1 Date of last update: May-12 Ref: : Application Engineering Europe ENHANCED VAPOUR INJECTION (EVI) FOR ZH*KVE SCROLL COMPRESSORS 1 Introduction Principle of operation Capacity effect Operating envelope with vapour Injection for models ZH09-48KVE Multiple compressors configuration Economizer selection and application Liquid receiver Expansion valve and solenoid valve selection for injection line Injection expansion valve setting Injection line diameter Expansion valve selection for main evaporator Main liquid line components Line lengths and insulation Additional application points Operation without vapour injection Discharge temperature protection Current sensing relay Reference List of Copeland Related Technical Information /10

2 1 Introduction This Technical Information describes the principle of operation and the system design of the Enhanced Vapour Injection for ZH*KVE Heat Pump optimized Copeland Scroll compressors, whatever they are used in single or tandem configuration. The vapour injection scroll compressor is for use with an economized vapour compression cycle heat pump. This cycle offers the advantages of more heat delivered and a better COP than with a conventional cycle. Both the heating capacity and the COP improvement are proportional to the temperature lift and this technology offers best results at high condensing operation where capacity and efficiency are most needed. Due to this increase in capacity, it is possible to specify a smaller displacement compressor for a given heating load. Additionally the cooling provided by injection inter-stage allows the operation of the compressor over a larger envelope compared to a conventional single stage model, providing higher heat delivery temperatures at low evaporating temperatures. 2 Principle of operation As shown in Figure 1, a portion of the condensed liquid, i, is expanded through an expansion valve into a counter flow plate heat exchanger, HX, which acts as a sub-cooler. Superheated vapour is then injected into the intermediate vapour injection port in the scroll compressor. The additional subcooling increases the evaporator capacity by reducing the temperature of the liquid from T LI to T LO, thus reducing its enthalpy. The additional condenser mass flow, i, increases the heating capacity by the same amount. Figure 1: Circuit diagrams showing the main circuit, mass flow rate m, and the economizer circuit, mass flow rate i Efficiency with vapour injection scroll compressor cycle is higher than that of a conventional single-stage scroll delivering the same capacity because the added capacity is achieved with less power. The incremental vapour created in the subcooling process is compressed only from the higher inter-stage pressure rather than from the lower suction pressure. The cooling effect is achieved by the addition of vapour to the compression process at the intermediate pressure and at temperature T VO, controlled by the HX expansion valve. Superheated vapour is injected into the scroll set at the intermediate point of the compression process, via two symmetrically positioned ports as shown on the left in Figure 2. The size and position of these ports have been optimized to ensure maximum COP and capacity benefit at typical operating conditions. The superheated vapour enters the compressor via an additional inlet connection on the compressor shell and flows to the injection ports of the fixed scroll via a tube as shown on the right. The tubing characteristics flexibility ensures that axial compliance is maintained. 2/10

3 Figure 2: Position of the injection ports in the scroll set and the internal tubing connecting the injection inlet with the scroll set 3 Capacity effect The vapour injection (VI) scroll is particularly suited to Air Source Heat Pumps (ASHP). Figure 3: Capacity variation and heat load characteristics The blue line in Figure 3 representing the VI scroll characteristic has a lower gradient than that of a conventional compressor. At low ambient conditions, a bigger capacity is available. On the other side, when the outdoor air temperature is above the design point, less capacity is delivered by the VI scroll compressor, resulting in less cycling than with a conventional compressor. The vapour injection scroll offers advantages particularly in air/water heating applications where the water temperatures need to be high and where domestic hot water is needed. Capacity can be further reduced if needed by switching off the vapour injection (see chapter 12.1). 3/10

4 4 Operating envelope with vapour Injection for models ZH09-48KVE Vapour injection + 10K Suction Superheat + 5K Economiser Superheat Vapour injection + 10K Suction Superheat + 5K Economiser Superheat Limited Operation < 2000 hours on compressor lifetime Figure 4: Operating envelope for vapour injection and standard Scroll compressors (considering condenser subcooling and temperature approach at the economizer of 5 K) Figure 4 shows the comparison of the compressor operating envelope for the standard and the VI scrolls, illustrating clearly the additional high temperature capability at evaporating temperatures below 5 C. For air-to-water heat pump application, an envelope extension may be required for high temperature water production by low outdoor temperature. This can be carried out by the use of wet vapour injection. For further information about wet injection, contact the Application Engineering department of Emerson Climate Technologies. 5 Multiple compressors configuration Multiple Vapour Injection compressors can share one economizer (HX) and one expansion valve (Figure 5). Due to the larger range of capacity brought by such configuration, an electronic expansion valve is recommended. Solenoid valves must be fitted to the individual vapour injection lines to close when the compressor is switched off, in order to avoid excessive quantities of liquid entering the compressor during standstill. Figure 5: Multiple compressors configuration when one injection expansion valve is sufficient. For further information about multiple ZH compressors possibilities, refer to the technical information C Paralleling of ZH Copeland scroll compressors for heat pump applications. 4/10

