TEMPERATURE CONTROLLER FOR CENTRAL HEATING BOILER WITH PELLET BURNER AND HEATING CIRCUIT. EXPERT Pellets. with STB protection OPERATION MANUAL

Size: px
Start display at page:

Download "TEMPERATURE CONTROLLER FOR CENTRAL HEATING BOILER WITH PELLET BURNER AND HEATING CIRCUIT. EXPERT Pellets. with STB protection OPERATION MANUAL"

Transcription

1 ZAKŁAD PRODUKCJI URZĄDZEŃ ELEKTRONICZNYCH ELSTER Sp.J. Obłaczkowo 150, Września fax tel Tel. serwisu: w.2, , TEMPERATURE CONTROLLER FOR CENTRAL HEATING BOILER WITH PELLET BURNER AND HEATING CIRCUIT EXPERT Pellets with STB protection OPERATION MANUAL Attention! The controller cooperates only with its relevant pellet burner. Please check the compliance of version control and burner. Please comply with all the safety guidelines and before connecting controller to the power network read operation manual carefully! Edition: July 2014 Software version: 3.2.x pellet Type of burner : BADO 25kW

2 Declaration of compliance in the range of the Directive 2006/95/EC and Directive 2004/108/EC ZPUE ELSTER Sp.J Września Obłaczkowo 150 declares on the exclusive responsibility, that the Temperature controller for the CH boiler Expert Pellets produced after the 5th of December 2008r. to which the present declaration treats he is compliant with directives: Low-tension directive 2006/95/EC with MG regulation MG from 15th of December 2005 on essential requirements for electrical equipment (Dz. U r. Nr 259, poz.2172) Directive of electromagnetic compatibility 2004/108/EC and norms: - PN-EN : EN :2002+A1:2003+A11:2003+A2:2005+A12: PN-EN :2002+A1:2006+A12:2004+A13:2005+A14:2006+A15:2007 +A16: EN :2000+A1:2004+A12:2003+A13:2004+A14:2005+A15:2007 +A16: PN-EN :2002+A1:2008+A2: EN :2000+A1:2004+A2: PN-EN :2007 / EN : PN-EN :1997+A1:2005+A2:2006 +IS1:2006+AC: EN :1995+A1:2001+A2:2005 +IS1:2005+AC:1997

3 WARNING! ELECTRICAL EQUIPMENT. Safety guidelines: 1. While connecting controller please keep in mind local conditions and legislations about electric power supply. 2. Electric instalations should be made by person with proper permissions, with the power plug unplugged. 3. Due to work safety while operating and also power network electromagnetic interferences, which may have influence on the controller (revealing for example by temperature measurement errors), controller has to be connected to power socket with properly connected safety contact!!! Not applying to this rule will void the warranty!!! 4. Before first startup of controller efficiency of blower and pups grounding has to be checked. 5. Power cord cannot be repaired. Replacement of power cord has to be made by producer or qualified serviceman! During atmospheric discharges voltage related to lighting may reach 300 kv, destroying electronic devices. Please remember to unplug controller and other devices from power network during storms and leaving home.

4 Spis treści I. General description... 5 II. Startup and operation of the controller III. Initial start-up Configuration Set-up of the language IV. Startup and shutdown of the boiler Enabling the burner - firing up the boiler Turning off the burner - boiler extinction... 8 V. Basic operation of the boiler Adjusting temperature setpoint Burning adjustment Setting the temperature set point for domestic hot water Additional boiler status information VI. Operation algorithm Burner`s work Operation of the pumps Operation of the central heating circulation pump Operation of DHW circulation pump Operation of the DHW loading pump VII. The additional settings Domestic Hot Water mode DHW circulation DHW circulation enabling Edition of the weekly program for DHW circulation Edition of the weekly temperature setpoint program Set-up of the time Set-up of the language VIII. Operation with mixing valves.modules Modes of the valve.oparation Cooperation the valve and the room panel Edition the module parameters of the valve IX. Error service X. Connecting controller to central heating installation XI. Installer Settings XII. Working conditions XIII. Warranty repairs card Warranty card... 36

5 I. General description. Expert Pellet is a temperature controller for central heating boilers with burner for combustion pellets. The controller has the following features: boiler temperature control by manually or programmatically set point temperature, automatic power control of the boiler depending on the heat demand (PID), with the possibility of switching the displacement control mode automatic operation of the central heating circulation pump operate one mixing three- or four-way valve with a separate pump, or the optional steering the central heating circulation pump with the room controller "Roomster", control of multiple independent heating circuits by attaching additional valve modules, domestic hot water (DHW), including the ability to enable the neutralization of Legionella, Manual operation or DHW circulation pump program Implemented in controller advanced control algorithm PID, basing on sensor measurements, automaticly controls amount of fuel and air, therefore boiler power. Advantages of such an approach: Stable boiler setted temperature, regardless of temporary changes in consumed power, Significantly reduces amount of soot, carbon monoxide and other harmful substances emitted to the atmoshpere substantially longer periods between cleaning of the boiler II. Startup and operation of the controller. We enclose the controller to the net by using the switch. The display shows the manufacturer s logo followed by installed software version and icons for button functions: 5

6 - restoring default settings, - entering service or installer mode After a short waiting controller displays the main screen. It will contain information about the status of the boiler, and a graphical view of the function buttons on the display. Navigating the interface controller is done by pressing the appropriate buttons located on both sides of the display. Functions available at the button change depending on the display screen. If a button is assigned any function, it is presented in a graphical display. Fig.1. View of the control panel and the main screen. Items shown on the main screen are: 1. graphic representation of the button s function 2. Information of the burner status (off, standby, lighting, heating) 3. Information of the DHW pump current status 4. indicator of the presence and size of the flame 6

7 5. current boiler temperature 6. target boiler temperature (heating temperature) 7. current time and day of the week 8. temperature setpoint (for the boiler or room) 9. information about active weekly programs and active heating temperature correction The button icons shown on the main screen of the controller are used to: a. - obtain additional information of the boiler status b. - burning process adjustments c. DHW setpoint temperature settings d. - transition to additional settings the user / installer e. or - accordingly to enable or disable the burner f. - if present, serves to set the valve modules g., - increasing or decreasing the setpoint temperature of the boiler Moreover, on all screens the button icons means: - go to the next screen - return to the previous screen, - increase or decrease the set value - confirmation of the changes III. Initial start-up. 1. Configuration The controller is adapted to pre-burner operating at full power rating. In case of mounted the burner in the boiler of a lower power installer, with the available parameters, should set the appropriate power rating of the boiler - otherwise user will be exposed to unnecessary loss of fuel For proper burner start is required starting dose of fuel approx g. Responsible for this parameter is a starting dose of fuel installation (measured in seconds). Instalator should check that feeder, working for the time specified by this parameter, provides appropriate amount of pellets 7

8 and, if necessary. correct parameter setting Attention! Too much fuel in the burner during ignition may result in unnecessary prolongation of heater operation in extreme cases, also reporting a bug firing. 2. Set-up of the language. Language in which the controller communicates with the user is going by selecting the buttons: SETTINGS -> GENERAL -> LANGUAGE. IV. Startup and shutdown of the boiler. 1. Enabling the burner - firing up the boiler. The message "Burner off" on the main screen and the presence of a button indicates automatic shutdown of the burner. To properly make the boiler firing up: Press the button - then go to the manual filling of fuel. Before starting feeder storage tank should be completely filled with pellets. Press the On and Off manually run the feeder storage tank until the first pellet feeder discharge. Press the button to turn on the burner and the transition to a state of Readiness. After turning on the burner main screen appears. The controller switches to automatic mode. If the current boiler temperature is below the set point at least 5 degrees followed Firing-Up. Otherwise, the controller expects the Readiness state for the right conditions to start. 2. Turning off the burner - boiler extinction Turning off the burner (extinction boiler) can be made when the burner is on. 8

9 Press the button. Can be canceled by pressing NO. Confirm the YES button to stop the burner. If the burner is currently in a state of combustion of the fuel, before turning off the burner will Burn-Out fuel remains and Clean. V. Basic operation of the boiler 1. Adjusting temperature setpoint. The current temperature of the boiler is displayed under the bar temperatures. The regulator calculates the operating temperature on the basis of the boiler temperature setpoint and adjustments entered in the weekly program. Additionally, the operating temperature can be impacted by other functions active, such as filling DHW tank or connected 3-way valve modules. Boiler temperature is set directly from the home screen by pressing and. 2. Burning adjustment. If you find out that the used fuel is of poor quality, you can adjust the burning process by pressing button. Select one of available options that impact burning quality by pressing the button next to given description 9

