Technical & service manual 2005

Size: px
Start display at page:

Download "Technical & service manual 2005"

Transcription

1 HVAC EUROPE SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical & service manual 005 R40a Wall Mounted [Models] GCM07N niet leverbaar GHM07N niet leverbaar GCM09N GHM09N GCMN GHMN GCM8N GHM8N

2 GC(H)M Series (R40A) Contents. Features 0. Specification Dimensions Refrigeration cycle diagram table Capacity table Wiring diagram Electronic function Troubleshooting Characteristic of temp. sensor 36

3 .Features. Compact design. High efficiency and quiet operation.3 A class energy level

4 .Specification Model GCM-07N GHM-07N GCM-09N GHM-09N Power supply Ph-V-Hz, 0-40V~, 50Hz, 0-40V~, 50Hz, 0-40V~, 50Hz, 0-40V~, 50Hz Capacity Btu/h Cooling Input W Rated current A EER Btu/w.h, w/w,3.,3.,3.,3. Capacity Btu/h Heating Input W Rated current A COP W/W Moisture Removal L/h Max. input consumption W Max. current A Starting current A Model PA8XC-4DZDE PA8XC-4DZDE PA08XC-4FTDE PA08XC-4FTDE Type Rotary Rotary Rotary Rotary Brand TOSHIBA TOSHIBA TOSHIBA TOSHIBA Capacity Btu/h Compressor Input W Rated current(rla) A Locked rotor Amp(LRA) A Thermal protector MRA MRA MRA MRA Capacitor uf Refrigerant oil ml Model RPG3H RPG3H RPG3H RPG3H Brand Welling Welling Welling Welling Indoor fan motor Input W Capacitor uf.... Speed(hi/mi/lo) r/min 050/90/80 050/90/80 00/950/850 00/950/850 Indoor air flow (Hi/Mi/Lo) m3/h 450/400/ /400/ /430/ /430/370 Indoor noise level (Hi/Mi/Lo) db(a) 35/3/30 35/3/30 37/34/3 37/34/3 Dimension (W*H*D) mm Indoor unit Packing (W*H*D) mm Net/Gross weight Kg 8/0 8/0 8/0 8/0 Model YDK4-6T YDK4-6T YDK4-6F YDK4-6F Brand Welling Welling Welling Welling Outdoor fan motor Input W Capacitor uf Speed r/min Outdoor air flow m3/h Outdoor noise level db(a) Dimension(W*H*D) mm 700X535X35 700X535X35 780X540X50 780X540X50 Outdoor unit Packing (W*H*D) mm 85X580X35 85X580X35 90X575X335 90X575X335 Net/Gross weight Kg 3/34 3/35 36/39 37/40 Refrigerant type R40A g Design pressure MPa Liquid side/ Gas side mm(inch) Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Refrigerant piping Max. refrigerant pipe length m Max. difference in level m Connection wiring No No No No Plug type 6A 6A 6A 6A Thermostat type Electrolic control Electrolic control Electrolic control Electrolic control Operation temp Ambient temp 8~ ~ 45 8~ ~ 45 Application area m Qty per 0 /40 /40'HQ set 6/7/98 6/7/98 3/38/74 3/38/74 The noise date is base on hemi-anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition. 3

5 Model GCM-N GHM-N GCM-8N GHM-8N Power supply Ph-V-Hz, 0-40V~, 50Hz, 0-40V~, 50Hz, 0-40V~,50Hz, 0-40V~,50Hz Capacity Btu/h Cooling Input W Rated current A EER Btu/w.h, w/w,3.,3. 0.5,3. 0.5,3. Capacity Heating Input Rated current COP Moisture Removal L/h Max. input consumption W Max. current A Starting current A Model PA40XC-4FT PA40XC-4FT PA00XCS-4KU PA00XCS-4KU Type rotary Rotary Rotary Rotary Brand TOSHIBA TOSHIBA Toshiba Toshiba Capacity Btu/h Compressor Input W Rated current(rla) A Locked rotor Amp(LRA) A Thermal protector UP3RE059-T56 UP3RE059-T56 Internal Internal Capacitor uf Refrigerant oil ml ESTER OIL VG ESTER OIL VG Model RPG3D RPG3D RPG8D RPG8D Brand Welling Welling Welling Welling Indoor fan motor Input W Capacitor uf...5uf/450v.5uf/450v Speed(hi/mi/lo) r/min 0/000/800 0/000/800 80/080/800 80/080/800 Indoor air flow (Hi/Mi/Lo) m3/h 580/500/40 600/50/40 850/700/ /700/600 Indoor noise level (Hi/Mi/Lo) db(a) 40/37/34 40/37/34 4/39/37 4/39/37 Dimension (W*H*D) mm Indoor unit Packing (W*H*D) mm 875x85x x85x Net/Gross weight Kg 9.0/.5 9/ 3/5 3/5 Model YDK4-6F YDK4-6F YDK53-6K YDK53-6K Brand Welling Welling Welling Welling Outdoor fan motor Input W Capacitor uf Speed r/min Outdoor air flow m3/h Outdoor noise level db(a) Dimension(W*H*D) mm 780X540X50 780X540X50 845X695X X695X335 Outdoor unit Packing (W*H*D) mm 90X575X335 90X575X X770X X770X395 Net/Gross weight Kg 37/40 38/4 5/56 5/56 Refrigerant type R40A g Design pressure MPa Liquid side/ Gas side mm(inch) Ф6.35/Ф.7 Ф6.35/Ф.7 Ф6.35/Ф.7 Ф6.35/Ф.7 Refrigerant piping Max. refrigerant pipe length m Max. difference in level m Connection wiring No No No No Plug type 6A 6A NO PLUG NO PLUG Thermostat type Electrolic control Electrolic control Electronic control Electronic control Operation temp Ambient temp 8~ ~ ~45 Application area m ~40 8~40 Qty per 0 /40 /40'HQ set 94/99/3 94/99/3 70 / 48 / / 48 / 70 The noise date is base on hemi-anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition. 4

6 3.Dimensions 3. Indoor unit GCM-07N,GHM07N,GCM09N,GHM09N 3. Indoor unit GCM-N, GHMN 5

7 3. Indoor unit GCM-8N,GHM8N 6

8 3.4 Outdoor unit GCM-07N,GHM07N 3.5 Outdoor unit GCM-09N,GHM09N,GCMN,GHMN 7

9 GCM-8N,GHM8N. 5 8

10 4.Refrigeration cycle diagram 9

11 5. table Note: *The pressure data is from 3 way valve, the pressure data are pressure above atmosphere. *D: Dry bulb temp. *W: Wet bulb temp. 5.GCM07N Cooling mode Outdoor temperature (Dry bulb temp) Indoor Conditions 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W ºC D 3ºC W GHM07N Cooling mode Indoor Conditions Outdoor temperature (Dry bulb temp) 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W ºC D 3ºC W Heating mode Indoor Conditions 5ºC 8ºC 0ºC ºC OUTDOOR CONDITIONS ºC D 7ºC D 0ºC D -4ºC D -7ºC D -5ºC D ºC W 6ºC W -ºC W -6ºC W -9ºC W -xºc W / / / / 0

12 5.3GCM09N Cooling mode Outdoor temperature (Dry bulb temp) Indoor Conditions 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W ºC D 3ºC W GHM09N Cooling mode Outdoor temperature (Dry bulb temp) Indoor Conditions 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W ºC D 3ºC W Heating mode Indoor Conditions 5ºC 8ºC 0ºC ºC OUTDOOR CONDITIONS ºC D 7ºC D 0ºC D -4ºC D -7ºC D -5ºC D ºC W 6ºC W -ºC W -6ºC W -9ºC W -xºc W / / / /

13 5.5GCMN Cooling mode Outdoor temperature (Dry bulb temp) Indoor Conditions 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W 3ºC D 3ºC W GHMN Cooling mode Outdoor temperature (Dry bulb temp) Indoor Conditions 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W 3ºC D 3ºC W Heating mode Indoor Conditions 5ºC 8ºC 0ºC ºC OUTDOOR CONDITIONS ºC D 7ºC D 0ºC D -4ºC D -7ºC D -5ºC D ºC W 6ºC W -ºC W -6ºC W -9ºC W -xºc W / / / /

14 5.7GCM8N Cooling mode Outdoor temperature (Dry bulb temp) Indoor Conditions 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W 3ºC D 3ºC W GHM8N Cooling mode Outdoor temperature (Dry bulb temp) Indoor Conditions 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W 3ºC D 3ºC W Heating mode Indoor Conditions 5ºC 8ºC 0ºC ºC OUTDOOR CONDITIONS ºC D 7ºC D 0ºC D -4ºC D -7ºC D -5ºC D ºC W 6ºC W -ºC W -6ºC W -9ºC W -xºc W / / / / 3

