Effects of Air Conditioner Sizing on Energy Consumption and Peak Demand in a Hot-Dry Climate

Size: px
Start display at page:

Download "Effects of Air Conditioner Sizing on Energy Consumption and Peak Demand in a Hot-Dry Climate"

Transcription

1 Effects of Air Conditioner Sizing on Energy Consumption and Peak Demand in a Hot-Dry Climate Aaron Townsend, Building Science Corporation Kohta Ueno, Building Science Corporation ABSTRACT Oversizing of air conditioners is a common practice that reduces comfort and energy efficiency; the practice also results in higher first costs and exacerbates the effects of residential air conditioning on utility peak demand. At a subdivision in a hot dry climate (Redding, CA), a production homebuilder completed several houses at their standard practice equipment sizing of 155 to 185% of the total calculated Manual J load and subsequently built the remainder of the development with equipment resized to 135 to 150% of the total calculated Manual J load. Thirteen of these houses (7 in the standard practice sizing category; 6 in the resized category) were monitored for air conditioner runtime, interior temperature, and electricity consumption of the outdoor condenser unit. Data was collected for three months, covering the end of summer and start of the swing season. This study found that in comparison to the standard practice group, the resized group had longer average and maximum runtimes, consumed the same amount of energy, and if implemented on a large scale would reduce the electric utility s peak demand. Introduction Background on Air Conditioning Sizing and Energy Savings Oversizing of residential cooling systems is common among builders and HVAC contractors; it results in greater first cost and reduced energy efficiency and comfort due to short cycling. In humid climates, the short cycling results in reduced latent capacity. Mechanical contractors often oversize units in order to reduce time spent on load calculations, to lower their potential for callbacks, and to allow for extraordinarily low thermostat set points (Vieira 1995). Short-cycling decreases capacity and increases energy consumption due to start-up losses that occur at the beginning of each cycle. The power input to the air conditioning system rises to near its steady-state level within a few seconds, yet the cooling output rises to its steady-state level over the course of a few minutes. The Seasonal Energy Efficiency Ratio (SEER) rating accounts for this effect via the cycling loss coefficient (C D ), which is determined experimentally (ARI 2006). For single-speed systems, SEER is calculated as: SEER = EER 82 * ( 1 C D / 2 ) where EER 82 is the steady-state energy efficiency ratio at an outdoor temperature of 82 F. Decreasing the value of C D therefore increases the SEER rating. Due to increased SEER standards and market competition, equipment manufacturers have an incentive to reduce the value of C D, and have successfully done so. The SEER procedure allows for a default value (in lieu of testing) for C D of 0.25; most modern equipment has C D in the range of 0.05 to 0.10 (Sonne 2006, Sachs 2006)

2 Previous studies have found differing results in energy savings due to reductions in capacity. A study of 308 homes in Florida (James 1997) found an energy savings of 5.6% associated with reducing system capacity from 150% to 120% of design loads. In contrast, a more recent analysis of four houses in Florida (Sonne 2006) found that the savings potential is dependent on location of the duct system. They found that the savings was 2 to 3% in systems with ducts located within conditioned space and negligible in systems with ducts in unconditioned attics. Sonne et al. postulated that the difference between their findings and previous findings may be due to technology improvements aimed at reducing the value of C D. Experimental Overview Building Science Corporation (BSC) worked with a production homebuilder on a development in Redding, California. The project was partially underway when BSC became involved. The initial sixteen houses were built according to the homebuilder s standard methods in this region, which were substantially more energy efficient than the average new house in the region. The only major change BSC recommended was upgrading the space conditioning systems to high-efficiency furnaces and properly sized air conditioning systems. As part of the builder s standard practice, a third-party consultant specified 4-ton air conditioners for the two smaller house plans and 5-ton air conditioners for the 2 larger house plans. For these houses, the evaporator coil sizes were matched to the condenser units. BSC reviewed the Manual J sizing calculations and found that the air conditioners were oversized due to assuming typical amounts of duct leakage; these houses were specified and tested to confirm low duct leakage. The builder and HVAC contractor therefore reduced the size of the air conditioners; the two smaller plans received 3.5-ton condensers, and two larger plans received 4- ton condensers. Due to a miscommunication between the builder and contractor, all of the houses in the resized group received 4-ton evaporator coils and air handler units. Oversizing the air handler and evaporator coil with respect to the condenser is standard practice for some HVAC contractors in dry climates and results in higher evaporator coil temperatures and therefore higher efficiency; however in this case it would have been desirable to install all systems under uniform matching or mismatching criteria. In the remainder of this paper the houses built with the original size condensers will be considered the standard practice (S) group, and the houses built with the resized condensers will be considered the resized (R) group. Within the seven houses in the standard practice group, four houses were unoccupied model homes (M), and three others were occupied (O). All six of the resized group houses were occupied (O). Labels were applied to each house to uniquely identify them: SM1 through SM4, SO1 through SO3, and RO1 through RO6 (see Table 1). House Characteristics The houses in this study were newly-constructed, slab-on-grade homes. The four house plans in the community are all single-family, single story, and range from about 2100 to 2900 square feet of conditioned floor area. The enclosure insulation consists of R-38 ( F-hr-ft 2 /Btu) blown fiberglass at the ceiling plane and R-15 netted & blown fiberglass plus 1 of EPS sheathing (R-4) for the walls. The windows are double-pane low-e with an overall U-value of 0.33 Btu/hr-ft 2 - F and a solar heat gain coefficient (SHGC) of

3 The air handlers and duct systems were located in the vented attics. The duct system was entirely flex duct with R-6 insulation. The duct sizes were not changed when the air conditioners were resized, as they were not oversized for the lower airflow. All of the test houses were tested for enclosure leakage and duct leakage by a third party tester as part of the builder s normal quality assurance program. Enclosure leakage results ranged from 1.7 to 2.3 square inches per 100 square feet surface area leakage ratio. For these houses, these measurements were equivalent to 2.9 to 4.3 ACH 50. The average was 3.3 ACH 50, and there was little difference between the average air leakage of the standard practice and resized houses (2.0 and 1.9 square inches per 100 square feet surface area, respectively). Duct leakage was tested after the houses were finished using a duct pressurization test. Results were compared in terms of leakage normalized by nominal air handler flow. Results varied from 3.5% to 5.7% of nominal flow, with an average of 4.3%. There was little difference between the standard practice and resized houses (averages of 4.4% and 4.3%, respectively). Manual J Calculations A cooling load calculation was performed for each house in the study using a commercial software tool based on ACCA Manual J version 8 (ACCA 2003). The ASHRAE 0.4% design condition of 106 F for Redding, CA (ASHRAE 2005) was used for the outdoor temperature, along with an indoor temperature of 75 F, and appropriate values for the envelope attributes and internal loads. Table 1 below contains the results of these calculations along with the nominal size of the condenser unit, estimated air conditioning system capacity at design conditions, and the ratio of installed capacity to calculated design load. The system capacity had to be estimated, as a third-party evaporator coil was used (per the contractor s standard practice) and extended performance ratings were not available for the combination of condenser and evaporator coil. The estimate was made by assuming that the installed evaporator coil had the same performance characteristics as the condenser manufacturer s evaporator coil of the same nominal capacity, which allowed use of the condenser manufacturer s published extended performance ratings. The seven standard practice houses have installed capacities from 155% to 184% of their calculated total design loads, and the six resized houses have installed capacities from 135% to 152% of their calculated design loads. All of the condensers and furnaces were made by the same manufacturer, and the evaporator coils were made by a second manufacturer