10 MAX. BOILER POWER allows reducing maximum boiler power compared to rated power. FUEL CALORIFIC a change grade pellets to set the fuel calorific value declared in kwh / kg. Higher calorific value reduces administration time, lower - extends the time of administration. AIR CORRECTION increases or decreases the amount of air administered to the value set at the factory. The respective values can be chosen empirically: - high temperature in the chimney can provide too much air - rising smoke from the chimney may indicate that there is insufficient air 3. Setting the temperature set point for domestic hot water. Domestic hot water system control is exercised through control of the DHW charge pump based on water temperature measurement in the DHW tank. To change the DHW temperature setpoint press the button. Change the setpoint value using buttons,. Confirm the changes and exit the screen, press button or exit the screen without confirming the changes, press button. 10

11 4. Additional boiler status information. By choosing INFO screen you can access information about boiler parameters, status of controlled devices, and preview measurements of installed sensors. To go to INFO screen Press the button next to icon. The user can choose between two screens of information available, but after pressing the button always displays the last used screen. For example., If the user was interested in the parameters DHW and returned to the main screen by pressing, pressing it again Information screen will display "Info hot water" a) Information display of burner/boiler The individual elements on the screen means: 1 The heating central circulation pump ; if the triangle turns the pump is running 2 The heating central circulation pump mode: means winter mode, means summer mode pump does not work 3 current burner output in kw displayed alternately with an average daily fuel consumption 4 the actual temperature of the water in the boiler shell 5 animated symbol of fuel combustion depending on the operating state of the burner 11

12 6 igniter - During heater`s work, igniter symbol flashes 7 current blower control - if the blower is working icon of the rotor rotates 8 Fedder`s burner (auxiliary) - if the feeder is enabled, the icon moves 9 the actual temperature of the feeder 10 feeder storage tank (main) - if the feeder is enabled, the icon moves 11 current time of administration / pause of feeder storage tank Press to return to the main screen. Press to switch the screen DHW.Info. b) Information display of DHW The individual elements on the screen means: 1 - DHW charging pump mode: menas Winter mode, means summer mode 2 - DHW charging pump; if the triangle turns the pump is running 3 DHW setpoint temperature 4 actual hot water temperature in the tank 5 - DHW circulation pump; if the triangle turns the pump is running Press. to return to the main screen. Press to switch the screen Boiler Info.. VI. Operation algorithm. If the engine is switched off the controller controls only the pumps and heating circuits controlled by valve control modules. Any burner`s work 12

13 or its components is prohibited. 1. Burner`s work. Immediately after turning on the burner goes into READINESS state and is waiting for the proper temperature to start. Conditions of ignite / extinguish of the burner are based on the current temperature of the boiler and the hysteresis of work (as determined by the installer). If the water temperature exceeds a predetermined operating temperature hysteresis value of work (typically 5 C) the burner unconditionally, regardless of the method of adjustment, go to the READINESS state, and died previously contained in the fuel. Rekindle will be possible only when the water temperature falls below the operating temperature of the hysteresis work. Measuring the presence of the flame is implemented by a photoelement placed in the burner. It is recommended the periodic cleaning. FIRING-UP always starts pre-cleaning the burner by turning on blower to maximum Power. Then, the charge starting dose of fuel is following and warming heater of igniter. After warming up of The heater, blower starts at low power. After a relatively short time, the fuel ignites in the burner - heater is switched off. After switching off the heater, fuel is replenished in very small portions. Amount of fuel and Power of blowers are gradually increased until the optimal warm-up the burner. After completion of ignition controller enters WARMING-UP, next WARMING, starting the power control in accordance with the parameters set by installer. The maximum power of the boiler may be limited by the user by POWER BOILER parameter that is available in the combustion settings. If the installer set step adjustment of the burner, the controller controls the burner working at nominal capacity or less, according to the current demand for heat. After reaching the set temperature, + hysteresis work goes into the post-combustion. If there is selected method of PID control, the controller controls the boiler continuously changing according to the time of administration, length of intervals between administrations and the power of the blower. As reaching the desired temperature of the boiler power should fall to stabilize at a level appropriate to the received power. The unit proceeds to the afterburner if the boiler water temperature, because of the very low heat demand, exceeds the specified operating temperature hysteresis value of work. 13

14 In the state of post-combustion fuel supply is switched off - operates only auxiliary burner feeder to eject the rest of the pellet. The blower operates with such power as for power reduced. After the complete combustion of fuel, the CLEANING process begins - the blower runs maximum power. After cleaning time (defined by the manufacturer), the burner goes into READINESS the duty cycle can start again automatically after fulfillment of the conditions of temperature. The controller automatically detects the lack of fuel or extinguishing of the flame for other reasons. If subsequent attempts to ingnite do not work, the burner is turned off. 2. Operation of the pumps. If the boiler's temperature is smaller than 6ºC, the anti-freezing function is on: all the pumps are on. All the pumps are on always after filing the boiler overheating alarm. Pumps: the central heating circulation pump. and charging DHW can be switched just after reaching the boiler's temperature even the last, put through the installer, the PUMP STARTS TEMPERATURE. If the boiler's temperature falls about 5 degrees below the PUMP STARTS TEMPERATURE all pumps will be switched off Operation of the central heating circulation pump The central heating circulation pump work depends on set DHW mode: a) If the SUMMER mode is on this pump is switched off. b) When the DHW PRIORITY is on, and the domestic hot water sensor has been installed, the pump is switched off for the time of loading the DHW tank. c) If it is set to WINTER mode, the pump is operating normally, but if the built-in manual valve is turned off and room panel "ROOMSTER 'is connected, the controller controls the heating circuit, by switching, as needed, the central heating pump Operation of DHW circulation pump. This pump is controlled solely by the time, based on settings in DHW CIRCULATION, and additionally turned off in ECONOMIC MODE (pkt.ii.10). Condition for turning on the pump is temperature of 35 C in a DHW tank Operation of the DHW loading pump Without the regard on the DHW PRESET TEMPERATURE, the pump is always off if the boiler's temperature falls below the water's temperature in the DHW tank, to prevent to cool down water in the DHW tank 14

15 Przygotowanie C.W.U. może się odbywać w trzech trybach: a) WINTER mode - It loads the DHW tank so that the minimum of the two temperatures is held: OPERATING TEMPERATURE and DHW PRESET TEM- PERATURE. The pump is switching on when the DHW temperature drops 5 C (standard value of the parameter DHW HISTERESIS, defined through the installer) below the DHW PRESET TEMPERATURE. The pump is switched off after reaching that temperature. b) PRIORITY mode - On the time of loading the DHW tank the OPERATING TEMPERATURE is placed on the level what the least 10 C higher than DHW PRESET TEMPERATURE.. Po wyłączeniu pompy ładującej BOILER OPERATING TEMPERATURE returns to the level set by the user. The pump is switched on if DHW sensor shows the temperature lower at 5 C (standard value of the parameter DHW HISTERESIS, defined through the installer) from the DHW PRESET TEMPERATURE. The pump is switched off after reaching that temperature. c)summer mode - charging pump works the same way as in the PRIORITY mode but the circulating pump is turned off. Attention!!! In the situation of DHW sensor failure, until replacement of the sensor the pump can still work in failure mode parallel with the circulation pump. Attention!!! Controller has built-in function of Legionella pneumophila neutralization, which can be found in hot water containers. Neutralization function will result in setting DHW temperature to 70 C with priority on Saturday between 2:00am and 4:00am. In the current software version this function is turned off by default and can be turned on by installer. VII. The additional settings. button : To get access to additional settings, on the main screen, press the Screen will be displayed with list of parameters. Select, depending on the needs, one of the items 15

16 1. Domestic Hot Water mode By default, the preparation of hot water takes place in the WINTER mode - parallel with the room heating. Select one of the three available modes DHW 2. DHW circulation 2.1. DHW circulation enabling By default, the hot tap water circulation pump is turned off. It is possible to activate the pump to WORK BY THE CONTINUOUS or parttime work. When you select BY SCHEDULE, will be a prompt, if change the previous settings. If you press the YES button you will proceed to the next step - to change the program Edition of the weekly program for DHW circulation The weekly program of DHW circulation is used for scheduling operation of the DHW circulation pump. You can attribute an active or inactive state to every hour of the day with a 10-minute accuracy. The program is run separately for every day of the week. Program Review mode. Program screen of DHW circulation starts in Review mode - next to the button icon is displayed. Press (right)/ (left) to 16

17 choose the direction of movement of the clock timer. The button icon shows the currently selected direction. Use buttons,, to move about 10 minutes, 1 hour, or one day in the desired direction Program change mode. Press (programming) to enter the program change mode button changes to and the next is displayed. Press (off) / (ON) to select the state of the pump that is assigned to the program from the selected time. Selected state is displayed next to the icon button. Press to type the selected state Press for a given time. Pressing this button mode. will also move to the next record position 10 minutes forward or backward, depending on the choosen buttons and Direction of programming. Pressing will automatically save any settings and programming screen output 17 to return to viewing Example: Programming DHW water circulation pump activity for Monday through Friday, for 6 am. 8 am. and 3 pm. 10 pm. In other time slots the circulation pump will remain disabled. Select preview function. Using buttons,, select 6 am. Switch the preview function to programming function. Set the direction as (right). Set pump mode as ON.

