Denotes a new question! Denotes a revised/revisited question. September 2009 General:

Size: px
Start display at page:

Download "Denotes a new question! Denotes a revised/revisited question. September 2009 General:"

Transcription

1 General: 1) (Q) What does a contractor/permit holder have to supply for an inspection? (A) Section of the NC Administrative Code states that it is the duty of the permit holder to provide access to and means for inspection of the work for any inspections that are required by this code. 2) (Q) The Mecklenburg County inspection department preaches strongly about how hard it works to combat inconsistency in inspections and interpretations. When are you going to be consistent with other counties? (A) Mecklenburg County Code Enforcement prides itself on achieving a high level of consistency within the confines of Mecklenburg County. We however do not have authority over other counties or the decisions they render. We make interpretation recommendations and/or requests to the NC Department of Insurance from time to time and will continue to do so in and effort to provide consistent code enforcement within Mecklenburg County. 3) (Q) Where are shower pans required? (A) They are required on all showers with the exception of rinse showers at swimming pools or beaches. Shower pans shall meet the requirements list in section of the NC Plumbing Code. 4) (Q) Are FROET roof drains permitted to be used in limiting the roof penetrations on commercial roof drainage systems? (A) Yes, provided that the designer uses the dual outlet type and the separation of primary and secondary systems is maintained. The primary system shall be sized per the more restrictive secondary rate. 5) (Q) Does designated accessible hotel suites have to make the non code required convenience shower, accessible? (A) No, section of the NC Accessibility Code states tub OR shower, not both. 6) (Q) Does the Code allow the use of paint or spray materials for a shower pan liner? (A) No! Section allows the use of PVC sheet, CPE sheet, sheet lead, sheet copper and preformed ABS. 7) (Q) May plumbing piping be routed within a 2 hour exit enclosure shaft? (A) No. 1 st

2 General continued: 8) (Q) What is the definition of Core plumbing facilities? (A) These are restrooms centrally located directly off of an accessible corridor with the quantity sized for the square footage of the floor area it serves (one to two floors max.), taking into consideration all of the occupancy types. 9) (Q) Is there an alternative for the rainfall charts listed in chapter 11 of the NC Plumbing Code? (A) Yes. Section allows for rainfall rates determined from local weather data. Mecklenburg County has a chart developed from data gathered from Mecklenburg County Storm Water Services. Designers may use the chart provided they clearly identify its use on the submitted plans. A copy of the chart may be obtained from the plan submittal department. 10) (Q) When measurements differ between the approved set of plans and the NC Accessibility Code, which takes president? (A) The NC Accessibility Code. (ANSI A117 starting Jan 1, 2010) 11) (Q) Does the Accessibility Code require the handle of a urinal to be placed on the open side? (A) No! 12) (Q) Do locked faculty restrooms in schools require the lavatories to have metering faucets? (Q) Yes, all assembly occupancies. 13) (Q) Do small kiddy lavatories have to meet the accessibility code, including wrapping of the trap? (A) Yes 14) (Q) Do school class service sinks require trap wraps? (A) Yes, if designated accessible. 15 (Q) What is the definition of plumbing minor repair? (A) Minor repair is difficult to clearly define and is somewhat base on the specific situation. The State Board of Examiners of Plumbing, Heating and Fire Sprinkler Contractors defines minor repair: d) Any connection, repair, or alteration which requires interruption of the potable water supply and if poorly performed creates substantial risk of contamination of the potable water supply is not a minor repair, replacement or alteration. (e) Any connection, repair or alteration which if poorly performed creates substantial risk of fire or exposure to carbon monoxide, open sewage or other gases is not a minor repair, replacement or alteration. (Excerpt from GS 87-21c section.05.6)

3 General continued: 16) (Q) What should be done to a discarded plumbing system when a building is demolished? (A) The sewer line/s should be permitted first, cut, capped and inspected to prevent demolition debris from entering the sewer line and fouling the city main. 17) (Q) What should be done to a discarded plumbing system when one or more leased upfit spaces are demolished within a multi tenant building? (A) A licensed plumbing contractor should obtain a permit, remove and cap water lines, drainage and vent lines while assuring that vent systems serving adjoining unit/s remain uninterrupted and there will be no discharge of methane gas into a leased space. Call for inspection! 18) (Q) What is HB 1409? (A) House Bill 1409 is legislation that recently passed which exempts a one and two family homeowner from required permits when replacing electrical appliances, switches, receptacles or a water heater (gas or electric) provided that there is no change in location, voltage, capacity or amperage. The work is required to be performed by someone licensed on GS and/or GS

4 Equipment: 1) (Q) Does a ejector pump tank, installed for the future, require the contents (fluids) to be pumped prior to the final inspection? (A) The pumping of the tank would be advisable, but it would be the contractor s discretion. However, the unused openings (vent, etc.) need to be capped until they are used. 2) (Q) Does a residential fire sprinkler system require backflow devices? (A) If the fire sprinkler system is separate from the plumbing distribution system, then yes, a double check assembly would be required. 3) (Q) What size/type water heater requires a safety pan? (A) Section does not exempt any type or size water heater or tank from the requirement of safety pans. 4) (Q) What type of backflow protection is required on restaurant type beverage dispensers? (A) Beverage dispensers shall be protected by an air gap or a backflow device meeting the requirements of ASSE 1022 or CSA B Devices meeting these requirements are double check design, usually stainless steel. 5) (Q) May two water heaters piped together be placed in an alcove, one in front of the other? (A) Yes, provided that both equipment s controls are fully accessible for service or replacement without removing the other water heater. 6) (Q) May a plastic pan designed for use with a tankless water heater be used in an attic space? (A) Yes, provided that the equipment s distance to combustibles is maintained. 7) (Q) May a contractor use Armorflex insulation to to insulate the water lines feeding a gas fired water heater installed in an unconditioned space? (A) Armorflex with an R value of 6.5 may be used to insulate the pipe until it encroaches on the combustible clearance space so designated by the equipment manufacturer. 8) (Q) May a disappearing stairwell encroach on the required service space for a water heater installed in an attic? (A) No. 9) (Q) Does a building whose water service is connected through a backflow device, have to install an expansion device if the water heater used is of the instantaneous type? (A) No. There would be no thermal expansion. 1 st

