Jim Aswegan Chief Engineer
|
|
- Theodore Stevenson
- 6 years ago
- Views:
Transcription
1 Displacement Ventilation Jim Aswegan Chief Engineer
2 Displacement Ventilation Systems Comfort & Contaminate Control DV Concepts & System Benefits Outlet Types and Air Patterns Example l Space Layouts Displacement & LEED 2
3 ASHRAE 2011 Application Ch. 57 Fully Stratified Partially Mixed Fully Mixed Displacement Under Floor Air Distribution G.R.D.
4 Fully Mixed Air Distribution Cold & (Hot) Supply Air F F (85 90 F) High Velocity Supply Outside Occupied Zone Minimizes Temp. Variations in Space Uniform Contaminate Concentration 4
5 Fully Mixed Air Distribution Mixed Air Distribution Mixed Contaminates 5
6 Fully Stratified Air Distribution Cool Air Supply Only Air is Supplied Horizontally across the Floor at Low Velocity (< 70 fpm) Temperature Stratification from Floor to Ceiling (Return) Contaminate Concentration reduced in Occupied Zone 6
7 Fully Stratified Air Distribution 7
8 Displacement Ventilation BASIC CONCEPTS & SYSTEM BENEFITS 8
9 Basic System Concepts Low Energy ( < 0.04 Ps) Air Change Effectiveness (Std. 62.1, Ez = 1.2) Quiet Operation (< 25 NC)
10 Low Energy Higher equipment efficiency Uses warmer supply air 65 F compared to 55 F Energy consumption is often reduced by raising discharge temperature Extended Economizer Cycle
11 HVAC System Benefits Heat sources outside the stratification layer are not considered in airflow calculations l Lighting load is designed as equipment load, but not as space load Eff t li l d it b t t i Effects cooling load capacity, but not air distribution capacity
12 HVAC System Benefits Use 100% outside air overnight to cool Reduced chiller capacity Can be considered a thermal energy storage Can be considered a thermal energy storage system qualifying the owner for utility rebates
13 Low Energy Lower horsepower fans 004in 0.04 in. pressure is required for proper diffuser performance Results in lower horsepower fans required = Fan Energy egysavings
14 Improved Ventilation ASHRAE Standard d 62.1 Ventilation for Acceptable Indoor Air Quality Zone Air Distribution Effectiveness, E z Overhead Cooling System = 1.0 Displacement l t Ventilation = % Less Fresh Air Required
15 Return Air Outlet located at ceiling level Allows heat tfrom ceiling lights to be returned before it is able to mix with occupied zone Reduced supply volume Reduced supply volume means higher return temperatures
16 Humidity Issues A potential problem with warmer supply air temperatures is higher humidity Supply system must reduce relative humidity to less than 60% to meet IAQ concerns Condenser water reheat, run around coils, or face & bypass Use of a separate system to dry outside air or the use of desiccant dehumidification f l d f d h df If 55 o F supply air is used for dehumidification, return air can be mixed with supply air to achieve 65 o F air
17 Perimeter Heating Perimeter heating can not be accomplished with traditional displacement ventilation Separate system required in most applications: UFAD perimeter system Perimeter fan powered systems Ducting of hot or reheated air Baseboard Radiation Rdi Radiant panels Dual Chamber Diffuser 17
18 Dual Chamber Diffuser Dual chamber diffuser Dual chamber plenum Displacement cooling Mixed-air heating Actuated diverter (24V) Displacement diffuser cooling Linear diffuser heating 18
19 Application Examples Good applications Room height > 9.0 ft Open Plan Offices Meeting Rooms Casinos Restaurants Theaters, & Auditoriums Schools & Universities 19
20 Displacement Ventilation Advantages Smaller cooling power for desired room temperature in the occupied area Improved air quality in occupied area Longer periods of free cooling 20