15 6. Capacity table 6.GCM07N SUMMER Indoor Conditions ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W 3ºC D 3ºC W OUTDOOR TEMPERATURE DRY 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw GHM07N SUMMER OUTDOOR TEMPERATURE DRY Indoor 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC Conditions Total capacity kw ºC D Sensitive capacity kw ºC W Input kw Total capacity kw ºC D Sensitive capacity kw ºC W Input kw Total capacity kw ºC D Sensitive capacity kw ºC W Input kw Total capacity kw ºC D Sensitive capacity kw ºC W Input kw

16 WINTER Indoor Conditions 5ºC 8ºC 0ºC ºC OUTDOOR CONDITIONS ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D ºC W 6ºC W 3ºC W -ºC W -6ºC W -8ºC W Capacity kw Input kw Capacity kw Input kw Capacity kw Input kw Capacity kw Input kw GCM09N SUMMER Indoor Conditions ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W 3ºC D 3ºC W OUTDOOR TEMPERATURE DRY 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw

17 6.4GHM09N SUMMER Indoor Conditions ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W 3ºC D 3ºC W OUTDOOR TEMPERATURE DRY 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Indoor Conditions 5ºC 8ºC 0ºC ºC WINTER OUTDOOR CONDITIONS ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D ºC W 6ºC W 3ºC W -ºC W -6ºC W -8ºC W Capacity kw Input kw Capacity kw Input kw Capacity kw Input kw Capacity kw Input kw

18 6.5GCMN SUMMER Indoor Conditions ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W 3ºC D 3ºC W OUTDOOR TEMPERATURE DRY 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw GHMN SUMMER Indoor Conditions ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W 3ºC D 3ºC W OUTDOOR TEMPERATURE DRY 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw

19 Indoor Conditions 5ºC 8ºC 0ºC ºC WINTER OUTDOOR CONDITIONS ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D ºC W 6ºC W 3ºC W -ºC W -6ºC W -8ºC W Capacity kw Input kw Capacity kw Input kw Capacity kw Input kw Capacity kw Input kw GCM8N SUMMER Indoor Conditions ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W 3ºC D 3ºC W OUTDOOR TEMPERATURE DRY 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw

20 6.8GHM8N SUMMER Indoor Conditions ºC D 5ºC W 4ºC D 7ºC W 7ºC D 9ºC W 3ºC D 3ºC W OUTDOOR TEMPERATURE DRY 5ºC 30ºC 35ºC 40ºC 45ºC 50ºC Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Total capacity kw Sensitive capacity kw Input kw Indoor Conditions 5ºC 8ºC 0ºC ºC WINTER OUTDOOR CONDITIONS ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D ºC W 6ºC W 3ºC W -ºC W -6ºC W -8ºC W Capacity kw Input kw Capacity kw Input kw Capacity kw Input kw Capacity kw Input kw

21 h g f e d c b a 7. Schematic diagram and wiring diagram 7. Schematic diagram D C B A CN 4 3 TRANS C5 04 BUZ ' +5V CN +V T_room R8 8.K/% CN3 T_I.pipe R9 8.K/% Current A B C D R5 K C8 04 IC5 R4 K KIA704 BUZ BUZZER +5V +5V D D D3 D4 D6 D7 D8 D9 D5 IN448 D6 IN448 D7 IN448 D8 IN448 R K E6 0uF/6V IN4007*4 IN4007*4 3 R0 E5 E4 RST K 0uF/6V R K 0uF/6V +5V C5 04 D9 N448 R4.4K/% R3 6K E 00uF/5V E0 00uF/5V C 04 C3 04 C6 04 C7 04 D0 N448 R6 K/% IC 78 +V-a 3 Vin Vout T_room T_I.pipe GND GND CN5 3 COM CT +5V +5V 0057h +5V R 0K SEG3 SEG4 R 8.06K E 000uF/6V R6 0K R3 5.K C3 04 IC0 78 +V-b 3 Vin Vout E 000uF/6V GNDB C4 04 CN6 R59 0K FAN_IN IC V 3 Vin Vout +5V R60 0K TC_SELECT C4 GND C6 04 TC_SELECT FAN_IN BUZ STEP_I STEP_I STEP_I3 STEP_I4 COMP T_room T_I.pipe Current T.uF/450V K O +5V R4 FAN_IN BUZ STEP_I STEP_I STEP_I3 STEP_I4 COMP O SEG3 SEG4 T T CURRENT 0 TC_SELECT STEP_I STEP_I STEP_I3 STEP_I4 FAN_IN BUZ COMP C9 04 E3 470uF/6V V-a R5 5/W G IC7 C4 04 VSS0 VDD0 P5 P6 P00 P0 P0 P03 P04 VSS P05 P50 P5 P5 P53 AVDD AVREF AN0 AN AN AN3 IN IN IN3 IN4 IN5 IN6 IN7 VSS UJN003 T BT3 TR OUT OUT OUT3 OUT4 OUT5 OUT6 OUT7 C5 333 VDD? L IC6 PC87.JR=K JR. JRJR3 3. JR4JR5 4.JR6JR7 IC4 UPD V-a R6 K FAN_IN ' BUZ ' COMP ' Z V X X RESET XT XT VppIC P4 P3 P P VDD P0 P33 P3 P3 P30 P P0 AVSS AN5 AN4 +V-a FAN_IN ' X X RST SCL SDA COM COM COM3 FAN_OUT FANSP ZERO REC VALVE FRESH E9 470uF/5V R8 K/W CN SWING R7 M RST SCL SDA COM COM +5V COM3 ZERO REC X 4M FAN_OUT FANSP_FEEDBACK FRESH R9 K/W SEG3 SEG4 C C4 +5V D5 IN4007 JR4 JR5 JR JR C6 0 JR6 0K JR7 0K K 0K 0K 0K IC8 GND Vcc MR CP Dsb Dsa 74HC64 L N ZR 0D47K VALVE +5V CN N Q7 Q6 Q5 Q4 Q3 Q Q Q0 C3 A SCL SDA R38 0K D N448 D N448 B 3 R R DIS WT40BG com com R R R R R R uF/75VAC +5V t PTC 8RM R39 0K R6 K R5R7 K K Q8 90 CN5 TRANS_IN +5V IC VCC WC SCL SDA R6 K JR K 4C04 C9 04 A0 A A GND R8 0K Q9 90 REC COM COM COM3 +5V C ZERO Q 904 SW +5V R4+5V R4+5V K K R56 0K R57 0K R58 0K LED5 LED6 LED7 LED8 LED9 Q0 90 R9 50 R0 C0 0 R43 K K REC V C GND E7 04 0uF/6V O FAN_OUT VALVE REC RECEIVER_V FRESH R6 K R6 K Q +V-a 904 R33 K R34 K R35 K IC9 D IN448 FANSP_FEEDBACK PC87 COMP ' +V-a +V-a +V-a Q5 904 D3 IN448 Q6 904 D4 IN448 Q7 904 CN3 +V-a +V-b +5V D3 IN448 R5.K C 03 LOAD_HEAT L RY3 RELAY-SPST L LOAD_VALVE RY4 RELAY-SPST LOAD_FAN OUT R63 5.K C0 333 RY5 RELAY-SPST FUSE LOAD_COMP RY6 COMP SW R36 5/W L 3.5A/50V +VCN4 3 FAN_BACK +V-b GNDB CN6 Q 904 CN0 O_L L(POWER_IN PORT) D C B A SchemeFor UPD78F V

22 7. Wiring diagram 7.. Cooling only 7...GCM07N, GCM09N GCMN I NDOOR UNIT OUTDOOR UNI T (N) Y&G BLACK BLACK C BLACK RED RED Y&G S BLUE RED R COMPRESSOR CAPACI TOR FAN MOTOR RED BLUE

23 7...GCM8N INDOOR UNIT OUTDOOR UNI T Y&G RED BLACK BLACK OVERLOAD RELAY BLACK COMPRESSOR Y/G C BLUE R S WHITE COMPRESSOR CAPACI TOR FAN MOTOR RED BLUE FAN CAPACI TOR

24 7.. Heating/cooling 7... GHM07N, GHM09N GHMN I NDOOR UNIT OUTDOOR UNI T 3

25 7...GHM8N INDOOR UNIT OUTDOOR UNI T RED BLUE BLUE Y&G 4-WAY BLACK OVERLOAD RELAY BLACK BLACK COMPRESSOR Y/G C BLUE R S WHITE FAN MOTOR RED BLUE COMPRESSOR CAPACI TOR FAN CAPACI TOR 4

