SECTION (15733) - DEDICATED OUTDOOR AIR UNITS

Size: px
Start display at page:

Download "SECTION (15733) - DEDICATED OUTDOOR AIR UNITS"

Transcription

1 PART 1 GENERAL 1.01 SUMMARY SECTION (15733) - DEDICATED OUTDOOR AIR UNITS A. Section Includes: 1. Dedicated Outdoor-Air Units with Energy Recovery B. Related Sections: 1.02 REFERENCES 1. Section (15050) Common Work Results for HVAC 2. Section (15090) Common Motor Requirements for HVAC Equipment 3. Section (15070) Vibration Control for HVAC Piping and Equipment 4. Section (15075) Identification for HVAC Piping and Equipment 5. Section (15950) Testing, Adjusting and Balancing for HVAC 6. Section (15900) Instrumentation and Control for HVAC 7. Section (15940) Sequence of Operation for HVAC Controls 8. Division (15194) Facility Natural-Gas Piping 9. Division 26 (16) Sections for electrical connections. A. Air-Conditioning, Heating and Refrigeration Institute (AHRI) Publications: "Forced Circulation Air-Cooling and Air-Heating Coils "Performance of Air-to-Air Heat Exchangers for Energy Recovery Ventilation Equipment B. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Publications: Ventilation for Acceptable Indoor Air Quality (ANSI Approved) Energy Code for Commercial and High-Rise Residential Buildings C. ASTM International (ASTM) Publications: (Former American Society for Testing and Materials) 1. B117 "Standard Practice for Operating Salt Spray (Fog) Apparatus" D. National Fire Protection Association (NFPA) Publications: "National Electric Code" 2. 90A Standard for the Installation of Air Conditioning and Ventilating Systems 1.03 SUBMITTALS A. General: Submit the following in accordance with Conditions of Contract and Division 01 Specification Sections. B. Submit Letter of Conformance in accordance with Section (01330) indicating specified items selected for use in project with the following supporting data. 1. Product Data including manufacturer's technical data, clearly indicated for each model, including: rated capacities, operating characteristics, dimensions, weights (shipping, installed, and operating), furnished specialties, accessories, and installation and startup instructions. PAGE 1

2 2. Shop Drawings from manufacturer detailing equipment assemblies and indicate dimensions, weights, loadings, required clearances, method of field assembly, components, and location and size of each field connection. Detail mounting, securing, and flashing of roof curb to roof structure. Indicate coordinating requirements with roof membrane system. 3. Wiring Diagrams detailing wiring for power, signal, and control systems. Clearly differentiate between manufacturer-installed and field-installed wiring. 4. Commissioning report, including pre-functional testing checklists, indicating the results of unit startup, testing and commissioning requirements. 5. Maintenance data for energy recovery units to include in the operation and maintenance manual specified in Division 01 and in Section "Common Work Results for HVAC." 1.04 QUALITY ASSURANCE A. AHRI Certification: Units and their components shall be factory tested according to the applicable portions of AHRI 1060, "Performance of Air-to-Air Heat Exchangers for Energy Recovery Ventilation Equipment," and AHRI 410, "Forced Circulation Air-Cooling and Air- Heating Coils," and shall be listed and bear the label of the Air-Conditioning, Heating and Refrigeration Institute (AHRI ). B. UL and NEMA Compliance: Provide motors required as part of air-handling units that are listed and labeled by UL and comply with applicable NEMA standards. C. Comply with NFPA 70 for components and installation. D. Listing and Labeling: Provide electrically operated components specified in this Section that are listed and labeled. 1. The Terms "Listed" and "Labeled": As defined in the NFPA National Electrical Code, Article 100. E. Comply with ASHRAE/IESNA Standard , Section 7 "Construction and Startup." 1.05 DELIVERY, STORAGE, AND HANDLING A. Deliver rooftop units as factory-assembled units with protective crating and covering. B. Coordinate delivery of units in sufficient time to allow movement into building. C. Handle rooftop units to comply with manufacturer's written rigging and installation instructions for unloading and moving to final location COORDINATION A. Coordinate installation of roof curbs, equipment supports, and roof penetrations EXTRA MATERIALS A. Furnish extra materials described in Section (01790) Spare Parts and Materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents WARRANTY A. General Warranty: The manufacturer shall warrant all equipment for a period of one (1) year from date of substantial completion. Extended warranty specified in this Article shall not deprive Owner of other rights Owner may have under other provisions of the Contract Documents and shall be in addition to, and run concurrent with, other warranties made by Contractor under requirements of the Contract Documents. PAGE 2

