Installation and Operating Manual for the EcoStar 500 Oil Condensing Floor Standing Range Output Range kw

Size: px
Start display at page:

Download "Installation and Operating Manual for the EcoStar 500 Oil Condensing Floor Standing Range Output Range kw"

Transcription

1 Installation and Operating Manual for the EcoStar 500 Oil Condensing Floor Standing Range Output Range kw 1

2 Section 1.0 Appliance Type 1.1 ECOSTAR 500 Standard 1.2 ECOSTAR 500 Enhanced 2.0 Installation Regulations and Requirements 2.1 Appliance Warranties 3.0 Dimensions ECOSTAR Dimensions and Connections 3.6 Installation Clearances 4.0 Delivery and Mobility 5.0 Technical Data 6.0 Pressure Relief Valve 7.0 Electrical Connections 7.1 Internal Wiring Diagrams 8.0 Hydraulic Configurations 8.1 Hydraulic Single Unit 8.2 Hydraulic Cascade Unit 9.0 Filling The System 9.1 Pressure Vessel 10.0 System Water Quality 11.0 Appliance Controls 12.0 Appliance Fault Codes 13.0 Commissioning 13.1 Pre-Commissioning Checks Combustion System Commissioning 14.0 Routine Inspection and Servicing 14.1 Routine Service Inspection 14.2 Routine Cleaning and Maintenance 15.0 Weather Compensation Slope Graph and Sensor Curves 16.0 Optional System Controls (QAA73, RVA47, RVA 63, RVA46, QAA70, QAA50, QAA10) 17.0 Exploded Spares Diagrams 18.0 Parts List 18.0 Installer / End Users Note 2

3 1.0 Appliance Type There are four versions within the EcoStar 500 range. Each unit can be supplied with or without a cascade controller. Please ensure you have the correct unit for the application and where required located correctly within the cascade prior to beginning the installation. 1.1 The EcoStar 500 Standard unit without cascade controller appliances are designed to be applied to systems where the cascade control is undertaken via a remote system manager or a building management system. Either control system must be capable of providing a volt free enable per applied boiler. 1.2 The EcoStar 500 Enhanced unit with cascade controller appliances are designed to be applied to systems where the cascade control is undertaken by the lead boiler. Control of the system is enhanced by the addition of a dedicated room unit. The product codes for the standard range are: Product Name Product Code EcoStar 515 Blue Flame Oil EcoStar 518 Blue Flame Oil EcoStar 522 Blue Flame Oil EcoStar 527 Blue Flame Oil

4 2.0 Installation Regulations and Requirements MHG Heating Ltd The installation of EcoStar 500 boilers must be in accordance with the relevant requirements of Gas Safety (Installation & Use) Regulations 1994, Health & Safety at Work Act, Building Regulations, IEE Regulations, Construction (Design & Management) Regulations 1994, Local Authority Bye-Laws, National, Fire Regulations and Insurance Company requirements. The following Codes of Practice are also applicable:- BS : 2000 Installation of flues and ventilation for gas appliances of rated input not exceeding 70 kw net (1st, 2nd and 3rd family gases). Part 1: Specification for the installation of flues. BS : 2000 Installation of flues and ventilation for gas appliances of rated input not exceeding 70 kw net (1st, 2nd and 3rd family gases). Part 2: Specification for installation and maintenance of ventilation for gas appliances. BS 5449: 1990 Specification for forced circulation hot water central heating systems for domestic premises. BS 6644: 2005 Specification for gas fired hot water boilers of rated inputs between 70kW (net) and 1.8MW(net) (2nd and 3rd family gases). BS 6798: 1987 Specification for installation of gas fired hot water boilers of rated input not exceeding 60 kw. BS 6880: 1988 Code of Practice for low temperature hot water heating systems of output greater than 45kW. Parts 1, 2 & 3. BS 6891: 1988 Specification for installation of low pressure gas pipework of up to 28mm (R1) in domestic premises (2nd family gases) BS 7593: 1992 Code of Practice for treatment of water in domestic hot water central heating systems. BS 7671: 1992 Requirements for electrical installations. IEE Wiring Regulations. Sixteenth edition. CISBE Guide reference sections B7, B11 and B13. CP342 Part 2: 1974 Code of Practice for centralized hot water supply. IGE/UP/2 Gas installation pipework, boosters and compressors on industrial and commercial premises. IGE/UP/4 Commissioning of gas fired plant on industrial and commercial premises IGE/UP/10 Installation of gas appliances in industrial and commercial premises. Part 1: Flued appliances. And any addition prevailing regulation and or code of practice not detailed above. 4

5 2.1 Appliance Warranties All MHG appliances enjoy a full 36 month warranty as detailed in our terms and conditions. The guarantee period shall begin on the day of commissioning, or at latest 3 months after delivery has been made. The customer shall only be able to claim against MHG under guarantee if the commissioning of the object of delivery has been carried out by MHG staff or the authorised supplier, if the customer has followed MHG's instructions relating to the treatment and maintenance of the object of delivery, and if no replacement parts of outside origin have been fitted. Parts subject to wear such as ignition electrodes, seals etc. are strictly excluded from the guarantee. In addition to the above warranties, the Primary Heat Exchangers carry a 60 month guarantee against manufacturing or material defect. 5

6 3.0 Dimensions. ECOSTAR 500 Boilers 3.4 Dimension and Connection Dimension 6

7 3.6 Installation and Service Clearances 7

8 4.0 Delivery and Mobility All ECOSTAR 500s are supplied fully tested and therefore may contain residual test water. The test water utilised contains additives that will help prevent associated pumps from sticking and other metals from oxidising. To maintain the structural integrity of the appliance the internal components should not be used during the lifting and positioning of the unit. Place the primary heat exchanger assembly on the calorifier, boiler base or purpose made plinth. 8

9 Once correctly positioned install the baffles 1-3 as indicated above. Mount the door as indicated above. Ensure that the insulation is not damaged. 9

10 Mount the Blue Flame Rocket Burner as Indicated. Install the Burner/ Boiler wiring and control panel. 10

11 Install the thermostat probes as indicated. 11

12 Connect the remote RESET wiring. Connect the Boiler controller. Connect the field wiring loom. Connect the controller wiring HMI. Connect the Boiler Flow Sensor. Flue Gas Temperature Thermostat Install the flue gas thermostat assembly and route the cable to the controller in insert wires in place of the link wire in SK1 and SK2. 12

13 To programm the unit a QAA 75 must be connected to the control unit. This can be hard wired or if required plugged in to the boilers control facia. 13

14 An alternative to hard wiring the QAA75 room unit is to utilise a wireless QAA78 unit. A transducer must be connected to the boiler unit. 14

15 All packaging materials should be disposed of in an environmentally aware way. The unit illustrated below includes the option pump assemblies. 15