5 6 Economizer selection and application For applications with single or multiple ZH heat pump scroll compressors, plate heat exchanger recommendations are available in Tables 1, 2 & 3. Details about required economizer capacity and saturated injection temperature T SI are provided in Copeland brand products Selection Software to enable independent sizing of the economizer when required, as shown in Figure 6 below. The input subcooling is the natural condenser subcooling, not the subcooling at expansion valve inlet. Natural subcooling Additional information on vapour injection Figure 6: Selection Software Version 7 screen details The values of the temperatures T LO (temperature liquid out), T LI (temperature liquid in) and T VO (temperature vapour out) are also provided. It should be noted that the benefit of natural subcooling, i.e. condenser subcooling, is limited to a maximum of approximately 5K. Additional natural subcooling leads to little further reduction in liquid temperature T LO. The compressor performances published in the Select Software are based on a temperature difference THX = T LO -T SI (T SI in bubble) of 5K at the economizer and an injection superheat of 5K. Downstream extraction shown in Figure 7(b) refers to taking the liquid for the economizer expansion device from the economizer liquid exit as shown. This method is sometimes proposed to ensure good sub cooling at the TXV inlet. While there is no overall heat gain or loss compared to the usual upstream extraction, it does mean that the injected mass flow, i, is passing through the economizer twice and incurring extra pressure drop on the liquid cooling side. This may result in the need for a larger economizer. Also, downstream extraction requires more connections and tubing on the sub-cooled liquid side, all of which need to be insulated to ensure minimal heat gain. For these reasons, downstream extraction is less preferable than upstream (Figure 7(a)). 5/10

6 Figure 7: (a) upstream liquid extraction (highly recommended) - (b) downstream The performance data published in Select Software are for the system design (a). With other designs the injected mass flow is changing and with this the performance of the compressor. The economizer must be installed vertically with the vapour entry at the bottom. The expansion valve should be positioned at a distance between 150 and 200 mm from the entry expansion and at a position not lower than inlet connection. Figure 8: Position of the expansion valve and bulb when using a plate heat exchanger The bulb of the expansion valve should be located mm from the vapour outlet, preferably after a bend and on the inside as shown on the left in Figure 8. The position of the bulb relative to the section of the tube is illustrated. It should not be attached underneath the tube. External equalisation is not essential. The tubing between the expansion valve and the economizer entry may either be straight or include a bend as shown on the right in Figure 8. It is most important that the connection diameter at the entry to the economizer is small enough to induce the turbulence required for uniform distribution and evaporation. 6/10

7 The following table gives the recommended economizer size and inner diameter at the economizer ports. Table 1: SWEP heat exchanger recommendation for single compressor configuration Table 2: SWEP heat exchanger recommendation for tandem compressor configuration Vapour injection Liquid Alfa Laval Inlet Outlet Inlet Outlet S3 S4 S1 S2 ZH09KVE AC30-8EQ 1/4" H28 3/8" H27 1/4" H28 1/4" H28 ZH13KVE AC30-8EQ 3/8" H27 3/8" H27 3/8" H27 3/8" H27 ZH18KVE AC30-10EQ 3/8" H27 3/8" H27 3/8" H27 3/8" H27 ZH24KVE AC30-10EQ 1/2" H62 5/8" H22 1/2" H24 1/2" H24 ZH33KVE AC30-14EQ 1/2" H62 5/8" H22 1/2" H24 1/2" H24 ZH40KVE AC30-14EQ 5/8" H64 5/8" H22 5/8" H22 5/8" H22 ZH48KVE AC30-20EQ 5/8" H65 5/8" H22 5/8" H22 5/8" H22 Table 3: Alfa Laval heat exchanger recommendation for single compressor configuration The recommendations above give the best economizer performance with the lowest number of economizer models. If the diameter of the pipe work is not fitting to the economizer ports, use reducers into the economizer at the inlet and outlet. Use Emerson Climate Technologies recommended pipe work sizes (see below). If heat exchangers with recommended port sizes are not available, order the same economizer with larger ports and use reducers to fit required port diameters. 7/10