5 Equipment continued: 10) (Q) Are connections for other fixtures or equipment allowed between a water heater and its water service valve? (A) No! 11) (Q) Can you use a ¾ X1 pex adapter and a 1 pex pipe to install a t&p discharge drain? (A) The ones we have check did not seem to restrict the inside diameter and would be approved. However not all fittings are the same and there may be those that would not work. 12) (Q) Would standing on a set of steps serve as the required access to a water heater installed in an attic space? (A) No 13) (Q) When are thermal expansion devices required? (A) These devices are required on distribution systems containing a water heater and a backflow or check valve that would prohibit the expanding water from backing up into the main OR if the water main pressure exceeds the pressure rating of the T&P valve.

6 Fixtures: 1) (Q) What are the procedures for calculating the minimum number of plumbing facilities? (A) A brief explanation: (Step 1) Divide the upfit space into its various uses using the NC Building Code (i.e., assembly, business, storage, etc.) (Step2) Using the particular use, the associated square footage and the Building Code, obtain the number of people required for your egress calculation. Continue until all spaces/uses are calculated. (Step 3) Take these egress figures, divide by 2 to get a 50/50 split between male and female and enter table (NC Plumbing Code) one sex at a time. Do the math. Take the total/s, from the various uses and add them together for each fixture s grand total. Round up. This will be the fixtures TOTAL for the upfit. Repeat for each fixture for both male and female. This procedure is adequate for most occupancy uses but some types of occupancies may require additional, more detailed analysis. 2) (Q) May the 67% rule (section 419.2) for converting water closets to urinals be applied to the total male fixture count when there multiple restrooms? (A) No. The 67% rule is applied to each and every toilet room. 3) (Q) What water distribution protection is required for a baptismal pool? (A)The distribution system may be protected by an air gap, an atmospheric device or a double check assembly.

7 Interceptors & Special Waste: 1) (Q) Do car washes have to provide approved interceptors in the process loop of recycled wash water? (A) Designers wishing to clean recycled water (i.e., car washes, steaming stations, pressure washing) with systems like the Cyclonator, do not have to be on the approved interceptor list. The Code does not apply to process piping, only discharges to the sanitary sewer system. 2) (Q) May clear water waste such as a hand sink be installed on a greasy waste line? (A) The intent of the Code is to separate the waste however, if the designer would rather incorporate the additional load on the interceptor instead of adding a separate clear waste line, that would be acceptable. 3) (Q) Do residential style washing machines used in occupancies such as a doctor s office, hair salons, or day cares, have to discharge through a commercial lint interceptor? (A) Occupancies that use commercial tumble machines or coin operated machines would be better defined as a commercial laundry operation and would require a lint interceptor. Occupancies that utilize a residential style washing machine with intermittent use would NOT be defined as a commercial laundry operation and the filtering designed into the machine would be sufficient.

8 Drainage: 1) (Q) What are the stipulations, if any, on the replacement of drainage piping on fire damaged structures? (A) The damaged piping may be replaced with piping materials and methods used at the time the structure was built. The only difference would be penetrations through rated assemblies. These penetrations are considered life safety and would have to meet the Code. 2) (Q) Is a drain required at a swimming pool rinse shower? (A) A drain is not required unless the designer changes the scope of the rinse shower to a shower for washing by the addition of hot water. 3) (Q) What is the meaning of exception 5 of of the NC Plumbing Code? (A) The exceptions are other acceptable ways to meet the requirements for a C/O at the upstream end of a drain line. Exception 5 would allow a horizontally run line catching a fixture such as a shower, to locate the C/O for that line on the fixtures vent as long as it is above the fixtures flood rim. 4) (Q) Do we require a roof over a can wash located outside? (A) No. 5) (Q) Does the plumbing code allow slopes less than 1/8 per foot? (A) Yes the Code supports 1/16 per foot on 8 and larger lines. NCDENR allows 1/16 on the large lines including 6 lines. We will allow, as an alternative method, the uses of 1/16 per foot on 6 and larger lines provided the engineer provides a sealed letter stating the design load and slope will maintain a minimum 2 fps flow rate. 6) (Q) When can Fernco fittings be used? (A) Section allows the use fo connectors and adapters consisting of elastomeric sleeve and stainless steel clamps when joining dissimilar materials. The use of directional fittings (tee or wye) is prohibited. The adapter coupling may be used above or below grade. 7) (Q) May a contractor install a floor drain in a residential single family garage with a sloped floor for the purposes of collecting run off from a parked vehicle and direct that to a dry well or discharge above grade? (A) Water Quality does not want drains which could convey oil contaminants to the earth or water ways (streams). Drains in a garage should therefore be connected to a sanitary sewer connection. 1 st

9 Drainage continued: 8) 9) (Q) What is the minimum depth for the pump discharge line on a whole house sewage ejector? (A) 12 (Q) Exactly where does a condensate drain have to be located? (A) It should be as close as possible to the appliance it serves but accessible for priming. There may be other limitations depending on where you choose to locate the drain. 10) (Q) What are the limitations on the use of a 4X3 closet bend? (A) A 4X3 closet bend may be used directly below the closet flange. There shall be no tee fittings between the flange and the bend.