21 Application Examples Poor Applications Room height < 9 ft Surplus heat tis the main problem not air quality In combination with mixing systems Office/rooms with cubicles Spaces with heavy contaminants 21
22 Displacement Ventilation Disadvantagesg Risk of draft due to placement of the diffusers Wall mounted devices often occupy large wall areas Stratified air becomes uncomfortable when cooling load exceeds ~30 Btu/hr ft t 2 Cannot heat with displacement ventilation 22
23 Thermal Comfort ASHRAE Standard 55 Thermal Environmental Conditions for Human Occupancy Maximum recommended T hf = 5.4 F Avoid drafts by keeping T es < 36 F
24 Temperature Gradient Ceiling Height % Rule is applied 62 F 72 F 82 F 10 F 10 F (Displacement ventilation, REHVA)
25 Temperature Gradient Ceiling Height > 14 33% Rule 33% 67% 65 F 72 F 86 F 7 F 14 F (Displacement ventilation, REHVA)
26 Displacement Ventilation TYPES OF OUTLETS & DISTRIBUTION PATTERNS 26
27 Adjacent Zone 27
28 Discharge Air Patterns 28
29 Standard Air Patterns Adjusted Air Patterns 29
30 Rectangular Displacement Diffusers Mounts in wall 1 way pattern 30
31 Displacement Diffusers Rectangular Rectangular In wall, flush or floor mount 31
32 Displacement Diffusers Rectangular 3 Way Rectangular In wall, flush or floor mount 3 way pattern 32
33 Displacement Diffusers Rectangular Curved Face Flush or floor mount 3 way pattern 33
34 Displacement Diffusers Rectangular Stair Riser Steps, Stair Risers applications Great for auditoriums, concert, arena s, and lecture halls 34
35 Displacement Diffusers Circular Column l or floor mount 360º discharge 35
36 Displacement Diffusers Semi Circular 180º Sidewall or column applications 180º pattern 36
37 Displacement Diffusers U shaped Semi circular i i l w straight ih sides 3 way pattern 37
38 Displacement Diffusers Corner w/ Curved Face Corner mount applications i 2 way pattern 38
39 Displacement Diffusers Corner/Flat Face Corner mount applications 2 way pattern 39
40 Displacement Ventilation EXAMPLE SPACE LAYOUTS 40
41 Private Perimeter Office Perimeter Wall 41
42 Open Plan Interior Office 42
43 Interior Break Room Round Outlets 43
44 Perimeter Conference Room Outside Wall 44
45 Elementary School Classroom Perimeter Wall 45
46 ASHRAE Standards for LEED ASHRAE S 62.1 IEQ Prerequisite 1: Minimum IAQ Performance IEQ Credit 1: Outdoor Air Delivery Monitoring IEQ Credit 2: Increased Ventilation IEQ Credit 6.2: Controllability of Systems: Thermal Comfort (for naturally ventilated spaces) ASHRAE Standard 55 IEQ Credit 6.2: Controllability of Systems: Thermal Comfort IEQ Credit : Thermal Comfort: Design IEQ Credit 7.2: Thermal Comfort: Verification
47 Displacement & LEED Optimize Energy Performance (EAc1) Minimum IAQ Performance (EQp1) Increased d Ventilation i (Q2) (EQc2) Thermal Comfort: Design (EQc7.1)
48 Displacement Ventilation & LEED Minimum Energy Performance: EAp2 Optimize Energy Performance: EAc1 Minimum Indoor Air Quality Performance: IEQ p1 Increased Ventilation: IEQc2 Thermal Comfort Design: IEQc7.1 48
49 Minimum IAQ Performance (EQp1) Minimum IAQ per ASHRAE EQ Q Prereq 1 Required
50 Increased Ventilation (EQc2) Increase breathing zone outdoor air ventilation rates to all occupied spaces by at least 30% above the minimum rates required by ASHRAE Standard as determined by EQ Prereq. 1 Submit Narrative describing the project s ventilation system, including fresh air intake volume for each zone and confirmation that outdoor air exceeds ASHRAE 62.1 by 30% EQ Credit 2 1 Point
51 Thermal Comfort (EQc7) Design Comply with ASHRAE Standard Submit Narrative detailing established comfort criteria per ASHRAE Standard , the desired quality and occupant satisfactionwithbuildingperformance performance, and supporting documentation showing the system design meetsthese these criteria EQ Credit Point
