SECTION AXIAL FANS

Size: px
Start display at page:

Download "SECTION AXIAL FANS"

Transcription

1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections: 1. Section Mechanical Sound, Vibration, and Seismic Controls for HVAC Piping and Equipment : Product requirements for resilient mountings and snubbers for fans for placement by this section. 2. Section HVAC Insulation : Product requirements for power ventilators for placement by this section. 3. Section Metal Ducts : Product requirements for hangers for placement by this section. 4. Section Duct Accessories : Product requirements for Back-draft Dampers for placement by this section. 5. Section Wiring Connections : Execution and product requirements for connecting equipment specified by this section. 6. Section Mechanical Identification. 1.2 SUMMARY A. This Section includes propeller fans, equipment room filter vent sets, direct drive vaneaxial fans, belt driven vaneaxial fans, ceiling-mounted paddle fans, motors and fan accessories 1.3 REFERENCES A. ABMA STD 9 (American Boiler Manufacturers Association) - Load Ratings and Fatigue Life for Ball Bearings. B. ABMA STD 11 (American Boiler Manufacturers Association) - Load Ratings and Fatigue Life for Roller Bearings. C. AMCA 99 (Air Movement and Control Association) - Standards Handbook. D. AMCA 210 (Air Movement and Control Association) - Laboratory Methods of Testing Fans for Rating. E. AMCA 300 (Air Movement and Control Association) - Reverberant Room Method for Sound Testing of Fans. F. AMCA 301 (Air Movement and Control Association) - Methods for Calculating Fan Sound Ratings from Laboratory Test Data. G. NEMA MG1 (National Electrical Manufacturers Association) - Motors and Generators. H. UL 705 (Underwriters Laboratories, Inc.) - Power Ventilators. Page 1 of 17

2 1.4 PERFORMANCE REQUIREMENTS A. Project Altitude: Base air ratings on actual site elevations. B. Project Altitude: Base air ratings on sea-level conditions. C. Operating Limits: Classify according to AMCA 99. D. Fan Unit Schedule: The following information is described in an equipment schedule at the end of this Section. E. Fan Unit Schedule: The following information is described in an equipment schedule on the Drawings. 1.5 SUBMITTALS 1. Fan performance data including capacities, outlet velocities, static pressures, sound power characteristics, motor requirements, and electrical characteristics. 2. Fan arrangement including wheel configuration, inlet and discharge configurations, and required accessories. A. General: Submit each item in this Article according to the Conditions of the Contract and Specification Sections. B. No equipment shall be fabricated or delivered until receipt of approved shop drawings from the Owner. C. Provide the following information with each shop drawing submission. 1. Complete specification of the equipment which will be provided including all optional equipment. All equipment shall be tagged. Refer to "Mechanical Identification" Section for further requirements. 2. Submittal data shall show that all fans bear the AMCA Certified Performance Seal for both air and sound performance at the capacities specified on the Drawings. 3. Arrangement drawings showing proposed scroll arrangement, rotation, and discharge, drive arrangement, motor location, motor power connection location, access door location and drain connection locations as required. 4. Arrangement drawings including physical dimensions, support locations, identification of each component, and weight of fan assembly at each support location including drive and motor. Provide WR 2 for the fan wheel and drive assemblies, include individual WR 2 for each drive component. 5. Capacity and performance data corrected to actual operating temperature and altitude. Fan curves shall have operating points indicated. Refer to Engineering Service article in this section for actual fan curves and data required. 6. Motor data to verify motor type, efficiency and starting characteristics. 7. Wiring diagrams detailing wiring for power and control systems and differentiating clearly between manufacturer-installed wiring and field-installed wiring. 8. Fan noise characteristics including sound power levels for the 8 octave bands and a single sound power A-scale weighted level or sound levels in "Sones" Page 2 of 17

3 when the fan is operating at its peak horsepower output. Refer to Engineering Service article in this section for further data. 9. Blade position for vaneaxial fans. 10. Damper motor data for fan dampers controls, if applicable. 11. List of spare parts for one year's normal maintenance, including drive-belt part numbers where applicable. Include all "off the shelf" readily available purchased items on the list. List shall include subassembly part number (identifiable in maintenance manual or on shop drawings), manufacturer's name, manufacturer's part number and a part description. 12. Installation, operation, maintenance and lubrication instructions in shop manual format. D. Upon completion of the shop drawing submittal phase of the project, submit to the Owner for approval, three (3) copies of installation, operation and maintenance manuals which shall be in bound printed form. Each manual shall include one approved/reviewed copy of each item listed above. 1.6 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: Submit instructions for lubrication, motor and drive replacement, spare parts list, and wiring diagrams. 1.7 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years experience. B. Contractor: Company and company field staff specializing in performing Work of this section with minimum five years experience. 1.8 DELIVERY, STORAGE, AND HANDLING A. Protect motors, shafts, and bearings from weather and construction dust. 1.9 ENVIRONMENTAL REQUIREMENTS A. Do not operate fans for any purpose until ductwork is clean, filters in place, bearings lubricated, and fan has been test run under observation FIELD MEASUREMENTS A. Verify field measurements prior to fabrication EXTRA MATERIALS A. Supply two sets of belts for each fan size/type QUALITY CONTROL A. Electrical Component Standard: Provide components that comply with NFPA 70 and that are listed and labeled by UL where available. Page 3 of 17

