SERIES HC Heat-of-Compression Compressed Air Dryer

Size: px
Start display at page:

Download "SERIES HC Heat-of-Compression Compressed Air Dryer"

Transcription

1 SERIES HC Heat-of-Compression Compressed Air Dryer Models HC-3 HC-239 Information When making inquiries, please provide the following information: 1) Equipment Model Number 2) Equipment Serial Number 3) Equipment Operating Pressure 4) Equipment Operating Temperature 5) Approximate time in service 6) Nature of Problem IMPORTANT! BEFORE INSTALLING AND OPERATING THE DRYER, IT IS RECOMMENDED THAT THIS MANUAL BE STUDIED AND CLEARLY UNDERSTOOD. THIS DRYER IS DESIGNED TO BE USED ONLY WITH A NON- LUBRICATED COMPRESSOR. USE WITH A LUBRICATED COMPRESSOR WILL VOID ALL WARRANTIES AND MAY CAUSE SEVERE DAMAGE. For information, parts, or service, contact your local Ingersoll-Rand Service provider or reach us at

2 Reference No. 145 Final Rev 8 Page 2 October 2005

3 INDEX PREFACE SECTION 1: INTRODUCTION 1.1 General Information 1.2 Safety Instructions Identification of signs and symbols in this manual Safety tips for maintenance, inspection & assembly work 1.3 Personnel Qualification 1.4 Product Information Theory of Operation Pressure vessel regulations Airtightness test Overloading Technical data sheet Dryer Flow Capacities Transport Storage Use of an afterfilter SECTION 2: INSTALLATION 2.1 Set-up and installation Mechanical installation Filter installation Electrical installation SECTION 3: START UP AND OPERATION 3.1 Start-up / Shut down Pressurizing dryer Energizing dryer controls Reference No. 145 Final Rev 8 Page 3 October 2005

4 3.2 Operator interface Main screen Dryer status Settings Alarms 3.3 Program Steps SECTION 4: MAINTENANCE 4.1 Suggested preventive maintenance schedule 4.2 Replacement / Disposal of the desiccant 4.3 Dewpoint meter maintenance (DPDS Option only) 4.4 Filters General comments and use Function Assembly and installation Maintenance Changing of filter elements Accessories SECTION 5: SPARE PARTS LIST 5.1 Recommended spares for HC-3 TO HC-239 SECTION 6: TROUBLESHOOTING AND FAULTS 6.1 Introduction 6.2 High Dewpoint 6.3 Fail-to-shift 6.4 Primary Drain Failure 6.5 Secondary Drain Failure 6.6 Short-term shut-down 6.7 Shut-down in case of a fault or for maintenance Reference No. 145 Final Rev 8 Page 4 October 2005

5 SECTION 7: I-R ACTIVATED ALUMINA MSDS 7.1 Company Description 7.2 Material Description 7.3 Ingredients 7.4 Physical Data 7.5 Fire and Explosion Data 7.6 Reactivity Data 7.7 Health Hazard Information 7.8 Spill, Leak, and Disposal Procedures 7.9 Special Protection Information 7.10 Special Precautions and Comments 7.11 References SECTION 8: AUXILIARY MANUALS & DRAWINGS Reference No. 145 Final Rev 8 Page 5 October 2005

6 PREFACE: This technical manual from Ingersoll-Rand is an aid in getting to know the adsorption dryer better and in utilizing its possibilities for application in accordance with its intended use. Furthermore, this manual contains important information for safe, proper and economic operation. All instructions must be followed as written in order to avoid danger and damages which could cause downtime and premature wear and tear on the adsorption dryer. In addition to the technical manual and the accident prevention regulations which are valid in the particular location where the dryer is being used, the recognized special rules for safe and proper working procedures must also be followed. Each person involved with the set-up, start-up, operation, maintenance and repair of the adsorption dryer in the User Company must have first read and understood the technical manual and especially the safety tips. Reference No. 145 Final Rev 8 Page 6 October 2005

7 SECTION 1: 1.1 GENERAL INFORMATION The adsorption dryer of the HC-3 HC-239 series is built according to the latest technological developments and recognized safety rules. Its use, however, can endanger life and limb of the user or of third parties and can lead to considerable damage to the adsorption dryer and other material assets if: it is operated by personnel not trained or instructed in its use, it is improperly used, It is improperly maintained or serviced. This can result in the loss of all damage claims. This adsorption dryer is designed for neutral media (gas) free of aggressive water, oil and solid elements. Ingersoll-Rand accepts no liability for corrosion damage and malfunctions caused by aggressive media. Applications other than those mentioned in this manual must be agreed to by Ingersoll-Rand and confirmed in writing. In the interest of further development, Ingersoll-Rand reserves the right to make changes at any time, which, in keeping with the essential characteristics of the adsorption dryer described here, may be necessary for increasing efficiency or for reasons relating to safety or to normal business practice. 1.2 SAFETY INSTRUCTIONS This technical manual contains basic tips, which must be followed during set-up, operation and servicing. It is of utmost importance that it be read by the assembly technician before installation and start-up, as well as by the specialist / operator in charge, and it must always be within reach at the place where the adsorption dryer is being used. Reference No. 145 Final Rev 8 Page 7 October 2005

8 USER MANUAL SECTION 1: (Continued) Identification of signs and symbols in this technical manual The safety tips contained in this technical manual, whose disregard could endanger people and machines, are indicated by a general danger sign and the additional markings Danger! Or Attention! Danger! / Attention! Warning against electrical voltage! Safety tips printed directly on the adsorption dryer must also be followed at all times and must be kept completely legible. Advice: This sign refers to a procedure or sequence of particular interest or importance. All tips must be followed to ensure proper use of this adsorption dryer. This dot refers to working or operational steps. The steps are to be carried out in the order of their appearance from top to bottom. - The sign of a hyphen marks enumerations Safety tips for maintenance, inspection and assembly work The operator is to make sure that all maintenance, inspection and assembly work is carried out by special personnel who are authorized and qualified, and who are adequately informed through careful study of the technical manual. For this reason, special attention should be paid to the following attention and danger sign: Reference No. 145 Final Rev 8 Page 8 October 2005

9 USER MANUAL SECTION 1: (Continued) Safety tips for maintenance, inspection and assembly work (Continued) Attention! Never make structural changes to the adsorption dryer that are not specifically authorized by Ingersoll-Rand! Only use original spare and accessory parts! Carry out maintenance work only when the adsorption dryer is switched off, depressurized, and disconnected from the electric power supply! Attention! Multiple power sources may exist in the electrical panel. All possible power sources must be disconnected before servicing dryer. Advice: Refer to the desiccant material safety data sheet (MSDS) when installing or disposing of desiccant, which can be found in Section 7 of this User Manual. Danger! Wear protective goggles and mask when working with the desiccant! Advice for protection: If desiccant comes into contact with the eyes, rinse eyes immediately with large amounts of clear water. If the desiccant is spilled, clean up with effort to minimize the formation of dust. In case of fire, there is no restriction on the use of fire extinguishing material. A small dust mask must be worn. 1.3 PERSONNEL QUALIFICATION The personnel involved in operation, maintenance, inspection, and assembly must have the corresponding qualifications to do this work. Areas of responsibility and supervision of the personnel must be precisely established by the operator. Should the personnel not possess the necessary knowledge, then they must be trained and instructed. If need be, this training may be carried out by the manufacturer / supplier at the request of the operator of the adsorption dryer. Further, the operator is to make sure that the personnel completely understand the contents of the technical manual. Reference No. 145 Final Rev 8 Page 9 October 2005

10 SECTION 1: (Continued) 1.4 PRODUCT INFORMATION The adsorption dryer is used for the purpose of drying compressed air and other gases according to its respective design. As a "standard model" the adsorption dryer is equipped with two desiccant vessels and, depending on certain conditions, provides pure, dry and oil-free compressed air or gases Theory of Operation The HC heat-of-compression dryer uses the hot air from the compressor to regenerate the desiccant. Each tower is sized for a minimum of 4 hours online, but may be extended by use of the optional DPDS which will allow the dryer to switch towers based on water load rather than time. The DPDS (Dewpoint Demand System) is optional equipment and may or may not be present on your particular air dryer. If your dryer is equipped with the DPDS, see the associated DPDS Installation and Operating Guide for more operational details. The regeneration cycle is split up into three functions. Reference No. 145 Final Rev 8 Page 10 October 2005

11 SECTION 1: (Continued) A. Regeneration Cycles 1. Heating. Hot air directly from the compressor enters the inlet of the HC and is directed by the inlet 2-way valves into the regenerating tower. This hot, thirsty air regenerates the bulk of the water from the desiccant. The air is then directed into the aftercooler where it is cooled, the coalescing separator where liquid water is removed through the drain trap system, then into the drying tower where the air is actually dried to its final low dewpoint. The heating cycle lasts 90 minutes. Reference No. 145 Final Rev 8 Page 11 October 2005

12 SECTION 1: (Continued) 2. Stripping. At the end of heating, the inlet valves shift position, directing the hot inlet air directly into the aftercooler, separator, and drying tower. We now begin stripping. The stripping phase of regeneration lasts 90 minutes. At the beginning of stripping, the regenerating tower is depressurized through a muffler. During stripping, a small adjustable flow of dry air is used to remove the last little bit of moisture from the regenerating tower. If dryer is equipped with optional trim heater, reference operational instructions in Addendum at back of manual. Reference No. 145 Final Rev 8 Page 12 October 2005

13 SECTION 1: (Continued) 3. Cooling. At the end of stripping, the regenerating tower is repressurized. The cooling cycle valves open and cooling begins. The cooling cycle lasts 60 minutes. During cooling, a portion of the dry outlet air is directed into the regenerating tower to reduce the temperature of the bed prior to tower shift. Reference No. 145 Final Rev 8 Page 13 October 2005

14 SECTION 1: (Continued) Pressure vessel regulations The pressure vessels are designed according to the standard technical requirements. They fulfill the test of the certifying procedure and carry the U, UM ASME Symbol. Range of Application: Type Operating overpressure Operating Temperature Max. Max. Min. HC-3 HC PSIG 500 F 20 F Attention! Never weld on or alter a pressure vessel in any way! Airtightness test All adsorption dryers are subjected to an airtightness test prior to shipment using compressed air Overloading Attention! Protect the adsorption dryer from overloads! The adsorption dryer can become overloaded, if: The inlet flow is too high, The temperature of the air at the discharge of the aftercooler is too high, The min. operating pressure is too low, The temperature of the air at the discharge of the compressor is too low. Reference No. 145 Final Rev 8 Page 14 October 2005