4 Table 1: Manual J Cooling Load and Estimated System Capacity in Monitored Houses House Plan CFA (sf) Orientation Installed AC Size (Condenser/Evaporator, nominal tons) Estimated AC Capacity at 105 F (kbtu/hr) Manual J Load Capacity/Load Ratio (kbtu/h) total sensible latent total SM N 4/ SM N 4/ SM N 5/ SM N 5/ SO E 4/ SO SW 5/ SO SE 5/ RO W 4/ RO SE 4/ RO NW 4/ RO SW 3.5/ RO W 4/ RO N 3.5/ CFA = Conditioned Floor Area Data Collection Data collected by the monitoring equipment included outdoor temperature and relative humidity in one location in the community, indoor temperature at three locations in each house, relative humidity at one location in ten of the houses, and condenser runtime and condenser energy consumption in each house. The outdoor temperature sensor was mounted out of the direct sun under the north-facing eave of one of the houses. This sensor recorded the outdoor temperature every 15 minutes. Comparison of the recorded data with data from a nearby airport indicates that the sensor experienced indirect solar heating from the roof deck. The temperatures recorded by this sensor are similar to the airport data at night, yet peak 0 to 8 F higher during the day; the magnitude of the difference correlates with the solar declination. Temperature was recorded hourly at three locations in each house: at the thermostat, in the master bedroom, and in a second bedroom or den on the opposite side of the house from the master bedroom. In ten of the thirteen houses relative humidity was recorded in at least one of these locations as well. Transitions in operation state of the condenser unit were recorded, giving run time and length. A separate meter recorded total condenser electricity consumption in 30-day periods. During installation of the monitoring equipment, one-time measurements of the airflow, power draw, and external static pressure (ESP) across each air handler were made. Airflow was measured at each of the two returns in each house with an air handler/return filter flowmeter and a digital manometer. Power draw of the air handler was measured with a portable power meter. External static pressure was measured with a handheld digital manometer. At the conclusion of the field monitoring, a homeowner survey was administered, covering aspects such as thermostat set points, number of occupants, occupancy patterns, and unusual electrical loads

5 Monitored Period Due to the construction schedule, the monitoring period included only half of the cooling season. Installation of the monitoring equipment was completed on two separate dates. Monitoring began in the first ten houses (SM1 to SM4, SO1 to SO3, and RO1 to RO3) on 7/20/07 and in the remaining three houses (RO4 to RO6) on 8/1/07. Monitoring lasted three months, well past the end of the cooling period in this location. Figure 1 shows the daily high and low outdoor temperature for all of 2007 as recorded by a weather station at the Redding Municipal Airport. The three one-month long monitored periods are indicated on the graph. The monitored period did not include the hottest recorded temperatures this summer, which was 112 F on 7/4/07. The hottest temperature during the monitored period was 106 F on 8/23/07. The 0.4% recorded temperature for this summer was 104 F. For comparison, the ASHRAE extreme annual design condition is 111 F and the 0.4% design condition is 106 F. The monitored period included only 2 hours above the design condition of 106 F, but had 60 hours above 100 F. Figure 1: Redding Municipal Airport Daily High and Low Temperatures for Temperature ( F) monitored periods 0 Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Results Air Handler Efficiency The air handler (AHU) efficiency was calculated in terms of CFM per watt, and plotted against the external static pressure (ESP) in Figure

6 Figure 2: AHU Efficiency vs. External Static Pressure CFM Per Watt Model Houses Standard Practice Occupied Houses Resized Occupied Houses 0.5 IWC External Static Pressure (IWC) The model houses were built on an accelerated schedule and therefore had different AHUs than the remaining houses. The model homes had variable-speed AHUs, with measured air-moving efficiencies of 2.0 to 2.4 CFM/watt at ESP of 0.8 to 1.0 inches of water column (IWC) (199 to 249 Pa). The higher ESP in the models was due to dirty air filters (the models were the first houses built and were operating with their original filters) and slightly higher airflow (due to the variable-speed AHUs). The occupied houses had single-speed AHUs, with an average efficiency of 1.8 CFM/watt at ESP of 0.4 to 0.7 IWC (100 to 174 Pa), similar to other field studies showing average power draws of CFM/watt at ESP of 0.38 to 0.55 IWC (95 to 137 Pa) (Proctor and Parker 2000). Previous work including a survey of manufacturers data at 0.5 IWC (125 Pa) of ESP showed a median of 2.2 CFM/watt (CEC 2006). All of the standard practice units showed external static pressures higher than the manufacturer s recommendation of 0.5 IWC (125 Pa). The median of the occupied standard practice homes was 0.66 IWC (164 Pa). The median of the model homes was 0.84 IWC (209 Pa). This is consistent with measurements by CEC (2006), showing a median cooling speed ESP of 0.80 IWC (199 Pa) in a survey of 60 installed furnace systems. A significant portion of the pressure drop in the houses in the current study was due to the MERV-13 filters used at the return grilles. While the pressure drop across the filters was not measured directly, the median return pressure (as measured between the filter and the blower) in the standard occupied houses was 0.38 IWC (95 Pa), significantly above the 0.15 IWC (37 Pa) that would normally be expected. The filters are specified as having a pressure drop of 0.28 IWC (70 Pa) at 500 ft/min face velocity when first installed; with the measured flow volume and face area resulting in 250 to 350 ft/min face velocity and assuming the pressure drop is linearly related to the airflow, the estimated pressure drop across the filters would be 0.14 to 0.19 IWC (35 to 47 Pa). The pressure drop would increase as the filters became dirty. It is notable that the resized houses had lower ESP, in the range of the manufacturer s recommendation, due to the fact that the sizes of the ductwork, return grills, and return filters were not reduced when the air conditioning system was resized

7 Occupant Thermostat Behavior There was substantial variation in occupancy and occupant behavior among both the model and occupied homes. The model homes were unoccupied, but had all of the interior lights on during the day. Among the occupied houses, both occupancy and thermostat behavior varied widely. The number of occupants varied between 1 and 5 people per house, with a median of 3. Thermostat behavior was quite varied. All of the houses had programmable thermostats installed by the builder; however none of the occupants appeared to use the programmable feature. Previous studies (Parker 1996) have identified four categories of thermostat operation by the occupants: constant off, constant setpoint, daily set up/set down, and manual on/off. All of these behaviors were observed in the collection of occupied houses in this study. Only one house showed an example of the constant off category. The occupants in one house (SO1) turned off their air conditioner for a total of 22 days from 7/20 to 9/19, resulting in significantly lower energy consumption than their neighbors but at the expense of peak indoor temperatures of 90 F. The four model houses and five of the occupied houses had constant thermostat settings, with relatively infrequent adjustments to the setpoint. The model houses were locked at a single temperature and were not changed. These houses showed a strong relationship between air conditioner hourly runtime and indoor-outdoor temperature difference (see Figure 3). In the occupied houses, the correlation between air conditioner hourly runtime and indoor-outdoor temperature difference was not as strong, due to varied interior loads and occupant behavior (see Figure 4). Two of the occupied houses had daily setup/setback schedules. Both of the houses appeared to do so manually, as the schedule varied somewhat from day to day. One of the houses set up the thermostat at night and back in the morning. The second set up the thermostat at night and back in the late afternoon. One of the occupied houses was operated as a manual on/off system. This resulted in wide swings in temperature, long runtimes, and weak correlation between air conditioner hourly runtime and indoor-outdoor temperature difference (see Figure 5). Figure 3: Correlation of SM1 Runtime Fraction to Indoor-Outdoor Temperature Difference Runtime Fraction (Fraction of Hour) Indoor - Outdoor Temperature Difference ( F) 1-297

