Technical paper Selection of district heating house stations

Size: px
Start display at page:

Download "Technical paper Selection of district heating house stations"

Transcription

1 MAKING MODERN LIVING POSSIBLE Technical paper Selection of district heating house s Herman Boysen, Product Application Manager, Danfoss A/S Published in EuroHeat & Power English Edition III 2004 districtenergy.danfoss.com

2 TECHNICAL PAPER Selection of district heating house s Market demant today for district heating house s result on an increasing focus on the following items. Author(s) Herman Boysen, Product Application Manager, Danfoss A/S Danfoss District Energy, Nordborg, Denmark, boy@danfoss.com The fact that Danfoss is now a district heating sub builder gives some more benefits for the customers: More compact s. Higher rate of flexibility in control functions. Short developing time. Optimized adaption of control equipment in the. This article informs about different types of house s concerning: Function of the system. Control function in the system. Comments to the system concerning its control and performance. power distribution big house District heating house s A district heating house system is the connecting part between the district heating utility and the consumer of district heating. The house sub can be owned either by the district heating utility or the consumer. The task of the house is to adapt the supplied heat condition into a heat condition useful for the consumer s building. flat small The demand of the can be split up in two groups, utility demand and consumer demand. The utility demand for the could be: Type of system. Low return temperature. Maximum flow limitation. Heat exchanger between the district heating network and the house network. The consumer demand to the utility company could be: Sufficient supply temperature. Sufficient differential pressure. Low energy consumption. Accurate heat metering. Besides these demands, there are some needs that have to be fulfilled before the right house can be chosen. The demands that have infl uence on choosing the right concept could be: Easy maintenance. Low risk of bacteria. Low noise level. Minimum space demand. Safe function. Accurate and stable temperature control. Low cost. Nice appearance. Long life. FIGURE 1: Different types of district heating subs 2 Danfoss District Energy

3 Group of s in general The district heating subs are normally split up into groups such as: Distribution s. Big house s. Small house s. Flat s. Distribution s are normally connected to the transmission line from the power. The purpose for the distribution is to adapt the supply condition to the district heating network. Big house s are normally directly connected to the district heating network and is supplying a number of flats. Small house s are also directly connected to the district heating network and are normally supplying one-family houses. Flat house systems are normally indirectly connected to the district heating systems and therefore built as low conditioning (PN 10) systems. FIGURE 2: Plate heat exchanger with 4 and 6 connections Big house s Big house subs can be split up into the following main groups: 1. Parallel system with instantaneous heat exchangers for domestic hot-water (DHW) heating. 2. Two-step system with instantaneous heat exchangers for DHW heating. 3. Parallel system with DHW charging system. 4. Indirectly connected DHW charging system. The trend goes in the direction of system types 1 and 2 becoming the commonly used types in future. System types 3 and 4 are still most known in Germany, Austria, Italy and the Czech Republic but there is a trend towards system types 1 and 2 in these countries. This article describes how the systems function in and control parallel and two-step systems with room heating and DHW circuit connection. Heat exchangers The heat exchanger types used in house subs depend on: FIGURE 3: Parallel system with instantaneous DHW system Type of circuit, room heating or DHW. Type of systems, parallel system, two-step system with one or two heat exchanger in the DHW circuit. In room heating systems the used type of heat exchanger is a 4-connection type. In DHW circuits the number of connections depend on type of systems. In parallel systems normally 5 connections are used. In two-step systems with one heat exchanger a 6-connection heat exchanger is used. In two-step systems with two heat exchangers one 5 connection heat exchanger and one 4 connection heat exchanger are used. Fig. 2 shows heat exchangers with 4 and 6 connections. The connections on the heat exchanger are: Primary side of the heat exchanger: T11 T12 T112 T21 T22 T212 inlet for district heating water. outlet for district heating water. inlet for the primary return water room heating system (6 connections heat exchanger). secondary inlet for domestic cold water. secondary outlet of DHW. secondary inlet of return water from DHW circulation water. Parallel system with instantaneous heat exchanger In parallel systems (see fig. 3) the district heating supply water flow rate is split up into room heating and DHW supply system. The district heating water will return directly to the district heating supply system after it has been cooled down. Danfoss District Energy 3

4 The DHW system is an instantaneous system without a buff er or a storage tank to equalize the controlled temperature. Therefore the requirement to the control equipment is very high. In parallel systems the following system conditions infl uence the control of the position of the control valve during operation:. Temperature of the water in the supply net. Differential pressure in the supply net. Rate of capacity. Two-step systems with instantaneous heat exchanger In two-step systems as shown in fig. 4, the district heating supply water is also split up to supply the room heating and DHW supply systems. The primary return flow from the heat exchanger for the room heating is led into the domestic heat exchanger in order to preheat the incoming cold water in this exchanger. In case of hot water tapping it will give a better total cooling of the primary water from the room heating system. However, in case of low return temperature from the room heating system, the return water can be after heated some few C from the return water in the DHW circulation circuit. The system conditions that influence the control of the DHW system are the same as for parallel systems, however the temperature of the water in the supply net in two-step systems is even more critical than in parallel systems because of the preheating of the domestic cold water. As for parallel systems the conditions for sizing of DHW systems are summer conditions. In summer a preheating of the domestic cold water can t be expected and can therefore not be taken into consideration when calculating the system. Therefore the control valve and the heat exchanger for the DHW system have to be calculated for max. capacity at lowest supply temperature. In the wintertime where the capacity of the room heating system is high, a high rate of preheating can be expected. Very often the incoming domestic cold water can be preheated to a level of Two-step system with one DHW heat exchanger Two-step system with two DHW heat exchangers FIGURE 4: Two step heat exchanger system with one and two heat exchangers in the DHW circuit 39 C. This means that the task for the control valve only is to increase the domestic water temperature from 39 C to 55 C. In this case the control valve will operate with a very low lift at max. capacity with the risk of an unstable temperature at part load. Room heating system The room heating system can be directly connected or indirectly connected via a heat exchanger. Both of these types normally have weather compensated supply temperature of the supply water to the room heating system. In the indirectly connected system a heat exchanger is used for transferring the needed heat energy to the room heating system. Here the motorized control valve controls the primary flow rate in the heat exchanger and thereby adjusts the secondary supply temperature according to the outdoor temperature. Directly connected room heating systems normally are equipped with weather compensated mixing loop. Here the district heating supply 4 Danfoss District Energy

