Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans
|
|
- Anissa Norton
- 6 years ago
- Views:
Transcription
1 Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans A look at two accepted technologies..
2 System Characteristics In general, the pressure developed by a fan is a function of the impeller tip speed. The tip speed is a product of the impeller diameter and fan speed. With Varofoil Controllable Pitch in Motion (VPIM) fans, the tip speed is constant. Fans with variable speed control lose pressure capability as a square of the ratio of speed reduction. The If a relatively high fixed pressure system requirement component in a Variable Air Volume System is required, the VPIM fan can provided stable performance down to zero, or near-zero flow if necessary. Speedcontrolled fans can lose stability at low volume flows if fixed pressure components, such as VAV boxes are present in the system. VFD control can also cause problems with motor overheating at very low (10-15% of full) speeds and should not be attempted without coordination with both VFD and motor supplier. Often, special motors with auxiliary cooling means are required. Additionally, VFD use can cause premature bearing failures due to shaft currents set up by electronic harmonics. Special shaft grounding and bearing isolation may be required. Figure 1, VPIM Control result is that the Varofoil VPIM fan retains a high portion of its pressure development over its entire range whereas the speedcontrolled fan loses pressure faster than it loses speed. The illustrations show the effect of speed reduction on fan performance. Figure 2, VFD Control Although a majority of projects do not need a volume lower than that produced on the stable part of the fan curve, it is essential that the minimum flow required be checked against the fan performance, to avoid low duty problems after installation. Noise The noise from a speed-controlled fan reduces as the fan speed reduces. This variation in noise level can make it more noticeable. A Varofoil fan varies its air and motor noise by only a small amount (typically 3 db) across its entire range and the constant level can make it more acceptable compared to a fluctuating noise level. The motor noise from an inverter-controlled fan can be excessive due to harmonics created by the wave chopping which can be amplified and radiated by the structure of the fan. This can be a discrete pure tone, which is particularly noticeable and difficult to remove or attenuate. Some more recent invertors use higher pulse rates and the harmonicas are above the human ear audio
3 range, but not above the range of certain animals (i.e., dogs). If part of the fan has a natural frequency in sympathy with the harmonic frequency, it could resonate, generating additional noise problems. Silencers in a system are designed to reduce the maximum fan noise level and therefore are suitable for both VPIM and VFDcontrolled fans, but may not be capable of attenuating particular discrete frequencies generated in the motor by the VFD. Vibration All fans are suitably balanced at their maximum rotational speed. However, all machines have a natural resonance frequency where damage could occur if the fan is left at that frequency. When a fixed speed fan is started, it is often noticed that, at one point during acceleration the fan vibrates considerably. This is the fan s natural frequency and the phenomenon applies to all types of fans. The Varofoil VPIM fan runs at a fixed speed and can experience this natural frequency only when starting or stopping. A variable speed fan may be cycled into and out of its natural frequency often, and damage could occur. Some VFD manufacturers have acknowledged this problem and incorporate into their programming one or two bands of operating frequencies that can be omitted. This means, for example that the operating frequency could jump from say 23 Hz to 25 Hz, if the fan s natural frequency is 24 Hz, thus avoiding damage. The only drawback to this is that if the system actually requires operation at 24 Hz, the control may oscillate between 24 Hz and 25 Hz, possibly causing instability in the system. Electrical System Effects (in Cables) The Varofoil Fan produces no adverse harmonic effects. Invertors can draw harmonic currents from the electrical supply. It is essential that these harmonics be reduced below a level at the common point of coupling, ie, at the point where the building electrical supply joins the buss feeding the adjacent buildings. Local Code will indicate the maximum level and power companies have made them mandatory. It has been necessary to upgrade some invertors on site to reduce this effect at considerable extra cost. Interference There are no radio frequency interference problems with the Varofoil fan. The high switching frequency in cables from the invertors to the motor on VFD-controlled fans can cause a malfunction in other equipment or radio frequency problems to other users, if not adequately screened. For example, some sensitive military areas ban all invertors due to radio frequency interference. The recommendations of the invertor supplier must be carefully followed, noting that these vary to suit different invertor designs and suppliers. VPIM Impeller Peak Power With Varofoil fans, the peak shaft power is as shown on the curve and in the catalog, together with absorbed power. The peak power is the maximum absorbed power at any point on the fan curve, irrespective of the system duty. Backward curved centrifugal fans, mixed flow fans and all axial fans have non-overloading characteristics That means that, no matter at