52 Publications HVAC Applications Handbook, Chapter 57 (ASHRAE, 2011) Fundamentals Handbook, Chapter 20 (ASHRAE, 2009) System Performance Evaluation and Guidelines for Displacement Ventilation (ASHRAE, 2003) Displacement Ventilation in Non Industrial Premises (REHVA, 2002)
53 Thank you! Questions? 53
Airex University VAV Applications Displacement Ventilation
Airex University VAV Applications Displacement Ventilation Jim Aswegan Chief Engineer Copyright Titus 2015 All rights reserved Discussion Items Terminal Unit Systems Single Duct Dual Duct Fan Powered Terminal
More informationUFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas
UFAD and Displacement Ventilation Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and DV Systems, Objectives: Understand Differences between: Well Mixed, Partially Stratified and Fully
More informationDisplacement Ventilation
Displacement Ventilation Displacement Ventilation Displacement Ventilation vs. Dilution Ventilation Characteristics Design Considerations Layout and Selection Product Overview Casino Case Study Dilution
More informationdesign brief This design brief provides an introduction into the design and application of DV. It addresses the following issues:
energydesignresources design brief DISPLACEMENT VENTILATION Summary Displacement ventilation (DV) is an alternate air distribution method for commercial and industrial spaces. 1 Used since the late 1970s
More informationUnderfloor Air Distribution:
Underfloor Air Distribution: An underfloor air distribution system utilizes a plenum space between the structural slab and the underside of a raised floor to distribute the conditioned air to the room.
More informationEngineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.
VAV Diffusers lease refer to the rice Engineer s HVAC Handbook for more information on VAV Diffusers. Diffuser Types Ceiling Diffusers Conventional air distribution systems typically group several rooms
More informationDESCRIPTION OF TECHNOLOGY
March 2009 Underfloor Air Distribution INTRODUCTION Copyright 2009 Glumac. All rights reserved. While this Green Paper discusses primarily the use of raised access floors for air distribution, HVAC integration
More informationRaised Access Floor - (AE Breadth Area)
Raised Access Floor - (AE Breadth Area) Currently, the Plaza has a raised access flooring system on both the 7 th and 8 th floors. The 8 th floor is designed with an independent HVAC system utilizing an
More informationDisplacement Ventilation in Classrooms
TWO DIFFUSERS, THE WHITE COLUMNS ON EACH SIDE OF THE WHITEBOARD, PROVIDE COOL SUPPLY AIR TO THE DEMONSTRATION DV CLASSROOM. THE DV CLASSROOM DEMONSTRATION FEATURED A CUSTOMIZED ROOFTOP HVAC UNIT. Displacement
More informationRadiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems
Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems CBE Timothy Moore CENTER FOR THE BUILT ENVIRONMENT SimBuild
More informationAir Distribution for Comfort. David Pich P.E. LEED AP Director of HVAC Technology
Air Distribution for Comfort David Pich P.E. LEED AP Director of HVAC Technology What You Will Learn ASHRAE Standards for Comfort & IAQ Types of Comfort Cooling Systems Fully Mixed Partially Mixed Fully
More informationVentilation Strategies for Healthy IEQ and Energy Efficiency
Ventilation Strategies for Healthy IEQ and Energy Efficiency Lars Ekberg Energy Management AB A Chalmers Industriteknik Company The purpose of ventilation + - Pollution Climate Heat Pollution 2 Examples
More informationUFAD Underfloor air distribution system
UFAD Underfloor air distribution system Design guide Version 1.0 Index Introduction... 4 System description... 5 The raised access floor... 5 Underfloor air distribution... 5 Perimeter and interior zones...
