Qualification of Fan-Generated Duct Rumble Noise Part 1: Test Facility

Size: px
Start display at page:

Download "Qualification of Fan-Generated Duct Rumble Noise Part 1: Test Facility"

Transcription

1 8, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Published in Vol., Part. For personal use only. Additional reproduction, distribution, or transmission SL-8- (RP-9) Qualification of Fan-Generated Duct Rumble Noise Part : Test Facility Joshua Kading J. Adin Mann, III, PhD Michael B. Pate, PhD Associate Member ASHRAE Member ASHRAE Member ASHRAE This paper is based on findings resulting from ASHRAE Research Project RP-9. ABSTRACT Duct rumble noise in HVAC air distribution systems is commonly attributed to the poor aerodynamic discharge conditions of fan outlets. To date, qualitative descriptors published in ASHRAE Handbooks have been used as design guidelines for engineers to limit the amount of duct rumble noise. The objective of this study was to design, build, and verify a test facility that could be used to accurately quantify the amount of duct rumble noise that is caused by the change in discharge conditions of a fan and duct system. The measured changes in the noise level needed to be due to the change of the discharge configuration and not outside influences on the system. To cover a large range of typical installation configurations the test facility was to be capable of changing between fourteen different discharge conditions, consisting of four different fan orientations and different distances between the fan outlet and the primary duct inlet. Further, the fan was operated at eight operating points on the fan curve that were chosen to cover the full operating range of a fan. The design and evaluation of the test facility is described. INTRODUCTION The discharge configuration of a fan affects the amount of low frequency duct rumble noise downstream of the fan. Rumble noise, defined for this study as noise in the 6 Hz to Hz one third octave bands, is considered by many practicing engineers as an indication of turbulence caused by poorly designed fan discharge conditions. The ASHRAE Applications Handbook () presents a qualitative diagram correlating the discharge conditions with a qualitative descriptor of the resulting noise. However, there is no sound level data that is connected with the qualitative descriptor. Specifically, even though the descriptor gives a rough guideline it does not give a means to predict the increased rumble for various designs. The predictions are needed to compare design alternatives such as weighing the cost of modifying the orientation and position of the fan compared to a noise control measure such as lagging or lining the duct. With noise level predictions, the various design alternatives can be effectively compared. ASHRAE therefore funded a project to provide information on the changes in rumble noise generated by various fan configurations. In addition to providing predictions of the rumble noise levels, an auxiliary goal of the work was to identify the mechanisms for the changing rumble noise. The specification on the design of the test system was that four different fan discharge conditions could be tested with four different lengths of duct from the fan to the first transition in the system. The measurements were to be performed at 8 operating points of the fan, to be accomplished by varying inlet restriction to the fan and the fan speed. The design and verification of the test system along with initial results are presented. TEST SYSTEM The system consists of three rooms shown in Figure : a fan room, a measurement room and an outlet room. The fan room was the inlet to the duct system, the measurement room is acoustically isolated from the rest of the system and the outlet room was open to the rest of the building, including the Joshua Kading is a mechanical engineer at Stanley Consultants, Inc., Muscatine, IA. J. Adin Mann, III, is an associate professor and Michael B. Pate is a professor in the Department of Mechanical Engineering, Iowa State University, Ames, IA. 8 ASHRAE 7 Published in Vol., Part.

2 8, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Published in Vol., Part. For personal use only. Additional reproduction, distribution, or transmission Figure Test system layout. fan room. The inlet to the fan room was controlled with a hole in the door with adjustable area, thus acting as the volume damper. The fan room was -7 x - and -8 tall. The measurement room was -7 x - and -8 tall. These were the desired room dimensions to limit the number of low frequency room modes in the measurement room. Both the fan room and the measurement room have structural insulation walls, as well as insulated floors. Further, the ceiling was not connected to the rest of the building. The volume damper in the fan room door had a maximum open area of 7 x. There were three boards, two inches and one inches tall, each constructed from ¾ thick medium density fiberboard (MDF) that could be added or removed from the bottom of the dampers damper. These served as a means to make large adjustments to the open area of the volume damper. In addition, there was a 8-/ tall sheet of MDF that slides over the top section of the hole. This sliding board allowed a finer analog control over the inlet area that was necessary to ensure that the system was operating at the desired operating points. A board was placed between the fan room inlet at the fan inlet. The board was placed at distance nearly the same at the distance from the fan inlet ant the wall opposite the fan room inlet. The board was used to provide the greatest possibility that the inlet to the fan was uniform from each side. 8 The duct work was made from gauge sheet metal without insulation lining. Each joint was constructed with easily modified duct joints. The fixed section of the duct work began at a transition piece that extended from the middle of the fan room to the fan room wall. This transitioned the outlet of the fan from 9. x 6. to the measurement section of the duct which was 8 x 8. The transition was 7 - long, creating a slope ratio of : from the fan ducting to the test duct section. ASHRAE Application () recommends a slope of :7 to :. The transition was enclosed in a 5 by 9 by tall box constructed from MDF and lined with duct board fiberglass. The box was designed to isolate the transition duct from break in noise from the fan room. The fiberglass insulation on the inside of the box was suspended against the MDF in order to limit any vibration damping that might occur if the insulation touched the duct. The duct work continued through the measurement room and out into the outlet room through a 7 long duct work and terminates into an outlet plenum designed to keep the noise in the outlet room from the measurement room. The test ducting consisted of 5 long sections with stiffening creases every and a -/ angle support bars every -6 running along the exterior of the 8 width of the cross section. In the measurement room there was a single section Published in Vol., Part.