8 7 Liquid receiver A liquid receiver may be necessary to accommodate charge variations over the operating condition range and limit the condenser subcooling. It should always be fitted in the condenser outlet liquid line and not in the heat exchanger outlet liquid line (Figure 9). This is because vapour phase may be present in a receiver, and this is only possible with saturated liquid. Figure 9: Position of receiver 8 Expansion valve and solenoid valve selection for injection line The injection expansion device used in conjunction with the economizer will be preferably electronic to operate in the almost whole wide range of capacity that such EVI compressor models allow. A solenoid valve should be added if the expansion device does not completely close. This is to avoid liquid migration to the compressor during the off cycle. In single configuration, the solenoid valve may be in the liquid line or the vapour line. A liquid line position is usually preferred because the valve is smaller. When the compressor is rotating in reverse direction during the first seconds of the off cycle, the valve is to be installed in the vapour line. With multiple compressors used in parallel with one economizer it is necessary to install a solenoid valve in the single vapour line of each compressor. The following table may be used as a guide for selection of the injection expansion valve and liquid line solenoid valve in single configuration. A thermostatic expansion valve, due to its inherent smaller capacity range than an electronic valve will only operate adequately in a limited area of the envelope. The zone for which the TXV is recommended is specified below the table. Table 4: Electronic (EXV), thermostatic expansion valve (TXV) and liquid solenoid valve recommendations for the injection (single configuration only) If an electronic expansion valve is used, it should be a variable orifice type. Pulse modulating types are unsuitable because the internal volume of the economizer is low, and they will give rise to unstable operating conditions which may result in an unacceptable quantity of liquid overfeed. 8/10

9 9 Injection expansion valve setting The injection expansion valve will be set to maintain the injection superheat around 5K throughout the operating envelope. This is a good compromise not to inject any liquid refrigerant into the scroll and to have a sufficient cooling of the compressed gas and therefore limit the discharge temperature. 10 Injection line diameter Model Vapour injection line diameter The injection line diameter should be correctly sized for vapour with minimal pressure drops if optimum performance is to be maintained. The size should follow the size of the compressor injection connection: ZH09 KVE 3/8" ZH13 KVE 3/8" ZH18 KVE 3/8" ZH24 KVE 3/8" ZH33 KVE 1/2" ZH40 KVE 1/2" ZH48 KVE 1/2" Table 5: Vapour injection line diameter 11 Expansion valve selection for main evaporator When using a thermostatic expansion valve (TXV), it must be sized taking into account the appropriate liquid subcooling, and this will result in a smaller valve than would normally be the case. Air/Water application requires a broad range valve of the TCLE type. The Table 6 shows recommended electronic and thermostatic expansion valves for Air/Water (A/W) and Brine/Water (B/W) systems. Table 6: Electronic and thermostatic expansion valve recommendations for main evaporator (single application only) 12 Main liquid line components Main liquid line components also need to be sized taking into account the appropriate liquid subcooling, and recommendations are shown in the following tables. Where reversible systems are used either for defrost or for air conditioning, bi-flow filter driers should be installed. Model Liquid line diameter Liquid solenoid valve Filter drier Table 7: Main liquid line components selection (single application only) Filter drier (bi-flow) Sight glass ZH09KVE 1/4" 110RBT T2 ADK082S BFK052S MIA014 ZH13KVE 3/8" 200RB3 T3 ADK083S BFL163S MIA038 ZH18KVE 3/8" 200RB3 T3 ADK083S BFK163S MIA038 ZH24KVE 1/2" 200RB4 T3 ADK164S BFK164S MIA012 ZH33KVE 1/2" 200RB4 T3 ADK164S BFK164S MIA012 ZH40KVE 5/8" 200RB6 T5 ADK305S BFK305S MIA058 ZH48KVE 5/8" 200RB6 T5 ADK305S BFK305S MIA058 9/10

10 13 Line lengths and insulation Vapour lines between both expansion devices and the heat exchangers (evaporator and economizer) need to be kept as short as practical and well insulated. The economizer should also be insulated. 14 Additional application points 14.1 Operation without vapour injection The ZH KVE models may be operated without vapour injection when the evaporating temperature is above 5 C to give limited capacity control. Figure 10 shows the approximate percentage of heating capacity reduction obtained at various condensing temperatures when the vapour injection is shut off. The capacity reduction effect is limited, particularly at lower condensing temperatures, and since the COP is always higher with vapour injection it is usually preferable to maintain this mode of operation in all conditions. Figure 10: Approximate % heating capacity reduction obtained if changing to operation without VI 14.2 Discharge temperature protection High discharge temperature protection should always be fitted to each compressor as detailed in the application guideline C scroll compressors for heat pump applications ZH12K4E to ZH11M4E, ZH09KVE to ZH48KVE. This ensures the compressor cannot overheat in the event of loss of vapour injection cooling. It may be incorporated into the heat pump control circuit using an appropriate sensor. Larger models (ZH24KVE to ZH48KVE) have built-in protection in which case it may be desirable to install an external sensor integrated with the control circuit to avoid tripping the motor protector Current sensing relay It is recommended that compressors with internal motor protection (ZH09/13/18) are fitted with a current sensing relay which is connected to close the solenoid valve in the event of motor trip. 15 Reference List of Copeland Related Technical Information C Paralleling of ZH Copeland scroll compressors for heat pump applications C Discharge temperature protection with ZH compressors 10/10

Technical Information

Technical Information Date of last update: 02-08 Ref: Application Engineering Europe COPELAND SCROLL COMPRESSORS USING VAPOUR INJECTION FOR REFRIGERATION CONTENTS 1 Introduction...1 2 Principle of Operation...1 3 Capacity Effect...2