More informationASHRAE JOURNAL ON REHEAT
Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide
More informationTemperature Control and Zoning of UFAD Systems
Temperature Control and Zoning of UFAD Systems Presented by TROX USA Raised access flooring systems have become a very popular conduit for the delivery of power, voice and data services, as their accessibility
More informationSpace Air Diffusion II
MEBS6008 Environmental Services II http://me.hku.hk/bse/mebs6008/ Space Air Diffusion II Ir. Dr. Sam C. M. Hui Visiting Assistant Professor Department of Mechanical Engineering The University of Hong Kong
More informationBetter Air Dispersion for. Underfloor. Plenums
Better Air Dispersion for Underfloor Plenums Uniform Air Mixing for UFAD Plenums Inlet Connection Zippered inlet collar secures to metal using DuctBelt and Anchor UFAD Technology UnderFloorSox (UFSoxTM)
More informationModular Active. Chilled. Beams
Modular Active Chilled Beams How Twa MAC Beams Work Primary air (100% outside air) is dehumidified to between 50-57 F dew point and is used to: control the latent requirements of the space, provide fresh
More informationBALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT
BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT Ashak Nathwani AM Adjunct Senior Lecturer ashak.nathwani@sydney.edu.au PRESENTATION THREE SESSIONS This presentation will be in three parts addressing
More informationTopic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline
ME 414/514 HVAC Systems Overview Equipment Outline 2-1 The Complete System 2-2 The Air-Conditioning and Distribution System 2-3 Mechanical Equipment Air-handling Equipment Heating Equipment Boilers Furnaces
More informationUnderfloor Air Systems. How It s Different: Overhead vs. Underfloor Air Systems
Underfloor Air Fresher Design Developers, building owners and architects face a complex challenge: build buildings that are not only pleasing aesthetically, but also are efficient, flexible and smart.
More informationUNDERFLOOR PRODUCTS E3
UNDERFLOOR PRODUCTS E3 Introduction Introduction Changes in office space usage, sustainable design, and indoor air quality issues have sparked considerable interest in the application of supplying conditioned
More informationCHAPTER IV AIR DISTRIBUTION AND BALANCE
CHAPTER IV AIR DISTRIBUTION AND BALANCE 4.1. INTRODUCTION When projecting an air-conditioning system, the following steps should be followed: 1) Determine the heat gain or loss 2) Establish the air requirements
More informationSenior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1
Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9
More informationSingle Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return
Single Zone System One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return Multi Zone System Used in small to medium sized buildings
More informationHVAC OUTDOOR AIR VENTILATION STANDARD. ASHRAE Standard ASHRAE Standard
ASHRAE Standard 62.1-2013 BuildingsOne February 4, 2016 Landlord s HVAC system design capacity shall equal or exceed outdoor air ventilation requirements specified in ASHRAE Standard 62.1-2013 (prospect
More informationPRODUCTS TAO TAO PRODUCT: ADVANCING THE SCIENCE OF AIR DISTRIBUTION. temperature ambient optimizer. Redefine your comfort zone.
A I R D I S T R I B U T I O N PRODUCTS PRODUCT: TAO TAO temperature ambient optimizer F O C U S 04 ADVANCING THE SCIENCE OF AIR DISTRIBUTION Redefine your comfort zone. www.titus-hvac.com Rethink what
More informationmaximize displacement ventilation Opportunities
maximize displacement ventilation Opportunities DESIGN STRATEGIES In Seattle, the Amazon Headquarters building, features an open air atrium that provides natural ventilation throughout the facility. DESIGN
More informationComfort and health-indoor air quality
Comfort and health-indoor air quality 1 The human body has a complicated regulating system to maintain the human body temperature constant most of the time, which is 98.6 F (36.9 C) regardless of the environmental
More informationIDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions
IDL20e (2 way discharge) IDS60e ( way discharge) Frequently Asked Questions UDI (vertical discharge) Inffusers INFFUSER FREQUENTLY ASKED QUESTIONS The following are frequently asked questions (FAQ s) on
More informationA REASONABLE ALTERNATIVE TO CHILLED BEAMS Dan Int-Hout Chief Engineer
Page: 1 of 6 A REASONABLE ALTERNATIVE TO CHILLED BEAMS Dan Int-Hout Chief Engineer The DOAS Fan Powered Terminal Unit Page: 2 of 6 ASHRAE is advocating that energy use in buildings be reduced 30% below
More informationMechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation
Mechanical Technical Report 1 Standard 62.1 Ventilation Compliance Evaluation Lutheran Theological Seminary at Philadelphia The New Learning Center Prepared For: William P. Bahnfleth, Ph.D., P.E. Department
More informationAPPLICATION GUIDE BEAMS
BEAMS There is an increasing need for energy efficient air conditioning systems as energy codes become more stringent. Chilled beam systems are one such alternate to traditional all air conditioning systems.