3 8, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Published in Vol., Part. For personal use only. Additional reproduction, distribution, or transmission that was -7 long. This short length was in the measurement room because a 5 section was required to exit the measurement room to join into the outlet sound trap. Because of space limitations outside the measurement room, the location of the sound trap was fixed. On all the joints of the fixed section of the duct work a sealing adhesive was used along with bolts to join the duct together. The duct suspension system was standard and its vibration was not monitored. It was assumed that any excitation of the duct support would be part of a typical installation and should be included in the study. Further, while the duct walls could have resonance frequencies in the range of the study, they were again assumed to be part of the system being characterized, so were not identified or removed. The inlet to the duct system could be varied depending on the desired fan configuration. The fan outlet had a flexible rubber connector that consisted of a long fan flange, a length of rubber flex, and a length of duct flange. The duct section from the outlet of the flexible connector to the input of the transition section was variable. The fan could discharge horizontally, directly into the duct system, or vertically in an up blast position, into a length of duct and then into an elbow. Figure shows the fan exhausting in an up blast position, with a straight length of duct 8 long, and then the elbow at the inlet to the fixed section of ducting. When the elbow was not in place the farthest distance the fan can be extended from the transition is. The distance between the fan and the elbow could be up to 55 long. The duct work from the fan to the elbow was the same dimensions as the fan outlet, 9. x 6. The elbow had double wide turning vanes spaced evenly apart. The last piece of duct work that could be added to the system for the duct configuration was a short transition piece. The piece s inlet was 6 x 9. and the outlet is 9. x 6. The length is only 7. This allowed for the fan to be rotated 9 and have a discharge perpendicular to the elbow. On all of the joints in this section of the duct the ducting was bolted together. Clamps were used when possible and duct tape was applied to the exterior of the ducting joints. Fan Discharge Conditions The test system was flexible enough to achieve a total of fourteen discharge conditions. This was accomplished by manipulating the fan orientation and duct arrangement between the fan discharge and the down stream ducting. The four fan orientations are referred to as discharge configurations (shown in Figure ). Three of these configurations had four different duct lengths between the fan and the duct system inlet, and one had two different lengths between the fan and the duct inlet. Configuration : the fan was in front blast, blowing directly in to the transition piece. This configuration could only be moved away from the transition piece because of the room size. Configuration : the fan discharged air in a circular direction to the transition piece. The fan could be to 55 away from the elbow. Configuration : the fan discharged air against the circular direction of the duct. The fan could be to 55 away from the elbow. Configuration : the fan discharged air perpendicular to the duct. In this configuration there was a transition piece at the elbow that directed the air into the duct system. The transition piece was 7 long and therefore the fan was always at least 7 away from the elbow. This distance could also increase to 55. The distance between the fan and the elbow were set in terms of effective duct diameter, D h, which for a rectangular duct is D h = ( H W).65 ( H + W).5, where H is the height and W is the width of the duct. The effective duct diameter for the fan outlet used in the study (9. x 6 ) was. For the measurement duct (8 x 8 ) the effective duct diameter was. The distance away from the elbow was measured in increments of this duct diam- () Figure Four fan outlet configurations with distance D as the variable length ( to in. in Configuration, to 55 in. in Configurations and, and 7 to 55 in. in Configuration ). Published in Vol., Part. 9

4 8, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Published in Vol., Part. For personal use only. Additional reproduction, distribution, or transmission eter. There were distances away from the elbow that were achieved by the system:, ( ), (8 ) and. (55 ) duct diameters. It was hypothesized that the distance between the fan outlet and the first flow disturbance would have a great impact on the aerodynamics of the system. In order to measure all of these configurations, the fan needed to be capable of rotating on two axes. The fan also needed to be mounted in such a way that it could be lifted up and down depending on the distance D. To do this, the fan was always mounted to a base. The mounting base was a double steel strut that held the fan and motor assemble together. The mounting base had six vibration isolation springs that it supported by. The four corner springs were 8 lb, isolation springs, the middle two are lb, isolation springs. For Configuration the motor needed to be raised to reach the keyway of the fan shaft. This was done by mounting two additional cross beams directly under the motor. The mounting base was made with -5/8 gauge x combination framing strut. The mounting base was supported by the support base, also made of -5/8 gauge framing strut, and kept up by six pillar supports. The top and bottom cross bars helped to support the structure. The middle bars could be shifted up or down depending on the configuration or duct diameter that was desired. The isolation springs from the mounting base rested directly on the middle bar of the support structure. Additional diagonal beams were added on the sides and across the center to give extra rigidity and support. Because of the changes in the structure, the diagonal beams were not in the same location between configurations. The fan and motor were mounted to a single structural base with an 8 direct drive coupler shaft according to ASHRAE Standards (999) arrangement 7. The coupler was chosen so the assembly did not need to be rigid like a concrete pad. This was necessary because of the large number of configurations required for the test plan. The 5 hp motor was controlled with an inverter control variable speed drive that could reach a peak speed of 9 rpm. The fan was a Size 8 Class, double wide/double inlet, forward curve, 8-inch diameter wheel, scroll fan. Outlet Plenum The air flow exhausted into an outlet plenum that was constructed as a sound trap. The sound trap was designed to eliminate the noise path from the outlet to the rest of the system (Figure ). The outlet plenum had an internal path that forms an arc from the duct at the top of the plenum to the outlet at the bottom of the plenum. The exterior was made from medium density fiber board (MDF) shell that was mounted on a x structure. The interior consisted of three layers. The first was fiberglass board x x, these boards were cut to be stacked and fill in between the MDF and the duct lining insulation. The second layer was duct board fiberglass that consisted of x 8 x sections. This lining was the section that the air was directly against and was designed to withstand high velocities. The last layer was perforated aluminum sheet metal, oval pattern, with a width of., gauge, that was used to create a rigid lining to the insulation. The perforated aluminum sheet metal was held in place by wire hangers and stapled to the exterior walls (where possible) at the inlet and exit. The geometry of the sound trap resulted in a center airflow radius of. The inlet to the plenum was the same as the duct 8 x 8 ; the air flow was sloped to an exit of width of 5 -. This gave a ¾ inlet to exit ratio in order to control the air velocity and the turbulence that was generated at the exit. Selection of Operating Conditions The required operating points for the fan were stated in the research project RFP. These populate the fan curve to give a representation of the effects on sound level at different typical operating points. This fan curve was used as a basis for setting all of the operating points. The eight required operating condition matrix were as follows: One fan speed at. inch of water pressure drop that represents the 9% wide open flow load curve. Two fan speeds at. and.5 inches of water pressure drop that represents the 8% wide open flow load curve. Three fan speeds at.,.5 and. inches of water pressure drop that represents the 6% wide open flow load curve. Two fan speeds at.5 and. inches of water pressure drop that represents the 5% wide open flow load curve. Since there was some discussion in the research monitoring committee on the procedures for setting these conditions, the procedures are presented in detail. The values in the first row in Table are taken from the fan curve provided by the fan manufacturer. These values are all at a fan speed of, rpm. For the next rows, the flow rate is calculated as a percentage of % WOF and then from the fan curves, the fan pressure drop is found. These points define the load curve which is referred to by the percent wide open flow (%WOF). Figure Outlet plenum diagram the inlet is screwed to the outlet of the system duct. Published in Vol., Part.

