1 Charles M. LeMaistre PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and Element Z for technical design criteria related to general building components, requirements for preparation of Project Manuals, and for additional MD Anderson standards and other requirements. C. Refer to the Owner s Master Construction Specifications for product and construction execution requirements. D. Information provided within this document is intended to familiarize the A/E with the facility. The A/E must field verify existing conditions that are relevant to the project. PART 2 - BUILDING OCCUPANCY 2.01 OVERVIEW A. The Charles M. LeMaistre Clinic building is number 100P, the building is designed to house clinical space. PART 3 - EXISTING SYSTEMS AND ASSEMBLIES 3.01 ARCHITECTURAL AND GENERAL CONSTRUCTION A. The Charles M. LeMaistre Clinic building was constructed in The present twelve story building contains approximately 169,605 gross square feet and is built with steel reinforced concrete pan structure. B. Due to a mismatch in coordinating floor levels with Love Clinic, the LeMaistre Building does not have a named fourth floor; which would be called Level 5 since the Ground floor is named as Level one with the first floor named as Level 2 and so on STRUCTURAL SYSTEMS A. The floor to floor heights as follows: 1. Basement to Level 1: 15' 2. Level 1 - Level 5: Level 5 to Level 6: 13-6' 4. Level 6 to Level 7: Level 8 - Level 12: 13 ODG OF 6

2 Charles M. LeMaistre 6. The building s penthouse is located at Level 12. B. The depths of the reinforced concrete beams vary from 18 to 36 inches with the majority of beam depths measuring between 24 and 30 inches from the top of the floor slab FIRE SUPPRESSION SYSTEMS A. The building utilizes a wet pipe system PLUMBING SYSTEMS A. Water Distribution System: 1. Domestic water connects to a water softener system that provides soft water for make-up to the building hot water systems and the building chilled water system. Two redundant 100 percent capacity domestic hot water heaters located in the basement utilize low pressure (15psig) steam. There are five (5) electric, 6 gallon capacity hot water heaters rated at 3 kw each. B. Sanitary System: 1. The sanitary system drains through an 8 inch sanitary sewer pipe exiting the building through a wall penetration located at the northwest corner of the basement. A sanitary sewer ejector pump transfers waste from the basement sanitary sewer piping. C. Storm System: 1. There are three 8 inch storm drain risers that connect to a twelve (12) inch storm sewer that exits the northeast corner of the basement toward MD Anderson Boulevard. This building drains by gravity except for the basement. 2. There is a sump pump which serves the sub-soil drainage system located in the basement mechanical room. The 12 inch pipe size is adequate for the present building function. The piping material is cast iron. One duplex storm sump pump station is located in the basement of the building. D. High Purity Water System: 1. Not located or routed through this building. E. Medical Vacuum System: 1. The medical vacuum system utilizes four vacuum pumps. Two redundant vacuum pumps are used for purely medical service, and the remaining two redundant vacuum pumps are used for medical evacuation of anesthesia gases serving the clinic areas. The piping is copper. F. Lab Vacuum System: 1. The lab vacuum system has two redundant vacuum pumps serving the clinic areas. The piping is copper. ODG OF 6