4 B. Listing and Labeling: Provide electrically operated fixtures specified in this Section that are listed and labeled. 1. The Terms "Listed" and "Labeled": As defined in the National Electrical Code, Article Listing and Labeling Agency Qualifications: A "Nationally Recognized Testing Laboratory" (NRTL) as defined in OSHA Regulation C. AMCA Compliance: Provide products that are rated in accordance with AMCA Standard 210 and are licensed to use the AMCA Seal. D. NEMA Compliance: Motors and electrical accessories shall comply with NEMA standards WARRANTY A. The Fan Manufacturer shall warrant all equipment for one (1) year as described herein and as further required in the "Warranty" article of this Specification. B. Correct all critical defects within 24 hours following the Owner's verbal notification of a problem, for a period of one (1) year after acceptance by the Owner. A critical defect is defined as a defect in fan operation through bearing or shaft failure resulting from bearing burnout, or as a failure in fan operation resulting in belts breaking frequently. C. Correct all non-critical defects, such as excessive bearing noise or belt set replacement, within 30 days following the Owner's written notice, for a period of one (1) year after acceptance by the Owner. D. Acceptance date shall be considered date of issuance of a certificate of substantial completion. E. Failure to correct any defective work or equipment within 24 hours or within 30 days, as applicable, will render conduct negligent, in which case the Owner will be entitled to proceed with the correction of such defects at his discretion and to charge the Contractor cost plus 10% of the expenses incurred. F. The Contractor shall be responsible to repair all damage caused by any defect in the work or equipment, whose repair is covered under warranty. G. The Fan Manufacturer shall coordinate all labor and material provisions of the warranty with the Contractor ENGINEERING SERVICE A. The Fan Manufacturer shall furnish each fan with a motor which is 30% oversized and with capacity for a 10% increase in air flow and a corresponding 20% increase in total pressure. This increased capacity for each fan shall be based on an airflow and total pressure which are over and above the present and future values as scheduled on the Drawings. The Fan Manufacturer shall provide each fan with a drive which will meet the present capacity condition as scheduled on the Drawings. B. In addition to the design parameter stated above for increased capacity, the fan motor and drive selection shall be based on the following: Page 4 of 17

5 1. All fans shall be non-overloading. 2. The fan motor size shall be based on available sheave sizes, where fixed pitch sheaves are employed on both the motor and fan shafts. I.e. Based on the present or future scheduled condition for airflow and total pressure (whichever is worse) with replacement of the smaller sheave, the fan shall not overload. 3. The fan (single fan arrangements) shall be considered to be non-overloading when, with the fan operating 10 percent faster than the present (or future) scheduled conditions, a decrease in total pressure results in an increase in flow to 130% of the present (or future) scheduled air flow along the fan operating curve without the fan overloading. 4. Where dual fans are employed (two fans operating from a single plenum to another single plenum), the individual fans shall be considered to be non-overloading when, with the fans operating 10 percent faster than the present or future scheduled conditions, the fan is non-overloading on any part of its fan operating curve. 5. Per AMCA Publication 203, the following allowances shall be made for V-Belt Drive Losses: MOTOR BELT DRIVE MAXIMUM FAN HORSEPOWER LOSS (BHP) BRAKE HORSEPOWER 1/ / / / All motors shall be selected to operate with a service factor of 1.0 or less. Motors shall not be designed to operate over nominal motor horsepower. Page 5 of 17

6 C. The Fan Manufacturer's engineer shall prepare the following fan performance curves for submission: 1. Fan curve for present operating condition as scheduled on the drawing with proposed drive or fan blade setting. 2. Fan curve for future operating condition as scheduled on the drawing with proposed drive or fan blade setting. 3. Fan curve for fan speed 10 percent faster than for present (or future) operating condition, whichever is worse, as scheduled on the drawing with proposed drive or fan blade setting. Note: For proposed drive allow only one drive sheave to be changed. 4. For fans with motors 5 horsepower and larger, sound power levels when the fan is operating at its peak horsepower output shall be provided for each of the eight octave bands and for a single A-scale rated level. Power levels shall be in units of "db re 1pW". Power levels shall be provided for the present condition and the future condition and for the 10 percent faster condition listed above. 5. For fans with motors under 5 horsepower and for roof exhaust fans, sound levels shall be provided in "Sones" or in a manner similar to the larger fans at the Fan Manufacturer's option. 6. Correction factors shall be applied to the above curves for altitudes and for the lowest operating temperature. 7. Fan curves shall include allowances for fan inlet vanes, fan inlet boxes, fan inlet cones, and fan discharge cones which are provided by the Fan Manufacturer in conjunction with the individual fans. 8. Fan curves shall be constructed as follows: a. Flow in SCFM (ACFM) on the horizontal. b. Total or static pressure in inches of water gauge on the vertical. c. Fan brake horsepower at the fan shaft on the vertical (not including drive losses). d. Fan mechanical efficiency on the vertical. e. Any correction factors for the above shall be tabulated on the curve. f. Modifications to the above with varying positions of the fan inlet vanes of in-flight pitch fan blade controls from full open to full closed. g. A statement of the fan speed, the maximum fan speed, and of the maximum anticipated fan brake horsepower for the fan speed listed along any part of the fan curve. h. A statement of fan operating point with each of the four parameters (SCFM), (ACFM), Pressure, BHP, and Mechanical efficiency) listed. i. Note to Fan Manufacturer, generic fan curves which cover many sizes and speeds are not acceptable. All curves shall be tailored to the individual fan. j. Curves shall reflect operating parameters for standard air and non-standard air. Adjustments and calculations for fans moving non-standard air shall be provided. All corrections shall include elevation adjustments and temperature of air stream DELIVERY, STORAGE, AND HANDLING A. Deliver fans as factory-assembled units, to the extent allowable by shipping limitations, with protective crating and covering. B. Disassemble and reassemble units as required for movement to the final location following manufacturer's written instructions. C. Lift and support units with the manufacturer's designated lifting or supporting points. Page 6 of 17