16 16

17 5.0 Technical Data Technical Data Units ECOSTAR 515 ECOSTAR 518 ECOSTAR 522 ECOSTAR 527 Number of Sections Nominal Heat Input Net Max kw Nominal Heat Output Max kw Flow and Return Connections Flue Gas Temperature OC Minimum Water Pressure bar Max Water Pressure bar Burner Burner Burner Burner Power Supply (230 V / 50 Hz) Amps Dependant Dependant Dependant Dependant Max Power Consumption Watts Burner Dependant Burner Dependant Burner Dependant Burner Dependant Limit Temperature OC Maximum Flow Temperature OC Water Content Ltrs Minimum Flow Rate Kg/S Lift Weight (Dry) kg *ECOSTAR /ECOSTAR

18 Fluing Options The appliance must be flued in accordance with prevailing regulations. An extensive range for rigid and flexible flue components are available from MHG. The diagrams indicated below are for illustrative purposes only. Flexible flue installation. 18

19 Lined flue Stack installation. 19

20 The overall length of the flue system must be calculated with reference to the respective burner manual. The addition of every 87 0 Bend reduces the overall potential length by 1m. 20

21 6.0 Pressure (Safety) Relief Valve In accordance with the prevailing British Standard 5440/6644, the installer shall install as suitably sized Pressure (Safety) Relief Valve. The location of this valve is important with respect to the applied pressure of the boiler circulation pump, it is therefore recommended to locate the Pressure (Safety) Relief Valve on the flow pipe immediately adjacent to the boiler; furthermore, there must not be any means of isolation between the boiler and the Pressure (Safety) Relief Valve. To assist with the correct positioning of the pressure relief valve hydraulic connector kits are available as an optional extra. The minimum operating pressure of the system must remain above 0.5bar. Ensure that the location of the applied circulating pumps do not reduce the pressure within the boiler to below stated minimum. System Pressure managers and system pressure vessels are available from MHG if required. 21

22 7.0 Electrical Connections Basic electrical connection for all types of ECOSTAR 500s Legend High Voltage Output and Input Terminals 230 Volts B/ATB Flue Gas Limit (supplied with link installed S3 Lockout Output B4 Burner Run Output SK1 Safety Interlock BS1 Connector Plug SK3 Safety Interlock CL- QAA Room Unit/Programmer T1 Burner Enable / Lockout RESET CL+ QAA Room Unit/Programmer T2 Burner Enable IN (230V) G Display Light Power Supply W-SB Burner Connector Plug L Unit Power Supply Live b QAA Room /Programming Unit L1 Burner Power Supply b 1 Main Power Isolator N Unit Power Supply Neutral b 3 Limit Thermostat N A Appliance Connector Plug Mains IN b 4 Flue Gas Limit Thermostat N-R Connector Plug b 5 Lockout Reset Button OEV Wiring external to the appliance b r Brown RG Connector Socket for QAA Room Unit h 6 Lockout Light (Red) RS Appliance Controller RVS 53/63 sw Black 22

23 Burner Wiring Diagram 23

24 8.0 Hydraulic Configurations The ECOSTAR 500 range has been designed to suit a vast number of installation hydraulic configurations. In all cases the minimum flow rate detailed in the appliance data table must be achieved through the units when during operational periods Single Boiler Installation Boiler Without Integral RVA Controller 24

25 8. 12 Single Boiler Installation Boiler Without Integral RVA Controller With Low Loss Header 25

26 8. 13 Single Boiler Installation Boiler With Integral RVA Controller 26

27 9.0 Filling The System The Initial filling of a sealed heating system, and subsequent refilling, must be by a method that has been approved by the Water Regulation Advisory Scheme (WRAS) for that type of heating system. i.e. Domestic (In-House) Fluid Category 3 (C-3) Non Domestic (Other than In-House) Fluid Category 4 (C-4) For Category 3 systems, the approved method of filling must comprise of the following components in the arrangement shown; Control Valve incorporating a Double Check Valve on the Mains Cold Water pipework. Temporary Connecting Hose, which must be disconnected after use. Control Valve, on the heating system. For Category 4 systems, the approved method of filling must comprise of the following components in the arrangement shown; Control Valve. Strainer. Verifiable Backflow Device with Reduced Pressure Zone (RPZ Valve) Incorporating a Type BA Air Gap. Tundish. Control Valve. Further more, in accordance with BS 6644: 2005 system with an input greater than 70kW (nett), an automatic water replenishment unit shall be installed to automatically replenish any lost or evaporated water. Please refer to BS 6644: 2005 for allowable water replenishment methods for use with sealed/pressurized heating systems. For information on a comprehensive range of pressurization units that comply with current British Standards and WRAS Regulations, please contact MHG Heating Ltd Sales. 27

28 9.1 Expansion Vessel In accordance with BS 6644: 2005, WRAS Regulations, and Local Authority Water Regulations, as applicable, the installer shall install a suitably sized, and approved, Expansion Vessel to ensure that the water capacity of the system has ample expansion capacity. The location of the expansion vessel shall only be isolatable from the system via a Lockable Type Service Valve, which shall be locked in the OPEN position, to prevent accidental isolation. Furthermore, a drain facility should be provided adjacent to the expansion vessel to aide the routine maintenance, overhaul, of the vessels Air Pressure setting. For information on a comprehensive range of expansion vessels that comply with current British Standards and WRAS Regulations, please contact MHG Heating Ltd Sales System Water Quality Water Treatment, System Cleaning (BS 7592: 2006) The entire primary system MUST be thoroughly cleaned and flushed to remove debris, flux residues, etc. before opening the boiler isolation valves & flooding the boiler. Particular care must be taken where the ECOSTAR 500 boiler is being retro-fitted into an old/existing system, as system silt or magnetite can be very damaging to the new boiler. Following cleaning and flushing the system MUST be dosed with a good quality water treatment to prevent corrosion and the formation of scale. FAILURE TO OBSERVE THESE REQUIREMENTS WILL RENDER THE WARRANTEE ON THE APPLIANCE VOID. Cleaning, flushing and water treatment must be carried out in accordance with the requirements of BS 7593:1992, prior to commissioning the boiler. Repeated draining and refilling of the system, without replenishment of water treatment, must be avoided, as this is very damaging to the boiler. The boiler must not operate without the system water being correctly and adequately treated, and maintained, with an appropriate level of corrosion inhibitor. For specific guidance on water treatment, direct contact is advisable with:- Betz Dearborn Limited (Sentiel) Foundry Lane Widnes Cheshire WA8 8UD Tel: Fax: Alpha-Fry Technologies (Fernox) Cookson Electronics Forsyth Road Sheerwater Woking Surrey GU21 5RZ Tel: Fax:

29 11.0 Appliance Controls All appliance operational mode adjustments and settings are undertaken via the QAA75 or QAA78 unit. Please refer to the QAA technical manual for setting details. The level of adjustment and functionality will be dependent upon the controller used within the unit Appliance Fault Codes Manual Reset Fault Code. A large fault code is displayed on the screen along with the symbol. The appliance will stop operating until the error has been corrected and the RESET button has been pressed. If a fault is encountered within the appliance or Cascade LPB network, a fault code will be generated and displayed by the failing appliance and all LPB networked RVA and Opentherm units. If a fault is encountered by a RVS controller or is communicated to a RVS controller via the LPB network ER will be generated on the display. In either case the fault code should be noted for future reference. If the fault is related to a specific appliance the unit can be reset by pressing the Lockout Reset Button. If the fault is related to a RVS controller or the LPB communication network the fault code will clear automatically following the rectification of the fault. This is also applicable following the rectification of any appliance fault. This can take up to 10 minutes. 29

30 30

31 Maintenance Codes Special Operation Codes 31

32 13.0 Commissioning The Appliance 13.1 Pre-Commissioning Checks Prior to undertaking the commissioning of the unit please ensure that the system water has been cleansed and treated with a suitable inhibitor as detailed in Filling the system and system water quality. Prior to applying power to the appliance its circulation pump should be bled and checked to ensure free rotation of the armature Combustion System Commissioning. Please refer to the respective burner manual to ensure that the burner and boiler are commissioned correctly. A flue gas analyser must be used to ensure that the correct combustion setting are achieved. 32

33 14.0 Routine Inspection and Servicing. As with all appliances, we would highly recommended that a competent heating engineer services the ECOSTAR 500 boiler and burner, at least every 12 months. This is assuming a normal daily usage of 8 10 hours. If however the boiler is to be operated 24 hours a day, 7 days, we would recommend services every 6 months. If the Installer/Commissioning Engineer is unable to undertake the Routine Service Inspection, as detailed in the following section for the boiler and the respective section of the installed burner manual, please contact the MHG Technical Department, who will be able to arrange the Routine Service Inspection to be undertaken Routine Service Inspection Before commencing any service/maintenance work, the following tasks must be undertaken. a) Ask the end user about any problems with the operation of the boiler unit and note their comments. b) Check the water pressure of the installation. c) Remove the boiler casing and visually inspect all pipe and water joints for signs of leakage. d) Inspect the appliance for signs of water leakage or ingress. e) Run the unit, with the use of a flue gas analyzer record the CO & CO2 levels. f) Listen to the sound of the combustion fan. g) Undertake a System Water Analysis to check the concentration level of the Water Treatment, and note the level onto the Service Report. h) Check the flue route including the terminal position for conformity with prevailing regulations, and trim back any foliage that may be around the terminal. i) Check the plant room/compartment ventilation system for conformity with prevailing regulations. j) Check the Pressure (Safety) Relief Valve size, rating and orientation, for conformity with prevailing regulations. The results of the Inspections undertaken above must be acted upon, and all discrepancies should be recorded on the Service Report and brought to the Client / End User s attention. Undertake any maintenance, and if necessary any preventative maintenance, that s required Routine Cleaning & Maintenance As part of the Routine Service Inspection, certain areas of the boiler need to the checked and cleaned as necessary. a) Turn the boiler OFF at the ON/OFF switch and electrically isolate the boiler by removing the plug or fuse from the boiler supply. b) Turn off the fuel supply at the boiler isolation tap, fitted by the installer, adjacent to the appliance. c) Remove the electrical connections from the burner. d) Remove the burner from the boiler. e) Undertake the necessary cleaning, inspections and adjustments for the burner as detailed in the respective manual. f) Remove the front outer case and heat exchanger cover place to gain access to the heat exchanger. g) Utilize the supplied flue way brush to clean the flue ways and combustion chamber. h) If a combined unit is being serviced the Magnesium anode must be inspected. All necessary water treatments must be undertaken following the inspection of the anode. i) Re-fit the cover plates and the Burner in the reverse order of dismantling, ensure that all electrical connections are correctly and securely connected. j) Inspect all water joints. Any joints found to be leaking MUST be replaced. It is also advisable when replacing water joints to also change any adjacent joints at the same time. k) Inspect all fuel joints with a suitable leak detection method. Any joints found to be leaking MUST be replaced. It is also advisable when replacing joints to also change any adjacent joints at the same time. l) With the use of a suitable Flue Gas Analyser, check and adjust the combustion settings, as detailed in the respective burners manual. m) Inspect the general condition of the flue system, including the termination, repair as necessary or advice on any remedial action as required. n) Following the satisfactory completion of the above service procedure complete the required paperwork and leave the boiler as found if possible. 33

34 15.0 Weather Compensation Slope Flow Sensor Curve 34

35 Outside Air Sensor Curve Hydraulic Resistance 35

36 16.0 Optional System Controls. If required the following controls can be applied to the ECOSTAR 500 range to enhance boiler and system operational efficiency and longevity. (Further detailed guidance can be obtained from the respective controller manuals.) RVA47 Cascade Manager. This cascade manager has the capability to control up to twelve appliances, one CT circuit and one HWS primary circuit. The RVA47 cascade manager communicates with the RVA63 & 46 zone controllers via LPB, offering enhanced communication, zone and module temperature control. A dedicated housing is also available to ease the installation process. RVA63 Dual Zone Controller. This dual zone controller has the capability to control up to two independent CT/VT or a mixture of both. The RVA63 dual zone controller communicates with the master boiler mounted RVA47 Cascade Manager via LPB, offering enhanced communication, zone and module temperature control. A dedicated housing is also available to ease the installation process. RVA46 Single Zone Controller. This single zone controller has the capability to control one CT/VT zone. The RVA46 single zone controller communicates with the master boiler mounted RVA47 Cascade Manager via LPB, offering enhanced communication, zone and module temperature control. A dedicated housing is also available to ease the installation process. QAA70 Modulating Full Function Room Unit.(One unit per zone.) This modulating full function room unit offers the heating user full remote access to the all functions that effect the provision of heat to the respective zone. The unit also displays information from all attached temperature sensors. Boiler, Hot water, Outside and remote tamperproof room unit(qaw44). QAA50 Modulating Limited Function Room Unit.(One unit per zone.) This modulating limited function room unit offers the heating user reduced remote access to operating mode and temperature functions that effect the provision of heat to the respective zone. QAA10 Modulating Tamper-proof Room Sensor. (One Unit per zone.) This modulating tamper-proof room unit offers room temperature feedback from the heated space that effects the provision of heat to the respective zone. 36

37 17.0 Exploded Spares Diagram 37

38 18.0 Parts List 38

39 39

40 40

41 41

42 42

43 43

44 44

45 45

46 46

47 47

48 Notes 48

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual. 1 MHG Heating Ltd ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual. Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey, KT20 5LR Telephone 08456 448802 Fax 08456 448803

More information

Installation and Operating Manual for the ProCon 16, 27, 47, 75 & 77 Wall Mounted Condensing Boiler Range.