5 temperature is mixed up with the return temperature water from the room heating system to the supply temperature needed to heat up the room in the house. As the capacity of the room heating system change very slowly and as smaller variation in the flow temperature is not critical, a room heating system is normally not so complicated to control. Domestic hot-water (DHW) system The DHW part of the system is more complicated to control because of the stringent requirements as to a stable temperatures compared to room heating systems. Apart from this the capacity in this systems also change rapidly. The room heating system and the DHW system normally run independently of each other, unless a hot-water priority function in the controller is active. The hot-water priority is only in function if there is insufficient capacity for heating both the DHW at the same time as the room heating system. If this is the case, the hot water heating demand will have higher priority than the demand for room heating. If the DHW temperature is too low because of lacking capacity, the flow rate to the room heating system will be reduced or totally closed. Temperature of the water in the supply net Very often the supply temperature in the network varies over the year. In winter the supply temperature is high. In summer the supply temperature will normally be reduced to a level of C, sufficient enough to produce hot water at temperatures of C. As the hot water consumption is expected to be of the same size all around the year, the capacity of the control valve in the DHW system has to be sized according to the low supply temperature in summer. This will affect the fact that the control valve in the winter with the high supply temperature will operate with a valve cone lift lower than 100%. Constant permanent deviation from set point after a temperature change, ± 2 K Differential pressure in the network The valve sizing is based on a chosen or the min. available differential pressure across the control valve. If a differential pressure controller is not installed, an increasing differential pressure in the network will therefore result in that the control valve closes accordingly and operates at a lower opening degree. This can be critical for a stable temperature control. A differential pressure controller in the system will be able to minimize variations in the differential pressure across the control valve independently of the variation of the differential pressure in the network. Range of capacity Maximum permanent temperature oscillations, ± 2 K Maximum temperatuer deviation after a momentary laod change, 10 K Transient time after a load change <± 2 K within 120 sec FIGURE 5: Relevant temperature control performance in a DHW system with an instantaneous heat exchanger. A hot-water system has to be able to control a stable temperature under all relevant capacities. The lowest expected capacity for a DHW system can be the water flow that corresponds to one tapping. The capacity of the system then ranges from one tapping up to full capacity of the system. In big systems with one big valve dimension, the control of the flow rate which corresponds to one tapping will affect the operation near the closing point with the risk of unstable controlled tap water temperature. In this case it is recommended to choose two control valves in different sizes connected in parallel. The system can then be operated so that the small valve operates at low flow rates and both valves operate at increasing capacity. Control equipment Correctly chosen control equipment is an important factor for a well functioning system. Danfoss has especially developed control equipment for controlling instantaneous DHW systems. Research and design of this equipment are based on computer simulations, laboratory tests and field tests. Danfoss District Energy 5

6 A relevant example of the quality of the controlled temperature is shown in fig. 5. Experience from this R & D work is listed in the guidelines below (table 1) for a well functioning DHW system: Choose motorized control valves with a short running time, i.e. max seconds from fully closed to fully open valve. The time constant of the sensor must be less than or equal 3 seconds. The sensor must be placed as close to the heat exchanger as possible. Make sure that the required control ratio is met by choosing the right valves and properly pre-adjusted systems. Adjust the systems to operate with fully open valves under a 100 % load. Choose valves with a sufficient authority in the systems. This authority is especially critical in systems with a low differential pressure. Avoid large pressure variation in the systems by using differential pressure controllers. Differential pressure controllers also have a favorable effect on the control ratio of the control valve as well as the valve authority. Valve sizing Valve sizing of a DHW control valve in an instantaneous system can be done as shown in table 2. By means of the k vs value of the chosen control valve the needed Δp v can be calculated. The differential pressure controller can then be set to the sized Δp value so that the control valve operates with a 100 % opening degree at a 100 % load. The calculation shows the capacity of the control valve under different conditions and in different system types. In fig. 6 a split characteristic for a motorized control valve is illustration. The control valve has a k v of 6.3 m 3 /h and a max. valve cone lift of 5 mm at an opening degree of 100 %. In this graph, the valve cone lift can be seen under different conditions and in different systems. The opening degree for the valve at sizing point will be approx. 4.4 mm with the given specifications FIGURE 6: Valve characteristic with a split characteristic. From the figure the valve cone lift can be seen for different systems in winter and summertime After setting the ΔP controller, the valve will be fully open and the valve cone lift will be 5 mm. Under winter conditions the supply temperature is high, in this case 100 C. The control valve in a parallel system will therefore operate with a lower opening degree at 100 % load. Parallel systems has no preheating of the DHW system, thus the fully DHW capacity has to be heated from the primary flow rate in the DHW circuit. Here the valve cone opening degree will be approx. 3.5 mm. Two-step systems have the highest DHW preheating rate in winter where the load on the room heating system is 100 %. Consequently, the degree of after heating of the DHW is low. As can be seen from the graph, the valve opening degree at 100 % load during winter is approx. 2.9 mm. The lower the valve cone lift at 100 % load, the lower the valve cone lift is at part load. The consequence of this is an increased risk of unstable temperature control. Conclusion As mentioned parallel systems and two-step systems without charging tank seem to be the future sub solution. And the reasons are: These systems have no charging tank. System types with charging tanks are Valve lift at different load and systemtypes Valve lift after setting of the dp controller Calculated valve capacity Parallel system. Winter condition Valve opening mm Two step systems. Winter condition 0 0,0 2,1 2,5 2,9 3,2 3,6 3,9 4,3 4,7 normally more expensive than parallel and two step systems without charging tanks. However, the heat exchanger capacity is higher in systems with out charging or buffer tanks. A charging tank in a system will increase the risk of bacteria growth. The control equipment today is designed specifically for the purpose and obtainable for instantaneous DHW systems. Choosing between a parallel system and a two-step system can be difficult. It is established that two-step systems have a better cooling of the district heating water during tapping of DHW. The fact that the return temperature from the room heating system in some cases can be after heated from the DHW circulation return temperature is a disadvantage. However, as the heating costs normally are based on the energy calculation this will normally not have any influence. It has to be taken into consideration that the DHW heat exchanger in a two-step system often is bigger than in a parallel system because it has to be sized for the primary DHW flow rate as well for the room heating flow rate. As the variation of the supply differential pressure has influence on a stable control temperature in this type of systems, it is very important to install a differential pressure controller in the sub. 6 Danfoss District Energy

