Heating Capacity (MBtuh) Heat of Extraction (MBtuh) Leaving Air Temp () Input Power (kw) Coefficient of Performance Desuperheater Capacity (MBtuh) WPD Heating Heating with Desuperheater PSI FT EAT HC HE LAT KW COP HC HE LAT KW DH COP Figure 10: Typical Performance Data - Cooling Total Cooling, (MBtuh) = SC + LC (Latent Cap) Sensible Cooling (MBtuh) 036 Performance Data: 3.0 Ton, 1200 CFM, Cooling Heat of Rejection (MBtuh) Input Power (kw) Energy Efficiency Ratio EWT WPD EAT Cooling Cooling with Desuperheater DB/ PSI FT WB TC SC HR KW EER TC SC HR KW DH EER 75/ / / / / / / / / / / / / / / / / / Refrigeration/Troubleshooting Guide 11

12 Section 2: Heat of Extraction/Heat of Rejection Figure 13 includes an example water-to-air performing better than specifications. heat pump in heating mode; figure 14 shows the same heat pump in cooling. Following Example 2: l 036, ground loop system are two examples based upon these figures, with ProCool (ethanol) antifreeze solution, which are shown on the next page. cooling mode. Example 1: l 036, ground loop system with ProCool (ethanol) antifreeze solution, heating mode. 1) Fluid factor = 485 2) EWT = 30.0 LWT = 23.5 TD = 6.5 3) Pressure IN = 40 Pressure OUT = 36.6 Pressure drop = 3.4 From performance data, = 7.0 4) HE = x TD x Fluid Factor HE = 7.0 x 6.5 x 485 = 22,067 Btuh Catalog HE = 21,300 Btuh. Therefore, unit is 1) Fluid factor = 485 2) EWT = 90.0 LWT = TD = ) Pressure IN = 40 Pressure OUT = 36.3 Pressure drop = 3.7 From performance data, = 8.0 4) HR = x TD x Fluid Factor HR = 8.0 x 11.2 x 485 = 43,456 Btuh Catalog HR = 43,400 Btuh. Therefore, unit is performing better than specifications. NOTE: HE and HR should be within 10-15% of catalog values. Figure 11: Pressure Gauge with Adapter Gauge Adapter (P/N TSPTN) Adapter Protector Pressure Gauge (P/N TSPG-GC or equivalent) Figure 12: Pocket Thermometer Pocket Thermometer P/N TSDT or equivalent 12 Refrigeration/Troubleshooting Guide,

13 Section 2: Heat of Extraction/Heat of Rejection Figure 13: Heating Operation Example Load IN To suction line Load For water-to-water units substitute a second coaxial heat exchanger for the air coil. Load OUT Return Air Heating Supply Air Cooling Optional desuperheater installed in discharge line (always disconnect during troubleshooting) Line (saturation) temp Line (saturation) (loop) IN Figure 14: Cooling Operation Example (loop) OUT Load IN To suction line Load For water-to-water units substitute a second coaxial heat exchanger for the air coil. Load OUT Return Air Heating Supply Air Cooling Optional desuperheater installed in discharge line (always disconnect during troubleshooting) Line (saturation) temp Line (saturation) (loop) IN (loop) OUT Refrigeration/Troubleshooting Guide 13

14 Section 3: Superheat/Subcooling Overview Superheat and subcooling are used to determine if the heat pump has the proper refrigerant charge, as well as for verifying that the condenser and evaporator are performing properly. Superheat and subcooling can even be used to troubleshoot refrigerant circuit blockages or a bad. Definitions Saturation Temperature: Saturation temperature, sometimes called boiling point, is the temperature at which a refrigerant changes state. For example, Table 1 shows that refrigerant R-410A has a saturation temperature of 32 at 100. Therefore, the refrigerant at 100 is a liquid if it is below 32, and a gas (vapor) if it is above 32. Superheat: Superheat is defined as the number of degrees above the saturation temperature of a refrigerant. For example, if the temperature of refrigerant R-410A is 40 at 100, it has 8 of superheat, since the saturation temperature is 32. Subcooling: Subcooling is defined as the number of degrees below the saturation temperature of a refrigerant. For example, if the temperature of refrigerant R-410A is 28 at 100, it has 4 of subcooling, since the saturation temperature is 32. Checking Superheat and Subcooling Superheat and subcooling should only be checked after the heat of extraction or heat of rejection calculations (see section 2) indicate that the unit is performing poorly. Connecting refrigerant gauges should be done as a last resort. Checking superheat and subcooling requires a refrigeration gauge set with manifold and hoses, plus a digital thermocouple type thermometer. Heat pumps produced by have two schrader ports for service connections, one at the discharge line of the compressor, and one at the suction line of the compressor. When these pressures are used in conjunction with the suction line temperature and liquid line temperature, superheat and subcooling can be calculated. Insulation should be removed from the suction line and liquid line, and the copper should be free from insulation glue, so that the thermocouple makes a good connection at the copper line. Figures 15a and 15b illustrate the locations for taking pressure and temperature measurements. Notice that the two areas for temperature measurement are suction line and liquid line. In order to check superheat and subcooling, the saturation temperature must be determined, which requires the pressure of the refrigerant and the actual temperature of the refrigerant at the same location. However, the only location where both temperature and pressure are easily obtained is at the suction line. In section 1, temperatures and pressures were discussed in relation to components, both before and after the components. It was also mentioned that the discharge pressure and the liquid line pressure are within a few of each other. Most manufacturers of packaged equipment adjust their service data to allow the technician to use the discharge pressure as the liquid line pressure. Therefore, for checking superheat and subcooling, use discharge pressure with liquid line temperature, and suction pressure with suction temperature. Although superheat and subcooling can be calculated anywhere in the refrigeration 14 Refrigeration/Troubleshooting Guide,

