June Copyright Climatec
|
|
- Earl Wood
- 6 years ago
- Views:
Transcription
1 June 2013 Copyright Climatec
2 GUIDLINES FOR CENTRAL PLANT OPTIMIZATION The following document provides guidelines which if followed will maximize the energy savings potential for a central plant available through optimization. The attached drawing used is a typical primary variable flow chilled water plant which includes the minimum points required. There are many variations of this design based on size, budgets, and plant requirements but the guidelines will still be applicable. 1 OSA Temperature / Humidity A good quality temperature / humidity must be supplied with at least 3% humidity accuracy. It should be located in a location representative of the building and cooling tower air intakes. It must be located out of direct sunlight at all times throughout the day and out of area that can be heated up due to indirect sunlight, heat, or humidity generating equipment such as a cooling tower or other mechanical equipment. 2 Cooling Tower Selection Select cooling towers with the largest surface area as space and budget will allow. Ensure that low flow nozzles / doers are supplied to allow the best flow turndown possible. These are almost always a special order on cooling tower equipment so early communication with the contractor ordering the cooling tower is necessary. 3 Cooling Tower Isolation / Bypass Valves In a simple 2 chiller 2 tower plant, automatic CT Isolation valves are not required if the cooling towers are selected where the minimum flow for each tower is half the minimum flow of one chiller. If isolation valves are used on open circuit cooling towers make sure the isolation valves are on both the inlet and outlet of the cooling towers. A bypass valve is not typically needed in moderate climates due to the variable speed condenser water pumps. If one is used because of extremely cold conditions it must be installed below the cooling tower sump level.
3 4 Cooling Tower Outlet Temp Individual CT outlet temperature sensors are not required for optimization but are recommended for additional monitoring points and they will allow for fault detection. 5 VFD s Variable Speed Drives for all equipment must be have open protocol communication; preferably BACnet. Most drives provide the necessary points required for optimization through the interface however some may not have atrue kw reading which is required for optimization. Power reading in percent units or deriving power from Amps is not acceptable. 6 Condenser Water Temperatures Condenser supply and return water sensors are required in the common piping between multiple chillers and cooling towers. 7 Chiller Flow If the chillers do not have reliable condenser and evaporator flow readings available from the chiller interface, differential pressure (DP) sensors must be added to determine CHW flow as an analog measurement in gallons per minute (GPM). The following guidelines need to be followed: a. The chiller DP to flow curves need to be obtained from the chiller manufacturers along with the minimum and maximum flow requirements of the condenser and evaporator. Note: A formula as opposed to a graph is preferred for accuracy. The DP sensors should beof the wet-to-wet diaphragm type as opposed to the type with separatehigh and low side transducers with ±0.25% accuracy; recommend Setra Model 230. c. d. The DP sensor range should be selected as low as possible so that the maximum design flow (DP) is approximately in the 75% of the range and the minimum flow (DP) is not below 10% of the range of the instrument. The DP sensors should be installed with a 3-valve manifold for serviceability. Ensure the pressure taps in the pipe are on the chiller side of the isolation valves.
4 8 measurements Chillers should be selected with the lowest NPLV (non-standard part load value) based on the load characteristics the plant will be serving. The chiller must have a network interface which gives all the critical chiller information including water temperatures and refrigerant pressures and temperatures. Onmany chillers, the kw power is an option or not available. If the chiller does not come with a true kw reading then an external power meter will need to be supplied for each chiller. Note: Percent power or calculation from amps is not acceptable. 9 Bypass Valve A modulating bypass valve is required for primary variable pumping systems located on the building side of the chilled water pumps. The bypass valve must be modulating and properly sized for the minimum flow of one chiller. A decoupler is required for primary secondary systems located between the primary and secondary chilled water pump loops. 10 Flow/Energy Meter An Onicon magnetic insertion meter with matchedtemperatures sensors and a BTU (Energy) Totalizer with BACnet interface or similar is highly recommended. An accurate energy reading is critical for the optimization process. The following guidelines must be adhered to: a. The flow and temperature sensors must be mounted on the building side of the bypass valve or, in the case of a primary-secondary system after the secondary chilled water pumps. It is critical that there are enough straight runs of pipe before and afterthe flow meter to allow for accurate flow readings. This is the number one cause for inaccurate energy readings in the plant. c. It is imperative that that the location be coordinated with the mechanical engineer and contractor. Do not trust the drawings alone. Being involved with the shop drawing layout process and onsite location of the flow meter and temperature sensors is a must.