8 Figure 4: Correlation of SO2 Runtime Fraction to Indoor-Outdoor Temperature Difference Runtime Fraction (Fraction of Hour) Indoor - Outdoor Temperature Difference ( F) Figure 5: Correlation of RO4 Runtime Fraction to Indoor-Outdoor Temperature Difference Runtime Fraction (Fraction of Hour) Indoor - Outdoor Temperature Difference ( F) Air Conditioner Capacity and Runtime A major objective of the monitoring was to determine the effect of resizing on the run lengths and runtime fractions of the air conditioners. The HVAC contractor was concerned that the resized air conditioners would not be large enough. Two metrics were used to address this concern. The first metric was how long the air conditioner ran during the hottest day of the monitored period, and the second was how long the longest runtime of the entire monitored period was, and what caused it to be this long. A summary of the air conditioner operation during the hottest day in the monitored period is presented in Table 2. The hottest day occurred on 8/1/07, with the on-site temperature measurement reaching 109 F. The data show that the standard practice groups have maximum hourly runtime fractions in the range of 0.49 to 0.76, and the resized group has higher maximum hourly run fractions in the range of 0.74 to

9 Throughout the monitored period SM3 showed unusually short runtimes of 6 to 8 minutes. It was determined that the thermostat was causing this phenomenon, although it was still able to maintain the desired setpoint. Table 2: Results of Air Conditioner Operation on Hottest Day in Monitoring Period House Longest Run Length Highest Hourly Run Fraction (fraction (minutes) of hour) SM SM SM SM SO SO SO RO1 216* 1.00 RO RO RO4 109* 1.00 RO RO * These long runtimes were due to changes in the thermostat set point A summary of longest runs, and what caused those runs, is presented in Table 3. The cause of the long runs could be estimated based on the interior temperature response and occupancy of the houses. The rate of temperature reduction with the air conditioner active is the same at a given (constant) cooling load and outdoor temperature. Therefore, if indoor temperature response is different than usual under the same outdoor conditions, it is likely that there is a cooling load that is out of the ordinary. For the unoccupied models, this was usually an open door or window (due to prospective homebuyers wandering through the model). In the occupied houses, the load could be cooking, showering, open doors or windows, or other occupant behavior. Table 3: Summary of Longest Air Conditioner Runs House Date Longest Run Length Apparent Cause (minutes) SM1 9/2 110 Open door or window SM2 8/31 78 Open door or window SM3 9/19 27 Change in setpoint SM4 8/31 62 Open door or window SO1 8/ Change in setpoint SO2 8/ Change in setpoint SO3 7/ Change in setpoint RO1 7/ Change in setpoint RO2 7/ Change in setpoint RO3 7/ Cooking or open door or window RO4 9/1 224 Change in setpoint RO5 9/2 100 Change in setpoint RO6 8/3 215 Open door or window The data show that changes in set point are the most common cause of long runs, with non-envelope loads such as cooking or open doors or windows a close second. These non

10 envelope loads were not measured and therefore are suppositions based on a comparison of the rate of decrease in the indoor temperature upon air conditioner activation with the normal rate of decrease at the same outdoor conditions. The resized group does have longer maximum runs but variation due to individual occupant behavior is more pronounced than variation between sizing groups. Long runs most often happen when the enclosure load is highest and capacity is lowest (during peak outdoor temperatures) but drastic thermostat changes were observed even at night, which resulted in occasional long runtimes with minimal enclosure loads. Indoor Relative Humidity Relative humidity was measured at the thermostat in at least one location in ten of the thirteen houses. The measurements show that no houses had a significant number of hours over 60% relative humidity and all had median relative humidity of between 40% and 50%. Figure 6 shows the distribution of hourly measurements for the ten houses with relative humidity sensors. Seven of the ten houses had very similar behavior, with relative humidity most often in the 40% to 50% range and very few hours outside of the 30% to 60% range. SM3, SO1, and SO2 show behavior atypical of the remaining seven houses. SM3 had lower median and average relative humidity. SM3 had short, frequent runtimes (discussed later) so it is possible that the evaporator coil stayed cold enough between runs to effectively dehumidify the space; however coil temperature was not measured and so only speculation is possible. The occupants of SO1 turned off their air conditioner for several days, resulting in high temperatures and correspondingly low relative humidity for a large number of hours. Finally, SO2 shows a higher number of hours in the 50% to 60% range than the other houses. Analysis of time-series data shows uniformly higher relative humidity than other houses in either the standard or resized group; therefore it is more likely due to occupant behavior (cooking, bathing, plants, etc) than differences in the air conditioning system. Overall, there is no clear difference in the humidity levels between the standard and resized groups. Figure 6: Distribution of Relative Humidity Hourly Measurements Number of Hours SM1 SM2 SM3 SM4 SO1 SO2 SO3 RO1 RO2 RO Relative Humidity Bin Center (%) 1-300

11 Condenser Energy Consumption The monitoring period was broken into three 1-month-long periods: July 20 to August 19, August 20 to September 19, and September 20 to October 19. Air conditioner electricity consumption data for the houses are shown in Table 4. Because three houses (SO4 to SO6) were not monitored for all of the July 20 to August 19 period, daily average consumption was calculated as a comparable metric. Table 4: Daily Average Condenser Electricity Consumption Daily Average AC Consumption House (kwh), Period Ending: 8/20/07 9/20/07 10/20/07 SM SM SM SM SO SO SO RO RO RO RO RO RO After eliminating the four model houses and one standard practice occupied house (SO1) due to unusual occupancy habits, only two houses (SO2 and SO3) provided useful data for a basis of comparison in the standard practice group. The occupants of these two houses had normally expected behavior, with occasional but not drastic adjustments to the set point. Table 5 below shows the average and standard deviation of the electricity consumption of the standard practice comparison basis group (SO2 and SO3) and the resized group (RO1 through RO6). The difference between the two groups is statistically insignificant. Given the large variation in energy consumption due to occupant behavior, a much larger sample group would be needed before the uncertainty would be smaller than the difference between the averages. Table 5: Comparison of Condenser Energy Consumption in Standard Practice and Resized Groups Peak Demand Group Standard Practice (SO2 & SO3) Resized (RO1 to RO6) Quantity Daily Average AC Consumption 8/20/07 9/20/07 10/20/07 Average Standard Deviation Average Standard Deviation As the utility s peak demand for this summer occurred prior to completion of these houses, measured data during peak demand are not available. However assuming cycling losses are low, delivered cooling at a given temperature is nearly proportional to runtime. Therefore, 1-301

12 runtime during near-peak conditions can be extrapolated to peak conditions. Figure 7 below shows the runtime fraction during the peak demand period each day (4:00 PM to 7:00 PM) versus the daily maximum temperature for that day (which typically occurs earlier than the peak demand), for SM3 and RO4, the houses with the best and worst correlation, respectively. This data includes only the first two months of monitoring (7/20/07 through 9/19/07), as the third month had little cooling in any of the houses. Figure 7: Run Fraction during Peak Period Each Day, Best (SM3) and Worst (RO4) Correlations Runtime Fraction 4:00 PM to 7:00 PM y = 0.01x R 2 = Peak Temperature 112 F Runtime Fraction 4:00 PM to 7:00 PM y = x R 2 = Peak Temperature 112 F Daily Maximum Outdoor Temperature ( F) Daily Maximum Outdoor Temperature ( F) SM3 is a model home, with no occupants and a constant set point. In contrast, RO4 is an occupied home with an occupant that used the thermostat as a manual on/off switch for the air conditioner. The difference between the two is a rather extreme illustration of the variability that occupant behavior introduces into the cooling electric demand. Fortunately, over a large sample of the population this variability decreases and the utility s total load becomes more predictable. Using a linear curve-fit to the data, an estimate can be made for the runtime fraction under peak conditions of a large population of similar homes. Table 6 contains the curve-fit data, coefficient of determination, and estimated average runtime fraction under peak conditions for all of the monitored houses. The data shows that, under averaged occupant behavior (i.e. conforming to the curve-fit line), none of the houses in any of the groups would run continuously for the entire peak period; estimated runtime fractions are actually quite low for most of the houses, in the range of 0.46 to However, three of the six resized houses (RO1, RO2, and RO6) show average runtime fractions sufficiently high that actual occupant behavior would cause a portion of a population of these houses to run continuously during peak conditions. Figure 8 shows the extrapolation of two of these houses (RO1 and RO2) to peak temperatures