26 8 Electronic function 8. Electric Control working environment 8.. input voltage: 75~53V 8.. Input power frequency:50hz 8..3 Ambient temperature: -7 C~+43 C 8..4 Indoor fan normal working amp is less than A, 8..5 Outdoor fan. Normal working amp is less than.5a 8..6 Four-way valve normal working amp is less than A Swing motor: DCV Compressor: single-phase power supply. Its normal working amp is less than 5A 8. Proper symbols and their meanings: TA: Indoor ambient temperature TE: Indoor evaporator temperature TS: Setting temperature through the remote controller I 3sec : Self-protection amp of compressor, continue three seconds until turns off the compressor. I 5MIN : Self-protection amp of compressor, continue five minutes until turns off the compressor. I FAN : Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind. I RESTORE : Amp self-protection return value TH DEFROST : High wind, defrosting temperature difference TM DEFROST : Middle wind, defrosting temperature difference TL DEFROST : Low wind, defrosting temperature difference TE: Anti-cold wind, from Fan Off to Breeze temperature TE: Anti-cold wind, from Breeze to Setting Fan Speed temperature TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature TE4: Anti-cold wind, from Breeze to Fan Off temperature TE5: Evaporator low temperature protection entering temperature TE6: Evaporator low temperature protection restoring temperature TE7: Evaporator high temperature protection, compressor off temperature TE8: Evaporator high temperature protection, fan off temperature TE9: Evaporator high temperature protection, restoring temperature 8.3 Functions Remote receiving Testing and forced running Position set for indoor unit wind vane LED displaying and alarm On or off Timer Protection for the compressor Current protection High temperature protection of indoor heat exchanger at heating mode Auto defrosting and heating recovery at heating mode Anti cold air at heating mode Anti frozen at cooling mode 5

27 8.4 Protection minutes delay at restart for compressor Sensor protection at open circuit and breaking disconnection Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too low(lower than 400RPM), the unit stops and LED displays failure information and can t returns to normal operation automatically Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED displays failure information and can t returns to normal operation automatically The current protection of the compressor Condition Indoor fan Compressor Outdoor fan Remark Current up I< I RESTORE On On On I RESTORE <I< I FAN On On Off Heating mode Low speed On On Cooling mode I FAN <I<I 5MIN Off Off After 5 Minutes I 5MIN<I< I 3SEC Off Off After 3 Seconds Current down I 5MIN<I< I 3SEC Off Off After 3 Seconds I FAN <I<I 5MIN Off Off After 5 Minutes I RESTORE <I< I FAN On On Off Heating mode Low speed On On Cooling mode I< I RESTORE On On On If compressor turns off for continuously 4 times due to current protection in 5 minutes from Compressor On, the unit stops and LED displays failure information and can t returns to normal operation automatically. 8.5 Fan-only mode Fan speed is high/mid/low/ Auto 8.6 Cooling mode The 4-way valve is closed at cooling mode. The action of the compressor and the outdoor fan: Condition T=Indoor Temp. Ts=Setting Temp. Room temp. up Room temp. down 6 Compressor T> Ts+ On On T<Ts+ Off Off T> Ts On On T<Ts Off Off Auto fan at cooling mode: Room temp. up Room temp. down Condition T=Indoor Temp.-Setting Temp. T<4 4<T<5 T>5 Indoor fan speed Low Med. High T> 4 High <T<4 T< Med. Low Outdoor fan

28 Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. ) Condition Compressor Outdoor fan Temp. Time Evaporator Temp. up T> TE6 On On T< TE6 >5 Minutes Off Off Evaporator Temp. down T> TE5 On On T< TE5 >5 Minutes Off Off 8.7 Dehumidifying mode 8.7. The 4-way valve is off in dehumidifying mode 8.7. Compressor and Indoor Fan actions in dehumidifying mode NO Conditions Indoor Fan Compressor and Outdoor Fan TA TS+ TS TA<TS+ 3 TA < TS Repeat on and off cycle. LOW BREEZE LOW BREEZE LOW BREEZE ON 6minutes OFF 4minutes ON 5minutes OFF 5minutes ON 4minutes OFF 6minutes 7

29 8.7.3 Low room temperature protection: When room temperature decreases to below 0, compressor and outdoor fan will stop(indoor fan is Breeze). Dehumidifying operation will be resumed when room temperature restores to over At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of cooling mode At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode. 8.8 Heating mode 8.8. Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve must delay minutes compared with compressor if the compressor changed into non-heating mode or turned off. 4-way valve doesn't delay in dehumidifying mode Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except for the defrosting mode or the end of defrost Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes after starting and then judge temperature. Meanwhile other protections are still valid. Condition Compressor Outdoor fan Room temp. up T> Ts+3* Off Off T<Ts+3* On On Room temp. down T< Ts+* On On T>Ts+* Off Off * This parameter can be changed from 0 to Indoor Fan actions at heating mode Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function prevails. Optional : Anti-cold wind control function at heating mode Condition Indoor fan speed Indoor exchanger temp. up T= Indoor exchanger temp. T<TE TE<T<TE T>TE Off Breeze Setting fan speed Indoor exchanger temp. down T> TE3 Setting fan speed TE3<T<TE4 Breeze T<TE4 Off Option : Indoor fan changes breeze when compressor stop, after 7 second, indoor fan stop Auto wind at heating mode Condition Indoor fan speed Room temp. up T=Indoor Temp.-Setting Temp. T< T> High Med. Room temp. down T> 0 Med. 8

30 T<0 High 9

31 8.8.6 Indoor evaporator high-temperature protection at heating mode Condition T= Indoor exchanger temp. Compressor Outdoor fan Indoor exchanger temp. up T<TE8 On On TE8<T<TE7 On Off T>TE7 Off Off Indoor exchanger temp. down T>TE9 Off Off T<TE9 On On The louver opens to Standard Angle ANGLHEAT when power is on for the first time 8.9 Defrosting operation (Available for heating only) Defrosting condition: Defrosting starts when either of the following &: A and B are satisfied: A: The compressor keeps running for 40 minutes or more. B: The temperature difference of evaporator and room temperature meets one of the following: Temp. of evaporator---room temp. Fan speed is high Fan speed is mid Fan speed is low Breeze TH DEFROST TM DEFROST TL DEFROST Meet only if it is Breeze Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan with the compressor still running. Add up to 90 minutes Defrosting time If the temp. difference condition is satisfied for less than 40 minutes, this can be regarded as severe frosting. The defrosting time is 0 minutes. If the temp. difference condition is satisfied for more than 40 minutes, the defrosting time is 6 minutes. If the temp. difference condition is satisfied out of 40 minutes, generally the defrosting time is 6 minutes, after three continuous 6-minute defrost, the fourth should be 0 minutes defrost. The circulation is as following: 7.5-minute defrost 7.5-minute defrost 7.5-minute defrost 0-minute defrost Ending condition of defrosting If one of following conditions is satisfied, end the defrost and turn into heating mode: 30

32 A. The defrost time has reached to 7.5 or 0 minutes. B. The compressor current has reached to I DEFROST or above, I DEROST differs in different models. 3

33 8.9.4 Defrosting Actions: Defrost 0or 6minutes Compressor 45S 5S 4-way Valve Outdoor Fan 40S 3S Indoor Fan 0S 8.0 Automatic operation mode 8.0. The air conditioner automatically selects one of the following operation modes: cooling, heating or fan only according to the temp. difference between room temp. (TA) and set temp. (TS). TA TS TA TS> - TA-TS + Operation mode Cooling Fan-only TA-TS<- Heating (air-only for cooling only type) 8.0. The indoor fan blows automatically in corresponding selected mode The motion of indoor fan s blade should accord with the selected operation mode One mode should be carried out for at least 5 minutes once selected. If the compressor cannot start for 5 minutes, reselect the operation mode according to the room temp. and set temp., or reselect when the set temp. varies. 8. Forced cooling function 8.. Select forced cooling function with the forced cooling button or the switch. 8.. The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode is set as low, the A/C operates at the DRY mode with a set temp. of All protections of remote control cooling are available at forced cooling operation. 8. Forced Auto function Select forced auto function with the forced auto button or the switch. In forced auto status the A/C operates at remote control mode with a set temp. of Timer Function 8.4 Sleep mode 8.4. The sleep function is available at cooling, heating or auto mode. 3

34 8.4. Cooling: The set temperature rise per hour. Two hours later, the set temperature will maintain as a constant and the fan speed is kept at low speed. The total time is 7 hours, after 7 hours the unit stops Heating: The set temperature decrease per hour. Two hours later, the set temperature will maintain as a constant and the air circulation is kept at low speed (Cold air proof function takes precedence over all). The total time is 7 hours, after 7 hours the unit stops Auto: The economic running function operates in accordance with selected running mode by auto mode. The total time is 7 hours, after 7 hours the unit stops. 8.5 Auto restart function In case of a sudden power failure, this function automatically sets the unit to previous settings before the power failure when power returns. 8.6 PLASMA ( optional): Starts with indoor fan. Note: Plasma and Anion can be use together. 8.7 Anion (optional) Starts with indoor fan. Note: Plasma and Anion can be use together. 33

