Technical information Installation instructions

Size: px
Start display at page:

Download "Technical information Installation instructions"

Transcription

1 Technical information Installation instructions UltraGas (15-50) Condensing gas heating boilers for natural gas and liquid gas for modulating operation These instructions apply to the following types: Rated output levels at 40/30ºC and for natural gas 41-UltraGas (15) 3,1-15,5 kw 41-UltraGas (20) 4,0-20,2 kw 41-UltraGas (27) 5,0-27,2 kw 41-UltraGas (35) 5,8-35,7 kw 41-UltraGas (50) 8,3-50,1 kw Hoval products must be installed and commissioned only by appropriately qualified experts. These instructions are intended exclusively for the specialist. Electrical installations may only be carried out by a qualified electrician. The floor standing gas condensing boiler UltraGas are designed and approved for use as heat generators for hot water heating systems with a permissible flow temperature of up to 85ºC1), in accordance with EN 483 and EN 677. They are designed for continuously adjustable reduced output operation in heating systems. 1) See technical data Subject to modifi cations / 00-07/15 EN

2 TABLE OF CONTENTS 1. Important notes 1.1 Safety instructions Key to symbols used Warnings Symbols Acceptance of delivery Scope of guarantee Instruction manuals Regulations, official permits Germany Austria Switzerland Assembly 2.1 Set-up, levelling Technical data 3.1 Description of the boiler Technical data Dimensions Space requirements Boiler-Flow resistance Brief description of the automatic firing device Installation 4.1 Safety information Boiler room requirements Room air dependent installation Room sealed installation Flue gas connection and flue Condensate drainage Design variants Fitting the condensate drain (standard design with siphon) Fitting the neutralisation box Fitting the condensate delivery pump Fitting the neutralisation box and the condensate delivery pump Hydraulic connection Customer-side requirements Hydraulic interconnection Electrical connection Commissioning 5.1 Safety information Filling with water Water quality Bleeding the air from the gas line Switching on the system Gas inlet pressure Setting the gas flow rate CO 2 (O 2 ) and measurement of NOx/CO content in the flue gas (flue gas measurement) Changing over to a different gas type Handover to the user Record - Activation of screed function / 00

3 TABLE OF CONTENTS 6. Maintenance 6.1 Safety information Bleeding Water refilling Renewing fuse Information for combustion controller/chimney sweep regarding emission monitor key Cleaning Cleaning the burner cylinder Cleaning the exterior of the combustion chamber and burner cylinder Leakage testing Cleaning/adjusting the ignition and ionisation device Setting the gas flow rate CO 2 (O 2 ) and measurement of NOx/CO content in the flue gas Clean siphon or neutralisation box Procedure for servicing the neutralisation installation Maintenance of the Neutralisation equipment (if available) / 00 3

4 IMPORTANT INFORMATION 1. Important notes 1.1 Safety instructions The system shall not be put into operation until all relevant standards and safety regulations are met. For a test run, the following minimum conditions must be satisfied: Safety valve installed (closed system) Controls operative (connected to power supply) Sensor for safety temperature limiter is connected (= boiler temperature sensor) System filled with water Siphon filled with water Expansion tank connected Flue gas adapter pipe with flue gas pipe connected to flue. Burner is preset (see point 6.7). WARNING The heat generator can only be de-energised by disconnection from the mains (e.g. all-pole switch). WARNING All electric power supply circuits must be switched off before accessing the terminals. 1.2 Key to symbols used Warnings!!! DANGER... indicates a situation of immediate danger which will lead to serious or fatal injuries if not avoided. WARNING... indicates a situation of possible danger which can lead to serious or fatal injuries if not avoided. CAUTION... indicates a situation of possible danger which can lead to minor or slight injuries if not avoided. NOTICE... indicates a situation of possible danger which can lead to damage to property if not avoided Symbols General warning of a danger zone.! «Warning: dangerous electrical voltage» as a warning for accident prevention. Ensures that people do not come into contact with electrical voltage. The danger sign with the black lighting symbol warns against the danger of electrical voltage. Warning of cutting injuries: Avoid cutting injuries. Clearly indicate the danger of cutting on sharp-edged parts to avoid serious and costly injuries. «Warning of hot surface» sign for indicating safety. Indicates dangers of injury and burns on hot surfaces / 00

5 IMPORTANT INFORMATION Information: Provides important information. Follow the instructions for use. Requirements to comply with the instructions. 1.3 Acceptance of delivery A visual control of the heating boiler should be conducted upon delivery. In the event of damage, the necessary steps should be followed as specified in the delivery contract. The costs for correcting the damage shall be taken over by the individual risk bearer. Tool: Which tools and other equipment are required. Provides important information. Refers to standards and directives. 1.4 Scope of guarantee The guarantee does not cover defects caused by: non-observance of these instructions non-observance of the operating instructions incorrect Installation unauthorised alterations improper use contaminated operating media (gas, water, combustion air) unsuitable chemical additives to the heating water damage due to the exercise of force corrosion through halogen compounds corrosion through nonconforming water quality 1.5 Instruction manuals A summary of all the instruction manuals relevant to this system can be found in the Hoval System User Guide! In exceptional cases the instructions are kept with the respective components! Additional sources of information: Hoval catalogue Standards and regulations / 00 5

6 IMPORTANT INFORMATION 1.6 Regulations, official permits When installing and operating the system, the standards and regulations spec i fied in point to must be complied with at all times Germany DIN EN Heating systems in buildings - Methods for calculating the design heat load DIN EN Flue gas systems - Heat and flow calculation methods DIN EN Heating systems in buildings - Planning of hot water heating systems. DIN 4755 Oil fired combustion systems. Construction, design, safety requirements. DIN 4756 Gas fired combustion systems. Construction, design, safety requirements, design and execution (for gas burner operation). DIN Domestic chimneys, requirements, design and construction. TRD 702 Steam boilers with group II hot water generators. TRD 721 Safety equipment against excessive pressure / safety valves for group II steam boilers. VDI 2035 Prevention of damage through corrosion and scale formation in hot water heating systems. DIN / VDI 0116 Electrical equipment in combustion systems (VDE regulation). See enclosure N for further standards applicable in Germany Switzerland SN EN Heating systems in buildings - Methods for calculating the design heat load SN EN Flue gas systems - Heat and flow calculation methods SN EN Heating systems in buildings - Planning of hot water heating systems. VKF - Association of Cantonal Fire Insurances. Fire service regulations. SVGW Switzerland. Association of the gas and water trade. SNV Ventilation requirements for the boiler Installation room. SWKI BT Quality of water in installations of building technology. Technical tank regulations TTV and further standards and regulations issued by CEN, CEN ELEC, DIN, VDE, DVGW, TRD and by the legislator. Regulations from the local building authority, insurance companies and chimney sweeps must also be complied with. When using gas as fuel, the regulations of the responsible gas board must also be observed. An official permit may be required Austria OENORM Heating systems in buildings - Methods for calculating the design heat load OENORM Flue gas systems - Heat and flow calculation methods OENORM Heating systems in buildings - Planning of hot water heating systems. ÖNorm B 8130 Open water heating systems; safety equipment. ÖNorm B 8131 Closed water heating systems; requirements to safety, construction and testing. ÖNorm B 8133 Hot water supply systems; safety requirements. ÖNorm B 8136 Heating systems, space and other building requirements. ÖNorm M 7515 Dimensioning of chimneys; definitions and calculation procedure. ÖNorm H 5171 Heating systems - construction requirements for buildings. ÖVGW TR-Gas / 00

7 ASSEMBLY 2. Assembly 2.1 Set-up, levelling The boiler is fixed to wooden transport chocks. For transport up and down stairs, it is wise to leave these timbers in place under the boiler. A special foundation plate for the boiler is not an essential, but it is recommended. Space requirement For further information on space requirements, see chapter 3.4. The cleaning apertures must be easily accessible. Installing and levelling the boiler Remove transport chocks. Store nuts and washers. Lift the boiler on one side and put grub screws of boiler base from the bottom through the slot of the boiler sockets. Fix boiler feet using hexagonal nuts (Fig. 01). Using a spirit level, set the boiler in longitudinal and transverse direction and position it with a slight forward tilt. This is done by adjusting the nuts on the boiler feet. After this adjustment, the upper (locking) nuts on the boiler feet must be tightened. Fig / 00 7

8 TECHNICAL INFORMATION 3. Technical data 3.1 Description of the boiler The Hoval UltraGas is a low emission, energy-saving condensing gas boiler comprising the Ultraclean burner system, a gas fired premix burner with combustion air fan. The Hoval UltraGas has a vertically disposed combustion chamber of stainless steel as a primary heating surface and a secondary heating surface of a corrosion resistant aluminium alloy. The secondary heating surface is designed so that part of the water vapour contained in the flue gas is condensed and the vaporisation heat it contains is utilised for the heating circuit. The gas burner is in the form of a break draught burner, which can easily be swung up for maintenance purposes. The UltraGas is designed to operate with natural and liquid gas. The figure below shows the design principle. Gas safety and control devices Combustion air fan Feed tube on left and/or right side Electrode for ignition and flame monitoring TopTronic E controller High temperature return on left and/or right side Flue gas connection Low temperature return on left and/or right side alufer heat exchanger Condensate collection tray Fig / 00