3 Charles M. LeMaistre G. Medical Air System: 1. The medical air compressor is a duplex system consists of two (2) oil free compressors located in the basement mechanical room. The piping used on the medical air system is copper. H. Oxygen Gas System: 1. Oxygen tap is located north of the Clark Clinic building and is routed through Love Clinic via a ¾ inch copper distribution piping to the LeMaistre clinic s patient treatment rooms. I. Natural Gas System: 1. No natural gas in the building HVAC AND INTEGRATED AUTOMATION SYSTEMS A. Chilled Water System: 1. The LeMaistre building is supplied chilled water from TECO. Ten inch supply and return chilled water pipes from TECO are routed from the basement of the Love Clinic to basement of the LeMaistre Building. 2. TECO chilled water circulates through three (3) plate and frame heat exchangers to transfer heat from the building s chilled water system. The redundant pumps and the plate and frame heat exchangers are sized for 50 percent capacity of the system design cooling load requirement. 3. Two piping risers distribute chilled water to the stacked mechanical rooms located on the south side of the building. B. Steam System: 1. The LeMaistre building is supplied with high pressure steam from TECO. The high pressure (250psig) steam supplied by TECO is reduced to (70 psig) medium pressure steam by pressure reducing station located in this building's for mechanical equipment rooms. The low pressure steam is provided to the building s water heaters, and medium pressure (28 psig) steam preheats coils. Steam condensate is returned to TECO from two condensate receiver units. 2. The building has two redundant hot water pumps and tube shell heat exchangers each sized for 100 percent capacity of the buildings system design heating load requirement. C. Air Handling System: 1. Mechanical rooms are located in the basement, on Level 4, and on the roof in the penthouse structure. 2. The mechanical room in the basement contains two dual duct VAV air handlers with chilled water coils and hot water heating coils and fan-coil units. Two outside air pretreatment units are connected respectively with the dual duct air handlers. The ODG OF 6

4 Charles M. LeMaistre pretreatment units are equipped with two rows of chilled water cooling coils and steam pre-heat coils. 3. The two (2) dual duct air handlers serve separate floors. AHU B-1 provides conditioned air for Levels 1, 4, 5 and 6. AHU B-2 serves Levels 1, 2 and 3. AHU P-1 provides conditioned air for Levels 7, 8, and 9 and AHU P-2 serves Level The mechanical room in the Penthouse Level 11 contains two (2) dual duct VAV air handlers, outside air pretreatment units and fan coil units. The air handling units in the penthouse are arranged the same as those in the basement. The pedestrian bridges are served by fan-coil units. 5. Three (3) new secondary (building) side chilled water and two (2) new hot water pumps are located on Level 4, above the 500-year flood elevation. The three (3) primary chilled water pumps and the three (3) frame plate heat exchangers remain in the basement. A new control air compressor is located on Level 4 to supply air HVAC system control panels and control valves. 6. Computer room air handling units are located in rooms CS02.018, CS02.037, CS02.047, and CS These units use chilled water for the cooling medium and have electric heating coils. The humidifier is an infrared type. D. Exhaust and Relief Air Fans: 1. General exhaust air fan EFP-1 serves the basement, and Level 1 through Level 6 and EFP-2 serves Level 7 through Level This building has a stairwell pressurization fan and it also has a smoke removal fan that serves the basement up to Level ELECTRICAL SYSTEMS A. Normal Power System: 1. Main power boards are located in the basement, however, the power distribution and lighting panels required for normal operations are located on Level 2. B. Emergency Power System: 1. All emergency power and power distribution panels associated life safety are located on Level 2. C. Fire Detection and Alarm System: 1. Fire detection from ceiling smoke detectors and smoke detectors located in each of the HVAC systems serving the clinic COMMUNICATION SYSTEMS A. Fire alert audible alarms and nurse call systems. ODG OF 6

5 Charles M. LeMaistre 3.08 EXTERIOR IMPROVEMENTS AND LANDSCAPING A. None at this time CIVIL/SITE UTILITIES A. TECO Chilled Water, TECO Steam, City of Houston potable water, and sewer, electrical power, and communications telephone, and cable. PART 4 - PROPOSED SYSTEM CONCEPTS 4.01 OVERVIEW A. New controls are to be fully electronic with electronic sensors, thermostats, and electric actuators for terminal units, valves, and isolation and control air dampers to interface with the Siemens Apogee BAS. PART 5 - PRODUCTS 5.01 OVERVIEW A. Equipment Components: 1. To meet FEMA flood requirements, all electrical panels, medical air, vacuum pumps cold and hot domestic water pumps, and domestic hot water heaters are new and located in rooms above the basement of the building DIVISION 09 FINISHES A. Refer to Interior Finishes Standards DIVISION 22 PLUMBING 5.04 DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING 5.05 DIVISION 25 INTEGRATED AUTOMATION 5.06 DIVISION 26 ELECTRICAL ODG OF 6