5 8, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Published in Vol., Part. For personal use only. Additional reproduction, distribution, or transmission Fan laws (ASHRAE Systems and Equipment ()) were then used to determine the values for operating conditions for each required pressure drop and flow rate (%WOF). where N = the desired fan speed (rpm) N =, rpm p = the desired pressure drop (inch wg) p = the pressure drop of the %WOF (inch wg) Q = the desired volume flow rate (CFM) Q = the desired volume flow rate of the desired %WOF (CFM) Using these equations and the fan curve supplied by the fan manufacturer, the conditions for each of the specified operating points were calculated, Table. During testing, the first step was to set the system to a desired load curve. This was done by setting the fan at the speed of one of the operating points on the load curve and then Table. Fan Curve Values Fan Flow Rate % of Wide Open Flow (%WOF) -- p N = N ---- p -- p Q = Q ---- p Volume Flow Rate (CFM) Fan Pressure Drop (inches water) %, 9% 9,98.7 8% 7,76. 6%, 5. 5% 7,77.9 () () varying the inlet flow area until the required flow rate was obtained. The other operating points were obtained by changing the fan speed to the required value in Table. The flow rate was measured, but the inlet restriction was not varied to compensate for any difference between the measured and desired flow rate. Thus, setting the operating points requires determining the setting of the inlet restriction for each of the load curves for each of the fan/duct configuration. Acoustic Isolation Because the sound measurements were taken in the measurement room, it was critical that the measurement room be acoustically isolated from the rest of the system. There were many potential sound paths (ASHRAE Applications ().) Since there were no return or supply air vents in the room the major concerns were the airborne noise transmitted directly through the wall, the structural noise that is transmitted through the floor and walls (also known as flanking paths), and the breakout noise that is generated from the duct itself. Of these three, the only one that needed to be measured was the breakout noise of the duct. The other two paths had to be minimized so the measurements could reflect the change in noise of the duct. The ASHRAE research RFP required a transmission loss between the measurement room and fan room of at least db at one-third octave bands between 6 Hz and 5 Hz. Noise reduction measurements were performed in the rooms with the duct and outlet plenums installed. The duct work passes through holes in the walls that were ½ to ¾ larger than the duct. The duct was framed around the wall openings with MDF (medium density fiberboard) leaving a small gap so the MDF was not touching the duct work. Fiberglass insulation was added in the large gaps and the remaining gaps are sealed with caulking. The interior of the measurement room separating wall was lined with MDF for additional mass. After preliminary tests the door inlet to the measurement room was covered by a sheet of MDF board. Table. Calculated Values for Operating Points in Terms of %WOF and Pressure Drop Flow Rate (%WOF) Fan Speed (rpm) Volume Flow Rate (CFM) Fan Pressure Drop (inches water) 9% 986 5,7. 8% 7 9,7.,6 5, ,99. 6% 96 9,9.5,59,878. 5% 99 5,55.5,75 7,. Published in Vol., Part.

6 8, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Published in Vol., Part. For personal use only. Additional reproduction, distribution, or transmission Sound tests were performed by placing a broad-band white-noise source in the fan room and measuring the sound pressure level at 8 locations in the fan room and 9 locations in the measurement room, Figure. The duct work entrance in the fan room was covered by a sheet of MDF that covered the inlet. The requirements were a minimum noise reduction of db at all one-third octaves, which was achieved as indicated in Figure. Airflow Pressure Traverse The airflow pressure traverse station was used to measure pressure drop and airflow rate. The airflow station was 6. duct diameters (6-6 ) downstream from the transition exit and.9 (5 ) duct diameters upstream from the outlet plenum. The airflow station consisted of six pitot tubes connected to a single pressure transducer. It was assumed in using these pitot tubes that the airflow was parallel to the duct axis. The pressure traverse was set at five positions in the duct height in order to obtain air velocity measurements at the points specified in the ASHRAE Handbook Fundamentals (ASHRAE Handbook Fundamentals 5). The five heights were -/8, 5-/ 8, 9, -7/8, and 6-5/8 above the duct bottom and the six pitot tubes were spread across the bottom of the duct at, - /,, 7, 6-/ and 5 from the duct side. The measured velocity pressure was averaged over all pitot tube locations and then used to calculate a air flow rate through the duct in cubic feet per minute. Q C p = w ( L W) ρ V = velocity (ft/min) p w = averaged measured velocity pressure (lbf/in ) C = correction factor 96.5 ρ = air density (lbm/ft ) H = duct height (ft) W = duct width (ft) The pressure drop across the fan was estimated rather than directly measured. ASHRAE Standard 5 specifies that to measure the pressure rise across a fan the taps must be a distance at least an 8.5 duct diameters away from the fan. There were a large number of discharge configurations some that included the fan outlet to be directly against the elbow, making it impossible to consistently measure the down stream pressure 8.5 duct diameters down stream. Therefore the static pressure of the duct system was measured at the airflow station. This measured pressure drop, Δp meas, includes the pressure drop across the fan, Δp fan, and the down stream ducting system, Δp duct. () 6 of duct length and any duct diameters between the fan and elbow. Using tabulated values for parameters to model each of these elements, the value for Δp duct was estimated as Δp duct = fl + C ρ V D h 97, (6) where ΣC = the summation of the local loss coefficients f = friction factor L = duct length D h = equivalent duct diameter V = air velocity. A separate friction factor was calculated for each section of straight duct work f. ε 68 = (7) D h Re If f =.8: f = f If f <.8: f =.85f +.8 where ε = material absolute roughness factor, ft Re = Reynolds number. The loss coefficients, C, in Equation 6 were assumed to be constant for the duct geometry. Future work could be done using factors that take into account the flow profiles that are measured. Setup for Sound Testing The sound pressure level in the room and in the duct were measured in both discrete frequency spectra from to 8 Hz and one-third octave bands from.5 to, Hz. The primary output of the study was the one-third octave levels between 6 and 5 Hz. Δp meas = Δp fan Δp duct (5) In order to use equation 5 to solve for the Δp fan the pressure drop across the down stream ducting, Δp duct needed to be estimated. The duct system includes the elbow, transition, 6 - Figure Measured noise reduction between the fan and measurement room. Published in Vol., Part.

7 8, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Published in Vol., Part. For personal use only. Additional reproduction, distribution, or transmission Sound levels were measured at an array of 9 locations in the measurement room and 7 in the duct. The 9 microphone room locations were on a x array with the row spaced apart and each column spaced apart, Figure 5. The array was spaced from the building north wall and 6 from the building west wall. These measurements were made at different heights to avoid any room modes. The heights were 6, 56 and 8, denoted as L, L and L in Figure 5. The 7 locations on the duct were distributed along joints. The main purpose of these measurements was checking for duct modes. The microphones were mounted near joints in the duct to minimize the stiffness changes created by the microphone mounts. Joint A, at the entrance of the duct to the measurement room, consisted of a single microphone at the bottom corner of the duct. The second cross section, 5 down stream from the building west wall, joint B in Figure 5, contained six microphones. Five of the microphones were along the bottom evenly spaced apart; the sixth was along the side of the duct 9 high. Each duct microphone mount was designed to hold the microphone tightly, with minimal flow induced noise and a tight seal so that sound was not transmitted from the duct into the room through the microphone mount. The mount consisted of a plastic tube assembly that held the microphone with an o- ring around it. The microphone was secured with a rubber capped screw so as not to damage the microphone. The top of the tube contained a thick piece of fiberglass between the microphone face and the hole in the duct. A tube assembly at each of the seven measurement locations was positioned flush to the duct with a ½ inch diameter hole in the duct. When a microphone was not inserted into a holder, a ½ inch diameter wood dowel was inserted to minimize sound transmission through the assembly. bearings were mounted to and in the case of the motor, the accelerometer was mounted on one of the motor mount points. As an example of the results, Figure 7 shows the velocity peak values for the 8 operating points with Configuration and no duct diameters to the transition inlet. The values are all much higher than the.5 in/s requirement that are specified in the RFP. Table shows the fan speed in rpm and the resulting frequency in Hz. Table also contains a listing of the frequencies for the peaks in the frequency spectra for each operating condition. It is important to note:. The fan has 6 blades, so the blade passage frequency was far above the peaks that are causing concern. Thus the source of the peaks in the vibration response was not directly related to an interaction of each blade to an aerodynamic loading such as passing the cutoff in the fan shroud.. The fan and motor shaft were running at the same speed. The data in Table shows that the fan vibration was dominated by the shaft rpm and harmonics while the motor vibration was typically at multiples of three times the shaft rpm. These results indicate that the motor and fan were effectively decoupled with the shaft coupler. In the case of the fan, the results in Vibration and Balancing A maximum peak vibration velocity of.5 in/sec was specified in the research project RFP. In order to minimize vibration, each aspect of the system was balanced individually. For example, the tolerance of fan/motor shaft coupler was between.5 and.55. This measurement was made and verified at the beginning of each configuration. However, because of the large variations of the configurations for the tests, the support structure was more flexible than a typical field application. Therefore, it was important to monitor the fan vibration for every test. The fan vibration was measured with a tri-axial accelerometer since the direction of greatest vibration was not known. The accelerometer was attached with the orientation shown in Figure 6. The accelerometer signal was time integrated to produce a velocity time signal. The average of discrete frequency spectrum and 8 seconds of each signal was recorded for every test condition. The vibration measurements were taken at two locations, one on the fan and one on the motor. In the case of the fan, the accelerometer was mounted on the ¼ steel plate that the shaft Figure 5 Figure 6 Floor microphone locations. Accelerometer axis (the x-axis runs in plane with the duct work, the y-axis funs along the coupler shaft, and the z-axis runs perpendicular to the floor). Published in Vol., Part.