18 Pressing button set the clock until 8 am. Set pump mode as OFF Pressing button set the clock until 3 pm. Set pump mode as ON. Pressing button set the clock until 10 pm. Set pump mode as OFF Pressing button set the clock until 3 pm. of the following day. Repeat steps 5 to 12 for the next day of the week. 1. When the whole week is programmed, exit the programmer screen by pressing button.. 3. Edition of the weekly temperature setpoint program. By default, the weekly program of boiler is switched off. Weekly program of set temperature can be set to one of the temperature correction for each hour of the day to the nearest 10 minutes. Possible options: activate, deactivate and set the program. To go to the program changes, press the button. Press to change the settings of correction, or press the button to go to the programmer. In case of changing night correction, on next screen set the night adjustment value with buttons,. Proceed by pressing the button next to icon. 18

19 Set the economy adjustment value with buttons,. Proceed by pressing the button next to icon. Pressing button (right)/ (left) choose the direction for moving the programmer s clock. The currently selected direction is displayed in the button s icon. Pressing buttons,, move 10 minutes, 1 hour, 1 day in desired direction. Program change mode. Press (programming) to enter the program change mode button changes to displayed. Pressing button and the next is (day no adjustment) / (night) / (economy) choose the adjustment to be entered into the pro- from programming screen.. Press to save changes and exit grammer. The selected adjustment will be displayed next to the button s icon. mode. Press to return to viewing Pressing button program the desired function for selected hour. Pressing this button will result in moving the position to next save 10 minutes forward or backward, basing on programming direction chose 19

20 by buttons and. Example: Programming temperature setpoint adjustment for Monday through Friday, day adjustment: 6 am. 8 am., economy adjustment: 8 am. 3 pm., day adjustment: 3 pm. 10 pm., and night adjustment: 10 pm. 6 am. Select preview function. Using buttons,, select 6 am in Monday. Switch the preview function to programming function. Set the direction as (right). Set the day adjustment. Pressing button set the clock so that lasts until 8 am. Switch from day adjustment to economy adjustment. Pressing button set the clock so that lasts until 3 pm. Switch from economy adjustment to day adjustment. Pressing button set the clock so that lasts until 10 pm. Switch from day adjustment to night adjustment Pressing button set the clock so that lasts until 6 am. of the next day. Repeat steps 5 to 12 for the next day of the week. When the whole week is programmed, exit the programmer screen by pressing button 4. Set-up of the time. First, select a day of the week. When selected will automatically go to setting the time The setpoints will be stored automatically 20

21 Press, to set the hour and minute 5. Set-up of the language. From the list of available languages, select the appropriate and confirm. VIII. Operation with mixing valves.modules The controller can handle up to 10 modules of valves, including one built. To use the built-in module need to activate in the configuration mode or in the installer menu. If, during the system startup is detected at least one valve module, on the home screen appears button -press to display a list of valves. Module selection to view or to change the parameters, make by selecting items on the list. After selecting the module will display a screen with the current configuration of the valve. 1. Modes of the valve operation. Each valve module can operate in different modes of operation, which is set in the parameter menu of the valve. You can select from the following configurations heating circuits: a) the shuttle valve supply underfloor heating 21

22 b) the shuttle valve power heaters c) the shuttle valve working on mixing return d) four-way valve supply underfloor heating e) four-way valve supply heating radiator or the entire substation 22

23 2.Cooperation the valve and the room panel. Each module is connected to the control valve Expert PID, with the exception of the valve is configured to work in return, can work with the room panel - ROOMSTER. In this case, the temperature of the feedwater of heating circuit is automatically adjusted based on the current room temperature and desired temperature. Information about connecting and correct use of the room panel is displayed on the valve`s screen in the form of a house icon with displayed current room temperature. 3. Edition the module parameters of the valve. To set the operating parameters of the valve, being in the valve`s screen, press. Displays a list of parameters to adjust. The following parameters are available: [1] TEMPERATURE SETPOINT depending on the configuration of the valve, temperature set point is set to for the heating circuit: - 3-W (three-way) floor or radiator - temp. Power, - 3-W return - temp. return, - 4-W (four-way) floor or radiator - setpoint temperature supply and return The set temperature for FLOOR mode is always limited to 40 C. If the panel ROOMSTER is connected, the power setpoint temperature setting is locked. [2] OPERATION MODE set one of five possible modes of mixing valve 3W (Tyree- way) FLOOR mode provides regulation of floor heating circuit, while reducing the maximum temperature of the water in circulation to. 3W RADIATOR mode provides quality heating control based on set temperature or outdoor temperature. 3W ON RETURN mode is used to ensure a minimum return temper- 23

24 ature to the boiler. In modes 4-W (four-way) FLOOR and RADIATOR, during adjustment, priority is to maintain the minimum return set temperature. Only after this condition the program allows the valve to open up and send a heating fluid for heating circuits. Attention! To correct adjustment four-way valve is required to connect two temperature sensors: supply and return. Return temperature sensor should be placed as close to the boiler. The manner of the heating system, in particular the place pumps, should ensure a continuous flow of water returning to the boiler lack of exchange cause incorrect measurements of temperature and mixing valve malfunction. [3] NAME OF THE SYSTEM - can be selected one of 20 predefined names for the heating circuit, in order to further distinguish if there will be more modules of valves. [4] TIME OF MOVEMENT it is the smallest amount of time that will move the valve actuator. Should be selected according to a full revolution of the valve. If TIME MOVEMENT is short and the time for a full rotation of the valve very long, the valve will be very slow to react to changes in temperature. If TIME MOVEMENT is too long compared to the time a full rotation, it will create fluctuations in temperature at the output of the valve, and may even make impossible to set desired temperature. [5] ADJUSTMENT RANGE - determines the range of temperatures before TEMPERATURE SETPOINT, at which the controller selects an automatically valve opening. Below SCOPE OF CONTROL valve is opened to maximum [6] WEEKLY PROGRAM - to set and enable and disable the weekly program of temperature correction for the heating circuit, in analogy to the setup described above, a program for the boiler temperature. IX. Error service. In case of error state like boiler overheating, refrigeration of the boiler, fire in the fuel container or sensor failure appropriate information will be shown on screen: a) Overheating the boiler - temperature of boiler s water above 92ºC. On the display appears the announcement of the boiler's overheating and the sound signal is generated. To chill the boiler switched off becomes blowing fan and feeder and turned on all pumps. When the temperature of boiler s water falls below 90ºC, the boiler comes back to the previous mode of the work. 24

25 b) Lighting oneself the fuel in the feeder or in the fuel container. The feeding device s temperature sensor, installed on the pipe of the feeder, controls his temperature. In the case of catching the fire the fuel in feeder or pipe that connects feeders,.possibly sensor failure, the display appears the announcement of the feeder failure and generated the continuous sound signal. The notification of this alarm causes disconnection the blower and the feeder and permanently incorporate the burner`s feeder. After the end of the alarm, the burner is OFF. d) Damage of the boiler s temperature sensor. Displayed becomes the screen with suitable information and the sound signal is generated. Switched off becomes blowing fan and feeder and turned on all pumps. The damage of the boiler's temperature sensor makes impossible the more far work of the controller. You should exchange the damaged sensor on new (one can temporarily use the DHW sensor as the boiler's sensor). e) Damage of the DHW temperature sensor. Displayed becomes the screen with suitable information and the sound signal is generated. After stepping out this breakdown the work of the boiler still is realized in the way provided for the work without the sensor. You should install the new sensor or, through switching off and renewed switching on the controller, give up the DHW sensor. f) Damage of the chimney temperature sensor. Displayed becomes the screen with suitable information and the sound signal is generated. Further operation of the burner is not possible - the burner switches to OFF. If you try to a proper message is displayed. Work of pumps runs normally, according to the settings Other faults and actions the user. Fault Cause User's action 1 The controller does not react to the user s action. Crashed microprocessor s system. 2 Blowing fan, pumps or feeder does not work. 3 The controller does not work. As a result of short circuit in the circuit of the damaged device the fuse to work.. As a result of short circuit in the power circuit the fuse to work. 25 Restart the controller using main switch. Check all equipment. Restart the controller using main switch. Restart the controller using main switch.

