H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

Size: px
Start display at page:

Download "H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog"

Transcription

1 H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog

2

3 Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size Unit Orientation Revision Voltage Interior Corrosion Protection Model Option A1 - Cooling Type Model Option A2 - Cooling Rows Model Option A3 - Cooling Stages Model Option A4 - Cooling FPI Model Option B1 - Heating Type Model Option B2 - Heating Designation Model Option B3 - Heating Stages Supply Blower Configuration Supply Blower Model Supply Blower Motor Supply Blower Control/Control Vendors Refrigeration Options Special Controls Additional Controls Return Air Damper Position Outside Air Damper Position Mixing Box Damper Control Pre Filter Box Unit Filter Type Final Filter Box Filter Options Coil Coating Expansion Valve Expansion Valve Controls Exterior Corrosion Protection Tonnage Added or Modified Systems GPM Cooling Coil GPM Heating Coil Control Panel Warranty Type General Data Unit Information Filter Information Controls Control Vendors

4 Electrical Service Sizing Data R94190 Rev. A (ACP 30585) Index of Tables and Figures Tables: Table 1 - Unit Sizes Table 2 - Electric Heating Capacities Table 3 - A Cabinet (up to 1,200 cfm) Information Table 4 - B Cabinet (up to 2,000 cfm) Information Table 5 - C Cabinet (up to 4,000 cfm) Information Table 6 - D Cabinet (up to 6,000 cfm) Information Table 7 - E Cabinet (up to 10,000 cfm) Information Table 8 - E Cabinet (up to 10,000 cfm) Information Continued Table 9 - Chilled Water and Hot Water Coil Connection Sizes Table 10 - H3 Series A Cabinet Pre Filters Table 11 - V3 Series A Cabinet Pre Filters Table 12 - H3 Series B Cabinet Pre Filters Table 13 - V3 Series B Cabinet Pre Filters Table 14 - H3 Series C Cabinet Pre Filters Table 15 - V3 Series C Cabinet Pre Filters Table 16 - H3 Series D Cabinet Pre Filters Table 17 - V3 Series D Cabinet Pre Filters Table 18 - H3 Series E Cabinet Pre Filters Table 19 - V3 Series E Cabinet Pre Filters Table 20 - H3 Series A Cabinet Unit Filters Table 21 - V3 Series A Cabinet Unit Filters Table 22 - H3 Series B Cabinet Unit Filters Table 23 - V3 Series B Cabinet Unit Filters Table 24 - H3 Series A Cabinet Final Filters Table 25 - V3 Series A Cabinet Final Filters Table 26 - H3 Series B Cabinet Final Filters Table 27 - V3 Series B Cabinet Final Filters Table 28 - H3 Series C Cabinet Final Filters Table 29 - V3 Series C Cabinet Final Filters Table 30 - H3 Series D Cabinet Final Filters Table 31 - V3 Series D Cabinet Final Filters Table 32 - H3 Series E Cabinet Final Filters Table 33 - V3 Series E Cabinet Final Filters

5 Figures: Figure 1- H3 Series Unit Orientation Figure 2 - V3 Series Unit Orientation Figure 3 - Magnehelic Gauge Figure 4 - Example Low Voltage Terminal Block Figure 5 - WattMaster VCM-X Controller Figure 6 - VCM-X Controller Operator Interfaces Figure 7 - JENEsys Controller Figure 8 - Remote Mounted AAON Mini Controller

6 AAON H3/V3 Series Features and Options Introduction Energy Efficiency Direct Drive Backward Curved Plenum Supply Fans Mixing Box/Airside Economizer Double Wall Rigid Polyurethane Foam Panel Construction, R-6.25 Insulation Modulating/SCR Electric Heat Premium Efficiency Motors VFD Controlled Supply Fans ECM Driven Supply Fans Heat Pump Configuration Matching Energy Efficient Condensing Units Indoor Air Quality 100% Outside Air High Efficiency Filtration Double Wall Construction Interior Corrosion Protection Polymer E-Coated Coils Stainless Steel Drain Pans Humidity Control High Capacity Cooling Coils Modulating Hot Gas Reheat Safety Phase and Brown Out Protection Return Air Smoke Detector Supply and Return Air Firestats Installation and Maintenance Left or Right Hand Connections Clogged Filter Switch Color-Coded Wiring Diagram Labeled Components Direct Drive Supply Fans Hinged Access Doors with Lockable Handles Access to Fans, Coils, Drain Pans, Heating, Filters and Controls Factory Installed TXV Factory Installed Electric Heating Factory Installed Mixing Box Magnehelic Gauge Single Point Power Connection Supply and Return Duct Flange System Integration ,000 cfm in Five Cabinet Sizes Horizontal and Vertical Airflow Chilled Water Cooling Coils Customer Provided Controls Electric Heating Hot Water/Steam Heating Coils Non-Compressorized R-410A DX Coils Controls Flexibility Environmentally Friendly Mixing Box/Airside Economizer R-410A DX Coils Extended Life Exterior Corrosion Protection Interior Corrosion Protection Polymer E-Coated Coils Stainless Steel Drain Pans 6

7 H3/V3 Base Model Description Model Number H3 A R A Series and - Unit Unit Revision Generation Size Orientation - 3 Voltage - 0 Corrosion Protection C A1 A2 A3 A4 - BASE MODEL SERIES AND GENERATION H3 = Horizontal - Back Intake, Front Discharge V3 = Vertical - Back Intake, Top Discharge UNIT SIZE A = Up to 1,200 cfm B = Up to 2,000 cfm C = Up to 4,000 cfm D = Up to 6,000 cfm E = Up to 10,000 cfm UNIT ORIENTATION R = Right Hand Connections L = Left Hand Connections REVISION A = First Revision VOLTAGE 1 = 230V/1Φ/60Hz 2 = 230V/3Φ/60Hz 3 = 460V/3Φ/60Hz 4 = 575V/3Φ/60Hz 8 = 208V/3Φ/60Hz 9 = 208V/1Φ/60Hz Model Option A: COOLING A1: COOLING TYPE 0 = No Cooling 1 = R-410A DX Cooling 2 = Chilled Water Cooling A2: COOILNG ROWS 0 = No Cooling 4 = 4 Row Coil 6 = 6 Row Coil 8 = 8 Row Coil A3: COOLING STAGES 0 = No Cooling 1 = Single Circuit 2 = Two Circuits - Interlaced Coil D = Double Serpentine F = Single Serpentine H = Half Serpentine Q = Quarter Serpentine A4: COOLING FPI 0 = No Cooling A = 10 fpi B = 8 fpi C = 12 fpi CORROSION PROTECTION 0 = None A = Interior Corrosion Protection 7

8 H3/V3 Base Model and Features Description Model/Feature Number 1 2 F A A B B : B1 B2 B3 1A 1B 1C 1D - Model Option B: HEATING B1: HEATING TYPE 0 = No Heating 1 = Hot Water 3 = Electric Heating 4 = Steam Distributing B2: HEATING DESIGNATION 0 = No Heating 1 = 1 Row Coil 2 = 2 Row Coil A = 7 kw ( V) B = 14 kw ( V) C = 21 kw ( V) D = 28 kw ( V) E = 35 kw ( V) F = 42 kw ( V) G = 49 kw ( V) H = 56 kw ( V) J = 63 kw ( V) K = 70 kw ( V) L = 77 kw ( V) M = 84 kw ( V) B3: HEATING STAGES 0 = No Heating 1 = 1 Stage 2 = 2 Stage 3 = 3 Stage 4 = 4 Stage S = Modulating/SCR Electric F = Single Serpentine 10 fpi H = Half Serpentine 10 fpi Q = Quarter Serpentine 10 fpi Feature 1: SUPPLY FAN 1A: SUPPLY AIR BLOWER CONFIGURATION 0 = 1 Blower + Premium Eff. Motor 1 = 1 Blower + Premium Eff. Motor + 1 VFD A = 1 Blower + 1 High Efficiency EC Motor B = 2 Blowers + 2 High Efficiency EC Motors 1B: SUPPLY AIR BLOWER 1 = 15 Backward Curved Plenum Fan 2 = 15 BC Plenum, 50% Width with Banding 3 = 18.5 Backward Curved Plenum Fan 4 = 18.5 BC Plenum Fan, 70% Width with Banding 5 = 22 Backward Curved Plenum Fan 6 = 24 Backward Curved Plenum Fan 7 = 27 Backward Curved Plenum Fan 8 = 27 BC Plenum Fan, 70% Width with Banding A = 310 mm Direct Drive BC Plenum Fan B = 355 mm Direct Drive BC Plenum Fan C = 450 mm Direct Drive BC Plenum Fan 1C: SUPPLY AIR BLOWER MOTOR 1 = 1 hp rpm 2 = 2 hp rpm 3 = 3 hp rpm 4 = 5 hp rpm 5 = 7.5 hp rpm 6 = 10 hp rpm A = 500 W (0.67 hp) B = 1.0 kw (1.34 hp) C = 1.7 kw (2.28 hp) D = 3.0 kw (2.90 hp or 4.02 hp) 1D: SUPPLY BLOWER CONTROL/CONTROL VENDORS 0 = Standard - Terminal Block A = Potentiometer Supply Fan Control B = WattMaster Orion Controls System C = Field Installed Controls by Others 8

9 H3/V3 Features Description Feature Number 0 C 0 F T B A 5B 5C - Feature 2: REFRIGERATION OPTIONS A = Single Circuit External Hot Gas Bypass B = Dual Circuit External Hot Gas Bypass C = Heat Pump D = Option B + H E = Options B + J F = Options C + H G = Options C + J H = Modulating Hot Gas Reheat J = Factory Installed Modulating Hot Gas Reheat K = Dual Circuit Modulating Hot Gas Reheat + Option B L =Factory Installed Dual Circuit Modulating Hot Gas Reheat + Option B M = Dual Circuit Modulating Hot Gas Reheat + Option C N = Factory Installed Dual Circuit Modulating Hot Gas Reheat + Option C P = Option H (Circuit 1) + Option A (Circuit 2) Q = Option J (Circuit 1) + Option A (Circuit 2) Feature 3: SPECIAL CONTROLS A = Constant Volume Controller - CV Cool + CV Heat B = Constant Volume Controller with Modulating Hot Gas Reheat - CV Cool + CV Heat C = VAV Controller - VAV Cool + CV Heat D = VAV Controller with MHGR - VAV Cool + CV Heat E = Make Up Air Controller - CV Cool + CV Heat F = Make Up Air Controller with Modulating Hot Gas Reheat - CV Cool + CV Heat G = WattMaster Modulating Hot Gas Reheat Controller Feature 4: ADDITIONAL CONTROLS A = Phase and Brownout Protection B = Return and Supply Air Firestat C = Return Air Smoke Detector D = Options A + B E = Options A + C F = Options B + C G = Options A + B + C Feature 5: MIXING BOX 5A: RETURN AIR DAMPER POSITION F = Front L = Left Hand (Front OA Damper Required) R = Right Hand (Front OA Damper Required) T = Top (Front OA Damper Required) 5B: OUTSIDE AIR DAMPER POSITION F = Front L = Left Hand (Front RA Damper Required) R = Right Hand (Front RA Damper Required) T = Top (Front RA Damper Required) 5C: MIXING BOX DAMPER CONTROL A = 2 Position Actuators B = Fully Modulating Actuators C = Fixed Position Dampers 9

10 H3/V3 Features Description Feature Number 0 G A A A - 6A 6B 6C Feature 6: FILTER BOX 6A: PRE FILTER BOX A = 2 Pleated - 30% Eff. - MERV 8 B = 4 Pleated - 30% Eff. - MERV 8 C = 4 Pleated - 65% Eff. - MERV 11 D = 4 Pleated - 85% Eff. - MERV 13 E = 4 Pleated - 95% Eff. - MERV 14 F = 2 Pleated - 30% Eff. - MERV Pleated - 30% Eff. - MERV 8 G = 2 Pleated - 30% Eff. - MERV Pleated - 65% Eff. - MERV 11 H = 2 Pleated - 30% Eff. - MERV Pleated - 85% Eff. - MERV 13 J = 2 Pleated - 30% Eff. - MERV Pleated - 95% Eff. - MERV 14 6B: UNIT FILTER A = 2 Pleated - 30% Eff. - MERV 8 B = 4 Pleated - 30% Eff. - MERV 8 C = 4 Pleated - 65% Eff. - MERV 11 D = 4 Pleated - 85% Eff. - MERV 13 E = 4 Pleated - 95% Eff. - MERV 14 F = 2 Pleated - 30% Eff. - MERV Pleated - 30% Eff. - MERV 8 G = 2 Pleated - 30% Eff. - MERV Pleated - 65% Eff. - MERV 11 H = 2 Pleated - 30% Eff. - MERV Pleated - 85% Eff. - MERV 13 J = 2 Pleated - 30% Eff. - MERV Pleated - 95% Eff. - MERV 14 Feature 7: FILTER OPTIONS A = Magnehelic Gauge B = Clogged Filter Switch C = Options A + B Feature 8: COIL COATING A = E-coated Cooling and Heating Coils Feature 9: EXPANSION VALVE 0 = None A = Thermal Expansion Valves Feature 10: EXPANSION VALVE CONTROLS 0 = None A = Standard Control Feature 11: EXTERNAL PAINT A = AAON Gray Paint B = Special Paint 6C: FINAL FILTER BOX A = 2 Pleated - 30% Eff. - MERV 8 B = 12 Cartridge - 65% Eff. - MERV 11 C = 12 Cartridge - 85% Eff. - MERV 13 D = 12 Cartridge - 95% Eff. - MERV 14 E = 2 Pleated - 30% Eff. - MERV Cartridge - 65% Eff. - MERV 11 F = 2 Pleated - 30% Eff. - MERV Cartridge - 85% Eff. - MERV 13 G = 2 Pleated - 30% Eff. - MERV Cartridge - 95% Eff. - MERV 14 10