13 Table 6: Extrapolation of Runtime Fraction to Peak Conditions Curve Fit: y = mx + b Estimated Runtime m b R^2 Fraction at Peak SM SM SM SM SO SO SO RO RO RO RO RO RO Figure 8: Houses with High Likelihood of Running Continuously During Peak Conditions 1.00 Peak Temperature 112 F 1.00 Peak Temperature 112 F Runtime Fraction 4:00 PM to 7:00 PM y = x R 2 = Runtime Fraction 4:00 PM to 7:00 PM y = x R 2 = Daily Maximum Outdoor Temperature ( F) Daily Maximum Outdoor Temperature ( F) Peak demand savings due to resizing air conditioners depends on whether or not the air conditioner was cycling during peak demand prior to resizing. For the houses with air conditioners that are cycling during peak conditions, the average power draw during peak will be the power draw while running times the runtime fraction. A marginal decrease in capacity will result in a marginal increase in runtime fraction, a marginal decrease in power draw while running, and little impact on peak power demand. Only power draw due to cycling losses will be reduced. On the other hand, for the houses with air conditioners running continuously during peak conditions, the runtime fraction cannot be increased and therefore the average power will be the same as the power draw while running. In this case, a marginal decrease in capacity will not be offset by an increase in runtime fraction; therefore any decrease in capacity will result in a direct reduction of peak demand. Therefore, houses with air conditioning equipment sized such that they run continuously during peak load conditions provide the majority of the potential peak demand savings due to marginal decreases in air conditioner capacity. For air conditioning systems that cycle under peak load conditions, large decreases in capacity are needed in order to significantly affect peak load

14 Conclusions The resized equipment is sufficient to meet the loads in the houses. Both the resized and standard practice systems can have excessive runtimes when set points are changed, particularly if the change is large or happens during periods of high outdoor temperature. The resized group has longer average and maximum runs. For maximum runs, variation due to individual occupant behavior is more pronounced than variation between sizing groups. The results of this study agree with a recent study (Sonne 2006) finding only a small difference in cooling energy use would be expected between resized systems and systems oversized within normal ranges (50-100% oversized). The houses in the current study had ducts in unconditioned attics, which would tend to reduce any energy savings gained by sizing closer to the actual load due to longer runtime and the resulting increase in duct leakage and heat gain. Differences in monthly energy consumption between the groups are statistically insignificant, in large part due to varying occupant behavior. Of the standard practice group, only one house (SM3) had cycle times short enough to cause concern in terms of short-cycling inefficiencies and equipment durability; this was due to a malfunctioning thermostat and not the equipment sizing. In a large sample of houses with air conditioning equipment sized similar to the standard practice group (155% to 180% of Manual J), virtually none would be expected to run continuously during peak electrical demand; therefore modest reductions in size are of marginal value as they save only the cycling losses (reductions in instantaneous power draw would be offset by longer runtimes). In a large sample of houses with air conditioning equipment sized similar to the resized group (135 % to 150% of Manual J), a fraction of the houses will run continuously during peak electric demand, therefore reducing peak demand by the reduction in electricity draw of the system (instantaneous power draw is reduced and runtime is still 100%). Houses with air conditioning equipment sized even closer to Manual J will increase both the fraction of houses running continuously and the peak demand savings of each house, therefore more significantly reducing peak demand. However, houses sized closer to Manual J will also experience longer average and maximum runtimes; when designing systems at this level care should be taken to properly locate and size supply and return registers to minimize noise and comfort issues associated with air conditioner operation. Previous research (Proctor 1998) has demonstrated that actual house loads in hot-dry climates were on the order of 67% of ACCA Manual J calculated loads; reducing equipment size closer to 100% of calculated load or lower has been shown to provide acceptable results in this and other studies (Rudd 2000). Acknowledgements The authors would like to thank the Department of Energy and the Building America Program for funding this research, as well as the homeowners and builder partners for their cooperation and participation. References Air Conditioning Contractors of America (ACCA) Manual J Residential Load Calculations, 8th Edition. Arlington, Va.: Air Conditioning Contractors of America

15 Air-Conditioning and Refrigeration Institute (ARI) Standard for Performance Rating of Unitary Air-Conditioning and Air-Source Heat Pump Equipment. Arlington, Va.: Air- Conditioning and Refrigeration Institute American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) ASHRAE Handbook Fundamentals. Atlanta, Ga.: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. California Energy Commission (CEC) California Building Energy Efficiency Standards: Fan Watt Draw and Air Flow. Sacramento, Calif.: California Energy Commission. James, P., J.E. Cummings, J. Sonne, R. Vieira, and J. Klongerbo The Effect of Residential Equipment Capacity on Energy Use, Demand, and Run-Time. In ASHRAE Transactions, Vol 103, Pt. 2. Atlanta, Ga.: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. Parker, D., S. Barkaszi, J. Sherwin, and C.S. Richardson Central Air Conditioner Usage Patterns in Low-Income Housing in a Hot and Humid Climate: Influence on Energy Use and Peak Demand. In 1996 ACEEE Summer Study on Energy Efficiency in Buildings Proceedings, 8: Washington, D.C.: American Council for an Energy Efficient Economy. Proctor, John Monitored In-Situ Performance of Residential Air-Conditioning Systems. In ASHRAE Transactions, 104(1B): Atlanta, Ga.: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. Proctor, J., and D. Parker Hidden Power Drains: Trends in Residential Heating and Cooling Fan Watt Power Demand. In 2000 ACEEE Summer Study on Energy Efficiency in Buildings Proceedings. Washington, D.C.: American Council for an Energy Efficient Economy. Rudd, A., J. Lstiburek, and K. Ueno Unvented-Cathedralized Attics: Where We've Been and Where We're Going In ACEEE Summer Study on Energy Efficiency in Buildings Proceedings. Washington, D.C.: American Council for an Energy Efficient Economy. Sachs, H., H. Henderson, D. Shirley, S. Nadel, D. Jaynes Can SEER Be Saved? In 2006 ACEEE Summer Study on Energy Efficiency in Buildings Proceedings. Washington, D.C.: American Council for an Energy Efficient Economy, Washington, D.C. Sonne, J., D. Parker, and D. Shirey III Measured Impacts of Proper Air Conditioner Sizing in Four Florida Case Study Homes. Final Report FSEC-CR Cocoa, Fla.: Florida Solar Energy Center. Vieira, R.K., J. Klongerbo, J.K. Sonne and J.E. Cummings Florida Residential Air Conditioning Sizing Survey Results, In ASHRAE Transactions V.101, Part 2. Atlanta, Ga.: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me!

