Transcription

1 CXM/DXM CXM/DXM Digital Heat Pump Controllers Application, Operation & Maintenance Instructions 97B0003N08 Revision: 01/10/05 Table of Contents CXM / DXM Control Features Comparison 2 Part I - CXM Control 3 CXM Overview 3 Physical Dimensions and Layout 3 Product Specification 3 Safety Features 5 Diagnostic Features 6 Unit Operation Description 6 Typical Schematic 7 Part II - DXM Control 8 DXM Overview 8 Physical Dimensions and Layout 8 Basic Control Features 9 Field Selectable Inputs 9 Safety Features 10 Diagnostic Features 12 Unit Operation Description 12 Special Application Notes 13 Communications 14 Typical Schematic 16 Part III - CXM/DXM Notes CXM/DXM Sensors 17 Thermostats 18 CXM and DXM Inputs and Outputs Reference 19 Troubleshooting Chart 20 Functional Troubleshooting 21 Performance Troubleshooting 22 Revisiom History 24

2 CXM / DXM Electronic Control Features Comparison Basic Features CXM CXM-Lon CXM-MPC DXM DXM-Lon DXM-MPC High and Low Refrigerant Pressure Protection S S S S S S Water Coil Freeze Protection S S S S S S True 24VA Thermostat Signals S S S S S S Thermostat Inputs Compatible with Triacs S S S S S S Condensate Overfl ow Sensor S S S S S S Anti-Short-Cyle Time Delay S S S S S S Random Start S S S S S S Alarm (selectable dry contact or 24VA) S S S S S S Water Valve Relay S S S S S S Water Valve Relay with Compressor Delay N/A N/A N/A S S S Emergency Shutdown N/A DDC DDC S DDC DDC Night Setback with Override N/A DDC DDC S DDC DDC Outdoor Air Damper Control N/A N/A N/A S S S Advanced Features Intelligent Reset S S S S S S High and Low Voltage Protection S S S S S S Air Coil Freeze Protection S S S S S S Freeze Setpoint Field Select (water, antifreeze) S S S S S S Electric Heat Control Outputs S S S S S S Boilerless Electric Heat Control N/A N/A N/A S S S Intelligent Reversing Valve Operation N/A DDC DDC S S S High/Low Fan Speed Outputs N/A N/A N/A S S S Intelligent Fan Speed Control N/A N/A N/A S S S Thermostat Type Select (Y,O or Y,W) N/A N/A N/A S N/A N/A Reversing Valve Signal Select (O or B) N/A N/A N/A S N/A N/A Dehumidistat Input N/A N/A N/A S S S Reheat Dehumidifi cation Control* N/A N/A N/A O O O Multiple Units on One Thermostat/Wall Sensor N/A DDC DDC S DDC DDC Service and Reliability Features Service Test Mode S S S S S S LED Fault and Status Lights S S S S S S Fault Memory after Reset S S S S S S Unit Performance Sentinel S S S S S S Harness-Type Factory Wiring Connections S S S S S S Fully Noise-Tested Design S S S S S S CE Approval S S S S S S Removable Low Voltage Connector N/A N/A N/A S S S DDC / Energy Management Features Echelon LonMark Compliant N/A S N/A N/A S N/A BACNET Compliant N/A N/A S N/A N/A S Johnson N2 Compliant N/A N/A S N/A N/A S Modbus Compliant N/A N/A S N/A N/A S Leaving Air and Water Temperature Sensor N/A S S N/A S S Digital Wall Sensor N/A O O N/A O O S = Standard O = Optional DDC = Feature can be provided by DDC System CXM-Lon = CXM with LonMark Module DXM-Lon = DXM with LonMark Module CXM-MPC = CXM with MPC Module DXM-MPC = DXM with MPC Module * = Check with your Factory Representative for model availability MPC = Multiple ProtoCol (BACNET, N2, Modbus) Page 2 CXM/DXM Electronic Heat Pump Control

3 CXM Overview The CXM control is a microprocessor based heat pump controller that is simple to use, yet provides all the necessary features to improve the operation and safety of water source heat pumps. CM Part Number: 17B0001N01 CXM Control Board General Operating Parameters The following are general operating parameters for the CXM control: Operating Environment: -40 F to 176 F and up to 95% relative humidity, non-condensing. Storage Environment: -40 F to 185 F and up to 95% relative humidity, non-condensing. Power Requirements: CXM only power draw - Normally 5 VA draw at 24VAC. Maximum 9 VA draw at 24VAC. A dedicated 24VAC, 50-60Hz, 1Ph, 40VA transformer minimum is required for typical wshp application. Relay Contact Ratings: The following relays are mounted on the CXM control. Compressor Relay: 40VA at 24VAC. Alarm Relay: 28VA at 24VAC. Part I - CXM Electronic Heat Pump Control PART I CXM ELECTRONIC HEAT PUMP CONTROL Grounding: The control board is grounded through two of the metal standoffs. Field connection ratings for the CXM Control: "A" terminal: 20VA at 24VAC. Product Specification Features Anti-short cycle protection High and Low pressure cutouts Water Coil freeze protection Air Coil freeze protection Random Start Unit Performance Sentinel Over/Under Voltage protection Diagnostic LED Reset Lockout at unit or disconnect Intelligent Reset Condensate Overflow sensor Test Mode Electric Heat Outputs Accessory Water Valve Connection CXM Physical Dimensions and Layout Factory Quick Connects 4.00 Field Thermostat Connections 6.00 C R Y Y W O G R C AL1 AL2 A P1 BR BRG Test JW3 JW2 JW1- AL2 Dry CCG CC Off On FP1 Low Temp FP2 Low Temp Micro Comp Relay Status LED P2 1 HP HP LP LP FP1 FP1 FP2 FP2 RV RV CO 12 CO 1 4 P3 24Vdc EH1 EH Factory Low Voltage Molex connector for unit harness Factory Low Voltage Molex connector for electric heat harness 3/8 standoff Alarm Relay CO 17B0001N Mounting Screws: #6 sheet metal screw 1 long CXM Electronic Heat Pump Control Page 3

4 Part I - CXM Electronic Heat Pump Control Field Selectable Inputs Test Mode - Test Mode allows the service personnel to check the operation of the control in a timely manner. By momentarily shorting the test terminals, the CXM control enters a 20 minute Test Mode period in which all time delays are sped up 15 times. Upon entering Test Mode, the Status LED will fl ash a code representing the last fault. For Diagnostic ease at the thermostat, the alarm relay will also cycle during test mode. The Alarm relay will cycle on and off similar to the status LED to indicate a code representing the last fault, at the thermostat. Note: Code 1 indicates there is no fault in memory; stated differently, the control has not faulted since the last power-down to power-up sequence. Test mode can be exited by shorting the test terminals for 3 seconds. Test mode can also be entered and exited by cycling the G input, 3 times within a 60 second time period. During Test mode, the control monitors to see if the FP1 and FP2 thermistors are in the appropriate place. If the control is in Test mode, the control will lockout, with Code 9, after 30 seconds if: a) the compressor is On in cooling mode and the FP1 sensor is colder than the FP2 sensor. Or, b) the compressor is On in heating mode and the FP2 sensor is colder than the FP1 sensor. Retry Mode - If the control is attempting a retry of a fault, the status LED will slow fl ash (slow fl ash=one fl ash every 2 seconds) to indicate the control is in process of retrying. Note: In the following field configuration options, jumper wires should be clipped ONLY when power is removed from the CXM control. Water Coil Freeze Protection Limit Setting - Jumper 3 (JW3-FP1 Low Temp) provides field selection of temperature limit setting for FP1 to be 30 F or 10 F. Not Clipped=30 F. Clipped=10 F. Table 1: LED & Alarm Relay Operations Air Coil Freeze Protection Limit Setting - Jumper 2 (JW2- FP2 Low Temp) provides field selection of temperature limit setting for FP2 to be 30 F or 10 F. Not Clipped=30 F. Clipped=10 F. Alarm Relay Setting - Jumper 1 (JW1-AL2 Dry) provides field selection of Alarm Relay terminal AL2 to be jumpered to 24VAC or to be dry (no connection). Not Clipped=AL2 connected to R. Clipped=AL2 dry contacts (no connection). DIP Switches Note: In the following field configuration options, DIP switches should only be moved when power is removed from the CXM control, to insure proper operation. DIP Switch 1: Unit Performance Sentinel Disable - provides field selection to disable the UPS feature. On = Enabled. Off = Disabled. DIP Switch 2: Stage 2 Selection- provides selection of whether compressor has an on delay. If set to stage 2, the compressor will have a 3 second delay before energizing. Also, if set for stage 2, the alarm relay will NOT cycle during test mode. On = Stage 1. Off = Stage 2 DIP Switch 3: - Not Used. DIP Switch 4: DDC Output at EH2 - provides selection for DDC operation. If set to DDC Output at EH2, the EH2 terminal will continuously output the last fault code of the controller. If set to EH2 normal, then the EH2 will operate as standard electric heat output. On = EH2 Normal. Off = DDC Output at EH2. NOTE: Some CXM controls only have a 2 position DIP switch package. If this is the case, then this option can be selected by clipping the jumper which is in position 4 of SW1: Jumper not clipped = EH2 Normal. Jumper clipped = DDC Output at EH2. DIP Switch 5: Factory Setting - Normal position is On. Do not change selection unless instructed to do so by the Factory. Description of Operation LED Alarm Relay Normal Mode On Open Normal Mode with UPS Warning On Cycle (closed 5 sec., Open 25 sec.) CXM is non-functional Off Open Fault Retry Slow Flash Open Lockout Fast Flash Closed Over/Under Voltage Shutdown Slow Flash Open (Closed after 15 minutes) Test Mode - No fault in memory Flashing Code 1 Cycling Code 1 Test Mode - HP Fault in memory Flashing Code 2 Cycling Code 2 Test Mode - LP Fault in memory Flashing Code 3 Cycling Code 3 Test Mode - FP1 Fault in memory Flashing Code 4 Cycling Code 4 Test Mode - FP2 Fault in memory Flashing Code 5 Cycling Code 5 Test Mode - CO Fault in memory Flashing Code 6 Cycling Code 6 Test Mode - Over/Under shutdown in memory Flashing Code 7 Cycling Code 7 Test Mode - UPS in memory Flashing Code 8 Cycling Code 8 Test Mode - Swapped Thermistor Flashing Code 9 Cycling Code 9 Special Notes and Examples: - Slow Flash = 1 flash every 2 seconds - Fast Flash = 2 flashes every 1 second - Flash code 2 = 2 quick flashes, 10 sec. pause, 2 quick flashes, 10 sec. pause, etc. - On pulse 1/3 sec.; off pulse 1/3 sec. Page 4 CXM Electronic Heat Pump Control