35 8.8 Models and Parameters Model GCM-07N GHM-07N GCM-09N GHM-09N GCM-N GHM-N I3SEC 7.5A 7.5A 0.0A 0.0A.0A.0A I5MIN 6.A 6.A 7.5A 7.5A 8.5A 8.5A IFAN 5.A 5.A 5.5A 5.5A 7.5A 7.5A IRESTORE 4.A 4.A 4.5A 4.5A 6.5A 6.5A IDEFROST 3.A 3.5A 5.0A TE TE TE TE4 6 6 TE TE TE TE TE ANGLCOOL ANGLHEAT ANGLOFF TH DEFROST 7 C 7 C 0 C TM DEFROST 8 C 8 C 3 C TL DEFROST 9 C 9 C 6 C 34

36 9.Troubleshooting 9. Display board Signal receptor AUTO indicator Thi s indicator illuminates when the air conditioner i s in AUTO operation. DE FROST indicator (F or Cooling & H eating mo dels only) This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air control feature is activated in heating oper ation. TEMPERATURE indicator Displays the temperature settings when the air conditioner is operational. OPERATION in dicator This indicator fl ashe s after power is on and illuminate s when the unit is in operation. TIMER indicator This indicator il luminates when TIMER is set ON/OFF. 9. For all heat pump model Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over minute X Indoor room temp. or evaporator sensor is open circuit or short circuit On Over current protection of the compressor occurs 4 times X EEROM error On No over-zero signal r Extinguish Flash at 5Hz 35

37 9.3 Diagnostic Chart 9.3. After energizing, no indicator is lighted and the air conditioner can t be operated. After energizing, the air conditioner can t be operated Check if AC0V power supply outputs to Indoor PCB. Yes Check if AC0V exists at the primary coil of transformer. Yes No Indoor PCB is defective Check if AC4.5V exists at the secondary coil of transformer. No Take off the secondary plug of transformer, and then check if AC4.5V exists at the secondary coil of transformer. Yes Yes No The transformer is defective. Indoor PCB is defective 9.3. Resetting phenomenon often occurs during operation. (That is automatically entering to the status when power is on.) The reason is that the instantaneous voltage of main chip is less than 4.5V. Check according to the following procedure: Resetting phenomenon often occurs during operation. Yes After changing Indoor PCB, check if the failure releases. No Yes After changing indoor fan motor, check if the failure releases. Indoor PCB is defective No Power supply circuit has problems. 36

38 9.3.3 Failure phenomenon Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over minute X Indoor room temp. or evaporator sensor is open circuit or short circuit On Over current protection of the compressor occurs 4 times X EEROM error On No over-zero signal r Extinguish Flash at 5Hz Operation lamp flashes and Timer lamp off. Is connector connection good? Yes No Is voltage being applied to the fan motor? Repair the connector Yes Fan motor is defective No Indoor PCB is defective Operation lamp flashes and Timer lamp on. Is connection to connector good? Yes Replace the sensor No Repair connector Operation lamp off and Timer lamp flashes Operation lamp off and Timer lamp flashes After changing the main control board, check if the failure releases. No The voltage of power supply is too low (less than 87V)? Yes Yes Indoor PCB is defective Yes Power supply fault No Outdoor unit fault (such as the compressor) Operation lamp on and Timer lamp flashes EEROM error, indoor PCB is defective Operation lamp flashes, Timer lamp flashes. This is alarm signal when the main chip can t detect over-zero signal. When such failure occurs, the main control board must have fault. 37

39 0. Characteristic of temp. sensor Temp. Resistance KΩ Temp. Resistance KΩ Temp. Resistance KΩ

1. Features Specification Dimensions Refrigeration cycle diagram Operation limits

1. Features Specification Dimensions Refrigeration cycle diagram Operation limits GLORY (ECO) STAR SERIES 1. Features 60 2. Specification 61 61 3. Dimensions 67 67 4. Refrigeration cycle diagram 70 70 5. Operation limits 71 6. Wiring diagram 72 7. Troubleshooting 80 8. Electronic function

More information

Service Manual. Multi Split Type Heat Pump Air Conditioners. Applied to: HS-9U2IM_HOS-18U2IM HS-9U11IM_HS-12U11IM_HOS-21U11IM

Service Manual.   Multi Split Type Heat Pump Air Conditioners. Applied to: HS-9U2IM_HOS-18U2IM HS-9U11IM_HS-12U11IM_HOS-21U11IM Service Manual Multi Split Type Heat Pump Air Conditioners Applied to: HS-9U2IM_HOS-18U2IM HS-9U11IM_HS-12U11IM_HOS-21U11IM CONTENT 1. Product features 2. Specification 3. Dimensions 4. Refrigeration cycle

More information

WALL MOUNTED UNITS SDH W SDH W SDH W SDH W

WALL MOUNTED UNITS SDH W SDH W SDH W SDH W WALL MOUNTED UNITS Technical Dossier WALL MOUNTED UNITS SDH 14-026 W SDH 14-036 W SDH 14-051 W SDH 14-065 W 2010 1- CONTENTS 1- Contents... 2 2- Technical specifications... 3 3- Temperature by capacities...

More information

Cover. Service Manual PAC9037 PAC12037 PAC13037 PAC18037

Cover. Service Manual PAC9037 PAC12037 PAC13037 PAC18037 Cover Service Manual PAC9037 PAC12037 PAC13037 PAC18037 Content Content 1. Precaution 2 1.1 Safety Precaution 2 1.2 Warning 2 2. Function 4 3. Dimension 6 3.1 Indoor unit 6 3.2 Outdoor unit 6 4. Refrigerant

More information

Content Precaution...2 Function...3 Dimension...5 Refrigerant cycle diagram...7 Operation limits...8 Wiring diagram...9 Installation details...

Content Precaution...2 Function...3 Dimension...5 Refrigerant cycle diagram...7 Operation limits...8 Wiring diagram...9 Installation details... Cover Content Content 1. Precaution...2 1.1 Safety Precaution...2 1.2 Warning...2 2. Function...3 3. Dimension...5 3.1 Indoor unit...5 3.2 Outdoor unit...5 4. Refrigerant cycle diagram...7 5. Operation

More information

Ceiling & Floor type Unit

Ceiling & Floor type Unit Ceiling & Floor type Unit Part 1. Product Features Quietest operation, low noise. Thin design, space-saving. Easy to operate, remote control. 16 Part 2. Specification Model MUA-18HRN2 MUA-24HRN2 MUA-24HRN2

More information

High Wall SERVICE MANUAL. TLCA-TLHA 07 to 18 FSAAAR TLCA-07 / TLHA-07 TLCA-09 / TLHA-09 TLCA-12 / TLHA-12 TLCA-18 / TLHA-18 SM-TLCA-TLHA-07-18GB 06-08

High Wall SERVICE MANUAL. TLCA-TLHA 07 to 18 FSAAAR TLCA-07 / TLHA-07 TLCA-09 / TLHA-09 TLCA-12 / TLHA-12 TLCA-18 / TLHA-18 SM-TLCA-TLHA-07-18GB 06-08 High Wall TLCA-TLHA 07 to 18 FSAAAR SERVICE MANUAL TLCA-07 / TLHA-07 TLCA-09 / TLHA-09 TLCA-12 / TLHA-12 TLCA-18 / TLHA-18 SM-TLCA-TLHA-07-18GB 06-08 1. Precaution 1.1 Safety Precaution To prevent injury

More information

Multi Inverter Air Conditioning Condensing Units - Summary

Multi Inverter Air Conditioning Condensing Units - Summary Multi Inverter Air Conditioning Condensing Units - Summary Model Description Nominal Max of Cooling Inverter No. Heating of (kw) Fan Condensing (kw) Coils Unit ECO18MS2 Twin Multi Inverter 5kW 5.2 6.1

More information

High static Pressure Duct Type Air-conditioner

High static Pressure Duct Type Air-conditioner High static Pressure Duct Type Air-conditioner Part 1. Product Features In case the ceiling is super-high. Blowing pressure of Indoor Unit can reach 196Pa. The air conditioner delivers cold wind to every

More information

Service Manual. Room Air Conditioner Split Wall-Mounted Type. Applies to: HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1

Service Manual. Room Air Conditioner Split Wall-Mounted Type. Applies to: HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1 Service Manual Room Air Conditioner Split Wall-Mounted Type Applies to: HSG-09CRN1 HSG-12CRN1 HSG-18CRN1 HSG-24CRN1 HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1 NOTE: Please read this first before servicing

More information

Floor-Standing Type(E Series)

Floor-Standing Type(E Series) Floor-Standing Type(E Series) Model: MFE-60CE, MFE-60AE Part 1. Product Features With a spiral shape, the computer-aided simulation designed air passage system can efficiently reduce noise. The Soft touch