4 what point the system curve crosses the fan curve, the motor will not draw more than the peak power for which it was selected. Forward-curved centrifugal fans experience their peak power at maximum volume/zero pressure. For commercial reasons, motors are normally selected for the required operating area of the fan curve and not for the peak power. If all the dampers in a system served by a forward-curved fan were opened to reduce system resistance, the motor may overload and fail. Centrifugal fans are normally belt-driven and belt losses must be included when comparing with direct-drive fans. Direct drive axial flow fan motors are normally airstream-rated (TEAO) enabling more power to be drawn from a smaller motor frame because of additional cooling by the fan s airstream. The net result of these factors is that VFDcontrolled fans experience extra losses at high duties, compared to VPIM fans at the same shaft horsepower. Starting VFD controlled fans, supplied with starter contacts provide an inherently soft start. That is, they start at zero speed and slowly increase speed to the duty required by the control system. Typically, the maximum current drawn is the full-load current. Care should be taken that the invertor/starter is suitable to start the fan against idling rotation, and not just from a standing start. Larger VPIM fans provide larger opportunity for energy savings Varofoil fans are driven by constant speed motors. At lower power (say, up to 20 HP) across-the-line starting can be used without creating too large a voltage drop in the power supply. Above that point, wye/delta starting can be incorporated to reduce the starting current to about one third. Wye /delta starting and auto-transforming starting have been successfully used for many years. The Varofoil fan can have its controls set so that the fan starts and runs up to full speed at minimum blade angle. The controls can then increase blade angle to that required by the system. While this will not decrease the starting current level, it will decrease the length of time that the current is present, because the fan will reach speed faster. An additional benefit is that the motor will experience less heating, extending the life of the insulation system. Low Blade angle cannot be used to reduce cable sizes or overload protection, because it is possible to start the fan with the pitch set to maximum angle. Protection Conventional overload protection in starters, either current sensing or temperature sensing can be used with the Varofoil fan. With VFD drives, complex protection circuits may be needed for the safety of electronic circuits and system power devices. These are normally included in the VFD package, but purchasers must not assume that adequate protection is always provided. Any motor can have either thermistors or thermostats incorporated in the motor winding for overload protection. As a point of interest, if fans are being installed for emergency use, i.e., as smoke exhaust fans,
5 care must be taken that the overload devices are bypassed in the event of an emergency, so that the fan will run throughout the emergency. This applies to VFD protection devices and programming as well. Maintenance Invertors are solid-state electronic device that require minimal maintenance. However, should anything go wrong, it is best to call a specialist to correct the problem. Varofoil fans are mechanical devices, which require regular inspection and limited maintenance. When required, maintenance is provided by the user s own maintenance engineer and does not rely on expensive external personnel. With the Varofoil, service is limited to lubrication of motor bearings (as with VFD-driven units) and checking for smooth operation. Overhaul, i.e. replacement of worn parts, may be required after a long period of service. Reliability Varofoil fans have been installed and operate satisfactorily in over 20,000 systems around the world since their introduction in Overhaul is limited to a time when the mechanism becomes balky, as seen on a 3- month inspection schedule and involves replacing some simple parts, with a down time of no more than 2 or 3 hours. Time-to- Overhaul depends on use, but even with continuous operation, the service interval for 1800 RPM units should be not less than 5 years and could be considerably longer depending on the actual service conditions. VFD controlled fans have been a fact in HVAC installation for many years. The units are quite reliable, with the only area of VFD-Controlled Fan doubt involving the effect of electrical