3 B. Extended Warranty: Manufacturer's standard form in which manufacturer agrees to replace components of rooftop air conditioners that fail in materials or workmanship within specified warranty period. 1. Extended Warranty Period for Compressors: Manufacturer's standard, but not less than five years from date of Substantial Completion. 2. Extended Warranty Period for Heat Exchangers: Manufacturer's standard, but not less than 10 years from date of Substantial Completion. 3. Extended Warranty Period for Energy Wheels: Manufacturer's standard, but not less than 5 years from date of Substantial Completion. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Approved Manufacturers: 1. Dedicated Outdoor Air Unit a. "Rebel"; Daikin ( ) b. SolutionAir ; JAFT Corp ( x-108) c. RN Series ; AAON, Inc. ( ) d. "TotalAire (QS) Series"; Desert Aire ( ) e. Model ERCH ; Greenheck Fan Corporation ( ) f. "Complevent"; Munters Corporation ( ) g. "OAU"; Trane ( ) h. Seresco ( ) i. Advantix Systems ( ) 2.02 DEDICATED OUTDOOR-AIR UNITS WITH ENERGY RECOVERY A. Description: Packaged self-contained, outdoor rooftop, DX/gas, 100% outside air, energy recovery unit of capacities and characteristics as scheduled on the drawings. 1. Each unit shall be completely factory assembled, piped, wired, tested and shipped in one piece. 2. Unit shall be capable of varying the amount of outside air delivered to the space based on occupancy, humidity, indoor air quality and differential pressure. 3. In the event that the space dry bulb temperature begins to deviate from set point, the DOAS shall be capable of varying the outside air supply air temperature to supplement the cooling or heating requirements of the space. 4. Unit shall be capable of varying the moisture content of outside air to the space based on space humidity. To maintain 59 grains of moisture per pound of dry air space conditions, the DOAS must be able deliver air down to 39 F dew point supply air at low air volume conditions. 5. Units shall be designed to cool or dehumidify with entering air temperatures of F and operate in heating mode down to -40 F. Units shall be capable of supplying air with a maximum of 59 grains of moisture per pound of dry air, or less if specified, at both the dry bulb / mean coincidental wet bulb and dew point / mean coincidental dry bulb temperatures at the 0.4% ASHRAE design conditions for the location of the installation. PAGE 3

4 Units not capable of delivering 59 grains of moisture per pound of dry air, or less if specified, at both design conditions are unacceptable. 6. Units shall provide 100% outdoor air directly to the space, or delivered to the terminal unit(s) supply air duct. Mixed Air units are NOT acceptable. B. Unit Cabinet: 1. Unit shall be specifically designed for outdoor rooftop application with a fully weatherproof cabinet. The unit roof shall be sloped or cross-broken to assure drainage. Unit base shall overhang the roof curb for water run-off. Rain break overhangs shall be provided above access doors. 2. Cabinet shall be of double wall, insulated design. The cabinet exterior shall be constructed of painted 20 gauge or heavier G90 galvanized steel, or unpainted Type 5052 marine grade aluminum using 12 gauge panels & 8 gauge structural members, or unpainted Type 304 stainless steel using 18 gauge panels & 14 gauge structuratl members. The interior shall be Type 5052 aluminum or Type 304 stainless of similar gauge to the cabinet exterior. The cabinet shall be weatherproof and suitable for outdoor construction and the entire floor shall be designed to operate as a drain pan so that in the event that rain would enter the cabinet, it will drain via the condensate drain connection. Insulation shall be in accordance with the requirements of ASHRAE Standard , and shall be non-wicking and moisture resistant. The insulation must not be capable of supporting any biological growth of any kind. All insulation shall have a smoke and fire rating of 5-5 and shall be rated Class A. The insulation shall have a VOC content of zero (0). 3. Paint finish shall be capable of withstanding at least 2500 hours, with no visible corrosive effects, when tested in a salt spray and fog atmosphere in accordance with ASTM B test procedure. 4. Unit shall have insulated, hinged access doors with quarter turn handles and full perimeter gasketed seals. Door fastening screws are not acceptable. 5. Unit shall be factory pre-rigged for a 4-point crane lift. 6. All openings through the base pan of the unit shall have upturned flanges of at least 1/2 in height around the opening through the base pan. 7. Unit shall have a factory-installed cleanable, insulated, double-sloped condensate drain connection of aluminum or stainless steel. 8. Outdoor and exhaust air openings shall have a hood or louver with bird screen. Construction and color shall match cabinet. 9. Dampers: a. Motor operated outside air damper assembly constructed of extruded aluminum, hollow core, airfoil blades with rubber edge seals and aluminum end seals. Damper blades shall be gear driven and designed to have no more than 15 CFM of leakage per sq. ft. of damper area when subjected to 2 w.g. air pressure differential across the damper. b. Gravity type backdraft damper at the exhaust discharge. 10. All evaporator, condenser and water coils shall be cleanable. All coils shall be a maximum of 4 rows thick, 10 fins per inch and include a minimum of a 4 inch clean-out access between coils. The floor below the coil shall be suitable for drainage of the cleaning solution. All coils must be coated in order to reduce corrosion from contaminants from outside air and moisture and increase watershed capability. The PAGE 4