26 If the user lost the control over the burning's process because of the selection of unsuitable parameters or the regulator works irregularly, then you should restore producer's settings in the way described below. In the aim of restoration of default producer settings for the given type of the controller you should switch off the regulator and again switch it on. After the system's start will appear the take-off screen You should press the button to pass to the screen of restoring the producer's settings. Then confirm the desire of the restoration using button YES. 26

27 X. Connecting controller to central heating installation. Attention! The installation should be carried out by a person having appropriate qualifications, applying to all comments provided by manual on usage safety. Urządzenia oraz czujniki podłączyć następująco: a) Burner: completed three burner control cable plug, marked BURNER, connect to the appropriate terminals on the connector plate burner Screw and tighten the cable gland b) Storage tank feeder: zakończony wtykiem typu IEC przewód podajnika, podłączyć do gniazda Storage tank feeder, c) Pumps: One end of provided cord for central heating pump (optionally also for loading pump and circullation pump of DHWand valve pump), ended with plug type IEC, connect to the correct pump socket in the pump power panel. Another end of the wire, ended with blue, brown and yellow-green (safety core) cores, connect to the correct terminals in the pump junction box, d) Power cord: Power cord plug int 230V power socket only after connecting all the pumps and sensors. 27

28 e) Valve actuator the three-valve actuator connected to the attached plug-ins: middle common External - rotate left, rotate right Connect the plug into the socket VALVE ACTUATOR Warning! Orginal wires with IEC plugs are recommended. Before unplugging plug from the socket please hold the casing with the other hand to avoid damaging panel mount to the boiler casing. f) Sensors Warning! Sensor sockets are protected from accidentally slipping out he plug. To remove the sensor plug from the socket in the slot, press the button marked "PUSH". Improper removal can damage the plug or socket mounting on the panel.. Boiler temperature sensor. Ended with plug type XLR sensor wire end connect to BOILER SEN- SOR; sensor add to the wells measured in the boiler, if this is not possible otherwise permitted to attach the sensor to securely read the temperature of the water in the boiler; DHW tank temperature sensor. Ended with plug type XLR sensor wire end connect to DHW sensor socket in the sensor panel;; Place sensor in the correct mount in DHW tank; ROOM PANEL (option) two-wire cable connecting the room panel ROOMSTER with controller supplied must be connected to the XLR connector as described in the manual panel, zakończony wtykiem typu XLR koniec przewodu podłączyć do gniazda ROOM PANEL; Mixing valve sensors: valve and return connect the sensors according to the needs XLR terminated with the end of the sensor connected to sensor socket; sensor mounted on the heating pipe and isolated from the environment; 28

29 Additional valve module (option) The first external valve module is connected to the valve module slot using UTP cable terminated RJ45 plug. Subsequent modules connected to each other in series. XI. Installer Settings. To access the installer's settings, turn off and on again with the switch controller. After the startup screen appears with the version number of the program and buttons i. Click the button to go to the screen to enter the installer code. Enter the six-digit installer code (default ). If you enter the correct code, the system saves privileges, which was included the controller and move to the setting's screen. Transition to this screen can also be done by pressing a button from the main screen level. If the system was run with the installer's privileges then in the setting's screen are available separately the user parameters and the installer parameters. Dla instalatora dostępne są następujące parametry: [1] PUMP STARTS TEMPERATURE [ C] Parameter represents lowest boiler temperature at which pumps will work. All the pumps controlled directly by the controller turns on, if boiler temperature will be higher than set value and turns off, if boiler temperature will be 5 C lower than this value. Setting high enough value prevents condensation in boiler and helps in quick warm-up. However value must not be set higher than the lowest possible set point temperature for the boiler. [2]MODE CONTROL PID / Displacement Mode selected PID controller selects the amount of fuel and air vol- 29

30 ume based on PID calculation program, according to the demand for power boiler. This adjustment takes place in the range between the minimum allowable power and RATED POWER. The displacement control mode burner, depending on the current demand for power can operate at rated power or POWER REDUCED. [3] DHW HISTERESIS 2 10 [ C] Parameter describes permissible variance of temperature in DHW water container. DHW pump turns on when water temperature get lower than DHW TEMPERATURE minus DHW HISTERESIS. Too low values of this parameter result in too frequent turning on DHW pump and unstable work of boiler. Recommended values are 3 5 C. [4] DHW DESINFECTION. active / inactive Parameter allows turning on or off function of germs neutralization in DHW container. While active, once a week at Saturday from 2:00am to 4:00am DHW temperature is automatically set for 70 C and DHW PRIORITY is turned on. This parameter if turned off by default. [5] RATED POWER 6 30[kW] The controller is pre-configured to work with the strength of the burner plate. After installing the burner in the boiler must be adjusted to the maximum output power rating of the burner boiler. [6] REDUCED POWER 6 30[kW] Parameter specifies the power level adjustment mode reduced displacement. Additionally, during the post-combustion blower blows with the power corresponding to the reduced power of the burner. The recommended setting is approx. 50% POWER RATED. [7]HYSTERESIS WORK 1 10 [ C] This parameter defines the acceptable range of fluctuation of water temperature in the boiler. Regardless of the mode of regulation, if the boiler water temperature exceeds the set hysteresis work, burner enters the READY state, and died previously fuel and cleaning the grate. The burner will go to LIGHTING only when the water temperature falls below the setpoint hysteresis work The recommended setting is 3 5 C. [8] STARTING DOSE OF FUEL [s] This parameter defines the time before lighting the fuel supply, indirectly the size of the initial amount of fuel. This time should be set the starting dose of fuel weighs g. 30

31 [9] SUPPLY TO CIRCUIT Here set the heating circuit's power in the case of three-way valve connected module. If you choose the option that the boiler is not supplying directly any of the heating circuit (ie, that all heating circuits are powered by the valve modules), then the required temperature of the boiler is determined by the valve module. If the are several valve modules, the temperature of the boiler shall be established according to the valve, which needs the highest temperature.. [10] BUILT-IN VALVE. Enables or disables built-in mixing valve module If the built-in valve is switched off there is a possibility of direct cooperation between the controller and room`s controller, called ROOMSTER.involving the appropriate on and off the central heating. circulation pump, Attention! Before the start of the heating season it is recommended to purge photo-optical element located in the burner and control the correctness of its actions 31

32 XII. Working conditions. Ambient temperature 0 40 C Supply voltage 230V 50Hz Power consumption 4 W Load capacity of outputs: Burner (feeder, blower, heater) Central heating circulation pump DHW circulation pump Mixing valve pump DHW charge pump Mixing valve Storage tank feeder 650 VA 100 VA 100 VA 100 VA 100 VA 50 VA 100 VA This device is marked as required by the Act dated 29 July 2005 on used electric and electronic equipment Journal of Laws No 180, section The symbol placed on the product or documents attached to it means that the product is not classified as household waste. Dispose of the device by taking it to relevant disposal point for recycling electric and electronic components. The device should be disposed of in compliance with local waste disposal regulations. By disposing this device properly you will contribute to limiting risk of adverse impact of the product on environment and human health that could be present if the device was disposed of improperly. Additional information regarding disposal and recycling of the device can be obtained in local town hall, in municipal waste disposal and recycling center or at the supplier.. 32

Declaration of Conformity No. 27/2008

Declaration of Conformity No. 27/2008 ST-44 USER S MANUAL ST-45 User's Manual Declaration of Conformity No. 27/2008 Hereby, we declare under sole responsibility that the ST-45 230V 50Hz thermoregulator manufactured by TECH, ul. St. Batorego

More information

OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER. Version DC19

OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER. Version DC19 OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER Version DC19 1. Application. Controller RK-2006LPP is designed for temperature control of solid fuel fired water boilers

More information

Electronic Pellet Burner Controller NPBC-V3-1

Electronic Pellet Burner Controller NPBC-V3-1 Electronic Pellet Burner Controller NPBC-V3- SOFTWARE VERSION 3.2/3. page of 3 CHANGES IN THE TECHNICAL AND USER GUIDE OR IN THE SOFTWARE VERSION Technical and User Guide's version Changes Page 2.8. The