system effects on the motors. Shaft currents induced by harmonic effects can go to ground through the motor bearings and cause premature failure unless protective features are installed in the motor. Installation VPIM fans are limited to the axial type. Invertors can be used on any type of fan, as long as the motor is VFD Compatible. Space needs to be allocated in the area near the fan for the invertors, frequently in a ventilated panel. Smaller VFD units are freestanding, but care must be taken to ensure that they have adequate cooling ventilation. If the distance between the fan motor and VFD exceeds 150 feet, a voltage spike can be generated that may damage the motor winding and power wiring. Retrofit The VPIM impeller cannot be fitted to existing axial fans. A complete new fan is required. Existing fans can be VFDcontrolled, but only if the motor is VFDcompatible. Frequency Boost A VPIM fan can run only at it s motor s synchronous speed, minus any slip. If more performance is required, blade pitch can be increased if the motor has adequate additional power available. An invertordriven fan can be run at increased speed, provided the motor is sized for the additional load and suitable for the overspeed operation. Power Factor With inverter-driven fans, power factor is near unity at all speeds. VPIM fans use a standard squirrel-cage induction motor with power factors ranging from 0.7 to 0.9. If
6 higher power factors are required, power factor capacitors can be provided. Capital Costs These costs are often difficult to compare. Fan, Motor and VFD prices vary with market segment and geography. Also, the state of the economy at the time of purchase may depress or inflate prices. As a general rule, VFD-driven fans tend to be cheaper than VPIM fans for installations with less than 15 HP. Energy Savings Each project is unique and it is necessary to do an individual energy evaluation for each situation. The first task in that is to determine the overall duty profile throughout the year. A typical profile may well indicate that a variable flow fan will operate at 100% duty for only 5% of the time and 10% duty 5% of the time and may run the majority of the remainder at 70% duty. Once this profile has been derived the input duty for each of the comparative systems should be assessed and the total input power be determined. Note that with VFD-driven fan, the power delivered to the VFD, rather than to the fan motor should be measured. With the VPIM Fan, the input power is the power to the fan motor. As the load on the VPIM fan is reduced, the blade angle decreases and the motor becomes less efficient. This should be allowed for in the energy calculation. The efficiency of motors operating at reduced loads is sometimes difficult to obtain from Varofoil Fan, showing control attachment at hub motor manufacturers. Losses in the inverter itself (VFD s show this inefficiency as heat) and belt losses in belt-driven fans also need to be included. Taking these factors into account, it is generally accepted that there is greater power savings with the VPIM fan at maximum duty and greater power savings with the VFD-controlled fan at minimum duty. The crossover point varies with the individual fan selected, but is considered to be between 60% and 70% of maximum duty. In other words, if a fan is to run at maximum duty the majority of the time, the VPIM fan will be the more energy-efficient choice. Generally, the energy consumption differences at lower duties, in actual HP, is less than at higher duties. However, if this is critical, a two-speed motor can be used in the VPIM fan to give better energy saving. The fan can be run at the appropriate motor speed, i.e. high speed for summer duty and low speed for winter duty. Summary Although the size and types of fans available from American Fan/Flaktwoods spans the entire range of centrifugal and axial fans and includes all means of flow control, our experience indicates that the Varofoil VPIM fan has many advantages over the other types and should be considered by all variable air system designers.
Selecting the Correct Fan
Selecting the Correct Fan Ryan B. Johnson Air Purification Company Sales Engineer Member, ASHRAE Pikes Peak Chapter rjohnson@airpurificationcompany.com 1 Your Speaker circa 1998 Fan Types Applications
More informationCOMMERCIAL HVAC AIR-HANDLING EQUIPMENT. Fans in VAV Systems
COMMERCIAL HVAC AIR-HANDLING EQUIPMENT Fans in VAV Systems Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.
More informationIntroduction to Fans. The Basics of Fan Principles and Terminology
Introduction to Fans The Basics of Fan Principles and Terminology Airflow Principles A fan is a rotating device that creates pressure differential that results in air movement Pressure rise in a fan Downstream
More informationFans: Features and Analysis
Technical Development Program COMMERCIAL HVAC EQUIPMENT Fans: Features and Analysis PRESENTED BY: Michael Ho Version 1.2 Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Section
More informationInternal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.