15 Section 3: Superheat/Subcooling circuit, there are two points that are most useful for troubleshooting purposes. First of all, it is imperative that liquid is not returned to the compressor. Liquid refrigerant will wash some of the compressor oil away from critical internal parts, causing premature compressor failure. Plus, the compressor is designed to pump gas, not liquid, and will be operating under adverse conditions. Checking for superheat at the suction line of the compressor insures that the state of the refrigerant at this point is a gas (vapor). The amount of superheat at the suction line determines how well the evaporator (coax in heating, air coil in cooling) is working. Superheat is normally in the 8 to 12 range, but the installation manual will provide specific information for the unit being serviced. NOTE: Check the temperature of the suction line near the bulb, especially on split systems. is overcharged. If subcooling is measured, the high value would indicate that there is a problem with the refrigeration charge. Table 3 lists the conditions associated with high or low superheat and subcooling. Table 4 is an example of typical data found in the installation manual. Figures 16 through 18 illustrate examples of a normally charged system, an undercharged system, and an overcharged system. The other location to check is the liquid line. Since the liquid line is located after the condenser (air coil in heating, coax in heating), the amount of subcooling determines how well the condenser is working. In most cases subcooling is in the 4 to 10 range, but the installation manual will provide specific information for the unit being serviced. Putting It All Together In section 1, operation was discussed. Since the spring has been adjusted to maintain 8 to 12 of superheat, it will close down when necessary to maintain the predetermined superheat setting. Therefore, subcooling plays a crucial part in evaluating the unit s refrigeration charge. In other words, if the unit is overcharged, the will close down to maintain superheat, backing up liquid refrigerant in the condenser. If only superheat is measured, the technician would not know that the unit Refrigeration/Troubleshooting Guide 15

16 Section 3: Superheat/Subcooling Table 1: Pressure/Temperature Chart, R-410A Refrigerant Saturation Saturation Saturation Pressure Temp () Pressure Temp () Pressure Temp () PSIG R-410A PSIG R-410A PSIG R-410A Refrigeration/Troubleshooting Guide,

17 Section 3: Superheat/Subcooling Table 2: Pressure/Temperature Chart, R-22 Refrigerant Saturation Saturation Saturation Pressure Temp () Pressure Temp () Pressure Temp () PSIG R-22 PSIG R-22 PSIG R Refrigeration/Troubleshooting Guide 17

18 Section 3: Superheat/Subcooling Figure 15a: Superheat/Subcooling Measurement - Heating Load IN Load 1 To suction line 2 R-410A Manifold/Gauge Set For water-to-water units substitute a second coaxial heat exchanger for the air coil. Load OUT Return Air Supply Air Optional desuperheater installed in discharge line (always disconnect during troubleshooting) Line (saturation) temp Line (saturation) (loop) IN Thermometer 1 2 (loop) OUT Figure 15b: Superheat/Subcooling Measurement - Cooling Load IN To suction line 1 R-410A Manifold/Gauge Set Load 2 For water-to-water units substitute a second coaxial heat exchanger for the air coil. Load OUT Return Air Supply Air Optional desuperheater installed in discharge line (always disconnect during troubleshooting) Line (saturation) temp Line (saturation) (loop) IN Thermometer 1 2 (loop) OUT 18 Refrigeration/Troubleshooting Guide,

