HydroZone Installation Manual
|
|
- Shanon Hardy
- 6 years ago
- Views:
Transcription
1 Hydronic omfort Zoning System 4, 8, and 12 Zone apacity Installation Information HydroZone Installation Manual Thermostat Installation Electrical Startup rocedures Wiring Schematics IM1550EW 11/10
2
3 HDZNE INSTALLATIN MANUAL Table of ontents Model Nomenclature eneral Installation Information... 5 Dimensional Data Electrical atings Electrical Wiring... 7 Wiring Schematics Thermostat Installation ontroller peration System Startup and heckout arts Lists... 21
4 HDZNE INSTALLATIN MANUAL Model Nomenclature 1-2 HZ A S 8 N Model Type HZ = HydroZone ontrol anel Number of Zones 04 = 4 Zone 08 = 8 Zone 12 = 12 Zone Vintage A = urrent Future N = None ontroller N = Standard with ontroller E = 12 Zone Expansion - No ontroller Zone utput Voltage A = 24 VA (Zone Valves) 9 = 115 VA (Zone umps) Zone Thermostat Zone Thermostat HydroZone ontroller utdoor Air Sensor Zone ump/valves Backup Heat - W H alls - 1 and 2 Load lumbing Accessory Box adiant Floor Tank Sensor Source lumbing eotank Envision Air Handler 4
5 HDZNE INSTALLATIN MANUAL eneral Installation Information Safety onsiderations Installing and servicing heating and air conditioning equipment can be hazardous due to system electrical components. nly trained and qualified service personnel should install, repair or service heating and air conditioning equipment. When working on equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. WANIN: Before performing service or maintenance operations on the system, turn off main power switches to the indoor unit. Turn off accessory heater power switch if applicable. Electrical shock could cause serious personal injury. HydroZone ontrol anel Locate the HydroZone panel in an indoor area that has enough space for service personnel to perform maintenance or repair. rovide sufficient room to make electrical connection(s). The HydroZone is not approved for outdoor installation and, therefore, must be installed inside the structure being conditioned. Do not locate the control panel in areas where ambient conditions are not maintained within 45 F to 95 F and are greater than 75% relative humidity. The HydroZone control panel should be mounted on or as close to the unit as possible by using the sheet metal screws provided. See the HydroZone ontrol anel Mounting illustration for mounting hole locations. Note: Use longer screws (not provided) to penetrate through drywall into stud. Delivery Information When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine the contents for shipping damage, removing them from the cartons if necessary. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage. Installation and Design Steps 1. Decide which areas of a home or office will comprise each of the individual zones. A maximum of twelve individual zones can be chosen. If more zones are necessary, a 12 zone expansion is available. 2. alculate loads using software or other recognized methodology. 3. Use software to determine the equipment size and performance based on the total heating and cooling demands of the building, not the sum of the individual zone demands. 4. Find the peak heating and cooling demands and the peak M or FM required for each of the zones. 5. Lay out and size the radiant tubing or supply air ductwork. are should be taken to avoid under sizing either the buffer tank, radiant tubing and spacing, supply air systems, return air systems, or diffusers. 6. Decide where to locate the thermostats. 7. Install the unit, storage tank and the HydroZone system. 5
6 HDZNE INSTALLATIN MANUAL Dimensional Data HZ04, HZ08, and HZ12 Dimensions HZ00 Dimensions
7 HDZNE INSTALLATIN MANUAL Electrical atings 4 Zone 115V ump Model: Voltage: 115 hase: 1 Frequency: HZ04A9*N 60Hz Total FLA: 9.3 Maximum Fuse Size: omments: 15 - HA breaker or time delay fuse Maximum current per pump must not exceed 2.15 amps. 4 Zone 24V Valve (1 transformer included) Model: Voltage: 115 hase: 1 Frequency: HZ04AA*N 60Hz Total FLA: 0.65 Maximum Fuse Size: 3 omments: Maximum VA load per valve must not exceed 10 VA or 0.42 amps at 24VA. 8 Zone 115V ump Model: Voltage: 115 hase: 1 Frequency: HZ08A9*N 60Hz Total FLA: 17.9 Maximum Fuse Size: omments: 30 - HA breaker or time delay fuse Maximum current per pump must not exceed 2.15 amps. 8 Zone 24V Valve (2 transformers included) Model: Voltage: 115 hase: 1 Frequency: Total FLA: 1.3 Maximum Fuse Size: 6 omments: HZ08AA*N 60Hz B5 Maximum VA load per valve must not exceed 10 VA or 0.42 amps at 24VA. 12 Zone 115V ump Model: Voltage: 115 hase: 1 Frequency: HZ12A9*N 60Hz Total FLA: 26.5 Maximum Fuse Size: omments: 45 - HA breaker or time delay fuse Maximum current per pump must not exceed 2.15 amps. 12 Zone 24V Valve (2 transformers included) Model: Voltage: 115 hase: 1 Frequency: Total FLA: 1.3 Maximum Fuse Size: 6 omments: HZ12AA*N 60Hz Maximum VA load per valve must not exceed 10 VA or 0.42 amps at 24VA. Electrical Wiring B4 Wiring Zone Valves or umps All wiring must comply with local and state codes. Disconnect the power supply before beginning to wire to prevent electrical shock or equipment damage. All wiring should be run back to the control panel. Keep wires a minimum of 12 inches from any high voltage lines. See the Wiring Schematics section for additional information. Main ower Block Hydrozone ower 115/60/1 B1 WANIN: All wiring must comply with local and state codes. Disconnect the power supply before beginning to wire to prevent electrical shock or equipment damage. 7
8 HDZNE INSTALLATIN MANUAL Wiring Schematics 12 Zone 24VA Valves eotank Sensor AT Sensor Future B B3 Tank Tank AT AT lg om om om Brown (18) Brown (17) ellow (16) ellow (15) HZ A+ B+ ND AT TS ND HydroZone ontroller V /B ellow (1) ink () range (/B) Black () ed () reen (4) ray (3) Blue (2) Note 3 Zone Stats 1-4 Zone Stats 5-8 Zone Stats B5 Z1 Z2 Z3 Z4 reen/ellow (ND) B7 Z5 Z6 Z7 Z8 B9 Z9 Z10 Z11 Z12 Black/White (14) 4 2 elay Black/White Black/White (26) Black/White (34) ellow (13) ellow ellow (25) ellow (33) el (Z1) rn (Z3) Blk (1) Blue (Z2) ink (Z4) el (Z5 ) rn (Z7) Blk (2) Blue (Z6) ink (Z8) el (Z9) rn (Z11) Blk (3) Blue (Z10) ink (Z12 ) Black/White (12) ZB ZB ZB ellow (11) EA Seri es B E4 E3 E2 E1 N N N N EA Series B E4 E3 E2 E1 N N N N Black (6) Black (20) Black (28) Black Black Black Black Black Black EA Seri es B E4 E3 E2 E1 N N N N Black Black Black Note 1 Black (10 ) Black (9) Black (8) Black (7) Black (24) Black (23) Black (22) Black (21) Black (32) Black (31) Black (30) Black (29) White () White () White () White () White () White () White () White () White () White (5) White (19) White (27) ellow Transformer2 Black Black/White 24V 115V White B4 B6 B8 24V Transformer1 115V Black White Note 2 Note 2 Note 2 Zone Valves 1-4 Zone Valves 5-8 Zone Valves VA 24VA 24VA Hydrozone ower 115/60/1 B1 8