11 H3/V3 Features Description Feature Number C A A 14B Feature 12: TONNAGE A = 2 ton Capacity B = 3 ton Capacity C = 4 ton Capacity D = 5 ton Capacity E = 6 ton Capacity F = 7 ton Capacity G = 8 ton Capacity H = 10 ton Capacity J = 14 ton Capacity K = 17 ton Capacity L = 22 ton Capacity M = 25 ton Capacity N = 30 ton Capacity P = 31 ton Capacity Q = 34 ton Capacity R = 45 ton Capacity S = 55 ton Capacity T = 63 ton Capacity Feature 13: ADDED OR MODIFIED SYSTEMS Feature 14: GPM 14A: GPM COOLING COIL A = gpm B = gpm C = gpm D = gpm E = gpm F = gpm G = gpm H = gpm 14B: GPM HEATING COIL A = gpm B = gpm C = gpm D = gpm E = gpm F = gpm G = gpm H = gpm Feature 15: CONTROL PANEL 0 = None A = Small Control Panel - 12 x 12 B = Medium Control Panel - 25 x 22 C = Large Control Panel - 48 x 22 Feature 16: BLANK Feature 17: BLANK Feature 18: BLANK Feature 19: BLANK Digit 41: Feature 20: BLANK Feature 21: BLANK Feature 22: WARRANTY 0 = Standard - 1 Year Parts Feature 23: TYPE 0 = Standard X = Special Pricing Authorization 11

12 Model Number Unit Size The first letter of the model string designates the airflow configuration, the second number designates the generation and the third letter designates the unit size. Refer to AAONEcat32 for unit dimensions. Model H3-A H3-B H3-C H3-D H3-E V3-A V3-B V3-C V3-D V3-E Cabinet Size Up to 1,200 cfm Up to 2,000 cfm Up to 4,000 cfm Up to 6,000 cfm Up to 10,000 cfm Up to 1,200 cfm Up to 2,000 cfm Up to 4,000 cfm Up to 6,000 cfm Up to 10,000 cfm Table 1 - Unit Sizes Configuration Intake Location Discharge Location Horizontal Back Front Vertical Back Top Model Number Unit Orientation R = Right Hand Connections - Refrigerant piping stub outs, hydronic coil stub outs and unit access panels are located on the right hand side of the air handling unit. Condensate drain pan connections are available on either the right or left hand side of the unit. L = Left Hand Connections - Refrigerant piping stub outs, hydronic coil stub outs and unit access panels are located on the left hand side of the air handling unit. Condensate drain pan connections are available on either the right or left hand side of the unit. 12

13 H3 Series Left Hand Side Top View Return Air Air Flow Supply Air Connections and service access on right side for right hand orientation Right Hand Side Figure 1- H3 Series Unit Orientation Consider the air flow to be hitting the back of your head. V3 Series Top View Left Hand Side Right Hand Side Supply Air Return Air Connections and service access on right side for right hand orientation Consider the air flow to be Air Flow hitting the back of your head. Figure 2 - V3 Series Unit Orientation 13

14 Model Number Revision A = First Revision - This digit is used for future product updates and improvements. Model Number Voltage 1 = V/1Φ/60Hz 2 = V/3Φ/60Hz 3 = 460V/3Φ/60Hz Model Number Interior Corrosion Protection A = Interior Corrosion Protection - All exposed metal surfaces in the air tunnel except the coils, coil casings and condensate drain pans are spray coated with a two-part polyurethane, heat baked coating. Selection covers coating of the fans, dampers, filter rack and service door interiors. Option is intended for use in coastal saltwater conditions under the stress of heat, salt, sand and wind and is applicable to all corrosive environments where a polyurethane coating is acceptable. Coating exceeds 2,500 hours when tested under ASTM B requirements. Condensate drain pans are fabricated of 18 gauge 304 stainless steel. See Feature 8 for coil corrosion protection options. 14

15 Model Number Model Option A1 - Cooling Type 0 = No Cooling - Heating only air handling unit. 1 = R-410A DX Cooling - Draw-through R-410A DX evaporator coil air handling unit. 2 = Chilled Water Cooling - Draw-through chilled water coil air handling unit. No valves or valve controls are included with this option. Chilled water coil air handling unit includes supply and return water connection stub outs. Model Number Model Option A2 - Cooling Rows 0 = No Cooling - Heating only air handling unit. 4 = 4 Row Coil - Four row coil. 6 = 6 Row Coil - Six row coil. 8 = 8 Row Coil - Eight row coil. 15

16 Model Number Model Option A3 - Cooling Stages 0 = No Cooling - Heating only air handling unit. 1 = Single Circuit - Single circuited evaporator coil. 2 = Two Circuits - Interlaced Coil - Dual circuited evaporator coil with interlaced circuitry. D = Double Serpentine - Chilled water coil with double serpentine circuitry. No valves or valve controls are included with this option. Chilled water coil air handling unit includes supply and return water connection stub outs. F = Single Serpentine - Chilled water coil with single serpentine circuitry. No valves or valve controls are included with this option. Chilled water coil air handling unit includes supply and return water connection stub outs. Standard chilled water coil circuitry option. H = Half Serpentine - Chilled water coil with half serpentine circuitry. No valves or valve controls are included with this option. Chilled water coil air handling unit includes supply and return water connection stub outs. Q = Quarter Serpentine - Chilled water coil with quarter serpentine circuitry. No valves or valve controls are included with this option. Chilled water coil air handling unit includes supply and return water connection stub outs. Model Number Model Option A4 - Cooling FPI 0 = No Cooling - Heating only air handling unit. A = 10 fpi - Cooling coil with 10 fins per inch. Standard cooling coil fpi option. B = 8 fpi - Cooling coil with 8 fins per inch. C = 12 fpi - Cooling coil with 12 fins per inch. 16

17 Model Number Model Option B1 - Heating Type 0 = No Heating - Cooling only air handling unit. 1 = Hot Water Coil - Hot water heating coil located in the preheat position upstream of the cooling coil. No valves or valve controls are included with this option. 3 = Electric Heat - Electric heater with multiple elements located downstream of the cooling coil and supply fan. 4 = Steam Distributing Coil - Steam heating coil located in the preheat position upstream of the cooling coil. No valves or valve controls are included with this option. 17

18 Model Number Model Option B2 - Heating Designation 0 = No Heating - Cooling only air handling unit. 1 = 1 Row Coil - Single row hot water or steam heating coil. No valves or valve controls are included with this option. 2 = 2 Row Coil - Two row hot water or steam heating coil. No valves or valve controls are included with this option. Table 2 - Electric Heating Capacities Electric Heat Capacity kw (230V, 460V) kw (208V) A = Heat A B = Heat B C = Heat C D = Heat D E = Heat E F = Heat F G = Heat G H = Heat H J = Heat J K = Heat K L = Heat L M = Heat M Note: AAONEcat32 will select the correct heating designation option for electric heat based on the desired leaving air and entering air temperature conditions. For heat pump units this is the emergency or backup heat capacity, which is the capacity of the secondary heater available when heat pump heating is not in use. See General Data section for model specific heating information. 18

19 Model Number Model Option B3 - Heating Stages 0 = No Heating 1 = 1 stage - Single stage heat control. 2 = 2 stage - Two stage heat control. 3 = 3 stage - Three stage heat control. 4 = 4 stage - Four stage heat control. S = Modulating/SCR Electric Modulating/SCR Electric - Potentiometer Control - Fully modulating electric heating, controlled by a Silicon Controlled Rectifier (SCR) and DDC controller. Includes a factory wired supply air temperature sensor, which is field installed in the supply ductwork, and a factory wired supply air temperature setpoint adjustment potentiometer, which is field mounted. Potentiometer dial uses variable resistance to provide simple setpoint control. Modulating/SCR Electric VDC Control Signal - Fully modulating electric heating, controlled by an SCR and DDC controller. A terminal strip to connect a 0-10 VDC control signal by others is included. Heating elements line voltage is modulated linearly with respect to the control signal. F = Single Serpentine 10 fpi - Hot water or steam heating coil with single serpentine circuitry and 10 fins per inch. No valves or valve controls are included with this option. Standard hot water and steam heating coil options. H = Half Serpentine 10 fpi - Hot water heating coil with half serpentine circuitry and 10 fins per inch. No valves or valve controls are included with this option. Q = Quarter Serpentine 10 fpi - Hot water heating coil with quarter serpentine circuitry and 10 fins per inch. No valves or valve controls are included with this option. Note: For heat pump units this is the number of emergency or backup heat stages, which is the number of stages of the secondary heater available when heat pump heating is not in use. See General Data section for tonnage specific heating information. 19

20 Feature 1A Supply Blower Configuration 0 = 1 Blower with Premium Efficiency Motor 1 = 1 Blower with Premium Efficiency Motor with 1 VFD A = 1 Blower with High Efficiency Electronically Commutated Motor (ECM) B = 2 Blowers with 2 High Efficiency Electronically Commutated Motors (ECM) AAONEcat32 will select the correct available options for Feature 1A based on unit conditions and the input from the fan selection program. When all of the other features have been selected, you will be prompted to select supply fans, motors and VFDs under the Fan Selection window. In the Fan Selection window you will be able to choose the number of fans, VFDs and motor efficiency. General fan information, fan sound information and fan curves will be available for viewing in the Fan Selection window. Feature 1B Supply Blower Model 1 = 15 Backward Curved Plenum Fan 2 = 15 Backward Curved Plenum Fan, 50% Width with Banding 3 = 18.5 Backward Curved Plenum Fan 4 = 18.5 Backward Curved Plenum Fan, 70% Width with Banding 5 = 22 Backward Curved Plenum Fan 6 = 24 Backward Curved Plenum Fan 7 = 27 Backward Curved Plenum Fan 8 = 27 Backward Curved Plenum Fan, 70% Width with Banding A = 310 mm Direct Drive Backward Curved Plenum Fan B = 355 mm Direct Drive Backward Curved Plenum Fan C = 450 mm Direct Drive Backward Curved Plenum Fan AAONEcat32 will select the correct available options for Feature 1B based on unit conditions and the input from the fan selection program. When all of the other features have been selected, you will be prompted to select supply fans, motors and VFDs under the Fan Selection window. In the Fan Selection window you will be able to choose the number of fans, VFDs, and motor efficiency. General fan information, fan sound information, and fan curves will be available for viewing in the Fan Selection window. 20

21 Feature 1C Supply Blower Motor 1 = 1 hp rpm 2 = 2 hp rpm 3 = 3 hp rpm 4 = 5 hp rpm 5 = 7.5 hp rpm 6 = 10.0 hp rpm A = 500 W (0.67 hp) B = 1.0 kw (1.34 hp) C = 1.7 kw (2.28 hp) D = 3.0 kw (2.90 hp or 4.02 hp) AAONEcat32 will select the correct available options for Feature 1C based on unit conditions and the input from the fan selection program. When all of the other features have been selected, you will be prompted to select supply fans, return or exhaust fans, motors and VFDs under the Fan Selection window. In the Fan Selection window you will be able to choose the number of fans, VFDs and motor efficiency. General fan information, fan sound information and fan curves will be available for viewing in the Fan Selection window. Note: High efficiency Electronically Commutated Motors (ECM) are kw rated. 21

22 Feature 1D Supply Blower Control/Control Vendors 0 = Standard - Terminal Block - No factory provided unit controller. Terminal block is provided for unit and supply fan control. Field supplied control signal is required with a VFD driven fan. A = Potentiometer Supply Fan Control - No factory provided unit controller. Supply air cfm setpoint potentiometer is factory provided and installed. Potentiometer dial uses variable resistance to provide simple setpoint control. B = WattMaster Orion Controls System - AAON provided and factory installed WattMaster VCM-X controller (Feature 3). Option requires the selection of an operator interface in AAONEcat32 to set up controller. Supply fan speed is controlled by WattMaster VCM-X unit controller. See Controls section for more information. C = Field Installed Controls By Others - No factory provided unit controller. Terminal block is provided for unit and supply fan control. Field supplied 0-10 VDC control signal is required with an ECM driven fan. 22

23 Feature 2 Refrigeration Options - DX air handling unit includes factory installed expansion valve and liquid and suction line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. Chilled water coil air handling unit includes supply and return water connection stub outs. A = Single Circuit External Hot Gas Bypass - Factory installed and field adjustable pressure activated bypass valve on the lead refrigeration circuit factory setup to divert hot compressor discharge gas to the evaporator coil if pressure on the evaporator side of the valve drops below 105 psi for R-410A (34 F at sea level). The bypass valve is at full capacity after six degrees of differential (28 F at sea level). This option is used to prevent coil freeze-up during periods of low airflow or cold entering coil conditions without cycling of the compressors on and off. Option is required on all Variable Air Volume (VAV) and Make Up Air (MUA) units without variable capacity scroll compressors. This option is used for refrigeration system protection only and cannot be used for cooling capacity modulation. When lead circuit includes a variable capacity scroll compressor, this option includes hot gas bypass on the lag circuits. DX air handling unit includes factory installed expansion valve, factory installed hot gas bypass valve, and liquid, suction and hot gas line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. B = Dual Circuit External Hot Gas Bypass - Factory installed and field adjustable pressure activated bypass valves on all refrigeration circuits factory setup to divert hot compressor discharge gas to the evaporator coil if pressure on the evaporator side of the valve drops below 105 psi for R-410A (34 F at sea level). The bypass valve is at full capacity after six degrees of differential (28 F at sea level). This option is used to prevent coil freeze-up during periods of low airflow or cold entering coil conditions without cycling of the compressors on and off. Option is required on all Variable Air Volume (VAV) and Make Up Air (MUA) units without variable capacity scroll compressors. This option is used for refrigeration system protection only and cannot be used for cooling capacity modulation. DX air handling unit includes factory installed expansion valves, factory installed hot gas bypass valves, and liquid, suction and hot gas line stub outs for connection to a matching condensing unit. Expansion valve sensing bulbs must be field installed on the suction lines. C = Heat Pump - Heat pump air handling unit which can provide energy efficient heating and cooling. DX air handling unit includes factory installed expansion valves with check valve, and liquid and suction line stub outs for connection to a matching heat pump condensing unit. Heat pump filter dryer is factory provided for field installation at the indoor coil. Expansion valve sensing bulbs must be field installed on the suction lines. Reversing valves, accumulators and outdoor coil filter dryers, check valves and thermal expansion valves should be provided with the matching condensing unit. See Model Options B1, B2 and B3 for emergency (backup) heat options and Feature 3. 23