19 Section 3: Superheat/Subcooling Table 3: Superheat/Subcooling Conditions Superheat Subcooling Condition Normal Normal Normal operation Normal High Overcharged High Low Undercharged High High Restriction or is stuck almost closed Low Low is stuck open Table 4: Typical R-410A Unit Superheat/Subcooling Values EWT Per Ton Pressure (PSIG) Pressure (PSIG) Heating - Without Desuperheater Super Heat Sub Cooling Air Temperature Rise (-DB) Water Temperature Drop () EWT Per Ton Pressure (PSIG) Pressure (PSIG) Cooling - Without Desuperheater Super Heat Sub Cooling Air Temperature Drop (-DB) Water Temperature Rise () Refrigeration/Troubleshooting Guide 19

20 Section 3: Superheat/Subcooling Figure 16: Normally-Charged System, Heating Load IN 90.0 Load For water-to-water units substitute a second coaxial heat exchanger for the air coil. Load OUT 70.0 Return Air Heating Supply Air Cooling To suction line Optional desuperheater installed in discharge line (always disconnect during troubleshooting) Line (saturation) 29 temp 300 Line (saturation) Superheat = = 10 Subcooling = = (loop) IN (loop) OUT Figure 17: Under-Charged System, Heating Load IN 87.0 Load For water-to-water units substitute a second coaxial heat exchanger for the air coil. Load OUT Return Air Heating Supply Air Cooling To suction line Optional desuperheater installed in discharge line (always disconnect during troubleshooting) Line (saturation) 29 temp Line (saturation) Superheat = = 15 Subcooling = = (loop) IN (loop) OUT 20 Refrigeration/Troubleshooting Guide,

21 Section 3: Superheat/Subcooling Figure 18: Over-Charged System, Heating Load IN 85.0 Load For water-to-water units substitute a second coaxial heat exchanger for the air coil. Load OUT Return Air Heating Supply Air Cooling To suction line Optional desuperheater installed in discharge line (always disconnect during troubleshooting) Line (saturation) 34 temp Line (saturation) Superheat = = 10 Subcooling = = (loop) IN (loop) OUT Figure 19: Water-to-Air Refrigerant Circuit with Desuperheater Load IN To suction line Load For water-to-water units substitute a second coaxial heat exchanger for the air coil. Load OUT Return Air Supply Air Line (saturation) temp Line (saturation) (loop) IN Heating Cooling Desuperheater (loop) OUT Refrigeration/Troubleshooting Guide 21

22 Section 4: Desuperheater Operation The desuperheater option includes a waterto-refrigerant coaxial heat exchanger installed between the compressor discharge line and reversing valve, which is connected to the condenser (air coil in heating, coax in cooling) as shown in figure 19. Unlike the source coax in all geothermal heat pumps, the desuperheater coax is a doublewall, vented water-to-refrigeration heat exchanger. Figure 20 illustrates a cut-away of the desuperheater coax. The operation of the desuperheater takes advantage of the superheat at the discharge line. For example, in figure 16, the discharge pressure is 300. The saturation temperature at 300 is 96. The discharge line at these conditions would typically be around 160. Therefore, the superheat (actual temperature saturation temperature) is 64. As domestic hot water flows through the desuperheater heat exchanger, some of the superheat at the discharge line is used to heat domestic water, which lowers the superheat at the discharge line, thus the term desuperheater. Water flow rate through the desuperheater coax must be very low to avoid turning the desuperheater into a condensor, and robbing too much heat from the main condenser. Typically, about 0.4 per ton is used for desuperheater flow rate. The desuperheater pump operates anytime the compressor is operating (unless the one of the temperature limits is open). In heating, the desuperheater takes some of the heat that would have been used to heat the space via the condenser (air coil), and uses it to make domestic hot water. Even though the desuperheater is robbing some of the heat from the space, it is a very small amount, and the system is heating water at a very high C.O.P. (3.0 to 4.0, depending upon loop temperature), compared to an electric water heater at a C.O.P. of 1.0. Some geothermal heat pumps turn off the desuperheater pump when back up heat is energized. However, studies show that on an annual basis, the system is more energy efficient when the desuperheater is utilized any time the compressor is running. When the hot water tank is already heated, a thermal switch turns off the desuperheater pump. The pump may also be turned off if the compressor discharge line is too cool. Figure 20: Desuperheater coax cut-away Smooth Wall Inner Tube Rifled Copper Tube Steel Outer Wall Refrigerant Air Gap Water In cooling, the desuperheater takes some of the heat that would have been rejected to the ground loop via the condenser (coax), and uses it to make domestic hot water. Therefore, the desuperheater produces nearly free hot water (other than the fractional horsepower circulating pump) in the cooling mode. 22 Refrigeration/Troubleshooting Guide,