9 Zone Thermostat HDZNE INSTALLATIN MANUAL Wiring Schematics cont. 12 Zone 24VA Valves cont. B Note1 elay Board -2 elay 2 elay elay 1 elay elay 4 elay elay 3 elay Synergy3D option Synergy 3D Synergy 3D Synergy 3D Synergy 3D NSW/NDW ompressor 2 ompressor 1 ompressor 4 ompressor 3 B2 Tank ump Note 4 N 115 or 230/60/1 B8 Note 2 Note 1 elay Board 6-4 elay 42 elay ptional connection if auxiliary heat is used and heat pump 4 is not connected Notes 1. If an auxiliary water heater is used, connect to 6 on the relay board as shown above. 2. Wire zone valves or zone pumps to B4, B6, and B8 3. Wire zone thermostats to B5, B7, and B9 4. Use HZAB or field supplied contactor N Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring ptional block D Voltage B traces Junction Quick connect terminal Wire nut Field wire lug round - elay ontacts N.., N.. Fuse HZ - Hydrozone ontrol B - elay Board B - ower Block Legend Water Heater 2 T 3 230/60/1 1 Thermistor Light emitting diode - reen elay coil olarized connector ZB - Zone elay Board HZAB - HydroZone Accessory Box Note /11/10 Thermostat Wiring Z1 B5, 7, & 9 9
10 HDZNE INSTALLATIN MANUAL Wiring Schematics cont. 12 Zone 115V umps B3 eotank Sensor AT AT AT Sensor Tank Tank Future lg om om om Brown (18) Brown (17) ellow (16) ellow (15) HZ A+ B+ ND AT TS ND HydroZone ontroller V /B ellow (1) ink () range (/B) Black () ed () reen (4) ray (3) Blue (2) B Note 3 Zone Stats 1-4 Zone Stats 5-8 Zone Stats B5 Z1 Z2 Z3 Z4 ellow (13) reen /ellow (ND) B7 Z5 Z6 Z7 Z8 Black/White (14) B9 Z9 Z10 Z11 Z12 4 ela Black/White ellow Black/White (26) ellow (25) Black/White (34) ellow (33) ZB1 el (Z1) rn (Z3) Blk (1) Blue (Z2) ink (Z4) ZB2 el (Z5) rn (Z7) Blk (2) Blue (Z6) ink (Z8) ZB3 el (Z9) rn (Z11) Blk (3) Blue ink (Z12) (Z10) Black/White (12) ellow (11) EA Series B E4 E3 E2 E1 N N N N EA Series B E4 E3 E2 E1 N N N N EA Series B E4 E3 E2 E1 N N N N Note 1 Transformer Black Black Black Black Black (10) Black (9) Black (8) Black (7) Black Black Black Black (24) Black (23) Black (22) Black (21) Black (6) Black (20) Black (28) White () White () White () White () White () White () B4 White (5) White (19) White (27) B6 Black Black Black B8 Black (32) Black (31) Black (30) Black (29) White () White () White () 115V 24V White Note 2 Note 2 Note 2 Zone umps 1-4 Zone umps 5-8 Zone umps /60/1 115/60/1 115/60/1 Hydrozone ower 115/60/1 B1 10
11 Zone Thermostat HDZNE INSTALLATIN MANUAL Wiring Schematics cont. 12 Zone 115V umps cont. To Heat umps NSW/NDW Synergy3D option ompressor 2 B -2 elay 2 Synergy3D elay ompressor 1 1 elay 1 elay Synergy3D ompressor Note1 elay Board -4 elay 4 elay elay 3 elay Synergy 3D Synergy3D ompressor 3 Note 4 Tank ump Note 1 elay Board B2-4 elay 42 N N 115 or 230/60/1 Water Heater 230/60/1 Note 4 elay Legend Note 2 ptional connection if auxiliary heat is used and heat pump4 is not connected Notes 1. If an auxiliary water heater is used, connect to 6 on the relay board as shown above. 2. Wire zone valves or zone pumps to B4, B6, and B8 3. Wire zone thermostats to B5, B7, and B9 4. Use HZAB or field supplied contactor Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring ptional block D Voltage B traces Junction Quick connect terminal Wire nut Field wire lug round - elay ontacts N.., N.. Fuse HZ - Hydrozone ontrol B - elay Board 2 B - ower Block ZB - Zone elay Board T 3 Thermistor Light emitting diode - reen elay coil 1 olarized connector /22/10 Thermostat Wiring Z1 B5, 7, & 9 11
12 Zone Thermostat HDZNE INSTALLATIN MANUAL Wiring Schematics cont. 12 Zone 24VA Valves Note 2 Zone Stats 1-4 Zone Stats 5-8 Zone Stats 9-12 B5 Z1 Z2 Z3 Z4 B7 Z5 Z6 Z7 Z8 B9 Z9 Z10 Z11 Z12 reen /ellow (ND) Black/White ellow Black/White (26) ellow (25) Black/White (34) ellow (33) ZB1 el (Z1) rn (Z3) Blk (1) Blue (Z2) ink (Z4) ZB2 el (Z5) rn (Z7) Blk (2) Blue (Z6) ink (Z8) ZB3 el (Z9) rn (Z11) Blk (3) Blue (Z10) ink (Z12) Black/White (12) ellow (11) B2 EA Series B E4 E3 E2 E1 N N N N EA Series B E4 E3 E2 E1 N N N N EA Series B E4 E3 E2 E1 N N N N Black (6) Black (20) Black (28) Black Black Black Black (10) Black (9) Black (8) Black (7) Black Black Black Black (24) Black (23) Black (22) Black (21) Black Black Black Black (32) Black (31) Black (30) Black (29) White (5) White () White () White () White () White () White () White () White () White () B4 B6 B8 White (19) White (27) Note 1 Note 1 Note 1 ellow Black/White 24V ellow Black/White Transformer1 115V 24V Transformer2 Hydrozone ower 115/60/1 Black White 115V B1 Zone Valves 1-4 Zone Valves 5-8 Zone Valves 9-12 Black White 24VA 24VA 24VA Notes 1. Wire 24VA zone valves to B4, B6, and B8. 2. Wire zone thermostats to B5, B7, and B9. Legend Factory Low voltage wiring T Factory Line voltage wiring Field low voltage wiring Field line voltage wiring ptional block D Voltage B traces 2 3 Junction Quick connect terminal Wire nut Field wire lug round - elay ontacts N.., N.. Fuse HZ - Hydrozone ontrol B - elay Board B - ower Block ZB - Zone elay Board 1 Thermistor Light emitting diode - reen elay coil olarized connector /22/10 Thermostat Wiring Z1 B5, 7, & 9 12
13 HDZNE INSTALLATIN MANUAL Thermostat Installation Locating the Thermostats The thermostats must be located in the room or zone that each controls. Locate a thermostat about five feet above the floor. Do not locate a thermostat where it may be exposed to direct sunlight, drafts or direct supply air. Do not place a thermostat on an outside wall. Follow the same guidelines that apply with standard thermostat installation. If two or more rooms are on a single zone, locate the thermostat in a hallway or area where it can sense the return air from all rooms. Four Zone Thermostat Location Utility oom Dining Kitchen Bath Bath Master Bedroom Family oom Living oom Bedroom Bedroom Zone 1 Main Living Zone 2 Bedrooms Not Shown Zone 3 Master Suite Zone 4 Basement HydroZone Thermostat Mounting and Wiring the Thermostat osition the thermostat subbase against the wall so that it is level and the thermostat wires protrude through the middle of the subbase. Mark the position of the subbase mounting holes and drill holes with a 3/16-inch bit. Install supplied anchors and secure base to the wall. Thermostat wire must be eight-conductor 18 AW. Strip the wires back 1/4 inch (longer strip lengths may cause shorts) and insert the thermostat wires into the HydroZone connector as shown to right. Tighten the screws to ensure tight connections. The thermostat has the same type connectors, requiring the same wiring. aulk the hole in the wall where the wires enter the thermostat. Note: See the instructions enclosed in the thermostat for detailed installation and operation information. 13