8 8, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Published in Vol., Part. For personal use only. Additional reproduction, distribution, or transmission Figure 7 Velocity peaks of the operating points for Configuration, duct diameters. Table. Operating Points, Fan Speed in Terms of RPM and Frequency and Peak Frequencies Operating Points Fan Speed Peaks in Frequency Spectra % WOF ΔP (inch) rpm 5% 6% 8% Hz (fundamental + two harmonics) Fan Motor ,., ,.6, 5 6.9,., 6.9.,7 9.6, 9., ,.6, , 8., , 8.8, 9.7.,.,.., 6., ,., 5.6 5,.6, ,.6, 6..,7 9.5, 9., ,.6, , 8., ,.8, 5.7.9,.8,.6 6., 7.9,.8.5,6 8.8, 7.6, , 7.5, ,.8, 7. 9% ,., ,., 9. 5.,., 5. Table also show that the vibration was dominated by a once per revolution imbalance in the fan and fan shaft assembly. The peaks in the discrete frequency sound spectra have been compared to the harmonics of the fan and motor assembly vibration. The peaks in the discrete frequency spectra generally corresponded to the vibration harmonics. The th and 8 th harmonics have the largest peaks. These peaks reached up to db greater than the rest of the frequency spectra. In Figure 8 the discrete frequency spectra of 9% at. inch pressure drop is shown. The major peaks occur at the st, th, 8 th, and 9 th harmonics. These are only slightly greater than the rest of the frequency peaks. Figure 9 shows autospectra of the vibrations. All of the operating points have been analyzed in the same way. The largest peaks consistently occur at the th and the 8 th harmonic from the noise data. However, as seen in these examples, the peak vibration response was not at the th and 8 th harmonic. At the peaks in the vibration spectra there was little or no effect on the sound data. Therefore, the spectra support a conclusion that the peaks in the measured sound spectra are not caused by the fan or motor vibration and the vibration levels of the fan and motor are acceptable. To identify the source of the th and 8 th harmonic in the measured sound spectra, it should be noted that the fan blades are supported by four rods which extend over three quarters of the inlet. This is strong evidence that the th and 8 th harmonics that are seen in the noise spectra are results of aerodynamic disturbance of the fan rather than a vibration problem. This is further evidence that the fan and motor vibration levels, while exceeding the RFP initial requirement, are not contaminating the sound measurements. Repeatability An uncertainty analysis has been performed with the system. Three tests were taken at all of the operating points and at a single configuration (Configuration, duct diameters). Each test used a different testing sequences. The first was test was done with a constant operating point and rotating the microphones among the locations in the room. The second test was Published in Vol., Part.

9 8, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Published in Vol., Part. For personal use only. Additional reproduction, distribution, or transmission Figure 8 9% WOF in. pressure drop, average discrete frequency spectra with fan rpm harmonics shown (fan frequency 6.5 Hz). Figure 9 Frequency spectrum vibration of the fan. The x-axis is the horizontal; the y-axis is the axial, and the z-axis is the vertical. 9 load curve at. in. pressure drop operating point. done with constant microphone locations and rotating among the operating points. The last test was done randomly changing both the operating conditions and the microphone locations. Once the three test were taken the results were averaged and the variance in db was analyzed. Figure shows the uncertainty of three trials at the operating point 5% of the wide open flow,.5 inch pressure drop for the one third octave bands between 6 and 5 Hz. These results are consistent with all the operating points collected. Table is the maximum uncertainty for each operating point in the test that was described above. These values are only for Configuration and duct diameters away from the elbow. The uncertainty pertains to one measurement without changing the configuration or duct diameter. These results indicate that the uncertainty in the measured data is db, well within the range required by the RFP. Published in Vol., Part. 5

10 8, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Published in Vol., Part. For personal use only. Additional reproduction, distribution, or transmission Table. Uncertainty of Sound Measurements (db) 9%,. 8%,. 6%,. 8%,.5 6%,.5 5%,.5 6%,. 5%,. ±.8 db ±.6 db ±. db ±. db ±. db ±.9 db ±.8 db ±.7dB Figure Uncertainty of the 5% WOF at.5 in. pressure drop. System Modes The presence of modes in the system was analyzed. The modes that have been identified can be seen in the measured sound spectra. Further, the variation in the sound levels at the frequencies of the identified modes also has a spatial pattern typical of the modes in the duct and room. However none of the modes identified have a great impact on the sound results. Room Modes The predicted modes, shown in Table 5, are based on the dimensions of the room. The X, Y, and Z are the axis of the room and directions of the modes. The estimations are taken from equation, where L x, L y and L z are the dimensions of the room. f n = c -- n ---- x L x ---- n y L y ---- n z + + L z c = ( m s) The X axis follows the duct along the room, the Y axis is perpendicular to the duct, and the Z axis is along the vertical of the room. These modes were then compared to the narrow band sound pressure levels that were recorded in the room (Figure ). At 68 Hz there is the indication that there is a (,,) room mode when looking at the sound pressure level distribution in the room. However, looking at the narrow band it does not have a large impact on the sound level. It was therefore concluded that room modes did not impact the measured sound levels. (8) Duct Modes The duct modes were estimated in the same way as the room modes and it was concluded that they did not had a significant impact on the sound pressure levels. The narrow band sound pressure levels are shown in Figure. These are the sound averages of 5 locations along the duct and not all 7. To identify the duct modes the sound pressure levels are observed along the cross section of the duct. By looking at the narrow band frequency levels and the distribution of the sound pressure level in the duct there are no distinguishable duct modes. There is possibly one at Hz that peaks 5 db higher than the broad band levels; however, this is not significant enough to isolate. Looking at both the room and duct narrow band frequency, sharp peaks can be seen. These peaks are not consistent between each operating point, and were therefore concluded not to be room or duct modes. These are likely caused by aerodynamic disturbances. CONCLUSIONS The purpose of this facility was to measure the effects of aerodynamic disturbances on the sound levels. The system that was developed was capable of fourteen different fan outlet conditions: four different discharge configurations and four different duct distances to the duct inlet. Three of the four configurations could use all four of the duct distances, one of the configurations could only use two. The system could regulate operating conditions by changing fan speed and an inlet restriction. The operating conditions could be kept constant and verified by using the fan laws and a fan curve that were provided by the fan manufacturer. The measurement room was acoustically isolated from the rest of the system by added mass and an outlet plenum, and other potential sources of problems such as fan vibration, motor vibration, room modes, and duct modes, were studied and concluded to not impact the measured sound levels. The output from the system is the one third octave band and discrete frequency sound levels transmitted from the duct to the measurement room. The one-third octave band values were repeatable to within db. With the control available for the fan speed, fan orientation, and system flow rate, the system was shows capable to study the impact of fan orientation in a duct system on rumble noise transmitted through a duct system. REFERENCES ASHRAE Fundamentals (5). ASHRAE Handbook-5 ASHRAE Fundamentals, American Society of Heating, Refrigeration and Air-conditioning Engineers Inc. 6 Published in Vol., Part.