15 SECTION 1: (Continued) Technical data sheet MODEL HC-3 HC-6 HC-7 HC-9 Flow 100 PSIG 100 F Drying Temperature Vessel OD Inches Desiccant type IR Activated Alumina Lbs. Desiccant / Vessel Inlet connection 2 NPT 2 NPT 3 FLG 3 FLG Outlet connection 2 NPT 2 NPT 3 FLG 3 FLG FILTER Afterfilter AF-350 AF-550 AF-1000 AF-1000 Voltage 115/1/60 Standard - Consult Factory for other voltages Cooling Water GPM Stripping Flow SCFM Cycle time 8 Hour NEMA Cycle 4 Hours drying/ 4 Hours Regeneration Outlet Dewpoint Variable DPDS Control High Humidity Alarm Adjustable Adjustable Pressure Switch Setpoints 10 PSI Fail to Shift 60 PSI Initiate Cooling Cooler outlet high temperature alarm 105 F Low regeneration temperature alarm Process flow Adjustable Downward Regeneration / Upward Drying Reference No. 145 Final Rev 8 Page 15 October 2005

16 SECTION 1: (Continued) Technical data sheet MODEL HC-14 HC-21 HC-30 HC-41 Flow 100 PSIG 100 F Drying Temperature Vessel OD Inches Desiccant type IR Activated Alumina Lbs. Desiccant / Vessel Inlet connection 3 FLG 4 FLG 4 FLG 6 FLG Outlet connection 3 FLG 4 FLG 4 FLG 6 FLG FILTER Afterfilter AF-1400 AF-2400 AF-3600 AF-7200 Voltage 115/1/60 Standard - Consult Factory for other voltages Cooling Water GPM Stripping Flow SCFM Cycle time 8 Hour NEMA Cycle 4 Hours drying/ 4 Hours Regeneration Outlet Dewpoint Variable DPDS Control High Humidity Alarm Adjustable Adjustable Pressure Switch Setpoint 10 PSI Fail to Shift 60 PSI Initiate Cooling Cooler outlet high temperature alarm 105 F Low regeneration temperature alarm Process flow Adjustable Downward Regeneration / Upward Drying Reference No. 145 Final Rev 8 Page 16 October 2005

17 SECTION 1: (Continued) Technical data sheet MODEL HC-54 HC-69 HC-85 HC-103 Flow 100 PSIG 100 F Drying Temperature Vessel OD Inches Desiccant type IR Activated Alumina Lbs. Desiccant / Vessel Inlet connection 6 FLG 6 FLG 8 FLG 8 FLG Outlet connection 6 FLG 6 FLG 8 FLG 8 FLG FILTER Afterfilter AF-7200 AF-7200 AF-7200 AF Voltage 115/1/60 Standard - Consult Factory for other voltages Cooling Water GPM Stripping Flow SCFM Cycle time 8 Hour NEMA Cycle 4 Hours drying/ 4 Hours Regeneration Outlet Dewpoint Variable DPDS Control High Humidity Alarm Adjustable Adjustable Pressure Switch Setpoint 10 PSI Fail to Shift 60 PSI Initiate Cooling Cooler outlet high temperature alarm 105 F Low regeneration temperature alarm Process flow Adjustable Downward Regeneration / Upward Drying Reference No. 145 Final Rev 8 Page 17 October 2005

18 SECTION 1: (Continued) Technical data sheet MODEL HC-122 HC-143 HC-166 Flow 100 PSIG 100 F Drying Temperature Vessel OD Inches Desiccant type IR Activated Alumina Lbs. Desiccant / Vessel Inlet connection 8 FLG 8 FLG 10 FLG Outlet connection 8 FLG 8 FLG 10 FLG FILTER Afterfilter AF AF AF Voltage 115/1/60 Standard - Consult Factory for other voltages Cooling Water GPM Stripping Flow SCFM Cycle time 8 Hour NEMA Cycle 4 Hours drying/ 4 Hours Regeneration Outlet Dewpoint Variable DPDS Control High Humidity Alarm Adjustable Adjustable Pressure Switch Setpoint 10 PSI Fail to Shift 60 PSI Initiate Cooling Cooler outlet high temperature alarm 105 F Low regeneration temperature alarm Process flow Adjustable Downward Regeneration / Upward Drying Reference No. 145 Final Rev 8 Page 18 October 2005

19 SECTION 1: (Continued) Dryer Flow Capacities Model Selection Chart: MODEL 85 PSI 90 PSI 95 PSI 100 PSI 105 PSI 110 PSI 115 PSI HC HC HC HC HC HC HC HC HC HC HC HC HC HC HC Note: Maximum operating pressure is 150 PSIG; higher pressures available as an option. Consult factory. Minimum Inlet Pressure (PSIG) Correction Factor CORRECTION FACTOR FOR COOLING WATER TEMPERATURE TEMPERATURE ºF Correction Factor To correct for a cooling water temperature other than 85 F, or an operating pressure other than 100 psig, multiply dryer capacity by the correction factors listed above. Example: To size for an inlet flow of Psig, using 90 F cooling water: Multiply 1300 * (1.1) * (1.2) = 1716 Use model HC-21 Reference No. 145 Final Rev 8 Page 19 October 2005

20 SECTION 1: (Continued) Transport After the adsorption dryer has been delivered, it must be checked for damage that may have occurred during transport. The Transport Company must be informed to register any damage. Shipping damage is not covered by any warranty Storage If the adsorption dryer is to be stored for a prolonged period of time, it should be stored in a dry place, preferably indoors; protected from the elements including freezing or extremely warm temperatures Use of a pre and afterfilter Use of a prefilter is not necessary with a heat-of-compression dryer. An afterfilter should be provided to prevent desiccant dust from migrating downstream. Reference No. 145 Final Rev 8 Page 20 October 2005

21 USER MANUAL SECTION 2: INSTALLATION 2.1 SET-UP AND INSTALLATION Once at the installation location, the adsorption dryers of the series HC-3 HC-239, which are supplied with a base frame, must be positioned so that all sides are easily accessible. Should vibrations occur on the installation location, the adsorption dryer is to be placed onto vibration dampeners. Since the adsorption dryer has already been completely wired at our factory, the customer only has to connect the power supply cable to the terminal strip according to the supplied wiring diagrams. Advice Should you still have questions regarding installation, you can request installation blueprints separately from Ingersoll-Rand Davidson NC. Warning! Use the appropriate, load-rated lifting equipment and observe safe lifting procedures during all operations of installation. The equipment should be unloaded as close as possible to the installation site to minimize any chances of equipment damage. Reference No. 145 Final Rev 8 Page 21 October 2005

22 SECTION 2: (Continued) Mechanical installation The equipment should be located in an area as practically possible with adequate clearances for service. An overhead clearance of not less than three feet above each adsorber tower is required for loading of the desiccant. Access clearance of three feet in front of the control panel should be provided. Insulate the pipe between the compressor and dryer to minimize heat loss. Remove all protective shipping crates, flange covers, etc. Utilizing the mounting holes provided on the skid, anchor the Ingersoll-Rand type HC Dryer to a solid, level foundation designed to support the dryer. Do not hydrostatically test the pressure vessels. All HC dryers pressure vessels are hydrostatically tested at one and one-half times the design pressure after fabrication and before assembly. Desiccant is shipped loose (HC-41 and above) and must be installed. Refer to section 4.2 for installation of desiccant. If the equipment is installed in a high traffic area, protective barriers may be required to prevent possible damage of equipment and to prevent contact with hot surfaces. Because of vibration during shipping, some tube fittings may have loosened; therefore, inspect all connections and tighten if required. Also, flange connections may have loosened; therefore tighten all flange bolts. Ensure that the inlet and outlet connections to and from the Ingersoll-Rand type HC Dryer are made using the correct rated fittings and piping to meet the design conditions. System isolation and by-pass valves should be installed. If not supplied as part of the equipment package by Ingersoll-Rand, they should be supplied and installed by others. It must be verified that these exist, so that future servicing of the Dryer System may take place. Full flow relief valves to protect the system from over-pressure must be provided by others in accordance with local regulations. The purge exhaust connection on the HC larger dryers may be connected to a vent header. To ensure satisfactory regeneration of the desiccant chambers is achieved, the purge exhaust piping should be sized as follows to prevent "back pressure" build up. Installed length of exhaust pipe Up to 10 Ft Up to 25 Ft Up to 50 Ft Up to 100 Ft Pipe size required Same size as the dryer exhaust One size larger than dryer exhaust Two sizes larger than dryer exhaust Three sizes larger than dryer exhaust Reference No. 145 Final Rev 8 Page 22 October 2005

23 SECTION 2: (Continued) Filter installation dryers are shipped with the afterfilter loose or with the filter skid mounted on a separate steel frame. The following installation applies to all models that are shipped with filters loose. Afterfilter Installation Mount afterfilter in such a way as to allow clearance for the element installation and removal. The filter must be piped so that the correct flow direction indicated on the filter is followed. Ensure that all piping and valves are equivalent or larger in size to the dryer inlet connection. Filter Skid with 3-Valve Bypass Installation Filters skid should be located as close to dryer as possible. Use the skid bolt holes to secure the assembly. Ensure that the skid is located such that the 3-valve bypass will bypass the dryer and filters when in use. Check the flow direction of each filter to ensure the after filter is connected to the outlet pipe of the dryer. Connect the filter skid piping and dryer skid piping using materials and fabrication procedures that are suitable for compressed air pressure piping. All flanges are ANSI B16.5 Class 150 Raised Face flanges. Reference No. 145 Final Rev 8 Page 23 October 2005

24 SECTION 2: (Continued) Electrical installation Connect the dryer to a correctly sized power supply. The dryer requires a 115V 60 cycle connection. A disconnect switch is not provided with the dryer and must be supplied by end user in accordance with the recognized electrical codes. Ground the frame of the dryer in accordance with the recognized electrical codes. It is recommended that the common alarm relay, located in the dryer control panel, be connected to the control room or operator station so that an immediate response to the dryer alarm may be given when required. Reference No. 145 Final Rev 8 Page 24 October 2005