5 coating shall be a thermal set acrylic having an ASTM B117 salt test rating that exceeds 1000 hours. Coatings shall be hydrophobic to aid in draining water from the coil. Interlaced coils shall NOT be acceptable. Units with coils that have more than 10 fins per inch or that have lanced fins are NOT acceptable. 11. Color coded wiring diagrams shall be laminated in plastic and permanently affixed inside the control compartment. 12. Unit shall have decals and tags to indicate unit lifting and rigging, service areas and caution areas. 13. Unit nameplates shall be fixed to the main control panel door. C. Roof Curb: (DOAS-2) 1. Roof curb shall be constructed of similar metal as the cabinet construction. Curbs are to be factory welded construction providing full perimeter support, cross structure support and air seal for the unit. Curb shall be as described on the drawings. D. Supply and Exhaust Fans: 1. Plenum supply fan shall be backward inclined, direct drive with factory installed variable frequency drive, non-overloading, and designed for high efficiency operation at higher static pressures with lower noise levels. Blowers shall be constructed of epoxy-coated steel for corrosion resistance. 2. Exhaust fan shall be backward inclined, direct drive type, non-overloading, and designed for high efficiency operation at higher static pressures with lower noise levels. Blowers shall be constructed of epoxy-coated steel for corrosion resistance. 3. Fans shall be statically and dynamically balanced. 4. The fan assembly shall be Blower and motor base is to be mounted on 4 spring and rubber isolators having minimum 3/4-inch deflection. Blower to be isolated from the cabinet with a flexible connector having a fire rating. 5. Fan shaft bearings shall be heavy duty, permanently lubricated, self-aligning ball or roller pillow block type. Bearings shall have a minimum life (L-10) of 80,000 hours at maximum operating speed and horsepower for each construction level. E. Air-Cooled Condenser: 1. The condensing section shall be equipped with vertical discharge, propeller type, direct drive fans with corrosion-resistant blades and supports. Direct drive fans shall be directly connected to and supported by the motor shaft. Fans shall be statically and dynamically balanced. 2. Condenser coils shall have enhanced surface aluminum plate fins mechanically bonded to the copper tubes with all joints brazed. F. Refrigerant System: 1. Unit shall be factory charged with R-410A refrigerant. 2. Compressors: a. Fully hermetic, scroll type compressors with crankcase heater, overload protection and short cycle protection with minimum on and off timers. b. Compressors shall be mounted on the compressor manufacturer s recommended rubber vibration isolators and shall be isolated from the base pan and supply air to avoid transmission of noise from the compressor into the building. Vibrasorb PAGE 5

6 isolators shall be installed in both the suction and discharge tubing of each compressor. c. Compressors shall be mounted in an isolated compartment to permit operation of the unit without affecting air flow when the door to the compartment is open. d. Each compressor shall be individually staged for capacity control. Units exceeding 2,000 cfm shall have a minimum of 3 independent refrigeration circuits that have no shared components. Each circuit must be able to operate at any time without the assistance or aid of any component of the other circuits with the exception of the controls and blower. Any or all components of any single circuit must be constructed in such a way as to be removable without disturbing or disrupting or contaminating any of the other circuits. Each compressor shall be dedicated to an individual evaporator coil, TXV and condenser coil and operate independently. Tandem compressors shall NOT be acceptable. Minimum 2-stage capacity control on units over 10 tons and above. 3. Refrigerant System Specialties for each circuit: a. Refrigerant dryer. b. Adjustable thermostatic expansion valve. c. High and low pressure switches. d. Gage connection ports. e. Liquid line sight glass. f. Service/charging valves. 4. Reheat Coil: Hot gas reheat coil with 0-100% modulating hot gas reheat control valves piped to all reheat refrigerant circuits. 5. Capacity Control: a. Multiple compressor design and Variable Speed Scroll compressor design shall provide 0-100% capacity control for continuous dehumidification upon demand. Energy wasting hot gas bypass refrigerant control shall NOT be acceptable. b. Unit shall be equipped with variable speed low ambient head pressure control to allow operation down to 35 F. 6. Evaporator coil shall have minimum corrosion potential from dissimilar metals. Coil casing shall be either copper, aluminum, stainless steel. Galvanized steel coil casings shall NOT be acceptable 7. Evaporator coil shall be furnished with a double sloped drain pan fabricated of Type 5052 aluminum, or Type 304 stainless steel for the positive drainage of condensate. G. Filter Section: 1. The outdoor air steams shall have 4 thick pleated, high efficiency filters with a minimum MERV-13 rating and the exhaust air steams shall have MERV-8 filters. H. Filter Section: 1. Both outdoor and exhaust air steams shall have 2 thick fiberglass filters with a minimum MERV-7 rating. I. Energy Recovery Wheel: 1. Wheel shall be of the enthalpy type for both sensible and latent recovery; moisture transfer shall occur entirely in the vapor phase. Wheel shall be constructed of alternate PAGE 6