11 8, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Published in Vol., Part. For personal use only. Additional reproduction, distribution, or transmission Table 5. Predicted Modes in the Measurement Room X Y Z Freq X Y Z Freq Figure Average discrete frequency spectra in the measurement room, Configuration, duct diameters, ΔP =. in. Figure Average discrete frequency spectra in the duct, Configuration, duct diameters, ΔP =. in. ASHRAE Systems and Equipment (). ASHRAE Handbook- Systems and Equipment, American Society of Heating, Refrigeration and Air-conditioning Engineers Inc. ASHRAE Applications, (). ASHRAE Handbook- Applications, American Society of Heating, Refrigeration and Air-conditioning Engineers Inc. ASHRAE Standards, (999). ASHRAE Standard 5-999Laboratory Methods of Testing Fans for Aerodynamic Performance Rating, American Society of Heating, Refrigeration and Air-conditioning Engineers Inc. Bies and Hansen () Engineering Noise Control Theory and Practice, New York, NY: Spon Press. p. 7. Published in Vol., Part. 7

12 ESL-PA Reproduced with permission of the copyright owner. Further reproduction prohibited without permission. Published in Vol., Part.

Fans: Features and Analysis

Fans: Features and Analysis Technical Development Program COMMERCIAL HVAC EQUIPMENT Fans: Features and Analysis PRESENTED BY: Michael Ho Version 1.2 Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Section

More information

Fan Laws. Keith Miller. Samuel Tepp Associates. Paul Cenci, P. E.-Principal Brian England-Principal. Samuel Tepp Associates 1/6/10

Fan Laws. Keith Miller. Samuel Tepp Associates. Paul Cenci, P. E.-Principal Brian England-Principal. Samuel Tepp Associates 1/6/10 Fan Laws Keith Miller Samuel Tepp Associates Paul Cenci, P. E.-Principal Brian England-Principal Basic Terms CFM - Cubic Feet per Minute, volume (amount) of air being moved SP - Static Pressure, resistance

More information

FAN WALL Technology. Product

FAN WALL Technology. Product FAN WALL Technology is a new approach to air handler design using an array of smaller fans to replace a traditional single large fan. FAN WALL Technology This is a fan-array approach to air handler design

More information

EXPERIMENTAL ACOUSTIC CHARACTERIZATION OF A WET VACUUM CLEANER

EXPERIMENTAL ACOUSTIC CHARACTERIZATION OF A WET VACUUM CLEANER EXPERIMENTAL ACOUSTIC CHARACTERIZATION OF A WET VACUUM CLEANER Cinzia Buratti, Elisa Moretti and Michele Urbani Department of Industrial Engineering, University of Perugia, via G. Duranti 67, 06125 Perugia,

More information

Fan Selection. and Energy Savings

Fan Selection. and Energy Savings Fan Selection and Energy Savings Reducing power consumption by minimizing system pressure loss and choosing the right equipment HBy BRIAN MLEZIVA Greenheck Fan Corp. Schofield, Wis. Power Consumption HVAC

More information

ARI 260 Standard: Sound Rating of Ducted Air Moving and Conditioning Equipment

ARI 260 Standard: Sound Rating of Ducted Air Moving and Conditioning Equipment Return to www.enoisecontrol.com ARI 260 Standard: Sound Rating of Ducted Air Moving and Conditioning Equipment Common Sources of Noise in Air Handling Equipment ASHRAE Seminar 51 Sponsored by TC 2.6 Michael

More information

Understanding Fan System Effects

Understanding Fan System Effects Fan Application FA/101-99 A technical bulletin for engineers, contractors and students in the air movement and control industry. Understanding Fan System Effects The air moving industry uses a common term

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP)

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) Our Expertise, Your Air-Moving Solution ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) PART# 0601710001_rev_A INSTALLATION, OPERATION & MAINTENANCE MANUAL Please read and save these instructions for future reference.

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.

More information

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,

More information

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) www.blowtech.in we make air move Blowtech Air Devices Pvt. Ltd. was founded in 1988 and quickly established

More information

PDH & Professional Training

PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 PDH & Professional Training PDH Storm, by Engineers Edge, LLC CONTENTS 1. INTRODUCTION 1.1 GENERAL CRITERIA 1.2 DESIGN PROCEDURE

More information

AcoustiFlo Fans: Retrofit Solutions and Beyond

AcoustiFlo Fans: Retrofit Solutions and Beyond AcoustiFlo Fans: Retrofit Solutions and Beyond The Most Energy Efficient Plenum Fan in the World! The AcoustiFLO Modular Fan RETROFITS Ideal for fan replacement inside any air handling unit Module is 35

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans

Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans PARAG FANS & COOLING SYSTEMS LTD. Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans Registered Office & Works Plot No.1/2B & 1B/3A, Industrial Area No.1 A.B.Road, Dewas 455001 (M.P.)

More information

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating.

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating. SECTION 15890 DUCTWORK PART 1 - GENERAL 1.1 SECTION INCLUDES A. Metal ductwork. B. Duct cleaning. 1.2 RELATED SECTIONS A. Section 09900 - Painting: Weld priming, weather resistant, paint or coating. B.

More information

Introduction to Fans. The Basics of Fan Principles and Terminology

Introduction to Fans. The Basics of Fan Principles and Terminology Introduction to Fans The Basics of Fan Principles and Terminology Airflow Principles A fan is a rotating device that creates pressure differential that results in air movement Pressure rise in a fan Downstream

More information

Agitation and Mixing

Agitation and Mixing Agitation and Mixing Agitation: Agitation refers to the induced motion of a material in a specified way, usually in a circulatory pattern inside some sort of container. Purpose is to make homogeneous phase.