7 D. The Fan Manufacturer shall identify shipments from the Fan Manufacturer and his suppliers with the Contractor's purchase order number. The Fan Manufacturer shall furnish a detailed list of parts in each shipment to permit satisfactory checking when received. E. The Fan Manufacturer shall tag and place separate parts too small to mark in containers plainly marked on outside as to contents and the Contractor's purchase order number. In shipping bolts, different kinds and sizes shall be kept separate, either by separate containers or partitions in same container. F. After loading equipment for shipment, the Fan Manufacturer shall notify the Contractor via telephone facsimile with the name of carrier, car number, description of equipment, order number, weight of heaviest piece, shipping point, date of shipment, and estimated time of arrival. G. The fans shall not be shipped until the Owner has given his verbal approval that the site has been prepared to a sufficient degree that it is ready for delivery PROJECT CONDITIONS A. Field Measurements: Verify dimensions by field measurements. Verify clearances. B. Do not operate fans until ductwork is clean, filters are in place, bearings are lubricated, and fans have been commissioned COORDINATION AND SCHEDULING A. Coordinate the size and location of concrete housekeeping pads as applicable. Cast anchor-bolt inserts into pad. Concrete reinforcement and formwork requirements are specified in Division 3 Sections. B. Coordinate the installation of roof curbs, equipment supports, and roof penetrations. Roof specialties are specified in Division 7 Sections EXTRA MATERIALS A. Furnish one set of belts for each belt-driven fan that match products installed, are packaged with protective covering for storage, and are identified with labels clearly describing contents. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated in the Work include, but are not limited to, the following: B. Manufacturers: Subject to compliance with requirements, provide products by one of the following: Page 7 of 17

8 1. Propeller Fans: a. Greenheck Fan Corp. b. Cook (Loren) Co. c. Twin City Fan & Blower Co. 2. Vaneaxial Fans: a. Greenheck Fan Corp. b. Cook (Coren) Co. c. Twin City Fan & Blower Co. 2.2 AIR MOVING EQUIPMENT-GENERAL A. All air moving equipment shall be licensed to bear the AMCA seal. The ratings for the fans shall be based on tests which are made in accordance with AMCA Standard 210 and which comply with the requirements of the AMCA Certified Rating Program. Fans shall be AMCA certified for both air moving capacity and sound performance. B. All fan drive arrangements and motor positions listed on the drawings shall be based on AMCA Standards. C. Refer to the drawings for actual fan scroll arrangements. D. All fans or the fan motors shall bear the Underwriter's Laboratory Label. 2.3 FAN DRIVES A. For belt-driven fans serving main air handling units, the Fan Manufacturer shall provide V-belt drives with a minimum service factor of 2.0 with all belts in service and of 1.3 with one belt broken. Drive horsepower ratings shall be based on the nominal fan motor horsepower. B. For all other applications the Fan Manufacturer shall provide V-belt drives with a service factor of 1.65 minimum based on nominal fan motor horsepower. C. V-belt drives for motor sizes up to 25 horsepower shall be adjustable type (plus or minus 10 percent) with the fan sheave being fixed and the motor sheave being adjustable; the drive shall be selected with the fan operating near the mid-point of the drive sheave based on the performance scheduled under the present condition. D. V-belt drives for motor sizes 30 horsepower and larger shall be fixed sheave type for both the fan and the motor and shall be selected based on the performance scheduled under the present condition. E. All exposed V-belt drives shall be enclosed in an OSHA approved removable belt cover with tachometer openings. F. The Fan Manufacturer shall provide all V-belts in matched sets for all initial installations and for warranty work. G. Under the base contract and after initial balancing, the Fan Manufacturer shall furnish the Air Balancing Subcontractor with the correct fixed pitch sheave(s) (with belts) to match Page 8 of 17

9 the air balance requirements. These sheaves shall be installed by the Contractor at no additional charge to the Owner. 2.4 PROTECTIVE COATINGS AND FINISHES A. Unless otherwise noted, all interior carbon steel surfaces in contact with the airstream shall be finished with the Fan Manufacturer's standard enamel finish. B. Unless otherwise noted, fans or fan parts constructed of aluminum or stainless steel will not require interior or exterior surfaces to be painted. C. On fume exhaust fans, when noted, all metal surfaces in contact with the exhaust airstream shall be finished with a DuPont or Heresite air-dried epoxy paint. The epoxy paint shall be applied in 3 even coats in accordance with the coating manufacturer's instructions; minimum final coating thickness shall be as scheduled. Each coat of epoxy paint shall be color-coded. All metal surfaces which are to receive an epoxy paint finish shall be sandblasted to bare metal and all metal edges shall be hand-rounded prior to applying the paint finish. D. Fans located indoors shall have the Fan Manufacturers standard enamel finish applied to the exterior of the fan. E. Standard (non-fume) fans located outdoors shall have the exterior of the fan finished with the same finish as the interior except the finished shall be of a thickness as scheduled. F. Fume exhaust fans located outdoors shall have the exterior of the fan finished with the same finish as the interior except the finished shall be of a thickness as scheduled. G. Fan shafts shall not be painted. 2.5 SPARK RESISTANT CONSTRUCTION A. Fans tagged shall be furnished with all parts of the fan, which are in contact with the air or gas handled, made of non-ferrous material to meet AMCA Type A spark-resistant construction. B. Fans tagged shall be furnished with a non-ferrous wheel and ring around the opening through which the shaft passes, to meet AMCA Type B spark-resistant construction. C. Fans tagged shall be furnished with a non-ferrous inlet cone and housing coverplate on the side opposite the inlet, to meet AMCA Type C spark-resistant construction. 2.6 FAN CONSTRUCTION CLASSIFICATION A. Fan construction classification shall be based on AMCA Class Standard AS B. Minimum fan construction class for this project is Class II or III. C. Fans shall be constructed in accordance with the following schedule: Page 9 of 17