5 Part I - CXM Electronic Heat Pump Control Safety Features The following safety features are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions. Anti-Short Cycle Protection- The control features a 5 minute anti-short cycle protection for the compressor. Note: The 5 minute anti-short cycle also occurs at power up. Random Start - The control features a 5-80 second random start upon power up. Extended Compressor Operation Monitoring - If the compressor relay has been on for 4 continuous hours, then the control will automatically turn off the compressor relay and wait the short cycle protection time. All appropriate safeties including the LP will be monitored during the off time. If all operation is normal, then if the compressor demand is still present, the control will turn the compressor back on. Fault Retry - In Fault Retry mode, the Status LED begins slow flashing to signal that the control is trying to recover from a fault input. The CXM control will stage off the outputs and then try again to satisfy the thermostat "Y" input call. Once the thermostat input calls are satisfied, the control will continue on as if no fault occurred. If 3 consecutive faults occur without satisfying the thermostat "Y" input call, then the control will go to Lockout mode. The last fault causing the lockout will be stored in memory and can be viewed by going into test mode. Note: If 1 Try is selected for FP1 and FP2, then there will be no retries for FP1 and FP2 faults. The control will only try one time for these faults. Lockout - In Lockout mode, the Status LED will begin fast flashing. The compressor relay is turned off immediately. Lockout mode can be soft reset via the thermostat Y input or can be hard reset via the disconnect. The last fault causing the lockout will be stored in memory and can be viewed by going into test mode. Lockout with Emergency Heat - While in Lockout mode, if W becomes active, then Emergency Heat mode will occur. High Pressure Switch - When the High Pressure Switch opens due to high refrigerant pressures, the Compressor relay is de-energized immediately since the High Pressure Switch is in series with the compressor contactor coil. The High Pressure Fault recognition is immediate as well. High Pressure Lockout Code = 2 Example: 2 quick flashes, 10 sec pause, 2 quick flashes, 10 sec. pause, etc. Low Pressure Switch - The Low Pressure Switch must be open and remain open for 30 continuous seconds during "on" cycle to be recognized as a Low Pressure fault. If the low pressure switch is open for 30 seconds prior to compressor power up it will be considered a low pressure (loss of charge) fault. The Low Pressure Switch input is bypassed for the initial 120 seconds of a compressor run cycle. Low Pressure Lockout Code = 3 Water Coil Freeze Protection (FP1) - The control will recognize an FP1 fault, during a compressor run cycle if: a) the thermistor temperature is below the selected freeze protection limit setting, AND b) the thermistor temperature is rising (getting warmer) at a rate LESS than 2 F per 30 second time period. The FP1 input is bypassed for the initial 120 seconds of a compressor run cycle. FP1 Lockout Code = 4 Air Coil Freeze Protection (FP2) - The control will recognize an FP2 fault, during a compressor run cycle if: a) the thermistor temperature is below the selected freeze protection limit setting, AND b) the thermistor temperature is rising (getting warmer) at a rate LESS than 2F per 30 second time period. The FP2 input is bypassed for the initial 120 seconds of a compressor run cycle. FP2 Lockout Code = 5 Condensate Overflow - The Condensate Overflow sensor must sense overflow levels for 30 continuous seconds to be recognized as a CO fault. Condensate Overflow will be monitored during compressor run cycle. CO Lockout Code = 6 Over/Under Voltage Shutdown - An Over/Under Voltage condition exists when the control voltage is outside the range of 18VAC to 31.5VAC. Over/Under Voltage Shutdown is self resetting in that if the voltage comes back within range of 18.5VAC to 31VAC for at least 0.5 seconds, then normal operation is restored. This is not considered a fault or lockout. If the CXM is in over/under voltage shutdown for 15 minutes, the alarm relay will close. Over/Under Voltage Shutdown Code = 7 Unit Performance Sentinel-UPS (patent pending) - The UPS feature warns when the heat pump is operating inefficiently. A UPS condition exists when: a) in heating mode with compressor energized, if FP2 is greater than 125 F for 30 continuous seconds, or b) in cooling mode with compressor energized, if FP1 is greater than 125 F for 30 continuous seconds, OR FP2 is less than 40 F for 30 continuous seconds. If a UPS condition occurs, the control will immediately go to UPS warning. The status LED will remain on as if the control is in Normal mode. (see "LED and Alarm Relay Operation Table" ). Outputs of the control, excluding LED and Alarm Relay, will NOT be affected by UPS. The UPS condition cannot occur during a compressor off cycle. During UPS warning, the alarm relay will cycle on and off. The cycle rate will be On for 5 seconds, Off for 25 seconds, On for 5 seconds, Off for 25 seconds, etc. Unit Performance Sentinel Warning Code = 8 CXM Electronic Heat Pump Control Page 5

6 Part I - CXM Electronic Heat Pump Control Swapped FP1/FP2 Thermistors - During Test mode, the control monitors to see if the FP1 and FP2 thermistors are in the appropriate place. If the control is in Test mode, the control will lockout, with Code 9, after 30 seconds if: a) the compressor is On in cooling mode and the FP1 sensor is colder than the FP2 sensor. Or, b) the compressor is On in heating mode and the FP2 sensor is colder than the FP1 sensor. Swapped FP1/FP2 Thermistor Code = 9. Diagnostic Features The Status LED on the CXM control advises the serviceman of the current status of the CXM control. The status LED can display either the current CXM mode or the last fault memory if in test mode. See Table 1 for a complete listing of codes. If the Fault type is "Primary" (HP, LP, FP1, FP2, or CO) then the Fault type will always be retained in memory (Primary faults will over write Secondary faults). If the Fault type is "Secondary" (Over/Under Voltage, UPS or Swapped FP1/FP2) then the Fault type will only be retained if there are no "Primary" faults in memory. The Secondary Fault types will not "overwrite" the Primary fault memory. Unit Operation Description PowerUp - The unit will not operate until all the inputs and safety controls are checked for normal conditions. Note: The compressor will have a 5 minute anti-short cycle delay at power-up. Standby - In Standby mode, Y and W inputs are not active. Inputs O and G may be active. Compressor will be off. Cooling - To enter Cooling mode, Y and O become active. The first time after power-up that there is a call for compressor, the compressor will follow a 5 to 80 second random start delay. There will also be a 5 minute compressor anti-short cycle protection time as well. After the random start delay and the anti-short cycle delay, the compressor relay is energized. On all subsequent compressor calls, the random start delay is omitted. Heating Stage 1 - To enter Heating Stage 1 mode, Y becomes active. The first time after power-up that there is a call for compressor, the compressor will follow a 5 to 80 second random start delay. There will also be a 5 minute compressor anti-short cycle protection time as well. After the random start delay and the anti-short cycle delay, the compressor relay is energized. On all subsequent compressor calls, the random start delay is omitted. Heating Stage 2 - To enter Heating Stage 2 mode, W becomes active (Y already active). The G input must be active or the W input is ignored. The Compressor relay remains on. EH1 is turned on immediately. With continuing Heating Stage 2 demand, EH2 will turn on after 10 minutes. The EH2 will not turn on (or will turn off if already on) if FP1 temperature is greater than 45 F and FP2 is greater than 110 F. Emergency Heat - In Emergency Heat mode, W becomes active while Y is not active. The G input must be active or the W input is ignored. EH1 is turned on immediately. With continuing Emergency Heat demand, EH2 will turn on after 5 minutes. The FP1 and FP2 temperatures do not effect emergency heat operation. Engineering Guide Specifications The following engineering guide specifications for the CXM control should be a part of all product submittals. CXM Control A microprocessor-based compressor controller (CXM) shall be provided to monitor and control unit operation. The control shall provide compressor and electric heater sequencing, high and low pressure monitoring, field selectable water and air coil freeze protection sensing, condensate overflow sensing, over/under voltage monitoring, and unit performance sentinel. The control shall also provide for water valve connection, a test mode, short cycle protection, random start-up, as well as fault LED, fault memory, and intelligent fault retry. The control shall employ a quick attach harness assembly for low voltage connections to the CXM control board to aid in troubleshooting or replacement. An integral terminal block with screw terminals shall be provided on the CXM control for all field low voltage connections. Table 1a: Fault Description Table Fault Fault LED Code Fault Condition No Fault In Memory 1 There has been no fault detected since the last power down/power up sequence High Pressure Switch 2 HP Open Instantly Low Pressure Switch or LOC 3 Freeze Protection Coax - FP1 4 Freeze Protection Air Coil - FP2 5 Condensate overflow 6 Over/Under Voltage Shutdown LP open for 30 continuous seconds before or during a call (bypassed for first 120 seconds) FP1 below Temp limit for 30 continous seconds (bypassed for first 120 seconds of operation) FP2 below Temp limit for 30 continous seconds (bypassed for first 120 seconds of operation) Sense overflow (grounded) for 30 continous seconds 7 (Autoreset) "R" power supply is <18VAC or >31.5VAC UPS Warning 8 Unit Performance Warning signal has Swapped FP1/FP2 9 FP1 and FP2 are in reversed positions Page 6 CXM Electronic Heat Pump Control