5 11 Plant DP A differential pressure (DP) sensor in the plant is required at a minimum. Optionally, DP sensors can be located near the end of runs or at remote buildings for informational inputs but they are not required if all the chilled water valve positions at the loads are known. If there are areas where valve positions are not known, DP sensors need be located in a representative location near those loads and a minimum DP established for each DP location. 12 Building loads All building loads must be known and understood for proper optimization of the chiller and chilled water pumps. The status of the loads must be available through an Open Protocol network (BACnet preferred). Loadinformation that is highly recommended in order of preference are: a. CHW valve positions. The power (kw) for any variable speed loads that are influenced by CHW temperature. c.` The dehumidification control signal of any humidity sensitive areas.
SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section
More informationA. Detail drawing M1 Standard Chilled Water Schematic 1.03 DESCRIPTION OF THE PULLMAN CAMPUS CENTRAL CHILLED WATER LOOP SYSTEM:
33 60 00 PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. These standards and procedures apply to the use and interface requirements of the Washington State University Central Chilled Water (CCW) system.
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section
More informationMethod to test HVAC equipment at part load conditions
IPLV Method to test HVAC equipment at part load conditions For water cooled chillers: 100% load ( % hrs) + 75% ( Hrs ) + 50% ( Hrs ) + 25% ( Hrs ) = IPLV value Manufacturer can favor this number by tweaking
More informationopti-visor ultra-efficient chiller plant automation Typical specification
opti-visor ultra-efficient chiller plant automation Typical File No: 90.893 Date: february 9, 2015 Supersedes: 90.893 Date: april 20, 2012 contents 1.0 Chilled water plant 4 1.1 General system requirements
More informationF-1100 Series Single Turbine Meters Suitable for pipe sizes 1 ¼ and larger.
ONICON Insertion Turbine Flow Meters Provide an accurate, cost effective option for flow measurement of relatively clean liquids such as those found in closed loop HVAC systems. Each meter is built to
More informationHVAC Water chiller selection and optimisation of operation
HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water
More informationSeries. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost
LL Chillers and Outdoor Mechanical Rooms Air-Cooled Features: Air-cooled condenser chillers with capacities from 35-345 tons Evaporative-cooled condenser chillers with capacities from 35-540 tons Variable
More informationNovember 11, City of Sparks 215 S. 21 st St. Sparks, NV
November 11, 2014 City of Sparks 215 S. 21 st St. Sparks, NV 89432-0857 Attn: Brian Cason Re: Sparks City Hall HVAC Upgrade Project-Alerton Direct Digital HVAC Control System to Match Existing City of
More informationPackaged Instantaneous Domestic Hot Water Generator Energy Source: Boiler Water
Packaged Instantaneous Domestic Hot Water Generator Energy Source: Shown with optional boiler water valve and electronic feed-forward control. Operates with low boiler water supply and return temperatures
More informationChiller Plant Design. Application Guide AG McQuay International. Elevation Difference. Column Height When Pump Is Off
Application Guide AG 31-003-1 Chiller Plant Design 51.5F Return Water To Chiller Two 400 Ton Chillers Each At 300 Tons (Balanced Load) 51.5F 480 gpm Flow Through Decoupler 44F 54F Building Load 600 Tons
More informationA. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.
SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate
More informationWater-cooled chillers with High Speed Centrifugal Compressors
Water-cooled chillers with High Speed Centrifugal Compressors Refrigerant R134a 190-760 (395 to 2660 kw) Refrigerant R1234ze 135 G - 505 G (310 to 1820 kw) Table of Contents Introduction...3 Features and
More informationBES-TECH TECHNOLOGY & SYSTEM INTEGRATION
BES-TECH TECHNOLOGY & SYSTEM INTEGRATION BES-TECH TECHNOLOGY & SYSTEM INTEGRATION DIGI-ACC Digi-ACC is a control kit for air cooled chiller systems, optimizing both chiller and pumps thereby reducing consumption
More informationBOILER APPLICATION GUIDE for:
T MFC Series Boiler Application Guide GF-148-B TECHNICAL APPLICATION GUIDE BOILER APPLICATION GUIDE for: Piping and Controls, Water Quality, and Single/Multi Installations Applies to MFC Series Models:
More informationEZ Plate Instantaneous
EZ Plate Instantaneous Packaged Instantaneous Domestic Hot Water Generator Energy Source: Boiler Water PVI.com Packaged Instantaneous Domestic Hot Water EZ Plate Instantaneous is a factory-packaged, skid-mounted
More informationChiller Plant Design. Julian R. de Bullet President debullet Consulting
Chiller Plant Design Julian R. de Bullet President debullet Consulting 703-483-0179 julian@debullet.com This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer ASHRAE
More informationCommercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark
Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Introduction: Energy use is the single largest operating expense in commercial office
More informationCONTROLLED CHILLED BEAM PUMP MODULE
FIRST COST SAVINGS PROACTIVE CONTROL CONTROLLED CHILLED BEAM PUMP MODULE Active condensation control system effectively eliminates chilled beam condensation High efficiency, variable speed pump uses a
More informationENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY
SUPERIOR IAQ LOW FIRST COST BEST ROI ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY Pinnacle manages 100% of a building s ventilation and indoor humidity load in a single package. Chilled beams have
More informationPACKAGED AIR COOLED Product Data Catalog
PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES
More informationAC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT
AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT Central Chiller Plant (with Cooling Tower and Chilled Water distribution) The other AC configuration is called a Chilled Water or Larger Cooler system. It
More informationSAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.
Chapter 4 Variable-speed pumps. A variable-speed pump varies the flow rate by maintaining a constant pressure differential as zone valves open and close. A sensor measures the difference in pressure between
More informationTITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F
Temperature Control Units Water & Oil - F Portable Chillers Air & Water-Cooled - 7 F Central Chillers Air & Water-Cooled Packages & Modules - 7 F Pump Tank Stations Chilled or Tower Water - gallons Cooling
More informationRSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs
Lesson 1 - Basic Heat Pump Theory (Part 1) Describe the basic operation of a heat pump. Explain the function of various heat pump controls. Interpret the wiring diagrams and performance data provided by
More informationSeries PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:
RZ PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS Features: Air-cooled condenser, water-cooled condenser, or evaporative-cooled condenser packaged rooftop units from 55-240 tons Water-source
More informationIntegrated Automation Instrumentation & Terminal Devices
Sections Included In This Standard: 1.1 Building Systems Control 1.2 Building Aumotation Systems (BAS) 1.1 BUILDING SYSTEMS CONTROL A. HVAC CONTROLS: 1. General: Temperature control zones shall not combine
More informationCONTROLLED CHILLED BEAM PUMP MODULE
ENERGY SAVINGS 1 ST COST SAVINGS PROACTIVE CONTROL CONTROLLED CHILLED BEAM PUMP MODULE Active condensation control system effectively eliminates chilled beam condensation High efficiency, variable speed
More informationterminal units only provide sensible cooling, a separate dehumidification system is usually needed.