9 TECHNICAL INFORMATION 3.2 Technical data UltraGas (15-50) Type (15) (20) (27) (35) (50) Nominal output 80/60 C with natural gas 1 kw 3,0-14,3 3,8-18,7 4,5-25,0 5,2-32,8 7,5-46,1 Nominal output 40/30 C with natural gas 1 kw 3,3-15,5 4,3-20,3 5,0-27,2 5,8-35,7 8,3-49,9 Nominal output 80/60 C with liquid gas 2 kw 4,5-13,8 4,9-18,6 6,6-24,3 6,9-32,2 9,9-45,5 Nominal output 40/30 C with liquid gas 2 kw 5,0-15,3 5,5-20,7 7,3-27,0 7,7-35,7 10,9-49,9 Nominal load with natural gas 1 kw 3,1-14,5 4,0-19,0 4,7-25,4 5,4-33,3 7,7-46,9 Nominal load with liquid gas 2 kw 4,7-14,3 5,1-19,3 6,8-25,2 7,2-33,4 10,2-47,2 Working pressure heating max./min. bar 3,0/1,0 3,0/1,0 3,0/1,0 3,0/1,0 3,0/1,0 Working temperature max. C Boiler water capacity l Flow resistance boiler 3 z-value 3,5 3,5 3,5 1,1 1,1 Min. water circulation l/h Boiler Weight (without water content, incl. casing) kg Boiler efficiency at full load at 80/60 C % (related to net/gross calorific value) 97,5/87,8 97/88,1 97,9/88,2 97,9/88,2 98,0/88,3 Boiler efficiency at partial load 30% (according to EN 303) % (related to net / gross calorific value) 107,9/97,2 108,0/97,3 108,0/97,3 108,1/97,4 108,1/97,4 Standard efficiency 40/30 C % 109,5/98,6 109,5/98,6 109,5/98,6 109,5/98,6 109,5/98,6 (net calorific value / gross calorific value) 75/60 C % 107/96,4 107/96,4 107/96,4 107,0/96,4 107,0/96,4 Heat loss rate at 70 C Watt Standard emission rate NOx. mg/kwh CO. mg/kwh Content of CO 2 in the exhaust gas max./min. power % 9,0/8,8 9,0/8,8 9,0/8,8 9,0/8,8 9,0/8,8 Dimensions See table of dimensions Connections Flow /ReturnInches R 1 R 1 R 1 R 1¼ R 1¼ Gas Inches Rp ¾ Rp ¾ Rp ¾ Rp ¾ Rp ¾ Flue gas Ø mm E80 E80 E80 E80 E80 Gas flow pressure min./ max. Natural gas E/LL mbar Liquid gas mbar Gas connection value at 0 C / 1013 mbar: Natural gas E - (Wo = 15,0 kwh/m 3 ) Hu = 9,97 kwh/m 3 m 3 /h 1,5 1,9 2,6 3,3 4,7 Natural gas LL- (Wo = 12,4 kwh/m 3 ) Hu = 8,57 kwh/m 3 m 3 /h 1,7 2,2 3,0 3,9 5,5 Propane gas (Hu = 25,9 kwh/m 3 ) m 3 /h 0,6 0,8 1,0 1,3 1,8 Operation voltage V/Hz 230/50 230/50 230/50 230/50 230/50 Control voltage V/Hz 24/50 24/50 24/50 24/50 24/50 Min./Max. electrical power consumption Watt 22/44 22/62 22/56 26/95 28/119 Standby Watt IP rating (integral protection) IP Acoustic capacity - Heating noise (EN part 1) (room air-dependent) db(a) Exhaust noise is radiated from the mouth db(a) (DIN part 47) (room air-dependent/room air-independent) Acoustic pressure level (depending on installation) 4 db(a) Condensate quantity (Natural gas ) at 40/30 C l/h 1,3 1,8 2,4 3,1 4,4 ph value of the condensate ph ca. 4,2 ca. 4,2 ca. 4,2 ca. 4,2 ca. 4,2 Value for flue calculation Temperature class T120 T120 T120 T120 T120 Flue gas mass flow kg/h ,0 78,0 Flue gas temperature at nominal output and operation 80/60 C C Flue gas temperature at nominal output and operation 40/30 C C Mass flow combustion air Nm 3 /h Feed pressure for combustion air/ flue gas system Pa Maximal Draft / negative pressure flue gas outlet Pa Data related to H u. The boiler series is tested for EE/H-settings. With a factory setting of the Wobbe coefficient of 15,0 kwh/m 3 operation at a Wobbe coefficient of 12,0 up to 15,7 kwh/m 3 is possible (a readjustment may be necessary). 2 Data related to H u. 3 Flow resistance boiler in mbar = volume flow (m 3 /h) 2 x z 4 See also notes at Engineering. Boiler flow resistence see diagram / 00 9

10 TECHNICAL INFORMATION 3.3 Dimensions (Dimensions in mm) Type UltraGas (15-27) (35,50) Fig. 03 Type A B C D E F G H UltraGas (15-27) UltraGas (35,50) Heating flow / safety flow R 1" R 1¼" 2 Low temperature-return R 1" R 1¼" 2a High temperature-return R 1" R 1¼" 3 Gas connection Rp ¾" Rp ¾" 4 Flue gas outlet DN80 DN80 5 Boiler control 6 Condensate drain (left or right) incl. siphon DN25 and 2 m PVC continuousflow tube inner Ø 19 x 4 mm 7 Draining 8 Electric cable entry point 9 Sound absorber hood 10 Heating armature group or loading group (Option) / 00

11 TECHNICAL INFORMATION 3.4 Space requirements (Dimensions in mm) Fig. 04 Boiler door incl. burner swings upward and to the left or outward. A = minimum 150 mm * Burner service position front - boiler cleaning from the right A = optimum 300 mm * - Burner service position left - boiler cleaning from the front - Boiler can be placed with the right side directly against the wall - however, a minimum gap of 160 mm is required. * without armature group, 500 mm with armature group The cleaning aperture must be easily accessible. Ensure access to the area beh / 00 11

12 TECHNICAL INFORMATION 3.5 Boiler-Flow resistance UltraGas (15-27) [mbar] UltraGas (35,50) [mbar] [m3/h] 0 0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 m 3 /h = Volume flow mbar = Flow resistance [m 3 /h] 3.6 Brief description of the automatic firing device The automatic firing device BIC960 of the UltraGas only operates in conjunction with the heating controller TopTronic E/UG. For this reason, the automatic firing device only needs to take care of the last remaining functions to ensure the correct operation of a modulating gas boiler. The automatic firing device comprises the following functions: PWM fan control (230V AC) Modulating operation Common electrode for ignition and flame monitoring (ionisation) LPG valve and boiler room fan controllable Inputs for flow sensor 1 flow sensor 2 flue gas sensor water pressure sensor safety temperature limiter (not used) air pressure switch (not used) gas pressure switch Status outputs fault and flame signal Allows connection of additional (external) ignition device RS 485 connection to TopTronic E/UG RS 232 connection to PC Start attempts: maximum 4 Safety period: 5 sec Pre-ignition period: 5 sec Pre-purging period: 50 sec Follow-on time pump (230V AC): 5 min after heat demand Sicherungen: The BIC 960 is fitted with 3 fuses: 2AT Mains 4AT Pump 4AT Burner fan Blowing of one of the two 4AT fuses securing the pump or the burner fan, respectively, will prevent the affected device from starting. A failure of the mains fuse of the automatic firing device is displayed on the TopTronic E/UG by the failure message B:30 Bus interruption to automatic device. The failure appears when there is no communication between automatic firing device and TopTronic E/UG / 00

13 INSTALLATION 4. Installation 4.1 Safety information CAUTION Sharp edges pose a cutting hazard. Handle the cladding parts with care and avoid contact with sharp edges. 4.2 Boiler room requirements The boiler room must satisfy the applicable local building regulations. The boiler room ventilation must satisfy the applicable local regulations in this regard. Boilers may not be installed in rooms containing halogen compounds which can be carried into the combustion air (e.g. wash rooms, drying rooms, DIY rooms, hair dresser rooms). Halogen compounds can originate, for example, from cleaning and degreasing agents, solvents, glue, and bleaching lyes. Ensure that the required combustion air can flow unhindered at all times. This is important for the correct operation of all the boilers installed therein and to protect the users from an oxygen depleted atmosphere. An adequate fresh air supply meeting the local regulations must be provided Room sealed installation Configuration based on a concentric flue system: The suction air is supplied through a double-wall flue system. Ensure the boiler room is sufficiently ventilated. Configuration using a separating piece (optional): The following must be observed when laying out the intake pipe: If the intake opening is installed on the house facade near to a noise-sensitive area (e.g. bedroom windows, garden seating area, etc.) we recommend installing a noise damper in the direct fresh air suction line. The intake opening must be easily accessible. No chemicals or poisonous substances may be stored close to the intake opening The intake opening may not be installed beside fume extraction outlets or other venting outlets. Ensure that the intake aperture is free from any obstructions at all times (leaves, snow,...) A safety grid must be installed on the suction opening on the outside wall Room air dependent installation The applicable regulations do not normally provide any specific data on the size of air intakes. They only require the pressure in the boiler room not to be below 3 N/ m 2. This means that for a rated thermal output of up to 50 kw an air intake with a cross section of at least 300 cm 2 must be available. For rectangular apertures the aspect ratio should not exceed 1.5:1. If a grid is fitted on the air intake, a suitable allowance must be made to obtain an air intake cross section of 300 cm / 00 13