24 Feature 2 - Refrigeration Options Continued D = Modulating Hot Gas Reheat with Dual Circuit External Hot Gas Bypass - Option B + refrigerant reheat coil mounted downstream of the evaporator coil. Coil must be field piped to the lead cooling circuit, with factory provided reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON modulating hot gas reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. E = Factory Installed Modulating Hot Gas Reheat with Dual Circuit External Hot Gas Bypass - Option B + refrigerant reheat coil mounted downstream of the evaporator coil. Coil is factory piped to the lead cooling circuit, with reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. F = Heat Pump with Modulating Hot Gas Reheat - Option C + refrigerant reheat coil mounted downstream of the evaporator coil. Coil must be field piped to the lead cooling circuit, with factory provided reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON modulating hot gas reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. G = Heat Pump with Factory Installed Modulating Hot Gas Reheat - Option C + refrigerant reheat coil mounted downstream of the evaporator coil. Coil is factory piped to the lead cooling circuit, with reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. H = Modulating Hot Gas Reheat - Refrigerant reheat coil mounted downstream of the evaporator coil. Coil must be field piped to the lead cooling circuit, with factory provided reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON modulating hot gas reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. 24

25 Feature 2 - Refrigeration Options Continued J = Factory Installed Modulating Hot Gas Reheat - Refrigerant reheat coil mounted downstream of the evaporator coil. Coil is factory piped to the lead cooling circuit, with reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. K = Dual Circuit External Hot Gas Bypass with Dual Circuit Modulating Hot Gas Reheat - Option B + Interlaced refrigerant reheat coil mounted downstream of the evaporator coil. Coil must be field piped to the cooling circuits, with factory provided reheat valves and check valves, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON dual circuit reheat condensing unit includes receiver tanks and condensing unit reheat valves. DX air handling unit includes factory installed expansion valves and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulbs must be field installed on the suction lines. L = Dual Circuit External Hot Gas Bypass with Factory Installed Dual Circuit Modulating Hot Gas Reheat - Option B + Interlaced refrigerant reheat coil mounted downstream of the evaporator coil. Coil is factory piped to the cooling circuits, with reheat valves and check valves, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON reheat condensing unit includes receiver tanks and condensing unit reheat valves. DX air handling unit includes factory installed expansion valves and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulbs must be field installed on the suction lines. M = Heat Pump with Dual Circuit Modulating Hot Gas Reheat - Option C + Interlaced refrigerant reheat coil mounted downstream of the evaporator coil. Coil must be field piped to the cooling circuits, with factory provided reheat valves and check valves, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON dual circuit reheat condensing unit includes receiver tanks and condensing unit reheat valves. DX air handling unit includes factory installed expansion valves and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulbs must be field installed on the suction lines. N = Heat Pump with Factory Installed Dual Circuit Modulating Hot Gas Reheat - Option C + Interlaced refrigerant reheat coil mounted downstream of the evaporator coil. Coil is factory piped to the cooling circuits, with reheat valves and check valves, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON reheat condensing unit includes receiver tanks and condensing unit reheat valves. DX air handling unit includes factory installed expansion valves and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulbs must be field installed on the suction lines. 25

26 Feature 2 - Refrigeration Options Continued P = Modulating Hot Gas Reheat with Single Circuit External Hot Gas Bypass - Refrigerant reheat coil mounted downstream of the evaporator coil on refrigeration circuit 1 and hot gas bypass (Option A) on refrigeration circuit 2. Reheat coil must be field piped to the lead cooling circuit, with factory provided reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON modulating hot gas reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. Q = Factory Installed Modulating Hot Gas Reheat with Single Circuit External Hot Gas Bypass - Refrigerant reheat coil mounted downstream of the evaporator coil on refrigeration circuit 1 and hot gas bypass (Option A) on refrigeration circuit 2. Reheat coil is factory piped to the lead cooling circuit, with reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. Feature 3 Special Controls - Terminal strip for use with a thermostat. See Controls section for more information. A = Constant Volume Unit Controller - Constant Volume Cooling and Constant Volume Heating - Standard Constant Volume controls for non-heat pump systems. During the cooling mode of operation the supply fan provides constant airflow and mechanical cooling modulates based on the controlling temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Outside air temperature sensor, supply air temperature sensor and space temperature sensor with setpoint reset and unoccupied override are factory supplied for field installation. See Controls section for more information. 26

27 Feature 3 - Special Controls Continued B = Constant Volume Unit Controller with Modulating Hot Gas Reheat - Constant Volume Cooling and Constant Volume Heating - Standard Constant Volume controls for non-heat pump systems. During the cooling mode of operation the supply fan provides constant airflow and mechanical cooling modulates based on the controlling temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Outside air temperature sensor, supply air temperature sensor and space temperature sensor with setpoint reset and unoccupied override are factory supplied for field installation. Modulating hot gas reheat provides the unit with a dehumidification mode of operation for when the cooling load has been satisfied. This option provides constant supply air temperature control during dehumidification, which prevents space temperature swings. Complete system, with AAON air handling unit and AAON condensing unit, includes modulating condenser control valve, modulating reheat control valve, supply air temperature sensor and controller to maintain the supply air temperature during the dehumidification mode of operation. A terminal contact (RH1) is included for connecting a humidistat. A wall mounted humidistat is available as an accessory. With this option, receiver tanks are provided with the condensing unit. See Feature 2 and Controls section for more information. C = Variable Volume Unit Controller - Variable Volume Cooling and Constant Volume Heating - Standard VAV controls for non-heat pump systems and heat pump systems. During the cooling mode of operation the supply fan modulates based on the supply static pressure and mechanical cooling modulates based on the supply air temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Outside air temperature sensor, return air temperature, supply air temperature sensor and supply air static pressure probe are factory supplied for field installation. Space temperature sensor with setpoint reset and unoccupied override is factory supplied with WattMaster VCM-X controller for field installation. See Controls section for more information. D = Variable Volume Unit Controller with Modulating Hot Gas Reheat - Variable Volume Cooling and Constant Volume Heating - Standard VAV controls for non-heat pump systems and heat pump systems. During the cooling mode of operation the supply fan modulates based on the supply static pressure and mechanical cooling modulates based on the supply air temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Outside air temperature sensor, return air temperature, supply air temperature sensor and supply air static pressure probe are factory supplied for field installation. Space temperature sensor with setpoint reset and unoccupied override is factory supplied with WattMaster VCM-X controller for field installation. Modulating hot gas reheat provides the unit with a dehumidification mode of operation for when the cooling load has been satisfied. This option provides constant supply air temperature control during dehumidification, which prevents space temperature swings. Complete system, with AAON air handling unit and AAON condensing unit, includes modulating condenser control valve, modulating reheat control valve, supply air temperature sensor and controller to maintain the supply air temperature during the dehumidification mode of operation. A terminal contact (RH1) is included for connecting a humidistat. A wall mounted humidistat is available as an accessory. With this option, receiver tanks are provided with the condensing unit. See Feature 2 and Controls section for more information. 27

28 Feature 3 - Special Controls Continued E = Make Up Air Unit Controller - Constant Volume Cooling and Constant Volume Heating - Standard Make Up Air controls for non-heat pump systems. During the cooling mode of operation the supply fan provides constant airflow and mechanical cooling modulates based on the controlling temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Outside air temperature sensor and supply air temperature sensor are factory supplied for field installation. See Controls section for more information. F = Make Up Air Unit Controller with Modulating Hot Gas Reheat - Constant Volume Cooling and Constant Volume Heating - Standard Make Up Air controls for non-heat pump systems. During the cooling mode of operation the supply fan provides constant airflow and mechanical cooling modulates based on the controlling temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Outside air temperature sensor and supply air temperature sensor are factory supplied for field installation. Modulating hot gas reheat provides the unit with a dehumidification mode of operation for when the cooling load has been satisfied. This option provides constant supply air temperature control during dehumidification, which prevents space temperature swings. Complete system, with AAON air handling unit and AAON condensing unit, includes modulating condenser control valve, modulating reheat control valve, supply air temperature sensor and controller to maintain the supply air temperature during the dehumidification mode of operation. A terminal contact (RH1) is included for connecting a humidistat. With this option, receiver tanks are provided with the condensing unit. See Feature 2 and Controls section for more information. G = WattMaster Modulating Hot Gas Reheat - Modulating hot gas reheat provides the unit with a dehumidification mode of operation for when the cooling load has been satisfied. This option provides constant supply air temperature control during dehumidification, which prevents space temperature swings. Complete system, with AAON air handling unit and AAON condensing unit, includes modulating condenser control valve, modulating reheat control valve, supply air temperature sensor and controller to maintain the supply air temperature during the dehumidification mode of operation. A terminal contact (RH1) is included for connecting a humidistat. A wall mounted humidistat is available as an accessory. With this option, receiver tanks are provided with the condensing unit. See Feature 2 for more information. 28

29 Feature 4 Additional Controls A = Phase and Brown Out Protection - Voltage monitor that is used to protect motors and compressors from voltage imbalance, over/under voltage and phase loss. Reset is automatic. B = Return and Supply Air Firestats - Bimetallic snap-action safety switches sensing temperature only, mounted in both the supply and return air streams. The supply air switch is rated to 200 F and the return air switch is rated to 125 F. Both switches manually reset and are wired to shut down the 24 VAC control circuit. Firestats are non-addressable. C = Return Air Smoke Detector - Photoelectric type smoke detector factory mounted in the return air section of the unit. Detector is wired to shut down the 24 VAC control circuit upon detector activation, thereby shutting off the unit. Relay contacts are provided for interfacing the detector with alarm panels. A test magnet is supplied in the unit controls cabinet. Smoke detectors are non-addressable. D = Phase and Brown Out Protection + Return and Supply Air Firestats - Options A + B E = Phase and Brown Out Protection + Return Air Smoke Detector - Options A + C F = Return and Supply Air Firestats + Return Air Smoke Detector - Options B + C G = Phase and Brown Out Protection + Return and Supply Air Firestats + Return Air Smoke Detector - Options A + B + C 29

30 Feature 5A Return Air Damper Position F = Front - Mixing box with return air damper located on the front of the mixing box. Damper includes its own independent actuator. L = Left Hand - Front Outside Air Damper Required - Mixing box with return air damper located on the left hand side of the mixing box. Damper is manually adjustable fixed position or will include its own independent actuator. Outside air damper must be located on the front of the mixing box (Feature 5B). R = Right Hand - Front Outside Air Damper Required - Mixing box with return air damper located on the right hand side of the mixing box. Damper is manually adjustable fixed position or will include its own independent actuator. Outside air damper must be located on the front of the mixing box (Feature 5B). T = Top - Front Outside Air Damper Required - Mixing box with return air damper located on the top of the mixing box. Damper is manually adjustable fixed position or will include its own independent actuator. Outside air damper must be located on the front of the mixing box (Feature 5B). Feature 5B Outside Air Damper Position F = Front - Mixing box with outside air damper located on the front of the mixing box. Damper includes its own independent actuator. L = Left Hand - Front Return Air Damper Required - Mixing box with outside air damper located on the left hand side of the mixing box. Damper is manually adjustable fixed position or will include its own independent actuator. Return air damper must be located on the front of the mixing box (Feature 5A). R = Right Hand - Front Return Air Damper Required - Mixing box with outside air damper located on the right hand side of the mixing box. Damper is manually adjustable fixed position or will include its own independent actuator. Return air damper must be located on the front of the mixing box (Feature 5A). T = Top - Front Return Air Damper Required - Mixing box with outside air damper located on the top of the mixing box. Damper is manually adjustable fixed position or will include its own independent actuator. Return air damper must be located on the front of the mixing box (Feature 5A). 30

31 Feature 5C Mixing Box Damper Control A = 2 Position Actuator - Two position actuators on the return air and outside air mixing box dampers. Position one is the closed position. Position two is the fully open position, which is activated when there is a call for supply fan operation. The actuators are spring return closed. B = Fully Modulating Actuator - Fully modulating actuators on the return air and outside air mixing box dampers. Position one is the closed position. Position two is the minimum outside air position, which is activated when there is a call for supply fan operation. During the economizer mode the outside air actuator modulates between minimum position and having the outside air dampers fully open to maintain a discharge temperature of 55 F. The minimum outside air position can be field adjusted for the desired amount of outside air. The actuators are spring return closed. C = Fixed Position Dampers - Manually adjustable fixed position return air and outside air mixing box dampers. Feature 6A Pre Filter Box A = 2 Pleated Pre Filter - 30% Efficient - 2 inch pleated, 30% efficient, MERV 8 pre filters mounted in a pre filter box downstream of the return and outside air openings. B = 4 Pleated Pre Filter - 30% Efficient - 4 inch pleated, 30% efficient, MERV 8 pre filters mounted in a pre filter box downstream of the return and outside air openings. C = 4 Pleated Pre Filter - 65% Efficient - MERV 11-4 inch pleated, 65% efficient, MERV 11 pre filters mounted in a pre filter box downstream of the return and outside air openings. D = 4 Pleated Pre Filter - 85% Efficient - MERV 13-4 inch pleated, 85% efficient, MERV 13 pre filters mounted in a pre filter box downstream of the return and outside air openings. E = 4 Pleated Pre Filter - 95% Efficient - MERV 14-4 inch pleated, 95% efficient, MERV 14 pre filters mounted in a pre filter box downstream of the return and outside air openings. F = 2 Pleated Pre Filter - 30% Efficient with 4 Pleated Pre Filter - 30% Efficient - 2 inch pleated, 30% efficient, MERV 8 pre filters mounted upstream of 4 inch pleated, 30% efficient, MERV 8 pre filters mounted in a pre filter box downstream of the return and outside air openings. 31