7 DHW specifications DHW flow rate Q DHW 3 m 3 /h DHW temperature T C DCW temperature T C Capacity P = Q DHW (T 22 T 21) / 0,86 P = 3 (55 10) / 0, kw Basics for sizing a control valve, Summer, parallel and two-step system Capacity P 157 kw Primary supply temperature T C Primary return temperature T C Disposal Δp for the control valve Δp v 0,5 Bar Primary flow rate Q 11 = P 0,86 /(T 11 T 12) Q 11 = /(65 25) 3,4 m 3 /h Calculated k v k v = Q 11 / Δp v k v = 3.4/ 0,5 4,8 m 3 /h Chosen valve capacity k vs 6,3 m 3 /h Real Δp v Δp Vmin = (Q 11 / k vs ) 2 Δp Vmin = (3.4/ 6.3) 2 0,29 Bar Control ratio r 50 Min kv for stable temperature control k Vr = k Vs / r k Vr = 6.3 / 50 0,13 m 3 /h Winter, parallel system T supply winter T sw 100 C T return T rw 18 C dp valve 0,29 Bar flow rate Q 11 = P 0.86 /(T 11 T 12) Q 11 = /(100 18) 1,65 m 3 /h k v at max. capacity k v = 1.65 / 0,29 3,06 m 3 /h Winter, two-step system Relevant preheat temperature DHW T pre 39 C After heating ΔT = T22 T pre ΔT = C Preheat capacity P pre = Q DHW (T pre T21) / 0,86 P pre = 3.0 (39 10) / 0, kw Afterheat capacity P after = P P pre P after = kw T supply summer T C T return relevant T C dp valve 0,29 Bar After heat fl ow rate Q after = P after 0.86 /(T 11 T 12) Q after = /(100 45) 0,87 m 3 /h k v k v = Q after / Δp v k v = 0,87 / ,62 m 3 /h Danfoss District Energy 7

8 More information Find more information on Danfoss District Energy products and applications on our homepage: VF.LA.N2.02 Produced by Danfoss A/S, DH-SM/PL 09/2011

Technical paper Hydraulic balance in a district cooling system

Technical paper Hydraulic balance in a district cooling system MAKING MODERN LIVING POSSIBLE Technical paper Herman Boysen, Product Application Manager, Danfoss A/S Published in DBDH 2003 (www.dbdh.dk) districtenergy.danfoss.com TECHNICAL PAPER Hydraulic balance in

More information

Hydraulic balance in a district cooling system

Hydraulic balance in a district cooling system Article Hydraulic balance in a district cooling system Herman Boysen, Product Application Manager, Danfoss A/S, Published in DBDH 2003 (www.dbdh.dk) www.danfoss.com Herman Boysen Product Application Manager,

More information

Technical Paper. Auto tuning and motor protection as part of the pre-setting procedure in a heating system

Technical Paper. Auto tuning and motor protection as part of the pre-setting procedure in a heating system Technical Paper Auto tuning and motor protection as part of the pre-setting procedure in a heating system By Herman Boysen Product Application Manager Auto Tuning inside ECL Comfort The result of Auto

More information

New ways of balancing two-pipe systems

New ways of balancing two-pipe systems Technical Article - hydronic balancing New ways of balancing two-pipe systems How to achieve superior hydronic balance in heating systems by utilising the Danfoss Dynamic Valve type RA-DV and the Grundfos

More information

Distribution systems in apartment buildings

Distribution systems in apartment buildings Article Distribution systems in apartment buildings Halldor Kristjansson, Danfoss A/S www.danfoss.com Halldor Kristjansson, Danfoss A/S Published at the 11th International Symposium on District Heating

More information

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16)

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16) Data sheet Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16) Description XB06 IHPT The XB is a brazed plate heat exchanger designed for use with district heating systems

More information

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16)

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16) Data sheet Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16) Description XB06 IHPT The XB is a brazed plate heat exchanger designed for use with district heating systems

More information

ECL Comfort 110, application 116

ECL Comfort 110, application 116 Operating Guide ECL Comfort 110, application 116 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

Technical paper Distribution systems in apartment buildings

Technical paper Distribution systems in apartment buildings MKIG MODE LIVIG POSSILE Technical paper Distribution systems in apartment buildings Halldor Kristjansson, Danfoss /S Published at the 11th International Symposium on District Heating and ooling, ugust