6 Charles M. LeMaistre PART 6 - EXISTING DOCUMENTATION 6.01 OVERVIEW A. Design Guideline Elements, Master Construction Specifications, and other supplemental resources needed for design may be downloaded from MD Anderson s Facilities Management internet website at the following address 6.02 DRAWINGS 1. A. Request existing construction drawings and project as-built drawings from Capital Planning and Management, Data Management Group. B. For facilities located within the Main Building 1515 Holcombe Boulevard, note the floor Level designation is originally noted as ground, Level 1, etc. All floors are now designated as Level 1, Level 2, etc STUDIES A. Heat Recovery Chiller Feasibility Study dated May PART 7 - DOCUMENT REVISION HISTORY Issue Date Revision Description Reviser Initial Adoption of Element Rev. 1 Rev. 2 Rev. 3 Rev. 4 Rev. 5 END OF ELEMENT ODG OF 6

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and Element Z for technical

More information

DIVISION 23 - HVAC HVAC

DIVISION 23 - HVAC HVAC DIVISION 23-23 00 00 PART 1 - GENERAL 1.01 GENERAL CRITERIA A. The heating system typical set point shall be 70 F inside. 1. The winter outdoor design temperature for most systems shall be -6 F. 2. The

More information

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available. PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS AND APPLICATIONS Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS Earliest air conditioning system used only for heating (winter) Provided heated air for comfort

More information

CENTRAL STATE HOSPITAL PLAN PLANT OPERATIONS UTILITIES MANAGEMENT PLAN

CENTRAL STATE HOSPITAL PLAN PLANT OPERATIONS UTILITIES MANAGEMENT PLAN Page 1 of 11 CENTRAL STATE HOSPITAL PLAN SUBJECT: PLANT OPERATIONS UTILITIES MANAGEMENT PLAN ANNUAL REVIEW MONTH: RESPONSIBLE FOR REVIEW: March CSH Safety Officer LAST REVISION DATE: November 2003 I. SCOPE:

More information

21. Plumbing fixture mixing valves, PRV, electronic faucets and flush valve(excluding batteries)optional Cost proposal to include these device

21. Plumbing fixture mixing valves, PRV, electronic faucets and flush valve(excluding batteries)optional Cost proposal to include these device DIVISION 23800 APPENDIX A ASHTABULA CAMPUS: 1. Air Handling Equipment And Appurtenances 2. Exhaust Fans 3. Fume Hood Exhaust Fans 4. Fume Hood monitoring devices and annual certification of face velocity

More information

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES 2.05 PLUMBING GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.05 It is expected that the plumbing design professional will conform to accepted good engineering design practices.

More information

4. OVERVIEW OF MECHANICAL SYSTEM

4. OVERVIEW OF MECHANICAL SYSTEM 4. OVERVIEW OF MECHANICAL SYSTEM The 87,000 SF SLCC is served by six (6) Trane M-Series Climate Changer Air Handing Units (AHUs). Each unit serves a distinct zone within the facility that is unique in

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story

More information

Mechanical System Description

Mechanical System Description 1. Building Description: Mechanical System Description The building is a Type-1B construction, 9-levels, non-high rise building with 67 affordable family housing units. The first level of the structure

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section includes criteria for the design of building heat generating systems including all isolation valves and steam piping and fittings, steam specialties, control

More information

Element D Services Electrical

Element D Services Electrical PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as a Specification.

More information

Project Description Clinical Research Building (CRB) Animal Area Renovation

Project Description Clinical Research Building (CRB) Animal Area Renovation Table of Contents INTRODUCTION... 3 PROJECT OVERVIEW... 4 CONSTRUCTION SYSTEMS AND ASSEMBLIES... 10 SPECIAL ISSUES AND CONSIDERATIONS... 19 PRODUCTS... 20 Issued: June 22, 2012 1 OF 24 Issued: June 22,

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL)

SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL) SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL) Basketball Courts 15 25 Built Improvements Playgrounds, Site Furniture, etc. 20 20 Catch Basin 40 40 Cold Water Lines 40 40 Compactors DHW Supply

More information

Technical Assignment 3

Technical Assignment 3 0 David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option Technical Assignment 3 Mechanical Systems and Existing Conditions Report David H. Koch Institute for Integrative

More information

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc.