7 Part I - CXM Electronic Heat Pump Control CXM Electronic Heat Pump Control Page 7

8 Part II - DXM Electronic Heat Pump Control PART II DXM ELECTRONIC HEAT PUMP CONTROL DXM Overview The DXM Electronic Control is a robust, microprocessor based heat pump controller that is advanced and featureladen for maximum application flexibility. The DXM control has all of the basic CXM control features plus additional inputs and outputs which allow for extensive system capability. The DXM control has relay outputs for compressor, fan, fan speed, reversing valve, alarm relay, and 2 configurable accessory outputs. There are 3 LEDʼs which provide status indication. There are inputs for safety pressure switches, freeze protection thermistors, condensate overflow sensor, DIP switch selection inputs, thermostat inputs, night setback inputs, and emergency shutdown input. There are also 2 communications ports: one for communications with DXM dual compressor heat pumps, and another for communications with DXM slaved heat pumps. CM Part Number: 17B0002N01 DXM Control Board Physical Dimensions and Layout General Operating Parameters The following are general operating parameters for the DXM control: Operating Environment: -40 F to 176 F and up to 95% relative humidity, non-condensing. Storage Environment: -40 F to 185 F and up to 95% relative humidity, non-condensing. Power Requirements: DXM only power draw - - Normally 8 VA draw at 24VAC - Maximum 12 VA draw at 24VAC. A dedicated 24VAC, 50-60Hz, 1Ph, 40VA transformer minimum is required for typical WSHP application. Relay and Connection Contact Ratings: The following relays are mounted on the DXM control: Compressor Relay: 40VA at 24VAC Alarm Relay: 28VA at 24VAC Reversing Valve: 28VA at 24VAC Accessory Relay 1: 28VA at 24VAC Accessory Relay 2: 28VA at 24VAC Fan Enable Relay: 1 HP at 240VAC Fan Speed Relay: 1 HP at 240VAC Connection ratings on the DXM control: A terminal: 20VA at 24VAC. Larger solenoid valve draw should be used with accessory relays. Grounding: The control board is grounded through two of the metal standoffs. 5" P1 Y1 Y2 W1 O/W2 G R C AL1 C R R C Sig P5 Com2 Sig DXM 17P0002N01 C P4 Com1 Fan Enable (240Vac) N.O. Fan Speed (240Vac) N.O. Com Com N.C. 3/8 standoff 7" AL2 R NSB C ESD OVR H A R NO1 NC1 COM NO2 NC2 COM R P3 P2 Alarm Relay Facttory Use JW4 AL2 Dry Acc1 Relay Acc2 Relay Micro U2 Off Micro U1 On Status 1 HP HP Test LP LP Fault FP1 FP1 FP2 FP2 RV Relay RV RV CO 12 CO P7 Test Jumpers JW3 - FP1 Low Temp 1 24Vdc JW2 - FP2 Low Temp EH1 JW1 - LP Norm. Open 4 EH2 P6 Off On Comp Relay CCG CC 6 1/2" Factory low voltage molex connection for unit harness Factory low voltage molex connection for electric heat harness S1 S /2" 4 Mounting Screws #6 sheet metal screw 1 long Page 8 DXM Electronic Heat Pump Control

9 Part II - DXM Electronic Heat Pump Control Basic Control Features Anti-short cycle protection High and Low pressure cutouts High and Low voltage cutouts Water Coil freeze protection Air Coil freeze protection Random Start Status LED, Test LED, and Fault LED Reset Lockout at unit or disconnect Intelligent Reset Condensate Overflow sensor Test Mode Electric Heat Outputs Accessory Water Valve Connection Advanced Control Features Two accessory relays configurable for multiple applications Night setback with override capability Emergency shutdown capability Communications port for DXM dual compressor applications Communications port for DXM slave heat pump applications Intelligent fan speed capabilities Boilerless electric heat Removable thermostat connector for ease of installation and service Accepts heat pump (Y,O) or heat/cool (Y, W) thermostat types Accepts heat pump thermostats with O or B reversing valve control logic Dehumidistat input for advanced functions Field Selectable Inputs Test Mode Test Mode allows the service personnel to check the operation of the control in a timely manner. By momentarily shorting the test terminals, the DXM control enters a 20 minute Test Mode period in which all time delays are sped up 15 times. During Test Mode, the Test LED will turn on. For Diagnostic ease at the thermostat, the alarm relay will also cycle during test mode. The Alarm relay will cycle on and off similar to the fault LED to indicate a code representing the last fault, at the thermostat. Note: Code 1 indicates there is no fault in memory; stated differently, the control has not faulted since the last power-down to power-up sequence. Test mode can be exited by shorting the test terminals for 3 seconds. Test mode can also be entered and exited by cycling the G input, 3 times within a 60 second time period. During Test mode, the control monitors to see if the FP1 and FP2 thermistors are in the appropriate place. If the control is in Test mode, the control will lockout, with Code 9, after 30 seconds if: a) the compressor is On in cooling mode and the FP1 sensor is colder than the FP2 sensor. Or, b) the compressor is On in heating mode and the FP2 sensor is colder than the FP1 sensor. Retry Mode - If the control is attempting a retry of a fault, the status LED will slow fl ash (slow fl ash=one fl ash every 2 seconds) to indicate the control is in process of retrying. Note: In the following field configuration options, jumper wires should be clipped ONLY when power is removed from the DXM control. Water Coil Freeze Protection Limit Setting - Jumper 3 (JW3-FP1 Low Temp) provides field selection of temperature limit setting for FP1 to be 30 F or 10 F. Not Clipped=30 F. Clipped=10 F. Air Coil Freeze Protection Limit Setting - Jumper 2 (JW2- FP2 Low Temp) provides field selection of temperature limit setting for FP2 to be 30 F or 10 F. Not Clipped=30 F. Clipped=10 F. Alarm Relay Setting - Jumper 4 (JW4-AL2 Dry) provides field selection of Alarm Relay terminal AL2 to be jumpered to 24VAC or to be dry (no connection). Not Clipped=AL2 connected to R. Clipped=AL2 dry contacts (no connection). Low Pressure Normally Open Jumper 1 (JW1-LP Norm Open) Provides field selection for Low Pressure input to be Normally Closed or Normally Open. Not Clipped = LP Normally Closed. Clipped = LP Normally Open. DIP Switches Note: In the following field configuration options, DIP switches should only be moved when power is removed from the DXM control to insure proper operation. DIP Package #1 (S1) DIP Package #1 is 8 position and provides the following setup selections. DIP 1.1: Unit Performance Sentinel Disable - provides field selection to disable the UPS feature. On = Enabled. Off = Disabled. DIP 1.2: Compressor Relay Staging Operation - provides selection of Compressor Relay Staging Operation. The compressor relay can be selected to turn on with Stage 1 or Stage 2 call from the thermostat. This is used with Dual Stage units (2 compressors where 2 DXM controls are being used) or with Master/Slave applications. In Master/Slave applications, each compressor and fan will stage according to its appropriate DIP 1.2. If set to stage 2, the compressor will have a 3 second on-delay before energizing during a Stage 2 demand. Also, if set for stage 2, the Alarm relay will NOT cycle during Test Mode. On=Stage 1. Off=Stage 2. DIP 1.3: Thermostat Type (heat/cool) - provides selection of Thermostat Type. Heat Pump or Heat/Cool thermostats can be selected. When in Heat/Cool mode, Y1 is input call for Cooling Stage 1, Y2 is input call for Cooling Stage 2, W1 is input call for Heating Stage 1, and O/W2 is input call for Heating Stage 2. In Heat Pump mode, Y1 is input call for Compressor Stage 1, Y2 is input call for Compressor Stage 2, W1 is input call for Heating Stage 3 or Emergency Heat, and O/W2 is the input call for RV (heating or cooling dependent upon DIP 1.4). On=Heat Pump. Off=Heat/Cool. DXM Electronic Heat Pump Control Page 9