14 HDZNE INSTALLATIN MANUAL ontroller peration The WaterFurnace HydroZone controller is a part of the hydronic heat pump system. The WaterFurnace part number for this product is HZ. This controller is a human interface and water tank control device. The controller displays and regulates the water tank temperature as configured. A 2-1/2 in. x 2-1/2 in. LD display and five push button keys serve as the human interface. The five keys are: the up and down keys ( and ) for changing the selection or temperature, the right and left keys ( and ) for changing the selection or mode, and the enter key ( ) is for accepting and/or saving the selection. ontroller peration Adjusting Temperature 1. To select a MDE, use the keypad arrows to scroll to MDE. Then, press the enter button on the key pad to enter the operating mode menu. 2. Select the desired mode by scrolling up or down, with the arrows. Then press the enter button on the keypad to enter into that mode. 3. ou are now returned to the Main Menu and Figure 1 is a similar view. NTE: utdoor air temperature is only displayed if an outdoor air sensor is installed. 4. To increase the temperature set point, use the arrow up button. To decrease the set point, use the arrow down button. Five (5) seconds after the last button push, the new setpoint is saved. utdoor reset control is done in the installer s setup and cannot be adjusted from the front screen. Setting Date And Time 1. From the Main Menu, scroll to MENU and press the enter button on the keypad. 2. Select SET DATE. 3. SET MNTH by using the up and down arrows. Then press the enter button on the keypad to save the month. 4. SET DA by using the up and down arrows. Then press the enter button on the keypad to save the day. 5. SET EA by using the up and down arrows. Then press the enter button on the keypad to save the year. 6. Select SET TIME. 7. SET HU by using the up and down arrows. Then press the enter button on the keypad to save the hour. 8. SET MINUTE by using the up and down arrows. Then press the enter button on the keypad to save the minute. 9. If your area observes daylight savings time, select AUT DALIHT SAVIN; scroll to N, then press the enter button to save. ou will be returned to the SET DATE AND TIME menu. Scroll to SET DATE AND TIME and press the enter button on the keypad. Figure The date and time are now set. ou can return to the Main Menu by pressing the left arrow key to return to the previous menu. hanging Modes 1. From the main screen select MDE. 2. Select the operating mode you need and press the enter button. NTE: If selecting EMEEN HEAT, the backlight color will change from blue to red indicating that auxiliary heat is operating instead of the heat pump compressor. Auxiliary/emergency heat is significantly more expensive to operate than the heat pump compressor, and should not be selected unless the heat pump compressor is not operational. Fahrenheit or elsius 1. From the Main Menu, scroll to MENU and press the enter button on the keypad. 2. Select FAHENHEIT/ELSIUS. 3. Select which scale you prefer. Backlight on Time This controller has a two color backlight feature. Anytime a button is pressed, the blue backlight stays on for a certain amount of time. A red backlight is visible if you are selecting Emergency Heat mode. ou can adjust the amount of time the backlight stays on in the menu options. 1. From the Main Menu, scroll to MENU and press the center button on the keypad. 2. ou can change the backlight on time by using the up and down arrows. BAKLIHTIN N (all the time), 15 sec., 30 sec., and N BAKLIHTIN are your choices. ress the enter button to save the new backlight on time. 14
15 HDZNE INSTALLATIN MANUAL ontroller peration cont. Advanced Settings Security Lockout This controller has the option to set security features to lockout everything but the adjustment of the temperature or a total keypad lockout. 1. From the Main Menu, scroll to MENU and press the enter button on the keypad. 2. Select LK/UNLK. 3. The selection will bring you to the Enter in Number screen. 4. Using the up and down arrows, select a pin number to lock out the thermostat. The right arrow moves you to the next pin digit. 5. nce you ve entered the 4-digit pin number, press the enter button to save the pin. The screen will display LKED and return to the main Screen. 6. nce you return to the Main Screen, in the upper left of the screen will alternate between LKED and the date and time. 7. nce unlocked, you will have to reset a pin number again to lockout the thermostat again. 8. In the event the pin number is lost, the default is Installer Information and Advanced Features Safety onsiderations Improper wiring or installation may damage the controller. Wiring must conform to local and national electrical codes. Introduction The controller is a low-voltage controller which maintains geo storage tank temperature by controlling the operation of multiple hydronic heat pumps system. Batteries are not required; temperature and mode settings are preserved with the power off. The controller is not a power stealing device and MUST have both and connected. HydroZone Installation 1. Turn off all power to unit. 2. Separate the front and back pieces of the HZ0. 3. Mount the base of the HZ0. 4. onnect wires to proper terminal on the pump relay. (see wiring schematic on page 4). 5. eplace the cover on the base. 6. Turn on power to the unit. Main Screen After exiting from the setup mode, controller displays the main screen. EATIN, displays the current controller setup selection. They are UTD, T AUT, and T MANUAL MDE. If the operation mode is outdoor reset or tank control auto, the MDE should display FF, N, or EHEAT. If the operation mode is tank control manual, the MDE should display FF, HEAT, L, or EMHT. UTUT shall display the current status of the outputs (WAM WEATHE SHUTDWN, STANDB, 1, 2, 3, 4, or AUX). STANDB mode is active when the controller is satisfied and waiting for a call. 1, 2, 3, and 4 will be off and will stay in its previous state. If the outputs are off due to a warm weather shutdown condition, the proper message should be displayed. Tank setpoint temperature utdoor air temperature urrent mode of operation urrent tank temperature urrent compressor outputs FF, N, EMEEN SET DATE, SET TIME, BAKLIHTIN, F/, LK/ UNLK, SEVIE NTAT INF 15
16 HDZNE INSTALLATIN MANUAL ontroller peration cont. Mode Select Display and Thermostat ontrols Manual Tank Display EATIN MDE SELETIN utdoor eset or Tank Auto ontrol EATIN MDE SELETIN FF HEATIN NL LIN NL EMEEN HEAT FF N EMEEN HEAT SELETIN EVIUS ENTE SELETIN EVIUS ENTE Maximum water temperature needed for minimum AT hange setpoint, temperature, or mode selection Lowest design water temperature Enter or save selection Lowest design outside air temperature hange selection or mode Highest design outside air temperature hange setpoint temperature or mode selection 16
17 HDZNE INSTALLATIN MANUAL ontroller peration cont. Wiring Schematic eotank Sensor AT Sensor B -2 elay 2 To Heat umps Synergy3D option Synergy 3D 5-4 NSW/NDW ompressor 2 B3 Future Future Tank Tank AT AT Brown (ND) Brown (AT) ellow (TS) ellow (ND) HZ A+ B+ ND AT TS ND HydroZone ontroller V /B reen (4) ray (3) Blue (2) ellow (1) ink () range (/B) Black () ed () elay elay 1 elay Synergy 3D ompressor 1 ompressor 4 elay 4 ellow (1) Black/White (2) Note1 elay elay 3 elay 3-3 Synergy 3D ompressor 3 elay Board -4 elay 42 elay 41 elay Board ellow (3) 6-3 Synergy 3D ptional connection if auxiliary heat is used and heat pump 4 is not connected Notes 1. If an auxiliary water heater is used, connect to 6 on the relay board as shown above. N N HydroZone Accessory ontrol Box Tank ump 115 or 230/60/1 HydroZone Accessory ontrol Box Water Heater 230/60/1 Legend Factory Low voltage wiring T Thermistor Factory Line voltage wiring Field low voltage wiring Light emitting diode - reen Field line voltage wiring ptional block elay coil D Voltage B traces Junction Quick connect terminal olarized connector Wire nut HZ - Hydrozone ontrol Field wire lug B - elay Board B - ower Block round ZB - Zone elay Board elay ontacts- N.., N.. Fuse /14/09 Installer Settings These options are intended to be used by the installer. End users are not advised to change or modify any of these settings. Doing so may make your equipment stop working properly and/or may void the warranty of the controller as well as the equipment hooked up to the controller. To access the installer setting menu, the mode must be set to FF. Then, press both the up and down arrow keys at the same time for at least 5 seconds to enter the installer screen. After initial power-up, you re-enter installer setup. If no selection is made within 30 seconds, the controller will return to the main screen. ontroller Setup ptions to select from: 1. utdoor eset - This control mode uses the outdoor reset algorithm to continuously adjust the set point. The set up menu allows selection of Maximum Tank Temperature at a corresponding outdoor air 17