25 SECTION 3: START UP AND OPERATION 3.1 START UP Attention! All pipes and wire connections are to be tightened! Furthermore, before start-up: The pipes must be checked for the presence of scale, abraded material from the threading, or other similar impurities. All shut off valves on the adsorption dryer, after-filter and on the bypass line should be closed. The ambient temperature must not be less than 33 F. Breakdowns resulting from faulty installation do not fall under Ingersoll-Rand's warranty obligation Pressurizing dryer Prior to pressurizing the Ingersoll-Rand Dryer system, verify the following: - Dryer On Off switch is in the off position. - System outlet block valve is closed. - Cooling water is turned on to the aftercooler. Slightly open the inlet isolation valve slowly admitting compressed air to the system. When full system operating pressure has been reached all connections should be soap bubble tested for leaks. Any leaks should be repaired and retested prior to placing the equipment in service. If some gas other than the process air will be used for leak testing, consult Ingersoll-Rand for its compatibility with system components before proceeding. Fully open the inlet isolation valve. When the system is filled with process air, is leak tight and start-up is completed, then slowly open the system outlet valve to pressurize the downstream piping. During the procedure, ensure that the dryer system pressure does not fall below 95% of its reading prior to opening the system outlet valve. This will protect the equipment internal components (i.e. filter elements, desiccant) from gas velocities above design conditions. Reference No. 145 Final Rev 8 Page 25 October 2005

26 SECTION 3: (Continued) Pressurizing dryer (Continued) When pressurizing is complete then fully open the system outlet valve to place the equipment in service. Verify the system inlet pressure and temperature are at the design operating levels Energizing dryer controls Turn ON-OFF switch to the ON position. A Micrologix programmable controller with individual input/output modules controls the dryer cycle. A copy of the program complete with a full listing of inputs, outputs, internal coils, timers and counters is included later in this manual. This should be used as a reference guide to ensure dryer is cycling. A manual mode is included in the dryer program to allow for fast cycling to verify the operation of the dryer. While dryer is in the stripping mode for either chamber, the regeneration flow setting should be checked. The stripping flow valve should be set at 1.5 turns open at start-up and adjusted as necessary to maintain the specified dewpoint. The pressure gauge on the regenerating tower should not exceed 10 psig. Warning! Failure to correctly set the stripping flow can lead to improper regeneration of the desiccant bed, resulting in a dewpoint failure when that chamber is returned to service. It is recommended that the operational program of the dryer and the wiring schematic be studied before operating the dryer. NOTE : If the DPDS (Dewpoint Demand System) option is purchased, reference the DPDS Installation and Operating Guide for instructions. Reference No. 145 Final Rev 8 Page 26 October 2005

27 SECTION 3: (Continued) 3.2 OPERATOR INTERFACE Function keys F1 through F4 perform the function displayed on the screen. ARROWS ALLOW USER TO SCROLL UP OR DOWN INSIDE OF THE SCREEN LIST SELECTOR. AN ARROW ON THE RIGHT SIDE OF THE SCREEN NAMES INDICATES WHICH SCREEN IS BEING SELECTED. ENTER=> SELECTS THE SCREEN IN WHICH THE ARROW IS POINTING AND DISPLAYS THAT SCREEN. Reference No. 145 Final Rev 8 Page 27 October 2005

28 SECTION 3: (Continued) Main Screen This is the main screen. This screen will be displayed upon initial startup or after an alarm has been cleared. Using the up or down arrow keys and the enter key you may select a screen to view Status This screen will give you the dryer s current status. The top line will tell you which tower is onstream. The second line is the regeneration cycle in which the opposite tower (regenerating) is in. This will toggle from HEATING to STRIPPING to REPRESSURIZATION to COOLING. If the optional dewpoint demand system (DPDS) is installed, you may also see STANDBY below the current tower status. The lower left hand corner gives the time remaining in the current regeneration cycle. This starts counting down from 240 minutes (four hours). Note: When the dryer is in DPDS Standby, the time remaining will read zero. The lower right hand corner is another screen selector list. This list is the same as the one on the MAIN screen, except it only displays one screen name at a time. Use the up or down arrow key to select the screen name you would like to go to then press the enter key. Reference No. 145 Final Rev 8 Page 28 October 2005

29 SECTION 3: (Continued) Settings The settings screen allows you to toggle between Dewpoint Demand and straight Time cycle. While in Time cycle, the dryer will shift towers every four hours. When utilizing the optional DPDS, the dryer will complete its four hour regeneration and go into a standby mode until the outlet dewpoint has reached the dewpoint monitor s set point. When dewpoint demand is not purchased, this screen will not be available Alarms The alarm screen will display any and all alarms. Alarms are displayed in the order in which they occur, for instance the top alarm is always the most recent one. When an alarm situation occurs, this screen will automatically be displayed. When an alarm clears, the operator interface will automatically return to the MAIN screen. The optional fail-to-shift alarm comes with an alarm horn. The F4 key will allow an operator to disable this horn while they are in the area to fix the alarm condition. When fail-to-shift is not purchased, this function will not be present. Using the other function keys, per the above designations, you may toggle to any other screen. When screen is switched with a pre-existing alarm, this alarm screen will not automatically pop back up until all alarms are cleared. Reference No. 145 Final Rev 8 Page 29 October 2005

30 3.3 PROGRAM STEPS: (Continued) Part numbers for the instrument abbreviations listed in the program steps below (i.e. V1, V2, etc.) can be found in the Spare Parts List in Section 5 of this User Manual. STEP TIME DESCRIPTION OF ACTION 1 0 min. De-energize SV1-2 Energize SV1-1; Opens V3, 6, 8 & 9 Closes V4, 5, 7 & 10 Left Tower Onstream Start time delay of 60 seconds; When time delay times out if pressure switch PS2 is greater than 10 Fail to Shift alarm 2 2 min. De-energize SV2-2 Energize SV2-1; Opens V1 & 15 Closes V2 Heating Right Tower 3 90 min. De-energize SV2-1 Energize SV2-2; Opens V2 Closes V1 & 15 Energize SV4-1; Opens V12 Energize SV3-1; Opens V11 Stripping Right Tower min. De-energize SV4-1; Closes V12 Re-pressurizing Right Tower When PS3 reaches setpoint of 60 PSI then, Energize SV5-1; Opens V13 Cooling Right Tower min. If dewpoint is below the analyzer set-point and the Dewpoint/Timer selector switch is on Dewpoint then; Begin standby Standby Reference No. 145 Final Rev 8 Page 30 October 2005

31 3.3 PROGRAM STEPS: (Continued) min. If the dewpoint rises above the analyzer set-point or the Dewpoint/ +stdby Timer selector switch is on Timer then; De-energize SV5-1; Closes V13 De-energize SV1-1 Energize SV1-2 Opens V4, 5, 7 & 10 Closes V3, 6, 8 & 9 Right Tower Onstream Start time delay of 60 seconds; When time delay times out if pressure switch PS2 is greater than 10 Fail to Shift alarm min. De-energize SV2-2 Energize SV2-1; Opens V1 & 15 Closes V2 Heating Left Tower min. De-energize SV2-1 Energize SV2-2; Opens V2 Closes V1 & 15 Energize SV4-1; Opens V12 Energize SV3-1; Opens V11 Stripping Left Tower min. De-energize SV4-1; Closes V12 Re-pressurizing Left Tower When PS3 reaches setpoint of 60 PSI then, Energize SV5-1; Opens V13 Cooling Left Tower min. If dewpoint is below the analyzer set-point and the Dewpoint/Timer selector switch is on Dewpoint then; Begin standby Standby Reference No. 145 Final Rev 8 Page 31 October 2005

32 3.3 PROGRAM STEPS: (Continued) min. If the dewpoint rises above the analyzer set-point or the Dewpoint/ +stdby Timer selector switch is on Timer then; De-energize SV5-1; Closes V13 GOTO STEP 1 NOTES: 1.) At any time during the cycle, if Inlet temperature (TH1) drops below the setpoint (240 F) then; Low Regeneration Temperature Alarm 2.) At any time during the cycle, if the cooler outlet temperature (TS1) rises above the setpoint (105 F) then; High Cooler Outlet Temperature Alarm 3.) At any time during the cycle, if the dewpoint (DPDS) rises above the setpoint (-20 F) for more than five continuous minutes then; High Dewpoint Alarm 4.) At any time during the cycle, if the compressor goes unloaded (CR1) then stop the timing cycle of the dryer until the compressor is loaded. Reference No. 145 Final Rev 8 Page 32 October 2005

33 USER MANUAL SECTION 4: MAINTENANCE Advice: In order to ensure continuous and trouble-free operation, a maintenance contract with Ingersoll-Rand is recommended. 4.1 SUGGESTED PREVENTIVE MAINTENANCE SCHEDULE Introduction The compressed air dryer requires a minimum of maintenance as most components are "maintenance-free". However, a certain amount of "preventive maintenance" is recommended to assure years of trouble-free, highperformance service Periodic Maintenance Schedule Whereas it is recommended that the dryer be observed and inspected as often as it is practical, the following is a minimum requirement: A. EVERY 2000 HOURS OR 3 MONTHS 1. Check the inlet air temperature; make adjustments, if necessary. 2. Check the air temperature at intercooler outlet; above 100 F means: a. Increase the cooling water flow. b. Lower the cooling water temperature. c. Back flush and thoroughly clean the intercooler, to restore efficiency. 3. "Blow off" the vessel relief valves to assure their integrity. 4. Test the drain trap assembly and drain the sump at the separator drain of sludge that may have accumulated by closing off the primary drain until the secondary valve actuates. All of the above can be accomplished while the dryer is operating. B. EVERY 4000 HOURS OR 6 MONTHS 1. Perform steps 1 through 4 as outlined in "Every 2000 Hours or 3 Months". Reference No. 145 Final Rev 8 Page 33 October 2005

34 SECTION 4: (Continued) 2. Isolate and depressurize the dryer. 3. Disconnect power to the dryer. 4. Replace afterfilter elements (the proper number and quantity is indicated on the filter and in the Spare Parts List in Section V of this manual). 5. Make certain all air and electrical connections are sound. 6. Repressurize the dryer and place "on stream". 7. Reconnect power to the dryer. C. EVERY 8000 HOURS OR 12 MONTHS 1. Perform steps 1 through 4 as outlined in "Every 4000 Hours or 6 Months". DO NOT REPRESSURIZE DRYER OR RECONNECT POWER TO THE DRYER YET! 2. Rebuild the actuators by installing repair kits in the major switching valves. (V1-V13 and V15) 3. Carefully disassemble and clean the solenoid valves in the control group; rebuild with new parts only if damage or serious wear is evident. 4. Carefully disassemble and clean the 3-way solenoid valve on the separator drain trap. 5. Rebuild the secondary drain valve by installing a valve repair kit. (SD - P/N ) 6. Disassemble and clean the primary drain. (FT) 7. It is recommended that the aftercooler be back-flushed and thoroughly cleaned, both tubeside and shellside, at 8,000 hours; but this interval should be adjusted shorter or longer, based on water quality and plant experience. Reference No. 145 Final Rev 8 Page 34 October 2005