10 Venting: 1) (Q) Does the Code allow the use of a combination instead of a sanitary tee in a waste stack catching a lavatory or sink? (A) Table would suggest that a combination may be used in any position in the direction of flow. However, section stipulates that a fixture branch may not exceed it s hydraulic gradient and therefore would prohibit the use a combination in this situation. 2) (Q) Does the Code still require that water closets back to back be installed with a double combination? (A) The 2006 Code required the use of a double combination on back to back water closets. The restriction was removed in the 2009 NC Plumbing Code. 3) (Q) In the drawing (2) of the 2006 NC Plumbing Code Commentary a floor drain (no trap) is discharging above the trap seal of a second floor drain. Is this installation legal? (A) This installation may be used with receptors receiving condensate and clear water drips and is approved on a case by case basis. When allowed, the maximum distance shall not exceed 25. 4) (Q) There seems to be some discrepancy with the enforcement and understanding of section of the NC Plumbing Code (2009). When will the code as written be enforced? (A) We will additional in house training to get Plan Review and Field up to speed. Permits issued after Sept 1, 2009 should be in compliance.

11 Venting continued: 5) (Q) Will the 2009 NC Plumbing Code allow the use of AAV s in acid waste systems? (A) Section prohibits installation of AAV s in nonneutralized special waste systems (acid) or supply or return air plenums. 6) (Q) Does the 2009 NC Plumbing Code require floors without plumbing (i.e. parking decks, etc.) when calculation relief vents? (A) No. 7) (Q) May AAV s be placed outside the building? (A) They must be installed per manufacturer s instructions. Two of the ones I checked have maximum cold weather limitation of - 40 degrees. PVC should not be installed in direct sun light. 8) (Q) May you install a single branch with two traps (fixtures) on a vertical combination waste and vent system? (A) Vertical combination waste and vent systems are designed to have each trap connect individually to the vertical stack. A branch with more than on fixture trap would have to be conventionally vented and the load would be accounted for in the stacks total.

12 Water Distribution: 1) (Q) May a contractor use CPVC water distribution piping in HVAC return air plenums? (A) Plastic water piping may be used in return air plenums provide it meets the requirements of section of the NC Mechanical Code which requires that material located in a return plenum have a developed flame/smoke index of 25/50 or less (in accordance with ASTM E84). Not all CPVC products will have the required index rating. 2) (Q) Does a CPVC hot water loop have to be insulated? (A) Yes (per 2009 NC Energy Code). The hot water loop (not the run outs) must be insulated with 1 insulation having a btu transfer rate not exceeding 0.27 per foot. 3) (Q) Do shower valve replacements require permitting and inspections? (A) Yes

Land Use and Environmental Service Agency (Code Enforcement) Plumbing 2010

Land Use and Environmental Service Agency (Code Enforcement) Plumbing 2010 General: 1) (Q) Who enforces the cutting and notching requirements found in the plumbing code? (A) The plumbing inspector would question the contractor initially. A building inspector would either take

More information

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2009

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2009 General: 1) (Q) What does a contractor/permit holder have to supply for an inspection? (A) Section 107.2 of the NC Administrative Code states that it is the duty of the permit holder to provide access

More information

Chapter 4: Fixtures, Faucets & Fittings:

Chapter 4: Fixtures, Faucets & Fittings: Table of Contents Chapter 1 Administration 0 Chapter 2 Definitions 0 Chapter 3 General Regulations 0 Chapter 4 Fixtures, Fau & Fit. 12 Chapter 5 Water Heaters 14 Chapter 6 Water Supply & Dist. 10 Chapter

More information

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2009

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2009 General: 1) (Q) What does a contractor/permit holder have to supply for an inspection? (A) Section 107.2 of the NC Administrative Code states that it is the duty of the permit holder to provide access

More information

2016 Plumbing Supplemental Plan Review List

2016 Plumbing Supplemental Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Plumbing Supplemental Plan Review List POTABLE WATER SYSTEM P1. Specify which fixtures are for private use and which are for

More information

Level I Chapter 1 Worksheet

Level I Chapter 1 Worksheet Chapter 1 Worksheet 1. For applicability requirements of the Plumbing Code, refer to: a. Building Code b. Administration and Enforcement Code c. Plumbing Code d. Residential Code 2. The provisions of the

More information

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Ohio Administrative Code Rule Number OPC Section IPC origin Reason for proposed 4101:3-2-01 Alternate on-site 2015 Added definition

More information

ICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

ICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. ICP Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A 1 inch diameter faucet, where the inside edge of the spout opening is 2.5 inches away

More information

Read Only Document Not For Distribution

Read Only Document Not For Distribution Chapter 9 Indirect Waste Piping and Special Wastes 9.1 INDIRECT WASTES 9.1.1 General Drains from fixtures, fixture compartments, equipment, appliances, appurtenances, and other devices requiring protection

More information

MATERIALS Traps TRAPS. No. IPC IRC Description

MATERIALS Traps TRAPS. No. IPC IRC Description MATERIALS Traps TRAPS MAX " MAX 0" No. IPC IRC Description 00. P0.6 00. P0.6 00. P0. 00. () P0.6 Exc. Vertical distance from fixture to the trap weir can not exceed ". Horizontal distance from the fixture

More information

STACKS AND STACK VENTS

STACKS AND STACK VENTS CHAPTER 9 VENTS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of vent systems. 901.2 Trap seal protection. The plumbing