18 HDZNE INSTALLATIN MANUAL ontroller peration cont. temperature (AT), and Minimum Tank Temperature at its corresponding AT. An outdoor air sensor must be installed. Set point A is the maximum tank temperature set point: Tank temperature (TANK_A) range is 100 F to 130 F, and default as 120 F. utdoor air temperature (AT) range is 0 F to 20 F, and default as 0 F. Set point B is the minimum tank temperature set point: Tank temperature (TANK_B) range is 70 F to 90 F, and default as 80 F. utdoor air temperature (AT) range is 40 F to 60ºF, and default as 60 F. be changed from the main screen by pushing the U or DWN buttons. Selecting ENTE shall take the screen to the NTLLE SETU screen. This option will maintain the temperature with a tighter deadband and automatically switch the heat pump between heating and cooling to maintain the setpoint. The factory default is 120 F heating and 5 F dead band. All these temperature setting are with increments of 1 F. The dead band is 2 F to 15 F with Increments of 1 F. Tank Temperature Set point is calculated internally by the outdoor reset algorithm, and updated every 30 minutes if this setup is selected. Warm Weather Shutdown: If the warm weather shutdown is selected, the controller will check the outdoor air temperature sensor every 30 minutes. If the temperature is higher than the set temperature selected for 50 continuous hours, then the HydroZone ontroller will enter the warm weather shutdown mode. If the temperature drops below the selected setpoint for 5 continuous hours, the controller will exit the warm weather shutdown mode and return back to normal. Warm weather shutdown selections are None, 45, 50, 55, 60, and 65. The factory default is None. 3. Tank ontrol Manual - There shall be no automatic changeover from heating to cooling or vice versa. Heating and cooling modes must be selected manually. If heating fixed is selected, the default temperature for tank setpoint is 120 F with a 10 F deadband. The set range is 80 F to 130 F, with Increments of 1 F. The dead band is 2 F to 15 F with Increments of 1 F. The factory defaults are 120 F heating and 5 F dead band, 80 F cooling and 5 F dead band, and warm weather shutdown is None. When the selection is moved to WAM WEATHE SHUTDWN, ENTE shall take the screen to the WAM WEATHE SHUTDWN screen. When ENTE is selected, the installer shall be taken to the LIN screen. 2. Tank ontrol Auto - Default temperature for tank setpoint is 120 F with a 5 F deadband. The set range is 40 F to 130 F, with Increments of 1 F. The dead band is 2 F to 5 F with Increments of 1 F. The setpoint can 18
19 HDZNE INSTALLATIN MANUAL ontroller peration cont. If no heating is selected, the screen shall go to the LIN screen. If cooling fixed is selected, the default temperature for tank setpoint is 80 F with a 10 F deadband. The set range is 40 F to 85 F, with Increments of 1 F. The dead band is 2 F to 15 F with Increments of 1 F. utput Setup onfiguration ptions Factory Defaults 1 Single Dual1 Stage1 Single 2 Single Dual1 Stage2 ff ff 3 Single Dual2 Stage1 ff ff 4/W Single Dual2 Stage2 Aux ff ff If AUX is selected in stage 4, ENTE would take the user to ADDITINAL DEAD BAND F AUX HEAT screen and then to MAXIMUM AT F AUX HEAT screen. The ADDITINAL DEAD BAND F AUX HEAT would enable the installer to select how much extra dead band should be added on top of the heat dead band before auxiliary heat would come on. The range is between 5 and 15 F. Staging The controller can control up to four stages of compressors or three compressors and one auxiliary heat. How the unit stages the outputs will be determined by how the outputs are configured. When selecting a dual capacity unit, the next available stage will automatically become dual stage 2. Example: If DUAL 1 ST 1 has been selected for 1 then 2 will automatically be DUAL 1 ST 2. Staging Screen STAIN Staging Setup of 1 Dual ompressor and 1 Single with Aux Enabled STAIN In the MAXIMUM AT F AUX HEAT the installer can select between NNE or a certain outdoor air temperature. If the installer selects a certain temperature for AT, the AUX heat shall not come on if the outdoor air temperature is above that temperature. The range is between 0 F and 40 F. If NNE is selected, the AUX heat can come on at any time regardless of the outdoor air temperature. An outdoor air sensor must be installed for this option. 1 SINLE / DUA ST1 2 FF / SINLE / DUA ST2 3 FF / SINLE / DUA ST1 4 FF / SINLE / DUA ST2 / AUX WANT T HANE? ES N TIN ENTE DUA ST1 DUA ST2 SINLE AUX ADDITINAL DEAD BAND F AUX 5 MAXIMUM AT F AUX HEAT 40 WANT T HANE? ES N TIN ENTE 19
20 HDZNE INSTALLATIN MANUAL ontroller peration cont. Lead/Lag If only 1 is selected in the staging, the lead/lag will be selected as N, and can not be changed. Each compressor output will have an accumulator to keep track of total run time. If any accumulator ran up to the maximum count, all the accumulators shall be reset. Total run time will be reset when lead/lag N is selected. The default setting is N. When the installer selects ENTE from any of the BAND NAME, MDEL NUMBE, SEIAL NUMBE, NTAT NAME, and NTAT HNE screens, the main INUT DEALE INF screen is shown. In order to save the dealer information in the permanent memory, the installer shall select SAVE from the main INUT DEALE INF screen and hit ENTE. The following screen is shown summarizing the information the installer has inserted in the previous screens. First n ompressor stage with least amount of accumulated run time. First ff ompressor stage with most amount of accumulated run time. Factory Defaults When ES is selected for ESTE FAT DEFAULTS, the controller will restore the factory defaults configuration. Factory default control option is tank control manual. The factory defaults are 120 F heating, 5 F dead band, and warm weather shutdown None. Service ontact Information Input dealer info. INUT DEALE INF BAND NAME MDEL NUMBE SEIAL NUMBE NTAT NAME NTAT HNE DEALE INF BAND NAME: USE T SLL THU HAATES WATE FUNAE SAVE SELET TIN EVIUS ENTE HANE LETTE EVIUS ENTE 20