23 Troubleshooting Form Please make copies of this form. Customer/Job Name: Date: l #: Serial #: Antifreeze Type: Diagram: Water-to-Air and Water-to-Water Units Load IN Load For water-to-water units substitute a second coaxial heat exchanger for the air coil. Load OUT Return Air Heating Supply Air Cooling To suction line Optional desuperheater installed in discharge line (always disconnect during troubleshooting) Line (saturation) temp Line (saturation) (loop) IN Note: DO NOT connect refrigerant gauges until Heat of Extraction or Rejection has been checked. Note: Disconnect desuperheater before proceeding (loop) OUT HE or HR = x TD x Fluid Factor (Use 500 for water; 485 for antifreeze) SH = Temp. - Sat. SC = Disch. Sat. - Liq. Line Temp. Refrigeration/Troubleshooting Guide 23

24 P.O. Box 245 Syracuse, NY US CAN FAX * ** *** * AHRI certification is shown as the brand under the Enertech Manufacturing certification reference number ** Industries geothermal heat pumps are shown as a multiple listing of Enertech Manufacturing s ETL certification *** geothermal heat pumps are listed as a brand under Enertech Manufacturing s Energy Star ratings

Residential Application/Design Manual

Residential Application/Design Manual P.O. Box 245 Syracuse, NY 13211 www.roth-america.com 888-266-7684 Residential Application/Design Manual P/N: 2300100905 Table of Contents: Overview...2 Section 1: System Selection Packaged Water-to-Air

More information

*20D082-05NN* 20D082-05NN

*20D082-05NN* 20D082-05NN 2506 South Elm Street Greenville, IL 62246 www.enertechgeo.com info@enertechmfg.com HT Models Packaged Water-to-Air Horizontal Heat Pumps Engineering Data and Installation Manual Rev.: 25 May 2012D P/N:

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING UNIT OBJECTIVES After studying this unit, the reader should be able to Select the correct instruments for checking an air conditioning unit

More information

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AIR CONDITIONING. Carrier Corporation 2002 Cat. No AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)

More information

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS HVAC Systems What the Rater Needs to Know in the Field This presentation used CASE* studies from the following *CASE Copy And Steal Everything HVAC Systems - What the Rater Needs to Know in the Field This

More information

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system. Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs the unwanted heat, this raises the refrigerant

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the operation of reverse-cycle refrigeration (heat pumps) Explain

More information

Desuperheater Fitting Kit Installation Guide

Desuperheater Fitting Kit Installation Guide P.O. Box 245 Syracuse, NY 13211 www.roth-america.com 888-266-7684 Desuperheater Fitting Kit Installation Guide P/N: 2300100908 Table of Contents: Section 1: Introduction Contents of Kit... 2 Guide Revision

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012 SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons) ENGINEERING DATA HEAT PUMP OUTDOOR UNITS HP40 50HZ Capacity 6.2 to 16.3 (21 200 to 55 500 Btuh) Heating Capacity 6.4 to 16.1 (21 800 to 55 500 Btuh) Bulletin No. 490088 October 2004 Supersedes August 1999

More information

Engineering Data and Installation Manual

Engineering Data and Installation Manual Engineering Data and Installation Manual RT MODELS OUTDOOR SPLIT SYSTEM WATER-TO-AIR HEAT PUMPS REVISION: A *20D085-01NN* 20D085-01NN PAGE LEFT INTENTIONALLY BLANK Table of Contents: Section 1: Model Nomenclature

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

Energy Use in Refrigeration Systems

Energy Use in Refrigeration Systems 2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is

More information

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

Compact, Self-Contained unit that offer low installation cost plus dependable performance. 0 Compact, Self-Contained unit that offer low installation cost plus dependable performance. From carrier s excellence in engineering come a new, compact of single package horizontal and vertical water

More information

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.2 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information

T P A 120 S 4 S N 1 Y

T P A 120 S 4 S N 1 Y PRODUCT SPECIFICATIONS HEAT PUMP OUTDOOR UNITS TP T-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ Bulletin No. TPA-090-120 (11/2012) EER up to 11.0 7.5 to 10 Tons Cooling Capacity - 89,000 to 180,000 Btuh Heating

More information

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

Technical Development Program

Technical Development Program Technical Development Program PRESENTED BY: James Parker Insert your logo here AIR HANDLERS Coils: Direct Expansion Chilled Water and Heating Menu Section 1 Introduction Section 2 Typical Coil Applications

More information

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation INTRODUCTION In recent years air conditioning industry technology has advanced rapidly. An important byproduct of this growth has been development of the heat pump. Altogether too much mystery has surrounded