More informationCHAPTER 4 VENTILATION AIR SUPPLY
CHAPTER 4 VENTILATION AIR SUPPLY 401.0 General. This chapter contains requirements for ventilation air supply and exhaust, evaporative cooling systems and makeup-air requirements for direct-gas-fired heaters,
More informationENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory
Overview of Chilled Beam Technology Purpose Chilled beam technology is new to the United States but has been used in Europe since the 1950 s. Chilled beams can reduce energy costs, improve indoor air quality,
More informationEarthWise System Seminar
EarthWise System Seminar Tim Gasper, P.E. Solutions Engineer Brady-Trane Services, Inc. EarthWise Systems? Energy Efficiency Emissions Buildings use 39% of the Primary Energy Consumed in the United States
More informationUnderfloor Air Conditioning in North America David Arnold Troup Bywaters + Anders/ Director and Regional Chair ASHRAE Region at Large
CIBSE/ASHRAE Group Meeting 08 December 2004 Underfloor Air Conditioning in North America David Arnold Troup Bywaters + Anders/ Director and Regional Chair ASHRAE Region at Large UFAC/UFAD in North America
More informationUNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationDISPLACEMENT VENTILATION AND STATIC COOLING DEVICES
Code of Practice COP 17/99 DISPLACEMENT VENTILATION AND STATIC COOLING DEVICES Tariq Abbas Code of Practice COP17/99 DISPLACEMENT VENTILATION AND STATIC COOLING DEVICES Tariq Abbas The Building Services
More informationDESIGNING MODULAR VAV SYSTEMS
FORM 5.2 REV 0905 THERMA-FUSER THERMALLY POWERED VAV DIFFUSER DESIGNING MODULAR VAV SYSTEMS MODULAR VAV SYSTEMS The Therma-Fuser diffuser is a simple stand alone device that provides VAV control when supplied
More informationTechnical Report Three
Technical Report Three Existing Conditions for Mechanical Systems Contents Executive Summary...2 Building Overview...2 Mechanical Systems Overview...2 Mechanical System...3 Outdoor & Indoor Design Conditions...3
More informationLIGHTING CONTROLS
260923 LIGHTING CONTROLS PART 1: GENERAL 1.01 SUMMARY COMMENTS A. CU has developed this lighting control guideline to direct design professionals toward standard solutions that meet the University s performance
More information80-6-ISD A Better Solution for Proper Space Air Distribution
Air Handling Systems Engineering & Technical Bulletin 80-6-ISD A Better Solution for Proper Space Air Distribution In designing an HVAC system, an engineer has the following goals: 1. True building load
More informationActive & Passive Beams
Active & Passive Beams www.price-hvac.com Active & Passive Beams Introduction Beam systems are an alternative to traditional all-air conditioning systems. Beams use water to move energy through a building
More informationTechnical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer
Technical Development Program PRESENTED BY: COMMERCIAL HVAC SYSTEMS Water Source Heat Pump Systems Ray Chow Sales Engineer TDP Updates Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 23 0594 - TESTING, ADJUSTING, AND BALANCING (TAB) PART 1 - GENERAL 1.1 SUMMARY A. This Section includes testing, adjusting and balancing HVAC systems to provide design conditions as indicated by
More informationAir Conditioning Clinic
Air Conditioning Clinic VAV Systems One of the Systems Series July 2012 TRG-TRC014-EN VAV Systems One of the Systems Series A publication of Trane Preface VAV Systems A Trane Air Conditioning Clinic Figure