35 SECTION 4: (Continued) 8. If the DPDS option is purchased, refer to the DPDS Installation and Operating Guide for instructions. 9. Make certain all air, electric, and water connections are sound. 10. Open the cooling water supply valve and adjust as required. 11. Repressurize the dryer and place "on-stream". 12. Reconnect power to the dryer. D. EVERY 16,000 HOURS OR 24 MONTHS 1. Perform steps 1 through 9 as outlined in "Every 8000 Hours or 12 Months. DO NOT REPRESSURIZE DRYER OR RECONNECT POWER TO THE DRYER YET! 2. Drain all the desiccant from both vessels through the drain at the bottom of each vessel. 3. Refill both vessels with the proper amount of desiccant as noted in the specifications at the front of this manual. NOTE: Desiccant can be purchased only through Ingersoll-Rand distributors authorized to sell dryers and related products. 4. Make certain all air, electric, and water connections are sound. 5. Open the cooling water supply valve and adjust as required. 6. Repressurize the dryer and place "on-stream". 7. Reconnect power to the dryer. Reference No. 145 Final Rev 8 Page 35 October 2005

36 SECTION 4: (Continued) D. ADJUSTMENTS The inlet air temperature (as indicated on the Instrument Panel) should be adjusted to obtain the desired temperature/dewpoint performance (reference the Regenerative Dryer Specification Sheet in Section I). This can be accomplished through manipulation of the inlet piping insulation and/or the compressor intercooling. The temperature of the air leaving the dryer aftercooler should be maintained at or below 90 F. Adjust the cooling water supply as required. 4.2 REPLACEMENT / DISPOSAL OF THE DESICCANT NOTE : Refer to the desiccant MSDS in the appendix of this manual for detailed information regarding material description and ingredients. The dryer is filled from the top and emptied from the bottom. Refer to the General Arrangement drawing for location of fill and drain ports. To drain the desiccant, remove the drain plug/cover and catch the old desiccant in a suitable container. Replace the desiccant drain plug/cover. Remove the fill cap and refill the chamber with the specified desiccant. Refer to the spare parts section for desiccant quantity. Do not tamp the desiccant. Replace the fill cap. Soap test both fill and drain ports for leaks before returning the dryer to service. Reference No. 145 Final Rev 8 Page 36 October 2005

37 SECTION 4: (Continued) 4.3 DEWPOINT METER MAINTENANCE (DPDS Option only) NOTE: Refer to the Dewpoint Demand Installation & Operating Guide included with this User Manual for information on dewpoint meter maintenance and operation. 4.4 FILTERS General comments and use Filters of the series AF are suitable for filtering solids out of compressed air and other neutral, compressed gases. This new filtration concept is characterized by high flows at low differential pressure Function The soiled medium flows through the filter element "Series AF" from the outside to the inside. Solids are filtered out by impact or by the effect of inertia Assembly and installation Advice The piping system must be cleaned before assembling filter. The filter must always be installed vertically Maintenance Advice The filter element should be replaced when a differential pressure of > 10 PSID has been reached or, at latest, after 6 months of operation. Reference No. 145 Final Rev 8 Page 37 October 2005

38 SECTION 4: (Continued) Changing of filter elements Danger! The soiled filter elements are changed only when the housings are DEPRESSURIZED! Filter elements are to be changed according to the following steps: Open the hand hole. Loosen and remove the element by hand. Install the new element and make sure that the element seats perfectly. Re-install hand hole cover. Elements of the AF series can NOT be cleaned with compressed air Accessories Advice Pressure differential gauge: Indicates the degree to which the elements are soiled. Reference No. 145 Final Rev 8 Page 38 October 2005

39 SECTION 5: RECOMMENDED SPARE PARTS LIST 5.1 RECOMMENDED SPARE PARTS FOR HC-3 TO HC-14 Part No. Description ID HC-3 HC-6 HC-7 HC-9 HC Probe, for Dewpoint Demand option Thermocouple, armoured, Filter, particle removal, miniature, inline, ¼, for DPDS option SB350 filter element for AF afterfilter B filter element D33 filter element, high efficiency, coalescing, for HEF-60 prefilter Fuse, 3 amp Muffler, 2 MNPT Relay, DPDT, 115/1/ Gasket, grafoil, 3, 150#, ring, 1/ Gasket, grafoil, 6, 150#, ring, 1/ Gasket, grafoil, 3, 150#, FF, 1/ Switch, pressure, PSIG Switch, pressure, 3-30#, SPDT, for Fail-to-shift Alarm option Repair kit, actuator, CTD&S-020 V Repair kit, actuator, CTD&S-030 V Repair kit, actuator, CTD&S-040 V1-10, Repair kit, actuator, CTS-050 V Repair kit, ball valve, 1 V Repair kit, ball valve, 1½ V Repair kit, ball valve, 2 V1-10, Repair kit, butterfly valve, 3 V1-10, Repair kit, actuator, MX-60 V1-10, Repair kit, diaphragm valve, ¾ SD Valve, ¼ solenoid single coil 4-way, SV aluminum Valve, ¼ solenoid dual coil 4-way, aluminum SV Part No. Description Alumina, 3/16" IR Activated 50 lbs bag Alumina, 3/16" IR Activated 2000 lbs sack Reference No. 145 Final Rev 8 Page 39 October 2005

40 SECTION 5: (Continued) RECOMMENDED SPARE PARTS LIST 5.1 RECOMMENDED SPARE PARTS FOR HC-21 TO HC-54 Part No. Description ID HC-21 HC-30 HC-41 HC Probe, for Dewpoint Demand option Thermocouple, armoured, Filter, particle removal, miniature, inline, ¼, for DPDS option B filter element D33 filter element, high efficiency, coalescing, for HEF-60 prefilter Fuse, 3 amp Seal, gasket, Manway, 11x15, PTFE Seal, gasket, Manway, 12x16, PTFE Muffler, 2 MNPT Relay, DPDT, 115/1/ Gasket, grafoil, 3, 150#, ring, 1/ Gasket, grafoil, 4, 150#, ring, 1/ Gasket, grafoil, 6, 150#, ring, 1/ Gasket, grafoil, 8, 150#, ring, 1/ Gasket, grafoil, 10, 150#, ring, 1/ Gasket, grafoil, 12, 150#, ring, 1/ Gasket, grafoil, 4, 150#, FF, 1/ Gasket, grafoil, 6, 150#, FF, 1/ Switch, pressure, PSIG Switch, pressure, 3-30#, SPDT, for Fail-to-shift Alarm option Repair kit, actuator, CTD&S-040 V Repair kit, actuator, CTS-050 V Repair kit, actuator, CTS-060 V Repair kit, ball valve, 2 V Repair kit, butterfly valve, 3 V Repair kit, actuator, MX-200 V1-10, Repair kit, actuator, MX-60 V1-10, Repair kit, actuator, MX-60 V Repair kit, butterfly valve, 4 V1-10, Repair kit, butterfly valve, 6 V1-10, Check valve, 3, CI, rebuilt CV Repair kit, diaphragm valve, ¾ SD Valve, ¼ solenoid single coil 4-way, SV aluminum Valve, ¼ solenoid dual coil 4-way, aluminum SV Part No. Description Alumina, 3/16" IR Activated 50 lbs bag Alumina, 3/16" IR Activated 2000 lbs sack Reference No. 145 Final Rev 8 Page 40 October 2005

41 SECTION 5: (Continued) RECOMMENDED SPARE PARTS LIST 5.1 RECOMMENDED SPARE PARTS FOR HC-69 TO HC-122 Part No. Description ID HC-69 HC-85 HC-103 HC Probe, for Dewpoint Demand option Thermocouple, armoured, Filter, particle removal, miniature, inline, ¼, for DPDS option B filter element D33 filter element, high efficiency, coalescing, for HEF-60 prefilter Fuse, 3 amp Seal, gasket, Manway, 12x16, PTFE Muffler, 2 MNPT Relay, DPDT, 115/1/ Gasket, grafoil, 3, 150#, ring, 1/ Gasket, grafoil, 4, 150#, ring, 1/ Gasket, grafoil, 6, 150#, ring, 1/ Gasket, grafoil, 8, 150#, ring, 1/ Gasket, grafoil, 12, 150#, ring, 2 1/ Gasket, grafoil, 14, 150#, ring, 2 1/ Gasket, grafoil, 16, 150#, ring, 2 2 1/ Gasket, grafoil, 6, 150#, FF, 1/ Gasket, grafoil, 8, 150#, FF, 1/ Switch, pressure, PSIG Switch, pressure, 3-30#, SPDT, for Fail-to-shift Alarm option Repair kit, actuator, CTS-050 V Repair kit, actuator, CTS-060 V Repair kit, ball valve, 1 ½ V Repair kit, butterfly valve, 3 V Repair kit, actuator, MX-200 V1-10, Repair kit, actuator, MX-60 V Repair kit, actuator, MX-450 V1-10, Repair kit, butterfly valve, 4 V11,13, Repair kit, butterfly valve, 6 V1-10, Repair kit, butterfly valve, 8 V1-10, Check valve, 3, CI, rebuilt CV Check valve, 4, CI, rebuilt CV Repair kit, diaphragm valve, ¾ SD Valve, ¼ solenoid single coil 4-way, SV aluminum Valve, ¼ solenoid dual coil 4-way, aluminum SV Part No. Description Alumina, 3/16" IR Activated 50 lbs bag Alumina, 3/16" IR Activated 2000 lbs sack Reference No. 145 Final Rev 8 Page 41 October 2005

42 SECTION 5: (Continued) RECOMMENDED SPARE PARTS LIST 5.1 RECOMMENDED SPARE PARTS FOR HC-143 TO HC-239 Part No. Description ID HC-143 HC-166 HC-186 HC-211 HC Probe, for Dewpoint Demand option Thermocouple, armoured, Filter, particle removal, miniature, inline, ¼, for DPDS option B filter element D33 filter element, high efficiency, coalescing, for HEF-60 prefilter Fuse, 3 amp Seal, gasket, Manway, 12x16, PTFE Muffler, 2 MNPT Relay, DPDT, 115/1/ Gasket, grafoil, 4, 150#, ring, 1/ Gasket, grafoil, 6, 150#, ring, 1/ Gasket, grafoil, 8, 150#, ring, 1/ Gasket, grafoil, 10, 150#, ring, 1/ Gasket, grafoil, 18, 150#, ring, 1/ Gasket, grafoil, 20, 150#, ring, 1/ Gasket, grafoil, 8, 150#, FF, 1/ Gasket, grafoil, 10, 150#, FF, 1/ Switch, pressure, PSIG Switch, pressure, 3-30#, SPDT, for Fail-to-shift Alarm option Repair kit, actuator, CTS-050 V Repair kit, actuator, CTS-060 V Repair kit, actuator, CTS-060 V Repair kit, actuator, CTS-065 V Repair kit, ball valve, 1 ½ V Repair kit, ball valve, 2 V Repair kit, actuator, MX-200 V Repair kit, actuator, MX-60 V Repair kit, actuator, MX-750 V1-10, Repair kit, actuator, MX-450 V1-10, Repair kit, butterfly valve, 4 V11,13, Repair kit, butterfly valve, 6 V11,13, Repair kit, butterfly valve, 8 V1-10, Repair kit, butterfly valve, 10 V1-10, Check valve, 4, CI, rebuilt CV Check valve, 6, CI, rebuilt CV Repair kit, diaphragm valve, ¾ SD Valve, ¼ solenoid single coil 4-way, SV aluminum Valve, ¼ solenoid dual coil 4-way, aluminum SV Part No. Description Alumina, 3/16" IR Activated 50 lbs bag Alumina, 3/16" IR Activated 2000 lbs sack Reference No. 145 Final Rev 8 Page 42 October 2005