10 2.7 PROPELLER FANS 1. Use Class I for outlet velocities up to 2000 FPM or pressures up to 2.5" w.g. 2. Use Class II for outlet velocities from 2000 up to 2750 FPM or pressures from 2.5" w.g. up to 4.5" w.g. 3. Use Class III for outlet velocities over 2750 FPM or pressures over 4.5" w.g. A. Provide propeller exhaust fans as scheduled on the drawings. B. Fans shall be constructed of cast aluminum or fabricated steel blades and a minimum 14-gauge steel mounting panel with rolled Venturi inlet finished with enamel paint. Fan wheel shall be statically and dynamically balanced. Fan shaft and motor shaft bearings shall be the permanently lubricated, heavy duty, sealed type. C. Fan drive shall be direct type or V-belt driven. Refer to Fan Drive article in this section for further requirements. D. All motors under 1/2 horsepower shall be single-phase type with permanent split capacitor design. Motors 1/2 horsepower and over shall be 3-phase. Refer to Section "Motors" for fan motor requirements. E. Fans shall be furnished with rear guard for fan motor and blades and motorized relief damper (operable louver) constructed with edge sealed aluminum blades, nylon bearings and stainless steel pins. Relief damper shall be painted color as selected by the Owner. F. Fans shall be AMCA-certified for both air and sound performance at the capacities listed on the Drawings. G. Fans shall be UL listed and shall have UL label affixed. H. Design Basis: Greenheck Direct Drives S or Belt Drive - SB. I. Accessories: The following accessories are required as indicated: 1. Gravity Shutters: Aluminum blades in aluminum frame, interlocked blades with nylon bearings. 2. Motor-Side Back Guard: Galvanized steel, conforming to OSHA specifications, removable for maintenance. 3. Wall Sleeve: Galvanized steel to match fan and accessory size. 4. Weathershield Hood: Galvanized steel to match fan and accessory size. 5. Weathershield Front Guard: Galvanized steel with expanded metal screen. 6. Variable-Speed Controller: Solid-state control to reduce speed from 100 percent to less than 50 percent. 7. Disconnect Switch: Nonfusible type, with thermal-overload protection mounted inside fan housing, factory wired through an internal aluminum conduit. 2.8 DIRECT DRIVE VANE A. Provide direct drive adjustable pitch or fixed pitch vaneaxial fans with arrangement and capacities as scheduled on the drawings. All scheduled capacities are without inlet or discharge cones. Page 10 of 17

11 B. Housings shall be tubular type to provide straight through airflow and shall be constructed of heavy gauge welded steel. Housings for fans 24 inches in size and larger shall be provided with access doors for inspection of the motor and fan wheel. Housings shall be furnished with stationary curved guide vanes, welded within the housing and located on the discharge side of the fan. C. Adjustable pitch fans shall have a wheel constructed of cast aluminum airfoil shaped blades with a cast aluminum hub. Manual blade adjustment shall be accomplished without removing wheel. Fixed pitch fans shall have a fan wheel constructed of steel blades. D. Fan motors shall be totally enclosed air over type, refer to Section "Motors" for further requirements. Electrical motor leads shall be extended to a junction box located on the outside of the fan housing. All motor bearings shall be prelubricated at the factory prior to shipment and shall be provided with extended lubrication fittings. Grease supply lines shall be extended to the outside of the fan housing. E. The fan with motor shall be completely assembled at the factory by the fan manufacturer and given a running test prior to shipment. F. Each fan shall be provided with hanger or support brackets for mounting the fan in the horizontal or vertical position shown on the drawings. Each fan shall be provided with rubber in shear or spring type vibration isolators; refer to "Vibration and Seismic Controls for HVAC Piping and Equipment" for further requirements. G. Motor operated in-flight blade pitch control or fan inlet vanes shall be provided when scheduled on the drawings. Refer to Fan Volume Controls article in this section for further requirements. H. Where shown on the plans, the fans shall be provided with inlet boxes, inlet cones and outlet cones. All outlet cones shall be provided with access doors for adjustment of blades. Refer to articles in this section for further requirements for these items. I. Fan shall be provided with the Fan Manufacturers standard enamel finish. J. Fans shall be tested in accordance with AMCA certification procedures for air and sound performance at the capacities listed on the Drawings. K. Accessories: The following accessories are required as indicated: 1. Companion Flanges: Rolled-steel flanges. 2. Inlet and Outlet Screens: Wire mesh screen on fans not connected to ductwork. 3. Backdraft Dampers: Butterfly style, for mounting with flexible connection to the discharge of the fan or direct mounted to the discharge diffuser section. 4. Stall Alarm Probe: Sensing probe capable of detecting fan operation in stall and signaling control devices. Control devices and sequence of operation are specified in Section HVAC Instrumentation and Controls. 5. Flow Measurement Port: Pressure measurement taps installed in the inlet of the fan to detect and signal airflow readings to temperature-control systems. Control devices and sequence of operation are specified in Section Sequence of Operations. Page 11 of 17

12 2.9 BELT DRIVEN VANE A. Provide adjustable or fixed pitch vaneaxial fans with arrangement and capacities as scheduled on the drawings. All scheduled capacities are without discharge cones. B. Housings shall be tubular type to provide straight through airflow and shall be constructed of heavy gauge welded steel. Housings shall be provided with access doors for inspection of the fan bearings, fan drive, and fan wheel. Housings shall be furnished with stationary curved guide vanes, welded within the housing and located on the discharge side of the fan. C. The fan wheels shall be constructed of fabricated or cast steel blades with a steel hub. Fan wheels shall be capable of operating in an environment of 300 deg. F for 2-hours. Normal operating temperature will be 70 deg. F to 85 deg. F. Manual blade adjustment shall be accomplished without removing wheel (for adjustable pitch fans). D. Bearings shall be anti-friction ball bearing pillow blocks rated for an L-10 life of 200,000 hours. Bearings shall be mounted out of the air stream in an airtight gasketed enclosure. All bearings shall be lubricated with high temperature grease at the factory prior to shipment and provided with extended lubrication fittings. Grease supply lines shall be extended to the outside of fan housing. Provide nameplate at grease fittings indicating "Hi-Temperature Grease Only". E. Fans shall be provided with V-belt drive and streamlined belt drive fairings. Fairings shall be continuously welded to prevent caustics, corrosives and fumes from entering belt drive assembly. Belt drive assembly shall be selected for fan speed offering peak efficiency (coordinated with fan blade position). Refer to Fan Drives article in this section for further requirements. Exterior belt guard shall be OSHA approved type with expanded metal sides. F. The fan with motor shall be completely assembled at the factory by the fan manufacturer and given a running test prior to shipment. Refer to Section "Motors" for fan motor requirements. G. Each fan shall be provided with hanger or support brackets for mounting the fan in the horizontal or vertical position shown on the drawings. Each fan shall be provided with rubber in shear or spring type vibration isolators; refer to Section "Vibration and Seismic Controls for HVAC Piping and Equipment" for further requirements. H. Vertical discharge (up blast) roof mounted fans shall be provided with heavy duty mounting plate frame with vibration isolation type roof curb. The entire assembly shall be suitable to withstand a 100 miles per hour windstorm and shall include guy wires, if necessary. Refer to Roof Curb article in this section for further curb requirements. Refer to Section "Vibration and Seismic Controls for HVAC Piping and Equipment" for vibration control requirements. I. Fans shall be provided with the following accessories: 1. Refer to Section Motors and Variable Frequency Drives for fan volume control. 2. Spark resistant construction shall be provided on those fans listed in the Spark Resistant Construction article in this section. Page 12 of 17