32 Feature 6A - Pre Filter Box Continued G = 2 Pleated Pre Filter - 30% Efficient with 4 Pleated Pre Filter - 65% Efficient - MERV 11-2 inch pleated, 30% efficient, MERV 8 pre filters mounted upstream of 4 inch pleated, 65% efficient, MERV 11 pre filters mounted in a pre filter box downstream of the return and outside air openings. H = 2 Pleated Pre Filter - 30% Efficient with 4 Pleated Pre Filter - 85% Efficient - MERV 13-2 inch pleated, 30% efficient, MERV 8 pre filters mounted upstream of 4 inch pleated, 85% efficient, MERV 13 pre filters mounted in a pre filter box downstream of the return and outside air openings. J = 2 Pleated Pre Filter - 30% Efficient with 4 Pleated Pre Filter - 95% Efficient - MERV 14-2 inch pleated, 30% efficient, MERV 8 pre filters mounted upstream of 4 inch pleated, 95% efficient, MERV 14 pre filters mounted in a pre filter box downstream of the return and outside air openings. Feature 6B Unit Filter Type A = 2 Pleated Unit Filter - 30% Efficient - 2 inch pleated, 30% efficient, MERV 8 unit filters mounted adjacent and upstream of the evaporator coil. B = 4 Pleated Unit Filter - 30% Efficient - 4 inch pleated, 30% efficient, MERV 8 unit filters mounted adjacent and upstream of the evaporator coil. C = 4 Pleated Unit Filter - 65% Efficient - MERV 11-4 inch pleated, 65% efficient, MERV 11 unit filters mounted adjacent and upstream of the evaporator coil. D = 4 Pleated Unit Filter - 85% Efficient - MERV 13-4 inch pleated, 85% efficient, MERV 13 unit filters mounted adjacent and upstream of the evaporator coil. E = 4 Pleated Unit Filter - 95% Efficient - MERV 14-4 inch pleated, 95% efficient, MERV 14 unit filters mounted adjacent and upstream of the evaporator coil. F = 2 Pleated Unit Filter - 30% Efficient with 4 Pleated Unit Filter - 30% Efficient - 2 inch pleated, 30% efficient, MERV 8 unit filters mounted upstream of 4 inch pleated, 30% efficient, MERV 8 unit filters mounted adjacent and upstream of the evaporator coil. G = 2 Pleated Unit Filter - 30% Efficient with 4 Pleated Unit Filter - 65% Efficient - MERV 11-2 inch pleated, 30% efficient, MERV 8 unit filters mounted upstream of 4 inch pleated, 65% efficient, MERV 11 unit filters mounted adjacent and upstream of the evaporator coil. H = 2 Pleated Unit Filter - 30% Efficient with 4 Pleated Unit Filter - 85% Efficient - MERV 13-2 inch pleated, 30% efficient, MERV 8 unit filters mounted upstream of 4 inch pleated, 85% efficient, MERV 13 unit filters mounted adjacent and upstream of the evaporator coil. J = 2 Pleated Unit Filter - 30% Efficient with 4 Pleated Unit Filter - 95% Efficient - MERV 14-2 inch pleated, 30% efficient, MERV 8 unit filters mounted upstream of 4 inch pleated, 95% efficient, MERV 14 unit filters mounted adjacent and upstream of the evaporator coil. 32

33 Feature 6C Final Filter Box A = 2 Pleated Final Filter - 30% Efficient - 2 inch pleated, 30% efficient, MERV 8 final filters mounted downstream of the supply fan and heating. B = 4 Pleated Final Filter - 65% Efficient - MERV 11-4 inch pleated, 65% efficient, MERV 11 final filters mounted downstream of the supply fan and heating. C = 4 Pleated Final Filter - 85% Efficient - MERV 13-4 inch pleated, 85% efficient, MERV 13 final filters mounted downstream of the supply fan and heating. D = 4 Pleated Final Filter - 95% Efficient - MERV 14-4 inch pleated, 95% efficient, MERV 14 final filters mounted downstream of the supply fan and heating. E = 2 Pleated Final Filter - 30% Efficient with 4 Pleated Final Filter - 65% Efficient - MERV 11-2 inch pleated, 30% efficient, MERV 8 final filters mounted upstream of 4 inch pleated, 65% efficient, MERV final filters mounted downstream of the supply fan and heating. F = 2 Pleated Final Filter - 30% Efficient with 4 Pleated Final Filter - 85% Efficient - MERV 13-2 inch pleated, 30% efficient, MERV 8 final filters mounted upstream of 4 inch pleated, 85% efficient, MERV 13 final filters mounted downstream of the supply fan and heating. G = 2 Pleated Final Filter - 30% Efficient with 4 Pleated Final Filter - 95% Efficient - MERV 14-2 inch pleated, 30% efficient, MERV 8 final filters mounted upstream of 4 inch pleated, 95% efficient, MERV 14 final filters mounted downstream of the supply fan and heating. Feature 7 Filter Options *A = Clogged Filter Switch (CFS) - Adjustable differential pressure switch sensing pressure drop across the unit filter bank and cooling coil. The range of adjustment is 0.17 to 5.0 in. W.C. with contact closure on rise. The switch is mounted in the fan compartment with terminal connections in the low voltage control section. Normally open dry contacts (C1 and C2) are provided for clogged filter indication. *B = Magnehelic Gauge - Magnehelic gauge reading pressure drop across the filter bank and cooling coil. The gauge reads from 0 to 3 in. W.C. in 0.10 in. graduations, and is mounted in the control cabinet. *C = Clogged Filter Switch + Magnehelic Gauge - Options A + B *A Special Pricing Authorization (SPA) is required if the CFS or Magnehelic gauge is to be used to respond to the pressure drop across only the cooling coil. 33

34 Figure 3 - Magnehelic Gauge Feature 8 Coil Coating 0 = Standard A = Polymer E-Coated Cooling and Heating Coils - Polymer e-coating applied to both the cooling and heating coils. Complete coil and casing are coated. Coating exceeds a 6,000 hour salt spray test per ASTM B requirements, yet is only mils thick and has excellent flexibility. Option is intended for use in coastal saltwater conditions under the stress of heat, salt, sand and wind and is applicable to all corrosive environments where a polymer e-coating is acceptable. Coating includes a 5 year non-prorated warranty. 34

35 Feature 9 Expansion Valve 0 = None - Chilled water cooling or heating only air handling unit. A = Thermal Expansion Valves - Factory installed thermal expansion valve on the evaporator coils. Expansion valve sensing bulb must be field installed on the suction line. Feature 10 Expansion Valve Controls 0 = None - No DX cooling coil. A = Standard Control - Factory installed standard thermal expansion valve control. Feature 11 Exterior Corrosion Protection A = AAON Gray Exterior Paint - Cabinet exterior is primer washed then spray coated with a two-part polyurethane, heat-baked exterior paint. The paint is gray in color and capable of withstanding at least 2,500 hours, with no visible corrosive effects, when tested in a salt spray and fog atmosphere in accordance with the ASTM B test procedure. B = Special Price Authorization with Special Paint - If a special paint color is specified, a set-up charge and price add per unit is required. Use this designation if other special paint options are necessary. The Applications Department must issue a Special Pricing Authorization (SPA) to include a non-standard option. 35

36 Feature 12 Tonnage - Chilled water cooling or heating only air handling unit. A = 2 ton Capacity - Two ton capacity matching condensing unit. B = 3 ton Capacity - Three ton capacity matching condensing unit. C = 4 ton Capacity - Four ton capacity matching condensing unit. D = 5 ton Capacity - Five ton capacity matching condensing unit. E = 6 ton Capacity - Six ton capacity matching condensing unit. F = 7 ton Capacity - Seven ton capacity matching condensing unit. G = 8 ton Capacity - Eight ton capacity matching condensing unit. H = 10 ton Capacity - Ten ton capacity matching condensing unit. J = 14 ton Capacity - Fourteen ton capacity matching condensing unit. K = 17 ton Capacity - Seventeen ton capacity matching condensing unit. L = 22 ton Capacity - Twenty two ton capacity matching condensing unit. M = 25 ton Capacity - Twenty five ton capacity matching condensing unit. N = 30 ton Capacity - Thirty ton capacity matching condensing unit. P = 31 ton Capacity - Thirty one ton capacity matching condensing unit. Q = 34 ton Capacity - Thirty four ton capacity matching condensing unit. R = 45 ton Capacity - Forty five ton capacity matching condensing unit. S = 55 ton Capacity - Fifty five ton capacity matching condensing unit. T = 63 ton Capacity - Sixty three ton capacity matching condensing unit. Feature 13 Added or Modified Systems 36

37 Feature 14A GPM Cooling Coil A = gpm B = gpm C = gpm D = gpm E = gpm F = gpm G = gpm H = gpm Feature 14B GPM Heating Coil A = gpm B = gpm C = gpm D = gpm E = gpm F = gpm G = gpm H = gpm 37

38 Feature 15 Control Panel 0 = None A = Small Control Panel - 12 x 12 - Small external control panel which can be attached to the unit or located near the unit. Six feet of separate control wiring with conduit and power wiring with conduit is factory provided between the control panel and unit. B = Medium Control Panel - 25 x 22 - Medium external control panel which can be attached to the unit or located near the unit. Six feet of separate control wiring with conduit and power wiring with conduit is factory provided between the control panel and unit. C = Large Control Panel - 48 x 22 - Large external control panel which can be attached to the unit or located near the unit. Six feet of separate control wiring with conduit and power wiring with conduit is factory provided between the control panel and unit. Feature 16 Blank Feature 17 Blank 38

39 Feature 18 Blank Feature 19 Blank Feature 20 Blank Feature 21 Blank 39

40 Feature 22 Warranty 0 = Standard - 1 Year Parts - Parts only warranty for a period of 12 months from the date of equipment startup or 18 months from the date of shipment, whichever is less. Feature 23 Type 0 = Standard X = Special Price Authorization - The Applications Department must issue a Special Pricing Authorization (SPA) to include a non-standard option. 40

41 General Data Unit Information Table 3 - A Cabinet (up to 1,200 cfm) Information Model H3-A V3-A Evaporator Coil Number of Circuits 1 or 2, Interlaced Quantity/Face Area 1/2.2 ft 2 Rows/fpi 4, 6 or 8/8, 10 or 12 Chilled Water Cooling Coil Quantity/Face Area 1/2.2 ft 2 Rows/fpi Standard Coil 4, 6 or 8/8, 10 or 12 (Double, Single, Half or Quarter Serpentine) Single Serpentine with 10 fpi Electric Heat Capacity (kw) 230/460V 3Φ 7, V 3Φ 5.3, kw - 1 or Fully Modulating with SCR Stages 14 kw - 1, 2 or Fully Modulating with SCR Hot Water Heating Coil Quantity/Face Area 1/2.19 ft 2 Rows/fpi 1 or 2/10 (Single, Half or Quarter Serpentine) Standard Coil 1 Row Single Serpentine 10 fpi Steam Heating Coil Quantity/Face Area 1/2.19 ft 2 Rows/fpi 1 or 2/10 (Single Serpentine) Standard Coil 1 Row Single Serpentine 10 fpi Supply Fans Quantity/Type 1/ Direct Drive Backward Curved Plenum 41

42 Table 4 - B Cabinet (up to 2,000 cfm) Information Model H3-B V3-B Evaporator Coil Number of Circuits 1 or 2, Interlaced Quantity/Face Area 1/3.5 ft 2 1/3.7 ft 2 Rows/fpi 4, 6 or 8/8, 10 or 12 Chilled Water Cooling Coil Quantity/Face Area 1/3.54 ft 2 1/3.44 ft 2 Rows/fpi Standard Coil 4, 6 or 8/8, 10 or 12 (Double, Single, Half or Quarter Serpentine) Single Serpentine with 10 fpi Electric Heat Capacity (kw) 230/460V 3Φ 7, 14, 21, V 3Φ 5.3, 10.5, 15.8, 21 7 kw - 1 or Fully Modulating with SCR 14 kw - 1, 2 or Fully Modulating with SCR Stages 21 kw - 1, 2, 3 or Fully Modulating with SCR 28 kw - 2, 3, 4 or Fully Modulating with SCR Hot Water Heating Coil Quantity/Face Area 1/3.54 ft 2 1/3.44 ft 2 Rows/fpi 1 or 2/10 (Single, Half or Quarter Serpentine) Standard Coil 1 Row Single Serpentine 10 fpi Steam Heating Coil Quantity/Face Area 1/3.54 ft 2 1/3.44 ft 2 Rows/fpi 1 or 2/10 (Single Serpentine) Standard Coil 1 Row Single Serpentine 10 fpi Supply Fans Quantity/Type 1/Belt Driven or Direct Drive Backward Curved Plenum 42

43 Table 5 - C Cabinet (up to 4,000 cfm) Information Model H3-C V3-C Evaporator Coil Number of Circuits 1 or 2, Interlaced Quantity/Face Area 1/7.2 ft 2 1/7.1 ft 2 Rows/fpi 4, 6 or 8/8, 10 or 12 Chilled Water Cooling Coil Quantity/Face Area 1/7.22 ft 2 Rows/fpi Standard Coil 4, 6 or 8/8, 10 or 12 (Double, Single, Half or Quarter Serpentine) Single Serpentine with 10 fpi Electric Heat Capacity (kw) 230/460V 3Φ 14, 21, 28, 35, V 3Φ 10.5, 15.8, 21.0, 26.3, kw - 1, 2 or Fully Modulating with SCR 21 kw - 1, 2, 3 or Fully Modulating with SCR Stages 28 kw - 2, 3, 4 or Fully Modulating with SCR 35 kw - 2, 3, 4 or Fully Modulating with SCR 42 kw - 3, 4 or Fully Modulating with SCR Hot Water Heating Coil Quantity/Face Area 1/7.22 ft 2 Rows/fpi 1 or 2/10 (Single, Half or Quarter Serpentine) Standard Coil 1 Row Single Serpentine 10 fpi Steam Heating Coil Quantity/Face Area 1/7.22 ft 2 Rows/fpi 1 or 2/10 (Single Serpentine) Standard Coil 1 Row Single Serpentine 10 fpi Supply Fans Quantity/Type 1 or 2/Belt Driven or Direct Drive Backward Curved Plenum 43

44 Table 6 - D Cabinet (up to 6,000 cfm) Information Model H3-D V3-D Evaporator Coil Number of Circuits 1 or 2, Interlaced Quantity/Face Area 1/10.3 ft 2 1/10.2 ft 2 Rows/fpi 4, 6 or 8/8, 10 or 12 Chilled Water Cooling Coil Quantity/Face Area 1/10.28 ft 2 1/10.38 ft 2 Rows/fpi Standard Coil Connection Sizes 4, 6 or 8/8, 10 or 12 (Double, Single, Half or Quarter Serpentine) Single Serpentine with 10 fpi Electric Heat Capacity (kw) 230/460V 3Φ 14, 21, 28, 35, 42, 49, 56, 63, V 3Φ 10.5, 15.8, 21.0, 26.3, 31.5, 37.0, 42.0, 47.3, kw - 1, 2 or Fully Modulating with SCR 21 kw - 1, 2, 3 or Fully Modulating with SCR 28 kw - 2, 3, 4 or Fully Modulating with SCR 35 kw - 2, 3, 4 or Fully Modulating with SCR Stages 42 kw - 3, 4 or Fully Modulating with SCR 49 kw - 3, 4 or Fully Modulating with SCR 56 kw - 3, 4 or Fully Modulating with SCR 63 kw - 3, 4 or Fully Modulating with SCR 70 kw - 4 or Fully Modulating with SCR Hot Water Heating Coil Quantity/Face Area 1/10.28 ft 2 1/10.38 ft 2 Rows/fpi 1 or 2/10 (Single, Half or Quarter Serpentine) Standard Coil Single Serpentine with 10 fpi Steam Heating Coil Quantity/Face Area 1/10.28 ft 2 1/10.38 ft 2 Rows/fpi 1 or 2/10 (Single Serpentine) Standard Coil Single Serpentine with 10 fpi Supply Fans Quantity/Type 1 or 2/Belt Driven or Direct Drive Backward Curved Plenum 44