A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall
More informationDirect Fired Heater Model AD Specification
Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI
More informationSPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS
SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification
More informationWash and Clean By Michael Rasmussen, Industry application team, Grundfos, Denmark
Wash and Clean By Michael Rasmussen, Industry application team, Grundfos, Denmark Introduction Wash & Clean systems for the food processing industry is an utility application that sets high requirements
More informationDucted Propeller. Airflow Volume
Total Pressure Radial-Blade Centrifugal Tubeaxial Backward-inclined Airfoil Centrifugal Forward-curved Centrifugal Ducted Propeller Airflow Volume Figure 2: Forward-Curved Centrifugal Fan
More informationFan Selection. and Energy Savings
Fan Selection and Energy Savings Reducing power consumption by minimizing system pressure loss and choosing the right equipment HBy BRIAN MLEZIVA Greenheck Fan Corp. Schofield, Wis. Power Consumption HVAC
More informationFAN ENGINEERING. Surge, Stall and Instabilities in Fans
FAN ENGINEERING Industrial Fans & Services Information and Recommendations for the Engineer Surge, Stall and Instabilities in Fans Introduction Users of fan systems would like to experience a steady, continuous
More informationConstruction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA
Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified
More informationECO-ANT21 Corporation
ANT Turbo blower - Summary Turbo Blower is a device generating compressed air using an applied air bearing, impeller, high speed motor, inverter and controller connected to a robust centrifugal turbine
More informationmore than just a fan supplier more than just a fan supplier Axair Fans UK Limited
1 more than just a fan supplier The most diverse range of industrial fans & accessories available from a single source... 2 products oem & industrial 3 single inlet centrifugal backward curved centrifugal
More informationPumps SELECTION OF A PUMP
Pumps SELECTION OF A PUMP A water system needs to move the water produced from the source to its customers. In almost all cases in Minnesota, the source is at a lower elevation than the user so the water
More informationEC Plug Fans EC FanGrid Retrofits for High Efficiency Air Handling Units
GET A GRID ON EC Plug Fans EC FanGrid Retrofits for High Efficiency Air Handling Units EC Plug Fans for HVAC Efficiency Using an EC FanGrid Continuous and consistent airflow is essential to virtually every
More informationHow to Cut Chiller Energy Costs by 30%
How to Cut Chiller Energy Costs by 30% Pre-packaged retrofit cuts centrifugal compressor chiller energy costs by 30% while reducing required maintenance and extending operating life at Duke Realty Corporation
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating
More informationFAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design
FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design Fan motor (PSC or ECM). UL Listed 1 insulation conforms to UL Test 181 and NFPA 90A. Plenum air filter rack. (Filter Optional) Casing has
More informationGlossary of Terms Laboratory & Fume Exhaust Fans
Glossary of Terms Laboratory & Fume Exhaust Fans ACTUATOR, 2-POSITION SPRING RETURN A spring return actuator generally used to control the isolation dampers below the fans. This actuator allows for fully
More informationHigh Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)
High Plume Blowers Suggested Specification Section 15500 (Master Format 1996) Suggested Specification Section 23 38 16 (Master Format 2004) PART 1 GENERAL 1.01 WORK INCLUDED High Plume Laboratory Exhaust
More informationDAE Systems. Fan Selection Guide. Section 1: Terminology
DAE Systems Fan Selection Guide Section 1: Terminology CFM : Cubic Feet per Minute Technical Terms This refers to the amount of air a fan is able to move. Pressure Inches of water is a common method of
More informationLow-noise fans are not a product of chance
Press News Quiet blowers with inner qualities Low-noise fans are not a product of chance Noise put out by machines can be annoying, especially in those areas that really require a quiet environment. For
More informationEnergy Conservation with PARAG Energy Efficient Axial Flow FRP Fans
PARAG FANS & COOLING SYSTEMS LTD. Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans Registered Office & Works Plot No.1/2B & 1B/3A, Industrial Area No.1 A.B.Road, Dewas 455001 (M.P.)