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

1 Exam Prep Plumber s Handbook Tabs and Highlights

1 Exam Prep Plumber s Handbook Tabs and Highlights 1 Exam Prep Plumber s Handbook Tabs and Highlights These 1 Exam Prep Tabs are based on the Plumber s Handbook Revised 2006. Each Tabs sheet has five rows of tabs. Start with the first tab at the first

More information

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. IPC Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A vent stack handling 25 dfu s with a developed length of 35 feet shall be inches minimum

More information

PLUMBING REQUIREMENTS

PLUMBING REQUIREMENTS PLUMBING REQUIREMENTS This handout is a compilation of the standard requirements based on the State Plumbing Code and City Ordinance for projects of this type. This information sheet does not contain all

More information

Special Requirements For Health Care Facilities

Special Requirements For Health Care Facilities Chapter 14 Special Requirements For Health Care Facilities 14.1 GENERAL This Chapter applies to special fixtures and systems that occur in health care facilities and to the special plumbing requirements

More information

CHAPTER 9 VENTS SECTION

CHAPTER 9 VENTS SECTION CHAPTER 9 VENTS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of vent systems. 901.2 Trap seal protection. The plumbing

More information

Chapter 3 General Regulations:

Chapter 3 General Regulations: Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Water Heaters Chapter 7 Sanitary Drainage Chapter 9 Vents Chapter 11 Storm Drainage POLICY Table of Contents Chapter 2 Definitions Chapter

More information

Sanitary Drainage Systems

Sanitary Drainage Systems 11.1 MATERIALS See Section 3.1. Sanitary Drainage Systems 11.2 BUILDING SEWERS AND BUILDING DRAINS 11.2.1 Sewer or Drain in Filled Ground Chapter 11 Building sewers or building drains that are installed

More information

TABLE OF CONTENTS. Part I Administrative... 1

TABLE OF CONTENTS. Part I Administrative... 1 Part I Administrative............................ 1 CHAPTER 1 ADMINISTRATION............... 1 R101 Title, Scope and Purpose.................... 1 R102 Applicability.............................. 1 R103

More information

CHAPTER 9 VENTS. run undiminished in size and as directly as possible from the building drain through to the open air above the roof.

CHAPTER 9 VENTS. run undiminished in size and as directly as possible from the building drain through to the open air above the roof. CHAPTER 9 VENTS SECTION 90 GENERAL run undiminished in size and as directly as possible from the building drain through to the open air above the roof. 90. Scope. The provisions of this chapter shall govern

More information

PLUMBING INSTALLATIONS

PLUMBING INSTALLATIONS PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT PLUMBING INSTALLATIONS A homeowner guide to plumbing requirements for single-family dwellings November 2017 contents Permit Requirements... 3 Inspection Requirements...

More information

INSPECTION OF COMMERCIAL KITCHEN PLUMBING

INSPECTION OF COMMERCIAL KITCHEN PLUMBING INSPECTION OF COMMERCIAL KITCHEN PLUMBING 801.1 SCOPE Food-handling establishments 2 - by John Williams, Jr. Plumbing Control Supervisor Onondaga County Water Environment Protection Commercial Kitchens

More information

CHAPTER 5 Water, Plumbing, and Waste

CHAPTER 5 Water, Plumbing, and Waste CHAPTER 5 Water, Plumbing, and Waste Parts 5-1 Water 5-2 Plumbing System 5-3 Mobile Water Tank 5-4 Sewage, Other Liquid Waste, and Rainwater 5-5 Refuse, Recyclables, and Returnables 5-1 Water 5-101 Source

More information

PLUMBING FIXTURES CHAPTER 27

PLUMBING FIXTURES CHAPTER 27 CHAPTER 27 PLUMBING FIXTURES SECTION P2701 FIXTURES, FAUCETS AND FIXTURE FITTINGS P2701.1 Quality of fixtures. Plumbing fixtures, faucets and fixture fittings shall be constructed of approved materials,

More information

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. IPC Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. The minimum air gap for a fixture with an effective open of 1/2", located away from a

More information

Read Only Document Not For Distribution

Read Only Document Not For Distribution Chapter 14 Special Requirements For Health Care Facilities 14.1 GENERAL This Chapter applies to special fixtures and systems that occur in health care facilities and to the special plumbing requirements

More information

PLAN REVIEW SUBMITTAL GUIDE

PLAN REVIEW SUBMITTAL GUIDE PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide

More information

TABLE OF CONTENTS Limitations of Authority...6 Table Swimming Pool, Spa, and Hot Tub Permit Fees...7

TABLE OF CONTENTS Limitations of Authority...6 Table Swimming Pool, Spa, and Hot Tub Permit Fees...7 TABLE OF CONTENTS CHAPTER 1 ADMINISTRATION..............1 101.0 General.......................1 101.1 Title..........................1 101.2 Scope........................1 101.3 Purpose......................1

More information

2015 UPC Chapter 8 Indirect Wastes RV

2015 UPC Chapter 8 Indirect Wastes RV PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.

More information

CHAPTER 31. VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R

CHAPTER 31. VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R CHAPTER 31 VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R This page left intentionally blank. 426R 2003 INTERNATIONAL RESIDENTIAL CODE For SI: PIPE SIZE (inches) TABLE P3107.3 COMMON VENT SIZES

More information

2009 IRC. and Fuel gas Provisions

2009 IRC. and Fuel gas Provisions 2009 IRC Q &A Plumbing, MechanICAl and Fuel gas Provisions TABLE OF CONTENTS PREFACE... vii ABOUT THE INTERNATIONAL CODE COUNCIL...viii PLUMBING PROVISIONS... 1 CHAPTER 25 PLUMBING ADMINISTRATION....3