7 layers of corrugated and flat aluminum. Enthalpy wheels shall be permanently bonded with "Micro-Sieve" a desiccant adsorbent specifically developed for the selective transfer of moisture for equal transfer of sensible and latent energy. The air channels shall be formed smooth to ensure laminar airflow for low-pressure drops and allow free passage of particles up to 900 microns. Rotor structure shall be internally reinforced and mounted on pillow block type bearings. The rotor shall also be removable from the frame. Brush seals shall be provided around the periphery of the rotor and between the inlet and outlet air passages to effectively prevent air leakage and cross contamination between airflows. An adjustable purging sector shall be installed to prevent carryover of contaminated exhaust air into the supply air stream. Performance and cross contamination shall be documented through an independent laboratory conducted in accordance with ASHRAE and AHRI standards. 2. Factory provided integral DDC automatic temperature control that shall include remote temperature sensors mounted in each of the four airstreams to monitor exchanger performance. The control shall modulate rotor speed to prevent frost build-up. A rotor bypass section shall be incorporated into the cabinet design to bypass the rotor when conditions are beneficial for overall energy savings. J. Winter Heating Mode 1. Indirect-Fired Gas Heating: K. Controls: a. Gas heating shall be induced-draft combustion type with an energy saving direct spark ignition system and redundant main gas valves. b. Heat exchanger shall be tubular section type, constructed of 20 gauge stainless steel. c. Burners shall be modulating (10:1 turndown) in-shot type constructed of stainless steel and have sufficient staging as to provide the supply air temperature within 2 degrees (F) of the DOAS supply air setpoint, even at startup, regardless of the entering air temperature. As the supply air volume modulates to meet ventilation demands, the supply air temperature shall not rise above or below the set point temperature, +/- 2 degrees (F). d. Gas shall enter the unit at a single location. 1. Dedicated Outdoor-Air Unit Controller: a. The unit shall include a factory installed microprocessor based unit controller which controls the operation of all unit functions including: dampers, supply and exhaust fans, energy recovery wheel, refrigerant system and gas heater. b. Controller shall be capable of the monitoring the following functions, safeties and alarms. 1) Factory-installed dirty filter status for both supply and exhaust filter banks. 2) Factory-installed fan status switch for both supply and exhaust fans. 3) Energy wheel defrost control and air bypass. c. Controller shall be BACNet, Modbus and LonWorks protocol compatible. d. Shall include and alarm indicator and audible alarm signal. 2. Fan current transducer. 3. Supply air temperature sensor. PAGE 7

8 4. Outside air temperature sensor. 5. Relative humidity sensor. L. Fire Alarm System Interface: 1. Provide dry contact control interface to connect to fire alarm panel, so that unit shuts down in the event the fire alarm system goes into alarm. M. Airflow Monitoring/Control & Building Pressure Control: 1. Provide building pressure differential sensor and controls to maintain building pressure at a user adjustable setting (initially set at 0.05 w.g.). The building pressure sensor is to be accurate to within 0.02 w.g. and is to be self-calibrating. Upon a rise in building pressure, the unit controls are to slow down the supply air fan (through the variable speed drive). The opposite is to happen on a drop in building pressure. N. Electrical: 2.03 MOTORS 1. Unit shall be provided with a factory installed and wired main disconnect switch. Integral branch fusing shall be accomplished through the use of resettable circuit breakers. Replaceable fuses are NOT acceptable. 2. Unit shall be provided with phase and brown-out protection to shut down all motors in the unit if the phases are more than 10% out of balance on voltage, or the voltage is more than 10% under design voltage or on phase reversal. In the event that a poor power condition is detected, the power monitoring feature will instantaneously shut the unit down and isolate the microprocessor controller from the incoming power supply. The Power Monitor feature shall record and save a minimum of 10 fault conditions in the fault history log. The Power Monitor feature shall automatically restart the unit after power has returned within acceptable parameters for a preset period of time. 3. Unit shall be provided with a factory installed and wired 115 volt, 12 amp ground fault service receptacle powered by a 1.5 KVA transformer. The convenient outlet shall be fed by an independent power supply. A. Refer to Division 23 Section "Common Motor Requirements for HVAC Equipment" for general requirements for factory-installed motors. B. Motor Construction: NEMA MG 1, general purpose, continuous duty, Design B. C. Enclosure Type: Open, dripproof. PART 3 EXECUTION 3.01 EXAMINATION A. Examine roof for compliance with requirements for conditions affecting installation and performance of rooftop units. Do not proceed with installation until unsatisfactory conditions have been corrected INSTALLATION A. Install units according to manufacturer's written instructions. B. Install units level and plumb, maintaining manufacturer's recommended clearances CONNECTIONS A. Piping installation requirements are specified in other Division 23 Sections. Drawings indicate the general arrangement of piping, fittings, and specialties. The following are specific connection requirements: PAGE 8