More informationStulz CyberMOD EC Fan Retrofit Kit Switch & Save
Stulz CyberMOD EC Fan Retrofit Kit Switch & Save Stulz CyberMOD Provides significant op-ex energy savings Reduces an existing data center s carbon footprint Improves a data center s reliability with fan
More informationCopy Right By: Thomas T.S. Wan
Chapter 23 Motor and Starter Copy Right By: Thomas T.S. Wan 温到祥著 Sept. 3, 2008 All rights reserved Electric Motors All the motors are to be designed and constructed in accordance with NEMA code. Electric
More informationCONTENTS. B. System Design and Performance Requirements
15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes
More informationEnergy Guide. Fan Efficiency Grades. FEG Ratings. July
Energy Guide Fan Efficiency Grades s July 2013 Certified Fans Location Mounting Airflow Application Drive Type Impeller Type Performance Model Outdoor Indoor Roof Curb Base/Floor Hanging Wall Ceiling Mounted
More informationPFS Single stage axial fan The axial fan for modern boiler plants
PFS Single stage axial fan The axial fan for modern boiler plants This large axial fan, type PFS- 400-236, was installed in 1987 at the Salmisaari coal-fired power station in Helsinki, Finland. The photo
More informationKERONE (AN ISO 9001: 2008 CERTIFIED COMPANY)
KERONE (AN ISO 9001: 2008 CERTIFIED COMPANY) Role of Agriculture and Allied Sector in Indian Economy Largest economic sector, plays a significant role in socio-economic development of India. More than
More informationINSTALLATION, OPERATION & MAINTENANCE MANUAL
CENTRAL FANS COLASIT LTD Unit 12A, Palmers Road, East Moons Moat, Redditch. Worcs. B98 0RF Tel: 01527-517200 Fax: 01527-517195 Edition 04_13 INSTALLATION, OPERATION & MAINTENANCE MANUAL CIV Fan Range Valid
More informationENGINEERING LETTER 4
ENGINEERING LETTER 4 The New York Blower Company 7660 Quincy Street, Willowbrook, Illinois 60521-5530 TEMPERATURE AND ALTITUDE AFFECT FAN SELECTION INTRODUCTION Fan performance changes with the density
More informationPractical Consideration of Noise from Fans
Practical Consideration of Noise from Fans Charles BURGESS 1 ; Rhys THOMPSON 2 1 AirEng, Australia 2 AirEng, Australia ABSTRACT Fan noise is often stated based on fan casing breakout alone, ignoring additional
More informationA. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:
SECTION 15860 - FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR MECHANICAL
More informationENERGY EFFICIENT RETROFITS. Date
ENERGY EFFICIENT RETROFITS Date CONTENT High Volume Low Speed Fan HVLS for Conditioned Space Air Handling Units Centrifugal Blower to BLDC EC fan Efficiency improvement of outdoor chillers Shade net for
More informationCentrifugal Fans, Non-Overloading, Backward Inclined
BACKWARD INCLINED CENTRIFUGAL FANS Centrifugal Fans, Non-Overloading, Backward Inclined MVA, MVZ, MVX & MVW Series with laminar blades MAVA, MAVZ & MAVX Series with aerofoil blades Features The combination
More informationwe make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)
we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) www.blowtech.in we make air move Blowtech Air Devices Pvt. Ltd. was founded in 1988 and quickly established
More informationModular Supply Make-Up Air Unit
Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features
More informationAerofoil Axial - Flow Fan www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions Part No.416421 CONTENTS Paragraphs Safety Introduction And Purpose 1 General 1.1 Storage
More informationDirect Gas-Fired Make-Up Air
Direct Gas-Fired Make-Up Air Model TSU Heavy Duty, High Airflow Applications Manufacturing and Industrial Facilities Up to 64,000 cfm August 2012 Products Model TSU Direct Gas-Fired Make-Up Air Unit The
More informationFAN WALL Technology. Product
FAN WALL Technology is a new approach to air handler design using an array of smaller fans to replace a traditional single large fan. FAN WALL Technology This is a fan-array approach to air handler design
More informationIndustrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation
Industrial Space Heating Direct Gas-Fired Heating Greenheat 00% Outdoor Air Greenheat 50/50 Recirculation 80/0 Recirculation March 008 Product Overview Industrial Space Heating Greenheck s space heating
More informationEXPERIMENTAL ACOUSTIC CHARACTERIZATION OF A WET VACUUM CLEANER
EXPERIMENTAL ACOUSTIC CHARACTERIZATION OF A WET VACUUM CLEANER Cinzia Buratti, Elisa Moretti and Michele Urbani Department of Industrial Engineering, University of Perugia, via G. Duranti 67, 06125 Perugia,
More informationModel LTN-3R Outdoor Rated Uninterruptible Power System Single Phase
Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics
More informationAXICO ANTI-STALL CONTROLLABLE PITCH-IN-MOTION AND ADJUSTABLE PITCH-AT-REST VANEAXIAL FANS
Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS AXICO ANTI-STALL CONTROLLABLE PITCH-IN-MOTION AND ADJUSTABLE PITCH-AT-REST VANEAXIAL FANS FPAC FPMC FPDA CATALOG AX351 JULY 2001 WWW.TCF.COM
More informationMidea VFD Centrifugal Chiller Technology
Midea VFD Centrifugal Chiller Technology Content Why VFD VFD centrifugal chiller technology Solution 2 HVAC major issues Energy conservation Global warming reduction 3 Why VFD No Compressor A/C Lower GWP
More informationARI 260 Standard: Sound Rating of Ducted Air Moving and Conditioning Equipment
Return to www.enoisecontrol.com ARI 260 Standard: Sound Rating of Ducted Air Moving and Conditioning Equipment Common Sources of Noise in Air Handling Equipment ASHRAE Seminar 51 Sponsored by TC 2.6 Michael
More informationVariable speed hydraulic coupling and drive unit of hydraulic coupling
Variable speed hydraulic coupling and drive unit of hydraulic coupling I. Model designation YO / / / Modificait on code Output speed of drive unit (r/min) Input speed of coupling or drive unit (r/min)
More informationSECTION DOMESTIC WATER PUMPS
SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,
More informationCENTRIFUGAL BLOWERS & FANS TM MITTAL ENGINEERING
CENTRIFUGAL BLOWERS & FANS TM MITTAL ENGINEERING TM MITTAL ENGINEERING M i t t a l E n g i n e e r i n g i s o n e o f t h e l e a d i n g m a n u f a c t u r e r s q u a l i t y e n g i n e e r i n g
More informationSECTION (15833) - HVAC POWER VENTILATORS
PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted
More informationHVAC Clinic. Helical Rotary & Centrifugal Water Chillers
HVAC Clinic Helical Rotary & Centrifugal Water Chillers Table Of Contents Introduction... 3 Chiller Types... 3 Chiller Components... 4 Refrigeration Cycle... 15 Application Considerations... 19 Introduction
More informationWater engineers and utilities are often
FWRJ Horizontal or Vertical? High-Service Pump Selection Mark Ludwigson, Len Rago, and Jeff Greenfield Water engineers and utilities are often faced with a decision concerning the best type of pump when
More informationSECTION FAN COIL UNITS
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.
More informationFan Motor. user manual INSTALLATION - OPERATION - MAINTENANCE
user manual Fan Motor INSTALLATION - OPERATION - MAINTENANCE Z0239042_B ISSUED 8/2017 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT installation Receiving Storing A motor
More informationSubmittal Data Performance Data Electrical Data
ERMS Series Submittal Data Submittal Data Unit Designation: Job name: Architect: Engineer: Contractor: Performance Data Revision: 07/01/11 Cooling Capacity: EER: Heating Capacity: COP: Ambient Air Temp:
More informationApplication Note. Technique description CPB measurements give early fault detection with minimal risk of false alarms
Application Note Technique description CPB measurements give early fault detection with minimal risk of false alarms Application Note Technique description CPB measurements give early fault detection with
More informationLGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.
Service Literature The LGH/LCH high and standard efficiency 5, 0, 5 and 50 ton (, 0.7, 58. and 75.9 kw) units, are configure to order units (CTO) with a wide selection of factory installed options. The
More informationATEX - Implications for manufacturers
ATEX - Implications for manufacturers 1. With the introduction of the ATEX Directives in 2003, mechanical equipment for use in hazardous areas will be subject to similar certification as now applies to
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS
PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Placement within a mechanical room is required for all major mechanical equipment. Only small units may be roof-mounted, and shall be made as inconspicuous
More informationPlenum Fans. Model HPA. Direct Drive
Plenum Fans Model HPA Direct Drive October 2012 Quiet & Efficient HPA Plenum Fans Greenheck s modular plenum fan, model HPA, is designed and engineered to provide superior performance and reliability in
More informationFANS & BLOWERS ENERGY EFFICIENCY REFERENCE GUIDE TRAINING & SUPPORT
FANS & BLOWERS ENERGY EFFICIENCY REFERENCE GUIDE TRAINING & SUPPORT Disclaimer: Neither CEATI International, the authors, nor any of the organizations providing funding support for this work (including
More informationRemoval. CAUTION: Do not let tensioner arm snap back to the freearm position, sever damage may occur to the tensioner.