Installation and Operating Manual for the ProCon 16, 27, 47, 75 & 77 Wall Mounted Condensing Boiler Range. Installation and Operating Manual for the ProCon 16, 27, 47, 75 & 77 Wall Mounted Condensing Boiler Range. 1 Section Page # 1.0 Appliance Type 3 1.1 ProCon H 3 1.2 ProCon S 3 1.3 ProCon HS 3 1.4 ProCon

More information

Installation and Operating Manual for the ProCon HT 150 & 225 Floor Standing Condensing Boiler Range.

Installation and Operating Manual for the ProCon HT 150 & 225 Floor Standing Condensing Boiler Range. Installation and Operating Manual for the ProCon HT 150 & 225 Floor Standing Condensing Boiler Range. MHG Heating Ltd, Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey, KT20 5LR 0845 6448802

More information

Ultramax PB. Floor standing premix gas fired condensing boilers with outputs at 65, 85, 100 & 120kW BOILERS

Ultramax PB. Floor standing premix gas fired condensing boilers with outputs at 65, 85, 100 & 120kW BOILERS Ultramax PB Floor standing premix gas fired condensing boilers with outputs at 65, 5, 100 & 120kW BOILERS Feature packed and powerful Ultramax PB range of floor standing boilers includes four models with

More information

Contents. 1 General Appliance Type Single Units Cascade Manager Units Cascade Slave Units...

Contents. 1 General Appliance Type Single Units Cascade Manager Units Cascade Slave Units... 1 Contents 1 General... 3 1.1 Appliance Type... 3 1.1.1 Single Units... 3 1.1.2 Cascade Manager Units... 4 1.1.3 Cascade Slave Units... 4 2 Installation... 5 2.1 Installation Regulations and Requirements...

More information

Euron. Compact Wall Mounted Gas Fired Condensing Boilers and Combis with Outputs 24kW - 30kW BOILERS

Euron. Compact Wall Mounted Gas Fired Condensing Boilers and Combis with Outputs 24kW - 30kW BOILERS Euron Compact Wall Mounted as Fired Condensing Boilers and Combis with Outputs 24kW - 30kW BOILERS Compact, Efficient & Easy to Install & Maintain The Euron range of wall mounted gas fired condensing boilers

More information

Cast Iron Boilers. G Series ( kW)

Cast Iron Boilers. G Series ( kW) Cast Iron Boilers G Series (320-1017kW) Mikrotherm G Series Cast Iron Boilers The Mikrotherm G Series of cast iron sectional boilers offer all the advantages of cast iron durability and longevity coupled

More information

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL STREBEL GENEVA CE ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL INDEX TABLE 1 TECHNICAL DATA SECTION 1 SECTION 2 SECTION 3 SECTION 4 SECTION 5 SECTION 6 SECTION 7 SECTION 8 SECTION

More information

ProCon Boiler Controller Commissioning Quick Reference Guide

ProCon Boiler Controller Commissioning Quick Reference Guide ProCon Boiler Controller Commissioning Quick Reference Guide This sheet is intended as a quick reference guide and should be read in conjunction with the operating and maintenance manual for the boiler

More information

Installation and Operating Manual for the ProCon HT & HTP 150 & 225 Floor Standing Condensing Boiler Range. **RVS Controlled**

Installation and Operating Manual for the ProCon HT & HTP 150 & 225 Floor Standing Condensing Boiler Range. **RVS Controlled** Installation and Operating Manual for the ProCon HT & HTP 150 & 225 Floor Standing Condensing Boiler Range. **RVS Controlled** MHG Heating Ltd, Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey,

More information

GAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw

GAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw GAS FIRED ATMOSPHERIC ELECTRONIC VERSION 51-102 kw GENERAL DESCRIPTION 900 D a3 1000 762 672 E 222 The PEGASUS F2 range of atmospheric natural gas-fired boilers are constructed of cast iron finned sections

More information

Installation and Operating Manual for the ProCon 47, 75 & 77 Wall Mounted Condensing Boiler Range

Installation and Operating Manual for the ProCon 47, 75 & 77 Wall Mounted Condensing Boiler Range Installation and Operating Manual for the ProCon 47, 75 & 77 Wall Mounted Condensing Boiler Range 1 Section Page # 1.0 Appliance Type 3 2.0 Installation Regulations and Requirements 4 2.1 Appliance Warranties

More information

Jetflush 4 Instruction Manual

Jetflush 4 Instruction Manual The Sentinel range of water treatment products for domestic central heating systems. GE Water & Process Technologies Jetflush 4 Instruction Manual Foundry Lane, Widnes, Cheshire WA8 8UD. Tel: 0151 420

More information

Thision L. Wall mounted gas fired condensing boilers with individual unit outputs from 48kW to 145kW and multi-boiler cascade sets up to 1140kW

Thision L. Wall mounted gas fired condensing boilers with individual unit outputs from 48kW to 145kW and multi-boiler cascade sets up to 1140kW Thision L Wall mounted gas fired condensing boilers with individual unit outputs from 48kW to 145kW and multi-boiler cascade sets up to 1140kW Dependable performance and lifelong high efficiency The Thision

More information

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw Superior A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler Outputs 120, 160, 200, 240, 280 kw 1 The Superior is a, pre-assembled floor standing, gas fired high efficiency

More information

SEALED THERMAL STORE

SEALED THERMAL STORE ISSUE 3 0717 INSTALLATION AND USER GUIDE ENERGYMANAGER SEALED THERMAL STORE ADVANCE APPLIANCES LTD PLEASE RETAIN AND ENSURE SERVICE RECORDS ARE KEPT UP TO DATE. SCHEMATIC DIAGRAM OF ENERYMANAGER THERMAL

More information

Assessment Schedule - TS.6

Assessment Schedule - TS.6 The Assessor shall determine the business s commitment and support to good and safe working practices; also that it has a positive culture in all aspects of its work. In particular, the assessor shall

More information

Sirius FS. Working towards a cleaner future

Sirius FS. Working towards a cleaner future Sirius FS Floor Standing Stainless Steel Condensing Boilers Single Boiler Applications: 50 to 160kW Modular Boiler Applications: up to 640kW Working towards a cleaner future heating specialists 1. Product

More information

Ultramax R600. High output, floor standing gas fired condensing boilers with outputs from 150kW to 571kW

Ultramax R600. High output, floor standing gas fired condensing boilers with outputs from 150kW to 571kW Ultramax R600 High output, floor standing gas fired condensing boilers with outputs from 150kW to 571kW Delivering excellence with every feature The Ultramax R600 series of boilers is packed with features

More information

DANESMOOR 12-14, 15-19, 20-25, 26-32, 32-50, FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE

DANESMOOR 12-14, 15-19, 20-25, 26-32, 32-50, FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE DANESMOOR 12-14, 15-19, 20-25, 26-32, 32-50, 50-70 FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE EXCELLENCE COMES AS STANDARD Thank you for purchasing a Danesmoor