More information

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2007

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2007 General: 1) (Q) May the gas be turned on temporarily to the gas piping system without the installation of the appliance? (A) NO! 2) (Q) Are traps required on all condensate drains from equipment? (A) Only

More information

THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO TELEPHONE: (440) FAX: (440) Building Department

THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO TELEPHONE: (440) FAX: (440) Building Department 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO 44039 TELEPHONE: (440) 353-0822 FAX: (440) 353-0823 INSTRUCTIONS FOR SWIMMING POOLS REQUIREMENTS FOR PERMIT: Completed application form Plot plan showing lot

More information

A GUIDE TO PASSING THE PLUMBING EXAM

A GUIDE TO PASSING THE PLUMBING EXAM A GUIDE TO PASSING THE PLUMBING EXAM BASED ON THE INTERNATIONAL PLUMBING AND FUEL GAS CODES WRITTEN BY JOHN WHITE REVISED 2014 2007-2014 This manual is the sole property of Energy Marketing Services. No

More information

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS City of Redwood City Community Development Department Building and Inspection Department 1017 Middlefield Road Redwood City, CA 94063 Phone (650) 780-7350 2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY

More information

CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT PLUMBING. Test Code: 5924 Version: 01

CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT PLUMBING. Test Code: 5924 Version: 01 CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT PLUMBING Test Code: 5924 Version: 01 Specific competencies and skills tested in this assessment: Safety Follow rules for fire safety Follow rules for housekeeping

More information

THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO TELEPHONE: (440) FAX: (440) Building Department

THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO TELEPHONE: (440) FAX: (440) Building Department THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO 44039 TELEPHONE: (440) 353-0822 FAX: (440) 353-0823 Building Department INSTRUCTIONS FOR DECKS REQUIREMENTS FOR PERMIT: Completed

More information

2015 UPC CODE - CHAPTER 8 INDIRECT WASTES

2015 UPC CODE - CHAPTER 8 INDIRECT WASTES 801.0 General. 2015 UPC CODE - CHAPTER 8 INDIRECT WASTES 801.1 Applicability. This chapter shall govern the materials, design, and installation of indirect waste piping, receptors, and connections; and

More information

Read Only Document Not For Distribution

Read Only Document Not For Distribution Chapter 5 Traps, Cleanouts and Backwater Valves 5.1 SEPARATE TRAPS FOR EACH FIXTURE a. Plumbing fixtures shall be separately trapped by a water seal trap placed as close as possible to the fixture outlet.

More information

2012 Virginia Plumbing Code & VRC (Plumbing) Update Training

2012 Virginia Plumbing Code & VRC (Plumbing) Update Training 2012 Virginia Plumbing Code & VRC (Plumbing) Update Training ----------------------------- Henrico County Department of Building Construction and Inspections Introduction This presentation was prepared

More information

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES 2.05 PLUMBING GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.05 It is expected that the plumbing design professional will conform to accepted good engineering design practices.

More information

APPENDIX L ALTERNATE PLUMBING SYSTEMS

APPENDIX L ALTERNATE PLUMBING SYSTEMS ALTERNATE PLUMBING SYSTEMS L 1.0 General. L 1.1 Applicability. The intent of this appendix is to provide clarification of procedures for the design and approval of engineered plumbing systems, alternate

More information

plumbing for greywater

plumbing for greywater plumbing for greywater october 2015 christina bertea ~union trained journeywoman plumber (1978) ~plumbing contractor (1996) ~greywater action singingwater@jps.net plumbing for greywater basic parts of

More information

Bill de Blasio, MAYOR. build safe live safe. Rick D. Chandler P.E., COMMISSIONER

Bill de Blasio, MAYOR. build safe live safe. Rick D. Chandler P.E., COMMISSIONER E LAA limited alteration application - FILING GUIDE information you need to know Bill de Blasio, MAYOR build safe live safe Rick D. Chandler P.E., COMMISSIONER FIXTURES COMMENTS efile Backflow Preventer

More information

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents Table of Contents Chapter 1 Administration Chapter 2 Definitions Chapter 3 General Regulations Chapter 4 Ventilation. Chapter 5 Exhaust Systems Chapter 6 Duct Systems Chapter 7 Combustion Air Chapter 8

More information

ENERGY MARKETING SERVICES

ENERGY MARKETING SERVICES 1 IMPORTANT STUFF This manual has been designed as a supplemental aid for students preparing to take the Plumbing Exam based on the international codes. It is not intended to replace any manuals or material

More information

Matrix of changes for the National Standard Plumbing Code July 2013

Matrix of changes for the National Standard Plumbing Code July 2013 Matrix of changes for the National Standard Plumbing Code July 2013 Item # Section Number Person Submitting Change Committee Action 10-77 10.20.8 and Table 3.1.3 XI Certification 10-82 12.16 Size and Lengths

More information

2015 MPC, MMC and IFGC Significant Changes

2015 MPC, MMC and IFGC Significant Changes 2015 MPC, MMC and IFGC Significant Changes Based on the 2015 Michigan Plumbing Code, (MPC), the 2015 Michigan Mechanical Code (MMC) and the 2015 International Fuel GaS Code (IFGC) Purpose This program

More information

PLUMBING FIXTURES Reserved

PLUMBING FIXTURES Reserved CHAPTER 27 PLUMBING FIXTURES Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 395R This page left intentionally blank. 396R 2003 INTERNATIONAL RESIDENTIAL CODE SECTION P2708 SHOWERS P2708.1 General. Shower