21 HDZNE INSTALLATIN MANUAL System Startup and heckout System heckout The HydroZone controller needs to be set to manual heating and cooling for the following start-up procedures. Set all of the zone thermostats to the cooling mode. educe the cooling set point to 1 above the actual zone temperature on all thermostats. First stage cooling should energize after a delay. utput LEDs on ZB1-3 should be on. Verify zone valve is operating or pump is running Set all zone thermostats to heating mode Increase heating set point to 1 above the actual zone temperature on all thermostats. First stage heating should energize after a delay. utput LEDs on ZB1-3 should be on. Verify zone valve is operating or pump is running. Instruct the owner/operator of correct thermostat and system operation. Fill out and forward all warranty registration papers to WaterFurnace. arts Lists art Number HZ HZ0 HZ04AANN HZ04A9NN HZ08AANN HZ08A9NN HZ12AANN HZ12A9NN HZ12AAEN HZ12A9EN HZAB Specification HydroZone ontrol nly HydroZone ontrol with signal isolation board - 0 Zone (24V only) HydroZone ontrol with signal isolation board - 4 Zone 24V output (valve) HydroZone ontrol with signal isolation board - 4 Zone 115V output (pump) HydroZone ontrol with signal isolation board - 8 Zone 24V output (valve) HydroZone ontrol with signal isolation board - 8 Zone 115V output (pump) HydroZone ontrol with signal isolation board - 12 Zone 24V output (valve) HydroZone ontrol with signal isolation board - 12 Zone 115V output (pump) 12 Zone expansion and not equipped with the HydroZone ontrol or relay board - 24V output (valve) 12 Zone expansion and not equipped with the HydroZone ontrol or relay board - 115V output (pump) HydroZone Accessory Box (water heater or pump control) L /4" SWT Zone valve motorized sweat (Qty 1) L " SWT Zone valve motorized sweat (Qty 1) TSU02* utdoor Air Sensor (required with utdoor eset ontrol ) NTES: HZ0 is for tank control only with no zones. HydroZone ontroller arts List art Number Quantity Description Mass Label Sheet osition Terminal Block ontrol Box ontrol Box over Wire Kit 91001A18 6 Screw #6-32 X 5/ HydroZone ontroller Low Voltage elay Board 91001A43 4 Screw #10-24 X 3/ A12 1 Nut #
22 HDZNE INSTALLATIN MANUAL Notes 22
23
24 Manufactured by WaterFurnace International, Inc onservation Way Fort Wayne, IN IM1550EW 11/10 roduct: Type: Size: Document: HydroZone Hydronic omfort Zoning System 4, 8, and 12 Zone apacity Installation Manual 2010 WaterFurnace International, Inc., 9000 onservation Way, Fort Wayne, IN WaterFurnace has a policy of continual product research and development and reserves the right to change design and specifications without notice.
Product Instructions. Viega Programmable Heat/Cool Thermostat. Technical data
Programmable Heat/ool Thermostat The programmable heat/cool thermostat is easy to install, easy to wire, and easy to program. It can be used for single stage heating and cooling applications, making it
More informationNON-PROGRAMMABLE THERMOSTAT. The following Payne equipment is not compatible with the AC version (TSTATPPBAC01-B) of this
Installation Manual NN-PAMMABLE THEMSTAT TSTAT < < Fig. 1 Non-Programmable Thermostat NTE: ead the entire instruction manual before starting the installation. A98193 SAFET NSIDEATINS ead and follow manufacturer
More informationCommercial Thermostat
ommercial Thermostat Submittal Data *204* 204 ev.: November 18, 2016 limatemaster works continually to improve its products. As a result, the design and specifications of each product at the time of order
More informationUser s Manual
997-060180-4e User s Manual 8403-060 Menu Driven Display 1120-445 I. CONTROLLER OPERATION ADJUSTING TEMPERATURE (Temporary Override when in Programmable mode) 1. Before you can adjust the temperature,
More informationInstallation and Operating Instructions
Visit www.carrier.com Non-Programmable Thermostat TSTATN(A,HP,2S)01- Installation and perating Instructions NTE: ead the entire instruction manual before starting the installation. This symbol indicates
More informationInstruction Guide: Thermostat Operation
Instruction Guide: Elite Communicating Thermostats TPCM32U03*/TPCM32U04* (*GSR, GSM, TRN, AST) INSTRUCTION GUIDE: ELITE COMMUNICATING THERMOSTAT Thermostat Operation NOTE: These communicating thermostats
More informationINSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT Color Touchscreen Communicating with Humidity Control Thermostat TPCC32U01.
Instruction Guide: INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT Color Touchscreen Communicating with Humidity Control Thermostat TPCC32U01 Menu Press the Menu button. Color Touchscreen
More informationMAXIMUM UNIT AMPS MINIMUM WIRE SIZE
WIIN DIAAMS FM 58MVP VAIALE-APAIT NDENSIN AS FUNAE (have attached arrier single stage A & arrier Humidifier) Table 5 Electrical Data UNIT SIZE VLTS HETZ PHASE PEATIN VLTAE ANE Maximum* Minimum* MAXIMUM
More informationINSTALLATION MANUAL. Need Help? This manual covers the following models: T905. Power Type. Thermostat Applications Guide. Page.
INSTALLATION MANUAL This manual covers the following models: T905 Thermostat Applications uide Description as or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or
More informationCommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET
CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or
More informationINSTALLATION MANUAL. Need Help? This manual covers the following models: T705. Power Type. Thermostat Applications Guide. Page.
INSTALLATION MANUAL This manual covers the following models: T705 Thermostat Applications uide Des cription as or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or
More informationTP-Z-955W VIVE Comfort 1111 S. Glenstone Ave., Suite Springfield, MO 65804
INSTALLATION MANUAL OM F O R T TP-Z-955W VIVE omfort S. lenstone Ave., Suite -00 Springfield, MO 65804 Thermostat Applications uide Description as or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency
More informationIntelliZone Installation Manual
Comfort Zoning System Four Zone Capability Installation Information Damper Installation IntelliZone Installation Manual Thermostat Installation Electrical Startup Procedures Wiring Schematic IM1958 03/09
More informationEnvision Air Handler Specification Catalog
Air Handler Design Features Factory ptions Accessories Dimensional Data Physical Data Performance Data Engineering uide Specifications Envision Air Handler Specification atalog S00HN 0/ ENVISIN AI HANDLE
More informationSPECIFICATION CATALOG
SPEIFIATIN ATAL ETHEMAL HEAT PUMPS AFFDABLE ENEWABLE LEAN ASTN SEIES AI HANDLE ASTN SEIES AI HANDLE SPEIFIATIN ATAL Table of ontents Air Handler Nomenclature...........................................................
More informationTP-S-855i MENU AUTO HEAT. Installation Tips. Installation Manual. Installation Tips. Installation Tips. Hardwire - 24 VAC Common Wire
Installation Manual Vive omfort P.O. Box 3377 Springfield, MO 65804 Toll Free : 888-776-47 Web: www.vivecomfort.com Hours of Operation: M-F 9AM - 6PM Eastern Thermostat Application uide Description as
More informationINSTALLATION MANUAL. Need Help? This manual covers the following models: T805. Power Type. Thermostat Applications Guide. Page.
INSTALLATION MANUAL This manual covers the following models: T805 Thermostat Applications uide Des cription as or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or
More informationOperator: Save these instructions for future use!