13 3. Fan inlet boxes, inlet cones, and outlet cones shall be provided where shown on the drawings. All fans with adjustable pitch blades and with outlet cones shall be provided with access doors in the outlet cones for blade adjustment. 4. Disconnect switches for each fan mounted on the roof, refer to Section Motors for further requirements and coordinate with the Electrical Contractor. J. Refer to Protective Coating and Finish article in this section for fan finish requirements. K. Fans shall be AMCA-certified for both air and sound performance at the capacities listed on the Drawings FAN INLET BOXES, INLET CONES AND OUTLET CONES A. Fans tagged shall be furnished with inlet boxes, inlet cones and outlet cones. B. Each inlet box, inlet cone and outlet cone shall be furnished with a factory-installed access door for servicing fan bearings and for blade adjustment. Refer to Access Door article in this section for further requirements. C. Fan inlet boxes, inlet cones and outlet cones shall be furnished by the Fan Manufacturer. The performance of these devices (flow and pressure drop characteristics) shall be guaranteed by the Fan Manufacturer. D. The Fan Manufacturer shall furnish fan inlet boxes, whether or not indicated on the Drawings, for all fans which are configured with a 90 degree turn at the air inlet. E. Fan inlet boxes, inlet cones, and outlet cones shall meet or exceed SMACNA construction and gauge requirements. F. The fan inlet boxes, inlet cones and outlet cones shall be constructed with the same materials, protective coatings and finishes, as the fans for which they are provided. G. The fan inlet boxes, inlet cones, and outlet cones shall be constructed of the same material thickness as the adjoining duct system WEATHER HOODS A. All fans located outdoors shall be provided with the Fan Manufacturer's standard ventilated weather hood for protection of both the fan motor and drive ACCESS DOORS A. All access doors for fans with scheduled total pressures of 2 inches or less shall be provided with hinged, gasketed access doors with cam-type levers. B. All access doors for fans with over 2 inches total pressure shall be provided with gasketed access doors with steel stud fasteners. C. All hardware (i.e. hinges, latches, studs, and nuts) for access doors located outdoors shall be 304 stainless steel. Page 13 of 17

14 2.13 ROOF CURBS A. The individual Fan Manufacturer(s) shall furnish prefabricated roof curbs for each roof fan and hood. Curbs shall be of box section design, 18 gauge galvanized steel with continuous welded corner seams, factory installed wood nailer and insulated with 1-1/2 inch, 3 pound density rigid fiberglass board. Height of curb shall be determined in field (15" minimum). B. The base of each curb shall be pitched to match the roof pitch while maintaining a level fan installation. C. Curb shall be Fan Manufacturer's standard curb similar to the Roof Products Systems (RPS) Type RC-2A. D. In addition, the roof curbs for the following fans shall be provided with the Fan Manufacturer's standard sound attenuation material, refer to Section Vibration and Seismic Controls for HVAC Piping and Equipment SOURCE QUALITY CONTROL A. Testing Requirements: The following factory tests are required as indicated: 1. Sound Power Level Ratings: Comply with AMCA 301, "Methods for Calculating Fan Sound Ratings from Laboratory Test Data." Test fans according to AMCA 300, "Reverberant Room Method for Sound Testing of Fans." Label fans with the AMCA Seal. 2. Fan Performance Ratings: Establish flow rate, pressure, power, air density, speed of rotation, and efficiency by factory tests and ratings according to AMCA 210, "Laboratory Methods of Testing Fans for Rating." PART 3 - EXECUTION 3.1 EXAMINATION A. Examine areas and conditions for compliance with requirements for installation tolerances and other conditions affecting performance of the fans. Do not proceed with installation until unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. Install fans according to manufacturer's written instructions. B. Support units using the vibration-control devices indicated. Vibration-control devices are specified in Section "Vibration and Seismic Controls for HVAC Piping and Equipment." C. Suspend units from structure using threaded steel rods and vibration isolation springs. Vibration-control devices are specified in Section 15074"Vibration and Seismic Controls for HVAC Piping and Equipment." D. Install units with clearances for service and maintenance. Page 14 of 17