More information

Corona Plus varmepumper

Corona Plus varmepumper Corona Plus varmepumper SERVICEMANUAL MSC-09HRDN1-QD0E MSC-12HRDN1-QC6E CONTENTS 1. Precaution... 1 1.1 Safety Precaution... 1 1.2 Warning... 1 2. Function... 4 3. Dimension... 6 3.1 Indoor Unit... 6 MSC-09HRDN1-QD0(E)

More information

Mobile Type Air Conditioner

Mobile Type Air Conditioner Mobile Type Air Conditioner 1. Features 2. Specification 3. Wiring diagram 4. Trouble shooting 5. Electronic function 36 1. Features 1.1The currently manufactured mobile air conditioners include the following

More information

Window Y9USC/E 09 / 12 / 18 B5R

Window Y9USC/E 09 / 12 / 18 B5R Window Y9USC/E 09 / 12 / 18 B5R SERVICE MANUAL Y9USC-09 B5R; Y9USE-09 B5R Y9USC-12 B5R; Y9USE-12 B5R Y9USC-18 B5R; Y9USE-18 B5R SM-Y9USC-E-09-18GB 03-07 1. Precaution... 2 1.1 safety Precaution... 2 1.2

More information

Installation, Operation & Maintenance

Installation, Operation & Maintenance Installation, Operation & Maintenance Contura 5G Series R410a High Ambient & High Efficiency MS-SVX041A-EN 1 Contents 1. Precaution 1.1 Safety Precuation 03 1.2 Warning 03 2. Product Specifications 06

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL TECHNICAL & SERVICE MANUAL CASSETTE TYPE AIR-CONDITIONER (One-way cassette) FSK-94HF FI-SM-040830 One-way Cassette Air-conditioner Table of Contants Part 1. Product Features 2 Part 2. Specification 3 Part

More information

Four-way Cassette Type

Four-way Cassette Type Four-way Cassette Type Part 1. Product Features 1) Low operation noise ---Streamline plate ensures quietness ---Creates natural and comfortable environment 2) Efficient cooling ---Equal, fast and wide

More information

Product Data FEATURES AND BENEFITS. QHF 50Hz Heat Pump Inverter Single Phase 2.5kW to 8.0kW

Product Data FEATURES AND BENEFITS. QHF 50Hz Heat Pump Inverter Single Phase 2.5kW to 8.0kW 0Hz Heat Pump Inverter Single Phase.kW to 8.0kW turn to the experts Product Data FEATURES AND BENEFITS AVAILABLE SIZES: Nominal capacity are available from.kw through 8.0kW to meet the needs of residential

More information

Floor-Standing Type(S2 Series)

Floor-Standing Type(S2 Series) Floor-Standing Type(S2 Series) Model: MFS2-24CR(N2), MFS2-24HR(N2), MFS2-24AR(N2), MFS2-48CR(N2), MFS2-48AR(N2) Part 1. Product Features Strong air supply. Wide angle and long distance air supply. Easy

More information

TAC-09CS/K TAC-12CS/K TAC-18CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-12CHS/K TAC-18CHS/K TAC-24CHS/K

TAC-09CS/K TAC-12CS/K TAC-18CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-12CHS/K TAC-18CHS/K TAC-24CHS/K TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE040427 Models TAC-07CS/K TAC-09CS/K TAC-2CS/K TAC-8CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-2CHS/K TAC-8CHS/K TAC-24CHS/K CONTENTS. IMPORTANT

More information

High Wall Split Systems Cool Only 9K - 12K - 18K - 24K. Auto. Auto. Fan Speed. Smart LCD Wireless Control. Auto Mode.

High Wall Split Systems Cool Only 9K - 12K - 18K - 24K. Auto. Auto. Fan Speed. Smart LCD Wireless Control. Auto Mode. HFC4 1 0 A 0-40V ~, 0Hz 1Ph High Wall Split Systems Cool Only 9K - 1K - 18K - 4K R-410A IAQ $ Auto Auto Fan Speed Timer s Easy Flexible Installation Smart LCD Wireless Control Auto Mode Auto Restart Easy

More information

V ~, 50Hz 1Ph. High Wall Split Systems Heat Pump 9K - 12K - 18K - 24K - 28K. Auto. Auto Fan Speed. Auto. Smart LCD Wireless Control.

V ~, 50Hz 1Ph. High Wall Split Systems Heat Pump 9K - 12K - 18K - 24K - 28K. Auto. Auto Fan Speed. Auto. Smart LCD Wireless Control. HFC4 1 0 A 0-40V ~, 0Hz 1Ph High Wall Split Systems Heat Pump 9K - 1K - 18K - 4K - 8K R-410A Compressor Super Quiet AMS Anti-dust Filters Auto Fan Speed Timer Functions Defrost Protection Smart LCD Wireless

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASY9USCCW ASY9USCCW ASY12USCCW Outdoor unit AOY9USCC AOY9UFCC AOY12USCC CONTENTS SPECIFICATIONS.................. 1 OUTLINE AND DIMENSIONS.........

More information

UCV CONDENSING UNITS SPECIFICATIONS 1. Specifications

UCV CONDENSING UNITS SPECIFICATIONS 1. Specifications UCV CONDENSING UNITS SPECIFICATIONS 1. Specifications Model UCV-76C UCV-96C Code 220075900040 220075900020 Power supply V- Ph-Hz 380-415~3~50 Capacity Btu/h 76000 96000 Cooling Input W 8100 10000 Rated

More information

Blanc ON-OFF Series. Service Manual 2016

Blanc ON-OFF Series. Service Manual 2016 Blanc ON-OFF Series Service Manual 2016 MSMA1A-07HRN1 / MOAB02-07HN1 MSMA1A-09HRN1 / MOAB02-09HN1 MSMA1B-12HRN1 / MOBA01-12HN1 MSMA1C-18HRN1 / MOBA03-18HN1 MSMA1D-24HRN1 / MOCA02-24HN1 1 Blanc On-off DM16-01.01.07en

More information

Cassette SERVICE MANUAL. YKHC 18 to 48 YKHC 18 YKHC 24 YKHC 30 YKHC 36 YKHC 48 SM-YKHC-18-48GB 03-07

Cassette SERVICE MANUAL. YKHC 18 to 48 YKHC 18 YKHC 24 YKHC 30 YKHC 36 YKHC 48 SM-YKHC-18-48GB 03-07 Cassette YKHC 18 to 48 SERVICE MANUAL YKHC 18 YKHC 24 YKHC 30 YKHC 36 YKHC 48 SM-YKHC-18-48GB 03-07 How to read the model? * * * Y K H C 24 F S B A A A Range: F = Floor standing H = High wall M = Master

More information

SERVICE MANUAL INVEST HEAT PUMP DC INVERTER SPLIT WALL-MOUNTED TYPE MSC-24/QD FP MSH-24/QD FP

SERVICE MANUAL INVEST HEAT PUMP DC INVERTER SPLIT WALL-MOUNTED TYPE MSC-24/QD FP MSH-24/QD FP SERVICE MANUAL INVEST HEAT PUMP DC INVERTER SPLIT WALL-MOUNTED TYPE MSC-24/QD FP MSH-24/QD FP V1.0 Nov, 2009 CONTENTS 1. Precaution... 1 1.1 Safety Precaution...1 1.2 Warning... 1 2. Function... 4 3. Dimension...

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models CONTENTS

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models CONTENTS SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASY9USCCW ASY9USCCW ASY12USCCW Outdoor unit AOY9USCC AOY9UFCC AOY12USCC CONTENTS SPECIFICATIONS.................. 1 OUTLINE AND DIMENSIONS.........

More information

MODEL: CCT 301 INV CCT 501 INV CCT 70 INV-S CCT 100 INV-S CCT 140 INV-S CCT 170 INV-S

MODEL: CCT 301 INV CCT 501 INV CCT 70 INV-S CCT 100 INV-S CCT 140 INV-S CCT 170 INV-S MODEL: CCT 301 INV CCT 501 INV CCT 70 INV-S CCT 100 INV-S CCT 140 INV-S CCT 170 INV-S Compact Four-way Cassette Type 1. Features... 2. Specification... 3. Dimension... 4. Service Space... 5. Wiring Diagram...