providing insights for today s hvac system designer Engineers Newsletter volume 44 3 Dual-Temperature Chiller Plants This Engineers Newsletter describes several dual-temperature configurations that can
More informationFLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK
FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK ENERGY CONSERVATION MEASURE 1 Partial Steam System Decentralization SIEMENS will Furnish and Install condensing hot water boilers with associated
More informationSeries. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:
RL Packaged Rooftop Units, heat pumps and Outdoor air handling Units Features: Air-cooled condenser, water-cooled condenser, or patented AAON evaporative-cooled condenser, with capacities from 45-240 tons
More informationVERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled
FORM 145.05-EG1 (1004) VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU 10 105 Ton Water-Cooled Table of Contents FORM 145.05-EG1 (0804) Features and Benefits.....................................................
More informationGP SERIES Packaged Chillers
Material Handling Process Cooling Temperature Control Size Reduction Temperature Control Process Cooling Material Handling Size Reduction GP SERIES Packaged Chillers Precision Comprehensive Engineered
More informationRooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating
Rooftop Ventilator with Packaged Cooling & Heating Models RV and RVE Institutional Commercial Industrial 800-1,500 cfm.0 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating Packaged
More informationTOTAL SYSTEM EFFICIENCY: CONTROL STRATEGIES & SYSTEM DISTRIBUTION. David Grassl PE Mechanical Engineer Principal
TOTAL SYSTE EFFICIENCY: CONTROL STRATEGIES & SYSTE DISTRIBUTION David Grassl PE echanical Engineer Principal This is the second paper in the total system efficiency series that will detail various control
More informationBy Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE
By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE T he advent of the small scroll or screw chiller, capable of producing condenser water as high as 140
More informationUpdate In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL
Section 23 20 00 FLUID SYSTEMS EQUIPMENT PART 1 GENERAL 1. CHILLERS Page 23 20 00-1 A. Provide chiller packages with centrifugal compressors, or screw compressors, and water cooled condensers. B. Design
More informationDaikin Blueprint: Delivering Hot Water with a Chiller
Daikin Blueprint: Delivering Hot Water with a Chiller Analyzing the design of heat recovery on air-cooled chillers and the effect it has on building energy consumption By Paul Crisman Daikin Chiller Applications
More informationUniversity of Delaware
SECTION 23 21 23_HYDRONIC PIPING SYSTEMS ABOVE GRADE PART 1 GENERAL 1.1 SUMMARY University Contact: Energy & Engineering Group (302) 831-1744 This standard includes hydronic piping requirements for both
More informationDistrict Heat Montpelier. Customer Training
District Heat Montpelier Customer Training 1 Welcome & Overview of Training Introductions District Heat Montpelier Overview In Building Components On Going Maintenance and Best Practices Optimizing Performance
More informationPURCHASING SECTION th Street, Surrey, B.C. V3S 3C7 Tel: Fax: ADDENDUM NO.
PURCHASING SECTION 6645 148 th Street, Surrey, B.C. V3S 3C7 Tel: 604-590-7274 Fax: 604-599-0956 E-mail: purchasing@surrey.ca ADDENDUM NO. 2 REQUEST FOR QUOTATIONS (RFQ) NO.: 1220-040-2014-001 TITLE: DISTRICT
More informationCHILLED WATER SYSTEM 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods
230510 CHILLED WATER SYSTEM PART 1: GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 230000 Basic HVAC Requirements B. Section 230500 HVAC Basic Materials and Methods C. Section
More informationP-K MACH 'n' ROLL DOMESTIC HOT WATER AND COMFORT HEAT SYSTEM
P-K MACH 'n' ROLL DOMESTIC HOT WATER AND COMFORT HEAT SYSTEM Harsco Industrial Patterson-Kelley continues to create innovative solutions that change the expectations of what a domestic hot water system
More informationSummary Comparison of Simulation Program Features
Summary Comparison of Simulation Program Features FEATURE DOE2.2 equest TRACE 700 HAP Public/Proprietary Public Domain Proprietary Proprietary Proprietary Simulation Method 8760 hours 8760 hours 8760 hours
More informationImproving Cold Chain Competitiveness with Danfoss Energy Efficiency Solutions.