14 INSTALLATION 4.3 Flue gas connection and flue Due to the low flue gas temperatures, condensate forms within the flue. For this reason, Hoval gas heating boilers can not be connected to conventional house chimneys. The flue gas extraction system must comply with the following directives: DVGW (TRGI) ÖVGW SVGW/VKF Pursuant to the abovementioned regulations, a flue gas temperature limiter must be installed in the boiler. The flue gas system must meet the following requirements: Gastight Watertight Acid-proof Approved for flue gas temperatures of up to 120ºC (T 120) Approved for overpressure Unhindered back flow of condensate into the boiler can only be ensured if: The gradient of the horizontal connection elements is at least 50 mm/m. Only one heat generator may be connected to the same chimney. If two heat generators are to be connected to the same chimney, the relevant regulations must be complied with. Cross sections and maximum lengths are calculated on the basis of graphs or tables. The tables can be obtained from the chimney or flue system manufacturer. The calculation values can be obtained from the table under point 3.2. The flue gas conduit cross sections and lengths are calculated following the technical data for the boiler. The concentric supply air/exhaust system of the boiler can also be conducted horizontally backwards. The Hoval remodelling set allows a remodelling on site / 00

15 INSTALLATION 4.4 Condensate drainage The condensate drainage pipes on the boiler must be made of corrosion resistant material. The following materials are suitable for condensate drainage: Possibility 3 - see chapter 4.8 Siphon and condensate delivery pump Without neutralisation, condensate discharge into higher drain line. PVC, PE, PP, ABS The local regulations regarding condensate drainage must be observed. 4.5 Design variants Possibility 1 - see chapter 4.6 Execution with siphon Condensate discharge into lower drain line. Fig. 07 Possibility 4 - see chapter 4.9 Neutralisation box and condensate delivery pump With condensate neutralisation - condensate discharge into higher drain line. Fig. 05 Possibility 2 - see chapter 4.7 Execution with neutralisation box For condensate discharge in lower drain line, incl.condensate neutralisation. Fig. 08 Fig / 00 15

16 INSTALLATION 4.6 Fitting the condensate drain (standard design with siphon) 1. Remove front cover (1a, Fig. 09). Release lateral locking bolt (1, Fig. 09) (approx. ¼ turn to the left). Lift the front cover straight upwards and remove towards the front. 2. Remove base plate (2, Fig. 09). Lift base plate straight upwards and remove. 3. Screw siphon (3, Fig. 09) on the condensate tray (4, Fig. 09) and tighten securely (connection must be sealed)! 4. NOTICE Slide the siphon support (3a) under the siphon. 6. Fit drain (5, Fig. 09) on siphon (3, Fig. 09) and lead it outwards (optionally left or right side) through the aperture (5a, Fig. 09). 7. Fit connecting line (5, Fig. 09) to the drain line (2m hose enclosed with the boiler). 8. Reattach front cover (1a, Fig. 09) and base plate (2, Fig. 09).! CAUTION Before commissioning, the siphon must be filled with water in order to prevent flue gas leakage. If a neutralisation box is to be fitted, you will find the further installation steps on the next page. NOTICE The condensate drain must be made of corrosion-resistant material. 1 1a a 3a 5 Fig / 00

17 INSTALLATION 4.7 Fitting the neutralisation box (if fitted) 1. Remove the neutralisation box from its packaging. Remove the front and rear cover of the neutralisation box. 2. Empty the neutralisation granulate (Neutroxid) into the neutralisation box and distribute evenly. 5. Fit rear cover (9, Fig. 12) of the neutralisation box. 6. Fit jubilee clip (10, Fig. 12) approx. 20mm from the upper end of the hose and tighten slightly. The hose (10a, Fig. 12) of the connection eccentric (10b, Fig. 12) must be aligned towards the left a front Neutralisation granulate (Neutroxide) Fig Remove front cover (1a, Fig. 11). Release lateral locking bolt (1, Fig. 11) (approx. ¼ turn to the left). Lift the front cover straight upwards and remove it towards the front. 4. Remove base plate (2, Fig. 11). Lift the base plate straight upwards and remove it. 10b Fig Slide the neutralisation box (11, Fig. 13) into the boiler until the hose of the siphon (6, Fig. 10) is directly beneath the drain connection. 1 1a 11 Fig Fig / 00 17

18 INSTALLATION 8. The hose of the siphon (11, Fig. 14) can be easily pushed onto the drain connection of the condensate drip tray by lifting the neutralisation box (10a, Fig. 12). 4.8 Fitting the condensate delivery pump 13. Install the condensate delivery pump (14, Fig. 17) as shown in the drawing. Fig Slightly loosen the jubilee clip (10, Fig. 15) and push it upwards. Firmly tighten the jubilee clip (connection must be sealed) Fig. 15 Fig Fill the neutralisation box with water. 11. Fit the front cover (13, Fig. 16) of the neutralisation box. 12. Fit base plate (2, Fig. 16) and front cover (1a, Fig. 11) Fig. 16! CAUTION Before commissioning the neutralisation box must be filled with water in order to prevent flue gas leakage. The condensate drain must be made of corrosion-resistant material / 00

19 INSTALLATION 4.9 Fitting the neutralisation box and the condensate delivery pump 1. Fit condensate delivery pump. (14, Fig. 18). 4. Remove front cover (1a, Fig. 20). Release lateral locking bolt (1, Fig. 20) (approx. ¼ turn to the left). Lift the front cover straight upwards and remove towards the front. 5. Remove base plate (2, Fig. 20). Lift base plate straight upwards and remove a 2 Fig. 20 Fig Fit rear cover (9, Fig. 21) of the neutralisation box. 7. Fit jubilee clip (10, Fig. 21) approx. 20mm from the upper end of the hose and tighten slightly. The hose (10a, Fig. 21) of the connection eccentric (10b, Fig. 21) must be aligned towards the left. 2. Remove the neutralisation box from its packaging. Vorderen und hinteren Remove the front and rear cover of the neutralisation box. 3. Empty the neutralisation granulate (Neutroxide) into the neutralisation box and distribute evenly a Fig. 19 front Neutralisation granules (Neutroxide) 10b Fig / 00 19

20 INSTALLATION 8. Slide the neutralisation box (11, Fig. 22) into the boiler until the hose of the siphon (10a, Fig. 21) is directly beneath the drain connection. 11. Fill the neutralisation box with water. 12. Fit the front cover (13, Fig. 25) of the neutralisation. 13. Fit base plate (2, Fig. 25) and front cover (1a, Fig. 20). Fig The hose of the siphon (10a, Fig. 21) can be easily pushed onto the drain connection of the condensate drip tray by lifting the neutralisation box (11, Fig. 23).! 2 13 Fig. 25 CAUTION Before commissioning the neutralisation box must be filled with water in order to prevent flue gas leakage. The condensate drain must be made of corrosion-resistant material. Fig Slightly loosen the jubilee clip (10, Fig. 24) and push it upwards. Firmly tighten the jubilee clip (connection must be sealed). Fig / 00

21 INSTALLATION 4.10 Hydraulic connection The boiler comprises the following safety equipment, in accordance with EN 12828: Minimum pressure limiter DBmin Safety maximum pressure limiter DBmax Hydraulic pressure monitor DBmax + 50% Thermostat Temperature monitor TBmax + 20% Safety temperature limiter Example: UltraGas (15-50) with calorifier and direct heating circuit Hydraulic schematic BDEE005 To achieve an optimal efficiency, ensure that the return pipe is properly connected. 1 2 Fig. 27 Fig High temperature return (e.g. venting group or calorifier) 2. Low temperature return (e.g. underfloor heating) Customer-side requirements A pressure expansion tank adapted to the heating system, water volume and static height. TTE-WEZ B1 AF DKP Optional RBM TTE-GW NOTICE Make sure to close off unused connectors tightly. TopTronic E basic module heat generator (installed) Flow temperature monitor (optional) Outside sensor Pump for heating circuit without mixer TopTronic E room control module TopTronic Gateway Hydraulic interconnection When combining a calorifier with floor heating, a mixer needs to be installed. A minimum amount of circulating water is not required. Regarding suitable hydraulic connections, please observe the notes in the planning documentation of the relevant Hoval sales company! / 00 21

22 INSTALLATION 4.11 Electrical connection The electrical connection must be carried out by an approved electrician. The connection diagram is located within the boiler control box. The electrical circuit diagram is supplied separately. Refer to this for the conductor cross section required for the mains supply. The following applies to Austria and Germany: A connection diagram is provided with the boiler control unit. The power supply must be fitted with an omnipolar isolation switch with a contact gap of at least 3 mm. The following applies to Switzerland: The electrical connections must comply with the systemspecific electrical circuit diagram! Safety measures for EMC installation Bei Regelgeräten mit eigenem Netzanschluss, Netz- Fühler- bzw. Busleitungen getrennt verlegen. CAUTION Do not reach into the marked area (Fig. 28) when folding out the terminal box. Danger of cuts and pinching in the area of the trim strip (7). Wear gloves. Grip the terminal box by the left and right sides, not by the underside! Cable trunking with dividing partitions should be used. The electrical connection must be connected in accordance with the applicable standards of nationally or internationally recognised professional associations. Procedure to remove the front covering panel 1. Remove front cover (1, Fig. 28), after first releasing the lateral locking bolt (1a, Fig. 28) (turn approx. ¼ turn to the left and pull out as far as the stop). Lift the front cover (1) straight upwards and remove towards the front. 2. Remove lower front cover (2, Fig. 28), after first releasing the lateral locking bolt (2a) (turn approx. ¼ turn to the left and pull out as far as the stop). Slightly raise the lower front cover (2 and 4, Fig. 28) and remove towards the front. 3. Remove the locking screw (3a, Fig. 28) on the right. 4. Lift the switch control box (3, Fig. 28) and fold it out. 5. Cable entry refer to the Technical Datasheet (6, Fig. 28). The electrical connection is to be made in accordance with the diagram supplied. 1 1a 3a The mains connection for the heating system (boiler-control panel-control unit) must be configured in form of an independent electric circuit. No other electrical loads (light, power outlets,...) may be connected to that electric circuit. The external sensor may not be installed close to transmitters or receivers (garage door openers, amateur radio aerials, radio alarm systems,...). Recommended conductor cross sections: Conductor type Cross section Length Power supply of the heat generator (230 V) Cables carrying mains supply voltages from actuators Extra-low voltage cables (sensors) Data bus cables (screened) min 1.5 mm 2 with 13 A fuse min 1.0 mm 2 min 0.5 mm 2 2x2x0.6 mm 2 unlimited m unlimited m max. 50m max. 100m Fig / 00