More information

Contact person Date Reference Page Daniel Månsson P07886C-rev2 1 (14) Energy and bioeconomy

Contact person Date Reference Page Daniel Månsson P07886C-rev2 1 (14) Energy and bioeconomy Contact person Daniel Månsson 2016-04-15 5P07886C-rev2 1 (14) Energy and bioeconomy +46 10 516 53 28 Daniel.Mansson@sp.se FairHeat Ltd, 10 Stoney Street, London SE1 9AD16 United Kingdom Testing of heat

More information

AVTI Multifunctional self - acting controller

AVTI Multifunctional self - acting controller AVTI Multifunctional self - acting controller Description / Application AVTI is a self - acting combined controller developed for controlling small heat units with a room heating system and a hot service

More information

Weather compensated flow temperature control of heating and boiler systems

Weather compensated flow temperature control of heating and boiler systems Instructions ECL Comfort 110 Application 130 Weather compensated flow temperature control of heating and boiler systems User guide, Installation & Maintenance DH-SMT/DK VI.KT.G3.02 Danfoss 06/2008 How

More information

ECL Comfort 110, application 130

ECL Comfort 110, application 130 Operating Guide ECL Comfort 110, application 130 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

Contact person Date Reference Page Björn Folkeson P (15) Energy and bioeconomy

Contact person Date Reference Page Björn Folkeson P (15) Energy and bioeconomy Contact person Björn Folkeson 2016-06-27 6P04381 1 (15) Energy and bioeconomy +46 10 516 54 46 bjorn.folkeson@sp.se Thermal Integration Ltd 8 Curzon Road Sudbury Suffolk CO10 2XW Great Britain Testing

More information

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502* User's Guide VI.7C.C5.02 2005.09 C66 *vi7cc502* *087R8069* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8069* *vi7cc502* Mixing controller with PI controlled

More information

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16)

Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16) Brazed heat exchanger XB06 & Flow-compensated temperature controller IHPT (PN16) Description XB06 The XB is a brazed plate heat exchanger designed for use with district heating systems (i.e. air conditioning,

More information

Contact person Date Reference Page Daniel Månsson P07886E-rev2 1 (14) Energy and bioeconomy

Contact person Date Reference Page Daniel Månsson P07886E-rev2 1 (14) Energy and bioeconomy Contact person Daniel Månsson 2016-04-15 5P07886E-rev2 1 (14) Energy and bioeconomy +46 10 516 53 28 Daniel.Mansson@sp.se FairHeat Ltd, 10 Stoney Street, London SE1 9AD16 United Kingdom Testing of heat

More information

House Installations, district heating substations

House Installations, district heating substations House Installations, district heating substations Energy sources Heat production Distribution Consumer installations End consumption Placed at the end user Purpose of preparing domestic hot water and delivering

More information

Contact person Date Reference Page Björn Folkeson P (14) Energy and bioeconomy

Contact person Date Reference Page Björn Folkeson P (14) Energy and bioeconomy Contact person Björn Folkeson 2016-11-18 6P06855 1 (14) Energy and bioeconomy +46 10 516 54 46 bjorn.folkeson@sp.se Caleffi S.p.A. S.R. 229, n. 25 IT-28010 Fontaneto d'agogna (NO) Italy Testing of heat

More information

30% Safe. Take lead on your project with an efficient system concept. Technical handbook Danfoss EvoFlat systems from A-Z. evoflat.danfoss.

30% Safe. Take lead on your project with an efficient system concept. Technical handbook Danfoss EvoFlat systems from A-Z. evoflat.danfoss. MAKING MODERN LIVING POSSIBLE Technical handbook Danfoss EvoFlat systems from A-Z Take lead on your project with an efficient system concept Safe and comfortable EvoFlat systems provide heating and domestic

More information

WL Instantaneous water heater

WL Instantaneous water heater WL Instantaneous water heater WL Table of contents WL...1 Table of contents...1 Safety notes...2 Delivery...2 Transport and storage...2 Mounting...3 Pipes connections...3 Electrical connection...3 Filling,

More information

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602* User's Guide VI.7C.E6.02 2005.09 C37 *VI7CE602* *087R8070* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8070* *VI7CE602* Mixing controller with ON / OFF controlled

More information

30% Take lead on your project with an efficient system concept. lower energy.

30% Take lead on your project with an efficient system concept. lower energy. Technical handbook Danfoss EvoFlat systems from A-Z Take lead on your project with an efficient system concept 30% lower energy consumption by individual metering in each apartment www.evoflat.danfoss.com

More information

Technical paper Analysis on flat station concept (Preparing DHW decentralised in flats)

Technical paper Analysis on flat station concept (Preparing DHW decentralised in flats) MAKING MODERN LIVING POSSIBLE Technical paper (Preparing DHW decentralised in flats) Jan Eric Thorsen, Senior Project Manager, M.Sc., The 12th International Symposium on District Heating and Cooling, September

More information

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102*

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102* User's Guide VI.KM.E1.02 2005.09 C62 *VIKME102* *087R8091* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8091* *VIKME102* Double mixing controller C62 VI.KM.E1.02

More information

4 th Generation District Heating. Dr. Oddgeir Gudmundsson Director of Projects Application Center Danfoss Heating Segment

4 th Generation District Heating. Dr. Oddgeir Gudmundsson Director of Projects Application Center Danfoss Heating Segment 4 th Generation District Heating Dr. Oddgeir Gudmundsson Director of Projects Application Center Danfoss Heating Segment What are the district heating generations? 1G 2G 3G 4G Temperatures Principles Same