Improving Cold Chain Competitiveness with Danfoss Energy Efficiency Solutions www.danfoss.com Agenda Brief on Danfoss Danfoss Business Divisions / Areas Danfoss Drive Solutions for Energy Efficiency in
More informationChapter-8 Capacity Control of Refrigeration Systems
Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control
More information100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION
100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest
More informationWater Piping and Pumps
Technical Development Program DISTRIBUTION SYSTEMS Water Piping and Pumps PRESENTED BY: Michael Ho carriertdp@gmail.com 424-262-2144 Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section
More informationOpen Protocol Data Communications
MicroTech Series-100 Centrifugal Chiller Open Protocol Data Communications Information Packet Version 3.2 April, 1996 - C O N F I D E N T I A L - This Document may not be copied or reproduced in any way
More informationSeptember 19, 20, 2009 Fort Lee, VA
International Energy Agency Energy Conservation in Buildings and Community Systems (ECBCS) Programme Annex 46, U.S. Army Installations Management Command (IMCOM), US Department of Energy, Ft. Lee and The
More informationDISTRIBUTION SYSTEMS. Water Piping and Pumps
DISTRIBUTION SYSTEMS Water Piping and Pumps Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They are targeted
More informationFans and Pumps I. Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong
MEBS6008 Environmental Services II http://www.mech.hku.hk/bse/mebs6008/ Fans and Pumps I Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail: cmhui@hku.hk Sep 2012
More informationWater-Cooled Dual Compressor Screw Chiller
Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,
More informationPRESSURE INDEPENDENT CONTROL VALVE TECHNOLOGY. 3/16/2012 Fred Ferrara 1
PRESSURE INDEPENDENT CONTROL VALVE TECHNOLOGY 3/16/2012 Fred Ferrara 1 Typical Hydronic System Problems Low Delta T s resulting in: 1. Chillers operating at higher capacities and/or longer than necessary
More informationTechnical Development Program
Technical Development Program COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers PRESENTED BY: Omar Rojas Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7
More informationHeat Pumps COMFORT NEED IT. When You
Heat Pumps COMFORT When You NEED IT COMFORT When You NEED IT SpacePak s Solstice heat pumps are air-to-water reverse cycle heat pumps that use the comfort of Hydronics as the primary source for both heating
More informationLL Series Chillers and Outdoor Mechanical Rooms. Engineering Catalog
LL Series Chillers and Outdoor Mechanical Rooms Engineering Catalog Evaporative-Cooled Condenser Air-Cooled Condenser Table of Contents Features and Benefits... 7 Application Information... 11 Unit Selection...
More informationSmardt Oil-Free Chillers
Smardt Oil-Free Chillers Company History in Brief Turbocor compressor invented in Australia in 1993 Turbocor was relocated to Montreal in 1999 Danfoss forms 50/50 partnership in 2004 Smardt was founded
More informationRTHE Series R Helical Rotary Liquid Chiller Tons 60Hz
Features Product and Benefits Catalog RTHE Series R Helical Rotary Liquid Chiller 75-255 Tons 60Hz January 2015 RTHE-PRC002-EN Introduction To meet a wide range of applications in the 75~255 ton water-cooled
More informationSPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw
SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:
More informationTRACE 700. Slide 1. Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE.