More information

HHIC consumer guide to gas boiler servicing

HHIC consumer guide to gas boiler servicing HHIC consumer guide to gas boiler servicing Gas Boiler Servicing Keep your home heating system in good working order. As a consumer, it is reasonable to assume that when procuring a service of your gas

More information

Clyde CK40. Cast Iron Boiler. Engineering Data Sheet 663/8 May Natural gas Class D oil Dual Fuel. 350 kw to 500 kw

Clyde CK40. Cast Iron Boiler. Engineering Data Sheet 663/8 May Natural gas Class D oil Dual Fuel. 350 kw to 500 kw atural gas Class D oil Dual Fuel 350 kw to 500 kw Clyde CK40 Cast Iron Boiler Contents Page General information Dimensions 3 Technical data 3 Installation requirements 4 & 5 Boiler control panel 6 Wiring

More information

LST Plus Vertical. Plus Vertical 3 models. Lengths: 560mm, 660mm & 760mm. Outputs: 1335 to 1862 watts, 4555 to 6353 Btu/hr

LST Plus Vertical. Plus Vertical 3 models. Lengths: 560mm, 660mm & 760mm. Outputs: 1335 to 1862 watts, 4555 to 6353 Btu/hr LST Plus Vertical CPD BIM Height: Plus Vertical 3 models 2110mm Lengths: 560mm, 660mm & 760mm Outputs: 1335 to 1862 watts, 4555 to 6353 Btu/hr Type: K2 Safety Stelrad has created a range of Low Surface

More information

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data. ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data. The RVA 46 Zone Controller can only be used in conjunction with a RVA47 controlled boiler installation. The RVA46 controller

More information

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500 Unvented Calorifier Range. Operating and Maintenance Manual. For Models 125 300 & 500 Telephone 08456 448802 Fax 08456 448803 Emial info@mhgheating.co.uk Web www.mhgheating.co.uk TABLE OF CONTENTS. Section

More information

Clyde Alkon 90. Floor standing condensing boilers. Natural Gas. 90 kw. LP Gas. 90 kw

Clyde Alkon 90. Floor standing condensing boilers. Natural Gas. 90 kw. LP Gas. 90 kw 90 kw Clyde Alkon 90 LP Gas Floor standing condensing boilers Natural Gas 90 kw Contents General information Dimensions and Data Installation requirements Boiler wiring diagram Hydraulic systems Page Fully

More information

Bath Shower Mixer

Bath Shower Mixer 86004490 Bath Shower Mixer Installation and operating instructions The showerhead and hose supplied with this product are a safety critical part of your shower. Failure to use genuine Triton parts may

More information

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB 6 720 648 662-00.1T UNI 7000 F Operating instructions For the user AU/G 2 Contents Contents Contents 2 1 Safety information and explanation of symbols 3 1.1 For your safety 3 1.2 Explanation of symbols

More information

DANESMOOR FRONT SERVICE (FS) 12-18, FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE

DANESMOOR FRONT SERVICE (FS) 12-18, FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE DANESMOOR FRONT SERVICE (FS) 12-18, 18-25 FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE EXCELLENCE COMES AS STANDARD Thank you for purchasing a Danesmoor Front Servicing

More information

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15 CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15 COMPACT PLUS 10 and 15 Litre Unvented Under and Over Sink Water Heater INSTALLATION AND USER GUIDE 1 DIMENSIONS 10L - 250mm 15L - 310mm 100mm 80mm 410mm

More information

FLUEBOOST. flueboost 350 gas fire model

FLUEBOOST. flueboost 350 gas fire model 350 FLUEBOOST flueboost 350 gas fire model The flueboost is a box shaped unit with in line spigots for the flue connection, a pressure switch to ensure safe operation and plug-in electrical fittings for

More information

Baxi Maxflow Combi WM

Baxi Maxflow Combi WM Baxi Maxflow Combi WM Gas Fired Wall Mounted Combination Boiler with Unvented Hot Water Storage Please keep these instructions safe. Should you move house, please hand them over to the next occupier. User

More information

Dene Bath Shower Mixer

Dene Bath Shower Mixer Dene Bath Shower Mixer Installation and operating instructions The showerhead and hose supplied with this product are an integral part of the safety of your shower. Failure to use genuine Triton parts

More information

TEMPRA. Wall Mounted Fan Flue System boiler. Wall mounted fanned flue boiler INSTALLATION AND USE INSTRUCTIONS. Appr. nr. B A - CE 0063 AQ 2150

TEMPRA. Wall Mounted Fan Flue System boiler. Wall mounted fanned flue boiler INSTALLATION AND USE INSTRUCTIONS. Appr. nr. B A - CE 0063 AQ 2150 Wall Mounted Fan Flue System boiler Appr. nr. B 94.04 A - CE 0063 AQ 2150 Phone numbers: Installer Service Engineer Serial N Wall mounted fanned flue boiler INSTALLATION AND USE INSTRUCTIONS Please read

More information

Unvented Electric Water Heater 10/15 litre Undersink

Unvented Electric Water Heater 10/15 litre Undersink Unvented Electric Water Heater 10/15 litre Undersink Fitting Instructions and User Guide 1 CONTENTS SECTION PAGE 1.0 INTRODUCTION 2 2.0 TECHNICAL SPECIFICATION 3 3.0 INSTALLATION 4 4.0 COMMISSIONING 9

More information

Calder. Steel Hot Water Boiler Suitable for Pressure Jet burners Oil, gas, LPG or dual fuel firing. Outputs kw. Calder Model

Calder. Steel Hot Water Boiler Suitable for Pressure Jet burners Oil, gas, LPG or dual fuel firing. Outputs kw. Calder Model Calder Steel Hot Water Boiler Suitable for Pressure Jet burners Oil, gas, LPG or dual fuel firing Outputs 70-3500 kw Calder Model 70-1300 Calder Model 1400-3500 Calder - Steel Hot Water Boiler The Calder

More information

ferroli Boiler Replacement Maxima 35C- Modena HE

ferroli Boiler Replacement Maxima 35C- Modena HE ferroli Boiler Replacement Maxima 35C- Modena HE Introduction Although the new Ferroli Modena 32C HE high efficiency condensing combination boiler has an output slightly less than that of the Ferroli Maxima

More information

Calder Plus. High Efficiency Steel Hot Water Boiler Suitable for Pressure Jet burners Gas or LPG firing. Outputs kw. Calder Plus Model

Calder Plus. High Efficiency Steel Hot Water Boiler Suitable for Pressure Jet burners Gas or LPG firing. Outputs kw. Calder Plus Model Calder Plus High Efficiency Steel Hot Water Boiler Suitable for Pressure Jet burners Gas or LPG firing Outputs 70-3500 kw Calder Plus Model 70-1300 Calder Plus Model 1400-3500 Calder Plus - High Efficiency