Removal 3.7L/4.7L ENGINE CAUTION: Do not let tensioner arm snap back to the freearm position, sever damage may occur to the tensioner. 1. Disconnect negative battery cable from battery. 2. Rotate belt
More informationPresented By: John Dolan, P.E.
Variable Speed Compressor Technologies Presented By: John Dolan, P.E. President - Thermosystems, Inc. BS in Mechanical Engineering from UIUC 29 years HVAC Equipment Application Experience jdolan@thermohvac.com
More information1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.
Issued 2006/08/01 Section 13920 Packaged Fire Pumps and Controllers Page 1 of 7 PART 1 GENERAL 1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1
More informationWith the world-renowned SIGMA PROFILE
www.kaeser.com Rotary Screw Compressors BSD/CSD/CSDX T SFC Series With the world-renowned SIGMA PROFILE Free air delivery 0.87 to 16.10 m³/min, Pressures 5.5 to 15 11 What do you look for in a compressor
More informationBoiler Manager Technical Report
Boiler Manager Technical Report Boiler Manager Technical Report Process Description The Boiler Manager works by controlling the boiler firing cycle. What is the Boiler Firing cycle? When the central heating
More informationCPF PRODUCT DESCRIPTION
CPF 175 340 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPF 175-340 compressor is a quiet, complete and ready-for-use unit for the production of compressed air in industrial applications. OVERVIEW The CHICAGO
More informationSECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.
SECTION 15650 REFRIGERATION PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units. 4. Air
More informationDSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data
DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data July 28, 2008 Page 1 1 of 3 PROJECT: TAG: Gross Cooling Capacity [Btuh]: 37,800* Design CFM: 1,200 Seasonal
More informationHeating and Cooling Systems
Heating and Cooling Systems Figure 1. Typical Engine Cooling System Introduction Engines generate a great amount of heat. This heat is created when the fuel and air mixture is ignited and expands inside
More informationFan Arrays. White Paper. Energy Labs White Paper Series Volume 0412 Issue 001 April 2012 Rev. 0. Series
White Paper Series Volume 0412 Issue 001 April 2012 Rev. 0 Copyright Energy Labs Inc. All rights reserved. Energy Labs Inc. and EnergyLabs Inc. logo are registered trademarks of Energy Labs Inc. in the
More informationINDUSTRIAL BLOWERS. With over 70 years of experience and expertise our fans will ensure your projects are a success.
BLOWERS With over 70 years of experience and expertise our fans will ensure your projects are a success. ABOUT OUR PARTNERSHIP has been representing Chicago Blower Corporation (USA) since 2004, offering
More informationUEE11 Electrotechnology. Training Package. UEENEEJ107A Air conditioning and refrigeration systems, major components and associated equipment SAMPLE
UEE Electrotechnology Training ackage UEEEEJ07A Air conditioning and refrigeration systems, major components and associated Learner Workbook Version Training and Education Support Industry Skills Unit
More informationWater Pumps. turbo-hydraulic pumps, positive-displacement pumps.
WATER PUMPS Water Pumps Water pumps are devices designed to convert mechanical energy to hydraulic energy. All forms of water pumps may be classified into two basic categories: turbo-hydraulic pumps, positive-displacement
More informationDS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP
DS series Industrial End Suction Pumps ISO/DP 5199 www.sterlingpumps.com.au DS series Capacities from: Heads from: 340 to 5,680 m3/h (1,500 to 25,000 USPGM) 21 to 106 metres (70 to 350 feet) Power range
More informationINTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012
HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More informationMIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/
1 of 3 Cooling Capacity [Btuh] 24,800 * Condensing Unit SEER: 13.0 ** Condensing Unit CFM: 1,600 Condenser Fan No./Type: 1/CENTRIFUGAL Diameter x Width [in]: 10x10 Drive: Adjustable Belt Motor HP: 0.5
More informationChiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years.