More information

ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys

ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys Designed in Denmark Description ECL Comfort 210 controller series ECL 210 The ECL Comfort 210 is an electronic weather

More information

Contact person RISE Date Reference Page Björn Folkeson P03675B 1 (11) Energy and circular economy

Contact person RISE Date Reference Page Björn Folkeson P03675B 1 (11) Energy and circular economy Contact person RISE Björn Folkeson 2017-08-15 7P03675B 1 (11) Energy and circular economy +46 10 516 54 46 bjorn.folkeson@ri.se Gemina Termix A/S Navervej 15-17 DK-7451 SUNDS Danmark Testing of a HIU according

More information

IDEA CAMPUSENERGY2017 February Miami, FL

IDEA CAMPUSENERGY2017 February Miami, FL IDEA CAMPUSENERGY2017 February 20-24 Miami, FL Low Temperature Thermal Networks: Domestic Hot Water Production Jeff Flannery Table of contents 1. Objective for DHW devices 2. Building demands 3. Centralized

More information

Danfoss Solar Solutions Application Handbook

Danfoss Solar Solutions Application Handbook MAKING MODERN LIVING POSSIBLE Danfoss Solar Solutions Application Handbook Danfoss district heating Meeting your requirements - for a truly efficient use of solar energy Increased requirements for energy

More information

Operating Guide. Termix Solar A+/B+ 1.0 Table of Contents. 1.0 Table of Contents

Operating Guide. Termix Solar A+/B+ 1.0 Table of Contents. 1.0 Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................

More information

General information on refrigerant controllers

General information on refrigerant controllers General information on refrigerant controllers Condensing pressure controller The condensing or condenser pressure controller is a back pressure controller and its task is to maintain the condensing pressure

More information

Contact person Date Reference Page Daniel Månsson P07886B-rev2 1 (14) Energy and bioeconomy

Contact person Date Reference Page Daniel Månsson P07886B-rev2 1 (14) Energy and bioeconomy Contact person Daniel Månsson 2016-04-15 5P07886B-rev2 1 (14) Energy and bioeconomy +46 10 516 53 28 Daniel.Mansson@sp.se FairHeat Ltd, 10 Stoney Street, London SE1 9AD16 United Kingdom Testing of heat

More information

Technote. Frese AquaHeat HW - DH. Application. Design. Features and Benefit. Operation. Optional.

Technote. Frese AquaHeat HW - DH. Application. Design. Features and Benefit. Operation. Optional. Page 1 of 5 Application The Single Plate heat interface unit (HIU) for the generation of instantaneous domestic hot water and the direct supply of space heating. This HIU provides hydraulic separation

More information

Akva Vita Instantaneous water heater

Akva Vita Instantaneous water heater Akva Vita Instantaneous water heater Akva Vita Table of Contents Akva Vita... 1 Table of Contents... 1 Safety notes... 2 Delivery... 2 Transport and storage... 2 Mounting... 3 Pipes connections... 4 Electrical

More information

Automatic balancing valves ASV-PV (new generation) DN 32-50

Automatic balancing valves ASV-PV (new generation) DN 32-50 Automatic balancing valves ASV-PV (new generation) DN 32-50 ASV-PV DN 32-50 Description ASV whiteboard animation SMT/SI ASV valves are automatic balancing valves. Together with Danfoss presetting radiator

More information

Munters DesiCool removes excess heat in server room

Munters DesiCool removes excess heat in server room Munters DesiCool removes excess heat in server room DesiCool Corporate IT in Copenhagen University is bringing all their servers into two large server rooms located respectively in Copenhagen University

More information

SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production

SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production SATK0 - SATK0 series ACCREDITED ISO 900 FM 009/ GB replaces dp 009/ GB Function The latest generation of Heat Interface

More information

Secondary systems used in Europe.

Secondary systems used in Europe. Secondary systems used in Europe. Production Distribution Consumption Preface Secondary systems are the parts of the heating systems with a lower pressure and temperature level, installed in buildings.

More information

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length HEIMO WALTER Institute for Thermodynamics and Energy Conversion Vienna University

More information

HVAC Water chiller selection and optimisation of operation

HVAC Water chiller selection and optimisation of operation HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water

More information

heat interface units A BOILER WITHOUT A FLAME

heat interface units A BOILER WITHOUT A FLAME A BOILER WITHOUT A FLAME heat interface units Communal Heat Networks A central boiler house will generate heat which is distributed through a network of pipe to each home or apartment in the building.

More information

Contact person Date Reference Page Daniel Månsson P (13) Energy and circular economy

Contact person Date Reference Page Daniel Månsson P (13) Energy and circular economy Contact person Daniel Månsson 2017-04-18 7P01636 1 (13) Energy and circular economy +46 10 516 53 28 daniel.mansson@ri.se Fortes Import Installatie Agenturen B.V. Loodsboot 26 NL-3991 CJ Houten Nederländerna

More information

60 C water temperature ensures thermal disinfection during hot water production

60 C water temperature ensures thermal disinfection during hot water production Product Catalog - Product Sheets Work smarter and get the complete overview of Danfoss Systems & Water Heaters for domestic hot water and district heating applications 60 C water temperature ensures thermal

More information

HW 22 District heating substation for indirect heating and domestic hot water systems

HW 22 District heating substation for indirect heating and domestic hot water systems HW 22 District heating substation for indirect heating and domestic hot water systems HW 22 Table of contents HW 22... 1 Table of contents... 1 Safety notes... 2 Delivery... 2 Transport and storage...

More information

Domestic hot water (DHW) The substation can be supplied with connection pipes for DHW cylinder on the supply or return line.