WHITE-ODES 1F89-11 Non-Programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPEATION INSTUTIONS Operator: Save these instructions for future use! FAILUE TO EAD AND FOLLOW ALL INSTUTIONS
More informationTP-S-855C. Installation Tips. Installation Manual. Installation Tips. Installation Tips
Installation Manual Vive omfort P.O. Box 3377 Springfield, MO 65804 Toll Free : 888-776-47 Web: www.vivecomfort.com Hours of Operation: M-F 9AM - 6PM Eastern Thermostat Application uide Description as
More informationCommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits
CommStat 4 PRODUCT DATA SHEET Controller for Redundant Telecom HVAC Systems General Description The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners,
More informationInstallation Instructions / User s Manual TSTAT0406 and TSTAT0408
997-060180-5 Installation Instructions / User s Manual TSTAT0406 and TSTAT0408 4 HEAT 2 COOL DUAL FUEL TSTAT0406 & TSTAT0408-4 WIRE CAPABLE THERMOSTAT (NAXA00201DB Daughter Board sold separately) LEFT
More information1F Non-programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION Your new White-Rodgers Digital Thermostat
More informationSafety & Installation Instructions
Model 8620 Thermostat with Event-Based Air leaning and Humidity or Ventilation ontrol Safety & Installation Instructions READ AND SAVE THESE INSTRUTIS Table of contents Installation Installation location
More informationT-32-TS Touchscreen Thermostat. Installation Manual
T-32-TS Touchscreen Thermostat Installation Manual TABLE OF CONTENTS Introduction...4 Getting Started...5 Installing the Thermostat...6, 8 Disassembly...6 Thermostat Location...6 Mounting the Subbase...6,
More information2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT
CONTENTS Installation Instructions for Heating & Air Conditioning 1F79 n-programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...
More informationInstallation Instructions MODEL 8870
Installation Instructions MDEL 8870 These instructions are for connecting the Thermostat to the HVA equipment. To connect communication features, please reference the ommunicating Thermostat System Installation
More informationINSTALLATION MANUAL. This manual covers TopTech models: TT-N-851. Need Help? Power Type. Thermostat Applications Guide. Page.
INSTALLATION MANUAL This manual covers TopTech models: TT-N-851 Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or
More informationCommercial Thermostat Submittal Data
ommercial Thermostat Submittal Data English anguage/i-p Units SUBMITTA DATA Unit Designation: Job Name: Architect: Engineer: ontractor: ev.: 02/23/06D limatemaster works continually to improve its products.
More informationIF79 CAUTION CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS. Installation Instructions for. Heating & Air Conditioning
CONTENTS Installation Instructions for Heating & Air Conditioning IF79 n- Programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...
More informationIntelliZone2 24V Installation Manual
omfort Zoning System Four Zone apability Designed for Use with Typical 4VA Heat Pump ontrollers Installation Information Damper Installation Thermostat Installation IntelliZone 4V Installation Manual Electrical
More information1F Non-Programmable Electronic Digital Thermostat INSTALLATION AND OPERATION INSTRUCTIONS
FAILURE T READ AND FLL ALL INSTRUCTINS CAREFULL EFRE INSTALLIN R PERATIN THIS CNTRL CULD CAUSE PERSNAL INJUR AND/R PRPERT DAMAE. DESCRIPTIN our new hite-rodgers Digital Thermostat uses the technology of
More informationCommStat 4 Controller
CommStat 4 Controller CommStat 4 Telecom HVAC Controller The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners, heat pumps and air conditioners with
More informationAIR HANDLER R-410A Refrigerant 2-5 Tons. Submittal Data English Language/IP Units SD1008HN 07/15
AI HANDLE -0A efrigerant - Tons Submittal Data English Language/IP Units SD00HN 0/ ontractor: ENVISIN AI HANDLE - Tons Model Nomenclature - - - 0 NAH 0 * 00 0 Model NAH Envision Series Air Handler Unit
More informationSafety & Installation Instructions
Model 8800 Universal Communicating Thermostat Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Installation Installation location recommendations... 2 Thermostat mounting...
More information1F Non-Programmable Electronic Digital Multi-Stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS
1F83-261 Non-Programmable Electronic Digital Multi-Stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
More informationInstaller : Save these instructions for future use!
Model EWT-3900 Wireless Programmable Digital Thermostat Installer : Save these instructions for future use! FAILUE T EAD AND FLLW INSTUTINS AEFULL EFE INSTALLATIN PEATIN ULD DAMAE THIS NTL AUSE PPET DAMAE.
More informationINSTALLATION MANUAL. Need Help? This manual covers the following models: T755. Power Type. Thermostat Applications Guide. Page.
INSTALLATION MANUAL This manual covers the following models: T755 Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or
More informationStandard Programmable Thermostat Homeowner s Guide / Installation, Start-Up, and Operating Instructions
Standard Programmable Thermostat Homeowner s uide / Installation, Start-Up, and perating Instructions Visit www.carrier.com Homeowner s uide < < Fig. 1 Standard Programmable Thermostat A99068 Programming
More informationCommercial Touchscreen Thermostat
55,13M 1/27 Supersedes 12/25 Commercial Touchscreen Thermostat 25 Lennox Industries, Inc. Dallas, Texas, USA APPLICATION Page 1 INSTALLATION INSTRUCTIONS The Lennox Commercial Touchscreen Thermostat provides
More informationINSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help?
INSTALLATION MANUAL This manual covers the following models: T955W Master Thermostat Base Module Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency
More informationT855S 5:23. Installation Manual. Installation Tips. Installation Tips. Installation Tips
Installation Manual Pro Technologies S. lenstone Ave., Suite -00 Springfield, MO 65804 Toll Free: 888-776-47 Web: www.proiaq.com Hours of Operation: M-F 9AM - 6PM Eastern Thermostat Application uide Description
More informationSafety & Installation Instructions
Model 8476 Thermostat with Event-Based Air Cleaning Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Installation Installation location recommendations... 3 Outdoor
More informationPhone-A-Stat. MODEL Command Center With Thermostat Operation, Maintenance & Installation Manual. Introduction.
Introduction The UL listed Phone-A-Stat (model # 7632 ) is designed and approved for the safe operation of remotely controlling four independent loads, such as a sprinkler system or a water heater via
More informationOWNERS MANUAL YEAR LIMITED WARRANTY READ ALL INSTRUCTIONS BEFORE PROCEEDING. Store this booklet for future reference
3100 Premier Series Non-Programmable 2 Heat / 2Cool & Heat / Cool Digital Thermostat OWNERS MANUAL Compatible with low voltage multi-stage heat / cool systems with up to two stages of heating and two stages
More informationInstallation Instructions
50ES--A, 50EZ--A, 50VG--A, B, 50VL--A, B, 50VR--A, 50VT--A, B 604D-- --A, 607C-- --A, B, 607E-- --A, 704D-- --A, 707C-- --A, B, 707E-- --A PA3G -- -- A, PH3G -- -- A, PA4G, PH4G PAD3, PHD3, PAD4, PHD4,
More informationInstaller : Save these instructions for future use!
Model EWT-3900 Wireless rammable Digital Thermostat Installer : Save these instructions for future use! FAILUE T EAD AND FLLW INSTUTINS AEFULL EFE INSTALLATIN PEATIN ULD DAMAE THIS NTL AUSE PPET DAMAE.