15 E. Label fans according to requirements specified in Section "Mechanical Identification." 3.3 CONNECTIONS A. Duct installation and connection requirements are specified in other Division 15 Sections. Drawings indicate the general arrangement of ducts and duct accessories. Make final duct connections with flexible connector. B. Electrical: Conform to applicable requirements in Division 16 Sections. C. Grounding: Ground equipment. Tighten electrical connectors and terminals, including grounding connections, according to manufacturer's published torque-tightening values. Where manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B. 3.4 FIELD QUALITY CONTROL A. Manufacturer's Field Service: Provide services of a factory-authorized service representative to supervise the field assembly of components and installation of fans, including duct and electrical connections, and to report results in writing. 3.5 ADJUSTING A. Adjust damper linkages for proper damper operation. B. Adjust belt tension. C. Lubricate bearings. 3.6 CLEANING A. After completing installation, inspect exposed finish. Remove burrs, dirt, and construction debris, and repair damaged finishes including chips, scratches, and abrasions. B. Clean fan interiors to remove foreign material and construction debris. Vacuum clean fan wheel and cabinet. 3.7 START-UP OF FANS A. The Fan Manufacturer or his authorized service representative shall provide start-up service for each centrifugal and axial fan with a scheduled capacity of 5 horsepower or larger and for each roof exhaust and cabinet exhaust fan with a scheduled capacity of 3/4 horsepower or larger. B. The Contractor shall provide start-up service for all other fans. C. Lubricate and start-up all fans in accordance with manufacturer's published instructions. Prepare and submit for approval a completed start-up data sheet or checklist for each equipment item. The Fan Manufacturer's representative shall be present at fan start-up as stated above and shall sign the start-up data sheet certifying correct installation and Page 15 of 17

16 start-up. Do not energize any large 3-phase fan motors except in the presence of the Fan Manufacturer's authorized service representative. D. Start-up service shall, as a minimum, include the following: 1. Lock out power source. 2. Verify that mounting arrangement and duct connections are adequately installed in accordance with recognized acceptable installation practices and with the Fan Manufacturer's recommendations. 3. Check adjustable pitch vane axial fans for proper blade setting positions. 4. Check and tighten all securing bolts. 5. Spin wheel to verify that rotation is free and that the wheel does not rub or bind. 6. Inspect wheel to verify proper rotation for fan design. 7. Check all set screws and tighten, if necessary. 8. Check lubrication. 9. Verify all electrical power connections. 10. Check V-belt drive or coupling for proper alignment. 11. Check V-belt drive for proper tension. For construction projects with 3 months or longer between fan shipment and start-up, all belt-driven fans shall be furnished with V-belts shipped loose. The Fan Manufacturer shall provide a factory-trained service representative for tightening the belts in accordance with the manufacturer's directions. The Contractor shall check belt tension during the second and seventh day's operation and re-adjust belts, as may be required, to maintain proper tension as directed by the Fan Manufacturer. 12. Remove all foreign loose material in ductwork leading to and from the fan and in the fan itself. 13. Disengage all shipping fasteners on vibration isolation equipment. 14. Check safety guards to insure they are properly secured. 15. Secure all access doors to the fan and the ductwork. 16. Switch electrical supply "on" and allow fan to reach full speed. 17. Check carefully for correct wheel rotation, proper belt alignment, proper lubrication, proper amperage and voltage readings, excessive vibration and unusual noise. 18. Tabulate voltage and amperage readings. 19. Physically check each fan at start-up and shut-down to insure no abnormal or problem conditions exist. 20. If any problem arises, switch the fan "off" immediately. Lock out the electrical supply, check carefully for the cause of the problem and correct as necessary. E. The Fan Manufacturer shall provide the services of an authorized service representative for one blade pitch adjustment of each adjustable pitch vaneaxial fan under the base contract. This service will not be used for adjusting blades to settings shown on the equipment submittals; blade settings, as shown on submittals, shall be provided at the factory before shipment of fans. 3.8 DEMONSTRATION A. Train Owner's maintenance personnel on procedures and schedules related to startup and shutdown, troubleshooting, servicing, and preventive maintenance. B. Review data in the operation and maintenance manuals. Refer to Section "Contract Closeout." C. Schedule training with Owner with at least 7 days' advance notice. Page 16 of 17

17 D. Demonstrate operation of products specified in this Section. Conduct walking tour of the Project. Briefly identify location and describe function, operation, and maintenance of each product. END OF SECTION Page 17 of 17

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

SECTION (15833) - HVAC POWER VENTILATORS

SECTION (15833) - HVAC POWER VENTILATORS PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Placement within a mechanical room is required for all major mechanical equipment. Only small units may be roof-mounted, and shall be made as inconspicuous

More information

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

A. General: Refer to paragraph entitled SUBMITTAL in Section Include the following data: SECTION 15860 - FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR MECHANICAL

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

A. Codes and Standards that are Standard at the University:

A. Codes and Standards that are Standard at the University: PART 1: GENERAL 1.01 Purpose: 1.02 References: 1.03 Requirements: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The

More information

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004) High Plume Blowers Suggested Specification Section 15500 (Master Format 1996) Suggested Specification Section 23 38 16 (Master Format 2004) PART 1 GENERAL 1.01 WORK INCLUDED High Plume Laboratory Exhaust

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

SECTION FAN COIL UNITS

SECTION FAN COIL UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

Construction Standards Page

Construction Standards Page Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,

More information

Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS. Model TCBS

Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS. Model TCBS Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST S Model TCBS CATALOG AX220 May 2013 TubeaxialFans Model TCBS The Twin City Fan & Blower model TCBS is a belt driven tubeaxial fan that is

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork. SECTION 15855 AIR HANDLING UNITS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15885 - Air Filtration Equipment. 3. 15890 - Ductwork. 1.02 REFERENCES A. Air Moving

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 233516 - ENGINE EXHAUST SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Exhaust fans. B. Ductwork and duct fittings. C. Inlet fittings. D. Accessories. E. Carbon monoxide detectors. 1.2 RELATED

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems. 15855 AIR HANDLING UNITS SPECIFIER: CSI MasterFormat 2004 number: 237313 PART 1 GENERAL 1.1 SUMMARY A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013 SECTION 15800 - AIR HANDLING EQUIPMENT 1.1 GENERAL A. All air handlers installed shall conform to the University of Rochester specification Guideline for Semi-Custom and Pre-Engineered Air Handling Units.