10 Part II - DXM Electronic Heat Pump Control DIP 1.4: Thermostat Type (O/B) - provides selection of Thermostat Type. Heat Pump Thermostats with O output on with Cooling or B output on with Heating can be selected. On=HP Stat with O output with Cooling. Off=HP Stat with B output with Heating. DIP 1.5: Dehumidifi cation Mode - provides selection of normal or dehumidification fan mode. In dehumidification mode, the Fan Speed relay will remain off during Cooling Stage 2. In normal mode, the Fan Speed relay will turn on during Cooling Stage 2. On=Normal fan mode. Off=Dehumidification mode. DIP 1.6: DDC Output at EH2 - DIP Switch 1.6 provides selection for DDC operation. If set to DDC Output at EH2, the EH2 terminal will continuously output the last fault code of the controller. If set to EH2 normal, then the EH2 will operate as standard electric heat output. On = EH2 Normal. Off = DDC Output at EH2. DIP 1.7: Boilerless Operation - provides selection of Boilerless Operation. In Boilerless mode, only the compressor is used for heating mode when FP1 is above the temperature specified by the setting of DIP 1.8. If DIP 1.8 is set for 50 F, then the compressor is used for heating as long as FP1 is above 50 F. Below 50 F, the compressor is not used and the control goes into Emergency Heat mode, staging on EH1 and EH2 to provide heating. If a thermal switch is being used in place of the FP1 thermistor, then only the compressor will be used for heating mode when the FP1 terminals are closed. If the FP1 terminals are open, then the compressor is not used and the control goes into Emergency Heat mode. On=normal. Off=Boilerless operation. DIP 1.8: Boilerless Changeover Temperature - provides selection of Boilerless changeover temperature setpoint. On=50 F. Off=40 F. Table 2: Accessory Relay 1 Configuration Dip 2.1 Dip 2.2 Dip 2.3 Acc1 Relay Option On On On Cycle with fan Off On On Digital NSB On Off On Water valve slow opening On On Off OAD Off Off Off Reheat option - Humidistat Off On Off Reheat option - Dehumidistat All other DIP combinations are invalid Table 3: Accessory Relay 2 Configuration Dip 2.4 Dip 2.5 Dip 2.6 Acc2 Relay Option On On On Cycle with compressor Off On On Digital NSB On Off On Water valve - slow opening On On Off OAD All other DIP combinations are invalid DIP Package #2 (S2) DIP Package #2 is 8 position and provides the following setup selections. DIP 2.1: Accessory1 relay personality - provides selection of Acc1 relay personality. See Table 2. DIP 2.2: Accessory1 relay personality - provides selection of Acc1 relay personality. See Table 2. DIP 2.3: Accessory1 relay personality - provides selection of Acc1 relay option. See Table 2. DIP 2.4: Accessory2 relay personality - provides selection of Acc2 relay personality. See Table 3. DIP 2.5: Accessory2 relay personality - provides selection of Acc2 relay personality. See Table 3. DIP 2.6: Accessory2 relay personality - provides selection of Acc2 relay option. See Table 3. DIP 2.7: Auto Dehumidifi cation Fan Mode or High Fan Mode - provides selection of Auto Dehumidification Fan Mode or High Fan Mode. In Auto Dehumidification Mode, the Fan Speed relay will remain off during Cooling Stage 2 IF the H input is active. In High Fan Mode, the Fan Enable and Fan Speed relays will turn on when the H input is active. On=Auto Dehumidification Mode. Off=High Fan Mode. DIP Switch 2.8: Factory Setting - Normal position is On. Do not change selection unless instructed to do so by the Factory. Safety Features The following safety features are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions. Anti-Short Cycle Protection - The control features a 5 minute anti-short cycle protection for the compressor. Note: The 5 minute anti-short cycle also occurs at power up. Random Start - The control features a 5-80 second random start upon power up. The random start delay will be present after a control power up and after returning from Night Setback or Emergency Shutdown modes. Extended Compressor Operation Monitoring - If the compressor relay has been on for 4 continuous hours, then the control will automatically turn off the compressor relay and wait the short cycle protection time. All appropriate safeties including the LP will be monitored during the off time. If all operation is normal, then if the compressor demand is still present, the control will turn the compressor back on. Fault Retry - In Fault Retry mode, the Status LED begins slow flashing to signal that the control is trying to recover from a fault input. The Fault LED will also begin flashing a code representing the last fault, which occurred. The DXM control will stage off the outputs and then try again to satisfy the thermostat call for compressor. Once the thermostat input calls are satisfied, the control will continue on as if no fault occurred. If 3 consecutive faults occur without satisfying the thermostat call for compressor, then the control will go to Lockout mode. The last fault causing the lockout will be stored in memory and is displayed by the Fault LED. Page 10 DXM Electronic Heat Pump Control

11 Part II - DXM Electronic Heat Pump Control Note: If 1 Try is selected for FP1 and FP2, then there will be no retries for FP1 and FP2 faults. The control will only try one time for these faults. Lockout - In Lockout mode, the Status LED will begin fast flashing. The Fault LED will be flashing a code representing the last fault, which occurred that caused the lockout. The compressor relay is turned off immediately. Lockout mode can be soft reset via the thermostat by removing the call for compressor, or can be hard reset via the disconnect. The last fault causing the lockout will be stored in memory and is displayed by the Fault LED. Lockout with Emergency Heat - If the DXM is configured for Heat Pump thermostat mode (see DIP 1.3), the DXM is in Lockout mode, and the W input becomes active, then Emergency Heat mode will occur during Lockout. High Pressure Switch - When the High Pressure Switch opens due to high refrigerant pressures, the Compressor relay is de-energized immediately since the High Pressure Switch is in series with the compressor contactor coil. The High Pressure Fault recognition is immediate as well. The Fault LED will immediately begin flashing Code 2 when a High Pressure Fault occurs. High Pressure Lockout Code = 2 Example: 2 quick flashes, 10-sec pause, 2 quick flashes, 10- sec. pause, etc. Low Pressure Switch - The Low Pressure Switch must be open and remain open for 30 continuous seconds during a compressor on cycle to be recognized as a Low Pressure fault. If the low pressure switch is open for 30 seconds prior to compressor power up it will be considered a low pressure (loss of charge) fault. The Low Pressure Switch input is bypassed for the initial 120 seconds of a compressor run cycle. The Fault LED will immediately begin flashing Code 3 when a Low Pressure Fault occurs. Low Pressure Lockout Code = 3 Water Coil Freeze Protection (FP1) -The control will recognize an FP1 fault, during a compressor run cycle if: a) the thermistor temperature is below the selected freeze protection limit setting, AND b) the thermistor temperature is rising (getting warmer) at a rate LESS than 2 F per 30 second time period. The FP1 input is bypassed for the initial 120 seconds of a compressor run cycle. The Fault LED will immediately begin flashing Code 4 when a FP1 Fault occurs. FP1 Lockout Code = 4 Air Coil Freeze Protection (FP2) - The control will recognize an FP2 fault, during a compressor run cycle if: a) the thermistor temperature is below the selected freeze protection limit setting, AND b) the thermistor temperature is rising (getting warmer) at a rate LESS than 2 F per 30 second time period. The FP2 input is bypassed for the initial 120 seconds of a compressor run cycle. The Fault LED will immediately begin flashing Code 5 when a FP2 Fault occurs. FP2 Lockout Code = 5 Condensate Overflow - The Condensate Overflow sensor must sense overflow levels for 30 continuous seconds to be recognized as a CO fault. Condensate Overflow will be monitored at all times. The Fault LED will immediately begin flashing Code 6 when a Condensate Overflow Fault occurs. Condensate overflow will be monitored during compressor run cycle. CO Lockout Code = 6 Over/Under Voltage Shutdown - An Over/Under Voltage condition exists when the control voltage is outside the range of 18VAC to 31.5VAC. Over/Under Voltage Shutdown is self-resetting in that if the voltage comes back within range of 18.5VAC to 31VAC for at least 0.5 seconds, then normal operation is restored. This is not considered a fault or lockout. If the DXM is in over/under voltage shutdown for 15 minutes, the alarm relay will close. Over/Under Voltage Shutdown Code = 7 Unit Performance Sentinel-UPS (patent pending) - The UPS feature warns when the heat pump is operating inefficiently. A UPS condition exists when: a) In heating mode with compressor energized, if FP2 is greater than 125 F for 30 continuous seconds, or b) In cooling mode with compressor energized, if FP1 is greater than 125 F for 30 continuous seconds, OR FP2 is less than 40 F for 30 continuous seconds. If a UPS condition occurs, the control will immediately go to UPS warning. The status LED will remain on as if the control is in Normal mode. (see "LED and Alarm Relay Operation Table"). Outputs of the control, excluding Fault LED and Alarm Relay, will NOT be affected by UPS. The UPS condition cannot occur during a compressor off cycle. During UPS warning, the Alarm Relay will cycle on and off. The cycle rate will be On for 5 seconds, Off for 25 seconds, On for 5 seconds, Off for 25 seconds, etc Unit Performance Sentinel Warning Code = 8 Swapped FP1/FP2 Thermistors - During Test mode, the control monitors to see if the FP1 and FP2 thermistors are in the appropriate place. If the control is in Test mode, the control will lockout, with Code 9, after 30 seconds if: a) the compressor is On in cooling mode and the FP1 sensor is colder than the FP2 sensor. Or, b) the compressor is On in heating mode and the FP2 sensor is colder than the FP1 sensor. Swapped FP1/FP2 Thermistor Code = 9. ESD The ESD (Emergency Shut Down) mode is utilized when the ERV (Energy Recovery Ventilator) option is applied to an RE series rooftop unit to indicate an ERV fault. A contact closure at the ERV unit will connect common to the ESD terminal, which will shut down the rooftop/erv units. The green status light will flash code 3 when the unit is in ESD mode. The ESD mode can also be enabled from an external common signal to terminal ESD (see Thermostat Inputs section for details). ESD mode = code 3 (green status LED) DXM Electronic Heat Pump Control Page 11