43 SECTION 5: (Continued) I-R Theory of Operation Illustration Legend: BE = visual moisture indicator CS = separator F = filter FS = float switch FT = primary float trap P = pressure gauge PRV = pressure relief valve SD = secondary drain SV = solenoid valve T = temperature gauge TW = thermowell V = valve Reference No. 145 Final Rev 8 Page 43 October 2005

44 SECTION 6: TROUBLESHOOTING & FAULTS 6.1 INTRODUCTION Following proper preventive maintenance procedures will go far toward assuring trouble-free dryer performance; however, failures will still occur. This troubleshooting part will help to identify the source of the problem and to effect a remedy. 6.2 HIGH DEWPOINT Changed Operating Conditions Check to see that flow rate, pressure, and temperature are still within specification Old Desiccant If the dryer is not able to maintain dewpoint for a sufficiently long period, the desiccant may have aged to the point where its capacity is inadequate. Replace the desiccant with the appropriate quantity and type of desiccant Towers Not Reversing Check PLC, solenoid valve, inlet switching valves, and, if supplied, Dewpoint Demand System meter Cooler Discharge Air Temperature Too High Check cooling water flow rate and temperature. Fouled or dirty cooler may require cleaning on air and/or water side Dewpoint Indication In Error Check calibration/operation of dewpoint measuring instrument. Reference No. 145 Final Rev 8 Page 44 October 2005

45 SECTION 6: (Continued) Two-way Valve Leakage Valve leakage here will allow relatively wet inlet air to leak into the dry outlet air stream, thereby raising the dewpoint of the composite air. Compare the dewpoint of the air at the dryer outlet to the dewpoint measured at the top (outlet) of the drying tower (i.e., at the relief valve location). If there is a significant difference in dewpoint, one or both closed 2-way valves is leaking. Check actuator operation and check for seat wear. 6.3 FAIL-TO-SHIFT Solenoid Valve Failed To Operate Check electrical connection, coil, and valve seat Pilot Air Tubing Leakage Check tubing fittings for leakage Two-way Switching Valve Actuator Leakage A leaking actuator can cause the switching valve to malfunction; low pilot pressure due to leakage (or solenoid valve failure) will cause the FAIL-TO- SHIFT ALARM to activate. Check for leakage. 6.4 PRIMARY DRAIN FAILURE Plugging Or Sticking Due To Foreign Matter If the PRIMARY DRAIN FAILURE ALARM activates, the probable cause is sediment plugging the orifice or impeding the proper operation of the float. Disassemble, inspect, and clean as necessary. Reference No. 145 Final Rev 8 Page 45 October 2005

46 SECTION 6: (Continued) 6.5 SECONDARY DRAIN FAILURE Solenoid Valve Failure When the liquid level rises above the primary float valve elevation and contacts the liquid level probe, a circuit is completed energizing the 3-way normally open solenoid valve depressurizing the secondary drain valve actuator. The system pressure should open the secondary drain valve. If the PRIMARY DRAIN FAILURE ALARM activates, but the secondary drain valve fails to open, check the 3-way normally open solenoid valve. Clean, repair, or replace as necessary Liquid Level Probe Failure If the PRIMARY DRAIN FAILURE ALARM does not activate after or during failure of the float operated drain, check the liquid level probe for proper operation. 6.6 SHORT-TERM SHUT-DOWN Advice The following sequence is to be heeded when switching off the adsorption dryer: First close all the shut off valves up and downstream of dryer Then immediately switch off the adsorption dryer. Attention! Dryer will remain pressurized. 6.7 SHUT-DOWN IN CASE OF A FAULT OR FOR MAINTENANCE Danger! Before any kind of maintenance or repair work is done, the adsorption dryer must be depressurized and disconnected from the power source. Apply the general safety regulations! Reference No. 145 Final Rev 8 Page 46 October 2005

HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL

HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL H-Series & 203 THRU 223 SERIES ARROW PNEUMATICS, INC. REGENERATIVE DRYER DIVISION 2111 WEST 21ST STREET BROADVIEW, IL 60155 708-343-9595 708-343-1907

More information

EXHAUST PURGE DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL MODEL RE-231 THROUGH RE-252

EXHAUST PURGE DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL MODEL RE-231 THROUGH RE-252 EXHAUST PURGE DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL MODEL RE-231 THROUGH RE-252 ARROW PNEUMATICS, INC. REGENERATIVE DRYER DIVISION 500 NORTH OAKWOOD RD LAKE ZURICH, IL,60047 PHONE # (847)

More information

HEATLESS REGENERATIVE DRYERS

HEATLESS REGENERATIVE DRYERS HEATLESS REGENERATIVE DRYERS PHL SERIES Pioneer Air Systems Inc. 210, Flatfork Road, Wartburg, TN - 37887 Tel. : (423) 346-6693 Fax : (423) 346-3865, (423) 346-7522 Email : sales@pioneerair.com Internet

More information

SECTION AIR COMPRESSORS AND ACCESSORIES

SECTION AIR COMPRESSORS AND ACCESSORIES PART 1 GENERAL 1.01 WORK INCLUDED SECTION 11370 AIR COMPRESSORS AND ACCESSORIES A. This specification includes air compressors with air dryers. B. Furnish, install, start-up, and test air compressors and

More information

MR Series Heatless Mini Regenerative Desiccant Dryer. Operator s Manual

MR Series Heatless Mini Regenerative Desiccant Dryer. Operator s Manual MR Series Heatless Mini Regenerative Desiccant Dryer Operator s Manual Introduction Many years of trouble-free service can be expected from your Numatics regenerative dryer. Superior dew point depression

More information

WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS

WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS INSTRUCTION MANUAL FOR WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS DE3 - DE5 OPERATIONS GENERAL This instruction manual covers the installation, operation, maintenance and troubleshooting

More information

INGERSOLLrAND AIR COMPRESSORS CAUTION: HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS

INGERSOLLrAND AIR COMPRESSORS CAUTION: HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS INGERSOLLrAND AIR COMPRESSORS HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS CAUTION: For HMD Models 84 Through 385 ONLY 1. Remove Dryer Chambers And Protective

More information

Fred C. Gilbert Co. 106 Norris Road Bakersfield, Ca fax

Fred C. Gilbert Co. 106 Norris Road Bakersfield, Ca fax A R R O W P N E U M A T I C S Fred C. Gilbert Co. 106 Norris Road Bakersfield, Ca. 93308 661-399-9569 fax 661-393-9654 F I L T E R S R E G U L A T O R S L U B R I C A T O R S A C C E S S O R I E S H E

More information

Heatless Regenerative Air Dryers

Heatless Regenerative Air Dryers Heatless Regenerative Air Dryers CPAD Series / CPADM Series Owner s Manual Jan. 2009 DATE OF PURCHASE MODEL SERIAL NO. Record above information from nameplate. Retain this information for future reference.

More information

SERIES TZ TZ820 - TZ1710 EMS OPTION LDP OPTION 3V OPTION. TZ Heatless Desiccant Compressed Air Dryers

SERIES TZ TZ820 - TZ1710 EMS OPTION LDP OPTION 3V OPTION. TZ Heatless Desiccant Compressed Air Dryers SERIES TZ TZ820 - TZ1710 EMS OPTION LDP OPTION 3V OPTION TZ Heatless Desiccant Compressed Air Dryers More Than Air. Answers. Online answers: http://www.air.irco.co Phone : 1-800-526-3615 Form :APDD 789

More information

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings. SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.

More information

HEATLESS REGENERATIVE COMPRESSED AIR DRYER models THL-200 through THL- 5000

HEATLESS REGENERATIVE COMPRESSED AIR DRYER models THL-200 through THL- 5000 P.O Box 879 50 W. 6th Ave. - unit P Broomfield, CO 8008 Phone:0-65-06 Order Entry Fax: 0-65-99 www.airdryers.com INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR HEATLESS REGENERATIVE COMPRESSED AIR DRYER

More information

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100 HTD High Temperature Non-Cycling Refrigerated Compressed Air Dryers Operation & Maintenance Manual MODELS HTD 21 thru HTD 100 - TABLE OF CONTENTS - 1.0 GENERAL 2 1.1 How to use this manual 1.2 Symbols

More information

ZPA Heatless Regeneration ZHA Heated Regeneration ZBA Heated Blower Regeneration

ZPA Heatless Regeneration ZHA Heated Regeneration ZBA Heated Blower Regeneration INNOVATIVE COMPRESSED AIR SOLUTIONS TM DESICCANT AIR DRYERS 90-8000 scfm ZPA Heatless Regeneration ZHA Heated Regeneration ZBA Heated Blower Regeneration www.zeks.com RELIABLE PERFORMANCE. DESIGN INNOVATION.

More information

Heated Desiccant Air Dryer

Heated Desiccant Air Dryer OWNERS MANUAL F-0073 HEATED DESICCANT AIR DRYER Heated Desiccant Air Dryer MODELS RE231-RE250 ARROW PNEUMATICS Table of Contents Unpacking/Application/Analysis 3 Specifications 4 Dimensional Drawings 5-6

More information

OPERATING MANUAL MODEL AIR 1500TM AIR DRYER

OPERATING MANUAL MODEL AIR 1500TM AIR DRYER OPERATING MANUAL MODEL AIR 500TM AIR DRYER Puregas, LLC 226-A Commerce St. Tel: 800-52-535 Broomfield, Colorado Fax: 303-657-2205 P/N P0255 REV A, 02/9/4 TABLE OF CONTENTS.0 GENERAL... 3 2.0 SPECIFICATIONS...