More information

Operating Functions Temperature Parameters

Operating Functions Temperature Parameters Operating Functions Temperature Parameters Room set temperature (T set) Room ambient temperature (T amb) Fundamental Functions After powered on, no matter when the compressor is started, the time interval

More information

[U] Serie MOV. Manual de Ingeniería

[U] Serie MOV. Manual de Ingeniería [U] Serie MOV Uniidades Condensadoras (Fllujjo Verttiicall) 6..3,, 8 y 12..5 Ton Manual de Ingeniería - 112- Outdoor Units_MOV 1. Specifications.... 2. Dimension... 3. Service Space. 4. Piping Diagrams

More information

The latest innovation in cool 7 YEAR 1 YEAR WARRANTY ON PARTS WARRANTY ON COMPRESSORS

The latest innovation in cool 7 YEAR 1 YEAR WARRANTY ON PARTS WARRANTY ON COMPRESSORS The latest innovation in cool 7 YEAR WARRANTY ON COMPRESSORS 1 YEAR WARRANTY ON PARTS Engineered to be both aesthetically pleasing and energy-efficient, Katashi air conditioning units bring the latest

More information

TCL SERVICE MANUAL. Models WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS. No.TE CONTENTS

TCL SERVICE MANUAL. Models WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS. No.TE CONTENTS TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE031229 Models TAC-07CS/K TAC-09CS/K TAC-12CS/K TAC-18CS/K TAC-24CS/K TAC-07CSC/K TAC-09CSC/K TAC-12CSC/K TAC-18CSC/K TAC-24CSC/K TAC-07CHS/K

More information

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA 0.8180.472.0 07/2005 Page 1. SPECIFICATIONS 3 1-1 Unit Specifications 3 1-2 Major Component Specifications 4 2. DIMENSIONAL DATA 6 2-1 Unit Dimensions 6 3. ELECTRICAL

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AO* R09LECN AO* R12LECN

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AO* R09LECN AO* R12LECN SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS* A09LEC AS* A12LEC AO* R09LECN AO* R12LECN R410A CONTENTS 1. DESCRIPTION OF EACH CONTROL

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASY9USCCW ASY9USCCW ASY12USCCW Outdoor unit AOY9USCC AOY9UFCC AOY12USCC CONTENTS SPECIFICATIONS................................... 1

More information

KSIM20912-H216 KSIM30912-H216 KSIM40912-H216

KSIM20912-H216 KSIM30912-H216 KSIM40912-H216 SERVICE MANUAL KLIMAIRE AIRCONDITIONER KSIM DC INVERTER MULTI TYPE KSIM20912-H216 KSIM30912-H216 KSIM40912-H216 DC MULTI OUTDOOR UNITS CONTENTS 1. General information of Outdoor Units...3 2 Features...4

More information

Contents. Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79

Contents. Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79 MCAC-TSM-2008-02 Contents Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79 Contents i MCAC-TSM-2008-02 Introduction Introduction Midea Mini Unitary

More information

MANUAL DE INGENIERIA. Part 1 General Information... 1 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 30

MANUAL DE INGENIERIA. Part 1 General Information... 1 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 30 MANUAL DE INGENIERIA Evaporadora Sopladora 'MVA' con Condensadora 'MOV' - Blue Star Part 1 General Information... 1 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 30 Part 1 General Information 1. Model

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

Service manual. MIV V4+ Mini

Service manual. MIV V4+ Mini DM12-01.01.05en Service manual MIV V4+ Mini DC INVERTER R410A (~220V, 50Hz, 1Ph) MVUH80A-VA1 Contents Part 1 General Information... 1 Part 2 Outdoor Units... 6 Part 3 Installation... 44 DM12-01.01.05en

More information

BTU Units WORKING PROGRAM MANUAL

BTU Units WORKING PROGRAM MANUAL 9000-24000BTU Units WORKING PROGRAM MANUAL SUMMARIZE FUNCTIONS & OPERATION MODES TIMER, SLEEP MODE, FAN SPEED PROTECTION FUNCTIONS EMERGENCY SWITCH TEST GUIDE MEMORY FUNCTIONS SUMMARIZE The Operation Modes

More information

CEILING CONCEALED DUCT R410A 60HZ 3D INVERTER CONTROL 2017 TECHNICAL MANUAL

CEILING CONCEALED DUCT R410A 60HZ 3D INVERTER CONTROL 2017 TECHNICAL MANUAL TM_DUCT_60R410A_3D INVERTER_US_S_NA_171113 CEILING CONCEALED DUCT R410A 60HZ 3D INVERTER CONTROL 2017 TECHNICAL MANUAL Table of Contents Page 1.... 4 1. Model Reference 2. General 3. Dimensional Drawings

More information

F SERIES ON-OFF SERIES. Service Manual 2016

F SERIES ON-OFF SERIES. Service Manual 2016 F SERIES ON-OFF SERIES Service Manual 2016 CONTENTS 1. Precaution... 3 1.1 Safety Precaution... 3 1.2 Warning... 3 2. Function... 6 3. Dimension... 7 3.1 Indoor Unit... 7 3.2 Outdoor Unit... 9 4. Refrigerant

More information

R410 a. Air Conditioners. Residential and commercial. R410 a

R410 a. Air Conditioners. Residential and commercial. R410 a Fresh Aireasy Breathe R410 a Air Conditioners Residential and commercial R410 a Airco Branded Products The Airco brand dates back to 1949 when it was first launched into the local market. This brand has

More information

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA ARGO 245C / 3SC Cooling only model ARGO 235H / 3HP Heat pump model 0.8180.405.2 09/2006 Table of contents Page A SPECIFICATIONS 1) Unit specifications 3

More information

PRODUCT LINE-UP Residential & Light Commercial air conditioners

PRODUCT LINE-UP Residential & Light Commercial air conditioners PRODUCT LINE-UP Residential & Light Commercial air conditioners Carrier air conditioning Energy savings Maximum energy savings thanks to accurate digital power control and super-efficient compressor. Comfort

More information

Part 1 General Information... 1 Part 2 Indoor Units... 7 Part 3 Outdoor Units Part 4 Installation Part 5 Control...

Part 1 General Information... 1 Part 2 Indoor Units... 7 Part 3 Outdoor Units Part 4 Installation Part 5 Control... MCAC-UTSM-2008-11 Contents Part 1 General Information... 1 Part 2 Indoor Units... 7 Part 3 Outdoor Units... 88 Part 4 Installation... 127 Part 5 Control... 136 The specifications, designs, and information

More information

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF AOU 9RLFW AOURLFW R40A CONTENTS. DESCRIPTION OF EACH CONTROL OPERATION. COOLING

More information

Mini Split Air Conditioners and Heat Pump

Mini Split Air Conditioners and Heat Pump new improved design Mini Split Air Conditioners and Heat Pump TECHNOLOGY Environment concern is a priority all over the world. Environment concern is our responsibility and working philosophy. 140 105

More information

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Cassette type Duct type Ceiling type INVERTER AO* G45LETL AO* G54LETL

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Cassette type Duct type Ceiling type INVERTER AO* G45LETL AO* G54LETL SPLIT TYPE ROOM AIR CONDITIONER Cassette type Duct type Ceiling type INVERTER SERVICE INSTRUCTION Models Indoor unit AU* G45LRLA AR* G45LMLA AR* G45LHTA AB* G45LRTA Outdoor unit AO* G45LETL AO* G54LETL

More information

3. INDOOR UNIT OPERATION

3. INDOOR UNIT OPERATION 3. INDOOR UNIT OPERATION INDOOR UNIT OPERATION 3- FAN CONTROL 3-- Fan Speed Setting Fan speed setting Press the FAN CONTROL button to set the fan speed. AUTO HIGH MED LOW 3-- "AUTO" Position. COOL OPERATION

More information

SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz)

SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz) SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz) Indoor unit MS6YF Outdoor unit MR6YF CONTENTS SPECIFICATIONS... OUTLINE AND DIMENSIONS... REFRIGERANT SYSTEM DIAGRAM.... CIRCUIT DIAGRAM... INDOOR PCB

More information

AIR CONDITIONING SYSTEMS WALL MOUNTED UNIT

AIR CONDITIONING SYSTEMS WALL MOUNTED UNIT AIR CONDITIONING SYSTEMS WALL MOUNTED UNIT SERVICE MANUAL MODELS: L4VI32-18/L4VO32-18 L4VI32-24/L4VO32-24 ENGLISH Table of Contents Part Ⅰ : Technical Information...1 1. Summary...1...2...3 2.2 Operation

More information

NORTH AMERICAN HVAC PRODUCTS LTD. Tel: Fax: DC Inverter Single Zone Split Wall-Mounted Type

NORTH AMERICAN HVAC PRODUCTS LTD. Tel: Fax: DC Inverter Single Zone Split Wall-Mounted Type NORTH AMERICAN HVAC PRODUCTS LTD Tel: 604-4308496 Fax: 1-866-9034371 www.northamericanhvac.com Service Manual DC Inverter Single Zone Split Wall-Mounted Type Model Refrigerant type Power supply MSV1-18HRDN1-MQ0

More information

Miraco MISR REFRIGERATION & AIR CONDITIONING MFG. CO.