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc. FAARM-Underground Facility Conceptual Design Review Mechanical Systems Prepared by: Dunham Associates, Inc. April 17, 2012 Dunham Project Number: 0412145-000-00 Dunham Associates Inc. Page 1 of 8 Mechanical

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

Architectural Engineering Senior Thesis Mechanical System Redesign

Architectural Engineering Senior Thesis Mechanical System Redesign Saint Joseph Medical Center Architectural Engineering Senior Thesis Mechanical System Redesign Chris Nicolais Building Description Existing Mechanical System Proposed Redesign Alternative Option Emergency

More information

Existing Mechanical System Operation

Existing Mechanical System Operation majority of the air handlers. There are louvers along the north side of the building that allow for outdoor air to come in and feed the air handlers. On levels 4-8 the research laboratories are variable

More information

DIVISION 15 MECHANICAL

DIVISION 15 MECHANICAL DIVISION 15 MECHANICAL A. GENERAL DESIGN CONDITIONS 1. Design occupied spaces to maintain 72 F and a space dew point temperature not to exceed 55 F. 2. Design classroom and office space buildings with

More information

DOCUMENT TABLE OF CONTENTS

DOCUMENT TABLE OF CONTENTS DOCUMENT 00003 June 16, 2005 TABLE OF CONTENTS DOCUMENT NO. INTRODUCTORY INFORMATION DOCUMENT 00003 TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS SECTION 01011 SECTION 01025 SSP21.1-1 SECTION 01026

More information

SCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE

SCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE SCHEDULE OF S Penalty Fees. The fee for construction work performed before securing permit(s), where required, may be charged a fee of TWO TIMES THE COST OF THE PERMIT (S). Building Fee Schedule Residential

More information

Technical Report Three

Technical Report Three Technical Report Three Existing Conditions for Mechanical Systems Contents Executive Summary...2 Building Overview...2 Mechanical Systems Overview...2 Mechanical System...3 Outdoor & Indoor Design Conditions...3

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning Air Handling Distribution PART 1 - GENERAL 1.01 OVERVIEW A. This section describes criteria for design of facility air handling distribution systems, including air handlers, ductwork, ductwork accessories,

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

Cleveland Clinic Design Standards MECHANICAL SYSTEMS DESIGN GUIDELINES HVAC AIR DISTRIBUTION PART I - GENERAL 1.1 SUMMARY

Cleveland Clinic Design Standards MECHANICAL SYSTEMS DESIGN GUIDELINES HVAC AIR DISTRIBUTION PART I - GENERAL 1.1 SUMMARY PART I - GENERAL 1.1 SUMMARY A. This section addresses the general requirements for air handling distribution systems, including air handlers, ductwork, ductwork accessories, terminal units, air devices,

More information

Technical Assignment 3 11/15/04. Executive Summary

Technical Assignment 3 11/15/04. Executive Summary Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria

More information

Charter Township of Flushing Construction Permit Fee Schedule.Construction and Development Services Department

Charter Township of Flushing Construction Permit Fee Schedule.Construction and Development Services Department Charter Township of Flushing Construction Permit Fee Schedule.Construction and Development Services Department 1. CONSTRUCTION PERMIT FEES: A. General: Fee basis/value of construction shall be determined

More information

S AGE E NGINEERING A SSOCIATES, LLP

S AGE E NGINEERING A SSOCIATES, LLP S AGE E NGINEERING A SSOCIATES, LLP 1211 Western Avenue Albany, NY (518) 453 6091 F (518) 453 6092 Kingston Library Mechanical and Electrical Systems Field Report Date of Visits: Mechanical - September