Slide 1 TRACE 700 Chiller Sequencing and Controls Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE. Today, we will be talking about the Plant Sequencing and Controls
More informationEnergy Recovery with Cooling and Heating Model ERCH
Energy Recovery with Cooling and Heating Model ERCH 100% Outdoor Air System Dedicated Outdoor Air System 1,000-10,000 cfm 1.75 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating,
More informationDate: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days
Proposal Trane A Division of American Standard Inc. Prepared For: John Weston Desmet Ballestra Job Name: LAUER1 Biodiesel Chiller Pennsylvania Date: August 21, 2006 Proposal Number: G1-95502-1 Engineer:
More informationEnergy / Temp / Flow Monitoring with Ultrasonic Flow Meters
Ultrasonic Flow Meters Energy / Temp / Flow Monitoring with Ultrasonic Flow Meters You will be connected to audio using your computer s speakers. Or, you may select Use Telephone after joining the Webinar
More informationLife Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint. Daryl Showalter ChillerApplications Manager McQuay International
Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint Daryl Showalter ChillerApplications Manager McQuay International Equipment Using Different Kinds Of Equipment Or Different Performance
More informationMEDICAL CHILLER SYSTEMS
Mission Critical Chilled Water Systems Engineered to Exacting Standards Magnetic Resonance Imaging Systems CT Scanners Oncology Linear Accelerators Blood Cooling Systems Precise Laboratory Applications
More informationMicroTech Series-200 Flooded Screw Chiller
Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D
More informationBRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application
1 BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application By: T. S. Wan Date: Oct. 7, 1995 Copy Right 1995 by T. S. Wan All rights
More informationAmerican University Design Standards
25 95 00 CONTROL SEQUENCES FOR HVAC PART 1. GENERAL 1.01 SECTION INCLUDES A. Description of Work B. Control Sequences General Requirements C. System Specific Control Sequences 1.02 RELATED DOCUMENTS A.
More informationModular Chiller Systems. Application Guide
Modular Chiller Systems Application Guide Table of Contents Introduction.... 1 References/Nomenclature Conventions... 2 Terms & Definitions.... 2 Module Size Selection...3 Water Source, Cooling Only and
More informationAPPLICATION GUIDE BEAMS
BEAMS There is an increasing need for energy efficient air conditioning systems as energy codes become more stringent. Chilled beam systems are one such alternate to traditional all air conditioning systems.
More informationHVAC Controls Upgrades: Requirement Details ( )
REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in
More informationCVGF. Water Cooled Centrifugal Chillers
CVGF Water Cooled Centrifugal Chillers January 2010 CVGF Key Features 2 stage centrifugal compressor Semi-hermetic compressor R134a refrigerant Falling film evaporator Economizer cycle NEW Tracer Adaptiview
More informationTRIDENT GS SERIES Central Chiller
Blending Conveying Drying Process Cooling Heat Transfer Size Reduction TRIDENT GS SERIES Central Chiller Compact Innovative Scalable Innovative and compact designs with 50 to 120 individual circuit chilling
More informationWater-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X
Product Data Catalog Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Variable Speed Total Access Modules MS010W, MS020W, MS030W, MS050W MS010V, MS020V,
More informationEVAPORATIVE COOLING AND HUMIDIFICATION. High-Pressure System Wetted Media System
EVAPORATIVE COOLING AND HUMIDIFICATION High-Pressure System Wetted Media System Energy efficient Provides both direct and indirect evaporative cooling Multiple zone capabilities in air handlers, ducts,
More informationMagnetic Bearing Technology: Achievements in Higher Efficiency
Magnetic Bearing Technology: Achievements in Higher Efficiency Magnetic Bearing Compressor 100% Oil Freeeliminates oil system maintenance costs. R134a Refrigerantmeets Montreal protocol and is not subject
More information96% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR
CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR 5:1 FIRING RATE MODULATION LESS THAN 20 ppm NOx DIRECT VENT FLEXIBILITY TO 100 FEET 96% AFUE
More informationCONTENTS. B. System Design and Performance Requirements
15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes
More informationMicroTech Series 200 Centrifugal Chiller
Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History
More informationChiller Plant Efficiency
Chiller Plant Efficiency CW & CHW Temperature Reset Centrifugal Chiller AFDs Variable Primary Pumping (VPP) Doug Hansberry, PE 2014 Spring Forum March 7, 2014 Abstract Adjustable frequency drives (AFDs)
More informationNET ENERGY WATER LOOPS A clear path to net zero energy buildings
Presents NET ENERGY WATER LOOPS A clear path to net zero energy buildings Alan Niles WaterFurnace International This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer
More informationRetrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems
IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended
More informationUW Purchase Specification Section Steam Condensate or Hot Water Meter Page 1 of 9
Page 1 of 9 PART 1 GENERAL 1.02 DESCRIPTION A. Purpose 1. This section covers steam condensate meters, steam condensate sub-meters and hot water sub-meters for use in the Owner's steam systems. 1.03 QUALIFICATIONS
More informationTechnical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: ,
Purpose 355 West Queens Road Technical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: 604-990-2480, building@dnv.org The purpose of this document is to provide
More informationThis guide will discuss the scope of work, and technical requirements of connecting to the Energy Transfer Station(s) (herein referred to as ETS).