More information

MDH Series Air Dryer. User s Guide

MDH Series Air Dryer. User s Guide MDH Series Air Dryer User s Guide Models covered: MDH1 MDH2 MDH3 MDH4 MDH5 MDH6 1. Welcome & Congratulations Congratulations on your purchase of a new PUREGAS MDH SERIES AIR DRYER! We here at PUREGAS

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

Externally Heated Exhaust Purge Regenerative Compressed Air Dryer

Externally Heated Exhaust Purge Regenerative Compressed Air Dryer Externally Heated Exhaust Purge Regenerative Compressed Air Dryer Provides safety and reliability Designed for medium flow rates Conservative design for optimal energy efficiency and savings World Leader

More information

VSA Series Air Dryer. User s Guide

VSA Series Air Dryer. User s Guide VSA Series Air Dryer User s Guide Models covered: VSA1 VSA2 VSA3 VSA4 1. Welcome & Congratulations Congratulations on your purchase of a new PUREGAS VSA SERIES AIR DRYER! We here at PUREGAS are very proud

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR DRY PAK PACKAGED COMPRESSED AIR TREATMENT SYSTEM MODEL: DPP-150 WARNING

INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR DRY PAK PACKAGED COMPRESSED AIR TREATMENT SYSTEM MODEL: DPP-150 WARNING January 207 80-572 Rev - 2950 Mechanic Street Lake City, PA 6423 USA Phone: -800-840-9906 Fax: 84-774-0778 Email: info@vanairsystems.com www.vanairsystems.com INSTALLATION, OPERATION & MAINTENANCE MANUAL

More information

Equipment Designed for Industrial Applications

Equipment Designed for Industrial Applications Equipment Designed for Industrial Applications Industrial equipment with moving components requires maintenance. As a manufacturer of industrial equipment we strive to produce a product that operates as

More information

150-3,000 scfm AEHD Series. Desiccant Air Dryers AEHD Series. Externally Heated Desiccant Air Dryer 150-3,000 scfm. Front Page

150-3,000 scfm AEHD Series. Desiccant Air Dryers AEHD Series. Externally Heated Desiccant Air Dryer 150-3,000 scfm. Front Page 150-3,000 scfm AEHD Series Desiccant Air Dryers AEHD Series Externally Heated Desiccant Air Dryer 150-3,000 scfm Front Page 1 AEHD Series Heated Dryer Externally Heated Desiccant Dryer 150-3,000 scfm Since

More information

H & HC Heat-Of-Compression Air Dryers

H & HC Heat-Of-Compression Air Dryers H & HC Heat-Of-Compression Air Dryers Air Quality Solutions by Ingersoll-Rand Introduction Heat-of-compression dryers are dual tower, desiccant designs. The HOC dryer is the most energy efficient dryer

More information

Heatless Regenerative Compressed Air Dryers. Compressed Air System Products. Made in America

Heatless Regenerative Compressed Air Dryers. Compressed Air System Products. Made in America Heatless Regenerative Compressed Air Dryers Compressed Air System Products Made in America 22 AIR/TAK Heatless Regenerative Air Dryers Compressed Air System Products That Save Energy & Improve Operations.

More information

DGH Series Global Air Treatment

DGH Series Global Air Treatment DGH Series Global Air Treatment 2 DGH Desiccant Dryers Customizable Performance Gardner Denver DGH Series Heatless Desiccant Dryers were designed to help you meet your goals. Customizable performance technology

More information

MODEL MW200 MODEL MW600 AIR DRYER

MODEL MW200 MODEL MW600 AIR DRYER OPERATING MANUAL MODEL MW200 MODEL MW600 AIR DRYER Mail Address: 226A Commerce St. Tel: 303-465-3063 Broomfield, CO 80020 Fax: 303-465-9294 TABLE OF CONTENTS 1.0 GENERAL...3 2.0 SPECIFICATIONS...3 3.0

More information

Quality Components as a basis for Quality Equipment

Quality Components as a basis for Quality Equipment Above & Beyond Regenerative Type Compressed Air Dryers SPS - Heatless Regenerative Dryers SPEH - External Heated Regenerative Dryers SPBS - Heated Blower Purge Regenerative Dryers Quality Components as

More information

Desiccant Air Dryers. Heatless, Heated and Heated Blower

Desiccant Air Dryers. Heatless, Heated and Heated Blower Desiccant Air Dryers Heatless, Heated and Heated Blower Desiccant Dryers... When we designed the Ingersoll Rand heatless, heated and heated blower desiccant dryers we set our sights on creating the most

More information

DESICCANT DRYER USER MANUAL

DESICCANT DRYER USER MANUAL DESICCANT DRYER USER MANUAL AHLD Series Heatless Regenerative 70-4,000 scfm WARRANTY NOTICE Failure to follow the instructions and procedures in this manual, or misuse of this equipment, will void its

More information

AirCel. Heated Regenerative Desiccant Dryers. AEHD Externally Heated, HRE Blower Purge, and HRS-L Zero Purge Series

AirCel. Heated Regenerative Desiccant Dryers. AEHD Externally Heated, HRE Blower Purge, and HRS-L Zero Purge Series AirCel Heated Regenerative Desiccant Dryers AEHD Externally Heated, HRE Blower Purge, and HRS-L Zero Purge Series ié~çáåö=íüé=t~ó=áå=^áê=mìêáñáå~íáçå As one of the world s leading manufacturers of compressed

More information

Desiccant Air Dryers. ABP Series. Blower Purge Desiccant Air Dryer 70-8,000 scfm

Desiccant Air Dryers. ABP Series. Blower Purge Desiccant Air Dryer 70-8,000 scfm Desiccant Air Dryers ABP Series Blower Purge Desiccant Air Dryer 70-8,000 scfm Since 1994, Aircel has been delivering quality, industry leading compressed air dryers and accessories for production lines

More information

Laboratory Enclosed Rotary Screw Air Compressor System with Air Treatment Center Package

Laboratory Enclosed Rotary Screw Air Compressor System with Air Treatment Center Package System with Air Treatment Center Package Specification General The Powerex Laboratory Screw Compressor Enclosure package shall include multiple oil-free rotary screw air compressors modules and associated

More information

CDT Series MCGUIRE AIR COMPRESSORS INC MCGUIRE AIR COMPRESSORS INC Heatless Desiccant Air Dryers 40 5,400 SCfm

CDT Series MCGUIRE AIR COMPRESSORS INC MCGUIRE AIR COMPRESSORS INC Heatless Desiccant Air Dryers 40 5,400 SCfm CDT Series Heatless Desiccant Air Dryers 40 5,400 SCfm ISO Quality Dew Points Three Controller Selection NEMA4 Electrical Construction Standard on Two Controllers Purge Optimal Savings 2 Personalized Performance

More information

DRY-PAK INDUSTRIAL AIR DRYER Installation and Instruction Manual

DRY-PAK INDUSTRIAL AIR DRYER Installation and Instruction Manual DRRRRDRY-PAK Instruction and Installation Manual IB-160 Rev. B P/N 36595 Registered by UL to ISO 9001 DRY-PAK INDUSTRIAL AIR DRYER Installation and Instruction Manual INSTALLATION: Models DS0-00-000 through

More information

CLEAN, DRY COMPRESSED AIR

CLEAN, DRY COMPRESSED AIR CLEAN, DRY COMPRESSED AIR Adsorption Air Dryers Air and gas purification have been at the core of Xebec adsorption technology since 1967. We have built, installed and continue to service over 9000 dryers.

More information

DHW Series INSTRUCTION MANUAL. Pressure Swing Desiccant Compressed Air Dryer Models 7 through 50 scfm

DHW Series INSTRUCTION MANUAL. Pressure Swing Desiccant Compressed Air Dryer Models 7 through 50 scfm INSTRUCTION MANUAL DHW Series Pressure Swing Desiccant Compressed Air Dryer Models 7 through 50 scfm FORM NO.: 3215738 REVISION: 07/2014 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING

More information

TITAN FLOW CONTROL, INC.

TITAN FLOW CONTROL, INC. PREFACE: TITAN FLOW This manual contains information concerning the installation, operation, and maintenance of Titan Flow Control (Titan FCI) Suction Diffusers. To ensure efficient and safe operation

More information

clean, dry compressed air

clean, dry compressed air clean, dry compressed air Adsorption Air Dryers Air and gas purification have been at the core of Xebec adsorption technology since 1967. We have built, installed and continue to service over 9000 dryers.

More information

HEAT OF COMPRESSION DESICCANT AIR DRYERS. DHC Series

HEAT OF COMPRESSION DESICCANT AIR DRYERS. DHC Series HEAT OF COMPRESSION DESICCANT AIR DRYERS DHC Series Why Heat of Compression? The DHC Series heat of compression desiccant air dryers from Gardner Denver provide an energy efficient solution to remove moisture

More information

EN Installation and Operation Manual

EN Installation and Operation Manual EN Installation and Operation Manual Heatless Regenerated Dryer DRYPOINT XC Premium Series XCp models 80 to 800 with BEKOTOUCH Controller READ MANUAL FIRST BEFORE INSTALLATION AND OPERATION Contents 1.

More information

Regenerative Desiccant Dryers. KAD, KED, KBD and Hybritec Series

Regenerative Desiccant Dryers. KAD, KED, KBD and Hybritec Series Regenerative Desiccant Dryers KAD, KED, KBD and Hybritec Series The Right Dryer For You Most compressed air applications require only refrigerated dryers; however, if your compressed air is exposed to

More information

DRY AIR SYSTEMS, INC Metro Boulevard Maryland Heights, Missouri (314) fax (314)

DRY AIR SYSTEMS, INC Metro Boulevard Maryland Heights, Missouri (314) fax (314) DRY AIR SYSTEMS, INC. 2655 Metro Boulevard Maryland Heights, Missouri 63043 (314) 344-1114 fax (314) 344-0677 HD SERIES DRIERS TABLE OF CONTENTS WHY AN AIR DRYER 3 WHAT IS A DESICCANT AIR DRYER 3 Desiccant

More information

DESICCANT DRYER USER MANUAL

DESICCANT DRYER USER MANUAL DESICCANT DRYER USER MANUAL ABP Series Blower Purge 800-10,000 scfm WARRANTY NOTICE Failure to follow the instructions and procedures in this manual, or misuse of this equipment, will void its warranty.