More information

Virginia Tech Standards for Building Automation System

Virginia Tech Standards for Building Automation System March 1, 2016 Virginia Tech Standards for Building Automation System A. Existing Conditions: The Campus Building Automation System is Siemens Apogee and controls all significant campus facilties. Virginia

More information

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods 230520 HEAT GENERATION Cornell s Design and Construction Standards provide mandatory design constraints and acceptable or required products for all construction at Cornell University. These standards are

More information

SECTION : MEPS IDENTIFICATION & LABELING

SECTION : MEPS IDENTIFICATION & LABELING SECTION 01 70 10: MEPS IDENTIFICATION & LABELING 1. GENERAL A. The intent of this section is to define the labeling and identification requirements for building mechanical, electrical, plumbing, and specialty

More information

Cook - Wissahickon Elementary School

Cook - Wissahickon Elementary School Cook - Wissahickon Elementary School 201 E. Salaignac St., Philadelphia, PA 19128 HVAC Replacement Project Scope Determination Report May 10, 2018 Prepared by: G.P. Lamina, Jr., P.E., MBA School District

More information

Demonstration and Training of MEP Systems Page 1 of 15

Demonstration and Training of MEP Systems Page 1 of 15 Page 1 of 15 Last Update: May 17, 2018 A. General: 1. Demonstrations and Training of various MEP and other systems is very important to BSU Facilities, especially on new building or major renovation projects.

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance Groton Heights School Mechanical Evaluation TO: FROM: Amy Vaillancourt, Project Manager Harley Langford, Project Manger Jason Curtis, P.E. DATE: February 24, 2016; Revised May 31, 2016 On Monday, December

More information

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1 Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9

More information

CONNECTICUT. Downloaded

CONNECTICUT. Downloaded Housekeeping/Laundry/Maintenance J. Laundry. CONNECTICUT Downloaded 01.15.11 (1) This service, if provided, shall be used exclusively for laundry and shall be remote from resident and food service areas,

More information

SECTION INSPECTION AND TESTING OF WORK

SECTION INSPECTION AND TESTING OF WORK SECTION 01455 PART I - GENERAL 1.01 SECTION INCLUDES A. Project Inspections and Procedures B. Scheduling Inspectors Notification requirements 1.02 RELATED SECTIONS A. Section 01310 COORDINATION B. Section

More information

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3 Existing System Evaluation Executive Summary The MBNA Career Services Center is a 44,000 square foot, 4-story office type building at Penn State University, University Park Campus. The building is located

More information

4. Plumbing fixtures. a) The plumbing fixtures are from the original building. They are appear old and not to comply with ADA requirements.

4. Plumbing fixtures. a) The plumbing fixtures are from the original building. They are appear old and not to comply with ADA requirements. From: Jian Zhang Sheet: 1 of 8 Date of Visit: 12/7/10 Coach House: Plumbing Systems b) All original building storm piping shows significant signs of aging. b) All original building sanitary piping shows

More information

HVAC 101. H V A C S y s t e m s

HVAC 101. H V A C S y s t e m s H V A C 1 0 1 S y s t e m s Introduction & Overview Should you care? Mechanical System Types Components & operation Popular Application Key Issues and Design Considerations System Comparisons First Cost

More information

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following: PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe

More information

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Facility Condition Assessment Summary Report British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Submitted by: VFA Canada Corp. Burnaby Centre 4211 Kingsway Burnaby, BC V5H 1Z6

More information

Appendix B. Facilities Assessment Report

Appendix B. Facilities Assessment Report Mile Lane Army Reserve Center Redevelopment Plan September 2008 Appendix B Facilities Assessment Report RKG Associates, Inc. Mile Lane Army Reserve Base Middletown, CT MEP System Evaluation For RKG Associates

More information

Dates of Construction Construction Start 2/28/1999 Date of Completion 4/2000 Occupancy 5/2000

Dates of Construction Construction Start 2/28/1999 Date of Completion 4/2000 Occupancy 5/2000 Executive Summary The Milton S. Hershey Medical Center Academic Support Building is located on The Pennsylvania State University's campus in Hershey, PA. The building is owned by The Pennsylvania State