More information

Technical Information

Technical Information Date of last update: May-15 Ref: C7.19.2/0813-0515/E Application Engineering Europe ZF* REFRIGERATION COPELAND SCROLL COMPRESSORS USING R407A, R407F, R448A OR R449A IN LOW TEMPERATURE APPLICATIONS ZF*

More information

Application Engineering

Application Engineering Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved

More information

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

Figure 1: Schematic of internal heat exchanger vapor-injection cycle Vapor-injection technique Development Guideline 1. Introduction This guideline shows the advantage and characteristics of Mitsubishi vapor injected-scroll compressor. The vapor injected-scroll compressor

More information

Scroll compressors with vapour injection for Dedicated Heat Pumps. ZH24 KVE to ZH48 KVE Application Guidelines

Scroll compressors with vapour injection for Dedicated Heat Pumps. ZH24 KVE to ZH48 KVE Application Guidelines Scroll compressors with vapour injection for Dedicated Heat Pumps ZH24 KVE to ZH48 KVE Application Guidelines APPLICATION GUIDELINES: COPELAND SCROLL COMPRESSORS WITH VAPOUR INJECTION FOR DEDICATED HEAT

More information

Refrigeration Scroll Enhanced Vapour Injection

Refrigeration Scroll Enhanced Vapour Injection Refrigeration Scroll Enhanced Vapour Injection ZF13KVE... ZF18KVE Application Guidelines APPLICATION GUIDELINES: ENHANCED VAPOUR INJECTION (EVI) REFRIGERATION SCROLL COMPRESSORS ZF13KVE-ZF18KVE 1 Introduction...2

More information

Scroll compressors with vapour injection for Dedicated Heat Pumps. ZH13 KVE & ZH18 KVE Application Guidelines

Scroll compressors with vapour injection for Dedicated Heat Pumps. ZH13 KVE & ZH18 KVE Application Guidelines Scroll compressors with vapour injection for Dedicated Heat Pumps ZH13 KVE & ZH18 KVE Application Guidelines APPLICATION GUIDELINES: COPELAND SCROLL COMPRESSORS WITH VAPOUR INJECTION FOR DEDICATED HEAT

More information

AE R13 August 2018 Economized Vapor Injection (EVI) for ZF*KVE and ZF*K5E Compressors TABLE OF CONTENTS

AE R13 August 2018 Economized Vapor Injection (EVI) for ZF*KVE and ZF*K5E Compressors TABLE OF CONTENTS August 2018 Economized Vapor Injection (EVI) for ZF*KVE and ZF*K5E Compressors TABLE OF CONTENTS Safety Instructions... 3 Safety Icon Explanation... 3 Instructions Pertaining to Risk of Electrical Shock,

More information

Scroll Compressors for Heat Pump Applications ZH12K4E to ZH11M4E, ZH06KVE to ZH48KVE

Scroll Compressors for Heat Pump Applications ZH12K4E to ZH11M4E, ZH06KVE to ZH48KVE Scroll Compressors for Heat Pump Applications ZH12K4E to ZH11M4E, ZH06KVE to ZH48KVE About this guideline... 1 1 Safety instructions... 1 1.1 Icon explanation... 1 1.2 Safety statements... 1 1.3 General

More information

LZT High efficiency air to water heat pumps with E.V.I. compressors

LZT High efficiency air to water heat pumps with E.V.I. compressors High efficiency air to water heat pumps with E.V.I. compressors -20 C +43 C +65 C E.V.I. C.O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating

More information

REFRIGERANT CHANGEOVER

REFRIGERANT CHANGEOVER Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants

More information

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors infolinia: +48 691 262 691-15 C +63 C +43 C E.V.I. HP The series of high efficiency heat pumps has been specifically designed for use with

More information

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps AM-4249223-1 - Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps Christian K. Bach, Graduate Student, Eckhard A. Groll, Reilly Professor, James

More information

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the operation of reverse-cycle refrigeration (heat pumps) Explain

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information

WZT High Efficiency Air to Water Split System Heat Pumps With E.V.I. Compressors

WZT High Efficiency Air to Water Split System Heat Pumps With E.V.I. Compressors High Efficiency ir to Water Split System Heat Pumps With E.V.I. ompressors -20 +43 +65 HP E.V.I..O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor

More information

Technical Bulletin (TB-0037)

Technical Bulletin (TB-0037) Technical Bulletin (TB-0037) BITZER Software Guide Version 4, January 2015 DEFINITION OF TERMS Terms Found in the BITZER Software Condenser Capacity: The power needed to reject heat from the refrigerant

More information

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors -15 C +63 C E.V.I. The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems or

More information

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A

More information

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)

More information

500 EX Fusion Compressor Series

500 EX Fusion Compressor Series 500 EX Fusion Compressor Series R404A M/T R404A L/T Capacity RANGE 13.8kW - 20.4kW 7.7kW -11.2kW Copeland Fusion Semi-Hermetic Horizontal Scroll Compressors For Medium and Low Temperature Applications