TURBOCOR COMPRESOR CHILLERS General Description Microprocessor controlled, water chiller using HFC 134a refrigerant, two stage centrifugal oil free variable speed compressor's and electronic expansion
More informationSECTION AIR HANDLING UNIT
SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR
More informationAPC BC300 Series 40kW 208/450/480V User Guide
APC BC300 Series 40kW 208/450/480V User Guide Copyright 2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor Thank You Thank
More informationUnderstanding Fan System Effects
Fan Application FA/101-99 A technical bulletin for engineers, contractors and students in the air movement and control industry. Understanding Fan System Effects The air moving industry uses a common term
More informationIndirect Gas-Fired Make-Up Air
Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up
More informationAcoustiFlo Fans: Retrofit Solutions and Beyond
AcoustiFlo Fans: Retrofit Solutions and Beyond The Most Energy Efficient Plenum Fan in the World! The AcoustiFLO Modular Fan RETROFITS Ideal for fan replacement inside any air handling unit Module is 35
More informationCold Weather Operation Of Cooling Towers
This article was published in ASHRAE Journal, March 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
More informationPOWERENERGY
ASME 2016 POWER CONFERENCE JUNE 26 JUNE 30, 2016 CHARLOTTE, NORTH CAROLINA, USA POWERENERGY2016-59067 EVACUATION SYSTEMS FOR STEAM SURFACE CONDENSERS: VACUUM PUMPS OR STEAM JET AIR EJECTORS? Ranga Nadig,
More informationBRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application
1 BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application By: T. S. Wan Date: Oct. 7, 1995 Copy Right 1995 by T. S. Wan All rights
More informationBrown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS
SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett
More informationSelecting Fans and Determining Airflow for Grain Drying and Storage
Proceedings of the Integrated Crop Management Conference Proceedings of the 1993 Integrated Crop Management Conference Dec 2nd, 12:00 AM Selecting Fans and Determining Airflow for Grain Drying and Storage
More informationScrew Compressors SM SERIES. Capacities from: 16 to 54 cfm Pressures from: 80 to 217 psig
Screw Compressors SM SERIES Capacities from: 16 to 54 cfm Pressures from: 80 to 217 psig Rotary Screw Compressor Maximum Reliability and Efficiency For years, customers have depended on Kaeser for reliable
More informationConstruction Standards Page
Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationThe Corona air inlet TECHNICAL SPECIFICATIONS
710 The Corona air inlet Proper distribution of air in a house for animals can be a challenging task. The ventilation system should be able to maintain a perfect climate throughout the production cycle.
More informationA Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio Phone: (513) Fax: (513)
A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio 45014-2035 Phone: (513) 874-2400 Fax: (513) 870-6249 JM AEROFOIL FANS Installation, Operation and Maintenance Instructions Site Storage The fan must
More informationFan Arrangements, Rotation, Discharge and Motor Position
FAN ENGINEERING Information and Recommendations for the Engineer Fan Arrangements, Rotation, Discharge and otor Position FE-3900 Introduction Fan arrangements and classes are industry standards that have
More informationCENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components:
Pumps DOE-HDBK-1018/1-93 CENTRIFUGAL PUMPS CENTRIFUGAL PUMPS Centrifugal pumps are the most common type of pumps found in DOE facilities. Centrifugal pumps enjoy widespread application partly due to their
More informationan ISO 9001 Company Bulletin PR-112
an ISO 9001 Company Bulletin PR-112 Airfoil Fans SINGLE WIDTH DOUBLE WIDTH SQUARE SQA FANS DIRECT DRIVE FANS Known for high efficiency, low sound levels, and low horsepower, the Design 51 fan is used extensively
More informationPulse Jet Baghouse ASTEC PULSE JET BAGHOUSE. for Asphalt Facilities
Pulse Jet ASTEC PULSE JET BAGHOUSE for Asphalt Facilities ASTEC PULSE JET BAGHOUSE FOR ASPHALT MIXING PLANTS Astec baghouses deliver superior performance and efficiency, while helping your plant meet
More informationDestratification Fan Units DRF-VK & DRF-VKM & DRF-OV
Destratification Fan Units DRF-VK & DRF-VKM & DRF-OV Thermal Stratification Number One Reason for Energy Waste in Todays Buildings Tel: 1-888-640-0925 Tel: 513-348-3853 Fax: 513-268-4597 sales@ventsus.com
More informationTURBO AND HIGH PRESSURE REGENERATIVE BLOWERS
NEW! TURBO AND HIGH PRESSURE REGENERATIVE BLOWERS Turbo Blowers Blower housings from cast aluminum, closed impellers from sheet aluminum, maintenance-free squirrel cage rotor motors of our own manufacture
More information