More information

2009 IPC ,IMC Q &A ANDIFGC

2009 IPC ,IMC Q &A ANDIFGC 2009 IPC,IMC ANDIFGC Q &A TABLE OF CONTENTS PREFACE.... ix ABOUT THE INTERNATIONAL CODE COUNCIL...x IPC CHAPTER 1 SCOPE AND ADMINISTRATION...1 Section 101 General... 1 Section 102 Applicability... 1 Section

More information

Pipe Sizing Table. Hydraulic Load Served (fixture units)

Pipe Sizing Table. Hydraulic Load Served (fixture units) MODULE 1 INTRODUCTION Notes: A Pipe Type Horizontal branch Pipe Sizing Table Hydraulic Load Served (fixture units) Size (in.) Code Reference 2 + 1.5 = 3.5 2 7.4.9.1.(1) B Soil stack 13.5 + 13.5 = 27 3

More information

1 Exam Prep Plumbing State Contractors Practice Exam 2

1 Exam Prep Plumbing State Contractors Practice Exam 2 1 Exam Prep Plumbing State Contractors Practice Exam 2 1 According to Chapter 64E-6, when sizing a grease interceptor used in a restaurant, the correct formula is. A. (S) x (EW 12) x (LF) B. (S) x (GS)

More information

Building Utilities 1 Plumbing and Sanitary Systems

Building Utilities 1 Plumbing and Sanitary Systems Building Utilities 1 Plumbing and Sanitary Systems Taken from UST Architecture exams by Arch. Rafael Alli Recommended review material for UST Preboard Exam Prepared by: arkireviewph.multiply.com Types

More information

Methods of Venting Plumbing Fixtures and Traps in the 2018 IPC

Methods of Venting Plumbing Fixtures and Traps in the 2018 IPC People Helping People Build a Safer World Methods of Venting Plumbing Fixtures and Traps in the 2018 IPC Installation, Flexibility and Opportunity for Savings Lee Clifton, Senior Director of PMG Resources,

More information

BACKFLOW PREVENTION GUIDE FOR COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL DEVELOPMENTS

BACKFLOW PREVENTION GUIDE FOR COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL DEVELOPMENTS AG AVB PVB DCVA PA 1 Abattoir (slaughter house) 2 Air compressor oil cooler 3 Agricultural chemicals (sprayers 4 Animal watering 5 Apartment building (within the scope of Part 3 of the Ontario Building

More information

Land Use and Environmental Service Agency (Code Enforcement) Mechanical 2010

Land Use and Environmental Service Agency (Code Enforcement) Mechanical 2010 Table of Contents Chapter 1 Administration 0 Chapter 2 Definitions 1 Chapter 3 General Regulations 11 Chapter 4 Ventilation. 2 Chapter 5 Exhaust Systems 13 Chapter 6 Duct Systems 12 Chapter 7 Combustion

More information

MINIMUM CONSTRUCTION STANDARDS AND SPECIFICATIONS CHECKLIST

MINIMUM CONSTRUCTION STANDARDS AND SPECIFICATIONS CHECKLIST Rev: 10/23/08 MINIMUM CONSTRUCTION STANDARDS AND SPECIFICATIONS CHECKLIST The following standards apply to constructing, renovating or converting buildings to use for preparing, processing, storing or

More information

PLUMBING CURRICULA OUTLINE

PLUMBING CURRICULA OUTLINE PLUMBING CURRICULA OUTLINE CORE CURRICULUM 2015 Basic Safety (Construction Site Safety Orientation) (12.5 Hours) (Module ID 00101-15) Presents basic jobsite safety information to prepare workers for the

More information

Test Code: 8117 / Version 1

Test Code: 8117 / Version 1 Pennsylvania Customized Assessment Blueprint Plumbing Technology/Plumber PA Test Code: 8117 / Version 1 Copyright 2012. All Rights Reserved. General Assessment Information Plumbing Technology/Plumber PA

More information

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire Suppression Systems; and Chapter 34-National Electric

More information

Land Use and Environmental Services Code Enforcement. Table of Contents

Land Use and Environmental Services Code Enforcement. Table of Contents 3rd Quarter 2013 Code Answers in blue (Jul Sep) 2013 Code Answers in red (Oct Dec) Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Chimneys & Vents Chapter 7 Gaseous Hydrogen S. POLICY

More information

BUILDING MATERIALS EVALUATION COMMISSION (BMEC) AUTHORIZATION REPORT

BUILDING MATERIALS EVALUATION COMMISSION (BMEC) AUTHORIZATION REPORT BUILDING MATERIALS EVALUATION COMMISSION (BMEC) AUTHORIZATION REPORT DATE OF AUTHORIZATION June 28, 2001 BMEC REFERENCE BMEC # 01-07-259 BMEC APPLICATION # BMEC #A 2001-10 OATEY CANADA INC. SURE-VENT AND

More information

CONNECTICUT. Downloaded

CONNECTICUT. Downloaded Housekeeping/Laundry/Maintenance J. Laundry. CONNECTICUT Downloaded 01.15.11 (1) This service, if provided, shall be used exclusively for laundry and shall be remote from resident and food service areas,

More information

Perkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet

Perkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet Perkins Statewide Articulation Agreement Documentation item: Secondary Task List Coversheet The Secondary School agrees to: A. Implement the approved PDE Program(s) of Study. B. Provide assessment of student

More information

Community Development Department Commercial Permit Application

Community Development Department Commercial Permit Application Commercial Permit Application Permit # Property Project Information Address Suite # Business Name Parcel # Fire Department County Type of Improvement (check all that apply) New Addition Alteration Repair