9 1. Install piping to allow service and maintenance. 2. Gas Piping: Comply with applicable requirements in Division 22 Section "Natural Gas Piping." Connect gas piping to burner, full size of gas train inlet, and connect with union and shutoff valve with sufficient clearance for burner removal and service. B. Duct installation requirements are specified in other Division 23 Sections. Drawings indicate the general arrangement of ducts FIELD QUALITY CONTROL AND COMMISSIONING A. Verify that installation is as indicated and specified. B. Complete commissioning pre-functional testing and functional testing as part of the following. C. Complete manufacturer's installation and startup checks and perform the following: 1. Level unit on curb or steel, and flash curbs to unit and to roof. 2. Inspect for visible damage to unit casing. 3. Verify that clearances have been provided for servicing. 4. Check that labels are clearly visible. 5. Verify that controls are connected and operable. 6. Remove shipping bolts, blocks, and tie-down straps. 7. Verify that filters are installed. 8. Clean furnace flue and inspect for construction debris. 9. Connect and purge gas line. 10. Adjust vibration isolators. 11. Inspect operation of barometric dampers. 12. Check operation of mixing dampers. D. Lubricate bearings on fan. E. Check fan-wheel rotation for correct direction without vibration and binding. F. Adjust fan belts to proper alignment and tension. G. Start unit according to manufacturer's written instructions. H. Check and record performance of interlocks and protection devices; verify sequences. I. Operate unit for an initial period as recommended or required by manufacturer. J. Check internal isolators. K. Check outside-air damper for proper stroke and interlock with return-air dampers. L. Check controls for correct sequencing of heating, cooling, mixing dampers, and normal and emergency shutdown. M. Perform the following operations for both minimum and maximum firing and adjust burner for peak efficiency. Adjust pilot to stable flame. 1. Measure gas pressure on manifold. 2. Measure combustion-air temperature at inlet to combustion chamber. 3. Measure flue-gas temperature at furnace discharge. PAGE 9

10 4. Perform flue-gas analysis. Measure and record flue-gas carbon dioxide and oxygen concentration. 5. Measure supply-air temperature and volume when burner is at maximum firing rate and when burner is off. Calculate useful heat to supply air. N. Start refrigeration system and measure and record the following: 1. Coil leaving-air, dry- and wet-bulb temperatures. 2. Coil entering-air, dry- and wet-bulb temperatures. 3. Outside-air, dry-bulb temperature. 4. Outside-air-coil, discharge-air, dry-bulb temperature. O. Measure and record the following minimum and maximum airflows. Plot fan volumes on fan curve. 1. Supply-air volume. 2. Return-air volume. 3. Relief-air volume. 4. Outside-air intake volume. P. After starting and performance testing, change filters, vacuum heat exchanger and coils, lubricate bearings, and adjust belt tension DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel. 1. Conduct training as specified in Section "Training. 2. Train Owner's maintenance personnel on procedures and schedules related to startup and shutdown, troubleshooting, servicing, and preventive maintenance. 3. Review data in the maintenance manuals. END OF SECTION PAGE 10

SECTION (15733) - DEDICATED OUTDOOR AIR UNITS

SECTION (15733) - DEDICATED OUTDOOR AIR UNITS PART 1 GENERAL 1.01 SUMMARY SECTION 23 74 33 (15733) - DEDICATED OUTDOOR AIR UNITS A. Section Includes: 1. Dedicated Outdoor-Air Units with Energy Recovery B. Related Sections: 1.02 REFERENCES 1. Section

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

SECTION ROOFTOP REPLACEMENT AIR UNITS

SECTION ROOFTOP REPLACEMENT AIR UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections, apply to this Section. B. Related

More information

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating Rooftop Ventilator with Packaged Cooling & Heating Models RV and RVE Institutional Commercial Industrial 800-1,500 cfm.0 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating Packaged

More information

A. Section includes factory-packaged units capable of supplying up to 100 percent outdoor air and providing cooling and heating.