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me! 97.501B Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-24800 Monitored In-Situ Performance of Residential Air-Co onditioning Systems Sponsored By: Arizona Public Service Company

More information

Practical and Effective Approaches to Residential Ventilation for Production Builders

Practical and Effective Approaches to Residential Ventilation for Production Builders Practical and Effective Approaches to Residential Ventilation for Production Builders by Armin Rudd USDOE Building America Program for Affordable Comfort Conference 2002 Cincinnati, Ohio 18 April 2002

More information

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida Case Study of an Innovative HVAC System with Integral Dehumidifier Richard A. Raustad Don B. Shirey, III Senior Research Engineer Program Manager Florida Solar Energy Center Cocoa, Florida ABSTRACT In

More information

Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada

Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada building science.com 2008 Building Science Press All rights of reproduction in any form reserved. Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada

More information

Time-Based Scheduling of Residential Ventilation

Time-Based Scheduling of Residential Ventilation Time-Based Scheduling of Residential Ventilation by Armin Rudd USDOE Building America Program for EEBA Conference 2000 Building for Peak Performance Denver, Colorado 26 October 2000 Climate Specific Design

More information

Systems Engineering Approach to Development of Advanced Residential Buildings

Systems Engineering Approach to Development of Advanced Residential Buildings building science.com 2000 Building Science Press All rights of reproduction in any form reserved. Systems Engineering Approach to Development of Advanced Residential Buildings Building Ameria Report 0010

More information

New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review

New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review FSEC-PF-454-11 May 2011 Author Carlos Colon Copyright 2011 Florida Solar Energy Center/University

More information

Relative Humidity in Schools Jim Cummings and Chuck Withers

Relative Humidity in Schools Jim Cummings and Chuck Withers to Co n tr o l Relative Humidity in Schools Jim Cummings and Chuck Withers SEEC Southern Energy-Efficiency Center Energy Efficient Strategies to Control Relative Humidity in Schools James Cummings and

More information

RESNET HERS Rater Sample Test Questions 2

RESNET HERS Rater Sample Test Questions 2 RESNET HERS Rater Sample Test Questions 2 1. Which of the following is the best device for removing standing water from a crawl space? A. Dehumidifier B. Sump pump C. Air-to-air heat exchanger D. Crawl-space

More information

Understanding Ventilation in Hot Humid Climates by Joseph Lstiburek

Understanding Ventilation in Hot Humid Climates by Joseph Lstiburek building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Building Science Digest 107 Understanding Ventilation in Hot Humid Climates 2006-10-26 by Joseph Lstiburek

More information

99.503A. Prepared by: (415) Drains: Power. Prepared for: ACEE. Final Report Contributors: Danny Parkerr. Me!

99.503A. Prepared by: (415) Drains: Power. Prepared for: ACEE. Final Report Contributors: Danny Parkerr. Me! Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-24800 Hidden Power Drains: Residential Heating and Cooling Fan Power Demand Prepared for: ACEE Final Report 2000 Contributors:

More information

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed

More information

TESTS OF ADSIL COATING

TESTS OF ADSIL COATING TESTS OF ADSIL COATING Test B - Long Term Test FSEC-CR-1259-01 July 11, 2001 Prepared for: Bob Suggs Florida Power & Light Company 9250 W. Flagler Street Miami, Florida 33174 Principal Investigator Dr.

More information

Prepared by: (415) itioner. Contributors: Me!

Prepared by: (415) itioner. Contributors: Me! Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-24800 Effects of Occup pant Control, System Parameters, and Program Measures On Residential Air Condi itioner Peak Loads Final

More information

Unvented Roof Summary Article

Unvented Roof Summary Article building science.com 2008 Building Science Press All rights of reproduction in any form reserved. Unvented Roof Summary Article Research Report - 0301 2003 Kohta Ueno Abstract: This article was written

More information

Special Topics on Residential HVAC

Special Topics on Residential HVAC Special Topics on Residential HVAC by Armin Rudd USDOE Building America Program for EEBA Conference 2002 Phoenix, Arizona 10 October 2002 Page 1 of 25 Two Main Topics: 1. Cyclical trade-offs between building

More information

Optimizing Energy Efficiency and Improved Dehumidification Performance of Variable Capacity Air Conditioning Systems

Optimizing Energy Efficiency and Improved Dehumidification Performance of Variable Capacity Air Conditioning Systems Optimizing Energy Efficiency and Improved Dehumidification Performance of Variable Capacity Air Conditioning Systems FSEC-PF-473-18 August 17, 2018 Presented at 2018 ACEEE Summer Study on Energy Efficiency

More information

Design Methodology and Economic Evaluation of Central-Fan-Integrated Supply Ventilation Systems

Design Methodology and Economic Evaluation of Central-Fan-Integrated Supply Ventilation Systems building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Design Methodology and Economic Evaluation of Central-Fan-Integrated Supply Ventilation Systems Building

More information

Duct Design and Installation

Duct Design and Installation Duct Design and Installation John Proctor, P.E. Proctor Engineering Group, Ltd. San Rafael, CA 2004 Proctor Engineering Group, Ltd. 1-888-455-5742 mail@proctoreng.com www.proctoreng.com Duct Design ACCA

More information

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM Page 1 UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM Each of the 38 points of requested information is discussed, and references to the supporting manual are given to substantiate the requirement.

More information

Improving Air Handler Efficiency in Houses

Improving Air Handler Efficiency in Houses Improving Air Handler Efficiency in Houses Iain S. Walker, Lawrence Berkeley National Laboratory ABSTRACT Although furnaces, air conditioners and heat pumps have become significantly more efficient over

More information

Residential Heating and Cooling Loads

Residential Heating and Cooling Loads OVERVIEW Residential Heating and Cooling Loads Brief systems engineering introduction Discussion of heating and cooling loads by way of examining the system sizing process. By: Armin Rudd Building Science

More information

Building America AC Installation Using CheckMe!

Building America AC Installation Using CheckMe! Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-2480 Building America AC Installation Using CheckMe! Prepared for: Building Science Corporation Pulte Homes Sierra Air Final

More information

Pacific Gas and Electric Company

Pacific Gas and Electric Company Pacific Gas and Electric Company Emerging Technologies Program Application Assessment Report #0724 Hot Dry Climate Air Conditioner Pilot Field Test Phase II Issued: 2/08/2008 Project Manager: Lance Elberling

More information

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection. Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using

More information

An Innovative Product s Path to Market. The influence of laboratory and field evaluations on adoption and implementation

An Innovative Product s Path to Market. The influence of laboratory and field evaluations on adoption and implementation Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-2480 An Innovative Product s Path to Market. The influence of laboratory and field evaluations on adoption and implementation

More information

Field Tests of Specially Selected Air Conditioners for Hot Dry Climates

Field Tests of Specially Selected Air Conditioners for Hot Dry Climates Field Tests of Specially Selected Air Conditioners for Hot Dry Climates Abram Conant and John Proctor, Proctor Engineering Group Lance Elberling, Pacific Gas and Electric Company ABSTRACT This paper presents

More information

Data driven insights from the nation s deepest ever customer energy research

Data driven insights from the nation s deepest ever customer energy research Pecan Street Research Institute Pike Powers Lab and Center for Commercialization Data driven insights from the nation s deepest ever customer energy research Change in peak load 70,000 by customer class

More information

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,

More information

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report East Liberty Presbyterian Church 14 009 For: By: East Liberty Presbyterian Church Jeffery Ison, James Construction Date: October

More information

Strategies for Summer Utility Savings. Residential Environmental Program Series May 15, 2013

Strategies for Summer Utility Savings. Residential Environmental Program Series May 15, 2013 Strategies for Summer Utility Savings Residential Environmental Program Series May 15, 2013 Are FC Summers Getting Hotter? 200 Fort Collins Annual Hours 90 F or Above 150 100 50 1970 1980 1990 2000 2010

More information

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.