More information

WATER HAMMER ARRESTORS & MISC. SPECIALTIES

WATER HAMMER ARRESTORS & MISC. SPECIALTIES TABLE OF CONTENTS Pictorial Index Water Hammer Arrestors Certification Sizing & Placement Backwater Valves Typical Installations Trap Seal Primers Compliance Pressure & Flow Characteristics Typical Installations

More information

AIRPORT PLUMBING DESIGN STANDARDS REV. 2 11/02/2015

AIRPORT PLUMBING DESIGN STANDARDS REV. 2 11/02/2015 1.1 GOALS The goal of this section is to provide guidance in the design of Plumbing and Fire Protection systems to LAWA standards. The LAWA Plumbing Design Standards are a compilation of general design

More information

AIRPORT PLUMBING DESIGN STANDARDS REV. 3 3/18/2016

AIRPORT PLUMBING DESIGN STANDARDS REV. 3 3/18/2016 1.1 GOALS The goal of this section is to provide guidance in the design of Plumbing and Fire Protection systems to LAWA standards. The LAWA Plumbing Design Standards are a compilation of general design

More information

FIXTURES, FAUCETS AND FIXTURE FITTINGS

FIXTURES, FAUCETS AND FIXTURE FITTINGS CHAPTER 4 FIXTURES, FAUCETS AND FIXTURE FITTINGS SECTION 401 GENERAL 401.1 Scope. This chapter shall govern the materials, design and installation of plumbing fixtures, faucets and fixture fittings in

More information

Mechanical System Description

Mechanical System Description 1. Building Description: Mechanical System Description The building is a Type-1B construction, 9-levels, non-high rise building with 67 affordable family housing units. The first level of the structure

More information

TABLE OF CONTENTS. Part I Administrative

TABLE OF CONTENTS. Part I Administrative Part I Administrative.......................... 1-1 CHAPTER 1 SCOPE AND ADMINISTRATION. 1-1 R101 General............................. 1-1 R102 Applicability......................... 1-2 R103 (Not adopted)........................

More information

Pro Vent TM. Provent Systems Inc Capital Circle Lawrenceville Georgia

Pro Vent TM. Provent Systems Inc Capital Circle Lawrenceville Georgia Pro Vent TM Guide to Design and Usage Provent Single System Handling Installation Corrosion Ease Simplicity Resistance IPMO Copyright (c) 2014, Pro Vent Systems Inc., plus *2016 Revisions ll Rights Reserved

More information

Code verification sign-off

Code verification sign-off Code verification sign-off Following is a list of the most common manufactured home code non-compliant items found in used or altered manufactured homes. These are only the most commonly found items and

More information

2015 IPC, IMC and IFGC Significant Changes

2015 IPC, IMC and IFGC Significant Changes Accreditation 2015 IPC, IMC and IFGC Significant Changes Based on the International Plumbing Code (IPC ), the International Mechanical Code (IMC ) and the International Fuel Gas Code (IFGC ) The International

More information

Habitability Guidelines

Habitability Guidelines Habitability Guidelines for Relocated Manufactured Homes dced.pa.gov/mh @PADCEDnews Purpose The purpose of these habitability guidelines is to provide a reasonable level of assurance that the relocated

More information

MAXI-VENT Air Admittance Valve

MAXI-VENT Air Admittance Valve MAXI-VENT Air Admittance Valve Manufacturer: Studor, Inc. Connec on Size: 3 or 4 Model #: MAXI VENT Item #: 20302 An air admittance valve shall be acceptable as a vent termination for any individual vent,

More information

About the Presenters:

About the Presenters: About the Presenters: Mark Matheny, Asheville, 828-259-5667 ( mmatheny@ashevillenc.gov ): Mark is employed by Asheville and serves as a Plan Review Coordinator for new construction, alteration, renovation,

More information

SECTION PLUMBING

SECTION PLUMBING SECTION 22 10 00 PLUMBING PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish all labor, material and equipment necessary for the complete installation of the sanitary sewer system (including soil and vent piping),

More information

FAIRA TRANSPARENCY REPORTS Stone Ave N, #205, Seattle, WA 98133

FAIRA TRANSPARENCY REPORTS Stone Ave N, #205, Seattle, WA 98133 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 11550 Stone Ave N, #205, Seattle, WA 98133 Thank you for your interest in this Faira Certified

More information

TABLE OF CONTENTS. CHAPTER 2 DEFINITIONS General Applicability Definition of Terms General...

TABLE OF CONTENTS. CHAPTER 2 DEFINITIONS General Applicability Definition of Terms General... TABLE OF CONTENTS CHAPTER 1 ADMINISTRATION................1 101.0 Title, Scope, and General...........1 101.1 Title............................1 101.2 Purpose.........................1 101.3 Plans Required...................1

More information

SCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE

SCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE SCHEDULE OF S Penalty Fees. The fee for construction work performed before securing permit(s), where required, may be charged a fee of TWO TIMES THE COST OF THE PERMIT (S). Building Fee Schedule Residential

More information

CHAPTER 1 ADMINISTRATION SECTION 101 (IFGC) GENERAL

CHAPTER 1 ADMINISTRATION SECTION 101 (IFGC) GENERAL CHAPTER 1 ADMINISTRATION SECTION 101 (IFGC) GENERAL 101.1 Title. These regulations shall be known as the North Carolina Fuel Gas Code as adopted by the North Carolina Building Code Council on March 11,

More information

FAQ. (Frequently Asked Questions) What is required to convert my unfinished basement to finished space?