Domestic hot water (DHW) The substation can be supplied with connection pipes for DHW cylinder on the supply or return line. MAKING MODERN LIVING POSSIBLE VX Solo II Substation for single-family, semi-detached and terraced houses as well as flats District heating substation for indirect heating. With connection pipes for W cylinder.

More information

Arrangements of heating systems in compliance with official regulations

Arrangements of heating systems in compliance with official regulations Arrangements of heating systems in compliance with official regulations Michael Hartmann, chartered engineer Hydraulic problems in heating systems and related difficulties are very common in everyday life.

More information

TA-COMFORT-S. Prefabricated units Heating interface unit for surface heating and hot water services

TA-COMFORT-S. Prefabricated units Heating interface unit for surface heating and hot water services TA-COMFORT-S Prefabricated units Heating interface unit for surface heating and hot water services IMI TA / Control valves / TA-COMFORT-S TA-COMFORT-S All in one design with STAP differential pressure

More information

Wall-mounted substation PKL-113

Wall-mounted substation PKL-113 Wall-mounted substation PKL-113 You have chosen a high-quality product to your home. We hope you will be as pleased with the substation as those customers we have served for over 30 years! Application

More information

Building services installation. Sustainable retrofitting of buildings- Sub module 3

Building services installation. Sustainable retrofitting of buildings- Sub module 3 Building services installation Sustainable retrofitting of buildings- Sub module 3 District heating Towards lower temperature on primary side New demands to secondary side Prerequisits Low flow temperature

More information

Minimization of Mass Flow in District Heating Network Equipped with One Stage Domestic Hot Water Production Substations

Minimization of Mass Flow in District Heating Network Equipped with One Stage Domestic Hot Water Production Substations Minimization of Mass Flow in District Heating Network Equipped with One Stage Domestic Hot Water Production Substations ŻARSKI K. University of Technology and Life Sciences, Bydgoszcz *Corresponding author,

More information

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's PDF, also known as Version of record Link to publication

More information

Contact person RISE Date Reference Page. Daniel Månsson P (13) Energy and circular economy

Contact person RISE Date Reference Page. Daniel Månsson P (13) Energy and circular economy Contact person RISE Daniel Månsson 2017-09-26 7P03172 1 (13) Energy and circular economy +46 10 516 53 28 daniel.mansson@ri.se Evinox Energy Ltd. Unit 37, Barwell Business Park Leatherhead Road, Chessington

More information

Measurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation.

Measurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation. Measurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation. Bengt Perers 1, Elsa Andersen 2, Simon Furbo 2, Ziqian Chen 2 and Agisilaos

More information

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

Refrigeration and Air Conditioning Controls. Applications. PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING

Refrigeration and Air Conditioning Controls. Applications. PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING Refrigeration and Air Conditioning Controls Applications PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING Introduction Danfoss PM regulators have been on the market

More information

FHM-Cx Mixing Shunts for Floor Heating

FHM-Cx Mixing Shunts for Floor Heating FHM-Cx Mixing Shunts for Floor Heating Application Mixing shunt FHM-C5/C6 (UPS pump) The Danfoss compact mixing shunts are used for regulation of flow and supply temperature in hydronic floor heating systems.

More information

ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys Designed in Denmark

ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys Designed in Denmark ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys Designed in Denmark Description ECL Comfort 210 controller series The ECL Comfort 210 is an electronic weather compensated

More information

Increase the attractiveness of your multi-family building

Increase the attractiveness of your multi-family building Modern heating technology for housing associations Increase the attractiveness of your multi-family building Energy-efficient and reliable heating solutions. Up to 23% energy savings thanks to intelligent

More information

Akva Vita TDP District heating flat station for direct heating and domestic hot water systems

Akva Vita TDP District heating flat station for direct heating and domestic hot water systems Akva Vita TDP District heating flat station for direct heating and domestic hot water systems Akva Vita TDP Table of contents Akva Vita TDP... 1 Table of contents... 1 Safety notes... 2 Delivery... 2 Transport

More information

Domestic Hot Water Application manual

Domestic Hot Water Application manual Document Electrical Heating category Product name Domestic Hot Water Application manual 90% of the Legionella bacteria dies within the first 2 min at 60 C Let Danfoss do the work Index Danfoss Group is

More information

FHM-Cx Mixing Shunts for Floor Heating

FHM-Cx Mixing Shunts for Floor Heating Data Sheet FHM-Cx Mixing Shunts for Floor Heating Application A self-acting proportional regulator is used to regulate the supply temperature. The regulator ensures that the desired supply temperature

More information

Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production

Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production THE SIMPLEST SOLUTION FOR A CONDENSING BOILER DIVACONDENS D PLUS is the generator of condensation

More information

T. +44 (0) E.

T. +44 (0) E. Twin Plate Heat interface unit for indirect heating and instantaneous domestic hot water with electronic thermostatic control. Designed for wall-mounting. Application The is the complete solution for hot

More information

Design-Edition. Design-Edition Thermostatic valves and lockshields, sets

Design-Edition. Design-Edition Thermostatic valves and lockshields, sets Design-Edition Design-Edition Thermostatic valves and lockshields, sets IMI HEIMEIER / Design-Edition / Design-Edition Design-Edition The sets are an elegant solution for e. g. design radiators. A sublime

More information

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER Poster P.4.2 - - ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER Jan Sedlar, University Centre for Energy Efficient Buildings and Faculty of Mechanical Engineering, Czech Technical University in Prague, Czech

More information

Thermostatic head K. with contact or immersion sensor. Thermostat-Köpfe For medium temperature control