More informationPS4000 and PS5000 Touchscreen Programmable Thermostat Installation and Owners Manual Robertshaw 01/
PS4000 and PS5000 Touchscreen Programmable Thermostat Installation and Owners Manual www.robertshaw.com 2016 Robertshaw 01/16 352-00244-001 IMPORTANT SAFETY INFORMATION WARNING: ELECTRICAL SHOCK HAZARD
More informationInstallation, Start-Up, and Operating Instructions
33CS Commercial Programmable Thermostat Installation, Start-Up, and perating Instructions Part Number 33CS220-LA CNTENTS Page SAFETY CNSIDERATINS... 1 GENERAL... 1 INSTALLATIN... 1-6 Select Thermostat
More informationATA11U03. Non-Programmable Heat Pump Thermostat. Installation Manual. 97B0082N06 Revised: 16 September, 2013 FOR INSTALLER AND OWNER ONLY
Table of Contents Non-Programmable Heat Pump Thermostat Installation Manual 97B0082N06 Revised: 16 September, 2013 Safety Considerations 3 General 3 Package Contents 3 Installation Considerations 3 Power
More informationNAH Series HYDRONIC AIR HANDLER 2 TO 5 TONS. Submittal Data English Language IP/Metric Units SD1028HG1 05/17
HYDNI AI HANDLE T TNS Submittal Data English Language IP/Metric Units SD0H 0/ ontractor: Model Nomenclature - Tons 0Hz - - - 0 NAH 0 * 00 0 H Model NAH Unit apacityacity 0 MBTUH 0 MBTUH 0 MBTUH 00 MBTUH
More informationSafety & Installation Instructions
8400 Series Thermostats Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS 61000652C 8400 Tstat Install.indd 1 10/13/09 11:08:56 AM Table of contents Installation Installation location
More informationINSTALLATION MANUAL. Need Help? This manual covers TopTech models: TT-N-721 and T721. Power Type. Thermostat Applications Guide.
INSTALLATION MANUAL This manual covers TopTech models: TT-N-721 and T721 Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump ( Aux. or Emergency Heat) Heat Pump (with Aux.
More informationINSTALLATION MANUAL. Need Help? This manual covers the following models: T725. Power Type. Thermostat Applications Guide. Page.
INSTALLATION MANUAL This manual covers the following models: T725 Thermostat Applications Guide Des cription Gas or Oil Heat Electric Furnace Heat Pump ( Aux. or Emergency Heat) Heat Pump (with Aux. or
More informationInstallation Manual for Hot Yoga Studio Electric Radiant Heating Version 3.0
Comfort System HG-122 Universal Thermostat Installation Manual for Hot Yoga Studio Electric Radiant Heating Version 3.0 More Ah ha! Less Uhhh? For easy to follow programming instructions visit: www.heatinggreen.com/thermostatinstructions-wiring-diagrams/
More informationInstallation Instructions
TP --- PRH --- A, TP --- NRH --- A PerformancetSeries Edger Thermidistatt Control Installation Instructions Programmable Control A07049 A07048 Non---Programmable Control NOTE: Read the entire instruction
More informationInstaller Guide. WARNING Important Safety Information. 1 Specifications
1 Specifications cont. Premier Series Universal Auto Changeover Up to 3 Heat / 2 Cool Heat Pump or 2 Heat / 2 Cool Conventional Thermostat Installer Guide Before Installing, Programming or Operating, PLEASE
More informationInstallation Manual for Hot Yoga Studio Electric Radiant Heating
105 Comfort System HG-122 Universal Thermostat Installation Manual for Hot Yoga Studio Electric Radiant Heating Version 3.0 More Ah ha! Less Uhhh? For easy to follow programming instructions visit: www.heatinggreen.com/thermostatinstructions-wiring-diagrams/
More informationACCESSORY KIT INSTALLATION MANUAL
AESSY KIT INSTALLATIN MANUAL MMUNIATIN INTEFAE NTL FIELD KIT - ET FIT APPLIATINS F USE ITH MDELS: All Models (Non-ommunicating Units) ENEAL INFMATIN To be used with non-communicating indoor units and some
More informationThermidistat Control Installation, Start-Up, and Operating Instructions
Visit www.carrier.com Thermidistat ontrol Installation, Start-Up, and perating Instructions NTE: ead the entire instruction manual before starting the installation. INDEX Page SAFET NSIDEATINS...1 INTDUTIN...1
More informationInstallation, Start-Up, and Operating Instructions
Installation, Start-Up, and Operating Instructions IMPORTANT: Read entire instructions before starting the installation. SAFETY CONSIDERATIONS Read and follow manufacturer instructions carefully. Follow
More informationINSTALLATION MANUAL. Need Help? This manual covers the following models: T915. Power Type. Thermostat Applications Guide. Page.
INSTALLATION MANUAL This manual covers the following models: T915 Thermostat Applications Guide Des cription Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux.
More informationINSTALLATION AND OPERATING INSTRUCTIONS
TTALINE 1c.eps gold-1.pdf INSTALLATI AND PEATIN INSTUTIS esidential Programmable Thermostats Part No. P274-1100, 1200, 1300 TENTS Page SAFET SIDEATIS...................... 1 ENEAL........................................
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com Manual: 200-393O Supersedes: 200-393N Date: 2-26-6 Page of 8 CONTENTS Shipping
More informationSafety & Installation Instructions
8400 Series Thermostats Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS 61000652A 8400 Tstat Install.indd 1 7/23/09 2:20:45 PM Table of contents Installation Installation location recommendations...
More informationEmerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING
Emerson Inspire 1HDEZ-1521 Installation Instructions Thermostat/Interface Equipment Control TROUBLESHOOTING FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL
More informationEL-TSTAT-8820 Safety & Installation Instructions
EL-TSTAT-8820 Safety & Installation Instructions TABLE OF CONTENTS WI-FI SETUP Wi-Fi Setup 2 INSTALLATION Installation location recommendations 3 Outdoor temperature sensor (included) 3 Remote temperature
More informationInstaller Guide. WARNING Important Safety Information. 1 Specifications
1 Specifications cont. Premier Series Universal Auto Changeover Up to 3 Heat / 2 Cool Conventional and Heat Pump Thermostat Installer Guide Before Installing, Programming or Operating, PLEASE READ ALL
More informationNAH Series. NAH Series Hydronic Air Handler Installation Manual. Air Handler. Installation Information. Water Piping Connections
NAH Series Air Handler Installation Information Water Piping onnections Electrical onnections Startup Procedures Preventive Maintenance NAH Series Hydronic Air Handler Installation Manual IM0H 0/ NAH
More informationSC Installation, Operation & Application Guide
SC 5211 2-Stage Heat Pump Auto Changeover Hardwire Programmable Electronic Thermostat 7-Day, 5-2-Day or 5-1-1-Day Programmable Configurable 2-Stage Heat Pump Systems Large Display With Backlight Selectable
More informationGEOTHERMAL HYDRONIC CONTROL MODULE By TERRA-THERM, INC.
GEOTHERMAL HYDRONIC CONTROL MODULE By TERRA-THERM, INC. Physical Dimensions: 15-11/16 H x 11-13/16 W x 6-19/32 D M2-0152 HEAT PUMP HYDRONIC CONTROL MODULE With 2-stage heat, 2-stage cooling setpoint controls
More informationIntelliZone2 Installation Manual
omfort Zoning System Six Zone apability IntelliZone Installation Manual Installation Information Damper Installationlation Thermostat Installation Electrical Startup Procedures Wiring Schematic IM578EW
More informationCarrier NON-PROGRAMMABLE DIGITAL THERMOSTAT. Dual Setpoint Thermoglow Backlight No Batteries Required Auto Changeover Locking Keypad
Carrier Heating & Cooling TSTATCCNB00 NON-PROGRAMMABLE DIGITAL THERMOSTAT USER INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW THERMOSTAT NON-PROGRAMMABLE DIGITAL THERMOSTAT AUTO 74 Dual
More informationOperator: Save these instructions for future use!