12 Part II - DXM Electronic Heat Pump Control Diagnostic Features The Status LED and Fault LED on the DXM control advises service personnel of the current status of the DXM control. The Status LED will indicate the current mode that the DXM control is in. The Fault LED will ALWAYS flash a code representing the LAST fault in memory. If there is no fault on memory, then the Fault LED will flash Code 1. See Table 4 for a complete listing of codes. Unit Operation Description Power Up The unit will not operate until all the inputs and safety controls are checked for normal conditions. Note: The compressor will have a 5-minute anti-short cycle delay at power-up. Standby/Fan Only In Standby mode, the compressor will be off. The Fan Enable, Fan Speed, and RV relays may be on if appropriate inputs are present. If there is a Fan 1 demand, then the Fan Enable relay will turn on immediately. If there is a Fan 2 demand, then the Fan Enable and Fan Speed relays will turn on immediately. Note: DIP1.5 (Dehum Fan Mode Select) has no effect upon Fan 1 and Fan 2 outputs. The RV relay will not directly track the input demands for RV, the DXM control will employ smart RV control. This ensures that the RV will only switch positions if the thermostat has called for a heating/cooling mode change. Heating Stage 1 In Heating Stage 1 mode, the Fan Enable and Compressor relays are turned on immediately. If configured as Stage 2 (DIP1.2=off), then the compressor and fan will not turn on until there is Stage 2 demand. The Fan Enable relay and Compressor relay are turned off immediately when the Heating Stage 1 demand is removed. The control reverts to Standby mode. If there is a Master/Slave situation or a Dual Compressor situation, all Compressor relays and related functions will track with their associated DIP1.2. Heating Stage 2 In Heating Stage 2 mode, the Fan Enable and Compressor relays remain on. The Fan Speed relay is turned on immediately. The Fan Speed relay is turned off immediately when the Heating Stage 2 demand is removed. The control reverts to Heating Stage 1 mode. If there is a Master/Slave situation or a Dual Compressor situation, all Compressor relays and related functions will track with their associated DIP1.2. Heating Stage 3 In Heating Stage 3 mode, the Fan Enable, Fan Speed and Compressor relays will remain on. EH1 output is turned on immediately. With continuing Heating Stage 3 demand, EH2 will turn on after 10 minutes. EH1 and EH2 are turned off immediately when the Heating Stage 3 demand is removed. The control reverts to Heating Stage 2 mode. During Heating Stage 3 mode, EH2 will be off (or will turn off if already on) if FP1 is greater than 45 F AND FP2 is greater than 110 F (FP2 greater than 110 F includes the condition that FP2 is shorted). This condition will have a 30-second recognition time. During Heating Stage 3 mode, EH1, EH2, Fan Enable and Fan Speed will be on if the G input is not active. Table 4: LED and Alarm Relay Output Table Description of Operation Status LED (green) Test LED (yellow) Fault LED (red) Alarm Relay Normal mode On - Off Open Normal mode with UPS On - Flashing Code 8 Cycle (closed 5 sec, open 25 sec) DXM is non-functional Off Off Off Open Fault Retry Slow Flash - Flashing fault code Open Lockout Fast Flash - Flashing fault code Closed Test Mode - On - - Night Setback Flashing Code ESD Flashing Code Invalid T-stat Inputs Flashing Code HP Fault Slow Flash - Flashing Code 2 Open LP Fault Slow Flash - Flashing Code 3 Open FP1 Fault Slow Flash - Flashing Code 4 Open FP2 Fault Slow Flash - Flashing Code 5 Open CO Fault Slow Flash - Flashing Code 6 Open Over/Under Voltage Slow Flash - Flashing Code 7 Open (closed after 15 minutes) Notes: a)"flashing Appropriate Code" means that the Fault LED will ALWAYS flash a code representing the LAST fault in memory. If there is no fault in memory, the Fault LED will flash code 1. b) Codes will be displayed with a 10 second Fault LED off period. c) Slow flash will be 1 flash per every 2 seconds. d) Fast flash will be 2 flash per every 1 second. e) On pulse 1/3 sec.; off pulse 1/3 sec. Page 12 DXM Electronic Heat Pump Control

13 Part II - DXM Electronic Heat Pump Control Emergency Heat In Emergency Heat mode, the Fan Enable and Fan Speed relays are turned on. EH1 is turned on immediately. With continuing Emergency Heat demand, EH2 will turn on after 5 minutes. EH1 and EH2 are turned off immediately when the Emergency Heat demand is removed. The Fan Enable and Fan Speed relays will turn off after a 60-second delay. The control reverts to Standby mode. During Emergency Heat mode, EH1, EH2, Fan Enable and Fan Speed will be on if the G input is not active. Cooling Stage 1 In Cooling Stage 1 mode, the Fan Enable, Compressor, and RV relays are turned on immediately. If configured as Stage 2 (DIP1.2=off), then the compressor and fan will not turn on until there is Stage 2 demand. The Fan Enable and Compressor relays are turned off immediately when the Cooling Stage 1 demand is removed. The control reverts to Standby mode. The RV relay remains on until there is a Heating demand. If there is a Master/Slave situation or a Dual Compressor situation, all Compressor relays and related functions will track with their associated DIP1.2. Cooling Stage 2 In Cooling Stage 2 mode, the Fan Enable, Compressor, and RV relays remain on. The Fan Speed relay is turned on immediately (see DIP1.5). The Fan Speed relay is turned off immediately when the Cooling Stage 2 demand is removed. The control reverts to Cooling Stage 1 mode. If there is a Master/Slave situation or a Dual Compressor situation, all Compressor relays and related functions will track with their associated DIP1.2. Night Low Limit (NLL) Staged Heating In NLL Staged Heating mode, the OVR input becomes active and is recognized as a call for Heating (OVR is an alternate means of calling for Heating mode). In NLL Staged Heating mode, the control will immediately go into Heating Stage 1 mode With an additional 30 minutes of NLL demand, the control will go into Heating Stage 2 mode. With another additional 30 minutes of NLL demand, the control will go into Heating Stage 3 mode. Special DXM Application Notes Generally the following applications are based upon configuring the accessory relays. Cycle with Fan - If Accessory relay 1 is configured to cycle with fan, Accessory relay 1 will be on any time the Fan Enable relay is on. Cycle with Compressor - If Accessory relay 2 is configured to cycle with compressor, Accessory relay 2 will be on any time the Compressor relay is on. Digital Night Setback - If an Accessory relay is configured for Digital NSB, the Accessory relay will be on any time the NSB input is connected to Ground C. Note: If there are no Accessory relays configured for Digital NSB, then the NSB and OVR inputs are automatically configured for mechanical operation. See Mechanical NSB operation below. Mechanical Night Set Back - When the NSB input is connected to Ground C, all thermostat inputs (G, Y1, Y2, W1, and O/W2) are ignored. A thermostat setback Heating call can then be connected to the OVR input. If the OVR input becomes active, then the DXM will enter NLL Staged Heating mode. NLL Staged Heating Mode would then provide heating during the NSB period. Water Valve/Slow Opening - If an Accessory relay is configured for Water Valve/Slow Opening, the Accessory relay will turn on 60 seconds prior to the Compressor Relay turning on. Outside Air Damper-If an Accessory relay is configured for OAD, the Accessory relay will normally turn be on any time the Fan Enable relay is on. But, following a return from NSB (NSB input no longer connected to Ground C ) to Normal Mode, the Accessory relay will not turn on for 30 minutes even if the Fan Enable relay is on. After this 30-minute timer expires, the Accessory relay will turn on if the Fan Enable relay is on. Thermostat Inputs Table 5 shows the resulting demand from differing combinations of inputs. Y1 - Y1 is the input for compressor stage 1 if DIP1.3=on. Y1 is the input for Cooling Stage 1 if DIP1.3=off. Y2 - Y2 is the input for compressor stage 2 if DIP1.3=on. Y2 is the input for Cooling Stage 2 if DIP1.3=off. W1 - If Y1 and Y2 are active and DIP1.3=on, then W1 is the input for Heating Stage 3. If Y1 and Y2 are not active and DIP1.3=on, then W1 is the input for Emergency Heat. If DIP1.3=off, then W1 is the input for Heating Stage 1. O/W2 - O/W2 is the input for Reversing Valve relay if DIP1.3=on and DIP1.4=on. O/W2 is the input for Heating Stage 2 if DIP1.3=off. O/W2 is the input for Heat Mode if DIP1.3=on and DIP1.4=off; this means that the thermostat outputs a B call when in Heating mode and does NOT have an O output. The DXM control will employ Smart RV control. This ensures that the RV will only switch positions if the thermostat has called for a heating/cooling mode change. G - G is the input for Fan Enable relay. NSB and Override - NSB is the input for Night Setback mode. When Digital NSB is selected via the Accessory relays DIPswitch inputs and the NSB input is connected to Ground C, then the appropriately configured Accessory relay is turned on to signal the digital thermostat to go to Night Setback Setpoints. Stated differently, when configured for Digital NSB mode, the Accessory relay directly tracks the NSB input. When Digital NSB is NOT selected via the Accessory relays DIPswitch inputs and the NSB input is connected to Ground C, then Y1, Y2, W1 and O/W2 and G are ignored. During this time period, if OVR is momentarily connected to 24VAC, then Y1, Y2, W1 and O/W2 and G are once again monitored for 2 hours. After the 2 hour Override period, the DXM reverts back to ignoring Y1, Y2, W1 and O/W2 and G, assuming the NSB input is still connected to Ground C. There will be a random start timer when coming back from NSB mode. DXM Electronic Heat Pump Control Page 13

14 Part II - DXM Electronic Heat Pump Control Note: The maximum number of DXM controls with daisychained "NSB" terminals is 75. Also, the maximum total wire resistance of the "NSB" wiring is 500 Ohms. ESD - ESD is the input for Emergency Shutdown mode. When the ESD input is connected to Ground C, all inputs are ignored and all outputs are turned off. There will be a random start timer when coming back from ESD. Note: The maximum number of DXM controls with daisy-chained "ESD" terminals is 75. Also, the maximum total wire resistance of the "ESD" wiring is 500 Ohms. OVR - OVR is the input for Night Setback Override or Night Low Limit Staged Heating input (NLL). When Digital NSB is NOT selected via the Accessory relays DIP switch inputs and NSB is connected to Ground C, then if OVR is momentarily connected to 24VAC (minimum 1 second) then the OVR input is recognized as a Night Setback Override signal and the DXM control reverts from Night Setback and begins monitoring thermostat inputs for heating and cooling calls for a 2 hour override period. If NSB is connected to ground "C", then if OVR is continuously connected to 24V AC, then the OVR input is recognized as a call for NLL staged heating and the control enters NLL staged heating. H - The H input function is determined by the setting of DIP2.7. If DIP2.7=on then the H input is defined as Automatic Dehumidification Mode and is used as an automatic counterpart to DIP1.5, meaning if H is connected to 24VAC then the Fan Speed Relay will not turn on during Cooling Stage 2. If H is not connected to 24VAC then the Fan Speed Relay will turn on during Cooling Stage 2. If DIP2.7=off then the H input is defined as High Speed Fan input and is used as an input to call for High Speed Fan. If the control is in normal operating modes such as Standby, Cooling or Heating AND the H input is connected to 24VAC, then the Fan Enable and Fan Speed relays will be on at all times (this operation is very similar to the G/Fan Enable operation). Table 5: Thermostat Inputs with resulting demands Other Outputs Table 12 displays input and output signals. Electric Heat Outputs EH1 and EH2 turn on whenever the DXM control is in the following modes: Heating Stage 3, Emergency Heat, and boilerless operation. Status LED The Status LED is green. The Status LED indicates what mode the DXM control is in. See Table 4: LED and Alarm Relay Operation. Test LED The Test LED is yellow. The Test LED will be on any time the control is in Test mode. See Table 4: LED and Alarm Relay Operation. Fault LED The Fault LED is red. The Fault LED ALWAYS flashes the corresponding code for the last fault that has occurred. If there is no fault in memory, then the fault LED will flash Code 1. If the Fault type is Primary (HP, LP, FP1, FP2, or CO) then the Fault type will always be retained in memory (Primary faults will over write Secondary faults). If the Fault type is Secondary (Over/Under Voltage, UPS or Swapped FP1/FP2) then the Fault type will only be retained if there are no Primary faults in memory. The Secondary Fault types will not overwrite the Primary fault memory. See Table 4: LED and Alarm Relay Operation. Communications There are two communications ports (Com1 and Com2) which provide robust communications to external DXM control boards via a simple noise resistant low speed protocol. Wiring to Com1 and Com2 does NOT require the use of shielded wiring for operation; standard thermostat wire can be used. Com1 Com1 is used to communicate thermostat and external calls to other DXM Master/Slave controls. In this configuration, up to 3 heat pumps can be controlled by one thermostat. Note: Each heat pump could potentially be a Dual Compressor unit thus there could be up to 6 DXM controls being controlled by one thermostat. However, only 1 DXM control in each heat pump will be daisychained on Com1. See schematic on page 16. The Master DXM control is defined as the DXM control, which is directly connected to the wall-mounted thermostat, time clock, fire alarm, and humidistat. The Master DXM communicates to the Slave DXM typical signals such as: Y1, Y2, W1, O/W2, G, NSB, ESD, OVR, and H. The Slave DXM controls should have no direct connections to any exterior devices such as thermostats, time clocks, fire alarms, humidistats, etc Page 14 DXM Electronic Heat Pump Control