More information

Ventilation in Humid Climates: Data from Field Experiments

Ventilation in Humid Climates: Data from Field Experiments Gaylord Texan Resort & Convention Center October 20-23, 2004 - Dallas, Texas Ventilation in Humid Climates: Data from Field Experiments Neil Moyer FSEC Yearly Housing Starts Past 3 Years Source: NAHB x

More information

MANUAL J/S Summary One summary sheet for each system

MANUAL J/S Summary One summary sheet for each system MANUAL J/S Summary One summary sheet for each system NOTE: The load calculation must be calculated on a room basis. Room loads are a mandatory requirement for making Manual D duct sizing calculations.

More information

ASHRAE JOURNAL ON REHEAT

ASHRAE JOURNAL ON REHEAT Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide

More information

Promoting quality installation of central AC (and heat pump) systems

Promoting quality installation of central AC (and heat pump) systems Promoting quality installation of central AC (and heat pump) systems Energy Design Conference and Expo Duluth, MN February 26, 2014 and gas furnaces In accordance with the Department of Labor and Industry

More information

Overview. Case Study 2008 Building America Prototype ICI Showcase House. Daytona Beach, Florida. Project Team: ICI Homes, Building Science Corporation

Overview. Case Study 2008 Building America Prototype ICI Showcase House. Daytona Beach, Florida. Project Team: ICI Homes, Building Science Corporation 008 /009Building America Prototype ICI Showcase House Case Study 008 Building America Prototype ICI Showcase House Daytona Beach, Florida Project Profile Overview Building Science Corporation (BSC) collaborated

More information

MAD-AIR 2016 Mechanical Air Distribution and Interacting Relationships. John Tooley Advanced Energy (919)

MAD-AIR 2016 Mechanical Air Distribution and Interacting Relationships. John Tooley Advanced Energy (919) MAD-AIR 2016 Mechanical Air Distribution and Interacting Relationships John Tooley Advanced Energy (919) 857-9000 Tuesday, April 05, 2016 MAD-AIR When? 31 years ago 30 years ago 28 years ago Bought a blower

More information

Closing the Gap: Getting Full Performance from Residential Central Air Conditioners. Task 4 - Develop New Climate-Sensitive Air Conditioner

Closing the Gap: Getting Full Performance from Residential Central Air Conditioners. Task 4 - Develop New Climate-Sensitive Air Conditioner Closing the Gap: Getting Full Performance from Residential Central Air Conditioners Task 4 - Develop New Climate-Sensitive Air Conditioner Simulation Results and Cost Benefit Analysis April 27, 27 Prepared

More information

In the past, contractors sized heating and cooling systems GETTING HVAC RIGHT

In the past, contractors sized heating and cooling systems GETTING HVAC RIGHT GETTING HVAC RIGHT Calculating loads is just the first step. For a trouble-free system that s long on comfort, you need to specify the equipment, design the ductwork, and make certain everything is correctly

More information

Why Doesn t My HVAC System Work?

Why Doesn t My HVAC System Work? Why Doesn t My HVAC System y y y Work? Defining Not Working Too hot and humid in the Summer-- Maybe the whole house, or just certain rooms. Too cold in the Winter Goldilocks and the three bears problem--

More information

Dehumidification: Energy Efficiency Comparisons

Dehumidification: Energy Efficiency Comparisons Fourth Annual Energy Management Workshop Cocoa, Florida February 10-11, 2003 Dehumidification: Energy Efficiency Comparisons Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting,

More information

Executive Summary: Evaluation of the Impact of Vacant Home Space Conditioning Strategies on Summer Relative Humidity, Energy, and Peak Load; Phase II

Executive Summary: Evaluation of the Impact of Vacant Home Space Conditioning Strategies on Summer Relative Humidity, Energy, and Peak Load; Phase II Executive Summary: Evaluation of the Impact of Vacant Home Space Conditioning Strategies on Summer Relative Humidity, Energy, and Peak Load; Phase II Authors James B. Cummings, Charles R. Withers, Jr.,

More information

RECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES FOR RESIDENTIAL BUILDINGS

RECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES FOR RESIDENTIAL BUILDINGS ESL-TR-7-9-1 RECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES FOR RESIDENTIAL BUILDINGS A Project for Texas Senate Bill 5 Legislation For Reducing Pollution in Nonattainment and Affected Areas

More information

BEST PRACTICE FOR THE LOCATION OF THE AIR AND THERMAL BOUNDARIES IN SMALL COMMERCIAL BUILDINGS

BEST PRACTICE FOR THE LOCATION OF THE AIR AND THERMAL BOUNDARIES IN SMALL COMMERCIAL BUILDINGS BEST PRACTICE FOR THE LOCATION OF THE AIR AND THERMAL BOUNDARIES IN SMALL COMMERCIAL BUILDINGS James B. Curnrnings Charles Withers Principal Research Analyst Research Analyst Florida Solar Energy Center

More information

buildingscience.com Windows and Occupant Comfort EEBA Building Solutions 2003 Lincolnshire, IL

buildingscience.com Windows and Occupant Comfort EEBA Building Solutions 2003 Lincolnshire, IL Windows and Occupant Comfort EEBA Building Solutions 2003 Lincolnshire, IL Phil Kerrigan, Jim Larsen, Cardinal Glass Industries PR-0307: Windows and Occupant Comfort Page 1 of 56 Code House in Zone 5 R38

More information

Energy Efficiency Potential of Heat Pump Water Heaters in Commercial Buildings

Energy Efficiency Potential of Heat Pump Water Heaters in Commercial Buildings Energy Efficiency Potential of Heat Pump Water Heaters in Commercial Buildings Christopher Gray, Southern Company ABSTRACT As energy prices continue to rise and pressures increase to reduce global warming

More information

Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards

Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards Date: February 15, 2018 Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards Grantee Name: University of Central

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

When Duct Sealing Kills HVAC Equipment and Efficiency

When Duct Sealing Kills HVAC Equipment and Efficiency When Duct Sealing Kills HVAC Equipment and Efficiency National Comfort Institute is an international training and development company headquartered in Cleveland, Ohio, with offices in Nashville, Tennessee,

More information

Residential HVAC System Design

Residential HVAC System Design Residential HVAC System Design Crosswalk to NATE Competencies and Tasks The following North American Technical Excellence (NATE) competencies and tasks are covered in this publication. These competencies

More information

Performance of Solar Water Heating Systems in the United States

Performance of Solar Water Heating Systems in the United States Performance of Solar Water Heating Systems in the United States Danny Parker & Camilo Gil Florida Solar Energy Center ACEEE Hot Water Forum June 2009, Asilomar,, California Rebate situation in Florida

More information

Fifteen Years of Dehumidification Results from Heat Pump Water Heaters

Fifteen Years of Dehumidification Results from Heat Pump Water Heaters Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Fifteen Years of Dehumidification Results from Heat Pump Water Heaters

More information

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Continuous Commissioning: A Valuable Partner to Retrofit Projects Continuous Commissioning: A Valuable Partner to Retrofit Projects Yeqiao Zhu Aamer Athar Kenneth Banks Ph.D. PE, CEM PE, CEM Energy Systems Laboratory Sempra Energy Solutions Sempra Energy Solutions Charles

More information

The Ed Roberts Campus Berkeley, CA

The Ed Roberts Campus Berkeley, CA The Ed Roberts Campus Berkeley, CA Anderson Clemenceau Mechanical Option Penn State A.E. Senior Thesis April 14, 2015 Leddy Maytum Stacy Architects, Photo by Tim Griffith ASHRAE Climate Zone 3C 99.6% Heating