More information

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No HEAT PUMPS Carrier Corporation 2003 GT72-01 Cat. No. 020-018 1. This refresher course covers topics contained in the HEAT PUMPS specialty section of the North American Technician Excellence (NATE) certification

More information

Refrigeration Systems and Accessories

Refrigeration Systems and Accessories As with the Chapter Review Tests and the Final Exam, the tests your understanding of the materials underlying the learning objectives. After you ve reviewed your answers to the Chapter Review Tests, try

More information

Installation, Operation & Maintenance: Field-Installed Electric Heater for RXT Series Units

Installation, Operation & Maintenance: Field-Installed Electric Heater for RXT Series Units P.O. Box 245 Syracuse, NY 13211 www.roth-america.com 888-266-7684 Installation, Operation & Maintenance: Field-Installed Electric Heater for RXT Series Units P/N: 2300100902 Table of Contents: Section

More information

HEAT CONTROLLER, INC. HSS Series 1 1/2 to 5 Tons Indoor Split System Geothermal Heat Pumps

HEAT CONTROLLER, INC. HSS Series 1 1/2 to 5 Tons Indoor Split System Geothermal Heat Pumps HEAT CONTROLLER, INC. ENGINEERING DESIGN GUIDE HSS Series 1 1/2 to 5 Tons Indoor Split System Geothermal Heat Pumps HEAT CONTROLLER, INC. 1900 Wellworth Ave., Jackson, Michigan 49203 Ph. 517-787-2100 Fax

More information

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support Contact information Instructors: Don Reynolds 616-560-9903 Doug McGee 517-294-3932 Factory Tech Support 888-593-9988 Product Improvements for 2017 Todays Objectives Job Site Information Sheets Low Ambient

More information

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models)

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models) 4-1280 Application Engineering Bulletin AE-1280R4 Revised April, 1995 APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models) Introduction The Compliant Scroll Compressor has been

More information

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT

Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT EarthLinked TXV Kit Installation Manual for Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT CONTENTS PAGE Pre-Installation 3 Hydronic Water Module Conversion

More information

2 shp 13 lc 1 36 t - 1 a

2 shp 13 lc 1 36 t - 1 a HEAT PUMPs 2SHP3 PRODUCT SPECIFICATIONS Dry Charge Split System - 60 HZ Bulletin No. 20645 July 203 Supersedes June 202 3 to 5 Tons MODEL NUMBER IDENTIFICATION 2 shp 3 lc 36 t - a Refrigerant Type 2 =

More information

RTP Technical Bulletin

RTP Technical Bulletin RTP Technical Bulletin Category: REFRIGERATION REGISTERED TECHNICIANS PROGRAM Volume 1 Bulletin 2 the information contained in this bulletin contains some important c o n c e p t s regarding pressure/

More information

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

HVAC Fundamentals & Refrigeration Cycle

HVAC Fundamentals & Refrigeration Cycle HVAC Fundamentals & Refrigeration Cycle Change of State of Water & the Refrigeration Cycle Change of State Water The Basic Refrigeration Cycle Types of DX Systems The Chilled water System The Cooling Tower

More information

The Saturation process

The Saturation process SOUTH METROPOLITAN TAFE WA The Saturation process Dennis Kenworthy 8/5/2016 A student study guide to measuring and interpreting the saturation process of refrigeration and air-conditioning equipment System

More information

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM EFFICIENT UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase REFRIGERATION CIRCUIT S 2- stage scroll compressors

More information

Richard Hiles ClimateMaster

Richard Hiles ClimateMaster Minnesota Geothermal Heat Pump Association 2012 Properly Sizing Ground Source Heat Pump Systems Richard Hiles ClimateMaster Objective Properly Size and Select GSHP System for Low Operating Costs And Proper

More information

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014 Class 1: Basic Refrigera0on Cycle October 7 & 9, 2014 Refrigeration Cycle 4 key components needed in a basic refrigera0on cycle: 1. Compressor 2. Condenser 3. Evaporator 4. Metering Device Compressor Compressor

More information

3 TON Heating Performance Data TON Cooling Performance Data TON Heating Performance Data TON Cooling Performance Data...

3 TON Heating Performance Data TON Cooling Performance Data TON Heating Performance Data TON Cooling Performance Data... Table of Contents I. Key & Legend... 4 Key to Model Numbers... 4 Legend for Tables... 4 II. Warnings & Cautions... 5 III. General Information... 5 Inspection... 5 Storage 5 Protection... 5 Pre- Installation

More information

R.A.S.E.R.S System. Installation Guide

R.A.S.E.R.S System. Installation Guide R.A.S.E.R.S System Installation Guide Contents R.A.S.E.R.S System components... 1 Required components for heating, cooling, and hot water...1 Provided...1 Not provided...2 Optional components...3 R.A.S.E.R.S