DXM CONTROLS. DXM Digital Heat Pump Controllers. Application, Operation, & Maintenance. Table of Contents

DXM CONTROLS. DXM Digital Heat Pump Controllers. Application, Operation, & Maintenance. Table of Contents Table of Contents DXM CONTROLS DXM Electronic Controls Features Comparison 2 DXM Electronic Heat Pump Controls 3 DXM Physical Dimensions & Layout 4 DXM Controls 5 DXM Service & Application Notes 13 Troubleshooting

More information

UNIT DIGITAL CONTROLS APPLICATION, OPERATION & MAINTENANCE

UNIT DIGITAL CONTROLS APPLICATION, OPERATION & MAINTENANCE DM2 Digital Heat Pump Controller Rev: 3 November 2017 DM2 Overview 3 Physical Dimensions and Layout 4 Layout and Connections 5 Field Selectable Inputs 6 Safety Features 8 Unit Operation Description 10

More information

Application, Operation and Maintenance Guide. DXM Electronic Heat Pump Control

Application, Operation and Maintenance Guide. DXM Electronic Heat Pump Control Application, Operation and Maintenance Guide DXM Electronic Heat Pump Control TABLE OF CONTENTS DXM Overview 3 Physical Dimensions and Layout 3 General Operating Parameters 4 Control Features 4 Field Selectable

More information

DXM2 Digital Heat Pump Controller

DXM2 Digital Heat Pump Controller APPLICATION, OPERATION & MAINTENANCE MANUAL DM2 Digital Heat Pump Controller Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com Application, Operation, & Maintenance

More information

BasicTroubleshooting Information and Guidelines

BasicTroubleshooting Information and Guidelines BasicTroubleshooting Information and Guidelines BasicTroubleshooting Information and Guidelines Information and Guidelines May 2017 BasicTroubleshooting PRIOR TO CONTACTING CLIMATEMASTER TECHNICAL SUPPORT,

More information

Operation and Maintenance Manual OM MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps

Operation and Maintenance Manual OM MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps Operation and Maintenance Manual OM 239 Group: WSHP Document PN: 906530 Date: July 205 MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps Large Capacity

More information

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW Operation & Maintenance Manual OM 931-6 Group: WSHP Part Number: 910157590 Date: September 2014 MicroTech III Unit Controller for Water Source Heat Pump Units Used with Enfinity Models CCH/CCW, VFC/VFW,

More information

Installation and Maintenance Manual OM

Installation and Maintenance Manual OM Installation and Maintenance Manual OM 1149-3 Group: WSHP Document PN: 910208203 Date: April 2017 MicroTech III SmartSource Unit Controller with I/O Expansion Module for Single and Two Stage Water Source

More information

Auxiliary Electric Heater Interface kit ASKHTR

Auxiliary Electric Heater Interface kit ASKHTR Auxiliary Electric Heater Interface kit ASKHTR Installation, Operation & Maintenance Table of Contents General Information 2 INSTRUCTIONS for 1: Boilerless 2 INSTRUCTIONS for 2: Supplemental 3 Typical

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL 500644 FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES A047-001 FIGURE 1: Demand Defrost Control Module ANTI-SHORT CYCLE DELAY

More information

Pioneer Gold Controller Technical Guide

Pioneer Gold Controller Technical Guide Pioneer Gold Controller Technical Guide Pioneer Gold Controller Code: Version 1.03 Electric Heat Expansion Module Code: Version 1.0 Used with AAON WSHP WV Series Vertical and WH Series Horizontal This

More information

Tranquility Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series

Tranquility Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Tranquility Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Table of Contents Model Nomenclature 3 General Information 4-5 Storage 5 Pre-Installation 5 Physical Data 6 Dimensional Data

More information

Pioneer Gold Controller Technical Guide. Pioneer Gold Controller Code: Version 1.1 Used with AAON WSHP WV Series Vertical and WH Series Horizontal

Pioneer Gold Controller Technical Guide. Pioneer Gold Controller Code: Version 1.1 Used with AAON WSHP WV Series Vertical and WH Series Horizontal Pioneer Gold Controller Technical Guide Pioneer Gold Controller Code: Version 1.1 Used with AAON WSHP WV Series Vertical and WH Series Horizontal WARNING QUALIFIED INSTALLER IMPROPER INSTALLATION, ADJUSTMENT,

More information

I/O ZONE 560/583 AND OPERATION MANUAL

I/O ZONE 560/583 AND OPERATION MANUAL UPM I I/O ZONE 560/583 INSTALLATION AND OPERATION MANUAL 1 UNIT PROTECTION MODULE HARDWARE OPERATION IMPORTANT: This manual is for UPM board part numbers 8733 800 259. See controller label as shown in

More information

UPM I. Unit Protection Module. Installation and Operation Manual (2015/06)

UPM I. Unit Protection Module. Installation and Operation Manual (2015/06) UPM I Unit Protection Module Installation and Operation Manual 6 720 220 321(2015/06) 2 Key to Symbols Contents Key To Symbols...2 Warnings...2 Specifications... 3 Unit Protection Module (UPM)....3 Power

More information

ClimaDry II. Table of Contents. ClimaDry II Whole House Dehumidification Option. Tranquility 30 Tranquility 20

ClimaDry II. Table of Contents. ClimaDry II Whole House Dehumidification Option. Tranquility 30 Tranquility 20 ClimaDry II ClimaDry II Whole House Dehumidification Option Tranquility 30 Tranquility 20 Applications Guide 97B0051N01 Revision: 10 Feb., 2016 Table of Contents Model Nomenclature Example 3 ClimaDry Overview

More information

ACDU02 Communicating Service Tool

ACDU02 Communicating Service Tool ACDU02 Communicating Service Tool Operation Manual 97B0106N01 Rev.: 4/17/14 Caution: These instructions are intended to be used by the installer or service personnel. End users are NOT advised to change

More information

BACnet Points List for Single Compressor Water to Water PROSSWWE-01

BACnet Points List for Single Compressor Water to Water PROSSWWE-01 The network variables will be listed by point type instance convention. 2:1 would mean point type 2, point instance 1. All volatile (Output) type points will revert to the uncommanded values after a power

More information

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS HP727S Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS 1. General Description 2. Specifications 3. Installation Instructions 4. Electrical Wiring 5. Instrument Wiring

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

Heat Pump Defrost Board Replacement Kit

Heat Pump Defrost Board Replacement Kit Bard Manufacturing Company, Inc. Bryan, Ohio 43506 8620-223 Heat Pump Defrost Board Replacement Kit KIT FEATURES This kit is made up of the current defrost control board 8201-129 and a new defrost sensor.