More information

ST 53.1 User s manual

ST 53.1 User s manual Tech - 1 - ST 53.1 User s manual Table of contents I. Safety... 3 II. Description... 4 III. Installation... 4 IV. Operating the Controller... 6 IV.a) Principle of Operation... 6 IV.b) Control... 6 V. Controller

More information

Declaration of Conformity no. 56/2012

Declaration of Conformity no. 56/2012 tech -1- ST 280 Instructions manual Declaration of Conformity no. 56/2012 We, TECH Sp.j., with our registered company office at Wieprz 1047A, 34-122 Wieprz, Poland declare under our full responsibility

More information

Electronic Pellet Burner Controller NPBC-V3M

Electronic Pellet Burner Controller NPBC-V3M Electronic Pellet Burner Controller NPBC-V3M SOFTWARE VERSION 3.3a/3.2 page of 27 CHANGES IN THE USER MANUAL OR IN THE CONTROLLER'S SOFTWARE Version of the user manual Changes Page 2.2. The software version

More information

ecomax 200 W Boiler regulator FOR SOLID FUEL BOILERS WITH A FAN OPERATION AND MAINTENANCE MANUAL ISSUE:

ecomax 200 W Boiler regulator FOR SOLID FUEL BOILERS WITH A FAN OPERATION AND MAINTENANCE MANUAL ISSUE: Boiler regulator ecomax 200 W FOR SOLID FUEL BOILERS WITH A FAN OPERATION AND MAINTENANCE MANUAL ISSUE: 1.3 APPLICABLE TO SOFTWARE 10.034 10.035 10.036 2010-04-14 TABLE OF CONTENTS 1 Safety... 4 2 General

More information

TECH. Declaration of conformity no 23/2007

TECH. Declaration of conformity no 23/2007 ST-81 USER'S MANUAL TECH Declaration of conformity no 23/2007 We, company Tech, ul. St. Batorego 14, 34-120 Andrychów declare with full responsibility that ST-81, 230 V, 50 Hz thermo regulator that we

More information

GH10PA USER MANUAL. Program version 01 MANUAL FOR CONTROLLER FOR CONTROLLING CENTRAL HEATING BOILERS FIRED WITH PELLETS AND OATS

GH10PA USER MANUAL. Program version 01 MANUAL FOR CONTROLLER FOR CONTROLLING CENTRAL HEATING BOILERS FIRED WITH PELLETS AND OATS MANUAL FOR CONTROLLER GH10PA FOR CONTROLLING CENTRAL HEATING BOILERS FIRED WITH PELLETS AND OATS Program version 01 USER MANUAL We request that users carefully study applicable Instructions before connecting

More information

INSTRUCTION FOR THE USER THC V E OIL BLU

INSTRUCTION FOR THE USER THC V E OIL BLU INSTRUCTION FOR THE THC V E OIL BLU CONTENTS General safety information 4 Precautions 4 Control panel 5 Mode selection 8 User levels 10 Start-up 12 Temporary shutdown 15 Preparing for extended periods

More information

TECHNICAL INSTRUCTIONS USE AND MAINTENANCE

TECHNICAL INSTRUCTIONS USE AND MAINTENANCE TECHNICAL INSTRUCTIONS USE AND MAINTENANCE Cm Pelet-set For boilers CentroPlus 25/35 and CentroPlus-B 25/35 (solid fuel and wood pellets fuel firing) TUPSCP-K-11-2016-ENG CONTENTS 1.Introduction 2. Status

More information

USE AND MAINTENANCE. Cm Pelet-set (60-90 kw) TECHNICAL INSTRUCTIONS

USE AND MAINTENANCE. Cm Pelet-set (60-90 kw) TECHNICAL INSTRUCTIONS CENTROMETAL d.o.o. Glavna 12 40306 Macinec Croatia tel: +385 40 372 600; fax : +385 40 372 611 TECHNICAL INSTRUCTIONS USE AND MAINTENANCE Cm Pelet-set (60-90 kw) For boilers: EKO-CK P 70-110 TUPS-90K-09-2015-E-N-eng

More information

INSTRUCTION MANUAL & SERVICE MANUAL ORLIGNO 400

INSTRUCTION MANUAL & SERVICE MANUAL ORLIGNO 400 INSTRUCTION MANUAL & SERVICE MANUAL ORLIGNO 400 Content 1. Delivery......................................................................... 3 2. Installation and assembly.........................................................

More information

BIO 30, BIO 50, BIO 95

BIO 30, BIO 50, BIO 95 BIO 30, BIO 50, BIO 95 STEEL BOILER FOR HEATING WITH BURNER AND AUTOMATIC FUEL FEEDER BIO 30-50 kw POWER USER MANUAL, USER GUIDE, INSTALLATION, USE AND MAINTENANCE OF THE BOILER 1. Introduction Biokaitra

More information

Operation manual. Daikin Altherma Low temperature split EHBH04CBV EHBH08CBV EHBH11CBV EHBH16CBV

Operation manual. Daikin Altherma Low temperature split EHBH04CBV EHBH08CBV EHBH11CBV EHBH16CBV EHBH04CBV EHBH08CBV EHBH11CBV EHBH16CBV EHVH04S18CBV EHVH08S18CBV EHVH08S26CBV EHVH11S26CBV EHVH16S26CBV English Table of contents Table of contents 1 About this document 2 2 About the system 2 2.1 Components

More information

USE AND MAINTENANCE. Cm Pelet-set TECHNICAL INSTRUCTIONS. (14-35 kw) For boilers: EKO-CK P (EKO-CK 20-40) EKO-CKB P (EKO-CKB 20-40)

USE AND MAINTENANCE. Cm Pelet-set TECHNICAL INSTRUCTIONS. (14-35 kw) For boilers: EKO-CK P (EKO-CK 20-40) EKO-CKB P (EKO-CKB 20-40) TECHNICAL INSTRUCTIONS USE AND MAINTENANCE Cm Pelet-set (14-35 kw) For boilers: EKO-CK P 20-40 (EKO-CK 20-40) EKO-CKB P 20-40 (EKO-CKB 20-40) TUPS-K-02-2011-E-N-ENG CONTENTS 1. Introduction....... 2. Status

More information

ecoal.pl V3.5 Adaptive controller Operating manual Kutno Software version:

ecoal.pl V3.5 Adaptive controller Operating manual Kutno Software version: ecoal.pl V3.5 Adaptive controller Software version: 1.1.20.0 Operating manual Kutno 2016-10-07 Table of Contents 1. Safety...3 2. Assembly... 5 2.1 Environmental conditions...5 2.2 Control panel setup...5

More information

Operation manual. Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3

Operation manual. Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3 EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3 English Table of Contents Table of Contents 1 About this document 2 2 About the system 2 2.1 Components in a typical system layout... 2 3 Operation 3 3.1 Overview:

More information

heat interface units A BOILER WITHOUT A FLAME

heat interface units A BOILER WITHOUT A FLAME A BOILER WITHOUT A FLAME heat interface units Communal Heat Networks A central boiler house will generate heat which is distributed through a network of pipe to each home or apartment in the building.

More information

GA01HC-02. Service manual. Room Panel. Programme version 01a. Operating with GH07EA regulator for controlling electrode boilers

GA01HC-02. Service manual. Room Panel. Programme version 01a. Operating with GH07EA regulator for controlling electrode boilers Room Panel GA01HC-02 Operating with GH07EA regulator for controlling electrode boilers Programme version 01a Service manual We request that users carefully study applicable Instructions before connecting

More information

Room panel. for ecomax800 R or T regulators. OPERATION AND MAINTENANCE MANUAL ISSUE: 1.3 APPLICABLE TO SOFTWARE: v , v , v08.21.

Room panel. for ecomax800 R or T regulators. OPERATION AND MAINTENANCE MANUAL ISSUE: 1.3 APPLICABLE TO SOFTWARE: v , v , v08.21. Room panel ecoster 200 for ecomax800 R or T regulators OPERATION AND MAINTENANCE MANUAL ISSUE: 1.3 APPLICABLE TO SOFTWARE: v08.21.014, v08.21.015, v08.21.016 2010-08-31 TABLE OF CONTENTS 1. SAFETY...