More information

ADVANCE ECB ELECTRIC COMBINATION BOILER

ADVANCE ECB ELECTRIC COMBINATION BOILER ISSUE ISSUE 45 0115 0317 INSTALLATION AND USER GUIDE ADVANCE ECB ELECTRIC COMBINATION BOILER ADVANCE APPLIANCES LTD HOUSEHOLDER - PLEASE RETAIN AND ENSURE SERVICE RECORDS ARE KEPT UP TO DATE 1 SCHEMATIC

More information

FCX FUEL OIL CONDENSING BOILER RANGE

FCX FUEL OIL CONDENSING BOILER RANGE FCX FUEL OIL CONDENSING BOILER RANGE BOILERS FUEL OIL, CONDENSING CHIMNEY OR BALANCED FLUE HEATING ONLY DOMESTIC HOT WATER OPTIONS OUTPUT 22.3 kw or 30.5 kw Why choose a Geminox boiler? To benefit from

More information

Remeha Avanta Plus. Remeha Avanta Plus. Installation and service manual. Remeha Avanta Plus 28c. Remeha Avanta Plus 35c. Remeha Avanta Plus 39c

Remeha Avanta Plus. Remeha Avanta Plus. Installation and service manual. Remeha Avanta Plus 28c. Remeha Avanta Plus 35c. Remeha Avanta Plus 39c Installation and service manual Remeha Avanta Plus Remeha Avanta Plus Remeha Avanta Plus 28c Remeha Avanta Plus 35c Remeha Avanta Plus 39c Remeha Avanta Plus 24s 1 Remeha Avanta Plus INTRODUCTION 1 SAFETY

More information

USERS GUIDE 24, 30. For installation guide see reverse of book

USERS GUIDE 24, 30. For installation guide see reverse of book USERS GUIDE 24, 30 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification

More information

Hoval Cosmo heating boilers, outputs from 100 to 4000kW. Working pressures to 8 bar. Heatpack boilers. to 2900kW.

Hoval Cosmo heating boilers, outputs from 100 to 4000kW. Working pressures to 8 bar. Heatpack boilers. to 2900kW. Hoval Cosmo heating boilers, outputs from 100 to 4000kW. Working pressures to bar. Heatpack boilers to 2900kW. Whether your application is for single, multiple or space saving heatpack boilers, Hoval always

More information

INSTALLATION MANUAL. RD SERIES Digital Electric Water Heater Wall-hung Unvented

INSTALLATION MANUAL. RD SERIES Digital Electric Water Heater Wall-hung Unvented INSTALLATION MANUAL RD SERIES Digital Electric Water Heater Wall-hung Unvented WELCOME Dear Customer, Thank you for choosing the RD Series electric water heater, with an exclusive electronic temperature

More information

System s30. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS SYSTEM BOILER

System s30. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS SYSTEM BOILER System s30 User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS SYSTEM BOILER When replacing any part on this appliance, use only spare parts that you can be assured conform to the

More information

Hamworthy. Dorchester DR-SA & DR-SE Fully Automatic and Permanent Pilot Direct Gas-Fired Storage Water Heaters. Exceeds Minimum Requirements

Hamworthy. Dorchester DR-SA & DR-SE Fully Automatic and Permanent Pilot Direct Gas-Fired Storage Water Heaters. Exceeds Minimum Requirements Exceeds Minimum Requirements Hamworthy Dorchester DR-SA & DR-SE Fully Automatic and Permanent Pilot Direct Gas-Fired Storage Water Heaters 18.9 kw to 20.1 kw, Natural Gas or LPG Continuous outputs 369

More information

INSTALLATION AND SERVICING

INSTALLATION AND SERVICING AND SERVICING HARRIER GTS 5-9 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use reconditioned

More information

Alpha CombiMax 350 and 600

Alpha CombiMax 350 and 600 Installation and Servicing Instructions Alpha CombiMax 350 and 600 Unvented Hot Water Store for use with the Alpha 240/280 Range of Gas Fired Combination Boilers For Technical help or for Service call...

More information

Baxi Maxflow Combi FS

Baxi Maxflow Combi FS Baxi Maxflow Combi FS Gas Fired Floor Standing Combination Boiler with Unvented Hot Water Storage Please keep these instructions safe. Should you move house, please hand them over to the next occupier.

More information

Installation, operating and servicing instructions

Installation, operating and servicing instructions English 57-115 - 144-1 - 259 Installation, operating and servicing instructions ITALIA EN 1 ITALIA English INDEX WARnINGS 3 Who should read these instructions 3 Symbols 3 Recommendations 3 Importants notes

More information

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A cod. 6272262A GENERAL DATA Heating Data Heat Output Input (Adjustable) (Adjustable) Format 34i 11.2 34KW 45 145MJ/hr Format 34e 11.2 34KW 45 145MJ/hr General Specifications FORMAT 34i 34e Main burner injectors

More information

Alpha FlowSmart 25 and 50

Alpha FlowSmart 25 and 50 Installation and Servicing Instructions Alpha FlowSmart 25 and 50 Hot Water System incorporating a Flue Gas Heat Recovery Device, Primary Store and an Alpha CD Condensing Combination Boiler For Technical

More information

Baxi System 100 HE Plus. User s Operating Instructions. Wall Mounted Powered Flue Condensing Gas Fired Central Heating Boiler

Baxi System 100 HE Plus. User s Operating Instructions. Wall Mounted Powered Flue Condensing Gas Fired Central Heating Boiler User s Operating Instructions Baxi System 100 HE Plus Wall Mounted Powered Flue Condensing Gas Fired Central Heating Boiler Please keep these instructions safe. Should you move house, please hand them

More information

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book USER GUIDE IMAX XTRA EL 320-620kW For Installation Guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

remeha Gas 3c ECO Technical information Fully condensing atmospheric gas boiler kw

remeha Gas 3c ECO Technical information Fully condensing atmospheric gas boiler kw remeha Gas 3c ECO Technical information Fully condensing atmospheric gas boiler 101-407 kw 1 remeha Gas 3c ECO CONTENTS Preface 2 1. Boiler description 3 2. Construction 3 2.1 General 3 2.2 The burners

More information

Sirius WH. Working towards a cleaner future

Sirius WH. Working towards a cleaner future Sirius WH Wall Hung Stainless Steel Condensing Boilers Single Boiler Applications: 50 to 110kW Modular Boiler Applications: up to 880kW Working towards a cleaner future heating specialists 1. Product Overview

More information

USER GUIDE LOGIC HEAT H

USER GUIDE LOGIC HEAT H USER GUIDE LOGIC HEAT H 12 15 18 24 30 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not

More information

S-AF Floor Standing Condensing Boiler kW

S-AF Floor Standing Condensing Boiler kW Clean Heating Naturally STREBEL MMERCIAL BOILERS S-AF Floor Standing Condensing 11-620 Why choose Strebel? S-AF Floor Standing Condensing Strebel Ltd has been supplying, installing and servicing coercial