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide Aurora Touch UPC Kit Instruction Guide For use in single compressor water-to-air equipment utilizing fi rmware UPCSWASTD01-01 Aurora Touch UPC Kit Instruction Guide *IG1583EW* IG1583EW 08/14 Aurora Touch

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

ATC32U01A Communicating, Programmable Thermostat

ATC32U01A Communicating, Programmable Thermostat ATC32U01A Communicating, Programmable Thermostat Installation Manual 97B0055N07 Created: 10/1/12 Caution: These instructions are intended to be used by the installer or service personnel. End users are

More information

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits CommStat 4 PRODUCT DATA SHEET Controller for Redundant Telecom HVAC Systems General Description The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners,

More information

Product Manual SZ1009

Product Manual SZ1009 Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional

More information

HPC. Heat Pump Controller. Installation, Operation, and Maintenance Manual (2019/02)

HPC. Heat Pump Controller. Installation, Operation, and Maintenance Manual (2019/02) HPC Installation, Operation, and Maintenance Manual 8733819577 (2019/02) 2 CONTENTS Document Conventions...3 Key to Symbols... 3 Safety Warnings...3 Introduction...4 Product Description... 4 Bosch EasyStart

More information

CommStat 4 Controller

CommStat 4 Controller CommStat 4 Controller CommStat 4 Telecom HVAC Controller The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners, heat pumps and air conditioners with

More information

Water Source Heat Pump Module Technical Guide

Water Source Heat Pump Module Technical Guide Factory Packaged Controls Tulsa Water Source Heat Pump Module WSHP WSHP Protection Module Module Orion No.: OE334-23-WPM-A NON-DIGITAL COMPRESSORS #1 THRU #4 +5V SUCT. +5V SUCTION PR. SENSOR PRES PRES

More information

Ultra Classic (VT) Series Residential Vertical Two-Stage Geothermal Heat Pumps

Ultra Classic (VT) Series Residential Vertical Two-Stage Geothermal Heat Pumps Ultra Classic (VT) Series Residential Vertical Two-Stage Geothermal Heat Pumps Installation, Operation & Maintenance Instructions 69197343 Revision: 07/07/05D TABLE OF CONTENTS Model Nomenclature 2 Storage

More information

ATC32U02 igate Communicating, Programmable Thermostat

ATC32U02 igate Communicating, Programmable Thermostat ATC32U02 igate Communicating, Programmable Thermostat Installation Manual 97B0055N03 Rev.: 2/24/14 Caution: These instructions are intended to be used by the installer or service personnel. End users are

More information

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1-316-832-4357

More information

McQuay. Ceiling Concealed Horizontal Water Source Heat Pump. CCH, CCG, CCW 048, 060 Vintage A. Last Manufactured: 1995

McQuay. Ceiling Concealed Horizontal Water Source Heat Pump. CCH, CCG, CCW 048, 060 Vintage A. Last Manufactured: 1995 Replacement Parts List No. 055236000 Revision B 06/2015 McQuay Ceiling Concealed Horizontal Water Source Heat Pump CCH, CCG, CCW 048, 060 Vintage A Last Manufactured: 1995 To find your Daikin Applied parts

More information

L SERIES UNITS 504,520M. 10/2001 Supersedes 504,413M

L SERIES UNITS 504,520M. 10/2001 Supersedes 504,413M Litho U.S.A. 2 L SERIES UNITS 54,52M /2 Supersedes 54,4M M 6 VERSION 4. INTEGRATED MODULAR CONTROL (IMC) GUIDE TO THE M 6 VERSION 4. INTEGRATED MODULAR CONTROL USED IN L SERIES THROUGH TON UNITS TABLE

More information

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS Note: This manual may also be used for 6536-871 series heat pumps if the 6535-3209 Replacement

More information

ATC32U01 igate Communicating, Programmable Thermostat

ATC32U01 igate Communicating, Programmable Thermostat ATC32U01 igate Communicating, Programmable Thermostat Installation Manual 97B0055N03 Rev.: 2/4/13 Caution: These instructions are intended to be used by the installer or service personnel. End users are

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

RSMSD Technical Guide

RSMSD Technical Guide RSMSD Technical Guide www.aaon.com AAON/WattMaster Controls Inc. 8500 NW River Park Drive Parkville, MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 FAX: (816) 505-1101 E-mail: mail@wattmaster.com

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

EnviroZone-4 & EnviroZone-2 Quick-Start Guide

EnviroZone-4 & EnviroZone-2 Quick-Start Guide EnviroZone-4 & EnviroZone-2 Quick-Start Guide This guide is intended to give the installer a brief set of instructions about how to set up the FHP EnviroZone System. For more detailed information about

More information

Zoning System for Residential Communicating, Variable Air Volume Heating/Cooling Systems

Zoning System for Residential Communicating, Variable Air Volume Heating/Cooling Systems PRODUCT SPECIFICATIONS ZONING IHARMONY Zoning System for Residential Communicating, Variable Air Volume Heating/Cooling Systems Bulletin No. 20663 November 207 Supersedes August 205 COMPONENTS AND EQUIPMENT

More information

HEAT HEAT HEAT COOL COOL

HEAT HEAT HEAT COOL COOL OWNER S MANUAL AUTO 74 COOL 7 2 HEAT T O T A L I N E HEAT COOL COMMERCIAL THERMOSTAT P/N P374-2700 HEAT PUMP NON-PROGRAMMABLE DIGITAL THERMOSTAT 3 Configurable Outputs Control up to 2 Heat & 2 Cool Stages

More information

Product Manual SZ1022/SZ1031/SZ1035/

Product Manual SZ1022/SZ1031/SZ1035/ Product Manual SZ1022/SZ1031/SZ1035/ Conventional Heating & Cooling Thermostats Communicating Thermostats Description The SZ1022, SZ1031, and SZ1035, are microprocessorbased mable thermostats designed

More information

SPECIFICATION CATALOG. Console 0.75 to 1.5 Tons. Geothermal/Water Source Heat Pump

SPECIFICATION CATALOG. Console 0.75 to 1.5 Tons. Geothermal/Water Source Heat Pump SPECIFICATION CATALOG Console 0.75 to 1.5 Tons Geothermal/Water Source Heat Pump Table of Contents Model Nomenclature.............................................................. 4 AHRI Data......................................................................

More information

L SERIES UNITS 505,191M. 4/2006 Supersedes 504,908M

L SERIES UNITS 505,191M. 4/2006 Supersedes 504,908M Litho U.S.A. 26 L SERIES UNITS 55,191M 4/26 Supersedes 54,98M M1 7 VERSION 5.2 INTEGRATED MODULAR CONTROL (IMC) GUIDE TO THE M1 7 VERSION 5.2 INTEGRATED MODULAR CONTROL USED IN L SERIES AND S CLASS 3 THROUGH

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! 50V64-743 Integrated Furnace Control for Furnaces with Variable Fan Speed INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY

More information

Tranquility Digital Quick Start Guide

Tranquility Digital Quick Start Guide Tranquility Digital Quick Start Guide 97B0107N01 Residential Packaged and Split DIGITAL Geothermal Heat Pumps With igate and vflow Technology B Step Title Page 1 Thermostat Confi guration 3 Staging 3 Auxiliary

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS COMFORT CONTROL CENTER 2 THERMOSTAT OPERATING INSTRUCTIONS PROGRAMMABLE THERMOSTAT MODEL 3314080.000 BLACK 3314080.015 WHITE USA SERVICE OFFICE Dometic Corporation 1120 North Main Street Elkhart, IN 46514

More information

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to range before servicing, unless testing requires power.

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to range before servicing, unless testing requires power. Technical Information Electric Slide-In Range JES8850BC* JES9900BC* JES9860BC* Due to possibility of personal injury or property damage, always contact an authorized technician for servicing or repair

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8800 Universal Communicating Thermostat Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Installation Installation location recommendations... 2 Thermostat mounting...

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

Installation Instructions / User s Manual TSTAT0406 and TSTAT0408

Installation Instructions / User s Manual TSTAT0406 and TSTAT0408 997-060180-5 Installation Instructions / User s Manual TSTAT0406 and TSTAT0408 4 HEAT 2 COOL DUAL FUEL TSTAT0406 & TSTAT0408-4 WIRE CAPABLE THERMOSTAT (NAXA00201DB Daughter Board sold separately) LEFT

More information

McQuay. Vertical Water Source Heat Pump. FCV, FCG, FCW 036, 042 Vintage A. Last Manufactured: 1993

McQuay. Vertical Water Source Heat Pump. FCV, FCG, FCW 036, 042 Vintage A. Last Manufactured: 1993 Replacement Parts List No. 055237600 Revision D 08/2017 McQuay Vertical Water Source Heat Pump FCV, FCG, FCW 036, 042 Vintage A Last Manufactured: 1993 To find your Daikin Applied parts distributor, call

More information

Omega PCB Installation/Operation Dev A - Version 14

Omega PCB Installation/Operation Dev A - Version 14 Omega PCB Installation/Operation Dev A - Version 14 Note: 1) The installation of PCB & Thermostat has to be done by certified technician 2) Please make sure that thermostat is compatible with heat pump

More information

Product Data. Single-Package Horizontally Mounted Water Source Heat Pumps with Electronic

Product Data. Single-Package Horizontally Mounted Water Source Heat Pumps with Electronic Product Data Aquazone 0RHE006-060 Water Source Heat Pumps Horizontal Unit 0 Hz, CE Mark R-407C 1.to13.7NominalkW(Cooling) 1.8 to 16. 8 Nominal kw (Heating) TM Copyright 2004 Carrier Corporation Single-Package

More information

GT-X. 50YBV Ultra High Efficiency Vertical Two-Stage Geothermal System. Installation, Operation & Maintenance Instructions TABLE OF CONTENTS

GT-X. 50YBV Ultra High Efficiency Vertical Two-Stage Geothermal System. Installation, Operation & Maintenance Instructions TABLE OF CONTENTS GT-X 50YBV Ultra High Efficiency Vertical Two-Stage Geothermal System INSTALLED BY: Installation, Operation & Maintenance Instructions Revision: 07/21/05D TABLE OF CONTENTS Model Nomenclature 2 Storage

More information

T-32-TS Touchscreen Thermostat. Installation Manual

T-32-TS Touchscreen Thermostat. Installation Manual T-32-TS Touchscreen Thermostat Installation Manual TABLE OF CONTENTS Introduction...4 Getting Started...5 Installing the Thermostat...6, 8 Disassembly...6 Thermostat Location...6 Mounting the Subbase...6,

More information

Fan Coil Unit (FCU) Application Guide

Fan Coil Unit (FCU) Application Guide Fan Coil Unit (FCU) Series Room Controllers TABLE OF CONTENTS and SCs Fan coil terminal equipment controllers 2 A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves

More information

Smart Temp. Model

Smart Temp. Model Smart Temp Model 42-160 SINGLE STAGE PROGRAMMABLE THERMOSTAT 1 Heat / 1 Cool Single Stage Thermostat. 5+2 Programmable, Compatible with Gas Heat & Heat Pump System Installation and Operation Manual SPECIFICATIONS:--------------------------------------------------------------------------------