More information

Everything You. NEED to KNOW. TXV does this by keeping the coil supplied

Everything You. NEED to KNOW. TXV does this by keeping the coil supplied Everything You NEED to KNOW About TXVs } With the higher SEER air conditioners, technicians need to reacquaint themselves with thermostatic expansion valves B Y A L M A I E R Before the 13 SEER minimum

More information

LZT LZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSION ACCESSORIES

LZT LZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSION ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors -15 +63 E.V.I..O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems

More information

LZT High efficiency air to water heat pumps with E.V.I. compressors

LZT High efficiency air to water heat pumps with E.V.I. compressors High efficiency air to water heat pumps with E.V.I. compressors -20 +43 +65 E.V.I..O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems

More information

AE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A

AE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A AE4-1392 July 2014 Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A Section TABLE OF CONTENTS Page Safety Safety Instructions...2 Safety Icon Explanation...2 Instructions

More information

S-Therm Air to Water Heat Pumps

S-Therm Air to Water Heat Pumps S-Therm Air to Water Heat Pumps AIR TO WATER HEAT PUMP Air to water heat pump Nowadays, people are increasingly focusing on the cost of heating as well as on environmental issues. Traditional heating systems

More information

Emerson R290 Solutions for Commercial Refrigeration Applications

Emerson R290 Solutions for Commercial Refrigeration Applications Emerson R290 Solutions for Commercial Refrigeration Applications Emerson R290 Solutions for Commercial Refrigeration Applications Many end-users and equipment manufacturers are investigating ways to minimize

More information

Air Conditioning Clinic. Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN

Air Conditioning Clinic. Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN Air Conditioning Clinic Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES BUSINESS REPLY MAIL FIRST-CLASS MAIL PERMIT NO. 11 LA CROSSE,

More information

Natural Refrigeration with Hydrocarbons Emerson s R290 Solutions

Natural Refrigeration with Hydrocarbons Emerson s R290 Solutions Natural Refrigeration with Hydrocarbons Emerson s R290 Solutions Atmosphere Conference 2016 20/04/2016, Barcelona Hydrocarbons - Favouring Reduced Charge & Indirect Systems Traditional Rack Refrigeration

More information

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison Emerging Technologies: VFDs for Condensers Douglas T. Reindl Director, IRC University of Wisconsin-Madison University of Wisconsin-Madison 1 We ve looked at VFDs on Evaporators and compressors, what is

More information

EN aquatech.piovan.com

EN aquatech.piovan.com EN aquatech.piovan.com Refrigeration Technologies: scroll-compressor chillers The scroll compressor is the most suitable component for the small and medium duty requirements in the industrial applications.

More information

Application Guidelines. Copeland Scroll Summit Series ZB50KCE to ZB114KCE & ZB66K5E to ZB114K5E ZF25K5E to ZF49K5E

Application Guidelines. Copeland Scroll Summit Series ZB50KCE to ZB114KCE & ZB66K5E to ZB114K5E ZF25K5E to ZF49K5E Application Guidelines Copeland Scroll Summit Series ZB50KCE to ZB114KCE & ZB66K5E to ZB114K5E ZF25K5E to ZF49K5E About these guidelines... 1 1 Safety instructions... 1 1.1 Icon explanation... 1 1.2 Safety

More information

AE October 1965 Reformatted October Hot Gas Bypass Control Systems

AE October 1965 Reformatted October Hot Gas Bypass Control Systems Hot Gas Bypass Control Systems AE21-1160 AE21-1160 October 1965 Reformatted October 2010 On many refrigeration and air conditioning systems, the refrigeration load will vary over a wide range. This may

More information

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 111 CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 7.1 INTRODUCTION Energy is the primary component to run any system in the world. According to

More information

Outdoor Refrigeration Unit - ZX Range High Efficiency In Compact Design

Outdoor Refrigeration Unit - ZX Range High Efficiency In Compact Design Outdoor Refrigeration Unit - ZX Range High Efficiency In Compact Design Outdoor Refrigeration Unit - ZX The Best Choice For Small Retail And Food Service Applications The new generation of Copeland EazyCool

More information

Enhancement of COP in Vapour Compression Refrigeration System

Enhancement of COP in Vapour Compression Refrigeration System Enhancement of COP in Vapour Compression Refrigeration System M. Krishna Prasanna #1 M.E student, Heat Transfer studies in Energy Systems Department of Mechanical Engg., Andhra University Visakhapatnam-530003,

More information

MODEL URS-1: FACTORY RETROFIT PROGRAM

MODEL URS-1: FACTORY RETROFIT PROGRAM MODEL URS-1: FACTORY RETROFIT PROGRAM The USR-1 unit has gone through extensive testing in order to attain maximum performance. It has been determined that in order to set the unit for all weather operation,