More information

Chilled Water DOAS Fan Powered Terminal Units

Chilled Water DOAS Fan Powered Terminal Units Chilled Water DOAS Fan Powered Terminal Units CHILLED WATER DOAS FAN POWERED TERMINAL UNITS DOAS TERMINAL UNITS FEATURES AND BENEFITS MINIMUM VENTILATION CONTROL The DOAS unit provides the Designer, Owner

More information

Sound Performance Rating of Non-ducted Indoor Airconditioning

Sound Performance Rating of Non-ducted Indoor Airconditioning AHRI Standard 350 2015 Standard for Sound Performance Rating of Non-ducted Indoor Airconditioning and Heat Pump Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

SECTION DUCTWORK

SECTION DUCTWORK PART 1 GENERAL 1.1 REFERENCES SECTION 23 31 00 DUCTWORK A. ASHRAE - Handbook, Duct Design B. ASHRAE - Handbook, Duct Construction C. ASTM A90/A90M - Standard Test Method for Weight (Mass) of Coating on

More information

Glossary of Terms Laboratory & Fume Exhaust Fans

Glossary of Terms Laboratory & Fume Exhaust Fans Glossary of Terms Laboratory & Fume Exhaust Fans ACTUATOR, 2-POSITION SPRING RETURN A spring return actuator generally used to control the isolation dampers below the fans. This actuator allows for fully

More information

IBIS INTERNATIONAL, INC. DESIGN STANDARDS FOR DUCTING OF EQUIPMENT

IBIS INTERNATIONAL, INC. DESIGN STANDARDS FOR DUCTING OF EQUIPMENT IBIS INTERNATIONAL, INC. DESIGN STANDARDS FOR DUCTING OF EQUIPMENT INTRODUCTION This bulletin will assist in the design and modification of ducting used to connect IBIS equipment to machinery or areas

More information

Direct Fired Heater Model AD Specification

Direct Fired Heater Model AD Specification Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI

More information

The Current (2017) State of the Art for Air Leakage in Ductwork

The Current (2017) State of the Art for Air Leakage in Ductwork The Current (2017) State of the Art for Air Leakage in Ductwork Over the last ten years there has been a major shift in the way ASHRAE has approached air leakage in ductwork. This is reflected in the latest

More information

SECTION DUCTWORK

SECTION DUCTWORK SECTION 15890 DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07270 - Firestopping and Fire and Smoke Barrier Caulking. 2. 15260 - Vibration Isolation. 3. 15280 - Thermal Insulation (HVAC).

More information

GIVE A FAN A CHANCE Installation Dos & Don ts

GIVE A FAN A CHANCE Installation Dos & Don ts GIVE A FAN A CHANCE Installation Dos & Don ts 1 Give a Fan a Chance Installation Dos & Don ts Choosing the right fan for the right application is paramount, which is why every product in our range is designed

More information

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements. SECTION 15855 AIR HANDLING UNITS WITH COILS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Central Station Air Handling Units. B. Related Sections: 1.02 REFERENCES 1. Section 15010 - Basic Mechanical

More information

INSTALLATION DO S AND DON TS

INSTALLATION DO S AND DON TS 4.0 NOISE CONTROL Figure 4.1. - Transitions Abrupt transitions immediately adjacent to an attenuator will cause the attenuator pressure drop to increase. Ensure transitions close to attenuators are gradual

More information

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design Fan motor (PSC or ECM). UL Listed 1 insulation conforms to UL Test 181 and NFPA 90A. Plenum air filter rack. (Filter Optional) Casing has

More information

Selecting Fans and Determining Airflow for Grain Drying and Storage

Selecting Fans and Determining Airflow for Grain Drying and Storage Proceedings of the Integrated Crop Management Conference Proceedings of the 1993 Integrated Crop Management Conference Dec 2nd, 12:00 AM Selecting Fans and Determining Airflow for Grain Drying and Storage

More information

Queen St E & Leslie St Noise Analysis Toronto, Ontario. Toronto Transit Commission Streetcar Department 1900 Yonge Street Toronto, ON M4S 1Z2

Queen St E & Leslie St Noise Analysis Toronto, Ontario. Toronto Transit Commission Streetcar Department 1900 Yonge Street Toronto, ON M4S 1Z2 ASSESSMENT REPORT - Project: 151.08 Queen St E & Leslie St Noise Analysis Toronto, Ontario Prepared for: Toronto Transit Commission Streetcar Department 1900 Yonge Street Toronto, ON M4S 1Z2 Prepared by:

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 233516 - ENGINE EXHAUST SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Exhaust fans. B. Ductwork and duct fittings. C. Inlet fittings. D. Accessories. E. Carbon monoxide detectors. 1.2 RELATED

More information

Development of Motor Fan Noise Prediction Method in Consideration of Operating Temperature during Engine Idling

Development of Motor Fan Noise Prediction Method in Consideration of Operating Temperature during Engine Idling New technologies Development of Motor Fan Noise Prediction Method in Consideration of Operating Temperature during Engine Idling Yasuhito Suzuki* Masahiro Shimizu* Abstract In these years there is an increasing

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

CASE HISTORY: RETROFIT OF COAL MILL EXHAUST FAN STUDY OF FAN PERFORMANCE AND EROSION

CASE HISTORY: RETROFIT OF COAL MILL EXHAUST FAN STUDY OF FAN PERFORMANCE AND EROSION CASE HISTORY: RETROFIT OF COAL MILL EXHAUST FAN STUDY OF FAN PERFORMANCE AND EROSION David R. Grupp Director of Research Robinson Industries, Inc. 400 Robinson Drive Zelienople, PA 16063 CASE HISTORY:

More information

THE CONTROL METHOD OF THE INFLOW TURBU- LENCE INTERACTION NOISE FOR ROUTER COOLING FAN

THE CONTROL METHOD OF THE INFLOW TURBU- LENCE INTERACTION NOISE FOR ROUTER COOLING FAN The 21 st International Congress on Sound and Vibration 13-17 July, 2014, Beijing/China THE CONTROL METHOD OF THE INFLOW TURBU- LENCE INTERACTION NOISE FOR ROUTER COOLING FAN Yingbo Xu, Xiaodong Li School

More information

Smoke extraction duct of sheet steel

Smoke extraction duct of sheet steel Smoke extraction duct of sheet steel The accessories that are available, as for example inspection openings, steel grilles, plenum boxes, ceiling diffusers, splitter attenuators, bends, tees and connecting

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type Plenum box with damper blade and square diffuser face Horizontal swirling air discharge For comfort zones, with fixed air control blades Circular and

More information

Rosemex Products 96 VENTILATION CLIMATAIR COMPARTMENT AIR HANDLING UNITS

Rosemex Products 96 VENTILATION CLIMATAIR COMPARTMENT AIR HANDLING UNITS 10 Rosemex Products 96 VENTILATION CLIMATAIR COMPARTMENT AIR HANDLING UNITS 2 INDEX Page Description - Introduction -Application - Data... 2 Typical Installation... 3 Sound performance... 3-6 Dimensional

More information

FCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual

FCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual FCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual FAN POWERED TERMINALS Receiving Inspection Prior to removing the shipping material, visually inspect the packing materials. There

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type Plenum box with damper blade (optional) Horizontal swirling air discharge With very low sound power level for comfort zones, with fixed air control blades