Miraco MISR REFRIGERATION & AIR CONDITIONING MFG. CO. MISR REFRIGERATION & AIR CONDITIONING MFG. CO. COOL EER HEAT COP 0V ~ 50Hz 1Ph Inverter High Wall Split Systems For Energy Saving Heat Pump 1K - 18K - 4K DC Inverter R-410A Inverter Technology R-410A HFC

More information

COLDWAVE. Portable Air Conditioner. Model MPPD-12CRN BTU/h 110V/1Ph/60Hz R410A

COLDWAVE. Portable Air Conditioner. Model MPPD-12CRN BTU/h 110V/1Ph/60Hz R410A COLDWAVE Portable Air Conditioner 12000 BTU/h 110V/1Ph/60Hz R410A Model MPPD-12CRN1 Features: 4 Speed Fan Ion Generator Sleep Mode Timer Auto/Cool/Dry Mode Swing Function Follow Me Temperature Sensor Swing

More information

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467. SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-HC35VA- E2 and MUZ-HC35VAB- E2 have been added. Please void OBH467 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH467 REVISED EDITION-B

More information

SPLIT TYPE AIR CONDITIONER WAS-09HSTD WINTAIR

SPLIT TYPE AIR CONDITIONER WAS-09HSTD WINTAIR SPLIT TYPE AIR CONDITIONER SERVICE MANUAL WAS-09HSTD WINTAIR Type of contents 1. OPERATION RANGE 2. SPECIFICATION 3. INSTALLATION 4. REFRIGERANT FLOW DIAGRAM 5. ELECTRICAL DATA 6. CONTROL MODE 7. TROUBLE

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G24LFL AO*G24LFCC AO*G30LFT

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G24LFL AO*G24LFCC AO*G30LFT SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS*G4LFCA AS*G4LFCC AS*G0LFCA AO*G4LFL AO*G4LFCC AO*G0LFT R40A CONTENTS. DESCRIPTION OF EACH

More information

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

Room Air Conditioner CONTENTS CS-E9BKP CU-E9BKP5 CS-E12BKP CU-E12BKP5. Order No: MAC C2

Room Air Conditioner CONTENTS CS-E9BKP CU-E9BKP5 CS-E12BKP CU-E12BKP5. Order No: MAC C2 Order No: MAC008C Room Air Conditioner CS-E9BKP CU-E9BKP5 CS-EBKP CU-EBKP5 CONTENTS Page Page Features Functions Product Specifications 6 Dimensions 0 5 Refrigeration Cycle Diagram 6 Block Diagram 7 Wiring

More information

Service Manual AIR CONDITIONER

Service Manual AIR CONDITIONER Service Manual AIR CONDITIONER DC INVERTER MULTI TYPE This manual applies to models: High Wall Duct Cassette Console Universal CDU 42QHF009DS 42QHF012DS 42QHF018DS 42QSM009DS 42QSM012DS 42QSM018DS 42QTD009DS

More information

R410A50Hz Universal Outdoor Series Technical Manual

R410A50Hz Universal Outdoor Series Technical Manual Outdoor Unit R410A 50Hz Universal Outdoor Series Technical Manual 2013 Version LCAC/2.0/201308 I GD Chigo Heating & Ventilation Equipment Co., Ltd. Content Content PART 1.General Information... 1 1.Nomenclature...

More information

SPECIFICATIONS for AIR CONDITIONING CONTROLLER ZONE CONTROL

SPECIFICATIONS for AIR CONDITIONING CONTROLLER ZONE CONTROL SPECIFICATIONS for AIR CONDITIONING CONTROLLER ZONE CONTROL 1. INTROUCTION Zone control is a two pieces fan coil thermostat available for Heat/Cool versions. Its application is for the duct type system

More information

SERVICE MANUAL Room Air Conditioner Multi Split Type Indoor units Light Commercial Series

SERVICE MANUAL Room Air Conditioner Multi Split Type Indoor units Light Commercial Series SERVICE MANUAL Room Air Conditioner Multi Split Type Indoor units Light Commercial Series FSKMIF-71AE2-EU FSKMIF-91AE2-EU FSKIF-121AE2-EU FSKMI-181AE2-EU FSLMIF-71AE2 FSLMIF-91AE2 FSLIF-121AE2 FSLMI-180AE2

More information

SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS

SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS SPECIFICATION... 1 FUNCTIONS... 5 SERVICE FUNCTION EXPLANATION... 7 OPERATION DETAILS... 8 TROUBLESHOOTING GUIDE... 13 PERFORMANCE

More information

SERVICE MANUAL SPLIT WALL-MOUNTED TYPE MODELS MWCOHC30S/MRCOHC30AS MWCOHC36S/MRCOHC36AS

SERVICE MANUAL SPLIT WALL-MOUNTED TYPE MODELS MWCOHC30S/MRCOHC30AS MWCOHC36S/MRCOHC36AS SERVICE MANUAL SPLIT WALL-MOUNTED TYPE MODELS MWCOHC30S/MRCOHC30AS MWCOHC36S/MRCOHC36AS CONTENTS 1. Precaution... 1 1.1 Safety Precaution... 1 1.2 Warning... 1 2. Function... 6 3. Dimension... 7 3.1 Indoor

More information

Technical Manual. R410A 50Hz Universal Outdoor Series Inverter type. R410A50Hz Universal Outdoor Series Technical Manual LCAC/2016.

Technical Manual. R410A 50Hz Universal Outdoor Series Inverter type. R410A50Hz Universal Outdoor Series Technical Manual LCAC/2016. Outdoor Unit R410A 50Hz Universal Outdoor Series Inverter type Technical Manual LCAC/2016.1 I GD Chigo Heating & Ventilation Equipment Co., Ltd. Content Part 1. General Information... 1 1. Nomenclature...

More information

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control...

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control... R410A Tropical Split Type AC Technical Manual Content Content Part 1 General Information... 2 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 88 Part 4 Installation... 120 Part 5 Control... 154 Indoor

More information

VMI-1102-A SERVICE MANUAL AIRCONDITIONER DC INVERTER MULTI TYPE MSV1I-09HRDN1-M TAS-09MVHN TAS-12MVHN INDOOR VERTU DC INVERTER MULTI SERIES

VMI-1102-A SERVICE MANUAL AIRCONDITIONER DC INVERTER MULTI TYPE MSV1I-09HRDN1-M TAS-09MVHN TAS-12MVHN INDOOR VERTU DC INVERTER MULTI SERIES VMI-1102-A SERVICE MANUAL AIRCONDITIONER DC INVERTER MULTI TYPE MSV1I-09HRDN1-M TAS-09MVHN TAS-12MVHN INDOOR VERTU DC INVERTER MULTI SERIES CONTENTS 1. Precaution... 1 1.1 Safety Precaution...1 1.2 Warning...1

More information

Hi - Wall Split Systems. Super Quiet. Auto. Mode. Wireless Control. Smart Airflow ECO ECO. Function SLEEP. Vertical Auto Swing.

Hi - Wall Split Systems. Super Quiet. Auto. Mode. Wireless Control. Smart Airflow ECO ECO. Function SLEEP. Vertical Auto Swing. R407C 220-240V ~, 50Hz Hi - Wall Split Systems Technology Tropical Compressor Super Quiet Auto Mode Auto Restart Easy Flexible Installation IAQ Anti-dust Filters AMS AMS Wireless Control Independent Dehumidification

More information

K sin. Mini Split Air Conditioners and Heat Pump

K sin. Mini Split Air Conditioners and Heat Pump Mini Split Air Conditioners and Heat Pump K sin Environment concern is a priority all over the world. Environment concern is our responsibility and working philosophy. 140 105 70 35 Noise Level db(a) Level

More information

CEILING type (60Hz) SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models

CEILING type (60Hz) SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models SPLIT TYPE ROOM AIR CONDITIONER CEILING type (60Hz) Models Indoor unit ABU6RSLX Outdoor unit AOU6RLX CONTENTS SPECIFICATIONS....................... OUTLINE AND DIMENSIONS............. REFRIGERANT SYSTEM

More information

CONTROL PANEL INSTRUCTIONS RSQ-4

CONTROL PANEL INSTRUCTIONS RSQ-4 CONTROL PANEL INSTRUCTIONS RSQ-4 FOR SIRAC AIR TO WATER HEAT PUMP (SINGLE COMPRESSOR, AIR TO WATER) 1) System Configuration This system is composed of mainboard and wire control panel. 146mm Φ4 4 Mainboard

More information

MHH. 13 SEER High Efficiency R410a. SPECIFICATION sheet

MHH. 13 SEER High Efficiency R410a. SPECIFICATION sheet Air Conditioning and Heating SPECIFICATION sheet MHH 13 SEER High Efficiency R410a Split System Heat Pump Standard features: R410a system High efficiency compressor Compact design for easy installation

More information

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G09LTCN AO*G12LTCN AO*G14LTCN