Introduction This guide will discuss the scope of work, and technical requirements of connecting to the Energy Transfer Station(s) (herein referred to as ETS). The Purpose of the ETS is to deliver chilled
More informationSequence of operation
Sequence of operation IPS 4000 secondary variable speed control File No: 90.96 Date: february 21, 2013 Supersedes: new Date: new sequence of operation ips 4000 2 list of abbreviations: adj: Field Adjustable
More informationSEQUENCE OF OPERATIONS
SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,
More informationOhio Energy. Workshop HH. Strategies & Technologies to Improve the Boiler Room Efficiency. Wednesday, February 21, p.m. to 3:15 p.m.
Ohio Energy Workshop HH Strategies & Technologies to Improve the Boiler Room Efficiency Wednesday, February 21, 2018 2 p.m. to 3:15 p.m. Biographical Information Jon Green, Mechanical Equip. Consultant
More informationCold Weather Operation Of Cooling Towers
This article was published in ASHRAE Journal, March 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
More informationTrailblazer air cooled scroll chillers
Trailblazer air cooled scroll chillers Changing the way you think about air cooled chillers 30 to 240 tons with Variable Speed Condenser Fan Technology People and ideas you can trust. Changing the way
More informationBOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:
4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XIN INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This
More informationSmardt vs. McQuay Comparison of Standard Options and Other Benefits < 400 tons
Smardt vs. McQuay Comparison of Standard Options and Other Benefits < 400 tons Mike Hayes Director of Sales Smardt vs. McQuay Staging valves for models with 3 or more compressors Level sensor exv control
More informationSmartVFD HVAC and BYPASS
SmartVFD HVAC and BYPASS The Smart Choice for Energy Savings. Saving Energy the Smart Way Buildings consume more than 70 percent of the electricity produced in North America and roughly half of that is
More information96% COMMERCIAL INDUSTRIAL HEATER. Condensing Gas Water Heating System. Thermal Efficiency
NX COMMERCIAL INDUSTRIAL HEATER Condensing Gas Water Heating System 96% Thermal Efficiency Hubbell NX Input 200 to 800,000 BTU/H Easy use touch screen display Stainless steel heat exchanger Floor or wall
More informationTOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal
TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS David Grassl PE Mechanical Engineer Principal Similar to traditional boiler systems, condensing boiler systems have many designs they can operate
More information60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES
60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,
More informationMedium Mass Boilers. Maxim Power VT
Medium Mass Boilers Maxim Power VT What is a Medium Mass Boiler? Sufficient Mass (Boiler water capacity) to act as a built in buffer tank. Sufficient Mass to handle varying system design flows without
More informationINTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012
HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More informationCutting Edge Compressor Technology
CHILLER MODULES Cutting Edge Compressor Technology MagLev ; magnetic levitation Oil Free design Quieter than typical background noise Soft start; pulls only 2 amps at 460V Superior part load efficiency
More information