23 COMMISSIONING 5. Commissioning After filling the system with water, bleed any air and check for water leaks. Before putting the boiler into operation, the siphon and neutralisation tank needs to be filled with water. When starting up the system for the first time, the correct operation of all the safety and control devices must be verified. The operation and maintenance of the system must be explained to the user in detail. he combustion air needs to be filtered in very dusty environments. The gas flow pressure must be checked and the CO 2 value set correctly. 5.1 Safety information! CAUTION Sharp edges pose a cutting hazard. Handle the cladding parts with care and avoid contact with sharp edges! Danger of injury for unqualified personnel. Maintenance and cleaning work may only be performed by trained personnel or by the Hoval Customer Service. NOTICE Danger of damaging the system by filling it with incorrect liquids. Water filled into the system must have drinking quality. 5.2 Filling with water Filling of the heating system may only be carried out by qualified personnel. Die ÖNORM H5195, The European Standard EN and the Directive VDI 2035 must be observed (see point 5.3). 1. Open the isolating valves in the flow and return lines. 2. Connect the water hose to the filling tap. 3. Fill the heating system slowly. Monitor the water level on the manometer. Use only chemical additives with suppliers confirmation of their safe usage. Anti-freeze additive may be filled up to a maximum of 40% and to a minimum according to the manufacturer s information. The anti-freeze or anti-corrosion agent concentration must be checked at least once per year. The identical product must be used when replenishing the anti-freeze or anti-corrosion agents. When transferring to operation without antifreeze or anti-corrosion agents, the system is to be thoroughly flushed through several times before refilling with water / 00 23

24 COMMISSIONING 5.3 Water quality Heating Water The European Standard EN and the directive VDI 2035 must be observed. In particular, attention must be paid to the following stipulations: Hoval boilers and calorifi ers are designed for heating plants without signifi cant oxygen intake (plant type I according to EN 14868). Plants with - continuous oxygen intake (e.g. underfloor heating systems without diffusion proof plastic piping) or - intermittent oxygen intake (e.g. where frequent refilling is necessary) must be equipped with separate circuits. Treated fi lling and replacement water must be tested at least 1x yearly. According to the inhibitor manufacturer s instructions, more frequent testing may be necessary. A refi lling is not necessary if the quality of the heating water in existing installations (e.g. exchange of boiler) conforms to VDI The Directive VDI 2035 applies equally to the replacement water. New and if applicable existing installations need to be adequately cleaned and fl ushed befor being fi lled. The boiler may only be fi lled after the heating system has been fl ushed! Parts of the boiler / calorifi er which have contact with water are made of ferrous materials and stainless steel. On account of the danger of stress cracking corrosion in the stainless steel section of the boiler the chloride, nitrate and sulphate content of the heating water must not exceed 50 mg/l. The ph value of the heating water should lie between 8.3 and 9.5 after 6-12 weeks of heating operation. Filling and replacement water For a plant using Hoval boilers untreated drinking water is generally best suited as heating medium, i.e. as fi lling and replacement water. However, as not all drinking water is suitable for use as as fi lling and replacement water the water quality must fulfi l the standard set in VDI Should the mains water available not be suited for use then it must be desalinated and/ or be treated with inhibitors. The stipulations of EN must be observed. In order to maintain a high level of boiler effi ciency and to avoid overheating of the heating surfaces the values given in the table should not be exceeded (dependent on boiler performance ratings - for multi-boiler plants rating of smallest boiler applies - and on the water content of the plant). The total amount of fi lling and replacement water which is used throughout the total service life of the boiler must not exceed three times the water capacity of the plant. Maximum filling capacity based on VDI 2035 Total hardness of the filling water up to... [mol/m 3 ] 1 <0,1 0,5 1 1,5 2 2,5 3 >3,0 f H < >30 d H <0,56 2,8 5,6 8,4 11,2 14,0 16,8 >16,8 e H <0,71 3,6 7,1 10,7 14,2 17,8 21,3 >21,3 ~mg/l <10 50,0 100,0 150,0 200,0 250,0 300,0 >300 Conductance 2 <20 100,0 200,0 300,0 400,0 500,0 600,0 >600 Boiler size of the individual boiler maximum filling quantity without desalination to 50 kw NO REQUIREMENT 20 l/kw 1 Sum of alkaline earths 2 If the conductance in µs/cm exceeds the tabular value an analysis of the water is necessary / 00

25 COMMISSIONING 5.4 Bleeding the air from the gas line Observe the relevant regulations when bleeding the gas line Open the gas shut-off valve. Bleed the air up to the gas armature. 5.5 Switching on the system Switch on blocking switch to release the burner. WARNING The heat generator is live when it has been connected to the mains. 5.6 Gas inlet pressure The gas flow may only be adjusted and the heating system therefore started up, if the minimum flow pressure values are achieved (see point 5.7 Adjusting the gas flow). The minimum flow pressure in the connector pipe must reach the following values: Natural Gas 18 to 50 mbar Liquid gas 37 to 50 mbar / 00 25

26 COMMISSIONING 5.7 Setting the gas flow rate CO 2 (O 2 ) and measurement of NOx/CO content in the flue gas (flue gas measurement) Torx T40, screwdriver, size 5 and/or allen key 4 mm The Honeywell multiple actuator allows measuring the inlet pressure on meas uring nipple A. A B C D Measuring nipple gas inlet pressure Measuring nipple gas outlet pressure Gas choke Offset screw D 1. Press the emission monitoring key. After 20 min. the controller switches over to normal operation automatically. 2. Position the emission monitor in the flue gas duct. 3. Set the boiler to maximum output (100%). 4. Set the CO 2 (O 2 ) value by turning the chokescrew C. The content in the flue gas must be between CO 2 = (O 2 = 5,9-5,5) vol% (dry). 5. Set the boiler to minimum output (1%) 6. Set the CO 2 (O 2 ) value by turning the choke screw D. The content in the flue gas must be between CO 2 = (O 2 = 5,9-5,5) vol% (dry). 7. Measurement of NOx and CO content. The measured values must meet the limiting values prescribed by the regulations. Values exceeding these reference values are an indication of faulty burner setting, gas burner or heat exchanger contamination or gas burner defect. NOTICE If the limiting values prescribed by the regulations are exceeded, the boiler must be put out of operation and the corresponding measures for repair work must be initiated. 8. Press the emission monitoring key. Fig. 29 C B A Flow setting operation: To set the flow on the venturi, both flue gas values need to be controlled. e.g.: Set upper value - control lower value - value incorrect - set lower value - control upper value / 00

27 COMMISSIONING 5.8 Changing over to a different gas type This changeover may only be carried out by an authorised specialist or by the Hoval Customer Service. 5. Set the CO 2 (O 2 ) content to CO 2 = (O 2 = 5,9-5,5) vol% (dry). (flow setting operation as described in section 6.7) 6. Install the boiler hood Changeover from natural gas H to natural gas L An emission check is required when changing to a natural gas of lower calorific value; a correction of the CO 2 (O 2 ) value may be necessary (see point 6.7 Setting the gas flow rate). Changeover from natural gas to liquid gas The applicable local provisions for operating a boiler with liquid gas are to be complied with. VKF, DVGW, ÖVGW Changeover only possible by means of a conversion kit. NOTICE Ensure that the fuel type in the measuring device has been set correctly. 5.9 Handover to the user The manufacturer of the unit is responsible for providing operating instructions for the complete system. The following must be carried out during handover to the user: Provide instructions in the operation and maintenance of the system Handover of all the instruction manuals and documents Explain to the user that these instructions must be kept with the system at all times Written confirmation of receipt of instruction The handover report is on the last page of the document. The conversion kit contains: gas pressure switch yellow sticker Removing the gas pressure switch: 1. Close the gas shut-off valve. 2. Set the blocking switch to «0» and disconnect the heat generator from the mains (main switch, fuse). 3. Take off the boiler hood 4. Remove the gas pressure switch Install the liquid gas pressure switch: NOTICE Ensure that the liquid gas line is free of any air. Any air in the liquid gas line can have a negative influence on the flue gas values. 1. Install the liquid gas pressure switch Set the AMP flat pin to position 1 and 3 2. Affix the yellow sticker on the boiler name plate 3. Open the gas valve 4. Set the main system switch to 1 NOTICE Adjust fan speed of rotation according to the list of parameters Liquid gas adaptations / 00 27

28 COMMISSIONING 5.10 Record - Activation of screed function Description of function The control module of the TopTronic E contains a functional sequence used for drying out screed fl oors. To start the screed drying, it is necessary for the individual functions to be set accordingly. Flow temperature Heating-up phase ( ) Inertia phase (04-064) Cool down phase ( ) 40 C 35 C Stabilisation temperature (04-063) 30 C 5 K -5 K 25 C Current heat generator temperature = start temperature 1 d 1 d 20 C 0 Start End Days Function Parameters Value Description Heating-up phase K/d Kelvin per day (rising) Stabilisation temperature C Set maximum temperature Inertia phase Number of days in stabilisation temperature Cooling off phase K/d Kelvin per day (falling) Activate screed function (ON) Start and stop screed drying NOTICE The graphic/table shows the factory settings. The time profi le and the maximum fl ow temperature must be discussed with the screed layer, otherwise there could be damage to the screen and in particular, cracks. REACTION screed function Start/stop: Switch parameter ON (1) or OFF (0) Power failure in heating-up phase: program restart Failure in the steady-state phase: Retain maximum temperature and add the failure time to the steady-state phase Power failure in the cooling off phase: Measurement of actual fl ow value and continue cooling until start value reached Program end: Previous basic program active again Settings in the TopTronic E control module Can only be set in the corresponding user level. Settings under Start screen > Main menu > Service > H-GEN > Heating circuit > Heating circuit 1, 2, 3* > Screen > to * If there are several heating circuits, a separate screed function must be assigned to each heating circuit / 00