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G09LTCN AO*G12LTCN AO*G14LTCN SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS*G09LTCB AS*GLTCB AS*G4LTCB AO*G09LTCN AO*GLTCN AO*G4LTCN R40A CONTENTS. DESCRIPTION OF EACH

More information

HIGH-EFFICIENCY DUCTLESS INDOOR COMFORT

HIGH-EFFICIENCY DUCTLESS INDOOR COMFORT UP TO 15 SEER Performance MINI-SPLIT SYSTEM UNITS AIR CONDITIONING AND HEAT PUMPS COMPLETE ROOM COMFORT WITH EASY-TO-USE REMOTE CONTROL HIGH-EFFICIENCY DUCTLESS INDOOR COMFORT The Goodman brand offers

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOU9RLS2H AOU12RLS2H AOU15RLS2H

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOU9RLS2H AOU12RLS2H AOU15RLS2H SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU9RLS ASURLS ASU5RLS AOU9RLSH AOURLSH AOU5RLSH R40A CONTENTS. DESCRIPTION OF EACH CONTROL

More information

NORTH AMERICAN HVAC PRODUCTS LTD. Tel: Fax: DC Inverter Single Zone Split Wall-Mounted Type

NORTH AMERICAN HVAC PRODUCTS LTD. Tel: Fax: DC Inverter Single Zone Split Wall-Mounted Type NORTH AMERICAN HVAC PRODUCTS LTD Tel: 604-4308496 Fax: 1-866-9034371 www.northamericanhvac.com Service Manual DC Inverter Single Zone Split Wall-Mounted Type Vertu series Model Refrigerant type Power supply

More information

6. DUCT TYPE AR 60FUAK, AR 60UUAK

6. DUCT TYPE AR 60FUAK, AR 60UUAK R410A 6. AR 60FUAK, AR 60UUAK ART60UUAK D2D_AR010E/04 2006.05.30 - (06-01) - 6-1. FEATURE MODELS : AR 60FUAK / AO 60FMAYT AR 60UUAK / AO 60UMAYT ART60UUAK / AOT60UMAYT FEATURES Universal design indoor

More information

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH502 Wireless type Models MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA Indoor unit service manual MSZ-D NA Series (OBH501) MSY-D

More information

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit SPLIT TYPE AIR CONDITIONER CASSETTE type (50Hz) Models Indoor unit Outdoor unit RCW-12HA RO-12HB C O N T E N T S SPECIFICATIONS........................................ 1 OUTLINE AND DIMENSIONS..............................

More information

PRODIGY 3D Inverter. Technical Manual

PRODIGY 3D Inverter. Technical Manual PRODIGY 3D Inverter Technical Manual CONTENTS 1. Precaution... 3 1.1 Safety Precaution... 3 1.2 Warning... 3 2. Function and specifications... 5 3. Dimension... 10 3.1 Indoor Unit... 10 3.2 Outdoor Unit...

More information

Hi - Wall Split Systems 12K - 18K - 24K

Hi - Wall Split Systems 12K - 18K - 24K R22 220-240V ~ 50Hz 1Ph Hi - Wall Split Systems 12K - 18K - 24K Technology Tropical Compressor Super Quiet Auto Auto Fan Speed Auto Restart Function Self diagnostic function Active Carbon Electrostatic

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC Revision E: MUZ-FH25VE- E4, ER4, ET3, MUZ- FH35VE- E3, ER3, ET3 and MUZ- FH50VE- E2, ER2, ET2 have been added. Please void OBH624 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624

More information

Part 3 Troubleshooting

Part 3 Troubleshooting Part Troubleshooting What is in this part? This part contains the following chapters: Chapter See page Troubleshooting 2 Error Codes: Hydro-box 7 Error Codes: Outdoor Units Error Codes: System Malfunctions

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information

Service Manual. Contents. 1.Important Notice Technical Specification Operation Details Wiring Diagram...

Service Manual. Contents. 1.Important Notice Technical Specification Operation Details Wiring Diagram... Split type Wall Mounted Air Conditioner E series Service Manual Contents 1.Important Notice...1 2.Technical Specification...2-9 3.Operation Details...10-13 4.Wiring Diagram...14-15 5.Troubleshooting Guide...16-23

More information

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD.

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD. Technical Support Division 2017-4-25 New CMV System - Floor ceiling Indoor Unit 1 1. External appearance 2. Nomenclature 3. Specifications 4. Dimensions 5. Service space 6. Piping diagram 7. Wiring diagram

More information

ASU18RLF ASU24RLF AOU18RLXFWH AOU24RLXFWH CONTENTS WALL MOUNTED TYPE ROOM AIR CONDITIONER FOR EXTRA LOW TEMP. DISTRICT

ASU18RLF ASU24RLF AOU18RLXFWH AOU24RLXFWH CONTENTS WALL MOUNTED TYPE ROOM AIR CONDITIONER FOR EXTRA LOW TEMP. DISTRICT WALL MOUNTED TYPE ROOM AIR CONDITIONER FOR EXTRA LOW TEMP. DISTRICT Indoor unit ASU8RLF ASURLF Outdoor unit AOU8RLXFWH AOURLXFWH CONTENTS SPECIFICATIONS.................... DIMENSIONS........................

More information

SERVICE MANUAL 42QHF009DS* 42QHF012DS* 42QHF018DS* 42QHF022DS* 38QUS009DS* 38QUS012DS* 38QUS018DS* 38QUS022DS* Indoor unit.

SERVICE MANUAL 42QHF009DS* 42QHF012DS* 42QHF018DS* 42QHF022DS* 38QUS009DS* 38QUS012DS* 38QUS018DS* 38QUS022DS* Indoor unit. SERVICE MANUAL Indoor unit Outdoor unit 42QHF009DS* 42QHF012DS* 42QHF018DS* 42QHF022DS* 38QUS009DS* 38QUS012DS* 38QUS018DS* 38QUS022DS* INDEX PART1 GENERAL INFORMATION PART2 ELECTRICAL DIAGRAM PART3 TROUBLE

More information

Air Conditioner CONTENTS

Air Conditioner CONTENTS ORDER NO. MAC0509068C2 Air Conditioner CS-F24DD1E5 CU-B24DBE5 CS-F28DD1E5 CU-B28DBE5 CS-F28DD1E5 CU-B28DBE8 CS-F34DD1E5 CU-B34DBE5 CS-F34DD1E5 CU-B34DBE8 CS-F43DD1E5 CU-B43DBE8 CS-F50DD1E5 CU-B50DBE8 CONTENTS

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA

More information

DC Inverter Multi-split System Technical Manual - 50Hz/R410a

DC Inverter Multi-split System Technical Manual - 50Hz/R410a DC Inverter Multi-split System Technical Manual - 50Hz/R410a A/1/LCAC/2/TM/1.0/201111 Content Contents Part 1. General Information... 1 1. Features... 1 2. Nomenclature... 3 3. Products Line-up... 5 4.

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A09LEC AS A12LEC OUTDOOR AO R09LECN AO R12LECN 1.INDOOR UNIT : AS A09LEC AS A12LEC DTR_AS047E_01 2010.10.05 1. INDOOR UNIT CONTENTS

More information

Mono DC. VERTU MONO Split DC Inverter Air Conditioner SERVICE MANUAL MSV1-18HRDN1-MQ0W. Revision A: , Content updated.

Mono DC. VERTU MONO Split DC Inverter Air Conditioner SERVICE MANUAL MSV1-18HRDN1-MQ0W. Revision A: , Content updated. VERTU MONO Split DC Inverter Air Conditioner SERVICE MANUAL Mono DC Revision A: 1305080001, Content updated. Model Numbers: 0 MSV1-09HRFN1-MT0W MSV1-12HRDN1-MQ0W MSV1-24HRDN1-MQ0W MSV1-12HRFN1- MT0W MSV1-18HRDN1-MQ0W

More information

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 Indoor unit service manual MSZ-DM VA Series (OBH750) CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES

More information

SERVICE MANUAL CONDENSING UNIT ASE-18AH, ASE-24AH, ASE-36AH, ASE-48AH, ASE-60AH

SERVICE MANUAL CONDENSING UNIT ASE-18AH, ASE-24AH, ASE-36AH, ASE-48AH, ASE-60AH SERVICE MANUAL CONDENSING UNIT ASE-18AH, ASE-24AH, ASE-36AH, ASE-48AH, ASE-60AH Outdoor Units - appearance 18,000Btu/h 30,000~36,000Btu/h 24,000Btu/h 48,000Btu/h-60,000Btu/h Model Names of Outdoor Units

More information

WORKING PROGRAM. Heating dehumidifying cooling T 27

WORKING PROGRAM. Heating dehumidifying cooling T 27 I. Functions and Operation Modes WORKING PROGRAM The operation modes of the unit run like the following: Auto cooling dehumidifying heating --------------------------------------- Note: Cooling only unit

More information