Thermostatic head K. with contact or immersion sensor. Thermostat-Köpfe For medium temperature control Thermostatic head K with contact or immersion sensor Thermostat-Köpfe For medium temperature control IMI HEIMEIER / Thermostatic Heads & Radiator Valves / Thermostatic head K with contact or immersion

More information

District Heating Fact Finding Mission to DK for Energy Cities members September Experience with Low temperature DH in DK

District Heating Fact Finding Mission to DK for Energy Cities members September Experience with Low temperature DH in DK District Heating Fact Finding Mission to DK for Energy Cities members 12-14 September 2016 Experience with Low temperature DH in DK Jan Eric Thorsen Director, Application Centre Danfoss Heating Segment

More information

ModuSat TP. Energy. Heat Interface Units

ModuSat TP. Energy. Heat Interface Units Energy Twin Plate Heat interface unit for indirect heating and instantaneous domestic hot water with electronic thermostatic control. Designed for wall-mounting. Application The is the complete solution

More information

Contact person RISE Date Reference Page Björn Folkeson P (13) Energy and circular economy

Contact person RISE Date Reference Page Björn Folkeson P (13) Energy and circular economy Contact person RISE Björn Folkeson 2017-09-21 7P03972 1 (13) Energy and circular economy +46 10 516 54 46 bjorn.folkeson@ri.se Thermal Integration Ltd 8 Curzon Road Sudbury Suffolk CO10 2XW Great Britain

More information

MINIMISING THE RISK OF WATER HAMMER AND OTHER PROBLEMS AT THE BEGINNING OF STAGNATION OF SOLAR THERMAL PLANTS- A THEORETICAL APPROACH

MINIMISING THE RISK OF WATER HAMMER AND OTHER PROBLEMS AT THE BEGINNING OF STAGNATION OF SOLAR THERMAL PLANTS- A THEORETICAL APPROACH MINIMISING THE RISK OF WATER HAMMER AND OTHER PROBLEMS AT THE BEGINNING OF STAGNATION OF SOLAR THERMAL PLANTS- A THEORETICAL APPROACH Wolfgang Streicher Institute of Thermal Engineering, Graz University

More information

A complete, compact steam heat exchange solution for process and domestic water heating requirements.

A complete, compact steam heat exchange solution for process and domestic water heating requirements. Precisely matched steam controls. Electric or pneumatic actuated valves. Highly efficient steam plate heat exchanger. Minimal scaling. Integral recirculation pump Can operate partially flooded. Condensate

More information

ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International Presentation Overview Water Heater Piping Strategies How to size a water heater?

More information

Balancing & Control. Frese PV Compact. Differential Pressure Control Valve

Balancing & Control. Frese PV Compact. Differential Pressure Control Valve Balancing & Control Frese PV Compact Differential Pressure Control Valve Balancing & Control Frese PV Compact Differential Pressure Control Frese Innovative solutions from Frese balance global HVAC systems

More information

HyBo - Hydraulic Interface Unit AMBIENT HEATING AND DOMESTIC HOT WATER PRODUCTION FOR CENTRAL HEATING SYSTEM UNIT CODE EHIU1

HyBo - Hydraulic Interface Unit AMBIENT HEATING AND DOMESTIC HOT WATER PRODUCTION FOR CENTRAL HEATING SYSTEM UNIT CODE EHIU1 HyBo - Hydraulic Interface Unit AMBIENT HEATING AND DOMESTIC HOT WATER PRODUCTION FOR CENTRAL HEATING SYSTEM UNIT CODE EHIU1 INSTALLATION, COMMISSIONING AND OPERATING INSTRUCTIONS Contents Unit as delivered

More information

APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps

APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual Suggestions for the hydraulic integration of chillers and heat pumps Table of Contents From practical experience, for your practical needs...

More information

Contact person RISE Date Reference Page Daniel Månsson P (13) Energy and circular economy

Contact person RISE Date Reference Page Daniel Månsson P (13) Energy and circular economy Contact person RISE Daniel Månsson 2018-08-07 8P04823 1 (13) Energy and circular economy +46 10 516 53 28 daniel.mansson@ri.se Flamco LTD Washway Lane, St. Helens Merseyside WA10 6PB Great Britain Testing

More information

Akva Vita TDP-F District heating flat station for direct heating and domestic hot water systems

Akva Vita TDP-F District heating flat station for direct heating and domestic hot water systems Akva Vita TDP-F District heating flat station for direct heating and domestic hot water systems Akva Vita TDP-F Table of contents Akva Vita TDP-F...1 Table of contents...1 Safety notes...2 Delivery...2

More information

HEAT INTERFACE UNITS (Sanitary Hot Water Only)

HEAT INTERFACE UNITS (Sanitary Hot Water Only) HEAT INTERFACE UNITS (Sanitary Hot Water Only) T-FAST i20 (Sanitary Hot Water Only) 20 The T-Fast i20 is an instantaneous domestic hot water production module that produces a flow rate of 20L per/min at

More information

A study of Transient Performance of A Cascade Heat Pump System

A study of Transient Performance of A Cascade Heat Pump System Available online at www.sciencedirect.com ScienceDirect Energy Procedia 79 (2015 ) 131 136 2015 International Conference on Alternative Energy in Developing Countries and Emerging Economies A study of

More information

a Danfoss Platform for Flensburg Secondary Network

a Danfoss Platform for Flensburg Secondary Network DSP MINI a Danfoss Platform for Flensburg Secondary Network General description and application The DSP MINI is designed for use in district heating networks, suitable for heating and for providing DHW

More information

Domestic Hot Water production

Domestic Hot Water production Domestic Hot Water production Domestic Hot water Specified quality (local regulations and standards): drinking water How hot should the water be? Depends on needs and consumption habits Generally: 40-55