More information

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation Form 30-217 / January 2007 Heat Reclaim Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation While the vapor-compression cycle has

More information

Versatec Specification Catalog

Versatec Specification Catalog Water-to-Water Heat Pumps 15 and Tons Design Features Versatec Specification Catalog Factory Options Accessories Dimensional Data Physical Data Performance Data Engineering Guide Specifications SP1063

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

T-SERIES COMMERCIAL SPLIT SYSTEMS R-410A - 60 HZ

T-SERIES COMMERCIAL SPLIT SYSTEMS R-410A - 60 HZ PRODUCT SPECIFICATIONS HEAT PUMP OUTDOOR UNITS ELP T-SERIES COMMERCIAL SPLIT SYSTEMS R-410A - 60 HZ Bulletin No. ELP-090-120 (4/2018) MODEL NUMBER IDENTIFICATION EER up to 11.0 7.5 to 10 Tons Cooling Capacity

More information

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING Sample Questions and Answers CHAPTER 5 EVAPORATORS 1. What is Evaporator? Classify the various types of evaporator. Evaporator

More information

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant EarthLinked TXV Kit Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant CONTENTS PAGE Pre-Installation 3 Air Handler Conversion 4 System

More information

Installation & Operation Manual Hydronic

Installation & Operation Manual Hydronic Installation & Operation Manual Hydronic Installation & Operation Manual Engineering Specifications GeoSource Hydronic Models RGS-W036 RGS-W120 This Page Intentionally Left Blank Table of Contents I. Key

More information

HSXA15 HSXB15. IMPORTANT Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A.

HSXA15 HSXB15. IMPORTANT Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A. Service Literature Corp. 0128 L12 Revised 10 2004 HSXB15 & HSXB15 SERIES UNITS The and HSXB15 are high efficiency residential split system condensing units, which features a scroll compressor and R410A

More information

GUIDE SPECIFICATIONS AQUARIUS ii

GUIDE SPECIFICATIONS AQUARIUS ii Catalog (AP Technical Data Sheet) GUIDE SPECIFICATIONS AQUARIUS ii AP Series Two Stage R-410A GENERAL Units shall be performance certified to ISO standard 13256-1 for Water Loop Heat Pump, Ground Water

More information

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts GTIP60 ISO GT Series, Inch Pounds 60 Hz GT010070 (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts Rev: 903 Rev 1 Revisions: 31103 Changed HZ dwg to field convertible 5902 changed Unit

More information

T-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ. EER up to to 20 Tons Cooling Capacity - 71,000 to 236,000 Btuh AIR CONDITIONERS TS

T-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ. EER up to to 20 Tons Cooling Capacity - 71,000 to 236,000 Btuh AIR CONDITIONERS TS PRODUCT SPECIFICATIONS CONDITIONERS TS T-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ Bulletin No. TSA-072-240 (11/2016) 072-090 Models 180-240 Models 120-150 Models EER up to 11.7 6 to 20 Tons Cooling Capacity

More information

Superheat charging curves for technicians

Superheat charging curves for technicians This website requires certain cookies to work and uses other cookies to help you have the best experience. By visiting this website, certain cookies have already been set, which you may delete and block.

More information

Tranquility 30 Two-Stage (TT) Series

Tranquility 30 Two-Stage (TT) Series Tranquility 30 Two-Stage (TT) Series Submittal Data Models TT/H/V 026-072 60Hz - HFC-410A *LC1020* LC1020 Rev.: November 18, 2016 Table of Contents Two- Stage TT Series Unit Features 3 Selection Procedure

More information

GEOTEC GV Series High Efficiency Geothermal/Water Source Packaged Step-Capacity Heat Pump R-410A

GEOTEC GV Series High Efficiency Geothermal/Water Source Packaged Step-Capacity Heat Pump R-410A GEOTEC GV Series High Efficiency Geothermal/Water Source Packaged Step- Heat Pump R-410A Ground Water Application: Water Temp 45 to 75 Ground Loop Application: Temp Range to 110 The Bard GEOTEC Geothermal/Water

More information

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration.

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

Otherwise, you can continue reading the file on the following pages.

Otherwise, you can continue reading the file on the following pages. If you d like to be able to print this file out to study off-line or use on the job, a printable version is available for an administrative fee of $3.97 USD. To download the unlocked file, click here.