45 Table 7 - E Cabinet (up to 10,000 cfm) Information Model H3-E V3-E Evaporator Coil Number of Circuits 1 or 2, Interlaced Quantity/Face Area 1/17.5 ft 2 1/17.3 ft 2 Rows/fpi 4, 6 or 8/8, 10 or 12 Chilled Water Cooling Coil Quantity/Face Area 1/17.19 ft 2 1/17.57 ft 2 Rows/fpi Standard Coil 4, 6 or 8/8, 10 or 12 (Double, Single, Half or Quarter Serpentine) Single Serpentine with 10 fpi Electric Heat Capacity (kw) 230/460V 3Φ 14, 21, 28, 35, 42, 49, 56, 63, 70, 77, V 3Φ 10.5, 15.8, 21.0, 26.3, 31.5, 37.0, 42.0, 47.3, 52.5, 57.8, kw - 1, 2 or Fully Modulating with SCR 21 kw - 1, 2, 3 or Fully Modulating with SCR 28 kw - 2, 3, 4 or Fully Modulating with SCR 35 kw - 2, 3, 4 or Fully Modulating with SCR 42 kw - 3, 4 or Fully Modulating with SCR Stages 49 kw - 3, 4 or Fully Modulating with SCR 56 kw - 3, 4 or Fully Modulating with SCR 63 kw - 3, 4 or Fully Modulating with SCR 70 kw - 4 or Fully Modulating with SCR 77 kw - 4 or Fully Modulating with SCR 84 kw - 4 or Fully Modulating with SCR 45

46 Table 8 - E Cabinet (up to 10,000 cfm) Information Continued Model H3-E V3-E Hot Water Heating Coil Quantity/Face Area 1/17.19 ft 2 1/17.57 ft 2 Rows/fpi 1 or 2/10 (Single, Half or Quarter Serpentine) Standard Coil Single Serpentine with 10 fpi Steam Heating Coil Quantity/Face Area 1/17.19 ft 2 1/17.57 ft 2 Rows/fpi 1 or 2/10 (Single Serpentine) Standard Coil Single Serpentine with 10 fpi Supply Fans Quantity/Type 1 or 2/Belt Driven or Direct Drive Backward Curved Plenum Table 9 - Chilled Water and Hot Water Coil Connection Sizes Coil gpm Sweat Connection Size (inches) / / / / / / / /8 46

47 Filter Information Table 10 - H3 Series A Cabinet Pre Filters Feature 6A (Quantity) Size Type 0 No Pre Filters A (1) 16 x 25 x 2 Pleated, 30% Eff, MERV 8 B Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 (1) 16 x 25 x 4 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14 F Pleated, 30% Eff, MERV 8 G H J (1) 16 x 25 x 2 and (1) 16 x 25 x 4 Pleated, 65% Eff, MERV 11 Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Table 11 - V3 Series A Cabinet Pre Filters Feature 6A (Quantity) Size Type 0 No Pre Filters A (1) 16 x 25 x 2 Pleated, 30% Eff, MERV 8 B Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 (1) 16 x 25 x 4 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14 F Pleated, 30% Eff, MERV 8 G H J (1) 16 x 25 x 2 and (1) 16 x 25 x 4 Pleated, 65% Eff, MERV 11 Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 47

48 Table 12 - H3 Series B Cabinet Pre Filters Feature 6A (Quantity) Size Type 0 No Pre Filters A (2) 16 x 20 x 2 Pleated, 30% Eff, MERV 8 B Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 (2) 16 x 20 x 4 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14 F Pleated, 30% Eff, MERV 8 G H J (2) 16 x 20 x 2 and (2) 16 x 20 x 4 Pleated, 65% Eff, MERV 11 Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Table 13 - V3 Series B Cabinet Pre Filters Feature 6A (Quantity) Size Type 0 No Pre Filters A (1) 24 x 24 x 2 Pleated, 30% Eff, MERV 8 B Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 (1) 24 x 24 x 4 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14 F Pleated, 30% Eff, MERV 8 G H J (1) 24 x 24 x 2 and (1) 24 x 24 x 4 Pleated, 65% Eff, MERV 11 Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 48

49 Table 14 - H3 Series C Cabinet Pre Filters Feature 6A (Quantity) Size Type 0 No Pre Filters A (2) 20 x 20 x 2" and (1) 16 x 20 x 2" Pleated, 30% Eff, MERV 8 B Pleated, 30% Eff, MERV 8 C (2) 20 x 20 x 4" and Pleated, 65% Eff, MERV 11 D (1) 16 x 20 x 4" Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14 F G H J (2) 20 x 20 x 2" and (1) 16 x 20 x 2" and (2) 20 x 20 x 4" and (1) 16 x 20 x 4" Pleated, 30% Eff, MERV 8 Pleated, 65% Eff, MERV 11 Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Table 15 - V3 Series C Cabinet Pre Filters Feature 6A (Quantity) Size Type 0 No Pre Filters A (4) 16 x 20 x 2 Pleated, 30% Eff, MERV 8 B Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 (4) 16 x 20 x 4 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14 F Pleated, 30% Eff, MERV 8 G H J (4) 16 x 20 x 2 and (4) 16 x 20 x 4 Pleated, 65% Eff, MERV 11 Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 49

50 Table 16 - H3 Series D Cabinet Pre Filters Feature 6A (Quantity) Size Type 0 No Pre Filters A (1) 20 x 20 x 2 and (4) 16 x 20 x 2" Pleated, 30% Eff, MERV 8 B Pleated, 30% Eff, MERV 8 C (1) 20 x 20 x 4 and Pleated, 65% Eff, MERV 11 D (4) 16 x 20 x 4" Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14 F G H J (1) 20 x 20 x 2 and (4) 16 x 20 x 2" and (1) 20 x 20 x 4 and (4) 16 x 20 x 4" Pleated, 30% Eff, MERV 8 Pleated, 65% Eff, MERV 11 Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Table 17 - V3 Series D Cabinet Pre Filters Feature 6A (Quantity) Size Type 0 No Pre Filters A (2) 20 x 20 x 2 and (4) 16 x 20 x 2" Pleated, 30% Eff, MERV 8 B Pleated, 30% Eff, MERV 8 C (2) 20 x 20 x 4 and Pleated, 65% Eff, MERV 11 D (4) 16 x 20 x 4" Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14 F G H J (2) 20 x 20 x 2 and (4) 16 x 20 x 2" and (2) 20 x 20 x 4 and (4) 16 x 20 x 4" Pleated, 30% Eff, MERV 8 Pleated, 65% Eff, MERV 11 Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 50

51 Table 18 - H3 Series E Cabinet Pre Filters Feature 6A (Quantity) Size Type 0 No Pre Filters A (10) 16 x 20 x 2 Pleated, 30% Eff, MERV 8 B Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 (10) 16 x 20 x 4 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14 F Pleated, 30% Eff, MERV 8 G H J (10) 16 x 20 x 2 and (10) 16 x 20 x 4 Pleated, 65% Eff, MERV 11 Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Table 19 - V3 Series E Cabinet Pre Filters Feature 6A (Quantity) Size Type 0 No Pre Filters A (3) 20 x 20 x 2 and (6) 16 x 20 x 2" Pleated, 30% Eff, MERV 8 B Pleated, 30% Eff, MERV 8 (3) 20 x 20 x 4 and C Pleated, 65% Eff, MERV 11 (6) 16 x 20 x 4" D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14 F G H J (3) 20 x 20 x 2 and (6) 16 x 20 x 2" and (3) 20 x 20 x 4 and (6) 16 x 20 x 4" Pleated, 30% Eff, MERV 8 Pleated, 65% Eff, MERV 11 Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 51

52 Table 20 - H3 Series A Cabinet Unit Filters Feature 6B (Quantity) Size Type 0 No Unit Filters A (1) 16 x 25 x 2 Pleated, 30% Eff, MERV 8 B Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 (1) 16 x 25 x 4 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14 F Pleated, 30% Eff, MERV 8 G H J (1) 16 x 25 x 2 and (1) 16 x 25 x 4 Pleated, 65% Eff, MERV 11 Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Table 21 - V3 Series A Cabinet Unit Filters Feature 6B (Quantity) Size Type 0 No Unit Filters A (1) 16 x 25 x 2 Pleated, 30% Eff, MERV 8 52

53 Table 22 - H3 Series B Cabinet Unit Filters Feature 6B (Quantity) Size Type 0 No Unit Filters A (2) 16 x 20 x 2 Pleated, 30% Eff, MERV 8 B Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 (2) 16 x 20 x 4 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14 F Pleated, 30% Eff, MERV 8 G H J (2) 16 x 20 x 2 and (2) 16 x 20 x 4 Pleated, 65% Eff, MERV 11 Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Table 23 - V3 Series B Cabinet Unit Filters Feature 6B (Quantity) Size Type 0 No Unit Filters A (2) 24 x 12 x 2 Pleated, 30% Eff, MERV 8 53

54 Table 24 - H3 Series A Cabinet Final Filters Feature 6C (Quantity) Size Type 0 No Final Filters A (1) 16 x 25 x 2 Pleated, 30% Eff, MERV 8 B Cartridge, 65% Eff, MERV 11 C (1) 16 x 25 x 12 Cartridge, 85% Eff, MERV 13 D Cartridge, 95% Eff, MERV 14 E F G (1) 16 x 25 x 2 and (1) 16 x 25 x 12 Cartridge, 65% Eff, MERV 11 Cartridge, 85% Eff, MERV 13 Cartridge, 95% Eff, MERV 14 Table 25 - V3 Series A Cabinet Final Filters Feature 6C (Quantity) Size Type 0 No Final Filters A (1) 16 x 25 x 2 Pleated, 30% Eff, MERV 8 B Cartridge, 65% Eff, MERV 11 C (1) 16 x 25 x 12 Cartridge, 85% Eff, MERV 13 D Cartridge, 95% Eff, MERV 14 E F G (1) 16 x 25 x 2 and (1) 16 x 25 x 12 Cartridge, 65% Eff, MERV 11 Cartridge, 85% Eff, MERV 13 Cartridge, 95% Eff, MERV 14 54

55 Table 26 - H3 Series B Cabinet Final Filters Feature 6C (Quantity) Size Type 0 No Final Filters A (2) 16 x 20 x 2 Pleated, 30% Eff, MERV 8 B Cartridge, 65% Eff, MERV 11 C (2) 16 x 20 x 12 Cartridge, 85% Eff, MERV 13 D Cartridge, 95% Eff, MERV 14 E F G (2) 16 x 20 x 2 and (2) 16 x 20 x 12 Cartridge, 65% Eff, MERV 11 Cartridge, 85% Eff, MERV 13 Cartridge, 95% Eff, MERV 14 Table 27 - V3 Series B Cabinet Final Filters Feature 6C (Quantity) Size Type 0 No Final Filters A (2) 24 x 12 x 2 Pleated, 30% Eff, MERV 8 B Cartridge, 65% Eff, MERV 11 C (2) 24 x 12 x 12 Cartridge, 85% Eff, MERV 13 D Cartridge, 95% Eff, MERV 14 E F G (2) 24 x 12 x 2 and (2) 24 x 12 x 12 Cartridge, 65% Eff, MERV 11 Cartridge, 85% Eff, MERV 13 Cartridge, 95% Eff, MERV 14 55

56 Table 28 - H3 Series C Cabinet Final Filters Feature 6C (Quantity) Size Type 0 No Final Filters A (2) 20 x 20 x 2 and (1) 16 x 20 x 2" Pleated, 30% Eff, MERV 8 B Cartridge, 65% Eff, MERV 11 (2) 20 x 20 x12 and C Cartridge, 85% Eff, MERV 13 (1) 16 x 20 x 12" D Cartridge, 95% Eff, MERV 14 E F G (2) 20 x 20 x 2 and (1) 16 x 20 x 2" and (2) 20 x 20 x12 and (1) 16 x 20 x 12" Cartridge, 65% Eff, MERV 11 Cartridge, 85% Eff, MERV 13 Cartridge, 95% Eff, MERV 14 Table 29 - V3 Series C Cabinet Final Filters Feature 6C (Quantity) Size Type 0 No Final Filters A (4) 16 x 20 x 2 Pleated, 30% Eff, MERV 8 B Cartridge, 65% Eff, MERV 11 C (4) 16 x 20 x 12 Cartridge, 85% Eff, MERV 13 D Cartridge, 95% Eff, MERV 14 E F G (4) 16 x 20 x 2 and (4) 16 x 20 x 12 Cartridge, 65% Eff, MERV 11 Cartridge, 85% Eff, MERV 13 Cartridge, 95% Eff, MERV 14 56

57 Table 30 - H3 Series D Cabinet Final Filters Feature 6C (Quantity) Size Type 0 No Final Filters A (1) 20 x 20 x 2" and (4) 16 x 20 x 2" Pleated, 30% Eff, MERV 8 B Cartridge, 65% Eff, MERV 11 (1) 20 x 20 x 12" and C Cartridge, 85% Eff, MERV 13 (4) 16 x 20 x 12" D Cartridge, 95% Eff, MERV 14 E F G (1) 20 x 20 x 2" and (4) 16 x 20 x 2" and (1) 20 x 20 x 12" and (4) 16 x 20 x 12" Cartridge, 65% Eff, MERV 11 Cartridge, 85% Eff, MERV 13 Cartridge, 95% Eff, MERV 14 Table 31 - V3 Series D Cabinet Final Filters Feature 6C (Quantity) Size Type 0 No Final Filters A (2) 20 x 20 x 2" and (4) 16 x 20 x 2" Pleated, 30% Eff, MERV 8 B Cartridge, 65% Eff, MERV 11 (2) 20 x 20 x 12" and C Cartridge, 85% Eff, MERV 13 (4) 16 x 20 x 12" D Cartridge, 95% Eff, MERV 14 E F G (2) 20 x 20 x 2" and (4) 16 x 20 x 2" and (2) 20 x 20 x 12" and (4) 16 x 20 x 12" Cartridge, 65% Eff, MERV 11 Cartridge, 85% Eff, MERV 13 Cartridge, 95% Eff, MERV 14 57