More information

FAN ENGINEERING. Surge, Stall and Instabilities in Fans

FAN ENGINEERING. Surge, Stall and Instabilities in Fans FAN ENGINEERING Industrial Fans & Services Information and Recommendations for the Engineer Surge, Stall and Instabilities in Fans Introduction Users of fan systems would like to experience a steady, continuous

More information

Isolation room exhaust fan noise in a hospital

Isolation room exhaust fan noise in a hospital Isolation room exhaust fan noise in a hospital Chad HIMMEL 1 1 JEAcoustics, USA ABSTRACT Healthcare facilities with airborne infection isolation rooms for patients will often use a central building exhaust

More information

Don t Turn Active Beams Into Expensive Diffusers

Don t Turn Active Beams Into Expensive Diffusers This article was published in ASHRAE Journal, April 2012. Copyright 2012 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be

More information

CAT-SIUH-2000(3) SUPERSEDES CAT-SIUH-98(2) SARAVEL INDUSTRIAL UNIT HEATERS

CAT-SIUH-2000(3) SUPERSEDES CAT-SIUH-98(2) SARAVEL INDUSTRIAL UNIT HEATERS CAT-SIUH-2000(3) SUPERSEDES CAT-SIUH-98(2) SARAVEL INDUSTRIAL UNIT HEATERS TABLE OF CONTENTS Introduction...3 Selection & Application.....4 Selection Examples......5-6 Ratings......7-8 Correction Factors......9-10

More information

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004) High Plume Blowers Suggested Specification Section 15500 (Master Format 1996) Suggested Specification Section 23 38 16 (Master Format 2004) PART 1 GENERAL 1.01 WORK INCLUDED High Plume Laboratory Exhaust

More information

2. HEAT EXCHANGERS MESA

2. HEAT EXCHANGERS MESA 1. INTRODUCTION Multiport minichannel and microchannel aluminium tubes are becoming more popular as components in heat exchangers. These heat exchangers are used in various industrial applications and

More information

Displacement Ventilation

Displacement Ventilation Displacement Ventilation Displacement Ventilation Displacement Ventilation vs. Dilution Ventilation Characteristics Design Considerations Layout and Selection Product Overview Casino Case Study Dilution

More information

Ceiling diffusers. Type DLQL

Ceiling diffusers. Type DLQL X X testregistrierung Type Horizontal one-way air discharge Horizontal two-way air discharge Horizontal four-way air discharge Horizontal duct connection For horizontal one-way to four-way air discharge,

More information

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems 233100 AIR DISTRIBUTION PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230700 HVAC Insulation B. Section 237300 Air Handling C. Section 230900 Building Automation and Control System Guidelines D. Section

More information

AGN 088 Air Flow and Cooling

AGN 088 Air Flow and Cooling Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 088 Air Flow and Cooling COOLING AIR FOR AN ALTERNATOR Both open air ventilated alternators and enclosed alternators

More information

EHH SERIES DRAW THROUGH FAN COILS CFM

EHH SERIES DRAW THROUGH FAN COILS CFM EHH SERIES DRAW THROUGH FAN COILS 400-5000 CFM TABLE OF CONTENTS TABLE OF CONTENTS 2 INTRODUCTION 3 GUIDE SPECIFICATIONS 4 UNIT OVERVIEW 6 TECHNICAL DATA 8 DIMENSIONS 10 COMPUTER SELECTION 11 GEMCOOL PROFILE

More information

FAN TYPES CENTRIFUGAL FAN Forward Curve Centrifugal Fan

FAN TYPES CENTRIFUGAL FAN Forward Curve Centrifugal Fan FAN TYPES In order to cover a wide range of applications, fans are manufactured in a variety of type. They can be classified under three general types : (a) Centrifugal, (b) Axial and (c) Mixed flow. Table

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

MPA Modular Plenum Array Installation, Operation, and Maintenance Manual

MPA Modular Plenum Array Installation, Operation, and Maintenance Manual MPA Modular Plenum Array Installation, Operation, and Maintenance Manual This publication contains the installation, operation and maintenance procedures for standard units of the MPA: Modular Plenum Array.

More information

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat Abstract Axial flow fans, while incapable of developing high pressures, they are well suitable for handling large volumes of air at relatively

More information

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup. SECTION 23 70 00- CENTRAL HVAC EQUIPMENT PART 1: GENERAL 1.1 PURPOSE: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

AXICO ANTI-STALL CONTROLLABLE PITCH-IN-MOTION AND ADJUSTABLE PITCH-AT-REST VANEAXIAL FANS

AXICO ANTI-STALL CONTROLLABLE PITCH-IN-MOTION AND ADJUSTABLE PITCH-AT-REST VANEAXIAL FANS Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS AXICO ANTI-STALL CONTROLLABLE PITCH-IN-MOTION AND ADJUSTABLE PITCH-AT-REST VANEAXIAL FANS FPAC FPMC FPDA CATALOG AX351 JULY 2001 WWW.TCF.COM

More information

CHAPTER IV AIR DISTRIBUTION AND BALANCE

CHAPTER IV AIR DISTRIBUTION AND BALANCE CHAPTER IV AIR DISTRIBUTION AND BALANCE 4.1. INTRODUCTION When projecting an air-conditioning system, the following steps should be followed: 1) Determine the heat gain or loss 2) Establish the air requirements

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Submittal Data Performance Data Electrical Data

Submittal Data Performance Data Electrical Data ERMS Series Submittal Data Submittal Data Unit Designation: Job name: Architect: Engineer: Contractor: Performance Data Revision: 07/01/11 Cooling Capacity: EER: Heating Capacity: COP: Ambient Air Temp:

More information

SAFETY AND INSTALLATION MANUAL MODEL 8100

SAFETY AND INSTALLATION MANUAL MODEL 8100 SAFETY AND INSTALLATION MANUAL ENERGY RECOVERY VENTILATORS MODEL 8100 Provides year-round fresh air Recovers 77% of the apparent heating or cooling energy from the exhausted air See Warnings Page 3 Table

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 can be

More information

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack #1 Digvijay A. Shelar, #2 N.S. Gohel, #3 R. S. Jha #1 Mechanical Engineering Department,

More information

ENGINEERING LETTER 4

ENGINEERING LETTER 4 ENGINEERING LETTER 4 The New York Blower Company 7660 Quincy Street, Willowbrook, Illinois 60521-5530 TEMPERATURE AND ALTITUDE AFFECT FAN SELECTION INTRODUCTION Fan performance changes with the density

More information

Direct Gas-Fired Make-Up Air

Direct Gas-Fired Make-Up Air Direct Gas-Fired Make-Up Air Model TSU Heavy Duty, High Airflow Applications Manufacturing and Industrial Facilities Up to 64,000 cfm August 2012 Products Model TSU Direct Gas-Fired Make-Up Air Unit The

More information

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

RAMAPO COLLEGE OF NEW JERSEY CCA0803 PHASE II HOUSING REHABILITATION 2012

RAMAPO COLLEGE OF NEW JERSEY CCA0803 PHASE II HOUSING REHABILITATION 2012 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Trane Engineers Newsletter Live

Trane Engineers Newsletter Live Trane Engineers Newsletter Live Presenters: John Murphy, Dustin Meredith and Jeanne Harshaw (host) Trane program number: APP-CMC059-EN Agenda Trane Engineers Newsletter Live Series Abstract The Air Movement