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION WATER-TUBE BOILERS

SECTION WATER-TUBE BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

MXI Mixed Flow Inline Fan

MXI Mixed Flow Inline Fan MXI Mixed Flow Inline Fan PRODUCT GUIDE PennBarry Your Single Source for Commercial & Industrial Supply & Exhaust Fans www.pennbarry.com TABLE OF CONTENTS INTRODUCTION 3 CERTIFICATIONS & LISTINGS 4 MIXED

More information

Selecting the Correct Fan

Selecting the Correct Fan Selecting the Correct Fan Ryan B. Johnson Air Purification Company Sales Engineer Member, ASHRAE Pikes Peak Chapter rjohnson@airpurificationcompany.com 1 Your Speaker circa 1998 Fan Types Applications

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 23 81 26 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

More information

A. This Section includes air-handling units with coils for indoor installations.

A. This Section includes air-handling units with coils for indoor installations. SECTION 237313 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes air-handling units with coils for indoor installations. 1.2 SUBMITTALS A. Product Data: For each type of indoor air-handling unit

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM SECTION 23 81 06 - PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. This Section includes equipment types that contain all the components of the refrigeration process within

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters. SECTION 15622 DIRECT GAS-FIRED BURNER & MANIFOLD SYSTEM PART 1: GENERAL 1.1 Section includes: A. Direct gas-fired heater modules B. Controls C. Equipment schedule 1.2 Related Sections A. Section 01655:

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 WATER-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals. SECTION 23 21 23 - HYDRONIC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 08:50:16 AM Job Name: EarthWise Modular Climate Changer Full Spec Location: Any Town, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SUBMITTALS Submittals

More information

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters. Section 15 _ Energy Recovery Air Handling System Part 1: GENERAL 1.1 Section Includes: A. Energy Recovery Air Handler B. Controls (most by Others) C. Equipment Schedule 1.2 Related Sections: A. Section

More information

Bulletin FH05 FUME EXHAUST

Bulletin FH05 FUME EXHAUST Bulletin FH05 FUME EXHAUST Models: FH, FHL Curb Mounted Centrifugal Fans Fume Exhaust Systems - FH/FHL Introduction The PennBarry FH fans are designed to meet the various requirements for fume exhaust

More information

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS SECTION 23 62 13 - AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,

More information

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES SECTION 15856 MODULAR AIR HANDLING UNITS PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. NFPA Compliance: Modular air handling units and components shall be designed, fabricated, and installed in compliance

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name University of Houston Master Construction Specifications Insert Project Name SECTION 23 82 20 - FANS, AIR INTAKES AND RELIEF VENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract

More information

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections, apply to this Section. B. Related

More information

SECTION DOMESTIC WATER PUMPS

SECTION DOMESTIC WATER PUMPS SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,

More information

SECTION ROOFTOP REPLACEMENT AIR UNITS

SECTION ROOFTOP REPLACEMENT AIR UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections, apply to this Section. B. Related

More information

15900 HVAC INSTRUMENTATION AND CONTROLS

15900 HVAC INSTRUMENTATION AND CONTROLS 15900 HVAC INSTRUMENTATION AND CONTROLS PART 1 GENERAL - Andover Controls BAS system is the standard for the University, and may be specified as a proprietary item. 1.0 RELATED DOCUMENTS A. Drawings and

More information

Modular Supply Make-Up Air Unit

Modular Supply Make-Up Air Unit Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR- HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR- HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup. SECTION 23 70 00- CENTRAL HVAC EQUIPMENT PART 1: GENERAL 1.1 PURPOSE: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section. SECTION 15855 GAS FURNACE/DX COOLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of contract including General and Supplementary Conditions of Division 1 of Specification

More information

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP)

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) Our Expertise, Your Air-Moving Solution ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) PART# 0601710001_rev_A INSTALLATION, OPERATION & MAINTENANCE MANUAL Please read and save these instructions for future reference.

More information

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components. Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.

More information

Direct Fired Heater Model AD Specification

Direct Fired Heater Model AD Specification Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI

More information

SECTION CONVECTION HEATING AND COOLING UNITS

SECTION CONVECTION HEATING AND COOLING UNITS PART 1 GENERAL 1.01 SECTION INCLUDES A. Baseboard radiation. B. Finned tube radiation. C. Convectors. D. Unit heaters. E. Cabinet unit heaters. F. Fan-coil units. G. Unit ventilators. H. Blower-coil units.

More information

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION COOLING TOWERS

SECTION COOLING TOWERS SECTION 23 65 00 COOLING TOWERS PART 1 - GENERAL 1.1 DESCRIPTION A. Packaged, induced draft open circuit cooling tower complete with fill, fan, inlet louvers and associated accessories and equipment. 1.2

More information

Enviro KES INSTALLATON MANUAL

Enviro KES INSTALLATON MANUAL Enviro KES INSTALLATON MANUAL Spring Air Systems Inc., Oakville, Ontario Phone (905) 338-2999, Fax (905) 338-0179, info@springairsystems.com www.springairsystems.com KES Installation Manual. This publication

More information

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more.