More information

$ Each additional variance per petition. $ All Other Zoning Districts: One variance per petition

$ Each additional variance per petition. $ All Other Zoning Districts: One variance per petition 2015 SCHEDULE COMMUNITY DEVELOPMENT DEPT. ENGINEERING PLAN REVIEW Single Family New Construction All Other Plan Reviews Minimum Engineering Fee Planned Unit Development - PUD: Step #1: Step #2: See Site

More information

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS PITTSBURG STATE UNIVERSITY HVAC and BUILDING AUTOMATION SYSTEM STANDARDS CHILLERS In new construction, liquid-cooled models are preferred for systems larger than 100 ton. o Trane, York and McQuay brands

More information

Element D Services Electrical ODG010107

Element D Services Electrical ODG010107 Element D Services Electrical ODG010107 D5090 Other Electrical Systems Part 1. General This section includes design standards and requirements for other electrical systems. This is a design standard and

More information

Appendix 13. Categories of Cooling and Heating systems

Appendix 13. Categories of Cooling and Heating systems EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01

More information

CHURCH MUTUAL AND HARTFORD STEAM BOILER SENSOR TECHNOLOGY PROGRAM: IDENTIFYING FROZEN PIPE EXPOSURES

CHURCH MUTUAL AND HARTFORD STEAM BOILER SENSOR TECHNOLOGY PROGRAM: IDENTIFYING FROZEN PIPE EXPOSURES CHURCH MUTUAL AND HARTFORD STEAM BOILER SENSOR TECHNOLOGY PROGRAM: IDENTIFYING FROZEN PIPE EXPOSURES Where to Install Pipe Temperature Sensors for Freeze Protection 1 WHICH PIPES SHOULD I MONITOR FOR FREEZE

More information

Packaged Semi-Instantaneous Steam Fired Water Heater

Packaged Semi-Instantaneous Steam Fired Water Heater MODEL STX Packaged Semi-Instantaneous Steam Fired Water Heater Shell and Tube Style Heater Features Reliable Only high grade materials used in construction to ensure long operating life Heat exchange pressure

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Technical Assignment 1

Technical Assignment 1 0 Technical Assignment 1 ASHRAE Standard 62.1 Ventilation and Standard 90.1 Energy Design Evaluations Compliance Analysis David H. Koch Institute for Integrative Cancer Research Massachusetts Institute

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 23 05 93 - TESTING, ADJUSTMENT AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK ENERGY CONSERVATION MEASURE 1 Partial Steam System Decentralization SIEMENS will Furnish and Install condensing hot water boilers with associated

More information

9/18/2017. Nicholas Thornton, CEM. Systems: HVAC, Electrical, and Technology. Overview. Today s Goals Introductions HVAC Electrical Technology Q&A

9/18/2017. Nicholas Thornton, CEM. Systems: HVAC, Electrical, and Technology. Overview. Today s Goals Introductions HVAC Electrical Technology Q&A Nicholas Thornton, CEM 1 Overview Today s Goals Introductions HVAC Electrical Technology Q&A 2 1 Today s Goals An overview, a crash course Maybe a few tangents (ASK QUESTIONS!) Show typical arrangements

More information

2016 Plumbing Supplemental Plan Review List

2016 Plumbing Supplemental Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Plumbing Supplemental Plan Review List POTABLE WATER SYSTEM P1. Specify which fixtures are for private use and which are for

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

General Catalogue. FORM SSI - G.C (94)

General Catalogue. FORM SSI - G.C (94) FORM SSI - G.C (94) www.ssi.co.ir General Catalogue INDEX 09CDF 16DNS 16DES 16JBP 16JBP Air Cooled Condenser Air Cooled Condenser Absorption Chiller Double Effect Direct Fired Absorption Chiller Double

More information

Technical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: ,

Technical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: , Purpose 355 West Queens Road Technical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: 604-990-2480, building@dnv.org The purpose of this document is to provide

More information

Alex Masterton, PE Electrical Engineer Reviewer AHCA Neal Boothe, PE Electrical Engineer/Principal

Alex Masterton, PE Electrical Engineer Reviewer AHCA Neal Boothe, PE Electrical Engineer/Principal Alex Masterton, PE Electrical Engineer Reviewer AHCA Neal Boothe, PE Electrical Engineer/Principal FBC 419.3.15.6 All low-voltage system main or branch circuits entering or exiting the structure shall

More information

C13-Series Engineering Guide

C13-Series Engineering Guide Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................