More information

wattsmart New Homes Contractor-Certified HVAC Quality Assurance (HVAC-QI)

wattsmart New Homes Contractor-Certified HVAC Quality Assurance (HVAC-QI) Contractor-Certified HVAC Quality Assurance (HVAC-QI) HVAC Quality Assurance (HVAC-QI) Checklists The following checklists are required, with all applicable items completed and checked, including final

More information

Energy Impacts of Various Residential Mechanical Ventilation Strategies

Energy Impacts of Various Residential Mechanical Ventilation Strategies Energy Impacts of Various Residential Mechanical Ventilation Strategies Authors Robin K. Vieira, Danny S. Parker, Lixing Gu, and Michael Wichers Original Publication Vieira, R., Parker, D., Gu, L., and

More information

The Housing Assistance Council is a national nonprofit organization that helps build homes and communities

The Housing Assistance Council is a national nonprofit organization that helps build homes and communities communities across rural America. The Housing Assistance Council is a national nonprofit organization that helps build homes and communities across rural America. PRACTITIONERS GUIDE TO MEETING ENERGY

More information

Saying Mahalo to Solar Savings: A Billing Analysis of Solar Water Heaters in Hawaii

Saying Mahalo to Solar Savings: A Billing Analysis of Solar Water Heaters in Hawaii Saying Mahalo to Solar Savings: A Billing Analysis of Solar Water Heaters in Hawaii Jenny Yaillen, Evergreen Economics Chris Ann Dickerson, CAD Consulting Wendy Takanish and John Cole, Hawaii Public Utilities

More information

Air Distribution Fan and Outside Air Damper Recycling Control

Air Distribution Fan and Outside Air Damper Recycling Control building science.com 2008 Building Science Press All rights of reproduction in any form reserved. Air Distribution Fan and Outside Air Damper Recycling Control Research Report - 0991 5-July-1999 Armin

More information

b.) Technical Information:

b.) Technical Information: Section VI- Strategies a.) Summary: It is important for new construction designers to consider the heating, ventilation, and air conditioning needs within a building. There are many different systems,

More information

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC VOLUME ONE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Part-Load Strategies Why they re important.......... 1 What Things

More information

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING Rebeca Barbosa 1, Martin Barták 1, Jan L. M. Hensen 1, 2, Marcel G. L. C. Loomans 2 1 Czech Technical

More information

Executive Summary

Executive Summary Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-2480 Investigation of Coil Failures - A Whole Systems Approach Prepared for: Geothermal Heat Pump Consortium Final Report July

More information

Modular Construction. Live/Work Urban Infill Townhome. Modular Construction. Enclosure Design. San Francisco Bay Area Net Zero Urban Infill

Modular Construction. Live/Work Urban Infill Townhome. Modular Construction. Enclosure Design. San Francisco Bay Area Net Zero Urban Infill Learning Objectives for this Session Kohta, June 25-29, 11, Montreal, QC Compare the present and predicted future affordability of net zero energy homes. Provide an estimate of required PV price for NZEH

More information

COMMERCIAL HVAC PACKAGED EQUIPMENT. Split Systems

COMMERCIAL HVAC PACKAGED EQUIPMENT. Split Systems COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They are

More information

2019 Smart Energy Existing Homes Program Manual

2019 Smart Energy Existing Homes Program Manual 2019 Smart Energy Existing Homes Program Manual Reduce the Use: Residential Table of Contents INTRODUCTION... 1-1 1.1 PROGRAM OVERVIEW... 1-1 1.2 PROGRAM ASSISTANT... 1-1 1.3 SANTEE COOPER RESIDENTIAL

More information

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs Abstract Fan and coil evaporators as used in the industrial refrigeration industry can be certified for performance per ANSI/AHRI Standard 420-2008, Performance Rating of Forced-Circulation Free-Delivery

More information

ENGINEERING. Edition No. 13 October 2002

ENGINEERING. Edition No. 13 October 2002 Edition No. 13 October 2002 ENGINEERING S Y S T E M S O L U T I O N S W e at McQuay are very proud of our tradition of producing industry leading water source heat pumps. Our heritage stretches back more

More information

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION DL Bohac * Center for Energy and Environment, Minneapolis, MN USA ABSTRACT Extensive

More information

The Unplanned Impacts On Houses By Powered Attic Ventilators

The Unplanned Impacts On Houses By Powered Attic Ventilators The Unplanned Impacts On Houses By Powered Attic Ventilators John J. Tooley Jr., Natural Florida Retrofit Bruce Eugene Davis, Advanced Energy Corporation Applied Building Science Center 1994 ABSTRACT It

More information

MEASURED PERFORMANCE DATA FOR

MEASURED PERFORMANCE DATA FOR MEASURED PERFORMANCE DATA FOR HOUSE #4 INVERNESS GARDENS MILLER HOMES FEBRUARY 2013 Submitted to: NYSERDA 17 Columbia Circle Albany, NY 12203 Submitted by: HOMEPIC Team CDH Energy Corp. PO Box 641 Cazenovia,

More information

Fan Selection. and Energy Savings

Fan Selection. and Energy Savings Fan Selection and Energy Savings Reducing power consumption by minimizing system pressure loss and choosing the right equipment HBy BRIAN MLEZIVA Greenheck Fan Corp. Schofield, Wis. Power Consumption HVAC

More information

Working With DHPS and Other Variable Capacity Heat Pumps. October 05, 2017

Working With DHPS and Other Variable Capacity Heat Pumps. October 05, 2017 Working With DHPS and Other Variable Capacity Heat Pumps October 05, 2017 1 Housekeeping Welcome Safety Bathrooms Cell phones 2 Session Survey Instructions At the end of each session, you will be given

More information

Managing HVAC in High Performance Buildings

Managing HVAC in High Performance Buildings Managing HVAC in High Performance Buildings Ultra-Aire is one of five brands manufactured in Madison, WI under Therma-Stor, LLC. Our company, established in 1977, is considered the pioneer of whole-house

More information

Final Report. Investigation of Energy Impacts of Ducted Dehumidifier Duct Configurations and Location. DBPR Project #B21551 UCF/FSEC #

Final Report. Investigation of Energy Impacts of Ducted Dehumidifier Duct Configurations and Location. DBPR Project #B21551 UCF/FSEC # + Final Report Investigation of Energy Impacts of Ducted Dehumidifier Duct Configurations and Location DBPR Project #B21551 UCF/FSEC #2012-7106 FSEC-CR-2038-18 June 1, 2018 Submitted to: Mo Madani Florida

More information

BSC Building America High Performance Homes: Today & Tomorrow. Peter Yost Senior Building Scientist

BSC Building America High Performance Homes: Today & Tomorrow. Peter Yost Senior Building Scientist BSC Building America High Performance Homes: Today & Tomorrow Peter Yost Senior Building Scientist Building America homes... create energy efficient environments that: - are affordable to operate - use

More information

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001 This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.