58 Table 32 - H3 Series E Cabinet Final Filters Feature 6C (Quantity) Size Type 0 No Final Filters A (10) 16 x 20 x 2 Pleated, 30% Eff, MERV 8 B Cartridge, 65% Eff, MERV 11 C (10) 16 x 20 x 12 Cartridge, 85% Eff, MERV 13 D Cartridge, 95% Eff, MERV 14 E F G (10) 16 x 20 x 2 and (10) 16 x 20 x 12 Cartridge, 65% Eff, MERV 11 Cartridge, 85% Eff, MERV 13 Cartridge, 95% Eff, MERV 14 Table 33 - V3 Series E Cabinet Final Filters Feature 6C (Quantity) Size Type 0 No Final Filters A (3) 20 x 20 x 2 and (6) 16 x 20 x 2" Pleated, 30% Eff, MERV 8 B Cartridge, 65% Eff, MERV 11 (3) 20 x 20 x 12 and C Cartridge, 85% Eff, MERV 13 (6) 16 x 20 x 12" D Cartridge, 95% Eff, MERV 14 E F G (3) 20 x 20 x 2 and (6) 16 x 20 x 2" and (3) 20 x 20 x 12 and (6) 16 x 20 x 12" Cartridge, 65% Eff, MERV 11 Cartridge, 85% Eff, MERV 13 Cartridge, 95% Eff, MERV 14 58

59 Controls Control Options Terminal Block Low voltage terminal block for field wiring unit controls Required Features Feature 1D - Terminal Block, or Feature 1D - Potentiometer Supply Fan Control, or Feature 1D - Field Installed Controls by Others Standard Terminals Labels [R] - 24VAC control voltage [E] - Common [G] - Fan enable [Y1], [Y2], - Cooling stage enables [W1], [W2], - Heating stage enables [+], [-] - SCR supply air temperature controls signal, 0-10VDC [A1], [A2] - Actuator override contacts, factory wired together, used to control occupied/unoccupied operation. [EC1-], [EC2+] - DDC actuator control signal, 4-20mA. Remove resistor for 0-10VDC operation. [RH1] - Humidistat or dehumidification enable input control terminal, used to activate hot gas reheat option. [C1], [C2] - Clogged filter switch contacts, normally open. [C6], [C7] - Supply air temperature sensor control signal, 0-10VDC. [1], [2] - SCR supply air temperature control signal, 0-10VDC [S1], [S2], - Supply fan VFD or ECM control contacts, 0-10VDC or 4-20mA. Figure 4 - Example Low Voltage Terminal Block 59

60 Variable Air Volume (VAV) Unit Controller Operation - Variable Air Volume Cooling and Constant Volume Heating Standard AAON VAV controls for standard and heat pump systems. During the cooling mode of operation the supply fan modulates based on the supply air duct static pressure and cooling modulates based on the supply air temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Factory provided VFDs or ECM driven motors are used to vary the speed of the supply fans and thus vary the amount of supply air. Because of the reduced speed, VAV units can be very energy efficient at part load conditions. VAV units can be used to serve multiple spaces with diverse or changing heating and cooling requirements, with only a single unit being required for multiple zones. AAON VAV units can also be applied to a single zone. Space temperature sensor included with WattMaster controller is used for supply air temperature setpoint reset and unoccupied override. See Control Venders section for WattMaster, JENEsys, and Mini Controller specifics. Required Features Feature 2 - Hot Gas Bypass - Units without variable capacity scroll compressors. Feature 3 - VAV Unit Controller Standard Supplied Sensors Outside Air Temperature - Field Installed Supply Air Duct Temperature - Field Installed Supply Air Duct Static Pressure - Field Installed Return Air Temperature Space Temperature with Temperature Setpoint Reset and Unoccupied Override (WattMaster) - Field Installed Model Option B3 - Modulating/SCR Electric Heat Recommended Features Feature 1A - VFD Controlled or ECM Driven Supply Fans Feature 2 - Modulating Hot Gas Reheat Feature 5A and 5B - Mixing Box Feature 5C - Fully Modulating Actuators 60

61 Constant Volume (CV/CAV) Unit Controller Operation - Constant Volume Cooling and Constant Volume Heating Standard AAON Constant Volume controls for standard systems. During the cooling mode of operation the supply fan provides constant airflow and mechanical cooling modulates based on the controlling temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. A Constant Volume unit can be used to serve spaces with uniform heating and cooling requirements. Multiple units may be required for multiple zones. Space or supply air temperature sensor can be used as the controlling sensor. If supply air temperature is not used as the controlling sensor it is used as a temperature lockout. If supply air temperature sensor is used as the controlling sensor, space temperature sensor is used for supply air temperature setpoint reset and unoccupied override. See Control Venders section for WattMaster, JENEsys, and Mini Controller specifics. Required Features Feature 3 - Constant Volume Unit Controller Standard Supplied Sensors Outside Air Temperature - Field Installed Supply Air Duct Temperature - Field Installed Space Temperature with Temperature Setpoint Reset and Unoccupied Override - Field Installed Model Option B3 - Modulating/SCR Electric Heat Recommended Features Feature 1A - VFD Controlled or ECM Driven Supply Fans Feature 2 - Modulating Hot Gas Reheat Feature 5A and 5B - Mixing Box Feature 5C - Fully Modulating Actuators 61

62 Make Up Air (MUA) Unit Controller Operation - Constant Volume Cooling and Constant Volume Heating Standard AAON Make Up Air controls for standard systems. During the cooling mode of operation the supply fan provides constant airflow and mechanical cooling modulates based on the controlling temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Make Up Air units are designed to provide 100% outside air to the system for ventilation purposes. Make Up Air units can improve indoor air quality (IAQ) and also be used to positively pressurize to the space. See Control Venders section for WattMaster, JENEsys, and Mini Controller specifics. Required Features Feature 2 - Hot Gas Bypass - Units without variable capacity scroll compressors. Feature 3 - Make Up Air Unit Controller Standard Supplied Sensors Outside Air Temperature - Field Installed Supply Air Temperature - Field Installed Model Option B3 - Modulating/SCR Electric Heat Recommended Features Feature 1A - VFD Controlled or ECM Driven Supply Fans Feature 2 - Modulating Hot Gas Reheat 62

63 Single Zone Variable Air Volume (Single Zone VAV) Unit Controller Operation - Variable Air Volume Cooling and Constant Volume or Variable Air Volume Heating Standard AAON Single Zone VAV controls for standard and heat pump systems. During the cooling mode of operation the supply fan modulates based on the space temperature and cooling modulates based on the supply air temperature. For constant volume heating, during the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. For variable air volume heating, the supply fan modulates based on the space temperature and heating modulates based on the supply air temperature. Factory provided VFDs or ECM driven motors are used to vary the speed of the supply fans and vary the amount of supply air. Because of the reduced speed, single zone VAV units can be very energy efficient at part load conditions. Single zone VAV units can be used to serve a single space or multiple zones with uniform heating and cooling requirements. Space temperature sensor included with WattMaster controller is used for supply air temperature setpoint reset and unoccupied override. See Control Venders section for WattMaster, JENEsys, and Mini Controller specifics. Required Features Model Option B3 - Modulating/SCR Electric Heat, with auxiliary electric VAV heating Feature 3 - Single Zone VAV Unit Controller Standard Supplied Sensors Outside Air Temperature Sensor - Field Installed Supply Air Duct Temperature - Field Installed Return Air Temperature Space Temperature with Temperature Setpoint Reset and Unoccupied Override (WattMaster) - Field Installed Feature 1A - VFD Controlled or ECM Driven Supply Fans Recommended Features Feature 2 - Modulating Hot Gas Reheat Feature 5A and 5B - Mixing Box Feature 5C - Fully Modulating Actuators 63

64 Control Vendors WattMaster - Orion Controls System Figure 5 - WattMaster VCM-X Controller The WattMaster VCM-X unit controller, which is part of the Orion Controls System, can be factory provided and factory installed in AAON H3/V3 Series units. It provides advanced control features, without complexity, in an easy to install and setup package. The VCM-X controller can be individually configured, including setpoint adjustment, sensor status viewing, and occupancy scheduling. It can control VAV, CV, MUA and Single Zone VAV units. Additional features and options can be managed by the controller with the addition of modular expansion I/O boards for the controller. The VCM-X controller can be operated as a Stand Alone System, connected via modular cable to multiple VCM-X controllers in an Interconnected System, or connected via modular cable to multiple VCM-X controllers, VAV/Zone controllers, and Add-On controllers in a Networked System. Protocol Adaptability is available from WattMaster for interfacing to LonWorks, BACnet or Johnson Controls N2 controls systems with the addition of specific gateways. Required Options To configure the VCM-X controller an operator interface is needed. Available operator interfaces are the Modular Service Tool, Modular System Manager, System Manager TS, Tactio SI Touch Screen Interface connected via a Commlink II and a PC equipped with free Microsoft Windows based Orion Prism II software connected via a Commlink II. With optional accessories, remote connectivity to the controller via Prism II software can be accomplished. Figure 6 - VCM-X Controller Operator Interfaces 64

65 AAON JENEsys Control System Figure 7 - JENEsys Controller The AAON JENEsys controller, powered by Niagara AX Framework, is an Internet-based stand alone controller developed for network applications which can be factory provided and factory installed in AAON H3/V3 Series units. It can be configured to control VAV, CV, MUA and Single Zone VAV units, as well as other custom controls solutions. The controller is IP addressable, can reside on a TCP/IP network and can have all unit and system functions controlled with an Internet browser in real-time; including setpoint adjustment, scheduling, alarming, trending, logging, and diagnostics. Interoperability The JENEsys controller can be directly integrated into LonWorks, BACnet, Modbus and other widely-used building automation systems. Connections included on controller include two RJ-45 Ethernet ports, one RS-232 port and one RS-485 port. No external devices are needed for integration. Scalability The JENEsys controller is scalable with up to one 34 I/O point and two 16 I/O point expansion modules available to manage additional features and options. Individual sensor options and unit control options are also scalable with extra sensors available to be added to any controls package. Security The JENEsys controller uses XML security functions that cover platform, administration and user access. Thus, operational control of the unit controller will be allowed only to those who need it. Contact the Applications Department for more information. Required Options In order to configure the JENEsys controller, a PC connected directly to the controller or connected to the TCP/IP network that the controller resides on is needed. From the PC, direct Internet browser control is then available. 65

66 AAON Mini Controller Figure 8 - Remote Mounted AAON Mini Controller The AAON Mini Controller is a simple controls option for energy saving applications. It is remote mounted in the space similar to a conventional thermostat. Controllable Features A lead/single variable capacity scroll compressor (with up to two total compressor stages), air conditioner or heat pump configuration, ECM driven/vfd controlled variable speed supply fan, sensible or enthalpy controlled economizer and modulating gas/scr electric heating are controllable with the AAON Mini Controller. Modulating hot gas reheat is available with a space temperature sensor and space relative humidity sensor version of the controller. Push button override, alarms and trend logging are available directly from the controller. Applications The controller can be used for constant volume air conditioner and heat pump applications or single zone VAV air conditioner and heat pump applications. Scheduling Weekday, weekend, entire week or daily scheduling is available with the AAON Mini Controller. Twelve days of holiday scheduling are also available. Networking The AAON Mini Controller can be directly connected to a BACnet MSTP network through an EIA-485 connection. The MAC Address, Baud Rate and Max Master are configurable. Security The AAON Mini Controller includes password protected User, Operator and Administrator profiles for configuration, scheduling and setpoint adjustment levels of control. Required Options The AAON Mini Controller is available for AAON split systems with a variable capacity scroll compressor. 1-2 stages of heat are available with an air conditioner and 1 stage of emergency heat is available with a heat pump. The controller has a limited quantity of inputs and outputs and thus the quantity of features which can be controlled and are available in AAONEcat32 are limited. 66

67 Electrical Service Sizing Data Use the following equations to size the electrical service wiring and disconnect switch for the unit. Electrical data for a specific unit configuration can be found with the AAONEcat32 software. For further assistance in determining the electrical ratings, contact the Applications Department, or consult U.L The Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) must be calculated for all modes of operation which include the cooling mode of operation, the heating mode of operation, and if the unit is a heat pump the emergency heating mode of operation and auxiliary heating mode of operation. The emergency or backup heating mode of operation is when the secondary heater is in operation and heat pump or compressor heating is not in operation. The auxiliary or supplemental heating mode of operation is when heat pump or compressor heating is in operation and the secondary heater is also in operation. To calculate the MCA and MOP, the number of motors and other current drawing devices in operation must be known for each mode of operation. The largest MCA and MOP values calculated from all the modes operation are the correct values and are also on the unit nameplate. For example, during the cooling mode of operation of an air-cooled DX unit or an air-source heat pump the supply fans, compressors, and condenser fans are all in operation. During the heating mode of operation of an air-cooled DX unit or the emergency heating mode of operation of an air-source heat pump only the supply fans and heater are in operation. During the auxiliary heating mode of operation of an air-source heat pump the supply fans, compressors, condenser fans, and secondary heater are all in operation. Once it is determined what current drawing devices are operating during each mode of operation use the equations shown below to calculate the MCA and MOP. Use Rated Load Amps (RLA) for compressors and Full Load Amps (FLA) for all other motors and electric heaters. Load 1 = Current of the largest motor/compressor in operation Load 2 = Sum of the currents of the remaining motors/compressors in operation Load 3 = Current of electric heaters in operation Load 4 = Any remaining loads greater than or equal to 1 amp Single Phase Electric Heat FLA Calculation Three Phase FLA = ( Heating Element kw ) x1000 Rated Voltage FLA = ( Heating Element kw ) x1000 ( Rated Voltage) x 3 67