29 COMMISSIONING Function display 1 2 No. Icon Function 1 Screed drying active Various settings can be made as well. Prioritisation of the screed function means the settings are only active at the end of the function. 2 Information remaining run time Request of the active function phase, the ACT temperature as well as the remaining run time. Logging Please cut out the log and attach it to the controller during active screed function. NOTICE The time profi le and the maximum fl ow temperature must be discussed with the screed layer, otherwise there could be damage to the screen and in particular, cracks. Screed function activated by: Profile and flow temperature discussed with: Screed function activated on: Screed function ends on:... Date and signature / 00 29

30 MAINTENANCE 6. Maintenance NOTICE Missing or faulty cleaning and maintenance may cause damage to the installation. The heating installation must be surveyed and cleaned once a year. If required, installation maintenance must be carried out. Defects must be remedied immediately in order to prevent damages to the installation! 6.1 Safety information CAUTION Sharp edges pose a cutting hazard. Handle the cladding parts with care and avoid contact with sharp edges. 6.3 Water refilling The European Standard EN and the Directive VDI 2035 must be observed (see point 5.3). The systems warns when the water pressure falls below 1 bar and the boiler output is reduced to 50%. If the water pressure falls below 0.5 bar, the boiler is set automatically to a fault state. The system must be refilled with water when the pressure falls below the minimum system pressure: 5. Connect the filling hose to the water supply 6. Remove the air from the filling hose 7. Connect the filling hose to the filling and draining cock 8. Top up with water (see point 5.2).! CAUTION Danger of injury for unqualified personnel. Maintenance and cleaning work may only be performed by trained personnel or by the Hoval Customer Service. NOTICE After repair work respectively exchanging boiler parts, a flue gas measurement according to point 6.7 must be carried out imperatively. WARNING The heat generator must be de-energised for maintenance. Set the blocking switch to «0» and disconnect the heat generator from the mains (main switch, fuse). 6.4 Renewing fuse WARNING Electrical installations may only be carried out by a qualified electrician. 1. Set the blocking switch to «0» and disconnect the heat generator from the mains (main switch, fuse). 2. Remove the front casing according to the procedure in chapter Remove the cover from TopTronic E - WEZ (press to the side and remove). 4. Renew fuse (T 10A 250V). WARNING All electric power supply circuits must be switched off before accessing the terminals. Perform reset. See operating manual. 6.2 Bleeding 1. Open all radiator valves. 2. Heat up the system for at least half a day with a high flow temperature. 3. Turn off the boiler and wait 5 minutes. 4. Bleed all the air form the system. 5. Mount protecting cover, close casing. 6. Restore the electrical power supply. Fig / 00

31 MAINTENANCE 6.5 Information for combustion controller/chimney sweep regarding emission monitor key This chapter is exclusively intended to describe the function of emissions and manual operation settings for the fi ring monitoring technician / chimney sweep. All operating elements are described in the operating instructions.! CAUTION Danger of scalding with hot water, since the hot water temperature can exceed the target setpoint temperature. NOTICE In order to protect underfl oor heating systems against impermissible superheating during emissions measurement / manual operation, it is necessary to implement appropriate safety measures (e.g. pump switch-off with maximum thermostat). The output and duration of the emission measurement can be set in the "Emission" main menu, and reactivated if required. Emission metering Setting at: Home screen > Main menu (page 1) > Emission. For detailed information see operating instructions, "Emission" chapter. Power limitation with 2-stage burner: 0 to 50% = 1st stage 51 to 100% = 2nd stage REACTION to emission metering Go back after expiry of the time unit/time specifi cation of return to the main menu Setpoint temperature = Maximum temperature limit Forced energy is used in an attempt to keep the corresponding heat generator temperature to 60 C Regulate heating circuits and the calorifi ers to their maximum temperature (in the direct heating circuit only if the hot water basic program is set to parallel operation) Manual mode Settings under: Home screen > Main menu (page 2) > Manual operation. For detailed information see operating instructions, "Emission" chapter. REACTION for manual operation Setting the required setpoint temperature using the selected heating or hot water circuit All heating pumps ON Note the maximum permissible temperature of surface heating! / 00 31

32 MAINTENANCE 6.6 Cleaning The boiler may only be cleaned by an authorised technician or by the Hoval Customer Service. Reassembly: 1. Replace the gasket on the gas connection 2. Reassemble the burner in reverse order 3. Check for leaks 4. Carry out a flue gas measuring according to point 5.7 The Hoval gas heating boiler should be cleaned and maintained once every year. If the Hoval gas heating boiler was in operation during the building phase, it will be necessary to carry out a check for cleanliness. If the boiler is dirty, clean it Cleaning the burner cylinder The burner cylinder must be cleaned if visible contamination exists (such as deposits, e.g. builder s dust) Fig. 31 Adjustable spanner, screw driver, open end spanner SW 8, vacuum cleaner, compressed air, water. Preparation: 1. Set the blocking switch to «0» and disconnect the heat generator from the mains (main switch, fuse). 2. Close the main gas valve 3. Remove the sound insulation covers 4. Disconnect all the burner connector plugs 5. Pull the corrugated hose (1, Fig. 31) off the venturi tube on the burner (if present). 6. Disconnect the earthing cable (2, Fig. 32) from the burner cylinder 7. Disconnect the gas connection from the gas armatures. 8. Unscrew the fan with the gas mixing unit in place (3, Fig. 32) Removal and cleaning: CAUTION Danger of burns, let the boiler cool down or wear protective clothing Fig. 32 Fig Safety gloves must be worn when removing the burner cylinder 2. Lift the burner cylinder out (4, Fig. 33). 3. Clean the premix burner with compressed air inside and out, or rinse thoroughly with water 4. Remove dust and dirt particles with a vacuum cleaner (Fig. 34). Fig / 00

33 MAINTENANCE Cleaning the exterior of the combustion chamber and burner cylinder! WARNING Chemical burn hazard through cleaning agents. Safety gloves and eye protection must be worn when using cleaning agents. Observe the information on the original packaging. NOTICE The system can be damaged when using incorrect cleaning agents. Use only cleaning agents approved for gas boilers with aluminium components. Spray on the cleaning agent undiluted Open end spanner SW 17, adjustable spanner, screw driver, spray gun Preparation: 1. Set the main switch on the boiler control unit to 0. vom Netz trennen (Hauptschalter, Sicherung). 2. Close the main gas valve 3. Remove the sound insulation cover 4. Disconnect all the burner connector plugs 5. Pull the corrugated hose off the venturi tube on the burner (if present) Reinigen: 1. Spray the combustion chamber and alufer tubes (10, Fig. 36). The best results are obtained with a spray gun with a suitable wide jet nozzle (fan or conical jet). We recommend, e.g.: Desoxin 2. Leave the applied cleaning agent to react as instructed by the manufacturer 3. Then remove the contamination on the combustion chamber and alufer tubes by spraying them with clean water Use a powerful jet 4. Repeat the procedure in case of stubborn dirt 5. Flush clean the bottom tube plate Use an angled spray lance 6. Clean and dry the boiler tray 7. Clean the siphon see point 6.8: screw it off clean it screw it back on fill it with water 8. Clean the fabric material in the burner cylinder with compressed air 9. Reconnect the gas and electrical connections 10. Place the boiler into operation 11. Carry out a flue gas measuring according to point 5.7. Correct the settings, if necessary. Complete a measurement record. 10 Opening the combustion chamber: 1. Loosen the cap nut SW17 2. Lift and turn the burner with the boiler door sideways (8, Fig. 35) 3. Remove the neutralisation box and siphon or maintenance of the neutralisation unit see point 6.9) Fig Fig / 00 33

34 MAINTENANCE Leakage testing After cleaning or at least every five years, the seal between the combustion chamber and the condensate drip tray must be checked for leakage. This can be done by filling the boiler with water. Ignition electrode Ignition/ionisation electrode 80 1 Fig Water fill level Fig mm 5 mm Cleaning/adjusting the ignition and ionisation device The distance between the ignition electrode and the burner cylinder must be approx. 4 mm. Fine sanding paper, long-nosed pliers, blowtorch, compressed air. Fig. 39 Preparation: 1. Set the blocking switch to «0» and disconnect the heat generator from the mains (main switch, fuse). 2. Open the combustion chamber as described under point mm Cleaning: 1. Sand the ignition and ionisation device with fine sanding paper. 2. Clear the sanding dust. Adjustment: 1. Heat the ignition electrode at the kink with the blowtorch until it glows red (Fig. 38). 2. Bend the ignition electrode with the long-nosed pliers (Fig. 39). Distance to the burner cylinder 10 mm. Assembly: 1. Renew seal on gas connection. 2. Assemble burner in the reverse order. 3. Check for gas leaks. Fig Setting the gas flow rate CO 2 (O 2 ) and measurement of NOx/CO content in the flue gas (according to point 5.7.) Maintenance should be carried out at least every second year or after consumption of the neutralisation granulate (check ph value with litmus paper, if necessary) / 00