More information

Southwest Air Conditioning

Southwest Air Conditioning Southwest Air Conditioning John Proctor, P.E. Proctor Engineering Group, Ltd. San Rafael, CA 94901 415-451-2480 mail@proctoreng.com SWEEP 2012 Copyright 2012 Proctor Engineering Group, Ltd. Southwest Climate

More information

Heating and Hot Water

Heating and Hot Water Heating and Hot Water Funding Funding for this class was provided by the Alaska Housing Finance Corporation (AHFC). This course is designed to empower homeowners with the knowledge to live in and maintain

More information

Technical Report Three

Technical Report Three Technical Report Three Existing Conditions for Mechanical Systems Contents Executive Summary...2 Building Overview...2 Mechanical Systems Overview...2 Mechanical System...3 Outdoor & Indoor Design Conditions...3

More information

Measured Duct Leakage at Operating Conditions in 48 Homes

Measured Duct Leakage at Operating Conditions in 48 Homes Measured Duct Leakage at Operating Conditions in 48 Homes Erin Kruse, Ecotope, Inc. Paul Francisco, University of Illinois, Building Research Council Larry Palmiter and Bob Davis, Ecotope, Inc. ABSTRACT

More information

Air-Conditioning Buying Guide

Air-Conditioning Buying Guide Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence

More information

Cold comfort: The rising use (and cost) of air conditioning in B.C. Report. July 2018 BCH18-712

Cold comfort: The rising use (and cost) of air conditioning in B.C. Report. July 2018 BCH18-712 Cold comfort: The rising use (and cost) of air conditioning in B.C. Report July 2018 BCH18-712 Cold comfort: The rising use (and cost) of air conditioning in B.C. With another hot summer upon us, British

More information

Demonstration of 2nd Generation Ducted GE "Brillion" Hybrid Water Heater in the PNNL Lab Homes

Demonstration of 2nd Generation Ducted GE Brillion Hybrid Water Heater in the PNNL Lab Homes Demonstration of 2nd Generation Ducted GE "Brillion" Hybrid Water Heater in the PNNL Lab Homes 2013 ACEEE Hot Water Forum Sarah Widder Research Engineer Pacific Northwest National Laboratory Project Participants

More information

Comparative Summer Thermal Performance of Finished and Unfinished Metal Roofing Products with Composition Shingles

Comparative Summer Thermal Performance of Finished and Unfinished Metal Roofing Products with Composition Shingles Comparative Summer Thermal Performance of Finished and Unfinished Metal Roofing Products with Composition Shingles Danny Parker John Sherwin Jeff Sonne Florida Solar Energy Center 1679 Clearlake Rd, Cocoa,

More information

2018 Smart Energy Existing Homes Program Manual

2018 Smart Energy Existing Homes Program Manual 2018 Smart Energy Existing Homes Program Manual Reduce the Use: Residential Table of Contents Section 1 Section 2 Section 3 Section 4 Appendix A Appendix B Appendix C Introduction... 1-1 1.1 Program Overview...

More information

Monty Anderson Construction Group Home Address: 3251 Great Oaks Boulevard Kissimmee, FL Certified: Score: 164

Monty Anderson Construction Group Home Address: 3251 Great Oaks Boulevard Kissimmee, FL Certified: Score: 164 Builder: Monty Anderson Construction Group Home Address: 3251 Great Oaks Boulevard Kissimmee, FL Certified: 2-12-13 Score: 164 Level: Gold Version: 9 FGBC Certifying Agent: Scott Grieves, sgrieves@kua.com

More information

Humidity Control in Humid Climates

Humidity Control in Humid Climates Humidity Control in Humid Climates Armin Rudd Building Science Corporation August 2013 NOTICE This report was prepared as an account of work sponsored by an agency of the United States government. Neither

More information

In Air Conditioning, If Bigger Is Not Better, What Is?

In Air Conditioning, If Bigger Is Not Better, What Is? Page 1 of 8 In Air Conditioning, If Bigger Is Not Better, What Is? Article published in Home Energy Magazine Issue Dated: September/October, 1996 Written by: Michael Blasnik Since the publication of Bigger

More information

Effect Of Setup Thermostat Schedule On Heat Pump Water Heater Energy Consumption, Coefficient Of Performance And Peak Load

Effect Of Setup Thermostat Schedule On Heat Pump Water Heater Energy Consumption, Coefficient Of Performance And Peak Load Effect Of Setup Thermostat Schedule On Heat Pump Water Heater Energy Consumption, Coefficient Of Performance And Peak Load Philip Boudreaux, Roderick Jackson, Jeffrey Munk and Anthony Gehl, Oak Ridge National

More information

AN ANALYSIS OF THE RESIDENTIAL ENERGY SAVINGS FROM THE IMPLEMENTATION OF THE 2001 IECC AND 2006 NAECA APPLIANCE STANDARDS IN THE STATE OF TEXAS

AN ANALYSIS OF THE RESIDENTIAL ENERGY SAVINGS FROM THE IMPLEMENTATION OF THE 2001 IECC AND 2006 NAECA APPLIANCE STANDARDS IN THE STATE OF TEXAS AN ANALYSIS OF THE RESIDENTIAL ENERGY SAVINGS FROM THE IMPLEMENTATION OF THE 2001 IECC AND 2006 NAECA APPLIANCE STANDARDS IN THE STATE OF TEXAS Jaya Mukhopadhyay, Zi Liu Ph.D., Mini Malhotra, Jeff Haberl

More information

ENERGY SYSTEMS LABORATORY

ENERGY SYSTEMS LABORATORY ESL-TR-8-11-2 RECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES ON IMPLEMENTING HOUSTON AMENDMENTS TO SINGLE-FAMILY BUILDINGS IN HOUSTON TEXAS Zi Liu, Ph.D. Jaya Mukhopadhyay Mini Malhotra

More information

Evaporative Cooling in a Hot-Dry Climate

Evaporative Cooling in a Hot-Dry Climate Evaporative Cooling in a Hot-Dry Climate David Springer Davis Energy Group SWEEP Workshop July 10, 2007 Sponsors: Clarum Homes California Energy Commission U.S.Department of Energy Issues for Discussion

More information

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA CITY OF DANA POINT COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 33282 Golden Lantern, Suite 209 Dana Point, CA 92629 949 248 3594 www.danapoint.org INDOOR AIR QUALITY B011 AIR 2013 CALIFORNIA CODES CODE

More information

Design and Operation of a Conditioning Energy Recovery Ventilator (CERV) for Passive Houses

Design and Operation of a Conditioning Energy Recovery Ventilator (CERV) for Passive Houses Design and Operation of a Conditioning Energy Recovery Ventilator (CERV) for Passive Houses Ben Newell and Ty Newell January 22, 2009 Newell Instruments Inc. 1103 N High Cross Rd Urbana, IL 61802 Phone:

More information

Cork County Energy Agency

Cork County Energy Agency Cork County Energy Agency Energy Audit Midleton Area Office December 2009 Table of Contents 1. Introduction...1 2. Site description...2 3. On site energy use...3 3.1 Energy management...3 3.2 Breakdown

More information

NAHB Green Home Building Guidelines. 3.1 Prerequisites. ResCheck. Energy Efficiency

NAHB Green Home Building Guidelines. 3.1 Prerequisites. ResCheck. Energy Efficiency NAHB Green Home Building Guidelines Energy Efficiency 3.1 Prerequisites 3.1.1 Home is equivalent to the IESS 2003 or local energy code. Conformance shall be based on plan analysis using software. 3.1.2

More information

HVAC Field Evaluation

HVAC Field Evaluation WESTERN COOLING EFFICIENCY CENTER // PROJECT REPORT HVAC Field Evaluation SDG&E Energy Innovation Center, San Diego, CA June 215 By: Caton Mande Development Engineer Western Cooling Efficiency Center 215

More information

Monetization of Thermal Comfort in Residential Buildings

Monetization of Thermal Comfort in Residential Buildings Monetization of Thermal Comfort in Residential Buildings Xia Fang, Marcus V. Bianchi, Craig Christensen, National Renewable Energy Laboratory ABSTRACT Building energy simulations can help us determine

More information