68 Cooling Mode Equations Electrical Service Sizing Data Continued MCA = 1.25(Load 1) + Load 2 + Load 4 MOP = 2.25(Load 1) + Load 2 + Load 4 Heating Mode or Emergency/Backup Heating Mode without Electric Heat Equations MCA = 1.25(Load 1) + Load 2 + Load 4 MOP = 2.25(Load 1) + Load 2 + Load 4 Heating Mode or Emergency/Backup Heating Mode with Less than 50 kw of Electric Heat Equations MCA = 1.25(Load 1 + Load 2 + Load 3 + Load 4) MOP = 2.25(Load 1) + Load 2 + Load 3 + Load 4 Heating Mode or Emergency/Backup Heating Mode with Greater than or Equal to 50 kw of Electric Heat Equations MCA = 1.25(Load 1 + Load 2) + Load (Load 4) MOP = 2.25(Load 1) + Load 2 + Load 3 + Load 4 Auxiliary/Supplemental Heating Mode without Electric Heat Equations MCA = 1.25(Load 1) + Load 2 + Load 4 MOP = 2.25(Load 1) + Load 2 + Load 4 Auxiliary/Supplemental Heating Mode with Less than 50 kw of Electric Heat Equations MCA = 1.25(Load 1) + Load (Load 3) + Load 4 MOP = 2.25(Load 1) + Load 2 + Load 3 + Load 4 Auxiliary/Supplemental Heating Mode with Greater than or Equal to 50 kw of Electric Heat Equations MCA = 1.25(Load 1) + Load 2 + Load 3 + Load 4 MOP = 2.25(Load 1) + Load 2 + Load 3 + Load 4 68

69 Electrical Service Sizing Data Continued Fuse Selection Select a fuse rating equal to the MOP value. If the MOP does not equal a standard fuse rating select the next lower standard fuse rating. If the MOP is less than the MCA then select the fuse rating equal to or greater than the MCA. The standard ampere ratings for fuses, from the NEC Handbook, 240-6, shall be considered 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800 and 1000 amperes. Disconnect (Power) Switch Size DSS MOP Select the standard switch size equal to the calculated MOP value. If this value is not a standard size, select the next larger size. 69

70 Literature Change History July 2010 First Revision, Rev. A, of the H3/V3 Engineering Catalog. April 2012 Update to the catalog changing the 2 pleated 30% efficient filter from MERV 7 to MERV 8, adding additional modulating hot gas reheat options to Feature 2, and adding the Water Coil Connection Sizes table. July 2012 Update to the catalog showing single serpentine as the only circuitry option for steam heating, and that the steam heating coil option is stream distributing (Model Option B1 = 4), and adding Single Zone VAV and AAON Mini Controller information. 70

71

72

73

74 AAON 2425 South Yukon Ave. Tulsa, OK Phone: Fax: H3/V3 Series Engineering Catalog R94190 Rev. A (ACP 30585) It is the intent of AAON to provide accurate and current product information. However, in the interest of product improvement, AAON reserves the right to change pricing, specifications, and/or design of its product without notice, obligation, or liability. Copyright AAON, all rights reserved throughout the world. AAON and AAONAIRE are registered trademarks of AAON, Inc., Tulsa, OK.

H3/V3 Series. Installation, Operation & Maintenance. Horizontal and Vertical Indoor Air Handling Units WARNING WARNING WARNING

H3/V3 Series. Installation, Operation & Maintenance. Horizontal and Vertical Indoor Air Handling Units WARNING WARNING WARNING H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Installation, Operation & Maintenance WARNING WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance

More information

ALL PRODUCTS BROCHURE

ALL PRODUCTS BROCHURE ALL PRODUCTS BROCHURE www.aaon.com d e d i c at i o n t o cust o m e r service since the founding of aaon in 1988, we have maintained our commitment to design, develop, manufacture and deliver heating

More information

V3 Series. Installation, Operation & Maintenance. Vertical Indoor Air Handling Units WARNING WARNING WARNING QUALIFIED INSTALLER

V3 Series. Installation, Operation & Maintenance. Vertical Indoor Air Handling Units WARNING WARNING WARNING QUALIFIED INSTALLER V3 Series Vertical Indoor Air Handling Units Installation, Operation & Maintenance QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal

More information

H3 Series. Installation, Operation & Maintenance. Horizontal Indoor Air Handling Units WARNING WARNING WARNING QUALIFIED INSTALLER

H3 Series. Installation, Operation & Maintenance. Horizontal Indoor Air Handling Units WARNING WARNING WARNING QUALIFIED INSTALLER H3 Series Horizontal Indoor Air Handling Units Installation, Operation & Maintenance QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property damage,

More information

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS.

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS. RN/RQ Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS RQ Series Features: Air-cooled or water-cooled condenser, with unit capacities

More information

RN SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING

RN SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING RN SERIES Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units Installation, Operation, & Maintenance WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result

More information

Heat Pumps M2 SERIES. Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features:

Heat Pumps M2 SERIES. Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features: Heat Pumps M2 SERIES Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features: Water-source and geothermal heat pump self-contained units with capacities from 3-70 tons 10%-100% variable

More information

RN SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING

RN SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING RN SERIES Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units Installation, Operation, & Maintenance WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result

More information

RQ SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING

RQ SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING RQ SERIES Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units Installation, Operation, & Maintenance WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result

More information

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc. System Components with ` Emphasis on Packaged Rooftop Application and Installation Jerry Cohen President Jacco & Assoc. Agenda Define and relate in practical terms the following components: System Effect

More information

RN SERIES. Installation, Operation & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING

RN SERIES. Installation, Operation & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING RN SERIES Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units Installation, Operation & Maintenance WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result

More information

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series.

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series. RN/RQ Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS RQ Series Features: Air-cooled or water-cooled condenser, with unit capacities

More information

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features:

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features: Heat Pumps SA SERIES SA Series Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features: Vertical self-contained units with capacities from 23 70 tons Direct drive backward curved plenum

More information

RN SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING

RN SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING RN SERIES Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units Installation, Operation, & Maintenance WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result

More information

RN SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING

RN SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING RN SERIES Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units Installation, Operation, & Maintenance WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result

More information

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features:

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features: Heat Pumps SA SERIES Features: Vertical self-contained units with capacities from 23 70 tons Direct drive backward curved plenum and reduced maintenance Double wall rigid polyurethane foam injected panel

More information

RQ SERIES. Installation, Operation & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING

RQ SERIES. Installation, Operation & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING RQ SERIES Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units Installation, Operation & Maintenance FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious

More information

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features: RL Packaged Rooftop Units, heat pumps and Outdoor air handling Units Features: Air-cooled condenser, water-cooled condenser, or patented AAON evaporative-cooled condenser, with capacities from 45-240 tons

More information

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features: RZ PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS Features: Air-cooled condenser, water-cooled condenser, or evaporative-cooled condenser packaged rooftop units from 55-240 tons Water-source

More information

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units TECHNICAL SPECIFICATIONS R7DA Series 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units 5.4 ISMRE Commercial System 81% Steady State Efficiency Standard Features Fits Pre-Existing Curbs High-Efficiency Low

More information

VertiCool Aurora Engineering Guide

VertiCool Aurora Engineering Guide Engineering Guide Effective August 2016 Air-Cooled, Water-Cooled and Water Source Heat Pump Contents Product Features... 3 Options... 4 Physical Data...5-6 Air-Cooled Performance Data (a) (b) (c)...7-8

More information

RQ SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING

RQ SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units WARNING WARNING RQ SERIES Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units Installation, Operation, & Maintenance WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result

More information

THE ULTIMATE ROOFTOP SOLUTION

THE ULTIMATE ROOFTOP SOLUTION Configured Packaged Rooftop Solutions Specializing in Dedicated Outdoor Air Systems (DOAS) Capacities from 6 to 90 Tons Available in 208, 230, 460 and 575 Volts THE ULTIMATE ROOFTOP SOLUTION Service Friendly

More information

Heat Pumps SB SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (3-18 tons) Features:

Heat Pumps SB SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (3-18 tons) Features: Heat Pumps SB SERIES SB Series Vertical Self-Contained Unit Water-Source Heat Pumps (3-18 tons) Features: Vertical self-contained units with capacities from 3-18 tons ECM driven direct drive backward curved

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

RL SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units & Outdoor Air Handling Units WARNING WARNING

RL SERIES. Installation, Operation, & Maintenance. Packaged Rooftop Units & Outdoor Air Handling Units WARNING WARNING RL SERIES Packaged Rooftop Units & Outdoor Air Handling Units Installation, Operation, & Maintenance WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury,

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating Rooftop Ventilator with Packaged Cooling & Heating Models RV and RVE Institutional Commercial Industrial 800-1,500 cfm.0 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating Packaged

More information

From 230 tons to. Water-Source Heat Pump Products. Premium Performance Environmentally Friendly Superior Construction

From 230 tons to. Water-Source Heat Pump Products. Premium Performance Environmentally Friendly Superior Construction From 230 tons to Water-Source eat Pump Products Premium Performance Environmentally Friendly Superior Construction Water-Source eat Pump Products Small Packaged Water-Source eat Pumps (1/2 to 30 tons)

More information

SA SERIES. Installation, Operation & Maintenance. Vertical Self-Contained Units and Indoor Air Handling Units WARNING WARNING WARNING

SA SERIES. Installation, Operation & Maintenance. Vertical Self-Contained Units and Indoor Air Handling Units WARNING WARNING WARNING Vertical Self-Contained Units and Indoor Air Handling Units SA SERIES Installation, Operation & Maintenance QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can

More information

CB/CF. Series CONDENSERS AND CONDENSING UNITS. Features:

CB/CF. Series CONDENSERS AND CONDENSING UNITS. Features: CB/CF CONDENSERS AND CONDENSING UNITS CF CB Features: 2-70 ton air-cooled condensing units and remote air-cooled condensers Air-source heat pump configurations for energy efficient heating Variable capacity

More information

VariCool VAV Engineering Guide

VariCool VAV Engineering Guide Engineering Guide Effective September 2017 Water-Cooled and Chilled Water, Variable Air Volume Contents Product Features... 3 UNIT FEATURES... 3 Product Features... 4 Marvel Plus Microprocessor Control

More information

Modular Heating & Ventilating Unit Model IGX-HV

Modular Heating & Ventilating Unit Model IGX-HV Modular Heating & Ventilating Unit Model IGX-HV Indirect Gas-Fired Heating Evaporative Chilled Water DX Cooling October 2008 Product Features Model IGX-HV Indirect Gas-Fired Heating and Ventilating Unit

More information

Heat Pumps SB SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (3-18 tons) Features:

Heat Pumps SB SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (3-18 tons) Features: Heat Pumps SB SERIES Features: Vertical self-contained units with capacities from 3-18 tons ECM driven direct drive backward curved plenum supply fans for improved energy Double wall rigid polyurethane

More information

Modular Supply Make-Up Air Unit

Modular Supply Make-Up Air Unit Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features

More information

M2 Series. Installation, Operation & Maintenance. Modular Indoor Air Handling Units & Self-Contained Units WARNING WARNING FIRE OR EXPLOSION HAZARD

M2 Series. Installation, Operation & Maintenance. Modular Indoor Air Handling Units & Self-Contained Units WARNING WARNING FIRE OR EXPLOSION HAZARD M2 Series Modular Indoor Air Handling Units & Self-Contained Units Installation, Operation & Maintenance WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious

More information

SB Series. Installation, Operation & Maintenance. Vertical Self-Contained Units WARNING WARNING

SB Series. Installation, Operation & Maintenance. Vertical Self-Contained Units WARNING WARNING SB Series Vertical Self-Contained Units Installation, Operation & Maintenance QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal

More information

VCM-X Controller Technical Guide

VCM-X Controller Technical Guide 2 2 www.orioncontrols.com VCM-X Controller Technical Guide VCM-X Controller Code: SS1026 & Y200920 Version 2.0 and up; VCM-X Modular Controller: Tulsa - SS1030; Coil - SS1034 VCM-X WSHP Controller: Tulsa

More information

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

RT-OA TM Rooftop Outdoor-Air (DOAS)

RT-OA TM Rooftop Outdoor-Air (DOAS) RT-OA TM Rooftop Outdoor-Air (DOAS) A/C s & HEAT PUMPS Dedicated Outside-Air System (DOAS) Solutions Office Buildings, Schools, Hospitals, Restaurants, Gyms & Fitness Centers, Hotels, Retail Stores...!

More information

Daytona Beach Pier Building Renovation Jun 2010 SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

Daytona Beach Pier Building Renovation Jun 2010 SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 15732 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

62DA,DB,DC,DD,DE,DF07-38

62DA,DB,DC,DD,DE,DF07-38 62D-3SB 62DA,DB,DC,DD,DE,DF07-38 DEDICATED VERTICAL OR HORIZONTAL 100% OUTDOOR AIR UNIT PERFORMANCE DATA UNIT DIMENSION PRINTS ACCESSORY DIMENSION PRINTS Copyright 2011 Carrier Corporation Syracuse, New

More information

FEATURES AND BENEFITS

FEATURES AND BENEFITS FEATURES AND BENEFITS Product Features and Benefits Full Product Line Offering Feature All models are 80% thermally efficient Blower performance up to 3.0 W.C. DX or chilled water section with factory

More information

CONDENSERS AND CONDENSING UNITS

CONDENSERS AND CONDENSING UNITS CONDENSERS AND CONDENSING UNITS CF Series Features: 2-70 ton air-cooled condensing units and remote air-cooled condensers Air-source heat pump configurations for energy efficient heating Variable capacity

More information

Multi-Path RTU-TYPE 2

Multi-Path RTU-TYPE 2 ALDI # CITY, STATE SUPERMARKET MultiPath RTUTYPE 2 (RTU1) CESMPU025RHVAV2 Date: February 17, 201 2013 Consolidated Energy Solutions, Inc. UNIT FEATURES CES TYPE VAV2 Unit features include: 25 Ton MultiPath

More information

Your Home. Jacco & Assoc.

Your Home. Jacco & Assoc. Your Home Fan on with call for heating or cooling Heating on with call from space thermostat Stage as required to maintain The 75F Basics adj. - First stage of heating shall be heat pump Cooling on with

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Gas-Fired Indoor and Outdoor Duct Furnaces

Gas-Fired Indoor and Outdoor Duct Furnaces July, 2008 Gas-Fired Indoor and Outdoor Duct Furnaces INDOOR GRAVITY VENTED DFG, DBG, DCG INDOOR SEPARATED COMBUSTION DFS, DBS, DCS OUTDOOR GRAVITY AND POWER EXHAUSTED H Series table of contents A complete

More information

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump VertiCool CLASSIC Engineering Guide Effective March 2018 Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump Contents Product Features... 3 UNIT FEATURES... 3 OPTIONS:... 3 Physical Data...