Technical information Installation instructions

Technical information Installation instructions Technical information Installation instructions UltraGas (125-1000) Condensing gas heating boilers for natural gas and liquid gas for modulating operation Rated output levels at 40/30ºC and for natural

More information

Hoval TopGas (12, 16, 22)

Hoval TopGas (12, 16, 22) Hoval TopGas (2, 6, 22) Wall gas condensing boiler with or without calorifier TopVal Description Hoval TopGas Boiler Wall mounted gas condensing boiler Heat-exchanger out of corrosion resistance aluminium

More information

Technical information Installation instructions. Uno-3 ( ) Oil/gas boiler. These instructions apply to the following types:

Technical information Installation instructions. Uno-3 ( ) Oil/gas boiler. These instructions apply to the following types: Technical information Installation instructions Uno-3 (130-280) Oil/gas boiler These instructions apply to the following types: 41-Uno-3 (130, 160, 190, 220, 250, 280) Hoval products must be installed

More information

Technical information Installation instructions. UltraOil (16-35) Oil condensing boiler. These instructions are applicable to the following

Technical information Installation instructions. UltraOil (16-35) Oil condensing boiler. These instructions are applicable to the following Technical information Installation instructions UltraOil (16-35) Oil condensing boiler These instructions are applicable to the following types: Rated output levels at 40/30ºC 32-UltraOil (16) 32-UltraOil

More information

Max-3 plus. Output range 420 to 2700 kw TopTronic E control. Steel Shell Boiler. Responsibility for energy and environment

Max-3 plus. Output range 420 to 2700 kw TopTronic E control. Steel Shell Boiler. Responsibility for energy and environment Max-3 plus Steel Shell Boiler Responsibility for energy and environment Output range 420 to 2700 kw Now with new TopTronic E control 1 Why choose Max-3 plus? The Hoval Max-3 plus boiler delivers market-leading

More information

Hoval UltraGas ( ) Floor-standing gas condensing boiler

Hoval UltraGas ( ) Floor-standing gas condensing boiler Floor-standing gas condensing boiler Description Hoval UltraGas (125-1150) Floor-standing gas condensing boiler Floor-standing gas condensing boiler, combustion chamber made of stainless steel Maximal

More information

TopGas Cascade Condensing Gas Boilers Technical Information and Assembly Manual Output range 60 to 720 kw /17 Subject to modification

TopGas Cascade Condensing Gas Boilers Technical Information and Assembly Manual Output range 60 to 720 kw /17 Subject to modification TopGas Cascade Condensing Gas Boilers Technical Information and Assembly Manual Output range 60 to 720 kw Subject to modification Contents 1. Important Information 4 1.1. Documentation 4 1.2. Guarantee

More information

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit Service instructions for contractors VIESMANN Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit VITOLADENS 300-T 1/2007 Please keep safe. Safety instructions Safety instructions

More information

Technical information Installation instructions

Technical information Installation instructions Technical information Installation instructions TopGas classic (35,45,60,80,100,120) Wall-mounted gas condensing boilers for natural gas and liquid gas Nominal output ranges at 40/30 C and natural gas

More information

Technical information Assembly instructions. UltraOil ( ) Oil condensing boiler

Technical information Assembly instructions. UltraOil ( ) Oil condensing boiler Technical information Assembly instructions UltraOil (110-200) Oil condensing boiler These instructions apply to the following types: 30-UltraOil (110) 30-UltraOil (130) 30-UltraOil (160) 30-UltraOil (200)

More information

Technical information Installation instructions. 41-TopGas (80) Gas condensing boiler for natural and liquid gas

Technical information Installation instructions. 41-TopGas (80) Gas condensing boiler for natural and liquid gas Technical information Installation instructions TopGas (80) Gas condensing boiler for natural and liquid gas These instructions apply to the following types: 41-TopGas (80) 17,3-80,0 kw Hoval products

More information

WHE 2.24 / WHE 2.24 FF

WHE 2.24 / WHE 2.24 FF EN Wall-hung gas boilers WHE 2.24 WHE 2.24 FF User Guide 300011777-001-C . Contents 1 Introduction.............................................................................3 1.1 Symbols used...........................................................................................3

More information

Installation and maintenance instructions

Installation and maintenance instructions 6304 4995 0/004 GB For installer Installation and maintenance instructions Flue gas heat exchanger WT50/60 Please read thoroughly prior to installation and maintenance. Summary About this manual This equipment

More information

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Service instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler For applicability, see the last page VITORONDENS 200-T 6/2011 Please keep safe. Safety

More information

Technical information Installation instructions

Technical information Installation instructions EN Technical information Installation instructions Oil/gas boiler Uno-3 (130-280) Hoval products must be installed and commissioned only by appropriately qualifi ed experts. These instructions are intended

More information

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner Installation instructions for contractors VIESMANN Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner VITOCROSSAL 200 2/2007 Dispose after installation. Safety instructions

More information

AirUnit. Operating manual. mfh systems modern floor heating. Decentralised domestic ventilation

AirUnit. Operating manual. mfh systems modern floor heating. Decentralised domestic ventilation mfh systems modern floor heating AirUnit Decentralised domestic ventilation Operating manual List of contents, Operating manual Page 1. General information... 02 2. Device description... 03 3. Adjustment

More information

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner Installation instructions for contractors VIESMANN Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner VITOCROSSAL 300 2/2013 Dispose after installation. Safety instructions Please

More information

Technical information Assembly instructions. Uno-3 (320, 360) Oil/gas boilers

Technical information Assembly instructions. Uno-3 (320, 360) Oil/gas boilers Technical information Assembly instructions Uno-3 (320, 360) Oil/gas boilers These instructions are applicable to the following types: 7-Uno-3 (320, 360) 7-Uno-3 b-i * (320, 360) * = Burner integrated

More information

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l Installation instructions for contractors VIESMANN Vitocell 300-B Type EVBA-A Dual mode DHW cylinder, 300 and 500 l VITOCELL 300-B 1/2017 Dispose after installation. Safety instructions Please follow these

More information

Light oil burners. One stage operation

Light oil burners. One stage operation Installation, use and maintenance instructions Light oil burners One stage operation CODE MODEL TYPE 3505 RDB CF 38 50 T3 350050 RDBR CF 6 50 TR 35050 RDBR CF 33 50 TR 35050 RDBR CF 38 50 T3R 350650 RDBR

More information

Friwa Compact. Operating instructions EN

Friwa Compact. Operating instructions EN Operating instructions EN Version 1.1 / Edition 09/2013 Contents 1 Key background information... 3 1.1 Limitation of liability... 3 1.2 Responsibilities of the operator... 3 1.3 Documentation... 3 1.3.1

More information

AirUnit. Installation instructions. mfh systems modern floor heating. Decentralised domestic ventilation

AirUnit. Installation instructions. mfh systems modern floor heating. Decentralised domestic ventilation mfh systems modern floor heating AirUnit Decentralised domestic ventilation Installation instructions List of contents, Installation instructions Page 1. General information... 03 2. Function / planning

More information

INSTALLATION AND MANINTENANCE INSTRUCTIONS

INSTALLATION AND MANINTENANCE INSTRUCTIONS INSTALLATION AND MANINTENANCE INSTRUCTIONS Appr. Nr. A 9503 T - 0085 AQ 0765 PEGASUS F2 T HIGH EFFICIENCY GAS-FIRED CAST-IRON BOILERS Models 51-68 - 85-102 2 Contents 1. General technical data 2. Dimensional

More information

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A cod. 6272262A GENERAL DATA Heating Data Heat Output Input (Adjustable) (Adjustable) Format 34i 11.2 34KW 45 145MJ/hr Format 34e 11.2 34KW 45 145MJ/hr General Specifications FORMAT 34i 34e Main burner injectors

More information

Steel Shell Boilers. Max-3 plus kw. Max-3 E & Max-3 condens E kw. CompactGas kw. SR-plus and SR-H plus kw

Steel Shell Boilers. Max-3 plus kw. Max-3 E & Max-3 condens E kw. CompactGas kw. SR-plus and SR-H plus kw Steel Shell Boilers Max-3 plus 420-2700 kw Description 194 Technical Data and Dimensions 198 Typical Hydraulic Schematic 204 Engineering 205 Max-3 E & Max-3 condens E 3000-6839 kw Description 207 Technical

More information

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler Gas boiler UPON COMPLETION OF THE INSTALLATION THE INSTALLER MUST INSTRUCT THE OWNER AND OPERATOR ON THE FUNCTIONALITY AND THE PROPER OPERATION OF THE BOILER AND THE HEATING SYSTEM. INSTALLER MUST REVIEW

More information

Operating instructions

Operating instructions Operating instructions Gas condensing boiler WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

More information

Decentralised ventilation units

Decentralised ventilation units Notes on installation Decentralised ventilation units FSL / SCHOOLAIR GB/en TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany Phone: +49 (0) 2845 2020 Fax: +49 (0) 2845 202265 E-mail: trox@trox.de

More information

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use GB122 7210 1300-12/2002 GB(EN) For trade use Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C Please read thoroughly before attempting to diagnose fault List of contents

More information

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use GB122 Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C For trade use Please read thoroughly before attemting to diagnose fault 7217 4900 (03/2010) GB/IE List of contents

More information

Installation and maintenance instructions

Installation and maintenance instructions 6304 4994 03/2006 GB For installer Installation and maintenance instructions Flue gas heat exchanger WT30/40 Please read thoroughly prior to installation and maintenance. Contents Contents Contents 2 1

More information

/2010 US/CA

/2010 US/CA 6 720 646 148-11/2010 US/CA (en) For the user User s Instructions Condensing gas boiler Logamax plus GB162-L.B. 80 kw/100 kw Please read thoroughly before operating This manual is available in the English