More information

CASE STUDY REGARDING ENERGY EFFICIENCY OF A VENTILATION SYSTEM WITH RECUPERATIVE HEAT RECOVERY

CASE STUDY REGARDING ENERGY EFFICIENCY OF A VENTILATION SYSTEM WITH RECUPERATIVE HEAT RECOVERY JOURNAL OF APPLIED ENGINEERING SCIENCES Article Number: 131_VOL.3(16), issue 2_2013, pp.27-32 ISSN 2247 3769 ISSN-L 2247 3769 (Print) / e-issn 2284-7197 CASE STUDY REGARDING ENERGY EFFICIENCY OF A VENTILATION

More information

Residential heating and domestic hot water. Customized heat transfer solutions

Residential heating and domestic hot water. Customized heat transfer solutions Residential heating and domestic hot water Customized heat transfer solutions Heat transfer solutions that will help you break barriers 1. 2. Ehaust gas recuperator Secondary heat echanger for tap water

More information

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Introduction: Energy use is the single largest operating expense in commercial office

More information

ThermoClean Domestic water heating system with legionella growth prevention through thermal disinfection

ThermoClean Domestic water heating system with legionella growth prevention through thermal disinfection ThermoClean Domestic water heating system with legionella growth prevention through thermal disinfection Description/Application The ThermoClean system is compact and effective solution for legionella-free

More information

Akva Lux VX District heating substation for indirect heating and domestic hot water systems

Akva Lux VX District heating substation for indirect heating and domestic hot water systems Akva Lux VX District heating substation for indirect heating and domestic hot water systems Akva Lux VX Table of Contents Akva Lux VX... 1 Table of Contents... 1 Safety notes... 2 Delivery... 2 Transport

More information

Multilux 4-Eclipse-Set

Multilux 4-Eclipse-Set Multilux -Eclipse-Set Design-Edition with two-point connection, angle and straight type, for R / and connection, with automatic flow limitation IMI HEIMEIER / Design-Edition / Multilux -Eclipse-Set Multilux

More information

ModuSat TP. Energy. Heat Interface Units

ModuSat TP. Energy. Heat Interface Units Energy Twin Plate Heat interface unit for indirect heating and instantaneous domestic hot water with electronic thermostatic control. Designed for wall-mounting. Application The is the complete solution

More information

COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS

COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS - 1 - COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS W. Mittelbach, Managing Director, SorTech AG, Weinbergweg 23, 06120 Halle, Germany T. Büttner, Head of R&D / production, SorTech AG,

More information

80HMA. Comfort Module Range for Monobloc Heat Pumps. Compact comfort module. DHW management possibility. Multi zone option control.

80HMA. Comfort Module Range for Monobloc Heat Pumps. Compact comfort module. DHW management possibility. Multi zone option control. product selection data Compact comfort module DHW management possibility Multi zone option control Easy installation Comfort module with two-zone kit Single-zone comfort module Comfort Module Range for

More information

INDIVIDUAL APARTMENT SUBSTATION TESTING DEVELOPMENT OF A TEST AND INITIAL RESULTS

INDIVIDUAL APARTMENT SUBSTATION TESTING DEVELOPMENT OF A TEST AND INITIAL RESULTS INDIVIDUAL APARTMENT SUBSTATION TESTING DEVELOPMENT OF A TEST AND INITIAL RESULTS Martin Crane CEng 1, 1 Carbon Alternatives Ltd Keywords: district heating, substation, low return temperature, performance

More information

prestige Control Application Supplement - ACVMax

prestige Control Application Supplement - ACVMax 2015-10 Prestige ACVMax Control Sup 12-14-15_ACVMax_Control 12/15/15 7:36 AM Page 1 prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory

More information

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

TOTAL SYSTEM EFFICIENCY: CONTROL STRATEGIES & SYSTEM DISTRIBUTION. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: CONTROL STRATEGIES & SYSTEM DISTRIBUTION. David Grassl PE Mechanical Engineer Principal TOTAL SYSTE EFFICIENCY: CONTROL STRATEGIES & SYSTE DISTRIBUTION David Grassl PE echanical Engineer Principal This is the second paper in the total system efficiency series that will detail various control

More information

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller Mounting and Operating Instructions Electronics from SAMSON EB 5610 EN Firmware version 1.40 Edition December 2014 Controller

More information

Technical description. Atec.

Technical description. Atec. www.thermia.com Thermia Värmepumpar is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions.

More information

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A... 70 80 99-00-O Residential Gas Condensing Boiler ZBR//8/35/4-3A... ZWB8/35/4-3A... 70 80 993 (03/03) CA/US Operating Instructions Contents Contents Key to symbols and safety instructions............................

More information

SOLAR COMBISYSTEMS IN DENMARK - THE MOST COMMON SYSTEM DESIGNS

SOLAR COMBISYSTEMS IN DENMARK - THE MOST COMMON SYSTEM DESIGNS SOLAR COMBISYSTEMS IN DENMARK - THE MOST COMMON SYSTEM DESIGNS Klaus Ellehauge SolEnergi Center Danmark, Danish Technological Institute, Energy, Teknologiparken, DK-8 Aarhus C, Tel.: +45 722 137, Fax:

More information

CALEFFI. SATK wall-mounted heat interface unit Fitted for connection to DHW storage. SATK40 series 01216/14 GB

CALEFFI. SATK wall-mounted heat interface unit Fitted for connection to DHW storage. SATK40 series 01216/14 GB 4 RESET ON DHW CH FAULT SATK wall-mounted heat interface unit Fitted for connection to DHW storage SATK4 series ACCREDITED CALEFFI 6/4 GB ISO 9 FM 64 ISO 9 No. The latest generation of heat interface units

More information