More informationREPORT OF THE UMC VENTILATION TASK GROUP
REPORT OF THE UMC VENTILATION TASK GROUP THE TASK GROUP PROPOSES TO REVISE CHAPTER 4, VENTILATION AIR SUPPLY OF THE UMC AS FOLLOWS: 401.0 General. This chapter contains requirements for ventilation air
More informationCOMcheck Software Version Mechanical Compliance Certificate
COMcheck Software Version 3.8.2 Mechanical Compliance Certificate 90.1 (2007) Standard Section 1: Project Information Project Type: New Construction Project Title : Rudy's Star Motors Construction Site:
More informationDehumidifying with Dedicated Outdoor Air
Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,
More informationResidential ventilation concepts based on the idea of displacement airflow distribution
A strategy for reducing energy demand Student: Aris Gkitzias (I.D:4180380) Mentors: Dr. Regina Bokel, Ir. John van der Vliet MSc graduation project Department of Building Technology, faculty of architecture
More informationFan Laws. Keith Miller. Samuel Tepp Associates. Paul Cenci, P. E.-Principal Brian England-Principal. Samuel Tepp Associates 1/6/10
Fan Laws Keith Miller Samuel Tepp Associates Paul Cenci, P. E.-Principal Brian England-Principal Basic Terms CFM - Cubic Feet per Minute, volume (amount) of air being moved SP - Static Pressure, resistance
More informationHAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001
This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.
More informationNEW AR-L AR-C AND HIGH-CAPACITY LINEAR COOLING PANELS. Higher energy efficiency. Increased thermal comfort
NEW AR-C AND HIGH-CAPACITY LINEAR COOLING PANELS Higher energy efficiency Increased thermal comfort Higher capacity than standard radiant ceilings Significant space savings Reduced new construction costs
More informationSECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationQuestions??????? Thank you
Questions??????? Thank you Sustainable Design Products and Systems Dan Hahne/Eric Dowell ASP Sustainable Designs Overview Price and Uponor Hydronic Heating and Cooling Price Displacement Ventilation Price
More informationDo All DOAS Configurations Provide the Same Benefits?
TECHNIL FTURE This article was published in ASHE Journal, July 2014. Copyright 2014 ASHE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without
More informationCity of Duluth Festival Center 04/25
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationThe new ASHRAE-REHVA Active and Passive Beam Application Design Guide
Swegon Air Academy Seminar. Tallinn. 2015 December 3 The new ASHRAE-REHVA Active and Passive Beam Application Design Guide Carlos Lisboa carlos.lisboa@blcnavitas.pt Office +351 214 415 546 Cell +351 919
More informationCHAPTER 4. HVAC DELIVERY SYSTEMS
CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer
More informationMaking UFAD Systems Work BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE
his article was published in ASHRAE Journal, March 2016. Copyright 2016 ASHRAE. Posted at www.ashrae.org. his article may not be copied and/or distributed electronically or in paper form without permission
More informationGARCIA GALUSKA DESOUSA Consulting Engineers
L#57295/Page 1/July 21, 2017 HVAC SYSTEMS NARRATIVE REPORT The following is the HVAC system narrative, which defines the scope of work and capacities of the HVAC system as well as the Basis of Design.