WHITE-RODGERS 1F82-51 Programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
More informationTEC210x-2 Series Networked Thermostats
Product Bulletin Issue Date February 1, 2005 TEC210x-2 Series Networked Thermostats The TEC210x-2 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment
More informationAMANA PHWT-A200 THERMOSTAT
AMANA PHWT-A200 THERMOSTAT 3) SAFETY INFORMATION This thermostat is for LOW voltage applications only. Turn OFF electricity to all heating and cooling components. All wiring must conform to applicable
More informationSafety & Installation Instructions
Home omfort ontrol Model 8910 READ AND SAVE THESE INSTRUTIS Safety & Installation Instructions Table of contents Installation Thermostat installation location recommendations.. 2 Thermostat mounting...
More informationInstallation Guide ProR221J, ProR212J, ProR321J and ProR312J
ProZone I n t e l l i g e n t Z o n i n g Zones See table below. ompatible Equipment All panels operate with gas/electric systems, conventional heat pumps and dual fuel heat pumps. Equipment Selection
More informationPump-Down Controller MODEL 4052
Pump-Down Controller 4-20mA Input/Scalable Output Seal Fail Monitoring Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters RS-485/Modbus Communications DESCRIPTION The Model 4052 Pump-Down
More informationUser s Manual. THE iq Drive SYSTEM USER S INFORMATION IMPORTANT. Variable Speed Ultra-High SEER Split System IMPORTANT NOTE
User s Manual Variable Speed Ultra-High SEER Split System These units have been designed and tested for capacity and effi ciency in accordance with ARI standards. These outdoor air conditioning units are
More informationCAUTION: ELECTRICAL HAZARD
R R Installation Guide 53DF50-HW hermostat System ypes Cool Only (single stage) Heat Pump (with electric heat) CAUION: ELECRICAL HAZARD Can cause electrical shock or equipment damage. Disconnect power
More informationInstallation Instructions
50ES---A, 50EZ---A, 50VL---A, 50VG---A, 50VR---A, 50VT---A, 604D--- ---A, 607C--- ---A, 607E,--- ---A, 704D--- ---A, 707C--- ---A, 707E--- ---A PA3G --- --- A, PH3G --- --- A SMALL PACKAGED PRODUCTS Electric
More informationInstaller s Guide ACONT200AN11AA 1 Heat (Gas, Oil* or Elec) / 1 Cool Electronic Non-Programmable, 4 Wire Hookup
11-HD03D1-3 Available in French Canadian (FC) Installer s uide ACONT200AN11AA 1 Heat (as, Oil* or Elec) / 1 Cool Electronic Non-Programmable, 4 ire Hookup ALL phases of this installation must comply with
More informationPremier 2-Zone Controller model Installer Guide
Premier 2-Zone ontroller model 140202 Installer uide ONTENTS 1 Specifications 4 onfiguration 2 Suitable Mounting Locations 5 System heckout 3 Wiring Diagrams 6 Operation Warning Read all of the instructions
More information1F98EZ-1421, Easy Install
1F98EZ-1421, -1441 Easy Install For up to 4 Stages and 2 Stages Cool INSTALLATION INSTRUCTIONS APPLICATIONS Configuration Options Single Stage Multi Stage Pump Pump with Dual Fuel FAILURE TO READ AND FOLLOW
More informationInstallation Instructions
EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 Installation Instructions NOTE: Read the entire instruction manual before starting
More informationOperator: SaVe these instructions forfuture use
Whiter Rodgers 1F86-344 Non-Programmable Electronic Digital Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: SaVe these instructions forfuture use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
More informationINSTALLATION MANUAL. This manual covers TopTech models: TT-S-755H. Need Help? Thermostat Applications Guide. Power Type. Table of Contents.
INSTALLATION MANUAL This manual covers TopTech models: TT-S-755H Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or
More informationSC Installation, Operation & Application Guide
SC 5811 2 Heat/2 Cool Auto Changeover Hardwire Programmable Electronic Thermostat 7-Day, 5-2-Day or 5-1-1-Day Programmable Configurable 2-Stage Heat/2-Stage Cool Systems 2-Stage Heat Pump Systems Large
More informationPump-Up Controller MODEL 4062
Pump-Up Controller 4-20mA Input/Scalable Output Seal Fail Monitoring Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters RS-485/Modbus Communications DESCRIPTION The Model 4062 Pump-Up
More informationRCS Residential Control Systems Inc.
RCS Residential Control Systems Inc. Model TZ16 Z-Wave Communicating Thermostat with Rev P HVAC Control Unit INSTALLATION AND OPERATION MANUAL DCN: 141-00882 Rev 02 5/18/06 This manual applies to the following
More informationEmerson Blue Easy Set 1H/1C
Emerson Blue Easy Set 1H/1C Model: 1F86EZ-0251 Non-Programmable Thermostat with 3 Temperature Pre-Sets Home, Sleep and Away Installation Instructions and User Guide Message to Homeowner Congratulations
More informationCOMFORT CONTROL - 4 HEAT (GAS, OIL*, OR ELECTRIC)/3 COOL/HEAT PUMP COMMUNICATING PROGRAMMABLE 3 WIRE HOOKUP
COMFORT CONTROL - 4 HEAT (GAS, OIL*, OR ELECTRIC)/3 COOL/HEAT PUMP COMMUNICATING PROGRAMMABLE 3 WIRE HOOKUP ALL phases of this installation must comply with NATIONAL, STATE, AND LOCAL CODES INSTALLER S
More informationINSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT Color Touchscreen Communicating with Humidity Control Thermostat TPCC32U01
Instruction Guide: INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT Color Touchscreen Communicating with Humidity Control Thermostat TPCC32U01 Thermostat Operation Adjusting Temperature (Temporary
More informationSC Installation, Operation & Application Guide
SC 3006 Auto Changeover 7-Day Programmable Hardwired Programmable Electronic Thermostat 7-Day Programmable Single Stage Heat Pump/Non-Heat Pump Systems Backlit Display Single Stage Heat/Cool Systems Field
More informationVisionPRO 8000 with Wi-Fi
VisionPRO 8000 with Wi-Fi FEATURES PRODUCT DATA Thermostat acquires weather data through either a wired sensor or an Internet connection, making for a truly universal installation. U1 Terminals One set
More informationProgrammable Thermostat
Programmable Thermostat with Humidity Control Auto Changeover Dual Power 7-Day, 5-2-Day, or 5-1-1- Day Programmable Configurable for Multiple Systems Large Display with Backlight Selectable Fahrenheit
More information1 PREPARATIONS 2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT. 1E78 Non-Programmable Thermostat CONTENTS
CNTENTS Installation Instructions for Heating & Air Conditioning 1E78 Non-Programmable Thermostat Preparations... 1 Thermostat Details... 1 Removing ld Thermostat... 1 Mounting and iring... 2 Check Thermostat
More informationOWNER S MANUAL DLFCAB / DLFCHB / DLFDAB / DLFDHB High Wall Ductless System Sizes 09 36
OWNER S MANUAL DLFCAB / DLFCHB / DLFDAB / DLFDHB High Wall Ductless System Sizes 09 36 TABLE OF CONTENTS PAGE SAFETY PRECAUTIONS... 2 GENERAL... 2 INDOOR UNIT PART NAMES... 3 REMOTE CONTROL PART NAMES...
More informationSafety & Installation Instructions
Premium Programmable Thermostat Safety & Installation Instructions Model 8570 READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS PAGE SPECIFICATIONS............................. 1 WIRE REQUIREMENTS.........................
More informationTEC2100 Series Networked Thermostats
Product Bulletin Issue Date February 11, 2004 TEC2100 Series Networked Thermostats The TEC2100 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment
More information