A. Section includes factory-packaged units capable of supplying up to 100 percent outdoor air and providing cooling and heating. SECTION 15850 PACKAGED DEDICATED OUTDOOR-AIR UNITS SPECIFIER: CSI MasterFormat 2004 number: 23 74 33. PART 1 GENERAL 1.1 RELATED SECTIONS A. 15960 Variable Frequency Drives. 1.2 SUMMARY A. Section includes

More information

Construction Standards Page

Construction Standards Page Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 23 81 26 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

62DA,DB,DC,DD,DE,DF07-38

62DA,DB,DC,DD,DE,DF07-38 62D-3SB 62DA,DB,DC,DD,DE,DF07-38 DEDICATED VERTICAL OR HORIZONTAL 100% OUTDOOR AIR UNIT PERFORMANCE DATA UNIT DIMENSION PRINTS ACCESSORY DIMENSION PRINTS Copyright 2011 Carrier Corporation Syracuse, New

More information

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features: RL Packaged Rooftop Units, heat pumps and Outdoor air handling Units Features: Air-cooled condenser, water-cooled condenser, or patented AAON evaporative-cooled condenser, with capacities from 45-240 tons

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section. SECTION 15855 GAS FURNACE/DX COOLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of contract including General and Supplementary Conditions of Division 1 of Specification

More information

THE ULTIMATE ROOFTOP SOLUTION

THE ULTIMATE ROOFTOP SOLUTION Configured Packaged Rooftop Solutions Specializing in Dedicated Outdoor Air Systems (DOAS) Capacities from 6 to 90 Tons Available in 208, 230, 460 and 575 Volts THE ULTIMATE ROOFTOP SOLUTION Service Friendly

More information

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features: RZ PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS Features: Air-cooled condenser, water-cooled condenser, or evaporative-cooled condenser packaged rooftop units from 55-240 tons Water-source

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM SECTION 23 81 06 - PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. This Section includes equipment types that contain all the components of the refrigeration process within

More information

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

A. General: Refer to paragraph entitled SUBMITTAL in Section Include the following data: SECTION 15860 - FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR MECHANICAL

More information

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components. Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.

More information

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information

SECTION (15833) - HVAC POWER VENTILATORS

SECTION (15833) - HVAC POWER VENTILATORS PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted

More information

Addendum Downsville Pike Hagerstown MD April 29, 2016

Addendum Downsville Pike Hagerstown MD April 29, 2016 10435 Downsville Pike Hagerstown MD 21740 301-766-2800 Addendum 2 TO: All Prospective Offerors FROM: Lisa C. Freeman, CPM, Supervisor of Purchasing REF: Bid #2016-56 Kitchen Renovation at E. Russell Hicks

More information

C. Samples for Initial Selection: For units with factory-applied color finishes.

C. Samples for Initial Selection: For units with factory-applied color finishes. SECTION 238126- SPLIT-SYSTEM AIR-CONDITIONERS PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

RHEEM PACKAGE GAS/ELECTRIC

RHEEM PACKAGE GAS/ELECTRIC INDEX ACCESSORIES... 4-2 SAMPLE SPECIFICATIONS... 4-2 RKNL (3-5 TON) SERIES... 4-6 RKNL-B (6-12.5 TON) SERIES... 4-7 RKNL-B (15-25 TON) SERIES... 4-8 RKNL-C (6-12.5 TON CLEAR CONTROL ) SERIES... 4-9 RKNL-C

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges. Service Literature The LGH/LCH high and standard efficiency 5, 0, 5 and 50 ton (, 0.7, 58. and 75.9 kw) units, are configure to order units (CTO) with a wide selection of factory installed options. The

More information

Submittal Data DESCRIPTION STANDARD FEATURES. Base Unit. Cabinet. Refrigerant System. Gas Heat

Submittal Data DESCRIPTION STANDARD FEATURES. Base Unit. Cabinet. Refrigerant System. Gas Heat SINGLE PACKAGE ROOFTOP, GAS HEATING/ELECTRIC COOLING UNIT WITH PURON R (R-410A) REFRIGERANT ONE STAGE COOLING CAPACITY CONTROL: SIZES 08-12 TWO STAGE COOLING CAPACITY CONTROL: SIZES 08, 12 & 14 Submittal

More information

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,

More information

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters. Section 15 _ Energy Recovery Air Handling System Part 1: GENERAL 1.1 Section Includes: A. Energy Recovery Air Handler B. Controls (most by Others) C. Equipment Schedule 1.2 Related Sections: A. Section

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS AutoZone R Model Single Package Rooftop Gas Heating/Electric Cooling Unit Size 07 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION

More information

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004) High Plume Blowers Suggested Specification Section 15500 (Master Format 1996) Suggested Specification Section 23 38 16 (Master Format 2004) PART 1 GENERAL 1.01 WORK INCLUDED High Plume Laboratory Exhaust

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS Single Package Rooftop Gas Heating/Electric Cooling Unit Two Stage Cooling Capacity Control with Puronr (R---410A) Refrigerant Sizes: 17, 20, 24, 28, 30 Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS Single Package Rooftop Gas Heating/Electric Cooling Unit Two Stage Cooling Capacity Control with NOVATIONt Coil Sizes 08, 12, 14 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

Submittal Data Performance Data Electrical Data

Submittal Data Performance Data Electrical Data ERMS Series Submittal Data Submittal Data Unit Designation: Job name: Architect: Engineer: Contractor: Performance Data Revision: 07/01/11 Cooling Capacity: EER: Heating Capacity: COP: Ambient Air Temp:

More information

Modular Supply Make-Up Air Unit

Modular Supply Make-Up Air Unit Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features

More information

Chilled Water DOAS Fan Powered Terminal Units

Chilled Water DOAS Fan Powered Terminal Units Chilled Water DOAS Fan Powered Terminal Units CHILLED WATER DOAS FAN POWERED TERMINAL UNITS DOAS TERMINAL UNITS FEATURES AND BENEFITS MINIMUM VENTILATION CONTROL The DOAS unit provides the Designer, Owner

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Direct Gas-Fired Make-Up Air Models DG and DGX

Direct Gas-Fired Make-Up Air Models DG and DGX Direct Gas-Fired Make-Up Air Models DG and DGX Commercial, Industrial and Kitchen Applications 800-48,000 cfm 4 in. wg External Static Pressure Direct Gas-Fired Heating Optional Cooling - Packaged DX (2.5

More information

48PGD/E/F/L/M/N PG20-28

48PGD/E/F/L/M/N PG20-28 48/50PG-10SB 48PGD/E/F/L/M/N20-28 50PG20-28 SINGLE-PACKAGE COOLING UNITS WITH FACTORY-INSTALLED GAS HEAT SINGLE-PACKAGE COOLING UNITS WITH OPTIONAL ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINTS

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

XeteX, Inc. All Rights Reserved.

XeteX, Inc. All Rights Reserved. Model DXH Custom, packaged, roof mounted or indoor mounted unit with cooling (DX or Chilled Water) and an air-to-air aluminum flat plate exchanger designed to provide pre-cooling and reheat. The DXH is

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

TYPICAL CPA SPECIFICATIONS

TYPICAL CPA SPECIFICATIONS TYPICAL CPA SPECIFICATIONS 4/10/2017 UNIT CONSTRUCTION: Casing: The exterior casing of the unit shall be constructed of 18-gauge, G235 galvanized steel (optional stainless steel or aluminum), unpainted.

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

Energy Recovery with Cooling and Heating Model ERCH

Energy Recovery with Cooling and Heating Model ERCH Energy Recovery with Cooling and Heating Model ERCH 100% Outdoor Air System Dedicated Outdoor Air System 1,000-10,000 cfm 1.75 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating,

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

Direct Gas-Fired Make-Up Air

Direct Gas-Fired Make-Up Air Direct Gas-Fired Make-Up Air Model TSU Heavy Duty, High Airflow Applications Manufacturing and Industrial Facilities Up to 64,000 cfm August 2012 Products Model TSU Direct Gas-Fired Make-Up Air Unit The

More information

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - Systems and Equipment. Page 238239-1 SECTION 238239 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems. 15855 AIR HANDLING UNITS SPECIFIER: CSI MasterFormat 2004 number: 237313 PART 1 GENERAL 1.1 SUMMARY A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution

More information

BARD MANUFACTURING COMPANY, INC. W24G-W60G Gas Heat/Electric Cooling Engineering Specification Guide

BARD MANUFACTURING COMPANY, INC. W24G-W60G Gas Heat/Electric Cooling Engineering Specification Guide BARD MANUFACTURING COMPANY, INC. W24G-W60G Gas Heat/Electric Cooling Engineering Specification Guide 1.0 GENERAL Furnish and install a self-contained, vertical, exterior wall mount, electric air conditioner

More information

The ultimate fresh air solution.

The ultimate fresh air solution. Fresh Access The ultimate fresh air solution. Introducing Fresh Access TM. Expertly designed, our innovative energy recovery ventilator (ERV) unit, split dedicated outside air system (DOAS), and packaged

More information

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT SECTION 23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes packaged roof top unit, unit controls, remote panel, roof mounting curb and base, maintenance service,

More information

HVAC REPAIR/REPLACEMENT 07/18/12 SECTION HVAC - MAJOR EQUIPMENT

HVAC REPAIR/REPLACEMENT 07/18/12 SECTION HVAC - MAJOR EQUIPMENT SECTION 15300 - HVAC - MAJOR EQUIPMENT PART 1 - GENERAL 1.1 MECHANICAL GENERAL A. Section 15010 is applicable. PART 2 - PRODUCTS 2.1 FANS A. General: 1. All fans shall bear the AMCA Certified Performance

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS Single Package Rooftop, High---Efficiency Heat Pump Units With Field---Installed Electric Heat Sizes 08 --- 14 with Puron R (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS

More information

SECTION PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES. A. Chiller package. B. Charge of refrigerant and oil.