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-194 REV. 2 Supersedes Form No. A22-194 Rev. 1 Commercial High-Efficiency Condensing Units RAWL High Efficiency 6.5 & 7.5 TON MODEL [22.86 & 26.38 kw] TABLE OF CONTENTS Model Number Designation...2

More information

Refrigerant changeover guidelines

Refrigerant changeover guidelines Refrigerant changeover guidelines HCFC R-22 to HFC R-407A/F, R-448A or R-449A for medium and low temperature applications HCFC R-22 to HFC R-407C for high, medium and low temperature applications HCFC

More information

HP13 WARNING WARNING. Service Literature HP13 SERIES UNITS

HP13 WARNING WARNING. Service Literature HP13 SERIES UNITS Service Literature Corp. 0610 L1 Revised 07 2006 HP13 SERIES UNITS HP13 The HP13 is a high efficiency residential split system heat pump unit, which features a scroll compressor. HP13 units are available

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS INTRODUCTION Please note that HUD Manufactured Home Construction and Safety Standard Section 3280.714, paragraph (a) and subparagraph

More information

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System

More information

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration Calhoon MEBA Engineering School Study Guide for Proficiency Testing Refrigeration 1. To prevent an injury when working with refrigerants, what safety precautions are necessary? 2. When halogens are in

More information

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A900-22007), 120/208/240/1/60, R404A, LT/MT APPS Introduction The superheat controller is designed

More information

ClimaDry II. Table of Contents. ClimaDry II Whole House Dehumidification Option. Tranquility 30 Tranquility 20

ClimaDry II. Table of Contents. ClimaDry II Whole House Dehumidification Option. Tranquility 30 Tranquility 20 ClimaDry II ClimaDry II Whole House Dehumidification Option Tranquility 30 Tranquility 20 Applications Guide 97B0051N01 Revision: 10 Feb., 2016 Table of Contents Model Nomenclature Example 3 ClimaDry Overview

More information

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical ENGINEERING GUIDE Water-Cooled Self-Contained Units C-Series, Vertical TABLE OF CONTENTS Introduction...2 Product Overview...3 Nomenclature...4 General Data...5 Cooling Performance Data....6 Evaporator

More information

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions CONTENTS PAGE Pre-Installation 3 Placement & Mechanical Information 4 System Application Options 10 Antifreeze Protection 14 Electrical

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-193 REV. 3 Supersedes Form No. A22-193 Rev. 2 Commercial High-Efficiency Condensing Units 15 & 20 TON MODEL [52.8 & 70.3 kw] 10 & 12.5 TON MODEL [35.2 & 44.0 kw] 10 THROUGH 20 NOMINAL TON

More information

INSTALLATION AND SERVICE OF WATER-SOURCE AND GEOTHERMAL HEAT PUMPS WaterFurnace International

INSTALLATION AND SERVICE OF WATER-SOURCE AND GEOTHERMAL HEAT PUMPS WaterFurnace International INTRODUCTION It is assumed that the reader has sufficient knowledge of the heat pump refrigeration cycle, and electrical knowledge, to understand heat pumps and their refrigeration and electrical circuits.

More information

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant EarthLinked TXV Kit Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant CONTENTS PAGE Pre-Installation 3 Cased Coil Conversion 4 System Start-Up 17 TXV CCS-410-KIT

More information

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Introduction to Hydronics A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Hydronic heating systems use hot water or steam to deliver the

More information

Tranquility Console (TRC) Series Submittal Data

Tranquility Console (TRC) Series Submittal Data Tranquility Console (TRC) Series Submittal Data Models TRC09-18 60Hz - HFC-410A *LC386* LC386 Rev.: June 19, 2017 Table of Contents TRC Console Series Unit Features 3 Selection Procedure 4 TRC Series Nomenclature

More information

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE CAS Product Specifications Single stage cooling capacity control on all models with Micro channel

More information

PACKAGE AIR CONDITIONER

PACKAGE AIR CONDITIONER PACKAGE AIR CONDITIONER FORM NO. ATZ-206 TZAA- HIGH EFFICIENCY SERIES NOMINAL SIZE 10 TON [35.2 kw] 10 TON MODEL [35.2 kw] This product is shipped with a nitrogen holding charge that must be vented prior

More information

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration

More information

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc. The Refrigeration Cycle Jerry Cohen President Jacco & Assoc. Basic Refrigerant Cycle P/h Chart Compressor Options Condenser Options Head Pressure Control Thermal Expansion Evaporator Options Lift Evaporative

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

Outdoor Split Unit. Pure and Simple

Outdoor Split Unit. Pure and Simple Outdoor Split Unit TM Pure and Simple Hydron Module will revolutionize the way you think about heating & cooling. Outdoor Split Unit Wishing for higher efficiency out of your existing conventional furnace

More information

COMMON WATERSIDE ECONOMIZER APPLICATIONS:

COMMON WATERSIDE ECONOMIZER APPLICATIONS: APPLICATION MANUAL WATERSIDE ECONOMIZER TABLE OF CONTENTS Safety Approvals...1 Common Waterside Economizer Applications...1 Sequence of Operation (Single)...1 Cooling Mode...2 Heating Mode...2 Sequence

More information

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit

More information

EarthLinked SC Series Compressor Unit R-407C Quik-Start Instructions

EarthLinked SC Series Compressor Unit R-407C Quik-Start Instructions EarthLinked SC Series Compressor Unit R-407C Quik-Start Instructions CONTENTS PAGE Pre-Installation 3 Placement & Mechanical Information 4 System Application Options 11 Desuperheater Kit 15 Antifreeze

More information

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad- 500 043 B.Tech (III II SEM) MECHANICAL ENGINEERING REFRIGERATION AND AIR CONDITIONING Prepared by, Dr. CH V K N S N Moorthy, Professor

More information

DRY CHARGE UNITS. 1.5 to 5 Tons. HEAT PUMP OUTDOOR UNITS lps13dc PRODUCT SPECIFICATIONS L P S 13 DC MODEL NUMBER IDENTIFICATION

DRY CHARGE UNITS. 1.5 to 5 Tons. HEAT PUMP OUTDOOR UNITS lps13dc PRODUCT SPECIFICATIONS L P S 13 DC MODEL NUMBER IDENTIFICATION HEAT PUMP OUTDOOR UNITS lps13dc DRY CHARGE UNITS PRODUCT SPECIFICATIONS Bulletin No. 210637 June 2014 Supersedes June 2012 1.5 to 5 Tons MODEL NUMBER IDENTIFICATION L P S 13 DC - 036-230 - 2 Lennox Minor

More information

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz ENVIRONMENTALLY SOUND REFRIGERANT N4H4 Performance Series Product Specifications 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION

More information

Warm Case Troubleshooting Guide 9/18/2014

Warm Case Troubleshooting Guide 9/18/2014 Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last

More information

CO2 TRANSCRITICAL BOOSTER SYSTEMS

CO2 TRANSCRITICAL BOOSTER SYSTEMS CO2 TRANSCRITICAL BOOSTER SYSTEMS William Katz Sr. Technical Writer Hillphoenix 2016 Gees Mill Road Conyers, GA 30013 Tel: 678-613-9364 Email: william.katz@hillphoenix.com Refrigeration systems for supermarkets

More information

HSXA16 WARNING. WARNING R 410A refrigerant can be harmful if it is inhaled. R 410A refrigerant must be used and recovered responsibly.

HSXA16 WARNING. WARNING R 410A refrigerant can be harmful if it is inhaled. R 410A refrigerant must be used and recovered responsibly. Service Literature Corp. 0507 L2 Revised 07 2006 HSXA16 HSXA16 SERIES UNITS The HSXA16 is a high efficiency residential split system condensing unit, which features a two stage scroll compressor and R

More information

A Treatise on Liquid Subcooling

A Treatise on Liquid Subcooling A Treatise on Liquid Subcooling While the subject of this article is Liquid Refrigerant Subcooling, its affect on the operation of the thermostatic expansion valve (TEV), and ultimately on system performance

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz) DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage

More information

HPXA15 HPXB15 WARNING

HPXA15 HPXB15 WARNING Service Literature Corp. 0202 L1 Revised 09 2004 HPXA15 HPXB15 HPXA15 and HPXB15 SERIES UNITS The HPXA15 and HPXB15 are high efficiency residential split system heat pump units, which features a scroll

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

HVAC Service Technicians Training Center

HVAC Service Technicians Training Center HVAC Service Technicians Training Center 48-03 32 nd Place, Long Island City, NY 11101 Tel: (718) 472-0404 (718) 472-0414 Fax: (718) 433-0676 Introduction to the Refrigeration Cycle: Part 1 (AC/R-1) This

More information

Application Engineering

Application Engineering Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved

More information

The Essentials Of Working With R-410A

The Essentials Of Working With R-410A The Essentials Of Working With R-410A By Norm Christopherson Several major manufacturers are producing comfort air conditioning equipment using refrigerant 410A. The trend towards the use of 410A continues

More information

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh AIR CONDITIONERS 13ACXN PRODUCT SPECIFICATIONS

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh AIR CONDITIONERS 13ACXN PRODUCT SPECIFICATIONS PRODUCT SPECIFICATIONS AIR CONDITIONERS 13ACXN MERIT Series R-410A Bulletin No. 210831 January 2018 Supersedes Bulletin No. 210739 SEER up to 15.50 1.5 to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh

More information