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Best Practices for Applied Rooftop ` Systems - Application and. Jerry Cohen President Jacco & Assoc. Installation

Best Practices for Applied Rooftop ` Systems - Application and. Jerry Cohen President Jacco & Assoc. Installation Best Practices for Applied Rooftop ` Systems - Application and Jerry Cohen President Jacco & Assoc. Installation Who is Jacco Established 1968 Hudson, Ohio Columbus, Ohio Toledo, Ohio Systems Knowledgeable

More information

Water-Cooled Self-Contained Units

Water-Cooled Self-Contained Units CATALOG FORM SK145.15-EG1 (1017) Water-Cooled Self-Contained Units C-Series, Vertical Nomenclature WATER-COOLED SELF-CONTAINED UNIT 1, 2 3 4, 5, 6 7 8 9 10 11 12 13 14 15 16 17 CS V 180 B 2 M 1 V A A A

More information

Mission Critical. Series 6, 8 & 9. vertical floor mount Ton Units. Air Conditioning Systems

Mission Critical. Series 6, 8 & 9. vertical floor mount Ton Units. Air Conditioning Systems Mission Critical Air Conditioning Systems vertical floor mount Series 6, 8 & 9 2-30 Ton Units Single Circuit for Superior Economy and Dual Circuit for Ultimate Protection Series 6 2-5 tons Compact Footprint

More information

Bring the fresh in. D E D I C A T E D O U T S I D E A I R S Y S T E M

Bring the fresh in. D E D I C A T E D O U T S I D E A I R S Y S T E M Bring the fresh in. D E D I C AT E D O U T S I D E A I R S Y S T E M Breathe easier. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting

More information

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled FORM 145.05-EG1 (1004) VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU 10 105 Ton Water-Cooled Table of Contents FORM 145.05-EG1 (0804) Features and Benefits.....................................................

More information

Best Practices for Applied Rooftop ` Systems, Applications and. Jerry Cohen President Jacco & Assoc. Installation

Best Practices for Applied Rooftop ` Systems, Applications and. Jerry Cohen President Jacco & Assoc. Installation Best Practices for Applied Rooftop ` Systems, Applications and Jerry Cohen President Jacco & Assoc. Installation Established 1968 Hudson, Ohio Columbus, Ohio Toledo, Ohio Focused on the Engineered Environment

More information

Tulsa, OK Longview, TX

Tulsa, OK Longview, TX Tulsa, OK Longview, TX An Overview, presented by: Custom Air & Power Официальный дистрибьютор в России - Компания ООО «Альфа Инвест Инжиниринг» 109052, г.москва, ул. Нижегородская, д. 50 Сайт: www.ai-engineering.ru

More information

C13-Series Engineering Guide

C13-Series Engineering Guide Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................

More information

Direct Gas-Fired Make-Up Air Models DG and DGX

Direct Gas-Fired Make-Up Air Models DG and DGX Direct Gas-Fired Make-Up Air Models DG and DGX Commercial, Industrial and Kitchen Applications 800-48,000 cfm 4 in. wg External Static Pressure Direct Gas-Fired Heating Optional Cooling - Packaged DX (2.5

More information

THE RIGHT SPEC. RIGHT NOW.

THE RIGHT SPEC. RIGHT NOW. THE RIGHT SPEC. RIGHT NOW. 6-12.5 TONS R7DA Gas/Electric Packaged DOAS System MADE FOR THOSE WHO RESPECT THE SPEC. Reznor light commercial packaged rooftops are highly configurable at the factory, so consultant

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

Architecture - Engineering - Planning

Architecture - Engineering - Planning Architecture - Engineering - Planning www.mkcinc.com Mansfield, Ohio New Philadelphia, Ohio Powell, Ohio 9-55-0 - phone 0-6-887 - phone 70-657-0 - phone 9-55-8 - fax 0--075 - fax 70-657-77 - fax SHOP DRAWING

More information

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical ENGINEERING GUIDE Water-Cooled Self-Contained Units C-Series, Vertical TABLE OF CONTENTS Introduction...2 Product Overview...3 Nomenclature...4 General Data...5 Cooling Performance Data....6 Evaporator

More information

Energy Recovery with Cooling and Heating Model ERCH

Energy Recovery with Cooling and Heating Model ERCH Energy Recovery with Cooling and Heating Model ERCH 100% Outdoor Air System Dedicated Outdoor Air System 1,000-10,000 cfm 1.75 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating,

More information

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges. Service Literature The LGH/LCH high and standard efficiency 5, 0, 5 and 50 ton (, 0.7, 58. and 75.9 kw) units, are configure to order units (CTO) with a wide selection of factory installed options. The

More information

VCM-X Modular E-BUS Controller Technical Guide

VCM-X Modular E-BUS Controller Technical Guide www.orioncontrols.com VCM-X Modular E-BUS Controller Technical Guide VCM-X Modular E-BUS Controller: Tulsa - SS1030; Coil - SS1034 VCM-X WSHP E-BUS Controller: Tulsa - SS1032; Coil - SS1033 Requires Service

More information

Direct Gas-Fired Make-Up Air Models DGK, DG and DGX

Direct Gas-Fired Make-Up Air Models DGK, DG and DGX Direct Gas-Fired Make-Up Air Models DGK, DG and DGX Kitchen and Industrial Applications 800-48,000 cfm 4 in. wg External Static Pressure Direct Gas-Fired Heating Packaged DX (3 to 16 tons), Split DX Cooling,

More information

LC Series Chillers. Engineering Catalog. Air-Cooled Condenser

LC Series Chillers. Engineering Catalog. Air-Cooled Condenser LC Series Chillers Engineering Catalog Air-Cooled Condenser Table of Contents Features and Benefits... 5 Application Information... 7 Unit Selection... 11 Evaporator Pressure Drops... 14 LC Base Model

More information

Product Data. 75 to 150 Nominal Tons

Product Data. 75 to 150 Nominal Tons Product Data WeatherExpert 48/50N2,N3,N4,N5,N6,N7,N8,N9 Packaged Rooftop Cooling Units with Gas Heat, Optional Electric Heat, or Hydronic Heat and ComfortLink Controls 75 to 150 Nominal Tons WeatherExpert

More information

TYPICAL CPA SPECIFICATIONS

TYPICAL CPA SPECIFICATIONS TYPICAL CPA SPECIFICATIONS 4/10/2017 UNIT CONSTRUCTION: Casing: The exterior casing of the unit shall be constructed of 18-gauge, G235 galvanized steel (optional stainless steel or aluminum), unpainted.

More information

Data Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified

Data Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified Data Aire LCS TM (Large Ceiling System) 6, 8, 10, and 13 ton ISO 9001 Certified LCS TM (LARGE CEILING SYSTEMS) DX Product Description Performance and Electrical Data 3 the pioneer and builder of the most

More information

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost LL Chillers and Outdoor Mechanical Rooms Air-Cooled Features: Air-cooled condenser chillers with capacities from 35-345 tons Evaporative-cooled condenser chillers with capacities from 35-540 tons Variable

More information

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL PREPARED FOR: DATE: JOB NAME: WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL EQUIPMENT DETAILS ITEM TAG DESCRIPTION MODEL NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 EQUIPMENT

More information

PACKAGED HVAC EQUIPMENT CATALOG

PACKAGED HVAC EQUIPMENT CATALOG PACKAGED HVAC EQUIPMENT CATALOG COMMERCIAL/INDUSTRIAL HVAC CAPACITIES 5-70 Tons Cooling (Fixed and Modulating Capacity) Dehumidification 1,000-13,000 CFM 100-1,600 MBH (Gas Heating) 8:1 or 16:1 Gas Heating

More information

Product Catalog. Horizon Outdoor Air Unit Water Source Heat Pump For 100% Outdoor Air Applications Models: OABE, OADE, OAGE, OAKE, OANE OAU-PRC003C-EN

Product Catalog. Horizon Outdoor Air Unit Water Source Heat Pump For 100% Outdoor Air Applications Models: OABE, OADE, OAGE, OAKE, OANE OAU-PRC003C-EN Product Catalog Horizon Outdoor Air Unit Water Source Heat Pump For 100% Outdoor Air Applications Models: OABE, OADE, OAGE, OAKE, OANE March 2016 OAU-PRC003C-EN Introduction The Horizon Outdoor Air Unit

More information

EP Model. EP Model Water Source Heat Pump. ½ to 6 Ton

EP Model. EP Model Water Source Heat Pump. ½ to 6 Ton EP Water Source Heat Pump ½ to 6 Ton Industry-leading single-stage efficiencies, standard features, and a variety of options - providing energy efficient solutions to accommodate your building requirements.

More information

RT-OA TM Rooftop Outdoor-Air (DOAS)

RT-OA TM Rooftop Outdoor-Air (DOAS) RT-OA TM Rooftop Outdoor-Air (DOAS) A/C s & HEAT PUMPS (DX - Air Source Data) Dedicated Outside-Air System (DOAS) Solutions Office Buildings, Schools, Hospitals, Restaurants, Gyms & Fitness Centers, Hotels,

More information

HVAC Mandatory Provisions Part II, Page 1

HVAC Mandatory Provisions Part II, Page 1 HVAC Mandatory Provisions Part II, Page 1 Mandatory Equipment Efficiency Worksheet (6.4.1.1) System Equipment Type Size Category (Tables 6.8.1A through K) Sub-Category or Rating Condition Units of Efficiency

More information

technical guide Water-Cooled Self-Contained Units

technical guide Water-Cooled Self-Contained Units technical guide Water-Cooled Self-Contained Units C-Series, Vertical Technical Guide: YK145.00-EG3 (710) TABLE OF CONTENTS Water-Cooled Self-Contained Units Introduction...............................................................................

More information

Greensource Residential Water Source Heat Pumps. Simply Smart. i Series: SV Model. boschheatingandcooling.com

Greensource Residential Water Source Heat Pumps. Simply Smart. i Series: SV Model. boschheatingandcooling.com Greensource Residential Water Source Heat Pumps i Series: SV Model Simply Smart The i Series SV Model is a cost-effective single stage water source heat pump that is designed for commercial retrofit and

More information

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A ISO 9001 Certified Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

BOOK 2 SPECIFICATIONS

BOOK 2 SPECIFICATIONS 4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XIN INSTALLATION AND OPERATION MANUAL BOOK 2 SPECIFICATIONS This book provides

More information

Mini-Space EC DX and CW 4 12 kw Systems Vertical Floor Mounted, 60 Hz Data

Mini-Space EC DX and CW 4 12 kw Systems Vertical Floor Mounted, 60 Hz Data Mini-Space EC DX and CW 4 12 kw Systems Vertical Floor Mounted, 60 Hz Data Engineering Manual ABOUT STULZ STULZ is a privately owned, global manufacturer of highly efficient temperature and humidity management

More information

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps Product Data OMNIZONE 50BV020-064 Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps 18 to 60 Nominal Tons omnizonebwlogo 50BVC,E,J,K,Q020-034 SINGLE PIECE OMNIZONE

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL The Kitchen Cool by Hood Depot is a conditioned make up air unit design with flexibility, form and function kept in mind. Our unit offers a variety of configurations that allow the customer to customize

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

Cultivator & Hybrid Cultivator

Cultivator & Hybrid Cultivator Cultivator & Hybrid Cultivator Precision Temperature & Humidity Packaged Unit INTRODUCTION The Cultivator Series package unit is the industry s MOST ENERGY EFFICIENT and HIGHEST capacity dehumidifier on

More information

Product Data. Features/Benefits. 62DA,DB,DC,DD,DE,DF07-38 Dedicated Vertical or Horizontal Outdoor Air Unit with Optional Energy Wheel

Product Data. Features/Benefits. 62DA,DB,DC,DD,DE,DF07-38 Dedicated Vertical or Horizontal Outdoor Air Unit with Optional Energy Wheel Product Data 62DA,DB,DC,DD,DE,DF07-38 Dedicated Vertical or Horizontal Outdoor Air Unit with Optional Energy heel 6 to 35 Nominal Tons a62-393 a62-394 a62-395 62D07-09 62D12-20 Carrier s 62D Series commercial

More information

The ultimate fresh air solution.

The ultimate fresh air solution. Fresh Access The ultimate fresh air solution. Introducing Fresh Access TM. Expertly designed, our innovative energy recovery ventilator (ERV) unit, split dedicated outside air system (DOAS), and packaged

More information

Chilled Water DOAS Fan Powered Terminal Units

Chilled Water DOAS Fan Powered Terminal Units Chilled Water DOAS Fan Powered Terminal Units CHILLED WATER DOAS FAN POWERED TERMINAL UNITS DOAS TERMINAL UNITS FEATURES AND BENEFITS MINIMUM VENTILATION CONTROL The DOAS unit provides the Designer, Owner

More information

Product Catalog. Horizon Outdoor Air Unit For 100% Outdoor Air Applications Model: OADG OAU-PRC004A-EN. November 2017

Product Catalog. Horizon Outdoor Air Unit For 100% Outdoor Air Applications Model: OADG OAU-PRC004A-EN. November 2017 Product Catalog Horizon Outdoor Air Unit For 100% Outdoor Air Applications Model: OADG November 2017 OAU-PRC004A-EN Introduction The Horizon Outdoor Air Unit... The Trane DX Horizon Outdoor Air Unit for

More information

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data July 28, 2008 Page 1 1 of 3 PROJECT: TAG: Gross Cooling Capacity [Btuh]: 37,800* Design CFM: 1,200 Seasonal

More information

Vertical self-contained air conditioner

Vertical self-contained air conditioner Compact and sleek Broad range of functions and performance Energy efficient (EC motor) and self-regulating control Easy to install ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY L'ENVIRONNEMENT Cooling

More information

INDOOR/ OUTDOOR SPLIT SYSTEM HVAC CATALOG

INDOOR/ OUTDOOR SPLIT SYSTEM HVAC CATALOG INDOOR/ OUTDOOR SPLIT SYSTEM HVAC CATALOG COMMERCIAL/INDUSTRIAL AIR HANDLER AND CONDENSING UNIT AIR HANDLER CAPACITIES 563-7,593 CFM Air 20-400 MBH Heating (Gas/LP) 10-120 kw Heating (Electric) 5-20 Tons

More information

CF Series. Installation, Operation, & Maintenance. Condenser and Condensing Units WARNING

CF Series. Installation, Operation, & Maintenance. Condenser and Condensing Units WARNING CF Series Condenser and Condensing Units Installation, Operation, & Maintenance WARNING If the information in this manual is not followed exactly, a fire or explosion may result causing property damage,

More information