FAQ. (Frequently Asked Questions) What is required to convert my unfinished basement to finished space? NEW CASTLE COUNTY DEPARTMENT OF LAND USE FAQ (Frequently Asked Questions) What is required to convert my unfinished basement to finished space? 1. To convert an unfinished basement to finished space, at

More information

CHAPTER VI BUILDING PLUMBING

CHAPTER VI BUILDING PLUMBING CHAPTER VI BUILDING PLUMBING 6.1. INTRODUCTION The chapter covers questions related to water demand, distribution and drainage. The basic principles for planning and installing common plumbing systems

More information

2018 International Fire Code. Add new text as follows:

2018 International Fire Code. Add new text as follows: CCC-F-1-18 IFC: 311.2.2, 403.11.1.2, 1010.3.2; IBC: 424.3, 428.3.9, 506.2.2.1, 506.2.4.1, 1705.12.6, 2603.3, 3104.5.3, 2606.7.4; IRC: R101.2, R302.2.2, R313, R313.1, R313.1.1, R313.2, R313.2.1, R325.3,

More information

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE 1. BUILDING FEES: 1 AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE ESTABLISHMENT OF FEES PURSUANT TO N.J.A.C.

More information

Install Configurations

Install Configurations Table of Contents EQUIPMENT SPECS: 1 WATER SUPPLY CONFIGURATIONS 2 OPTION 1 (OPTIMIZED): BRING WATER TO MACHINES 2 OPTION 2 (ENHANCED): INSTALLING A DEDICATED WATER SOURCE 3 OPTION 3 (ENHANCED CONT.):

More information

HOME INSPECTOR EDUCATION EXPO 2016

HOME INSPECTOR EDUCATION EXPO 2016 An Education in Hot Water HOME INSPECTOR EDUCATION EXPO 2016 Residential Water Heater Inspection Course Objective Course Objective Completing this course should enable an inspector to identify components

More information

BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS

BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used by

More information

REGISTRATION EXAMINATION, NOVEMBER 2011 CERTIFYING PLUMBER ANSWER SCHEDULE

REGISTRATION EXAMINATION, NOVEMBER 2011 CERTIFYING PLUMBER ANSWER SCHEDULE No. 9195 REGISTRATION EXAMINATION, NOVEMBER 2011 CERTIFYING PLUMBER ANSWER SCHEDULE Plumbers, Gasfitters and Drainlayers Board, 2011. All rights reserved. No part of this publication may be reproduced

More information

STUDENT NOTES Plan, size and layout sanitary pipe work and fixtures

STUDENT NOTES Plan, size and layout sanitary pipe work and fixtures 4. SANITARY PLUMBING FULLY VENTED SYSTEM On completion of this module, the student should be able to: Design, install and develop bills of quantities for a fully vented modified system for commercial and

More information

2012 B.C. Building Code Compliance Review (Division B Part 3)

2012 B.C. Building Code Compliance Review (Division B Part 3) Planning and Building Department 2012 B.C. Building Code Compliance Review PROJECT NAME:.. CIVIC ADDRESS:...... PERMIT APPLICATION NO.:. DATE:... I,, have: 1. reviewed the design, plans and supporting

More information

SEISCO - MOUNTING CLEARANCES

SEISCO - MOUNTING CLEARANCES SEISCO - MOUNTING CLEARANCES SEISCO Installation Guide Horizontal Spacing** 24 Minimum Top Clearance: 12 inches * 15 ¾ 15 ¾ SEISCO FRONT VIEW Screw Holes 14 ¾ SIDE VIEW Screw Holes 16 1/8 Front Clearance

More information

Food Establishment Guidelines. Food Service Plan Review

Food Establishment Guidelines. Food Service Plan Review Food Service Plan Review Food service plan review in the City of Grand Prairie begins at the Environmental Services Department at the Development Center, 201 NW 2 nd Street in Suite 100. The City of Grand

More information

COMMERCIAL PERMIT APPLICATION AND CHECKLIST. Depending on the scope of your project, the following submittal requirements will apply:

COMMERCIAL PERMIT APPLICATION AND CHECKLIST. Depending on the scope of your project, the following submittal requirements will apply: Planning/Building Department 115 Ramsdell Street Fircrest WA 98466 (253) 564-8902 COMMERCIAL PERMIT APPLICATION AND CHECKLIST Depending on the scope of your project, the following submittal requirements

More information

HVAC Equipment Access Equipment Location

HVAC Equipment Access Equipment Location City of Lancaster- Building Department 121 East Chestnut Street, Suite 102, Lancaster, Ohio 43130-3825 (740) 687-6649, Fax (740) 681-5030 Web site: www.ci.lancaster.oh.us/dept/building HVAC Heating, Ventilating,

More information

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance Groton Heights School Mechanical Evaluation TO: FROM: Amy Vaillancourt, Project Manager Harley Langford, Project Manger Jason Curtis, P.E. DATE: February 24, 2016; Revised May 31, 2016 On Monday, December

More information

Plumbing Technology/Plumber CIP Task Grid

Plumbing Technology/Plumber CIP Task Grid 1 Secondary Task List 100 DEMONSTRATE PERSONAL SAFETY IN THE TRAINING LABORATORY 101 Follow rules for fire safety. 102 Follow rules for housekeeping safety. 103 Follow shop rules. 104 Follow rules for

More information

REGISTRATION EXAMINATION, NOVEMBER 2017 TRADESMAN PLUMBER ANSWER SCHEDULE

REGISTRATION EXAMINATION, NOVEMBER 2017 TRADESMAN PLUMBER ANSWER SCHEDULE No. 9192 REGISTRATION EXAMINATION, NOVEMBER 2017 TRADESMAN PLUMBER ANSWER SCHEDULE Plumbers, Gasfitters and Drainlayers Board, 2017. All rights reserved. No part of this publication may be reproduced by

More information