More information

L SERIES UNITS 504,908M. 10/2004 Supersedes 9/2004

L SERIES UNITS 504,908M. 10/2004 Supersedes 9/2004 Litho U.S.A. 4 L SERIES UNITS 54,98M /4 Supersedes 9/4 M 7 VERSION 5.x INTEGRATED MODULAR CONTROL (IMC) GUIDE TO THE M 7 VERSION 5.x INTEGRATED MODULAR CONTROL USED IN L SERIES AND S CLASS 3 THROUGH 5

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

Tranquility Water-to-Water (THW) Series

Tranquility Water-to-Water (THW) Series Tranquility Water-to-Water (THW) Series Residential High Temperature Water-to-Water Geothermal Heat Pumps (Heating Only) - 50Hz Table of Contents Model Nomenclature 3 General Information 4 Physical Data

More information

OWNER S MANUAL Venstar Inc. 08/07

OWNER S MANUAL Venstar Inc. 08/07 Digital Thermostat residential THERMOSTAT T1 900 7-DAY MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP with HUMIDITY CONTROL Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd &

More information

Tranquility Coaxial Geothermal Open Loop Water-to-Water (TCW) Series

Tranquility Coaxial Geothermal Open Loop Water-to-Water (TCW) Series Tranquility Coaxial Geothermal Open Loop Water-to-Water (TCW) Series Table of Contents Model Nomenclature 3 General Information 4-5 Storage 5 Pre-Installation 5 Physical Data 6 Dimensional Data 7 Unit

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 50A55-474 & 50A55-571 Integrated Furnace Controls INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE

More information

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING Emerson Inspire 1HDEZ-1521 Installation Instructions Thermostat/Interface Equipment Control TROUBLESHOOTING FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL

More information

Table of Contents. WSHP Open v3

Table of Contents. WSHP Open v3 WSHP Open v3 Integration Guide CARRIER CORPORATION 2012 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-500-01 11/29/2012 Table of Contents Introduction... 1

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN April 2005 CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation

More information

ECM OPERATION MANUAL

ECM OPERATION MANUAL ECM OPERATION MANUAL FOR USE WITH MODEL: SINGLE STAGE OH6FA072DV4 OH8FA119DV5 OD6F/RA072DV5 OL6F/RA072DV5 2-STAGE OH6FX072DV4 OD6F/RX072DV5 OL6F/RX072DV5 : IF YOU DO NOT FOLLOW THE SAFETY PRECAUTIONS BELOW

More information

SC Installation, Operation & Application Guide

SC Installation, Operation & Application Guide SC 5211 2-Stage Heat Pump Auto Changeover Hardwire Programmable Electronic Thermostat 7-Day, 5-2-Day or 5-1-1-Day Programmable Configurable 2-Stage Heat Pump Systems Large Display With Backlight Selectable

More information

RSMV Technical Guide

RSMV Technical Guide RSMV Technical Guide TABLE OF CONTENTS OVERVIEW... 4 Features and Applications... 4 Module Dimensions... 5 INSTALLATION & WIRING... 6 Input Wiring... 6 Suction Pressure Sensor...6 Head Pressure Sensor...6

More information

24 VAC Intermittent Pilot Gas Ignition Control

24 VAC Intermittent Pilot Gas Ignition Control C610U Universal 24 VAC Intermittent Pilot Gas Ignition Control Issue Date: 08/24/2016 Quick Reference Guide The C610U Universal Intermittent Pilot Gas Ignition Control module replaces many popular flame

More information

CONTENTS. Installation Guide. VT7200 Series

CONTENTS. Installation Guide. VT7200 Series VT7200 Series Installation Guide For mercial HVAC Applications November 2015 CONTENTS Installation 2 Location 2 Installation 2 Configurable BI/UI inputs overview 4 Network ready 6 Terminal, Identification

More information

Networkable Fan Coil Controller Specification and Installation Instructions

Networkable Fan Coil Controller Specification and Installation Instructions Controller Models EFCB10T-OE1 (24Vac / 0 relays) EFCB12T-OE1 (240Vac / 0 relays) EFCB10TU4-OE1 (24Vac / 4 relays) EFCB12TU2-OE1 (240Vac / 2 relays) EFCB12TU4-OE1 (240Vac / 4 relays) TFL Series Thermostat

More information

Tranquility Digital Quick Start Guide

Tranquility Digital Quick Start Guide Tranquility Digital Quick Start Guide 97B0107N01 Residential Packaged and Split DIGITAL Geothermal Heat Pumps With igate and vflow Technology Rev.: January 25, 2016 Step Title Page 1 Thermostat Confi guration

More information

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires it.

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires it. Electric Wall Oven Technical Information JJW8627DD*, JJW8630DD*, JJW9627DD*, JJW9630DD*, JJW9827DD*, JJW9830DD* Refer to Service Manual 16022506 for detailed installation, operating, testing, troubleshooting,

More information

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to range before servicing, unless testing requires power.

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to range before servicing, unless testing requires power. Technical Information Electric Slide-In Range JES9750BA* JES9860BA* Due to possibility of personal injury or property damage, always contact an authorized technician for servicing or repair of this unit.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS MC3000 SERIES SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual No.: 2100-452 Supersedes:

More information

Dexter Industrial On Premise Dryer. Troubleshooting, Fault Codes, And Schematics. Starting serial number Part # /13

Dexter Industrial On Premise Dryer. Troubleshooting, Fault Codes, And Schematics. Starting serial number Part # /13 Dexter Industrial On Premise Dryer Troubleshooting, Fault Codes, And Schematics Starting serial number Dryer Trouble Shooting Symptom Probable Cause Suggested Remedy Tumbler does not turn Drive belts Check

More information

Factory Packaged Controls. MHGRV-X Controller Field Technical Guide

Factory Packaged Controls. MHGRV-X Controller Field Technical Guide Factory Packaged Controls MHGRV-X Controller Field Technical Guide TABLE OF CONTENTS CONTROLLER OVERVIEW... 3 Features...3 INSTALLATION & WIRING... 4 Important Wiring Considerations...5 MHGRV-X Controller

More information

H32 Uni- Zone Model H32

H32 Uni- Zone Model H32 H32 Uni- Zone Model H32 Installation and Operating Instructions Controlling Your Comfort Room By Room F o l l o w u s o n H32 PANEL FEATURES System Mode Indicator LED Power Indicator LED HVAC Equipment

More information

OWNER S MANUAL Venstar Inc. 08/07

OWNER S MANUAL Venstar Inc. 08/07 Digital Thermostat residential THERMOSTAT T1 800 7-DAY PROGRAMMABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd & 3rd Stage Timers

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

Smart Temp. ApolloP/n Installation Manual. Version 1.0

Smart Temp. ApolloP/n Installation Manual. Version 1.0 Smart Temp ApolloP/n 44-800 Installation Manual Version 1.0 TABLE OF CONTENTS Introduction...6 Getting started...7 Installing the thermostat...8 Disassembly...8 Thermostat location...8 Mounting the subbase...8,

More information

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller All volatile (Output) type points will revert to the uncommanded values after a power interruption.

More information

GT-PW Water-to-Water Series (50YEW Models) Table of Contents. Installation, Operation and Maintenance Instructions

GT-PW Water-to-Water Series (50YEW Models) Table of Contents. Installation, Operation and Maintenance Instructions GT-PW Water-to-Water Series (50YEW Models) Installation, Operation and Maintenance Instructions Residential Water-to-Water High Temperature, Heating Only Geothermal Heat Pumps 97B0063N03 Revised 21 July,

More information

HEAT HEAT HEAT COOL COOL PUMP OWNER S MANUAL 7-DAY TOTALINE

HEAT HEAT HEAT COOL COOL PUMP OWNER S MANUAL 7-DAY TOTALINE OWNER S MANUAL COMMERCIAL THERMOSTAT P/N P374-2800 I 2 : 0 0 Su AUTO Pm 74 COOL 7 2 HEAT T O T A L I N E HEAT COOL 7-DAY HEAT PUMP PROGRAMMABLE DIGITAL THERMOSTAT 3 Configurable Outputs Control up to 2

More information

Auto-Changeover: Cool Setpoint: Deadband: Dehumidify: Differential: Heat Setpoint: Humidify: Icon: Mode: Non-Programmable Thermostat:

Auto-Changeover: Cool Setpoint: Deadband: Dehumidify: Differential: Heat Setpoint: Humidify: Icon: Mode: Non-Programmable Thermostat: SM CAUTION Follow the Installation Instructions before proceeding. Set the thermostat mode to OFF prior to changing settings in setup or restoring Factory Defaults. This Explorer thermostat has the ability

More information

HEAT COOL. Meets Commercial California Title 24

HEAT COOL. Meets Commercial California Title 24 Digital Thermostat commercial THERMOSTAT T2900 7-DAY MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd & 3rd Stage Timers & Deadbands

More information

Installation & Operation Instructions

Installation & Operation Instructions Installation & Operation Instructions Installation Precautions This Zoning System must be installed by a qualified HVAC Contractor! Caution - Electrical Hazard Can cause personal injury or equipment damage.

More information

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS 50M56-743 Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD

More information

DAP III Zone Master User s Guide

DAP III Zone Master User s Guide DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP

More information

Factory Packaged Controls. MHGRV-X Controller Field Technical Guide

Factory Packaged Controls. MHGRV-X Controller Field Technical Guide Factory Packaged Controls MHGRV-X Controller Field Technical Guide TABLE OF CONTENTS CONTROLLER OVERVIEW... 3 Features... 3 INSTALLATION & WIRING... 4 Important Wiring Considerations... 4 MHGRV-X Controller

More information

Instruction Guide: Thermostat Operation

Instruction Guide: Thermostat Operation Instruction Guide: Elite Communicating Thermostats TPCM32U03*/TPCM32U04* (*GSR, GSM, TRN, AST) INSTRUCTION GUIDE: ELITE COMMUNICATING THERMOSTAT Thermostat Operation NOTE: These communicating thermostats

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information