More information

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600 I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d Model code: BORA600 Contact Caple on 0844 8003830 or for spare parts www.4caple.co.uk 1 Y O U R A P P L I A N C E Thank you for buying your

More information

DIRECTIVE NO: D-B

DIRECTIVE NO: D-B DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting

More information

USER GUIDE VOGUE MAX SYSTEM

USER GUIDE VOGUE MAX SYSTEM USER GUIDE VOGUE MAX SYSTEM 15 18 26 32 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not

More information

Hoval SR-plus heating boilers Outputs from 350 to 4000kW Working pressures to 8 bar

Hoval SR-plus heating boilers Outputs from 350 to 4000kW Working pressures to 8 bar Hoval SR-plus heating boilers Outputs from 30 to 4000kW Working pressures to 8 bar ...built in the UK where high quality and reliability have been a way of life for generations. Hoval SR-plus Simplicity

More information

Installation and Servicing Instructions. Alpha FlowSmart

Installation and Servicing Instructions. Alpha FlowSmart Installation and Servicing Instructions Alpha FlowSmart Hot Water System incorporating an Alpha InTec 30/40GS Condensing Combination Boiler with Integrated Flue Gas Heat Recovery Device and wall mounted

More information

940ES Tankless Water Heater

940ES Tankless Water Heater Engineering Submittal Sheet Overview and Certifications LOW-LEAD U P C C US Massachusetts Plumbing Board Approved Engineering Specifications Water heater shall be a Model Therm 940 ES. Plant shall consist

More information

CAST IRON PREMIX HIGH EFFICIENCY GAS FIRED BOILER kw BRILEY DESIGN MANUAL

CAST IRON PREMIX HIGH EFFICIENCY GAS FIRED BOILER kw BRILEY DESIGN MANUAL BRILEY CAST IRON PREMIX HIGH EFFICIENCY GAS FIRED BOILER 60 140 kw 0604.2 Beeston Briley cast-iron premix gas-fired boiler 60-140kW Contents 1 Boiler specifications Page 3 2 Appliance general dimensions

More information

USERS GUIDE. Esprit eco 24, 30. For installation guide see reverse of book

USERS GUIDE. Esprit eco 24, 30. For installation guide see reverse of book USERS GUIDE Esprit eco 24, 30 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification

More information

Fusion 200, 300 & 500

Fusion 200, 300 & 500 Fusion 200, 300 & 500 Installation and Operating Manual Issue 07/07 Part of The Mikrofill Group Contents 1 Fusion 2 1.1. Safety Provisions 3 1.2. Delivery 3 1.3. Hydraulic system Diagram 3 1.4. 2 Fusions

More information

USER INSTRUCTIONS & CUSTOMER CARE GUIDE Si II SERIES

USER INSTRUCTIONS & CUSTOMER CARE GUIDE Si II SERIES 24-28Si II SERIES G.C. NUMBERS APPLIANCE NATURAL GAS L.P.G. 24Si II 47 311 65 47 311 66 28Si II 47 311 67 47 311 68 USER INSTRUCTIONS & CUSTOMER CARE GUIDE EXCELLENCE COMES AS STANDARD CONTENTS Page No.

More information

INSTALLATION AND SERVICING

INSTALLATION AND SERVICING INSTALLATION AND SERVICING IMAX XTRA E80 E120 E160 E200 E240 E280 For Users Guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to

More information

INSTALLATION & TECHNICAL MANUAL

INSTALLATION & TECHNICAL MANUAL The COMET Range of Boilers the ultimate solution for central heating INSTALLATION & TECHNICAL MANUAL If you require any further assistance: Telephone: 01698 820533 Fax: 01698 825697 E-mail: info@electric-heatingcompany.co.uk

More information

940ES Tankless Water Heater

940ES Tankless Water Heater Engineering Submittal Sheet Dimensions and Connections B C D C Combustion air inlet Exhaust outlet Optional combustion air inlet Top view Top view A Hot water outlet Cold water inlet E F Front view Side

More information

ADMP. Commercial Atmospheric Water Heater ADM - 40/50/60/80/90/115. Installation, User and Service Manual. Innovation has a name.

ADMP. Commercial Atmospheric Water Heater ADM - 40/50/60/80/90/115. Installation, User and Service Manual. Innovation has a name. ADMP Commercial Atmospheric Water Heater ADM - 0/50/60/80/90/115 0311812 2718-ChangesReserved. Installation, User and Service Manual Innovation has a name. your installer A.O. Smith UK, Unit B8 Amstrong

More information

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5 4 ±0.5 12.0 Servicing 12.2 Annual Servicing Inspection (Cont) Flame Sensing 5 ±1 10 ±1 Position Fig. 45 Spark Ignition 5. Remove the clip securing the gas feed pipe to the air/gas venturi. Disconnect the

More information

Installation & Service Manual Remeha Avanta Range. 24c 28c 35c 39c 18s 24s 30s

Installation & Service Manual Remeha Avanta Range. 24c 28c 35c 39c 18s 24s 30s Installation & Service Manual Remeha Avanta Range 24c 28c 35c 39c 18s 24s 30s Remeha Avanta Plus Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers

More information

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No 53 416 06 Publication No. ZZ 180/17 May 2000 These appliances are tested and certified by B G Technology for

More information

Ca 6s and BCa 6s kw INSTALLATION AND OPERATING INSTRUCTIONS. Page 1 31/07/00

Ca 6s and BCa 6s kw INSTALLATION AND OPERATING INSTRUCTIONS. Page 1 31/07/00 Ca 6s and BCa 6s 33-64 kw INSTALLATION AND OPERATING INSTRUCTIONS Page 1 CONTENTS: General specification Dimensions for Ca6s and BCa6s boilers. Boiler room clearance requirements Boiler block assembly

More information

Combi C30 & C35. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

Combi C30 & C35. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER Combi C30 & C35 User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER When replacing any part on this appliance, use only spare parts that you can be assured confirm

More information

Heat 45 & 55. User Instructions FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

Heat 45 & 55. User Instructions FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER Heat 45 & 55 User Instructions FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER CE/PI No. 86-CN-69 Heat 45 - GC No. 41-930-40 Heat 55 - GC No. 41-930-41 These instructions

More information

Vote for your Installer of the year at HEATSLAVE

Vote for your Installer of the year at   HEATSLAVE Vote for your Installer of the year at www.worcester-bosch.co.uk HEATSLAVE 12/14, 15/19, 20/25, 26/32 FLOOR-STANDING OIL-FIRED COMBINATION BOILERS FOR CENTRAL HEATING AND MAINS-FED DOMESTIC HOT WATER USER

More information

Installation and Servicing Instructions

Installation and Servicing Instructions Installation and Servicing Instructions Zenex GasSaver GS-1 Passive Flue Gas Heat Recovery Device (PFGHRD) Recognised by the Government s Standard Assessment Procedure (SAP) IMPORTANT: Read these instructions