More information

GRF-SERIES REFRIGERATION TYPE NON CYCLING STANDARD

GRF-SERIES REFRIGERATION TYPE NON CYCLING STANDARD Great Lakes Air Products 1515 S. Newburgh Road Westland, MI 48186 PH: 734-326-7080 www.glair.com COMPRESSED AIR DRYER INSTRUCTION MANUAL GRF-SERIES REFRIGERATION TYPE NON CYCLING STANDARD Contents Introduction

More information

Dual Tower Heat Reactivated Desiccant Air Dryer

Dual Tower Heat Reactivated Desiccant Air Dryer Dual Tower Heat Reactivated Desiccant Air Dryer idhpe Dryer idbpe Dryer Eliminate Water from Your Compressed Air System Moisture in compressed air is damaging. Without proper treatment, this vital energy

More information

Dry Air Pac ENGINEERED COMPRESSED AIR DRYING SYSTEMS FOR COLD STORAGE/ FREEZER ROOM DRY PIPE SPRINKLER SYSTEMS

Dry Air Pac ENGINEERED COMPRESSED AIR DRYING SYSTEMS FOR COLD STORAGE/ FREEZER ROOM DRY PIPE SPRINKLER SYSTEMS Dry Air Pac ENGINEERED COMPRESSED AIR DRYING SYSTEMS FOR COLD STORAGE/ FREEZER ROOM DRY PIPE SPRINKLER SYSTEMS Installation, Operation and Maintenance Manual MODELS DAP500, DAP1000 & DAP2000 Model Number

More information

Corrosion Dry Air Pak

Corrosion Dry Air Pak Corrosion Dry Air Pak ENGINEERED COMPRESSED AIR DRYING SYSTEMS FOR MIC REDUCTION IN DRY PIPE SPRINKLER SYSTEMS Installation, Operation, & Maintenance Manual MODELS CDP500, CDP1000, & CDP2000 MFG#: 5403584

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR PREP-40 PORTABLE COMPRESSED AIR DRYER SYSTEM model FR-800 (P/N )

INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR PREP-40 PORTABLE COMPRESSED AIR DRYER SYSTEM model FR-800 (P/N ) SEPTEMBER 0 950 Mechanic Street Lake City, PA 643 USA Phone: 800-840-9906 Fax: 84-774-348 www.vanairsystems.com INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR PREP-40 PORTABLE COMPRESSED AIR DRYER SYSTEM

More information

Desiccant Air Drying Technologies HCS Series HCL Series HCT Series

Desiccant Air Drying Technologies HCS Series HCL Series HCT Series Desiccant Air Drying Technologies HCS Series HCL Series HCT Series HCS, HCL and HCT Series Heatless Dryers Models 40-450 Models 590-5400 HCS, HCL and HCT Series Heatless Desiccant Dryers Since 1961, compressed

More information

Rev. None AUGUST 2012 MDM SERIES MODULAR MEMBRANE AIR DRYERS OPERATOR MANUAL MDM1 MDM4 MDM9 MDM13 MDM24 MDM49 MDM66 MDM106 MDM138

Rev. None AUGUST 2012 MDM SERIES MODULAR MEMBRANE AIR DRYERS OPERATOR MANUAL MDM1 MDM4 MDM9 MDM13 MDM24 MDM49 MDM66 MDM106 MDM138 7428146 Rev. None AUGUST 2012 MDM SERIES MODULAR MEMBRANE AIR DRYERS OPERATOR MANUAL MDM1 MDM4 MDM9 MDM13 MDM24 MDM49 MDM66 MDM106 MDM138 1.0 SAFETY All compressed gases, including air, can be dangerous.

More information

INSTRUCTION MANUAL FOR LECTRODRYER BAC-50 HYDROGEN DRYING SYSTEM. Lectrodryer Serial Number:

INSTRUCTION MANUAL FOR LECTRODRYER BAC-50 HYDROGEN DRYING SYSTEM. Lectrodryer Serial Number: INSTRUCTION MANUAL FOR LECTRODRYER BAC-50 HYDROGEN DRYING SYSTEM Manufactured for: End User: Plant Name: Unit Number: General Electric Lectrodryer Serial Number: P.O. Box 2500 Richmond, Kentucky 40476-2602

More information

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Specification General The Powerex Laboratory Scroll Enclosed Air Compressor System is designed to provide clean, dry air for

More information

Niles Steel Tank Hot Water Generator Installation and Operation Manual

Niles Steel Tank Hot Water Generator Installation and Operation Manual Niles Steel Tank Hot Water Generator Installation and Operation Manual Contents: Contents 1 Hazard definitions 1 1. General Information.... 2 Availability... 3 Optional Control Packages... 5 2. Installation....

More information

Laboratory Open Scroll Air Compressor System with Premium NFPA Controls

Laboratory Open Scroll Air Compressor System with Premium NFPA Controls Laboratory Open Scroll Air Compressor System with Premium NFPA Controls Specification General The Powerex Laboratory Open Scroll Air Compressor System is designed to provide clean, dry air for applications

More information

Moduflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU

Moduflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU Moduflex Dry Air System Desiccant Air P3TJA13A1AN - P3TJA13A7AN EN USER GUIDE (Original Language) NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU LV LT RU SL TR MT CONTENTS 1 Safety Information...2 1.1

More information

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S Polar Air Dryer R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S PDRCF1150029 PDRCF4602000 Instructions Manual TABLE OF CONTENTS 1. Important safety notes - Please read... 1 1.1. Transportation...

More information

HEATLESS DESICCANT AIR DRYERS

HEATLESS DESICCANT AIR DRYERS HEATLESS DESICCANT AIR DRYERS HHS, HHL AND HHE SERIES HANKISON HEATLESS DESICCANT DRYERS HHS, HHL AND HHE SERIES Since 1948, sensitive applications requiring clean, dry, compressed air have turned to Hankison

More information

MANUAL. Dryspell INSTALLATION OPERATION MAINTENANCE. Regenerative Type Heatless Desiccant Dryer

MANUAL. Dryspell INSTALLATION OPERATION MAINTENANCE. Regenerative Type Heatless Desiccant Dryer MANUAL INSTALLATION OPERATION MAINTENANCE Regenerative Type Heatless Desiccant Dryer Dryspell Contents 1. Introduction 2 1.1 Design 1.2 Relevant Units 1.3 Statement of Conformity 1.4 Description 1.5 Adsorbant

More information

Installation, Operation, and Maintenance Instructions. Heatless Regenerative Air Dryers and HLD-PAK Dryer/Filter Packages HLD-25 through HLD-6250

Installation, Operation, and Maintenance Instructions. Heatless Regenerative Air Dryers and HLD-PAK Dryer/Filter Packages HLD-25 through HLD-6250 107 W. Main Street, Worthington, PA 16262 Phone: 724-297-3416 Fax: 724-297-5189 URL: http://www.airtak.com e-mail: airtak@airtak.com Installation, Operation, and Maintenance Instructions Heatless Regenerative

More information

Owner s Manual Refrigerated Compressed Air Dryer Model F-50

Owner s Manual Refrigerated Compressed Air Dryer Model F-50 Owner s Manual Refrigerated Compressed Air Dryer Model F-50 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all

More information

Unique, Energy-Saving Models HC & SP World Leader in Regenerative Dryer Technology

Unique, Energy-Saving Models HC & SP World Leader in Regenerative Dryer Technology Sahara-Pak Heat-of-Compression Regenerative Compressed Air Dryers Unique, Energy-Saving Models HC & SP World Leader in Regenerative Dryer Technology World Leader in Regenerative Dryer Technology The Competetive

More information

ARV -3 & ARV -10 Active Reservoir Vent Installation and Operation Manual

ARV -3 & ARV -10 Active Reservoir Vent Installation and Operation Manual ARV -3 & ARV -10 Active Reservoir Vent Installation and Operation Manual Manual P568800 Rev 1, Mar 30, 2010 1 As the installer or operator, you should make yourself familiar with this Installation and

More information

SSB Blower Purge Desiccant Dryers SSE Heat Reactivated Desiccant Dryers 220 to 10,500 scfm

SSB Blower Purge Desiccant Dryers SSE Heat Reactivated Desiccant Dryers 220 to 10,500 scfm SSB Blower Purge Desiccant Dryers SSE Heat Reactivated Desiccant Dryers 220 to 10,500 scfm Dry air as low as -100 F pressure dew point Clean, dry compressed air solves the problems of moisture contamination

More information

OWNER/OPERATOR MANUAL COMPONENTS, INSTALLATION, OPERATION AND SERVICE INSTRUCTIONS

OWNER/OPERATOR MANUAL COMPONENTS, INSTALLATION, OPERATION AND SERVICE INSTRUCTIONS OWNER/OPERATOR MANUAL COMPONENTS, INSTALLATION, OPERATION AND SERVICE INSTRUCTIONS REFRIGERATED COMPRESSED AIR DRYER WRA-0050 WRA-0200 WARNING READ ALL INFORMATION IN THIS MANUAL BEFORE BEGINNING INSTALLATION

More information

SULLAIR DESICCANT DRYERS

SULLAIR DESICCANT DRYERS SULLAIR DESICCANT DRYERS Sullair An industry leader Leadership Since 1965, Sullair has been recognized worldwide as an innovator and leader in rotary screw compression and vacuum technology. Sullair designs

More information

Refrigerated & Desiccant Compressed Air Dryer Product Selector

Refrigerated & Desiccant Compressed Air Dryer Product Selector Refrigerated & Desiccant Compressed Air Dryer Product Selector ASD and HTD Series Refrigerated Dryer Units DD Series Desiccant Dryer Units Service Parts For faster service and to avoid errors, please use

More information

Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350

Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350 Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others

More information

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL DATE OF PURCHASE: MODEL: SERIAL NO.: Record above information from nameplate. Retain this information for future reference.

More information

COMPRESSED AIR DRYER. SAFETY... Page 2 MAINTENANCE... Page 5. INSTALLATION... Page 3 PARTS AND KITS... Page 6

COMPRESSED AIR DRYER. SAFETY... Page 2 MAINTENANCE... Page 5. INSTALLATION... Page 3 PARTS AND KITS... Page 6 OWNERS MANUAL BOSS COMPRESSED AIR DRYER Distributed by Air & Vacuum Process, Inc. Phone: 281-866-9700 Fax: 281-866-9717 Email: sales@airvacuumprocess.com SAFETY... Page 2 MAINTENANCE... Page 5 INSTALLATION...

More information

Owner s Manual Refrigerated Compressed Air Dryers Model F-100

Owner s Manual Refrigerated Compressed Air Dryers Model F-100 Owner s Manual Refrigerated Compressed Air Dryers Model F-100 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing

More information

CDH Series Heatless Desiccant Dryers CFM

CDH Series Heatless Desiccant Dryers CFM CDH Series Heatless Desiccant Dryers 0 500 CFM NEW Engineered to Save CDH Desiccant Dryers Customizable Performance CompAir CDH Series Heatless Desiccant Dryers were designed to help you meet your goals.