More information

ecomax 800, model R1 Boiler regulator Dzia Zintegrowanego Systemu Zarz dzania version: ec FOR SOLID FUEL-FIRED BOILERS WITH FEEDING SCREW

ecomax 800, model R1 Boiler regulator Dzia Zintegrowanego Systemu Zarz dzania version: ec FOR SOLID FUEL-FIRED BOILERS WITH FEEDING SCREW Boiler regulator ecomax 800, model R1 version: ec Dzia Zintegrowanego Systemu Zarz dzania FOR SOLID FUEL-FIRED BOILERS WITH FEEDING SCREW SERVICE AND ASSEMBLY MANUAL ISSUE: 1.2 APPLICABLE TO SOFTWARE:

More information

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

1 DOCUMENT REVISION CONTROL ELEMENTS... 9 CONTENTS Contents 1 DOCUMENT REVISION... 8 2 SOFTWARE VERSION... 8 3 BASIC DESCRIPTION... 8 4 CONTROL ELEMENTS... 9 4.1 BASIC DISPLAYS...10 4.2 CONTROL KEYS...11 4.2.1 Rotary button (Press / Turn)...11

More information

USER MANUAL ACQUAHOME 32 B BLU

USER MANUAL ACQUAHOME 32 B BLU USER MANUAL ACQUAHOME 32 B BLU Dear Customer, Thank you for preferring a T heating unit, a modern, high-quality product that is able to guarantee your maximum well-being for a long period of time, with

More information

Operating manual. Pellet boiler. Orlan Pellet ISO 9001

Operating manual. Pellet boiler. Orlan Pellet ISO 9001 Operating manual Pellet boiler Orlan Pellet ISO 9001 Contens 1. Boiler s use...................................................................... 3 2. Boiler s way of working...........................................................

More information

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A... 70 80 99-00-O Residential Gas Condensing Boiler ZBR//8/35/4-3A... ZWB8/35/4-3A... 70 80 993 (03/03) CA/US Operating Instructions Contents Contents Key to symbols and safety instructions............................

More information

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump. English Table of contents Table of contents About this document About the system. Components in a typical system layout... 3 Operation 3 3. Overview: Operation... 3 3. The user interface at a glance...

More information

USE AND MAINTENANCE. Cm Pelet-set TECHNICAL MANUAL. CENTROMETAL d.o.o. Glavna Macinec Croatia tel: ; fax :

USE AND MAINTENANCE. Cm Pelet-set TECHNICAL MANUAL. CENTROMETAL d.o.o. Glavna Macinec Croatia tel: ; fax : CENTROMETAL d.o.o. Glavna 12 40306 Macinec Croatia tel: +385 40 372 600; fax : +385 40 372 611 TECHNICAL MANUAL USE AND MAINTENANCE Cm Pelet-set TUPS-3-2008-eng-E-N CONTENT 1. Introduction.. 2. Delivery

More information

THESE INSTRUCTIONS SHOULD BE READ CAREFULLY AND RETAINED FOR FUTURE REFERENCE.

THESE INSTRUCTIONS SHOULD BE READ CAREFULLY AND RETAINED FOR FUTURE REFERENCE. TE-700I Installation and Operating Instructions Haverland TOWELS THESE INSTRUCTIONS SHOULD BE READ CAREFULLY AND RETAINED FOR FUTURE REFERENCE. GENERAL RECOMMENDATIONS: * Please read these installation

More information

Operating instructions

Operating instructions Operating instructions For the operator Operating instructions ecotec plus Gas-fired wall-hung high-efficiency boiler GB, IE Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Telefon

More information

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump. EGSQH0S8AA9W English Table of contents Table of contents About this document About the system Components in a typical system layout Operation Overview: Operation The user interface at a glance Buttons

More information

Monitoring Software for NPBC-V3M-1 User Manual

Monitoring Software for NPBC-V3M-1 User Manual Monitoring Software for NPBC-V3M-1 User Manual User Manual ver 1.5 page 1 of 14 Contents: 1. Introduction... 3 2. Requirements... 3 3. Installing the software... 4 4. Connecting the devices... 4 5. Updating

More information

SOLARCOMP 951 CONTROLLER FOR SOLAR COLLECTORS

SOLARCOMP 951 CONTROLLER FOR SOLAR COLLECTORS SOLARCOMP 951 CONTROLLER FOR SOLAR COLLECTORS Installation and Operating Instructions for model u7.x, Rev. 1, April 2014 Pb Safety Instructions Before installation read these Operation and Installation

More information

bruli.pl V3.5 Operating manual Kutno Software version:

bruli.pl V3.5 Operating manual Kutno Software version: bruli.pl V3.5 Software version: 1.1.20.0 Operating manual Kutno 2016-10-07 Table of Contents 1. Safety...3 2. Assembly...5 2.1 Environmental conditions...5 2.2 Control panel setup...5 2.3 Connecting the

More information

OPERATION MANUAL. Indoor unit for hot water heat pump system and options EKHBH016AB EKHBX016AB

OPERATION MANUAL. Indoor unit for hot water heat pump system and options EKHBH016AB EKHBX016AB OPERATION MANUAL Indoor unit for hot water heat pump system and options EKHBH016AB EKHBX016AB EKHBH016AB*** EKHBX016AB*** Indoor unit for hot water heat pump system and options CONTENTS Page Introduction...1

More information

Boiler regulator ecomax810p3-l TOUCH

Boiler regulator ecomax810p3-l TOUCH Boiler regulator ecomax810p3-l TOUCH FOR PELLET BOILERS A, B, C - functions which are available in modules, respectively: A, B, C SERVICE AND ASSEMBLY MANUAL ISSUE: v1.1 APPLICABLE TO SOFTWARE: MODULE

More information

Control Application. Supplement - ACVMax

Control Application. Supplement - ACVMax prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

BOILER CONTROLLER COMPACT

BOILER CONTROLLER COMPACT BOILER CONTROLLER COMPACT page 2 Index Index 1 General information 5 1.1 Introduction 5 1.2 Features 5 1.3 Safety precautions 7 1.4 Disposal of old equipment 8 2 Connecting to the system 9 2.1 General

More information

Operation manual. Daikin Altherma Low temperature split EHBH04CB EHBH08CB EHBH11CB EHBH16CB EHBX04CB EHBX08CB EHBX11CB EHBX16CB

Operation manual. Daikin Altherma Low temperature split EHBH04CB EHBH08CB EHBH11CB EHBH16CB EHBX04CB EHBX08CB EHBX11CB EHBX16CB EHBH04CB EHBH08CB EHBHCB EHBH6CB EHBX04CB EHBX08CB EHBXCB EHBX6CB EHVH04S8CB EHVH08S8CB EHVH08S6CB EHVHS8CB EHVHS6CB EHVH6S8CB EHVH6S6CB EHVX04S8CB EHVX08S8CB EHVX08S6CB EHVXS8CB EHVXS6CB EHVX6S8CB EHVX6S6CB

More information

prestige Control Application Supplement - ACVMax

prestige Control Application Supplement - ACVMax 2015-10 Prestige ACVMax Control Sup 12-14-15_ACVMax_Control 12/15/15 7:36 AM Page 1 prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory

More information

OPERATION MANUAL RK-2001W2 SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER. Version 9A15

OPERATION MANUAL RK-2001W2 SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER. Version 9A15 OPERATION MANUAL RK-2001W2 SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER Version 9A15 1. Application. RK-2001W2 controller is a controller designed for temperature control of solid fuel fired boilers.

More information

Cm Pelet-set (60-90 kw)

Cm Pelet-set (60-90 kw) CENTROMETAL d.o.o. Glavna 12 40306 Macinec Croatia tel: +385 40 372 600; fax : +385 40 372 611 TECHNICAL INSTRUCTIONS FOR THE COMMISSIONING AND ADJUSTMENT Cm Pelet-set (60-90 kw) For boilers: EKO-CK P

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

Modulating clock thermostat

Modulating clock thermostat EN Digital timer thermosatat Modulating clock thermostat Installation and Service Manual 123189-AB Contents 1 Preface...4 1.1 General...4 2 Location of the installation...5 2.1 Position of the regulator...5

More information

TPOne-B. Electronic Programmable Room Thermostat. Installation Guide. Danfoss Heating

TPOne-B. Electronic Programmable Room Thermostat. Installation Guide. Danfoss Heating TPOne-B Electronic Programmable Room Thermostat Danfoss Heating Installation Guide TPOne is an intelligent programmable heating control made easy. TPOne includes features which are designed to save energy.

More information

User Manual for model

User Manual for model User Manual for model RKA 24 /20 Wall mounted storage combi boiler premix condensing boiler CE 0694 Technical specification RADIANT BRUCIATORI S.p.A. Montelabbate RKA 24.20 - RAD - ING - MAN.UT - 1309.1

More information

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM Thank you for choosing a DOMUSA TEKNIK heating boiler. Within the product range offered by DOMUSA TEKNIK you have chosen BioClass HM model. With a suitable

More information

EBC20. Instructions for fitting, installation and operation. Read and save these instructions!