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more. Page 237323-1 SECTION 237323 - For large systems, 50,000 cfm or more. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

HVAC REPAIR/REPLACEMENT 07/18/12 SECTION HVAC - MAJOR EQUIPMENT

HVAC REPAIR/REPLACEMENT 07/18/12 SECTION HVAC - MAJOR EQUIPMENT SECTION 15300 - HVAC - MAJOR EQUIPMENT PART 1 - GENERAL 1.1 MECHANICAL GENERAL A. Section 15010 is applicable. PART 2 - PRODUCTS 2.1 FANS A. General: 1. All fans shall bear the AMCA Certified Performance

More information

Glossary of Terms Laboratory & Fume Exhaust Fans

Glossary of Terms Laboratory & Fume Exhaust Fans Glossary of Terms Laboratory & Fume Exhaust Fans ACTUATOR, 2-POSITION SPRING RETURN A spring return actuator generally used to control the isolation dampers below the fans. This actuator allows for fully

More information

Section (CSI ) I-Series Drum & Tube (04/23/10) Indirect-Fired Heating & Ventilating

Section (CSI ) I-Series Drum & Tube (04/23/10) Indirect-Fired Heating & Ventilating Section 15700 (CSI 23 74 33) I-Series Drum & Tube (04/23/10) Indirect-Fired Heating & Ventilating Note: Optional items and/or items requiring a choice, will be shown between brackets and/or parentheses

More information

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT

More information

SECTION COMMERCIAL-KITCHEN HOODS

SECTION COMMERCIAL-KITCHEN HOODS SECTION 23 38 13 COMMERCIAL-KITCHEN HOODS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber

More information

SECTION AIR OUTLETS AND INLETS

SECTION AIR OUTLETS AND INLETS SECTION 23 37 00 AIR OUTLETS AND INLETS PART 1 - GENERAL 1.1 SUMMARY A. Section includes diffusers, light troffer diffusers, registers/grilles, door grilles, louvers, louvered penthouses, roof hoods, goosenecks.

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 15815 Metal Ducts This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

Indirect Gas-Fired Make-Up Air

Indirect Gas-Fired Make-Up Air Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION (15820) - AIR DUCT ACCESSORIES

SECTION (15820) - AIR DUCT ACCESSORIES PART 1 GENERAL 1.01 SUMMARY A. Section includes: SECTION 23 33 00 (15820) - AIR DUCT ACCESSORIES 1. Manual-Volume Dampers 2. Fire Dampers 3. Turning Vanes 4. Duct-Mounted Access Doors 5. Flexible Connectors

More information

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - Systems and Equipment. Page 238239-1 SECTION 238239 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION DUCTWORK

SECTION DUCTWORK PART 1 GENERAL 1.1 REFERENCES SECTION 23 31 00 DUCTWORK A. ASHRAE - Handbook, Duct Design B. ASHRAE - Handbook, Duct Construction C. ASTM A90/A90M - Standard Test Method for Weight (Mass) of Coating on

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

SECTION COOLING TOWERS

SECTION COOLING TOWERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 65 00 COOLING TOWERS SPEC WRITER NOTES: 1. DELETE BETWEEN //---// if not applicable to project. Also delete any other item or paragraph not applicable in the

More information

Fans: Features and Analysis

Fans: Features and Analysis Technical Development Program COMMERCIAL HVAC EQUIPMENT Fans: Features and Analysis PRESENTED BY: Michael Ho Version 1.2 Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Section

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements 15815 Metal Ducts This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

AXPR Wall Mounted Axial Panel Fans

AXPR Wall Mounted Axial Panel Fans Bulletin 78-January-03-06 AXPR Wall Mounted Axial Panel Fans INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance instructions for the AXPR

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Modular Heating & Ventilating Unit Model IGX-HV

Modular Heating & Ventilating Unit Model IGX-HV Modular Heating & Ventilating Unit Model IGX-HV Indirect Gas-Fired Heating Evaporative Chilled Water DX Cooling October 2008 Product Features Model IGX-HV Indirect Gas-Fired Heating and Ventilating Unit

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION DUCTWORK

SECTION DUCTWORK SECTION 15890 DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07270 - Firestopping and Fire and Smoke Barrier Caulking. 2. 15260 - Vibration Isolation. 3. 15280 - Thermal Insulation (HVAC).

More information

Michigan State University Construction Standards. COOLING TOWERS Page SECTION COOLING TOWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Michigan State University Construction Standards. COOLING TOWERS Page SECTION COOLING TOWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS Page 236500-1 SECTION 236500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

MPA Modular Plenum Array Installation, Operation, and Maintenance Manual

MPA Modular Plenum Array Installation, Operation, and Maintenance Manual MPA Modular Plenum Array Installation, Operation, and Maintenance Manual This publication contains the installation, operation and maintenance procedures for standard units of the MPA: Modular Plenum Array.

More information

SECTION (15767) - UNIT HEATERS

SECTION (15767) - UNIT HEATERS SECTION 23 82 39 (15767) - UNIT HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Unit Heaters. 2. Cabinet Unit Heaters. 3. Duct Heaters. 4. Baseboard Heaters. B. Related Sections: 1. Section

More information

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL SWP (Models SWP08 through SWP20) OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Plenum Fans. Model HPA. Direct Drive

Plenum Fans. Model HPA. Direct Drive Plenum Fans Model HPA Direct Drive October 2012 Quiet & Efficient HPA Plenum Fans Greenheck s modular plenum fan, model HPA, is designed and engineered to provide superior performance and reliability in

More information

SECTION XXXXX POSITIVE DISPLACEMENT BLOWER WITH SOUNDSEAL COMPACT ENCLOSURE

SECTION XXXXX POSITIVE DISPLACEMENT BLOWER WITH SOUNDSEAL COMPACT ENCLOSURE SECTION XXXXX POSITIVE DISPLACEMENT BLOWER WITH SOUNDSEAL COMPACT ENCLOSURE PART 1 GENERAL 1.01 SECTION INCLUDES A.) Provide one (1) rotary positive displacement blower and all related appurtenances assembled

More information

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications Bulletin C6200 MAY 20 3 Buffalo Air Handling Big Buffalo Custom Applications Buffalo Air Handling Big Buffalo The historic strength of Buffalo Air Handling is the custom designed air handling equipment

More information

Direct Gas-Fired Make-Up Air

Direct Gas-Fired Make-Up Air Direct Gas-Fired Make-Up Air Model TSU Heavy Duty, High Airflow Applications Manufacturing and Industrial Facilities Up to 64,000 cfm August 2012 Products Model TSU Direct Gas-Fired Make-Up Air Unit The

More information