SECTION PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES. A. Chiller package. B. Charge of refrigerant and oil. 1 1 1 1 1 1 1 1 0 1 0 1 SECTION 1 PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES A. Chiller package. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled

More information

Indirect Gas-Fired Make-Up Air

Indirect Gas-Fired Make-Up Air Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Placement within a mechanical room is required for all major mechanical equipment. Only small units may be roof-mounted, and shall be made as inconspicuous

More information

Modular Heating & Ventilating Unit Model IGX-HV

Modular Heating & Ventilating Unit Model IGX-HV Modular Heating & Ventilating Unit Model IGX-HV Indirect Gas-Fired Heating Evaporative Chilled Water DX Cooling October 2008 Product Features Model IGX-HV Indirect Gas-Fired Heating and Ventilating Unit

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

SECTION AIR-SOURCE UNITARY HEAT PUMPS

SECTION AIR-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 81 43 AIR-SOURCE UNITARY HEAT PUMPS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES SECTION 15856 MODULAR AIR HANDLING UNITS PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. NFPA Compliance: Modular air handling units and components shall be designed, fabricated, and installed in compliance

More information

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

SECTION WATER-TUBE BOILERS

SECTION WATER-TUBE BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections

More information

GUIDE SPECIFICATIONS - 48HC*D17-28

GUIDE SPECIFICATIONS - 48HC*D17-28 Note about this specification: GUIDE SPECIFICATIONS - 48HC*D17-28 These specifications are written in Masterformat as published by the Construction Specification Institute. Please feel free to copy this

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. Design and specify refrigeration systems and equipment in accordance with "Energy Conservation Standards" stipulated in Section 15010, Basic

More information

Direct Fired Heater Model AD Specification

Direct Fired Heater Model AD Specification Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013 SECTION 15800 - AIR HANDLING EQUIPMENT 1.1 GENERAL A. All air handlers installed shall conform to the University of Rochester specification Guideline for Semi-Custom and Pre-Engineered Air Handling Units.

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.

More information

Advance Release September 2009

Advance Release September 2009 Vertical Air Cooled DSV Series R 410A Model DSV096 DSV120 DSV144 DSV180 Nominal Cooling (Tons) 8 10 12 15 Refrigerant R 410A R 410A R 410A R 410A Cooling Performance Gross Cooling Capacity(Btu/h) 95,000*

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 WATER-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System PART 1 SYSTEM DESCRIPTION 1.1 The HVAC system is based on the CGC HYBRID Hydronic Heat Pump System. 1.2 The system will automatically

More information

SECTION FAN COIL UNITS

SECTION FAN COIL UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections, apply to this Section. B. Related

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional

Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional 1,000-6,000 cfm 2.0 in. wg External Static Pressure Aluminum Plate Heat Exchanger April 2017 Heat Recovery Ventilators Greenheck

More information

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters. SECTION 15622 DIRECT GAS-FIRED BURNER & MANIFOLD SYSTEM PART 1: GENERAL 1.1 Section includes: A. Direct gas-fired heater modules B. Controls C. Equipment schedule 1.2 Related Sections A. Section 01655:

More information

CxA to Answer this Section

CxA to Answer this Section EXHIBIT 01 91 13-3, SAMPLE Construction checklist items are to be completed as part of initial checkout and subsequent startup, preparatory to Functional testing. This checklist does not take the place

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc. System Components with ` Emphasis on Packaged Rooftop Application and Installation Jerry Cohen President Jacco & Assoc. Agenda Define and relate in practical terms the following components: System Effect

More information

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC PART 1 GENERAL 1.01 RELATED REQUIREMENTS SECTION 23 0913 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC A. Section 26 2717 - Equipment Wiring: Electrical characteristics and wiring connections. 1.02 ADMINISTRATIVE

More information

University of Delaware

University of Delaware University Contact: Energy & Engineering Group (302) 831-1744 SECTION 23 73 00_AIR HANDLING UNITS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Modular custom & semi-custom built indoor air handling

More information

B. Unit shall be shipped as a single package unless the unit is too large to fit on a standard tractor-trailer.

B. Unit shall be shipped as a single package unless the unit is too large to fit on a standard tractor-trailer. SECTION 23 72 23 ENERGY RECOVERY UNITS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A Publication No. WT-CSX-0616A Central Station Air Handling Units Complete HVAC Capability Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

BARD MANUFACTURING COMPANY, INC. WG3S-WG5S 2-Stage Cooling with Gas Heat Engineering Specification Guide

BARD MANUFACTURING COMPANY, INC. WG3S-WG5S 2-Stage Cooling with Gas Heat Engineering Specification Guide BARD MANUFACTURING COMPANY, INC. WG3S-WG5S 2-Stage Cooling with Gas Heat Engineering Specification Guide 1.0 GENERAL Furnish and install a self-contained, vertical, exterior wall mount, electric air conditioner

More information

A. Codes and Standards that are Standard at the University:

A. Codes and Standards that are Standard at the University: PART 1: GENERAL 1.01 Purpose: 1.02 References: 1.03 Requirements: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The

More information