More information

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual Instructions Manual 1. Important safety notes - Please read... 1 1.1. Transportation... 1 1.2 Positioning... 1 1.3 Installation... 1 1.4 Before operating... 1 1.5 Maintenance by an engineer... 1 1.6 Maintenance

More information

Laboratory Open Scroll Air Compressor System with Premium NFPA Controls Rev. 06/27/14

Laboratory Open Scroll Air Compressor System with Premium NFPA Controls Rev. 06/27/14 Laboratory Open Scroll Air Compressor System with Premium NFPA Controls Rev. 06/27/14 GENERAL The Powerex Laboratory Open Scroll Air Compressor System is designed to provide clean, dry air for applications

More information

Owner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532

Owner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532 Owner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

HR Heated HB Blower. Smart Solutions for Drying Compressed Air. Dual Tower Heat Reactivated Desiccant Air Dryer

HR Heated HB Blower. Smart Solutions for Drying Compressed Air. Dual Tower Heat Reactivated Desiccant Air Dryer Smart Solutions for Drying Compressed Air Dual Tower Heat Reactivated Desiccant Air Dryer HR Heated HB Blower 800.943.794 www.engineeredairproducts.com Engineered Air Products Moisture in compressed air

More information

Compressed Air System Products That Save Energy & Improve Operations. Dry, Clean Air for Sensitive Equipment. Refrigerated Air Dryers

Compressed Air System Products That Save Energy & Improve Operations. Dry, Clean Air for Sensitive Equipment. Refrigerated Air Dryers Refrigerated Air Dryers Compressed Air System Products That Save Energy & Improve Operations. Dry, Clean Air for Sensitive Equipment. 107 W. Main St. Worthington, Pennsylvania 16262 Phone: (724) 297 3416

More information

CNG. PSB Industries. NG Series -- Natural Gas Dryers

CNG. PSB Industries. NG Series -- Natural Gas Dryers CNG PSB Industries NG Series -- Natural Gas Dryers NG-SR NG-SR NG-SRD NG-SRD NG-EV NG-EV NG-SV NG-SV NGR NGR PSB Industries PSB Industries Inc., General Air Division, specializes in the Design and Fabrication

More information

DESICCANT AIR DRYERS. BD + CD + CD series

DESICCANT AIR DRYERS. BD + CD + CD series DESICCANT AIR DRYERS BD + CD + CD series AIR TREATMENT, A CRUCIAL INVESTMENT WHY YOU NEED QUALITY AIR Compressed air contains oil, solid particles and water vapors. Together, they form an abrasive, often

More information

Single Tower Heat Reactivated Desiccant Air Dryer

Single Tower Heat Reactivated Desiccant Air Dryer Single Tower Heat Reactivated Desiccant Air Dryer iste Dryer Understanding Compressed Air Moisture in compressed air is damaging. Using untreated air results in water and contaminants in your air lines,

More information

Heat Les Desiccant Compressed Air Dryers. DSE Series DSS Series DHD Series

Heat Les Desiccant Compressed Air Dryers. DSE Series DSS Series DHD Series Heat Les Desiccant Compressed Air Dryers DSE Series DSS Series DHD Series DSE, DSS and DHD Series Heat Les Desiccant Dryers For decades, compressed air users have relied on Pneumatic Products to deliver

More information

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap. Operation & Maintenance Manual MDX MODELS 18 THRU 250

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap. Operation & Maintenance Manual MDX MODELS 18 THRU 250 MDX Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap Operation & Maintenance Manual MDX MODELS 18 THRU 250 TABLE OF CONTENTS HOW TO USE THIS MANUAL 2 SYMBOLS 2 WARRANTY

More information

EXTERNALLY HEATED DESICCANT AIR DRYERS. DHP Series

EXTERNALLY HEATED DESICCANT AIR DRYERS. DHP Series EXTERNALLY HEATED DESICCANT AIR DRYERS DHP Series Critical Performance Gardner Denver DHP Gardner Denver DHP externally heated series is designed for applications that were previously forced to accept

More information

Heat of Compression Desiccant Air Dryers. NRG-LES SERIES scfm ( nm 3 /h)

Heat of Compression Desiccant Air Dryers. NRG-LES SERIES scfm ( nm 3 /h) Heat of Compression Desiccant Air Dryers NRG-LES SERIES 350-10000 scfm (595-16990 nm 3 /h) Where Ideas Meet Industry Since 1946, the world has turned to SPX FLOW s Pneumatic Products brand for the quality

More information

Desiccant Drying DRYPOINT XC. efficient low dew point heatless desiccant drying. Truth in Compressed Air.

Desiccant Drying DRYPOINT XC. efficient low dew point heatless desiccant drying. Truth in Compressed Air. Desiccant Drying DRYPOINT XC efficient low dew point heatless desiccant drying Truth in Compressed Air. At a Glance DRYPOINT XC Heatless Desiccant Dryers Regenerative desiccant dryers are frequently found

More information

DESICCANT DRYER USER MANUAL

DESICCANT DRYER USER MANUAL DESICCANT DRYER USER MANUAL AEHD Series Externally Heated 150-3,000 scfm WARRANTY NOTICE Failure to follow the instructions and procedures in this manual, or misuse of this equipment, will void its warranty.

More information

Instruction Manual Dry spell HFH INSTALLATION, OPERATION, MAINTENANCE. Regenerative Type Heatless Desiccant Dryer

Instruction Manual Dry spell HFH INSTALLATION, OPERATION, MAINTENANCE. Regenerative Type Heatless Desiccant Dryer Adsorption dryer Instruction Manual Dry spell HFH INSTALLATION, OPERATION, MAINTENANCE Regenerative Type Heatless Desiccant Dryer WE REDEFINE COMPRESSED AIR TREATMENT SYSTEMS 5/232 KNG Pudur road, Somayampalayam

More information

PNLDII-28 Condensate Drain Instruction Manual

PNLDII-28 Condensate Drain Instruction Manual PNLDII-28 Condensate Drain Instruction Manual Installation and Maintenance More Than Air. Answers. Online answers: CCN:22810568 FEBRUARY 2006 Limited One Year Warranty This product is warranted to be free

More information

TWP & TWB Series Externally Heated and Blower Purge Desiccant Air Dryers

TWP & TWB Series Externally Heated and Blower Purge Desiccant Air Dryers TWP & TWB Series Externally Heated and Blower Purge Desiccant Air Dryers Parker Airtek Externally Heated and Blower Purge Desiccant Air Dryers use the adsorption method to remove moisture from compressed

More information

Heat of Compression Desiccant Air Dryers. HOC SERIES scfm ( nm 3 /h)

Heat of Compression Desiccant Air Dryers. HOC SERIES scfm ( nm 3 /h) Heat of Compression Desiccant Air Dryers HOC SERIES 350-10000 scfm (595-16990 nm 3 /h) Where Ideas Meet Industry HOC Series Deltech HOC Series heat of compression desiccant air dryers provide a cost effective

More information

Desiccant Dryers. Desiccant Dryers. Heatless Heated Purge Blower Purge Modular

Desiccant Dryers. Desiccant Dryers. Heatless Heated Purge Blower Purge Modular Desiccant Dryers Desiccant Dryers Heatless Heated Purge Blower Purge Modular Desiccant Air Dryers Quincy desiccant air dryers purify compressed air by adsorbing water vapor. Pressure dewpoints of -40 F

More information

INSTALLATION AND OPERATION MANUAL STEAM COIL BASE CONVECTION STEAMER MODEL SCX-16

INSTALLATION AND OPERATION MANUAL STEAM COIL BASE CONVECTION STEAMER MODEL SCX-16 INSTALLATION AND OPERATION MANUAL STEAM COIL BASE CONVECTION STEAMER MODEL SCX-16 CROWN FOOD SERVICE EQUIPMENT LTD. 70 OAKDALE ROAD, DOWNSVIEW, (TORONTO), ONTARIO, CANADA, M3N 1V9 TELEPHONE: (416) 746-2358,

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

SECTION air supply system + WARNING: + NOTE: GENERAL DESCRIPTION COMPRESSED AIR RESERVOIRS / 1.

SECTION air supply system + WARNING: + NOTE: GENERAL DESCRIPTION COMPRESSED AIR RESERVOIRS / 1. 08-000.02/ 1 2011JA14 SECTION 08-000.02 GENERAL DESCRIPTION See Figure 1 for a schematic diagram of the. See the Nova LFS parts manual for a detailed schematic of the. The function of the vehicle s is

More information

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain. Operation & Maintenance Manual MODELS MDX

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain. Operation & Maintenance Manual MODELS MDX MDX Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Operation & Maintenance Manual MODELS MDX 800 1000 1200 TABLE OF CONTENTS HOW TO USE THIS MANUAL 2 SYMBOLS 2 WARRANTY 2 1.0

More information

ECLIPSE DESICCANT DRYERS ZHA HEATED PURGE MODELS

ECLIPSE DESICCANT DRYERS ZHA HEATED PURGE MODELS COMPRESSED AIR SOLUTIONS TECHNICAL MANUAL ECLIPSE DESICCANT DRYERS ZHA HEATED PURGE MODELS TABLE OF CONTENTS PAGE 1. INTRODUCTION 1 2. ABBREVIATED WARRANTY 1 3. NOMENCLATURE 2 4. RECEIVING AND INSPECTION

More information

PURest Air Dryer Installation and Maintenance

PURest Air Dryer Installation and Maintenance PURest Air Dryer Installation and Maintenance L31170 Rev. 4/04 The Haldex PURest is a desiccant type dryer that effectively removes moisture, oil and contaminants from the compressed air system. This reduces

More information

HS Dryer. Smart Solutions for Drying Compressed Air. Single Tower Heat Reactivated Desiccant Air Dryer. Engineered Air Products

HS Dryer. Smart Solutions for Drying Compressed Air. Single Tower Heat Reactivated Desiccant Air Dryer. Engineered Air Products Smart Solutions for Drying Compressed Air Single Tower Heat Reactivated Desiccant Air Dryer TM HS Dryer 800.943.794 www.engineeredairproducts.com Engineered Air Products Moisture in compressed air is damaging.

More information

ACT Cartridge Dust Collector

ACT Cartridge Dust Collector IOM-101-1 ACT Cartridge Dust Collector Installation and Operation Manual ACT Dust Collectors CAUTION! Accidents happen, be careful and always follow all local and federal regulations! Fires and explosions

More information

SECTION AIR COMPRESSORS AND ACCESSORIES

SECTION AIR COMPRESSORS AND ACCESSORIES PART 1 GENERAL 1.01 WORK INCLUDED SECTION 11370 AIR COMPRESSORS AND ACCESSORIES A. This specification includes air compressors with air dryers. B. Furnish, install, start-up, and test air compressors and

More information