EBC20. Instructions for fitting, installation and operation. Read and save these instructions! EBC20 UK Instructions for fitting, installation and operation Read and save these instructions! 2 3002878 EBC20 UK 290415 1. Product information............................................... 4 1.1 Delivery.............................................................

More information

For the owner and the heating engineer. Operating and Installation Manual VRC 400. Programmable weather compensator with separat HW time control

For the owner and the heating engineer. Operating and Installation Manual VRC 400. Programmable weather compensator with separat HW time control For the owner and the heating engineer Operating and Installation Manual VRC 400 Programmable weather compensator with separat HW time control GB Contents Contents Notes on the documentation..... 4 Symbols

More information

USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel

USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel PU SENS 01 CONTENTS Safety requirements... 3 Purpose... 4 Technical data... 4 Overall dimensions [mm]... 4 Mounting and set-up... 5

More information

Cm Pelet-set TECHNICAL INSTRUCTIONS FOR THE COMMISSIONING AND ADJUSTMENT. (14-35 kw) For boilers: EKO-CKB P (EKO-CKB 20-40)

Cm Pelet-set TECHNICAL INSTRUCTIONS FOR THE COMMISSIONING AND ADJUSTMENT. (14-35 kw) For boilers: EKO-CKB P (EKO-CKB 20-40) TECHNICAL INSTRUCTIONS FOR THE COMMISSIONING AND ADJUSTMENT Cm Pelet-set (14-35 kw) For boilers: EKO-CK P 20-40 (EKO-CK 20-40) EKO-CKB P 20-40 (EKO-CKB 20-40) TUPS-M-11-2015-E-N-ENG CONTENTS 1. Introduction.....

More information

95M-200. Gas-Fired Direct Vent Modulating Hot Water Boiler. Control Manual And Troubleshooting Guide. P/N , Rev.

95M-200. Gas-Fired Direct Vent Modulating Hot Water Boiler. Control Manual And Troubleshooting Guide. P/N , Rev. 95M-200 Gas-Fired Direct Vent Modulating Hot Water Boiler Control Manual And Troubleshooting Guide P/N 24000604, Rev. C [04/09] WARNING! Revise boiler control parameters only if you fully understand the

More information

Controller PCSol 300 FOR SOLAR COLLECTORS. INSTALLATION AND OPERATION MANUAL 62.X.2 REVISION SOFTWARE

Controller PCSol 300 FOR SOLAR COLLECTORS.  INSTALLATION AND OPERATION MANUAL 62.X.2 REVISION SOFTWARE Controller PCSol 300 FOR SOLAR COLLECTORS www.econet24.com PUMP PUMP CIRCULATION PUMP ROTATION CONTROL CIRCULATION PROGRAM HEATER SUPPORT HEATER PROGRAM SIMPLE IN USE INTELLIGENT ALARM CLOCK 10 DAYS CLOCK

More information

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data. ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data. The RVA 46 Zone Controller can only be used in conjunction with a RVA47 controlled boiler installation. The RVA46 controller

More information

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

User instructions DHP-AT

User instructions DHP-AT User instructions DHP-AT VUGFC202 If these instructions are not followed during installation and service, Danfoss A/S liability according to the applicable warranty is not binding. Danfoss A/S retains

More information

1. COMMISSIONING OF THE BOILER en DESCRIPTION FUNCTION BUTTON DESCRIPTION SYMBOL DISPLAY

1. COMMISSIONING OF THE BOILER en DESCRIPTION FUNCTION BUTTON DESCRIPTION SYMBOL DISPLAY RC 06 0712_1403 it - Istruzioni TELECONTROLLO en - Remote controller instruction hu - Utasítás TÁVVEZÉRLÉS ru - Руководство по эксплуатации pl - Instrukcja obsługi { 1. Commissioning of the boiler 26 2.

More information

Programmable Thermostat

Programmable Thermostat Set & $ave Programmable Thermostat Installation and Operation Manual English Model 44360 Form# 42710-01 20091204 2009 Hunter Fan Co. 2 Table of Contents Important Information... 5 Tools... 6 Uninstalling

More information

Sensor Control Panel

Sensor Control Panel USER S MANUAL PU SENS 01 Sensor Control Panel V55-6EN-03(SENS).indd 1 18.08.2015 10:37:16 2 PU SENS 01 CONTENTS Safety Requirements 2 Main Technical Data 3 Control Panel Mounting 3 Control Panel Operation

More information

ProCon Boiler Controller Commissioning Quick Reference Guide

ProCon Boiler Controller Commissioning Quick Reference Guide ProCon Boiler Controller Commissioning Quick Reference Guide This sheet is intended as a quick reference guide and should be read in conjunction with the operating and maintenance manual for the boiler

More information

INTRODUCTION... VI I. IOS... 1

INTRODUCTION... VI I. IOS... 1 Contents INTRODUCTION... VI PURPOSE... VI KEY FUNCTIONS OF THE SYSTEM... VI TERMS AND ABBREVIATIONS... VII SMART HEATER APPLICATION:... X ios:... x Android:... x Windows:... x PRIVACY POLICY... XI ADAX

More information

INTRODUCTION... VI I. IOS... 1

INTRODUCTION... VI I. IOS... 1 Contents INTRODUCTION... VI PURPOSE... VI KEY FUNCTIONS OF THE SYSTEM... VI TERMS AND ABBREVIATIONS... VII SMART HEATER APPLICATION:... X ios:... x Android:... x Windows:... x PRIVACY POLICY... XI ADAX

More information

/2010 US/CA

/2010 US/CA 6 720 646 148-11/2010 US/CA (en) For the user User s Instructions Condensing gas boiler Logamax plus GB162-L.B. 80 kw/100 kw Please read thoroughly before operating This manual is available in the English

More information

multimatic Operating instructions AT, BE (de), CH (de), DE VRC 700f/4

multimatic Operating instructions AT, BE (de), CH (de), DE VRC 700f/4 Operating instructions multimatic VRC 700f/4 AT, BE (de), CH (de), DE Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Tel. +49 21 91 18 0 Fax +49 21 91 18 2810 info@vaillant.de

More information

Operating instructions

Operating instructions Operating instructions Capriz 2 24c 28c GB, IE Contents Contents 1 Safety... 3 1.1 Action-related warnings... 3 1.2 Intended use... 3 1.3 General safety information... 4 2 Notes on the documentation...

More information

INSTRUCTION MANUAL REMOTE CONTROL DEVICE EASYREMOTE

INSTRUCTION MANUAL REMOTE CONTROL DEVICE EASYREMOTE INSTRUCTION MANUAL REMOTE CONTROL DEVICE EASYREMOTE Technical features Guide to LCD symbols Guide to keys Technical features Supply by communication bus Number of temperature levels 2 (DAY / NIGHT) Temperature

More information

Multi Boiler Guide. Kit #

Multi Boiler Guide. Kit # Multi Boiler Guide Kit # 550002186 Technical Support @ 800-325-5479 Phone: (315) 797-1310 Fax: (866) 432-7329 e-mail: info@ecrinternational.com web site: www.ecrinternational.com Information and specifications

More information

Bosch. Gas Condensing Boiler. Applications Manual. 100, 151 Combi Boiler 57, 100, 131, 151 Heating Boiler

Bosch. Gas Condensing Boiler. Applications Manual. 100, 151 Combi Boiler 57, 100, 131, 151 Heating Boiler WARNING: Improper installation, setup, modification, operation or maintenance of the heating system can cause personal injury and property damage. Follow each appliances' instructions precisely. For assistance

More information

ENGLISH. REMOTE CONTROL / ROOM THERMOSTAT Wireless INSTALLATION SERVICING AND USER MANUAL

ENGLISH. REMOTE CONTROL / ROOM THERMOSTAT Wireless INSTALLATION SERVICING AND USER MANUAL ENGLISH REMOTE CONTROL / ROOM THERMOSTAT Wireless INSTALLATION SERVICING AND USER MANUAL DANGER! Serious danger to safety and health ATTENTION! Possible dangerous situation for the product and the environment

More information

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

- Data Brochure Universal Reset Module 422

- Data Brochure Universal Reset Module 422 - Data Brochure Universal Reset Module 422 D 422 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS...

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS... User Manual Contents 1 DOCUMENT REVISION... 4 2 SOFTWARE VERSION... 4 3 BASIC DESCRIPTION... 4 4 BASIC OVERVIEW OF HYDRAULIC DIAGRAMS... 5 4.1 BOILER NOT CONTROLLED BY THE CONTROLLER:... 5 4.2 BOILER CONTROLLED

More information

Operating instructions

Operating instructions The energy you need Operating instructions Betacom 3 24c -A (H-GB) 30c -A (H-GB) GB, IE Contents Contents 1 Safety... 3 1.1 Action-related warnings... 3 1.2 Intended use... 3 1.3 General safety information...