More information

Parts Available from

Parts Available from Montage und Bedienungsanleitung Manuel d entretien Installation, use and maintenance instructions Installatie-, gebruiks- en onderhoudsvoorschriften Oδηγίες εγκατάστασης, χρήσης και συντήρησης D F GB NL

More information

Forced draught gas burner

Forced draught gas burner Installation, use and maintenance instructions Forced draught gas burner Code Model Type 3751982 GAS 3 519T80 291 (3) - 02/2010 DECLARATION Declaration of conformity in accordance with ISO / IEC 17050-1

More information

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A Installation instructions for contractors VIESMNN Vitocell 300-V/W Type EVI- DHW cylinder with internal indirect coil 160 to 500 l VITOCELL 300-V/W 3/2017 Dispose after installation. Safety instructions

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

Operating Instructions

Operating Instructions Operating Instructions P4 Pellet 8-60 Read and follow the operating instructions and safety information. Subject to technical change. July 2009 Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse

More information

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors Service instructions for contractors VIESMANN Vitocell 300-B Type EVB DHW cylinder, 300 and 500 l Vitocell 300-V Type EVI DHW cylinder, 200 to 500 l For applicability, see the last page VITOCELL 300-B

More information

WOLF GAS CONDENSING BOILERS COMFORTLINE

WOLF GAS CONDENSING BOILERS COMFORTLINE WOLF GAS CONDENSING BOILERS COMFORTLINE CGB-35/50 / CGB-75/100 30m 3 /h THE EXTENSIVE EQUIPMENT RANGE from system supplier WOLF offers the ideal solution for commercial and industrial buildings, new build

More information

and Installation Instructions The installation instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack.

and Installation Instructions The installation instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack. Technical Guide and Installation Instructions MKS / MUS Steel boiler 70-550 kw The installation instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack. The control

More information

Technical information Installation instructions. Modul-plus (F21-52) High performance calorifiers

Technical information Installation instructions. Modul-plus (F21-52) High performance calorifiers Technical information Installation instructions Modul-plus (F21-52) High performance calorifiers These instructions apply to the following types: 5/6-Modul-plus F (21) 5/6-Modul-plus F (31) 5/6-Modul-plus

More information

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power VICTRIX 90 is the new wall-hung condensing boiler for room heating only, set-up for independent functioning and for that in cascade mode

More information

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL Heating, Air Conditioning, Ventilation Отопление-Кондиционеры-Вентиляция MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL 1. Usage MTM 8-30 universal oil heater is designed for heating commercial rooms

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL HOT WATER HEATING BOILERS DOMESTIC WATER HEATERS 150,000-300,000 Btu/hr MODELS EB-EWU-02 IMPORTANT INSTALLER - AFFIX INSTALLATION MANUAL ADJACENT TO THE BOILER CONSUMER - RETAIN

More information

VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw

VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw Datasheet Part no. and prices: see pricelist VITOCROSSAL 300 Type CT3B Gas condensing boiler for natural gas E, LL and LPG With modulating MatriX

More information

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw Superior A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler Outputs 120, 160, 200, 240, 280 kw 1 The Superior is a, pre-assembled floor standing, gas fired high efficiency

More information

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual. 1 MHG Heating Ltd ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual. Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey, KT20 5LR Telephone 08456 448802 Fax 08456 448803

More information

Model No: Little Devil II (inc ss)

Model No: Little Devil II (inc ss) GAS HEATER Model No: Little Devil II (inc ss) PART NO: 6926020, 6926025 (SS) OPERATION & MAINTENANCE INSTRUCTIONS LS1213 INTRODUCTION Thank you for purchasing this CLARKE Gas Heater. Before attempting

More information

VICTRIX Superior kw Export VICTRIX Superior kw X Export

VICTRIX Superior kw Export VICTRIX Superior kw X Export Wall-hung condensing VICTRIX Superior kw is the instantaneous sealed chamber wallhung boiler with power of 32 kw which, thanks to condensation technology, is characterised for its high efficiency and guarantees

More information

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT DOC1066 GB STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 08707 707 747 FAX: 08707 707 767 E-MAIL:info@stokvisboilers.com

More information

1 VICTRIX ZEUS Superior kw I features

1 VICTRIX ZEUS Superior kw I features Wall-hung condensing VICTRIX ZEUS Superior kw I is the new range of wall-hung condensing boilers with 54 litre stainless steel storage tank available in two versions with nominal heat output of 26 kw and

More information

HX Field Replacement Kit

HX Field Replacement Kit Quantity Kit Part Number Description PE 110 Natural Gas Stainless Steel Condensate Pan PT 110 Natural Gas Polypropylene Condensate Pan Model PE 110 LP Stainless Steel Condensate Pan PT 110 LP Polypropylene

More information

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Service instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler For applicability, see the last page VITORONDENS 200-T 2/2013 Please keep safe. Safety

More information

Oil burners Brûleurs fioul Stookoliebranders

Oil burners Brûleurs fioul Stookoliebranders Installation, use and maintenance instructions Manuel d entretien Installatie-, gebruiks- en onderhoudsvoorschriften GB F NL Oil burners Brûleurs fioul Stookoliebranders One stage operation Fonctionnement

More information

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM Thank you for choosing a DOMUSA TEKNIK heating boiler. Within the product range offered by DOMUSA TEKNIK you have chosen BioClass HM model. With a suitable

More information

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Installation instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler VITORONDENS 200-T 5/2013 Dispose after installation. Safety instructions Please

More information

Installation and maintenance manual

Installation and maintenance manual Installation and maintenance manual Warm air heater WS/WO (Copy of the original version) Wolf GmbH D-84048 Mainburg Postfach 1380 Telefon +498751/74-0 Telefax +498751/741600 Internet: www.wolf-heiztechnik.de

More information

PELLET BURNER PV 350

PELLET BURNER PV 350 PELLET BURNER PV 350 INSTRUCTION MANUAL v1.1 1 PRODUCT DESCRIPTION...3 2 SAFETY RULES...3 3 WARNINGS...4 4 INSTALLATION INSTRUCTIONS...5 4.1 BOILER REQUIREMENTS...5 4.2 PELLET CONTAINER...6 4.3 INSTALLATION

More information

TermEfekt USER S MANUAL AIR HEATER. Model PGA 14

TermEfekt USER S MANUAL AIR HEATER. Model PGA 14 Przedsiębiorstwo Produkcyjno-Wdrożeniowe ARAJ sp. z o.o. 55-080 Kąty Wrocławskie, ul. Mireckiego 30 POLAND USER S MANUAL AIR HEATER TermEfekt Model PGA 14 Kąty Wrocławskie, 2004 Product identification

More information

Installation and operating instructions. DK energy storage and DK energy buffer

Installation and operating instructions. DK energy storage and DK energy buffer Installation and operating instructions DK energy storage and DK energy buffer Edition: 08-2015 1 Preliminary note With this DK energy storage / DK energy buffer you purchased a DK quality product. The

More information

ECONOFLAME R6000 GAS FIRED CONDENSING BOILERS (KM628 CONTROLLER)

ECONOFLAME R6000 GAS FIRED CONDENSING BOILERS (KM628 CONTROLLER) ECONOFLAME R6000 GAS FIRED CONDENSING BOILERS (KM628 CONTROLLER) INSTALLATION, OPERATION & MAINTENANCE DOCUMENTATION STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 020 8783 3050

More information

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB 6 720 648 662-00.1T UNI 7000 F Operating instructions For the user AU/G 2 Contents Contents Contents 2 1 Safety information and explanation of symbols 3 1.1 For your safety 3 1.2 Explanation of symbols

More information

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 HG 675 X 60 HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 1 2 1. : 93/68: 90/396: 2006/95/CE: 2004/108/CE: - 1935/2004:. 2002/95/CE: RoHS 2.,.,,,,...,. (,..)..,,.,. ( ),,, ;,,.,.....,.,,,,,,...,. (..),,.,..,.,,,,

More information

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation.

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation. Installation instructions for contractors PYROMAT ECO PYROMAT ECO 8/2012 Dispose after installation. Safety instructions Please follow these safety instructions closely to prevent accidents and material

More information

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20 INSTALLATION, OPERATION AND MAINTENANCE Ariterm Hybrid 20 TABLE OF CONTENTS General...3 Installation... 4-5 Dimensions - with flue gas exhauster...6 Dimensions - without flue gas exhauster...7 Pipe installations...8

More information

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A Remeha Fuel oil/gas boilers EN Installation and Service Manual 300016859-001-A 63115 Declaration of conformity The appliance complies with the standard model described in declaration of compliance. It

More information

Operating Instructions only for authorised experts RENDAMAX 30. doc /2007 Art. No

Operating Instructions only for authorised experts RENDAMAX 30. doc /2007 Art. No Operating Instructions only for authorised experts RENDAMAX 30 doc2030 01/2007 Art. No. 12 076 446 Table of contents Table of contents...2 General information...3 Conditions...3 Warranty conditions...3

More information

ELECTRIC BOILERS FOR CENTRAL HEATING

ELECTRIC BOILERS FOR CENTRAL HEATING ELECTRIC BOILERS FOR CENTRAL HEATING TermoMax INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS FOR INSTALLATION We reserve the right of alternations WE ARE NOT LIABLE FOR DAMAGES RESULTING FROM NON- OBSERVING

More information

Installation and instruction manual SOLAR STATION

Installation and instruction manual SOLAR STATION INSTALLATION AND INSTRUCTION MANUAL SOLAR STATION Installation and instruction manual SOLAR STATION SST 25-1E / SST25-2E EN April 2015 1 Table of contents Usage 3 Warranty 3 Safety instructions and symbol

More information

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND Aqua Balance AquaBalance TM CONTROL MODULE QUICK START GUIDE 10 1 Domestic Hot Water temperature setpoint decreasing button 2 Domestic Hot Water temperature setpoint increasing button 3 Central Heating

More information

manual Installation and operating instructions

manual Installation and operating instructions manual Installation and operating instructions Condensing boilers Weishaupt Thermo Condens WTC 45-A / WTC 60-A 83240702-1/2008 Conformity Certification to ISO/IEC Guide 22 Manufacturer: Max Weishaupt GmbH

More information

Operating instructions

Operating instructions Operating instructions Gas-fired condensing boiler Logano plus GB312 For the user Please read carefully before use 7 747 009 296-01/2007 EN Contents 1 For your safety..............................................