More information

Refrigerant Glide and Effect on Performances Declaration

Refrigerant Glide and Effect on Performances Declaration Refrigerant Glide and Effect on Performances Declaration Scope and Purpose As a consequence of the EU regulation 517/2014 (F-gas), the future synthetic refrigerants with a low global warming potential

More information

Scroll Compressor for Mobile HVAC/R Application

Scroll Compressor for Mobile HVAC/R Application Purdue University Purdue e-pubs International ompressor Engineering onference School of Mechanical Engineering 2004 Scroll ompressor for Mobile HVA/R Application Michael M. Perevozchikov opeland orporation

More information

Outdoor Condensing Unit - ZX Range. High Efficiency In Compact Design

Outdoor Condensing Unit - ZX Range. High Efficiency In Compact Design Outdoor Condensing Unit - ZX Range High Efficiency In Compact Design Outdoor Condensing Unit - ZX The Best Choice For Small Retail And Food Service Applications The new generation of Copeland EazyCool

More information

AE R8 March 2015

AE R8 March 2015 March 2015 Copeland Discus Compressors with Demand Cooling System TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to Risk

More information

Emerson Superheat Control. The smart solution for your application

Emerson Superheat Control. The smart solution for your application Emerson Superheat Control The smart solution for your application Trust in Emerson Climate Technologies for reliable, precise and efficient superheat control. When it comes to superheat control, Emerson

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

LZT LZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. A + A + VERSIONS ACCESSORIES

LZT LZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. A + A + VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors + + -0 +43 +65 E.V.I. The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems

More information

System Design, Commissioning, Operation

System Design, Commissioning, Operation PART 3: CO 2 as a Refrigerant System Design, Commissioning, Operation Service This series continues with the introduction of transcritical, cascade and secondary systems; how each system works; and compares

More information

Transcritical CO2 Bottle Cooler Development

Transcritical CO2 Bottle Cooler Development Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains

More information

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system. Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs the unwanted heat, this raises the refrigerant

More information

A Treatise on Liquid Subcooling

A Treatise on Liquid Subcooling A Treatise on Liquid Subcooling While the subject of this article is Liquid Refrigerant Subcooling, its affect on the operation of the thermostatic expansion valve (TEV), and ultimately on system performance

More information

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration Calhoon MEBA Engineering School Study Guide for Proficiency Testing Refrigeration 1. To prevent an injury when working with refrigerants, what safety precautions are necessary? 2. When halogens are in

More information

Danfoss scroll compressors SH- In parallel installation

Danfoss scroll compressors SH- In parallel installation MAKING MODERN LIVING POSSIBLE Application guidelines Danfoss scroll compressors SH- In parallel installation 50 Hz - 60 Hz - R410A www.danfoss.com CONTENTS General overview...4 Benefits... 4 Scope...

More information

Oxyvap Evaporative Cooling Applications

Oxyvap Evaporative Cooling Applications Oxyvap Evaporative Cooling Applications Oxycom Fresh Air BV March 9th, 2015 Abstract This paper shows two highly efficient applications of the Oxyvap direct evaporative cooling technology, developed by

More information

Danfoss scroll compressors SH - In parallel installation

Danfoss scroll compressors SH - In parallel installation Application guidelines Danfoss scroll compressors SH - In parallel installation 50 Hz - 60 Hz - R410A http://cc.danfoss.com Contents General overview... 5 Benefits... 5 Scope... 5 Design challenge...

More information

Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors

Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors AE4-1296 R3 March 2013 Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Instructions... 2 Safety Icon Explanation... 2

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING UNIT OBJECTIVES After studying this unit, the reader should be able to Select the correct instruments for checking an air conditioning unit

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models)

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models) 4-1280 Application Engineering Bulletin AE-1280R4 Revised April, 1995 APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models) Introduction The Compliant Scroll Compressor has been

More information

A WET-VAPOUR INJECTION AND VARIABLE SPEED SCROLL COMPRESSOR AIR TO WATER HEAT PUMP MODEL AND ITS FIELD TEST VALIDATION

A WET-VAPOUR INJECTION AND VARIABLE SPEED SCROLL COMPRESSOR AIR TO WATER HEAT PUMP MODEL AND ITS FIELD TEST VALIDATION Paper O.2.2.4-1 - A WET-VAPOUR INJECTION AND VARIABLE SPEED SCROLL COMPRESSOR AIR TO WATER HEAT PUMP MODEL AND ITS FIELD TEST VALIDATION Laurent Dardenne*, Enrico Fraccari*, Alessandro Maggioni**, Luca

More information

Air Conditioning Components

Air Conditioning Components Air Conditioning Components Agenda AC Components Compressor & Clutch Condenser Receiver-drier or Accumulator Expansion Valve or Orifice Tube Evaporator Compressor 2 primary purposes Increase pressure &

More information

DIN EN , DIN EN , DIN EN , DIN EN

DIN EN , DIN EN , DIN EN , DIN EN Test Report issued under the responsibility of: TEST REPORT EHPA-DACH Testing Regulation Supplemental requirements for granting the international quality label for heat pumps Testing of Air/Water Heat

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems . Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems PRESENTED BY NIRAJ MISTRY aircon@stroma.com Cooling Load The Refrigeration Load Cooling load on refrigeration system

More information

ECOFOREST GEOTERMIA. ecogeo. Ground/Air Source Heat Pumps.