More information

AHU Air Handling Unit Fundamentals. j.ilangumaran

AHU Air Handling Unit Fundamentals. j.ilangumaran AHU Air Handling Unit Fundamentals j.ilangumaran Objectives Review primary components of an AHU Understand the basic progression and advantages of advanced AHU control Understand the basic control sequences

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe

More information

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline ME 414/514 HVAC Systems Overview Equipment Outline 2-1 The Complete System 2-2 The Air-Conditioning and Distribution System 2-3 Mechanical Equipment Air-handling Equipment Heating Equipment Boilers Furnaces

More information

CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY TM READ AND SAVE THESE INSTRUCTIONS CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY INSTALLATION AND ASSEMBLY INSTRUCTIONS Fig. 1 Flex connectors (by PURE) AHU/duct casing Injection tube Stainless

More information

NC State University Design and Construction Guidelines Division 23 Basic Mechanical Requirements

NC State University Design and Construction Guidelines Division 23 Basic Mechanical Requirements 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents for mechanical and plumbing systems. 2.0 General Requirements A. Warranty and Guarantee 1. Specifications

More information

CHAPTER 4. HVAC DELIVERY SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer

More information

SECTION Heating, Ventilation & Air Conditioning CONSTRUCTION STANDARDS

SECTION Heating, Ventilation & Air Conditioning CONSTRUCTION STANDARDS PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University for Heating, Ventilating, and Air Conditioning (HVAC). B.

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 92 - BROOKLYN, 601 PARKSIDE AVENUE, New York, 11226 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-13 8:31 AM 2017-11-27 11:43 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 310 - BRONX, 260 WEST KINGSBRIDGE RD, New York, 10463 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-07 8:42 AM 2017-12-13 12:31 PM Asset Data Are there fuel tanks?

More information

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

November 11, City of Sparks 215 S. 21 st St. Sparks, NV November 11, 2014 City of Sparks 215 S. 21 st St. Sparks, NV 89432-0857 Attn: Brian Cason Re: Sparks City Hall HVAC Upgrade Project-Alerton Direct Digital HVAC Control System to Match Existing City of

More information

Ventilation System Description. September 8, 2000 HETA

Ventilation System Description. September 8, 2000 HETA September 8, 2000 HETA 99-0250 Harry Enoch, Ph.D. Director, Environmental Health and Safety University of Kentucky 252 East Maxwell Street Lexington, KY 40506-0314 Dear Dr. Enoch: On June 7, 1999, the

More information

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems 233100 AIR DISTRIBUTION PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230700 HVAC Insulation B. Section 237300 Air Handling C. Section 230900 Building Automation and Control System Guidelines D. Section

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

FHCRC/SCCA Facility Design Manual

FHCRC/SCCA Facility Design Manual Number Div Title Buildings Comment Documents ARCHITECTURAL 810 02 Landscaping Rain Water Sensor: Include rain water sensor feature to reduce unnecessary water use. 000 04 Masonry Chases: chases shall be

More information

MECHANICAL SERVICES 101. Ian White

MECHANICAL SERVICES 101. Ian White MECHANICAL SERVICES 101 Ian White Contents 1. Ventilation 2. Heat Gains & Losses 3. Heating Ventilation Air Conditioning (HVAC) Systems What are Building Services Building Services incorporate all aspects

More information

MOUNT MIGUEL COVENANT VILLAGE - EMERGENCY PREPAREDNESS PROGRAM SECTION G: DISASTER RECOVERY PLAN

MOUNT MIGUEL COVENANT VILLAGE - EMERGENCY PREPAREDNESS PROGRAM SECTION G: DISASTER RECOVERY PLAN MOUNT MIGUEL COVENANT VILLAGE - EMERGENCY PREPAREDNESS PROGRAM SECTION G: DISASTER RECOVERY PLAN October 2017 DISASTER RECOVERY PLAN TABLE OF CONTENTS Recovery Plan Overview... Damage and Operational Assessments...