More information

User s Information Manual

User s Information Manual Gas-fired Water boiler Series 2 NOTICE: Series 1/Series 2 identification Read the boiler rating plate to determine the series number. The rating plate is located on the right side of the boiler. User s

More information

M07. Wunda Premium Manifold. Before you start: Check the contents THE BRAND YOU CAN TRUST

M07. Wunda Premium Manifold. Before you start:  Check the contents THE BRAND YOU CAN TRUST Before you start: Check the manifold box contents against the list below. Check the contents 1. 2 x Manifold end blanks 2. 2 x Manual air vent & drain cocks 3. 2x Adjustable mounting brackets 4. Manifold

More information

Installation instructions and how to use and look after your built-in cooker hoods D5625/22/45 and D5855. NEFF (UK) Ltd

Installation instructions and how to use and look after your built-in cooker hoods D5625/22/45 and D5855. NEFF (UK) Ltd Installation instructions and how to use and look after your built-in cooker hoods D5625/22/45 and D5855 NEFF (UK) Ltd Operation Instructions Operating modes Exhaust-air mode: The extractor-hood fan extracts

More information

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified Thank you for purchasing our fully-automatic gas-fired tankless water heater. Please completely read this Manual

More information

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors Installation instructions for contractors VIESMANN Vitomax 200-HW Type M238 Oil/gas fired high pressure hot water boiler Combustion output 4.0 to 18.2 MW VITOMAX 200-HW 6/2007 Dispose after installation.

More information

CARVER CASCADE 2 & CASCADE 2 GE CARAVAN WATER HEATER INSTALLATION INSTRUCTIONS LEAVE THESE INSTRUCTIONS WITH THE USER

CARVER CASCADE 2 & CASCADE 2 GE CARAVAN WATER HEATER INSTALLATION INSTRUCTIONS LEAVE THESE INSTRUCTIONS WITH THE USER CARVER - CASCADE 2 & CASCADE 2 GE CARAVAN WATER HEATER INSTALLATION INSTRUCTIONS LEAVE THESE INSTRUCTIONS WITH THE USER 1:0 SPECIFICATIONS Water capacity Water connections Water supply 9 litres (2 gallons)

More information

INSTALLATION AND OPERATING INSTRUCTIONS EVOLUTION EV HFM

INSTALLATION AND OPERATING INSTRUCTIONS EVOLUTION EV HFM INSTALLATION AND OPERATING INSTRUCTIONS EVOLUTION EV HFM Thank you for choosing a DOMUSA TEKNIK heating boiler. From the range of DOMUSA TEKNIK products you have chosen the Evolution EV HFM model. This

More information

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28 The competent brand for energy saving systems NEW Gas-combi boiler CGG-1K-24/28 Gas-combi boiler CGG-1K Technical data room sealed fannned flue model gas combi boiler for low temperature heating and d.h.w.

More information

Gas Instantaneous Water Heater

Gas Instantaneous Water Heater 6 720 607 823 GB (06.06) SM Installation and Operating Instructions Gas Instantaneous Water Heater WR10..B... WR11..B... With electronic ignition and triple safety system consisting of ionisation detector,

More information

Operating Instructions

Operating Instructions Operating Instructions S3 Turbo Be sure to read and comply with the operating instructions and safety information Subject to technical change. Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse

More information

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80 IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80 EN OPERATING MANUAL OIL HEATER TRT-BA-IDE20-30-50-60-80-TC-001-EN Table of contents Information on the use of this manual... 1 Scope of delivery... 1 General safety...

More information

VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw

VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw Datasheet Part no. and prices: see pricelist VITOCROSSAL 300 Type CR3B Gas condensing boiler for natural gas E, LL and LPG 9/2011 Benefits

More information

Cooker Hood Instruction Manual

Cooker Hood Instruction Manual Cooker Hood Instruction Manual Model number(s): RHSCH601SS/B & RHSCH901SS/B IMPORTANT: RETAIN FOR FUTURE REFERENCE Contents Safety Instructions. 3-6 Product Overview. 7 Positioning. 8 Operational modes.

More information

Stokvis R600 LMS IP Water Heater Gas-Fired Floor Standing Condensing

Stokvis R600 LMS IP Water Heater Gas-Fired Floor Standing Condensing Stokvis R600 LMS IP Water Heater Gas-Fired Floor Standing Condensing Water Heater Supplement STOKVIS ENERGY SYSTEMS 96R Walton Road East Molesey Surrey KT8 0DL Tel: 020 8783 3050 / 0870 7707747 Fax: 020

More information

RIELLO 40 GS/M SERIES

RIELLO 40 GS/M SERIES The Riello 40 GS/M series of two stage progressive or modulating gas burners, is a complete range of products developed to respond to any request of gas burners for hot air generator according to EN 1020.

More information

Installation & Manual. Model T-25

Installation & Manual. Model T-25 Installation & Manual TR Central Heating Stove With Solid Fuel Model T-25 Tested according to DIN EN 13240 For product efficiency and emission values, see the declaration of conformity! TABLE OF CONTENTS

More information

Heating with log wood

Heating with log wood English Heating with log wood De Luxe 18-40 Lambda 18-40 1 Competence is our success... HERZ FACTS: 60 subsidiaries Group headquarter in Austria Research & development in Austria Austrian owner 2.600 employees

More information

VIESMANN. Operating instructions VITODENS 111-W. for the system user

VIESMANN. Operating instructions VITODENS 111-W. for the system user Operating instructions for the system user VIESMANN Heating system with control unit for constant temperature or weather-compensated mode VITODENS 111-W 4/2012 Please keep safe. Safety instructions For

More information

Operating instructions

Operating instructions ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-74673 Mulfingen Phone +49 (0) 793-0 Fax +49 (0) 793-0 info@de.ebmpapst.com www.ebmpapst.com CONTENTS. SAFETY REGULATIONS AND NOTES. Levels of hazard warnings.

More information

INSTRUCTION MANUAL W-400

INSTRUCTION MANUAL W-400 USE and MAINTENANCE INSTRUCTION MANUAL Bellaria WBX WB GRAVITY SPRAY GUN Series LPH-400 WB en it fr es pt de se TECHNICAL DATA Classic Plus Series LPH-400 (LVLP) Classic Plus Nozzle_Needle set Combination

More information

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4 Installation Operation Maintenance Ductable water unit FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

VERTICAL COOKING PRECISIO/PRECIJET COMBI OVEN PRECISIO/ PRECIJET OVENS S.A.V. MAINTENANCE AND REPAIR

VERTICAL COOKING PRECISIO/PRECIJET COMBI OVEN PRECISIO/ PRECIJET OVENS S.A.V. MAINTENANCE AND REPAIR VERTICAL COOKING S.A.V. PRECISIO/ PRECIJET OVENS MAINTENANCE AND REPAIR 27/03/2012 PPS-3BEFM10PC GENERAL Tools Every time this symbol appears, it is imperative to have the appropriate tool in order to

More information

4FLOOR-STANDING GAS CONDENSING BOILERS

4FLOOR-STANDING GAS CONDENSING BOILERS EASYLIFE PROJECT / SOLNEO / ECODENS RESIDENTIAL DTG (E) 130-15/25 Eco. NOx Plus DTG (E) 1300-15/25 Eco. NOx Plus/B150 DTG (E) 1300-15/25 Eco. NOx Plus/H150 DTG 1300-15/25 Eco. NOx Plus/V130 4FLOOR-STANDING

More information

INDEX RECOMMENDATIONS AND SUGGESTIONS... 4 CHARACTERISTICS... 5 INSTALLATION... 6 USE... 9 MAINTENANCE... 11

INDEX RECOMMENDATIONS AND SUGGESTIONS... 4 CHARACTERISTICS... 5 INSTALLATION... 6 USE... 9 MAINTENANCE... 11 INDEX EN RECOMMENDATIONS AND SUGGESTIONS... 4 CHARACTERISTICS... 5 INSTALLATION... 6 USE... 9 MAINTENANCE... 11 2 RECOMMENDATIONS AND SUGGESTIONS The Instructions for Use apply to several versions of this

More information

Propane Heater REMKO PGM 30 REMKO PGM 60

Propane Heater REMKO PGM 30 REMKO PGM 60 Propane Heater REMKO PGM 30 REMKO PGM 60 Operation Technology Spare Parts Edition GB L07 REMKO strong as a bear. Operating instructions Make sure to read these instructions carefully before starting/using

More information

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode Operating instructions for the system user VIESMANN Heating system with Vitotronic 100 control unit for constant temperature mode VITODENS VITOPEND 4/2007 Please keep safe. Safety instructions For your

More information

Operating instructions

Operating instructions Operating instructions For the operator Operating instructions HOME SYSTEM GB, IE Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Tel. +49 21 91 18 0 Fax +49 21 91 18 28 10 info@vaillant.de

More information