More information

INSTRUCTIONS FOR USE OF COMBINED BOILER INTENDED FOR COMBUSTION OF BOTH PELLETS AND SOLID FUEL ABC COMBO

INSTRUCTIONS FOR USE OF COMBINED BOILER INTENDED FOR COMBUSTION OF BOTH PELLETS AND SOLID FUEL ABC COMBO INSTRUCTIONS FOR USE OF COMBINED BOILER INTENDED FOR COMBUSTION OF BOTH PELLETS AND SOLID FUEL ABC COMBO .Technical specifications Boiler power DESCRIPTION Water content in a boiler Required draft Supply

More information

Installation and user manual

Installation and user manual Installation and user manual Please read carefully and retain for future reference Models EcoHeat: C3, C5, C6, C8, C9, C11, C12 Rev.1_09-07-15 Page 1 Table of Contents 1 IMPORTANT: WARNINGS 1.1 GENERAL

More information

USERS MANUAL FOR GAS BOILERS

USERS MANUAL FOR GAS BOILERS USERS MANUAL FOR GAS BOILERS PLEASE READ THE MANUAL CAREFULLY: IT CONTAINS IMPORTANT INFORMATION REGARDING SAFETY, INSTALLATION, USE AND MAINTENANCE OF THE APPLIANCE MODELS: NOVADENS 24 NOVADENS 24C NOVADENS

More information

G a

G a G2474 74 319 0081 0 a en Installation Instructions Heating controllers RVP3... Installation Place of installation In a dry room, e.g. in the boiler room Mounting choices: Control cabinet (in the front,

More information

TermEfekt USER S MANUAL AIR HEATER. Model PGA 14

TermEfekt USER S MANUAL AIR HEATER. Model PGA 14 Przedsiębiorstwo Produkcyjno-Wdrożeniowe ARAJ sp. z o.o. 55-080 Kąty Wrocławskie, ul. Mireckiego 30 POLAND USER S MANUAL AIR HEATER TermEfekt Model PGA 14 Kąty Wrocławskie, 2004 Product identification

More information

CS027 User Instructions

CS027 User Instructions CS027 User Instructions Battery Powered 7 Day Programmable Room Thermostat Programmable room thermostats are widely recognised as one of the best ways in which to control central heating. The CS027 programmable

More information

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller Mounting and Operating Instructions Electronics from SAMSON EB 5610 EN Firmware version 1.40 Edition December 2014 Controller

More information

Digital Thermostat Models: VS30W and VS30B

Digital Thermostat Models: VS30W and VS30B it600 VS30W - VS30B Installer - User Manual 015_Layout 1 28.07.2014 10:28 Digital Thermostat Models: VS30W and VS30B INSTALLER / USER MANUAL it600 VS30W - VS30B Installer - User Manual 015_Layout 1 28.07.2014

More information

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE)

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE) INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE) Thank you for choosing a DOMUSA TEKNIK heating boiler. Within the product range offered by DOMUSA TEKNIK you have chosen BioClass

More information

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. The RVA63 controller can be utilized to control the following system configurations via LPB communication. Equipment Required

More information

Technical Data Manual

Technical Data Manual VITOTRONIC 300 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating circuits Technical Data Manual Vitotronic 300 Model KW3, Part No. Z001 231 For operation

More information

Cooling kit UTW-KCL*D. Installation instructions FR NL EN DE IT. (Compatible with high-flow circulation pump, code UTW-PHF*D)

Cooling kit UTW-KCL*D. Installation instructions FR NL EN DE IT. (Compatible with high-flow circulation pump, code UTW-PHF*D) Document n 1541-1 ~ 24/04/2012 FR NL EN DE IT ES PT Cooling kit UTW-KCL*D (Compatible with high-flow circulation pump, code UTW-PHF*D) 3 8 7 Installation instructions intended for the professional technician

More information

Boiler controller S-Tronic Plus

Boiler controller S-Tronic Plus Operating Instructions Boiler controller S-Tronic Plus Version 50.0 - Build 05.0 Translation of the original German operating instructions for technicians and operators Read and follow the instructions

More information

CentaurStat 7 User Operating Instructions Central Heating Programmable Room ThermoStat

CentaurStat 7 User Operating Instructions Central Heating Programmable Room ThermoStat CentaurStat 7 User Operating Instructions Central Heating Programmable Room ThermoStat The Centaurstat 7 is a programmable room thermostat that provides precise temperature control from a single point

More information

User Manual RBS 24. for model CE series ENERGY. Wall mounted instantaneous combi boiler room sealed chamber

User Manual RBS 24. for model CE series ENERGY. Wall mounted instantaneous combi boiler room sealed chamber User Manual for model RBS 24 series ENERGY Wall mounted instantaneous combi boiler room sealed chamber CE 0694 RBS 24 - SERIE ENERGY - RAD - ING - MAN.UT - 1407.1 - DIGITECH TR - MIAH6 - E04 Technical

More information

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502* User's Guide VI.7C.C5.02 2005.09 C66 *vi7cc502* *087R8069* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8069* *vi7cc502* Mixing controller with PI controlled

More information

Ultracom cxi. Instructions for Use. High Efficiency Condensing System Boilers. To b e l e f t w i t h t h e u s e r.

Ultracom cxi. Instructions for Use. High Efficiency Condensing System Boilers. To b e l e f t w i t h t h e u s e r. Ultracom cxi High Efficiency Condensing System Boilers Instructions for Use To b e l e f t w i t h t h e u s e r WARNING GAS LEAK OR FAULT Turn off the gas emergency control valve immediately. Eliminate

More information

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL The SF-10 Temperature Control () is an efficient boiler operator with a digital LCD display with backlight, a boiler pump output, and an alarm. The

More information

Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert)

Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert) Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert) P.N. 7876C (export) February 12, 2015 For Spas equipped with BP2100, BP6013 controllers and Spa Touch panel. Spa

More information

CHESNEY S. Bio-Ethanol Installation & User Manual. model: EFB1200. Issue 01

CHESNEY S. Bio-Ethanol Installation & User Manual. model: EFB1200. Issue 01 CHESNEY S Bio-Ethanol Installation & User Manual model: EFB1200 Issue 01 1 2 Thank you for choosing this Chesney s Bio-Ethanol fire. Please read this information guide carefully in order to safely install,

More information

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602* User's Guide VI.7C.E6.02 2005.09 C37 *VI7CE602* *087R8070* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8070* *VI7CE602* Mixing controller with ON / OFF controlled

More information

Programmable Interactive User Manual

Programmable Interactive User Manual 67504B 02/16 (ALA) DH E RT 102/BW Programmable Interactive User Manual www.schluter.com 1. Contents 2. Menu Overview..............3 3. Introduction................ 4 4. General Operation............5 4.1.Navigation

More information

- Data Brochure Universal Reset Module 423

- Data Brochure Universal Reset Module 423 - Data Brochure Universal Reset Module 423 D 423 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

CentroPelet ZV14 TECHNICAL INSTRUCTIONS HEATING TECHNIQUE. for regulation, use and maintenance of pellet stove

CentroPelet ZV14 TECHNICAL INSTRUCTIONS HEATING TECHNIQUE. for regulation, use and maintenance of pellet stove HEATING TECHNIQUE Centrometal d.o.o. - Glavna 12, 40306 Macinec, Croatia, tel: +385 40 372 600, fax: +385 40 372 611 TECHNICAL INSTRUCTIONS for regulation, use and maintenance of pellet stove CentroPelet

More information

Installation & User s Instructions

Installation & User s Instructions Installation & User s Instructions 8 080 shown Part No. 00 day Wired Digital Programmer & Room Sensor Part No. 080 day Wireless Digital Programmer & Room Sensor Part No. 00 hr Wireless Digital Programmer

More information

Operating instructions

Operating instructions Operating instructions For the operator Operating instructions HOME SYSTEM GB, IE Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Tel. +49 21 91 18 0 Fax +49 21 91 18 28 10 info@vaillant.de

More information

PROGRAMMABLE 7-DAY RF THERMOSTAT

PROGRAMMABLE 7-DAY RF THERMOSTAT PROGRAMMABLE 7-DAY RF THERMOSTAT Installation and user instruction This instructions to be retained by the user 1 Thank you for choosing Beretta s radio frequency (RF) Radiostat. This central heating control

More information