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 29 - STATEN ISLAND, 1581 VICTORY BLVD, New York, 10314 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-10 11:28 AM 2018-01-17 11:37 AM Asset Data Are there fuel tanks?

More information

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Technical Report #3 Mechanical Systems Existing Conditions Evaluation Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents

More information

INSTY-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

INSTY-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY Read and Save These Instructions Sheet No. EMIP INSTY-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY INSTALLATION AND ASSEMBLY INSTRUCTIONS Fig. 1 Tube support AHU/duct Injection tube Typ. centers Flexible

More information

CxA to Answer this Section

CxA to Answer this Section EXHIBIT 01 91 13-3, SAMPLE Construction checklist items are to be completed as part of initial checkout and subsequent startup, preparatory to Functional testing. This checklist does not take the place

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

EADQUARTERS. Technical Report One. Stephanie Kunkel   Mechanical Option EADQUARTERS 707 N. Calvert St. Technical Report One ASHRAE Standard 62.1 Ventilation ASHRAE Standard 90.1 Energy Design Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option

More information

Introduction to Supermarket Vacuum Condensate Drainage Systems by AcornVac, Inc.

Introduction to Supermarket Vacuum Condensate Drainage Systems by AcornVac, Inc. What is Vacuum Drainage? Vacuum Condensate Drainage Systems are simply a viable alternative to underground piping that uses the combined energies of vacuum pressure and gravity for the collection and disposal

More information

Building Automation System (BAS) Design Criteria

Building Automation System (BAS) Design Criteria 25 0520 Building Automation System (BAS) Design Criteria 1. Design Statement a. During the various design phases of this project, the Engineer will develop options and strategies for selection of the appropriate

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

COMMERCIAL PERMIT APPLICATION AND CHECKLIST. Depending on the scope of your project, the following submittal requirements will apply:

COMMERCIAL PERMIT APPLICATION AND CHECKLIST. Depending on the scope of your project, the following submittal requirements will apply: Planning/Building Department 115 Ramsdell Street Fircrest WA 98466 (253) 564-8902 COMMERCIAL PERMIT APPLICATION AND CHECKLIST Depending on the scope of your project, the following submittal requirements

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 69 - STATEN ISLAND, 144 KEATING PLACE, New York, 10314 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-19 8:39 AM 2018-01-23 4:33 PM Asset Data Are there fuel tanks?

More information

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012) Madeira City Schools Madeira, Ohio HVAC Assessment December 2011 (Revised February 2012) Prepared by: CMTA Engineering Consultants, Inc. 10411 Meeting Street Prospect, KY 40059 www.cmtaegrs.com (502) 326-3085

More information

Cultivator & Hybrid Cultivator

Cultivator & Hybrid Cultivator Cultivator & Hybrid Cultivator Precision Temperature & Humidity Packaged Unit INTRODUCTION The Cultivator Series package unit is the industry s MOST ENERGY EFFICIENT and HIGHEST capacity dehumidifier on

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

NORTH CENTRAL MICHIGAN COLLEGE PETOSKEY CAMPUS. Facilities Conditions Assessment Mechanical And Electrical Petoskey, Michigan

NORTH CENTRAL MICHIGAN COLLEGE PETOSKEY CAMPUS. Facilities Conditions Assessment Mechanical And Electrical Petoskey, Michigan NORTH CENTRAL MICHIGAN COLLEGE PETOSKEY CAMPUS Facilities Conditions Assessment Mechanical And Electrical Petoskey, Michigan PBA Project No. 2014.0137.00 Prepared By: Wayne Kerbelis Terry Cleis September

More information

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas

More information