ECOFOREST GEOTERMIA. ecogeo. Ground/Air Source Heat Pumps. ECOFOREST GEOTERMIA www.ecoforest.es comercial.geotermia@ecoforest.es Ground/Air Source Heat Pumps ecogeo ECOFOREST GEOTERMIA New company, 2010, Ecoforest Geotermia Manufacture of ground/air source heat

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

The Saturation process

The Saturation process SOUTH METROPOLITAN TAFE WA The Saturation process Dennis Kenworthy 8/5/2016 A student study guide to measuring and interpreting the saturation process of refrigeration and air-conditioning equipment System

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical

More information

R32 Compressor for Air conditioning and Refrigeration applications in China

R32 Compressor for Air conditioning and Refrigeration applications in China Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2012 R32 Compressor for Air conditioning and Refrigeration applications in China Weihua

More information

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit

More information

Customers. The core of our innovation. Feeding&Conveying Drying Dosing Temperature Control Refrigeration. Granulation

Customers. The core of our innovation. Feeding&Conveying Drying Dosing Temperature Control Refrigeration. Granulation EN Customers. The core of our innovation Feeding&Conveying Drying Dosing Temperature Control Refrigeration Granulation scroll-compressor chillers The scroll compressor is the most suitable component for

More information

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Investigation of Refrigerant Vapor- Injection Technique for

More information

1+ SEER. 25% COP boost possible. Most valves expand your refrigerant EcoFlow expands your options. with silent defrost.

1+ SEER. 25% COP boost possible. Most valves expand your refrigerant EcoFlow expands your options.   with silent defrost. MAKING MODERN LIVING POSSIBLE Most valves expand your refrigerant EcoFlow expands your options 25% COP boost possible with silent defrost. 1+ SEER energy savings Reduce energy consumption and increase

More information

Use this Construction/HVAC Glossary to answer the questions below.

Use this Construction/HVAC Glossary to answer the questions below. www.garyklinka.com Page 1 of 21 Instructions: 1. Print these pages. 2. Circle the correct answers and transfer to the answer sheet on the second last page. 3. Page down to the last page for the verification

More information

Commercial CO 2 Refrigeration Systems

Commercial CO 2 Refrigeration Systems Commercial CO 2 Refrigeration Systems Guide for Subcritical and Transcritical CO 2 Applications 2 Contents Chapter 1. Introduction 4 Chapter 2. CO 2 Basics and Considerations as a Refrigerant 5 Section

More information

LECTURE-17. Multi-Stage Vapour Compression Refrigeration. 1. Introduction

LECTURE-17. Multi-Stage Vapour Compression Refrigeration. 1. Introduction Lecturer: -Dr. Esam Mejbil Abid Subject: Air Conditioning and Refrigeration Year: Fourth B.Sc. Babylon University College of Engineering Department of Mechanical Engineering LECTURE-17 Multi-Stage Vapour

More information

Natural Heat VITOCAL 300-A VITOCAL 350-A. Air source heat pumps

Natural Heat VITOCAL 300-A VITOCAL 350-A. Air source heat pumps Natural Heat VITOCAL 300-A VITOCAL 350-A Air source heat pumps Heat pumps Vitocal 300-A Vitocal 300-A is certified in accordance with the EHPA heat pump quality seal and NF-PAC. Top technology for top

More information

COMMECH SERIES AIR CONDITIONING CSH SEMI-HERMETIC SCREW PACKAGES. ORIGINAL MANUFACTURED EQUIPMENT Commech Series New Models BA AUS

COMMECH SERIES AIR CONDITIONING CSH SEMI-HERMETIC SCREW PACKAGES. ORIGINAL MANUFACTURED EQUIPMENT Commech Series New Models BA AUS COMMECH SERIES AIR CONDITIONING CSH SEMI-HERMETIC SCREW ACKAGES ORIGINAL MANUFACTURED EUIMENT Commech Series New Models BA-509-2 AUS roduct Features The BITZER ComMech Series compact screw compressor pack

More information

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation INTRODUCTION In recent years air conditioning industry technology has advanced rapidly. An important byproduct of this growth has been development of the heat pump. Altogether too much mystery has surrounded

More information

Refrigeration and Air Conditioning

Refrigeration and Air Conditioning Refrigeration and Air Conditioning 1. Pick up the wrong statement. A refrigerant should have (a) Tow specific heat of liquid (b) high boiling point (c) high latent heat of vaporisation (d) higher critical

More information

SEMI-HERMETIC SCREW COMPRESSORS

SEMI-HERMETIC SCREW COMPRESSORS SEMI-HERMETIC SCREW COMPRESSORS 50 Hz // SP-00-5 EN HS.53 // HS.64 // HS.74 // HS.5 // HS.95 WITH IQ MODULE BIGGER MODELS BITZER Innovation Targets Semi-hermetic screw compressors Products for refrigerants

More information

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger "COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger" 1 Prof.Gaffar G.Momin, 2 Sagar B. Tupe, 2 Swapnil A. Parate 2 Omkar G. Yewale 2 Aakash P.