More information

Selecting the Correct Fan

Selecting the Correct Fan Selecting the Correct Fan Ryan B. Johnson Air Purification Company Sales Engineer Member, ASHRAE Pikes Peak Chapter rjohnson@airpurificationcompany.com 1 Your Speaker circa 1998 Fan Types Applications

More information

Product Data. Features/Benefits. 36CBAC,AE,AF,AH,AQ,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm

Product Data. Features/Benefits. 36CBAC,AE,AF,AH,AQ,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm Product Data 36CBAC,AE,AF,AH,AQ,AN, PB,PD,PS Series Active and Passive Chilled Beams 11 to 190 cfm 36CBAC A36-449.eps Chilled beam units offer: An increase in total airflow Sensible cooling and heating

More information

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas HVAC Guideline Specifications WHISPER-JET: SET SERIES Two Stage Positive Pressure Gas-Fired Infrared Radiant Tube Type Heater Commercial/Industrial Applications Technical Summary Input Range: 80,000/60,000

More information

1997 STANDARD for APPLICATION OF SOUND RATING LEVELS OF OUTDOOR UNITARY EQUIPMENT. Standard NORTH FAIRFAX DRIVE! ARLINGTON, VIRGINIA 22203

1997 STANDARD for APPLICATION OF SOUND RATING LEVELS OF OUTDOOR UNITARY EQUIPMENT. Standard NORTH FAIRFAX DRIVE! ARLINGTON, VIRGINIA 22203 1997 STANDARD for APPLICATION OF SOUND RATING LEVELS OF OUTDOOR UNITARY EQUIPMENT Standard 275 4301 NORTH FAIRFAX DRIVE! ARLINGTON, VIRGINIA 22203 IMPORTANT SAFETY RECOMMENDATIONS It is strongly recommended

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

Vibration Of Cooling Tower Fans. Barry T. Cease Cease Industrial Consulting Vibration Institute 2015

Vibration Of Cooling Tower Fans. Barry T. Cease Cease Industrial Consulting Vibration Institute 2015 Vibration Of Cooling Tower Fans Barry T. Cease Cease Industrial Consulting Vibration Institute 2015 ceasevibration@icloud.com (843) 200-9705 1 WHAT IS A COOLING TOWER AND WHAT DOES IT DO? All cooling towers

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Placement within a mechanical room is required for all major mechanical equipment. Only small units may be roof-mounted, and shall be made as inconspicuous

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 08:50:16 AM Job Name: EarthWise Modular Climate Changer Full Spec Location: Any Town, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SUBMITTALS Submittals

More information

VentZone Systems VentZone Zoned IAQ with Heat Recovery Kits

VentZone Systems VentZone Zoned IAQ with Heat Recovery Kits RESIDENTIAL SYSTEM SOLUTIONS VentZone Systems VentZone Zoned IAQ with Heat Recovery Kits VentZone Zoned IAQ Kits with Heat Recovery combine a Standard Residential Heat Recovery Ventilator (HRV) with residential

More information

CENTRAL AIR CONDITIONER SPLIT SYSTEM

CENTRAL AIR CONDITIONER SPLIT SYSTEM CENTRAL AIR CONDITIONER SPLIT SYSTEM WITH ELECTRONIC CONTROL SERIES: DS INSTALLATION INSTRUCTIONS INDEX GENERAL... 2 UNIT LOCATION CRITERIA... 2 DIMENSIONAL DRAWINGS... 3 INDOOR UNIT INSTALLATION... 5

More information

PERFORMANCE OF A MODEL IN-LINE VORTEX SEPARATOR. Keng-Choon Lee Geothermal Institute, The University of Auckland, Private Bag 92019, Auckland, New

PERFORMANCE OF A MODEL IN-LINE VORTEX SEPARATOR. Keng-Choon Lee Geothermal Institute, The University of Auckland, Private Bag 92019, Auckland, New PERFORMANCE OF A MODEL IN-LINE VORTEX SEPARATOR Keng-Choon Lee Geothermal Institute, The University of Auckland, Private Bag 92019, Auckland, New Key words: Separator, condensate removal, two-phase flow

More information

ENERVEX RSV CHIMNEY FAN

ENERVEX RSV CHIMNEY FAN ENERVEX RSV 200-450 CHIMNEY FAN 3000775 06.16 Installation & Operating Manual READ AND SAVE THESE INSTRUCTIONS! ENERVEX Inc. 1685 Bluegrass Lakes Parkway Alpharetta, GA 30004 USA P: 770.587.3238 F: 770.587.4731

More information

FAN ENGINEERING. Sealing of Fan Housings

FAN ENGINEERING. Sealing of Fan Housings FAN ENGINEERING Information and Recommendations for the Engineer FE-700 Sealing of Fan Housings Introduction A variety of options are offered by fan manufacturers to seal fan housings. Sealing the housing

More information

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 1.1 MODIFICATIONS OF

More information

Sound Performance Rating of Outdoor Unitary Equipment

Sound Performance Rating of Outdoor Unitary Equipment 2015 Standard for Sound Performance Rating of Outdoor Unitary Equipment AHRI Standard 270 WITH ADDENDUM 1, Sound Performance Rating of Outdoor Unitary Equipment March 2016 Note: This addendum is not ANSI

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 23 0594 - TESTING, ADJUSTING, AND BALANCING (TAB) PART 1 - GENERAL 1.1 SUMMARY A. This Section includes testing, adjusting and balancing HVAC systems to provide design conditions as indicated by

More information

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork. SECTION 15855 AIR HANDLING UNITS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15885 - Air Filtration Equipment. 3. 15890 - Ductwork. 1.02 REFERENCES A. Air Moving

More information

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc. System Components with ` Emphasis on Packaged Rooftop Application and Installation Jerry Cohen President Jacco & Assoc. Agenda Define and relate in practical terms the following components: System Effect

More information

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters. Section 15 _ Energy Recovery Air Handling System Part 1: GENERAL 1.1 Section Includes: A. Energy Recovery Air Handler B. Controls (most by Others) C. Equipment Schedule 1.2 Related Sections: A. Section

More information

Pulse Jet Baghouse ASTEC PULSE JET BAGHOUSE. for Asphalt Facilities

Pulse Jet Baghouse ASTEC PULSE JET BAGHOUSE. for Asphalt Facilities Pulse Jet ASTEC PULSE JET BAGHOUSE for Asphalt Facilities ASTEC PULSE JET BAGHOUSE FOR ASPHALT MIXING PLANTS Astec baghouses deliver superior performance and efficiency, while helping your plant meet

More information

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

A. General: Refer to paragraph entitled SUBMITTAL in Section Include the following data: SECTION 15860 - FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR MECHANICAL

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

Practical Consideration of Noise from Fans

Practical Consideration of Noise from Fans Practical Consideration of Noise from Fans Charles BURGESS 1 ; Rhys THOMPSON 2 1 AirEng, Australia 2 AirEng, Australia ABSTRACT Fan noise is often stated based on fan casing breakout alone, ignoring additional

More information

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information