More information

Owner s Manual. Installation Details Owner s Information Warranty. 25L and 50L Electric Storage Water Heater

Owner s Manual. Installation Details Owner s Information Warranty. 25L and 50L Electric Storage Water Heater Owner s Manual & Installation guide 25L and 50L Electric Storage Water Heater MODELS 25W124, 25W136, 25W124P, 50W124, 50W136, 50W124P Installation Details Owner s Information Warranty For advice, repairs

More information

copper wall-mounted system, gas fired boiler for central heating, fan assisted, room sealed compartment, electronic flame ignition and control

copper wall-mounted system, gas fired boiler for central heating, fan assisted, room sealed compartment, electronic flame ignition and control TEMPRA 30 copper wall-mounted system, gas fired boiler for central heating, fan assisted, room sealed compartment, electronic flame ignition and control cod. 3543806/4-04/2005 Appr. nr. B99.05 A - CE 0461

More information

OWNER S GUIDE. Electric and Gas Storage Water Heaters. Safety Information Owner s Information Warranty. Models

OWNER S GUIDE. Electric and Gas Storage Water Heaters. Safety Information Owner s Information Warranty. Models OWNER S GUIDE Electric and Gas Storage Water Heaters Safety Information Owner s Information Warranty Models Electric Storage Water Heaters: 25THMS124P 25THMS136 50THMS124P 50THMS136 80THM136 125THM118

More information

Remeha Quinta 115. Technical information. Remeha Quinta 115. High-efficiency. condensing boiler for wall. mounted installation.

Remeha Quinta 115. Technical information. Remeha Quinta 115. High-efficiency. condensing boiler for wall. mounted installation. Technical information Remeha Quinta 115 Remeha Quinta 115 High-efficiency condensing boiler for wall mounted installation Output: 18-115 kw 111352.indd 1 2-4-2009 13:19:41 Remeha Quinta 115 TABLE OF CONTENT

More information

Baxi Bahama 100. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

Baxi Bahama 100. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions Baxi Bahama 100 Please keep these instructions safe. Should you move house, please hand them over to the next occupier. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Natural Gas

More information

Model No: Little Devil II (inc ss)

Model No: Little Devil II (inc ss) GAS HEATER Model No: Little Devil II (inc ss) PART NO: 6926020, 6926025 (SS) OPERATION & MAINTENANCE INSTRUCTIONS LS1213 INTRODUCTION Thank you for purchasing this CLARKE Gas Heater. Before attempting

More information

Remeha Quinta 85. Technical information. Remeha Quinta 85. High-efficiency. condensing boiler for wall. mounted installation.

Remeha Quinta 85. Technical information. Remeha Quinta 85. High-efficiency. condensing boiler for wall. mounted installation. Technical information Remeha Quinta 85 Remeha Quinta 85 High-efficiency condensing boiler for wall mounted installation Output: 14-90 kw TABLE OF CONTENT Preface 5 1 General description of the boiler 6

More information

superrange Super Series 4, Super Plus High efficiency modular boilers kW Commercial & Industrial Boilers

superrange Super Series 4, Super Plus High efficiency modular boilers kW Commercial & Industrial Boilers superrange Super Series 4, Super Plus High efficiency modular boilers 50-600kW Commercial & Industrial Boilers the super range Contents Introduction 3 The Super range 4-5 Product specification 6-7 System

More information

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. The RVA63 controller can be utilized to control the following system configurations via LPB communication. Equipment Required

More information

Domestic Gas Safety Assessments (DGA) Competency Assessment Certification Scheme for Registered Gas Installers

Domestic Gas Safety Assessments (DGA) Competency Assessment Certification Scheme for Registered Gas Installers Domestic Gas Safety Assessments (DGA) Competency Assessment Certification Scheme for Registered Gas Installers Issue 1 September 2013 Public Version REFERENCE: QUERIES TO: CER/13/273 Paul Tierney (ptierney@cer.ie)

More information

Highflow 400 ELECTRONIC BF FLOOR STANDING COMBINATION APPLIANCE FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER

Highflow 400 ELECTRONIC BF FLOOR STANDING COMBINATION APPLIANCE FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER Highflow 400 ELECTRONIC BF FLOOR STANDING COMBINATION APPLIANCE FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS GC NUMBER NATURAL GAS 47 311 62 BOILER OUTPUT

More information

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION SOLARCYL IM/SC INSTALLATION MANUAL This manual gives detailed advice for installation and should be read carefully prior to fitting any unvented

More information

i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book UIN A05 October 2017

i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book UIN A05 October 2017 24 1 2 23 3 4 5 20 6 I 19 7 18 8 9 15 14 11 13 12 i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book i 24 OFF MAX E STATUS BURNER RESET MIN PRE MIN MAX HEAT PREHEAT

More information

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION Ecoline Geo RI HP INSTALLATION MANUAL The Ecoline GEO is an indirect unvented cylinder designed and approved for use with a heat pump. The

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL HOT WATER HEATING BOILERS DOMESTIC WATER HEATERS 150,000-300,000 Btu/hr MODELS EB-EWU-02 IMPORTANT INSTALLER - AFFIX INSTALLATION MANUAL ADJACENT TO THE BOILER CONSUMER - RETAIN

More information

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40 USER GUIDE VOGUE COMBI GEN2 C26 C32 C40 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not

More information

User, Installation and Servicing Instructions. Silverlink 600 Gas Griddles GS4 and GS7 IS212 ECN3592

User, Installation and Servicing Instructions. Silverlink 600 Gas Griddles GS4 and GS7 IS212 ECN3592 User, Installation and Servicing Instructions Silverlink 600 Gas Griddles GS4 and GS7 IS212 ECN3592 INSTALLATION AND SERVICING INSTRUCTIONS Please read the following carefully before commencing work on

More information

Performa System 12e, 18e, 24e & 28e

Performa System 12e, 18e, 24e & 28e Performa System 12e, 18e, 24e & 28e Gas Fired Wall Mounted System Boilers Installation and Servicing Instructions Please leave these instructions with the user Natural Gas Potterton Performa System 12e

More information

RECESSED WARM CEILING HEATERS MODELS HSRCH3000RF, HSRCH4500RF INSTALLATION AND OPERATING MANUAL

RECESSED WARM CEILING HEATERS MODELS HSRCH3000RF, HSRCH4500RF INSTALLATION AND OPERATING MANUAL HSPBRF HSTIRF HSVTRF RECESSED WARM CEILING HEATERS MODELS HSRCH3000RF, HSRCH4500RF INSTALLATION AND OPERATING MANUAL INDEX Section General information -----------------------------------------------------------

More information

Logic+ Combi

Logic+ Combi USER GUIDE Logic+ Combi 24 30 35 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use

More information