More information1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT
Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story
More informationTLW Therma-Fuser Linear Sidewall Thermally Powered VAV Diffuser
TLW Therma-Fuser Linear Sidewall Thermally Powered VAV Diffuser Therma-Fuser Systems Models: TLW-C VAV cooling only TLW-CW VAV cooling with constant volume warm up TLW-D Manually adjustable blades TLW-RAD
More informationRAMAPO COLLEGE OF NEW JERSEY CCA0803 PHASE II HOUSING REHABILITATION 2012
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationMold/Moisture Control Case Study
Mold/Moisture Control Case Study Presented by Boggarm S. Setty, P.E., FASHRAE Setty & Associates, Ltd. www.clima2005.ch Clima 2005 Lausanne Solothurnstrasse 13 CH-3322 Schönbühl Switzerland th 8 REHVA
More informationPDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 PDH & Professional Training PDH Storm, by Engineers Edge, LLC CONTENTS 1. INTRODUCTION 1.1 GENERAL CRITERIA 1.2 DESIGN PROCEDURE
More informationENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY
SUPERIOR IAQ LOW FIRST COST BEST ROI ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY Pinnacle manages 100% of a building s ventilation and indoor humidity load in a single package. Chilled beams have
More informationAppendix 13. Categories of Cooling and Heating systems
EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01
More informationThe Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *
Journal of Environmental Protection, 2013, 4, 638-646 http://dx.doi.org/10.4236/jep.2013.46073 Published Online June 2013 (http://www.scirp.org/journal/jep) The Research of Performance Comparison of Displacement
More informationAIRSIDE COMPONENTS AND SYSTEMS
Ventilation: Outdoor air (OA) ventilation shall be introduced into each occupied building space in compliance with ASHRAE Standard 62. Adequate additional OA capability is needed to keep buildings under
More informationChristopher Kelly Technical Report Three
Christopher Kelly Technical Report Three Mechanical Systems and Existing Conditions Evaluation SALK HALL ADDITION The University of Pittsburgh, Pittsburgh Christopher Kelly, Mechanical Option Professor
More informationADRIATIC VF. Active chilled beam with cooling, heating and ventilation QUICK FACTS
Active chilled beam with cooling, heating and ventilation QUICK FACTS The ADRIATIC VF is a chilled beam with integrated recirculated air opening in the face plate. Air is discharged into the room along
More informationTrane Engineers Newsletter Live
Trane Engineers Newsletter Live Presenters: John Murphy, Eric Sturm and Jeanne Harshaw (host) Trane program number: APP-CMC061-EN Agenda Trane Engineers Newsletter Live Series Abstract A large number of
More informationMechanical System Redesign. Dedicated Outdoor Air System. Design Criteria
Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed
More informationSECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...
SECTION 230001 TABLE OF CONTENTS SECTION 230001 PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS... 1 1.00 FILED SUB BID... 1 1.01 PROJECT OVERVIEW... 2 1.02 DESIGN CRITERIA... 4 1.03 CODE ISSUES...
More informationLEED for Homes Points
LEED for Homes Points This document is a guideline of the maximum potential points American ALDES ventilation products can contribute to obtaining certification under the US Green Building Council s (USGBC)
More informationMultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications RESNET Conference Atlanta, GA
MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications 2014 RESNET Conference Atlanta, GA Ray Ivy and Mike Barcik Southface 1 About Southface 2 Topics Covered How to use
More informationIndoor Pool Design Considerations Colorado Springs, Colorado
Indoor Pool Design Considerations Colorado Springs, Colorado September 20, 2018 Presentation by Eric S. Johnson, P.E. LifeMember, ASHRAE, Austin Chapter DESIGN CONSIDERATIONS HUMIDITY CONTROL FOR INDOOR
More informationphoto by PFC Price Fan Column
photo by www.mrobinsonphoto.com PFC Price Fan Column Typical Applications The Price Fan Column (PFC) is a vertical fan unit designed to discharge into a raised access floor plenum. The unit s compact design
More informationTemp Change After Destratification between 12" below ceiling and 4" AFF
Optimizing Winter Heating: Is reversing the direction of your ceiling fan the best way to achieve thermal destratification? Discussion Effectiveness versus Draft Risk Sonya Milonova Research Fellow, Harvard
More informationTechnical Assignment 3 11/15/04. Executive Summary
Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria
More informationScholar III Unit Ventilator
Scholar III Unit Ventilator 800 to 2000 CFM Models SVI 1000-2000 General Description The Scholar III unit ventilator is designed to provide comfortable, quiet and efficient heating and cooling for school
More informationProblems Air and Water Distribution Systems
Problems Air and Water Distribution Systems ME419 D. Abata 1. Cooled air at 1 atm, 50 F, and 10% relative humidity is transported in a 600 ft long circular sheet metal duct at a rate of 800 cfm. If the
More informationC o o l i n g a n d h e a t i n g s y s t e m s
2 C o o l i n g a n d h e a t i n g s y s t e m s Cooling ceiling system description Preliminary remarks Cooling ceilings Cooling ceilings are room cooling systems for placement in the ceiling zone. Their
More informationAir Movement for Energy-Efficient Comfort in Conditioned Spaces
Air Movement for Energy-Efficient Comfort in Conditioned Spaces ASHRAE Standard 55-2010: Thermal Comfort Specify the combination of indoor thermal environmental factors and personal factors that will produce
More informationD-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency
Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)
More informationRadiant Heating & Cooling for Commercial Buildings
Radiant Heating & Cooling for Commercial Buildings Kaveesh Padiachy, PEng, PMP, LEED AP Business Development Manager Central Canada kaveesh.padiachy@uponor.com www.uponorpro.com/engineering Radiant Heating
More informationIRRAD - PHASE II RADIANT COOLING - DESIGNING FOR FLEXIBLE PARTITION OF SPACE
IRRAD - PHASE II RADIANT COOLING - DESIGNING FOR FLEXIBLE PARTITION OF SPACE Cooling System RADIANT COOLING PIPING LAYOUT Proposal for the REHAU core temperature control (CCTC) pipe size: RAUTHERM S 20x2,0mm
More informationTechnical Assignment 1
0 Technical Assignment 1 ASHRAE Standard 62.1 Ventilation and Standard 90.1 Energy Design Evaluations Compliance Analysis David H. Koch Institute for Integrative Cancer Research Massachusetts Institute
More informationIAQ Building Education and Assessment Model (I-BEAM)
Heating, Ventilation, and Airconditioning (HVAC) Text Modules IBEAM IAQ in L... http://www.epa.gov/iaq/largebldgs/ibeam/text/hvac.html Page 1 of 6 10/21/08 IAQ in Large Buildings http://www.epa.gov/iaq/largebldgs/ibeam/text/hvac.html
More informationHVAC 101. The Basics of Heating, Ventilation and Air Conditioning
HVAC 101 The Basics of Heating, Ventilation and Air Conditioning HVAC Heating, Ventilation and Air Conditioning Provides comfort for people Allows humans to exist under adverse conditions. Comfort Comfort
More informationAugust 15, 2013 Page 1 of 19
Section C401 Application Compliance with C402, C403, C404 and C405 AND (either C406.2, C406.3 or C406.4) Compliance with C402, C403, C404 or C405 Section C402 Building Envelope (Climate Zone 5A) Space-Conditioning
More informationChilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle
Chilled Beam and Radiant Cooling Basics Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle nsearle@dadanco.com Contents Radiant Ceilings & Chilled Beam Basics Energy & Space Savings First and
More informationVH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control
VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Unit with Enhanced Humidity Control Motorized Bypass Damper Temperature and Humidity Controller Reheat Control Elastomeric Foam Insulation High Efficiency,
More informationInvestigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings
Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Melanie T. Fauchoux, PhD Student University of Saskatchewan http://www.engr.usask.ca/dept/mee melanie.fauchoux@usask.ca
More informationSECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC
SECTION 23 05 93 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph
More informationCOMMERCIAL HVAC EQUIPMENT Indoor Self-Contained Units
COMMERCIAL HVAC EQUIPMENT Indoor Self-Contained Units Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection
More informationHVAC DISTRIBUTION and DELIVERY SYSTEMS
HVAC DISTRIBUTION and DELIVERY SYSTEMS (Part 1) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 REMINDER HVAC = Heating, Ventilating, Air-Conditioning The AC part of HVAC implies a system that
More informationTrane Performance Climate Changer Air Handlers. An air handler for every need.
Trane Performance Climate Changer Air Handlers An air handler for every need. Trane Performance Climate Changer air handlers: designed to optimize your HVAC system. Trane Performance Climate Changer air
More information