More information

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES SECTION 23 23 00 REFRIGERANT PIPING AND SPECIALITIES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Refrigerant piping. 2. Unions, flanges, and couplings. 3. Pipe hangers and supports. 4. Refrigerant

More information

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #32 System Soft-Optimized Test of Refrigerant D2Y60 in Air Source

More information

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING UNIT OBJECTIVES After studying this unit, the reader should be able to Describe how refrigerant is charged into systems in

More information

LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS

LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS 22-1182 Application Engineering Bulletin AE-1182-R24 Revised April 1, 1993 LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS One of the major causes of compressor failure is damage

More information

One. Save time and money Streamline your heat pump business! makes a difference.

One. Save time and money Streamline your heat pump business! makes a difference. Save time and money Streamline your heat pump business! Heat Pump Components - Selection guide One makes a difference Add one more Danfoss component to your system and find out how all element add up to

More information

(Refer Slide Time: 00:00:40 min)

(Refer Slide Time: 00:00:40 min) Refrigeration and Air Conditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 10 Vapour Compression Refrigeration Systems (Refer Slide

More information

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +

More information

Single Screw Ammonia Heat Pumps. Harness Your Heat... Don t Reject It

Single Screw Ammonia Heat Pumps. Harness Your Heat... Don t Reject It Single Screw Ammonia Heat Pumps Harness Your Heat... Don t Reject It Harness Your Heat Don't Reject It Industrial processes consume considerable energy from two primary sources in the production of their

More information

R07. Answer any FIVE Questions All Questions carry equal marks *****

R07. Answer any FIVE Questions All Questions carry equal marks ***** Set No: 1 III B.Tech. II Semester Supplementary Examinations, April/May 2013 REFRIGERATION AND AIR CONDITIONING (Mechanical Engineering) Time: 3 Hours Max Marks: 80 Answer any FIVE Questions All Questions

More information

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AIR CONDITIONING. Carrier Corporation 2002 Cat. No AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)

More information

Otherwise, you can continue reading the file on the following pages.

Otherwise, you can continue reading the file on the following pages. If you d like to be able to print this file out to study off-line or use on the job, a printable version is available for an administrative fee of $3.97 USD. To download the unlocked file, click here.

More information

Heat pump systems and Chillers

Heat pump systems and Chillers PRODUCT OVERVIEW Heat pump systems and Chillers HIdROS was formed in 1993 as a distribution company operating in the humidification and dehumidification sector of the air conditioning market. The expansion

More information

Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors

Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors August 2017 Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Safety... 2 Safety Instructions... 2 Safety Icon Explanation... 2 Instructions

More information

A Design for True Performance and Energy Savings In Refrigerated Compressed Air Dryers The Digital Scroll Dryer

A Design for True Performance and Energy Savings In Refrigerated Compressed Air Dryers The Digital Scroll Dryer A Design for True Performance and Energy Savings In Refrigerated Compressed Air Dryers The Digital Scroll Dryer Introduction By Timothy J. Fox, P.E. Hankison, an SPX Brand Canonsburg, Pennsylvania Refrigerated

More information

These units are available now from the Distribution Center. For a list of available models, click here.

These units are available now from the Distribution Center. For a list of available models, click here. NO: 39-10 DATE: 11/03/10 TO: EMERSON CLIMATE TECHNOLOGIES WHOLESALERS -EXECUTIVES -PRODUCT MANAGERS -BUYERS SUBJECT: COPELAND SCROLL OUTDOOR CONDENSING UNIT PRICING INFORMATION We are pleased to announce

More information

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou Condensers ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM A. Hadawey, Y. T. Ge, S. A. Tassou 4 7 8 5 3 2 6 1 Produced by: The Centre for Energy and Built Environment

More information

Danfoss scroll for refrigeration LLZ013 to low temperature

Danfoss scroll for refrigeration LLZ013 to low temperature MAKING MODERN LIVING POSSIBLE Application guidelines Danfoss scroll for refrigeration LLZ013 to 033 - low temperature 50-60 Hz - R404A - R507 http://cc.danfoss.com Contents Features...4 Scroll compression

More information

Refrigeration Systems and Accessories

Refrigeration Systems and Accessories As with the Chapter Review Tests and the Final Exam, the tests your understanding of the materials underlying the learning objectives. After you ve reviewed your answers to the Chapter Review Tests, try

More information